FOR CONSTRUCTION APPROVED by OE 26-Mar-22 0 14.MAR.2022 C 18.FEB.2022 B 3.NOV.2021 A 1.SEP.2021 REV DATE Owner H.K.YEOM H.K.YEOM H.K.YEOM H.K.YEOM PREPARED J.Y.OH J.Y.OH J.Y.OH J.Y.OH CHECKED S.G.KIM S.G.KIM S.G.KIM S.G.KIM APPROVED FOR CONSTRUCTION FOR APPROVAL FOR APPROVAL FOR APPROVAL STATUS CEO OFFICE ACKNOWLEDGED AND SIGNED Owner’s Engineer Date: Mar 27, 2022 R Contractor by I Approved by IRT on Mar 27, 2022 Sub-Supplier Project JAWA 9 & 10 COAL FIRED STEAM POWER PLANT Document Title OPERATION & CONTROL PHILOSOPHY-WTP Document Type □ Basic Engineering Document □ Detail Engineering Document ■ Vendor Document □ Other Document No. J910-XS01-P0GBB-125727 OPERATION & CONTROL PHILOSOPHY-WTP J910-XS01-P0GBB-125727 RECORD OF REVISION Rev. Date Page Affected Description of Revision A 1.SEP.2021 - First Issue B 3.NOV.2021 As marks Revised as per owner comments C 18.FEB.2022 As marks Revised as per owner comments 0 14.MAR.2022 - - Rev.0 Jawa 9&10 Coal Fired Steam Power Plant_Design Review Comment Sheet From : To : Cc : Dwg Title : Dwg No : Purpose : Document Controller HK Mr. Salam Syah IRT TEPSCO Mr. Kubota Hiroshi OPERATION & CONTROL PHILOSOPHY-WTP J910-XS01-P0GBB-125727 FC Comment Sheet Document No : J910-XS01-P0GBB-125727 Review Category A = Approved B = Approved with comments, forward final document C = Not Approved I = Accepted for reference (For information only) B No. Rev. Sheet/ Page/ Sect. 1 A 3 of 35 EPC should put all of WTP components , equipments, pumps, tanks, etc 's Noted and Revised tag number in this document completely ! O/E Comments Consortium Response Closed 2 A 5 of 35 EPC should inform document number that describing Settling Basin general arrangement (drawing and section) ! Closed Closed Closed Noted and add it to the para no 6. Reference documents and drawings as below - GA Drawing for Sea Water Settlement Basin(J910-YT01-P0GBD-125704) 3 A 6 of 35 EPC should complete what kinds of parameters & limitation value which Noted and Confirmed (Kindly refer detailed information para no 4.1 and for set points para no 5, where determine water product will be reject or store to the next process on this parameters & limitations by which product will be reject or store in indicated. operation philosophy-WTP 4 A 6 of 35 Noted and add it to the para no 4. Control Logic Description as below Give additional information of capacity for each equipment (MMF, SWRO, - 4.1 Settlement Basin (P0GBB11/12BB001, Qty: 2 x 100%, Cap : 500m3 BWRO, and other) example: ...x 100% - 4.2 MMF Feed pump (P0GBB31/32AP001, Qty: 2 x 100%, Cap: 500m3/hr, H : 3bar(g) Status Para no 3. general operation of the plant is explanation of the overall concept. For detail information, refer to the para no 4.12 SWRO Units (P0GBF61/62AT001) and for set point para no 5. set points indicated for off spec quality parameter. 5 A 6 of 35 Add mechanism to determine if the quality is "off spec". What is the key parameter. 6 A 6 of 35 please add DM to the abbreviations Noted and Revised (DM = Demineralised water) Closed 7 A 6 of 35 what process after this? Is there any disposal after the water has been saturated? Yes there will be process considering the conditions with decrease in flux and increase in pressure as below, CIP will be required, If normalized permeate flux decrease 10% and differential pressure increase 20% of BWRO unit, If normalized permeate flux decrease 15% of EDI unit after recirculation. Kindly refer to the para. 4.16. BWRO Units (P0GCF51/52AT001), 4.20. EDI Units (P0GCF81/82AT001) Closed 8 A 6 of 35 General typo: Plan Noted and Revised Closed 7 of 35 Give add sequences start and stop backwash system, because backwash include one unit in the process of WTP operation Noted and updated. Closed 9 A Closed Noted and Revised 'Start Service & Potable_Open(Block valve XV-P0GBF22AA051) 10 A 7 of 35 11 A 8 of 35 12 A 8 of 35 Closed service & potable pump? EPC should put all of WTP components , equipments, pumps, tanks, etc 's tag number in this document completely ! Please set page number for this docuemnt! Please differentiate the status of equipment (pump, fan, etc.) between stop and trip. The stop condition is intended by the operator or startup/shutdown sequence. Meanwhile, the trip condition is forced by the logic control/interlock. Noted and Revised Closed Noted and Revised Closed When the high level is reached, the valve(XV-P0GBB11AA051) is closed. If not high (Last for 2minutes) valve open. 13 A 8 of 35 Auto mode of control valve only? isn't it required interlock close by Level HH 8 of 35 The Not Low condition is to set the permissive start for the pump. The pump started or not, depends on the mode of operation, auto or manual. Closed Noted and agreed So, the conditions for manual and auto mode were described. 14 A 15 A 8 of 35 16 A 22 of 35 during Pump run, LL of pump outlet pressure will not trigger to stand by pump start? why there is no table of instrument logic description provided for FeCl3 and NaOCl dosing pump? Closed Except for the following two cases, it is recommended to operate after on-site check(or inspection) for the protection of piping and equipments. Closed please refer to the para. 4.29 FeCl3 Dosing Tank (P0GBN81/82BB001), 4.31. NaOCl Dosing Tank (P0GCN11BB001) Closed Noted and add it to the para no 4.37 RO CIP Tank (P0GBP51BB001), 4.39. UF CIP Tank (P0GBP52BB001) as below 17 A 25 of 35 what chemical is used for CIP? Closed EPC shall deliver explaination regarding : 1. what is the rated/ normal level for this settl basin? 1. Rated/ normal level(=operating level) is between L and H. 2. Add it to the para no 6. Reference documents and drawings as below - GA Drawing for Sea Water Settlement Basin(J910-YT01-P0GBD-125704) 2. How long is the settlement basin retention time/ settling time ? Please put the document number that describing this in detail ! 18 A 28 of 35 3 ~ 5. Kindly note that, It is continuous operating concept, pump will operate in continous basis between H and L 3. Based on item 01 of 24 incase now level is 2140mm (not Low level; level. Kindly refer P&ID also, level transmitter P0GBB11CL001 and P0 GBB12CL001 is interlocked with pump for 1200mm x 1,2) than pump is strated and within 25 minutes what will be pump operation with respect water level and if water level will be low low pump will stop, going to be here? With this MMF feed pump flow rate (item 02 of 24 below) is it a safe level for MMF feedpump with 486 m3/hr caps to pump in 25minutes ? Closed 4. Please confirm which level is the safe level for starting the pumps? 5. Please explain in detail ! If there is only outflow without inflow, there is retention time of about 0.41hr for operating. Therefore, the following logic is configured for the stability of the system. In the case of all basins, level control is carried out like this, and logic is reflected for each level. 19 A 29 of 35 EPC should confirm and check SWRO high press pump capacity following SWRO latest capacity as per latest Design Criteria of WTP (to be 300 m3/hr as per latest recomendation - please refer to section 5 item 07 and 08 of 24 this document) ! Kindly refer our deatiled calculation of service water requirement based on final DHI input for CHP (Dust suppression, stacker, reclaimimg etc) on latest Design Criteria - Service Water System (J910-XW01-P0GHE125010)_Rev F, The total quantity of service water consumption for CHP is incraesed by 2m3/day, However HVAC requrment of 4 m3/day reduced to zero. Therefore overall consumption of service water per day is reduced to 2m3/day. Hence 200m3/hr SWRO capacity is more than sufficient. Therefore we confirm SWRO capacity 200m3/hr is final and fixed based on latest and final input with adequate margin, Closed Since flow of SWRP capcity is reatined same based on latest input, so no rset is required for high operating rate and low operating rate. EPC should confirm and follow SWRO capacity suggestion as per latest Design Criteria of WTP to be >= 300m3/hr ! 20 A 29 of 35 Please reset the Operating rate, High operating rate, Low operating rate, etc.! Kindly refer our deatiled calculation of service water requirement based on final DHI input for CHP (Dust suppression, stacker, reclaimimg etc) on latest Design Criteria - Service Water System (J910-XW01-P0GHE125010)_Rev F, The total quantity of service water consumption for CHP is incraesed by 2m3/day, However HVAC requrment of 4 m3/day reduced to zero. Therefore overall consumption of service water per day is reduced to 2m3/day. Hence 200m3/hr SWRO capacity is more than sufficient. Therefore we confirm SWRO capacity 200m3/hr is final and fixed based on latest and final input with adequate margin, Closed Since flow of SWRP capcity is reatined same based on latest input, so no rset is required for high operating rate and low operating rate. EPC should confirm and follow SWRO capacity suggestion as per latest Design Criteria of WTP to be >= 300m3/hr ! 20 A 29 of 35 Please reset the Operating rate, High operating rate, Low operating rate, etc.! Kindly refer our deatiled calculation of service water requirement based on final DHI input for CHP (Dust suppression, stacker, reclaimimg etc) on latest Design Criteria - Service Water System (J910-XW01-P0GHE125010)_Rev F, The total quantity of service water consumption for CHP is incraesed by 2m3/day, However HVAC requrment of 4 m3/day reduced to zero. Therefore overall consumption of service water per day is reduced to 2m3/day. Hence 200m3/hr SWRO capacity is more than sufficient. Therefore we confirm SWRO capacity 200m3/hr is final and fixed based on latest and final input with adequate margin, Closed Since flow of SWRP capcity is reatined same based on latest input, so no rset is required for high operating rate and low operating rate. 21 B 3 of 38 Youre explantion is in Auto mode of Valve, in case of manual mode, is not In manual mode valve is operated through open / close selection from HMI by operator. it required There's no forced close logic in manual mode. Forced close logic ? But, There's start up permissive condition "Check for at least pneumatic valve in auto mode." So the WTP can operate safely. otherwise operator could not forcee close / open the valve. Closed 22 B 3 of 38 EPC : Please provide same philosphy to each vender. Please standalize Stanb-by start condition for overall the plant. at leaset water line (WTP, WWTP, etc), Closed 4 of 38 As per Contract requirement Exh B4 Book 1 section 4.5.11.6, it mentioned for the pumps only in WTP. We have EPC & MFG shall calculate again and make sure 5% margin to be included considered 5% margin on pump capacity for all pumps as well. for SWRO flow rate/ caps to be provided as per contract requirement Exhibit B4 Book 1 ; section 4.5.11.6 ! Kindly Refer -Annexure to CRS on WBD attached for detail calculation on margins available in all WTP main umits. For detailed margin calculation, Kindly also refer J910-XW01-P0GDF-125134 Design Criteria - Water Treatment PlantEPC & MFG shall provide performance curve that describes SWRO Rev 2 (APPROVED). flowrates/ capacity with margin ! We have 28% margin on CEDI, 28% margin on BWRO and more than 8% margin on SWRO. Please note that more Please confirm and fix! than sufficient margin has been already considered in the WTP plant (EDI,BWRO & SWRO), Kindly accept and approve. Closed 4 of 38 As per Contract requirement Exh B4 Book 1 section 4.5.11.6, it mentioned for the pumps only in WTP. We have EPC & MFG shall calculate again and make sure 5% margin to be included considered 5% margin on pump capacity for all pumps as well. for SWRO flow rate/ caps to be provided as per contract requirement Exhibit B4 Book 1 ; section 4.5.11.6 ! Kindly Refer -Annexure to CRS on WBD attached for detail calculation on margins available in all WTP main umits. For detailed margin calculation, Kindly also refer J910-XW01-P0GDF-125134 Design Criteria - Water Treatment PlantEPC & MFG shall provide performance curve that describes SWRO Rev 2 (APPROVED flowrates/ capacity with margin ! We have 28% margin on CEDI, 28% margin on BWRO and more than 8% margin on SWRO. Please note that more Please confirm and fix! than sufficient margin has been already considered in the WTP plant (EDI,BWRO & SWRO), Kindly accept and approve. Closed 4 of 38 As per Contract requirement Exh B4 Book 1 section 4.5.11.6, it mentioned for the pumps only in WTP. We have EPC & MFG shall calculate again and make sure 5% margin to be included considered 5% margin on pump capacity for all pumps as well. for SWRO flow rate/ caps to be provided as per contract requirement Exhibit B4 Book 1 ; section 4.5.11.6 ! Kindly Refer -Annexure to CRS on WBD attached for detail calculation on margins available in all WTP main umits. For detailed margin calculation, Kindly also refer J910-XW01-P0GDF-125134 Design Criteria - Water Treatment PlantEPC & MFG shall provide performance curve that describes SWRO Rev 2 (APPROVED flowrates/ capacity with margin ! We have 28% margin on CEDI, 28% margin on BWRO and more than 8% margin on SWRO. Please note that more Please confirm and fix! than sufficient margin has been already considered in the WTP plant (EDI,BWRO & SWRO), Kindly accept and approve. Closed 23 24 25 B B B For this startup operation step by step are they time based operating or other controlled operating? 26 B 9 of 38 27 B 10 of 38 Noted and confirmed. It specifies the just sequence for the overall start up and shutdown. for example step 1 within SWMU pump started into MMF feedpump started we need to make sure/ consider the Setl basin water level ! i) On the left side column defines sequence for start-up - means the same sequence shall be followed for start-up. ii) On the right side columndefines sequence for shutdown-means the sane sequnce shall be followed for shutdown. So we can say that, If the conditions(=other controlled operating) required for each step are satisfied, it can proceed to the next step. EPC to describe the specific "process condition". Noted and Updated in the document 'Process condition means all logics described to operation in auto mode. for example, Level, Flow, Pressure,etc. Closed Closed 28 B 16 of 38 As per Contract requirement Exh B4 Book 1 section 4.5.11.6, it mentioned for the pumps only in WTP. We have EPC & MFG shall calculate again and make sure 5% margin to be included considered 5% margin on pump capacity for all pumps as well. for SWRO flow rate/ caps to be provided as per contract requirement Exhibit B4 Book 1 ; section 4.5.11.6 ! .Kindly Refer -Annexure to CRS on WBD attached for detail calculation on margins available in all WTP main umits. For detailed margin calculation, Kindly also refer J910-XW01-P0GDF-125134 Design Criteria - Water Treatment PlantEPC & MFG shall provide performance curve that describes SWRO Rev 2 (APPROVED) flowrates/ capacity with margin ! We have 28% margin on CEDI, 28% margin on BWRO and more than 8% margin on SWRO. Please note that more Please confirm and fix! than sufficient margin has been already considered in the WTP plant (EDI,BWRO & SWRO), Kindly accept and approve. Closed Kindly note that, based on owner comments, we have indicated stand by pump start conditions logic as below, 29 C 4 of 40 Noconfirmnfirm by logic i) The duty pump fails to start ii)When the start signal of duty pump is not feedback To be closed We have conveyed this logic for standby start condition to WWTP vendor. Please accept. 30 C 15 of 40 There are normal flowrate and design flowrate for Mass balance condition. (Refer to the PFD_J910-XG07-P0GCF-125705) - Normal flowrate is requirement for water consumption, it is operating flow. EPC shall confirm and revise some pumps capacity in this document refer - Design flowrate is capability of the system. to J910-YT01-P0GBD-125725 Pumps in Water Treatment Plan, Pump no: 4.5 ; 4.7 ; 4.9 ; 4.10 ; 4.11; 4.14 ; 4.15 ; etc. ! The capacity of pump specified is based on the design flowrate in this document. 'In the case of J910-YT01-P0GBD-125725 Pumps in Water Treatment Plan, 5% margin is applied to the normal flowrate to select the pump specification. To be closed Table Contents Table Contents ..........................................................................................................................................1 1. Scope: ..................................................................................................................................................3 2. Abbreviations and definitions: .........................................................................................................3 3. General Operation of the Plant: .......................................................................................................3 4. Control Logic Description: ...............................................................................................................6 4.1 Settlement Basin (P0GBB11BB001 & P0GBB12BB001) ...............................................................6 4.2 MMF Feed pump (P0GBB31AP001 & P0GBB32AP001) ..............................................................6 4.3 Multi Media Filters (P0GBB51BB001 & P0GBB52BB001) ..........................................................6 4.4 Ultra-Filtration Units (P0GBB61AT001 & P0GBB62AT001) .......................................................8 4.5 Filter Backwash Blower (P0GBC11AP001 & P0GBC12AP001) .................................................10 4.6 Filter Backwash Tank (P0GBB81BB001) ......................................................................................10 4.7 Filter Backwash Pump (P0GBP31AP001 & P0GBP32AP001) ...................................................10 4.8 Filtered Water Storage Pond (P0GBB71BB001 & P0GBB72BB001) ......................................... 11 4.9 UF Backwash Pump (P0GBP11AP001 & P0GBP12AP001) ........................................................ 11 4.10 SWRO Water Feed Pump (P0GBF11AP001 & P0GBF12AP001)............................................. 11 4.11 SWRO High Pressure Pump (P0GBF41AP001 & P0GBF42AP001 & P0GBF43AP001) .......12 4.12 SWRO Units (P0GBF61AT001 & P0GBF62AT001) ..................................................................13 4.13 SWRO Permeate Water Storage Tank (P0GBF71BB001 & P0GBF72BB001) ........................14 4.14 BWRO Feed Pump (P0GCF11AP001 & P0GCF12AP001) .......................................................14 4.15 BWRO High Pressure Pump (P0GCF41AP001 & P0GCF42AP001 & P0GCF43AP001)......15 4.16 BWRO Units (P0GCF51AT001 & P0GCF52AT001) .................................................................15 4.17 BWRO Permeate Water Storage Tank (P0GCF61BB001) ........................................................16 4.18 EDI Feed Pump (P0GCF71AP001 & P0GCF72AP001).............................................................16 4.19 Flushing Pump (P0GBP41AP001 & P0GBP42AP001) ..............................................................17 4.20 EDI Units (P0GCF81AT001 & P0GCF82AT001) .......................................................................17 4.21 H2SO4 Bulk Storage Tank (P0GBN11BB001) ............................................................................18 4.22 H2SO4 Unloading CUM Transfer Pump (P0GBN21AP001 & P0GBN22AP001) ...................18 4.23 NaOH Bulk Storage Tank (P0GBN13BB001) .............................................................................19 4.24 NaOH Unloading CUM Transfer Pump (P0GBN23AP001 & P0GBN24AP001) ....................19 4.25 H2SO4 Dosing Tank (P0GBN41BB001) ......................................................................................20 4.26 H2SO4 Dosing Pump (P0GBN51AP001 & P0GBN52AP001) ...................................................20 4.27 NaOH Dosing Tank (P0GBN43BB001) ........................................................................................20 4.28 NaOH Dosing Pump (P0GBN53AP001 & P0GBN54AP001 & P0GBN55AP001 & P0GBN56AP001) ..........20 4.29 FeCl3 Dosing Tank (P0GBN81BB001 & P0GBN82BB001) .......................................................21 4.30 FeCl3 Dosing Pump (P0GBN83AP001 & P0GBN84AP001) .....................................................21 4.31 NaOCl Dosing Tank (P0GCN11BB001) .......................................................................................22 4.32 NaOCl Dosing Pump (P0GCN21AP001 & P0GCN22AP001 & P0GCN61AP001 & P0GCN62AP001) ........22 4.33 SBS Dosing Tank (P0GBN71BB001) ............................................................................................22 4.34 SBS Dosing Pump (P0GBN63AP001 & P0GBN64AP001).........................................................22 4.35 Anti-Scalant Dosing Tank (P0GBN91BB001) .............................................................................23 4.36 Anti-Scalant Dosing Pump (P0GBN93AP001 & P0GBN94AP001, P0GCN61AP001 & P0GCN62AP001)............23 4.37 RO CIP Tank (P0GBP51BB001) ..................................................................................................24 4.38 RO CIP Pump (P0GBP61AP001 & P0GBP62AP001)................................................................24 4.39 UF CIP Tank (P0GBP52BB001) ...................................................................................................25 4.40 UF CIP Pump (P0GBP63AP001 & P0GBP64AP001) ................................................................25 4.41 NaHCO3 Dosing Tank (P0GCN31BB001)...................................................................................25 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 4.42 NaHCO3 Dosing Pump (P0GCN41AP001 & P0GCN42AP001) ...............................................26 4.43 CaCl2 Dosing Tank (P0GCN33BB001) ........................................................................................26 4.44 CaCl2 Dosing Pump (P0GCN43AP001 & P0GCN44AP001) ....................................................26 4.45 Brine Storage Pond (P0GBB76BB001 & P0GBB77BB001).......................................................27 4.46 Backwash Waste Transfer Pump (P0GBB78AP001 & P0GBB79AP001).................................27 5. Set Point Summary ..........................................................................................................................28 6. Reference documents and drawings: .............................................................................................33 2 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 1. Scope: This document describes the regulatory control blocks and control loops including all the control functionality associated with the water treatment plan and it defines the interlocks within various water treatment stages and packages as below. It provides a brief description for equipment's and instruments explaining the interlocks and safeguards for safe operation. It provides operation principles, startup and shutdown sequence chart. 2. 3. Abbreviations and definitions: DCS Distributed Control System FCV Flow Control Valve MMF Multi Media Filter UF Ultra Filtration SWRO Sea Water Reverse osmosis BWRO Brackish Water Reverse osmosis EDI Continuous Electro Deionization CIP Cleaning in Place ORP Oxygen Reduction Potential TDS Total Dissolved Solids NTU Nethelometric Turbidity Unit SDI Silt Density Index AO/AFC Air to Open/Air Fail Close AC/AFO Air to Close/Air Fail Open TMC Toray Membrane Cleaning WTP Water Treatment Plant LCS Local Control Station MCC Motor Control Center OWS Operator Work Station EWS Engineering Work Station PV Process Value ERD Energy Recovery Device DM Demineralised Water General Operation of the Plant: Seawater makeup pump (not in the scope of this package) discharge line will be terminated one meter before the control valve station at the inlet of the settlement basin. 3 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP The water from the seawater makeup pump will let to the settlement basin with separate inlet system and outlet system with bottom slope arrangement. The MMF feed water pump will pump the water to Multimedia filter. The outlet from the MMF will be collected in the filter back wash tank for backwashing the filters. The remaining water from the MMF will be sent to filtered water storage tank. SWRO feed water pump will take suction from the filtered water storage tank and pump to micron cartridge filter. SWRO High pressure pump will be pump the water to SWRO units. Turbo charger shall be provided for each SWRO units. The permeate water from SWRO units will be stored in the SWRO permeate storage tank. The reject from the SWRO units will be sent to brine storage tank. If the quality of the permeate (Off spec) is not meeting the required permeate quality the water will be sent back to filtered water storage tank. A portion of the permeate water from SWRO units will be pass through remineralization units and stored in the service water storage tank and potable water storage tank. Sodium Bicarbonate and Calcium Chloride will be dosed at the Service water line and potable water line for remineralization. The water from SWRO permeate tank will be passed through micron cartridge filter by BWRO high pressure pump and sent to BWRO units. The permeate water from BWRO units will be stored in BWRO permeate water storage tank. The reject water from the BWRO units will be sent back to filtered water storage tank. If the quality of permeate is not meeting the required quality the water willl be sent back to filtered water storage tank. The water from BWRO permeate storage tank will be pumped by EDI feed Pump to EDI units. The outlet from the EDI unit will be stored in the DM (Demineralised Water) water storage tank. If the quality of permeate is not meeting the required quality the water will be sent back to SWRO permeate storage tank. Startup and shutdown of each subsystem of the Water Treatment Plant may be at any time, up to operator criteria. 4 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP For a complete Water treatment Plan startup and shutdown the following sequences are defined. STEP1 STEP2 STEP3 •Water Treatment Plant - STARTUP •Water Treatment Plant - SHUTDOWN •Start Sea Water Makeup Pump & MMF •Stop (Close Block Valve) Service & Feed Pump •Start Mutil Media Filter STEP2 •Start Ultrafiltration Unit STEP3 •Start (First) SWRO Water Feed Pump & STEP4 STEP6 (Second) SWRO High Pressure Pump STEP8 STEP9 STEP10 FINAL •Stop EDI Unit & (Second) BWRO Feed Pump STEP4 Potable Water (Remineralization) STEP5 •Stop BWRO Unit •Stop (First) SWRO High Pressure Pump •Start SWRO Unit & (Second) SWRO Feed Pump STEP6 •Start (First) BWROFeed Pump & STEP7 •Stop EDI Feed Pump •Stop (First) BWRO High Pressure Pump •Start (Open Block Valve) Service & STEP5 Potable Water (Remineralization) STEP1 (Second) BWRO High Pressure Pump STEP7 •Stop SWRO Unit •Stop MMF Feed Pump & Sea Water •Start BWRO Unit Makerup Pump STEP8 •Start EDI Feed Pump STEP9 •Start EDI Unit STEP10 •Water Treatment Plant - OPERATION FINAL •Stop Ultrafiltration Unit •Stop Mutil Media Filter •Water Treatment Plant - STOPPED Note 1. The Multi Media Filter Backwash Start Condition - Periodic Time : every 24hr & Differential Pressure : High 2. After backwash of Multi Media Filter it will go in to Standby mode 3. Other Multi Media Filter will operate to produce water for backwash of one filer. 5 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 4. Control Logic Description: 4.1 Settlement Basin (P0GBB11BB001& P0GBB12BB001, Q’ty : 2x100%, Cap. : 500m3) Instrument with Logic Description: No Cause Consequences 1 High level (LIT P0GBB11CL001& Valve close (XV-P0GBB11AA051). P0GBB12CL001) of Settlement basin If not high (Last for 2minutes) valve open. Low level (LIT P0GBB11CL001& MMF feed pump trip (P0GBB31AP001& P0GBB12CL001) of Settlement basin P0GBB32AP001). 2 If not low (Last for 2minutes) pump start. 4.2 MMF Feed pump (P0GBB31AP001& P0GBB32AP001, Q’ty : 2x100%, Cap. : 500m3/hr, H : 3bar(g)) DCS Operation : MMF Feed pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause Consequences 1 Low flow (FIT P0GBB51CF001& MMF feed pump trip (P0GBB31AP001& P0GBB52CF001) of Multi media filter suction P0GBB32AP001). If not low (Last for 2minutes) pump start. The automatic duty /standby changeover will be triggered by: The duty pump fails to start. When the start signal of the duty pump is not feed back. 4.3 Multi Media Filters (P0GBB51BB001& P0GBB52BB001, Q’ty : 2x100%, Cap. : 500m3/hr) Auto operation : Normally the multi media filter shall be kept in auto mode. The filters shall operate continuously. One filter will normally operate to produce water. During backwash, other filter will operate to produce water for backwash of one filer. Filter run time between backwashes shall be at least 24 hours maximum. After backwash of multi media filter it will go in to Standby mode. All backwash steps shall be completed automatically and unit goes to standby mode shall be available for service. Semi - auto operation : In Semi-auto mode, operator can select service / backwash operation. Service mode : With selection of this operation the multi media filter shall go into service. This mode is active only in semi auto mode. The service cycle is terminated based on periodic time(every 24hr) and pressure drop(0.8barg), however the unit goes to standby after service and backwash starts only after initiation from HMI. 6 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Backwash mode : In semi auto mode all backwash steps of multi media filter is carried out automatically. These selections are active only during the backwash of multi media filter. a) Step advance : if step advance is pressed, the sequence is moved to the next step. b) Step hold : By selection of step hold, the timer of backwash step will be on hold, and the hold will be removed only after deactivating step hold selection and backwash step timer will resume from where it was stopped. Standby mode : All the valves of selected train / unit go to the closed position. Manual mode : In manual mode each valve is operated through an open / close selection from HMI. This mode is useful in start up and for testing purpose. Start Up Permissive a) Check for at least multi media filter in auto mode. b) Check for at least UF unit in auto mode. c) Check for at least pneumatic valve in auto mode. d) Check for at least MMF feed pump in auto mode. e) Water demand defined by water level (LIT P0GBB71CL001&P0GBB72CL001) in filtered water storage pond (P0GBB71BB001& P0GBB72BB001). f) Water levels (P0GBB21CL001) in the settlement chamber basin shall not be low. Conditions associated to Service operation sequence interruption Service sequence is interrupted based on any of the following conditions: a) On receipt of High differential pressure (0.8barg) alarm across MMF. (PDIT P0GBB51CP001 & P0GBB52CP001) b) Periodic timer 24 hours c) If any on-off valve which is required to open / close in the particular step is not opened / closed, then the sequence is interrupted as per valve sequence chart. (valve fault) d) If associated multi media filter is removed from auto mode Conditions associated to backwash operation sequence interruption Backwash sequence is interrupted based on any of the following conditions: a) Other multi media filter is in backwash mode. b) Filter backwash blower (P0GBC11AN001&P0GBC12AN001) in manual mode. c) Filter backwash pump (P0GBP31AP001& P0GBP32AP001) in manual mode. d) If any on-off valve which is required to open / close in the particular step is not opened / closed, then the sequence is interrupted as per valve sequence chart. (valve fault) e) If associated multi media filter is removed from auto mode 7 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Instrument with Logic Description: No Cause Consequences 1 High Differential Pressure MMF duty change (P0GBB51BB001 & (PDIT P0GBB51CP001& P0GBB52CP001) of P0GBB52BB001). MMF If not High (Last for 2minutes) MMF start. Note 1. Refer to the table 1 for operation & backwash sequence chart . 4.4 Ultra-Filtration Units (P0GBB61AT001& P0GBB62AT001, Q’ty : 2x100%, Cap. : 483m3/hr) The ultra-filtration units will operate with regular service with backwashing based on the pre-set time and TMC (Toray Membrane Cleaning), if necessary. Service with backwashing a) Fill-up : 35 sec. b) Filtration : 30 min. c) Back-Wash : 45 sec. d) Aeration : 60 sec. e) Drain : 45 sec. TMC(Toray Membrane Cleaning) a) Interval : 1day b) Total TMC time : app. 25min c) Using chemical : NaOCl Auto operation : Normally the ultra-filtration units shall be kept in auto mode. The ultra-filtration units shall operate continuously. One ultra-filtration unit will normally operate to produce water. During backwash or TMC, other ultra-filtration unit will operate to produce water for backwash or TMC of ultra-filtration unit. Ultra-filtration unit run time between backwash or TMC shall be at time schedule. After backwash or TMC of ultra-filtration unit it will go in to standby mode. All backwash or TMC steps shall be completed automatically and unit goes to standby mode shall be available for service. Semi - auto operation : In semi-auto mode, operator can select service with backwashing / TMC operation. Service mode : With selection of this operation the ultra-filtration unit shall go into service. This mode is active only in semi auto mode. The service cycle is terminated based on periodic time (30min/cycle) and pressure drop (0.8barg), however the unit goes to standby after service starts only after initiation from HMI. Backwash mode : In semi auto mode all backwash steps of ultra-filtration unit is carried out automatically. These selections are active only during the backwash of ultra-filtration unit. a) Step advance : if step advance is pressed, the sequence is moved to the next step. b) Step hold : By selection of step hold, the timer of backwash step will be on hold, and the hold will be removed only after deactivating step hold selection and backwash step timer will resume from where it was stopped. 8 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Standby mode : All the valves of selected train / unit go to the closed position. Manual mode : In manual mode each valve is operated through an open / close selection from HMI. This mode is useful in start up and for testing purpose. Start Up Permissive a) Check for at least ultra-filtration unit in auto mode. b) Check for at least multi media filter in auto mode. c) Check for at least pneumatic valve in auto mode. d) Check for at least MMF feed pump in auto mode. e) Water demand defined by water level (LIT P0GBB71CL001&P0GBB72CL001) in filtered water storage pond (P0GBB71BB001& P0GBB72BB001). f) Water levels (P0GBB21CL001) in the settlement chamber basin shall not below. Conditions associated to Service Operation sequence Interruption Service sequence is interrupted based on any of the following conditions: a) On receipt of High differential pressure (1.5barg) alarm across ultra-filtration unit. (PIT P0GBB61CP001& P0GBB61CP002, PIT P0GBB62CP001& P0GBB62CP002) b) Periodic timer 30mins c) If any on-off valve which is required to open / close in the particular step is not opened / closed, then the sequence is interrupted as per valve sequence chart. (valve fault) d) If associated ultra-filtration unit is removed from auto mode Conditions associated to Backwash & TMC Operation sequence Interruption Backwash Sequence is interrupted based on any of the following conditions: a) Other ultra-filtration unit is in backwash mode. b) Filter backwash blower (P0GBC11AN001& P0GBC12AN001) in manual mode. c) NaOCl dosing tank (P0GCN11BB001) low level. d) NaOCl dosing pump (P0GBN61AP001& P0GBN62AP001) in manual mode. e) UF backwash pump (P0GBP11AP001& P0GBP12AP001) in manual mode f) If any on-off valve which is required to open / close in the particular step is not opened / closed, then the sequence is interrupted as per valve sequence chart. (valve fault) g) If associated ultra-filtration unit is removed from auto mode Instrument with Logic Description: No Cause Consequences 1 High Differential Pressure (1.5barg) Ultra-filtration unit duty change (PIT P0GBB61CP001 & P0GBB61CP002, (P0GBB61AT001 & P0GBB62AT001). P0GBB62CP001 & P0GBB62CP002) of ultra- If not High (Last for 2minutes) ultra-filtration unit filtration unit start Note 1. Refer to the table 2 for operation & backwash, TMC sequence chart. 9 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 4.5 Filter Backwash Blower (P0GBC11AP001&P0GBC12AP001, Q’ty : 2x100%, Cap. : 505Nm3/hr, H : 5,000mmAq) DCS Operation : Filter backwash blower operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty blower start and trip automatically based on process condition (Flow, Pressure etc). The automatic duty /standby changeover will be triggered by: - The duty blower fails to start. - When the start signal of the duty blower is not feed back. 4.6 Filter Backwash Tank (P0GBB81BB001, Q’ty : 1x100%, Cap. : 180m3) Instrument with Logic Description: No Cause 1 Low level (LIT P0GBB81CL001) of Filter Filter backwash pump trip (P0GBP31AP001 & backwash tank Consequences P0GBP32AP001). If not low (Last for 2minutes) pump strat. 2 High level (LIT P0GBB81CL001) of Filter Valve backwash tank close (XV-P0GBB53AA052) of Filter backwash tank suction. If not high (Last for 2minutes) valve open. 4.7 Filter Backwash Pump (P0GBP31AP001& P0GBP32AP001, Q’ty : 2x100%, Cap. : 350m3, H : 3bar(g)) DCS Operation : Filter backwash pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause 1 Low pressure (PIT P0GBP31CP001) of Filter Filter backwash pump trip (P0GBP31AP001 & backwash pump discharge Consequences P0GBP32AP001). If not low (Last for 2minutes) pump start. The automatic duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 10 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 4.8 Filtered Water Storage Pond (P0GBB71BB001&P0GBB72BB001, Q’ty : 2x50%, Cap. : 183m3) Instrument with Logic Description: No Cause 1 High Consequences level (LIT P0GBB71CL001 & Valve close (XV-P0GBB11AA051). P0GBB72CL001) of Filtered water storage If not high (Last for 2minutes) valve open. pond 4.9 UF Backwash Pump (P0GBP11AP001&P0GBP12AP001, Q’ty : 2x100%, Cap. : 580m3/hr, H : 2.5bar(g)) DCS Operation : UF backwash pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause 1 Low Consequences level (LIT P0GBB71CL001 & UF backwash pump trip (P0GBP11AP001 & P0GBB72CL001) of Filtered water storage P0GBP12AP001). pond 2 If not low (Last for 2minutes) pump start. Low pressure (PIT P0GBP11CP001) of UF UF backwash pump discharge backwash pump trip (P0GBP11AP001 & P0GBP12AP001). If not low (Last for 2minutes) pump start. The automatic duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.10 SWRO Water Feed Pump (P0GBF11AP001&P0GBF12AP001, Q’ty : 2 x 100%, Cap. : 476m3/hr, H : 5bar(g)) DCS Operation : SWRO water feed pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start & trip and control valve open & close automatically based on process condition (Level, Flow, Pressure etc). - Start condition a. Stroke(%) position of control valve is 80% open when SWRO water feed pump run alone. b. When the fifteen(15%) stroke of control valve is reached and after 5min, SWRO high pressure pump shall be run. c. Slowly open 1% stroke per setting time(sec) of control valve for flow control. d. If SWRO water feed pump no run, SWRO high pressure pump shall not be run. 11 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP - Trip condition a. Slowly close 1% stroke per setting time(sec) of control valve. b. When the fifteen(15%) stroke of control valve is reached, SWRO high pressure pump shall be trip. c. SWRO water feed pump shall be trip after 5min Instrument with Logic Description: No Cause Consequences 1 Low level (LIT P0GBB71CL001 & SWRO water feed pump trip (P0GBF11AP001 & P0GBB72CL001) of Filtered water storage P0GBF12AP001). Pond If not low (Last for 2minutes) pump start. Low pressure (PIT P0GBF41CP001 & SWRO water feed pump trip (P0GBF11AP001 & P0GBF42CP001 & P0GBF43CP001) of P0GBF12AP001). SWRO high pressure pump suction If not low (Last for 2minutes) pump start. 2 The automatic duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.11 SWRO High Pressure Pump (P0GBF41AP001&P0GBF42AP001& P0GBF43AP001, Q’ty : 3 x 100%, Cap. : 476m3/hr, H : 30bar(g)) DCS Operation : SWRO high pressure pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start & trip and control valve open & close automatically based on process condition (Level, Flow, Pressure etc). - Start condition a. Stroke(%) position of control valve is 80% open when SWRO water feed pump run alone. b. When the fifteen(15%) stroke of control valve is reached and after 5min, SWRO high pressure pump shall be run. c. Slowly open 1% stroke per setting time(sec) of control valve for flow control. d. If SWRO water feed pump no run, SWRO high pressure pump shall not be run. - Trip condition a. Slowly close 1% stroke per setting time(sec) of control valve. b. When the fifteen(15%) stroke of control valve is reached, SWRO high pressure pump shall be trip. c. SWRO water feed pump shall be trip after 5min 12 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Instrument with Logic Description: No Cause Consequences 1 High or Low pressure SWRO high pressure pump trip (PIT P0GBF61CP001 & P0GBF62CP001) of (P0GBF41AP001&P0GBF42AP001& SWRO unit suction P0GBF43AP001). If not high or Low (Last for 2minutes) pump start The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.12 SWRO Units (P0GBF61AT001& P0GBF62AT001, Q’ty : 2 x 100%, Cap. : 200m3/hr(Product)) Auto operation : Normally the SWRO units shall be kept in auto mode. The units shall operate continuously. Manual mode : In manual mode each valve is operated through an open / close selection from HMI. This mode is useful in start up and for testing purpose. Start Up Permissive a) Check for at least SWRO unit in auto mode. b) Check for at least pneumatic valve in auto mode. c) Check for at least SWRO water feed pump, SWRO high pressure pump in auto mode. d) Water demand defined by water level (LIT P0GBB71CL001&P0GBB72CL001) in filtered water storage pond (P0GBB71BB001& P0GBB72BB001). e) Water demand defined by water level (LIT P0GBF71CL001&P0GBF72CL001) in SWRO permeate water storage tank (P0GBF71BB001&P0GBF72BB001). Conditions associated to Service Operation sequence Interruption Service sequence is interrupted based on any of the following conditions: a) On receipt of High differential pressure (1.0barg) alarm across SWRO unit. (PIT P0GBF61CP001& P0GBF61CP002, P0GBF62CP001&P0GBF62CP002) b) If any on-off valve which is required to open/close in the particular step is not opened/closed, then the sequence is interrupted as per valve sequence chart. (valve fault) c) If associated SWRO unit is removed from auto mode Instrument with Logic Description: No Cause Consequences 1 Low or High flow (FIT P0GBF61CP001 & Flow control according to the set value. P0GBF62CP001) of SWRO unit discharge (FCV P0GBF41AP081& P0GBF43AP081). High conductivity value (AE Valve open (XV-P0GBF61AA052&P0GBF62AA052) P0GBF61CQ001) of SWRO units discharge and Valve close (XV-P0GBF61AA051 & 2 P0GBF62AA051) of SWRO units discharge. If not high (Last for 2minutes) valve open and close. 13 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP CIP Operation(Manual) is based on any of the following conditions: a) If normalized permeate flux decrease 10%. b) If differential pressure increase 20%. 4.13 SWRO Permeate Water Storage Tank (P0GBF71BB001&P0GBF72BB001, Q’ty : 2 x 50%, Cap. : 73m3) Instrument with Logic Description: No Cause Consequences 1 High level (LIT P0GBF71CL001 & Valve open (XV-P0GBF22AA051) of service & P0GBF72CL001) of SWRO permeate water potable water suction. 2 storage tank If low (Last for 2minutes) valve close. High level (LIT P0GBF71CL001& SWRO high pressure pump trip (P0GBF41AP001 P0GBF72CL001) of SWRO permeate water & P0GBF42AP001 & P0GBF43AP001). storage tank If not high (Last for 2minutes) pump start. 4.14 BWRO Feed Pump (P0GCF11AP001&P0GCF12AP001, Q’ty : 2 x 100%, Cap. : 118m3/hr, H : 2.5bar(g)) DCS Operation : BWRO feed pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). - Start condition a. BWRO water feed pump run alone. b. BWRO high pressure pump shall be run after 5min. c. If BWRO water feed pump no run, BWRO high pressure pump shall not be run. - Trip condition a. BWRO high pressure pump trip. b. BWRO water feed pump shall be trip after 5min. c. If BWRO high pressure pump no trip, BWRO water feed pump shall not be trip. Instrument with Logic Description: No Cause 1 Low pressure (PIT P0GCF31CP002) of Micro BWRO feed pump trip (P0GCF11AP001& cartridge filter discharge Consequences P0GCF12AP001). If not low (Last for 2minutes) pump start. 2 Low level (LIT P0GBF71CL001 & BWRO feed pump trip (P0GCF11AP001& P0GBF72CL001) of SWRO permeate water P0GCF12AP001). storage tank If not low (Last for 2minutes) pump start. 14 OPERATION & CONTROL PHILOSOPHY-WTP Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 The automatic duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.15 BWRO High Pressure Pump (P0GCF41AP001&P0GCF42AP001&P0GCF43AP001, Q’ty : 3 x 100%, Cap. : 118m3/hr, H : 11bar(g)) DCS Operation : SWRO high pressure pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). - Start condition a. BWRO water feed pump run alone. b. BWRO high pressure pump shall be run after 5min. c. If BWRO water feed pump no run, BWRO high pressure pump shall not be run. - Trip condition a. BWRO high pressure pump trip. b. BWRO water feed pump shall be trip after 5min. c. If BWRO high pressure pump no trip, BWRO water feed pump shall not be trip. Instrument with Logic Description: No Cause Consequences 1 High or Low pressure BWRO high pressure pump trip (PIT P0GCF51CP001&P0GCF52CP001) of (P0GCF41AP001&P0GCF42AP001&P0GCF43AP001). BWRO unit suction If not high or Low (Last for 2minutes) pump start. 2 High level (LIT P0GCF61CL001) of BWRO BWRO high pressure pump trip permeate water storage tank (P0GCF41AP001&P0GCF42AP001&P0GCF43AP001). If not high (Last for 2minutes) pump start. The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.16 BWRO Units (P0GCF51AT001&P0GCF52AT001, Q’ty : 2 x 100%, Cap. : 100m3/hr(Product)) Auto operation : Normally the BWRO units shall be kept in auto mode. The units shall operate continuously. Manual mode : In manual mode each valve is operated through an open / close selection from HMI. This mode is useful in start up and for testing purpose. 15 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Start Up Permissive a) Check for at least BWRO unit in auto mode. b) Check for at least pneumatic valve in auto mode. c) Check for at least BWRO water feed pump, BWRO high pressure pump in auto mode. d) Water demand defined by water level (LIT P0GBF71CL001&LIT P0GBF72CL001) in SWRO permeate water storage tank (P0GBF71BB001&P0GBF72BB001). e) Water demand defined by water level (LIT P0GCF61CL001) in BWRO permeate water storage tank. (P0GBF6BB001). Conditions associated to Service Operation sequence Interruption Service sequence is interrupted based on any of the following conditions: a) On receipt of High differential pressure (3.0barg) alarm across BWRO unit. (PIT P0GCF51CP001 & P0GCF52CP001, P0GCF51CP002 & P0GCF52CP002) b) If any on-off valve which is required to open/close in the particular step is not opened/closed, then the sequence is interrupted as per valve sequence chart. (valve fault) c) If associated BWRO unit is removed from auto mode Instrument with Logic Description: No Cause Consequences 1 Low or High flow (FIT P0GCF51CP001 & Flow control according to the set value. P0GCF52CP001) of BWRO unit discharge (FCV P0GCF51AP081 & P0GCF52AP081). High conductivity value (AE Valve open (XV P0GCF51AA053 & P0GCF51CQ001) of BWRO units discharge P0GCF52AA053) and Valve close (XV 2 P0GBF51AA052 & P0GBF52AA052) of BWRO units discharge. If not high (Last for 2minutes) valve open and close. CIP Operation(Manual) is based on any of the following conditions: a) If normalized permeate flux decrease 10%. b) If differential pressure increase 20%. 4.17 BWRO Permeate Water Storage Tank (P0GCF61BB001, Q’ty : 1 x 100%, Cap. : 108m3) Instrument with Logic Description : N/A 4.18 EDI Feed Pump (P0GCF71AP001&P0GCF72AP001, Q’ty : 2 x 100%, Cap. : 100m3/hr, H : 4bar(g)) DCS Operation : EDI feed pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). 16 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Instrument with Logic Description: No Cause Consequences 1 Low flow (FIT P0GCF71CF001) of EDI feed EDI feed pump trip (P0GCF71AP001 & pump discharge P0GCF72AP001). If not low (Last for 2minutes) pump start. 2 High level of Demineralized water storage EDI feed pump trip (P0GCF71AP001 & tank(Out of Scope) P0GCF72AP001). If not high (Last for 2minutes) pump start. 3 Low level (LIT P0GCF61CL001) of BWRO EDI feed pump trip (P0GCF71AP001 & permeate water storage tank P0GCF72AP001). If not low (Last for 2minutes) pump start. The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.19 Flushing Pump (P0GBP41AP001&P0GBP42AP001, Q’ty : 2 x 100%, Cap. : 300m3/hr, H : 3.5bar(g)) DCS Operation : Flushing pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause 1 Low Consequences pressure (PIT P0GBP41CP001) of Flushing pump trip (P0GBP41/42AP001). Flushing pump discharge 2 If not low (Last for 2minutes) pump start. Low level (LIT P0GCF61CL001) of BWRO Flushing pump trip (P0GBP41/42AP001). permeate water storage tank If not low (Last for 2minutes) pump start. The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.20 EDI Units (P0GCF81AT001&P0GCF82AT001, Q’ty : 2 x 100%, Cap. : 95m3/hr(Product)) Auto operation : Normally the EDI units shall be kept in auto mode. The units shall operate continuously. Manual mode : In manual mode each valve is operated through an open / close selection from HMI. This mode is useful in start up and for testing purpose. 17 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Start Up Permissive a) Check for at least EDI unit in auto mode. b) Check for at least pneumatic valve in auto mode. c) Check for at least EDI feed pump in auto mode. d) Water demand defined by water level (LIT P0GCF61CL001) in BWRO permeate water storage tank. (P0GCF61BB001). e) Water demand defined by water level in Demineralized water storage tank (Out of Scope). Conditions associated to Service Operation sequence Interruption Service Sequence is interrupted based on any of the following conditions: a) On receipt of High value alarm across EDI unit. (AE P0GCF81CQ001(Cond.), AE P0GCF81CQ002(pH), AE P0GCF81CQ003(SiO2), AE P0GCF81CQ004(Na)) b) If any on-off valve which is required to open/close in the particular step is not opened/closed, then the sequence is interrupted as per valve sequence chart. (valve fault) c) If associated EDI unit is removed from auto mode Instrument with Logic Description: No Cause Consequences 1 High value of EDI units discharge Valve open (XV-P0GCF81AA052) and Valve close AE P0GCF81CQ001(Cond.), (XV-P0GCF82AA051) of EDI units discharge. AE P0GCF81CQ002(pH), If not high (Last for 2minutes) valve open and close. AE P0GCF81CQ003(SiO2), AE P0GCF81CQ004(Na) CIP Operation(Manual) is based on any of the following conditions: a) If normalized permeate flux decrease 15%. 4.21 H2SO4 Bulk Storage Tank (P0GBN11BB001, Q’ty : 1 x 100%, Cap. : 6.8m3) Instrument with Logic Description: No Cause 1 Low level (LS P0GBN11CL001) of H2SO4 H2SO4 unloading CUM transfer pump trip bulk storage tank Consequences (P0GBN21AP001&P0GBN22AP001). If not low (Last for 2minutes) pump start. 4.22 H2SO4 Unloading CUM Transfer Pump (P0GBN21AP001&P0GBN22AP001, Q’ty : 2 x 100%, Cap. : 5m3/hr, H : 1.5bar(g)) DCS Operation : H2SO4 unloading CUM transfer pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. 18 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause 1 Low level (LS P0GBN41CL080) of H2SO4 H2SO4 unloading CUM transfer pump start dosing tank Consequences (P0GBN21AP001&P0GBN22AP001). If not low (Last for 2minutes) pump trip or When high pump trip The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.23 NaOH Bulk Storage Tank (P0GBN13BB001, Q’ty : 1 x 100%, Cap. : 6.8m3) Instrument with Logic Description: No Cause 1 Low level (LS P0GBN13CL001) of NaOH NaOH unloading CUM transfer pump trip bulk storage tank Consequences (P0GBN23AP001& P0GBN24AP001). If not low (Last for 2minutes) pump start. 4.24 NaOH Unloading CUM Transfer Pump (P0GBN23AP001&P0GBN24AP001, Q’ty : 2 x 100%, Cap. : 5m3/hr, H : 1.5bar(g)) DCS Operation : NaOH unloading CUM transfer pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause 1 Low level (LS P0GBN43CL080) of NaOH NaOH unloading CUM transfer pump start dosing tank Consequences (P0GBN23AP001&P0GBN24AP001). If not low (Last for 2minutes) pump trip. or When high pump trip The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 19 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 4.25 H2SO4 Dosing Tank (P0GBN41BB001, Q’ty : 1 x 100%, Cap. : 1m3) Instrument with Logic Description: No Cause 1 Low level (LS P0GBN41CL080) of H2SO4 H2SO4 dosing pump trip (P0GBN51AP001 & dosing tank Consequences P0GBN52AP001). If not low (Last for 2minutes) pump start. 4.26 H2SO4 Dosing Pump (P0GBN51AP001&P0GBN52AP001, Q’ty : 2 x 100%, Cap. : 10L/hr, H : 5bar(g)) DCS Operation : H2SO4 dosing pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause 1 Low or High pH (AE P0GBF21CQ001) of pH control according to the set value. SWRO water feed pump discharge Consequences If not low or high (Last for 2minutes) pump trip. Chemical Injection Point: H2SO4 dosing set is provided for pH control injection to (By automatic operation) a) Line mixer for SWRO(P0GBF21AM001) The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.27 NaOH Dosing Tank (P0GBN43BB001, Q’ty : 1 x 100%, Cap. : 1m3) Instrument with Logic Description: No Cause 1 Low level (LS P0GBN43CL080) of NaOH NaOH dosing pump trip dosing tank Consequences (P0GBN53AP001 & P0GBN54AP001 & P0GBN55AP001 & P0GBN56AP001). If not low (Last for 2minutes) pump start. 4.28 NaOH Dosing Pump (P0GBN53AP001 & P0GBN54AP001, Q’ty : 2 x 100%, Cap. : 10L/hr, H : 5bar(g) / P0GBN55AP001 & P0GBN56AP001, Q’ty : 2 x 100%, Cap. : 10L/hr, H : 5bar(g)) DCS Operation : NaOH dosing pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. 20 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause 1 Low or High pH (AE P0GCF31CQ001) of pH control according to the set value. BWRO feed pump discharge Consequences If not low or high (Last for 2minutes) pump trip. Chemical Injection Point: NaOH dosing set is provided for pH control injection to (By automatic operation) a) Line mixer for BWRO(P0GCF21AM001) by P0GBN53AP001&P0GBN54AP001 NaOH dosing set is provided for CIP & Process injection to (By Manual operation) a) RO CIP tank(P0GBP51BB001) by P0GBN53AP001&P0GBN54AP001 b) Line mixer for MMF(P0GBB41AM001) by P0GBN55AP001&P0GBN56AP001 The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.29 FeCl3 Dosing Tank (P0GBN81BB001&P0GBN82BB001, Q’ty : 2 x 50%, Cap. : 1m3) Instrument with Logic Description: No Cause Consequences 1 Low level (LS P0GBN81CL080 & FeCl3 dosing pump trip P0GBN82CL080) of FeCl3 dosing tank (P0GBN83AP001& P0GBN84AP001). If not low (Last for 2minutes) pump start. 4.30 FeCl3 Dosing Pump (P0GBN83AP001&P0GBN84AP001, Q’ty : 2 x 100%, Cap. : 20L/hr, H : 5bar(g)) DCS Operation : FeCl3 dosing pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Chemical Injection Point: FeCl3 dosing set is provided for process injection to (By Manual operation) a) Line mixer for MMF (P0GBB41AM001) The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 21 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 4.31 NaOCl Dosing Tank (P0GCN11BB001, Q’ty : 1 x 100%, Cap. : 1m3) Instrument with Logic Description: No Cause Consequences 1 Low level (LS P0GCN11CL080) of NaOCl dosing NaOCl dosing pump trip tank (P0GCN21AP001 & P0GCN22AP001, P0GCN61AP001 & P0GCN62AP001). If not low (Last for 2minutes) pump start. 4.32 NaOCl Dosing Pump (P0GCN21AP001 & P0GCN22AP001, Q’ty : 2 x 100%, Cap. : 1L/hr, H : 5bar(g) / P0GCN61AP001 & P0GCN62AP001, Q’ty : 2 x 100%, Cap. : 1,400L/hr, H : 5bar(g)) DCS Operation : NaOCl dosing pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Chemical Injection Point: NaOCl dosing set is provided for process injection to (By Manual operation) a) Line mixer for UF Backwash(P0GBP21AM001) by P0GCN21AP001&P0GCN22AP001 b) Line mixer for UF CIP(P0GBP52BB001) by P0GCN21AP001&P0GCN22AP001 c) Mixing Tee for Potable water by P0GCN61AP001&P0GCN62AP001 The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.33 SBS Dosing Tank (P0GBN71BB001, Q’ty : 1 x 100%, Cap. : 1m3) Instrument with Logic Description: No Cause 1 Low level (LS P0GBN71CL080) of SBS SBS dosing pump trip (P0GBN63AP001 & dosing tank Consequences P0GBN64AP001). If not low (Last for 2minutes) pump start. 2 Middle level (LS P0GBN71CL080) of SBS Agitator trip (P0GBN72AM001). dosing tank If not middle (Last for 2minutes) agitator start. 4.34 SBS Dosing Pump (P0GBN63AP001&P0GBN64AP001, Q’ty : 2 x 100%, Cap. : 25L/hr, H : 5bar(g)) DCS Operation : SBS dosing pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. 22 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause 1 Low or High ORP (AE P0GCF21CQ002) of ORP control according to the set value. SWRO feed pump discharge Consequences If not low or high (Last for 2minutes) pump trip. Chemical Injection Point: SBS dosing set is provided for ORP control injection to (By automatic operation) a) Line mixer for SWRO(P0GBF21AM001) The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.35 Anti-Scalant Dosing Tank (P0GBN91BB001, Q’ty : 1 x 100%, Cap. : 1.5m3) Instrument with Logic Description: No Cause 1 Low level (LS P0GBN91CL080) of Anti- Anti-Scalant dosing pump trip Scalant dosing tank Consequences (P0GBN93AP001 & P0GBN94AP001, P0GCN61AP001 & P0GCN62AP001). If not low (Last for 2minutes) pump start. 2 Middle level (LS P0GBN71CL080) of Anti- Agitator trip (P0GBN92AM001). Scalant dosing tank If not middle (Last for 2minutes) agitator start. 4.36 Anti-Scalant Dosing Pump (P0GBN93AP001 & P0GBN94AP001, Q’ty : 2 x 100%, Cap. : 30L/hr, H : 5bar(g) / P0GCN61AP001 & P0GCN62AP001, Q’ty : 2 x 100%, Cap. : 7L/hr, H : 5bar(g)) DCS Operation : Anti-Scalant dosing pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Chemical Injection Point: Anti-Scalant dosing set is provided for process injection to (By Manual operation) a) Line mixer for SWRO(P0GBF21AM001) by P0GBN93AP001 & P0GBN94AP001 b) Line mixer for BWRO(P0GCF21AM001) by P0GCN61AP001 & P0GCN62AP001 The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 23 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 4.37 RO CIP Tank (P0GBP51BB001, Q’ty : 1 x 100%, Cap. : 12m3) Instrument with Logic Description: No Cause 1 Low level (LS P0GBP51CL080) of RO CIP RO CIP pump trip (P0GBP61AP001 & tank Consequences P0GBP62AP001). If not low (Last for 2minutes) pump start. 2 Middle level (LS P0GBP51CL080) of RO CIP Agitator trip (P0GBP22AM001). tank 3 If not middle (Last for 2minutes) agitator start. High temp. (TT P0GBP51CT001) of RO CIP Electric heater trip (P0GBP51AH001). tank If not high (Last for 2minutes) electric heater start. 4.38 RO CIP Pump (P0GBP61AP001 & P0GBP62AP001, Q’ty : 2 x 100%, Cap. : 300m3/hr, H : 3bar(g)) DCS Operation : RO CIP pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Chemical Injection Point: CIP chemical dosing set is provided for process injection to (By Manual operation) a) SWRO unit (P0GBF61AT001 & P0GBF62AT001) b) BWRO unit (P0GCF51AT001 & P0GCF52AT001) c) EDI unit (P0GCF81BB001 & P0GCF82BB001) The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. Kind of Chemicals for CIP No Organic substances Inorganic substances Remark 1 NaOH (Concentration 0.1%) Citric acid(C6H8O7) (Concentration 2%) For RO Unit 2 NaOH (Concentration 1%) HCL (Concentration 2%) For EDI Unit & NaCl (Concentration 5%) & NaCl (Concentration 5%) 24 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 4.39 UF CIP Tank (P0GBP52BB001, Q’ty : 1 x 100%, Cap. : 12m3) Instrument with Logic Description: No Cause Consequences 1 Low level (LS P0GBP52CL080) of UF CIP UF CIP pump trip (P0GBP63AP001 & tank P0GBP64AP001). If not low (Last for 2minutes) pump start. 2 Middle level (LS P0GBP52CL080) of UF CIP Agitator trip (P0GBP23AM001). tank 3 If not middle (Last for 2minutes) agitator start. High temp. (TT P0GBP52CT001) of UF CIP Electric heater trip (P0GBP52AH001). tank If not high (Last for 2minutes) electric heater start. 4.40 UF CIP Pump (P0GBP63AP001 & P0GBP64AP001, Q’ty : 2 x 100%, Cap. : 302m3/hr, H : 3bar(g)) DCS Operation : UF CIP pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Chemical Injection Point: CIP chemical dosing set is provided for process injection to (By Manual operation) a) UF unit (P0GBB61AT001 & P0GBB62AT001) The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. Kind of Chemicals for CIP No Organic substances Inorganic substances Remark 1 NaOCl (Concentration 0.3%) Citric acid(C6H8O7) (Concentration 3%) or HCl (Concentration 0.3%) For UF Unit 4.41 NaHCO3 Dosing Tank (P0GCN31BB001, Q’ty : 1 x 100%, Cap. : 1.8m3) Instrument with Logic Description: No Cause Consequences 1 Low level (LS P0GCN31CL001) of NaHCO3 NaHCO3 dosing pump trip (P0GCN41AP001 & dosing tank P0GCN42AP001). If not low (Last for 2minutes) pump start. 2 Middle level (LS NaHCO3 dosing tank P0GCN31CL001) of Agitator trip (P0GCN32AM001). If not middle (Last for 2minutes) agitator start. 25 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP 4.42 NaHCO3 Dosing Pump (P0GCN41AP001 & P0GCN42AP001, Q’ty : 2 x 100%, Cap. : 50L/hr, H : 5bar(g)) DCS Operation : NaHCO3 dosing pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). Instrument with Logic Description: No Cause Consequences 1 Low or High Conductivity Conductivity control according to the set value. (AE P0GBF22CQ002) of SWRO unit If not low or high (Last for 2minutes) pump trip. discharge Chemical Injection Point: NaHCO3 dosing set is provided for Conductivity control injection to (By automatic operation) a) Line mixer for Potable water(P0GBF22AM001) The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.43 CaCl2 Dosing Tank (P0GCN33BB001, Q’ty : 1 x 100%, Cap. : 1.8m3) Instrument with Logic Description: No Cause 1 Low level (LS P0GCN33CL001) of CaCl2 CaCl2 dosing pump trip (P0GCN43AP001 & dosing tank Consequences P0GCN44AP001). If not low (Last for 2minutes) pump start. 2 Middle level (LS P0GCN33CL001) of CaCl2 Agitator trip (P0GCN34AM001). dosing tank If not middle (Last for 2minutes) agitator start. 4.44 CaCl2 Dosing Pump (P0GCN43AP001 & P0GCN44AP001, Q’ty : 2 x 100%, Cap. 50L/hr, H : 5bar(g)) DCS Operation : CaCl2 dosing pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). 26 Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP Instrument with Logic Description: No Cause Consequences 1 Low or High Conductivity Conductivity control according to the set value. (AE P0GBF22CQ002) of SWRO unit If not low or high (Last for 2minutes) pump trip. discharge Chemical Injection Point: CaCl2 dosing set is provided for Conductivity control injection to (By automatic operation) a) Line mixer for Potable water(P0GBF22AM001) The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 4.45 Brine Storage Pond (P0GBB76BB001 & P0GBB77BB001, Q’ty : 2 x 50%, Cap. 219m3) Instrument with Logic Description: No Cause Consequences 1 Low level (LIT P0GBB76CL001 & Backwash waste transfer pump trip P0GBB77CL001) of Brine storage pond (P0GBB78AP001 & P0GBB79AP001). If not low (Last for 2minutes) pump start. 4.46 Backwash Waste Transfer Pump (P0GBB78AP001 & P0GBB79AP001, Q’ty : 2 x 100%, Cap. 300m3/hr, H : 3bar(g)) DCS Operation : Backwash waste transfer pump operated through DCS in auto mode operation. Manual Mode Operation : In manual operation mode, each pump can be started and stopped manually through DCS in manual mode operation. Auto Mode Operation : In auto operation mode, duty pump start and trip automatically based on process condition (Level, Flow, Pressure etc). The manual duty /standby changeover will be triggered by: - The duty pump fails to start. - When the start signal of the duty pump is not feed back. 27 OPERATION & CONTROL PHILOSOPHY-WTP 5. Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 Set Point Summary P&ID Tag No. Service Consequence Set Point (Note 2) Page LIT01 of 24 P0GBB11CL001 & Level of Settlement Basin P0GBB12CL001 01 of 24 02 of 24 AE- Turbidity at outlet of MMF feed P0GBB31CQ001 pump FITP0GBB51CF001 & P0GBB52CF001 PDIT- 02 of 24 P0GBB51CP001 & P0GBB52CP001 03 of 24 PITP0GBB61CP001 & P0GBB61CP002 04 of 24 PITP0GBB62CP001 & P0GBB62CP002 04 of 24 05 of 24 AE-P0GBB61CQ001 LITP0GBB71CL001 & P0GBB72CL001 05 of 24 AEP0GBB21CQ001 05 of 24 05 of 24 2600mm (H) Action by control logic 1400mm (L) Action by control logic 700mm (LL) Alarm 10 NTU (H) Alarm Operation 486 m3/hr Flowrate at outlet of MMF feed 535m3/hr (H) pump 3 Alarm, 438m /hr (L) Action by control logic Differential Pressure of Multi 1.0barg (HH) Alarm media filter 0.8barg (H) Action by control logic of UF unit (Differential pressure 1.8barg (HH) Alarm is automatically calculated by 1.5barg (H) Action by control logic of UF unit (Differential pressure 1.8barg (HH) Alarm is automatically calculated by 1.5barg (H) Action by control logic 0.5 NTU (H) Alarm 4400mm (HH) Alarm Level of Filtered water storage 4200mm (H) Action by control logic pond 1400mm (L) Action by control logic 1200mm (LL) Alarm Operation 7.5 Action by control logic 8.5 (H) Alarm 6.5 (L) Alarm Operation below Action by control logic Pressure at suction and discharge each PIT) Pressure at suction and discharge each PIT) Turbidity at outlet of UF unit pH at outlet of SWRO feed pump AE- ORP at outlet of SWRO feed P0GBF21CQ001 pump AE- Conductivity at outlet of SWRO P0GBF21CQ003 feed pump 300mV 350 mV (H) Alarm 57000㎲/㎠(H) Alarm Operation 2.5barg 05 of 24 PIT- Pressure at discharge of UF P0GBP11CP001 backwash pump 28 3barg (H) Alarm 2barg (L) Action by control logic OPERATION & CONTROL PHILOSOPHY-WTP P&ID Tag No. Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 Service Consequence Set Point (Note 2) Page 06 of 24 LITP0GBB81CL001 Level of Filter backwash tank 12700mm (HH) Alarm 12500mm (H) Action by control logic 600mm (L) Action by control logic 400mm (LL) Alarm Operation 3.0barg 06 of 24 06 of 24 PIT- Pressure at discharge of Filter P0GBP31CP001 backwash pump PDIT- Differential Pressure of Micro P0GBF31CP001 cartridege filter for SWRO unit PIT06 of 24 3.5barg (H) Alarm 2.5barg (L) Action by control logic 0.8barg (H) Alarm Operation 5.0barg P0GBF41CP001 & Pressure at discharge of SWRO P0GBF42CP001 & water feed pump 6.0barg (H) P0GBF43CP001 Alarm 4.0barg (L) Action by control logic 3 06 of 24 FITP0GBF41CF001 & P0GBF42CF001 Operation 462 m /hr Flowrate at outlet of SWRO high 510m3/hr (H) pressure pump 3 420m /hr (L) Alarm Alarm Operation 51barg 07 of 24 PIT- Pressure at discharge of SWRO P0GBF61CP001 high pressure pump 56barg (H) Action by control logic 46barg (L) Action by control logic Operation 50barg 07 of 24 07 of 24 PIT- Pressure at discharge of SWRO P0GBF61CP002 brine FITP0GBF61CF001 Flowrate at outlet of SWRO unit 55barg (H) Alarm 45barg (L) Alarm Operation 194 m3/hr Action by control logic 213m3/hr (H) Alarm 175m3/hr (L) Alarm Operation 51barg 08 of 24 PIT- Pressure at discharge of SWRO P0GBF62CP001 high pressure pump 56barg (H) Action by control logic 46barg (L) Action by control logic Operation 50barg 08 of 24 08 of 24 PIT- Pressure at discharge of SWRO P0GBF62CP002 brine FITP0GBF62CF001 Flowrate at outlet of SWRO unit 55barg (H) Alarm 45barg (L) Alarm Operation 194 m3/hr Action by control logic 213m3/hr (H) Alarm 3 175m /hr (L) 29 Alarm Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP P&ID Tag No. Service Consequence Set Point (Note 2) Page 09 of 24 09 of 24 09 of 24 09 of 24 09 of 24 AE- Conductivity at outlet of SWRO 600㎲/㎠(HH) Alarm P0GBF61CQ001 unit 550㎲/㎠(H) Action by control logic AE- pH at outlet of SWRO unit 8.5 (H) Alarm P0GBF22CQ001 (for service & potable water) 6.5 (L) Alarm AE- Conductivity at outlet of SWRO 1000㎲/㎠(H) Alarm P0GBF22CQ002 unit (for service & potable water) 500㎲/㎠(L) Alarm AE- ORP at outlet of SWRO unit 400 mV (H) Alarm P0GBF22CQ003 (for potable water) 200 mV (L) Alarm 4900mm (HH) Alarm Level of SWRO permeate water 4700mm (H) Action by control logic storage tank 600mm (L) Action by control logic 400mm (LL) Alarm 0.8barg (H) Alarm Operation 7.5 Action by control logic 8.5 (H) Alarm 6.5 (L) Alarm LITP0GBF71CL001 & P0GBF72CL001 10 of 24 10 of 24 PDIT- Differential Pressure of micron P0GCF31CP001 cartridege filter AEP0GCF31CQ001 pH at outlet of BWRO feed pump Operation 2.5 barg 10 of 24 PIT- Pressure at discharge of BWRO P0GCF31CP002 feed pump 3barg (H) Alarm 2barg (L) Action by control logic Operation 13.5 barg 11 of 24 PIT- Pressure at discharge of BWRO P0GCF51CP001 high pressure pump 16barg (H) Action by control logic 10barg (L) Action by control logic Operation 8.5 barg 11 of 24 PIT- Pressure at discharge of BWRO P0GBF51CP002 brine 10barg (H) Alarm 7barg (L) Alarm 3 11 of 24 FITP0GCF51CF001 Flowrate at outlet of BWRO unit Operation 88 m /hr Action by control logic 96m3/hr (H) Alarm 3 80m /hr (L) Alarm Operation 13.5 barg 12 of 24 PIT- Pressure at discharge of BWRO P0GCF52CP001 high pressure pump 16barg (H) Action by control logic 10barg (L) Action by control logic Operation 8.5 barg 12 of 24 PIT- Pressure at discharge of BWRO P0GBF52CP002 brine 30 10barg (H) Alarm 7barg (L) Alarm Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP P&ID Tag No. Service Consequence Set Point (Note 2) Page 12 of 24 FITP0GCF52CF001 12 of 24 13 of 24 Flowrate at outlet of BWRO unit Operation 88 m3/hr Action by control logic 96m3/hr (H) Alarm 80m3/hr (L) Alarm, AE- Conductivity at outlet of BWRO 20㎲/㎠(HH) Alarm P0GCF51CQ001 unit 15㎲/㎠(H) Action by control logic 7700mm (HH) Alarm LIT- Level of BWRO permeate water 7500mm (H) Action by control logic P0GCF61CL001 storage tank 800mm (L) Action by control logic 600mm (LL) Alarm 3 Operation 88 m /hr 13 of 24 FIT- Flowrate at outlet of EDI feed P0GCF71CF001 pump 96m3/hr (H) Alarm 3 80m /hr (L) Action by control logic Operation 3.5 barg 13 of 24 PIT- Pressure at discharge of flushing P0GBP41CP001 pump AE15 of 24 P0GCF81CQ001 AE- 15 of 24 P0GCF81CQ002 AE- 15 of 24 P0GCF81CQ003 AE- 15 of 24 P0GCF81CQ004 4.5barg (H) Alarm, 2.5barg (L) Action by control logic 0.2㎲/㎠(HH) Alarm 0.18㎲/㎠(H) Action by control logic 8.5 (H) Alarm 6.5 (L) Alarm 0.02ppm(HH) Alarm 0.015ppm(H) Action by control logic 0.02ppm(HH) Alarm Conductivity at outlet of EDI unit pH at outlet of EDI unit Silica at outlet of EDI unit Sodium at outlet of EDI unit 0.015ppm(H) Action by control logic 3 Operation 84 m /hr 15 of 24 FITP0GCF81CF001 Flowrate at outlet of EDI unit 92m3/hr (H) 3 16 of 24 16 of 24 17 of 24 LSP0GBN11CL001 LSP0GBN13CL001 LSP0GBN41CL080 Level of H2SO4 bulk storage tank Level of NaOH bulk storage tank Level of H2SO4 dosing tank 31 Alarm, 76m /hr (L) Alarm 2800mm (H) Alarm 300mm (L) Action by control logic 150mm (LL) Alarm 2850mm (H) Alarm 350mm (L) Action by control logic 200mm (LL) Alarm 850mm (HH) Alarm 700mm (H) Action by control logic 250mm (L) Action by control logic 130mm (LL) Alarm Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 OPERATION & CONTROL PHILOSOPHY-WTP P&ID Tag No. Service Consequence Set Point (Note 2) Page 17 of 24 LSP0GBN43CL080 Level of NaOH dosing tank LS18 of 24 P0GBN81CL080 & Level of FeCl3 dosing tank P0GBN82CL080 19 of 24 19 of 24 LSP0GCN11CL080 LSP0GBN71CL080 20 of 24 LSP0GBN91CL080 21 of 24 LSP0GBP51CL080 TT21 of 24 P0GBP51CT001 AE- 21 of 24 21 of 24 21 of 24 P0GBP61CQ001 Level of RO CIP tank Temperature of RO CIP tank pH at outlet of RO CIP tank P0GBP71CP001 cartridege filter LS- P0GBP52CT001 AEP0GBP63CQ001 PDIT- 21 of 24 Level of Anti-Scalant dosing tank Differential Pressure of RO CIP TT- 21 of 24 Level of SBS dosing tank PDIT- P0GBP52CL080 21 of 24 Level of NaOCl dosing tank P0GBP72CP001 Level of UF CIP tank Temperature of UF CIP tank pH at outlet of UF CIP tank Differential Pressure of UF CIP cartridege filter 32 850mm (HH) Alarm 700mm (H) Action by control logic 250mm (L) Action by control logic 130mm (LL) Alarm 900mm (H) Alarm 300mm (L) Action by control logic 180mm (LL) Alarm 900mm (H) Alarm 300mm (L) Action by control logic 180mm (LL) Alarm 900mm (H) Alarm 600mm (M) Action by control logic 300mm (L) Action by control logic 180mm (LL) Alarm 1000mm (H) Alarm 600mm (M) Action by control logic 300mm (L) Action by control logic 180mm (LL) Alarm 2250mm (H) Alarm 800mm (M) Action by control logic 600mm (L) Action by control logic 480mm (LL) Alarm 38℃ (HH) Alarm 35℃ (H) Action by control logic 2 to 3 Inorganic cleaning 10 to 12 Organic cleaning 0.8barg (H) Alarm 2250mm (H) Alarm 800mm (M) Action by control logic 600mm (L) Action by control logic 480mm (LL) Alarm 38℃ (HH) Alarm 35℃ (H) Action by control logic 2 to 3 Inorganic cleaning 10 to 12 Organic cleaning 0.8barg (H) Alarm OPERATION & CONTROL PHILOSOPHY-WTP P&ID Tag No. Service Doc. No. : J910-XS01-P0GBB-125727 Rev : 0 Consequence Set Point (Note 2) Page 22 of 24 LSP0GCN31CL001 22 of 24 LSP0GCN33CL001 1300mm (H) Alarm 600mm (M) Action by control logic 300mm (L) Action by control logic 180mm (LL) Alarm 1300mm (H) Alarm 600mm (M) Action by control logic 300mm (L) Action by control logic 180mm (LL) Alarm 3050mm (H) Alarm 500mm (L) Action by control logic 300mm (LL) Alarm 0.7m3/hr (H) Alarm 0.7m3/hr (H) Alarm Pressure of Instrument air 4barg (L) Alarm Pressure of Service air 4barg (L) Alarm Level of NaHCO3 dosing tank Level of CaCl2 dosing tank LIT23 of 24 P0GBB76CL001 & Level of Brine storage pond P0GBB77CL001 23 of 24 23 of 24 FS- Flow of Eye washer & Safety P0GKC11CF080 shower FS- Flow of Eye washer & Safety P0GKC12CF080 shower PS24 of 24 P0GBY11CP080 PS- 24 of 24 P0GBY12CP080 Note 1. Actual set figure (point) will be derived based on the plant commissioning trials. 2. Refer to the para. 5. Control Logic Description 6. Reference documents and drawings: - P & I Diagram(J910-XG02-P0GCF-125706) - Process Flow Diagram(J910-XG07-P0GCF-125705) - System Description(J910-XS00-P0GCF-125709) - GA Drawing for Sea Water Settlement Basin(J910-YT01-P0GBD-125704) - GA Drawing for Filtered Water Storage Tank(J910-YT01-P0GBD-125761) - GA Drawing for Brine Water Storage Pond (J910-YT01-P0GBD-125762) 33 1. THE MULTI MEDIA FILTER SHALL BE OPERATED AS PER SEQUENCE. 51AA052 MMF A UNIT 51AA053 MMF B UNIT 51AA062 11AA051 52AA052 52AA058 52AA055 52AA062 11AA052 52AA059 (P0GBN-) FECL3 DOSING PUMP (P0GBN-) NAOH DOSING PUMP (P0GBP-) (P0GBC-) FILTER BACKWASH BLOWER (P0GBB-) MMF FEED PUMP (P0GBB-) BACKWASH TANK INLET (P0GBB-) RINSE OUTLET (P0GBB-) (P0GBB-) WATER BACKWASH INLET VENT WATER BACKWASH OUTLET 51AA056 51AA057 54AA051 REMARK 51AA055 51AA063 51AA060 52AA053 App.24hr 51AA059 51AA054 ● NOMINAL SERVICE PUMP & BLOWER 51AA058 53AA051 52AA054 1 (P0GBB-) (P0GBB-) AIRBACKWASH INLET DRAIN (P0GBB-) FLOW SERVICE OUTLET TIME (MIN) (P0GBB-) (P0GBB-) PROCESS (P0GBB-) STEP SERVICE INLET VALVE FILTER BACKWASH PUMP *Table 52AA063 52AA060 52AA056 51AA061 53AA052 31AP001 11AN001 31AP001 55AP001 83AP001 32AP001 12AN001 32AP001 56AP001 84AP001 ■ ■ 52AA061 52AA057 ■ ● 500m3/hr ● 2 DRAIN ▲ - 3 AIR BACKWASH 10 505Nm3/hr 4 WATER BACKWASH 10 350m3/hr 5 SETTING 5 - 6 RINSE 15 170m3/hr 7 AIR BACKWASH 10 505Nm3/hr 8 WATER BACKWASH 10 350m3/hr 9 SETTING 5 - 10 RINSE 15 170m3/hr 11 AIR BACKWASH 10 505Nm3/hr 12 WATER BACKWASH 10 350m3/hr 13 SETTING 5 - 14 RINSE 15 170m3/hr 15 STAD-BY - ● ● ● ■ ● ● FIRST CELL ■ ● FIRST CELL FIRST CELL ● ● ● ■ ■ ■ ■ ● ● SECOND CELL ■ ● FIRST CELL SECOND CELL SECOND CELL ● ● ● ■ ■ ■ ■ ● ● THIRD CELL ■ ● SECOND CELL THIRD CELL THIRD CELL ● - A. LEGEND : ● VALVE OPEN, ■ PUMP RUN, ▲ TIME FIELD SETTING B. THE SEQUENCE TIME WILL BE FIXED DEPENDING ON THE FIELD CONDITIONS. ● ■ ■ ■ THIRD CELL 2. UF UNIT SHALL BE OPERATED AS PER SEQUENCE. UF UNIT NORMAL SERVICE 61AA051 61AA056 ● 61AA053 61AA059 61AA061 61AA058 FILL-UP 35 479m3/hr ● SERVICE 30 min 479m3/hr ● WATER BACKWASH 45 580m3/hr ● AIR BACKWASH 60 505m3/hr ● DRAIN 45 - ● PRE BACKWASH 20 580m3/hr ● ● BACKWASH 45 580m3/hr ● ● 20 min - ● AIR BACKWASH 60 505Nm3/hr ● DRAIN 45 - ● WATER BACKWASH 30 580m3/hr ● AIR BACKWASH 30 505Nm3/hr ● DRAIN 45 - ● SOAKING 61AA060 A. LEGEND : ● VALVE OPEN, ■ PUMP RUN, B. TMC INTERVAL : ONE TIME PER DAY C. THE SEQUENCE TIME WILL BE FIXED DEPENDING ON THE FIELD CONDITIONS. (P0GBN-) 11AP001 11AN001 61AP001 12AP001 12AN001 62AP001 ● ■ ● ■ ● ● ● ● ■ ■ ■ ■ ■ ● TMC RINSE NAOCL DOSING PUMP (P0GBC-) (P0GBP-) FILTER BACKWASH PUMP (P0GBB-) DRAIN OUTLET (P0GBB-) WATER BACKWASH INLET VENT PUMP & BLOWER (P0GBB-) (P0GBB-) AIRBACKWASH INLET (P0GBB-) SERVICE OUTLET FLOW (P0GBB-) (sec) PRE SERVICE & TIME BACKWASH OUTLET PROCESS (P0GBB-) STEP SERVICE INLET VALVE FILTER BACKWASH BLOWER *Table ● ● ■ ● ■ ● ● ● REMARK