MOTOR CIRCUIT CALCULATION MOTOR CIRCUIT CALCULATION Step 6 Feeder Overcurrent Device Step 4 Branch Circuit Overcurrent Device Step 5 Feeder Wire Size Step 3 Branch Circuit Wire Step 2 Overload Protection MOTOR MOTOR Step 1 F.L.C STEP 1 “F.L.C (Full Load Current)” • Table 4.30.14.1 for Direct Current. • Table 4.30.14.2 for Two Phase AC motor. • Table 4.30.14.3 for Two Phase AC motor (4-Wire) • Table 4.30.14.4 for Three Phase AC motor. STEP 2 “Overload Protection” • Motor running overload protection. Thermal Protector called a “heater”. • PEC provision 4.30.3 not more than 600V • PEC Provision 4.30.9 more than 600V • If motor nameplate is given, use it, if not use FLC from tables Types of Overload Protection • Thermal Protection • Thermal Protection Types of Overload Protection • Separate Overload Device (Overload Relay) Types of Overload Protection A fuse shall be inserted in each ungrounded conductor and also in grounded condcutor • Separate Overload Device (Fuse) STEP 3 “Branch Circuit Wire” Refer to PEC 4.30.2.2 (Motor Circuit Conductor) Shall not be less than FLC x 125%= required ampacity Refer to Table 3.10.1.16 STEP 4 “Branch Circuit Overcurrent Device” • Branch circuit overcurrent device shall be selected from Table 4.30.4.2 • First select the type of motor (1Ø,3Ø,AC,DC,wound rotor,etc.) • Next Select the type of protective device(non-time delay fuse,dual element fuse,inverse time breaker) • Select the percentage from the proper column and multiply it times the FLC of the motor. • Use 2.40 to select the standard size overcurrent device. • When the value does not match a standard, the code permits the next higher STANDARD size for branch circuit OC device. Types of Overcurrent Devices • Non-Time Delay Fuse • Dual-Element time delay-fuse • Instantaneous trip circuit Break • Inverse time circuit breaker STEP 5 “Feeder Wire Size” • PEC provision 4.30.2.4 • Multiply the largest rated motor in FLC by 125% and add the FLC of all other motors connected to the same feeder conductor for the total amps. STEP 6 “Feeder Overcurrent Device” • Select the largest branch circuit overcurrent device and add all the other motor FLC connected on the same feeder conductor to find the amperage required to select the feeder fuse or CB. • The Code does NOT permit going to a higher size if the values does not match a standard size from 2.40.6 • Drop DOWN to the next smaller standard size. Code permits going up only on branch circuit. Example • A 230V,1 HP, Single Phase motor with SF 1.15. a.) Determine overload protection? b.) Determine the size of branch circuit using THW wire? c.) Determine the maximum rating of branch-circuit and ground-fault device. Use inverse-time circuit breaker?