1.13 PLANTING and its density as to be
enough to have the area fully covered.
Contractor to include the sedum price
in other plants items specified in the
BOQ.
The estimated length for fire rated
cable from MSDB to FFP is 100m, so:
• 1x185mm2 is 400m considering spare
length around +20%
• 1x95mm2 is 300m considering spare
length around +20%
These types of cables shall be included
in the Scope of Work.
Any difference in quantities should be
considered in the unit price rate for
the provided tender quantities.
The type of cable is the same in
drawings and BoQ. In schematic
drawings it’s shown the code of
specific cable used for calculation. In
the BoQ is shown the general
description of cable with the same
characteristics, without shown the
specific code.
RZ1-K: LV CABLE XLPE INSULATION
SZ1-K: LV CABLE FIRE RESISTANT
In the drawing each lighting fixture is
described by its PROJECT CODE and
INSTALLATION INFORMATION
For example, project code LCF31 C is a
CEILING installation and LFC31 D is an
installation that can be described only
in DETAIL. You can find this
information under the Lighting Legend
in the Lighting Design tables.
As for LFC31 is the linear fixture
proposed to illuminate all the
musharabia of the facade and should
be positioned in the lower and internal
part of it as to wall wash the facade. As
for LFC31 Ceiling Installation is only
present in the L02 001.
Our estimated length for Fire rated cable (3(1x185) +(1x95)
+(1G95) from MSDB to firefighting pumps are 100 meters,
since this is 3 sets, both 1x185mm2 and 1x95mm2 shall be
the same length, plus 300 meters also for (1G95) however
in the BOQ the 1x185mm2 is 250 meters and only 200
meters for 1x95mm2, please verify.
47
Kindly verify the code provided in the BOQ for cables vs in
the drawing are not matching.
48
In lighting system, there are type of lighting fixture like
LFC31-C which is installed on ceiling, but may we know
what is LFC31-D? this code is not available in the
installation info or lighting legend, kindly enlighten us.
49
Restaurant to give a similar effect over
the musharabia that is present on the
ceiling .
Your observation is right there is code
mistake in the area L00 005 Restaurant
entrance where erroneously the code
is LFD80. Ignore and substitute with
LFB80
The secondary line and related
junction boxes are not shown. The
number is estimated based on the area
to cover.
The different type of lighting point is
considered in BoQ based on the
different type of switching mode,
shown on the drawings in the same
area (i.e. in the room in which it’s
provided a push button, all the lighting
points of the room are considered in
BoQ with item 26.7.3)
For HVAC specs. refer to
TD.TLM.01_SPECIFICATIONS.pdf”
same air flow value just different units.
1 m3/hr = 0.278 L/sec
Kindy check the quantity of Cove fixture – LFB80 because
the numbers in the BOQ are 5.5, Also this item is not in the
drawing.
50
There are 150 nos. of 150x110x70 mm boxes and 150 also
for 300x220x120 mm In the BOQ S.N 26.6.16 & 17,
however not shown in the drawing, please verify.
51
In wiring devices, lighting points of S. No 26.7.1,2 & 3 are
not reflected in the drawing, kindly verify.
52
Mechanical Equipment’s specification not indicated in the
tender drawing.
53
Machine HVAC Equipment in tender drawing is indicated
as cubic meter per hour while in BOQ it is Liters per second.
54