BlueRidge Technologies www.BRTint.com : 800-241-9173 Blue Ridge Technologies® Relay Panel © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 Install Guide : Page 1 Hardware Installation and Setup Instructions Relay Panel BlueRidge Technologies www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 Install Guide : Page 2 Table of Contents Overview Document Component Assembly Dimensions 3 3 3 4 Preparation Door Removal Relay Cover Removal Interior Removal Enclosure 5 6 6 7 Mounting 7 Terminations Line Voltage Low Voltage 9 9 Controller Setup 12 Optional Equipment 13 Visit www.BRTint.com/tandc.html for Terms and Conditions of Sale Attention This section serves as a notice of the immediate or potential dangers involved when working with the equipment described throughout this manual. Any person involved in installation, maintenance, or service of the equipment should first carefully examine the equipment and read the instructions contained in this manual to ensure that personal and/or equipment injury is avoided. The following safety messages appear throughout this manual to alert of immediate or potential danger to life as well as property. Note : Indicates an important note. Tip : Indicates a helpful tip or trick. Safety Reminder : Applicable safety instructions will be included with this symbol. DANGER : Indicates an immediately hazardous situation which ,if not avoided, will result in serious injury or death. WARNING : Indicates a potentially hazardous situation which ,if not avoided, may result in serious injury or death. CAUTION : Indicates a potentially hazardous situation which ,if not avoided, may result in minor or moderate injury. Disclaimer This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designated to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense. Instructions contained in this user’s guide should be performed only by qualified persons in accordance with local and national codes. Blue Ridge Technologies International, LLC and its affiliates assume no responsibility for any consequences related to the improper use of this manual. Relay Panel BlueRidge Technologies www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 Install Guide : Page 3 Overview : Document This document provides mounting and connection instructions for the following Blue Ridge Technologies Relay Panel (RP) products : RP16, 32, 48, 64 with Surface / Flush Mount Doors RP enclosures are Type 1 rated and must be mounted in a dry / indoor environment. Sections of this Install Guide apply to optional equipment and may not be applicable. Siemens’ P1 and Automated Logic Corporation’s BACnet ARCnet protocols are only available to authorized integrators. For RP integration with a Building Automation System (BAS) as well as software configuration refer to the Application Guide. Overview : Component The RP includes the following items : 1 - RP 1 - BT485 BAS Network Terminator (BT485 Terminator) 3 3 4 4 Overview : Assembly 1. LEXP Digital Input Expansion Card (LEXP not applicable on RP16) 2. Controller 1 3. Lighting Tough Relay (LTR) 4. “Key Hole” Mounting Hole (Top of Panel) 5. Transformer 6. Earth Ground Lug 7. Panel Door 8. Relay Covers 9. Panel Interior 10. Panel Enclosure 1 2 2 5 5 6 6 10 7 7 8 8 9 10 9 (Figure 1) All circuits must be tested for wiring errors and shorts prior to RP installation. Disconnect line voltage power before performing RP installation. Before handling any RP components, the technician should be grounded to prevent circuit board damage. Relay Panel BlueRidge Technologies www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 Install Guide : Page 4 Overview : Dimensions RP16 : Enclosure Dimensions Surface Mount Door Dimensions 5.75” (146mm) Side RP32 : Enclosure Dimensions Surface Mount Door Dimensions 5.75” (146mm) Front 26.50” (673mm) Surface Mount Door Dimensions 5.75” (146mm) 18.00” (457mm) Surface Mount Door Dimensions 5.75” (146mm) 19.58” (497mm) 35.30” (897mm) Side RP64 : Enclosure Dimensions Recessed Mount Door Dimensions 18.08” (459mm) 34.05” (865mm) 33.80” (859mm) Front 19.58” (497mm) Side RP48 : Enclosure Dimensions 18.00” (457mm) Recessed Mount Door Dimensions 18.08” (459mm) 25.25” (641mm) 25.00” (635mm) 18.00” (457mm) 19.58” (497mm) 17.70” (450mm) 16.20” (411mm) Front Recessed Mount Door Dimensions 18.08” (459mm) 16.45” (418mm) 18.00” (457mm) 18.08” (459mm) (Figure 2) Recessed Mount Door Dimensions 19.58” (497mm) 35.30” (897mm) 33.80” (859m 34.05” (865mm Relay Panel BlueRidge Technologies www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 Install Guide : Page 5 Overview : Dimensions Front Side RP64 : Enclosure Dimensions Surface Mount Door Dimensions 5.75” (146mm) 18.08” (459mm) Front Side (Figure 3) (31.75mm) 17.00” (431.80mm) Preparation : Door Removal Remove the Panel Door from the Panel Enclosure. (Figure 4) 1. Open Panel Door 2. Remove fasteners from the door’s hinge. 0.00”(0.00mm) 0.00”(0.00mm) 3. Separate Panel Door from Panel Enclosure. 1.25” 1.25” 1.00”(25.40mm) 0.00”(0.00mm) RP32 Mounting Hole Dimensions 17.00” (431.80mm) 1.00”(25.40mm) RP16 Mounting Hole Dimensions 0.00”(0.00mm) 19.58” (497mm) 44.10” (1120mm) 42.85” (1088mm) 42.60” (1082mm) 18.00” (457mm) Recessed Mount Door Dimensions (31.75mm) 14.70” (373.38mm) Ø 0.25”(6.35mm) 23.50” (596.90mm) Ø 0.25”(6.35mm) 0.00”(0.00mm) 1.25” 0.00”(0.00mm) 1.25” 17.00” (431.80mm) 1.00”(25.40mm) 0.00”(0.00mm) RP64 Mounting Hole Dimensions 17.00” (431.80mm) 1.00”(25.40mm) 0.00”(0.00mm) RP48 Mounting Hole Dimensions (Figure 4) Relay Panel BlueRidge Technologies www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 Install Guide : Page 6 Preparation : Relay Cover Removal Remove the Relay Covers from the Panel Enclosure. (Figure 5) 1. Unlock 1/4 turn fasteners located near top and bottom of Relay Cover. 2. Remove Relay Covers by rotating inside edge outward and pulling Relay Covers free. (Figure 5) Preparation : Interior Removal Remove the Panel Interior from the Panel Enclosure. It is beneficial to mark position of penetrations in the Panel Enclosure prior to removing the Panel Interior. (Figure 6) 1. Unfasten the nuts retaining the Panel Interior. 2. Pull the Panel Interior outward to free it from the Panel Enclosure. 3. Store the Panel Interior in a secure location free of dust and debris. 1 2 (Figure 6) 8 Voltage Separation 7 Voltage Separation Relay Panel BlueRidge Technologies www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 Install Guide : Page 7 Preparation : Enclosure Prior to mounting the Panel Enclosure make penetrations for all applicable bushings and/or conduit. Ensure sufficient clearance for Panel Interior. (Figure 7) 1. Ensure the Panel Enclosure is oriented correctly. Key holes should be located at the top of the panel. 2. Drill or punch the appropriate hole(s) in the Panel Enclosure for the application. Voltage Separation Line Low Line Front 1 Mounting The Panel Enclosure may now be mounted. 1. Ensure the Panel Enclosure is oriented correctly. Key holes should be located at the top of the panel. 2. Mark the location of all Panel Enclosure mounting holes to the mounting surface. (Figure 8) 3. Prepare the mounting surface with hardware appropriate to support the panel’s weight. See Panel Weight Chart 4. Hang Panel Enclosure. 5. Remove dust and debris from Panel Enclosure.2 6. Reinstall Panel Interior. DO NOT exceed 40 in-lbs when tightening Panel Interior retention nuts. 7. Install appropriate bushings, conduit, and wire. Panel Weight Chart Relay Panel Capacity Approximate Weight at Full Capacity RP16 32 lbs (14.5 kg) RP32 47.5 lbs (21.5 kg) RP48 63.5 lbs (28.8 kg) RP64 82.5 lbs (37.4 kg) 3 4 (Figure 7) 44.10” ( 42.85 42.60 Relay Panel BlueRidge Technologies www.BRTint.com : 800-241-9173 Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 Install Guide : Page 8 Front Side 0.00”(0.00mm) 0.00”(0.00mm) 1.25” (31.75mm) 1.25” (31.75mm) 17.00” (431.80mm) 1.00”(25.40mm) RP32 Mounting Hole Dimensions 17.00” (431.80mm) 1.00”(25.40mm) 0.00”(0.00mm) RP16 Mounting Hole Dimensions 0.00”(0.00mm) Mounting 14.70” (373.38mm) Ø 0.25”(6.35mm) 23.50” (596.90mm) Ø 0.25”(6.35mm) 0.00”(0.00mm) 17.00” (431.80mm) 1.00”(25.40mm) 0.00”(0.00mm) RP64 Mounting Hole Dimensions 17.00” (431.80mm) 1.00”(25.40mm) 0.00”(0.00mm) RP48 Mounting Hole Dimensions 0.00”(0.00mm) 1.25” (31.75mm) 1.25” (31.75mm) 10.80” (274.32mm) 19.60” (497.84mm) 32.30” (820.42mm) Ø 0.25”(6.35mm) 41.10” (1043.94mm) Ø 0.25”(6.35mm) (Figure 8) Unsheilded Controller CTS-DDN 24VDC (Red) 24 Digital Input: Two Button Low Voltage Switch (Externally Powered) TerminationsG: Line Voltage Complete line 2voltage terminations. (Figure 9 and 10) Switch 2 1. Confirm power is disconnected from the panel. 2. Route leads as appropriate. Controller 24V Switch Switch 3. Cut to length and strip as GND appropriate. Digital Input: TwoLTR Button Low Voltage Switch (Externally Powered) 24VDC Supply 4. Complete Transformer and terminations. 5. Cap unused primary lead from Transformer. 6. Torque each LTR screw terminal to 36 in-lbs. witch 1 ommon witch 2 ND 24V cupancy Sensor G GND 24V COM N/O Belden 8760 N/C Controller A+ SignalTerminations (-) LEXP B- 8 456 78 1 2 3 4 5 6 7 8 456 DI 11 DI 12 DI 13 DI 14 DI 15 DI 16 GND H2 H1 + N(-) Contactor - 24VDC Power Supply Line In *DI Jumper Posit Relays 33-60 RELAYS 33-60 LEXP Port INPUT POWER 24VAC 24VDC Power Supply Terminations 24VAC(+) Power In G 17 18 19 20 21 22 23 24 9-16 R 24VAC(-) Power In N N G 1 2 GND DI 17 DI 18 DI 19 DI 20 DI 21 DI 22 DI 23 DI 24 LTR Relays 1-32 24VDC Out J26 LEXP Neutral Line In L(+) AUX VAC + Neutral N(-) - 24VAC(+) Auxiliary Out 24VAC(-) Auxiliary Out 24VDC Out 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G 24VDC Power Supply AI (Analog Input) / DI (Digital Input) / GND (Ground) *DI Jumper Position N(Dry Contact) / R(Externally Powered) ON (Figure 11) Baud Rate / Protocol Dip Switch: BACnet MS/TP Network Address 76800 ON 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 SW1 Network Address 1’s Network Address 10’s 2 3 4 5 6 7 8 2 76800 3 4 5 6 7 9600 Programming ON 8 901 901 23 38400 1 SW1 23 19200 1 SW1 J18 J19 B D DI 15 DI 16 GND Override Controls RELAYS 1-32 L(+) TO J26 OF Controller 1 24VAC(-) Auxiliary Out 9600 Wire Strip Length Indicator SW4 ON 24VAC(+) Auxiliary Out MS/TP Protocol Dip Switch: BACnet W1 SW1 X VAC ng 8 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 8 7 A C ADDRESS 7 1-8 R INPUTS 1-16 6 6 24VDC Out DI Jumper 9-16* GND DI 40 DI 39 DI 38 DI 37 DI 36 DI 35 DI 34 DI 33 5 5 N DI Jumper 17-24* DI Jumper 1-8* POWER N R 4 ON 4 Address Jumper INPUTS 17-32 J4 J5 GND DI 32 DI 31 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 3 ON 3 Controller Port INPUTS 1-16 N R A C ADDRESS J18 J19 B D TO J26 OF Controller Address Jumper 24VAC(+) Power In 24VAC(-) Power In 2 Contactor Coil L(+) Terminations Line In + 5V 5VDC A6 A5 AI 6 Neutral A4 A3 AI 5 A2 A1 AI 4 G AI 3 AI 2 AI 1 17-24 GND R 38400 DI 52 DI 53 DI 54 DI 55 DI 56 GND POWER INPUTS 17-32 J4 J5 GND DI 40 DI R39N DI 38 J13 DI 37 J9 DI 36 DI 35 DI 34 DI 33 Controller Port 2 Manual Override Lever SW1 SW3 1 LTR 901 901 23 J9 J13 DI 41 DI 42 GND DI 43 DI 40 DI 44 DI 39 DI 45 DI 38 DI 46 DI 37 DI 47 DI 36 DI 1-16 48 POWER DI 35 INPUTS GND DI 34 DI 33 DI 49 DI 50 DI 51 DI 52 J4 DI 53 J5 DI 54 N R DI 55 DI 56 GND J18 J19 B D GND DI 32 DI 31 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 N UT WER AC LEXP Termination Rotary Switch 1’s ON DDN Network Terminator Jumper Line J2In 33-40* 19200 LTR Line In 23 INPUTS 17-32 R N R N J9 J13 BT485 Terminator Power LED DI Jumper LEXP Terminations 25-32* *DI Jumper Position N(Dry Contact) / R(Externally DI Jumper Powered) 9600 Mounting Hole N(-)Load Neutral PWR 24VDC Power LED RUN DDN Network(-) Run LED DDN/CAN 24VDC Power Supply Terminations DDN Network(+) 24VDC Power Supply GND GND DI 32 DI 31 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 2 LEXP Port Shield Line In aud Rate / Relays Protocol Dip Switch: BACnet MS/TP 33-60 ogramming (Figure 10) Controller Line In BT485 Terminator Plug (if applicable) Neutral *DI Jumper Position N(Dry Contact) / R(Externally Powered) AYS 33-60 Signal (- Belden 8760 A+ BT485 S B-Power AUTO Terminations OVER 24VDC Supply Contactor DI Jumper 25-32* B- 49-56* VAC(+) Auxiliary Out VAC(-) Auxiliary Out Relays 1-32 ) Earth Ground Neutral Baud Rate / Protocol Network Address Rotary Switch 10’s Dip Switch Relay Output Network Address BAS(+) In BAS(-) In Shield DI Jumper 41-48* *DI Jumper Position N(Dry Contact) / R(Externally Powered) DI Jumper 24VAC(+) Auxiliary Out lays 33-60 49-56* 24VAC(-) Auxiliary Out Override Controls Power LED DI Jumper EXP Port G 25-32* Power LED Run DI Jumper VAC(+) Power In LED 33-40* VAC(-) Power In LAYS 1-32 Neutral Black Signal (+ Load Contactor Controller Terminations 23 24VAC(+) Power In 24VAC(-) Power In Earth Ground A+ *Do not terminate shield on BAS output. 901 SW4 OVER 347 Transformer Terminations Relay Output Neutral White Line In Contactor Coil Terminations DI 41 DI 42 DI 43 DI 44 DI 45 DI 46 DI 47 DI 48 GND J18 J19 B D A C ADDRESS Address Jumper A C ADDRESS Address Jumper ower LED un LED work Address Rotary Switch 10’s Relays 33-60 Network Address Rotary Switch 1’s 3-60 LEXP Port lays 1-32 3 TO J26 OF Controller Controller Port verride Controls Relays 1-32 N/C Line In Contactor Coil Terminations Relay Output Signal (-) Belden 8760 BLoad S Indicator Shield* Manual Override Lever Wire Strip Length LTR Terminations DI 41 DI 42 DI 43 DI 44 DI 45 DI 46 DI 47 DI 48 GND DI 49 DI 50 DI 51 DI 52 DI 53 DI 54 DI 55 DI 56 GND DI 49 DI 50 TO J26 DIOF 51Controller DI 52 DI 53 Controller DI 54 DIPort 55 DI 56 GND 1-32 Light Sensor GND 24V COM N/O Signal (+) BT485 Terminator Specifications DISJumperDI Jumper Shield 33-40* Power In: 24VAC +/-10%, 30VA, 50-60 Hz 41-48* Auxiliary Out: 24VAC Full Wave RectifiedDI Jumper Controller ontroller Earth Ground Common Mounting Hole Mounting Hole 277VAC Brown 23 Controller Run LED Neutral Black Phillips / Slot / Square Head Screw Terminals Signal (-) Belden 8760 Ground 347VACSignal Brown Manual Override Lever Wire Strip Length Indicator BAS Network (End-of-line Device) BAS Network (Input and Output) 347VAC Brown 120VAC Black 901 S Power LED Signal Phillips / Slot / Square Head Screw Terminals Terminations : Low Voltage Occupancy Address Rotary Switch 10’s S on the Controller and LEXP. These Shield are terminated All low voltage leads Sensor Network Address screw terminals accept a 0.4 x 2.5mm slot head screw driver. For reference, Rotary Switch 1’s Controller BT485 Terminator some terminal blocks may be removed to reveal terminal labels. (Figure 11) BAS Network (End-of-line Device) 1. Confirm power is disconnected from the RP. DI Jumper LEXPleads. Terminations 2. Route 41-48* BT485 3. Cut to length and strip as appropriate. DI Jumper A+ otary Switch 10’s 49-56* screw. 4.Controls Insert stripped leadSignal into screw terminal A+ and tighten (+) Override etwork Address Power LED BRepeat for each lead. otary Switch 1’s 5. SW4 VER Power Neutral White PhillipsEarth / SlotGround / Square Head Screw Terminals Common LTR Terminations 24V GND Terminations Occupancy Transformer Sensor 24VDC Supply LTR Specifications Type: UL Listed BAS Network (End-of-line Device) y Contact) COM N/O N/C SPST latching with manual override lever Electrically operated mechanically held, pulse BT485driven A+ Short Circuit Current Rating (SCCR) 30,000A @ 277 VAC Signal (+) A+ Ratings: Tungsten 20A @ 120VAC / Ballast 20A @ 277VAC / Ballast B20A @ 347VAC / Resistive 20A @ 277VAC / Resistive 20A @ 347VAC Signal (-) BBelden 8760 S BAS Network Load Terminal: Universal screw terminal, box type clamp (End-of-line Device) Terminal Capacity (per or (1) 8AWG (Solid or S Shieldside): (2) 14-10AWG roller BT485 Stranded copper wire) Earth Ground Power 277VAC Brown Controller Switch Neutral Black (Figure 9) LTR Terminations 120VAC Black Power G 347VAC Brown 347 Transformer Terminations Common 5V Controller A1 GND 24V 24VDC Supply Signal (+) Neutral White Analog Input: 5VDC Light Sensor Transformer Terminations Earth Ground N/O 1 Transformer Specifications G Common Type: 30VA Inherently Limited Primary: Dual Tap 120 Hz 2 2 or 277VAC +/-10%, 30VA, 50-60 Switch 24VAC +/-10% Inherently Limited COM Secondary: N/O N/C Wire Requirement: 18AWG Minimum (Solid or Stranded) Controller Switch Light Sensor 277VAC Brown Controller Digital Input: 4-Wire 24VDC Occupancy Sensor 120VAC(Dry BlackContact) Switch 1 1 Common Common 8 Contact) G 8 Contact) H2 Controller 1 Relay Panel H1 Switch Power Switch 1 Signal 1 1 Signal A1 Common Analog Input: 5VDC Light Sensor CL3P / 22AWG / 4 Conductor CTS Leads G G Common G Common Common Switch 2 Unsheilded Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 800-241-9173 Blue Light Sensor 2 2 Switch 2 Controller Power Power : Page 9 5V Install Guide GND 24V Switch 1 Switch 24VDC Supply Controller Controller Signal Switch Terminations Signal A1 Transformer Terminations 347 Transformer Common T e c h nDigital o l Input: o gTwo i eButton s Low Voltage Switch (Externally Powered) www.BRTint.com : 5V Ground (Black) H2 2 Switch 1 H1 h2 G Digital Input: Tw Power 78 B l u e R i d g eG Signal (-) (White) 78 mon L DI 9 DI 10 DI 11 DI 12 DI 13 DI 14 DI 15 DI 16 GND 1 Signal (+) (Green) Digital Input: Two Button Low Voltage Switch (Dry Contact) CTS-DDN GND DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 h1 Analog Input: 5VDC Light Sensor H 1 2 3 Ground (Black) 456 tact) Signal (-) (White) 456 Signal (+) (Green) 1 2 SW1 3 4 5 6 7 8 1 2 SW1 3 4 5 6 7 8 Controller 24VDC Supply 24V GND 24 24VDC (Red) H Signal (+) (Green) L Signal (-) (White) BlueRiG dge Controller CTS-DDN Relay Panel H Ground (Black) Technologies 24VDC (Red) 24 Signal (+) (Green) CTS-DDN L Signal (-) (White) CL3P / 22AWG / 4 Conductor CTS Leads Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 www.BRTint.com : 800-241-9173 Unsheilded G Ground (Black) Install Guide : Page 10 CL3P / 22AWG / 4 Conductor Unsheilded CTS Leads Terminations : Low Voltage Digital Input Specifications Controller: 24 two-wire inputs LEXP: 32 two-wire inputs Software Configuration: Maintained, state change, momentary on/off, momentary on, or momentary off Jumper Configuration: 8 input segments, dry contact (N) or 24VDC externally powered (R) Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / Dry Contact 500’(152m) or externally powered 1,000’(304m) Digital Input: Two Button Low Voltage Switch (Dry Contact) Digital Input: Two Button Low Voltage Switch (Externally Powered) Analog Input: 5V 1 Switch 1 1 Switch 1 5V G Common G Common A1 2 Switch 2 2 Switch 2 G Controller Controller Switch GND 24V 24VDC Supply Controller Switch S-DDN w/24VDC External Power Supply Digital Input: 4-Wire 24VDC Occupancy Sensor (Dry Contact) 4VDC Supply 24V GND N/O 1 G Common 24VDC (Red) Controller Signal (+) (Green) Signal (-) (White) Ground (Black) 22AWG / 4 Conductor Unsheilded CTS Leads GND 24V COM N/O 24V GND 24VDC Supply N/C Occupancy Sensor (Figure 12) BAS Network (End-of-line Device) BAS Network (Input and Output) Analog Input Specifications Signal (+) Analog Input: 6 three-wire 0-5VDC inputs A+ Wire Requirement / Maximum Length: 18AWG (Solid or Stranded) / 250’(76m) Signal (+) A+ Belden 8760 Signal (-) B- Shield S Signal (-) Belden 8760 w Voltage Switch (Externally Powered) BT485 B- S Light Sensor Shield* Analog Input: 5VDC Controller *Do not terminate shield on BAS output. Switch 1 5V Power Power Common Controller Terminations A1 Signal LEXP Terminations Signal Controller 6 7 8 SW4 OVER Earth Ground INPUTS 1-16 N R Power LED DI Jumper 25-32* DI Jumper 33-40* GND DI 40 DI 39 DI 38 DI 37 DI 36 DI 35 DI 34 DI 33 1 2 3 1 2 3 4 5 6 7 8 POWER J4 1-8 J5 RELAYS 33-60 N G 17 18 19 20 21 22 23 24 9-16 Neutral Black DI Jumper 41-48* DI Jumper 49-56* Phillips / Slot / Square Head Screw Terminals *DI Jumper Position N(Dry Contact) / R(Externally Powered) Relays 33-60 Mounting Hole J26 LEXP 17-24 R J9 Relays 1-32 LTR Terminations 347VAC Brown GND DI 32 DI 31 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 5V A6 A5 A4 A3 A2 A1 G J18 J19 B D J2 A C ADDRESS DI Jumper 17-24* RUN RELAYS 1-32 DDN Network Terminator Jumper 5VDC AI 6 AI 5 AI 4 AI 3 AI 2 AI 1 GND Power LEDNeutral White Run LED Earth Ground PWR DDN/CAN Address Jumper 24VDC DDN Network(-) DDN Network(+) GND J13 120VAC Black TO J26 OF Controller 277VAC Brown Override Controls 347 Transformer Terminations R N Transformer Terminations INPUTS 17-32 SW1 SW3 H2 5 AUTO 78 78 4 456 3 Controller Port BT485 Terminator Plug (if applicable) 901 901 2 456 1 H1 ON BT485 S B- A+ Light Sensor Rotary Switch 1’s 23 BAS(+) In BAS(-) InSwitch Shield INPUT POWER LEXP Port 24VAC(+) Power In BT485 Terminator Common Common DI 41 DI 42 DI 43 DI 44 DI 45 DI 46 DI 47 DI 48 GND Baud Rate / Protocol Network Address Rotary Switch 10’s Dip Switch Network Address DI 49 DI 50 DI 51 DI 52 DI 53 DI 54 DI 55 DI 56 GND G Switch 2 Controller 23 ND 24V VDC Supply Power CTS-DDN Ground Line In (Figure 13) Unsheilded Relay Panel BlueRidge T e c h n o lDigital o gInput: i e Two s Button Low Voltage Switch (Dry Contact) Digital Input: Two Button Low Voltage Switch (Externally Powered) www.BRTint.com : 800-241-9173 Blue Ridge Technologies® Switch 1 1 Switch 1 1 G Voltage G Terminations : Low Common BAS Network Specifications 2 2 Topology: RS-485, 3 conductor (+, -, and shield),Switch daisy2 chain wiring (no stars or t-taps) Wire Requirement / Maximum Length: Belden 8760 / 4000’(1216m) Controller BACnet MS/TP Controller Switch Baud Rate: DIP switch selectable 9.6K, 19.2K, 38.4K, or 76.8K Device Profile: BACnet Advance Application Controller (AAC) Address Range: 1 – 99 selectable with rotary dials Digital Input: 4-Wire Occupancy Sensor segment (Dry Contact) Unit Load: Full unit load, 3224VDC devices per MS/TP Points: See Application Guide and PIC Statement N2 N/O 1 Baud Rate: DIP switch selectable 9.6K Address Range: 1 – 255 selectable with rotary dials and DIP switch G Common P1 Controller Baud Rate: DIP switch selectable 4.8K, 9.6K, 19.2K, or 38.4K Power Address Range: 1 – 99 selectable with rotary dials Install Guide : Page 11 A1 Switch 2 G GND 24V 24VDC Supply Controll Switch Ground GND 24V COM N/O N/C Install BT485 Terminator if RP is operated as end of line device(first or last device on network). BT485 Terminator requires no specific orientation in relation 24V GND Occupancy to the terminal. Sensor 24VDC Supply See Controller Setup for Address and Protocol settings. BAS Network (End-of-line Device) Signal (+) Signal (-) Belden 8760 BT485 A+ BBelden 8760 S Shield* Signal (+) A+ Signal (-) B- Shield S Controller *Do not terminate shield on BAS output. Controller BT485 Terminator (Figure 14) Controller Terminations LEXP Terminations ON 901 6 7 8 78 78 5 456 4 R N SW4 OVER 1 2 3 1 2 3 4 5 6 7 8 DI Jumper 33-40* 24VDC Supply 24V GND Relays 33-60 *DI Jumper Position N(Dry Contact) / R(Externally Powered) Controller LEXPCTS-DDN Port 24 24VDC (Red) 24VAC(+) Power In 24VAC(-) Power In H Signal (+) (Green) 24VAC(+) Auxiliary Out 24VAC(-) Auxiliary Out L Signal (-) (White) G Ground (Black) 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G CL3P / 22AWG / 4 Conductor Unsheilded DI 9 DI 10 DI 11 DI 12 DI 13 DI 14 DI 15 DI 16 GND GND DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 GND DI 17 DI 18 DI 19 DI 20 DI 21 DI 22 DI 23 DI 24 G 1 2 AUX VAC INPUTS 1-16 CTS Leads POWER Unsheilded Power LED DI Jumper 25-32* GND DI 40 DI 39 DI 38 DI 37 DI 36 DI 35 DI 34 DI 33 Jumper CL3P / 22AWG / 4 DI Conductor 9-16* Ground (Black) N R N N INPUT POWER 24VAC J4 G 17 18 19 20 21 22 23 24 9-16 R J5 Signal (-) (White) N 1-8 R J9 RELAYS 33-60 J13 Signal (+) (Green) J18 J19 B D LEXP 17-24 R DI Jumper 17-24* DI Jumper 1-8* TO J26 OF Controller G J26 24VDC (Red) DI Jumper 41-48* DI Jumper 49-56* DDN Network: CTS-DDN w/24VDC External Power Supply Relays 1-32 GND DI 32 DI 31 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 L 5V A6 A5 A4 A3 A2 A1 G A C ADDRESS H J2 5VDC AI 6 AI 5 AI 4 AI 3 AI 2 AI 1 GND Address Jumper Terminator Jumper 24 Run LED RELAYS 1-32 DDN Network DDN Network: CTS-DDN Controller RUN Controller Port PWR DDN/CAN DDN Network(+) GND INPUTS 17-32 SW1 SW3 AUTO 456 3 23 901 2 23 1 BT485 S B- A+ DI 41 DI 42 DI 43 DI 44 DI 45 DI 46 DI 47 DI 48 GND DI 49 DI 50 DI 51 DI 52 DI 53 DI 54 DI 55 DI 56 GND DDN Network Specifications Baud Rate / Protocol Network Address Rotary Switch 10’s Network Address Protocol: Digital Device Network (DDN)Dip Switch BAS(+) In Rotary Switch 1’s Address Range: 1-60, DIP switch selectable BAS(-) In Topology: Daisy Chain Wiring (no stars or t-taps) Shield Wire Requirement: CL3P, BT485 22AWG, 4 conductor, Unsheilded Terminator Plug Maximum Stations (w/o external power): 10 CTS-DDN (if applicable) Maximum Length (w/o external power): 500’(152m) Override Controls Maximum Stations (w/ external power): 60 one-button, 30 two-button, or a combination for 60 buttons total Maximum Length (w/ external power): 2,000’(610m) 24VDC Power LED Power / Draw: 24VDC / 15mA per CTS-DDN DDN Network(-) CTS Leads CTS-DDN (Figure 15) AI (Analog Input) / DI (Digital Input) / GND (Ground) *DI Jumper Position N(Dry Contact) / R(Externally Powered) Baud Rate / Protocol Dip Switch: BACnet MS/TP Network Address Network Address 1’s Programming 9600 19200 5V Common See Automated Logic Corporation’s ARC156 Wiring Technical Instructions for the latest BACnet ARCnet specifications. BAS Network (Input and Output) Analog Inpu © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 38400 76800 24V GND 24VDC Supply Sensor 24VDC Supply Occupancy Sensor BAS Network (End-of-line Device) BAS Network (Input and Output) BAS Network (End-of-line Device) BAS Network (Input and Output) BBelden 8760 S Shield* www.BRTint.com : 800-241-9173 Blue Ridge Technologies® Signal (-) B- Relay Panel 78 78 78 1 2 3 1 2 3 4 5 6 7 8 J26 LEXP LEXP Port N INPUT POWER 24VAC G 17 18 19 20 21 22 23 24 9-16 R 1-8 R 24VAC(+) Power In 24VAC(-) Power In N N *DI Jumper Posit Relays 33-60 RELAYS 33-60 Neutral DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 Relays 1-32 Line In J18 J19 B D RELAYS 1-32 A C ADDRESS DI Jumper 33-40* 24VDC Po Address Jumper Power LED Run LED GND DI 40 DI 39 DI 38 DI 37 DI 36 DI 35 DI 34 DI 33 456 456 1 2 3 1 2 3 4 5 6 7 8 Line In Override Controls DI Jumper 9-16* N N INPUTS 1-16 N R INPUT POWER 24VAC SW4 OVER POWER J4 J5 G 17 18 19 20 21 22 23 24 9-16 R 1-8 R 8 DI Jumper 41-48* DI Jumper 49-56* 17-24 R DI Jumper 17-24* DI Jumper 1-8* N 7 J2 AI 1 GND RELAYS 33-60 17-24 R 6 SW1 SW3 TO J26 OF Controller J9 J13 GND DI 32 DI 31 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 J26 LEXP 5 Controller Port R N A C ADDRESS 5VDC AI 6 DDN Network Terminator Jumper AI 5 Testing AI 4 1. Connect for power up. AI 3power to the Controller. Wait 10 seconds Relays 33-60 2 2. ConfirmAI normal LED operation. AI 1 Power GNDLED: Solid illumination LEXP Port Run LED: Continuous blinking DI Jumper 17-24* Power In turn off. 3. Press and release the Over Button. Confirm24VAC(+) the Relays DI Jumper 24VAC(-) Power In 4. Press and 1-8* release the Over Button again. Confirm the Relays turn on. 24VAC(+) Auxiliary Out 5. Press and release the Auto Button to exit override mode. DI Jumper 24VAC(-) Auxiliary Out 9-16* 6. Test procedure complete. 4 AUTO 5V 5VDC A6 A5 AI 6 A4 A3 AI 5 A2 A1 AI 4 G AI 3 *DI Jumper Position N(Dry Contact) AI/ 2R(Externally Powered) J2 5V A6 A5 A4 A3 A2 A1 G 3 Neutral 901 901 2 Power LED PWR DIRUN Jumper DDN/CAN 25-32* 24VDC DDN Network(-) DDN Network(+) GND J18 J19 B D TO J26 OF Controller RELAYS 1-32 Address Jumper DDN/CAN RUN Controller Port PWR 1 BT485 S B- A+ BT485 Terminator Plug (if applicable) SW4 OVER Conta Rotary Switch 1’s ON INPUTS 17-32 SW1 SW3 AUTO DI 52 DI 53 DI 54 DI 55 DI 56 GND 8 BAS(+) In BAS(-) In Shield 23 7 23 6 23 BT485 S B- A+ 5 Baud Rate / Protocol Network Address Rotary Switch 10’s Dip Switch Network Address 901 901 4 LEXP Termination 23 Setup BAS(+) In Rotary Switch 1’s BAS(-) In 1. Confirm power is disconnected from the Controller and the Power / Shield Run LED’s are not illuminated. BT485 2. Terminator Set thePlug DDN Network Terminator Jumper if utilizing DDN Network. (if applicable) Two devices on the DDN Network should be set for network termination. If the Controller is the end-of-line, terminate Override Controls the Controller and the device at the opposite end of the network. If the Controller is positioned terminate devices at the 24VDC at a mid-point on the network, Power LED DDN Network(-) opposite ends of the network either side of Run theLED Controller. DDN Network(+) 3. Set theGND Digital Input (DI) Jumpers. (Controller and LEXP) DDN the Network 4. Set Baud Rate / Protocol Dip Switch for protocol and baud rate. Terminator Jumper 5. Set the Network Address. Relays 1-32 3 Shield Install Guide : Page 12 BT485 Terminator Controller Terminations DI 49 DI 50 DI 51 DI 52 DI 53 DI 54 DI 55 DI 56 GND Baud Rate / Protocol Network Address Rotary Switch 10’s Dip Switch Network Address 2 Signal (Contactor Belden 8760 S Shield* DI 41 DI 42 DI 43 DI 44 DI 45 DI 46 DI 47 DI 48 GND Controller Setup Controller Terminations LEXP Terminations Controller configuration and RP testing are the final steps of installation. (Figure 16) 1 Signal (+ B- Controller ON Manual Ov © 2012 Blue Ridge Technologies International, All Rights Reserved. BR-RP16-64-IG-V11.00 Controller *Do not terminate shieldLLC on BAS output. S Shield Controller *Do not terminate shield on BAS output. Belden 8760 A+ 78 Signal (-) Technologies Signal (+) A+ Signal (-) 456 B l Belden ueR idge 8760 Signal (+) BT485 A+ 456 Signal (+) 24VAC(+) Auxiliary Out 24VAC(-) Auxiliary Out AUX VAC AUX VAC Baud Rate / Protocol Dip Switch: BACnet MS/TP Network Address 1’s Network Address 10’s Programming 9600 78 3 4 5 6 7 8 ON 1 SW1 2 3 4 5 6 7 8 1 SW1 2 SW1 456 456 SW4 3 901 4 5 8 901 ON 1 1 2 3 4 5 6 2 3 Externally Powered 2 3 4 5 6 7 8 R Baud Rate / Protocol Dip Switch: P1 N N Programming 3 4 SW1 7 8 Dry6 Contact Terminated J2 1 3 4 5 6 7 8 SW1 3 4 5 6 SW1 Baud Rate / Protocol Dip Switch: BACnet ARCnet ARCnet 6 2 3 SW1 3 5 6 7 8 7 8 Network Ad 7 7 8 J2 5 6 3 4 5 6 7 1 8 2 3 4 7 8 SW1 Programming 19200 1 2 3 4 Un-terminated SW1 2 SW1 8 7 8 Terminated ON 1 1 ON ON 2 SW1 J2 4800 38400 ON 3 4 5 6 2 3 4 5 6 SW1 7 8 1 7 2 8 3 1 4 5 6 2 3 4 5 6 SW1 7 8 SW1 Baud Rate / Protocol Dip Switch: BACnet ARCnet ARCnet ON 4 6 ON 1 2 5 N2 Network ON 1 4 SW1 7 8 ON N ON 2 5 Baud Rate / Protocol Dip Switch: P1 DDN Network Terminator Jumper 1 1 4 Programming / 9600 R 9600 ON 2 8 3 SW1 SW4 1 2 3 Powered 4 5 6 Externally 5 N DDN Network Terminator Jumper 7 2 Baud Rate / Protocol Dip Switch: N2 SW1 4800 ON 6 1 Digital Input (DI) Jumper 2 R R 5 ON SW1 SW1 4 SW1 7 8 1 1 1 ON ON See right for N2 addresses 100-255 Network Address +100 Network Address +200 Programming / 9600 Digital Input (DI) Jumper J2 7 N2 Network Addresses 100-255 ON Un-terminated 6 SW3 Baud Rate / Protocol Dip Switch: N2 9600 76800 ON ON 78 2 DI 9 DI 10 DI 11 DI 12 DI 13 DI 14 DI 15 DI 16 GND Programming 23 78 Network Address 1’s Network Address 10’s 19200 38400 ON See right for N2 addresses 100-255 Dry Contact Baud Rate / Protocol Dip Switch: BACnet MS/TP 23 23 23 SW3 1 Network Address 78 ON 901 GND DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 GND DI 17 DI 18 DI 19 DI 20 DI 21 DI 22 DI 23 DI 24 DI 9 DI 10 DI 11 DI 12 DI 13 DI 14 DI 15 DI 16 GND GND DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7 DI 8 Network Address 901 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G AI (Analog Input) / DI (Digital Input) / GND (Ground) *DI Jumper Position N(Dry Contact) / R(Externally Powered) AI (Analog Input) / DI (Digital Input) / GND (Ground) *DI Jumper Position N(Dry Contact) / R(Externally Powered) 456 GND DI 17 DI 18 DI 19 DI 20 DI 21 DI 22 DI 23 DI 24 G 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 G 456 G 1 2 2 SW1 3 4 5 6 7 8 (Figure 16) BlueRidge Technologies www.BRTint.com : 800-241-9173 Blue Ridge Technologies® Line Low Relay Panel Line © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 Front Install Guide : Page 13 Optional Equipment RP may be equipped with the following optional equipment. (Figure 17) 1. Multi-pole Electrically Held Lighting Contactor 2. Line Voltage Bay 3. UL924 Emergency Bypass 4. Auxiliary Transformer w/Earth Ground Lug 5. Low Voltage Bay 6. BACnet IP Router 7. 24VDC Power Supply Complete optional equipment termination and configuration. 1. Confirm power is disconnected from the RP. 2. If applicable remove Dead Front Cover to reveal the Line/Low Voltage Bay a. Unlock 1/4 turn fasteners located on inside edge of the cover. b. Remove cover by rotating inside edge outward and pulling cover free. 3. Complete required termination and configuration. See Page 14 for specifications. 4. If applicable replace Dead Front Cover. a. Align cover tabs with matching slots in Panel Enclosure and rotate the covers inside edge inward. b. Lock 1/4 turn fasteners located on inside edge of the cover. 1 2 3 4 5 6 WARNING : Live Parts Disconnect before servicing. Disconnect provided by installer, located remotely. Panel protected by circuit breaker or equivalent current limiting device. Transformer Input Voltage Rating : 120 or 277 VAC +/- 10%, 30 VA, 50 / 60 Hz Transformer Output Voltage Rating : 24 VAC +/- 10% Relay Short Circuit Current Rating (SCCR) 20,000 Amps @ 277 VAC Use only copper conductors rated only @ 60 degree celsius minimum. 7 (Figure 17) Controller 2 N 2 24 V COM N/O Switch N/C H cy L Controller Switch Light Sensor Mounting Hole CTS-DDN Transformer Terminations Signal (-) (White) Line In 347 Transformer Terminations Relay Panel BlueRidge ntact) Common Common Phillips / Slot / Square Head Screw Terminals 24VDC (Red) GND 24V (+) (Green) 24VDCSignal Supply Controller LTR Terminations G Switch 2 H1 H2 G Relay Output Ground (Black) Technologies 277VAC Brown BAS Network (End-of-line Device) 120VAC Black CL3P / 22AWG / 4 Conductor CTS Leads Blue Ridge Technologies® © 2012 Blue Ridge Technologies International, LLC All Rights Reserved. BR-RP16-64-IG-V11.00 www.BRTint.com : 800-241-9173 Neutral White Manual Override Lever Wire Strip Length Indicator Unsheilded BT485 Earth Ground Signal (+) 24V COM N/O Controller N/C Low Voltage Bay LTR Terminations Load Phillips / Slot / Square Head Screw Terminals Mounting Hole Analog Input: 5VDC Light Sensor Line In INPUTS 17-32 2 DI 41 DI 42 DI 43 DI 44 DI 45 DI 46 DI 47 DI 48 GND DI 49 DI 50 DI 51 DI 52 DI 53 DI 54 DI 55 DI 56 GND x 5.00”(127mm)D s Rotary Switch 10’s RP Overall: Add approximately 9.00”(229mm) to overall RP height 5V Switch 1 1 Address Network Location: Bottom of RP Rotary Switch BAS 1’s Network (End-of-line Device) Custom Option: Dead Front Cover (reduces bay depth to 4.30”(109mm)) A1 G Common RP equipped with Low Voltage Bay UL Listed, BT485UL508A, US/Canada Switch 2 Signal (+) R N + Contactor Power Power Signal Signal Neutral Override Lever LineManual In G DI Jumper 41-48* DI Jumper 49-56* LTR Relay Output Wire Strip Length Indicator Common Common J5 J4 (Figure 18) POWER J9 INPUTS 1-16 H2 N R A C ADDRESS J13 TO J26 OF Controller Address Jumper LEXP Terminations dress Rotary Switch 10’s Multi-pole Earth Ground R N LEXP Port INPUTS 17-32 Electrically Held Lighting Contactors* (Figure 18) Jumper Position N(Dry Contact) / R(Externally Powered) 120 *DI / 277 VAC Contactors: 4 Pole 30A N/O (field convertible to N/C) Wire: 16-10AWG or 8-6AWG with ring terminals (Solid or Stranded) Jumper Quantity: 1, 2, or 4 Contactors for control of upDIto 16 circuits Network Address Coil: Relays 33-60 Rotary Switch 1’s J9 J13 41-48* DI Jumper Transformer) (Figure 49-56* Contactor Mounting Hole INPUTS 1-16 J4 J5 J18 J19 B D N R A C ADDRESS Address Jumper Line In L(+) + Line In Neutral N(-) - Relay Output DI 14 DI 15 DI 16 GND GND DI 40 DI 39 DI 38 DI 37 DI 36 DI 35 DI 34 DI 33 GND DI 32 DI 31 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 Manual Override Lever Wire Strip Length Indicator Signal (+) 24VDC Relays 33-60 9600 19200 24VAC(+) Power In BACnet 24VAC(-) Power In ON IP Contactor Coil Terminations Load 38400 76800 Router*Controller ON ON BT485 Terminator between BACnet MS/TP and BACnet Ethernet / IP wired and 96001 (19200, and 4 3 4 5 for 6 7power 8 1 BACnet 2 3 4 5 MS/TP 6 7 8 2 3 4 5 38400, 6 7 8 XP Terminations 76800 network capacity). SW1 SW1available at reduced SW1 Ethernet Connection Network Type: BACnet Ethernet / IP e / Protocol Dip Switch: N2 N2 Network Addresses 100-255 Data Rate: 10/100 Mbps Wire Requirement / Maximum Length: 328’(100m) NetworkCAT5 Address/ +200 Network Address +100 gramming / 9600 Routing 24VAC(+) Auxiliary Out Out1 2 Factory 5 24VAC(-) 6 7 8Auxiliary DI 12 DI 13 DI 14 DI 15 DI 16 GND DI 41 DI 42 DI 43 DI 44 DI 45 DI 46 DI 47 DI 48 GND DI 49 DI 50 DI 51 DI 52 DI 53 DI 54 DI 55 DI 56 GND INPUTS 17-32 R N DI Jumper ON 41-48* UL924 Emergency Bypass DI Jumper UL924 provides energy management 1 2 3 449-56* 5 6 7 8 1 2 ON J9 J13 TO J26 OF Controller POWER control of7 emergency lighting 3 4 5 6 8 2 3 4 5 6 7 8 circuits normal operation while Power LED d1Rate / Protocol Dip Switch:during BACnet MS/TP SW1maintaining emergency function SW1 DI Jumper during power loss. See the UL924 Install Guide for specific instructions. 25-32* INPUTS 1-16 N R ming 3 J4 J5 J18 J19 B D A C ADDRESS 9600 gramming e / Protocol Dip Switch: P1 ON DI Jumper 33-40* 4800 4 5 6 7 8 19200 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 GND DI 40 DI 39 DI 38 DI 37 DI 36 DI 35 DI 34 DI 33 GND DI 32 DI 31 DI 30 DI 29 DI 28 DI 27 DI 26 DI 25 2 ON SW1 3 4 5 6 7 8 1 2 SW1 3 4 5 6 7 8 1 2 SW1 3 4 5 6 7 5 6 7 LTR 8 Neutral Line In 24VDC Power Supply Terminations Line In L(+) + N(-) - 24VDC Out 24VDC Power Supply 38400 1 ON ARCnet 4 Neutral 19200 1 3 ON e / Protocol Dip Switch: BACnet ARCnet ON ON ON * Included third party documentation applies to this equipment. 1 2 76800 3 4 5 6 ON ON WARNING : Live Parts SW1 SW1 SW1 Disconnect before servicing. Disconnect provided by installer, located remotely. Panel protected by circuit breaker or equivalent current limiting device. Transformer : 120 or +/- 10%, 4 5 6 7 8 2 3 4 5 6 Input 7 8Voltage Rating 1 2 3 4 5 277 6 7 VAC 8 1 30 2 VA, 3 4 505 / 60 6 Hz 7 8 *DI Jumper Position N(Dry1 Contact) / R(Externally Powered) Transformer Output Voltage Rating :100-255 24 VAC +/- 10% d Rate / Protocol Dip Switch: N2 N2 Network Addresses SW1Relay Short Circuit CurrentSW1 Rating (SCCR) 20,000 Amps SW1 @ 277 VAC Use only copper conductors rated only @ 60 degree celsius minimum. Network Address +200 Network Address +100 Programming / 9600 1 1 SW1 Contactor ON 9600 1 ON 38400 ON 8 24VDC Out 24VDC Power Supply PowerA+ Supply* 20)Contact) / R(Externally Powered) *DI Jumper (Figure Position N(Dry Primary: 100-240VAC (50-60HZ) Signal (-) BSecondary: 2.5A 24 VDC +/- 1% (Adjustable from 22.5-29.5VDC) e / Protocol Dip Switch: BACnet MS/TP LEXP Port Wire: 24-12AWG (Solid or Stranded) S 2 (Figure 19) 24VDC Power Supply Terminations Phillips / Slot / Square Head Screw Terminals 19) Auxiliary Transformer Relays 1-32 Matched to primary transformer specification 120/277 or 347VAC BT485 Shield LTR Earth Ground Line In LTR Terminations line Device) ming Neutral Black Neutral POWER Controller Port TO J26 OF Controller 24VAC(+) Power In 24VAC(-) Power347VAC In Transformer (Replaces Standard Override Controls Power LED Type: UL Listed Single Tap 24VAC(+) Auxiliary Out DI Jumper 24VAC(-) Auxiliary Out Primary: 347VAC, 50VA, 60 Hz 25-32* Power LED Secondary: 24VAC +/-10% Inherently Limited Run LED DI Jumper Wire Requirement: 18AWG Minimum (Solid or33-40* Stranded) H1 Neutral White DI 41 DI 42 GND DI 43 DI 40 DI 44 DI 39 DI 45 DI 38 DI 46 DI 37 DI 47 DI 36 DI 48 DI 35 GND DI 34 DI 49 DI 33 DI 50 GND DI 51 DI 32 DI 52 DI 31 DI 53 DI 30 DI 54 DI 29 DI 55 DI 28 DI 56 DI 27 GND DI 26 DI 25 Relays 1-32 4 J18 J19 B D Controller Port Light Sensor 24VDC Power Supply Terminations Line Voltage Bay A+ Controller Dimensions Controller Contactor Coil Terminations GND 24V Signal (-) Override Controls Switch BBelden 8760 Power LED x 4.30”(109mm)D Bay24VDC Interior: 9.00”(229mm)H x 17.88”(454mm)W S Supply L(+) Line In + DI Jumper Load Terminations RP Overall: Add Shield approximately 9.00”(229mm) to overall RP height Transformer Terminations 347 Transformer S 25-32* Power LED 24VDC Out ller Location: Top of RP (maintains left and right wire chases from top of RP) Run LED N(-) Neutral DI Jumper Controller BT485 33-40* line and Accessories: Dead Front Cover (separates lowTerminator voltage 277VAC Brown compartments) 24VDC Power Supply 347VAC Brown 120VAC Black RP equipped with Line Voltage Bay UL Listed, UL508A, US/Canada - Earth Ground Contactor Coil Terminations BT485 Terminator Digital Input: Two Button Low Voltage Switch (Externally Powered) Dimensions pancy LEXP Terminations nsor Bay Interior: 9.00”(229mm)H x 17.88”(454mm)W Neutral Black Install Guide : Page 14 A+ Optional Equipment Signal (-) BBelden 8760 Specifications for the optional equipment are listed below. When applicable, additional third party documentation is S included for detailed specifications Shield and instructions. 347VAC Brown 7 8 1 ON 1 2 3 4 5 6 7 SW1 2 SW1 3 4 5 6 7 8 8 (Figure 20)