Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) Design Basis of Fire Fighting Systems. • Design of Fire Hydrant System. • Design of Fire Deluge System. • Design of Beam Detection System. Prepared By: Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) Table of Contents 1- SCOPE OF DESIGN ..................................................................................................................... 1 2- CODES & STANDARDS FOLLOWED ........................................................................................... 1 3- MAIN DESIGN PRINCIPLE .......................................................................................................... 2 4- FIRE WATER & PUMP DEMAND CALCULATIONS………………………………………………………………….3 Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) 1- SCOPE OF DESIGN This document defines the Design Basis for Fire Water system and water deluge system used for the following purposes: • Design of Fire Hydrant System. • Design of Fire Deluge System. • Design of Beam Detection System. 2- CODES & STANDARDS FOLLOWED 1) Main Yard and Outdoor Fire Hydrants System NFPA - 24 & 26 2) Water Monitors System NFPA - 11 3) Deluge fire Protection System NFPA - 13 & 15 4) Piping & Hose System NFPA - 14(1961 -62 edition) 5) Fixed Water Spray System NFPA - 15 6) Automatic Fire Detection System NFPA - 72(A-E) 7) Water Supply System NFPA - 13,15,20&22 8) Fire Pumps NFPA - 13 & 20 The fire protection system design will be adequate for the site conditions, to provide a high degree of protection to the plant, equipment's, buildings and employees. Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) 3- MAIN DESIGN PRINCIPLE According to NFPA, the firefighting measures for building and equipment in the plant is as mentioned in Table 3-1 below: Table 3-1 List of Building & Structure Sr. Description a b 1 External Buildings of the Plant 2 Internal Areas of the Plant √ 3 Warehouse √ c d √ √ √ Note: a. Fire Hydrant b. Fire Hose Reel c. Fire Detection System d. Fire Water Deluge System 2 Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) 4- FIRE FIGHTING WATER & PUMP DEMAND CALCULATION The source of water for the Fire Water Systems will be the proposed underground water storage with proposed automatic water make-up line for level control. Water supply Detail are as under according to the Fire Scenarios: FIRE SCENARIO (1): 2 Fire Monitor, 1 HOSE REEL and 180 DELUGE NOZZLES ARE OPERATING. D E N S IT Y M A X IM U M C O V E R A G E A R E A PUM P DEM AND D IS C H A R G IN G S P R IN K LE R M A X IM U M S P A C IN G S IN G LE S P R IN K LE R R E Q U IR E D F LO W A D D IT IO N F LO W A LLO W A N C E 2 M O N IT O R + 1 H O S E T O T A L P U M P R E Q U IR E D W A T E R R E S E R V IO R R E Q U IR E D 0.6 6400 3874 180 6 21.52222 565 4439 266340 G P M /S Q FT 24.6 L/M IN M S Q S Q FT G PM N os S Q .FT G PM 81.48 L/M G PM G PM U S G A LLO N S FIRE SCENARIO (2): 2 Fire Monitor, 1 HOSE REEL and all 720 DELUGE NOZZLES ARE OPERATING. D E N S IT Y M A X IM U M C O V E R A G E A R E A PUM P DEM AND D IS C H A R G IN G S P R IN K LE R M A X IM U M S P A C IN G S IN G LE S P R IN K LE R R E Q U IR E D F LO W A D D IT IO N F LO W A LLO W A N C E 2 M O N IT O R + 1 H O S E T O T A L P U M P R E Q U IR E D W A T E R R E S E R V IO R R E Q U IR E D 0.6 6400 15496 720 6 21.52222 565 16061 963660 G P M /S Q FT 24.6 L/M IN M S Q S Q FT G PM N os S Q .FT G PM 81.48 L/M G PM G PM U S G A LLO N S 3 Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) 5- REQUIRED FIRE PUMP SPECIFICATIONS FIRE SCENARIO (1): 2 Fire Monitor, 1 HOSE REEL and 180 DELUGE NOZZLES ARE OPERATING. Flow Head Quantity (GPM) (m) (set) ELECTRIC FIRE PUMP 4500 15.3-Bar 1 DIESEL FIRE PUMP 4500 15.3-Bar 1 JOCKEY FIRE PUMP 300 16.3-Bar 1 Pump Type • • • Electric Driven Fire Water Jockey Pump ( 01 No ) o Flow= 68.1 m3/hr. , Head= 16.3 Bar Electric Driven Fire Water Pump ( 01 No ) o Flow= 1022 m3/hr., Head= 15.3 Bar Diesel Driven Fire Water Pump ( 01 No ) o Flow= 1022 m3/hr., Head= 15.3 Bar Above 03 x pumps have auto start & stop sequence as per NFPA through pressure switches installed on main fire water header. During normal scenario electric driven Jockey Pump maintains the main header pressure. 4 Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) FIRE HYDRANT SYSTEM 5 FH -1 0 FHD FHD 201烟火药 制造及曳光 钢芯压药工 房 FHD 202枪弹 装配及弹 头装配工 房 FHD Hosereel Cabinet FH -1 2 箱变 FHD 6 Hydrants = 33 Nos FHD 5 FH -4 FH -1 FHD 废水处理池 FHD FH - FH FHD FH - FHD FH -7 FH -1 1 FHD FH -9 FHD FH -8 3 -1 FH Pipe 300mm -1 5 4 301 Pipe 250mm FH -1 8 FHD Pipe 200 mm 原有靶场 FH 2 -1 熔 压 6 -1 9 工 房 -1 7 -3 Pipe 100mm FH 铅 FH -2 8 FH FHD FH 47 10 FHD FH - Pipe 150mm Auto Targeting Fire Water Monitor = 2Nos 0 FH -3 1 W REQ AT U E I U FO S 516 R T RED OF R GA ,0 A FI 60 LLO00 NK RE M N FI INU S GH T TI ES NG FHD FH -4 5 10 FH -2 1 3 FH 枪 弹 27 FHD Manual Fire Water Monitor = 7 Nos -2 2 零 件 制 Gate Valve 造 工 FH 房 3 FHD FH -4 4 -2 0 FH -3 1 FH - -3 Automatic Fire Water Monitor = 5 Nos FH FHD 6 FHD PU 86 MP G P 00 M FH -3 2 FHD FH - -4 FHD PUMP CAPACITY 8,600 GPM FOR FIRE HYDRANT & DELUGE SYSTEM FHD FH FHD 2F FH FH -2 -2 1 6 FH -2 9 FH -3 9 FHD FHD FH -3 4 FH -2 5 FHD FH -2 FH FHD -3 5 -2 4 FIRE HYDRANT SYSTEM FHD FH -4 3 Title: FH Client: FH -3 FH FHD -3 FHD 0 FH FHD 1 -4 FHD FHD FH -4 7 FH - 38 FH -4 6 Contractor: 2 Date: Ref. No. Designed by: Scale: Naqash Kazmi 1:1 Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) FIRE DELUGE SYSTEM 6 Naqash Kazmi (CFPS®) NFPA CERTIFIED FIRE PROTECTION SPECIALIST(CFPS®) BEAM DETECTION SYSTEM 7