E2.4 9th International Conference on Insulated Power Cables E2.4 Calculation of the current rating for complex cable arrangement in a deep tunnel George J. ANDERS; Lodz University of Technology, Lodz, Poland, george.anders@bell.net, Boguslaw BOCHENSKI, Kinectrics Inc., Toronto, Canada, Boguslaw.bochenski@kinecrics.com Gunnar HENNING, ABB HV Cables, Karlskrona, Sweden, gunnar.henning@se.abb.com ABSTRACT This paper addresses several issues related to the calculation of rating of cables located in deep tunnels. It shows the results for ventilated and unventilated tunnel 3 m in diameter 30 m deep. The paper also introduces of a simplified model for the temperature calculations in a ventilated tunnel. KEYWORDS power cables, rating calculations, tunnel installations tunnel. The paper discusses also how such installations can be rated and shows the results for ventilated and unventilated tunnel 3 m in diameter 30 m deep. SIMPLIFIED MODEL FOR RATING OF CABLES IN A VENTILATED TUNNEL Rating of cables installed in a deep ventilated tunnel was discussed in detail in [1]. A comprehensive model shown there is fairly complex. Therefore, the authors of this paper decided to introduce a simplified set of equations that can be used in a first approximation of current rating calculations for such installations. INTRODUCTION List of symbols Due to congested infrastructure in urban centres, increasing number of cable circuits is installed in deep tunnels. An analytical model for rating of cables in such installations has been described in the Jicable’11 paper by Dorison and Anders [1]. They observed that due to the soil thermal inertia, a long duration is necessary to reach the steadystate value; thus, instead of using the standard IEC formula for the cable external thermal resistance, a more appropriate approach would be to use the transient analysis algorithm and iteratively find out what value of the current would give desired temperature at the end of the study period. They defined a fictitious equivalent depth of the cable circuit that with the application of the steady state algorithm would give the same value of the current as the one obtained from the transient analysis. D H L z0 m m m m Tunnel diameter Tunnel depth to centre Tunnel length Characteristic length of the tunnel v T0 m/s K×m/W air velocity in the tunnel Thermal resistance of the tunnel T0e K×m/W Equivalent thermal resistance of the Wc W/m tunnel Cable losses Wa ( z ) W Heat transported by air flow Wo ( z ) W/m Heat transferred through tunnel wall θ ( z) °C θi θ0 ∆θ °C Temperature of air in the tunnel at distance z. Temperature of air at the inlet °C Temperature of the ground level K c pa Ws/K⋅m Temperature drop in the transition layer at the tunnel wall Specific heat of air h W/K⋅m The analytical approach discussed in the above mentioned paper is applicable to simple cable geometry. However, in a recent project involving installation of four 230 kV cable circuits located in a new concrete tunnel, due to personnel safety of people entering the tunnel for maintenance and inspection, two of the four circuits will be installed inside ducts embedded in concrete on the tunnel side wall (see Fig. 1 below) or in trough at the bottom floor of the tunnel. The calculation of the current rating of such installations is not easily amenable to analytical approaches. One of the contributions of the paper is an introduction of a simplified model for the temperature calculations in a ventilated 3 2 Heat transfer coefficient at the tunnel wall. Heat balance equation Figure 1 shows heat balance at distance z in the tunnel. The heat dissipated from the cable is transported by the air flow along the tunnel and conducted through the tunnel wall. Jicable'15 - Versailles 21-25 June, 2015 1/6 E2.4 E2.4 9th International Conference on Insulated Power Cables dθ = Wc ⋅ T0 e + θ 0 − θ dz π⋅ (7) 2 D ⋅ v ⋅ c pa ⋅ T0 e 4 Introduction of the characteristic tunnel length zo gives: dθ dz = Wc ⋅ T0 e + θ 0 − θ z0 (8) Integrating along the tunnel, we obtain: z z θ ln (Wc ⋅ T0 e + θ 0 − θ ) θ = − i z0 0 Fig. 1 Illustration of the heat balance equation The temperature along the tunnel length is thus given by: The equation for heat balance in the tunnel is: Wc ⋅ dz = θ − ∆θ − θ 0 T0 (1) The temperature θ(z) of the air in the tunnel is a function of the distance z along the tunnel length. In the equations this dependency is omitted for clarity of the presentation. The heat transfer coefficient h at the tunnel wall gives rise to a temperature drop ∆θ over a transition layer. The temperature drop may be eliminated through introduction of an equivalent thermal resistance Toe as shown below. Equivalent thermal resistance The heat transfer through the transition layer of a tunnel length of 1 meter is: h ⋅ ∆θ ⋅ π ⋅ D = θ − ∆θ − θ 0 (2) T0 z zo (10) where T0 e is given in (5) and: z0 = π ⋅ D2 ⋅ v ⋅ c pa ⋅ T0e 4 (11) Comparison with the IEC Standard In 2014 IEC has published a new document 60287-2-3 [2] giving equations for the rating of cables installed in a ventilated tunnel. It is interesting to observe that equation (10) is almost identical to the one in the standard. A numerical example illustrates this point. Let’s consider three identical cables installed in a tunnel. Cable losses are 36.7 W/m×phase; that is,in total 330 W/m. The remaining parameters are as follows: H = 20 m θ − θ0 1 + h ⋅ π ⋅ D ⋅ T0 ∆θ = (3) An equivalent thermal resistance is defined from the equation: θ − θ0 − θ0 1 + h ⋅ π ⋅ D ⋅ T0 T0 T0 e = = θ − θ0 (4) T0 e 1 + h ⋅ π ⋅ D ⋅ T0 h ⋅π ⋅ D (5) It is clear from the last equation that the heat transfer coefficient at the tunnel wall has small influence on the heat transfer to the ambient. The heat transfer coefficient is at 2 least h = 2 W ⋅s/K⋅m . Solution of the heat balance equation The heat balance equation is modified as follows: θ − θ0 T0 e ⋅ dz + dθ ⋅ c pa ⋅ v ⋅ π ⋅ Separation of variables gives: L = 800 m v = 2 m/s W c = 330 W/m θI = 20 °C Thus: Wc ⋅ dz = − D=4m From (2), we obtain: θ− θ ( z ) = θ i + (Wc ⋅ T0e + θ 0 − θ i ) ⋅ 1 − e 2 D ⋅ dz + dθ ⋅ c pa ⋅ v ⋅ π ⋅ 4 (9) D2 4 (6) θ0 = 20 °C h = 1 W/K⋅m 2 In the simplified method temperature of air at the tunnel outlet is calculated. The cable conductor temperature is calculated with use of thermal resistances and the heat transfer coefficient between cable surface and air. The 2 value of the coefficient is h = 10 W/K⋅m . The air temperature at the tunnel outlet computed using the IEC approach is θIEC(L) = 28.6 °C and the simplified method gives θS(L) = 28.9 °C. As mentioned earlier in the text the agreement should be good between the methods. Of course, the problem lies in the details. One should remember that in (5) we did not say how the heat transfer coefficient is computed, nor how the value of T0 is obtained. These can be found in [1] and [2]. However, an important observation is made below equation (5); namely, that the value of this coefficient dos not play an important role in the calculations. Jicable'15 - Versailles 21-25 June, 2015 2/6 E2.4 9th International Conference on Insulated Power Cables E2.4 COMPLEX TUNNEL EXAMPLE This section addresses ampacity issues for 230 kV cables located in a tunnel. A new concrete tunnel in downtown Toronto approx. 3m in diameter, 30m below grade, 650 m long, and connect to the existing tunnel. There will be four circuits inside the new tunnel’. Due to personnel safety of people entering the ‘new tunnel’ for maintenance and inspection, two of the above four circuits will be installed inside ducts (PVC, FGBR or HDPE) embedded in concrete on the tunnel side wall and in trough at the bottom floor of the tunnel. The following sections review the input parameters and discuss the assumptions made during the calculations. The results are presented next followed by a discussion. Input data Given values Cable: XLPE 230 kV, 2000 kcmil. Cable maximum operating conditions: o maximum voltage of 127 kV, o maximum continuous load 1200 A in summer or 1300 A in winter, o emergency 2-hour limited time rating of 1700 A, o maximum allowable continuous conductor temperature of 90°C, o maximum allowable emergency (2-hr) conductor temperature of 105°C, Daily load factor of 0.85, Maximum soil temperature at tunnel depth of 15°C, Assumed thermal resistivity of soil of 1.0 (K*m/W). Cable installations presented in Fig. 2. Bonding – single point bonded. • • • • • • • (a) (b) Derived values – Losses Fig. 2 Cable installations: (a) Option A, (b) Option 1 Conductor 29.5 W/m @90°C, 1200 A, Load Factor=0.85 Conductor: 34.6 W/m @90°C, 1300 A, Load Factor =0.85 Sheath: 3.7 W/m @90°C, 1200 A Sheath: 4.3 W/m @90°C, 1300 A Dielectric: 1.3 W/m Two different tunnel constructions were investigated as shown in Fig. 2. Project requirements The main goal of the calculations was to assess whether the proposed cable arrangements satisfy the ampacity requirements specified above. The following calculations were specified by the client: • Assumptions The following assumptions were made either due to lack of data or for modeling purposes: • • • • The isothermal boundary conditions were assumed on all sides of the examined installation. The tunnel is long enough for two-dimensional models to be applicable. The tunnel is not ventilated during normal operation. Ampacity of the ventilated tunnel will also be computed. • • Calculate the current rating for the following preferred cables – 230 kV, 2000 kcmil copper conductor, XLPE insulated, HDPE served - in ducts embedded in concrete for the configuration shown in Fig.2a. Suggest suitable spacing between the ducts, for different type of ducts PVC, FGBR and HDPE. If the preferred cables conductor (2000 kcmil copper) is not able to carry required current of 1200/1300 A @ 90° C for both summer/winter continuous when installed in ducts embedded in concrete wall of the THES tunnel, suggest a cable conductor size that is adequate and available to meet all the ratings for conditions specified above. Also, suggest the required spacing between phases for ducts to be placed inside the tunnel wall. Create a thermal model for the whole tunnel system with two cable circuits on the rack/brackets in air and two Jicable'15 - Versailles 21-25 June, 2015 3/6 E2.4 • • E2.4 9th International Conference on Insulated Power Cables circuits in ducts embedded in concrete. Calculate the ambient air temperature inside the tunnel for a conductor temperature of 90°C and 105°C operation conditions and specified currents. Perform similar calculations as above for the trough section of the tunnel and suggest dimension of the troughs to be built at the floor of the tunnel. Perform calculations assuming forced longitudinal air flow at the speed of 1200 ft/min (6.096 m/s). solution which will result in the installation being capable to carry the required load. Calculation method For ampacity calculations commercial software called COMSOL was used which allows analysis of complex installations using the finite element method (FEM). The FEM was described in many textbooks; thus, the details will not be provided here. The models of the two tunnels are shown in Fig. 3. An application of the program involves preparation of: a) b) c) d) graphics, definition of materials, domain settings and boundary conditions, and creation of the mesh. The mesh is presented in Fig. 3. Materials were defined using either provided physical properties or from tables. Fig. 4 Temperature distribution and air velocity field in rated conditions for Option A Continuous winter ratings for the proposed installations The results for the winter steady state conditions are shown in Table 1. Table 1 Winter continuous ratings for both tunnels in original configuration Installation Ampacity (A) Option A 860 Option 1 866 Fig. 3 Mesh and contours of the cable installation models; the coordinates are expressed in meters [m]: Option A left and Option 1 right The heat transfer employs three physical phenomena: conduction (mainly in solids), convection (in air) and radiation from surfaces. Convection, however; requires some minimal volume of air to occur and is very limited in ducts where most of the heat is transferred by radiation. Results In order to determine whether the cables in the installations presented in Fig. 2 are capable to carry the load specified in the requirements, a number of computations (according to the specifications presented above) had to be performed. However, the order of the tasks was modified to avoid repeating unnecessary calculations. The results of each of them are presented below. Figs. 4, 5 and 6 present the results of the FEA analysis in a form of the temperature distribution and air flow maps for Option A and Option 1. The picture is similar for all further cases and the only difference is in the current which generates the losses. Fig. 5 Temperature distribution and air velocity field in rated conditions for Option 1 Result of the calculations show that the continuous rating of the proposed installations is lower than the requirements. The goal of the remaining studies was to recommend a Jicable'15 - Versailles 21-25 June, 2015 4/6 E2.4 E2.4 9th International Conference on Insulated Power Cables Table 3 The effect of the trough size on the cable rating – Winter continuous rating Trough size (H x W) Rating (A) 0.35m x 0.5m 866 0.35m x 0.75m (wide trough) 868 1m x 0.5m (tall trough) 895 1m x 0.75m (wide and tall trough) 900 Two additional conductor sizes Fig. 6 Temperature distribution in tunnels and in soil above the tunnels for Option A (left) and Option 1 (right) Three different types of ducts PVC, FRE and HDPE and different spacing between the ducts Study of the impact of the type of cable ducts and different spacing between ducts is presented in Table 2. The cables are planned to be laid in the 8” ducts; therefore, three ducts of the same size but different materials were tested. Table 2 The effect of the duct type on the cable rating The results of the analysis are presented in Table 4. Table 4 The effect of the conductor size on the cable rating – Winter continuous rating Cable Option A (A) Option 1 (A) 1000 mm2 860 866 2000 mm2 1229 1234 2500 mm2 1384 1388 Ampacity (A) The required value of ampacity for winter conditions is 1300 A and only the 2500 mm2 cable is capable to carry this load continuously without exceeding the temperature limit. Duct Distance 10.5° Distance 9.5° Distance 11.5° PVC 858 857 858 Continuous and 2-h winter ratings HDPE 857 856 858 FRE 860 859 859 The previous sections proved that the only solution to significantly increase the ampacity is by increasing the size of the cable; therefore, the final calculations were performed for these conditions. 2 The ducts were moved within the same boundaries as the initial proposed installation. The distance is expressed in degrees due to the way the ducts were drawn – one duct is copied with rotation referenced to the geometrical centre of the tunnel (coordinates 0,0). This approach allows keeping a constant distance from the outer surface of the tunnel and from its central point. There is limited space for ducts between small PVC ducts at the bottom and the top concrete surface on top; hence, limited range within which the distance between ducts can be changed. The results show an insignificant change of ampacity within the aforementioned boundaries. Table 5 Ampacity (A) of the 2500 mm cables without forced ventilation Winter Summer Continuous 2-hr rating Continuous 2-hr rating Option A 1384 2640 1338 2610 Option 1 1388 2650 1343 2625 Continuous and 2-hr ratings with forced air flow Different troughs dimensions Three different through dimensions were investigated for Option 1 as shown in Table 3. In order to increase the ampacity, forced air flow at the rate of 1200 ft/min is to be used. The calculations were performed for the initial cable size of 2000 kcmil and the results are presented in Table 6. Jicable'15 - Versailles 21-25 June, 2015 5/6 E2.4 E2.4 9th International Conference on Insulated Power Cables 2 Table 6 Ampacity of the 2000 kcmil (1000 mm ) cable in the tunnels with forced ventilation Ampacity Option A Ampacity Option 1 Air temperature (inlet) (°C) Continuous (A) 2-hr rating (A) Air temperature (inlet) (°C) Continuous (A) 2-hr rating (A) 20 1636 1977 20 1346 1743 25 1570 1924 25 1296 1705 30 1502 1871 30 1244 1668 35 1431 1817 35 1191 1630 Introducing the forced air flow significantly increases the ampacity. In fact, the ampacity of the cables in tunnels (trefoils) is much higher than presented in the table while the limiting cables are these in the ducts/troughs. In addition, Option A has higher ampacity than Option 1 because of better cooling conditions – the cables are separated and the mutual heating is decreased and at the same time the cooling surface is larger. c. Situation improves dramatically when the forced ventilation is introduced in the tunnel. With air velocity of 1200 ft/min, the 2000 kcmil cable will satisfy both the winter and summer continuous and emergency ratings when the inlet air temperature does not exceed 25°C. This is a reasonable assumption since the tunnel is located at the 30 m depth. At such depths, the soil temperature is expected to be constant during the year and likely will not exceed 10°C. Even with hot air temperature at the earth surface, the tunnel inlet temperature should be below 20°C. d. Because of cable separation and better cooling conditions, Option A shows better thermal performance. CONCLUSIONS The following conclusions can be drawn from the ampacity studies performed for the two tunnel cross sections shown in Fig. 2. a. When the tunnels are not ventilated, the existing 2000 kcmil cable construction will not meet ampacity requirements. b. The sensitivity studies have shown that only the 2 2500 mm cable will have sufficient rating to meet the steady state ampacity requirements in the unventilated tunnel. The requirements are also met 2 when the 1000 mm cables are on racks and the 2 2500 mm circuits are placed in ducts/troughs. Acknowledgements The authors would like to thank Mr. Badrinath Comar and Mr. Arnold Brakel from Hydro One Networks Inc. in Toronto, Canada for their support, encouragement and active involvement in performing these studies. REFERENCES [1] E. Dorison, G.J. Anders Current rating of cables installed in deep or ventilated tunnels. Jicable 2011 rapport C.8.3. [2] IEC Standard 60287 – ELECTRIC CABLES – CALCULATION OF THE CURRENT RATING – Part 2-3: Cables installed in ventilated tunnels. Jicable'15 - Versailles 21-25 June, 2015 6/6