UPS
12-1029
Valve Regulated Lead Acid Battery
Designed for UPS Standby Power Applications.
FEATURES & BENEFITS
APPLICATIONS
• 10 year design life @ 25˚C
• Data Centers
• Network Operations Centers
• Industrial Process Control Facilities
• Banks & Financial Markets
• Power Generation Plants
• Patented UL Recognized Flamearresting vents in each cell for safety and
long life.
• Hospitals & Testing Laboratories
• Emergency 911 Response Centers
Voltage
12
UPS12-400MR
12
103
UPS12-300MR
UPS12-350MR
12
12
12
12
UPS12-490MRLP
12
UPS12-490MR
UPS12-540MR
UPS6-620MR
34.6
53.8
78.6
93.2
118
12
141
6
199
12
149
* Nominal 20 hr rate to 1.75 VPC in Ampere-Hours.
• Not restricted for air transport - Complies
with IATA/ICAO Special Provisions A67.
• Designed with the same recombination,
thermal runaway prevention, gassing and
flame retardant characteristics of the
Bellcore 4228 compliant Dynasty Telecom
products.
• Flame retardant polypropylene case and
cover compliant with UL 1778
Model
UPS12-100MR
UPS12-150MR
UPS12-210MR
• Can be operated in any orientation.
Upright, side or end mounting
recommended.
• Patented Long Life Alloy having the
lowest calcium levels in the industry minimizing grid growth, reducing gassing,
and extending battery life.
• Semiconductor Manufacturing
AH
20 hr*
26.0
• Thermally welded case-to-cover bond to
eliminate leakage.
• 3 Year Warranty (refer Dynasty warranty
card, 41-9027)
• Internet Housing Sites
TECHNICAL DATA
• Proprietary Fixed Orifice Plate Pasting
technology applying active materials
on both sides of the grid for consistent
cell-to-cell performance, higher
capacity and uniform grid protection.
• Absorbent Glass Mat (AGM) technology
for efficient gas recombination of up
to 99% and freedom from electrolyte
maintenance.
• Not restricted for surface transport Classified as non-hazardous material
as related to DOT-CFR Title 49 parts
171-189.
• Not restricted for water transport Classified as non-hazardous material per
IMDG Amendment 27.
Constant Power Discharge Ratings - Watts per Cell @ 77°F (25°F)
Operating Time (in minutes) to 1.67 Volts per Cell
5
172
716
10
117
15
90.9
20
75.4
30
57.2
40
46.5
50
39.3
60
34.1
90
24.6
lbs
21.0
506
400
328
244
195
162
139
97.2
75.8
290
373
546
619
193
261
385
440
787
608
771
875
938
593
657
747
148
206
300
350
488
488
537
620
120
169
245
289
403
411
451
530
88.9
127
183
216
297
317
343
410
71.1
102
147
173
234
258
277
335
59.4
85.1
123
144
193
218
231
283
51.1
73.3
106
123
164
36.1
51.9
75.0
85.9
112
27.3
40.0
58.4
67.4
83.0
189
135
100.0
245
174
72.0
198
139
100.0
Weight
kg
10.0
12.4
18.0
26.5
30.5
34.4
38.0
45.0
45.0
33.0
UPS
SPECIFICATIONS
Operating Temperature Range
with temperature compensation
Discharge: -40˚F (-40˚C) to +160˚F (71˚C)
Charge: -10˚F (-23˚C) to +140˚F (60˚C)
Nominal Operating Temperature Range
+74˚F (23˚C) to +80˚F (27˚C)
Recommended Maximum Charging
Current Limit
C/5 amperes @ 20hr rate
Maximum AC Ripple (Charger)
0.5% RMS or 1.5% P-P of float charge voltage recommended for best results.
Max voltage allowed = 1.4% RMS (4% P-P) Max current allowed = C/20
Float Charging Voltage
13.65 ± 0.15 VDC average per 12V unit (6.75 to 6.90 per 6V unit)
Self Discharge
Battery can be stored up to 6 months at 77°F (25°C) before a freshening charge is
required. Batteries stored at temperatures greater than 77°F (25°C) will require
recharge sooner than batteries stored at lower temperatures. See C&D brochure
41-7272, Self-Discharge and Inventory Control for details.
Equalize charge and
cycle service voltage
14.40 to 14.80 VDC average per 12V unit @ 77˚F (25˚C) (7.20 to 7.40 VDC per 6V unit.)
Terminal: Flag
0.22 in. clearance hole to accept 0.1875 in. or 10-32 bolt (UPS12-100MR)
Terminal: Inserted
Threaded copper alloy insert terminal to accept
10-32 UNF bolt (UPS12-150MR, UPS12-210MR)
1
⁄4-20 UNC bolt (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MRLP, UPS12-490MR,
UPS12-540MR, UPS6-620MR)
Terminal Hardware Annual Retorque
32 in.-lbs (3.48 N-m) (UPS12-100MR)
Terminal Hardware Initial Torque:
Inserted Terminal
40 in.-lbs. (4.5 N-m) (UPS12-100MR)
30 in.-lbs. (3.4 N-m) (UPS12-150MR, UPS12-210MR)
110 in.-lbs. (12.4 N-m) (UPS12-300MR, UPS12-350MR, UPS12-400MR, UPS12-490MRLP, UPS12-490MR,
UPS12-540MR, UPS6-620MR)
DIMENSIONS
Battery Termination
UPS12-100MR
UPS12-150MR
1.33
33.88
0.75
19.0
UPS 12-300MR
5.07
6.37
(128.8) (161.7)
6.86
(174.3)
UPS12-150MR
7.76
(197.1)
7.54
(191.4)
5.19
(131.9)
5.02
6.52
(127.6) (165.7)
6.80
(172.7)
UPS12-210MR
9.0
(228.6)
8.86
(225.1)
5.48
(139.2)
5.31
7.89
(134.8) (200.3)
8.07
(205.1)
UPS12-300MR
10.27
(260.9)
10.17
(258.4)
6.83
(173.4)
6.65
7.89
(168.9) (200.3)
8.01
(203.5)
UPS12-350MR
12.04
(305.8)
11.95
(303.5)
6.83
(173.4)
6.65
7.94
(168.9) (201.6)
8.06
(204.8)
13.42
UPS12-490MRLP (340.9)
12.75
(323.7)
6.80
(172.7)
6.54
8.40
(166.0) (213.2)
8.52
(216.4)
UPS12-490MR
UPS12-540MR
13.57
(344.7)
12.74
(323.6)
6.80
(172.7)
6.63
10.81
(168.4) (274.5)
10.93
(277.7)
UPS6-620MR
12.63
(320.8)
12.51
(317.8)
6.97
(177.0)
6.83
8.82
(173.4) (224.0)
8.94
(227.2)
1.13
28.70
1/4-20 UNC
1.22
31.10
1/4-20 UNC
0.67
17.1
1.33
33.7
0.13
3.2
UPS6-620MR
3.50
89.0
1/4-20 UNC
1.22
31.10
0.13
3.18
5.17
(131.3)
UPS12-490MR/UPS12-540MR
0.13
3.18
6.45
(163.7)
0.98
24.9
0.19
4.7
0.19
4.7
6.54
(166.2)
UPS12-400MR/UPS12-490MRLP
1.31
33.32
UPS12-100MR
UPS12-350MR
F
0.13
3.18
E
1.33
33.68
C
0.13
3.18
D
0.87
22.2
0.50
12.62
B
1/4-20 UNC
0.18
4.67
D
A
#10-32 UNF
1.73
44.04
0.64
16.18
B
#10-32 UNF
1.31
33.32
E
0.66
16.6
0.25
6.42
0.2
5.5 2
6
F
0.50
12.70
A
UPS12-400MR
UPS12-210MR
C
*All dimensions in inches (mm). All dimensions are for reference only. Contact a C&D Representative for complete dimension information.
NOTE: Batteries to be mounted with 0.5 in (1.25 cm) spacing minimum and free air ventilation.
1/4-20 UNC
UPS
SPECIFICATIONS
Model
Cells per
Unit
UPS12-400MR
UPS12-490MRLP
UPS12-490MR
UPS12-540MR
UPS6-620MR
6
6
6
6
3
UPS12-100MR
UPS12-150MR
UPS12-210MR
UPS12-300MR
UPS12-350MR
6
6
6
6
6
Maximum Discharge
Current (AMPS)
500
500
600
800
800
Short Circuit Current
(AMPS @ 0.1 sec)
Ohms Impedance
60 Hz (Ω)
1750
2500
3000
3600
4200
800
800
800
800
800
0.0060
0.0060
0.0045
0.0040
0.0030
5100
5000
6000
5000
4350
0.0025
0.0023
0.0022
0.0023
0.0012
Additional product details available on the C&D Battery Sizing Program at www.cdstandbypower.net. Cabinet systems also available.
UPS12-100MR
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
End Point
Volts/Cell
1.90
1.85
1.80
1.75
5
157
168
172
174
179
.083
50.8
63.2
71.8
85.5
10
114
115
117
118
119
.25
32.9
38.1
41.6
45.7
.5
22.5
25.3
27.5
28.7
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
15
87.5
89.6
90.9
91.5
92.5
20
72.1
74.4
75.4
75.9
76.8
30
54.9
56.5
57.2
57.6
58.3
40
45.0
46.0
46.5
46.9
47.4
45
41.5
42.1
42.6
42.9
43.4
50
38.5
38.9
39.3
39.7
40.1
Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
.75
17.1
18.6
20.3
21.4
1
13.8
15.0
16.1
17.0
2
8.29
8.99
9.42
9.74
3
6.04
6.56
6.83
6.99
5
3.95
4.30
4.46
4.54
8
2.61
2.84
2.95
3.00
10
2.15
2.33
2.42
2.45
12
1.82
1.98
2.05
2.08
20
1.14
1.24
1.28
1.30
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS12-150MR
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
End Point
Volts/Cell
1.85
1.80
1.75
5
273
284
290
294
297
1
22.8
24.2
25.4
10
182
188
193
196
200
2
13.0
13.6
14.1
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
15
140
144
148
149
152
20
115
117
120
122
124
30
85.7
87.1
88.9
90.0
91.0
40
68.8
69.8
71.1
71.8
72.5
45
62.7
63.6
64.7
65.3
65.9
Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
3
9.08
9.46
9.80
5
5.70
5.91
6.11
8
3.76
3.90
4.00
10
3.10
3.21
3.28
12
2.64
2.72
2.79
60
33.7
33.8
34.1
34.5
34.8
24
0.96
1.05
1.08
1.10
90
24.0
24.4
24.6
24.8
25.0
72
0.34
0.37
0.38
0.39
100
0.24
0.26
0.27
0.28
50
57.6
58.4
59.4
60.0
60.5
60
49.7
50.3
51.1
51.5
51.9
90
35.0
35.7
36.1
36.4
36.6
20
1.64
1.69
1.73
24
1.38
1.41
1.45
72
0.47
0.48
0.49
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS
UPS12-210MR
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
5
341
366
373
378
391
10
243
253
261
262
265
End Point
Volts/Cell
1.85
1.80
1.75
1
32.6
34.8
36.7
2
19.1
20.3
21.1
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
15
193
200
206
205
207
20
162
166
169
170
172
30
123
125
127
128
129
40
99.0
100
102
102
103
45
90.3
91.1
92.6
93.3
94.0
3
13.6
14.4
14.9
5
8.68
9.20
9.43
8
5.79
6.12
6.25
10
4.72
5.00
5.05
12
4.01
4.24
4.28
Constant Power Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
50
83.0
83.6
85.1
85.7
86.3
60
71.5
71.8
73.3
73.8
74.2
20
2.51
2.65
2.69
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS12-300MR
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
5
493
525
546
564
579
10
360
379
385
395
402
End Point
Volts/Cell
1.85
1.80
1.75
1
48.3
51.1
52.7
2
28.1
29.3
30.1
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
End Point
Volts/Cell
1.85
1.80
1.75
5
534
596
619
638
669
10
410
425
440
455
471
1
53.0
58.8
62.6
2
31.8
34.5
36.3
24
2.12
2.23
2.27
72
0.73
0.76
0.77
15
281
293
300
302
306
20
232
240
245
247
250
30
175
179
183
183
186
40
141
144
147
147
150
45
129
131
134
134
137
50
119
120
123
124
126
60
103
104
106
107
109
90
73.5
74.0
75.0
76.2
77.7
3
19.9
20.7
21.2
5
12.6
13.1
13.4
8
8.36
8.84
9.16
10
6.82
7.23
7.46
12
5.79
6.13
6.32
20
3.62
3.83
3.93
24
3.05
3.22
3.30
72
1.05
1.08
1.10
Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS12-350MR
90
50.6
50.4
51.9
52.1
52.3
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
15
327
337
350
358
367
20
272
280
289
296
302
30
205
211
216
220
223
40
165
169
173
175
177
45
150
154
157
159
161
50
138
141
144
145
147
60
119
121
123
124
126
90
84.3
84.9
85.9
86.5
87.6
3
22.9
24.6
25.8
5
14.8
15.7
16.4
8
10.6
10.1
11.0
10
8.73
8.35
8.98
12
7.38
7.09
7.57
20
4.56
4.39
4.66
24
3.84
3.69
3.92
72
1.29
1.32
1.34
Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS
UPS12-400MR
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
5
612
678
716
740
767
10
470
490
506
515
530
End Point
Volts/Cell
1.85
1.80
1.75
1
56.2
62.1
67.9
2
33.7
36.5
39.2
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
15
374
388
400
403
411
20
310
323
328
332
337
30
232
241
244
247
249
40
186
193
195
197
199
45
169
176
177
179
180
50
155
161
162
164
165
60
134
138
139
140
142
90
94.7
96.6
97.2
98.1
99.2
3
24.4
26.1
27.8
5
15.7
16.7
17.6
8
10.8
11.4
11.9
10
8.85
9.38
9.73
12
7.56
8.00
8.26
20
4.8
5.03
5.17
24
4.06
4.23
4.35
72
1.38
1.43
1.46
Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS12-490MRLP
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
5
670
747
787
817
858
10
540
583
608
627
648
End Point
Volts/Cell
1.85
1.80
1.75
1
77.3
82.6
86.2
2
44.4
46.6
47.8
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
15
445
471
488
500
512
20
375
392
403
412
420
30
282
291
297
302
306
40
224
230
234
237
240
45
203
209
211
214
216
50
185
190
193
195
196
60
158
162
164
165
166
90
109
112
112
113
114
3
31.1
32.4
33.5
5
19.7
20.4
21.0
8
12.9
13.3
13.7
10
10.6
10.9
11.1
12
8.89
9.15
9.36
20
5.60
5.79
5.90
24
4.68
4.85
4.94
72
1.62
1.66
1.69
Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS12-490MR
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
5
655
740
771
799
838
10
527
573
593
614
640
End Point
Volts/Cell
1.85
1.80
1.75
1
80.8
86.4
91.0
2
48.4
51.3
53.5
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
15
443
470
488
497
513
20
382
400
411
419
429
30
300
310
317
321
325
40
247
253
258
261
264
45
227
233
237
239
241
50
210
215
218
220
222
60
183
187
189
191
193
90
132
134
135
137
138
3
34.8
36.7
38.2
5
22.4
23.4
24.4
8
15.0
15.6
16.2
10
12.3
12.7
13.1
12
10.5
10.8
11.1
20
6.66
6.88
7.06
24
5.64
5.82
5.98
72
1.93
1.99
2.03
Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS
UPS12-540MR
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
5
728
833
875
912
959
10
564
626
657
683
701
End Point
Volts/Cell
1.85
1.80
1.75
1
82.7
89.6
98.9
2
49.5
53.1
57.0
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
15
471
511
537
550
560
20
406
433
451
462
468
30
318
332
343
349
353
40
261
269
277
280
283
45
239
246
252
255
258
50
221
226
231
234
237
60
191
195
198
201
203
90
136
138
139
141
143
3
35.6
38.1
40.3
5
22.9
24.4
25.5
8
15.0
15.9
16.5
10
12.6
13.2
13.6
12
10.9
11.3
11.7
20
7.05
7.29
7.46
24
5.98
6.18
6.31
72
2.00
2.07
2.11
50
274
278
283
288
295
60
238
241
245
250
256
90
169
171
174
178
183
20
9.27
9.66
9.96
24
7.85
8.10
8.42
72
2.73
2.83
2.87
Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
UPS6-620MR
End Point
Volts/Cell
1.75
1.70
1.67
1.65
1.60
End Point
Volts/Cell
1.85
1.80
1.75
5
862
890
938
951
1000
1
106
114
121
10
681
718
747
763
794
2
63.6
67.6
71.2
Constant Power Discharge Ratings - Watts Per Cell @ 77˚F (25˚C)
Operating Time to End Point Voltage (in minutes)
15
573
602
620
634
655
20
497
517
530
542
557
30
392
403
410
419
429
40
323
330
335
342
349
45
297
302
307
313
320
Constant Current Discharge Ratings - Amperes @ 77˚F (25˚C)
Operating Time to End Point Voltage (in hours)
3
46.2
48.8
50.9
5
30.1
31.6
32.6
8
20.3
21.2
21.9
10
16.9
17.6
18.1
12
14.5
15.1
15.6
Note: Batteries to be mounted with 0.5 in. (1.25 cm) spacing minimum and free air ventilation. Specifications subject to change without notification.
Above ratings do not include interunit connector voltage drops.
High Rate Max Part Number
Manufacturer Approved Premium Replacement for:
UPS12-100MR
UPS12-150MR
UPS12-210MR
UPS12-300MR
UPS12-350MR
UPS12-400MR
UPS12-490MRLP
UPS12-490MR
UPS12-540MR
UPS6-620MR
UPS12-100FR
UPS12-140FR & MR12-150
UPS12-170FR, UPS12-200FR & MR12-210
UPS12-270FR & MR12-300
UPS12-310FR & MR12-350
UPS12-370FR & MR12-400
UPS12-475FR, MR12-490 & UPS12-490MR (Low profile high rate applications)
UPS12-475FR & MR12-490 (Extended run applications)
UPS12-530FR & MR12-540
UPS6-620FR
1400 Union Meeting Road
P.O. Box 3053 • Blue Bell, PA 19422-0858
(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630
customersvc@cdtechno.com
www.cdtechno.com
Any data, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc. without
notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc. makes no
warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or completeness of
such information. Further, because the product(s) featured herein may be used under conditions beyond its control,
C&D Technologies, Inc. hereby disclaims all warranties, either express or implied, concerning the fitness or suitability of such product(s) for any particular use or in any specific application or arising from any course of
dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s)
featured herein for user’s intended purpose and in user’s specific application.
Copyright 2010 C&D TECHNOLOGIES, INC.
Printed in U.S.A.
12-1029 0110/CD