GENERATOR TRANSFORMER TESTING REPORT LOCATION GT2 TRANSFORMER DETAILS: TRANSFORMER SR NO 6004725 CAPACITY MAKE VOLTAGE RATIO VECTOR GROUP TOTAL TAP 250 MVA BHEL 15.75/400KV YNd11 13 1. MAGNETISING CURRENT TEST: Date: 19/08/2023 INSTRUMENT USED INSTRUMENT SR NO multimeter 220451349 Clamp meter 1002002220 APPLIED VOLTAGE(V) OTI (°C) TAP POSITION 36 7 MAGNETISING CURRENT(mA) VR-N 242.4 IR 1.88 VY-N 242.3 IY 1.44 VB-N 242.5 IB 1.89 Points to be remember: Apply Single phase AC supply to HV winding and LV winding kept open. Compare the value with pre-commissioning values. Any abnormal increase of the order of 50 times indicates there is a fault inside. 2. CORE BALANCE TEST Date:19/08/2023 INSTRUMENT USED INSTRUMENT SR NO OTI (°C) WTI (°C) Multimeter 220451349 36 34 VOLTAGE APPLIED(V) VOLTAGE MEASURED(V) R-N 242.4 Y-N 220.7 B-N 23.10 Y-N 242.3 R-N 146.5 B-N 97.7 B-N 242.5 R-N 25.19 Y-N 217.6 Points to be remember: When extreme phase is excited centre phase shall be 50 to 95% of applied voltage. When centre phase is excited extreme phase voltage shall be 30 to 75% of the applied voltage. Sum of measured induced two phases should equal to the voltage applied. GENERATOR TRANSFORMER TESTING REPORT LOCATION GT2 3. TRANSFORMER TURNS RATIO: INSTRUMENT USED ATRT 03 B, Vanguard Date: 19/08/2023 INSTRUMENT SR NO LKN 14130 TAP POSITION OTI (°C) 36 WTI (°C) 34 WINDING COMBINATION R-N/r-b Y-N/y-r B-N/b-y 1 16.170 16.160 16.180 2 15.986 15.975 15.995 3 15.797 15.788 15.807 4 15.605 15.603 15.615 5 15.403 15.399 15.413 6 15.216 15.212 15.230 7 15.011 15.007 15.021 8 14.832 14.820 14.841 9 14.644 14.632 14.654 10 14.456 14.446 14.463 11 14.249 14.245 14.258 12 14.064 14.056 14.077 13 13.863 13.854 13.875 Service tap -07 15.019 15.010 15.026 Points to remember: Compare the trend of turns ratio with reference to pre-commissioning values The maximum allowable variation of turn’s ratio is ±0.5%. 5. TAN DELTA: file name -2023GT2 DATE- 16/08/2023 INSTRUMENT USED INSTRUMENT SR NO Doble M4100 050001343 OTI (°C) WTI (°C) 36 34 TAN DELTA OF WINDING: File name-GT#2 2KV TEST MODE 10KV CAPACITANCE(pf) 28073.00 GAR-R(CH) TAN DELTA(%) 0.524 CAPACITANCE(pf) 28066.15 TAN DELTA(%) 0.513 GND-RB(CH+CL) 0.518 56630.00 0.528 56590.00 UST-R(CHL) 0.521 28513.35 0.528 28518.70 GAR-R(CL) 0.507 64600.00 0.532 64570.00 GND-RB(CL+CLH) 0.509 93150.00 0.529 93340.00 UST-R(CLH) 0.517 28515.00 0.523 28531.35 GENERATOR TRANSFORMER TESTING REPORT LOCATION GT2 TAN DELTA OF BUSHING: 2KV TEST MODE 10KV TAN DELTA (%) CAPACITANCE(pF) TAN DELTA (%) CAPACITANCE(pF) UST-R(R-ph) 0.304 431.38 0.309 431.34 UST-R(Y-ph) 0.329 436.63 0.335 436.55 UST-R(B-ph) 0.277 428.40 0.277 427.74 Points to be remember: Allowable limit for tan delta =0.7%, Capacitance =110% of the commissioning value. Ensure bushings are clean and free from dust. Tan delta test point of bushing should be properly earthed after testing. 6. IR VALUE OF WINDING: INSTRUMENT USED Date:08.09.2023 INSTRUMENT SR NO OTI (°C) WTI (°C) 2210068279 32 32 Rishab INSULATION RESISTANCE WINDING COMBINATION TEST VOLTAGE 15SEC 60SEC 600 SEC HV-E 5KV 239 277 555 LV-E 5KV 204 322 639 HV-LV 5KV 231 377 847 Points to be remember: Calculate PI =IR at 10min/IR at 1min, Absorption factor (k) = IR at 60sec / IR at 15sec. Recommended PI values are PI < 1.0 –Dangerous, PI between 1.0-1.1 is poor, PI between 1.252.0 is satisfactorily, PI >2 is good. Ensure bushings are clean and free from dust. GENERATOR TRANSFORMER TESTING REPORT LOCATION GT2 7. WINDING RESISTANCE OF HV WINDING: INSTRUMENT USED Date: 06.09.2023 INSTRUMENT SR NO OTI (°C) 2307-02U481 32 TRM25,Scope T&M Pvt. Ltd. WINDING RESISTANCE ( mΩ ) TAP POSITION WTI (°C) 32 TEST CURRENT R-N Y-N B-N 10A 1 932 934 934 10A 2 924 924 925 10 A 3 920 920.1 919 10 A 4 907.1 910 910 10 A 5 901 903 903 10 A 6 892 894 894 10A 7 884 884 885 10A 8 891 894 894 10A 9 901 903 903 10 A 10 910 909 910 10 A 11 920 921 921 10 A 12 926.0 926 926 10 A 13 933 934 934 10A 885 884 884 10A SERVICE TAP-07 8.WINDING RESISTANCE OF LV WINDING: DATE 08.09.2023 INSTRUMENT USED INSTRUMENT SR NO OTI (°C) WTI (°C) TRM25,Scope T&M Pvt. Ltd. 2307-02.U481 32 32 WINDING r-y y-b b-r WINDING RESISTANCE 1652µΩ 1652µΩ 1653µΩ TEST CURRENT(A) 25 25 25 Points to be remember: Trend in variation shall be same. Deviation in absolute values to be within ±5%. This test shall be the last on winding to avoid possibility of erroneous test results during subsequent tests because of core saturation. GENERATOR TRANSFORMER TESTING REPORT LOCATION GT2 9. IR VALUE OF CORE: Date:11.09.2023 INSTRUMENT USED INSTRUMENT SR NO RISHAB 2210068279 CORE -EARTH IR VALUE 15 SEC TEST VOLTAGE 30 500 V CORE -YOKE YOKE-EARTH 226.2MΩ 26.2MΩ 28.1MΩ 60 SEC OTI (°C) 95.5KΩ 30.1MΩ Points to be remember: IR testing of core is to be done at 500V & IR value should be >=1M ohm 11.LEAKAGE CURRENT : DATE- 05/09/2023 EQUIPMENT OLTC BASE VOLTAMP(MVA) GT2 07 250 BASE VOLT (KV) 409.0 NAMEPLATE% IMPEDANCE % IMPEDANCE 15.00 15.839 % REACTANCE 15.810 12.EARTH RESISTANCE DATE-11.09.2023 INSTRUMENTS USED STQC POINT 1. INSTRUMENTS SR NO N156160UFV MAIN TANK 0.42 MB 0.36 NEUTRAL 0.28 LA R-Stru-0.41 R-Count-0.26 Y- Stru-0.40 Y-Count-0.38 B- Stru-0.33 B- Count-0.29 GENERATOR TRANSFORMER TESTING REPORT LOCATION GT2 13. FILTERATION DATE: 06/10/2023 14. DONE DURING OVERHAULING: 1. …SFRA DONE DATE …19/08/2023 2….FDS DONE DATE..23/08/2023 TESTING ENGINEER: SIGN: _______________ NAME:URVASHI GAUBA CHECKED BY: SIGN: _______________ NAME: URVASHI GAUBA