Uploaded by Estrella Lazo Romero

Passive Fire protection systems

advertisement
PASSIVE FIRE PROTECTION SYSTEMS
Application & Technical Manual:
M&E Services Enclosures
For Promat Asia Pacific Organisation • February 2014
PASSIVE FIRE PROTECTION SYSTEMS Application & Technical Manual: M&E Services Enclosures – Contents
M&E Services Enclosures General Information________ 1 - 3
M&E Services Enclosures System Index _____________ 4 - 5
PROMATECT®-H/ PROMATECT®-L/
PROMATECT®-L500 Electrical Cables Enclosure
(External Fire For Circuit Integrity) ___________________ 6
PROMATECT®-H/ PROMATECT®-L/
PROMATECT®-L500 Electrical Cables Enclosure
(Internal Fire) ____________________________________ 7
PROMATECT®-H/ PROMATECT®-L/
PROMATECT®-L500 Electrical Cables Enclosure
Fixing Details_____________________________________ 8 - 9
PROMATECT®-H/ PROMATECT®-L/
PROMATECT®-L500 Electrical Cables Enclosure
Architectural Specification _________________________ 10
PROMATECT®-H M&E Services Enclosure
(Integrity & Insulation) _____________________________ 11
PROMATECT®-H M&E Services Enclosure
(Integrity Only) ____________________________________ 12
PROMATECT®-L500 M&E Services Enclosure
(Integrity & Insulation) _____________________________ 13 - 14
PROMATECT®-H/PROMATECT®-L500/PROMINA® 60
M&E Services Enclosure Fixing Details ______________ 17 - 19
PROMATECT®-H/PROMATECT®-L500/PROMINA® 60
M&E Services Enclosure Architectural Specification ___ 20
PROMATECT®-S M&E Services Enclosure
(Integrity & Insulation) _____________________________ 21
PROMATECT®-S M&E Services Enclosure
(Integrity Only) ____________________________________ 22
PROMATECT®-S M&E Services Enclosure
Fixing Details_____________________________________ 23 - 24
PROMATECT®-S M&E Services Enclosure
Architectural Specification _________________________ 25
Enclosure
PROMATECT® 50 Riser Pipes Enclosu
ulation) _____________________________ 26
(Integrity & Insulation)
Enclosure
PROMATECT® 50 Riser Pipes Enclosu
____________________________________ 27
Fixing Details_____________________________________
Enclosure
PROMATECT® 50 Riser Pipes Enclosu
Architectural Specification _________________________ 28
PROMATECT® 50 M&E Services Enclosure
(Integrity Only) ____________________________________ 29
PROMATECT® 50 M&E Services Enclosure
Architectural Specification _________________________ 30
Cables _____
___ 31
PROMASTOP® CIS Coating For Electrical Ca
PROMASTOP® CIS Coating For Electrical Cables
Architectural Specification _________________________ 32
i
M&E Services Enclosures
General Information
General M&E services enclosure at the carpark of Tseung
Kwan O residential building in Sai Kung District, New
Territories, Hong Kong (above) and outside the warehouse of
9 Benoi Sector, Singapore (left). Both use PROMATECT®-H
boards.
Electrical cables coated with PROMASTOP® CIS at a
warehouse (below) in Ayer Rajah, Singapore.
M
echanical and electrical (M&E) services require fire
protection for the following reasons:
1) To maintain function of certain essential electrical
and/or mechanical systems and services, and
2) To prevent fire, smoke and toxic fume propagation
from one building compartment to another.
It is necessary to ensure the continued function of essential electrical
systems and services is maintained during fire, for a specified period
of time, until all the building occupants have escaped. Electrical
systems that need protection from fire may include:
 Smoke extraction venting systems
 Electrically operated fire alarms
 Water mains supply and pumps servicing sprinkler systems
 Emergency escape route lighting
 Essential life support and/or computer, communication or
information technology networks
 Electrically operated extinguishing systems
 Power supply for fire service elevators in high-rise buildings
1
i
M&E Services Enclosures
General Information
It is worth noting that most electrical and to some extent mechanical
services contain a high component of plastic materials such as
polyvinylchloride, polypropylene, polyethylene, synthetic rubbers etc.
The risks associated with these combustible plastics are such that
fire can and will spread or propagate through the services. Intensive
combustion also means that plastics frequently release toxic and
corrosive fumes that can include particulates, unburned fuel, carbon
dioxide and carbon monoxide which are not only harmful to the
building and its contents but also to its occupants. Such fires can also
cause the following problems:
 Production of highly corrosive and extremely toxic gases,
 Long term destruction of buildings and equipment,
 Smoke development and toxic gases in corridors and
escape routes,
 Difficult evacuation,
IEC 60331 fire test
 Impedance of rescue activities by firefighters.
Reliability Of Fire Resistant Cables
requirement to maintain the integrity of the encasement and any
penetrations through walls or floors, the standard requires that:
Typical uses of cables to, in and from M&E enclosure include fire
alarms, emergency lighting, addressable alarm systems, CCTV
systems, emergency power supplies and smoke and fire shutters.
These cables are normally designed to meet the standards for “Fire
Detection and Fire Alarm Systems for buildings” (BS 5839: Part 1:
2002 + A2: 2008) and “Codes of Practice for Emergency Lighting of
Premisses” (BS 5266: Part 1: 2005).
1) the cables continue to function for the duration of the exposure
period, and
Many fire resistant cables have been subjected to tests in accordance
with BS 6387: 1994 “Specification for performance requirements for
cables required to maintain circuit integrity under fire conditions” and/
or ISO IEC 60331: Parts 11, 21, 23 and 25 “Test for electric cables
under fire conditions – circuit integrity”. See also ISO IEC 60331: Parts
1, 2 and 3.
2) the temperature on the cable jacket should not exceed 150°C.
The tested encasement system protects a wide range of different
cable types. Electrical current is passed through the cables throughout
the test. As an added safety factor, the system described on page 6
will ensure that the temperature on the cable jacket does not exceed
120°C.
Unfortunately, these standards only test single cables or small
bunches of cables, without any support system, exposed to a small
gas flame by means of an elongated Bunsen burner. The heat applied
during the test is localised to a small area. While such a test may be
adequate for small cables carefully secured directly to a fire resisting
wall or floor, it is arguably not suitable to assess the fire performance
of larger cables or bunches of cables, exposed to a fully developed
fire on all sides, especially if they are supported on a suspended cable
tray which may pass through compartment walls or floors.
The Australian/New Zealand standard AS/NZS 3013: 2005 “Electrical
installations – Classification of the fire and mechanical performance
of wiring system elements” describes the level of protection of a
wiring system against fire and/or accidental mechanical damage. The
test methods described within this standard call for wiring systems
to maintain circuit integrity when subjected to fire tests, mechanical
damage and fire and water tests. The resistance to fire test is to
determine the ability of a wiring system to maintain circuit integrity
under fire conditions for a specified period of time of up to 120
minutes. The wiring system shall be tested in a horizontal furnace
complying with AS 1530: Part 4: 2005, which also employs the ISO
834 heating conditions.
Although the cables may achieve the highest classification of the
standard, they may not survive as expected if they are exposed on all
sides to a fully developed fire as described, for example, by the ISO
834 time-temperature fire curve.
Mechanical damage tests are to determine the degree of mechanical
impact and cutting load to which the wiring system can be subjected
without losing its circuit integrity. These tests are carried out
separately from the fire test.
Fire Resistance Test Standards
For Cable Protection Systems
The German standards DIN 4102, “Fire behaviour of building materials
and building components”, Parts 11 and 12 specify fire resistance
test for cable protection systems that simulate a fully developed
fire scenario.
Fire and water tests assess the ability of a wiring system to maintain
its circuit integrity when subjected to fire conditions followed by
hosing with water.
DIN 4102: Part 12: 1991 and AS/NZS 3013: 2005 are designed to test
the functionality of cables under fully exposed fire conditions, unlike
the IEC 60331 test regimes. The systems detailed herein relate to
maintaining compartmentation as well as the full function of the cables.
For more information related to such systems, please consult Promat.
DIN 4102: Part 11: 1985 assesses the encasement system when
exposed to a fully developed internal fire. The integrity of the
encasement, and any penetrations through walls and floors, is
measured, as well as the temperature on the outer surface of
the encasement (140°C mean temperature rise, 180°C maximum
temperature rise). The heating curve for DIN 4102: Part 11: 1985 is the
same as that used in BS 476: Part 20: 1987 and AS 1530: Part 4: 2005
and the failure criteria for integrity and insulation are identical. The
systems detailed herein have been successfully tested and assessed
and are approved for use to provide a performance in accordance with
BS 476: Part 20 and AS 1530: Part 4 in terms of compartmentation.
In the event of an internal or external fire performance, it has been
established that an enclosure fabricated from fire resistant boards
is one of the best solutions. Such systems have been tested
successfully with encasement constructed from fire protective boards
such as PROMATECT -H, PROMATECT -L, PROMATECT -L500,
PROMATECT 50 or PROMATECT -S. These well established board
systems are representative of the few systems which currently fulfil
all performance requirements, especially to the DIN 4102 standards.
DIN 4102: Part 12: 1991 assesses the encasement system when
exposed to a fully developed external fire. In addition to the
Continued on next page
2
General Design Considerations
®
®
®
®
®
M&E Services Enclosures
General Information
i
General Design Considerations
6 Access Hatches
A suitably designed duct will:
For future inspection and installation of cables, a loose lid construction,
described on pages 6 and 7, can be considered. Alternatively, the
lid can be fixed and the inspection openings with hatches can be
provided in the side walls of the enclosure, as shown on page 9. The
hatch is secured completely to the enclosure using threaded inserts
such as “Tecserts” (Armstrong Fastening Systems) at maximum
200mm centres.
 prevent the propagation of fire from one building compartment
to another,
 assist in maintaining smoke free escape routes,
 ensure the continuing operation of other services within a common
service shaft,
 reduce damage to a localised area,
 contain smoke and toxic fumes from burning cables, and
 where required, ensure cable maintain their function when exposed
to a fully developed fire.
7 Selection of Board Type
The Promat system constructed from PROMATECT®-H,
PROMATECT®-L or PROMATECT®-L500 is lighter than PROMATECT®
50, and would probably be used in most applications.
The following are some of the factors to consider when determining
the correct specification to ensure the enclosure system provides the
required fire performance. Please consult Promat.
PROMATECT®-H or PROMATECT® 50 offers a particularly robust
system which is also highly resistant to impact and abrasion. Although
these products are water tolerant, the latter is generally preferred for
more onerous conditions.
1 Required Fire Exposure
For tunnel environments and higher performance requirements, e.g.
to resist hydrocarbon fires, please consult Promat.
The specification of the enclosure system will depend on whether it is
expected to resist external fire, internal fire or both.
8 Other Requirements
2 Required Fire Performance
Generally, the most onerous requirement is to maintain the functional
integrity of the circuit(s) when the system is exposed to external fire.
If this is not needed, the performance requirements may be reduced
by the approval authority to provide only stability, integrity and
insulation of the enclosure system and/or wall and floor penetrations.
On some occasions, further relaxations may be approved, e.g. a
reduced insulation performance can sometimes be acceptable if no
combustible materials or personnel are likely to be in contact with the
enclosure.
3 Supporting Structure
The supporting hangers and their fixings should be capable of bearing
the load of the complete enclosure system including any applied
insulation material or other services suspended from it. Chemical
anchors are generally not suitable. It is usually not advisable to
employ unprotected hangers if the stress exceeds 6N/mm2 for up to
240 minutes fire exposure and 10N/mm2 for up to 120 minutes fire
exposure and/or if hanger lengths exceed 2m. Hanger centres should
not exceed the distance limits given for the relevant Promat system.
4 Penetrations Through Walls & Floors
Care should be taken to ensure that movement of the cable system
in ambient or in fire conditions does not adversely affect the
performance of the wall, partition or floor penetration seals.
5 Ventilation Openings
Heat is generated as current flows through cable core conductors. The
greater the electrical current, the hotter the conductor will get. Excessive
current flow will cause overheating and may result in overload, short
circuit or ground fault. The material of the cable sheath, commonly made
from material such as PVC, polyurethane or polyethylene, usually has a
self-ignition temperature between 340°C to 490°C.
In general, the heat generated by cables is negligible if appropriately
vented. Ventilation openings must have a self-enclosing capability in
the event of fire so as to prevent fire spread via such openings. It is
recommended that an electrical engineer is consulted to ensure heat
build-up does not become an issue. Should ventilation be required,
see page 9 for PROMASEAL® Ventilation Grille and Promat Ventbox.
Acoustic performance, thermal insulation, water tolerance,
strength and appearance can also be important considerations
(see BS 8313: 1997 Code of practice for accommodation of building
services in ducts).
Fibre Optics
Fibre optic cables have a lower failure temperature (typically 50-80°C)
due to the fact that the conductor consists bundles of glass fibres
which can be as thin as a human hair. Fibre optic cables are widely
used for IT networking in many industries, especially in financial
and healthcare services. For example, large banks depend on
their network cabling systems for most of their routine business
transactions. If fire occurs and even one metre of cabling is destroyed,
it could cost the company millions of dollars each day their systems
remain inoperative. These are problems that businessmen do not
want to face and one reason why it is necessary to protect sensitive,
strategically important cables against fire risk. Please consult Promat
to determine the required board thickness and construction details.
Riser Pipes
The Fire Safety Bureau of Singapore requires that the pipe work for a
rising main is adequately protected to prevent collapse and reduction
of water pressure at the point of water egress in the event of a fire. In
addition, fire will heat the water conveyed through the piping system.
It is conceivable that water in the pipe could reach boiling point. This
would result in additional pressure being placed upon the pipe system
as water expands considerably (1:1700) as it turns to steam. This will
result in premature failure of the pipes and joints transporting the
water, leading to a loss of pressure and consequential inability to fight
or extinguish the fire. Therefore it is required that the rising main pipe
work is adequately protected to:
 prevent collapse of the piping system,
 maintain the fire integrity and insulation of the compartment wall or
floor where the piping penetrates, and
 prevent water passing through the piping system from reaching
boiling point. The temperature at any point on the pipe external
surface, measured on the fire-exposed side, must not exceed
75°C above the initial temperature for at least the first 30 minutes
of exposure to fire.
The fire resistance test procedure is described in FSB/PSB/001/00
dated 8 November 2000.
3
M&E Services Enclosures
System Index
Type
PROMATECT®-H/ PROMATECT®-L/
PROMATECT®-L500
electrical cables enclosure (external fire)
PROMATECT®-H/ PROMATECT®-L/
PROMATECT®-L500
electrical cables enclosure (internal fire)
PROMATECT®-H M&E services enclosure
(integrity and insulation)
PROMATECT®-H M&E services enclosure
(integrity only)
PROMATECT®-L500 M&E services enclosure
(integrity and insulation / without cover strip)
PROMATECT®-L500 M&E services
enclosure (integrity and insulation)
4
Fire resistance
performance
Board thickness
30/30/30
From 20mm
60/60/60
From 35mm
Mineral wool
thickness x density
Test/Approval no.
Page no.
Not required
BRE CC1422.22
and
BRE CC90659C
to the
requirements of
BS 476: Part 20: 1987
and/or
AS 1530: Part 4: 2005
based on
DIN 4102: Parts 11 and 12
6
Not required
BRE CC1422.22
and
BRE CC90659C
to the
requirements of
BS 476: Part 20: 1987
and/or
AS 1530: Part 4: 2005
based on
DIN 4102: Parts 11 and 12
7
BRE CC242335
to the
requirements of
BS 476: Part 20: 1987
11
Not required
WF 169576
to the
requirements of
BS 476: Part 20: 1987
and
AS 1530: Part 4: 2005
12
Not required
WFRC C80076
and
WF 176908
to the
requirements of
BS 476: Part 20: 1987
13
BRE CC90659B
to the
requirements of
BS 476: Part 20: 1987
and
AS 1530: Part 4: 2005
14
90/90/90
From 50mm
120/120/120
From 70mm
30/30/30
From 15mm
60/60/60
From 30mm
90/90/90
From 35mm
120/120/120
From 40mm
60/60/60
9mm
50mm x 60kg/m3
120/120/120
15mm
50mm x 80kg/m3
240/240/240
20mm
100mm x 100kg/m3
120/120/-
9mm
240/240/-
12mm
120/120/30
25mm
240/240/120
50mm
120/120/120
20mm
240/240/240
50mm
50mm x 100kg/m3
80mm x 80kg/m3
M&E Services Enclosures
System Index
Type
Fire resistance
performance
Board thickness
Mineral wool
thickness x density
Test/Approval no.
Page no.
15
60/60/60
9mm
50mm x 100kg/m
WF 171133
to the
requirements of
BS 476: Part 20: 1987
120/120/-
9mm
Not required
WF 177444
to the
requirements of
BS 476: Part 20: 1987
16
120/120/120
6mm
100mm x 140kg/m3
BRE CC91117
to the
requirements of
BS 476: Part 20: 1987
21
BRE CC86559
to the
requirements of
BS 476: Part 20: 1987
22
BWA 23445-03
to the
requirements of
BS 476: Part 20: 1987
and
FSB/PSB/001/00
test procedure
26
Not required
FSRG 2010-019
and
FSRG 2010-021
to the
requirements of
BS 476: Parts 20
and 22: 1987
29
Not required
FM 3046711
to the
requirements of
FM 3971 Approval
Standard
31
3
PROMINA® 60 M&E services enclosure
(integrity and insulation)
PROMINA® 60 M&E services enclosure
(integrity only)
PROMATECT®-S M&E services enclosure
(integrity and insulation)
240/240/240
9.5mm
120/120/-
6mm
140mm x 140kg/m3
Not required
PROMATECT®-S M&E services enclosure
(integrity only)
PROMATECT® 50 riser pipes enclosure
(integrity and insulation)
240/240/-
9.5mm
120/120/120
15mm
240/240/240
19mm
50mm x 100kg/m3
50mm x 100kg/m3
PROMATECT® 50 M&E services enclosure
(integrity and insulation)
-/60/60
External fire for
circuit integrity
PROMASTOP® CIS
electrical cables coating
30mm
--
5
PROMATECT®-H/PROMATECT®-L/PROMATECT®-L500
Electrical Cables Enclosure (External Fire For Circuit Integrity)
51.30/51.60/
PH/PL/PE 51.90/51.12
6
7
5
4
1
9
3
8
2
Up to 120/120/120 fire resistance in accordance with the requirements of BS 476: Part 20: 1987 and AS 1530: Part 4: 2005
1 PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 board, thickness in accordance with table below
Internal Cross Section:
Equal or smaller than 110mm x 100mm
Internal Cross Section: Equal or greater than 110mm x
100mm and equal or smaller than 520mm x 250mm
Lid type
Board type
Up to
30/30/30
Up to
60/60/60
Up to
Up to
90/90/90 120/120/120
Up to
30/30/30
Up to
60/60/60
Up to
90/90/90
Up to
120/120/120
Fixed
24mm
45mm
60mm
75mm
20mm
40mm
50mm
65mm
PROMATECT®-H
Fixed
25mm
40mm
Loose fit
25mm
45mm
60mm
80mm
20mm
35mm
50mm
70mm
60mm
80mm
20mm
40mm
60mm
70mm
PROMATECT®-L or
PROMATECT®-L500
The board thicknesses given in the above table will ensure that when the encasement is exposed to a fully developed cellulosic external fire
(BS 476 curve), the cable jacket temperature rise will not exceed 120°C and the cables will remain functional. If the cables are not required
to maintain circuit integrity it may be possible to reduce the board thickness after consultation with Promat. Promat can also advise on
specifications for larger duct sizes. The board thickness is dependent on the internal dimensions of the duct and whether the duct has a loose
fit lid or a fixed lid
2 PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 internal cover strip 100mm x 20mm thick, located between tray and base of duct only.
Strips positioned at maximum 625mm centres and coinciding with board joints and supports 7
3 PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 external cover strip to top and side joints only. Not required for multi layer construction
providing the joints between the layers are staggered by at least 80mm and are fixed to each other
Up to 30/30/30
100mm x 20mm thick
Up to 90/90/90
100mm x 25mm thick
Up to 60/60/60
100mm x 20mm thick
Up to 120/120/120
100mm x 25mm thick
4 PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 batten, 25mm x 20mm thick fixed to loose fit lid. Not required for fixed lid option
5 PROMASEAL® Ventilation Grille, if required
6 Fixings in accordance with the table on page 8. Screws should be deep threaded, self-tapping, drywall type, e.g. Buildex HILO. Alternatively,
steel wire staples can be used
7 Threaded steel hanger rod, minimum diameter 8mm at maximum 1220mm centres, ensure maximum stress does not exceed 10N/mm² for up
to 120/120/120 fire resistance. Note that when calculating the stress on the support system, the weight of the cables must be considered
8 Supporting galvanised steel angle or channel, size according to weight and dimensions of the enclosure. Maximum permissible bending stress
10N/mm² for up to 120/120/120 fire resistance. Supports should be at maximum 1220mm centres and should coincide with an internal cover
strip 2. The cable duct should be supported not more than 500mm from either side of any wall or floor through which it passes
9 Electrical cables and steel cable tray. Cables contaning fibre optics will have a lower failure temperature. Please consult Promat to determine
the required board thickness. Note, steel cable trays are required for systems exposed to external fire
6
PROMATECT®-H/PROMATECT®-L/PROMATECT®-L500
Electrical Cables Enclosure (Internal Fire)
52.30/52.60/
PH/PL/PE 52.90/52.12
6
7
5
4
1
9
3
8
2
Up to 120/120/120 fire resistance in accordance with the requirements of BS 476: Part 20: 1987 and AS 1530: Part 4: 2005
1 PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 board, thickness in accordance with table below
For stability, integrity in fire compartment /
Insulation in adjacent compartment
For stability, integrity and insulation in
fire compartment
Lid type
Board type
Up to
30/30/30
Up to
60/60/60
Up to
90/90/90
Up to
120/120/120
Up to
30/30/30
Up to
60/60/60
Up to
90/90/90
Up to
120/120/120
Fixed
15mm
30mm
35mm
40mm
20mm
35mm
40mm
50mm
PROMATECT®-H
Fixed
20mm
30mm
35mm
40mm
25mm
35mm
40mm
52mm
Loose fit
20mm
30mm
35mm
40mm
25mm
35mm
40mm
52mm
PROMATECT®-L or
PROMATECT®-L500
The board thicknesses given in the above table will ensure that the stability, integrity and insulation of the encasement will be maintained when
exposed to fully developed cellulosic internal fire (BS 476 curve). For ducts which are not required to satisfy insulation criteria, and for larger
ducts, please consult Promat
2 PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 internal cover strip 100mm x 20mm thick, located between tray and base of duct only.
Strips positioned at maximum 625mm centres and coinciding with board joints and supports 7
3 PROMATECT®-H external cover strip, 100mm x 9mm thick, to top and side joints only. For ducts with an internal height greater than 300mm
replace the external strip with an PROMATECT®-H internal strip 100mm x 15mm thick. Fix side boards to ends of internal strip to strengthen
casing, external strips not required for multi layer construction providing the joints between layers are staggered by at least 80mm and are fixed
to each other
4 PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 batten, 25mm x 20mm thick fixed to loose fit lid. Not required for fixed lid option
5 PROMASEAL® Ventilation Grille, if required
6 Fixings in accordance with the table on opposite page. Screws should be deep threaded, self-tapping, drywall type, e.g. Buildex HILO.
Alternatively, steel wire staples can be used
7 Threaded steel hanger rod, minimum diameter 8mm at maximum 1220mm centres, ensure maximum stress does not exceed 10N/mm². Note
that when calculating the stress on the support system, the weight of the cables must be considered
8 Supporting galvanised steel angle or channel, size according to weight and dimensions of the enclosure. Maximum permissible bending stress
10N/mm². Supports should be at maximum 1220mm centres and should coincide with an internal cover strip 2. The cable duct should be
supported not more than 500mm from either side of the wall
9 Electrical cables and steel cable tray. Steel cable tray not required for systems exposed to internal fire only unless the cable weight exceeds
25kg/m when a cable tray should be used or the hanger centres reduced
7
PROMATECT®-H/PROMATECT®-L/PROMATECT®-L500
PH/PL/PE
Electrical Cables Enclosure Fixing Details
51/52
Fixing of Boards
Internal Cross Section Dimensions
The Promat cable protection system is fabricated from
PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 boards
with thickness according to the tables on pages 6 and 7. The boards
can be fixed together with steel staples at maximum centres of
100mm or screws at maximum centres of 200mm in accordance with
the table below. Up to three layers of boards can be used to fabricate
the required thickness.
The internal cross section of the enclosure system shall not be more
than 1000mm wide x 500mm high. Please consult Promat for cross
sections not within this range.
This is a self-supporting system and does not require any internal
steel framework (subject to width and height of the enclosure not
exceeding set limits).
Board
thickness
Screws
at 200mm centres
Staples
at 100mm centres
9mm
25mm x No.6
28/10/1.2
15mm
30mm x No.6
32/10/1.2
20mm
38mm x No.6
50/11/1.5
25mm
50mm x No.6
63/11/1.5
30mm
63mm x No.8
63/11/1.5
35mm
63mm x No.8
70/12/2
40mm
75mm x No.8
80/12/2
50mm
100mm x No.10
80/12/2
60mm
100mm x No.10
90/12/2
75mm
Multi layer
Fix first layer with screws
100mm
Multi layer
Fix first layer with screws
Joints between the sections of enclosure are reinforced with
external cover strips of PROMATECT®-H, PROMATECT®-L or
PROMATECT®-L500 board, each 100mm wide and a minimum of
9mm thick. The cover strips are fixed with steel staples or screws.
Cables And Enclosure Support
Cables are normally supported on steel cable trays within the
enclosure but these are not always required when the enclosures are
subject to internal fire exposure only.
The enclosure system must be supported, either by direct fixing to
other structural elements with suitable proprietary steel fixings or
by hangers at maximum centres of 1220mm. The hanger supports
should coincide with enclosure joints. The hangers consist of steel
threaded rods and a steel angle bearer section under the protection
system. The tensile and bending stresses of the unprotected hangers
and bearers must not exceed 10N/mm2 for up to 120 minutes fire
resistance.
One, Two or Three Sided Protection
A one, two or three sided enclosure is acceptable where the other sides of the rectangle are formed from an adjoining wall and floor/ceiling
of a fire resistance at least equal to that of the enclosure system, and where under fire conditions the substrates will suffer no deflection or
excessive movement.
General view of two
sided enclosure
for external fire
protection
6
1
2
Brackets or hanger
rods and angles at maximum
1220mm centres
1
2
3
4
5
6
8
3
Cantilever brackets
at maximum 1220mm centres
Cable tray supported independently within the enclosure on brackets or hangers
PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 board, thickness in accordance with the table on page 6
PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 board, thickness in accordance with the table on page 7
Board joints to coincide with bracket positions
Board joints covered with PROMATECT®-H cover strip 100mm x 9mm thick
PROMATECT®-L or PROMATECT®-L500 cover strip or light steel angle
6
General view of two
sided enclosure
for internal fire
protection
5
4
PROMATECT®-H/PROMATECT®-L/PROMATECT®-L500
PH/PL/PE
Electrical Cables Enclosure Fixing Details
51/52
Wall Penetrations
The enclosure system, where it passes through a fire compartment
wall, has to be fire stopped. At this penetration, gaps up to 20mm
wide may be sealed with mineral wool and PROMASEAL®-A Acrylic
Sealant. For wider gaps, a PROMATECT®-H, PROMATECT®-L or
PROMATECT®-L500 collar is required on both sides of the wall. The
minimum collar dimensions should be 150mm x 20mm thick. Please
refer to illustration at right.
PROMATECT® collar
PROMATECT®
collar
Access hatches have to be properly constructed to maintain the
fire resistance level of the enclosure system. Hatches generally are
comprised of an inner board stapled or secured to the outer board.
The inner board should be a close fit to the opening and should be the
same thickness as the wall of the enclosure. The outer board should
be at least 20mm thick and overlap the opening by at least 50mm on
all sides.
Mineral wool seal
6
1
3
1
2
3
4
General view of construction of inspection opening
for external or internal fire protection
1
2
3
4
5
6
5
General construction of PROMASEAL®
Ventilation Grille and Promat Ventbox
PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500 electrical cable enclosure
Outer board sized 50mm larger all around than inner dimensions of opening and 20mm thick
Inner board stapled to outer board, sized to fit opening and same thickness as side wall of duct
“Tecserts” or similar at maximum 200mm centres
PROMASEAL® Ventilation Grille if required and as detailed in illustration at right
Promat Ventbox
When the cables exit the enclosure, the opening made must be stiffened
with PROMATECT®-H, PROMATECT®-L or PROMATECT®-L500
board of at least 50mm width x 20mm thickness. The gaps in the
opening must be fully sealed with PROMASEAL®-A Acrylic Sealant
for the full depth of the board and the thickness of the stiffener board.
See illustration below.
PROMASEAL®
Ventilation Grille
 Standard grille
size is 93mm x 93mm overall. Can be combined in multiples to
create a larger free area.
 Free area of one grille is 0.0035m2.
 Friction fit grille in aperture. Use VICUBOND® WR adhesive if a
loose fit.
 Grilles supplied in various thicknesses as follows:
35mm (for 30 minutes), 60mm or 2 x 35mm (for 60 minutes), 75mm
(for 90 minutes) and 75 + 35mm (for 120 minutes).
 Secure 50mm wide cover strips if necessary to ensure grille fully
surrounded by board.
 The grille is supported on the inside of the duct by a perforated
steel plate (supplied) secured to the duct wall.
Promat Ventbox
 The ventbox consists of an integral outer frame with collar and an
automatically operated closing lid which is activated by a thermal
link in the event of a fire.
Ventilation openings if required must also be fitted with PROMASEAL®
Ventilation Grille or Promat Ventbox. These fittings will ensure that the
fire resistance level of the enclosure system is maintained in case of
a fire.
 Free area 0.021m2.
 Outer dimensions of frame and collar are 515mm x 130mm.
 Insert ventbox frame into aperture, 465mm x 80mm, and screw
down to the board through the collars.
9
PROMATECT®-H/PROMATECT®-L/PROMATECT®-L500
Electrical Cables Enclosure (External Fire For Circuit Integrity/Internal Fire)
PH/PL/PE
Architectural Specification
51.30/51.60/
51.90/51.12/
52.30/52.60/
52.90/52.12
Following is the standard Architectural Specification for electrical cable enclosure system using PROMATECT®-H/PROMATECT®-L/
PROMATECT®-L500.(1) The designer must determine the suitability of the design to the application and performance requirements before
undertaking or constructing any works relating to the specifications and where in doubt should obtain the advice of a suitably qualified engineer.
External Fire For Circuit Integrity / Internal Fire
(1)
Up to 120 minute fire resistance, integrity and insulation in accordance with the criteria of AS 1530: Part 4: 2005 or BS 476: Part 20: 1987(1).
Supporting Structure
Care should be taken that any structural element by which the enclosure system is supported, e.g. a beam, floor or wall, has at least equivalent
fire resistance.
Lining Boards
Single-layer or multi-layer(1) ____________mm(2) thick PROMATECT®-H/PROMATECT®-L/PROMATECT®-L500(1) matrix engineered mineral
boards as manufactured by Promat International (Asia Pacific) Ltd. Internal and external cover strips made of 100mm wide and a minimum of
9mm thick boards, where applicable, are secured to the enclosure over the board joints.
Type of Fixing
The boards can be fixed together with steel staples at maximum 100mm or screws at maximum centres of 200mm according to the
manufacturer’s recommendations.
The complete enclosure system will be suspended with hangers at maximum centres of 1220mm with threaded rods, the whole support system
is to have less than 10N/mm2 of stress.
Tests & Standards
The complete system along with material and framing is approved to meet the requirements of AS 1530: Part 4: 2005 and/or BS 476: Part 20:
1987.
Jointing
Plain butt joints between machined edges of boards.(1)
Joints filled in preparation for painting.(1)
Joints filled and taped in preparation for decoration.(1)
Follow-on Trades
Surface of boards to be prepared for painting/plastering/tiling(1) in accordance with manufacturer’s recommendations.
NOTE:
• (1) delete as appropriate.
• (2) insert thickness as appropriate taken from tables on pages 6 and 7.
• Perimeter gaps will be filled with fire resistant PROMASEAL®-A Acrylic Sealant.
10
PROMATECT®-H
M&E Services Enclosure (Integrity & Insulation)
8
0
5
2
1
58.60/
58.12/
58.24
PH
3
4
9
7
7
8
4
2
6
Hanger and
stud fixing
Up to 60/60/60, 120/120/120 or 240/240/240 fire resistance in accordance with the requirements of BS 476: Part 20: 1987
1 PROMATECT®-H board and mineral wool, requirements in accordance with table below
2 PROMATECT®-H cover strips 100mm wide, thickness in accordance with table below
Fire resistance
Board/cover strip/collar
thickness
Mineral wool
thickness x density
Screw length
to frame
Screw length
to cover strips
Maximum stress
allowance of hangers
60/60/60
9mm
50mm x 60kg/m³
25mm
20mm
15N/mm²
120/120/120
15mm
50mm x 80kg/m³
32mm
25mm
10N/mm²
240/240/240
20mm
100mm x 100kg/m³
35mm
25mm
6N/mm²
Where the enclosure penetrates a fire compartment wall, use 100mm wide PROMATECT®-H collars, thickness in accordance with the above table,
fitted around the duct on both sides of the wall forming an L shape using M6 anchor bolts at nominal 600mm centres. See details on page 18
3 Galvanised steel collars minimum 50mm x 50mm x 0.9mm thick coinciding with board joints at nominal 1220mm centres
4 Galvanised steel angles minimum 50mm x 50mm x 0.7mm thick (60/60/60 to 120/120/120 fire resistance) or minimum 50mm x 50mm x 2mm
thick (240/240/240 fire resistance) for one, two, three sided construction at corner joints, or
galvanised steel angles minimum 30mm x 30mm x 0.7mm thick for four sided construction at corner joints
5 Threaded steel hanger rod, maximum stress allowance in accordance with the above table
6 Galvanised steel angles, minimum 30mm x 30mm x 3mm thick and vary in accordance with weight and dimensions of the enclosure and
maximum stress allowance of the hanger
7 Service steel hanger and support, size according to weight and dimensions of the services
8 No. 8 self-tapping screws at maximum 200mm centres, length in accordance with the above table
9 General M&E services, e.g. electrical cable, cable tray, steel pipes etc
0 Fill all penetration gaps with PROMASEAL®-A Acrylic Sealant
11
PROMATECT®-H
58I.12/
58I.24
PH
M&E Services Enclosure (Integrity Only)
2
Nom
inal
125
1
0m
m
5
3a
9
4
7
7
7
4
8
6
Hanger and
stud fixing
Fire resistance
Board/cover
board/collar
thickness
Maximum stress
allowance of hangers
120/120/-
9mm
10N/mm²
240/240/-
12mm
6N/mm²
3b
Galvanised
steel collars
50mm x 25mm x
0.5mm thick
50mm x 25mm x
0.7mm thick
3a Galvanised steel collars coinciding with board joints at nominal 1220mm
centres, size and thickness in accordance with the above table
3b Additional support galvanised steel collars at middle span of the enclosure,
size and thickness in accordance with the above table
4 Minimum 30mm x 30mm x 0.5mm thick galvanised steel angles at corner
Typical double/large span enclosure
Up to 120/120/- or 240/240/- fire resistance in accordance with the
requirements of BS 476: Part 20: 1987
5 Threaded steel hanger rod, maximum stress allowance in accordance with
1 PROMATECT®-H board, thickness in accordance with the
6 Galvanised steel angles, minimum 30mm x 30mm x 3mm thick and vary in
table at top right
2 PROMATECT -H cover plates 75mm x 75mm and filled
®
12
joints, consult Promat for appropriate dimensions specification
the above table as per the required fire resistance performance
accordance with weight and dimensions of the enclosure and maximum
stress allowance of the hanger
with PROMASEAL®-A Acrylic Sealant in all gaps where rod
hanger penetrates the enclosure, thickness in accordance
with the table at top right
7 Service steel hanger and support, size according to weight and dimensions
Where the enclosure penetrates a fire compartment wall,
use 100mm wide PROMATECT®-H collars, thickness in
accordance with the above table, fitted around the duct on
both sides of the wall forming an L shape using M6 anchor
bolts at nominal 600mm centres. See details on page 18
8 Minimum 25mm long self-tapping screws at nominal 200mm centres
of the services
9 General M&E services, e.g. electrical cable, cable tray, steel pipes etc
PROMATECT®-L500
PE
M&E Services Enclosure (Integrity & Insulation /
Without Cover Strip)
58.12.1/
58.24.1
9
1
8
4
2
7
6
3
5
Up to 120/120/120 or 240/240/240 fire resistance in accordance with the requirements of BS 476: Part 20: 1987
1 PROMATECT®-L500 board, thickness in accordance with table below
Fire resistance
Board
thickness
Screw length
Maximum stress
allowance of hangers
120/120/30
25mm
50mm
10N/mm²
240/240/120
50mm
75mm
6N/mm²
Where the enclosure penetrates a fire compartment wall, use 100mm wide x 9mm thick PROMATECT®-H collars, fitted around the duct on both
sides of the wall forming an L shape using M6 anchor bolts at nominal 600mm centres. See details on page 18
2 Galvanised steel collars minimum 50mm x 25mm x 0.5mm thick at nominal 1220mm centres. All board joints to coincide with a framing member
3 Galvanised steel angle minimum 30mm x 30mm x 0.5mm thick at corners
4 Threaded steel hanger rod, maximum stress allowance in accordance with the above table
5 Galvanised steel angles, minimum 30mm x 30mm x 3mm thick and vary in accordance with weight and dimensions of the enclosure and
maximum stress allowance of the hanger
6 Service steel hanger and support, size according to weight and dimensions of the services
7 No. 8 self-tapping screws at maximum 200mm centres, length in accordance with the above table
8 General M&E services, e.g. electrical cable, cable tray, steel pipes etc
9 Fill all penetration gaps with PROMASEAL®-A Acrylic Sealant
13
PROMATECT®-L500
M&E Services Enclosure (Integrity & Insulation)
7
0
5
2
1
58.12.2/
58.24.2
PE
3
4
9
6
7
8
4
2
6
Hanger and
stud fixing
Up to 120/120/120 or 240/240/240 fire resistance in accordance with the requirements of BS 476: Part 20: 1987 and AS 1530: Part 4: 2005
1 PROMATECT®-L500 board and mineral wool, requirements in accordance with table below
2 100mm wide PROMATECT®-H cover strips, thickness in accordance with table below
(1)
Fire resistance
Board/cover strip/collar
thickness
Mineral wool
thickness x density
Screw length
Maximum stress
allowance of hangers
120/120/120 (1)
20mm
50mm x 100kg/m³
45mm
10N/mm²
240/240/240
50mm
80mm x 80kg/m³
75mm
6N/mm²
Tested to BS 476: Part 20: 1987 only
Where the enclosure penetrates a fire compartment wall, use 100mm wide PROMATECT®-H collars, thickness in accordance with the above table,
fitted around the duct on both sides of the wall forming an L shape using M6 anchor bolts at nominal 600mm centres. See details on page 18
3 Galvanised steel collars 50mm x 50mm x 0.9mm thick coinciding with board joints at nominal 1220mm centres. See more details on page 17
4 Galvanised steel angles minimum 50mm x 50mm x 0.9mm thick for one, two, three sided construction at corner joints, or
galvanised steel angles minimum 30mm x 30mm x 0.5mm thick for four sided construction at corner joints
5 Threaded steel hanger rod, maximum stress allowance in accordance with the above table
6 Galvanised steel angles, minimum 30mm x 30mm x 3mm thick and vary in accordance with weight and dimensions of the enclosure and
maximum stress allowance of the hanger
7 Service steel hanger and support, size according to weight and dimensions of the services
8 No. 8 self-tapping screws at maximum 200mm centres, length in accordance with the above table
9 General M&E services, e.g. electrical cable, cable tray, steel pipes etc
0 Fill all penetration gaps with PROMASEAL®-A Acrylic Sealant
14
PROMINA® 60
PMF
M&E Services Enclosure (Integrity & Insulation)
9
58.60
2
6
1
3
4
5
0
8
8
5
9
7
Hanger and
stud fixing
Up to 60/60/60 fire resistance in accordance with the requirements of BS 476: Part 20: 1987
1 PROMINA® 60 board 9mm thick
Where the enclosure penetrates a fire compartment wall, use 100mm wide x 9mm thick PROMINA® 60 collars fitted around the duct on both sides
of the wall forming an L shape using M6 anchor bolts at nominal 600mm centres. See details on page 18
2 PROMINA® 60 cover plates 75mm x 75mm x 9mm thick and filled with PROMASEAL®-A Acrylic Sealant in all gaps where rod hanger penetrates
the enclosure
3 Mineral wool 50mm x 100kg/m³
4 Galvanised steel collars 50mm x 30mm x 0.6mm thick coinciding with board joints at nominal 1220mm centres
5 Galvanised steel angles minimum 50mm x 50mm x 0.5mm thick for one, two, three or four sided construction at corner joints
6 Threaded steel hanger rod, maximum stress allowance 15N/mm²
7 Galvanised steel angles, minimum 30mm x 30mm x 3mm thick and vary in accordance with weight and dimensions of the enclosure
8 Service steel hanger and support, size according to weight and dimensions of the services
9 No. 8 x 25mm self-tapping screws at maximum 200mm centres
0 General M&E services, e.g. electrical cable, cable tray, steel pipes etc
15
PROMINA® 60
PMF
M&E Services Enclosure (Integrity Only)
58I.60
2
Nom
inal
122
1
0m
m
5
3a
9
7
7
7
4
4
8
6
Hanger and
stud fixing
3a Galvanised Galvanised steel collars 50mm x 30mm x 0.6mm coinciding
with board joints at nominal 1220mm centres
3b Additional support galvanised steel collars 50mm x 30mm x 0.6mm at
middle span of the enclosure
3b
4 Minimum 30mm x 30mm x 0.5mm thick galvanised steel angles at corner
joints, consult Promat for appropriate dimensions specification
5 Threaded steel hanger rod, maximum stress allowance 10N/mm²
Typical double/large span enclosure
6 Galvanised steel angles, minimum 30mm x 30mm x 3mm thick and vary in
accordance with weight and dimensions of the enclosure
Up to 120/120/- fire resistance in accordance with the requirements
of BS 476: Part 20: 1987
1 PROMINA® 60 board 9mm thick
Where the enclosure penetrates a fire compartment wall,
use 100mm wide x 9mm thick PROMINA® 60 collars fitted
around the duct on both sides of the wall forming an L
shape using M6 anchor bolts at nominal 600mm centres.
See details on page 18
2 PROMINA® 60 cover plates 75mm x 75mm x 9mm thick and
filled with PROMASEAL®-A Acrylic Sealant in all gaps where
rod hanger penetrates the enclosure
16
7 Service steel hanger and support, size according to weight and dimensions
of the services
8 No. 8 x 25mm self-tapping screws at nominal 200mm centres
9 General M&E services, e.g. electrical cable, cable tray, steel pipes etc
PROMATECT®-H/PROMATECT®-L500/PROMINA® 60
M&E Services Enclosure Fixing Details
PH/PE/
PMF
58/58I
Internal Steel Framework
Building Services And Enclosure Support
The corner junctions of the enclosure are reinforced with internal
steel angles, minimum size according to system specification. These
corner angles are not necessary if boards of thickness 20mm and
above are used, as the boards can be fixed to
each other using deep thread drywall type
screws or steel wire staples.
The hangers used to support the building services enclosure
must have tensile and bending stresses not exceeding 15N/mm2,
10N/mm2 and 6N/mm2 for fire resistance up to 60, 120 and 240
minutes respectively. If these stress levels are exceeded, the size of
the hanger members must be increased or, alternatively, the spacing
of the hangers reduced.
The fixings used to fasten the threaded hanger rods to concrete
soffits must be all steel expanding anchors with at least 80mm
length penetrating into the concrete of at least 40mm for 120
minute fire resistance and 60mm for 240 minute fire resistance.
The anchors must match the size of the threaded rods, be of
sufficient strength to support the weight of the enclosure and be
fitted in accordance with the manufacturer’s specification. When
the hanger rods are suspended from protected structural steel
beams, the rods must be protected for at least 300mm from the
beams with the same levels of protection as the structural beams.
External steel angle
Internal steel angle
Four-sided steel channel collars are positioned at approximately
1220mm centres to support the boards. The steel channels are of
minimum size 50mm x 25mm x 0.5mm, up to 50mm x 50mm x 1.2mm
thick depending on the system specification.
Collar section with external cover strips
Steel channel framed enclosure
Fixing of Boards & Mineral Wool
The type of board and thickness shall be selected according to system
specification and the required fire resistance level. The boards are
fastened to the channel frames and corner angles with self-tapping
screws of appropriate length at 200mm nominal centres.
For systems where corner angles are not used, i.e. for 20mm or
thicker boards, the boards are to be fastened at the corners with
steel self-tapping screws at 200mm nominal centres or steel staples
at 100mm nominal centres as per the below table.
Board
thickness
Screws
at 200mm centres
Staples
at 100mm centres
9mm
25mm x No.6
–
15mm
30mm x No.6
–
20mm
38mm x No.6
63/10/1.0
50mm
100mm x No.10
80/12/2.0
Longitudinal joints in the boards (other than the corner joints) must
be backed by a steel channel. All butt joints, as required by system
specification, are covered with 100mm x 9mm thick PROMATECT®-H
cover strips that may be placed either externally or internally.
The cavity between the boards and the building services is filled
with mineral wool with thickness and density corresponding to the
system’s requirement. The steel channels are also filled with the same
mineral wool. See the illustrations of Collar section with external or
internal cover strips.
Collar section with internal cover strips
Where the hangers exceed 2000mm in length, the hangers should be
clad with a material of similar thickness to the enclosure to prevent
excessive thermal expansion.
Where the hanger rods emerge from the enclosure, the hole/slot must
be sealed with PROMASEAL®-A Acrylic Sealant and with or without
a cover plate depending on the gap at penetration. Please consult
Promat when in doubt.
If the building service being encased is a plastic pipe, external hangers
and angles will be required to independently support the enclosure.
17
PROMATECT®-H/PROMATECT®-L500/PROMINA® 60
M&E Services Enclosure Fixing Details
PH/PE/
PMF
58/58I
Wall Penetrations
Where the enclosure passes through a fire compartment wall, the
penetration must be properly fire stopped. At this penetration, gaps up
to 20mm wide may be sealed with mineral wool and PROMASEAL®-A
Acrylic Sealant. For wider gaps, a PROMATECT®-H, PROMATECT®-L,
PROMATECT®-L500 or PROMINA® 60 collar is required on both sides
of the wall. The minimum collar dimensions should be 150mm x
20mm thick. The space between the enclosure and the reveal of the
opening in the wall is filled with mineral wool of minimum 110kg/m3
density. One layer of L-shaped PROMATECT®-H collar is required to
be fitted around the enclosure on both sides of the wall. See tables on
pages 11 to 14 for thicknesses suitable for different types of enclosure
and fire resistance requirements. Please refer to illustration at right.
PROMATECT®-H collar
PROMATECT®-H
collar
Mineral wool seal
Internal Cross Section Dimensions
(more than 1500mm x 1500mm)
The maximum approved internal dimensions of the enclosure
is 6000mm wide x 2500mm high. For enclosures with internal
dimensions greater than 1500mm x 1500mm, additional threaded
rods are fitted at each hanger position, at 1220mm maximum centres
across the width of the enclosure. These threaded rods pass through
the enclosure and support the horizontal hanger support element
beneath the enclosure. The rods also support the top of the enclosure
using a nut and large steel washer, this prevents bowing under fire
conditions of wide enclosure systems.
As the width of the enclosure system increases, the spacing of
the channel collars must be reduced so that the maximum area of
unsupported board does not exceed 1.5m2.
Typical enclosure up to 6000mm wide x 2500mm high
The penetrations of the rods through the enclosure are sealed with
PROMASEAL®-A Acrylic Sealant.
Please note, the requirements for additional hanger support within
the duct for greater width, e.g. 6000mm duct, will require two
central supports at maximum 1220mm centres.
One, Two or Three Sided Protection
One, two or three sided enclosures are constructed in the same way
as a four sided enclosure. Steel angles of 50mm x 50mm x 0.9mm
thick and 3mm thick for up to 120 and 240 minutes fire protection
respectively, are fastened to the floor soffit or wall with M8 all steel
expanding anchors at 500mm nominal centres. The PROMATECT®-H,
PROMATECT®-L500 or PROMINA® 60 boards forming the walls of the
protection to the building services are then fastened to the angles with
steel self-tapping drywall type screws in appropriate length at 200mm
nominal centres. The services are independently supported.
Two sided M&E services enclosure
One sided M&E services enclosure
18
Three sided M&E services enclosure
PROMATECT®-H/PROMATECT®-L500/PROMINA® 60
M&E Services Enclosure Fixing Details
PH/PE/
PMF
58/58I
Transformation Sections
The figure to the right shows a common
transformation section. Where board joints abut
at an angle and it is not possible to back the
joint with steel channels, angles bent to the
appropriate degree are used to back
these joints.
The steel channels should always
be placed to limit the total
unsupported area of board to
a maximum of 1.5m2. Bends
or curved shapes must be
supported with hangers at
mid-span.
Vertical Enclosures
Access Panels
The construction of vertical enclosures is the same as for the
horizontal enclosures. Where a vertical enclosure is located adjacent
to a wall, the enclosure should be restrained back to the wall with
threaded rods and support sections.
Maximum allowable dimensions of access panels are 600mm x
600mm. The panels are fixed to the enclosure through steel channels
using steel bolts and nuts at nominal 200mm centres. The thickness
of the boards and the mineral wool specifications should be according
to system requirements. The mineral wool can be encapsulated within
the C-channel sections which in turn are fixed to the access panel by
means of steel self-tapping screws.
Enclosure
The weight of the enclosure assembly must be fully supported at
each floor level. Steel angles may be fitted to the enclosure at floor
penetration level and sit upon the floor slab, supporting the weight of
the enclosure.
Access panel
Cross section of access panel
19
PROMATECT®-H/PROMATECT®-L500/PROMINA® 60
M&E Services Enclosure (Integrity & Insulation/Integrity Only)
Architectural Specification
PH/PE
58.60/58I.60
58.12/58I.12/
58.24/58I.24
Following is the standard Architectural Specification for general building services enclosure system constructed using PROMATECT®-H/
PROMATECT®-L500/PROMINA® 60.(1) The designer must determine the suitability of the design to the application and requirements before
undertaking or constructing any works relating to the specifications and where in doubt should obtain the advice of a suitably qualified engineer.
External & Internal Fire
____________ minute integrity and ____________ minute insulation in accordance with the criteria of AS 1530: Part 4: 2005 and/or BS 476:
Part 20: 1987.(1)
Supporting Structure
Care should be taken that any structural element by which the enclosure system is supported, e.g. a beam, floor or wall, has at least equivalent
fire resistance.
Lining Boards
Single-layer ____________mm(2) thick PROMATECT®-H/PROMATECT®-L500/PROMINA® 60(1) matrix engineered mineral boards as manufactured
by Promat International (Asia Pacific) Ltd. Internal or external cover strips made of 100mm wide and a minimum of ____________mm(2) thick
boards, where applicable, are secured to the enclosure over the board joints.
Type of Fixing
Galvanised steel frame made of channel sections minimum 50mm x 25mm x 0.5mm thick, up to 50mm x 50mm x 1.2mm thick depending on
the system specification, at 1220mm centres or at every butt joint of boards, with corner angles 30mm x 30mm with thickness of 0.5mm or
0.7mm, depending on the system specification, are fixed to the channel collars at the corners. The services will be suspended with hanger rods
with hanger diameter sized to limit stress, ____________N/mm2 (3).
PROMATECT®-H/PROMATECT®-L500/PROMINA® 60(1) boards will be screw fixed to the frame with ____________mm(4) self-tapping screws
at 200mm centres. Where applicable, butt joints should be covered with 100mm wide x ____________mm(2) thick cover strips. Mineral wool in
accordance with the system specification will be tightly filled around the existing services, i.e. between the gap of boards and the services.
Tests & Standards
The complete system along with material and framing is approved to meet the requirements of AS 1530: Part 4: 2005 and/or BS 476: Part 20:
1987.
Jointing
Plain butt joints between machined edges of boards.(1)
Joints filled in preparation for painting.(1)
Joints filled and taped in preparation for decoration.(1)
Follow-on Trades
Surface of boards to be prepared for painting/plastering/tiling(1) in accordance with manufacturer’s recommendations.
NOTE:
• (1) delete as appropriate.
• (2) insert appropriate board thickness taken from which system detailed on pages 11 to 14.
• (3) insert hanger stress limits by not exceeding 15N/mm2 for 60 minutes, 10N/mm2 for 120 minutes or 6N/mm2 for 240 minutes.
• (4) insert screw length as appropriate taken from which system detailed on pages 11 to 14.
• Perimeter gaps will be filled with fire resistant PROMASEAL®-A Acrylic Sealant.
20
PROMATECT®-S
58.12/
58.24
PS
M&E Services Enclosure (Integrity & Insulation)
2
1
3
6
7
4
2
5
Up to 120/120/120 or 240/240/240 fire resistance in accordance with the requirements of BS 476: Part 20: 1987
1 PROMATECT®-S board and mineral wool, requirements in accordance with table below
Fire resistance
Board thickness
Mineral wool
thickness x density
120/120/120
6mm
100mm x 140kg/m³
240/240/240
9.5mm
140mm x 140kg/m³
2 Galvanised steel flanges, fabricated by cutting and welding 50mm x 50mm x 3mm thick angles, are bolted together with M10 nuts and bolts at
nominal 200mm centres to form continuous sections
3 Corner galvanised steel angle reinforcement, 50mm x 50mm x 3mm thick, these corner angles do not require any mechanical fixing to the
flanges 2
4 Enclosure steel hanger and supporting angle, size according to weight and dimensions of the enclosure and the required fire resistance.
Maximum spacing of hanger is 1800mm centres. Stress limits less than 10N/mm² for 120/120/120 fire resistance and 6N/mm² for 240/240/240
fire resistance
5 Service steel hanger and support, size according to weight and dimensions of the services
6 35mm x 5.5mm Teks screws at nominal 200mm centres
7 General M&E services, e.g. cable trunking, steel pipes etc
The above M&E services enclosure is suitable for providing protection to services even under extremely aggressive environments
The maximum permissible dimensions for this enclosure are 2000mm x 500mm for up to 240/240/240 fire resistance. The width may be increased to
3000mm if an additional threaded rod is fitted at each hanger position at about mid width which passes through the enclosure and supports the angle
of the hanger under the enclosure
21
PROMATECT®-S
58I.12/
58I.24
PS
M&E Services Enclosure (Integrity Only)
1
2
3
6
7
4
5
2
Up to 120/120/- or 240/240/- fire resistance in accordance with the requirements of BS 476: Part 20: 1987
1 PROMATECT®-S board, thickness in accordance with table below
Fire resistance
Board thickness
120/120/-
6mm
240/240/-
9.5mm
2 Galvanised steel flanges, fabricated by cutting and welding 50mm x 50mm x 3mm thick angles, are bolted together with M10 nuts and bolts at
nominal 500mm centres to form continuous sections
3 Corner galvanised steel angle reinforcement, 50mm x 50mm x 3mm thick for enclosure up to 1500mm x 1500mm; 50mm x 50mm x 5mm thick
for enclosure up to 2000mm x 2000mm
4 Enclosure steel hanger and supporting angle, size according to weight and dimensions of the enclosure and the required fire resistance.
Maximum spacing of hanger is 1800mm centres
5 Service steel hanger and support, size according to weight and dimensions of the services
6 35mm x 5.5mm Teks screws at nominal 200mm centres
7 General M&E services, e.g. cable trunking, steel pipes etc
The above M&E services enclosure is suitable for providing protection to services even under extremely aggressive environments
The maximum permissible dimensions for this enclosure are 6000mm x 2000mm for up to 240/240/- fire resistance. Where the enclosure is more than
2400mm wide, all intermediate longitudinal board joints will require additional steel framing at the joints of 50mm x 50mm x 3mm thick double angles
(back to back) or 50mm x 50mm x 6mm thick T-section
22
PROMATECT®-S
M&E Services Enclosure Fixing Details
PS
58/58I
Steel Framework
The corner junctions of the PROMATECT®-S M&E services enclosure are reinforced with internal steel angles, minimum size 50mm x 50mm x
3mm. The PROMATECT®-S board is connected with M5.5mm steel self-tapping Teks screws at 200mm centres. Transverse board joints are
connected in the same manner but with 100mm x 3mm thick steel flat.
2
1
3
External steel angle
2
1
3
Internal steel angle
1 PROMATECT®-S board, 6 or 9.5mm thick depending on required fire resistance performance
2 Galvanised steel flanges, fabricated by cutting and welding 50mm x 50mm x 3mm thick angles, are bolted together with M10 nuts and bolts at
nominal 500mm centres to form continuous sections
3 Corner galvanised steel angle reinforcement, 50mm x 50mm x 3mm thick for enclosure up to 1500mm
x 1500mm or 50mm x 50mm x 5mm thick for enclosure up to 2000mm x 2000mm
Fitting of Mineral Wool
Mineral wool insulation is laid in the soffit boards of the PROMATECT®-S enclosure.
For the top and sides, however, the insulation is fixed in place using nominal M4 selftapping screws with 25mm diameter steel washers at nominal 300mm centres in a grid
formation. If the insulation is fitted in two or more layers, the joints between the slabs
are staggered by at least 300mm between layers. If the insulation is fitted in a single
layer, the joints between slabs are sealed and bonded together using VICUBOND® WR
adhesive.
23
PROMATECT®-S
M&E Services Enclosure Fixing Details
PS
58/58I
Internal Cross Section Dimensions
Wall Penetrations
The maximum approved internal dimension of the enclosure is
2500mm wide x 500mm high. The width may be increased to 3000mm
if an additional rod is fitted at each hanger position at mid width. The
rod passes through the enclosure and supports the horizontal bearer
of the support system beneath the enclosure. The rod also supports
the top of the enclosure with a nut and large steel washer on each
side of the board. The penetration of the rod through the enclosure
must be sealed with PROMASEAL®-A Acrylic Sealant.
Where the enclosure passes through a fire compartment wall, the
penetration must be properly constructed and sealed. Angles 50mm
x 50mm x 3mm are fixed to the top and sides of the enclosure and
should be set in a position central to the thickness of the compartment
wall. The gap between the exterior surface of the enclosure and the
perimeter of the wall aperture should be filled either side and over the
angles using 140kg/m3 mineral wool slabs friction fitted. The aperture
is then covered by an L-shape PROMATECT®-S collar which should
extend from the surface of the enclosure and overlap the wall aperture
by a minimum of 100mm. The PROMATECT®-S collar should be fixed
to the wall using all-steel anchors at nominal 500mm centres.
Building Services & Enclosure Support
The hangers used to support the building services enclosure must
have tensile and bending stresses not exceeding 10N/mm2 and
6N/mm2 for fire resistance up to 120 and 240 minutes respectively.
If these stress levels are exceeded, the size of the hanger members
must be increased. Alternatively, the spacing of the hangers can be
reduced. The maximum spacing of the hangers is 1800mm centres
but this depends on the length of the individual sections.
PROMATECT®-S
collar
PROMATECT®-S collar
The fixings used to fasten the threaded hanger rods to concrete
soffits must be all steel expanding anchors with a penetration into the
concrete of at least 40mm for 120 minute fire resistance and 60mm
for 240 minute fire resistance. The anchors must match the size of
the threaded rods and be of sufficient strength to support the weight
of the enclosure. Anchors must be fitted in accordance with the
manufacturer’s specification. When the hanger rods are suspended
from protected structural steel beams, the rods must be protected for
at least 300mm from the beams with the same levels of protection as
the structural beams.
Mineral wool seal
If the building service being encased is a plastic pipe, external hangers
and angles will be required to independently support the enclosure.
One, Two or Three Sided Protection
One, two or three sided enclosures are constructed in the same
manner as a four sided enclosure. The PROMATECT®-S board is
connected to the masonry/concrete wall or concrete floor soffit using
the same steel angle and screws to the board and M12 all steel
expansion bolts, at 500mm maximum centres into the substrate. The
bolts must have a minimum penetration into the wall or floor of 60mm.
The services are independently supported.
Two sided M&E services enclosure
One sided M&E services enclosure
Three sided M&E services enclosure
24
PROMATECT®-S
M&E Services Enclosure (Integrity & Insulation/Integrity Only)
Architectural Specification
PS
58.12/58.24/
58I.12/58I.24
Following is the standard Architectural Specification for general building services enclosure system using PROMATECT®-S. The designer
must determine the suitability of the design to the application and requirements before undertaking or constructing any works relating to the
specifications and where in doubt should obtain the advice of a suitably qualified engineer.
External & Internal Fire
Up to 240 minutes fire resistance, integrity and where pertinent insulation in accordance with the criteria of BS 476: Part 20: 1987.
Supporting Structure
Care should be taken that any structural element by which the enclosure system is supported, e.g. a beam, floor or wall, has at least equivalent
fire resistance.
Lining Boards
Single-layer 6mm/9.5mm(1) PROMATECT®-S cement/steel composite boards as manufactured by Promat International (Asia Pacific) Ltd.
Type of Fixing
The services will be suspended with hanger rods of diameter sized to limit stress, = 10N/mm2 and = 6N/mm2 for 120 minute and 240 minute
fire exposure respectively. Mild steel frame made of steel angles, minimum size 50mm x 50mm of thickness 3mm or 5mm, depending on the
system specification, are used at the corners of the enclosure. 100mm x 3mm thick steel flat plates are positioned such that they coincide with
the transverse joints of the boards. The steel framework may be mechanically connected or welded together at all junctions.
PROMATECT®-S boards will be screw fixed to the frame with 35mm x 5.5mm Teks screws at 200mm centres. Mineral wool in accordance with
the system specification will be tightly filled around the existing services, i.e. between the gap of boards and the services. External hangers
to support the enclosure with hanger diameter sized to limit stress, = 10N/mm2 and = 6N/mm2 for 120 minute and 240 minute fire exposure
respectively are located at not more than 1800mm centres.
Tests & Standards
The complete system along with the material and framing is approved to meet the requirements of BS 476: Part 20: 1987.
NOTE:
• (1) delete as appropriate.
• Perimeter gaps will be filled with fire resistant PROMASEAL®-A Acrylic Sealant.
25
PROMATECT® 50
P50
Riser Pipes Enclosure (Integrity & Insulation)
5
54.12/
54.24
3
4
2
7
6
1
Up to 120/120/120 or 240/240/240 fire resistance in accordance with the requirements of BS 476: Part 20: 1987 and FSB/PSB/001/00 test procedure
1 PROMATECT® 50 board and mineral wool, requirements in accordance with table below
Fire resistance
Board thickness
Mineral wool
thickness x density
Screw length
Maximum stress
allowance of hangers
120/120/120
15mm
50mm x 100kg/m³
45mm
10N/mm²
240/240/240
19mm
50mm x 100kg/m³
65mm
6N/mm²
2 Galvanised steel angle or collar minimum 50mm x 50mm x 0.6mm thick at maximum 1220mm centres
3 Joints to be fully sealed with all purpose plaster jointing compound
4 Galvanised steel angle minimum 30mm x 30mm x 0.6mm at corners
5 Riser pipe steel hanger and support, maximum stress allowance in accordance with the above table
6 No. 6 self-tapping screws at nominal 200mm centres, length in accordance with the above table
7 Riser pipe, with diameter and pipe thickness fall within following range
Nominal pipe diameter
100mm to 600mm
26
Pipe thickness
5mm to 12.5mm
Hp/A
-1
210m to 12.6m-1
PROMATECT® 50
P50
Riser Pipes Enclosure Fixing Details
54
Wall Penetrations
Where the enclosure passes through a fire compartment wall, the penetration must be properly sealed. The gap between the enclosure and the
wall opening is fully filled with PROMASEAL®-A Acrylic Sealant.
Typical riser pipes enclosure in wall penetration
Alternative method for
riser pipes enclosure in wall penetration
One, Two or Three Sided Protection
One, two or three sided enclosures are constructed in the same way
as a four sided enclosure. Steel angles of 40mm x 40mm x 0.6mm
thick are fastened to the floor soffit or wall with M6 all steel expanding
anchors at 600mm nominal centres. The PROMATECT® 50 boards
forming the walls of the protection to the building services are then
fastened to the angles with steel self-tapping screws in appropriate
length at 200mm nominal centres. The services are independently
supported.
Two sided riser pipes enclosure
One sided riser pipes enclosure
Three sided riser pipes enclosure
27
PROMATECT® 50
Riser Pipes Enclosure (Integrity & Insulation)
Architectural Specification
P50
54.12/
54.24
Following is the standard Architectural Specification for general building services enclosure system using PROMATECT® 50. The designer
must determine the suitability of the design to the application and requirements before undertaking or constructing any works relating to the
specifications and where in doubt should obtain the advice of a suitably qualified engineer.
External & Internal Fire
Up to 240 minutes fire resistance, integrity and where pertinent insulation in accordance with the criteria of BS 476: Part 20: 1987 and
FSB/PSB/001/00 Test Procedure.
Supporting Structure
Care should be taken that any structural element by which the enclosure system is supported, e.g. a beam, floor or wall, has at least equivalent
fire resistance.
Lining Boards
Single-layer 15mm/19mm(*) PROMATECT® 50 cement bound matrix boards as manufactured by Promat International (Asia Pacific) Ltd.
Type of Fixing
The services will be suspended with hanger rods of diameter sized to limit stress, = 10N/mm2 and = 6N/mm2 for 60 minutes and 240 minutes fire
exposure respectively. Steel frame is comprised of mild steel collars of 50mm x 50mm thickness and 6mm steel angle or “U” channel, located
at maximum 1220mm intervals, and connected by steel corner angle of 30mm x 30mm x 0.6mm at four corners.
PROMATECT® 50 boards will be screw fixed to the frame with No. 6 self-tapping drywall screws of appropriate length at nominal 200mm
centres. Mineral wool in accordance with the system specification will be tightly filled around the existing riser pipe, i.e. between the gap of
boards and the pipe.
Tests & Standards
The complete system along with the material and framing is approved to meet the requirements of BS 476: Part 20: 1987 and FSB/PSB/001/00
dated March 2007.
NOTE:
• (1) delete as appropriate.
• Perimeter gaps will be filled with fire resistant PROMASEAL®-A Acrylic Sealant.
28
PROMATECT® 50
P50
M&E Services Enclosure (Integrity & Insulation)
58I.60
2
6
1
5
7
2
8
4
1
7
Up to -/60/60 fire resistance in accordance with the requirements of BS 476: Parts 20 and 22: 1987
1 Two layers of PROMATECT® 50 board 15mm thick
2 Two layers of PROMATECT® 50 board 15mm thick access panel, maximum size 450mm x 350mm (optional)
3 Galvanised steel angle minimum 50mm x 50mm x 1mm
4 Galvanised steel angle minimum 60mm x 30mm x 1mm
5 Galvanised steel channel minimum 30mm x 50mm x 30mm x 1.2mm
6 M6 steel anchor bolts at nominal 500mm centres
7 No. 6 self-tapping screws at nominal 200mm centres
8 General M&E services
29
PROMATECT® 50
M&E Services Enclosure (Integrity & Insulation)
Architectural Specification
P50
58I.60
Following is the standard Architectural Specification for general building services enclosure system using PROMATECT® 50. The designer
must determine the suitability of the design to the application and requirements before undertaking or constructing any works relating to the
specifications and where in doubt should obtain the advice of a suitably qualified engineer.
External & Internal Fire
Up to 60 minutes fire resistance, integrity and insulation in accordance with the criteria of BS 476: Parts 20 and 22: 1987.
Supporting Structure
Care should be taken that any structural element by which the enclosure system is supported, e.g. a beam, floor or wall, has at least equivalent
fire resistance.
Lining Boards
Double layer 15mm PROMATECT® 50 cement bound matrix boards as manufactured by Promat International (Asia Pacific) Ltd.
Type of Fixing
The services will be fixed to wall or floor slab with appropriate steel anchor fixing. Steel frame comprised of 30mm x 50mm of thickness 1.2mm
steel channel and minimum 50mm x 50mm x 1.0mm angle, are constructed around services forming an enclosure for protection purposes.
Depending on dimensions of enclosure, additional supporting brackets may be incorporated where necessary.
Both layers of PROMATECT® 50 boards will be screw fixed to the frame with No. 6 self-tapping drywall screws of appropriate length at nominal
200mm centres.
Where necessary, access panel of maximum dimensions 350mm x 450mm, fabricated using 2 x 15mm PROMATECT® 50 boards may be
incorporated.
Tests & Standards
The complete system along with the material and framing is approved to meet the requirements of BS 476: Part 20: 1987.
NOTE:
• Perimeter gaps will be filled with fire resistant PROMASEAL®-A Acrylic Sealant.
30
PROMASTOP® CIS
Coating For Electrical Cables
CIS
57
1
3
2
Circuit integrity in accordance with the requirements of FM 3971 Approval Standard
1 PROMASTOP® CIS coated electrical cable and cable tray to provide DFT (dry film thickness) of minimum 1.6mm
2 Service steel hanger and support, size according to weight and dimensions of the services
3 General M&E services, e.g. electrical cable and cable tray
NOTE: In general coatings to cables are designed to restrict the spread of flame along the cables and thus reduce propagation of fire. Thin film coatings
will maintain circuit integrity to small diametrical cables in restricted applications. The specifier must use with caution when recommending cable
coatings to ensure the performance criteria clearly matches their expectations and requirements. If there is any doubt regarding performance and
the maintenance of the circuit integrity is imperative, the specifier should consider the use of a board cladding system. For further clarification and
assistance, please consult Promat
31
PROMASTOP® CIS Coating For Electrical Cables
Architectural Specification
CIS
57
Following is the standard Architectural Specification for cable coating system using PROMASTOP® CIS. The designer must determine the
suitability of the design to the application and requirements before undertaking or constructing any works relating to the specifications and
where in doubt should obtain the advice of a suitably qualified engineer.
External & Internal Fire
Maintain circuit integrity of cables in accordance with the criteria of FM 3971 Approval Standard.
Supporting Structure
Care should be taken that any structural element by which the enclosure system is supported, e.g. a beam, floor or wall, has at least equivalent
fire resistance.
Coating
DFT of minimum 1.6mm of PROMASTOP® CIS cable coating as supplied by Promat International (Asia Pacific) Ltd.
Application
The services will be suspended with hanger rods of diameter sized to limit stress = 15N/mm2 to withstand at least 60 minutes fire. PROMASTOP®
CIS is applied to the cables for a DFT of minimum 1.6mm. Cable trays, if supporting cables, should be coated in a similar manner.
Tests & Standards
The complete system along with the material and framing is approved to meet the requirements of FM 3971 Approval Standard.
32
For latest information of the Promat Asia Pacific organisation,
please refer to www.promat-ap.com.
ASIA PACIFIC HEADQUARTERS
HONG KONG
Promat International (Asia Pacific) Ltd.
Unit 19-02-01, Level 2 PNB Damansara
No.19 Lorong Dungun, Damansara Heights
50490 Kuala Lumpur
MALAYSIA
Tel:
+60 (3) 2095 5111
Fax:
+60 (3) 2095 6111
Email: info@promat-ap.com
Promat International (Asia Pacific) Ltd.
Room 1010, C.C. Wu Building
302-308 Hennessy Road
Wanchai
Tel:
+852 2836 3692
Fax:
+852 2834 4313
Email: apromath@promat.com.hk
AUSTRALIA
Promat (Malaysia) Sdn. Bhd.
(India Representative Office)
610-611, Ansal Imperial Tower
C-Block, Community Centre
Naraina Vihar, Naraina
New Delhi 110028
Tel:
+91 (11) 2577 8413
Fax:
+91 (11) 2577 8414
Email: info-india@promat-asia.com
Promat Australia Pty. Ltd.
1 Scotland Road
Mile End South, SA 5031
Tel:
1800 PROMAT (776 628)
Fax:
+61 (8) 8352 1014
Email: mail@promat.com.au
New South Wales Office
Promat Australia Pty. Ltd.
Unit 1, 175 Briens Road
Northmead, NSW 2152
Tel:
1800 PROMAT (776 628)
Fax:
+61 (2) 9630 0258
Email: mail@promat.com.au
Victoria Office
Promat Australia Pty. Ltd.
Suite 205, 198 Harbour Esplanade
Docklands, VIC 3008
Tel:
1800 PROMAT (776 628)
Fax:
1800 334 598
Email: mail@promat.com.au
Queensland Office
Promat Australia Pty. Ltd.
1/68 Lisgar Street
Virginia, QLD 4014
Tel:
1800 011 376
Fax:
1800 334 598
Email: mail@promat.com.au
CHINA
Promat China Ltd.
Room 506, Block A, Qi Lin Plaza
13-35 Pan Fu Road
510180 Guangzhou
Tel:
+86 (20) 8136 1167
Fax:
+86 (20) 8136 1372
Email: info@promat.com.cn
© Promat International (Asia Pacific) Ltd. 02/2014
Beijing Office
Promat North China
(Division of Promat China Ltd.)
Room 1507 Building 5, SOHO Xiandaicheng
No.88 Jianguo Road, Chaoyang District
100022 Beijing
Tel:
+86 (10) 8589 1254
Fax:
+86 (10) 8589 2904
Email: info@promat.com.cn
For Promat International and its worldwide
group, see www.promat-international.com.
• The technical data provided in this publication is based on mean values
prevalent at time of publication and is thus subject to fluctuation. It
should not be regarded as a guarantee to system performance.
• All data contained herein conforms to and frequently surpasses
generally accepted fire protection standards recognised by most
professional fire science practitioners and regulatory authorities
worldwide. The same general principle is equally applicable to all
Promat products and systems. Promat has access to a considerable
body of test authentication data and this can be provided on a
complimentary basis upon request. It should be noted however that
this publication replaces all previous editions in its entirety. Any form
of reproduction by any means – manual, electronic, digital or otherwise
– is strictly prohibited and subject to prior approval in writing from
Promat. All rights related or connected to the Promat logo, Promat
registered trademarks, featured illustrations, written information and
technical reports in this publication are the sole, exclusive and copyright
property of Promat and its legal partner companies.
INDIA
Bangalore Office
Promat (Malaysia) Sdn. Bhd.
(India Representative Office)
Cabin No. BC-10
Oculus Workspaces, No.66/1, 2nd Floor
Coles Road, Frazer Town
Bangalore 560005
Tel:
+91 (80) 4031 4151
Fax:
+91 (80) 4125 2135
Email: info-india@promat-asia.com
MALAYSIA
Promat (Malaysia) Sdn. Bhd.
Unit 19-02-01, Level 2 PNB Damansara
No.19 Lorong Dungun, Damansara Heights
50490 Kuala Lumpur
Tel:
+60 (3) 2095 8555
Fax:
+60 (3) 2095 2111
Email: info@promat.com.my
SINGAPORE
Promat Building System Pte. Ltd.
10 Science Park Road, #03-14 The Alpha
Singapore Science Park II
Singapore 117684
Tel:
+65 6776 7635
Fax:
+65 6776 7624
Email: info@promat.com.sg
SOUTH KOREA
Promat International (Asia Pacific) Ltd.
(Korea Branch Office)
Room 406, 811-2
Yeoksam-dong Gangnam-gu
Seoul 135080
Tel:
+82 (70) 7794 8216
Email: apromath@promat.com.hk
Your local Promat supplier
Download