IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 24, NO. 4, NOVEMBER 2009 1731 Maximum Frequency Deviation Calculation in Small Isolated Power Systems Ignacio Egido, Fidel Fernández-Bernal, Pablo Centeno, and Luis Rouco, Member, IEEE Abstract—Large frequency deviations due to a number of disturbances are frequent in small isolated power systems. The maximum frequency deviation in the system is limited to prevent other generator tripping. It is important to have an accurate model to calculate it, both for system planning and operation. A new simplified model to calculate the maximum frequency deviation when either a generator or load-related disturbance occurs in these systems is presented. This model takes into account the response of governor-prime mover even when different technologies are present in the power system. Model parameters can be easily obtained from either more complex models or from test records. Simulation results for an actual power system aimed at checking the model accuracy are presented. High accuracy is obtained while computation time is reduced due to the simplicity of the model. Index Terms—Frequency deviation, isolated power systems, load shedding, minimum frequency, spinning reserve. NOMENCLATURE Ramp gain of generator ( in ). Ramp gain of generator ( in ). Base frequency (Hz). Minimum frequency (Hz). Pre-disturbance system frequency (Hz). Equivalent inertia of the power system (s in ). Inverse of the droop of generator ( in ). Inverse of the droop of generator ( in ). Inverted sign frequency derivative . Number of generating units in the power system. System base power after disturbance (MVA). Rated power of generator (MVA). Time from disturbance (s). Time instant of minimum frequency occurrence (s). Time constant of governor (s). Frequency deviation . Manuscript received October 16, 2008; revised March 18, 2009. First published September 09, 2009; current version published October 21, 2009. Paper no. TPWRS-00837-2008. I. Egido, F. Fernández-Bernal, and L. Rouco are with Escuela Técnica Superior de Ingeniería (ICAI), Universidad Pontificia Comillas de Madrid, Madrid, Spain (e-mail: egido@iit.upcomillas.es). P. Centeno is with Alstom Power Systems, Baden, Switzerland. Digital Object Identifier 10.1109/TPWRS.2009.2030399 Maximum frequency deviation . Disturbance: increment of load power System frequency . . Pre-disturbance system frequency . I. INTRODUCTION S MALL isolated power systems exhibit special characteristics which make them particularly vulnerable to the occurrence of large frequency deviations affecting the security of the system. The main characteristic is the low value of the inertia constant due to the reduced number of generators connected to the system and the fact that most of the generators in isolated systems are driven by diesel engines. When a generator trips, these power systems may exhibit high initial rates of frequency decay. When a generator trips, not only a large amount of generation can be lost, but inertia also, both factors contributing to a high value of the initial slope of the frequency. This fact makes the existing spinning reserve useless in some cases, since it cannot be fast enough to arrest the frequency decay [1]. To address these issues, usual actions and limitations are: load shedding (by under-frequency relays and rate of frequency relays), minimum spinning reserve, load reconnection limitation, and wind power generation limitation (sometimes restricted during operation in isolated power systems for fear of a sudden trip of wind generation which can lead to load shedding) as shown in [2]–[4]. Adjusting frequency relays in load shedding schemes, estimation of the amount of necessary spinning reserve, limitation of the amount of load reconnection, or calculation of the wind power generation limit to preserve security in the power system are key examples where a model to estimate frequency deviation is essential. If these assessments are to be calculated in normal operation to provide adaptive adjustments or limitations, then a simple model is necessary. Model proposed in [5] has been used for this purpose in [6]–[8], although it has the drawback that all governors and prime movers in the system have to be very similar in speed and, in principle, all generation have to be of the reheat steam turbine type. On the other hand, the model proposed in this paper is a linear model that admits a variety of generation technologies with very different governors. This is the case in small isolated power systems, where the generation mix usually comprises diesel, gas, fossil-fueled steam, and sometimes combined cycle gas turbines. A method to obtain model parameters from a more complex model or from dedicated tests is detailed. Simulation results are also presented to verify the accuracy of the model. 0885-8950/$26.00 © 2009 IEEE 1732 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 24, NO. 4, NOVEMBER 2009 Fig. 3. IEEE recommended general model for steam turbine speed governing systems: IEEEG1 PSS/E model. Fig. 1. Equivalent model in Laplace transform of a power system to analyze the frequency behavior. Fig. 2. Typical diesel governor and prime mover: DEGOV1 PSS/E model. II. FREQUENCY DEVIATION MODELS IN THE LITERATURE Fig. 4. Typical gas turbine governor and prime mover: GASTWD PSS/E model. A. Classical System Model A typical model used to represent the frequency deviations in a power system is shown in Fig. 1 [2]. Governor represents the model of the speed governor and the prime mover of generating unit and will be detailed in Section II-B. This general model, and therefore all simplified models derived from it, assumes the following typical simplifications: 1) Frequency value is uniform throughout the system. Therefore, the inter-machine oscillations are neglected; 2) The inertias of the different generating units are joined in one equivalent , taking into account the different rated power of the inertia, generating units; 3) The overall damping of loads due to their frequency dependency is modeled by a single damping factor . B. Complex Speed Governor and Prime Mover Models Dynamic models to adequately represent the behavior of the speed governors and prime movers have been widely presented and used in the literature. Models of steam turbines are presented in [9]–[11]. Models of hydraulic turbines are detailed [12] whereas models of gas turbines are provided in [13]. Models of combined cycle plants are provided in [14] and [15]. Models for different technologies are also presented in [16]–[19]. Examples of typical models of governor-prime movers are shown in Figs. 2–4. A typical diesel model (DEGOV1 PSS/E model [20]) is shown in Fig. 2, IEEE recommended general model for steam turbine speed governing systems (IEEEG1 PSS/E model [20]) in Fig. 3, and a typical gas turbine model (GASTWD PSS/E model [20]) in Fig. 4. C. Simplified Speed Governor and Prime Mover Models As shown before, dynamic models to adequately represent the behavior of the speed governors and prime movers are usually complex, which makes it difficult to perform simplified calculations regarding the behavior of the frequency deviation. In technical literature, two levels of simplification have been applied to the model of Fig. 1: 1) Governors and prime movers are considered to keep con, and stant the output power after a step disturbance damping of the loads is neglected. In that case, frequency deviation is calculated by the well-known expression (1) [21]. Time response is shown in Fig. 5: (1) This assumption can be considered correct in the very first instants after the disturbance, and it is a very good approximation to the initial value of the frequency derivative. Note that (1) cannot be used to calculate the minimum value of frequency (frequency correction is due to governors actions modifying the output power in order to correct frequency deviation). 2) All the governors and prime movers in the system are considered to be identical, and therefore, all of them can be substituted by one equivalent governor. In [5], the proposed model assumes that all governor-prime movers are of the reheat steam turbine type, as shown in Fig. 6. This model has proved to be useful in frequency deviation prediction EGIDO et al.: MAXIMUM FREQUENCY DEVIATION CALCULATION IN SMALL ISOLATED POWER SYSTEMS 1733 Fig. 5. Evolution of frequency under the assumption of constant output power after a step disturbance. Fig. 7. Transient response for a 1% frequency step in DEGOV1 PSS/E model for an actual diesel unit (solid line). Comparison with a first-order model fitted to 25 s of data (dashed line) and fitted using only the first 4 s of data (dotted line). Fig. 6. Equivalent model of the power system to analyze the frequency behavior in [5]. and power imbalance estimation for adaptive load shedding methods as shown in [6]–[8]. III. PROPOSED MODEL TO OBTAIN THE MINIMUM FREQUENCY Model of Fig. 6 is limited to units of the reheat steam turbine type and all unit governor-prime movers should be identical. If other type of unit is present (e.g., diesel or gas), or unit governors are very different, the model of Fig. 6 cannot be used. Hence, a more general model is needed. The model proposed in this paper takes into account the response of the governors of all units in the system and produces sensible results where the aforementioned simple models cannot be used. A. First-Order Model for Speed Governor and Prime Mover In Figs. 7 and 8, the open-loop transient responses for a 1% frequency step for the models of Figs. 2 and 4 are shown in the solid line, respectively. Parameters used for simulation come from real generators in the Spanish isolated power systems. If the open-loop (governor-prime mover) is assumed to be similar to a linear first-order system [see (2)], the estimation of gain, (modeling the inverse of the permanent droop, ), and constant time, (modeling speed response), is necessary: (2) Fig. 8. Transient response for a 1% frequency step in GASTWD PSS/E model for a real gas turbine group (solid line). Comparison with a first-order model fitted to 25 s of data (dashed line) and fitted using only the first 4 s of data (dotted line). In Figs. 7 and 8, the response of a first-order system (dashed line) is shown. The value of parameter is calculated from the detailed model to obtain the same droop. Then, the value of parameter is obtained by fitting the response of the first-order model in (2) to the response of the detailed model in Figs. 2 and 4 using minimum-squared-error technique for 25 s of data. If data from a step test for a generator are available, the same technique can be used to fit model parameters to the real response of the group. In both cases (Figs. 7 and 8), this long-term first-order model obtained might be considered accurate enough. However, in isolated power systems, minimum frequency usually appears in the first seconds after the disturbance. To improve the fitting in these first seconds of the response, parameters are computed taking into account only the first seconds of data. Moreover, as the steady-state value is not important in this case, both and can be calculated using minimum squared-error techniques. As minimum frequency occurs in the range of 1 to 4 s after the disturbance in all the Canary Islands and Balearic Islands power systems, fitting results obtained using only the first 4 s after the 1734 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 24, NO. 4, NOVEMBER 2009 Fig. 9. Simplified equivalent model of the power system to analyze the frequency behavior using short-term first-order model for governors and prime movers. disturbances are shown as an example in Figs. 7 and 8 with a dotted line (a different time range might be necessary in other isolated systems). As can be seen in the figures, the short-term fitting in the first 4 s is improved although the long-term fitting is worsened. Then, as a first simplification, let us model governors and prime movers in the first seconds by a short-term first-order model as shown in Fig. 9. Note that in Fig. 9, steady state has instead of . Usually, droop is given in per been noted by unit of the generator [and then in (2)] and in the diagram of : Fig. 9 droop has to be in per unit of the system where is the base power of group and of the system with N generating units: Fig. 10. Simplified open-loop equivalent model of the power system to analyze the frequency behavior. C. Constant Ramp Model for Speed Governor and Prime Mover In Fig. 10, the output of governor is given by (5) Output begins with zero slope and in steady-state becomes a , being the slope of the frequency ramp of slope decay in (1). Since we are just interested in the evolution of frequency deviation down to its minimum value, let us assume given by (5) could the additional simplification that output as be approximated by an averaged constant ramp shown in (6): (3) (6) is the base power would be a value between 0 and a value lower than where . Note that is a kind of ramp gain of the group . The final simplified equivalent model proposed is shown in Fig. 11, where load variation with frequency, , is also neglected. With typical values of (5 s) and (1 ), the exponential response and the ramp response of are very of similar during the first seconds where minimum frequency usually takes place. is that A maximum value, and likely a good choice, for in (6) to be the same as the value given by which makes : (5) at the instant in which frequency is minimum (4) B. Breaking the Closed-Loop In Fig. 9, the sum of governor outputs is the input for the inertia integration that produces a lag in the frequency evolution. Therefore, to compute the maximum frequency deviation, the important effect is the output of governors some seconds before, when they where excited by the quasi-linear decay of frequency (see Fig. 14 as an example). Then, the input to the governors during the transient could be modeled by (1) (see Fig. 5). In that case, closed-loop can be broken yielding to the model in Fig. 10. (7) Then, from (7), is obtained (8) EGIDO et al.: MAXIMUM FREQUENCY DEVIATION CALCULATION IN SMALL ISOLATED POWER SYSTEMS 1735 Minimum is found solving the following: (11) and, taking into account (1), is obtained: (12) Substituting (12) in (10), maximum frequency deviation is found: (13) and minimum frequency in Hz is (14) Fig. 11. Proposed equivalent model of the power system to analyze the frequency behavior. where is the pre-disturbance system frequency and system base frequency. Had all the units the same averaged ramp gain, , minimum frequency in Hz would be is the (15) are preferred If the ramp gains in per unit of the group instead of the ramp gains in per unit of the system, , then (16) Substituting (16) in (14) and (15): (17) Fig. 12. C =K ratio as a function of t =T . and, if In Fig. 12, the ratio in function of a sensible range of using (8) is shown. Therefore, . IV. CALCULATION OF THE MINIMUM FREQUENCY From the model in Fig. 11, frequency deviation evolution is given by the following: (9) (18) from (8) is chosen as the value for , all ramp If gains can be calculated substituting (12) into (8) and solving equation system ( and are the resulting nonlinear known): .. . Solving (9) in time yields (19) (10) 1736 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 24, NO. 4, NOVEMBER 2009 TABLE I GENERATING UNIT DATA Fig. 13. Single line diagram of the power system. Solution of (19) can be found easily and fast enough using any iterative numerical method. However, an additional simplification can be made with some loss of accuracy. Assuming a for the system analyzed from expertise, a typical value of sensible value of can be obtained from (8) or Fig. 12. Thus, the minimum frequency for a specific perturbation can be obin tained directly from (14). For example, a typical value for . For the diesel unit the Spanish isolated systems is of 9.4 MVA of Fig. 7, , . If in the system, then and . Using could be a good tradeoff. Surprisingly, from (13), maximum frequency deviation seems . Mainly, this fact comes not to depend on system inertia, from (6), where it is assumed that the rate of change of output power is proportional to the rate of change of frequency. This is true to a certain extent, but it is really a simplification. Note are calculated from (19), then depends on that if and and depends on . is necesTo calculate maximum deviation from (13), is sary. If this calculation is to be performed offline, then directly the tripped power to be analyzed. If this calculation is to be performed online (for an adaptive shedding scheme, for exhas to be estimated from (1) by an estimation ample), then algorithm using frequency measurements—for instance, using the procedure and the Newton-type algorithm proposed in [8]. TABLE II VALLEY AND PEAK DEMAND SCENARIOS V. SIMULATION RESULTS Simulations have been carried out on several Spanish isolated power systems. This paper shows the results for an isolated system within the Canary Islands power system. This system consists of 19 diesel units and four gas turbine units adding up to 480 MVA. A simplified power system model for a peak scenario is depicted in Fig. 13. PSS/E model, inertia, rated power, and first-order model associated for 4 s fitting are presented in Table I. Simulations have been carried out on valley demand (three contingences) and peak (four contingences) scenarios, where no limits are reached. These scenarios are summarized in Table II. As an example, simulation results of the detailed model for a 18-MW unit trip in the valley scenario are shown in Fig. 14, , generator output , and dewhere system frequency are presented. Maximum frequency deviation yields mand is 2.98 s. On the other hand, 1110 mHz (0.0222 ) and using the simplified proposed model [using (19)], maximum freand is 2.45 s. quency deviation yields 970 mHz (0.0194 Note that generator tripping is equivalent to consider and that and have to be the ones after the disturbance. These results and others obtained for the seven contingences analyzed are summarized in Table III. Although load variation with voltage and frequency is not taken into account in the proposed model, the accuracy achieved in calculated system minimum frequency is very sensible for all cases. Results depend on the values of and of each generator. and are obtained using As explained in Section III-A, a minimum squared-error fitting for a given fitting time (in EGIDO et al.: MAXIMUM FREQUENCY DEVIATION CALCULATION IN SMALL ISOLATED POWER SYSTEMS 1737 Programming and computational effort to calculate maximum frequency deviation using this model is affordable using a simple PC with very short calculation time, which allows them to be performed even online if needed. The computational speed and accuracy obtained will help to provide adaptive adjustments or limitations in normal operation to frequency relays, spinning reserve, load reconnection, or wind generation, among others, in isolated power systems. This model has been used by the Spanish System Operator to assess all these issues in some of the Spanish islands power systems. Based on this model, new adaptive load shedding methods can be developed. REFERENCES Fig. 14. Simulation results for valley demand scenario in case a 18-MW unit tripping. TABLE III SIMULATION RESULTS FOR VALLEY AND PEAK DEMAND SCENARIOS TABLE IV MINIMUM FREQUENCY CALCULATED FOR DIFFERENT MODELS Section III-A, 4 s was used). In order to analyze the sensitiveness of minimum frequency calculation with the selection of the fitting time, minimum frequency calculated for parameters and estimated with different fitting times are presented in Table IV. Simulation times of 3 s, 4 s, and 5 s have been selected as reasonable values. As can be seen in the table, minimum frequency is nearly the same in the three cases. VI. CONCLUSION In this paper, a novel simple model to estimate maximum frequency deviations in small isolated power systems when generation or load related perturbations take place is presented. This model takes into account the regulation speed of spinning reserve even when different generation technologies with very different governors are present in the power system. Regulator closed-loops are opened and substituted by simple ramp gains, making the model simpler and calculations faster. The simple procedure to obtain model parameters from a more complex model or from real data has been presented. Detailed simulations have been conducted proving that the accuracy of the proposed model is very sensible. [1] R. M. Maliszewski, R. D. Dunlop, and G. L. Wilson, “Frequency actuated load shedding and restoration. I. Philosophy,” IEEE Trans. Power App. Syst., vol. PAS-90, no. 4, pp. 1452–1459, Jul.–Aug. 1971. [2] P. Kundur, Power System Stability and Control. New York: McGrawHill, 1994. [3] C. Concordia, L. H. Fink, and G. Poullikkas, “Load shedding on an isolated system,” IEEE Trans. Power Syst., vol. 10, pp. 1467–1472, 1995. [4] H. You, V. Vittal, and Z. Yang, “Self-healing in power systems: An approach using islanding and rate of frequency decline-based load shedding,” IEEE Trans. Power Syst., vol. 18, pp. 174–181, 2003. [5] P. M. Anderson and M. Mirheydar, “A low-order system frequency response model,” IEEE Trans. Power Syst., vol. 5, pp. 720–729, 1990. [6] P. M. Anderson and M. Mirheydar, “An adaptive method for setting underfrequency load shedding relays,” IEEE Trans. Power Syst., vol. 7, pp. 647–655, 1992. [7] S. J. Huang and C. C. Huang, “An adaptive load shedding method with time-based design for isolated power systems,” Int. J. Elect. Power Energy Syst., vol. 22, pp. 51–58, 2000. [8] V. Terzija, “Adaptive underfrequency load shedding based on the magnitude of the disturbance,” IEEE Trans. Power Syst., vol. 21, pp. 1260–1266, 2006. [9] F. P. DeMello, “Boiler models for system dynamic performance studies,” IEEE Trans. Power Syst., vol. 6, pp. 66–74, 1991. [10] F. P. DeMello, “Dynamic models for fossil fueled steam units in power system studies,” IEEE Trans. Power Syst., vol. 6, pp. 753–761, 1991. [11] T. Inoue, H. Taniguchi, and Y. Ikeguchi, “A model of fossil fueled plant with once-through boiler for power system frequency simulation studies,” IEEE Trans. Power Syst., vol. 15, pp. 1322–1328, 2000. [12] IEEE Working Group on Prime Mover and Energy Supply Models for System Dynamic Performance Studies, “Hydraulic turbine and turbine control models for system dynamic studies,” IEEE Trans. Power Syst., vol. 7, pp. 167–179, 1992. [13] W. I. Rowen, “Simplified mathematical representations of heavy duty gas turbines,” Trans. ASME, J. Eng. Power, vol. 105, pp. 865–870, 1983. [14] F. P. DeMello and D. J. Ahner, “Dynamic models for combined cycle plants in power system studies,” IEEE Trans. Power Syst., vol. 9, pp. 1698–1708, 1994. [15] Q. Zhang and P. L. So, “Dynamic modelling of a combined cycle plant for power system stability studies,” in Proc. 2000 IEEE Power Engineering Society Winter Meeting, Singapore, 2000, pp. 1538–1543. [16] R. T. Byerly, O. Aanstad, D. H. Berry, R. D. Dunlop, D. N. Ewart, B. M. Fox, L. H. Johnson, and D. W. Tschappat, “Dynamic models for steam and hydro turbines in power system studies,” IEEE Trans. Power App. Syst., vol. PAS-92, pp. 1904–1915, 1973. [17] V. Kola, A. Bose, and P. M. Anderson, “Power plant models for operator training simulators,” IEEE Trans. Power Syst., vol. 4, pp. 559–565, 1989. [18] L. Pereira, D. Kosterev, D. Davies, and S. Patterson, “New thermal governor model selection and validation in the WECC,” IEEE Trans. Power Syst., vol. 19, no. 1, pp. 517–523, Feb. 2004. [19] L. Pereira, J. Undrill, D. Kosterev, D. Davies, and S. Patterson, “A new thermal governor modeling approach in the WECC,” IEEE Trans. Power Syst., vol. 18, no. 2, pp. 819–829, May 2003. [20] PSS/E-29 Online Documentation, Power Technologies, Inc., Oct. 2002. [21] M. S. Baldwin and H. S. Schenkel, “Determination of frequency decay rates during periods of generation deficiency,” IEEE Trans. Power App. Syst., vol. PAS-95, pp. 26–36, 1976. 1738 Ignacio Egido was born in Arévalo (Ávila), Spain, in 1976. He received the M.S. and Ph.D. degrees in electrical engineering from the Universidad Pontificia Comillas, Madrid, Spain, in 2000 and 2005, respectively. He is currently an Assistant Professor in the Department of Electrical Engineering of the School of Engineering of Universidad Pontificia Comillas. He develops his research activities at the Instituto de Investigación Tecnológica (IIT) of the same university, where he has been involved in a number of research projects related to AGC and power system stability. His interests include control system design and power systems stability and control. Fidel Fernández-Bernal was born in Madrid, Spain, in 1968. He received the B.S., M.S., and Ph.D. degrees in electrical engineering from the Universidad Pontificia Comillas de Madrid in 1990, 1994, and 2000, respectively. From 1988 to 1992, he was working as a Programmer and System Manager in a number of software companies. From 1990 to 2000, he was a Lecturer at the Universidad Pontificia Comillas de Madrid. He is an Associate Professor in the Department of Electrical Engineering of the School of Engineering of Universidad Pontificia Comillas. He develops his research activities at Instituto de Investigación Tecnologica (IIT) of the same university. Dr. Fernández-Bernal was the recipient of the “Best B.S. degree in Electrical Engineering in Spain in 1990” Award and the “Honorable Mention” for his M.S. degree. IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 24, NO. 4, NOVEMBER 2009 Pablo Centeno was born in Madrid, Spain, in 1973. He received the M.S. degree in electrical engineering from Universidad Pontificia Comillas de Madrid in 1998. From 2000 to 2005, he worked as an Assistant Researcher at the Instituto de Investigación Tecnológica (IIT), Universidad Pontificia Comillas, where he carried out several projects involving steady-state and stability studies including design of load shedding schemes of the Spanish isolated power systems. From 2005 to 2007, he was with Red Eléctrica de España (REE), the Spanish TSO. During this period, he also worked as a part-time Lecturer at Universidad Pontifica Comillas. In 2007, he joined Alstom Power Systems, Baden, Switzerland, as a Senior Electrical Engineer. His areas of interest are modeling, analysis, and simulation of power systems. Luis Rouco (S’89–M’91) received the Ingeniero Industrial and Doctor Ingeniero Industrial degrees from Universidad Politécnica de Madrid, Madrid, Spain, in 1985 and 1990, respectively. He is a Professor of electrical engineering in the School of Engineering of Universidad Pontificia Comillas, Madrid, attached to the Department of Electrical Engineering. He served as Director of the Department of Electrical Engineering from 1999 to 2005. He develops his research activities at Instituto de Investigación Tecnologica (IIT) of the same university, where he has supervised more than 100 research and consultancy projects for Spanish and foreign companies. He has published more than 70 papers in conferences and journals. He has been a visiting researcher at Ontario Hydro, Toronto, ON, Canada; the Massachusetts Institute of Technology, Cambridge; and ABB Power Systems, Vasteras, Sweden. His areas of interest are modeling, analysis, simulation, and identification of electric power systems. Prof. Rouco is a member of Cigré, the Vice-President of the Spanish Chapter of the IEEE Power Engineering Society, and a member of the Executive Committee of Spanish National Committee of Cigré.