Experiment # 01 Objective: To calculate rate of absorption of CO2 in water from analysis of liquid solutions flowing down absorption column. Apparatus: • Gas Absorption Column Apparatus • CO2 Cylinder with Integral Pressure Regulator • Pyrex Bottle • Pipette • Burette • Flask • Measuring Cylinder. Figure 6: Schematic Diagram of Gas Absorption Column Apparatus 1 Reagents: • CO2 Gas • Water • Air • Phenolphthalein • 0.0277 Molar NaOH Solution • MolarNaHCO3 Solution. Procedure: 1. Fill the liquid reservoir tank at the base of the column to approximately three-quarters full with (preferably) deionized water. Note the volume added [VT liters]. 2. With gas flow control valves C2 and C3 closed, start the liquid pump and adjust the water flow through the column to approx. 6 liters/minute on flowmeter F1 by adjusting flow control valve C1. 3. Start the compressor and adjust control valve C2 to give an air flow of approx. 10% of full scale on flowmeter F2. 4. Carefully open the pressure regulating valve on the carbon dioxide cylinder, and adjust valve C3 to give a value on the flowmeter F3 approx., one half of the air flow F2 ensure the liquid seal at the base of the absorption column is maintained by, if necessary adjustment of control valve C4. 5. After 15 minutes of steady operation, take samples at 10 minute intervals from S4 and S5. Take 150ml samples at known times in each case. Analyze the samples according to the procedure detailed below. Analysis of Carbon Dioxide Dissolved in Water: Note: Water used for absorption should be deionized as presence of dissolved salts affect the analysis described below. If tap water is used, no metal ions should be present in greater quantities than 1.0 mg/liter and pH should be just alkaline: 7.1 to 7.8. 1. Phenolphthalein indicator prepared from carbon dioxide – free distilled water. 2. Standard 0.0277M NaOH solution, prepared by diluting 27.70ml of 1M NaOH standard solution to1 liter with carbon dioxide free distilled water. Prepare fresh and protect from carbon dioxide in the atmosphere by keeping in a stoppered Pyrex bottle. 2 3. Standard 0.01M NaHCO3 solution, prepared by dissolving approximately 0.1 gram of anhydrous NaHCO3 in carbon dioxide free distilled water to 100ml. 4. Withdraw a sample of liquid S5 from the sump tank with the sampler provided, approximate volume of 150ml, or from liquid outflow point S4. 5. Discharge the sample at the base of a 100 ml graduated cylinder, flicking the cylinder to throw off excess liquid above the 100 ml mark. 6. Add 5-10 drops of phenolphthalein indicator solution if the sample turns red immediately, no free C02 is present. If the sample remains colorless, titrate with standard NaOH solution. Stir gently with a glass rod until a definite pink color persists for about 30 seconds. This color change is the end point - note volume VB of NaOH solution added. For best results, use a color comparison standard, prepared by adding the identical volume of phenolphthalein solution to 100ml of sodium bicarbonate solution in a similar graduated cylinder. Observations and Calculations: Cd = Concentration of dissolved free carbon dioxide (gmol/liter). F = Volumetric Flowrate (liters/sec). VB = Volume of NaOH Solution Added in liquid analysis (ml). Subscripts used: T = Total i = Inlet Conditions to Column o = Outlet Conditions from Column The amount of free CO2 in the water sample is calculated from: Note: Solubility of CO2 in water is a strong function of temperature. And the accuracy of this titrimetric method is approximately ±10%. F1 = liters/sec. VT = Volume of Water in System (liters). 3 From Sump Tank S5 From Liquid Outlet Sample Point (Correspond to conditions at top of (minutes) S4 tower) Time from Start Cd in tank VB ml [Cdi] gmol/liter Cd at outlet VB ml [Cdo] gmol/liter 10 20 30 40 50 60 4 Experiment # 02 Objective: To examine the air pressure drop across the column as a function of air flow rate for different water flow rates through the column. • To plot the graph of column pressure drop against the air flow rate in a log – log graph. • To obtain the pressure drop from the generalized correlation chart as in Appendix. • To compare the experimental value and the correlated value. Apparatus: • SOLTEQ-QVF Absorption Column BP751-B Figure 7: The Packed Column Used in The Experiment with Raschig Rings as The Packings 5 Theory: Gas absorption is mass transfer operation where one or more species is removed from a gaseous stream by dissolution in a liquid. The component that is extracted from the gaseous stream is known as solute and the component that extracting the solute is known as solvent. Carrier gas is the insoluble component present in the gas that is not absorbed by the solvent. The transfer is based on the preferential solubility of solutes in the solvent (Gas Absorption And Desorption). Packed towers are used for continuous countercurrent contacting of gas and liquid in absorption.The mechanism in packed tower is the gas and liquid phases flows counter – currently where they interact on the packings interface. The liquid flows in downward direction, over the surface of the packing, whereas the gas flows through the space or voids of the packings in upward direction. The gas flow is driven by pressure while the liquid flow is driven by the gravity force. The gas undergoes pressure drop due to the liquid occupiedsome part of the open space and voids of the packing. Thus, reducing the area available for the gas to flow. If the packing is dry with no liquid feed, then maximum flow gas is available. The pressure drop increases as the liquid flowrate into the tower increases. High flux will resulting in flooding. This occurrence happen at the upper limit of the gas flow rate called flooding velocity since the liquid is blown out with the gas at the flooding point. The gas start to hinder the liquid flow at loading point where accumulation of liquid start appearing in the packing. Low flux will resulting in channelling or weeping. There are two types of packings types which is random and structured. Figure 8: Typical Packed Tower Packings: (a) Raschig ring, (b) Lessing ring, (c) Berl 6 One of the oldest specially manufactured types of random packings are Raschig rings and still in general use. (Separation Columns (Distillation, Absorption and Extraction)) They provide a large surface area within the volume of the column for the interaction between liquid and gas. They also enhance the contact time between liquid and gas. The generalized correlation for pressure drops in packed column. Figure 9: Generalized Correlation for Pressure Drop in Packed Columns Procedure: 1. All the valves are ensured to be closed except for the ventilation valve, V13. 2. All the gas connections are checked to be properly fitted. 3. All the valve on the compressed air supply line is opened. The supply pressure is set to between 2 to 3 bars by turning the regulator knob clockwise. 4. The shut-off valve on the CO2 gas cylinder is opened and the pressure is checked. 5. The power for the control panel is turned on. 6. The receiving vessel B2 is filled through the charge port with 50L of water by opening valve V3 and V5. Then, valve V3 is closed. 7. Valves V9 and V10 is opened slightly. The flow of the water from vessel B1 through pump P1 is observed. Pump P1 is switched on. 8. Valve V11 is slowly opened and adjusted to give a water flowrate of around 1L/min. 7 9. The water is allowed to enter the top of the column K1, flow down the column and accumulated at the bottom until it overflows back to vessel B1. 10. The valve V11 is opened and adjusted to give a water flow rate of 1 L/min into column K1. 11. The valve V1 is opened and adjusted to give and air flow rate of 20L/min into column K1. 12. The liquid and gas flow in the column K1 is observed. The pressure drop across the column at dPT-201 is recorded. 13. Steps 3 to 5 is repeated with different values of air flow rate, each time increasing by 20 L/min each time after two minutes while maintaining the same water flow rate. 14. Steps 3 to 6 is repeated with different values of water flow rate, each time increasing by 1 L/min by adjusting valve V11. 15. Pump, P1 is switched off. 16. Valves, V1, V2 and V12 is closed. 17. The valve on the compressed air supply line is closed and the supply pressure is exhausted by turning the regulator knob counter clockwise all the way. 18. The shut-off valve on the CO2 gas cylinder is closed. 19. All the liquid in the column K1 is drained by opening valve V4 and V5. 20. All the liquid from the receiving vessels, B1 and B2 is drained by opening valves, V7 and V8. 21. All the liquid from the pump P1 is drained by opening valve V10. 22. The power for the control panel is turned off. Observations and Calculations: Density of Air, ρy = 1.175kg/m3 Density of Water, ρX = 996kg/m3 (R. H. Perry, 1973) Packing Factor, FP = 900m3 Column Diameter, D = 80mm Water viscosity, μX = 0.0008 kg/ms (Bingham, 1922) *All properties are at T= 30°C *All calculation is done via excel so the value may vary from calculator. 8 9 10 Flow rate Pressure Drop (L/min) (mBar) Air 20 40 60 80 100 120 140 160 180 1.0 0 0 2 4 5 11 14 25 32 (F) 2.0 0 2 3 6 10 14 25 41(F) F 3.0 1 2 5 10 18 36(F) F F F 140 160 180 Water Flow rate Pressure Drop (L/min) (mm H2O/m) Air 20 40 60 80 100 1.0 0.00 0.00 25.49 50.99 63.73 140.21 178.45 318.66 2.0 0.00 25.49 38.24 76.48 127.46 178.45 318.66 3.0 12.75 25.49 63.73 127.46 229.44 Water 120 458.87 (F) Flow rate Theoretical Pressure Drop (L/min) (in H2O/ft) Air Water 20 40 60 80 100 120 522.60 (F) 407.89 (F) F F F F 140 160 180 F F 1.0 0.0000 0.0906 0.2000 0.2917 0.4205 2.0 0.0750 0.2500 0.3958 0.5000 1.0000 F F F F 3.0 0.1600 0.4318 0.7500 1.5000 F F F F F 0.7500 1.1667 11 Flow Theoretical Pressure Drop rate (mm H2O/m) (L/min) Air Water 20 40 60 1.0 0.0000 2.0 6.2483 20.8275 32.9741 3.0 7.5479 16.6620 80 100 120 F F 41.6550 83.3100 F Flow rate Log Pressure Drop (L/min) (mm H2O/m) Water 1.3010 1.6021 1.7782 1.9031 2.0000 1.0 - 2.0 - 3.0 - 1.4064 1.7074 1.8044 1.4064 1.5825 1.8835 2.1054 1.1054 1.4064 1.8044 2.1054 2.3607 F F F F F F F F 2.0792 2.1461 2.2041 2.2553 2.1468 2.2515 2.5033 2.2515 2.5033 2.6617 (F) Flow rate Log Theoretical Pressure Drop (L/min) (mm H2O/m) Air F 2.7182 (F) F 1.3010 1.6021 1.7782 1.9031 2.0000 2.0792 2.1461 2.2041 1.0 - 0.8778 1.2217 1.3856 1.5445 1.7958 1.9877 2.0 0.7958 1.3186 1.5182 1.6197 1.9207 F 3.0 1.1248 1.5560 1.7958 2.0968 F Water 160 180 24.3015 35.0319 62.4825 97.1978 13.3296 35.9733 62.4825 124.9650 Air 140 F 2.6105 (F) F F 2.2553 F F F F F F F F 12 Air Gas Capacity Liquid Mass Velocity Flow Parameter Flowrat Mass Paramete (𝑮𝒙) 𝐤𝐠/𝐦𝟐𝐬 (x-axis) e (𝐕𝐲) Velocity r(y-axis) LPM (𝑮𝐲) 1 2 3 1 2 3 𝐤𝐠/𝐦𝟐𝐬 LPM LPM LPM LPM LPM LPM 20 0.0779 0.0011 3.3025 6.6049 9.9074 1.4566 2.9132 4.3698 40 0.1558 0.0046 3.3025 6.6049 9.9074 0.7283 1.4566 2.1849 60 0.2338 0.0103 3.3025 6.6049 9.9074 0.4855 0.9711 1.4566 80 0.3117 0.0184 3.3025 6.6049 9.9074 0.3641 0.7283 1.0924 100 0.3896 0.0287 3.3025 6.6049 9.9074 0.2913 0.5826 0.8740 120 0.4675 0.0414 3.3025 6.6049 9.9074 0.2428 0.4855 0.7283 140 0.5454 0.0563 3.3025 6.6049 9.9074 0.2081 0.4162 0.6243 160 0.6234 0.0735 3.3025 6.6049 9.9074 0.1821 0.3641 0.5462 180 0.7013 0.0931 3.3025 6.6049 9.9074 0.1618 0.3237 0.4855 Water Flow Theoretical Flooding Experimental Flooding Percentage Error Rate Air Flow Rate Air Flow Rate (%) (L/min) (L/min) (L/min) 1 160 180 12.50 2 120 160 33.33 3 100 120 20.00 13