ECONOMIZER Ventilation Air Outdoor Air for Free Cooling Mixes Outdoor Air and Return Air ECONOMIZER Two sets of dampers, connected to an actuator, are opened and closed to provide more or less outside air, based on the demand for cooling, and the condition of the air with respect to it’s heat content. COMPONENTS W7459 LOGIC MODULE Responds to single or dual enthalpy sensors Discharge air sensor Used on “standard” economizers Does not have IAQ features W7212 IAQ LOGIC MODULE The W7212 control will modulate the economizer actuator in response to a variety of inputs. Not all terminals shown are used when this module is applied to all units. ENTHALPY SENSOR HONEYWELL C7400 Enthalpy is a measure of total heat. It’s output is 4-20 milliamps. Two are used when the application calls for dual enthalpy. C7650 AMBIENT SENSOR DRY BULB AMBIENT TEMPERATURE SENSOR Responds only to temperature (no humidity) Can be used for “dual” temp control with 1 in return and 1 in outside air 4-20 milliamps output Mounted in outdoor hood Slide 105 ACTUATOR HONEYWELL M7415 TR –TR1 = 24vac power T-T1 = Mixed air sensor P1-P – Minimum position 90 degree travel IAQ CO2 SENSOR model 2AQ04700324. Room sensor for CO2 monitoring If the unit has a W7459 Economizer Control, install a Honeywell Q769C Potentiometer signal converter 0-10 VDC Potentiometer Signal Converter (Honeywell Q769C)Q769C BOX . IAQ CO SENSOR WIRING WITH W7459 MODULE Q769C Converter SEQUENCE OF OPERATION SEQUENCE OF OPERATION Economizers should always be installed with a 2-stage thermostat Provides both economizer cooling and mechanical cooling as needed LOGIC MODULES W7459 LOGIC MODULE CONNECTIONS TR – TR1 = 24 vac power supply So - +o = Outside Air Enthalpy Sensor Sr - +r = Return Air Enthalpy Sensor. Not used in single enthalpy applications (620 ohm resister is put in it’s place) N = 24vac input to force the actuator to minimum position 1 = 1st stage cooling input 2 = 1st stage mechanical cooling output 3 = 2nd stage cooling input 4 = 2nd stage mech. Cooling output T & T1 = Mixed Air Sensor P & P1 = Remote Min Position W7459 MODULE ADJUSTMENTS Enthalpy set point • Sets where economizer will open in relation to temperature & Humidity Minimum position potentiometer • Used to set % of outside air for ventilation W7459 LOGIC MODULE LED LED • Lit whenever unit is in “free cooling” mode W7212 LOGIC MODULE INPUTS TR & TR1 - Provides 24vac to the control. Nothing happens unless these terminals are powered N - 24vac at this terminal indicates occupied mode. When TR & TR1 are powered, 24vac at this terminal will force the actuator to move to its minimum position P1 & P - This circuit is jumpered at the factory, but can be used with an optional minimum position potentiometer. When these terminals are jumpered, the module will control the minimum position of the outdoor air damper using the on-board adjustment. T1 & T - These terminals are used for the discharge air sensor. If the free cool LED is lit and a call for stage 1 cooling has been initiated, then the module will vary the 210vdc output to the actuator to maintain the discharge air temperature to between 50º and 56º. W7212 ADJUSTMENTS Min Pos - This setting is adjustable from 2 to 10 vdc. When the module has voltage at Tr1, Tr and N, this pot will control the output voltage supplied to the actuator for minimum position. DCV Max & DCV Set - These two pots are used to position the dampers in response to an input from an optional CO2 sensor placed across the AQ1 & AQ terminals. Enthalpy Setpoint - This adjustment pot, marked by letters A B C D, is used to by the module to determine under what conditions the module should allow free cooling. W7212 LED’S ExH - If this LED is energized, it indicates the module is in exhaust mode. Contacts EF & EF1 will be closed. DCV - If this LED is energized, it indicates the module is in demand ventilation mode. The IAQ sensor is providing a dc voltage higher than the DVC Setpoint. Free Cool - If this LED is energized, it indicates the module is in free cooling mode. When using a single outdoor enthalpy sensor, this indicates the enthalpy sensor is measuring an enthalpy level below the corresponding A, B, C, D setpoint W7212 EXHAUST MODE This mode of operation is used when an optional power exhaust is installed on the unit. If the voltage output to the actuator exceeds the adjustable setpoint, the ExH LED is energized and the normally open contacts between terminals EF & EF1 are closed. At this point, two things will happen: • The coil for relay CR is energized. Its normally closed contacts open, locking out the second stage compressor • The coil for relay ER is energized. Its normally open contacts close, energizing the power exhaust motor. NOTE: The 45 (+/- 15) second delay in closing the EF & EF1 contacts allows the actuator to drive to the exhaust fan setpoint. W7212 COOLING MODE In a single enthalpy application, when the logic module senses 24 vac at terminal 1, it compares its enthalpy setpoint (A, B, C or D) to the milliampere signal being sent by the C7400 sensor to terminals So+ & So. If the enthalpy of the air passing over the sensor is below the setpoint, the free cooling LED is energized and the voltage output to the actuator is now determined by the discharge air sensor. As the discharge air sensor resistance goes up (an indication the air temperature is dropping) the voltage output to the actuator goes down. As the sensor resistance goes down (indicating the air temperature is rising), the voltage output to the actuator goes up. W7212 DEMAND VENTILATION This mode of operation allows the logic module to respond to a 2 -10 vdc input on terminals AQ1 & AQ. There are a variety of sensors available, depending on which contaminant you want to control. The most frequently used sensor controls carbon dioxide (CO2) so we’ll use that to illustrate an example. If the carbon dioxide level, in the space where the sensor is located, begins to increase, the sensor sends a 2 -10 vdc signal to the AQ1 & AQ terminals on the logic module. If the output voltage from the CO2 sensor is higher than the DCV setpoint, then the demand ventilation mode will begin to drive the actuator open. However the voltage output to the actuator is limited by the DCV Max pot setpoint. W7212 FREEZE PROTECTION During demand ventilation mode, if the discharge air temperature drops below 45º, the voltage output to the actuator is reduced to the minimum position pot setpoint. This was designed into the W7212 to protect the coil and building from freezing. . ECONOMIZER SETTINGS Minimum Position Adjustment CORRECT MINIMUM POSITION SETPOINT Measure the temperature of the outside air. Multiply it by the percentage of outside air required. Measure the temperature of the return air, then multiply it by the percentage of return air required. Add the two remainders. That sum is the temperature of the mixed air. CORRECT MINIMUM POSITION SETPOINT (OAT X OA%) + (RAT X RA%) = MAT WHERE: OAT = Outdoor Air Temperature OA% = Percentage of Outdoor Air Required RAT – Return Air Temperature RA% = Percentage of Return Air Required MAT = Mixed Air Temperature CORRECT MINIMUM POSITION SETPOINT (OAT X OA%) + (RAT X RA%) = MAT EXAMPLE: The building requires 15% of outside air. The outdoor air is 50º and the return air is 78º. 50º outside air x 15% = 7.5º 78º return air x 85% = 66.3º 7.5º + 66.3º = 73.9º Therefore, our mixed air temperature, when the minimum position damper is set for 15%, will be 74º. Note: For greatest accuracy, this method requires a minimum temperature difference between OA & RA of 15 degrees TROUBLE SHOOTING SAFETY You've carefully thought out all the angles. You've done it a thousand times. It comes naturally to you. You know what you're doing. Its what you've been trained to do. Nothing could possibly go wrong, Right? TESTING THE MOD MOTOR With the module removed • Apply 24 VAC to TR & TR1 • Jump T & T1 • Jump P & P1 Motor should drive open If not, remove the linkage and try again TESTING THE ENTHALPY SENSOR 12.30 Normal reading between 4 and 20 milliamps + - TESTING C7400 ENTHALPY SENSOR Determine the dry bulb temperature and relative humidity of the air in the area where the sensor in located. Insert a dc amp meter in series with the So or Sr (whichever sensor is being tested), and compare with the mA output current shown on the attached chart. TESTING THE ENTHALPY SENSOR Jumper R to G on the unit control board. This will provide 24 volts to TR & TR1 on the logic module Insert a DC ammeter in series with either SO or SR, depending on which sensor is being checked Make sure to connect the positive lead from the meter to S on the sensor and the negative lear to either the wire or S on the control Meter should indicate a reading between 4 to 20 mA if the sensor is operating properly If the meter indicates “0”, the sensor may be wired backwards. If the reading is out of the 4 to 20 mA range --- replace the sensor. TESTING THE ECONOMIZER LOGIC MODULE Apply 24 VAC Power Supply •Jumper TR to 1 •Jumper T to T1 •Jumper P to P1 •Apply 24 VAC to TR and TR1 •Remove enthalpy sensor and leave resistor in place L.E.D. is off, motor to minimum position TESTING THE ECONOMIZER LOGIC MODULE Apply 24 VAC Power Supply •Jumper TR to 1 •Jumper T to T1 •Jumper P to P1 •Apply 24 VAC to TR and TR1 •Remove resistor from SR &+ •Jumper So & + L.E.D. is on, motor drives open TESTING THE LOGIC MODULE Disconnect power at TR & TR1. Remove the jumper across P & P1. Jumper TR to terminal 1 on the logic module Jumper T & T1 Remove leads from outdoor sensor at SO and +. Leave the factory installed 620 ohm resistor across SR & +. Apply 24 volts to TR & TR1 by energizing the blower circuit When power is applied, the L.E.D. should be OFF on the module and the dampers should be in the CLOSED position. Next, shut off power to the unit. Disconnect the 620 ohm resistor across SR & +. When power is reapplied, the L.E.D. should be ON and the dampers should drive to the FULL OPEN position ELECTRICAL TROUBLESHOOTING To electrically check the “staging relays” in the module, perform the ELECTRICAL TROUBLESHOOTING PROCEDURE as outlined on the following slide. To check out the sensors and L.E.D. on the module, use the chart marked “QUICK CHECK OUT CHART”. To BY-PASS the economizer, refer to the wiring diagram slide in this section Single Enthalpy Economizer Checkout T - T1 SO - + SR - + L.E.D. Outside Air Damper Position Jumper Jumper 620 ohm R On Full Open Jumper Open 620 ohm R Off Closes to Minimum Setting Open Open 620 ohm R Off Closes to Minimum Setting Open Jumper 620 ohm R On Closes to Minimum Setting Dual Enthalpy Economizer Checkout T - T1 SO - + SR - + L.E.D. Outside Air Damper Position Jumper Jumper Jumper On Full Open Jumper Jumper Open Off Closes to Minimum Setting Jumper Open Jumper Off Closes to Minimum Setting Open Jumper Open Off Closes to Minimum Setting Open Jumper Jumper Off Closes to Minimum Setting SIMULATING LOW ENTHALPY •Reconnect 620 ohm resistor to SR & + •Connect 1.2K ohm checkout resistor to SO &+ •Turn enthalpy setpoint pot to “A”. L.E.D. turns on, motor drives open SIMULATING HIGH ENTHALPY •Turn enthalpy setpoint pot to “D”. L.E.D. turns off, motor drives to minimum DISCHARGE AIR SENSOR A negative coefficient resister. 3K at 77 Degrees F DISCHARGE AIR SENSOR