THE DESIGN, SUPPLY AND INSTALLATION OF 245kV 1x250MVA AUTOTRANSFORMER, 1x120MVAr AND 1x240MVAr VARIABLE SHUNT REACTORS FOR THE SECOND ELECTRICAL MALTA-SICILY INTERCONNECTOR Control : Approve : Control: Approve: HV CABLE BOX CONSOLE for SHUNT REACTORS COMPANY Project Manager ISSUE OWNER Prepared Gürkan Saltık Checked Purpose □ For Information □ For Review □ For Approval □ For Construction □ As-Built Revision Date : DOCUMENT NO Bilgi Sınıfı: Hizmete Özel | Restricted Bu dokümanın onay sayfası KVKK kapsamında Kişisel Veri içermez. Reviewed 1 2 3 4 5 6 7 8 9 10 11 PIPE BETWEEN CONSERVATOR & CABLE BOX ( DN 25 ) A TRANSFORMER TANK 12 A REMOVABLE COVER VALVE FOR FILLING & OIL TREATMENT (OIL-INLET) DN25 EARTHING TERMINAL FOR TEST ( M12 ) FLEX CONDUCTOR Ø710 SHIELD Nexans - 245 kV - ISOB 60011 (Supplied by Cable Sealing End Manufacturer) (Out of ATT scope) HAND HOLE B B HV BUSHING GSA 245-00-1600 A C Ø960 1255 VALVE FOR DRAINING & OIL TREATMENT (OIL-OUTLET) DN25 CABLE SEALING END NEXANS - 245 KV - ISOB 60001 (Out of ATT scope) STUD BOLT,NUT,WASHER (Supplied by Cable Sealing End Manufacturer) C (Out of ATT scope) A TORQUE : 25 Nm HV CABLE BOX SUPPORT 2000 SUPPORT FOR " BAFT 97 " A A THICKNESS =24 mm MATERIAL : S235 JR DIN EN 10025-2 D D Interface acc. to IEC 62271-209 : VIEW " A " Ø475 R1 R10 24 22 16 0.0 7-0.1 E E Ø385 11+0.4 0.0 M12X16 Ø400 3100 SECTION A-A F Detail "A" HGW-2375-4 insulation pipe HGW-2375-4 insulation plate HGW-2375-4 insulation washer G FRONT VIEW OF 230kV HV CABLE BOX CONSOLE B Detail "B" 5 pieces adjustment plates ( t=5mm.) 20 20 mm. gap is predicted between ground&plate during design stage and according to this gap 5 pieces adjustment plates will be available. H 1 2 3 gap>20 4 If gap between ground&plate will be more than 20 mm., it should be fixed with two nuts for height adjustment. 5 7 8 9 10 11 12 C 2004