EE-40023 Revision 5 - April/2019 PREFACE Upon receipt of TOSHIBA Regulator, you will receive not only the assurance of a Japanese technology, but also the care of a stringent QUALITY control and the commitment with the environmental performance improvement. We are sure this manual will guide you properly in order to get from your Regulator everything your design engineering has specified. OBSERVATION: After the equipment and its accessories delivery, make sure about the presence and integrity of all the parts, checking the packing list. If any damage or missing part is observed, immediately notify Tsea Energia. REMEMBER: Damages caused by handling and/or improper operations void the warranty signed in the agreement. The information in this document is subjected to changes without previous notice. No part of this document can be reproduced or transmitted in any way or through any means, electronic or mechanic, for any purpose, without prior written authorization by Tsea Energia. Tsea Energia may have patents, trademarks, copyright or any other intellectual property rights that comprise this document content. Possession of this document does not warrant any right on such patents, trademarks, copyright or other intellectual property rights, except the ones expressly mentioned in a license agreement, in written, by Tsea Energia BASIC NORMATIVE REFERENCES: - NBR 11809/1992: REGULADORES DE TENSÃO (VOLTAGE REGULATORS) - ANSI C.57.15/1999: TERMINOLOGY, AND TEST CODE FOR STEP-VOLTAGE REGULATORS 1 EE-40023 Sumário 1 - INTRODUCTION.................................................................................................................................................. 4 2 - BASIC SCHEME OF POWER TRANSMISSION AND DISTRIBUTION: ........................................................... 4 3 - FUNCTIONING PRINCIPLE................................................................................................................................ 4 3.1- Functioning as step-up transformer ................................................................................................................... 5 3.2- Functioning as down-up transformer ................................................................................................................... 5 4 - REGULATOR ASSEMBLY ................................................................................................................................... 5 4.1- Reactor functions ................................................................................................................................................ 6 4.1.1- Voltage splitter ......................................................................................................... 6 4.1.2- Do not allow the circuit interruption during switching ............................................................. 6 4.1.3- Limit circulating current .............................................................................................. 7 4.2 - Equalization coil ................................................................................................................................................ 9 5 - CONNECTION TYPES IN REGULATORS BANK ........................................................................................... 11 5.1 - Star Connection .............................................................................................................................................. 11 5.2- Delta Closed Connection ................................................................................................................................. 12 5.3- Delta Open Connection.................................................................................................................................... 14 6 - PREFERRED RATINGS 60 Hz STEP VOLTAGE REGULATORS ................................................................. 15 7- PREFERRED RATINGS 60 Hz STEP VOLTAGE REGULATORS .................................................................. 16 8 - REGULATOR SIZING ........................................................................................................................................ 17 9 - REGULATOR FUNCTIONING ........................................................................................................................... 17 10 - ADJUSTMENT OF THE LINE DROP EQUALIZER ........................................................................................ 18 10.1- Adjustment of drop line compensation for the types of regulator connections ............................................. 18 10.1.1- Monophasic connection ............................................................................................. 18 10.1.2 Star connection ....................................................................................................... 19 10.1.3 Triangle connection .................................................................................................. 20 11 - TRANSPORTATION OF SINGLE-PHASE VOLTAGE REGULATORS ........................................................... 25 11.1 - Objective ........................................................................................................................................................ 25 11.2- Packaging ....................................................................................................................................................... 25 11.3- Fastening ........................................................................................................................................................ 25 11.4- Check before Shipping .................................................................................................................................... 25 11.5- Type of Tractor Trailer or Truck ........................................................................................................................ 25 11.6- Transportation Documents and Reports ......................................................................................................... 25 11.7- Speed Limits: .................................................................................................................................................. 25 12 - INSPECTION AND MAINTENANCE OF SINGLE-PHASE VOLTAGE REGULATORS ................................... 25 12.1- Introduction .................................................................................................................................................... 25 12.2- Receipt............................................................................................................................................................ 26 12.3- Storage ........................................................................................................................................................... 26 12.4- Installation ...................................................................................................................................................... 26 12.4.1- To operate the regulator ............................................................................................. 26 12.4.2- Typical connections for single-phase regulators.................................................................. 27 12.4.3- Maneuver on regulators ............................................................................................ 31 12.5 - Installation ..................................................................................................................................................... 32 12.5.1 - By-pass lightning rod ............................................................................................... 32 12.5.2- Pressure relief valve ................................................................................................ 32 12.6 - REGULATOR MAINTENANCE ..................................................................................................................... 33 12.6.1- Periodical inspection ............................................................................................... 33 12.6.2- Internal inspection of the regulator .............................................................................. 36 12.6.3- Removal of the tank active part .................................................................................... 36 12.6.4. Equipment required for the inspection .......................................................................... 36 13 - EXTERNAL ELECTRO-MECHANICAL POSITIONS INDICATOR (ANALOGICAL) TB-I900 ...................... 37 13.1- GOAL .............................................................................................................................................................. 37 13.2- DESCRIPTION, FEATURES, AND FUNCTIONING ....................................................................................... 37 13.3- INSTALLATION AND MAINTENANCE: .......................................................................................................... 37 13.3.4- Dimensions ........................................................................................................... 38 14 – SPECIAL CARE WITH HANDLING, WASTE DISCARDED, AND LEAKAGES ASSOCIATED TO S VOLTAGE REGULATORS..................................................................................................................................... 39 14.1- Goals ............................................................................................................................................................. 39 2 EE-40023 14.2- Definitions ....................................................................................................................................................... 39 14.3- General Requirements.................................................................................................................................... 39 14.3.1- Integrated Management Policy Quality, Environment, Occupational Health and Safety .................. 39 14.3.2- Environmental Aspects ............................................................................................. 39 14.3.3- Waste Handling and Destination ................................................................................... 40 14.4- Legal Requirements and Other Requirements ................................................................................................ 41 14.5- Training, Awareness and Competence ........................................................................................................... 42 14.6- Communication............................................................................................................................................... 42 15 - DRAWINGS AND SPECIFIC INSTRUCTIONS ATTACHED. ........................................................................... 42 3 EE-40023 1 - INTRODUCTION The application of voltage regulators in the power distribution systems started in the 1940's, in developed countries, mainly in the USA, due to its large territory, where the centers are spread in large areas far from the generation points and along with it, the appearance of a huge amount of new electro-electronics, sensitive to voltage oscillations, made consumers complains rise. Consumers started demanding good quality power distribution. Because of this, currently thousands of regulators are installed in several points of the country, providing the consumption points with a proper voltage regulation and ensuring quality to the power supply. This brings at least three benefits: Consumer satisfaction; Reduction of distribution losses; Increase to the power supply company income. Brazil presents some degree of similarity to the USA when it comes to territorial area, which makes viable the use of voltage regulators. These have great acceptance by the power supply companies due to economic, simplicity, and versatility reasons. Besides, today there are voltage regulators fully manufactured in Brazil, which eliminates the problems in obtaining spare parts observed up to 1986, when such equipment was fully or partially (on load tap changer) imported from the USA. 2 - BASIC SCHEME OF POWER TRANSMISSION AND DISTRIBUTION: 1 - Generator 2 - Step-up Transformer 3 - Transmission line 4- Step-down substation 5 - Distribution network 6 - Monophasic Voltage 6- regulator up to 36 kV 7 - Distribution Transformer 8 - Consumer 3 5 FIGURE 1 4 1 2 6 7 8 3 - FUNCTIONING PRINCIPLE 4 EE-40023 The working principle is similar to an autotransformer, that is, besides the magnetic coupling, between the primary and the secondary, there is an electric coupling, as shown in the figure below: B PRIMARY C SECONDARY FIGURE 2 There are two ways to perform electrical connection between the primary and the secondary, making the autotransformer operate as a step-up or a step-down: 3.1- Functioning as step-up transformer + B C 100 V 1100 V 1000 V + Voltage on load FIGURE 3 3.2- Functioning as down-up transformer + B C 100 V 900 V 1000 V + Voltage on load FIGURE 4 It is the COILs polarity that determines the electrical connection to the autotransformer functioning as step-up or step- down. Therefore, we are going to add a polarity reversal switch to the circuit, to enable the autotransformer to work as step-up or step-down. + M B K C FIGURE 5 4 - REGULATOR ASSEMBLY By adding taps to COIL “C”, then we have voltage steps. 5 EE-40023 FIGURE 6 Therefore, if the load is connected to tap 1, and if we need to switch its connection to tap 2, we will have to interrupt the circuit, i.e., de-energize the regulator. In order to avoid this, the solution is to add a reactor to the circuit, since while the reactor ends (legs) move to tap 2, the load supply is carried out through the other end of the reactor. REACTOR B LOAD M K C CENTER TAP FIGURE 7 4.1- Reactor functions Let's consider for better understanding the reactor circuit, a piece of COIL “C”. 4.1.1- Voltage splitter Considering the reactor in position 0 (neutral): REACTOR 0 A LOAD B Vd 1 C Vd 2 Vd= VOLTAGE STEPS FIGURE 8 Now let's go to: 0 A REACTOR Vd/2 Vd/2 LOAD Vd 1 C B Vd 2 FIGURE 9 Voltage applied to the reactor terminals is Vd, however the load voltage will increase or decrease in the Vd/2 rate, due to the center tap, which explains the reactor being a voltage splitter. 4.1.2- Do not allow the circuit interruption during switching 6 EE-40023 By analyzing the previous circuit, when “B” goes out from tap 0, and is moving to tap 1, the circuit energizing is made through "A", without the circuit interruption. 4.1.3- Limit circulating current 0 REACTOR 1 C Vd Ic 2 FIGURE 10 When Vd voltage is applied to the reactor terminals, a circulating current takes place, Ic, this current shall be limited so that excessive wear does not happen to the tap changer contacts and that their life cycle is preserved. The determination of the circulating current limit in the reactor is based on the extinction of arc in a circuit, as shown in the figure: IL "C" COIL 1 Vd Vb IR Ic Vb 2 REACTOR VR FIGURE 11 We have developed the following equations: VR = 2Vb-Vd IR = 1 IL-IC 2 From this point, these equations have been developed and the conclusion was the reactor shall be designed to: IC = 50% IL Tolerance for the circulating current Trial is from -20% to 0%.The reactor core has from 1 to 2 Gaps sized so that the circulating current is established within the previous parameters. These Gaps are filled with phonolite or premix. However, along the regulator's life cycle, the gap may increase or decrease due to vibrations and/or temperature, and the current calibration may not correspond to the previous parameters: Here is an example of the reactor recalibration: - Regulator: HCMR 60 Hz 138 kVA (1380 kVA) 13800 V ± 10% (32 steps) 100 A. Project - IC = 0.5 x 100 = 50 A with tolerance from -20% to 0% Field 7 - Assuming: IC = 70 A EE-40023 Measuring the Gap = 2 x 10.5 = 21 mm In order to recalibrate we take the direct proportion: 70 A 50 A - 21 mm -X X = 15 mm --> 2 x 7,5mm The reactor has the characteristic to enable the load current circulation, IL, free by it, not constituting impedance to this current. This happens because of the center tap, which promotes the half IL circulation on one side of the reactor (A) and the other IL half on the other side (B), as follows: 8 EE-40023 Ic IL 2 L c 2 IL CENTER TAP L 2 Ic IL 2 FIGURE 12 According to the figure above, we can see the magnetic flows,∅πΏ/2, created by the current,IL/2 become void, which, in an inductive circuit means that the tension induced on the reactor coil due to the load current circulation, is zero: 4.2 - Equalization coil Considering the circuits below: Circuit A: Since there is no voltage applied on the reactor, Ic = 0. REACTOR FIGURE 13 Circuit B: Since there is no voltage applied on the reactor, Ic = 0. 9 EE-40023 REACTOR FIGURE 14 The circulating current switching from zero (circuit A) to value 50% IL (circuit B) during the regulator switching times would di cause a high wear of the tap changer contacts due to the Ldt , i.e., the current variation rate from zero to 50% would be high, which would cause the arc voltage to increase and, consequently, the arc potency. In order to solve this problem and keep the circulating current in the reactor constantly at 50% IL, regardless of the tap changer position, it is recommended to add the equalization coil to the reactor circuit, as shown below: EQUALIZ. SPOOL REACTOR FIGURE 15 LOAD REACTOR The equalization coil is located in the active part of the regulator main transformer. This enables the coil to be an active element, i.e., a voltage source in the reactor circuit, when it is in the condition of circuit “A”. Thus, by analyzing the following circuit, we can see that the circulating current in this condition changes the direction, but it continues in module. EQUALIZ. COIL REACTOR LOAD REACTOR FIGURE 16 10 EE-40023 5 - CONNECTION TYPES IN REGULATORS BANK 5.1 - Star Connection BY PASS SWITCH SOURCE A B C C A B Shunt arresteres S Series arresteres SL L BY PASS SWITCH C B L O A D B S SL L C BY PASS SWITCH B C N S SL L N FIGURE 18 FIGURE 17 Assuming the regulators are stepping-up by +10%. The fasorial diagram would be: FIGURE 19 Recommendation is that if the regulators bank is connected in star, then the power supply necessarily is also in star so that the neutral current, due to possible load unbalances of the group, has the way closed to grounding, therefore to the power supply. Power supply Regulators Bank FIGURE 20 ALERT It is recommended that the grounding resistor is lower than 20 ohms. If the Power supply is in triangle and the regulators bank is in star form, the virtual neutral of the star connection will be displaced in case of load unbalance, and the regulators bank will undergo a series of switching. Typically, some regulators in the bank will go to the maximum step-up position and others to the maximum step-down position. 11 EE-40023 5.2- Delta Closed Connection BY PASS SWITCH A C A B Shunt arresteres S Series arresteres SL L BY PASS SWITCH B C B C B L O A D S SL L BY PASS SWITCH C B C S SL FIGURE 21 L FIGURE22 Assuming 13800 V regulators are stepping-up by +10%. 13800 x 0.1 = 1380 13800 V FIGURE 23 12 EE-40023 So: πππ 60° = πΆ^′/1380 πΆππ 60° = π΅′/1380 C’=1195 B’=690 ) 80 13 0+ 80 (13 A 1380 B' C' FIGURE 25 FIGURE 24 Thus: A= A = 15915 V Regulation (%) = 15915 = 115 % 13800 CLOSED DELTA CONNECTION GROUP REGULATION IS ± 15% 13 EE-40023 5.3- Delta Open Connection A C BY PASS SWITCH B A Shunt arresteres S Series arresteres B L O A D C B SL L BY PASS SWITCH B S SL L C C FIGURE 26 FIGURE 27 Assuming 138 kVA 13800 V regulators are stepping-up by +10%. POWER SUPPLY FIGURE 28 VOLTAGE BETWEEN PHASES AT THE BANK OUTPUT = A So: Cos 60º = X' X'=690 1380 A = 13800 + 2X = 15180 Regulation (%) = 15180 = 110% 13800 FIGURE 29 OPEN DELTA CONNECTION GROUP REGULATION IS ± 10% This is an advantageous connection when it comes to a cascade connection, with this, 2 regulators are placed in each point of the cascade, therefore saving 1 regulator. It is recommended to use 3 and at most 4 regulators bank in cascade due to possible overvoltage problems on the system when closing the reconnectors. 14 EE-40023 6 - PREFERRED RATINGS 60 Hz STEP VOLTAGE REGULATORS 15 EE-40023 7- PREFERRED RATINGS 60 Hz STEP VOLTAGE REGULATORS 16 EE-40023 8 - REGULATOR SIZING Through the table above we can show an example of how to size a regulator: Load: 10 MVA; Regulation voltage: 13800 V; Star power supply with grounding resistor below 20 Ohms; Star group connection. For this, current is: I = 10000 kVA = 418 A 3x1388 kV Nominal voltage of the regulator should be: VN = 13800 = 7967 V 3 By analyzing the previous table, we chose regulator 333 kVA - 7620 V - 438 A, with additional voltage of 7967 V. 9 - REGULATOR FUNCTIONING Voltage regulator control FIGURE 31 Winding 1, called excitement winding (winding B), induces a tension on winding 2 (also known as tape or regulation winding). In figure 31, TP4 (potential transformer) installed on the load side sends a signal to the voltage regulator control, which places the reactor 3 A and B terminals on the proper position to maintain the load voltage constant. The polarity reversal key shown in 6 will determine whether the regulator will increase or decrease the voltage, and its control is performed by the regulator control. TC5 (current transformer) installed on the load side will send to the regulator control a line loading signal, making it possible to compensate voltage drops that may occur in the system. 17 EE-40023 LOAD 10 - ADJUSTMENT OF THE LINE DROP EQUALIZER Regulator Control FIGURE 32 By using essential voltage equations, we can easily identify the voltage drop on the line referring to the control circuit, which is provided by: Where: RL: Line resistance in ohms. XL: Line reactance in ohms. RC: Compensator resistance in volts. XC: Compensator reactance in volts IC: Primary nominal current of TC (A) OBS.: For Toshiba regulators, the TC primary current is identical to the regulator nominal current. The TP ratio is provided by: RTP = Nominal regulator tension 120 By observing the above equations (1) and (2), we have a common factor Ic , which we will define as: TP Ratio FC: Line drop compensation factor Note: This factor depends on the regulator plate data only. 10.1- Adjustment of drop line compensation for the types of regulator connections 10.1.1- Monophasic connection 18 EE-40023 RL XL S Ic TP LOAD RL XL Ic SL FIGURE 33 Note: The FC adjustment in this connection depends on the grounding. Factor should be: 2.0: for ground-insulated system; 1.67: for system with neutral connected to the ground. 10.1.2 Star connection SOURCE A B C C B C L O A D B C B N FIGURE 34 19 EE-40023 With the TP and the load voltage are the phase is the ground: 10.1.3 Triangle connection A C B B C L O A D B C C B FIGURE 35 As the TP voltage is between phases, and the load voltage is from phase to ground: F x1,73 TP By considering the potency factor is equal to 1.0, we can state: - The phase voltage of a monophasic system and the load current are in phase; - The phase voltages for neutral in a multiple ground star connection system are in phase with the corresponding load currents. - The phase voltages for neutral in a triangle connection system are different by 30º related to the corresponding load currents. - Due to the difference between the voltage and the current in the triangle connection, it is necessary to correct the obtained values for the line drop equalizer according to items 10.1.3.1 and 10.1.3.2 below: 10.1.3.1 - Closed triangle connection, considering: V A, V B , V C : Voltage between phases VAN, VBN, VCN : Phase voltage for equivalent grounding RL : Line resistance (ohms) XL : Line reactance (ohms) FP : Potency factor = 1.0 20 IC : Load current EE-40023 10.1.3.2- Delayed Regulator We have: A NAMING: VA VAB = VA VBC = VB VCA = VC VAN B WS A C C B FIGURE 36 THIS PORTION REPRESENTS THE CORRECTION TO BE INCREMENTED ON THE LINE DROP EQUALIZER. FIGURE 37 By analyzing the previous figures, we can say that: 1 - Voltage between phases is advanced in 30, regarding the phase-neutral voltage of the corresponding phase. 2 - As the regulator is monophasic, i.e., the phase-neutral voltage is its reference, we can say the regulator is delayed. Regarding the line drop equalizer circuit, we can state: And it is easy to show that for determining the increment portion of the equalizer we just need to multiply the vector module by the unitary with its difference. Then, we have: (RC + jXC) x 1 + 30º (RC + jXC) x (+ 0.866 + j0.5) 21 EE-40023 0.866RC + j 0.5RC + j 0.866XC - 0.5XC So: 0.866R 0.5 0.866X 0.5 Where: R’C: Rc correction C X’C: Xc correction C After R'c and X'c calculation, the positive values should be adjusted on the control's polarity key with positive polarity and the negative values with negative polarity. However, TOSHIBA regulator control is programmed to automatically perform the R'c and X'c values correction, since Rc and Xc values and the triangle connection transformation are previously set in the control. (For more information, see the Voltage Regulator Control Manual). 10.1.3.3 - Advanced Regulator A Where: VAN VA B A V BA = V B V CB = V C V AC = V A WS C C B FIGURE 38 22 EE-40023 We have to: VC A) XL N VA IC E AS PH IC( RL IC VB VA FIGURE 39 By analyzing the previous figures, we can say that: 3 - Voltage between phases is delayed in 30, regarding the phase-neutral voltage of the corresponding phase. 4 - As the regulator is monophasic, i.e., the phase-neutral voltage is its reference, we can say the regulator is advanced. 5 - Thinking about the line drop equalizer circuit, we can state: And it is easy to show that for determining the increment portion of the equalizer we just need to multiply the vector module by the unitary with its difference. Then, we have: (RC + jXC-)30º x1 (RC + jXC) x (+ 0.866 - j0.5) 0.866RC - j 0.5RC + j 0.866XC + 0.5XC Therefore: Where: R’C: R correction X’C: X correction 0.866 0.5 0.866 0.5 C C After R'c and X'c calculation, the positive values should be adjusted on the control's polarity key with positive polarity and the negative values with negative polarity. However, TOSHIBA regulator control is programmed to automatically perform R'c and X'c values correction, since Rc and Xc values and the triangle connection transformation are previously set in the control. (For more information, see the Voltage Regulator Control Manual). 10.1.3.4- Open triangle connection 10.1.3.4.1- Connection with Phase "B" without regulator 23 EE-40023 A Where: WS B VCB = VC VAB = VA B C A VCN VAN C VC VA Figure 40 It is possible to say that the phase "C" regulator is the advanced one and that the one of phase "A" is the delayed one. R'c and X'c values are the same previously shown for the delayed and advanced regulator. 10.1.3.4.2- Connection with Phase "C" without regulator A C Where: WS VAC = VA VBC = VB B B A VAN VBN C VB VA FIGURE 41 We can say that the phase "A" regulator is the advanced one and that the one of phase "B" is the delayed one. R'c and X'c values are the same previously shown for the delayed and advanced regulators. After R'c and X'c calculation, the positive values should be adjusted on the control's polarity key with positive polarity and the negative values with negative polarity. However, TOSHIBA regulator control is programmed to automatically perform R'c and X'c values correction, as the Rc and Xc values and the triangle connection transformation are previously set in the control. (For more information, see the Voltage Regulator Control Manual). We can say that in open triangle connections one regulator is delayed and the other is advanced. However, on site, sometimes it is difficult to determine which regulator is delayed and which one is advanced to adjust the line drop equalizer R and X values. 24 EE-40023 11 - TRANSPORTATION OF SINGLE-PHASE VOLTAGE REGULATORS 11.1 - Objective To better protect the equipment during shipping and transportation, the preventive measures in this manual shall be taken for chocks. 11.2- Packaging The regulator shall be packaged in a wooden box. The base and upper side of the regulator shall be well wedged to the package in order to avoid its displacement during transportation. 11.3- Fastening To avoid displacements during transportation, holders shall be placed on the bottom of the tractor trailer or truck. The fastening on the upper side shall be performed by means of lashing to the hooks or the package. 11.4- Check before Shipping The person in charge of the transportation shall confirm the items below before going leaving the site: -Shipping condition -Equipment condition 11.5- Type of Tractor Trailer or Truck The tractor trailer or truck shall have a tachometer installed ALERT 11.6- Transportation Documents and Reports ALERT They shall be kept for at least 3 years. 11.7- Speed Limits: ALERT Paved roads: Maximum 60 Km/h Unpaved roads: Maximum 40 km/h These limits shall be strictly observed. Note: Non observance of these speed limits may cause the equipment warranty to be lost in case of any problem that may be a result from such event to be detected. 12 - INSPECTION AND MAINTENANCE OF SINGLE-PHASE VOLTAGE REGULATORS 12.1- Introduction TOSHIBA voltage regulator has been designed to provide good service on the line and to make its operation and maintenance easier. High quality materials and good manufacturing practices have been combined to offer the best regulator. Your regulator has been carefully inspected and adjusted at the plant; however, for satisfactory operation it is important that its installation 25 EE-40023 is excellent and maintenance is continuous. This manual is designed to help you get a long-standing and cost-effective service for your regulator. Read this manual before installing or operating your regulator. 12.2- Receipt Upon your regulator delivery, carefully check each item in the invoice. In case that anything is missing, or if there is something damaged, immediately contact the company responsible for the shipment and include the proper notes in the invoice. If necessary, contact Tsea Energia. 12.3- Storage If the regulator is not operated immediately, it shall be kept in a protected area or outdoors without major concerns since the control compartment and the inspection cover are well sealed. 12.4- Installation TOSHIBA voltage regulators can be installed both in covered areas and outdoors, on platforms or poles, provided the service condition limits established by NBR 11809 / ANSI C57.15 or the client's technical specification (whichever is most strict) is observed. 12.4.1- To operate the regulator 12.4.1.1- Check the oil level through its own indicator. 12.4.1.2- Check the bushings porcelains. WARNING The bushings porcelain can be broken due to improper handling or transportation. 12.4.1.3- Check the oil dielectric stiffness (this will not be necessary if the unit is installed upon receipt and in good conditions). If the dielectric stiffness is below 30 kV, it will be required to filter the oil before operating the regulator. ALERT Due to the viscosity of the insulating oil at low temperatures and the particularities of the tap changer's engine, IS NOT recommended to perform external powering via control panel (tap changer via electronic control panel), as well as the powering of the regulator itself, at an ambient temperature lower than -5°C. In case of the ambient temperature being lower than -5°C, it is essential to raise, by external means, the temperature of the insulating oil of the regulator before running any command on the tap changer( via external powering on the control panel) or before the direct powering of the regulator. 12.4.1.4- Cause a short-circuit on the power supply, load, and neutral bushings Measure the resistance (with MEGGER) between these bushings and the tank. The read values must be at least 2000 Mega Ohm at room temperature. 26 EE-40023 NOTE: 1 - The bushings are identified according to terminology described in the table below, according to the client's interest. This terminology will be clearly printed on the regulator cover. TERMINOLOGY INSULATOR S ANSI ABNT SOURCE “S” “F” LOAD “L” “C” NEUTRAL “SL” “FC” L S SL CONTROL ENCLOSURE Insulators placement on the regulator cover 2- If any one of the requirements previously described is not met, contact TSEA ENERGIA technical support by telephone +55(31)3329-6060, +55(31)3329-6565 or email: exportsales@tseaenergia.com.br / falecom@toshiba.com.br 12.4.1.5- Review the drawings on the identification plate and on the control diagram. WARNING Check the voltage the Single-Phase Voltage Regulator is connected. In order to be sure, follow the connections established on the regulator's identification plate. 12.4.2- Typical connections for single-phase regulators Figures 42 to 45 describe the four basic connections for monophasic and triphasic systems, where regulation is performed by monophasic regulators. 27 EE-40023 BY PASS W ITCH Shunt arresteres S Serie arrester SL L N FIGURE 42 SINGLE-PHASE VOLTAGE REGULATOR CONNECTION TO MONOPHASIC LINE. BY PASS SWITCH A Shunt arresteres S Series arresteres SL L BY PASS SWITCH B S SL C L Figure 43 OPEN DELTA Two single-phase regulators connected to a triphasic line in open delta providing the system with 10% of the regulation range on the 3 (three) phases. 28 EE-40023 BY PASS SWITCH A Shunt arresteres S Series arresteres SL L BY PASS SWITCH B S SL L BY PASS SWITCH C S SL L Figure 44- CLOSED DELTA Three single-phase regulators connected to a triphasic line in closed delta providing the system with 15% of the regulation range. 28 28 EE-40023 BY PASS SWITCH A Shunt arresteres S Series arresteres SL L BY PASS SWITCH B S SL L BY PASS SWITCH C S SL L N FIGURE 45- STAR CONNECTION Three single-phase regulators connected in star to a triphasic line with grounded neutral providing the system with 10% of the regulation range. 28 28 EE-40023 12.4.3- Maneuver on regulators Installation and removal of the service regulator must follow the procedure below. Note: This procedure applies to regulators with the TVC-MP control. FIGURE 46 31 EE-40023 12.5 - Installation 12.5.1 - By-pass lightning rod All the regulators, standard model, are equipped with by-pass lightning rod, which shall be assembled between the bushings of the power supply and load. The by-pass lightning rod limits voltage through the winding, but it does not work as protection for the line to ground. Protection against atmospheric discharges (Shunt Lightening rod): for higher protection of the regulator and the line, proper voltage lightening rods must be installed between line and ground, one on the power supply side and the other on the load side. WARNING Fuses: when they are used along with single-phase regulators, place them only on the power supply terminals, never place them on the neutral or common terminal. 12.5.2- Pressure relief valve Used to relieve the tank internal pressure, protecting it in case of high pressures due to problems on the active part of the regulator. ALERT Check in the “Outer Dimensions” drawing, attached, what type of valve applies to your regulator. 12.5.2.1- Functioning When the tank internal pressure is higher than the relief valve operating pressure, the valve will automatically open, releasing the pressure. When the tank internal pressure becomes lower than the operational pressure the valve will close off sealing the tank. Venting and sealing characteristics shall be as follows: a) Venting pressure = 69 kPa (10 psig) ± 13 kPa (gage) (2 psig). b) Resealing pressure = 6.9 kPa (gage) (1 psig) minimum. c) Zero leakage from reseal pressure to –56 kPa (gage) (–8 psig). d) Flow at 103 kPa (gage) (15 psig) = 16,5 l/s (35 standard cubic feet per minute), (SCFM)] minimum corrected for air pressure of 101 kPa (14.7 psi) (absolute) and air temperature of 21 °C 12.5.2.2- Notifying abnormalities If through a periodical inspection or in the standard operation any abnormality is identified, we ask you to notify the event to Tsea Energia. 32 EE-40023 12.6 - REGULATOR MAINTENANCE 12.6.1- Periodical inspection ELECTRONIC CONTROL Inspection Clause point Check Period - Manual actuation - Maximum and minimum block 1 Control 3 years Reference voltage 2 3 - Linear temporiz ation - Automati c actuation Rise and Low Procedure or checking item - Upon placing the operation adjust in “rise”, check if the control rises the tap, stopping at the set block. - Upon placing the operation adjust in “lowers”, check if the control lows the tap, stopping at the set block. With the regulator energized, adjust: Ur=0V, Ux= 0V. Check if the “Voltmeter” output voltage is equal (± 1V) the reference after stabilized. - Varying the reference adjustment for a higher voltage than the one of the network. - Check if the motor starts on the “Rise” direction after the set time. - Varying the gross tune for a lower voltage than the one of the network. - Check if the motor starts on the “Low” direction after the set time. 33 Evaluation / Correction According to the operating instruction. EE-40023 VOLTAGE REGULATOR Clause Inspection point Check Period Bushings Light-ening rod 4 Accessories Procedure or checked item Evaluation / Correction 1. Impurities accumulation on the porcelains; 2. Oil leakage; 3. Terminals tightening. 1. Impurities accumulation; 2. Insulation endurance. 1. When the contamination is excessive, clean with a cloth soaked with ammonia or carbon tetrachloride and apply a neutralizer. Afterwards, wash them with fresh water and dry with a dry cloth; 2. When the terminals are loose, tighten them. - Glass display replacement; - Tightening of indicator's body or gasket replacement. - Tighten A, if the leakage persists, the equipment shall be removed from service 3 years Oil level indicator - Break on the glass display; - Oil leakage. Oil drain valve - Oil leakage. 34 EE-40023 Clause 4 Inspection point Accessorie s Check Control box Procedure or checked Period item 3 -Water penetration inside the box; years -Check the connection of the multi cable to the control box. 5 Accessorie s 6 Tank outer side 7 Insulating oil 8 Miscellaneous Position Indicator Switch - Water penetration into 3 years the interior of an external. 3 years - Check the general condition of the tank painting. Dielec tric stiffn ess 3 yea rs Abnormal excitation noise and vibration - All the procedures shall be according to Standard ABNT NBR 6869. - Check the fixation condition of the parts connected to the tank. Evaluation / Correction -In case of water penetration, replace the door insulation gaskets; -Connection of multi cable loosen, tighten it. -Maintaining the indicator. -Remove moisture in the terminal box. - Restoration of the outer surface painting shall be performed according to the following frequency: 1. The equipment installed in industrial, maritime and polluted zones, approximately every 12 months. 2. The equipment installed in atmosphere free of pollution and out of the maritime coast, approximately every 3 years. 1. Satisfactory: Higher than 26kV/2.5 mm; 2. To be reconditioned: Lower than 26kV/2.5 mm. -Readjustment. Contact Tsea Energia at the numbers: (05531) 33296684 Email: falecom@tseaenergia.com.br 35 EE-40023 NOTES: * After all the tests, the adjustments shall be placed as previously found. * If there are no conditions to perform all the tests due to variations that they will cause on the load side, we suggest taking the regulator out of service and closing the by-pass and the disconnection of the load side (Check handling procedure instruction on control box cover), which allows testing all the relay functions, except the ones related to the line drop compensation. 12.6.2- Internal inspection of the regulator We recommend the internal inspection, together with the Tap Changer, observing in the Instruction it, the number of operations, for inspection or maintenance. Basically, the internal inspection consists of: a) Inspection on the Tap Changer, according to specific instruction for it. b) Inspection on Active Part (the entire structure with core, coil and e.tc). * It is not required to perform any trials or checks unless an abnormal functioning condition is seen and, in such case, Tsea Energia shall be notified. It is recommended to perform at least: - Spirals relation check; - Measurement of the electric resistance of the excitation and TAP’s windings; - Visual inspection. 12.6.3- Removal of the tank active part The removal of the tank active part shall be performed in a protected place, preferably with dust control, fully removing it from the tank. Procedures: A) Remove the cover fixing bolts; B) Remove all the fixing bolts and grounding of the control box to the regulator tank. The control box pulls out along with the cover if necessary; C) The active part shall be removed from the tank by the suspension pad eyes on the cover. Upon inspection, check if all the bolts, nuts and connections are well tightened; D) For each hour of exposure, the active part shall be submitted to two (2) hours of vacuum. Maximum 5 mmHg; E) After the vacuum period is concluded, the oil filling must start. When the oil level is complete, the vacuum can be broken; F) Leave the regulator in rest for 12 hours before energizing it. 12.6.4. Equipment required for the inspection 12.6.4.1 – Instruments A) Instrument to test the oil dielectric stiffness; B) Device for spirals relation test; C) Volt/ohm meter for calibration and test of the command device; D) Megger for insulation tests; E) Device for line current measurements. 36 EE-40023 13 - EXTERNAL ELECTRO-MECHANICAL POSITIONS INDICATOR (ANALOGICAL) TB-I900 13.1- GOAL Externally to the tank indicate by means of mechanical connection the position (tap) the on load tap changer is under voltage single-phase regulators load. It still has functions that allow for controlling the operation range limit (load-bonus) and indicators on the outer positions reached during an observance period (upper and lower tap). Except when expressly indicated otherwise in the purchase order, aluminum boxes are provided with finishing painting in grey Munsell N6.5 on both sides (internal and external). 13.2- DESCRIPTION, FEATURES, AND FUNCTIONING The indicator shall always be assembled inclined in relation to the ground (45º), to make easier the indication pointers visualization and to make possible to eliminate the humidity condensation; The bolts for fixation of the visor are in stainless steel and with partial thread (BSP 3/16”) to avoid their fall during the operation for accessing the pointers and load-bonus system. It enables the control of the operation range limit through microswitch. Limiting, as predicted in operating standard of singlephase regulators, can be performed both sides of the tap changer (Raise or Lower). It is accessible in the inner side of the visor by means of sliding keys, which have locking systems in pair positions from 8 to 16, both sides. Keys can be positioned independently on both sides (ex.: +12 and -16, +14 / -10, etc). For the operating range regulation, the operator shall loose the four bolts that attach the polycarbonate visor. The bolts are released the front visor without the need for their total removal (this avoids the need to hold them or risks that they will fall during this operation). On the visor back side, there is a bolt that allows its tilting in relation to the indicator's lower side, leaving the operator's hands free to work, thus, when releasing the visor, it won't fall and will not demand the operator to hold it. Operating range limit keys are made of stainless steel and painted in yellow. They are positioned by means of turning in relation to the display arc to the desired position. When placing the keys at the desired pair positions, check their correct locking through “click” of the movement mechanism. When placing it in the right position, the movement resistance increases, being possible to feel it during the adjustment. Placement out of the locking position can cause improper functioning of the indicator. 13.3- INSTALLATION AND MAINTENANCE: Open the front visor and place the operation range limit Keys (load-bonus) on the desired positions. Remember that the relay must be appropriate to receive the microswitches signal for the correct operation of this functionality; Perform the tap changer mechanical indication flexible cable connection to the inlet axis of the TB-I900 indicator. Remember that the cable must be connected in order to obtain a correct indication of the position signalized on the TB-I900 visor and the real position of the tap changer. This operation should be preferable performed in neutral position; Perform a manual test, using the relay's outer supply in order to evaluate the behavior and proper cables connection. Perform tests on reset and operation range limitation functions. Check if the system did not get heavy, causing the tap changer dragging. Check if the assembling is correct with regards to the system's tightness. If everything is operating properly, the regulator with TB-I900 indicator is ready to return to operation. During its life cycle, TB-I900 does not need periodical maintenance, being only required its functional monitoring so that adjustments can be performed in case of pointers misalignment. 37 EE-40023 13.3.4- Dimensions 2 3 "A" 1 .8 R0 R0 .8 C0.5 Detalhe "G" DESCRIPTION OF COMPONENTS: 1 FRONTAL ALUMINIUM CHILLED COVER 2 DISPLAY IN POLYCARBONATE 3 MECHANISM BOX ALUMINIUM CHILLED VIEW "A" The product may undergo changes due to changes in the manufacture processes, improvements or materials substitution without previous notice. 38 EE-40023 14 – SPECIAL CARE WITH HANDLING, WASTE DISCARDED, AND LEAKAGES ASSOCIATED TO S VOLTAGE REGULATORS 14.1- Goals Provide the necessary information for disposing wastes from potency transformers, distribution transformers, voltage regulators and derivation reactors that may cause any impact to the environment, as well as measures to be taken in case of leakage of oil, paint, solvent, etc. during transportation, reception, storage, and installation inspections. 14.2- Definitions Environmental aspect: Activity, product or service that may interact with the environment in normal or risky situation. E.g. Gas emissions, oil spillages. Aspect = causes. Environmental impact: consequence of environmental aspects that result in the environmental change. Example: Air contamination, ground water contamination. Impact = Aspect effect. 14.3- General Requirements The TSEA ENERGIA, aware of its compromise with the sustainable development, and answering the expectations from the customers and from society that are looking for products that do not attack the environment is investing in a permanent way in the improvement of its acting related to the environment. The TSEA ENERGIA in its continuous search of the development of its activities, products and services try to attend all the legislation and it is introducing its environmental administration system in order to attend also the NBR ISO 14001 and OHSAS 18001. 14.3.1- Integrated Management Policy Quality, Environment, Occupational Health and Safety The TSEA ENERGIA, located in the city of Contagem, state of Minas Gerais, has the commitment to comply with the needs of customers, shareholders, employees, partners and society, continuously improving its performance in the manufacture of transformers and services rendering. 14.3.2- Environmental Aspects Below we list the environmental aspects of transportation activities, receipt, storage and installation inspections for voltage transformers, distribution transformers, voltage regulators, and derivation reactors. 14.3.2.1 - Significant Environmental Aspects -Transformers, regulators, and reactors disposal, -Insulating oil discarding; -Oil barrels disposal; -Paints and/or solvents discarding; -Insulating oil leakage; -Paints and/or solvents leakage. 39 EE-40023 14.3.3- Waste Handling and Destination - The equipment you are purchasing contains insulating oil inside. Oil spillage, once not contained, changes the soil and/or water quality, harming the environment. - Transformers, triphasic voltage regulators, and derivation reactors shall be installed within contention bases in order to avoid, in case of leakage, soil and water contamination. The insulating oil contained in the equipment can be treated, filtered and reused, or co-processed in mortar stoves. The metal part may be sent for casting companies. 14.3.3.1- Transformers, Regulators and Reactors Discarded 14.3.3.1.1- Metallic scraps In general (silicon steel, copper, brass, carbon steel, aluminium). The metallic scraps must be selectively discarded and send for recycling. 14.3.3.1.2- Porcelain: It must be discarded as ordinary refuse in sanitary filled land. 14.3.3.2- Insulating Oil Discard Direct it to barrels for later treatment or filtering and reuse or co-processing in mortar stoves, incineration or discarded in Class I dump*. 14.3.3.3- Disposal of Insulating Oil Barrels Barrels contaminated with oil shall be treated and reused. There are licensed companies that perform the proper treatment and sell them. 14.3.3.4- Discarding Paints and Solvents Direct them to co-processing in mortar stoves, incineration or Class I dump*. 14.3.3.5- Insulating Oil Leakage 14.3.3.5.1- Small insulating oil leakage -Collect the leaked oil with the aid of rag, cloths or sawdust; -Collect the residues and direct them for co-processing in mortar stoves, incineration or Class I dump*; -In case of being able to collect the spilled oil, proceed according to item 13.3.3.2; Note: In case of insulating oil leakage due to the actuation of the pressure relief valve, proceed according to item 13.3.3.2. 14.3.3.5.2- Major insulating oil leakage -Immediately contain the oil using sandbags; -Collect the oil into barrels or canisters; -Proceed according to item 13.3.3.2. 40 EE-40023 14.3.3.6- Paints, Solvents and Other Leakages -Collect the leaked substance with the aid of rags, cloths or sawdust; -Collect the residues and direct them to co-processing in mortar stoves, incineration or Class I dump*; Note: In case of leakage, care must be taken regarding the generation of sparks, as the substances are flammable. 14.3.3.7- Discarding Cloths, Rags, Insulating Papers, Press Cardboard, Plastics, and Sawdust Impregnate with Oil Collect the residues and direct them to co-processing in mortar stoves, incineration or Class I dump*. 14.3.3.8- Discarding Wooden Packages Collect and send to recycling or reuse as fuel in stoves, auto stoves, etc. 14.3.3.9- Discarding Plastic Used in Packages Selectively collect and send to recycling. 14.3.3.10- Discarding Cardboard Used in Packages Selectively collect and send to recycling. 14.3.3.11- Discarding Steel Protections Selectively collect and send to recycling. 14.3.3.12- Discarding Gasket, Cork, Adhesive Tapes, Rubbers Collect as garbage and send to sanitary dump. 14.3.3.13- Discarding Paints, Solvents Packages Collect, send to recycling, reuse or send to sanitary dump. 14.3.3.14- Discarding of Oil Cleaning Filters Collect and send to co-processing in mortar stoves, incineration or Class I dump*. 14.3.3.15- Noise Check if it is according to federal or state environmental legislation, otherwise, perform maintenance to minimize noise. 14.4- Legal Requirements and Other Requirements When disposing a transformer, care must be taken to comply with the legislation in your State. We communicate below the most important points of legislation regarding the equipment supplied by: TSEA ENERGIA -Toxic wastes, as well as the ones that contain flammable (insulating oil), explosive, and other harmful substances, shall undergo treatment and/or proper conditioning at the production site and comply with the conditions established by the pollution control and environmental protection state agency. -Garbage or wastes shall not be discharged in waterways, courses, lakes or ponds, except in case of the need to dispose in artificial ponds, authorized by the pollution control and environmental protection state agency. -It is forbidden to deposit, discard, unload, burry, infiltrate, or accumulate any types of waste on soil, except for the ones whose disposal is made as established in specific projects of transportation and final destination, being forbidden the simple 41 EE-40023 discharge or deposit in public or private property. 14.5- Training, Awareness and Competence In case of subcontracting transportation, unloading, storage, and installation of the equipment, the information described herein must be forwarded to the subcontractor in order to make it aware of: -The importance of environmental policy; -The significance of actual or potential environmental impacts, its activities and benefits to the environment resulting from its performance improvement; -The potential consequences of non-observance of the procedures described herein. Personnel who perform tasks that may cause significant environmental impacts must be qualified, with proper education, training and/or expertise. 14.6- Communication In case of doubts regarding the waste disposal, please contact the Integrated Management Area for TSEA ENERGIA Programs through telephone (+55 31) 3329-6557. 15 - DRAWINGS AND SPECIFIC INSTRUCTIONS ATTACHED. Separately from this manual, you will also receive: -Instructions manual for the voltage regulator control; -Specific drawings applied to the regulator; -Specific painting process to the regulator. 42 EE-40023 43 EE-40023