CHAPTER 2 Miscellaneous or special loads in commercial buildings may include small or occasional loads that do not fit into the major load groups. A sample partial load calculation can be done for an office building to determine the demand load. Maximum total harmonic content of the power system waveforms should not exceed 5% with the equipment not operating. The demand load of a system is determined by calculating the highest point of the load profile, which represents the maximum demand load of the system. Frequency variation should not be greater than ±0.5 Hz. Line-to-line voltage balance is not usually specified, but 2.5% is a conservative figure. Voltage variations should be limited to +6% and -13%. Accumulated load: The accumulation of demand load for typical groups of loads (e.g., heating, cooling, lighting, etc.). Load profile: The graphic representation of the demand load, usually on an hourly basis, for a particular day. Electric service can be any commercially available voltage with an insulated equipment grounding conductor. Load factor: The ratio of the average load over a designated period of time to the peak load occurring in that period. Larger installations may require 208 Y/120 V or 480 Y/277 V power supply. Gross demand load: The summation of the demands for each of the several group loads. Diversity factor: The ratio of the sum of the individual maximum demands of the subdivisions of the system to the maximum demand of the complete system. Data processing equipment in buildings will have varying power requirements, with smaller installations potentially being adequate with single-phase power at 120V. Transportation systems in buildings, such as elevators, have varying load requirements based on the number and type needed. Demand factor: The ratio of the maximum demand of a system to the total connected load of the system. Fire detection and alarm systems have small magnitudes and can often be disregarded when calculating the building's total load. Interval of time: Generally 15 minutes, 30 minutes, or 60 minutes. Demand: The amount of power or energy required by a system over a specified interval of time, expressed in various units such as kilowatts, kilovoltamperes, kilovars, or amperes. Fire protection systems in buildings typically require a fire pump to maintain system pressure. Allowing for several 2 hp duplex units is a satisfactory allowance for the basement in terms of plumbing and sanitation equipment. Plumbing and sanitation equipment loads in commercial buildings are usually not large, with small sump and sewage pumps being commonly used. Larger heating loads should be connected to power panels to avoid voltage drop on lighting circuits. Some units provide hot water supply, ranging from large electric boilers to small units. Heating loads typically comprise one-third to one-half of the total electrical load in a building, ranging from large heat sources to small supplemental heaters. Electrical engineers should collaborate with mechanical designers to consider the use of large motors or electrical heating loads that could impact the initial load estimate. Small commercial buildings usually have small units with fractional horsepower motors, while larger buildings may have larger fans and pumps ranging from 10-75 hp or more. The electrical load for boiler room and mechanical auxiliary equipment typically does not exceed 5% of the total building load, but may reach up to 10% in schools. In absorption-based air-conditioning systems, the electrical load is reduced. A common practice is to multiply the total tonnage by a factor of 1.6 to 2.0 to estimate the total connected load. Examples of applications that may require shielded enclosures include research laboratories, computer facilities, test and measurement laboratories, and biomedical research and treatment rooms. Compressors typically make up 55% to 70% of the total connected air-conditioning load, with pumps, fans, and other components constituting the rest. Electrical requirements should be obtained from those responsible for system design, as they can vary significantly based on specific needs and technologies employed. Shielded enclosures may be necessary for applications requiring control of electromagnetic energy. Inadequate grounding can lead to electrical shock hazards and noise interference. The power requirements for space conditioning systems depend on factors like climate, building design, interior loads, and specialized equipment. Typically, 1 VA/ft² is sufficient for most commercial buildings, but wiring is often considered. Power required for appliances depends on the type of space usage, and the NEC's Article 220 outlines safe demand factor use for receptacle loads. The NEC provides guidelines, like Article 220, for calculating lighting loads in commercial buildings and determining feeder-circuit panel board sizing. Demand, or demand load, refers to the electrical load at the receiving terminals. Connected load is the sum of the continuous ratings of the powerconsuming apparatus connected to the system or any part thereof. Coincident demand is any demand that occurs simultaneously with any other demand and can also be the sum of any set of coincident demands. Branch-circuit load refers to the load on the portion of a wiring system beyond the final overcurrent device protecting the circuit. Diversity is the term used to describe the effect of total load variation and can be expressed as a diversity factor. Certain loads may be turned off or operated at reduced power levels, reducing the system load. The average load on the power system, known as the demand load, is usually less than the total connected load and may vary depending on the time interval over which the load is averaged. Total Load Considerations: Adding up all connected loads in the building may result in a seemingly larger power system capacity than actually needed to adequately serve the loads. An engineering study of the existing electric power distribution system should be included in the initial planning of the building renovation. When renovating or expanding a building, consideration should be given to the nature and magnitude of the additions to ensure proper grounding and shielding. Computers, communications equipment, and low-level electronic systems require special analysis of the grounding system. The use of electronic equipment in commercial buildings raises concerns about electromagnetic hazards, pollution, and environmental quality. Lighting loads in air-conditioned commercial buildings typically account for 20% - 50% of the total load, with a range of 3 - 6 VA/ft2. Non-coincidence of many loads often invites consideration of diversity or demand factors. Load characteristics such as repetitive starting or cycling of a load from lightly loaded to full load should be taken into consideration. The electric power distribution system in a building exists to serve the loads and electrical utilization devices. CHAPTER 3 Mitigating harmonics is done to reduce their negative impact. Tuned (Resonant) Filters: Designed to target and eliminate specific harmonic frequencies by providing a low-impedance path at the targeted frequencies. Active Filters: Use electronic components to actively inject equal but opposite harmonic currents into the system, canceling out unwanted harmonics. Band-Pass Filters: Allow a specific range or band of frequencies to pass through while attenuating frequencies outside this band. High-Pass Filters: Allow higher-frequency components to pass through while blocking lower-frequency fundamental and harmonics. Low-Pass Filters: Allow low-frequency components to pass through while attenuating higher-frequency harmonics. Common types of harmonic filters include passive filters, active filters, and tuned (resonant) filters. Harmonic filters are electronic devices or systems designed to reduce the presence of unwanted harmonic frequencies in an electrical system. Loads sensitive to voltage and frequency transients should be identified for proper protection. The required reliability and expected continuity of service should be identified. It is important to consider the average usage or load factor, seasonal and time-of-day variations, ratings of largest loads, and associated switching requirements. Switched loads and redistribution techniques can help balance the load and reduce strain on the system. Programmed loads and regenerative systems can help optimize energy usage. High-efficiency motors and motor-speed control can be implemented to reduce energy consumption. Power factor correcting equipment and power factor improvement techniques can help improve the power factor of the total load. Load limiters can be used to reduce the demand and connected load, as well as allow for possible expansion. Harmonic voltages are abnormal electrical patterns that disrupt the standard smooth flow of electricity in a power system. Before discussing rate structure and availability of service, the engineer should develop a load survey to estimate initial and future loads and their electrical characteristics. Harmonics are integral multiples of the fundamental frequency. Variations in single-phase loading cause the currents in the threephase conductors to be different, producing different voltage drops and causing the phase voltages to become unbalanced. Phase voltage unbalance in three-phase systems can be caused by the use of four-wire, grounded-wye distribution systems and the connection of single-phase distribution transformers. Voltage interruptions are sudden and temporary losses of voltage, often caused by faults, equipment failures, or lightning strikes. Electrical noise refers to short-duration, unwanted variations in voltage caused by electromagnetic interference (EMI) or radio frequency interference (RFI) from nearby electrical devices. The design of an electric distribution system should begin with a load survey to identify the size, location, and nature of the various loads. Momentary voltage swells can be caused by the sudden removal of a heavy load or a fault in the power system. Load tabulation is necessary as power systems for different buildings vary due to different load requirements. Voltage swells are short-lived increases in voltage above the nominal level. Voltage sags are short-duration decreases in voltage below the nominal level, often caused by sudden high-current demands or faults in the power distribution system. Minimum service and feeder sizes ensure the safety of electrical systems by preventing undersizing of components. Voltage spikes are sudden, short-lived increases in voltage caused by lightning strikes, power surges, or switching operations. NEC Load Estimate: Calculation based on the National Electrical Code (NEC) requirements. Examples of momentary voltage variations include voltage spikes, voltage sags, and voltage swells. Final Load Estimate: Calculated from ultimate electrical and mechanical drawings, includes motor sizes, permanent appliances, lighting loads, receptacle estimates, and heating equipment loads. Momentary voltage variations can damage or affect the operation of electronic devices, causing data loss, equipment malfunctions, or permanent damage. Early Design Load Estimate: More accurate assessment used to determine necessary services, utility negotiations, and choice of distribution systems and voltages, impacting space requirements for electrical rooms and substations. CHAPTER 4 Each electric utility differs in rate structure, service policies, and requirements, so it is important for the electrical engineer to contact the utility company early in the design phase. Useful information for electrical load requirements can be obtained from meter readings, measurements for similar buildings, electric utility companies, equipment manufacturers and associations, or governmental agencies. Data for load estimation is typically obtained from those involved in designing the building and its integral systems, such as lighting, heating, ventilation, air conditioning, and transportation. Energy codes, enacted by local governments, allocate electric power based on standards like ASHRAE/IES to promote energy conservation and may adjust power allowances based on usage patterns. Preliminary Load Estimate: Based on available data from existing buildings of the same usage and square footage or volume, used for preliminary engineering studies and cost feasibility. The engineer should make provisions for load growth and building expansion to ensure adequate electrical capacity and equipment provision. The power distribution system should provide sufficient reliability, safety, and flexibility to accommodate changing loads and building requirements. Electric utility metering and billing involve various aspects such as metering by type of premises, service voltage characteristics, meter location, and types of metering. Effective communication and collaboration among designers, stakeholders, and project managers are key to navigating these factors. The selection of a power source is determined by design engineers and utility engineers. An electric power supply is a device that converts electric current from a source to the correct voltage, current, and frequency to power an electrical load. Maintenance facilities and cost Communication with the local supplying utility is important to incorporate local requirements in building plans. Removable power circuit breaker with self-coupling disconnecting contacts Utility and project factors should be carefully considered throughout the design process. They absorb all the arc energy using a powder or sand filler around the fusible element. Each electric utility has different rate schedules for supplying power to customers under various conditions. Compliance with IEEE standards for safety and functionality. Class L Fuses (601-6000 A) Transformers in commercial installations are used to change voltage levels from utility distribution voltage to a usable voltage within a building and to reduce building distribution voltage for specific equipment. Applicable standards for transformers are the ANSI C57 Series and NEMA TR and ST Series. Power distribution apparatus includes medium- and high-voltage fuses, metal-enclosed load interrupter switchgear, metal-clad circuit breaker switchgear, low-voltage power switchgear and circuit breakers, metal-enclosed distribution switchboards, primary-unit substations, secondary-unit substations, panelboards, molded-case circuit breakers, low-voltage fuses, service protectors, enclosed switches, bolted pressure switches, high-pressure contact switches, network protectors, lightning and transient protection, load transfer devices, and interlock systems. Substation: Application - Outdoor substations, Ratings - Single-phase units: 750-5,000 kVA, Three-phase units: 750-25,000 kVA, Primary Voltage Range - 2,400 V and up, Taps - Usually manually operated when de-energized, Automatic load tap changing may be available, Secondary Voltage Range - 480-13,800 V, Primary Connection Usually delta connected, Secondary Connection - Usually wye connected (to ease grounding of the secondary neutral), Insulation and Cooling - Usually liquid medium, High-Voltage Connections - On cover-mounted bushings, Low-Voltage Connections - May be covermounted bushings Primary-unit substation, Secondary-unit substation (power center), Network, Pad-mounted, Indoor distribution transformers are also used in commercial buildings. Application: Used with their secondaries connected to mediumvoltage switchgear. Ratings: Three-phase units rated from 1,000 kVA to 10,000 kVA. Primary Voltage Range: 6,900 V to 138,000 V. Secondary Voltage Range: 2,400 V to 34,500 V. Taps: - Usually manually changed while de-energized. - Automatic load tap changing may be available. Primary Connection: Usually delta connected. Transformer Type: May be oil-filled, may use less-flammable liquid as insulation, air insulation may be used, dry-type transformers may be employed, cast-coil transformers may be used, gas-insulated transformers are an option. Primary Connection: Delta connected. Secondary Connection: Wye connected. Transformer Type: The methods and formulas used in these calculations are given in IEEE Std 493 - 1990 (ANSI) and MIL-HDBK-217, Reliability for Electric and Electronic Equipment Handbook. Statistical analysis methods involving the probability of power failure can be used to calculate the failure rate and forced downtime for the power distribution system. To ensure the reliability of a power distribution system, it is necessary to have reliability data on the electric utility supply and each piece of electrical equipment used in the system. Reliability data for electrical equipment is used to calculate the failure rate and forced downtime per year of the power system. This quantitative comparison can be used to make trade-off decisions involving initial cost versus failure rate and forced downtime per year. The standard includes a quantitative comparison of failure rates and forced downtime in hours per year for different circuit arrangements, such as radial, primary-selective, simple spot-network, and secondary-network circuits. It addresses considerations for system design, equipment selection, and operational practices to enhance the reliability and performance of power distribution systems. The standard provides recommendations for designing power systems that deliver reliable and high-quality electrical power to industrial and commercial facilities. IEEE Std 493-1990 provides guidance and recommendations for the design of reliable power systems in industrial and commercial settings, covering aspects such as system planning, equipment selection, system grounding, and protection. Power factor correction helps reduce losses in the distribution system and electricity bills. Power factor correction is achieved by adding capacitors to the electrical network to compensate for the reactive power demand of inductive loads and reduce the burden on the supply. Voltage at any utilization equipment should be within the guaranteed operative range of the equipment. Power Factor Correction: The process of improving the power factor of a system to reduce energy losses and lower costs. Voltage Regulation: The process of controlling the voltage of a system to keep it within a practical range. Remote 400 Hz UPS: A UPS system designed to provide backup power for remote 400 Hz applications. Point-of-Use 400 Hz UPS: A UPS system specifically designed for powering 400 Hz applications at the point of use. Point-of-Use Redundant 400 Hz UPS: A UPS system that provides backup power for 400 Hz applications at the point of use. Remote Redundant 400 Hz UPS: A remote UPS system that provides backup power for 400 Hz applications. - May be oil-filled. Combination UPS for Multiple-Mainframe Computer Site: A UPS system designed to power multiple mainframe computers at different locations. - May use less-flammable liquid as insulation. Alternative Combination UPS for Single Mainframe Computer Site: An alternative UPS configuration for powering multiple mainframe computers at a single site. - Air insulation may be used. CHAPTER 5: Transformers and Power Distribution Apparatus - Cast-coil transformers may be used. Availability and cost of space Initial cost including installation, operational personnel and cost - May be cover bushings. - Dry-type transformers may be employed. - Gas-insulated transformers are an option. High-Voltage Connections: - An air terminal chamber can be used. Delta-Connected Tertiary: Delta-connected tertiary is not acceptable with a three-legged core unless an upstream device opens all three phases for a single-phase fault. - Throat connections are another option. Low-Voltage Connection: Typically a throat connection. Circuit breaker as the main circuit interrupting and protective device Application: Used with their secondaries connected to low-voltage switchgear or switchboards. Transformer Type: The transformer may be oil-filled, use lessflammable liquid as insulation, use air insulation, be dry-type, employ cast-coil technology, or be gas-insulated. Ratings: Three-phase units rated from 112.5 kVA to 2,500 kVA. Primary Voltage Range: 2,400 V to 34,500 V. Pad-mounted transformer: A type of transformer that is mounted on a pad. Taps: Manually changed while de-energized. Secondary Voltage Range: 120 V to 480 V. High-Voltage Connection: Found in an air terminal chamber and can have pressure- or disconnecting-type connectors, or a disconnecting device. Primary Connection: Usually delta-connected. High-Voltage Connection Types: Can be for single or loop feed. Secondary Connection: Usually wye-connected. Low-Voltage Connection: Usually made by cable at the bottom, but can also be made by bus duct. Transformer Type: May be oil-filled, may use less-flammable liquid as insulation, air insulation may be used, dry-type transformers may be employed, cast-coil transformers may be used, gas-insulated transformers are an option. Dry-Type Transformer: Does not have the fire hazards of oil-filled transformers and is often mounted on building roofs for proximity to the load center. High-Voltage Connections: May be cover bushings, an air terminal chamber can be used, throat connections are another option. ANSI C57.12.22-1989 applies to oil-immersed transformers with primary voltages of 16,340 V and below. Low-Voltage Connection: Typically a throat connection. Pad-mounted transformer: Type of transformer, numbered as 5 in the list. Application: Used with secondary-network systems. Ratings: Three-phase units rated from 300 kVA to 2,500 kVA. Application: Used with panelboards and as separately mounted transformers. Primary Voltage Range: 4,160 V to 34,500 V. Ratings: Single-phase units range from 1 kVA to 333 kVA, while threephase units range from 3 kVA to 500 kVA. Taps: Manually operated while de-energized. High-Voltage Connection: Generally a network switch (on-off-ground) or alternatively, an interrupter-type switch with or without a ground position. Primary and Secondary Voltages: Both primaries and secondaries are 600 V and below. Cooling Medium: Air, which can be either ventilated or nonventilated. Smaller units may be encapsulated. High- and Low-Voltage Connections: Utilize pressure-type connections for cables. Secondary Connection: Generally an appropriate network protector or a low-voltage power air circuit breaker designed to provide the functional equivalent of a network protector. ANSI C57.12.40-1990, Requirements for Secondary Network Transformers, Subway and Vault Types (Liquid Immersed) applies to liquid immersed, subway- and vault-type network units. Impedances: Distribution transformers typically have lower impedances compared to substation or secondary-unit substation transformers. A subway-type unit is suitable for frequent or continuous operation while submerged in water; a vault-type unit is suitable for occasional submerged operation. Indoor and Outdoor Distribution Transformers: Available at primary voltages of up to 34,500 V. Application: Used outside buildings where conventional unit substations may not be suitable. Construction: Tamper-resistant construction, eliminating the need for fencing. Feature a basic impulse insulation level (BIL) of 150 kV. For three-phase transformers, a common secondary voltage is 480Y/277V, which is compatible with standard three-phase motors rated at 460V. Primary and Secondary Connections: Made in compartments adjacent to each other but separated by barriers from the transformer and each other. Phase-to-neutral 277V circuits are commonly used to serve fluorescent and high-intensity discharge (HID) lighting. General-Purpose Transformers: Access: Accessible through padlocked hinged doors designed to prevent unauthorized personnel from entering either compartment. Commonly used for distributing power at 480 V in commercial buildings. Ventilation: If ventilating openings are provided, tamper-resistant grills are used. Secondaries are typically rated at 208Y/120 V. Predominantly dry-type transformers. Gauges and Accessories: Located in the low-voltage compartment. Some smaller-sized units may come in encapsulated form. Ratings: Units are rated from 75 kVA to 2,500 kVA. Primary Voltage Range: 2,400 V to 34,500 V. Primarily used for supplying power to 120 V lighting, appliances, and receptacles in commercial buildings. Isolating or Insulating transformers: Taps: Taps are manually changed while the transformer is deenergized. Secondary Voltage Range: The secondary voltage range of the transformer is 120 V to 480 V. Primary Connection: The primary connection of the transformer is usually delta connected or special construction wye connected. Secondary Connection: The secondary connection of the transformer is usually wye connected. Virtually all power transformers used in commercial buildings are of the two-winding type. Autotransformers: One-winding type transformer. Advantages of Two-Winding Transformers: Provide positive isolation between the primary and secondary circuits. Desirable for various reasons, including safety, circuit isolation, reduction of fault levels, coordination, and reduction of electrical interference. Applications include x-ray machines, laboratories, electronic equipment, and special machinery. Health care applications are detailed in IEEE Std 602-1986, IEEE Recommended Practice for Electric Systems in Health Care Facilities (ANSI). Transformer specification: The "kVA" rating of a transformer stands for kilovolt-amperes and represents the apparent power rating of the transformer. Segregate Circuits for Sensitive Loads: Separate heavy variable loads from more sensitive loads and consider using a separate transformer or secondary-unit substation for the sensitive loads. Use Voltage Regulating Supplies for Sensitive Loads: Employ voltage regulating supplies specifically for sensitive loads to maintain consistent voltage levels. Typical impedance values for power transformers are outlined in Table 34 for self-cooled transformer kVA ratings. These typical impedance values have a tolerance of ±7.5% according to IEEE C57.12.00-1987 (ANSI) standards. The kVA rating indicates the maximum amount of power that the transformer can handle without exceeding its designed capacity. Nonstandard impedance values may be specified, resulting in higher costs or specific performance requirements. Transformers are available in various kVA ratings to suit different applications and power distribution needs. Impedance values for small transformers can vary considerably between manufacturers, so it is advisable to consult manufacturers' bulletins for specific values. Table 33 gives the preferred kVA ratings of both single-phase and three-phase transformers according to IEEE C57.12.00-1987, IEEE Standard General Requirements for Liquid Immersed Distribution, Power, and Regulating Transformers (ANSI). Transformers are manufactured with different insulation material systems, categorized into different classes. Performance Data Reference Temperature: Transformers with lower conductor losses and corresponding lower temperature rises are available, which can lead to longer life expectancy and reduced operating costs. Class 105 Insulation System allows for a 55 °C temperature rise above the reference temperature, with a total ultimate temperature limit of 105 °C. Class 120 Insulation System permits a 65 °C temperature rise with a total permissible ultimate temperature of 120 °C. Class 150 Insulation System allows an 80 °C temperature rise. 440Y/254V (Three-Phase, Four-Wire): Features a line-to-line voltage of 440V and a line-to-neutral voltage of 254V, used in larger industrial applications. Class 185 Insulation System permits a 115 °C temperature rise. Class 220 Insulation System allows a 150 °C temperature rise. 380/220V (Three-Phase, Four-Wire): Has a line-to-line voltage of 380V and a line-to-neutral voltage of 220V, commonly used for larger commercial and industrial facilities. The specific materials or combinations of materials included in each insulation material class are specified in IEEE C57.12.00-1987 (ANSI) standards. 480Y/277V (Three-Phase, Four-Wire): Represents a line-to-line voltage of 480V and a line-to-neutral voltage of 277V, commonly used in larger commercial and industrial settings. Transformer sound levels can be an issue in commercial building interiors, particularly in areas where a quieter environment is needed, such as conference rooms and certain office spaces. 240V (Single-Phase): Used in smaller commercial establishments for powering lighting, small appliances, and general electrical loads. Technical specifications may require transformer sound levels to be lower than the levels specified in tables in order to meet specific noise reduction goals. Voltage Taps: Used to change the ratio between high-voltage and lowvoltage windings in transformers. To minimize the effects of transformer sound levels, several measures can be taken, including isolating transformers in separate rooms, avoiding direct attachment, using sound-isolating pads and vibration dampers, and avoiding plenums and stairwells. Smaller transformer sizes typically apply to lower voltages, while larger sizes are for higher voltages. Voltage ratings and ratios should be selected based on available standard equipment as indicated in manufacturers' catalogs. Common Secondary Voltages in Commercial Projects: 208Y/120V, 480Y/277V 220/127V (Three-Phase, Four-Wire): Consists of a line-to-line voltage of 220V and a line-to-neutral voltage of 127V, commonly used in commercial buildings for equipment and lighting. Manual de-energized tap changing is commonly used to adjust for differences between transformer ratio and system's nominal voltage. Taps are classified as underload and no load. Taps on transformers can be adjusted even when the transformer is energized and under load to compensate for significant fluctuations in the supply voltage. For large transformers, flexible connections from the transformer to long busway runs can be provided to reduce the transmission of vibrations and noise. Air from transformer vaults should be directly exhausted outdoors to prevent the accumulation of hazardous gases or smoke in indoor spaces. Preference for Dry-Type Transformers: In situations where fire and smoke considerations are of paramount importance, dry-type transformers are usually preferred over liquid-filled transformers, including less-flammable liquid-insulated types. Transformer Protection: Well-designed transformer protection systems can minimize the extent of damage in the event of a fault or failure, regardless of whether the transformer is dry-type or liquidfilled. Tap changes are more commonly used in outdoor substations with transformers that have a capacity of over 5000 kVA. Load tap changers can be controlled automatically or manually. Automatic control systems are often used to continuously monitor and adjust the taps to maintain a stable output voltage, while manual control can be used for occasional adjustments. Transformer tap changes can only be performed when the transformer is deenergized for safety reasons. Most liquid-filled and sealed-type transformers are equipped with an externally operated tap changer with a lockable handle. Both dry-type and liquid-filled transformers can exhibit failure modes such as burning and generating smoke. In very small liquid-filled transformers and most ventilated-dry-type transformers, tap changes are adjusted by moving internal links accessible through a removable panel on the transformer's enclosure. Dry-type transformers, including cast-coil types, can burn when subjected to faults for an extended period. Liquid-filled transformers can burst, burn, and generate smoke. Request Utility Power Supply Improvement: Ask the utility provider to improve the regulation of the power supply to stabilize voltage levels. In critical areas or locations where transformer failures can have severe consequences, provisions should be made to address rare failure modes. This may include fire suppression systems, ventilation systems, and other safety measures. Voltage and BIL Ratings: Cast-coil transformers are available with primary voltage ratings up to 34.5 kV and BIL ratings up to 200 kV, making them suitable for various voltage levels. Alternative to Liquid or Gas-Filled Transformers: Cast-coil transformers are a good alternative to liquid-filled or gas-filled units, particularly in indoor or rooftop applications where space or environmental considerations are important. The effects of transformer failures are not mentioned in the given text. Harmonic currents generated by nonlinear loads such as computers, variable speed drives, electronic ballasts, HID lighting, arc furnaces, and rapid mode switching devices can impact transformer windings. Specifying %IR, %IX, and %IZ is required when paralleling transformers to address the effects of harmonics. Forced Air Cooling Option: Cast-coil transformers can be forced air cooled to increase their self-cooled ratings by 50%. Recent developments have highlighted transformer failures due to nonlinear loads and the introduction of third and higher harmonics. Totally enclosed, nonventilated-dry-type transformers are constructed similarly to ventilated-dry-type transformers. The enclosure of these transformers contains air, allowing them to have the same BIL capabilities as ventilated-dry-type transformers. They can be installed both indoors and outdoors, making them suitable for areas with a corrosive or dirty atmosphere. These transformers can be equipped with fans for forced air cooling, which increases their capacity by a minimum of 25% and allows them to handle higher loads. Primary circuit parts enclosed by grounded metal barriers Consider specifying special transformers designed to withstand and mitigate the effects of harmonic currents and fluxes for reliable performance in the presence of nonlinear loads. Liquid-filled transformers are a type of transformer construction. Liquid-filled transformers have windings contained in a sealed tank filled with insulating liquid, serving as both insulation and a cooling agent. It is generally advisable to avoid using liquid-filled transformers in commercial buildings unless they use nonflammable or lessflammable liquids and meet specific safety requirements. Transformers require temperature measurement equipment and controls to monitor winding temperatures and ensure safe operation. Temperature measurement equipment is used to determine the temperature of the transformer windings. The insulating liquid provides insulation between winding sections and also acts as a cooling medium, dissipating heat from the windings. Regular maintenance of the insulating liquid is crucial to keep it clean and moisture-free, as moisture can enter through leaks or humidity in the surrounding air. Temperature controls are linked to cooling systems, trip mechanisms, or alarm devices to activate them if the temperature exceeds safe limits. Embedded temperature detectors are commonly installed within each low-voltage winding to prevent the ultimate temperature of the insulating system from being exceeded. Applicable standards for medium- and high-voltage fuses are ANSI C37.46-1981 and NEMA SG2-1986. Distribution fuse cutouts have characteristics such as dielectric withstand strengths, application primarily on distribution feeders and circuits, mechanical construction adapted to pole or cross arm mounting, and operating voltages corresponding to distribution system voltages. A distribution fuse cutout consists of a mounting (insulating support) and a fuse holder. Power fuses are identified by their dielectric withstand strengths, application in various electrical systems, and adaptable mechanical construction. Power fuse components include the mounting structure, fuse holder or end fittings, and the refill unit or fuse unit. The refill unit or fuse unit contains the fuse element that breaks or interrupts the circuit when excessive current flows through it. Blown Fuse Indicators provide a visual signal when a power fuse has operated or "blown," helping to identify faults in the electrical system. Indoor Mountings are specialized configurations of power fuses designed for indoor use in electrical systems, suitable for mediumvoltage applications with a maximum voltage of 29 kV. Early power fuses used fiber lining and had limited interrupting capacity, making them unsuitable for indoor or enclosed use. In the 1930s, solid boric acid power fuses were developed, using densely molded boric acid powder in the interrupting chamber. When the fusible element melts, it generates non-combustible, deionized steam to interrupt the circuit. Periodic testing for dielectric breakdown voltage and neutralization number helps extend the transformer's lifespan. Dry-type transformers use air instead of insulating liquid. Transformers rated for lower temperatures can offer improved efficiency, overload capability, and longer lifespan. IEEE PC57.12.58 provides guidance for conducting transient voltage analysis of dry-type transformer coils to ensure the insulation system can withstand repetitive transients. Ventilated-Dry-Type Transformers have a sheet metal enclosure for mechanical protection and safety. Ventilating louvers allow for thermal air circulation over the windings. Fans can be added to increase the full load rating. They are typically installed indoors and require periodic cleaning and a clean ventilating air supply. They can also be built with special enclosures for outdoor use, matching the BIL (Basic Impulse Level) of liquid-immersed transformers. It is recommended to perform Megger testing before energizing after lengthy shutdowns or periods of exposure to moisture to ensure insulation integrity. Sealed-dry-type transformers are constructed in a manner similar to ventilated-dry-type transformers. The enclosing tank of a sealed-dry-type transformer is sealed and operated under positive pressures, filled with nitrogen or another dielectric gas. Heat generated in the windings of the transformer is transferred to the gas within the sealed housing, conducted to the tank, and dissipated to the surrounding air. Sealed-dry-type transformers can be installed both indoors and outdoors, suitable for areas with a corrosive or dirty atmosphere where a ventilated-dry-type transformer would be impractical. Solid boric acid power fuses have higher interrupting capacity, produce less noise, and require less exhaust gas clearance. They can be used indoors or in enclosures with exhaust control devices for quiet operation. Encapsulated Windings: Cast-coil transformers have both primary and secondary windings encapsulated in reinforced epoxy resin. Solid material boric acid power fuses are widely used in utility, industrial, and commercial power distribution systems. Current-limiting power fuses do not expel gases during operation. Ideal for Harsh Environments: Cast-coil transformers are suitable for applications where moisture or airborne contaminants are a concern due to the excellent protection provided by epoxy resin. Current-limiting fuses provide effective current limitation when the overcurrent greatly exceeds the fuse ampere rating. This reduces stresses and potential damage in the circuit up to the fault point. However, for lower overcurrent values, they may not achieve current limitation. Current-limiting fuses can be safely used indoors or in enclosures and require standard electrical clearances. They are commonly used for the protection of transformers and in high-voltage motor starters. Electronic power fuses are a recent technological development. They combine features and benefits of fuses and relays. Electronic power fuses offer coordination and ratings that other power fuses cannot achieve. They consist of two main components: an electronic control module and an interrupting module. The electronic control module defines time-current characteristics and provides the energy for tripping. This allows for various tripping options, including instantaneous or time-delayed tripping. Only the interrupting module needs replacement after fuse operation. Fuses are used for various applications. Metal-enclosed interrupter switchgear is used for switching and overcurrent protection in medium-voltage applications. It uses interrupter switches and power fuses for protection and control. Interrupter switches are air switches equipped with interrupters to make or break specified currents. Interrupter switchgear can also provide ground-fault protection for resistance-grounded systems. Rated maximum voltages range from 4.8 kV to 38.0 kV with various main bus ratings. Interrupting ratings are determined by the power fuses, which are available in a wide range of current ratings and time-current characteristics. Interrupter switches can be manually or automatically operated and are available with vacuum or SF6 gas interrupting mediums. SF6 interrupter switches cover all medium-voltage ranges, while vacuum switches are available up to 35 kV. Interrupter switches can be used in combination with power fuses to achieve higher ratings than when used alone. Metal-enclosed interrupter switchgear is available in the range of 534.5 kV. High-Voltage, Fiber Lined Power Fuses: Primarily used in outdoor applications at sub-transmission voltage levels. Automatic control devices can be integrated into metal-enclosed interrupter switchgear with motor-powered switch operators. High-Voltage, Solid Material, Boric Acid Fuses: Available in two styles: end fitting and fuse unit style, and fuse-holder and refill unit style. End fitting and fuse unit style used outdoors at various voltage levels, including sub-transmission and distribution, and indoors in metalenclosed interrupter switchgear, vaults, and pad-mounted switchgear. Fuse-holder and refill unit style suitable for medium- and highvoltage distributions, both indoors and outdoors. These devices enable automatic source transfer in case of faults or outages, enhancing service continuity in primary-selective systems. Optional features include manual or automatic back transfer, time delay on transfer, and lockout on faults. Switch operators can be disconnected from switches for testing without interrupting power to the load. Metal-enclosed interrupter switchgear is available in 5-34.5 kV. Metal-enclosed interrupter switchgear may include instrument transformers, voltage and current sensors, meters, and other auxiliary devices. Motor-powered switch operators allow remote operation of the interrupter switches. Blown fuse indicators are provided for visual checking of fuses while in their mountings. Metal-enclosed interrupter switchgear should comply with relevant standards and codes, such as the NEC (National Electrical Code) Article 710-21(e). Interrupter switches should safely withstand the effects of closing, carrying, or interrupting all possible currents up to the assigned maximum short-circuit rating. Voltage ratings: 4.16–34.5 kV Interrupting ratings: 8.8 kA at 4.16 kV to 40 kA at 34.5 kV Continuous current ratings: 1200 A, 2000 A, 3000 A, 3750 A Current-Limiting Power Fuses: Used for protecting auxiliary power transformers, small power transformers, and capacitor banks. Also available for medium-voltage transformers with high interrupting ratings. Some are designed specifically for high-voltage motors. Electronic Power Fuses are suitable for service entrance protection and coordination of commercial distribution circuits. Circuit instruments, relays, and control switches mounted on a control panel They have high current-carrying capability and unique time-current characteristics for coordination with overcurrent relays and load-side feeder fuses. Electronic Power Fuses are ideal for load feeder protection due to their high continuous and interrupting ratings. Power fuses are used as primary-side overcurrent protective devices for transformer banks. Power fuses are suitable for transformer banks rated up to 161 kV with a maximum rating of 15,000 kVA. Power fuses have high short-circuit interrupting capability and fast operation to clear faults at the transformer. Power fuses serve as backup protection in case of secondary overcurrent protective device malfunctions. Potential transformers and control power transformer fuses in drawout assemblies Power fuses are used to protect instrument transformers and capacitor banks in addition to main power transformers. Automatic shutters to shield stationary primary contacts Interlocking features for proper operation sequence Overcurrent protective devices at primary voltages have several key functions, including interrupting high overcurrents, acting as backup protection, opening circuits during overcurrent conditions, and coordinating with upstream and downstream protective devices. Draw out feature for easy inspection and maintenance Separable main and secondary disconnect contacts for connected, test, and disconnect positions Insulation is potential tracking-resistant and flame-retardant Types of medium-voltage power circuit breakers include minimumoil, air-type, SF6-type, and vacuum-type. Vacuum and SF6-type breakers are common through 15 kV. Modern medium-voltage power fuses are suitable for providing protection and coordination in various types and sizes of distribution systems. Switches can be applied outdoors in vaults or within metal-enclosed interrupter switchgear. Vacuum-type and SF6-type breakers offer advantages in reducing transient voltage surge effects. Metal-enclosed distribution switchboards are commonly used in commercial buildings for distribution at 600 V and below. Considerations for transient over voltages caused by high-speed circuit interruption. They serve as service entrance, power, or lighting distribution equipment. Vacuum-type and SF6-type breakers offer advantages in reducing transient voltage surge effects. They can be used as the secondary sections of unit substations. Metal-clad circuit breaker switchgear operates at voltages ranging from 5-34.5 kV. They are available in a wide range of protective devices and single- or multiple-section assemblies. Metal-enclosed, low-voltage power switchgear and circuit breakers operate at 600 V. Service capacities typically range from 40 A to 4000 A, with smaller service capacities recommended over 4000 A equipment. Air-type circuit breakers are used for low-voltage circuit protection and control. Compliance with NEMA PB2-1989 (Deadfront Distribution Switchboards) is required. Drawout switchgear offers flexibility and complex control circuitry. Ground-fault protection is recommended for grounded wye systems and required for services over 150 V to ground with a disconnecting mean rated 1000 A or more. Used in multiple-bus arrangements for redundancy. Available in indoor and outdoor construction. Automatic transfer switches for main and emergency sources are provided as complete packages with power and control features built into the assembly. Compliance with ANSI and IEEE standards. Air-type circuit breakers are housed in compartments that are isolated from each other and the bus area. Various ANSI sizes are available for circuit breakers, such as 225 A, 600 A, 1600 A, etc. Components of metal-enclosed distribution switchboards include service protectors, molded-case circuit breakers, fusible switches, motor starters, low-voltage ac power circuit breakers, bolted pressure and high-pressure switches, transfer devices or switches, and instrumentation, metering, and relaying equipment. Circuit breakers can be electrically or manually operated and may have additional devices like shunt trip and undervoltage. There are separable main and secondary disconnect contacts for different positions. Construction features of metal-enclosed distribution switchboards include front accessibility, installation against a wall, all connections made from the front, multiple-section switchboards with lined-up backs, enclosure on all sides except the bottom, maximum rating of 2000 A, no drawout low-voltage ac power circuit breakers as branch devices, and no availability of load-side risers. Compartments are provided for meters, relays, instruments, etc. Potential and control power transformers are front accessible. The rear section is dedicated to the main bus, feeder terminations, wiring, and terminal blocks. Rear Accessible — Front Connected: Designed to be free-standing, with rear accessibility for main connections and maintenance, and front accessibility for line and load connections for branch devices. Cross bus is located behind the branch devices and is accessible only from the rear. Multiple-section switchboards have fronts lined up and are capable of accepting all components. The bus work can be made of aluminum or copper, and the circuit breaker terminals are rear-accessible. Some switch designs may include integral ground-fault sensing capabilities. Control wiring is extended to terminal blocks for remote control and intercompartment wiring. The power switchgear and circuit breakers are metal-enclosed and operate at low voltage (600 V). Rear Accessible — Rear Connected: Designed to be free-standing, with rear accessibility for main connections and maintenance. All line and load connections for branch devices are made from the rear, and all cross bus and line and load connections for branch devices are accessible only from the rear. Multiple-section switchboards have fronts lined up and are capable of accepting all components. Long-life, quick-make and quick-break switching devices with overload and instantaneous trip units. Primary-unit substations transform power from high or medium voltages to a voltage above 1000 V. They provide protection and control for lower voltage feeder circuits. These substations are commonly used in commercial buildings to convert medium-voltage services to lower voltages, especially for powering large motors. Primary-unit substations are typically combinations of transformers and metal-enclosed interrupter switchgear or power circuit breaker switchgear. Short-time rating allows selective systems. Open construction for easy maintenance and replacement. Suitable for switchgear compartments or enclosures with deadfront construction. Field-adjustable tripping units, interchangeability within frame sizes. Static-type tripping units available for added selectivity. Can be used with integral current-limiting fuses for higher interrupting capacity. They can be configured for indoor or outdoor use and are adaptable to various power distribution circuit arrangements. Selection of Circuit Breaker Tripping Characteristics: Service continuity depends on coordination between circuit breaker tripping characteristics. Secondary-unit substations transform power from the 2300-35,000 V range down to 600 V or lower. They provide protection and control for low-voltage feeder circuits. Design goal is a fully selective system. Main circuit breakers equipped with long- and short-time delay trip devices. Secondary-unit substations are composed of three major sections available in various forms for indoor and outdoor applications. Feeder circuit breakers equipped with long-time delay and instantaneous functions, or both if required. There are four commonly used basic circuit configurations: simple radial system, secondary-selective system, primary-selective system, and secondary-network system. Selective system ensures only the circuit breaker nearest the fault trips, maintaining service continuity. This section is designed for use with simple radial, secondaryselective, or secondary-network systems. Metal-enclosed, low-voltage 600 v power switchgear and circuit breakers. It typically includes one fuse and a two-position (open-close) 5 kV or 15 kV interrupter switch. Dual-element time delay fuses provide protection for both motors and circuits and open the circuit on long continued overcurrent. Current Rating: The maximum current in amperes that a fuse can carry continuously without exceeding specified temperature rise limits. This setup enables one primary supply to serve the entire load in case the other is unavailable. Voltage Rating: The maximum voltage, whether AC or DC, at which the fuse is designed to operate. Transfer can be performed manually or automatically, with electrical or mechanical interlocks used to prevent inadvertent connections between the two sources. Interrupting Rating: The maximum short-circuit current at rated voltage that the fuse can safely interrupt. The transformer section is responsible for transforming incoming power from the higher primary voltage to the lower secondary voltage. Fuses should carry 110% of their rating continuously without exceeding specified temperature limits. Fuses should open within specified time frames when carrying 135% to 150% of their rating in a test circuit. Different current and voltage ratings of fuses should have specified physical dimensions to prevent interchangeability. Interrupter switches or air-filled terminal chambers may also serve the application. In primary-selective systems, two interrupter switches may serve a common bus or two buses with an interrupter tie switch. The transformer is mechanically and electrically coordinated with both the incoming line (primary) section and the low-voltage switchgear section. The low-voltage switchgear section offers protection and control for low-voltage feeder circuits. Fuses listed as having interrupting ratings above 10,000 A should display their interrupting rating on the fuse label. It can be composed of various components, such as a drawout circuit breaker switchgear assembly, a metal-enclosed distribution switchboard, a panelboard mounted in or on the transformer section, or a single secondary protective device. Class H Fuses (0-600 A) Class J Fuses (0-600 A) Class K Fuses (0-600 A) - Class K1 and K5 Class R Fuses (0-600 A) Most manufacturers use aluminum bus work as the standard, but copper is also available at an additional cost. Panelboards are classified into two main categories: lighting and appliance panels, and power distribution panels. Supplementary Fuses (Special characteristics for supplementary overcurrent protection) Lighting and appliance panels are used to distribute electrical power to lighting fixtures and various appliances in commercial buildings. Cable limiters are used in multiple-cable circuits to provide shortcircuit protection for cables. Power distribution panels are used to distribute electrical power to larger loads such as machinery, equipment, and HVAC systems. They are rated based on cable Panelboards for power distribution are designed to handle higher electrical currents and are equipped with circuit breaker devices or fuses capable of managing larger loads. Cable limiters are devices that limit the extent of a fault in a cable system while preserving service to the rest of the system. Cable limiters do not provide overload protection. Motor starter units may also be mounted on panelboards to control and protect electric motors. Low-voltage fuses are used for overload protection in low-voltage systems. NEMA PB11990 (Panelboards) is a relevant standard for panelboards that provides specifications and requirements for their design, construction, and safety. Low-voltage fuses have high interrupting ratings. A service protector is a non-automatic circuit-breaker-type switching and protective device. It includes an integral current-limiting fuse and can be operated manually or electrically. Service protectors are designed to handle currents up to at least 12 times their continuous current ratings. They are capable of closing and latching against fault currents of up to 200,000 A symmetrical rms. ANSI/UL 67-1988 (Panelboards) is another relevant standard for panelboards that ensures they meet industry standards and safety regulations. Thermal Magnetic MCCBs offer inverse time-delayed tripping for overloads and provide instantaneous tripping through coils or magnet and armature designs. Magnetic Only MCCBs are primarily used for instantaneous tripping in specific applications such as welding or motor circuits. Integrally Fused MCCBs incorporate current-limiting fuses within the molded case, ensuring safe operation in systems with high shortcircuit current ratings. Service protectors are capable of withstanding the stresses created by the let-through current of the fuses during fault interruption. Current Limiting MCCBs effectively reduce let-through current and energy (I²t) using electromagnetic principles and are suitable for systems with high fault currents. Service protectors are suitable for switching and protection under various conditions, including normal load, overload, and fault switching up to their maximum interrupting capacity. They provide protection against single-phasing, a condition where one of the three phases in a three-phase system is affected. Service protectors are mechanisms or tools that are used to ensure the uninterrupted functioning and availability of a service. High Interrupting Capacity MCCBs are designed for applications in systems with high fault currents and use strong, high-temperature materials. Molded-Case Circuit Breakers can be used in individual enclosures, panelboards and distribution switchboards, switchgear, combination starters and motor control centers, and automatic transfer switches. They are designed to detect and mitigate potential threats or disruptions to the service, such as cyber attacks, hardware failures, or natural disasters. Types of fuses include non-time delay fuses, time delay fuses, and dual-element time delay fuses. Service protectors may include features such as redundancy, backup systems, failover mechanisms, and monitoring systems. Non-time delay fuses are used in circuits other than motor circuits or in combination with circuit breakers. Electrical trip switches have a contact interrupting rating of 12 times their continuous rating. Time delay fuses have intentional built-in time delays and are commonly used for motor overcurrent protection. Their primary goal is to maintain the reliability, performance, and security of the service, even in the face of unexpected events or challenges. Service protectors are available in various continuous current ratings, including 800 A, 1200 A, 1600 A, 2000 A, 3000 A, 4000 A, 5000 A, and 6000 A. They are designed for use on both 240 Vac and 480 Vac systems. Service protectors come in two- and three-pole construction. They can be installed in wall-mounted and free-standing compartments, as well as switchboards. Service protectors are often used in conjunction with ground-fault protective equipment. Their circuit breaker-type construction allows for rapid fault clearing in the event of a ground fault, typically achieving a total fault clearing time of under 3 Hz after shunt tripping by the ground-fault detector. Ground Fault: Switches used as disconnects in conjunction with ground-fault detectors should be carefully coordinated with fuses to ensure proper operation and protection. Bolted Pressure Switches consist of movable blades and stationary contacts with arcing contacts, featuring a simple toggle mechanism and a spring for quick-make and quick-break switching action. High-Pressure Contact Switches employ an over-center toggle mechanism with high-energy springs, allowing for higher acceleration when parting or closing contacts and resulting in a higher interrupting capability. Electrical trip mechanisms can be added to bolted pressure switches and high-pressure contact switches for automatic electrical opening. Electrical trip switches are designed for remote tripping or for use with ground-fault protection equipment. Electrical trip switches can trip at 55% of normal voltage and have an opening time of approximately 6 Hz. Both manually operated and electrical trip switches are designed for use with Class L current-limiting fuses. IEEE C37.29-1981 (Reaff. 1985), IEEE Standard for Low-Voltage AC Power Circuit Protectors Used in Enclosures (ANSI), is the applicable standard for service protectors. Enclosed switches are switches that may or may not have fuse holders. They are completely enclosed in a metal enclosure. Trip switches are available in various current ratings, including 800 A, 1200 A, 1600 A, 2000 A, 2500 A, 3000 A, 4000 A, and 6000 A. Enclosed switches are designed to be operable without opening the enclosure. Trip switches are rated for 600 Vac and can carry 100% of their rating. They typically have provisions for padlocking in the off position. Trip switches are suitable for use on circuits with available fault currents of up to 200,000 A symmetrical rms. Detailed requirements and standards for enclosed switches can be found in NEMA KS1-1990 (Enclosed Switches) and ANSI/UL 98-1986 (Enclosed and Dead-Front Switches). Trip switches can be mounted in switchboards or housed in individual wall-mounted and free-standing enclosures. Bolted pressure switches and high-pressure contact switches are subject to standards such as ANSI/UL 977-1984 (Fused Power-Circuit Devices) and CSA Std C22.2-1980 (Canadian Electrical Code, Part 2: Safety Standards for Electrical Equipment, Electrical Signs). Manufacturers' catalogs should be consulted for a complete range of equipment features and specific application information. General-Duty switches can interrupt up to 600% of full load current 50 times at rated voltage and can achieve interrupting ratings up to 200,000 A when used with specific fuse types. These switches play a critical role in electrical distribution systems, providing reliable switching and protection capabilities, especially in applications where high interrupting capabilities are required. Heavy-Duty (Type HD) switches are available in ratings from 30 to 1200 A and are intended for systems not exceeding 600 Vac (and possibly 600 Vdc). Network protectors prevent backfeeding from the collector bus to the transformer or primary feeder during fault conditions or when restoring power to a feeder. Heavy-Duty switches accommodate Class H, J, L, or R fuses and approved kits are available to convert them for use with different fuse types. Network protectors do not provide forward overcurrent protection, but rely on fuses to open slowly under heavy short-circuit currents, allowing faults in network cables to self-clear and downstream overcurrent devices to operate. Cable limiters are used in modern network protection systems to isolate cable faults. Network protectors have fuses that are primarily used to remove a protector and transformer from the secondary bus in case of relay or protector trip mechanism malfunctions. Network protectors incorporate two plug-in relays: the master relay and the phasing relay. The relays trip the protector circuit breaker if power flows from the collector to a transformer and reclose the circuit breaker when the transformer secondary voltage is slightly above and leading the collector bus voltage. Relay settings involve complex considerations, including a 360° vector diagram for power direction and magnitude settings to account for voltage differences. General-Duty (Type GD) switches are rated from 30 to 600 A and are intended for light-duty applications where typical load conditions are present. General-Duty switches are designed for use in systems not exceeding 240 Vac and are compatible with Class H fuses. Heavy-Duty switches have interrupting requirements based on their equivalent horsepower (hp) ratings and should be able to interrupt 400% of full load current 50 times at rated voltage for switches approved for use with DC motors. UL categorizes switches into three categories: general use without an hp rating, general use with an hp rating, and fuse motor circuit type. UL specifies interrupting requirements for switches, such as operating 50 times at 150% of nominal current for general-use switches. Horsepower-rated switches have requirements similar to NEMA for ratings above 100 hp. Ratings less than 100 hp should interrupt load currents 50 times at approximately 160% of nominal current. Current Rating: Select switches with a current rating of at least 125% of the expected continuous load current. Frequency: Most AC-rated switches are approved for 60 Hz systems only unless otherwise specified. Network protectors are withdrawable and may require special safety precautions when removed from an energized circuit. Temperature: NEMA and UL specify temperature limits, with a maximum temperature rise of 30°C (86°F) throughout the conductor path when operated without fuses and carrying rated current. Some ratings of network protectors may require internal disconnection by maintenance personnel for withdrawal. Fused Switches: Enclosed switches with fuses are tested for their capability to withstand let-through currents of the fuses or interrupt currents that don't cause instantaneous fuse melting. Network protectors can be equipped with external controls to trip and lockout in response to various types of relaying, including overcurrent, ground, or heat sensing relays. Desensitizing relays may be used with network protectors to prevent nuisance tripping, especially in scenarios involving regenerative loads. Network protectors are available in various ratings and voltage levels, including 125 V, 240 V, 480 V, or 575 V. Maximum current ratings for network protectors can reach up to 5000 A. Network protectors come in different enclosure types, such as dustproof, dust-tight, dripproof, and submersible enclosures, allowing for flexible placement within buildings. Conventional network systems are optimally fed from "balanced feeders" that are physically identical and dedicated to network service. Using undedicated feeders requires special design considerations. Network protectors have limited overload capacity compared to the transformers they are associated with, which typically have heavy overload capabilities. Protectors are usually rated with higher current capacities than the transformer's full-load rating. The choice of loads to be transferred depends on the importance of the equipment and the allowable duration and frequency of interruptions. The reliability requirements for critical loads are classified into three levels: Level 1, Level 2, and Level 3. Examples of Level 2 critical loads include transportation systems and critical controls for heating, ventilating, and cooling. Examples of Level 3 critical loads include computer data processing systems and manufacturing processes. The choice of load transfer devices should be based on the required reliability classification of the utilization equipment. Consideration should be given to motor loads, ensuring that the transfer device and standby power source can handle the load's characteristics. Load transfer devices should have the capability to make and break load current, carry rated current continuously when closed, withstand fault currents, and interrupt full load currents as per applicable standards. Overhead power lines have higher insulation levels compared to terminal apparatus like transformers, switchgear, and potheads. Overhead lines are susceptible to overvoltages caused by lightning strikes and switching surges, which can vary in magnitude. Accessibility and ease of inspection of contact elements are important factors. Traveling voltage waves tend to increase in voltage when they reach equipment with a surge impedance higher than that of the incoming line. Automatic or manual transfer switches (up to 4000 A in low-voltage and 1200 A in medium-voltage class). Incoming waves can approximately double in magnitude at the terminals of transformers or open circuit breakers, leading to overvoltage risks. Automatic power circuit breakers (600–3000 A, low- and mediumvoltage). Manually or electrically operated bolted pressure switches (600 V, 800–6000 A). Examples of Level 1 critical loads include health care facilities, egress lighting, fire detection, and military systems. Static transfer switches for special applications, such as UPS systems. Automatic transfer switches are used primarily for emergency and standby power generation systems. They should be mechanically held and electrically operated to meet code and standard requirements for reliability. Special consideration should be given to their ability to handle high inrush currents, carry full rated current, withstand fault currents, and interrupt full load currents. Outdoor substation installations often employ grounded masts or overhead ground wires to intercept lightning strokes and protect power lines and equipment. Surge arresters and capacitors are used to limit overvoltages and attenuate excess energy during transients caused by events like lightning strikes, heavy current switching, and system faults. Surge capacitors act as a short circuit to high-frequency transients. Gapless-metal-oxide surge protectors are commonly used for high transient overvoltages. Circuit breakers may or may not require an energy source like an electric storage battery for operation. Equipment like solid-state electronic equipment, motors, and drytype transformers are susceptible to overvoltages and may require protection. Magnetically operated transfer switches and solenoid-operated circuit breakers are rapid in operation. Motor-operated circuit breakers are slower. Surge arresters come in three types: station, intermediate, and distribution, with varying abilities to handle surge energy. These devices operate rapidly (typically less than 0.5 seconds) and require special consideration for motor loads. Selection of arrester protection depends on factors like insulation levels, arrester characteristics, exposure to lightning, and surges. Measures may be needed to prevent phase differentials in motor loads upon transfer. Accessories like time delays, in-phase monitors, and controls to disconnect and reconnect motors may be used. Additional accessories include time delays, test switches, auxiliary contacts, remote annunciators, lockout relays, and switching neutral contacts as needed. Bypass isolation switches allow the isolation of the transfer switch for maintenance. Transfer devices can be unidirectional or bidirectional with manual reset from emergency to normal positions. Time delays and controls ensure proper timing of transfer operations. Consideration should be given to the interruption of equipment during a transfer operation and the need for automatic or manual restart. Switching of the neutral conductor may be necessary to properly ground the service source and alternate sources and simplify groundfault sensing. Positive Mechanical Interlocks involve physical connections or mechanisms that prevent the simultaneous operation of two devices. Electronic systems, including computers and communication systems, are sensitive to EMI from power supplies, interconnecting cables, and radiated electric and magnetic fields. Strategies for reducing EMI include specifying equipment with controlled emission levels, using filtering and noise suppression techniques, and employing optoelectronic isolation and fiber optics for sensitive circuits. Techniques for control and communication wiring include metallic conduit, shielding, twisted pairs, and effective grounding. Equipment like isolation transformers, motor-generator sets, power conditioners, and uninterruptible power supplies (UPS) can help mitigate the effects of poor-quality power, including transients, harmonics, dips, and voltage regulation issues. Various standards and guides, such as NEMA LA1-1986, IEEE C62.11989, IEEE C62.2-1987, and IEEE Std 518-1982, provide guidance on surge protection, noise reduction, and minimizing electrical noise inputs to controllers. Load transfer devices are essential to ensure continuity of power for critical loads in commercial buildings. Key Interlocks use keys to enforce staged or controlled operations of equipment or access control. Examples of Key Interlock Applications include preventing the simultaneous closing of two feeds in a double-ended substation, preventing the opening of a screen or door in front of a mediumvoltage fuse unless the associated interrupter switch is open, and preventing the closing of a feeder service. Key interlock assemblies can be designed to require the insertion and removal of several keys into a multiple-lock assembly block before any action can be taken, ensuring multiple conditions or steps are met before a specific operation is allowed. Proper control and management of keys are essential in key interlock systems to maintain safety and prevent unauthorized access or operations. Duplicate keys in the hands of operators pose a safety hazard and should be avoided. Nominal Ratings: All power equipment is assigned nominal ratings for voltage, current, phases, and frequency, representing the conditions at which the equipment is designed to operate. Ambient Conditions: The conditions of application, such as ambient temperature and altitude, can affect equipment ratings, and manufacturers' data and standards provide information about these limits and any necessary de-rating or uprating considerations. De-Rating: De-rating is the practice of reducing equipment's nominal rating to account for non-standard conditions, with the NEC and other standards specifying de-rating values for certain equipment types when operated under conditions other than normal. Full voltage starting is common for applications like ventilating fans or small pumps. Larger motors may cause voltage dips, affecting the lighting system. Electric utilities have restrictions on starting currents to limit voltage fluctuations. It is essential to check starting limitations with the utility and consider using reduced voltage starters before applying large motors. Time settings for overload relay should be longer than part-winding starters. Motors are primarily associated with controllers and are used in heating, ventilating, air conditioning, refrigeration, pumping, elevators, and conveyors. Standardized ratings for medium-voltage starters range from 25007200 V, and for fused Class E2 controllers range from 160-570 MVA. Controllers can be operated manually or automatically. Part-winding starters reduce inrush current and torque by 65% and 42% respectively by connecting part of the winding to supply lines and balancing, typically with two equal windings. Part-winding starters have a starting time of 2-4 seconds and require branch-circuit protection at 200% of each winding current. They are suitable for light loads such as high-speed fans or compressors. Resistor or reactor starters are the most basic reduced voltage starting method, using a primary reactor or resistor to reduce voltage across motor terminals and inrush current. After a predetermined acceleration period, a timer closes a second contactor to short the primary resistor and connect the motor to full line voltage, ensuring a smooth transition from starting to running. The impressed voltage on a motor is influenced by its speed. The starting torque of a motor is determined by the square of the applied voltage. Resistor- and reactor-type reduced voltage starters offer closed transitions for standard motors, with resistors typically selected for 5 seconds on and 75 seconds off. Resistor-type starters have better torque speed characteristics but are less expensive and are used more frequently. Resistor-type starters are difficult to adjust and are typically used for larger medium voltage motors. Fault-Make Rating: The ability of equipment to safely close on a fault. Short-Time Rating: The ability of equipment to withstand overcurrent for a limited time. Interrupting Rating: The ability of equipment to clear fault currents safely. Open vs. Enclosed Ratings: Equipment ratings may differ based on whether the equipment is installed in enclosures or used in the open. Temperature Considerations: Equipment terminals, particularly in low-voltage applications, may have temperature ratings that need to be considered when connecting cables. Power, distribution, and general-purpose transformers can withstand short-term overloads that are twice their normal rating. Circuit breakers and fuses are typically limited to smaller overloads, such as 10%. Medium-voltage equipment requires insulation coordination to ensure proper surge protection and system protection under surge conditions. Autotransformer starters are more efficient than resistor reactor starters due to their ability to reduce voltage by transformation. Insulation coordination involves studying BIL (Basic Impulse Insulation Level) ratings and applying surge protection measures as needed. The starting torque of a motor is directly proportional to line current, as the magnetizing current of the autotransformers usually does not exceed 25% of the full-load motor current. Autotransformer starters have taps for 65% and 80% voltage for motors up to 50 hp and 50%, 65%, and 80% voltage for larger motors. CHAPTER 6: Motor Controllers and Starting Methods The torque remains constant until the transfer from starting to running voltage in autotransformer starters. In closed transition, contactor 2S is smaller. An overload relay is included in wye-delta starters, set at 58% of the full-load motor current. The "Korndorfer connection" is commonly used with autotransformer starters to overcome the issue of constant torque during voltage transfer. Controllers are crucial in commercial buildings and are used to control heating, lighting, ventilation, air conditioning, elevators, and more. Wye-delta starters carry 58% of the motor load, with contactors 1M and 2M carrying 33.3%. Wye-delta starters have a higher NEMA rating than full voltage starters. The National Electrical Manufacturers Association (NEMA) publishes standardized ratings for controllers, ranging from 2 hp to 1600 hp. Open transition starters, especially for autotransformer starters, require careful selection of branch-circuit protection. Wye-delta starters are commonly used in Europe and the US for large air-conditioning units. Most integral horsepower motors in commercial buildings are squirrel-cage designs and powered by three-phase, AC, low-voltage distribution systems. A motor controller is a device that starts, stops, and protects a motor connected to it. Series-parallel starters connect two windings in series, allowing maximum impedance, inrush current, and torque. It uses a magnetically operated contactor to connect the motor to the power source. Solid-state starters provide a smooth, stepless method of acceleration for standard squirrel-cage motors. Each device should be tested and approved separately, except for fusible switches with 5000 A or less short-circuit current for size 1 and 2 starters. Combination starters consist of a disconnect device, pilot device, starter, and control transformer, all mounted on a wall or machine. They must be approved for short-circuit current and can withstand up to 100 kA at 480 V. Modular combination starters with multiple width and length dimensions are used in simplified control centers, placed in front of a steel structure and wired to a bus system. Motor branch circuit protection is divided into running overload and short-circuit protection. Complex panels, placed in large enclosures, have group protection and are used for controlling large machines or production lines. Running overloads are up to locked-rotor current, usually six times or eight to ten times the full-load motor current. Motor control centers are essential for central control of multiple motors and consist of basic vertical structures with a vertical and horizontal bus system. NEMA Standards have recommended three overload relays for running overload protection since 1972. Vertical sections of motor control centers have prefabricated units that can be plugged into the bus structure. The total width of each vertical section is not standardized, but most manufacturers use a basic width of 20 inches. Three methods of acceleration available for solid-state starters are constant current acceleration, current ramp acceleration, and linear timed acceleration. A tachometer feedback circuit is needed for acceleration. A solid-state control circuit manages silicon controlled rectifiers. Contactors provide isolation between the motor and load. Solid-state starters are suitable for fast or large operations and are used for speed control of AC and DC motors. Overload relays are divided into three classes: Class 30, 20, and 10. Class 20 overload relays are used for T-frame motors, while Class 30 is used for older U-frame motors. Leveling channels may be installed to ensure proper alignment. Ambient compensated and non-compensated overload relays are available for various applications. When selecting motor control centers, it's important to consider the placement of incoming and outgoing conduits. IEC-type overload relays provide single-phase protection for threephase motors without one phase. Conduits can be run horizontally on a ceiling or elevated structure, elbowed or bent downwards to enter the top of the centers. Removable top plates are typically provided for convenient conduit entrances. Short-circuit protection for the total motor branch circuit is provided by short-circuit protective devices (SCPD), which can be a fuse or circuit breaker. Protection of starters should also be considered as required by ANSI/NFPA 70-1990, National Electrical Code (NEC). In some cases, conduits may be run horizontally into an upper section of the centers, requiring a box-like metal structure. Inherent motor protection is obtained with thermistors, which change resistance at the switching point and de-energize the motor contactor. In some cases, conduits may be embedded in floors, necessitating a waterproofed trench below the centers. Undervoltage protection allows motors to restart when normal voltage is restored, while time delay undervoltage protection prevents motors from being disconnected. Metering, such as voltmeters, ammeters, kilowatt meters, power factor meters, and running time meters, should be installed in motor control centers. Solid-state overload relays have been developed for special motor branch circuit protection applications, combining current sensing, transformation, rectifying, and feeding to an analog unit or microprocessor. There are no current standards for the number or types of meters in motor control centers. Identification labels should be provided for each motor starter, devices, and compartments in motor control centers. Additional floor space should be allocated for anticipated growth or maintenance in motor control centers. These devices can react to motor overload, phase loss, phase reversal, mechanical jam, ground fault, current unbalance, voltage unbalance, low-voltage conditions, and more. Interlocking devices on compressors, vanes, dampers, and valves can ensure the motor doesn't start if the load exceeds the available torque. Frequent product redesign can render equipment obsolete, affecting equipment availability in motor control centers. Elaborate interlocking between motor controllers can ensure proper sequencing in conveying systems. Spare parts, such as starters and circuit breakers, should be provided for periodic replacement. Mechanically held contactors can perform additional functions like motor feeder disconnect and controlling loads. Spare fuses should be included for protective devices. Combinations of switches, relays, and contactors can alternate the operation of multiple-pump motors to equalize running time and provide sufficient capacity for maximum load conditions. Lockout tags/padlocks should be provided for safe disconnection and service. Enclosure types should be specified based on location and service, with NEMA defining different types for indoor and dust-free areas. Buses should be specified as either copper or aluminum. The proper conductor terminating or connecting devices should also be specified. Enclosures should be designed to ensure safety and efficiency in the operation of motor control centers. NEMA classifies motor control centers as Class 1 or Class 2 assemblies. Class 1 motor control centers are independent units with mechanical groupings of motor control units, feeder-tap units, and other electrical devices. Class 2 motor control centers are interconnected units with manufacturer furnished electrical interlocking and wiring between units. There are different arrangements available for control systems in commercial buildings, with the physical configuration varying depending on the complexity of the system. Panelboard-type constructions involve placing the fusible disconnect or circuit breaker for each branch circuit in one enclosure, with the handle attached to the door or disconnect device. The starter, control transformer, pushbuttons, and pilot devices are placed in other enclosures, interlocked to only be accessible when the disconnect device is off. The disconnect device is usually connected to the bus bar system of a switch-type panelboard. Separate enclosures can be used for disconnect devices and starters, connected by conduit or cable. Class 1-S and 2-S motor control centers have custom drawing requirements and special identifications for electrical devices, terminal numbering designations, and sizes of drawings. The most common controller is the across-the-line magnetic-type starter, which uses an electromagnet to close contactor contacts. The control voltage is typically 120 V, but other voltages can be used. Using parallel or sliding-type contacts is recommended for low control voltage to avoid continuity issues and the need for larger wires. 120 V is the most common control voltage due to greater insulation integrity and personnel safety precautions required for high control voltage. Overload relays are placed on the load side of contactors to provide overload protection in each phase. Overload relays can be nonambient or ambient compensated and have separate indicating contacts for tripping. Overload relays should be trip-free and reset manually, with automatic reset not acceptable on machines where automatic restarting of the motor could be hazardous. NEMA standardized starters and contactors have three classes of overload relays. Overload relays should trip at 125% full-load current for 40 °C rise motors and 115% full-load motor current for all other motors. NEMA-rated controllers provide high performance over a wide set of application conditions. IEC-type controllers are rated based on laboratory performance and are typically smaller and provide lower performance than NEMA-type devices. NEMA-type controllers are preferred for their longer life, higher short-circuit withstand capability, replaceable contacts, and broad application capability. NEMA-type controllers are suitable when motor service factor, duty cycle, contactor life requirement, or short-circuit protective device are unknown or terminal markings may cause problems. Defined-purpose contactors are used for specific applications, such as resistance heating, crop drying equipment, and commercial deep-fat fryers. Manually operated controllers are limited to size 1 maximum and have a longer life than circuit breakers due to their frequent switching of rated motor currents. Solid-state contactors are crucial for high-volume operations and high shock/vibration resistance. With decreasing costs, their market share will increase, making them competitive for adjustable frequency drives and reduced voltage starting applications. Fire pump controllers provide limited overcurrent protection and short-circuit protection. The standard for fire pump controllers is ANSI/NFPA 20-1990, Installation for Centrifugal Fire Pumps. Fire pump controllers can provide manual or combined manual and automatic operation, with the manual-only type rarely installed. Power for fire pump controllers is usually obtained from a tap or a separate service. Fire pump controllers are typically wired to the power source near the service entrance or provided with a separate service. ANSI/NFPA 20-1990 mandates that fire pump controllers have a withstand rating equal to the maximum short-circuit current that can flow to the controller. Medium-voltage starters and controllers are suitable for larger motors in commercial buildings. Medium-voltage starters and controllers offer lower currents and minimal line disturbance. Class E1 and Class E2 controllers function similarly to low-voltage controllers and are available in various configurations and contactor types. Motor disconnecting is achieved using disconnecting switches or multiple-disconnecting-type fuses. 120V control circuits are supplied through transformers. Medium-voltage controllers can withstand high basic impulse insulation levels. Synchronous motor starters bring the motor to synchronous speed with the dc field de-energized and energized near synchronism. Small induction motors can be mounted on the shaft for speed. Most synchronous motors are polyphase and can be started as squirrel-cage induction motors. Starting methods for synchronous motors include starting resistance, reactance, and combinations of these. DC motors can start with full voltage or reduced voltage methods, with reduced voltage starting involving a series resistance. Speed control for DC motors is achieved by varying resistance in fields or armature circuits. Solid-state DC motor drives are increasingly used for adjustable speed applications. There are manual and automatic pilot devices that initiate the control of motors. Manually operated devices include pushbuttons, selector switches, and master switches. Selector switches open and close coil circuits and connect to automatic switches. Magnetic motor starters can be connected to multiple-speed motors to achieve different motor velocities. The windings of each phase can be connected in two ways, resulting in a stator winding with half the poles in one position. Pushbuttons can change circuit states only as long as pushed. Two-speed motors can operate at equal power, equal torque, or variable torque. Standardized pushbutton lines include standard duty, heavy duty, and oil-tight. It is important to disconnect the high-speed winding to prevent high torque and overcurrent. Operators include mushroom-head buttons, key-operated switches, handles, and pilot lights. Two-speed motors with different speed ratios should have separate windings. Automatically operated devices switch a coil circuit based on the actuating medium. Motors with three and four speeds can be created by combining these elements and using controllers. Conventional limit switches convert mechanical motion into electrical control signals. Pole amplitude modification (PAM) motors are available for arbitrary speed ratios, using conventional two-speed motor controllers. Proximity limit switches operate when an object approaches a sensor. Fire pump controllers are essential in commercial buildings to maintain water pressure during fires. Float switches, pressure switches, sail switches, and temperature switches are examples of automatically operated devices. They are typically driven by electric motors or diesel engines, depending on reliability and environmental conditions. Logic diagrams can be developed using electromechanical relays, mechanically held relays, and timing relays. Timers can be motor-driven, dashpot, thermal, solid-state, or pneumatic. Legal requirements for services to meet construction standards exist in many states, often following utility and safety codes. Programmable controllers are microcomputer-based, solid-state devices that use digital logic and can be easily reprogrammed. Overhead service laterals are commonly terminated at brackets on small buildings for electrical service. They can add functions difficult to obtain with standard relays and are generally less expensive than relays. Larger buildings may be served by open-wire lines connected to external transformer substations or cable terminal poles. The central processing unit (CPU) checks the control plan stored in memory, which can be read-only, read and write, or random access. Aerial cable supported by grounded messengers is another option for supplying electrical service to buildings. Programmable controllers can be studied and checked on computer terminals, and can also be used as input sources for electromechanical control devices. The passage discusses the materials and construction methods used for open-wire lines, including conductor types and support structures. Compliance with voltage and insulation requirements is essential for overhead service design. Acceptance by the utility provider is a crucial factor in the design process for overhead service. Safety measures include maintaining clearances from buildings, railroad tracks, and driveways, providing adequate climbing and working space for personnel, and assessing mechanical strength based on factors like wind and ice loads, pole diameter, and wire size and strength. Speed control of DC motors involves regulating armature or field current, with torque inversely proportional to field strength and counter-electromotive force. The counter-electromotive force (CEMF) is equal to the applied armature voltage (V) minus the armature current (I) times the armature resistance. The speed of a shunt motor can be increased by changing the field strength, adding resistance to the field circuit, or by switching a resistor into the isolated armature circuit. The NESC classifies safety levels into construction grades B, C, and N, with Grade B being the strongest. The speed of series motors can be regulated by adding resistors in the armature and field circuit or parallel to the armature to DC. Insulation measures involve protecting against lightning surges using surge arresters, shield wires, and enhanced insulation, as well as safeguarding against voltage surges caused by power switching. Grounding systems help dissipate lightning currents and minimize damage. Safety near traffic areas or buildings is important. Medium-voltage services have different considerations compared to low-voltage services. Installing open-wire electrical lines over or near buildings can interfere with firefighting and maintenance operations. Fully insulated cables are recommended as a safer alternative, especially for medium-voltage applications. Cables attached to a building's exterior should be enclosed in grounded metallic conduits, and if on flammable surfaces, encased in concrete. DC motor control has evolved over time, with phase control of siliconcontrolled rectifier (SCR) converters being the main method. Full wave bridge-type rectification is used for single-phase AC, while three-phase AC uses three SCRs or six SCRs and three diodes. Motor reverse can be achieved by reversing the polarity of the field windings, armature voltage, SCR converters, or generator field voltage in a motor-generator system. AC induction motors' speed depends on synchronous speed, pole number, and slip. Supply frequency controls synchronous speed, while slip depends on voltage and current regulation. Wound-rotor motors offer stepless speed control due to adjustable secondary resistance. AC adjustable frequency drives offer energy savings and a wide range of speed and torque control. Safety clearances for personnel must be maintained when open wire is used over buildings, following NESC provisions or local code rules. Common types include variable voltage input (VVI) and pulse width modulated (PWM). "Tree" coverings should not be relied upon for insulation on overhead conductors above 2000 V to ground; proper insulation and shielding are necessary. AC-dc-ac controls control frequency and voltage, allowing braking and reversal. Bare conductors must be protected in line with regulatory requirements. These controls are used with both induction and synchronous motors, providing wide speed ranges. Safety and compliance with regulations are paramount in outdoor electrical installations. Designing outdoor structures, such as overhead electric lines, should factor in weather forces like wind and ice loads. Cycloconverter drives are an economical alternative to dc link drives, synthesizing adjustable frequency and voltage AC output directly from input waveforms, suitable for low speeds. Adjustable speed motor controls use solid-state techniques to create nonsinusoidal, square-edged AC input current waveforms. Location-specific considerations are essential, as weather severity varies across the United States. These currents may contain harmonic frequency components, which can cause damage to the power system. In areas with damp or polluted atmospheres, special insulators with extended leakage distances or resistance grounded insulators may be needed to prevent contamination-related issues. These harmonics can be eliminated by changing a capacitor bank rating, and electrical consultants and equipment suppliers can provide advice on preventing or curing these issues. This approach ensures the reliability of outdoor electrical structures. Underground construction may be necessary in various situations, including conflicts with overhead structures, high load density, local regulations in new residential areas, and aesthetic considerations. Underground systems offer advantages over overhead systems, such as improved aesthetics and fewer issues. Underground systems, particularly those involving conduits and manholes, are generally more costly than overhead systems. Direct-burial-type systems like URD and CIPUD can significantly reduce costs for new developments compared to conduit-andmanhole systems. CHAPTER 7: Overhead Service Incoming electric lines and service laterals connect a building to the utility's power source. Clearance conflicts with existing or future structures should be avoided when planning these connections. Factors like voltage, ownership, maintenance, and installation costs can vary by region. Underground construction is necessary under certain conditions, such as conflicts with overhead structures, high load density, local ordinances, or aesthetics in residential subdivisions. Underground systems offer benefits like fewer issues compared to overhead systems, but they come with higher repair costs and initial expenses. Direct-burial-type systems like URD (Underground Residential Distribution) and CIPUD (Commercial and Industrial Park Underground Distribution) are cost-effective options for new developments. URD is a single-phase distribution system for residential areas, using organic insulated and jacketed cables with pad-mounted transformers or prefabricated installations. CIPUD is a three-phase system for commercial/industrial park distribution, using looped cable systems with pad-mounted transformers or above-ground switchgear. Fault indicators aid in rapid fault detection and repair. Maintenance and operation of these systems should be managed by utilities or trained personnel due to their direct burial nature and limited load handling capability. Passing service entrance conductors through buildings poses a safety hazard. The circuit inside the building is typically not protected against short circuits, overloads, or arcing faults. Short distances for these circuits are considered safer. Longer circuits should be enclosed in a raceway encased in at least 2 inches of concrete or metallic conduit encased in concrete to enhance safety. Encasing service entrance conductors in concrete within the building is a recommended practice to enhance property and life safety. Busways, neutral grounds, overheat detectors, and cable limiters are discussed as methods and materials to protect against faults and ensure service continuity. The availability of multiple system voltages from the utility can lead to the provision of different voltages for various building functions. The physical characteristics of the building, such as size and distances between buildings within a facility, may require multiple services. Compliance with NEC and local code requirements, including considerations like fire walls, can impact service design. Provisions for future load capacity should be included in the initial design, with service capacity typically exceeding immediate needs. Service equipment design should allow for the addition of protective devices for future feeder expansions. The physical arrangement of the service entrance can vary based on the utility's distribution system and the building's type. Options for the physical arrangement include transformer vaults located outside the building with bus stabs through the basement wall, transformer vaults inside the building (in the basement or on upper floors), underground services, and overhead services. Engineers should check for high short-circuit current from transformers with low impedance. Service entrance equipment rooms should be easily accessible, welllit, dry, and compliant with electric utility and local code requirements. Plans should consider future equipment replacement and provisions for smoke exhaust in the event of an electrical fire. Service entrance equipment is important for supplying a building's electrical load. It should be designed to meet future demands or easily upgraded. Collaboration between the building's engineer and the utility is crucial for optimal equipment and voltage selection. Planning should consider both current and future needs and happen early in the process. The engineer should provide necessary data to the utility. Compliance with NEC requirements, state laws, and local ordinances is essential for service entrance conductor installations within buildings. Details like service type, voltage, and overhead/underground options must be decided. Proper routing of cable systems, avoiding high ambient temperatures and chemical exposure, is emphasized, with precautions for different cable types. Some utilities offer medium-voltage services, which require careful planning but offer flexibility and cost savings for both the facility and utility. Detailed load characteristics, including kilovoltampere demand, service continuity requirements, voltage specifications, special loads, carrier current needs, largest motor inrush current, and power factor considerations. Comprehensive utility service details, encompassing available voltages, billing demand clauses, rate structures, and potential need for equipment modifications. Physical and mechanical service entrance requirements, such as service termination points, metering equipment locations, access provisions, structural interference avoidance, and equipment construction standards. Electrical service requirements, including equipment voltage, BIL levels, surge protection coordination, system capacity, fault capability, protective device coordination, utility-approved equipment types, and grounding methods. Recommendations for manholes, pull boxes, and spare ducts in long duct runs are provided to facilitate cable installation, maintenance, and future expansion. Precautions against laying duct systems in the same trench as gas or sewer service are highlighted. Service entrance conductors connect a client's service equipment to the utility's service drop or lateral. Service equipment includes main service control or disconnect, circuit breakers, switches, fuses, and metering equipment. The client typically owns and pays for service entrance conductors and service equipment. Billing metering instruments are typically owned and maintained by the utility. Schedule data, indicating important deadlines for service, load requirements, and temporary construction service needs. The design of service entrance equipment should ensure a highquality electric service without affecting other customers. Medium-voltage system design flexibility, allowing control over distribution systems, unit substation installation, and transformer selection. Low-voltage equipment design is categorized into three groups based on capacity: Low-Capacity Circuits, which have current ratings under 600 A and are typically fed by individual transformers. When multiple services come from one transformer bank, shortcircuit duty may range from 15,000 to 100,000 A. Equipment choices are broad when available fault current is less than 10,000 A, and ground-fault protection is optional for lower current installations. Engineers must strike a balance between client needs and utility requirements when designing service entrance equipment. Service reliability requirements and power source influence the need for multiple services or standby service with load transfer arrangements. Economic factors may impact service availability considerations. The total load magnitude may necessitate additional services as individual service capacity is limited by the utility. Screening should prevent pests from entering, and fire-resistant construction, like reinforced concrete, is ideal. Vaults should have UL-approved 3-hour fire doors, sumps for spill containment, and sealed floors. Gratings should meet load requirements. Multiple transformer banks should be in separate compartments for safety, with associated switchgear enclosed. Compliance with local codes, NEC, insurance, and utility rules is vital. Pad-mounted three-phase transformers and switching equipment are cost-effective and safe for various applications. They are designed for surface pad installation, with no exposed energized parts. Additional enclosures can be added for specific needs or aesthetics. Adding reactance to cable circuits connecting transformers to a common bus or from each transformer bus to separate service entrance circuit breakers or switches. Posts should be installed in accessible areas to protect against traffic. Vaults should allow for crane-based unit insertion and removal. Installing reactors in the main service connection to reduce fault current to the rating of the service entrance main and feeder circuit breakers or switches. Concealment options like landscaping or architectural fencing can be used, considering utility operation and maintenance space. Reactors can reduce fault currents to about 60,000 A. Outdoor substations, except for pad-mounted equipment meeting NESC Article 380 requirements, should be enclosed by walls or fences with adequate aisles for safe operation and maintenance. Current-Limiting Busway: Using current-limiting busway to reduce very large short-circuit currents from 200,000 A to around 100,000 A. Proper clearances, grounding, high-voltage warning signs, and locking mechanisms are essential safety measures for substations. Indoor substations, whether metal-clad or enclosed, require separate enclosures or locked rooms for authorized personnel only. Vaults should have multiple emergency escape routes with hinged doors and panic bars for quick evacuation. In large modern metropolitan office or commercial high-rise buildings, multiple transformers are installed to meet high electric demands. Medium-Capacity Circuits: These circuits have short-circuit duties ranging from 50,000 to 100,000 A, with the actual fault current determined by the utility. High-Capacity Circuits: These service entrances have a short-circuit capability exceeding 65,000 A, typically found in buildings fed from ac secondary networks or large buildings with multiple parallel transformers. Engineers must examine the limiting characteristics of devices used in medium and high-capacity circuits to ensure downstream protection, and additional current-limiting devices may be necessary. Dividing the electric circuits into independent parts, each fed by one three-phase transformer or a group of transformers. Using smaller service disconnecting switches or circuit breakers equipped with current-limiting fuses to collectively handle the available short-circuit current. Current-limiting busway is effective when local codes permit installing service entrance equipment at a distance from the building entrance. Current Limiting by Cables: Achieving current-limiting effects using cables with controlled phase spacing, installed in nonmetallic conduits buried in concrete. Separating cables for each phase in three equally spaced nonmetallic conduits to provide current-limiting reactance. Current-limiting fuses start limiting current at 20-30 times their rating and interrupt the circuit before it reaches its peak value on the first half-cycle. These transformers are connected to a common low-voltage bus through a network protector. Buildings have multiple points of power supply, such as beneath the sidewalk, within the building, or on the roof. The peak let-through current depends on the continuous rating of the fuse and the available fault current. The design of network installations involves determining utilization voltage, the number of transformers, and service points while adhering to regulations and economic considerations. A crucial aspect of network design is ensuring the ability to install, maintain, or replace components without disrupting service. Network systems are designed to meet power demands on a contingency basis, maintaining full-load capability even with a predetermined number of components out of service. First contingency networks typically use two or three primary feeders, while second contingency networks may use more primary feeders. The NEC specifies the minimum clear working space in front of electrical equipment. A second contingency network can maintain full-load capability with two sets of components out of service, while a first contingency network can maintain full-load capability with only one set of components out of service. Contingency design considers the entire distribution system, from primary feeders to substations and switching stations, to ensure seamless operation in case of component failure or damage. The initial step in planning a network installation is creating a simple sketch of the proposed setup using a standard vault equipment arrangement. Using larger current-limiting fuses with the service entrance switch or circuit breaker can protect service equipment. Smaller downstream current-limiting fuses or other methods, such as current-limiting busway, cable runs, or reactors, can protect lowerrated equipment beyond the service entrance. The NEC, Article 230–95, covers ground-fault protection requirements for equipment. Arcing ground faults can cause extensive destruction of equipment, especially on high-capacity 480Y/277 V circuits. Fully coordinated ground-fault protection schemes are recommended for such systems. Achieving proper ground-fault coordination may require a combination of fixed time delay, inverse time delay, and zoneselective interlocking. The design engineer should check the effectiveness of coordination in all cases between the main service and feeder overcurrent protective devices, as well as between the feeder and subfeeder overcurrent protective device. Equipment vaults housing service transformers require effective ventilation to dissipate heat. Natural ventilation is preferred, with a minimum of 3 square inches of net ventilator area per kVA of transformer capacity. The sketch should consider adaptations required in the building structure and potential obstructions beneath the sidewalk. Additional ventilation may be needed based on local codes and climate conditions. The design should ensure adequate space is available near customer load centers. Vertical ventilating shafts may require larger vent areas, fans, and proper controls. Subsurface conditions should be favorable to avoid costly pilings or footings. Environmental factors, such as water, should not pose significant challenges. Special attention should be given to the space and clearance requirements of busway equipment. Underground transformers can utilize natural convection cooling. Adequate illumination should be provided for all areas in accordance with the NEC, NESC, and ANSI/IES RP7-1983. Exterior transformers may have corrosion-resistant finishes. Interior transformers may employ ventilated-dry-type designs with natural and forced air cooling options. Ventilation should be provided to limit the ambient temperature of the room to 40 °C (104 °F). Compliance with municipal regulations, including considerations for general structural design to support sidewalk loads or highway loads. When a transformer other than a signal-type transformer is installed in an electrical closet or room, some local codes require that a system of mechanical ventilation be provided. Specification of the location and size of ventilation and access panels. Adequate ventilation is necessary for network installations with vaults, typically requiring a minimum of 3 square inches of net open area per 1 kVA of transformer capacity. Electrical rooms and closets should only be used for electrical equipment and maintenance, with no storage or non-electrical utilities allowed to pass through. Proper sealing of cable and busway openings is essential to prevent issues like condensation, and fire stops should be in place where needed. Using these spaces for other purposes risks accidents and unauthorized access. Forced ventilation may be necessary, usually at a rate of 3 cubic feet per minute per kVA, as per local codes or utility requirements. Vaults should be constructed from reinforced concrete for strength and explosion containment. Vaults should be as watertight as possible, with provisions for drainage. Concrete floors should be sealed to prevent dust from entering equipment. CHAPTER 8: Cable System and Conductor Types Factors to consider in cable system design include load current, emergency overloading requirements, fault clearing time, voltage drop, ambient temperatures, circuit length, and system frequency. The ratio of vault volume to net ventilation area should be kept small, typically less than 50 cubic feet per square foot of open ventilation area, often around 30 cubic feet per cubic foot, to prevent excessive pressure during secondary explosions. The primary function of cables is to carry energy reliably between source and utilization equipment. Cables may be installed in raceway, cable trays, underground in duct or direct buried, messenger supported, in cable bus, or as open runs of cable. Vaults must provide direct and rapid access for maintenance and emergency personnel. Cable systems can be classified into solid insulations, taped insulations, and special-purpose insulations. Suitable access routes should be included for transformer replacement, which may involve removable slabs or walls. Isolation or protective relaying may mitigate equipment failures, such as explosions, fires, and smoke generation. Cables with different insulations have varying maximum and normal operating temperatures, flexibility, fire resistance, and mechanical and environmental protection. Aluminum is a commonly used electrical conductor material due to its high conductivity, availability, and lower cost. Copper is also widely used for its desirable electrical and mechanical properties. Considerations for isolation and protection include location, transformer type, and protective measures like overcurrent, groundfault, and differential protection. Physical isolation may be required to protect occupants and the public. The National Electrical Code (NEC) requires conductors of No. 8 AWG and larger to be stranded. Adequate working space around electrical equipment is necessary for various operations, including switchgear removal, fuse replacement, cleaning, and cable installation. Stranded conductors are commonly found in portable cords. Different types of stranded conductors include standard concentric, compressed, compact, rope, and bunched. A single insulated or bare conductor is defined as a "conductor," while an assembly of two or more insulated conductors, with or without an overall covering, is defined as a "cable." A comparison can be made between copper and aluminum conductors. Aluminum requires larger conductor sizes to carry the same current as copper. For equivalent ampacity, aluminum cable is lighter in weight and larger in diameter than copper cable. Basic insulating materials are either organic or inorganic. Mineral insulated cable employs the inorganic insulation magnesium oxide (MgO). The aging factors of heat, moisture, and ozone are among the most destructive to organic-based insulations. The comparisons include Relative Heat Resistance, Heat Aging, Ozone Resistance, and Corona Resistance. Heat Aging - The effect on elongation of an insulation when subjected to aging in a circulating air oven is an acceptable measure of heat resistance. The air oven test at 121 °C is used to grade materials for possible use at elevated conductor temperatures or in hot-spot areas. Additional factors to consider include roof structures for vehicular traffic, potential interferences, future street changes, drainage, spare conduits, duct separation for primary and secondary feeders, cable tie lengths, equipment loading balance, and illumination. Room dimensions should be sufficient to provide access and working space around electrical equipment for easy operation and maintenance. Damping treatment can be applied to reduce noise generated by transformers. Isolation techniques can be used to minimize vibration and noise transmission. Flexible connections can be implemented to reduce vibration and noise transfer. Proper placement of ventilation ducts can help dissipate heat and reduce noise. Service rooms and electrical closets should be located as close as possible to the areas they serve. Doors should be large enough to allow for easy installation or removal of electrical equipment. Electrical rooms and closets should be sized larger than the minimum criteria dictated by the NEC to allow for future expansion and growth. Additional utility working space may be required. The 150 °C oven aging is more severe and is used to compare materials with superior heat resistance. Ozone and Corona Resistance - Corona discharge produces concentrated and destructive thermal effects along with the formation of ozone and other ionized gases. Classification of circuits under Article 725: Class 1 power-limited circuits are restricted to not over 30V and not over 1000VA, while Class 2 circuits are required to be limited to lower levels of power than Class 3 circuits. Moisture Resistance - XLPE, polyethylene, and EPR insulations exhibit excellent resistance to moisture as measured by standard industry tests, such as the ICEA Accelerated Water Absorption Test. Class 2 (CL2) or Class 3 (CL3) power limited circuit cable or power limited tray cable can be used for remote control, signaling, and power limited circuits with power levels defined in NEC Article 725. Electrical design considerations include conductor size, type, insulation thickness, dielectric strength, insulation resistance, specific inductive capacitance, and power factor. These cables are rated 300 V and include copper conductors for electrical circuits and thermocouple alloys for thermocouple extension wire. Type MV power cables have solid extruded dielectric insulation and are rated from 2001 - 35,000 V. Thermal design considerations include compatibility with ambient and overload conditions, expansion, and thermal resistance. These cables are available as single- and multiconductor cables with nominal voltage ratings of 5 kV, 8 kV, 15 kV, 25 kV, and 35 kV. For operating voltages below 2 kV, non-shielded constructions are typically used. Mechanical design considerations include toughness, flexibility, jacketing or armoring, and resistance to impact, crushing, abrasion, and moisture. Chemical design considerations include stability of materials when exposed to oils, flame, ozone, sunlight, acids, and alkalies. Cables above 2 kV are required to be shielded to comply with NEC and ICEA Standards. Flame resistance is important for cables installed in cable trays, and they should be listed as flame-retardant and marked for installation in cable tray. Shielding is the practice of confining the electric field of the cable to the insulation surrounding the conductor. Low Smoke - The NEC authorized the addition of the suffix "LS" to the cable marking on any cable construction that was flame-retardant and had limited smoke characteristics. Insulation shields have several purposes, including confining the electric field within the cable, equalizing voltage stress within the insulation, protecting the cable from induced potentials, limiting electromagnetic or electrostatic interference, and reducing shock hazard. Toxicity - All electrical wire and cable installed or terminated in any building in the State of New York after December 16, 1987, should have the toxicity level and certain other data for the product on file with the New York Secretary of State. Cable outer finishes or outer coverings are used to protect the underlying cable components from environmental and installation conditions. Extruded Jackets: Outer coverings, either thermoplastic or vulcanized, that can be extruded directly over insulation or over electrical shielding systems. Low-voltage power cables are generally rated at 600 V, regardless of the voltage used. The selection of 600 V power cable is oriented more toward physical rather than electrical service requirements. Materials for extruded jackets can withstand service temperatures from -55 °C to +115 °C. Commonly used conductors for 600V include EPR or XLPE insulated cables with or without a jacket. Fiber Braids: Synthetic or natural fiber materials used for braiding, wrapping, or serving cables. Type RHW is used for 75 °C (167 °F) maximum operating temperature in wet or dry locations. Metallic Finishes: Used for mechanical, chemical, or short-time thermal protection of cable components. Commonly Used Shielded and Nonshielded Conductors are also mentioned. Installation and operating conditions are not specified in the text. Interlocked Armor provides mechanical protection with minimum reduction in flexibility. Interlocked galvanized steel armor should be avoided on singleconductor AC power circuits due to high hysteresis and eddy current losses. Corrugated Metal Sheath has corrugations formed perpendicular to the cable axis and offers mechanical protection equal to or greater than interlocked armor but at a lower weight. Lead Sheath, made of pure or alloy lead, is occasionally used for moisture protection in underground manholes, tunnels, or underground duct distribution systems subject to flooding. Aluminum or Copper sheaths, either extruded or die-drawn, are used for weight reduction and moisture penetration protection in certain applications. Wire Armor: Provides significant mechanical protection and longitudinal strength through the use of spirally wrapped or braided round steel armor wire. Single-Conductor and Multiconductor Constructions: Singleconductor cables are easier to handle and can be furnished in longer lengths compared to multiconductor cables. Multiconductor constructions have smaller overall dimensions, which is advantageous in limited space. Cable Ratings - Voltage Ratings: The selection of the cable insulation (voltage) rating is based on the phase-to-phase voltage of the system, whether it is grounded or ungrounded, and the time it takes to clear a ground fault on the system with protective equipment. Type RHH is used for 90 °C (194 °F) in dry locations only. Type RHW-2 is used for 90 °C (194 °F) maximum operating temperature in wet and dry locations. Type XHHW is commonly used for 600V XLPE or EPR insulated conductors without a jacket, with a maximum operating temperature of 75 °C (167 °F) in wet locations and 90 °C (194 °F) in dry locations only. Type XHHW-2 is commonly used for 600V XLPE or EPR insulated conductors without a jacket, with a maximum operating temperature of 90 °C (194 °F) in both wet and dry locations. Type THWN is commonly used for 600V PVC insulated conductors with a nylon jacket, with a maximum operating temperature of 75 °C (167 °F) in wet or dry locations. Type THHN is commonly used for 600V PVC insulated conductors with a nylon jacket, with a maximum operating temperature of 90 °C (194 °F) in dry locations only. Type THW is commonly used for 600V PVC insulated conductors without a jacket, with a maximum operating temperature of 75 °C (167 °F) in wet or dry locations. These conductors are suitable for installation in conduit, duct, or other raceway, and may be installed in cable tray (1/0 AWG and larger) or direct buried if NEC requirements are satisfied. Metal Clad Cable, Type MC: A multiconductor cable with either an interlocking tape armor or a continuous metallic sheath, suitable for installation in various environments. Power and Control Tray Cable, Type TC: A multiconductor cable with an overall flame-retardant nonmetallic jacket, suitable for use in cable trays and raceways. Load current criteria refer to parameters, standards, or guidelines that govern the current ratings and characteristics of electrical loads in various systems. Locating cable faults is a common problem that needs to be determined for repairs. Emergency overload criteria determine the normal loading limits of insulated wire and cable, based on practical experience, to ensure the most economical and useful life of the cable systems. Factors to consider in locating cable faults include the nature of the fault, type and voltage rating of the cable, value of rapid location of faults, frequency of faults, and experience and capability of personnel. Voltage-drop limitations are considered in conductor selection. Physical evidence of the fault, such as observation of a flash, sound, or smoke, can help locate the fault. Fault current criteria are taken into account in conductor selection. Number of conductors in cable and phase identification required Frequency criteria and hot-spot temperature criteria are factors to consider in conductor selection. Conductor size (AWG, kcmil) and material Insulation type (rubber, polyvinyl chloride, XLPE, EPR, etc.) The length of cable in elevated ambient temperature areas is considered in conductor selection. Voltage rating and insulation level required (100%, 133%, or 173%) Equipment termination requirements are taken into account in conductor selection. Shielding system required for systems rated 8 kV and above, and may be required for systems rated over 2001-8000 V The NEC recommends that the steady-state voltage drop in power, heating, or lighting feeders be no more than 3%. Installation approvals required (cable tray, direct burial, messenger supported, wet location, exposure to sunlight or oil, etc.) The total voltage drop, including feeders and branch circuits, should be no more than 5% overall. Busways originated as a result of a request from the automotive industry in Detroit in the late '20s for an overhead wiring system. The distance between the source and the load should be kept as short as possible in wiring systems layout. A busway consists of bare copper conductors supported on inorganic insulators mounted within a nonventilated steel housing. Open-wire construction consists of single conductors on insulators mounted on poles or structures. There are four types of busways: feeder busway, plug-in busway, lighting busway, and trolley busway. The conductors may be bare or have a covering or jacket for protection against corrosion or abrasion. Feeder busway is used to transmit large blocks of power and has a low and balanced circuit reactance for voltage control. Aerial cables may be self-supporting or messenger-supported and can be attached to pole lines or structures. Plug-in Busway: Used in industrial plants as an overhead system to supply power to utilization equipment with current ratings from 1004000 A. Self-supporting aerial cables have high tensile strength conductors for this application. Lighting Busway: Rated at a maximum of 60 A, 300 V to ground. Open runs are a low-cost method that utilizes adequate support surfaces between the source and the load. Trolley Busway: Constructed to receive stationary or movable takeoff devices. It is useful in combination with other methods, such as branch runs from cable trays, and when adding new circuits to existing installations. Standards: NEC Article, ANSI/UL 857-1989, Busways and Associated Fittings, NEMA BU1-1988. Cable tray is a rigid structure made of metal or noncombustible material used to support cables. Busways Over 600 V (Metal-Enclosed Bus): Referred to as "metalenclosed bus" and consists of three types: isolated phase, segregated phase, and nonsegregated phase. Cable bus is used for transmitting large amounts of power over short distances. Metal-enclosed bus was included in the 1975 NEC. The metal-enclosed bus nameplate must specify its rated voltage. Conduit made of rigid steel provides the greatest mechanical protection for above ground conduit systems. The metal-enclosed bus nameplate must specify its continuous current. The metal-enclosed bus nameplate must specify the frequency. The metal-enclosed bus nameplate must specify the 60 Hz withstand voltage. The metal-enclosed bus nameplate must specify the momentary current. Direct burial is when cables are buried directly in the ground without the need for conduit, typically when future maintenance is not anticipated. Terminations electrically connect insulated cable conductors to electrical equipment, physically protect and support the end of the cable conductor, and control electrical stresses for desired insulation levels. Splicing devices and techniques are used to join or connect cables together. CHAPTER 9: Effects and Protection of Faults in Power Systems Tape splices can be used for shielded cables, and the considerations are similar to nonshielded cables. Preassembled splices provide a moistureproof seal to the cable jacket and are suitable for submersible, direct burial, and other applications. Uncontrolled short-circuit faults can cause service outages, interruption of essential facilities or vital services, extensive equipment damage, fire damage, and possibly personnel injury or fatality. Grounding of cable systems is important for safety and proper functioning. Short-circuit is an overcurrent resulting from a fault of negligible impedance between live conductors having a difference in potential under normal operating conditions. Cables rated up to 35 kV in power distribution systems have strong insulation to compensate for installation handling and potential deterioration. Electric power systems should be as fault-free as possible through careful system and equipment design, proper installation, and maintenance. Testing in a wiring system is important for safety, reliability, and compliance with electrical codes and standards. Faults can occur due to loose connections, voltage surges, deterioration of insulation, vermin or rodents, seepage from concrete, etc. Various tests and inspections are performed at different stages of the wiring system's lifecycle. Arcs, flashes, and burning can occur at the fault location with consequent smoke generation from the fuel load of combustibles. "Symmetrical current envelopes" refer to envelopes of peak current waves that are symmetrical around the zero axis. Increased current flows from various sources to the fault location, causing increased thermal and mechanical stress on components. "Asymmetrical current envelopes" have peaks that are not evenly distributed around the zero axis. Voltages decrease throughout the system during a fault, with maximum voltage drop occurring at the fault location. Most short-circuit currents are initially asymmetrical, but gradually become symmetrical over a few cycles. Enclosures in contact with live conductors can experience elevated voltages, increasing the risk of electric shock. Short-circuit currents are typically asymmetrical in the first cycle after the short circuit. Circuit protecting devices such as circuit breakers and fuses are used to disconnect faults from the power system. Protective devices should be capable of interrupting the maximum short-circuit current, which can result in a bolted fault at the device location. The symmetrical component of short-circuit currents is at a maximum at the beginning of the short circuit and then decays to a steady-state value due to changes in machine reactance. In practical circuits with resistance, the DC component of asymmetrical currents diminishes to zero as its energy is released as an I²R loss in the circuit's resistance. The total short-circuit current is a combination of currents from the utility, local generator, synchronous motor, and induction motor, and it decays over time due to the reduction of flux in the machine. The induction motor component of the total short-circuit current usually disappears after one or two cycles, except for very large motors where it may be present for longer. Three-phase bolted fault: Conductors are physically connected with zero impedance, like being bolted together. Not the most common fault but leads to maximum short-circuit values. Fault currents can vary depending on the location of the fault and the impedance of the circuit elements. Line-to-Line bolted fault currents are about 87% of the three-phase bolted fault. Accurately calculating available fault currents is necessary to ensure proper protection and avoid short circuit and fire hazards. Line-to-Ground Bolted Faults: In solidly grounded systems, line-toground fault current is usually similar to the three-phase bolted fault current, but ground-fault current is generally lower due to the relatively high impedance of the ground return circuit. Resistance Grounded High-Voltage Systems: In resistance grounded high-voltage systems, a resistor is selected to limit ground-fault current within a range of 1-2000 A, and complex line-to-ground shortcircuit current calculations are generally unnecessary. The fault condition with no impedance results in a maximum shortcircuit current, known as the available short-circuit current. Bolted short circuits are rare, and faults typically involve arcing and burning, leading to lower fault currents. Faults involving ground can lead to elevated potential in the protective enclosure, increasing the risk of shock hazard. Maintaining adequate equipment grounds and quickly detecting and isolating faults are important for minimizing exposure voltage and reducing the duration of exposure. Implementing proper grounding techniques can reduce elevated potential and minimize the risk of shock to personnel. Continuous monitoring and regular maintenance of equipment can aid in the early detection and isolation of faults, ensuring a safer working environment. Circuit breakers and fuses can be designed for single- or multiple-pole use and have both protective and switching functions. Arcing Faults: Arcing faults in power systems have lower short-circuit currents than bolted faults. Single-phase voltage issues can result from utility supply failure, system defects, or single-pole interrupters. Arcing faults are challenging to detect and can pose safety risks. There are four basic sources of short-circuit currents. Arcing faults can cause damage from the effects of sustained arcs. The impedance of a rotating machine consists primarily of reactance, which is complex and variable with time. Equipment selection is crucial for personnel safety, equipment protection, and service continuity. Reactance of a rotating machine changes with time and affects current values in response to short circuits. Protective devices such as fuses and certain circuit breakers operate based on current detection. Devices can handle higher short-circuit currents than their rating with upstream current-limiting measures. A wide range of protective relays is available to detect abnormal conditions related to voltage, frequency, or real/reactive power. Rotating machines are assigned three reactance values for calculating short-circuit currents: subtransient reactance, transient reactance, and synchronous reactance. Relays should be used alongside circuit breakers or motorized switches to remove detected faults. Subtransient reactance (Xd'') is the apparent reactance of the stator windings at the instant of a short circuit and determines initial current flow. Circuit protective devices should be chosen to swiftly detect and interrupt faults without exceeding equipment ratings. Proper selection depends on knowledge of expected short-circuit current magnitudes for various fault types. Transient reactance (Xd') determines the current after the subtransient period, typically up to 0.5 seconds. Use equipment with short-circuit ratings equal to or higher than potential short-circuit currents for safety and equipment protection. ANSI/NFPA 70-1990, National Electrical Code (NEC), Section 110-9 states that devices intended to break current should have an interrupting rating sufficient for the voltage and current. Selection of a specific device depends on factors such as protective characteristics, economics, component protection, maintainability, and user preference. Components like busway and conductors must exceed the let-through currents of overcurrent protective devices if lower than the calculated short-circuit current at the fault point. The type of short-circuit calculation depends on the basis for rating interrupting devices and their operating. Synchronous reactance (Xd) determines the current flow when steady-state condition is reached but is not used for short-circuit calculations. Obtain the available utility three-phase short-circuit current and three-phase short-circuit X/R ratio from the serving utility. Primary voltage should be adjusted by considering transformer impedance and voltage ratio. Single line-to-ground short-circuit current and X/R ratio should be obtained from the serving utility for accurate calculations and analysis. "Symmetrical" describes AC waveforms with evenly distributed peaks around the zero axis. Unusual circuit configurations can subject devices to asymmetrical currents beyond their capabilities. The geometric relationship between the eye, task, and light source is the primary factor in minimizing veiling reflections. Short-circuit calculations should consider the X/R ratio at the fault point to determine power factor. Special lighting materials can be useful when achieving ideal geometry is challenging, especially in multi-occupancy rooms. Asymmetrical multiplying factors based on X/R ratio and circuit power factor can be estimated using available data. Visual comfort probability (VCP) Short-circuit current may change over time post-fault. Glare evaluation data have been developed through an empirically derived formula that assesses all the factors in a room. Device speed and rating basis determine the circuit impedances in the equation I = E/Z. Visual comfort probability (VCP) is a system that determines the brightness tolerances of individuals based on statistical testing. Total Current Basis of Rating is used in ANSI C37.6-1971 for highvoltage circuit breakers. VCP tables for specific luminaires can be obtained from luminaire manufacturers. ANSI C84.1-1989 lists 1000-100,000 V as "medium voltage". IEEE C37.5-1953 provides methods for determining the Rms value of a sinusoidal current wave and simplified calculation of fault. Air return luminaires allow for the transfer of air from occupied areas to the mechanical room through the luminaire lamp compartment and ceiling cavity. Advantages of task-ambient lighting: Energy-efficient. ANSI C37.5-1969 introduced a revised calculation procedure for obtaining short-circuit duties for total current rated circuit breakers. Electric lighting revolutionized commercial buildings, replacing daylight as the primary source of illumination. Despite advancements, lighting still consumes 40% of commercial building energy. The calculation of first-cycle duty (momentary) was determined by ANSI C37.5-1953 using a symmetrical short-circuit current value and multiplying factors to find asymmetrical short-circuit duty. ANSI C37.5-1969 modified the reactance values for small and medium-sized induction motors in the first-cycle duty calculation. Lighting objectives for owners may vary depending on the desired visual performance or creating mood and atmosphere. ANSI C37.5-1969 used subtransient reactance for generators, 1.5 times subtransient reactance for motors, and modified subtransient reactances for induction motors. The Department of Energy (DoE) created "The Model Code for Energy Conservation in New Buildings" to mandate energy conservation. Low-voltage protective devices are rated based on the maximum available symmetrical current at a specified power factor, using subtransient reactance X²d for all short-circuit current sources. The Federal Energy Administration (FEA) requested that states adopt a mandatory lighting efficiency standard at least as stringent as ANSI/ASHRAE 90-80, Section 9. High-voltage circuit breakers are rated on a symmetrical current basis, with the symmetrical short-circuit current rating applying only at the rated maximum voltage. On May 6, 1987, the DoE proposed "Energy Conservation Voluntary Performance Standards for New Commercial and Multi-Family HighRise Residential Buildings" in the Federal Register. The short-circuit capability at lower actual operating voltages is calculated by multiplying the rated current by the voltage. Ballast: An electrical device used with discharge lamps to supply voltage, control lamp current, and provide power factor correction. IEEE C37.010-1979 describes the method for applying symmetrically rated circuit breakers. Brightness: The subjective attribute of any light sensation, including qualities such as "bright," "light," "brilliant," and "dim." The first-cycle duty calculation is similar to IEEE C37.5-1979. Brightness refers to measurable photometric brightness, while "luminance" is the preferable term for objective measurements. Contact parting time short-circuit duty calculation in IEEE C37.0101979 uses the same reactance network as C37.5-1979. Contrast indicates the degree of difference in light reflectance between the details of a task and its background. A multiplying factor is applied to establish duty for comparison with symmetrically rated circuit breakers. Coefficient of utilization (CU) is the ratio of the average lumens delivered by a luminaire to a horizontal work plane to the lumens generated by the luminaire's lamps alone. If the X/R ratio is 15 or less, the multiplying factor is 1.0. When the X/R ratio exceeds 15, the factor is determined based on contact time. Efficacy is measured in lumens per watt (lm/W). The fault point X/R ratio calculation in IEEE C37.010-1979 is the same as in IEEE C37.5-1979. There are different types of light sources, including incandescent lamps, fluorescent lamps, and High-Intensity Discharge (HID) lamps. Calculation methods in IEEE C37.5-1979 and IEEE C37.010-1979 differ from ANSI C37.5-1953, primarily in data collection and the treatment of reactances. Equivalent Sphere Illumination (ESI) is a measure of the effectiveness of a lighting system in rendering a task visible compared to the visibility of the same task lit inside a sphere of uniform luminance. The first-cycle (momentary) duty calculated by present methods is generally similar to the earlier method. A fixture is a luminaire. Footcandle (fc) is a unit of illuminance. The interrupting duty calculated by the present method is often higher due to increased recognition of factors. Footlambert (fl): The unit of luminance that is defined as 1 lm uniformly emitted by an area of 1 ft2. Further details about these procedures can be found in IEEE Std 1411986, IEEE Recommended Practice for Electric Power Distribution for Industrial Plants. Glare: The undesirable sensation produced by luminance within the visual field. Lamp: Generic term for a man-made source of light. High-intensity discharge (HID) lamps: A group of lamps filled with various gases. Lumen (lm): The international unit of luminous flux or the time rate of the flow of light. Illuminance: The unit density of light flux that is incident on a surface. CHAPTER 10: Energy Conservation and Lighting Regulations Lighting contribution to building heating and cooling loads Lighting control techniques like polarizing materials, specific light distributions, and indirect lighting aim to reduce veiling reflections in visual tasks. Luminaire: A complete lighting unit that consists of parts designed to position a. Electric light sources and daylight have different characteristics in terms of efficacy, color, source size, lumen maintenance, starting and restarting attributes, and economics. Lumens per watt (lm/W): The ratio of lumens generated by a lamp to the watts consumed by the lamp. Incandescent lamps have low efficacies ranging from 17 to 24 lm/W, making them the least efficient lighting source. Luminaire efficiency: The ratio of lumens emitted by a luminaire and the lumens generated by the lamp(s) used. They can be energy-efficient when used for spotlighting in small areas from a distance, but are not suitable for large, long-operating spaces. Luminance: The light emanating from a light source or the light reflected from a surface, measured in cd/m2. Incandescent lamp life and efficacy have an inverse relationship, with lower filament temperatures resulting in longer lamp life but reduced efficacy. The selection of the right lamp life for incandescent lamps depends on factors such as energy costs, maintenance labor rates, and ease of access. Incandescent lamps provide good color rendering despite their warm color bias and limited cool colors. Additional colors can be achieved with filters applied to the bulbs or separate color filters in theatrical and display lighting. Tungsten halogen lamps: They use the halogen cycle to prevent deposits of evaporated tungsten from collecting on the inner bulb surface, resulting in a longer lamp life and consistent lumen output. Incandescent lamps (dimming): These lamps can be dimmed by adjusting the voltage at the socket, but this reduces light output and lamp efficiency. Fluorescent lamps: These lamps rely on an electric arc discharge through low-pressure mercury vapor to produce ultraviolet radiation, which then excites phosphors on the lamp's bulb wall to produce visible light. Fluorescent lamps are more energy-efficient compared to incandescent or mercury lamps. The efficacy of fluorescent lamps varies based on factors like color and wattage. Fluorescent lamps offer advantages such as low brightness and diffusion, making them suitable for applications where minimizing glare and controlling discomfort glare is essential. Fluorescent lamps come in various lengths and can operate at different currents. Rapid-start and slimline lamps typically use 430 mA, but ballasts allow these lamps to be operated at reduced currents like 200 mA or 300 mA. Lux: The metric measure of illuminance, equal to 1 lumen uniformly incident upon 1 m2. Reflectance: The ratio of the light reflected by a surface to the light incident. Rated life of a ballast or lamp: The number of burning hours at which 50% of the units have burned out and 50% have survived. RVP (performance): The potential task performance based upon the illuminance and contrast of the lighting system. Veiling reflections: Reflected light from a task that reduces visibility because the light is reflected specularly from shiny details of a task, which brightens those details and reduces contrast with the background. Electronic ballasts operate at higher frequencies for increased system efficiency. Task-ambient lighting: A concept involving a component of light directed toward tasks from appropriate locations by luminaires located close to the task for energy efficiency. VCP (visual comfort probability): A rating of a lighting system expressed as a percentage of people who, if seated at the center of the rear of a room, will find the lighting visually acceptable in relation to the perceived glare. Visual task: Work that requires illumination in order for it to be accomplished. Work plane: The plane in which visual tasks are located. Providing illumination without discomfort caused by glare. Minimizing veiling reflections in task details. Using a high color rendering source for critical appearances. Selecting sources and luminaires that provide sparkle and modeling on certain objects. High-output fluorescent lamps operate at 800 mA and offer around 45% more light per unit of length compared to 430 mA lamps. Using sources, equipment, and techniques to create the desired atmosphere in a space. Extra-high-output fluorescent lamps at 1500 mA provide 60% to 70% higher light output per unit length. Visual Comfort - providing illumination without annoyance or discomfort. High-output lamps cater to applications requiring increased illumination levels or where higher mounting heights allow for reduced lamp or fixture quantities, offering cost savings. Reduced wattage fluorescent lamps have been developed to reduce power consumption by 10% to 20% across various types, while providing improved luminous efficacy, color rendering, and longer average lamp life. Reduced wattage fluorescent lamps are suitable for energy-efficient lighting installations while maintaining illumination levels and can replace incandescent options. It is important to avoid using reduced wattage fluorescent lamps in areas below 60 °F. Fluorescent lamps offer various colors achievable by changing phosphor components. Improved technology allows for high-efficiency, high-color-rendering lamps, albeit at a higher cost. Minimizing veiling reflections to improve task visibility. Room finishes and their reflectance play a role in the efficient utilization of light and lighting energy. The color scheme and light source can impact the perception of temperature by occupants of the space, potentially affecting space heating or cooling. Different light sources can vary in terms of their efficacy of light production and color rendition. Psychological factors, although subjective, have been studied to understand how groups of people react to different lighting conditions. The Illuminating Engineering Society (IES) adopted a new system for recommended illumination levels in 1979, replacing single-number footcandle values with illuminance ranges aligned with international standards. Designers now have the responsibility to select illumination levels based on factors such as worker age, task background reflectance, and performance demands. Some fluorescent lamps provide saturated colors using specific phosphors or integrated color filters. The starting and operating characteristics of fluorescent lamps are significantly affected by temperature. Equivalent Sphere Illumination (ESI) is a useful metric for comparing lighting systems. Dimming systems are available for 30W and 40W rapid-start fluorescent lamps, expanding their use in various settings. Fluorescent lamps (dimming): Electronic dimming systems vary, so consulting manufacturers is essential for details on features, reliability, and cost. Special ballast designs enable the flashing of highoutput fluorescent lamps for signs and displays. High-intensity discharge (HID) lamps: This lamp family includes mercury metal-halide, high-pressure sodium, and low-pressure sodium lamps. They require ballasts and have a higher pressure in their arc tubes and a more intense, shorter discharge path compared to fluorescent lamps. High-intensity discharge (HID) lamps (mercury lamps): Mercury lamps, once commonly used, are now less specified due to the availability of more efficient options like metal-halide and highpressure sodium lamps. They are still suitable for lower wattage applications around 175 W. Special low-temperature ballasts are available for starting lamps in extremely cold conditions. Ballasts may overheat when lamps flicker near the end of life or when one of a pair of lamps is removed from the lampholder. Flickering or burned-out lamps should be replaced promptly to prevent possible ballast damage. Lamps remaining in energized fixtures cause the ballast to consume a small amount of energy at a very low power factor due to magnetized. Electronic ballasts for high-pressure sodium lamps have solid-state control circuits and reactors that monitor operating conditions. It is desirable to use an in-line fuseholder and time delay fuse with each fluorescent lamp ballast to prevent blackouts and provide a safe means of replacing ballasts. Circuit breakers used for frequent switching of fluorescent lamps should be UL listed as "SWD" for this duty. Radio interference from fluorescent lighting systems can be minimized by using appropriate lenses on the luminaire and installing available filters in the circuit feeding the ballasts. Most aspects of ballasts in fluorescent lamps also apply to HID lamps. High-pressure sodium lamp ballasts have a high-voltage pulse for lamp starting and hot-restart capability within a minute after voltage interruptions. Older ballasts required prompt lamp replacement and avoiding keeping them energized without a functioning lamp to prevent damage to the starting aid. HID ballasts should be grounded in compliance with the NEC or local codes. Luminaires for air return and their effect on air changes, fan horsepower, etc. It may be desirable to use a line-side fuse with HID ballasts to prevent branch-circuit breakers from opening in the case of a defective ballast. Lag- and reactor-type ballasts should have a supply voltage within ± 5% of the design voltage, while constant wattage autotransformer (CWA) ballasts should have a voltage within ± 10% of the design voltage. HID ballasts are available for a wide variety of utilization. Metal-halide lamps are more efficient than mercury lamps and should be used when color is important. Mercury and metal-halide lamps produce ultraviolet energy within their arc discharge, which can enhance color rendition. Mercury lamps have safety features that deactivate the lamp shortly after the outer bulb is damaged. Starting characteristics of mercury and metal-halide lamps are relevant considerations. Lamps require 5-8 minutes of starting time (warmup) before reaching full light output due to low vapor pressure of the arc tube gases at the start. High-intensity discharge (HID) lamps, such as high-pressure sodium lamps, have a relatively high-pressure electric arc discharge in a ceramic arc tube containing sodium in an amalgam form. Low-pressure sodium lamps have the highest lm/W efficacy but may not be acceptable for color recognition. HID lamps are larger in size compared to low-pressure sodium lamps and more similar to fluorescent lamps. Care should be taken in disposing of low-pressure sodium lamps as the free sodium in contact with water can create a fire hazard. Ballasts for high-intensity lamps perform several functions, including providing the appropriate voltage to start and maintain the lamp, as well as power factor correction. The primary choice for fluorescent lamps is the rapid-start ballast, which allows for quick lamp ignition and comes in various current options. Architectural character of the space to be lighted, including size, proportions, layout of furnishings, and structural and mechanical features, should be considered. Solid-state electronic ballasts, introduced in the 1980s, improve power factor but their harmonic currents should be considered to avoid overloading neutral circuits. The designer's concept of how the space should appear, including lighting patterns that emphasize structure or layout, should be taken into account. According to ANSI/NFPA 70-1990, all fixtures and lighting equipment, including ballasts, should be grounded. The styling of luminaires, whether simple or decorative, should be considered, noting that decorative luminaires may be primarily for decorative effect rather than illumination. Rapid-start ballasts require a starting aid consisting of a grounded metal strip running the full length of the lamp. General considerations that affect the selection of a lighting system include the appropriateness of the luminaires for providing illumination and the presence of other lighting systems, such as cove lighting or downlighting systems. Suitability for specific visual tasks or activities, including light distribution, diffusion or directional qualities, creation of shadows, veiling reflections, and uniformity of illumination. Visual comfort, including the use of appropriate shielding and diffusing media, opaque or luminous-sided luminaires, viewing orientation, and visual comfort probability (VCP). Efficiency, including the utilization of direct, indirect, and intermediate types of lighting, and power requirements. Flexibility, including the use of movable office furniture with task lighting fixtures, movable shelf-mounted fixtures, movable freestanding indirect fixtures, and movable plug-in recessed troffers. Maintenance, including the susceptibility to maintenance requirements. The fluorescent fixture housing acts as a starting aid. Slimline lamps are instant-start lamps that can operate at various currents based on the chosen ballast, with the two-lamp series type being the most popular and economical option. Lead-lag ballasts operate lamps in parallel to achieve a high-power factor circuit, but are more expensive than the series type. Recent fluorescent lamp ballasts reduce losses by almost half, run cooler, and last longer than traditional ballasts. Ballasts should be operated at no more than 5% higher or 10% lower than the rating to avoid overheating and shorten life. Ambient temperature and fixture design can affect ballast performance. Ballast case hot-spot temperature should not exceed 90°C (194°F) during operation. Thermally protected ballasts disconnect when temperatures exceed the limit, while those without thermal protection have shortened lifespans when operated above 90°C (194°F). -Dirt collection -Ease of cleaning -Ease of relamping -Characteristics of plastics, paints, and metals used -Coordination with mechanical system -Luminaires for air supply An alternative approach is to bypass the luminaire and return air directly to the ceiling cavity, which offers similar benefits but to a lesser extent. Benefits of using air return luminaires or bypassing luminaires for air return include reduced heat gain in occupied space, reduced requirement for air exchanges, reduced duct size and fan horsepower, and improved thermal comfort. Using air return luminaires or bypassing luminaires can also result in reduced fluorescent lamp. Reduced ballast operating temperature and longer life for older conventional ballasts. There is little effect on the life of low-watt loss ballasts. Several lighting techniques may be evaluated for specific applications. The purpose of the lighting system should be established before discussing lighting techniques for commercial buildings. Functional requirements for each area of the building should be clearly defined. Seeing clearly is crucial for task performance and the quantity and quality of light affect this requirement. Tools like visual comfort probability, contrast rendition factor, and equivalent sphere illuminance help assess the quality of light. Circuit breakers are not recommended as switches for lighting control unless designed for such a purpose. Approved 300 V wall switches can safely control lighting fixtures on 277 V circuits if voltage between switches remains below 300 V and grounded barriers are used when it exceeds. Two phases of a 480 V system sharing the same enclosure should have a voltage of 300 V according to NEC guidelines. Low-voltage remote control switching systems typically use a 24 V switch to actuate relays in the branch circuit for convenient and flexible control. Lighting contactors are used for controlling large groups of lighting or multiple branch circuits, with different standard control voltages such as 24 V dc, 24 V ac, 120 V ac, and 277 V ac. Advanced control systems with microprocessor logic and multiplexing are emerging to reduce wiring complexities in lighting control. Solid-state semiconductor dimmers have simplified the practice of dimming incandescent lamps and are popular due to their small size. Solid-state technology enables efficient dimming of HID lamps, providing energy savings while maintaining a constant level of illumination. Possible methods of dimming include variable resistance (rheostat), variable autotransformer, variable reactance, and solid-state electronics. Dimming systems are suitable for various applications, both indoors and outdoors, offering flexibility in energy management. Lighting maintenance should be in accordance with the plans of the lighting system designer. Illuminance plays a key role in creating varying moods within spaces. Lighting can guide people's movement through spaces. Aesthetic lighting focuses on enhancing the visual appeal of objects and people. Light loss in lighting systems due to dirt, dust, and environmental conditions varies based on the fixture type and cleaning frequency. Uniform lighting: Even illuminance throughout the area at task lighting level. Proper maintenance planning during design can significantly reduce the need for relamping and cleaning. Non-uniform lighting: Most light on the task, with general and noncritical levels reduced. Light loss factors acknowledge uncontrollable depreciation and controllable factors in depreciation. Task-ambient lighting: Direct lighting for task up close with ambient lighting from adjacent indirect or ceiling-mounted luminaires. Lumen maintenance data from manufacturers helps evaluate light output over time. Advantages of uniform lighting: Good eye adaptation, uniform appearance, energy-efficient, lower initial cost, provides space interest, emphasizes work areas. Planned maintenance, including relamping and cleaning, prevents burn-outs, maintains illumination levels, and saves on labor and expenses. Advantages of non-uniform lighting: Energy-efficient, tax benefits, easily movable. Group relamping and coordinated cleaning are cost-effective for lamps with similar life spans and operating hours. Disadvantages of uniform lighting: May be least energy-efficient, monotonous, may have higher initial cost. The efficiency, light output, life, and power consumption of lamps are all substantially affected by their operating voltage. Disadvantages of non-uniform lighting: Must know tasks, task locations, must be moved as task changes. Incandescent lamp performance, including efficiency, light output, lifespan, and power usage, depends significantly on their operating voltage. Disadvantages of task-ambient lighting: Veiling reflections, space confining, expensive fixtures, wiring and switching may be more difficult. The most common standard voltage for general-service incandescent lamps is 120 V. Typical uses: Large homogenous areas, libraries, drafting rooms Higher voltage options like 230 V, 250 V, and 277 V are available but are generally less efficient and durable. Typical uses: Clerical offices, supermarkets, cafeterias Typical uses: Gymnasiums Using lower voltage incandescent lamps in higher voltage sockets can cause them to shatter. Typical uses: Large non-homogenous areas, smaller areas, private offices, low employee density areas Lamp efficiency is often more critical than lamp life for incandescent lamps. Typical uses: Small work areas, furniture systems, open office plans Special-service incandescent lamps with longer lifespans exist, but they are about 15% less efficient than general-service lamps. Control of lighting in large homogenous areas is typically done manually by means of a switch located in a luminaire, a pull cord attached to the luminaire switch, or a fixed wall switch. Fluorescent lamps require proper ballast for optimal performance. Manufacturers provide recommended voltage limits for specific ballasts, with using 277 V and 480 V primary ballasts for HID lamps resulting in cost savings in commercial buildings. Connecting fluorescent luminaires line-to-neutral in 480Y/277 V power supply systems can be economical, but may introduce third Control of lighting in large non-homogenous areas, smaller areas, private offices, and low employee density areas can be done manually with a switch or pull cord, or more sophisticated options such as dimming and timed controls can be achieved through manual or automatic means. harmonic currents that require the neutral conductor to match the size of other circuit conductors as per NEC regulations. Incandescent filament lamps have a power factor of 100%, while fluorescent and HID lamps typically operate at a power factor of less than 50% due to ballast circuits with reactive elements. Most ballasts for general lighting applications can enhance the power factor. Two-lamp series fluorescent ballasts have a slightly leading power factor, which is advantageous in buildings with other loads having a lagging power factor. High-power-factor ballasts are recommended for lighting applications. Some ballast circuits used in devices like desk lamps and home appliances may operate low-wattage fluorescent lamps at a low power factor. Fixtures can vary in cost and quality due to factors like workmanship and reflector type. Lighting designers should consider overall economic factors when selecting fixtures, as the most expensive may not always be the best choice and the least expensive may not be the wrong choice. Effective communication between the lighting designer and the client is important in determining the appropriate lighting type and quality based on factors such as task characteristics, light source quality, visual comfort, lighting control, required light levels, and budget. Energy costs vary by state and region, and while energy efficiency is a concern for designers, clients are often more concerned with energy economics. The lighting designer should consider the cost of the lighting in relation to its energy efficiency and the client's budget. Maintenance: Lighting designers should consider the maintenance details from the client, taking into account the size and expertise of their maintenance department. High temperatures may shorten the life of ballasts, with thermal protectors opening the circuit and turning off the light. Incandescent lamps perform well in varying temperatures, while HID and fluorescent lamps are greatly impacted by cold temperatures. Low-maintenance systems can be costlier upfront, so a balance between maintenance and system costs should be considered. Appropriate ballasts are necessary to provide sufficient starting voltage for lighting. Effect on Personnel: The psychological effects of illumination on workers should be discussed with the end user to make informed decisions about the lighting system. Productivity is a key consideration, and the trade-off between production levels and illumination quality should be evaluated when preparing the illumination budget. Illuminance calculations: Two principal factors in lighting design are illuminance calculations and life-cycle costs. Illuminance calculations can be approached in two main ways: uniform distribution for densely occupied spaces like offices and classrooms, and non-uniform distribution for energy-efficient task lighting. For uniform illuminance, utilization coefficients from luminaire manufacturers, combined with maintenance factors, determine the number and arrangement of luminaires. Non-uniform illuminance calculations are more complex, involving direct luminaire contributions and interreflected light, often done point by point. Lighting in buildings can serve a dual purpose in the winter by providing both illumination and replacing heat losses when the outside temperature is low, with electric lamps being 100% lowtemperature heat source. It is important to assess each subsystem's impact on energy usage in future building designs to comply with energy budgets and ensure efficiency. Three variables to consider in computing the net effect of lighting on building energy usage are the lighting energy used directly, the heat gain on a cooling system caused by lighting load, and the lighting heat gain contribution to building heating. Lighting systems in winter can help maintain room temperature and reduce the need for frequent heating system cycling, especially when using oil or natural gas for space heating. Ceiling-installed lighting units in single-story buildings compensate for heat loss through the roof when the outside temperature drops below 65 °F (18.3 °C). Ballasts should be designed to withstand low temperatures. Placing the ballast in a heated environment may be a practical solution for building-mounted signs or security lighting equipment. Fluorescent lamps deliver optimal light output within a temperature range of 21.1°C to 26.7°C (70°F to 80°F). Above this temperature range, light output decreases by about 1% per every two degrees Fahrenheit, making it challenging for enclosed or recessed luminaires. In temperatures below this range, light output decreases at a rate of 2% per degree Fahrenheit, which can be problematic for outdoor fluorescent lighting. In very cold conditions, regular fluorescent lamps may not reach full light output, but in closed fixtures or shielded from drafts, the ambient temperature around the lamp may increase, improving light output. HID lamps can gradually reach normal light output when provided with sufficient voltage in cold weather. Ballasts designed for cold weather operation are recommended below 10 °C (50 °F). High temperatures can affect ballast life, so proper heat dissipation is crucial. The ballast hum may become noticeably audible above the ambient sound level. Fluorescent and HID lamp ballasts are typically quiet when placed on a vibration-resistant base, but vibrations in the luminaire itself can cause a noticeable tonal hum. Whether annoyance is likely to be ascribed to a lighting system depends on the sound level. The design and construction of the luminaire The design and construction of the ballast The VA rating of the luminaire and the illuminance level Low-rise buildings of one or two stories make up over 90% of the existing commercial and industrial buildings. The tonal quality is determined by the distribution of sound power among the harmonics of 120 Hz being radiated Fluorescent lamps reach temperatures of about 105 °F (40.6 °C) for 4foot rapid-start lamps and 140 °F (60 °C) for 1500 mA fluorescent lamps. Lighting systems store energy and contribute to building heating by radiating and convecting heat into the occupied space. In multi-story buildings, lighting on the top floor and around the perimeter of lower floors can replace heat losses throughout the building shell. Effective control and redistribution systems are required for useful interior zone heat. The ambient sound level in the area from other sources also affects the sound level Lighting economics is multifaceted and can be divided into several categories: -First costs -Type and quality of lighting desired -Energy costs -Maintenance costs -Effect on personnel Energy surplus from redistribution can be stored in insulated water tanks, saving energy and money. These systems can also be used in the summer to chill water during off-peak electric utility hours, reducing cooling requirements during occupied times. Considering lighting heat is important for managing cooling loads in warm climates. Building mechanical system designs should include allowances for refrigeration tonnage and air or water volume. The IEEE Gray Book Electrical Power System in Commercial Buildings covers the topic of lighting.