11-TMSS-02, Rev. 02 - 1x1200 CWS (261) mm2 - 110 kV

advertisement
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110kV CWS IEC 60840
Cable ID: 33010015
TRANSMISSION MATERIALS STANDARD SPECIFICATION
11-TMSS-02, Rev.02
7.0 DATA SCHEDULE
7.1
110kV/115kV/132kV, XLPE POWER CABLE (1200,2000,2500 mm²)
National Grid SA Enquiry
No.
Date:
National Grid SA Purchase
Order No.
or Contract No.
Date:
National Grid SA PTS No./Project Title with
J.O. No.
REFERENCE
SECTION NO.
3.0
DESCRIPTION
'B'
'C'
APPLICABLE CODES AND STANDARDS
AEIC CS9/IEC
60840
Reference Manufacturing Standard
4.0
DESIGN AND CONSTRUCTION REQUIREMENTS
4.1
Design Criteria/Rating
4.2
4.3
4.3.1
'A'
'B'
'C'
(*)
'A'
a. Cable Nominal Voltage, kV
b. System Short Circuit Current, kA
c. Maximum conductor short circuit current
temperature, °C
d. Normal Continuous Loading
x Maximum permissible continuous
conductor temperature, °C
x Permissible Load in Amps, A
e. Emergency Loading
x Maximum emergency conductor loading
temp,°C
x Permissible Load in Amps, A
x Allowable loading duration; hrs
110/115/132
40
110
40
250
250
90
90
*
873*
i) During any 12 months
ii) During the life of the cable
72
2160
72
2160
Copper
Copper
Material Details :
Conductor :
Material
-
AEIC CS9/IEC
60840
105
*
105
1682**
NATIONAL GRID SA SPECIFIED DATA/PARAMETERS
BIDDER/SUPPLIER/VENDOR/CONTRACTOR PROPOSED DATA/PARAMETERS
REMARKS SUPPORTING THE PROPOSED DEVIATION IN COLUMN 'B'
R/
DATA/PARAMETER TO BE PROVIDED/PROPOSED BY THE BIDDER/SUPPLIER/ VENDOR
CONTRACTOR IN COLUMN 'B'
11TMSS02R02/HKG
Date of Approval: January 02, 2018
License=Bahra Cable Company/SA-823-t Not For Resale ,2/8/2018 10:32:00 AM Saudi Time
PAGE NO. 19 OF 42
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110kV CWS IEC 60840
Cable ID: 33010015
TRANSMISSION MATERIALS STANDARD SPECIFICATION
11-TMSS-02, Rev.02
7.0 DATA SCHEDULE
7.1
110kV/115kV/132kV, XLPE POWER CABLE (1200,2000,2500 mm²)
REFERENCE
SECTION NO.
DESCRIPTION
'A'
'B'
Conductor for stranding
(Segmental)
*
Segmental
No. of strands
*
> 55
Dia. of strand prior to compaction, mm
*
2.36
Cross-sectional area, mm²
(1200, 2000 or 2500)
Per segment
1200
Maximum Diameter, mm
1200 mm²: 45.0
2000 mm²: 56.0
2500 mm²: 62.0
43.4
%HIRUHWDSHV
Resistance at 25°C, :/km
*
0.01540
DC resistance
Conductor AC resistance at 20°C
*
0.01968
trefoil formation
Conductor DC resistance at 20°C
*
0.01510
Temp. coefficient at 20°C/°C
*
0.00393
Skin effect loss factor (ks)
*
0.8
Proximity effect loss factor (kU)
*
0.37
DC resistance at 90°C, :/km
*
0.01925
Short circuit capability of conductor in kA for
1 second starting with 90°C conductor temperature
up to max. short circuit current temperature
40
40
*
yes
Water blocking material between strands
Conductor Moisture Impervious layer Material
4.3.2
'C'
Conductor shield:
Material
Average thickness, mm
1200, 2000, 2500 mm²
Minimum thickness, mm
1200, 2000, 2500 mm²
Dia. over conductor shield, mm
Thermal resistivity, K.m/W
11TMSS02R02/HKG
Semi-Conducting
Tape
Semi-Conducting
Tape
SEMICON
SEMICON
1.50
1.5
1.35
1.35
*
*
Date of Approval: January 02, 2018
License=Bahra Cable Company/SA-823-t Not For Resale ,2/8/2018 10:32:00 AM Saudi Time
49.04
2.5
approx.
PAGE NO. 20 OF 42
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110kV CWS IEC 60840
Cable ID: 33010015
TRANSMISSION MATERIALS STANDARD SPECIFICATION
11-TMSS-02, Rev.02
7.0 DATA SCHEDULE
7.1
REFERENCE
SECTION NO.
4.3.3
110kV/115kV/132kV, XLPE POWER CABLE (1200,2000,2500 mm²)
DESCRIPTION
'A'
Insulation:
Material
Nominal thickness , mm
Minimum thickness, mm
Diameter over insulation, mm
Thermal resistivity, K.m/W
Relative permittivity or
dielectric constant (H)
Loss factor (G )
Specific Resistance, M:-km
(Actual Test Value)
4.3.4
4.3.5
Insulation shield:
Material
Average thickness, mm
Minimumn thickness, mm
Diameter over insulation shield, mm
Thermal resistivity, K.m/W
'B'
'C'
SUPER CLEAN
XLPE
18.0
16.2
*
*
SUPER CLEAN
XLPE
18.0
*
2.5
*
0.001
16.2
85.04
3.5
*
as per IEC
60840
SEMICON
1.50
1.35
*
*
SEMICON
approx.
1.5
1.35
approx.
88.04
2.5
ƒ Copper wire + Copper tape
ƒ Lead Sheath
Copper wire +
ƒ Combination of Copper wire +
Open helix Copper tape
Copper tape and Lead Sheath.
ƒ Smooth Aluminum Sheath
Metallic shield:
Material
Total effective cross-sectional area mm²
ƒ Copper wire + Copper tape: 261
mm² (CUW only)
ƒ Lead Sheath, Combination of
Copper wire + Copper tape and
Lead Sheath & Smooth Aluminum
Sheath: based on short circuit
261 mm2
calculations
Diameter over metallic shield, mm
Temp. coefficient at 20°C,/°C
DC resistance at 20°C, :/km
AC resistance at 20°C :/km
Self inductance, mH/km
AC resistance at 90°C
DC resistance at 90°C
Resistivity at 20°C
Short circuit capability in kA for 1 second of the
metallic shield starting with 90°C conductor
temperature:
11TMSS02R02/HKG
*
*
*
*
*
40
Date of Approval: January 02, 2018
License=Bahra Cable Company/SA-823-t Not For Resale ,2/8/2018 10:32:00 AM Saudi Time
93.6
approx.
0.00393
0.0694
0.0694
Trefoil Formation
0.166
0.0885
0.0885
1.7241 e-8
Ohm.m
40
Conductor Initial temp. = 90 deg.C
Conductor Final temp. = 250 deg.C
PAGE
E NO.
NO 21
21 OF
OF 4
42
2
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110kV CWS IEC 60840
Cable ID: 33010015
TRANSMISSION MATERIALS STANDARD SPECIFICATION
11-TMSS-02, Rev.02
7.0 DATA SCHEDULE
7.1
REFERENCE
SECTION NO.
4.3.6
110kV/115kV/132kV, XLPE POWER CABLE (1200,2000,2500 mm²)
DESCRIPTION
Moisture impervious layer (first layer):
Material
Thickness, mm
Diameter over the layer, mm
5.4
6.0
SEMI-CONDUCTIVE
SWELLING TAPE
'B'
Yes/No
Yes
Jacket:
Material
Nominal thickness, mm
Minimum thickness, mm
Overall cable diameter, mm
HDPE
4.50
4.05
*
HDPE
4.5
Special Thermal Short Circuit Test
Special By-Product of XLPE
Special Test for Smooth Aluminum Sheath
Yes
Yes
Yes/No
approx.
SEMI-CONDUCTIVE
SWELLING TAPE
Third Moisture impervious layer
*
*
%HIRUHDSSOLFDWLRQ
0.25
89.2
0.25
94.7
Conductive layer :
Material
Thickness, mm
'C'
SEMI-CONDUCTIVE
SWELLING TAPE
0.25
*
Thickness, mm
Diameter over the layer, mm
4.3.8
SEMI-CONDUCTIVE
SWELLING TAPE
0.25
*
Moisture impervious layer (second layer):
Material
4.3.7
'A'
%HIRUHDSSOLFDWLRQ
approx.
Laminated Aluminum
tape (LAT)
4.05
104.8
approx.
Graphite Coating
0.01
Yes
Yes
NA
PACKING
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
Total quantity required, m
Are matched sets of cable reel length
required?
If "YES", how many reels are
required per set?
Tolerance in cable length of
matched reel sets
Conductor weight, kg/km
Cable weight, kg/km
Reel and cable weight, kg
Cable length per reel, m
Cable reel diameter, mm
Cable reel width, mm
11TMSS02R02/HKG
*
*
*
*
*
*
Date of Approval: January 02, 2018
License=Bahra Cable Company/SA-823-t Not For Resale ,2/8/2018 10:32:00 AM Saudi Time
10500
19125
10920
500
3200
2060
(+/-) 2 %
approx.
approx.
(+/-) 5 %
PAGE NO. 22 OF 42
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110kV CWS IEC 60840
Cable ID: 33010015
TRANSMISSION MATERIALS STANDARD SPECIFICATION
11-TMSS-02, Rev.02
7.0 DATA SCHEDULE
7.1
REFERENCE
SECTION NO.
110kV/115kV/132kV, XLPE POWER CABLE (1200,2000,2500 mm²)
DESCRIPTION
'A'
'B'
'C'
OTHER REQUIRED INFORMATION
Over 30
Over 30
a.
Life expectancy of cable, years
b.
3-phase inductance in trefoil/ flat formation,
mH/km
*
0.366
c.
3phase capacitance in trefoil/ flat formation
PF/km
*
0.252
d.
Maximum permissible overload in % of 3
cables in underground cable duct trefoil/
flat formation, at 40°C soil temperature,
for
1/2/3(I1-hour/I2-hours/I3-hours)
hours
starting with a prior loading of
I1-hour/ I2-hours/
I3-hours
*
50%
75%
100%
7UHIRLO)RUPDWLRQ
I1-hour/ I2-hours/
I3-hours
2757 // 2220
/ / 1973
/
/
2380 / 1938 / 1746
1682 / 1440 / 1340
60
e.
Maximum pulling Tension (kN)
*
f.
Maximum sidewall pressure, kN/m
*
28.64
g.
Minimum bending radius, mm
*
2095
Cable Marking will be as following in two lines:
BAHRA CABLES CO. KSA 1X1200/261 MM2 CU 110 KV ELECTRIC CABLE
PROPERTY OF SAUDI ELECTRICITY COMPANY MANUFACTURING YEAR
XLPE 18 MM
0p]a` y+sM5` \ʁ` ;(
* The Current was calculated based on TES-P-104.05 R0, Fig 05-03 but installed in ducts and the
following installation conditions:
1. Ground temperature = 40 deg. C.
2. Burial depth = 1.5 m.
3. Soil thermal resistivity = 2 k.m/w.
4. Backfill thermal resistivity = 1.2 k.m/w.
5. Duct Inner/Outer diameter = 154.1/168.3 mm.
6. The cable bonding type is cross bonding.
7. The Space between phases = 300 mm
** The Emergency Current was calculated based on the following:
1. before overloading the current was 873 A, based on the above mention installation conditions.
2. the overloading time assumed to be 1 hour.
3. the emergency temperature = 105 deg.C
11TMSS02R02/HKG
Date of Approval: January 02, 2018
License=Bahra Cable Company/SA-823-t Not For Resale ,2/8/2018 10:32:00 AM Saudi Time
PAGE NO. 23 OF 42
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110kV CWS IEC 60840
Cable ID: 33010015
TRANSMISSION MATERIALS STANDARD SPECIFICATION
7.0
7.1
A.
11-TMSS-02, Rev.02
DATA SCHEDULE
110kV/115kV/132kV, XLPE POWER CABLE (1200,2000,2500 mm²)
ADDITIONAL TECHNICAL INFORMATION OR FEATURES TO BE FURNISHED BY NATIONAL
GRID SA:
NIL
B.
ADDITIONAL
SUPPLEMENTARY
DATA
BIDDER/VENDOR/SUPPLIER/CONTRACTOR:
OR
FEATURES
PROPOSED
BY
NIL
C.
OTHER PARTICULARS TO BE FILLED UP BY BIDDER/VENDOR/SUPPLIER/ CONTRACTOR:
NIL
Actual Manufacturer
of Equipment/Material
Name of the Company
Location and address
Name and Signature of
authorized representative
and date
Vendor/Supplier/
Contractor
BAHRA CABLES COMPANY
Bahra, Jeddah, KSA
Lotfy Mohamed Idrees
Technology Manager - Technology Dept.
Official Seal/Stamp
of the Company & Date
11TMSS02R02/HKG
Date of Approval: January 02, 2018
License=Bahra Cable Company/SA-823-t Not For Resale ,2/8/2018 10:32:00 AM Saudi Time
PAGE NO. 24 OF 42
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110kV CWS IEC 60840
Cable ID: 33010015
TECHNOLOGY DEPARTMENT
110 kV, XLPE Power Cable
Normal Continuous Loading
Maximum Permissible Load in Amps
At Maximum Permissible Continuous Conductor Temperature, 90 °C
Cable Type
Description
Installation
Conditions
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110 kV CWS IEC 60840
Single Circuit installed in ducts buried underground in backfill and flat
formation
*. The current was calculated based on TES-P-104.05 R0, Same as Fig 05-03
but laid in ducts and the following installation conditions:
1. Ground temperature = 40 °C.
2. Burial depth = 1.5 m.
3. Soil thermal resistivity = 2 k.m/w.
4. Backfill thermal resistivity = 1.2 k.m/w.
5. The cable bonding type is cross bonding.
6. The space between phases = 300 mm.
7. Duct inner/outer diameter = 154.1/168.3 mm.
8. The dimension of the trench: (width = 1.0 m , height = 1.7 m)
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110kV CWS IEC 60840
TRANSMISSION MATERIALS STANDARD SPECIFICATION
Cable ID: 33010015
11-TMSS-02, Rev.02
7.0 DATA SCHEDULE
110kV/115kV/132kV, XLPE POWER CABLE (1200, 2000, 2500 mm2)
Cable Drawing
1
2
3
4
5
6
7
8
9
Description
Cu / XLPE / LAT / HDPE 1X1200/261 mm2 110 kV CWS IEC 60840
Diameters
Parameter
“Approximate”
1
Copper conductor segmental, Watertight
2
Extruded inner semi conductive layer (Bonded)
49.04
3
Extruded XLPE insulation
85.04
4
Extruded outer semi conductive layer (Bonded)
88.04
5
Semi-conductive water blocking tape
89.2
6
Copper wires screen + open helix copper tape
93.6
7
Semi-conductive water blocking tape
94.7
8
Laminated Aluminium Tape (AL Foil)
95.6
9
HDPE Outer Sheathing Black + Graphite Coating
104.8
11TMSS02R02/HKG
Date of Approval: January 02, 2018
43.4 “Before Tapes”
Cable Drawing