No. AOTS-T-2023-02 Date: June 23, 2023 You can access this information from the Daikin Business Portal https://global1d.daikin.com/business_portal/login/ Subject: Understanding EER, COP, IPLV and IEER. Issued by: AOTS <aots_group@dit.daikin.co.jp> Introduction Government and agency has their own different energy efficiency measurement methods. You may need to know how to calculate each energy efficiency ratings of air conditioners to support the markets in each country to meet their local requirements. Get to know about EER, COP, IPLV, IEER and calculations The four calculation methods presented in this newsletter are the most common and widely used - EER, COP, IPLV and IEER, which will be detailed as below. EER (Energy Efficiency Ratio) EER or Energy Efficiency Ratio is a calculation method of energy efficiency by dividing the cooling capacity of A/C (BTU/hr) by the power consumption that supply to A/C (W). EER = Cooling capacity of A/C (BTU/hr) Power consumption (W) Example Calculations : EER = Cooling capacity of A/C(BTU/hr) Power consumption (W) EER = Answer : Figure 1, Specification table -1- 9,000 (BTU/hr) 810 W EER = 11.11 COP (Coefficient Of Performance) COP or Coefficient Of Performance is a calculation method of energy efficiency by using capacity of A/C in (W) units to compared with power consumption in (W) units. This calculation method is similar to EER but the difference is in the Power Output units of measurement used. COP = Capacity of A/C (kW) Power consumption (kW) Example Calculations : COP = COP = Figure 2, Specification table Answer : Capacity of A/C (kW) Power consumption (kW) 16 kW 3.38 kW COP = 4.73 IPLV (Integrated Part Load Value) *Vietnam EER has similar formula. IPLV or Integrated Part Load Value is a calculation method of energy efficiency by using the EER values at the different capacity loads. This method is different from the previous two methods. IPLV is developed by AHRI (Air-Conditioning, Heating and Refrigeration Institute). IPLV will have same outdoor temperature at 35˚C for all capacity loads. IPLV = 0.01A+0.42B+0.45C+0.12D *Constant values can be change depending on ANSI/AHRI standard. Figure 3, Breakdown of frequency of loading % -2- Example Figure 4, Cooling capacity and Power Input at different loading Formula : IPLV = 0.01A+0.42B+0.45C+0.12D A = EER@ 100% Load, Outdoor temperature 35˚C. B = EER@ 75% Load, Outdoor temperature 35˚C. C = EER@ 50% Load, Outdoor temperature 35˚C. D = EER@ 25% Load, Outdoor temperature 35˚C. According to details as above. Use the data in Figure 4 to calculate the EER. Then input the EER value into IPLV formula. Calculations : IPLV = 0.01A+0.42B+0.45C+0.12D IPLV = (0.01x16.15)+(0.42x20.00)+(0.45x25.00)+(0.12x9.30) Answer : IPLV = 20.92 IEER (Integrated Energy Efficiency Ratio) IEER or Integrated Energy Efficiency Ratio is a calculation method of energy efficiency where it considers the loads at different outdoor temperature conditions. IEER will have different outdoor temperature for each capacity loads. IEER = 0.020A+0.617B+0.238C+0.125D -3- *Constant values can be change depending on AHRI standard. Figure 5, Breakdown of frequency of loading % and temperature Example Figure 6, Cooling capacity and Power Input at different loading and temperatures Formula : IEER = 0.020A+0.617B+0.238C+0.125D A = EER@ 100% Load, Outdoor temperature 35˚C. B = EER@ 75% Load, Outdoor temperature 27.5˚C. C = EER@ 50% Load, Outdoor temperature 20.0˚C. D = EER@ 75% Load, Outdoor temperature 18.3˚C. According to details as above, Use the data in Figure 6 to calculate the EER. Then input the EER value into IEER formula. Calculations : IEER = 0.020A+0.617B+0.238C+0.125D IEER = (0.020x16.00)+(0.617x20.60)+(0.238x23.83)+(0.125x16.30) Answer : IEER = 20.73 -4- Summary The energy efficiency ratings mentioned above are the most commonly used in the market. There are different consideration for the use of the different energy efficiency rating. There is no correct rating to use for any conditions. It is left to the system designer to make their own judgment on which efficiency rating is suitable for their design. Figure 7, Summary table -5-