December 25, 2016 December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time TRANSMISSION MATERIALS STANDARD SPECIFICATION 35-TMSS-01, Rev. 01 TABLE OF CONTENTS 1.0 SCOPE 2.0 CROSS REFERENCES 3.0 APPLICABLE CODES AND STANDARDS 4.0 DESIGN AND CONSTRUCTION REQUIREMENTS 4.1 4.2 4.3 4.4 General Performance Characteristics and Ratings Construction Nameplate 5.0 TESTS 6.0 DATA SSCHEDULE 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 2 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 1.0 35-TMSS-01, Rev. 01 SCOPE This Transmission Material Standard Specification (TMSS) specifies the minimum technical requirements for design, engineering, manufacture, inspection, testing and performance of Metal Oxide Surge Arresters for 11kV through 380kV system voltages, intended to be used in the system of National Grid SA. This standard is not applicable for GIS surge arrester and arresters provided in link box. 2.0 CROSS REFERENCES This Transmission Material Standard Specification shall be read in conjunction with the latest revision of National Grid SA General Specification No. 01-TMSS-01, titled "General Requirements for All Equipment/Materials", which shall be considered as an integral part of this TMSS. This TMSS shall also be read in conjunction with National Grid SA Purchase Order or Contract Schedules for project, as applicable. 3.0 APPLICABLE CODES AND STANDARDS The latest revisions of the following Codes and Standards shall be applicable for the equipment/material covered in this TMSS. In case of conflict, the vendor/manufacturer may propose equipment/material conforming to one group of Industry Codes and Standards quoted hereunder without jeopardizing the requirements of this TMSS 4.0 3.1 IEC 60099-4 Surge Arresters-Part 4 : Metal-Oxide Surge Arresters without gaps for a.c system 3.2 IEC 60099-5 Surge Arresters-Part 5 : Selection and Application Recommendations 3.3 IEC 62155 Hollow pressurized and unpressurized ceramic and glass insulators for use in electrical equipment with rated voltages greater than 1000 V DESIGN AND CONSTRUCTION REQUIREMENTS The analysis of a power system subject to temporary over-voltage, lightning over-voltage, or switching over-voltage at a transmission line structure requires specific data on the following parameters. 4.1 General The surge arrester shall be of metal oxide, gapless type for outdoor / indoor service, as specified in Data Schedule. 4.2 Performance Characteristics and Ratings Ratings and requirements of surge arrester shall be as specified in Data Schedule 4.2.1 The nominal discharge current for surge arresters shall not be less than 10kA 4.2.2 The ratings of the surge arrester shall be as specified in Table-1 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 3 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION Table - 1 Effectively Grounded System (kVrms) (kVrms) Nominal System voltage 11 13.8 33 34.5 69 110 115 132 230 380 4.2.3 10 12 30 30 60 96 108 120 192 360 8.4 10 24 24 48 76 84 92 152 265 35-TMSS-01, Rev. 01 Non-Effectively Grounded System Arrester Arreter Rating MCOV (kVrms) (kVrms) 12 10.2 15 12.7 36 29 39 31.5 72 57 120 98 132 106 Minimum acceptable single impulse energy capability in kj/kV of surge arrester rating shall be as specified in Table-2. Table - 2 Rating (kV rms) 4.2.4 4.3 Minimum Energy Absorption Capability (kJ/kV of Arrester Rating) for single impulse Arrester class per Table 1 of IEC 60099-4 3-48 4 SL 54-245 7.2 SM 360 10 SH Minimum external insulation withstand levels of the surge arrester housing shall be as specified in IEC 60099-4. Construction 4.3.1 35TMSS01R01/KSB General a. The surge arresters shall be of pedestal type , self-supporting and fitted with insulating bases. b. The surge arrester base shall be insulated from ground for 5kVminimum for outdoor surge arresters. c. The arrester shall not be used as a bus support device. d. Outdoor surge arresters shall be capable of withstanding a washing pressure of up to 3500kpa without penetration of water into the surge arrester. The manufacturer shall furnish evidence of withstanding this pressurized water washing pressure. Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 4 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 4.3.2 35-TMSS-01, Rev. 01 Insulator Housing Insulator housings shall be made of Silicone Rubber or electrical grade wetprocessed porcelain up to 380kV.. The manufacturer, if required, shall furnish evidence regarding integrity of the porcelain housings in accordance with IEC62155 or equivalent. 4.3.3 4.3.4 4.3.5 Pressure Relief Device a. When an arrester is fitted with a pressure-relief device, the failure of the arrester shall not cause explosive shattering of the housing. b. The pressure relief device shall be capable of withstanding the symmetrical fault current of the system as specified in Data Schedule or whichever is higher. c. The pressure relief device shall be designed to ensure safety to operating personnel and other apparatus in the vicinity, in case of the operation of the pressure relief device. Mounting Arrangement a. The surge arrester shall be suitable for base mounting with adopter plate in a vertical position. The arrester base or end casting shall be furnished with at least three mounting holes at 120 degrees on a 254 mm or 420mm diameter bolt circle. The mounting holes shall accommodate either 13mm or 19mm bolt with flat and lock washers. Surge arresters for the 13.8kV and 34.5kV system shall be bracket mounted, if specified. Structure is to be designed for wind load of 2kN per square meter on the arrestor and steel structure. b. Arrester shall never be mounted on pipe carrying oil. Fittings All exposed ferrous parts shall be hot-dip galvanized in accordance with 01-TMSS-01. 4.3.6 Terminals The surge arrester line terminal shall be of 4-hole terminal pad2 with NEMA Standard drilling, suitable for line conductor of sizes up to 240mm .The terminal pad shall be an integral part of the arrester head. The terminal pad shall be corrosion resistant. 4.3.7 35TMSS01R01/KSB Accessories a. 230kV and 380kV arresters shall be equipped with grading rings. b. Surge arresters for system voltages of 69kV and above shall have a surge (discharge) counter along with a built-in milli ammeter to monitor the leakage/internal current of the surge arrester continuously. c. The surge counter shall record the number of lightning and switching discharges of the surge arrester automatically on a five-digit cyclometer dial. The surge counter shall be non- resettable and capable of registering up to 5 discharges per second. d. The leakage and internal current indicator shall monitor and measure the sum of leakage current across the external porcelain insulator plus the internal current flowing through the surge arrester. The scale range shall be 0-50 mA Peak /√2 (nonlinear scale). Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 5 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION e. 35-TMSS-01, Rev. 01 The surge counter and leakage/internal current indicator unit shall be maintenance free, weatherproof sealed type. Insulated cable connection shall be provided between surge arrester ground terminal and surge monitor. The insulation withstand of the cable shall be 5kV minimum. By pass shunt shall be provided to establish continuity to ground from the surge arrester ground terminal for ease in maintenance. It is mandatory for the manufacturer to provide this cable. . 4.3.8 Grounding Each surge arrester shall be provided with one grounding pad, sized to accommodate connectors suitable for stranded copper conductor of sizes up to 70mm2. The connection between surge arrester and discharge counter/ leakage current indicator shall be made with 70mm2 insulated stranded copper conductor. Whereas the connection from leakage indicator to grounding grid shall be made with 2*240mm2 bare stranded copper conductor. 4.3.9 Pressure relief device The arrester should have the capability to withstand internal fault currents after a failure without violent shattering of the housing Therefore the fault current withstand of the arrester should be equal to or greater than the maximum fault current through the arrester at the installation point of the arrester in case the arrester equipped with pressure relief device. 4.3.10 Pollution withstand characteristics The pollution withstand capability of the arrester concerns three aspects: a. The arrester housing should withstand the pollution stresses without flashover according to IEC 60507. b. The arrester should withstand the possible temperature increase due to the changes in voltage distribution caused by the pollution activity on the surface of the housing. Consideration should be given to the pollution level and the frequency and amplitude of over voltages caused by faults and reclosing operations during polluted conditions. c. The arrester should withstand internal partial discharges, caused by disturbed voltage grading on the housing due to pollution, without damage to the varistors or to the internal mounting elements. 4.3.11 Live washing characteristics When live washing of the arrester is foreseen, assurance is required that the arrester housing will not flash over and that the temperature increase of the varistors remains within the specified maximum temperature. Suitable test procedures have to be defined. 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 6 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 4.4 35-TMSS-01, Rev. 01 Nameplate 4.4.1 Each surge arrester shall bear a nameplate permanently and legibly marked in English with the information listed per IEC 60099-4 or as applicable and the following additional information: a. The words “ ” kV Surge Arresters b. National Grid SA Purchase Order Number/Contract Number/J.O. Number. c. 35-TMSS-01, Rev.01 4.4.2 5.0 The nameplate material shall be of anti-corrosion material and shall be fastened to surge arrester by stainless steel screws or rivets. The marking shall be engraved. Type (Design) Tests All type tests prescribed in the latest revision IEC 60099-4 standard shall be performed on the representative unit or on the first unit of every new design or rating to be supplied to National Grid SA. In lieu of the actual type tests, certified test reports of type (design) tests performed on an identical unit may be submitted to National Grid SA for review and approval during bidding stage. All test results shall be provided for review and acceptance by National Grid SA. Tests will be accordingly but not limited to the following: 5.1 Type Test 1- Insulation withstand tests on the arrester housing comprising a. Lightning Impulse test b. Switching Impulse test c. Power frequency withstand test. 2- Residual voltage test a) Steep current impulse residual voltage test b) Lightning impulse residual voltage test c) Switching impulse residual voltage test 3- Test to verify Long term stability under continuous operating voltage. 4. 5. 6. 7. 8. 9. 10. 11. Repetitive Charge transfer withstand test Heat dissipation behavior verification of test sample Operating duty test. Power frequency voltage versus time Short circuit tests. Bending moment. Environmental tests Seal Leak rate 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 7 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 5.2 35-TMSS-01, Rev. 01 12. Radio interference voltage (RIV) 13. Test to verify the dielectric withstand of internal components 14. Test on internal grading components Routine (Production) Tests All routine tests prescribed in the latest revision IEC 60099-4 shall be performed on all surge arresters 5.3 Type, Special and Routine Tests for Polymer Insulator Tests per IEC 60099-4 shall be performed. 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 8 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 6.0 35-TMSS-01, Rev. 01 DATA SCHEDULE SURGE ARRESTER FROM 11kV THROUGH 380kV NOMINAL National Grid SA Enquiry No. Date: National Grid SA Purchase Order No.or Contract No Date: National Grid SA PTS No./Project Title with J.O. No. REFERENCE SECTION NO. DESCRIPTION 'A' 'B' 'C' SYSTEM DATA Nominal System Voltage(kV) (11kV, 13.8kV, 33Kv, 34.5kV, 69kV, 110kV, 115kV, 132kV, 230kV or 380kV) * System Fault Current Level at Rated System Voltage (kA) * Maximum Duration of Ground Fault (ms) * System Neutral Grounding at Arrester Point Of Installation (Effectively, Non-Effectively Grounded) 'A'- NATIONAL GRID SA SPECIFIED DATA/PARAMETER. 'B'- BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS. 'C'- REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'. (*)- DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/ VENDOR/CONTRACTOR IN COLUMN 'B'. 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 9 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 6.0 35-TMSS-01, Rev. 01 DATA SCHEDULE SURGE ARRESTER FROM 11kV THROUGH 380kV NOMINAL REFERENCE SECTION NO. DESCRIPTION 'A' 'B' 'C' System Component(s) to be protected Transmission Line Surge Impedance (ohms) Length (kM) * * Underground Cable Capacitance (µF/kM) Length (kM) * * Capacitor Banks Capacitance (MVAR) Others (Power Transformers, Reactors, GIS etc., attach details) * 3.0 APPLICABLE INDUSTRY STANDARDS * 4.0 DESIGN AND CONSTRUCTION REQUIREMENTS 4.1 General Type Model Designation Location (Indoor/Outdoor) 4.2 * * Performance Characteristics and Ratings Rated Voltage Arrester Class * Dielectric Withstand for Housing Lightning impulse sithstand voltage, with 1.2/50µs waveform (kVpeak) * Power frequency withstand voltage(Wet for outdoor/ Dry for indoor) * 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 10 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 6.0 35-TMSS-01, Rev. 01 DATA SCHEDULE SURGE ARRESTER FROM 11kV THROUGH 380kV NOMINAL REFERENCE SECTION NO. DESCRIPTION Switching impulse withstand voltage With 250/2500µs waveform (for arrester with rated voltage 200kV and above (kVpeak) 'A' 'B' 'C' * Nominal Discharge Current (Lightning Impulse Classyifying Current) with 8/20 µs waveform (kV) * High Current impulse Capability with 4/10µs Waveform (kApeak) * Maximum Lightning Impulse Residual Voltage With 8/20 µs waveform (kVpeak) at a Discharge classifying) current of : - 5kA - 10kA - 20kA - 40kA * * * * Maximum Switching Surge Residual Voltage (kVpeak) at Discharge Current of - 0.5kA - 1kA - 2kA * * * Maximum Steep Current /Front-of-Wave Residual Voltage Based on 1/ 2 or 0.5 µs Waveform as Applicable (kVpeak) - 10kA * - * 20kA Temporary over voltage capability (kVrms) (manufacturer shall submit curve for TOV for the Following duration with and without Prior duty) - 0.1second - 1 second - 10 second 100second * * * * Maximum R.I.V (µv) * 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 11 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 6.0 35-TMSS-01, Rev. 01 DATA SCHEDULE SURGE ARRESTER FROM 11kV THROUGH 380kV NOMINAL REFERENCE SECTION NO. DESCRIPTION 'A' Maximum External Insulation Levels Power Frequency Dry Withstand Voltage (kVrms) * 4.3 Power frequency wet withstand voltage (kVrms) * Lightning impulse withstand voltage (kVpeak) * Switching impulse withstand voltage (kVpeak) * Leakage current through Arrester at MCOV (mA) * Maximum Energy Absorption Capability i) kj/kV of arrester rating ii) kj/kv of MCOV * * Repetitive Charge Transfer rating (Qrs(C)) * Maximum resistive current acceptable * 'B' 'C' Construction Pressure Relief Capability (rms symmetrical) High Current Short duration Low current, long duration (A) 600 Porcelain Housing Color Creepage Distance (mm) Bending Failing Load (kN) Cantilever Strength min (kN) Torsional Strength (kN) Compression Strength (kNm) No. of Stacks in each unit Height (mm) * * * * * * * * 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 12 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 6.0 35-TMSS-01, Rev. 01 DATA SCHEDULE SURGE ARRESTER FROM 11kV THROUGH 380kV NOMINAL REFERENCE SECTION NO. DESCRIPTION Internal Pressure Required to Operate Pressure relief device as a Percent of Pressure required to Burst Porcelain (%) 'A' 'B' 'C' * Mounting arrangement Mode of mounting (self-supporting/bracket Bracket supporting) Bolt circle diameter (mm) No. of holes Size of Bolts (mm) * * * * Accessories Scale range of leakage ammeter(mA) * Diameter of the grading ring if applicable (mm) * Material of grading ring if applicable * Terminals Type Size (mm) Material (Al or CU) Pad * * Grounding Size (mm) Material * * MISCELLANEOUS Minimum clearance between live parts and earth parts (mm) * Minimum Permissible Center to Center Distance between Arresters (mm) * Overall Height of arrester (mm) * Weight of arrester (kg) * 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 13 OF 14 TRANSMISSION MATERIALS STANDARD SPECIFICATION 6.0 35-TMSS-01, Rev. 01 DATA SCHEDULE SURGE ARRESTER FROM 11kV THROUGH 380kV NOMINAL A. ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY NATIONAL GRID,SA: B. ADDITIONAL SUPPLEMENTARY DATA OR BIDDER/VENDOR/SUPPLIER/CONTRACTOR: C. OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/ CONTRACTOR: FEATURES Actual Manufacturer of Equipment/Material PROPOSED BY Vendor/Supplier/ Contractor Name of the Company Location and address Name and Signature of authorized representative and date Official Seal/Stamp of the Company & Date 35TMSS01R01/KSB Date of Approval: December 25, 2016 License=Air Products Middle East Industrial Gases LLC/SA-1111280-t Not For Resale ,2/7/2021 2:17:45 PM Saudi Time PAGE 14 OF 14