CEERS REVIEW CENTER EE REVIEW SEPTEMBER APRIL2022 2022 2021 APRIL PEC Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.philippines@yahoo.com BRANCH CIRCUIT ❑ PERMISSIBLE LOAD (a) 15- and 20-ampere branch circuit- A 15- or 20 – ampere branch circuit shall be permitted to supply lighting units or other utilization equipment, or a combination of both. 1. Cord-and –plug Equipment not Fastened in place. The rating of any one cord-and-plug connected utilization equipment not fastened in place shall not exceed 80 percent of the branch circuit rating. 2. Utilization equipment not Fastened in place. The total rating of utilization equipment not fastened in place other than luminaires shall not exceed 50 percent of the branch circuit rating where lighting units, cord-and-plug connected utilization equipment not fastened in place, or both, are also supplied Ex. 1. The rating of any one cord-and-plug connected appliance used in a 20-ampere branch circuit shall not exceed _____ amperes. Ex. 2. The total rating of appliances not fastened is in place connected to a 20-amp branch circuit which also supplies lighting units shall not exceed _____ amps (b) 30 ampere branch circuits; A 30-ampere branch circuit shall be permitted to supply fixed lighting units with heavy duty lampholders. A rating of any one cord-and-plug connected utilization equipment shall not exceed 80 percent of the branch circuit ampere rating. (c) 40-and 50-ampere branch circuit. A 40-and 50-amperes branch circuit shall be permitted to supply cooking appliances that are fastened in place in any occupancy (d) Branch circuits larger than 50 amperes Branch circuits larger than 50 ampere shall supply only nonlighting outlet loads. A dwelling unit is defines as “one or more rooms” with provision for eating, living, sleeping, cooking, and sanitation. ➢ For a dwelling the code lists only 3 rules you shall have when sizing the service. 1. Lighting load for listed Occupancies. A unit load of not less than that specified for occupancies listen therein shall constitute the minimum lighting load for each square meter of floor area. The floor area for each floor shall be computed from the outside dimensions of the building, apartment, or other area involved. For dwelling unit(s),the computed floor area shall not include open porches, garages, or unused or unfinished spaces not adaptable for future use. 2. In each dwelling unit the feeder load shall be computed at 1500 volt-amperes for each 2-wire small appliance branch circuit required for small appliances supplied by 15 or 20 ampere receptacles on 20 ampere branch circuits in the kitchen. Where the load is subdivided through two or more feeders, the computed load for each shall include not less than 1500 voltamperes for each 2-wire branch circuit for small appliances. These loads shall be permitted to be included with the general lighting load and subjected to the demand factors permitted for the general lighting load. 3. A feeder load of not less than 1500 volt-ampere shall be included for each 2-wire laundry branch circuit installed as required by . It shall be permissible to include this load with the general lighting load and subject it to the demand factors provided. These are the 3 items you shall have in a dwelling: ➢ ➢ ➢ 24va per sq meter of living area 2 small appliance circuits at 1500va each 1 laundry circuit at 1500va v. RANGE LOAD Lighting and Receptacle Loads a. Lights b. Stereo c. Dresser Lamp d. Floor Lamp e. Table Lamp f. Television Set g. Vacuum Cleaner Small Appliances a. Coffee Maker b. Refrigerator c. Food Mixer d. Deep Fryer e. Toaster f. Blender g. Hand Iron Fixed Appliance Load a. Ranges b. Water Heaters c. Dryers d. Dishwasher e. Disposer GENERAL METHOD I. GENERAL LIGHTING AND CONVENIENCE RECEPTACLES LOAD a. Lighting and convenience receptacle load, 24 VA per sq meter. b. Minimum of two small appliance circuits c. Laundry Load II. Air conditioning units and Heating load. (Noncoincident Loads) III. Fixed appliances or Fastened in place appliances For three or less appliances , D.F. =100% For four or more appliances, D.F.= 75% IV. DRYERS [1/3] pec CEERS REVIEW CENTER APRIL 2022 2021 EE REVIEW SEPTEMBER PEC Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.philippines@yahoo.com Types of Occupancy Unit Load per Sq. M. (Volt-Amperes) Armories & Auditoruim 8 Banks 28** Barber Shops and Beauty Parlor 24 Churches 8 Clubs 16 Court Rooms 16 *Dwelling Units 24 Garages – Commercial (Storage) 4 Hospitals 16 *Hotels and Motels, including apartment houses without provisions for cooking by tenants 16 Industrial Commercial (Loft) Building 16 Lodge Rooms Example. 5. What is the general lighting and receptacle demand load for dwelling 300 m2 area. ➢ 12 Office Buildings 28** Restaurants 16 Schools 24 Stores 24 Warehouses (storage) 2 In any of the above occupancies except one-family dwelling and individual dwelling units of two-family and of multifamily dwellings: Assembly Halls and Auditoriums Halls, Corridors, Closets, Stairways Storage Spaces 8 4 2 Table 2.20.3.3 Feeder Demand Factors for General Lighting Load and Small Appliance Load Types of Occupancy Dwelling Units *Hospitals *Hotels and Motels – Including Apartment Houses Without Provision for Cooking by Tenants Warehouses (Storage) All Others Example.4. Determine the minimum small appliance and laundry loads required in a dwelling Portion of Lighting Load to Which Demand Factor Applies (volt-amperes) First 3 000 or less at From 3 001 to 120 000 at Remainder over 120,000 at ……………. First 50 000 or less at Remainder over 50 000 at …………….. First 20 000 or less at From 20 001 to 100 000 at Remainder over 100 000 at …………… First 12,500 or less at Remainder over 12 500 at …………….. Total Volt-amperes …………………….. Demand Facto r Percent 100 35 25 40 20 50 40 30 100 50 Fixed or fastened in place appliances. The fixed appliance load is determined by adding wattage (voltamp) values from appliance nameplates for three or less fixed appliances. If there are four or more fixed appliances, 75% of the wattage values on the nameplate is permitted. This demand factor does not apply to ranges, dryers, air conditioners, or space heating units. Example: 6. Determine the demand load for the following fixed appliances. Water heater load 6000 watts Dishwasher load 1500 watts Compactor 900 watts Disposal load 800 watts Vent fan load 400 watts Attic fan load 1600 watts ➢ Number of Dryers Demand Factor (Percent) 1–4 5 6 7 8 9 10 11 12 – 22 100% 85% 75% 65% 60% 55% 50% 47% % = 47 – (number of dryers – 11) 23 35% 24 – 42 % - 35 - [0.5 x (number of dryers – 23)] 43 and over 25% Example: 7. Determine the demand load for six dryers rated at 5 kw each. Electric cloths Dryers ,- Dwelling Units. The load for household electric clothes dryers in dwelling unit shall be either 5000 watts (volt-amp) or the nameplate rating , whichever is larger, for each dryer served. The use of demand factors shall be permitted. Tables 2.20.3.15 Demand Factors for Household Electric Clothes Dryers 100 *The demand factors of this table shall not apply to the calculated load of feeders or services supplying areas in hospitals, hotels, and motels where the entire lighting is likely to be used at one time, as in operating rooms, ballrooms, or dining rooms. Example.3. Determine the lighting and receptacle loads for a dwelling unit of 400 m2 pec [2/3] CEERS REVIEW CENTER EE REVIEW SEPTEMBER APRIL 2022 2021 PEC Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.philippines@yahoo.com Tables 2.20.3.16 Demand Factors and Loads for Household Electric Ranges, Wall-Mounted Ovens, Counter-mounted Cooking Units, and Other Household Cooking Appliances over 1 ¾ kW Rating (Column C to be used in all cases except as otherwise permitted in Note 3.) Demand Factor(Percent)(See Notes) Column A (Less than 3 ½ kW Rating) Column B (3 ½ than 8 ¾ kW Rating) 1 80% 80% 2 75% 65% 11kW 3 70% 55% 14 kW 4 66% 50% 17 kW 5 62% 45% 20 kW 6 59% 43% 21 kW 7 56% 40% 22 kW 8 53% 36% 23 kW 9 51% 35% 24 kW 10 49% 34% 25 kW 11 47% 32% 26 kW 12 45% 32% 27 kW 13 43% 32% 28 kW 14 41% 32% 29 kW 15 40% 32% 30 kW 16 39% 28% 31 kW 17 38% 28% 32 kW 18 37% 28% 33 kW 19 36% 28% 34 kW 20 35% 28% 35 kW 21 34% 26% 36 kW 22 33% 26% 37 kW 23 32% 26% 38 kW 24 31% 26% 39 kW 25 30% 26% 40 kW 26 - 30 30% 24% 15 kW+ 1 31 - 40 30% 22% kW for each range 41 - 50 30% 20% 25 kW + ¾ 51 - 60 30% 18% kW for each range 61 and over 30% 16% Number of Appliances Column C Maximum Demand(kW) (See Notes) (Not over 12 kWRating) 8kW Example 9. What is the demand load for twenty 8 kW household ranges? Example 10. What is the demand on the service for 25 – 8.5 kW ranges? Example 11. What is the demand load on the service for two 12 kW ranges? Example 12. What is the demand load on the service for 4 – 3 kW counter-mounted cooktops? [3/3] pec CEERS REVIEW CENTER EE REVIEW APRIL 2021 2 NOTES: PEC MOTORS Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.philippines@yahoo.com STEP 5: Feeder wire size STEP 4: Branch circuit overcurrent device STEP 6: Feeder overcurrent device STEP 3: Branch circuit wires STEP 2: Overload M M STEP 1: F.L.C Step 1 FLC (Full-Load Current) Full-load currents in Amperes, Single-phase Alternating current Motors HP 1/6 1/4 1/3 1/2 3/4 1 1½ 2 3 5 7½ 10 115V 4.4 5.8 7.2 9.8 13.8 16 20 24 34 56 80 100 200V 2.5 3.3 4.1 5.6 7.9 9.2 11.5 13.8 19.6 32.2 46.0 57.5 208V 2.4 3.2 4.0 5.4 7.6 8.8 11 13.2 18.7 30.8 44.0 55.0 230V 2.2 2.9 3.6 4.9 6.9 8 10 12 17 28 40 50 Full-load Current, Three-Phase Alternating-Current Motors Induction Type Squirrel-Cage and Wound-Rotor (Amperes) Synchronous Type Unity Power Factor (Amperes) HP 115V 200V 208V 230V 460V 575V 2300V 230V 460V ½ 3/4 1 1½ 2 3 5 7½ 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 350 400 450 500 4.4 6.4 8.4 12.0 13.6 --------------------------------------------- 2.5 3.7 4.8 6.9 7.8 11.0 17.5 25.3 32.2 48.3 62.1 78.2 92 120 150 177 221 285 359 414 552 ------------- 2.4 3.5 4.6 6.6 7.5 10.6 16.7 24.2 30.8 46.2 59.4 74.8 88 114 143 169 211 273 343 396 528 ------------- 2.2 3.2 4.2 6.0 6.8 9.6 15.2 22 28 42 54 68 80 104 130 154 192 248 312 360 480 ------------- 1.1 1.6 2.1 3.0 3.4 4.8 7.6 11 14 21 27 34 40 52 65 77 96 124 156 180 240 302 361 414 477 515 590 .9 1.3 1.7 2.4 2.7 3.9 6.1 9 11 17 22 27 32 14 52 62 77 99 125 144 192 242 289 336 382 412 472 ------------------------------16 20 26 31 37 49 60 72 83 95 103 118 ----------------------53 63 83 104 123 155 202 253 302 400 ------------- ----------------------26 32 41 52 61 78 101 126 151 201 ------------- 575V ----------------------21 26 33 42 49 62 81 101 121 161 ------------- 2300V -----------------------------12 15 20 25 30 40 ------------- Step 2 Motor branch – circuit Over load current protection Motor Service Factor . Motor ratings are based on a service factor stamped on the on the plate of the motor, ranging from 1.00 to 1.35. If for a specific motor the service factor is 1.00, it means that if the motor is installed in a location where the ambient temperature is not over 40o C or 104o F, it can deliver its rated horsepower continuously without harm. But if the service factor is, for example 1.15, it means that the motor can be used up to 1.15 times its rated horsepower under the same conditions. For example, a 10 hp motor has a service factor of 1.15, the motor can be allowed to develop 11.5 hp without causing undue Pec motors [1/5] CEERS REVIEW CENTER EE REVIEW APRIL 2021 2 NOTES: PEC MOTORS Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.philippines@yahoo.com deterioration to the insulation. The higher service factor provides temporary extra power if needed. Temperature Rise. Current passing through the windings of a motor results in an increase in the motor temperature. The difference between the winding temperature of the motor when running and the ambient temperature is called the temperature rise. The temperature rise produced at full load is not harmful if it does not exceed 40oC (104oF). Higher temperature caused by increased current or higher ambient temperatures produces a deteriorating effect on the motor insulation and lubrication. Allowable Ampacities of Insulated Conductors Rated 0 – 2000V, 60C through 90C, Not More Than Three Current – Carrying Conductors in Raceway, Cable or Earth (Directly Buried), Based on Ambient Temperature of 30C Temperature Rating of Conductor. See Table 3.10.1.16 Size mm 2 60C 75C 90C 60C 75C 90C TYPES +TW +UF TYPES +FEPW, +RH +THHW +THW, +THWN, +XHHW, +USE, +ZW TYPES TBS, SIS, +FEP +FEPB, +RHH, +THHN, +THHW +XHHW TYPES +TW +UF TYPES +RH, +RHW +THHW, +THW +THWN, +XHHW, +USE TYPES TBS, SIS, +RHH +THHW, +THHN, +XHHW All Other Motors. Motor with a service factor less than 1.15 or a temperature rise more than 40oC would be classified All other motors. Branch Circuit Overload Protection Classification Motors marked with service factor 1.15 or greater Motors with a marked temperature rise 40C or less All other motors Overload Device 125% Overload Relay 140% 125% 140% 115% 130% Example 1: What is the minimum size running overload protection for a 1 ½-hp 230-V single-phase squirrel cage motor? FLC = 10 A. Example 2: What is the minimum size running overload protection for the motor in Problem 1 with a service factor of 1.2 Step 3. Branch Circuit Conductor Sizing Branch circuit conductors supplying a single motor shall have an ampacity not less than 125% of the motor full load current rating. COPPER 2.0 3.5 5.5 8.0 14 22 30 38 50 60 80 100 125 150 200 250 325 400 500 20 25 35 50 55 70 90 100 120 135 160 185 210 240 280 315 370 405 445 20 25 35 50 65 85 110 125 145 160 195 220 255 280 330 375 435 485 540 25 30 40 55 70 90 115 130 150 170 205 225 265 295 355 400 470 515 580 ALUMINUM OR COPPER ALUMINUM … … 20 20 25 30 30 40 40 50 55 65 65 80 75 90 95 110 100 120 120 145 140 170 165 200 185 225 220 265 255 305 305 365 335 405 370 440 CLAD … 25 35 45 65 80 90 105 125 135 165 190 225 250 300 345 410 460 495 Example 3. What must be the ampacity of the conductor required for a 1 hp single-phase 115 V motor? FLC = 16 A Example 4. A room air conditioner is to be attached to an individual branch circuit. If the load is 16A, what is the minimum size of branch circuit required? [2/5] Pec motors CEERS REVIEW CENTER 2 EE REVIEW APRIL 2021 NOTES: PEC MOTORS Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.philippines@yahoo.com AMPACITY CORRECTION FACTORS Ambient Temp. C 21-25 26-30 31-35 36-40 41-45 46-50 51-55 56-60 61-70 71-80 For ambient temperature other than 30C lasting for three hours or more, multiply the ampacities shown above by the appropriate factor shown below 1.08 1.05 1.04 1.08 1.05 1.04 1.00 1.00 1.00 1.00 1.00 1.00 0.91 0.94 0.96 0.91 0.94 0.96 0.82 0.88 0.91 0.82 0.88 0.91 0.71 0.82 0.87 0.71 0.82 0.87 0.58 0.75 0.82 0.58 0.75 0.82 0.41 0.67 0.76 0.41 0.67 0.76 … 0.58 0.71 … 0.58 0.71 … 0.33 0.58 … 0.33 0.58 … … 0.41 … … 0.41 The table shown are correct if you don’t install over three current carrying conductors in a raceway or o cable or exceed 30 F in ambient temperature When there are more than three current carrying conductors in a raceway or cable the ampacity of each conductor must be reduced A’ = CF AF A’ = = = ampacity of any other condition Correction Factor (CF = 1 at 30oC) adjustment factor (AF=1 if not more than 3 conductors) A (CF)(AF) Example 5. 2 A cable contains four current carrying 30 mm THW conductors in an ambient temperature o o of 24 C. The ampacity of the conductor of an ambient temperature of 30 C and not more than three conductors on the raceway is 110 amp. What is now the ampacity of the conductor? Example 6. What size TW insulation copper conductor is required for a 1 hp single-phase 115 V motor? FLC=16 A Step 4. Branch Circuit Overcurrent Device The motor branch circuit short-circuit and ground –fault protective device shall be capable of carrying the starting current of a motor. A protective device having a rating or setting not exceeding the maximum value calculated according to the values given in table shall be used. Maximum Rating or Setting of Motor Branch-Circuit Short-Circuit and Ground-Fault Protective Devices Table 3.10.1.15 (b)(2)a, ADJUSTMENT FACTORS Adjustment factors for more than three current – carrying conductors in a Raceway or Cable Number of Current – Carrying Conductors 4-6 7-9 10-20 21-30 31-40 41 and above Percent of values of Tables as Adjusted for Ambient Temperature if Necessary 80% 70% 50% 45% 40% 35% o When a conductor is installed in an ambient above or below 30 C a correction factor must be applied. To determine the ampacity of a conductor, multiply the ampacity as given in the table by the appropriate adjustment factor, the product multiplied to the correction factor. Let A = ampacity when not more than three conductors in a Percent of Full-load Current Type of Motor Non-time Delay Fuse Single-phase motors 300% DualElement (TimeDelay) Fuse 175% Instantaneous Trip Breaker Inverse Time Breaker AC Polyphase motors other than wound-rotor squirrel cage Other than Design E Design E Synchronous Motors Wound rotor 800% 250% 300% 300% 300% 150% 175% 175% 175% 150% 800% 1100% 800% 800% 250% 250% 250% 150% Direct current 150% 150% 250% 150% raceway, based on ambient temperature of 30oC Pec motors [3/5] CEERS REVIEW CENTER 2 EE REVIEW APRIL 2021 NOTES: PEC MOTORS Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.philippines@yahoo.com Step 6. Feeder Overcurrent Protection A feeder supplying a fixed motor load (s) and consisting of proper conductor sizes shall be provided with a protective device having a rating or setting of not less than the largest rating or setting of the branch circuit short circuit and ground –fault protective device (fuse or breaker) for any motor of the group, plus the sum of the full-load currents of the other motors of the group. Example 7: A motor with a FLC of 10 amps would require what size of inverse time breaker? Example 8: What size dual element fuse is required for a 1 ½-hp single-phase, 230-V motor? FLC = 10 A Example 13: Two single-phase motors (FLC = 10 A) are connected across a 230-V single-phase feeder. Each motor is protected by a 25-A CB. What size inverse time CB is required for the feeder overcurrent device? Example 9: What is the maximum size inverse time circuit breaker for a 2-hp single-phase, 115-V motor? FLC = 24 A. Step 5. Feeder Conductor Size Multiply the largest rated motor in FLC by 125% and add the FLC of all other motors connected to the same feeder for the total amps. From the calculated ampacity determine the proper conductor size from the table. Example 10: What is the feeder conductor ampacity required for two 2-hp single-phase 115-V motors? FLC = 24 A Example 11: Two 25-hp three-phase, 208 V motors are fed by the same feeder, the feeder conductor would be required to carry a minimum of how many amps? FLC = 74.8 A Example 14: Two single-phase motors (FLC = 20 A) are connected across a 120-V single-phase feeder. Each motor is protected by a 35-A fuse. What size dual element fuse is required for the feeder overcurrent device Example 15: Three 3-phase motors are connected to a 480 V, 3phase feeder. Motor A (FLC = 7.6 A), 25-A fuse protective device; Motor B (FLC = 11 A), 35-A fuse protective device; and Motor C (FLC = 14 A), 45-A fuse protective device. Determine the size of a non-time delay fuse required for the feeder overcurrent protection? Example 12: What is the minimum size copper feeder conductor permitted using TW insulation for a 5- hp (FLC = 28 A), single phase, 230-V and a 2hp (FLC = 12 A), single phase, 230-V motors? [4/5] Pec motors CEERS REVIEW CENTER EE REVIEW APRIL 2021 2 NOTES: PEC MOTORS Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.philippines@yahoo.com ❑ Motor Compressor (Hermetic motors) Overcurrent protection Minimum setting – not exceeding 175% Maximum setting – not exceeding 225% ➢ Overload – not more than 125% for fuse and CB, 140% for overload relay ➢ Disconnecting means – 115% Standard ampere ratings of Protection 15 20 25 30 35 40 45 50 60 70 80 90 100 110 125 150 175 200 225 250 300 350 400 450 500 600 700 800 1000 1200 1600 2000 2500 3000 4000 5000-6000 For Fuses only 1A, 3A, 6A, 10A and 601 A Example 16: A hermetic motor compressor has a rated current of 16A. What is the minimum ampere rating of the motor branch disconnecting means? Example 17: What is the minimum ampere rating of the disconnecting means of a hermetic motor having 30A rated current? Example 18: What size overload relay is required to protect a 3-phase, 230-V 42 A hermetic motor? Pec motors [5/5] CEERS REVIEW CENTER EE REVIEW APRIL 2022 PEC TERMS Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.reviewcenter@gmail.com DEFINITION D. being reached without use of a ladder 1. Surrounded by a case, housing, fence, or walls that prevent from accidentally contacting energized part is A. enclosed * C. guarded B. isolated D. concealed 8. _____ duty is a type of service where both the load and the time intervals may have wide variations. A. Continuous C. Intermitted B. Periodic D. Varying * 2. _____ means that equipment is not readily accessible to persons unless special means for access are used. A. Isolated * C. Elevated B. Guarded D. Concealed 9. 3. A piece of electrical equipment that is designed to operated at alternate intervals of (1) load and no load; or (2) load and rest; or (3) load, no load, and rest is called _____ duty. A. short time C. periodic B. intermittent * D. varying Continuous load is _____. A. a load where the maximum current is expected to continue for three hours or more * B. a load where the maximum current is expected to continue for one hour or more C. intermittent operation in which the load conditions are regularly recurrent D. operation at a substantially constant load for an indefinitely long time 4. 5. An electrical outlet constructed so that moisture will not enter the enclosure is classified as being _____ A. waterproof C. watertight * B. rainproof D. weatherproof The _____ is the conductor can carry conditions of use temperature rating. A. load B. demand current in amperes a continuously under the without exceeding its C. connected load D. ampacity * 6. _____ means so constructed or protected that exposure to the weather will not interfere with successful operation. A. Weatherproof * C. Weather-resistant B. Weather-tight D. Weather-sealed 7. An accessible conductor is A. not permanently enclosed by a structure * B. admitting close approach C. not guarded by locked doors, elevation or other methods 10. An isolating which is one that is _____. A. intended for cutting off an electrical circuit from its source of power * B. required to have a padlock C. primarily used with an insulation transformer D. used only for heavy motor overloads 11. A device actuated by the operation of some other device with which it is directly associated, to govern succeeding operations of the same or allied devices. A. relay C. interlock * B. controller D. governor BRANCH CIRCUITS 12. It is a device intended to provide protection from the effects of arc faults by recognizing the characteristics unique to arcing and by functioning to de-energize the circuit when an arc fault is detected. A. arc fault circuit breaker B. arc fault circuit interrupter * C. arc fault arrester D. arc fault de-energizer 13. For ranges of 8 ¾ kW or more rating, the minimum branch circuit rating shall be _____ amperes. A. 30 C. 50 B. 40 * D. 60 20. The unit lighting load for dwelling unit, expressed in volt-amperes per square meter shall be A. 16 C. 24 * B. 28 D. 8 14. The rating of any one cord-and-plug-connected utilization equipment not fastened in place shall not exceed _____ percent of the branch circuit ampere rating A. 125 C. 100 B. 110 D. 80 * 21. At least one receptacle outlet shall be installed directly above a show window for each _____ linear meters or major fraction thereof of show window area measured horizontally at its maximum width. A. 1 C. 3 * B. 2 D. 4 15. The total rating of utilization equipment fastened in place, other than luminaries shall not exceed ____ percent of the branch circuit ampere rating where lighting units, cord-andplug-connected utilization equipment not fastened in place or both are also supplied. A. 50 * C. 80 B. 75 D. 100 16. Branch circuit larger than _____ amperes shall supply only non lighting outlet loads A. 30 C. 50 * B. 40 D. 60 17. Appliance receptacle outlets installed in a dwelling unit for a specific appliances such as laundry equipment, shall be installed within _____ mm of the intended location of the appliances. A. 1000 C. 1800 * B. 1500 D. 2000 18. In kitchens and dining areas of dwelling units, a receptacle outlet shall be installed at each corner space wider than _____ mm. A. 250 C. 300 * B. 80 D. 350 19. The demand factor for air-conditioning load is _____% A. 50 C. 90 B. 80 D. 100 * 22. The rating of any one cord and a plug connected utilization equipment shall not exceed _____ percent of the branch circuit ampere rating. A. 50 C. 100 B. 80 * D. 125 23. For receptacle outlets, each single or each multiple receptacle on one strap shall be considered at not less than _____ voltamperes. A. 150 C. 200 B. 180 * D. 250 24. For hallways of _____ mm or more in length at least one receptacle outlet shall be required. A. 3000 * C. 3300 B. 3200 D. 3500 25. The unit load per square meter in volt-amperes of the following occupancies is 24, except A. dwelling units C. hospitals * B. schools D. stores 26. For over 600 volts nominal, open individual conductors shall not be smaller than _____ mm2 copper or _____ mm2 aluminum. A. 8, 14 C. 14, 30 B. 14, 22 * D. 22, 30 Page 1 of 3 Engr. Genry Oñate: 09323728227/09178164901 “Learn to Solve. Solve to Learn More!” Engr. Glenn Valenzona: 09328723377/09989712800 CEERS REVIEW CENTER EE REVIEW APRIL 2022 PEC TERMS Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 27. Conductors on poles not less than _____ racks or brackets. A. 300 * B. 250 email add: ceers.reviewcenter@gmail.com shall have a separation of mm where not placed on C. 200 D. 150 28. Open conductors shall be separated from open conductors of other circuits or systems by not less than _____ mm. A. 200 C. 100 * B. 150 D. 80 29. Conductors supported on poles shall provide a horizontal climbing space not less than _____ mm for power conductors, below communication conductors. A. 730 C. 780 B. 760 * D. 800 30. Conductors shall have a vertical clearance of not less than _____ mm from the roof surface. A. 1800 C. 2500 * B. 2000 D. 3000 31. The vertical clearance from the roof shall be maintained for a distance of not less than _____ mm on all direction from the edge of the roof. A. 500 C. 900 B. 800 D. 1000 * 32. The recommended maximum total voltage drop on both the feeders and branch circuits is _____ percent. A. 3.5 C. 5 * B. 2.5 D. 6 33. The service disconnecting means for each set of service-entrance conductors shall consist of not more than _____ switches. A. 6 * C. 10 B. 8 D. 12 A. B. 6 4 C. 8 D. 10 SERVICES 35. Services using copper conductors shall have sufficient capacity and shall not be smaller than A. 5.5 mm2 C. 14 mm 2 B. 8.0 mm2 D. 22 mm2 36. Conductors must have a clearance from windows, porches, fire escapes of not less than A. 800 mm C. 1100 mm B. 900 mm D. 1000 mm 37. For services not over 600 volts nominal service conductors shall have a vertical clearance of _____ mm from the roof surface. A. 2000 C. 2500 * B. 3000 D. 2200 38. Where the voltage between conductors does not exceed 300 volts, and the roof has a slope of not less than 00 mm in 300 mm, a reduction of clearance to ___mm shall be permitted A. 2000 C. 1500 B. 2200 D. 1000 * * 39. Service drop conductors where not in excess of 600 volts nominal, shall have a vertical clearance A. 2000 C. 3100 * B. 2500 D. 3300 40. Service drop conductors where not in excess of 600 volts nominal, shall have a vertical clearance of ____mm over public streets, parking areas subject to traffic, and driveway on other than residential areas. A. 4600 C. 5000 B. 5500 * D. 5300 34. How many times the diameter of the largest raceways shall the length of the box be in straight pulls? 41. A column pole or narrow base structure of wood, steel or other material supporting overhead conductors by means of arms or bracket. A. over head C. cleat B. mast * D. extension pole 42. The maximum setting the ground-fault protection in a service disconnecting means shall be ____ amperes. A. 800 C. 1200 * B. 1000 D. 2000 OVERCURRENT – PROTECTION 43. Overcurrent protection for conductors and equipment is provided to _____ the circuit if the current reaches a value that will cause an excessive or dangerous temperature in conductors or conductor insulation. A. open * C. interrupt B. close D. blow 44. The ampacity of a device to open under short circuit or ground fault is based on its ____ rating. A. operating C. ampacity B. interrupting * D. temperature 45. The largest standard cartridge fuse rating is _____ amps. A. 6000 * C. 1000 B. 1200 D. 600 46. What is the MAXIMUM number of overcurrent devices for a lightning and appliance that can be installed in a single cabinet? A. 36 C. 24 B. 42 D. 48 47. Defined as properly localizing a fault condition to restrict outages to the equipment effected, accomplished by choice of selective fault protective devices. A. Monitoring C. Sensing B. Coordination *D. Fault device 48. The maximum percent of overcurrent protection allowed is _____ of the input current to an autotransformer when less than 9 amps. A. 167% * C. 300% B. 150% D. 200% 49. Where the overcurrent device is rated over _____ amperes, the ampacity of the conductors it protects shall be equal to or greater than rating of the overcurrent device. A. 150 C. 500 B. 300 D. 800 * 50. Ground-fault circuit-interrupters shall be installed in the branch circuit supplying under water pool lighting fixtures operating at more than _____ volts. A. 12 C. 25 B. 15 D. 30 GROUNDING AND BONDING 51. Grounding Electrodes of pipe or conduit shall not be smaller than _____ mm trade size and where iron or steel shall have the outer surface galvanized. A. 10 C. 8 B. 20 D. 16 52. Grounding electrodes of rods end steel or iron shall be at least ____ mm in diameter. A. 16 * C. 10 B. 12 D. 20 53. Rod and pipe grounding electrodes shall be installed such that at least ____ mm in length and in contact with the soil. A. 1800 C. 2200 B. 2000 D. 2400 * 54. Each grounding plate electrode shall expose not less than ____ square meter of surface to exterior soil. A. ¼ C. 1/3 Page 2 of 3 Engr. Genry Oñate: 09323728227/09178164901 “Learn to Solve. Solve to Learn More!” Engr. Glenn Valenzona: 09328723377/09989712800 CEERS REVIEW CENTER EE REVIEW APRIL 2022 PEC TERMS Doña Esperanza Village, Tisa, Cebu City Tel. No. 261-2244 email add: ceers.reviewcenter@gmail.com B. 1/5 D. ½ 55. _____ grounding electrode is not permitted A. iron C. steel B. aluminum D. stainless steel 56. Connection between a conductive or metal object and an element of a protection system to accomplish continuity between the two. A. interlink C. connector B. messenger D. bonding inductive lightning electrical * 57. In a grounded system, what do you call the conductor that connects the circuit grounded conductor at the service and/or the equipment grounding conductor to the grounding electrode A. main grounding conductor B. common main grounding conductor C. equipment grounding conductor D. grounding electrode conductor * 58. What conductor used to connect the grounded circuit of a wiring system to a grounding electrode A. grounded conductor B. main bonding jumper C. bonding jumper D. grounding conductor 59. _____ is a system or circuit conductor that is intentionally grounded. A. Grounding conductor B. Neutral conductor C. Grounded conductor * D. Grounding electrode conduct 60. The grounded conductor of a branch circuit shall be identified by a continuous _____ color. A. gray C. white B. yellow D. white or gray * 61. The equipment grounding conductors of a branch circuit shall be identified by a continuous ______ color. A. Yellow B. Green * C. Gray D. White 62. According to the code the grounding conductor shall be identified by A. one continuous green color B. being bare C. a continuous green color with yellow stripes D. any of these 63. A/an _____ shall be used to connect the grounding terminal of a grounding type receptacle to a grounded box. A. feeder conductor B. equipment bonding jumper * C. branch circuit D. bonding jumper main 64. Which of the following shall be provided where necessary to ensure electrical continuity? A. Grounding C. Jumpers B. Bonding D. connectors 65. According to the Code, metal enclosures for grounding electrode conductors shall be _____. A. not permitted B. rigid conduit C. electrically continuous D. permitted PROTECTION AGAINST LIGHTNING 66. A device capable to drawing lightning discharge to it in preference to vulnerable parts of the protected area. A. rods C. air terminal B. points D. ground terminal 67. A conductor encircling a building and interconnecting all ground terminals A. counterpoise C. ground terminals B. bonding D. ground fittings 68. The average distance between down conductors used for lightning protection shall not exceed _____ meters. A. 15 C. 25 B. 20 D. 30 75. Type MI (mineral insulated) cable shall be securely supported at intervals not exceeding ___ mm A. 1500 C. 2000 B. 1800 * D. 2200 69. Protection of structures containing flammable liquid and gasses may be achieved to a considerable degree by the use of A. air terminals B. overhead ground wires C. masts D. any of these 76. Type NM (non metallic) or NMC cable supports shall be secured in place at intervals of ___ mm. A. 1500 C. 1000 B. 1300 * D. 800 MISCELLANEOUS 77. Intermediate metal conduit shall be supported at least every ___ mm A. 2000 C. 2700 B. 2400 D. 3000 70. Which of the following has the highest electrical breakdown strength and longest life compared to other insulating materials? A. mica C. rubber B. impregnated paper D. thermoplastic 78. Intermediate metal conduit or RMC or FMC smaller than ___ mm electrical trade size shall not be used A. 15 C. 25 B. 20 D. 32 71. To cut a rigid conduit, use a _____ A. 3-wheel pipe cutter B. hack saw and ream the ends * C. chisel and ream the ends D. band saw 79. Rigid metal conduit shall be firmly fastened within ___ mm of each outlet box, junction box, cabinet or fitting A. 500 C. 900 * B. 700 D. 1000 72. When do you use a tap tool? A. connecting wires B. cutting internal threads * C. reaming raceways D. cutting external threads 80. Flexible metal conduit shall be secured by an approved means at intervals not exceeding ___ mm. A. 1200 C. 1400 B. 1300 D. 1500 73. The ampacity of conductors in armored cable installed in thermal installation shall be that of ___ 0C conductors. A. 60 C. 85 B. 75 D. 90 81. Each length of HDPE shall be clearly and durably marked at least every _____ mm. A. 2000 C. 2800 B. 2400 D. 3000 74. Type MC (metal clad) cable shall be supported and secured at interval not exceeding ___ mm. A. 1800 * C. 2200 B. 2000 D. 2500 82. Wireway shall be supported at intervals not to exceed ___mm A. 1200 C. 1800 B. 1500 * D. 2000 Page 3 of 3 Engr. Genry Oñate: 09323728227/09178164901 “Learn to Solve. Solve to Learn More!” Engr. Glenn Valenzona: 09328723377/09989712800