Form – 4 SECONDARY WIRE COMPUTATION FOR T – 1 KVA SSPAN RIGHT SIDE To determine the size of the wire of the secondary lines, assume V drop = 5% of the operating voltage for no. of the span for 1ᴓ, 2 wire system. From P–1 to P – 2 I = Load KVA / 230 :Total load = 35.5270 = Distance = Total Load KVA: Refer to table: CM= span, 11 volts, assume voltage drop at 5% Total Maximum Demand of Transformer Bank KVA Rating of Transformer Refer to table: Actual DC Voltage Drop, 50 °C, 60 Hz, 8ʺ spacing. R= 1.89 Ω / mile 𝑿 𝑹 = Xa= 0.145 Ω / mile Xa + 9-0.049) R Actual DC Voltage Drop = (24 x d x I)/CM Actual Voltage Drop factor at 0.85 p.f. = Voltage Regulation = ADV x df 𝑥 230 100 Use ________, Hard Drawn Copper Conductor Xsf= 0.628 Ω / mile