DESIGN OF FOUNDATIONS Dr. Izni Syahrizal bin Ibrahim Faculty of Civil Engineering Universiti Teknologi Malaysia Email: iznisyahrizal@utm.my Introduction • Foundation – Part of structure which transmits load from the structure to the underlying soil or rock • All soils compress noticeably when loaded causing structure to settle Introduction • Requirements in the design of foundations: (i) Total settlement of the structure to be limited to a tolerably small amount (ii) Differential settlement of various parts of structure shall be eliminated Introduction • To limit settlement, it is necessary to transmit the structure load to a soil stratum of sufficient strength • Spread the structure load over a sufficiently large area of stratum to minimize bearing pressure • Satisfactory soil: Use footings • Adequate soil: Use deep foundations i.e. piles Introduction • Pressure distribution under a footing Uniform distributed Cohesive soil Cohesionless soil Types of Foundation Pad Footings • Transmit load from piers and columns • Simplest and cheapest type • Use when soil is relatively strong or when column loads are relatively light • Normally square or rectangular shape in plan • Has uniform thickness Types of Foundation Combine Footings • Use when two columns are closed together • Combine the footing to form a continuous base • Base to be arranged so that its centreline coincides with the centre of gravity of the load – provide uniform pressure on the soil Types of Foundation Strap Footings • Use where the base for an exterior column must not project beyond the property line • Strap beam is constructed between exterior footing & adjacent interior footing • Purpose of strap – to restrain overturning forces due to load eccentricity on the exterior footing Types of Foundation Strap Footings (continued) • Base area of the footings are proportioned to the bearing pressure • Resultant of the loads on the two footings should pass through the centroid of the area of the two bases • Strap beam between the two footings should NOT bear against the soil Types of Foundation Strip Footings • Use for foundations to load-bearing wall • Also use when pad footings for number of columns are closely spaced • Also use on weak ground to increase foundation bearing area Types of Foundation Raft Foundations • Combine footing which covers the whole building • Support all walls & columns • Useful where column loads are heavy or bearing capacity is low – need large base • Also used where soil mass contains compressible layers or soil is variable – differential settlement difficult to control Types of Foundation Pile Foundations • More economic to be used when solid bearing stratum i.e. rock is deeper than about 3 m • Pile loads can either be transmitted to a stiff bearing layer (some distance below surface) or by friction along the length of pile • Pile types – precast (driven into the soil) or cast in-situ (bored) • Soil survey is important to provide guide on the length of pile and safe load capacity of the pile Types of Foundation Pile Foundations Load from Structure Pile Cap Lower Density Medium Density High Density P I L E P I L E P I L E P I L E Design of Pad Footing Thickness and Size of Footing Area of pad: 𝑮𝒌 + 𝑸𝒌 + 𝑾 𝑨= 𝑺𝒐𝒊𝒍 𝒃𝒆𝒂𝒓𝒊𝒏𝒈 𝒄𝒂𝒑𝒄𝒊𝒕𝒚 Minimum effective depth of pad: 𝒅= 𝑵𝑬𝒅 𝒗𝒓𝒅,𝒎𝒂𝒙 ∙ 𝒖𝒐 NEd = Ultimate vertical load = 1.35Gk + 1.5Qk 𝑓 vrd,max = 0.5vfcd = 0.5 0.6 1 − 𝑐𝑘 250 uo = Column perimeter 𝑓𝑐𝑘 1.5 Design of Pad Footing Design for Flexure • Critical section for bending – At the face of the column • Moment is taken on a section passing completely across the footing and due to ultimate load on one side of the section • Moment & shear is assessed using STR (Structure) combination x y y x STR Combination 1: 𝑵 = 𝟏. 𝟑𝟓𝑮𝒌 + 𝟏. 𝟓𝑸𝒌 Design of Pad Footing Check for Shear • May fail in shear as vertical shear or punching shear Vertical shear sections Punching shear perimeters 2d d h Bends may be required d Design of Pad Footing Check for Shear (i) Vertical Shear • Critical section at distance d from the face of column • Vertical shear force = Load acting outside the section • If VEd VRd,c = No shear reinforcement is required Design of Pad Footing Check for Shear (ii) Punching Shear Axial Force Only • • • • • Critical section at a perimeter 2d from the face of the column Punching shear force = Load outside the critical perimeter 𝑽𝑬𝒅 Shear stress, 𝒗𝑬𝒅 = where u = Critical perimeter 𝒖∙𝒅 If vEd vRd,c = No shear reinforcement is required Also ensure that VEd VRd,max Design of Pad Footing Check for Shear (ii) Punching Shear (continued) Axial Force & Bending Moment • Punching shear resistance can be significantly reduced of a coexisting bending, MEd • However, adverse effect of the moment will give rise to a nonuniform shear distribution around the control perimeter • Refer to Cl. 6.4.3(3) of EC2 Design of Pad Footing Check for Shear (ii) Punching Shear (continued) Shear stress, 𝒗𝑬𝒅 = 𝜷𝑽𝑬𝒅 𝒖𝟏 ∙𝒅 where; = factor used to include effect of eccentric load & bending moment = 1+𝑘 𝑀𝐸𝑑 𝑉𝐸𝑑 𝑢1 𝑊1 k = coefficient depending on the ratio between column dimension c1 & c2 c1/c2 0.5 1.0 2.0 3.0 k 0.45 0.60 0.70 0.80 u1 = length of basic control perimeter W1 = function of basic control perimeter corresponds to the distribution of shear = 0.5𝑐1 2 + 𝑐1 𝑐2 + 4𝑐2 𝑑 + 16𝑑 2 + 2𝜋𝑑𝑐1 Design of Pad Footing Check for Shear (ii) Punching Shear (continued) Design of Pad Footing Cracking & Detailing Requirements • All reinforcements should extend the full length of the footing • If 𝐿𝑥 > 1.5 𝑐𝑥 + 3𝑑 , at least two-thirds of the reinforcement parallel to Ly should be concentrated in a band width 𝑐𝑥 + 3𝑑 centred at column where Lx & Ly and cx & cy are the footing and column dimension in x and y directions • Reinforcements should be anchored each side of all critical sections for bending. Usually possible to achieve using straight bar • Spacing between centre of reinforcements 20 mm for fyk = 500 N/mm2 • Reinforcements normally not provided in the side face nor in the top face (except for balanced & combined foundation) • Starter bar should terminate in a 90 bend tied to the bottom reinforcement, or in the case of unreinforced footing spaced 75 mm off the building Example 1 PAD FOOTING (AXIAL LOAD ONLY) Example 1: Pad Footing (Axial Load) Axial Force, N: Gk = 600 kN Qk = 400 kN Column size: 300 300 mm h B H • • • • • • • fck = 25 N/mm2 fyk = 500 N/mm2 soil = 150 N/mm2 Unit weight of concrete = 25 kN/m3 Design life = 50 years Exposure Class = XC2 Assumed bar = 12 mm Example 1: Pad Footing (Axial Load) Durability & Bond Requirements Min cover regards to bond, cmin,b = 12 mm Min cover regards to durability, cmin,dur = 25 mm Allowance in design for deviation, cdev = 10 mm Nominal cover, cnom = cmin + cdev = 25 + 10 = 35 mm cnom = 35 mm cmin = 25 mm Example 1: Pad Footing (Axial Load) Size Service load, N Assumed selfweight 10% of service load , W Area of footing required = 𝑁+𝑊 𝛾𝑠𝑜𝑖𝑙 = = 1000 kN = 100 kN 1000+100 150 = 7.33 𝑚2 Try footing size, B H h = 3 m 3 m 0.45 m Area, A = 9 m2 Selfweight, W = 9 0.45 25 = 101 kN Check Service Soil Bearing Capacity = = 122 kN/m2 150 kN/m2 OK 𝑵+𝑾 𝑨 = 𝟏𝟎𝟎𝟎+𝟏𝟎𝟏 𝟗 Example 1: Pad Footing (Axial Load) Analysis Ultimate axial force, NEd = 1.35Gk + 1.5Qk = 1.35 (600) + 1.5 (400) = 1410 kN 𝑁 1410 Soil pressure at ultimate load, P = 𝐸𝑑 = = 157 kN/m2 𝐴 9 Soil pressure per m length, w = 157 3 m = 470 kN/m 0.3 m 1.35 m w = 470 kN/m 1.35 m Example 1: Pad Footing (Axial Load) Analysis Ultimate axial force, NEd = 1.35Gk + 1.5Qk = 1.35 (600) + 1.5 (400) = 1410 kN 𝑁 1410 Soil pressure at ultimate load, P = 𝐸𝑑 = = 157 kN/m2 𝐴 9 Soil pressure per m length, w = 157 3 m = 470 kN/m MEd 0.3 m 1.35 m w = 470 kN/m 1.35 m 𝟏. 𝟑𝟓 𝑴𝑬𝒅 = 𝟒𝟕𝟎 × 𝟏. 𝟑𝟓 × 𝟐 = 428 kNm Example 1: Pad Footing (Axial Load) Main Reinforcement Effective depth, d = h – c – 1.5bar = 450 – 35 – (1.5 12) = 397 mm 𝐾= 𝑀𝐸𝑑 𝑓𝑐𝑘 𝑏𝑑 2 = 428×106 25×3000×3972 = 0.036 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝐸𝑑 0.87𝑓𝑦𝑘 𝑧 = = 0.97𝑑 0.95d 428×106 0.87×500×0.95×397 = 𝟐𝟔𝟏𝟏 mm2 Example 1: Pad Footing (Axial Load) Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 2.56 𝑏𝑑 = 0.26 0.0013𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 = 0.0013bd = 0.0013 3000 397 = 1589 mm2 𝐴𝑠,𝑚𝑖𝑛 = 0.26 As,min As,max = 0.04Ac = 0.04bh = 0.04 3000 397 = 54000 mm2 Provide 24H12 (As,prov = 2715 mm2) Example 1: Pad Footing (Axial Load) (i) Vertical Shear 3m 1.35 m d = 397 mm VEd 953 mm 3m w = 470 kN/m 0.953 m Critical shear at 1.0d from face of column: Design shear force, VEd = 470 0.953 = 448 kN Example 1: Pad Footing (Axial Load) (i) Vertical Shear 𝑘 =1+ 200 𝑑 =1+ 200 397 = 1.71 2.0 Note: Bar extend beyond critical section at = 953 – 35 = 918 mm 𝑙𝑏𝑑 + 𝑑 = 40∅ + 𝑑 = 40 × 12 + 397 = 877 mm 𝐴𝑠𝑙 2715 𝜌𝑙 = = = 0.0023 ≤ 0.02 𝑏𝑑 3000 × 397 Asl = 2715 mm2 Example 1: Pad Footing (Axial Load) (i) Vertical Shear 𝑉𝑅𝑑,𝑐 = 0.12𝑘 100𝜌𝑙 𝑓𝑐𝑘 1/3 𝑏𝑑 = 0.12 × 1.71 100 × 0.0023 × 25 1/3 3000 × 397 = 436463 N = 436 kN 𝑉𝑚𝑖𝑛 = 0.035𝑘 3/2 𝑓𝑐𝑘 𝑏𝑑 = 0.035 × 1.713/2 25 3000 × 397 = 465970 𝑁 = 466 kN VEd (448 kN) Vmin (466 kN) OK Example 1: Pad Footing (Axial Load) (ii) Punching Shear Critical shear at 2.0d from face of column: Average d = 450 – 35 – 12 = 403 mm 2d = 806 mm 1350 2d = 806 Control perimeter, u = (4 300) + (2 806) = 6265 mm 300 2d = 806 300 Area within perimeter, A = (0.30 0.30) + (4 0.30 0.806) + ( 0.8062) = 3.10 m2 544 𝑙𝑏𝑑 + 𝑑 = 40∅ + 𝑑 = 40 × 12 + 397 = 877 mm Reinforcement NOT contributed to punching resistance Example 1: Pad Footing (Axial Load) (ii) Punching Shear Punching shear force: VEd = 157 (32 – 3.10) = 925 kN Aall = 9 m2 Aperimeter = 3.10 m2 Punching shear resistance: 𝑉𝑅𝑑,𝑐 = 𝑉𝑚𝑖𝑛 = 0.035𝑘 3/2 𝑓𝑐𝑘 1/2 𝑢𝑑 = 0.035 1.71 3/2 25 1/2 6265 × 403 = 983199 N = 983 kN VEd (925 kN) OK Soil pressure = 157 kN/m2 Example 1: Pad Footing (Axial Load) (iii) Maximum Punching Shear at Column Perimeter Maximum punching shear force: VEd,max = 157 (32 – 0.09) = 1400 kN Aall = 9 m2 Acolumn = 0.09 m2 Maximum shear resistance: 𝑓𝑐𝑘 = 0.5𝑢𝑑 0.6 1 − 250 𝑓𝑐𝑘 𝑉𝑅𝑑,𝑚𝑎𝑥 1.5 25 = 0.5 4 × 300 × 403 0.6 1 − 250 = 2176 kN VEd,max OK 25 1.5 Soil pressure = 157 kN/m2 Example 1: Pad Footing (Axial Load) Cracking h = 450 mm 200 mm Max bar spacing 𝐴𝑠.𝑟𝑒𝑞 𝐺𝑘 +0.3𝑄𝑘 Steel stress, 𝑓𝑠 = 1.35𝐺𝑘 +1.5𝑄𝑘 𝐴𝑠,𝑝𝑟𝑜𝑣 600+0.3×400 2611 500 = = 213 1.35×600+1.5×400 2715 1.15 𝑓𝑦𝑘 1.15 N/mm2 For design crack width 0.3 mm: Maximum allowable bar spacing = 200 mm Actual bar spacing = 3000−2 35 −12 23 = 127 mm 200 mm Cracking OK Example 1: Pad Footing (Axial Load) Detailing 24H12 3000 24H12 3000 450 3000 24H12 Plan View Section View Example 2 PAD FOOTING (AXIAL LOAD & MOMENT) Example 2: Pad Footing (Axial Load & Moment) Axial Force, N = 1500 kN Moment = 50 kNm Column size: 250 350 mm h B H • Design Life = 50 years (Table 2.1: EN 1990) • Exposure Class = XC3 • fck = 30 N/mm2 • fyk = 500 N/mm2 • soil = 150 N/mm2 • Unit weight of concrete = 25 kN/m3 • Assumed bar = 12 mm Example 2: Pad Footing (Axial Load & Moment) Durability & Bond Requirements Min cover regards to bond, cmin,b = 12 mm Min cover regards to durability, cmin,dur = 25 mm Allowance in design for deviation, cdev = 10 mm Nominal cover, cnom = cmin + cdev = 25 + 10 = 35 mm cnom = 35 mm cmin = 25 mm Example 2: Pad Footing (Axial Load & Moment) Size Service axial, N Service moment, M Assumed selfweight 10% of service load , W Area of footing required = 𝑁+𝑊 𝛾𝑠𝑜𝑖𝑙 = 1071+107.1 150 = 1500 kN / 1.40 = 1071 kN = 50 kNm / 1.40 = 36.1 kNm = 100 kN = 7.85 𝑚2 Try footing size, B H h = 2.80 m 3.50 m 0.65 m Area, A = 9.80 m2 Selfweight, W = 9.80 0.65 25 = 159 kN Example 2: Pad Footing (Axial Load & Moment) Size (Continued) 𝐵𝐻 3 2.8×3.53 𝐼𝑥𝑥 = = = 12 12 𝐻 3.5 𝑦= = = 1.75 m 2 2 10.0 m4 Maximum soil pressure, 𝑃 = = 132 kN/m2 150 kN/m2 𝑁+𝑊 𝐴 𝑀𝑦 + = 𝐼 OK 1071+159 9.80 + 50×1.75 10.0 B x H x Example 2: Pad Footing (Axial Load & Moment) Analysis Ultimate soil pressure, 𝑃 = 50×1.75 10.0 𝑁 𝐴 ± 𝑀𝑦 𝐼 = 1500 9.80 x ± = 153 ± 8.7 kN/m2 1.275 Pmin = 144 kN/m2 and Pmax = 162 kN/m2 y y x 0.35 m 1.575 m 1.575 m 144 162 144 154 162 Example 2: Pad Footing (Axial Load & Moment) Analysis (Continued) 𝑀𝑥𝑥 x 1.5752 = 154 × 2 1.275 1.575 2 × 1.575 × 2 3 = 197 kNm/m 2.80 m = 553 kNm + 162 − 154 𝑀𝑦𝑦 = 𝟏𝟓𝟑 1.2752 × 2 y y x = 124 kNm/m 3.50 m = 0.35 m 1.575 m 435 kNm = 144 + 162 2 144 1.575 m 154 162 Example 2: Pad Footing (Axial Load & Moment) Effective Depth dx = h – c – 0.5bar = 650 – 35 – (0.5 12) = 609 mm dy = h – c – 1.5bar = 650 – 35 – (1.5 12) = 597 mm Main Reinforcement – Longitudinal Bar 𝐾= 𝑀𝑥𝑥 𝑓𝑐𝑘 𝑏𝑑 2 = 553×106 30×2800×6092 = 0.018 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝑥𝑥 0.87𝑓𝑦𝑘 𝑧 = = 0.98𝑑 0.95d 553×106 0.87×500×0.95×609 = 𝟐𝟏𝟗𝟕 mm2 Example 2: Pad Footing (Axial Load & Moment) Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 2.90 𝑏𝑑 = 0.26 0.0013𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 = 0.0013bd = 0.0013 2800 609 = 2217 mm2 𝐴𝑠,𝑚𝑖𝑛 = 0.26 As,min As,max = 0.04Ac = 0.04bh = 0.04 2800 609 = 72800 mm2 Since As As,min, Use As,min = 2217 mm2 Provide 21H12 (As = 2375 mm2) Example 2: Pad Footing (Axial Load & Moment) Main Reinforcement – Transverse Bar 𝐾= 𝑀𝑦𝑦 𝑓𝑐𝑘 𝑏𝑑 2 = 435×106 30×3500×5972 = 0.018 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝑦𝑦 0.87𝑓𝑦𝑘 𝑧 = = 0.99𝑑 0.95d 435×106 0.87×500×0.95×597 = 𝟏𝟕𝟔𝟓mm2 Example 2: Pad Footing (Axial Load & Moment) Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 2.90 𝑏𝑑 = 0.26 0.0013𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 = 0.0013bd = 0.0013 3500 597 = 3147 mm2 𝐴𝑠,𝑚𝑖𝑛 = 0.26 As,min As,max = 0.04Ac = 0.04bh = 0.04 3500 597 = 91000 mm2 Since As As,min, Use As,min = 3147 mm2 Provide 28H12 (As = 3167 mm2) Example 2: Pad Footing (Axial Load & Moment) (i) Vertical Shear 2.891 Critical shear at 1.0d from face of column: 2.8 Average pressure at critical section: 2.891 3.50 × 18 = 159 kN/m2 d = 0.609 = 144 + Design shear force, VEd = 159 0.966 2.80 = 431 kN 0.966 144 159 Note: Bar extend beyond critical section at = 966 – 35 = 931 mm 𝑙𝑏𝑑 + 𝑑 = 36∅ + 𝑑 = 36 × 12 + 609 = 1041 mm 162 Asl = 0 mm2 Example 2: Pad Footing (Axial Load & Moment) (i) Vertical Shear 𝑘 = 1+ 𝜌𝑙 = 200 𝑑 =1+ 200 609 = 1.57 2.0 𝐴𝑠𝑙 =0 𝑏𝑑 𝑉𝑅𝑑,𝑐 = 0.12𝑘 100𝜌𝑙 𝑓𝑐𝑘 1/3 𝑏𝑑 = 0.12 × 1.57 100 × 0 × 30 1/3 2800 × 609 = 0 N = 0 kN 𝑉𝑚𝑖𝑛 = 0.035𝑘 3/2 𝑓𝑐𝑘 𝑏𝑑 = 0.035 × 1.573/2 30 2800 × 609 = 644949 𝑁 = 645 kN VEd (430 kN) Vmin (645 kN) OK Example 2: Pad Footing (Axial Load & Moment) (ii) Punching Shear Critical shear at 2.0d from face of column: 609+597 = 603 mm 3500 Control perimeter; u = 2(350 + 250) + (2 1206) = 8779 mm 2d = 1206 350 2d = 1206 250 Area within perimeter; A = (0.35 0.25) + (2 0.35 1.206) + (2 0.25 1.206) + ( 1.2062) = 6.10 m2 2800 Average 𝑑 = 2 2d = 1206 mm 69 369 𝑙𝑏𝑑 + 𝑑 = 36∅ + 𝑑 = 36 × 12 + 609 = 1041 mm Reinforcement NOT contributed to punching resistance Example 2: Pad Footing (Axial Load & Moment) (ii) Punching Shear Average punching shear force at control perimeter: VEd = 153 [(2.80 3.50) – 6.10] = 566 kN Punching shear stress: 𝛽𝑉𝐸𝑑 𝑣𝐸𝑑 = 𝑢𝑑 𝑀 Where 𝛽 = 1 + 𝑘 𝑉 𝐸𝑑 k = 0.65 𝐸𝑑 𝑐1 𝑐2 Aall = 2.8 3.5 m Aperimeter = 6.10 m2 𝑢1 𝑊1 350 = 250 = 1.4 W1 = 0.5𝑐1 2 + 𝑐1 𝑐2 + 4𝑐2 𝑑 + 16𝑑 2 + 2𝜋𝑑𝑐1 = 0.5(3502 ) + 350 × 250 + 4 × 250 × 603 + 16 6032 + 2𝜋 × 603 × 350 = 7.9 106 mm2 𝛽 = 1 + 0.65 50×106 566×103 Therefore, 𝒗𝑬𝒅 = 𝟏.𝟎𝟔×𝟓𝟔𝟔×𝟏𝟎𝟑 𝟖𝟕𝟕𝟗×𝟔𝟎𝟗 8779 7.9×106 = 1.06 = 𝟎. 𝟏𝟏 N/mm2 Soil pressure = 153 kN/m2 Example 2: Pad Footing (Axial Load & Moment) (ii) Punching Shear Punching shear resistance: Aall = 2.8 3.5 m 𝑘 = 1+ 200 𝑑 =1+ 200 609 = 1.57 2.0 𝑣𝑅𝑑,𝑐 = 𝑣𝑚𝑖𝑛 = 0.035𝑘 3/2 𝑓𝑐𝑘 1/2 = 0.035 1.57 3/2 30 1/2 = 0.38 N/mm2 vEd (0.11 N/mm2) Aperimeter = 6.10 m2 OK Soil pressure = 153 kN/m2 Example 2: Pad Footing (Axial Load & Moment) (iii) Maximum Punching Shear at Column Perimeter Maximum punching shear force: VEd,max = 1500 kN Column perimeter, uo = 2(350 + 250) = 1200 mm Punching shear stress: 𝛽𝑉𝐸𝑑 𝑣𝐸𝑑 = 𝑢𝑜 𝑑 𝑀 Where 𝛽 = 1 + 𝑘 𝐸𝑑 k = 0.65 𝑉𝐸𝑑 𝑐1 = 𝑐2 𝑢𝑜 𝑊1 350 250 Aall = 2.8 3.5 m = 9.8 m2 Acolumn = 0.09 m2 Soil pressure = 153 kN/m2 = 1.4 W1 = 0.5𝑐1 2 + 𝑐1 𝑐2 = 0.5(3502 ) + 350 × 250 = 0.15 106 mm2 Example 2: Pad Footing (Axial Load & Moment) (iii) Maximum Punching Shear at Column Perimeter 𝛽 = 1 + 0.65 50×106 1500×103 Therefore, 𝒗𝑬𝒅 = 𝟏.𝟏𝟕×𝟏𝟓𝟎𝟎×𝟏𝟎𝟑 𝟏𝟐𝟎𝟎×𝟔𝟎𝟑 1200 0.15×106 Maximum shear resistance: 𝑓𝑐𝑘 𝑣𝑅𝑑,𝑚𝑎𝑥 = 0.5 0.6 1 − 250 30 30 = 0.5 0.6 1 − 250 1.5 = 5.28 N/mm2 vEd = 1.17 = 𝟐. 𝟒𝟒 N/mm2 Aall = 2.8 3.5 m = 9.8 m2 Acolumn = 0.09 m2 𝑓𝑐𝑘 1.5 Soil pressure = 153 kN/m2 OK Example 2: Pad Footing (Axial Load & Moment) Cracking h = 650 mm 200 mm Max bar spacing Assume steel stress is under quasi-permanent loading: = 0.6 𝑓𝑦𝑘 𝐴𝑠,𝑟𝑒𝑞 1.15 𝐴𝑠,𝑝𝑟𝑜𝑣 = 0.6 500 1.15 2197 2375 = 241 N/mm2 For design crack width 0.3 mm: Maximum allowable bar spacing = 150 mm 2800−2 35 −12 = 136 mm 150 mm 20 3500−2 35 −12 = 126 mm 150 mm 27 Actual bar spacing at x-x = ctual bar spacing at y-y = Cracking OK Example 2: Pad Footing (Axial Load & Moment) Detailing 21H12 2800 28H12 3500 650 3500 21H12 28H12 Plan View Section View Example 3 DESIGN OF COMBINED FOOTING Example 3: Design of Combined Footing NA = 1610 kN (Ultimate) NB = 1950 kN (Ultimate) 3.4 m Column size: 300 300 mm Column size: 400 400 mm h B H • • • • • • fck = 35 N/mm2 fyk = 500 N/mm2 soil = 200 N/mm2 Unit weight of concrete = 25 kN/m3 Cover = 40 mm Assumed bar = 12 mm Example 3: Design of Combined Footing Size Service axial: NA NB Total service axial, Ntotal = 1610 kN / 1.40 = 1150 kN = 1950 kN / 1.40 = 1393 kN = 1150 + 1393 = 2543 kN Assumed selfweight 10% of service load , W = 254.3 kN Area of footing required = 𝑁+𝑊 𝛾𝑠𝑜𝑖𝑙 = 2543+254.3 200 = 14.0 𝑚2 Try footing size, B H h = 2.70 m 6.00 m 0.65 m Area, A = 16.2 m2 Selfweight, W = 16.2 0.65 25 = 252.7 kN Example 3: Design of Combined Footing Size (Continued) 𝑁+𝑊 𝐴 Check Service Soil Bearing Capacity = = 173 kN/m2 200 kN/m2 OK = 2543+252.7 16.2 Arrange position of footing so that the distribution of soil pressure is uniform: Ntotal = 2543 kN NA = 1150 kN NB = 1393 kN x 3.4 m MA = 0 1393(3.4 ) + 2543x = 0 x = 1.86 m Example 3: Design of Combined Footing Analysis 𝑁 (1610+1950) Soil pressure at ultimate load, P = 𝐸𝑑 = = 219.8 kN/m2 𝐴 16.2 Soil pressure per m width, w = 219.8 2.7 m = 593.5 kN/m Example 3: Design of Combined Footing Shear Force & Bending Moment Diagram 3m 3m 1610 kN 0.3 0.99 1950 kN 1.34 1.71 1.26 0.4 0.65 x = 1.86 593.5 kN/m 1082 964 587 676 1.62 1.43 SFD (kN) 868 934 749 846 353 289 250 384 BMD (kNm) 473 430 634 Example 3: Design of Combined Footing Main Reinforcement Longitudinal Reinforcement: Bottom Effective depth: dx = h – c – 0.5bar = 650 – 40 – (0.5 12) = 604 mm 𝐾= 𝑀𝐸𝑑 𝑓𝑐𝑘 𝑏𝑑 2 = 473×106 35×2700×6042 = 0.014 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝐸𝑑 0.87𝑓𝑦𝑘 𝑧 = = 0.99𝑑 0.95d 473×106 0.87×500×0.95×604 = 𝟏𝟖𝟗𝟒 mm2 As,min = 2722 mm2 Example 3: Design of Combined Footing Main Reinforcement Longitudinal Reinforcement: Top 𝐾= 𝑀𝐸𝑑 𝑓𝑐𝑘 𝑏𝑑 2 = 353×106 35×2700×6042 = 0.010 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝐸𝑑 0.87𝑓𝑦𝑘 𝑧 = = 0.99𝑑 0.95d 353×106 0.87×500×0.95×604 = 𝟏𝟒𝟏𝟑 mm2 As,min = 2722 mm2 Example 3: Design of Combined Footing Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 3.2 𝐴𝑠,𝑚𝑖𝑛 = 0.26 𝑏𝑑 = 0.26 0.0017𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 As,min = 0.0017bd = 0.0017 2700 604 = 2722 mm2 As,max = 0.04Ac = 0.04bh = 0.04 2700 650 = 70200 mm2 Provide 25H12 at both top and bottom (As,prov = 2828 mm2) Example 3: Design of Combined Footing Main Reinforcement Transverse Reinforcement: Bottom Consider b = 1000 mm: Soil pressure per 1 m width, w = 219.8 1.0 m = 219.8 kN/m MEd 0.3 m 1.2 m w = 219.8 kN/m 1.2 m 𝟏. 𝟐 𝑴𝑬𝒅 = 𝟐𝟏𝟗. 𝟖 × 𝟏. 𝟐 × 𝟐 = 158 kNm/m Example 3: Design of Combined Footing Main Reinforcement Transverse Reinforcement: Bottom Effective depth: dy = h – c – 1.5bar = 650 – 40 – (1.5 12) = 592 mm 𝐾= 𝑀𝐸𝑑 𝑓𝑐𝑘 𝑏𝑑 2 = 158×106 35×𝟏𝟎𝟎𝟎×5922 = 0.013 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝐸𝑑 0.87𝑓𝑦𝑘 𝑧 = = 0.99𝑑 0.95d 158×106 0.87×500×0.95×592 = 𝟔𝟒𝟕 mm2/m As,min = 988 mm2/m Example 3: Design of Combined Footing Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 3.2 𝐴𝑠,𝑚𝑖𝑛 = 0.26 𝑏𝑑 = 0.26 0.0017𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 As,min = 0.0017bd = 0.0017 1000 592 = 988 mm2/m As,max = 0.04Ac = 0.04bh = 0.04 1000 650 = 26000 mm2/m Since As As,min, then use As,min = 988 mm2/m Provide H12-100 (As,prov = 1131 mm2/m) For secondary bar reinforcement: Provide H12-100 (As,prov = 1131 mm2/m) Example 3: Design of Combined Footing (i) Vertical Shear Critical shear at 1.0d from face of column: VEd 964 𝑉𝐸𝑑 = 1.02 1.62 × 964 = 𝟔𝟎𝟓 kN 587 1082 676 1.43 1.02 𝑘 = 1+ 𝜌𝑙 = 200 𝑑 =1+ 200 604 = 1.6 2.0 934 846 d = 0.604 868 749 1.62 𝐴𝑠𝑙 2828 = = 0.0017 ≤ 0.02 𝑏𝑑 2700 × 604 𝑉𝑅𝑑,𝑐 = 0.12𝑘 100𝜌𝑙 𝑓𝑐𝑘 1/3 𝑏𝑑 = 0.12 × 1.6 100 × 0.0017 × 35 1/3 2700 × 604 = 562369 N = 562.4 kN 𝑉𝑚𝑖𝑛 = 0.035𝑘 3/2 𝑓𝑐𝑘 𝑏𝑑 = 0.035 × 1.63/2 35 2700 × 604 = 6667734 𝑁 = 667 kN VEd (605 kN) Vmin (667 kN) OK Example 3: Design of Combined Footing (ii) Punching Shear Critical shear at 2.0d from face of column: 604+592 = 598 mm 2d = 1196 400 2d = 1196 400 Control perimeter; u = 2(400 + 400) + (2 1196) = 9116 mm Area within perimeter; A = (0.40 0.40) + (2 0.40 1.196) + (2 0.40 1.196) + ( 1.1962) = 6.57 m2 104 2700 Average 𝑑 = 2 2d = 1196 mm Example 3: Design of Combined Footing (ii) Punching Shear Average punching shear force at control perimeter: VEd = 1950 – (219.8 6.57) = 506 kN Punching shear stress: 𝑣𝐸𝑑 = 𝑉𝐸𝑑 𝑢𝑑 = 506×103 9116×598 = 0.09 N/mm2 Aperimeter = 6.57 m2 Punching shear resistance: 𝑘 =1+ 200 𝑑 =1+ 200 609 3/2 = 1.57 2.0 1/2 𝑣𝑅𝑑,𝑐 = 𝑣𝑚𝑖𝑛 = 0.035𝑘 𝑓𝑐𝑘 = 0.035 1.6 3/2 35 1/2 = 0.41 N/mm2 vEd (0.09 N/mm2) OK Soil pressure = 219.8 kN/m2 Example 3: Design of Combined Footing (iii) Maximum Punching Shear at Column Perimeter Maximum punching shear force: VEd,max = 1950 kN Column perimeter, uo = 4 400 = 1600 mm Acolumn = 0.16 m2 Maximum shear resistance: 𝑉𝑅𝑑,𝑚𝑎𝑥 𝑓𝑐𝑘 = 0.5𝑢𝑑 0.6 1 − 250 35 250 OK = 0.5 × 1600 × 598 0.6 1 − = 2880 kN VEd,max 𝑓𝑐𝑘 1.5 35 1.5 Soil pressure = 219.8 kN/m2 Example 3: Design of Combined Footing Cracking h = 650 mm 200 mm Max bar spacing Assume steel stress is under quasi-permanent loading: = 0.6 𝑓𝑦𝑘 𝐴𝑠,𝑟𝑒𝑞 1.15 𝐴𝑠,𝑝𝑟𝑜𝑣 = 0.6 500 1.15 1894 2828 = 175 N/mm2 For design crack width 0.3 mm: Maximum allowable bar spacing = 250 mm Actual bar spacing 1 = 2700−2 40 −12 24 2700−2 40 −12 24 = 109 mm 250 mm Actual bar spacing 2 = = 109 mm 250 mm Actual bar spacing 3 = 100 mm 250 mm Cracking OK Example 4 DESIGN OF STRAP FOOTING Example 4: Design of Strap Footing NB Gk = 1000 kN, Qk = 525 kN NA Gk = 800 kN, Qk = 275 kN 6000 • • • • • • Beam size: 300 900 mm Column size: 300 300 mm Column size: 300 300 mm 700 RA RB H S 2000 S fck = 30 N/mm2 fyk = 500 N/mm2 soil = 200 N/mm2 Unit weight of concrete = 25 kN/m3 Cover = 40 mm Assumed bar = 12 mm Example 4: Design of Strap Footing Loading Column Size (mm × mm) Load (kN) Gk Qk Total (1.0Gk + 1.0Qk) Column A 300 × 300 800 275 1075 Column B 300 × 300 1000 525 1525 Example 4: Design of Strap Footing Size Assumed self weight of footing is 10% of service load: WA = 108 kN and WB = 153 kN Beam self weight, WR = 25 (0.3 0.9 5.7) = 38 kN Example 4: Design of Strap Footing 𝑀@𝐵 = 0 Size 𝑅𝐴 − 𝑊𝐴 6.15 − 1.0 − 𝑁𝐴 6.0 − 𝑊𝑅 3.0 = 0 𝑅𝐴 − 108 6.15 − 1.0 − 1075 6.0 − 38 3.0 =0 𝑅𝐴 − 108 = 1275 RA = 1382 kN NB = 1525 kN NA = 1075 kN 6m 𝑅𝐴 = 200 2.0𝐻 1382 = 200 2.0𝐻 WR 0.3 m WA RA Footing A size: 2.00 × 3.50 m 0.3 m WB 0.7 m 𝑅𝐴 + 𝑅𝐵 = 𝑁𝐴 + 𝑁𝐵 + 𝑊𝐴 + 𝑊𝐵 + 𝑊𝑅 𝑅𝐴 + 𝑅𝐵 = 1075 + 1525 + 108 + 153 + 38 𝑅𝐵 = 2898 − 𝑅𝐴 𝑅𝐵 = 2898 − 1382 RA = 1516 kN RB H S 2m S H = 3.46 mm 𝑅𝐵 = 200 𝑆2 1516 = 200 𝑆2 S = 2.75 mm Footing B size: 2.75 × 2.75 m Example 4: Design of Strap Footing Footing Size Checks Total service load = 1075 + 1525 + 123 + 132 + 38 = 2893 kN Area of footing = (2.0 3.5) + (2.75 2.75) = 14.56 m2 Soil pressure = 2893 14.56 = 199 kN/m2 200 kN/m2 OK Example 4: Design of Strap Footing NA = 1075 kN NB = 1525 kN 6m R = 2893 kN Footing Self Weight X’ 0.3 m 0.3 m WA = 123 kN WA = 25 (2.0 3.5 0.7) = 123 kN WB = 25 (2.75 2.75 0.7) = 132 kN WR = 38 kN 2m Distance from resultant force R to centroid of column B: 1075 × 6.0 + 123 × 5.15 + 38 × 3.0 = 2893𝑋 ′ X’ = 2.48 m Distance from centroid of footings to centroid of column B: 2.0 × 3.50 5.15 = 2.0 × 3.5 + 2.75 × 2.75 𝑋′ X’ = 2.48 m WB = 132 kN 2.75 m Example 4: Design of Strap Footing Analysis Design Load: NA = (1.35 800) + (1.50 275) NB = (1.35 1000) + (1.50 525) WA = 1.35 123 WB = 1.35 132 WR = 1.35 38 = 1493 kN = 2138 kN = 165 kN = 179 kN = 52 kN Total Design Load, Ptotal = 4026 kN Ultimate soil pressure = 𝑃𝑡𝑜𝑡𝑎𝑙 𝐴𝑟𝑒𝑎 𝑜𝑓 𝐹𝑜𝑜𝑡𝑖𝑛𝑔 = 4026 14.56 = 276 kN/m2 Example 4: Design of Strap Footing Shear Force & Bending Moment Diagram 1493 kN 2138 kN 2.775 1.7 1.225 0.3 0.3 52 5.7 276.5 − 1.225 165 2.0×3.5 = 9.1 kN/m = 253 × 3.5 = 885 kN/m 1.40 276.5 − 179 2.75×2.75 = 253 × 2.75 = 695 kN/m 1077 262 SFD (kN) 237 -852 -1227 -1044 . -1004 BMD (kNm) -313 492 522 Example 4: Design of Strap Footing DESIGN OF FOOTING A Main Reinforcement Soil pressure, w = 253 2.0 m = 506 kN/m MEd 0.3 m 1.6 m 1.6 m 𝟏. 𝟔 𝑴𝑬𝒅 = 𝟓𝟎𝟔 × 𝟏. 𝟔 × 𝟐 = 647 kNm w = 506 kN/m Effective depth: d = h – c – 0.5bar = 700 – 40 – (0.5 16) = 652 mm Example 4: Design of Strap Footing 𝐾= 𝑀𝐸𝑑 𝑓𝑐𝑘 𝑏𝑑2 = 647×106 30×2000×6522 = 0.025 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝐸𝑑 0.87𝑓𝑦𝑘 𝑧 = = 0.98𝑑 0.95d 647×106 0.87×500×0.95×652 = 𝟐𝟒𝟎𝟐 mm2/m As,min Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 2.90 𝐴𝑠,𝑚𝑖𝑛 = 0.26 𝑏𝑑 = 0.26 0.0015𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 As,min = 0.0015bd = 0.0015 2000 652 = 1964 mm2 or 982 mm2/m As,max = 0.04Ac = 0.04bh = 0.04 2000 700 = 56000 mm2 Main Reinforcement: Provide 14H16 (As,prov = 2815 mm2) Secondary Reinforcement: H16-200 (As,prov = 1005 mm2/m) Example 4: Design of Strap Footing (i) Vertical Shear 3.5 2.552 Critical shear at 1.0d from face of column: d = 0.652 2.0 0.948 Design shear force, VEd = 253 0.948 2.0 = 479.4 kN Note: Bar extend beyond critical section at = 948 – 40 = 908 mm 𝑙𝑏𝑑 + 𝑑 = 36∅ + 𝑑 = 36 × 16 + 652 = 1228 mm Asl = 0 mm2 Example 4: Design of Strap Footing (i) Vertical Shear 𝑘 = 1+ 𝜌𝑙 = 200 𝑑 =1+ 200 652 = 1.55 2.0 𝐴𝑠𝑙 =0 𝑏𝑑 𝑉𝑅𝑑,𝑐 = 0.12𝑘 100𝜌𝑙 𝑓𝑐𝑘 1/3 𝑏𝑑 = 0.12 × 1.55 100 × 0 × 30 1/3 3500 × 652 = 0 N = 0 kN 𝑉𝑚𝑖𝑛 = 0.035𝑘 3/2 𝑓𝑐𝑘 𝑏𝑑 = 0.035 × 1.553/2 30 3500 × 652 = 484194 𝑁 = 484.2 kN VEd (479.4 kN) Vmin (484.2 kN) OK Example 4: Design of Strap Footing Cracking h = 700 mm 200 mm Max bar spacing Assume steel stress is under quasi-permanent loading: = 0.59 𝑓𝑦𝑘 𝐴𝑠,𝑟𝑒𝑞 1.15 𝐴𝑠,𝑝𝑟𝑜𝑣 = 0.59 500 1.15 2402 2815 = 219 N/mm2 For design crack width 0.3 mm: Maximum allowable bar spacing = 200 mm Actual bar spacing = 2000−2 40 −16 13 = 146 mm 200 mm Cracking OK Example 4: Design of Strap Footing DESIGN OF FOOTING B Main Reinforcement Soil pressure, w = 253 2.75 m = 695.75 kN/m MEd 0.3 m 1.225 m 1.225 m 𝟏. 𝟐𝟐𝟓 𝑴𝑬𝒅 = 𝟔𝟗𝟓. 𝟕𝟓 × 𝟏. 𝟐𝟐𝟓 × 𝟐 = 522 kNm w = 695.75 kN/m Effective depth: d = h – c – 1.5bar = 700 – 40 – (1.5 16) = 636 mm Example 4: Design of Strap Footing 𝐾= 𝑀𝐸𝑑 𝑓𝑐𝑘 𝑏𝑑2 522×106 30×2750×6362 = = 0.016 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝐸𝑑 0.87𝑓𝑦𝑘 𝑧 = = 0.99𝑑 0.95d 522×106 0.87×500×0.95×636 = 𝟏𝟗𝟖𝟓 mm2/m As,min = 2623 mm2 Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 2.90 𝐴𝑠,𝑚𝑖𝑛 = 0.26 𝑏𝑑 = 0.26 0.0015𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 As,min = 0.0015bd = 0.0015 2750 636 = 2623 mm2 As,max = 0.04Ac = 0.04bh = 0.04 2750 700 = 77000 mm2 Main Reinforcement: Provide 15H16 (As,prov = 3016 mm2) Example 4: Design of Strap Footing (i) Vertical Shear 2.75 d = 0.636 2.75 2.161 Critical shear at 1.0d from face of column: 0.589 Design shear force, VEd = 253 0.589 2.75 = 409.5 kN Note: Bar extend beyond critical section at = 589 – 40 = 549 mm 𝑙𝑏𝑑 + 𝑑 = 36∅ + 𝑑 = 36 × 16 + 636 = 1212 mm Asl = 0 mm2 Example 4: Design of Strap Footing (i) Vertical Shear 𝑘 = 1+ 𝜌𝑙 = 200 𝑑 =1+ 200 636 = 1.56 2.0 𝐴𝑠𝑙 =0 𝑏𝑑 𝑉𝑅𝑑,𝑐 = 0.12𝑘 100𝜌𝑙 𝑓𝑐𝑘 1/3 𝑏𝑑 = 0.12 × 1.56 100 × 0 × 30 1/3 2750 × 636 = 0 N = 0 kN 𝑉𝑚𝑖𝑛 = 0.035𝑘 3/2 𝑓𝑐𝑘 𝑏𝑑 = 0.035 × 1.563/2 30 2750 × 636 = 653774 𝑁 = 653.8 kN VEd (409.5 kN) Vmin (653.8 kN) OK Example 4: Design of Strap Footing Cracking h = 700 mm 200 mm Max bar spacing Assume steel stress is under quasi-permanent loading: = 0.54 𝑓𝑦𝑘 𝐴𝑠,𝑟𝑒𝑞 1.15 𝐴𝑠,𝑝𝑟𝑜𝑣 = 0.54 500 1.15 2623 3016 = 204 N/mm2 For design crack width 0.3 mm: Maximum allowable bar spacing = 200 mm Actual bar spacing = 2750−2 40 −16 14 = 189 mm 200 mm Cracking OK Example 4: Design of Strap Footing DESIGN OF TIE BEAM Design similar to beam design. Refer to RC1. Moment Design for Flexural Reinforcement 5H32 Shear Design for Shear Links H6-150 Cracking Checks DESIGN OF PILE FOUNDATIONS Design of Pile Foundation • To be used when the soil conditions are poor and uneconomical, or not possible to provide adequate spread foundations • The piles must extend down to firm soil • Load carried by either end bearing, friction or combination of both Design of Pile Foundation Load from Structure Pile Cap Lower Density Medium Density High Density P I L E P I L E P I L E P I L E Design of Pile Foundation Selection of Piles Type • Depends on loading, type of structure, soil strata & site conditions • Main types: a) Precast reinforced or pre-stressed concrete piles b) Cast in-situ reinforced concrete piles c) Timber piles d) Steel piles e) Bakau piles Design of Pile Foundation Determination of Pile Capacity • Safe load: a) Determined from test loading of a pile or using a pile formula b) Ultimate load divided by safety factor between 2 & 3 c) Depends on size & depth, & whether the pile is of the end bearing or friction type • Pile formula – gives resistance from the energy of the driving force & the final set or penetration of the pile per blow Design of Pile Foundation Determination of Piles Number & Spacing • Pile load Single pile capacity • Piles are usually arranged symmetrically with respect to the column axis Design of Pile Foundation Determination of Piles Number & Spacing Foundation Subjected to Axial Load Only Load applied at centroid of the group of piles: 𝑵+𝑾 𝑭𝒂 = 𝒏 N = Axial load from column W = Self weight of pile cap n = Number of piles Design of Pile Foundation Determination of Piles Number & Spacing Foundation Subjected to Axial Load & Moment • • Pile cap assumed to rotate about the centroid of the pile group Piles load resisting moment vary uniformly from zero at the centroidal axis to a maximum for the piles farthest away 𝑭𝒂𝒊 𝑵+𝑾 𝑴𝒙𝒊 = ± 𝒏 𝑰𝒚 Fai = Load per pile i M = Moment xi = Distance from pile i to centroid of pile cap Iy = Moment of inertial of pile group = 𝑥1 2 + 𝑥2 2 + ⋯ + 𝑥𝑛 2 Design of Pile Cap Design of Pile Cap pile cap Design of Pile Cap Size & Thickness • Depends of number of piles used, arrangement of piles & shape of piles • Thickness of the cap should be sufficient to provide adequate bond length for bars projecting from the piles as well for the dowel bars of the column Design of Pile Cap Main Reinforcement • Using bending theory or truss theory • Truss Theory: Force from the supported column is assumed to be transmitted by a triangular truss action – concrete providing the compressive members of the truss & steel reinforcement providing tensile force Design of Pile Cap Truss Theory – Axial Force Design of Pile Cap Truss Theory – Axial Force Design of Pile Cap Pile Cap Size Design of Pile Cap Pile Cap Size Design of Pile Cap Design for Shear • Critical section taken to be 20% pile diameter (or p/5) inside the face of the column • Shear enhancement may be considered such that the shear resistance of the concrete maybe increased to 𝑽𝑹𝒅,𝒄 × 𝟐𝒅 𝒂𝒗 where av = distance from the face of column to the critical section • For spacing of piles 3 pile diameter, this enhancement may be applied across the whole critical section Design of Pile Cap Design for Shear • For spacing 3 pile diameter, then the pile cap should be checked for punching shear on the perimeter • Check shear force at column face 0.5𝑣1 𝑓𝑐𝑑 𝑢𝑑 = 𝑓𝑐𝑘 0.5𝑣1 1.5 𝑢𝑑 where u is the perimeter of the column and strength reduction factor, 𝑣1 = 0.6 1 − 𝑓𝑐𝑘 250 Design of Pile Cap Design for Shear /5 Vertical shear @ 1.0d from column face /5 Punching shear @ 2.0d from column face Design of Pile Cap Detailing of Reinforcement • Main tension reinforcement should continue pass each pile and bent-up vertically to provide full anchorage length beyond the centre line of each pile • Normal to provide fully lapped horizontal link of size 12 mm @ spacing 250 mm Design of Pile Cap Detailing of Reinforcement Starter bars for columns Links for starter bars Bars projecting into cap from piles Vertical links between bars extending from piles Horizontal links around upstanding end of main bars ( 12 mm @ 250 mm, say) Main bars design to resist tensile forces Example 5 DESIGN OF PILE CAP – TRUSS THEORY Example 5: Design of Pile Cap – Truss Theory N • Axial Load, N: o Gk = 3500 kN & Qk = 2500 kN • fck = 30 N/mm2 • fyk = 500 N/mm2 • soil = 200 N/mm2 • Unit weight of concrete = 25 kN/m3 • Column size = 500 mm 500 mm • Cover = 75 mm • Assumed bar = 25 mm • Pile: o Pre-stressed spun pile: 500 mm dia. o Working load = 1800 kN Example 5: Design of Pile Cap – Truss Theory Size of Pile Cap Service load = 3500 + 2500 = 6000 kN Assumed self weight of pile cap, say W = 200 kN Pile capacity, Fa = 1800 kN No. of pile required, 𝑛 = 𝑁+𝑊 𝐹𝑎 = (6000 + 200) 1800 = 3.4 Use n = 4 Pile spacing, 𝑙 = 𝑘∅𝑝 = 3∅𝑝 = 3 × 500 = 1500 mm Width, B = 𝑘 + 1 ∅𝑝 + 300 = 3 + 1 × 500 + 300 = 2300 mm Length, H = 𝑘 + 1 ∅𝑝 + 300 = 3 + 1 × 500 + 300 = 2300 mm Depth, h = 2∅𝑝 + 100 = 2 500 + 100 = 1100 mm Example 5: Design of Pile Cap – Truss Theory Size of Pile Cap (continued) Try size: B H h = 2.3 2.3 1.1 m Self weight = 25(2.3 2.3 1.1) = 145 kN 200 kN OK av = 750 – 250 – 250 + 500/5 = 350 400 p/5 = 100 400 d 400 1500 400 h = 1100 1500 Critical shear section Example 5: Design of Pile Cap – Truss Theory Main Reinforcement Effective depth, d = h – c – 1.5bar = 1100 – 75 – 1.5(25) = 988 mm Ultimate load, N = 1.35Gk + 1.5Qk = 1.35(3500) + 1.5(2500) = 8475 kN From truss analogy: 𝑁𝑙 8475×1.5 Tension force, 𝑇 = = = 𝟏𝟔𝟎𝟗 kN 8𝑑 8×0.988 Area of reinforcement, 𝐴𝑠 = 𝑇 0.87𝑓𝑦𝑘 = 1609×103 0.87×500 = 𝟑𝟔𝟗𝟗 mm2 For the whole width of pile cap, 𝐴𝑠 = 2 × 3699 = 𝟕𝟑𝟗𝟗 mm2 Example 5: Design of Pile Cap – Truss Theory Main Reinforcement (continued) Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 2.90 𝐴𝑠,𝑚𝑖𝑛 = 0.26 𝑏𝑑 = 0.26 0.0015𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 As,min = 0.0015bd = 0.0015 2300 988 = 3421 mm2 As,max = 0.04Ac = 0.04bh = 0.04 2300 1100 = 101200 mm2 Provide 16H25 (As,prov = 7855 mm2) Example 5: Design of Pile Cap – Truss Theory Shear (i) Vertical Shear Critical shear at p/5 section inside pile: 8475 Load per pile = = 2119 kN 4 2 pile outside critical section Shear force, VEd = 2 2119 = 4238 kN Pile spacing 3p Consider shear enhancement on the whole width of the section Reduced shear force, 𝑉𝐸𝑑 = 4238 × 𝑎𝑣 2𝑑 = 4238 × 350 2×988 = 𝟕𝟓𝟏 kN Example 5: Design of Pile Cap – Truss Theory Shear Note: Bar extend beyond critical section at = 475 + 988 – 75 = 1388 mm 𝑙𝑏𝑑 + 𝑑 = 36∅ + 𝑑 = 36 × 25 + 988 = 1888 mm Asl = 0 mm2 av = 750 – 250 – 250 + 500/5 = 350 400 100 1500 Critical section 400 1500 400 475 1388 h = 1100 400 475 Critical section Example 5: Design of Pile Cap – Truss Theory Shear 𝑘 =1+ 200 𝑑 =1+ 200 988 = 1.45 2.0 𝑉𝑅𝑑,𝑐 = 𝑉𝑚𝑖𝑛 = 0.035𝑘 3/2 𝑓𝑐𝑘 𝑏𝑑 = 0.035 × 1.453/2 30 2300 × 988 × 10−3 = 760 kN VEd (751 kN) Vmin (760 kN) OK Example 5: Design of Pile Cap – Truss Theory Shear (ii) Punching Shear at Perimeter 2.0d from Column Face Since pile spacing 3p No punching shear check in necessary Example 5: Design of Pile Cap – Truss Theory Shear (iii) Maximum Punching Shear at Column Perimeter 𝑉𝑅𝑑,𝑚𝑎𝑥 𝑓𝑐𝑘 = 0.5 0.6 1 − 250 = 0.5 0.6 1 − 30 250 30 1.5 𝑓𝑐𝑘 𝑢𝑑 1.5 4 × 500 × 988 = 10428 kN VEd,max = 8475 kN OK Example 5: Design of Pile Cap – Truss Theory Cracking h = 1100 mm 200 mm Max bar spacing Assume steel stress is under quasi-permanent loading: = 0.50 𝑓𝑦𝑘 𝐴𝑠,𝑟𝑒𝑞 1.15 𝐴𝑠,𝑝𝑟𝑜𝑣 = 0.50 500 1.15 7399 7855 = 205 N/mm2 For design crack width 0.3 mm: Maximum allowable bar spacing = 200 mm Actual bar spacing = 2300−2 75 −25 15 = 142 mm 200 mm Cracking OK Example 5: Design of Pile Cap – Truss Theory Detailing 5H16 Binders 1500 h = 1100 400 16H25 @ 140 mm 400 16H25 @ 140 mm 400 1500 400 500 mm spun pile Example 5 DESIGN OF PILE CAP – BEAM THEORY Example 5: Design of Pile Cap – Beam Theory N M • • • • • • • • • • Axial Load, Nultimate = 4200 kN Moment, Multimate = 75 kNm fck = 30 N/mm2 fyk = 500 N/mm2 soil = 200 N/mm2 Unit weight of concrete = 25 kN/m3 Column size = 400 mm 400 mm Cover = 75 mm Assumed bar = 16 mm Pile: o Precast RC pile: 300 mm 300 mm o Working load = 600 kN • Safety factor = 1.40 Example 5: Design of Pile Cap – Beam Theory Size of Pile Cap 4200 Service load = = 3000 kN 1.40 Assumed self weight of pile cap, say W = 200 kN Pile capacity, Fa = 600 kN No. of pile required, 𝑛 = 𝑁+𝑊 𝐹𝑎 = (3000 + 200) 600 = 5.3 Use n = 6 Example 5: Design of Pile Cap – Beam Theory Size of Pile Cap 4200 Service load = = 3000 kN 1.40 Assumed self weight of pile cap, say W = 200 kN Pile capacity, Fa = 600 kN No. of pile required, 𝑛 = 𝑁+𝑊 𝐹𝑎 = (3000 + 200) 600 = 5.3 Use n = 6 Example 5: Design of Pile Cap – Beam Theory Size of Pile Cap 4200 Service load = = 3000 kN 1.40 Assumed self weight of pile cap, say W = 200 kN Pile capacity, Fa = 600 kN No. of pile required, 𝑛 = 𝑁+𝑊 𝐹𝑎 = (3000 + 200) 600 = 5.3 Use n = 6 Pile spacing, 𝑙 = 𝑘∅𝑝 = 3∅𝑝 = 3 × 300 = 900 mm Width, B = 𝑘 + 1 ∅𝑝 + 300 = 3 + 1 × 300 + 300 = 1500 mm Length, H = 2𝑘 + 1 ∅𝑝 + 300 = 2 3 + 1 300 + 300 = 2400 mm Depth, h = 2∅𝑝 + 500 = 2 300 + 500 = 1100 mm Example 5: Design of Pile Cap – Beam Theory Size of Pile Cap (continued) Try size: B H h = 1.5 2.4 1.1 m Self weight = 25(1.5 2.4 1.1) = 99 kN 200 kN OK av = 1200 – 200 – 450 + 300/5 = 610 p/5 = 60 300 x y 300 y 900 Critical shear section x 300 900 900 300 I = 4(0.9)2 = 3.24 m2 Example 5: Design of Pile Cap – Beam Theory Analysis Service moment, Mservice = 75 1.40 = 53.6 kNm Maximum service load per pile, 𝐹 = = 3000+99 6 + 53.6×0.90 3.24 𝑁+𝑊 𝑛 + 𝑀𝑥 𝐼 = 531 kN 600 kN Ultimate load per pile: 𝑁 𝑀 𝑥 4200 75×0.90 𝐹𝑥𝑥 = 𝑢𝑙𝑡 + 𝑢𝑙𝑡 = + = 𝟕𝟐𝟏 kN 𝐹𝑦𝑦 = 𝑛 𝑁𝑢𝑙𝑡 𝑛 = 𝐼 4200 6 6 3.24 = 𝟕𝟎𝟎 kN Maximum moment at column face: 𝑀𝑥𝑥 = 2 721 × 0.90 − 0.20 = 𝟏𝟎𝟎𝟗 kNm 𝑀𝑦𝑦 = 3 700 × 0.45 − 0.20 = 𝟓𝟐𝟓 kNm OK Example 5: Design of Pile Cap – Beam Theory Main Reinforcement Effective depth: dx = h – c – 0.5bar = 1100 – 75 – 0.5(16) = 1017 mm dy = h – c – 1.5bar = 1100 – 75 – 1.5(16) = 1001 mm Longitudinal Bar 𝐾= 𝑀𝐸𝑑 𝑓𝑐𝑘 𝑏𝑑 2 = 1009×106 30×1500×10172 = 0.022 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝐸𝑑 0.87𝑓𝑦𝑘 𝑧 = = 0.98𝑑 0.95d 1009×106 0.87×500×0.95×1017 = 𝟐𝟒𝟎𝟏 mm2 Example 5: Design of Pile Cap – Beam Theory Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 2.90 𝐴𝑠,𝑚𝑖𝑛 = 0.26 𝑏𝑑 = 0.26 0.0015𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 As,min = 0.0015bd = 0.0015 1500 1017 = 2298 mm2 As,max = 0.04Ac = 0.04bh = 0.04 1500 1100 = 66000 mm2 Provide 12H16 (As,prov = 2413 mm2) Example 5: Design of Pile Cap – Beam Theory Transverse Bar 𝐾= 𝑀𝐸𝑑 𝑓𝑐𝑘 𝑏𝑑 2 = 525×106 30×2400×10012 = 0.007 Kbal = 0.167 Compression reinforcement is NOT required 𝑧 = 𝑑 0.25 − 𝐴𝑠,𝑟𝑒𝑞 = 𝐾 1.134 𝑀𝐸𝑑 0.87𝑓𝑦𝑘 𝑧 = = 0.9𝑑 0.95d 525×106 0.87×500×0.95×1001 = 𝟏𝟐𝟔𝟗 mm2 Example 5: Design of Pile Cap – Beam Theory Minimum & Maximum Area of Reinforcement 𝑓𝑐𝑡𝑚 2.90 𝐴𝑠,𝑚𝑖𝑛 = 0.26 𝑏𝑑 = 0.26 0.0015𝑏𝑑 ≥ 0.0013𝑏𝑑 𝑓𝑦𝑘 500 As,min = 0.0015bd = 0.0015 2400 1001 = 3618 mm2 As,max = 0.04Ac = 0.04bh = 0.04 2400 1100 = 105600 mm2 Since As,req = 1269 mm2 As, min = 3618 mm2 Provide 18H16 (As,prov = 3620 mm2) Example 5: Design of Pile Cap – Beam Theory Shear (i) Vertical Shear Critical shear at p/5 section inside pile: 2 pile outside critical section Shear force, VEd = 2 721 = 1442 kN Pile spacing 3p Consider shear enhancement on the whole width of the section Reduced shear force, 𝑉𝐸𝑑 = 1442 × 𝑎𝑣 2𝑑 = 1442 × 610 2×1017 = 𝟒𝟑𝟐 kN Example 5: Design of Pile Cap – Beam Theory Shear Note: Bar extend beyond critical section at = 315 + 1001 = 1316 mm 𝑙𝑏𝑑 + 𝑑 = 36∅ + 𝑑 = 36 × 16 + 1001 = 1577 mm Asl = 0 mm2 av = 610 300 60 Critical section 300 315 300 900 900 300 315 1316 h = 1100 900 Critical section Example 5: Design of Pile Cap – Beam Theory Shear 𝑘 =1+ 200 𝑑 =1+ 200 1001 = 1.45 2.0 𝑉𝑅𝑑,𝑐 = 𝑉𝑚𝑖𝑛 = 0.035𝑘 3/2 𝑓𝑐𝑘 𝑏𝑑 = 0.035 × 1.453/2 30 1500 × 1001 × 10−3 = 501 kN VEd (432 kN) Vmin (501 kN) OK Example 5: Design of Pile Cap – Beam Theory Shear (ii) Punching Shear at Perimeter 2.0d from Column Face Since pile spacing 3p No punching shear check in necessary Example 5: Design of Pile Cap – Beam Theory Shear (iii) Maximum Punching Shear at Column Perimeter 𝑉𝑅𝑑,𝑚𝑎𝑥 𝑓𝑐𝑘 = 0.5 0.6 1 − 250 = 0.5 0.6 1 − 30 250 30 1.5 𝑓𝑐𝑘 𝑢𝑑 1.5 4 × 400 × 1017 = 8456 kN VEd,max = 4200 kN OK Example 5: Design of Pile Cap – Beam Theory Cracking h = 1100 mm 200 mm Max bar spacing Assume steel stress is under quasi-permanent loading: = 0.55 𝑓𝑦𝑘 𝐴𝑠,𝑟𝑒𝑞 1.15 𝐴𝑠,𝑝𝑟𝑜𝑣 = 0.55 500 1.15 2401 2413 = 238 N/mm2 For design crack width 0.3 mm: Maximum allowable bar spacing = 200 mm Actual bar spacing 1 = Actual bar spacing 2 = 2300−2 75 −16 17 1500−2 75 −16 11 = 131 mm 200 mm = 121 mm 200 mm Cracking OK Example 5: Design of Pile Cap – Beam Theory Detailing 300 12H16 300 900 18H16 900 900 300 h = 1100 300 4H12 Binders