Examples on OC and SC Test on Transformer By : Dr. Atul R. Phadke Associate Professor in Electrical Engineering Government College of Engineering, Karad (Maharashtra) EXAMPLE 1: Open-circuit and short-circuit tests conducted on a 10 kVA, 500/2000 V, 50 Hz, single phase transformer gave the following readings: Open circuit test on primary side: 500 V, 120 W, Short-circuit test on primary side: 15 V, 20 A, 100 W. Determine (a) efficiency on full load unity power factor, (b) secondary terminal voltage on full load 0.8 lagging and leading power factor. Given data: kVA rating = 10, Vi = 500 V, V2 = 2000 V, OC test: Vi = 500 V, W0 = 120 W = 0.12 kW, SC test: VSC = 15 V, ISC = 20 A, WSC = 100 W = 0.1 kW Iron loss Wi = Wo = 0.12 kW Full load current on primary side = πππ΄×1000 π1 = 10 ×1000 500 = 20 π΄ πΌππΆ = πΌπΉπΏ = 20 π΄ ο Copper loss at full load, WC = 0.1 kW π₯πππ΄πππ ∅ % ππππππππππ¦ ππ‘ π₯ % ππππ, ο¨π₯ = × 100 π₯πππ΄πππ ∅ + ππ + π₯ 2 ππ 1 × 10 × 1 ∴ ο¨πΉπΏ = × 100 = 97.85% 1 × 10 × 1 + 0.12 + (1)2 × 0.1 π 01 = πππΆ 2 πΌππΆ ο π 01 = ο 100 202 = 0.25 ο 2 EXAMPLE 1: Given data: kVA rating = 10, Vi = 500, Vi = 2000, OC test: Vi = 500 V, W0 = 120 W0 = 0.12 kW, SC test: VSC = 15 V, ISC = 20 A, WSC = 100 W = 0.1 kW π 01 = π01 100 202 πππΆ 15 = = = 0.75 ο πΌππΆ 20 ο π01 = πΎ= π 02 π02 = 0.25 ο 2 2 π01 − π 01 = 0.752 − 0.252 = 0.71 ο π2 2000 = =4 π1 500 = π 01 πΎ 2 = 0.25 × 42 = 4 ο = π01 πΎ 2 = 0.71 × 42 = 11.36 ο Full load current on secondary side = πππ΄×1000 π2 = 10 ×1000 2000 =5π΄ Approximate voltage drop at 0.8 p.f. lagging = πΌ2 π 02 πππ ∅ + πΌ2 π02 π ππ∅ = 5 × 4 × 0.8 + 5 × 11.36 × 0.6 = 50.08 π ο π2 = 2000 − 50.08 = 1949.92 π For 0.8 leading power factor π2 = 2000 − πΌ2 π 02 πππ ∅ − πΌ2 π02 π ππ∅ = 2018.08 π 3 EXAMPLE 2: Open circuit and short circuit tests were conducted on a 50 kVA, 6360/240 V, 50 Hz, single phase transformer to find its efficiency. The observations during the test are: Open-circuit test: Voltage across primary winding 6360 V, primary current 1.0 A, power input 2 kW. Short-circuit test: voltage across primary 180 V, current in secondary 175 A, power input 2 kW. Calculate the efficiency of transformer at full load 0.8 lagging power factor. Given data: kVA rating = 50, V1 = 6360 V, V2 = 240 V, I0 = 1 A, W0 = 2 kW, VSC = 180 V, WSC = 2 kW In OC test, voltage across primary = 6360 V = rated primary voltage ο ππ = π0 = 2 ππ Full load current on secondary side = πππ΄×1000 π2 = 50 ×1000 240 = 208.33 π΄ ISC = 175 A, which is not equal to the full load current ο WSC is not equal to WC, i.e., copper loss at full load. If I2 = 175 A, the percentage of loading π₯ = 175 208.33 = 0.84 π₯ 2 ππ = πππΆ ο Copper loss at full load, ππ = πππΆ π₯2 = 2 0.84 2 = 2.83 ππ π₯πππ΄πππ ∅ 1 × 50 × 0.8 % ππππππππππ¦ ππ‘ π₯ % ππππ, ο¨π₯ = × 100 = × 100 π₯πππ΄πππ ∅ + ππ + π₯ 2 ππ 1 × 50 × 0.8 + 2 + 12 × 2.83 = 89.23% EXAMPLE 3: A 250/500 V transformer gave the following test results. Open circuit test: 250 V, 1 A, 80 W on low voltage side, Short circuit test: 20 V, 12 A, 100 W on high voltage side. Calculate the circuit parameters and draw the equivalent circuit of transformer referred to primary. Given data: V1 = 250 V, V2 = 500 V, W0 = 80 W, I0 = 1 A,VSC = 20 V, WSC = 100 W, ISC = 12 A From Open-circuit test π0 80 πππ ∅0 = = = 0.32 π1 πΌ0 250 × 1 The working component of no-load current, πΌπ€ = πΌ0 πππ ∅0 = 1 × 0.32 = 0.32 π΄ ∅0 = πππ −1 0.32 = 71.340 ο π ππ∅0 = sin 71.34 = 0.947 The magnetizing component of no-load current πΌπ = πΌ0 π ππ∅0 = 1 × 0.947 = 0.947 π΄ π1 πΌπ€ = 250 0.32 ο Magnetizing reactance, π0 = π1 πΌπ = ο Core loss resistance, π 0 = = 781.25 ο 250 0.947 = 263.99 ο 5 EXAMPLE 3: A 250/500 V transformer gave the following test results. Open circuit test: 250 V, 1 A, 80 W on low voltage side, Short circuit test: 20 V, 12 A, 100 W. Calculate the circuit parameters and draw the equivalent circuit of transformer referred to primary. Given data: V1 = 250 V, V2 = 500 V, W0 = 80 W, I0 = 1 A,VSC = 20 V, WSC = 100 W, ISC = 12 A From Open-circuit test - π 0 = π1 πΌπ€ = 250 0.32 = 781.25 ο, π0 = π1 πΌπ = 250 0.947 = 263.99 ο From Short-circuit test – π 02 = π02 πππΆ 2 πΌππΆ = 100 122 I1 = 0.694 ο Iw πππΆ 20 = = = 1.67 ο πΌππΆ 12 ο π02 = 2 π02 − 2 π 02 = 0.174 ο π 01 1.672 − 0.6942 = 1.52 ο π 0 V1 781.25 ο I0 0.38 ο π01 πΌ2′ Iµ π0 263.99 ο π2′ π2 500 πΎ= = =2 π1 250 π 01 = π 02ΰ΅πΎ2 = 0.694Τ22 = 0.174 ο π01 = π02ΰ΅πΎ2 = 1.52ΰ΅22 = 0.38 ο 6