Uploaded by GAMAL YEHIA

C18 Generator Set Diagnostic Trouble Code List

advertisement
C18 Generator Set
(SEBP5558
- 16) - Documentation
Page 1 of 21
Shutdown SIS
Previous Screen
Product: GENERATOR SET
Model: C18 GENERATOR SET
Configuration: C18 Generator Set
Troubleshooting
EMCP3
Media Number -RENR7902-12
Publication Date -01/05/2014
Date Updated -07/05/2014
i06849520
Diagnostic Trouble Code List
SMCS - 7569
Reference: For a full explanation of the use of the enter function key that is referenced in this
section, refer to the Systems Operation, "Electronic Control Module (Generator Set)" section of
this publication.
Table 1 lists the diagnostic trouble codes for the genset. The column titled "Display Text String" is
the information that is displayed on the EMCP 3 control panel. In order to view the "Suspect
Parameter Number" (SPN) and the "Failure Mode Identifier" (FMI), press the "Enter" key while
viewing the "Display Text String".
If the diagnostic code was generated from the "Electronic Control Module" (ECM) for the engine,
refer to the Systems Operation, Testing and Adjusting manual for the particular engine. Perform
the diagnostic procedure as indicated by the SPN and FMI information.
If the diagnostic code is generated from the EMCP 3 ECM for the generator set, then refer to
Table 1 and refer to the information that is in the "Troubleshooting Topic" column.
Note: The "Emergency Shutdown Override Mode Active Warning" requires a level 3 password in
order to clear the code. All remaining listed codes require a level 1 password in order to clear the
code.
Portions of this material are reprinted with permission from SAE J1939DA_201607© 2016 SAE
International. SAE International is not responsible for any use or translation of this material, in
whole or in part. Please contact SAE International to obtain a complete copy of SAE
J1939DA_201607, the official definitive source of this standard.
Table 1
Trouble Codes
Suspect
Parameter
Number
(SPN)
Failure
Mode
Identifier
(FMI)
Code
Description
Display Text String
Troubleshooting
Topic
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
38
-(SEBP5558
Page 2 of 21
External Tank
High Fuel Level
Shutdown
EXT TANK HIGH
FUEL LEVEL
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
External Tank
Low Fuel Level
Shutdown
EXT TANK LOW
FUEL LEVEL
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
3
External Tank
Fuel Level
Sensor Short
High
EXT TANK FUEL
LEVEL SENSOR
SHORT HIGH
Analog Input Circuit
Fault
38
4
External Tank
Fuel Level
Sensor Short
Low
EXT TANK FUEL
LEVEL SENSOR
SHORT LOW
Analog Input Circuit
Fault
38
15
External Tank
High Fuel Level
Warning
EXT TANK HIGH
FUEL LVL
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
38
17
External Tank
Low Fuel Level
Warning
EXT TANK LOW
FUEL LVL
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
0
High Starting Air
Pressure
Shutdown
HIGH STARTING
AIR PRES
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
Low Starting Air
Pressure
Shutdown
LOW STARTING
AIR PRES
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
82
3
Starting Air
Pressure Sensor
Short High
STARTING AIR
PRES SENSOR
SHORT HIGH
Analog Input Circuit
Fault
82
4
Starting Air
Pressure Sensor
Short Low
STARTING AIR
PRES SENSOR
SHORT LOW
Analog Input Circuit
Fault
82
15
High Starting Air
Pressure
Warning
HIGH STARTING
AIR PRES
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
82
17
Low Starting Air
Pressure
Warning
LOW STARTING
AIR PRES
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
94
00
HIGH FUEL
high fuel pressure
PRESSURE
shutdown
SHUTDOWN
94
01
38
38
82
82
0
- 16) - Documentation
low fuel pressure
shutdown
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Page 3 of 21
LOW FUEL
PRESSURE
SHUTDOWN
15
HIGH FUEL
high fuel pressure
PRESSURE
warning
WARNING
16
HIGH FUEL
high fuel pressure
PRESSURE
derate
DERATE
94
17
low fuel pressure
warning
LOW FUEL
PRESSURE
WARNING
94
18
low fuel pressure
derate
LOW FUEL
PRESSURE
DERATE
0
High Fuel Filter
Differential
Pressure
Shutdown
HIGH FUEL FLTR
DIFF PRES
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
Low Fuel Filter
Differential
Pressure
Shutdown
LOW FUEL FILTER
DIFF PRES
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
3
Fuel Filter
Differential
Pressure Sensor
Short High
FUEL FLTER DIFF
PRES SENSOR
SHORT HIGH
Analog Input Circuit
Fault
4
Fuel Filter
Differential
Pressure Sensor
Short Low
FUEL FLTR DIFF
PRES SENSOR
SHORT LOW
Analog Input Circuit
Fault
15
High Fuel Filter
Differential
Pressure
Warning
HIGH FUEL FLTR
DIFF PRES
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
17
Low Fuel Filter
Differential
Pressure
Warning
LOW FUEL FILTER
DIFF PRES
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
96
0
High Fuel Level
Shutdown
HIGH FUEL LEVEL
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
96
1
Low Fuel Level
Shutdown
LOW FUEL LEVEL
SHUTDOWN
94
94
95
95
95
95
95
95
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Page 4 of 21
Digital Input Circuit
Fault and Analog
Input Circuit Fault
3
Fuel Level
Sensor Short
High
FUEL LEVEL
SENSOR SHORT
HIGH
Analog Input Circuit
Fault
4
Fuel Level
Sensor Short
Low
FUEL LEVEL
SENSOR SHORT
LOW
Analog Input Circuit
Fault
96
15
High Fuel Level
Warning
HIGH FUEL LEVEL
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
96
17
Low Fuel Level
Warning
LOW FUEL LEVEL
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
98
0
High Engine Oil
Level Shutdown
HIGH ENGINE OIL
LVL SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
98
1
Low Engine Oil
Level Shutdown
LOW ENGINE OIL
LVL SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
3
Engine Oil Level
Sensor Short
High
ENGINE OIL
LEVEL SENSOR
SHORT HIGH
Analog Input Circuit
Fault
98
4
Engine Oil Level
Sensor Short
Low
ENGINE OIL
LEVEL SENSOR
SHORT LOW
Analog Input Circuit
Fault
98
15
High Engine Oil
Level Warning
HIGH ENGINE OIL
LVL WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
98
17
Low Engine Oil
Level Warning
LOW ENGINE OIL
LVL WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
0
High Oil Filter
Differential
Pressure
Shutdown
HIGH OIL FILTER
DIFF PRES
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
99
1
Low Oil Filter
Differential
Pressure
Shutdown
LOW OIL FILTER
DIFF PRES
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
99
3
96
96
98
99
Oil Filter
Differential
Analog Input Circuit
Fault
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Pressure Sensor
Short High
Page 5 of 21
OIL FILTER DIFF
PRES SENSOR
SHORT HIGH
4
Oil Filter
Differential
Pressure Sensor
Short Low
OIL FILTER DIFF
PRES SENSOR
SHORT LOW
Analog Input Circuit
Fault
15
High Oil Filter
Differential
Pressure
Warning
HIGH OIL FILTER
DIFF PRES
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
17
Low Oil Filter
Differential
Pressure
Warning
LOW OIL FILTER
DIFF PRES
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
Low Engine Oil
Pressure
Shutdown
LOW ENGINE OIL
PRESS
SHUTDOWN
Data Link circuit
Fault and Digital
Input Circuit Fault
100
3
Engine Oil
Pressure Sensor
Short High
ENG OIL PRES
SENSOR SHORT
HIGH
100
4
Engine Oil
Pressure Sensor
Short Low
ENG OIL PRES
SENSOR SHORT
LOW
100
17
Low Engine Oil
Pressure
Warning
LOW ENGINE OIL
PRESS WARNING
Data Link circuit
Fault and Digital
Input Circuit Fault
0
High Air Filter
Differential
Pressure
Shutdown
HIGH AIR FILTER
DIFF PRES
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
Low Air Filter
Differential
Pressure
Shutdown
LOW AIR FILTER
DIFF PRES
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
3
Air Filter
Differential
Pressure Sensor
Short High
AIR FILTER DIFF
PRES SENSOR
SHORT HIGH
Analog Input Circuit
Fault
107
4
Air Filter
Differential
Pressure Sensor
Short Low
AIR FILTER DIFF
PRES SENSOR
SHORT LOW
Analog Input Circuit
Fault
107
15
99
99
99
100
107
107
107
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
High Air Filter
Differential
Pressure
Warning
Page 6 of 21
HIGH AIR FILTER
DIFF PRES
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
17
Low Air Filter
Differential
Pressure
Warning
LOW AIR FILTER
DIFF PRES
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
0
High Engine
Coolant
Temperature
Shutdown
HIGH ENGINE
COOLANT TEMP
SHUTDOWN
Data Link Circuit
Fault and Digital
Input Circuit Fault
3
Engine Coolant
Temperature
Sensor Short
High
ENG COOLANT
TEMP SENSOR
SHORT HI
4
Engine Coolant
Temperature
Sensor Short
Low
ENG COOLANT
TEMP SENSOR
SHORT LO
15
High Engine
Coolant
Temperature
Warning
HIGH ENGINE
COOLANT TEMP
WARNING
Data Link Circuit
Fault and Digital
Input Circuit Fault
110
17
Low Engine
Coolant
Temperature
Warning
LOW COOLANT
TEMP WARNING
Data Link Circuit
Fault and Digital
Input Circuit Fault
111
0
High Engine
Coolant Level
Shutdown
HIGH ENG COOL
LEVEL
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
Low Engine
Coolant Level
Shutdown
LOW ENG COOL
LEVEL
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
111
3
Engine Coolant
Level Sensor
Short High
ENGINE COOLANT
Analog Input Circuit
LEVEL SENSOR
Fault
SHORT HIGH
111
4
Engine Coolant
Level Sensor
Short Low
ENGINE COOLANT
Analog Input Circuit
LEVEL SENSOR
Fault
SHORT LOW
111
15
High Engine
Coolant Level
Warning
HIGH ENG COOL
LEVEL WARNING
111
17
107
110
110
110
110
111
Digital Input Circuit
Fault and Analog
Input Circuit Fault
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Low Engine
Coolant Level
Warning
LOW ENG COOL
LEVEL WARNING
Page 7 of 21
Digital Input Circuit
Fault and Analog
Input Circuit Fault
0
High Fire
Extinguisher
Pressure
Shutdown
HIGH FIRE EXTNG
PRES SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
137
1
Low Fire
Extinguisher
Pressure
Shutdown
LOW FIRE EXTNG
PRES SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
137
3
Fire Extinguisher
Pressure Sensor
Short High
FIRE EXTING PRES
Analog Input Circuit
SENSOR SHORT
Fault
HIGH
137
4
Fire Extinguisher
Pressure Sensor
Short Low
FIRE EXTNG PRES
SENSOR SHORT
LOW
Analog Input Circuit
Fault
15
High Fire
Extinguisher
Pressure
Warning
HIGH FIRE EXTNG
PRES WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
17
Low Fire
Extinguisher
Pressure
Warning
LOW FIRE EXTNG
PRES WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
167
17
Low Battery
Charging System
Voltage Warning
LOW BATTERY
CHARGING SYS
VOLT WARN
Charging System
168
0
High Battery
Voltage
Shutdown
HIGH BATTERY
VOLTAGE
SHUTDOWN
Charging System
168
15
High Battery
Voltage Warning
HIGH BATTERY
VOLTAGE
WARNING
Charging System
168
17
Low Battery
Voltage Warning
LOW BATTERY
VOLTAGE
WARNING
Charging System
0
High Ambient
Air Temperature
Shutdown
HIGH AMBIENT
AIR TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
Low Ambient Air LOW AMBIENT
Temperature
AIR TEMP
Shutdown
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
137
137
137
171
171
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
171
-(SEBP5558
3
- 16) - Documentation
Ambient Air
Temperature
Sensor Short
High
AMBIENT AIR
TEMP SENSOR
SHORT HIGH
Page 8 of 21
Analog Input Circuit
Fault
4
Ambient Air
Temperature
Sensor Short
Low
AMBIENT AIR
TEMP SENSOR
SHORT LOW
Analog Input Circuit
Fault
171
15
High Ambient
Air Temperature
Warning
HIGH AMBIENT
AIR TEMP
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
171
17
Low Ambient Air LOW AMBIENT
Temperature
AIR TEMP
Warning
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
173
0
High Exhaust
Temperature
Shutdown
HIGH EXHAUST
TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
173
1
Low Exhaust
Temperature
Shutdown
LOW EXHAUST
TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
3
Exhaust
Temperature
Sensor Short
High
EXHAUST
TEMPERATURE
SENSOR SHORT
HIGH
Analog Input Circuit
Fault
173
4
Exhaust
Temperature
Sensor Short
Low
EXHAUST
TEMPERATURE
SENSOR SHORT
LOW
Analog Input Circuit
Fault
173
8
Exhaust
Temperature
Signal Abnormal
EXHAUST TEMP
SIGNAL
ABNORMAL
173
15
High Exhaust
Temperature
Warning
HIGH EXHAUST
TEMP WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
173
17
Low Exhaust
Temperature
Warning
LOW EXHAUST
TEMP WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
0
High Engine Oil
Temperature
Shutdown
HIGH ENGINE OIL
TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
Low Engine Oil
Temperature
Shutdown
LOW ENGINE OIL
TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
171
173
175
175
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
175
-(SEBP5558
3
- 16) - Documentation
Engine Oil
Temperature
Sensor Short
High
ENGINE OIL TEMP
SENSOR SHORT
HIGH
Page 9 of 21
Analog Input Circuit
Fault
4
Engine Oil
Temperature
Sensor Short
Low
ENGINE OIL TEMP
SENSOR SHORT
LOW
Analog Input Circuit
Fault
175
15
High Engine Oil
Temperature
Warning
HIGH ENGINE OIL
TEMP WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
175
17
Low Engine Oil
Temperature
Warning
LOW ENGINE OIL
TEMP WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
190
0
Engine Over
Speed Shutdown
ENGINE OVER
SPEED
SHUTDOWN
Engine Over Speed
Warning
190
1
Engine Under
Speed Shutdown
ENGINE UNDER
SPEED
SHUTDOWN
Engine Under Speed
Warning
190
2
Engine Speed
Sensor Erratic or
Not Present
ENGINE SPEED
SENSOR
ERRATIC/LOST
Engine Speed Circuit
Fault
190
5
Engine Speed
Sensor Open
ENGINE SPEED
SENSOR OPEN
Engine Speed Circuit
Fault
190
17
Engine Under
Speed Warning
ENGINE UNDER
SPEED WARNING
Engine Under Speed
Warning
234
31
SOFTWARE
Software Version
VERSION
Mismatch
MISMATCH
625
11
SCADA Data
Link Fault
SCADA DATA
LINK FAULT
Data Link Circuit
Fault
639
11
Primary Data
Link Fault
PRIMARY DATA
LINK FAULT
Data Link Circuit
Fault
701
0
Custom Event #1
High Shutdown
CUSTOM EVENT
#1 HIGH
SHUTDOWN
Digital Input Circuit
Fault
701
1
Custom Event #1
Low Shutdown
CUSTOM EVENT
#1 LOW
SHUTDOWN
Digital Input Circuit
Fault
701
15
175
Custom Event #1
High Warning
CUSTOM EVENT
#1 HIGH
WARNING
Digital Input Circuit
Fault
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
-(SEBP5558
C18 Generator Set
- 16) - Documentation
Page 10 of 21
CUSTOM EVENT
#1 LOW
WARNING
Digital Input Circuit
Fault
701
17
Custom Event #1
Low Warning
701
31
Custom Event #1
Status
CUSTOM EVENT
#1 STATUS
ACTIVE
Digital Input Circuit
Fault
702
0
Custom Event #2
High Shutdown
CUSTOM EVENT
#2 HIGH
SHUTDOWN
Digital Input Circuit
Fault
702
1
Custom Event #2
Low Shutdown
CUSTOM EVENT
#2 LOW
SHUTDOWN
Digital Input Circuit
Fault
15
Custom Event #2
High Warning
CUSTOM EVENT
#2 HIGH
WARNING
Digital Input Circuit
Fault
17
Custom Event #2
Low Warning
CUSTOM EVENT
#2 LOW
WARNING
Digital Input Circuit
Fault
702
31
Custom Event #2
Status
CUSTOM EVENT
#2 STATUS
ACTIVE
Digital Input Circuit
Fault
703
0
Custom Event #3
High Shutdown
CUSTOM EVENT
#3 HIGH
SHUTDOWN
Digital Input Circuit
Fault
703
1
Custom Event #3
Low Shutdown
CUSTOM EVENT
#3 LOW
SHUTDOWN
Digital Input Circuit
Fault
703
15
Custom Event #3
High Warning
CUSTOM EVENT
#3 HIGH
WARNING
Digital Input Circuit
Fault
17
Custom Event #3
Low Warning
CUSTOM EVENT
#3 LOW
WARNING
Digital Input Circuit
Fault
703
31
Custom Event #3
Status
CUSTOM EVENT
#3 STATUS
ACTIVE
Digital Input Circuit
Fault
704
0
Custom Event #4
High Shutdown
CUSTOM EVENT
#4 HIGH
SHUTDOWN
Digital Input Circuit
Fault
704
1
Custom Event #4
Low Shutdown
CUSTOM EVENT
#4 LOW
SHUTDOWN
Digital Input Circuit
Fault
702
702
703
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
704
-(SEBP5558
15
- 16) - Documentation
Custom Event #4
High Warning
CUSTOM EVENT
#4 HIGH
WARNING
Page 11 of 21
Digital Input Circuit
Fault
17
Custom Event #4
Low Warning
CUSTOM EVENT
#4 LOW
WARNING
Digital Input Circuit
Fault
31
Custom Event #4
Status
CUSTOM EVENT
#4 STATUS
ACTIVE
Digital Input Circuit
Fault
705
0
Custom Event #5
High Shutdown
CUSTOM EVENT
#5 HIGH
SHUTDOWN
Digital Input Circuit
Fault
705
1
Custom Event #5
Low Shutdown
CUSTOM EVENT
#5 LOW
SHUTDOWN
Digital Input Circuit
Fault
705
15
Custom Event #5
High Warning
CUSTOM EVENT
#5 HIGH
WARNING
Digital Input Circuit
Fault
705
17
Custom Event #5
Low Warning
CUSTOM EVENT
#5 LOW
WARNING
Digital Input Circuit
Fault
31
Custom Event #5
Status
CUSTOM EVENT
#5 STATUS
ACTIVE
Digital Input Circuit
Fault
706
0
Custom Event #6
High Shutdown
CUSTOM EVENT
#6 HIGH
SHUTDOWN
Digital Input Circuit
Fault
706
1
Custom Event #6
Low Shutdown
CUSTOM EVENT
#6 LOW
SHUTDOWN
Digital Input Circuit
Fault
706
15
Custom Event #6
High Warning
CUSTOM EVENT
#6 HIGH
WARNING
Digital Input Circuit
Fault
706
17
Custom Event #6
Low Warning
CUSTOM EVENT
#6 LOW
WARNING
Digital Input Circuit
Fault
31
Custom Event #6
Status
CUSTOM EVENT
#6 STATUS
ACTIVE
Digital Input Circuit
Fault
707
0
Custom Event #7
High Shutdown
CUSTOM EVENT
#7 HIGH
SHUTDOWN
707
1
704
704
705
706
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Custom Event #7
Low Shutdown
CUSTOM EVENT
#7 LOW
SHUTDOWN
15
Custom Event #7
High Warning
CUSTOM EVENT
#7 HIGH
WARNING
707
17
Custom Event #7
Low Warning
CUSTOM EVENT
#7 LOW
WARNING
707
31
Custom Event #7
Status
CUSTOM EVENT
#7 STATUS
0
Custom Event #8
High Shutdown
CUSTOM EVENT
#8 HIGH
SHUTDOWN
1
Custom Event #8
Low Shutdown
CUSTOM EVENT
#8 LOW
SHUTDOWN
708
15
Custom Event #8
High Warning
CUSTOM EVENT
#8 HIGH
WARNING
708
17
Custom Event #8
Low Warning
CUSTOM EVENT
#8 LOW
WARNING
708
31
Custom Event #8
Status
CUSTOM EVENT
#8 STATUS
709
31
Custom Event #9
Status
CUSTOM EVENT
#9 STATUS
710
31
Custom Event
#10 Status
CUSTOM EVENT
#10 STATUS
711
31
Custom Event
#11 Status
CUSTOM EVENT
#11 STATUS
712
31
Custom Event
#12 Status
CUSTOM EVENT
#12 STATUS
713
31
Custom Event
#13 Status
CUSTOM EVENT
#13 STATUS
714
31
Custom Event
#14 Status
CUSTOM EVENT
#14 STATUS
715
31
Custom Event
#15 Status
CUSTOM EVENT
#15 STATUS
716
31
Custom Event
#16 Status
CUSTOM EVENT
#16 STATUS
707
708
708
Page 12 of 21
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
924
3
925
970
1122
1122
1122
1122
1122
1122
1124
1124
1125
- 16) - Documentation
Page 13 of 21
Digital Output #1 DIGITAL OUTPUT
Short High
1 SHORT HIGH
Digital Output
Circuit Fault
3
Digital Output #2 DIGITAL OUTPUT
Short High
2 SHORT HIGH
Digital Output
Circuit Fault
31
Emergency Stop
Shutdown
EMERGENCY
STOP SHUTDOWN
Digital Input Circuit
Fault
0
High Generator
Bearing #1
Temperature
Shutdown
HIGH GEN
BEARING #1 TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
Low Generator
Rear Bearing
Temperature
Shutdown
LOW GEN REAR
BEARING TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
3
Generator Rear
Bearing
Temperature
Sensor Short
High
GEN REAR
BEARING TEMP
SENSOR SHORT
HIGH
Analog Input Circuit
Fault
4
Generator Rear
Bearing
Temperature
Sensor Short
Low
GEN REAR
BEARING TEMP
SENSOR SHORT
LOW
Analog Input Circuit
Fault
15
High Rear
Generator
Bearing
Temperature
Warning
HIGH GEN REAR
BEARING TEMP
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
17
Low Generator
Rear Bearing
Temperature
Warning
LOW GEN REAR
BEARING TEMP
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
0
High Generator
Winding #1
Temperature
Shutdown
HIGH GEN
WINDING #1 TEMP
SHUTDOWN
15
High Generator
Winding #1
Temperature
Warning
HIGH GEN
WINDING #1 TEMP
WARNING
0
High Generator
Winding #2
Temperature
Shutdown
HIGH GEN
WINDING #2 TEMP
SHUTDOWN
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Page 14 of 21
15
High Generator
Winding #2
Temperature
Warning
HIGH GEN
WINDING #2 TEMP
WARNING
0
High Generator
Winding #3
Temperature
Shutdown
HIGH GEN
WINDING #3 TEMP
SHUTDOWN
1126
15
High Generator
Winding #3
Temperature
Warning
HIGH GEN
WINDING #3 TEMP
WARNING
1231
11
Accessory Data
Link Fault
ACCESSORY
DATA LINK
FAULT
Data Link Circuit
Fault
31
Fuel Tank Leak
(Fuel Rupture
Basin)
FUEL TANK LEAK
Digital Input Circuit
Fault
1383
11
Unexpected
Engine
Shutdown
UNEXPECTED
ENGINE
SHUTDOWN
1390
0
High Gas
Pressure
Shutdown
HIGH GAS
PRESSURE
SHUTDOWN
1390
1
Low Gas
Pressure
Shutdown
LOW GAS
PRESSURE
SHUTDOWN
1390
15
High Gas
Pressure
Warning
HIGH GAS
PRESSURE
WARNING
17
Low Gas
Pressure
Warning
LOW GAS
PRESSURE
WARNING
31
Engine Failure to
Start Shutdown
ENGINE FAILURE
TO START
SHUTDOWN
Engine Overcrank
Warning
2433
0
High Right
Exhaust
Temperature
Shutdown
HIGH RIGHT
EXHAUST TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
2433
1
LOW RIGHT
EXHAUST TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1125
1126
1239
1390
1664
Low Right
Exhaust
Temperature
Shutdown
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Page 15 of 21
3
Right Exhaust
Temperature
Sensor Short
High
RIGHT EXHAUST
TEMP SENSOR
SHORT HIGH
Analog Input Circuit
Fault
2433
4
Right Exhaust
Temperature
Sensor Short
Low
RIGHT EXHAUST
TEMP SENSOR
SHORT LOW
Analog Input Circuit
Fault
2433
8
Right Exhaust
Temperature
Signal Abnormal
RIGHT EXHAUST
TEMP SGNL
ABNORMAL
2433
15
High Right
Exhaust
Temperature
Warning
HIGH RIGHT
EXHAUST TEMP
WARNING
2434
8
Left Exhaust
Temperature
Signal Abnormal
LEFT EXHAUST
TEMP SGNL
ABNORMAL
17
Low Right
Exhaust
Temperature
Warning
LOW RIGHT
EXHAUST TEMP
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
0
High Left
Exhaust
Temperature
Shutdown
HIGH LEFT
EXHAUST TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
1
Low Left
Exhaust
Temperature
Shutdown
LOW LEFT
EXHAUST TEMP
SHUTDOWN
Digital Input Circuit
Fault and Analog
Input Circuit Fault
3
Left Exhaust
Temperature
Sensor Short
High
LEFT EXHAUST
TEMP SENSOR
SHORT HIGH
Analog Input Circuit
Fault
4
Left Exhaust
Temperature
Sensor Short
Low
LEFT EXHAUST
TEMP SENSOR
SHORT LOW
Analog Input Circuit
Fault
2434
15
High Left
Exhaust
Temperature
Warning
HIGH LEFT
EXHAUST TEMP
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
2434
17
2433
2433
2434
2434
2434
2434
Digital Input Circuit
Fault and Analog
Input Circuit Fault
Low Left
Exhaust
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Page 16 of 21
Temperature
Warning
LOW LEFT
EXHAUST TEMP
WARNING
Digital Input Circuit
Fault and Analog
Input Circuit Fault
0
Generator Over
Frequency
Shutdown
GEN OVER
FREQUENCY
SHUTDOWN
Generator Over
Frequency Warning
1
Generator Under
Frequency
Shutdown
GEN UNDER
FREQUENCY
SHUTDOWN
Generator Under
Frequency Warning
2436
2
Engine SpeedGenerator Output ENG SPEED-GEN
Frequency
FREQ MISMATCH
Mismatch
WARN
Warning
Engine Speed
Warning
2436
12
Generator Output GEN AC
Sensing System
METERING SYS
Failure
FAILURE
Generator Output
Sensing Circuit
Fault
2436
15
Generator Over
Frequency
Warning
GEN OVER
FREQUENCY
WARNING
Generator Over
Frequency Warning
17
Generator Under
Frequency
Warning
GEN UNDER
FREQUENCY
WARNING
Generator Under
Frequency Warning
0
Generator Over
Voltage
Shutdown
GEN OVER
VOLTAGE
SHUTDOWN
Generator Over
Voltage Warning
2440
1
Generator Under
Voltage
Shutdown
GEN UNDER
VOLTAGE
SHUTDOWN
Generator Under
Voltage Warning
2440
15
Generator Over
Voltage Warning
GEN OVER
VOLTAGE
WARNING
Generator Over
Voltage Warning
2440
17
Generator Under
Voltage Warning
GEN UNDER
VOLTAGE
WARNING
Generator Under
Voltage Warning
2448
0
Generator Over
Current
Shutdown
GEN OVER
CURRENT
SHUTDOWN
Generator Over
Current Warning
2448
15
Generator Over
Current Warning
GEN OVER
CURRENT
WARNING
Generator Over
Current Warning
2452
1
2436
2436
2436
2440
Generator Reverse
Power Warning
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Generator
Reverse Power
Shutdown
GEN REVERSE
POWER
SHUTDOWN
Page 17 of 21
2452
15
Generator High
Power Warning
GENERATOR HIGH
POWER WARNING
2452
17
Generator
Reverse Power
Warning
GEN REVERSE
POWER WARNING
Generator Reverse
Power Warning
2648
31
Service
Maintenance
Interval Warning
SERV MAINT
INTERVAL
WARNING
Service Maintenance
Interval Warning
3543
9
Engine
Controller Not
Responding
ENG
CONTROLLER
NOT
RESPONDING
3546
11
Utility Breaker
System Fault
UTILITY
BREAKER
SYSTEM FAULT
3783
31
Engine Inlet
Manifold Charge
Combustion
ENGINE INLET
MANIFOLD CHRG
COMBUSTION
3829
31
EPS Supplying
Load
EPS SUPPLYING
LOAD
3880
31
Custom Event
#17 Status
CUSTOM EVENT
#17 STATUS
3881
31
Custom Event
#18 Status
CUSTOM EVENT
#18 STATUS
3882
31
Custom Event
#19 Status
CUSTOM EVENT
#19 STATUS
3883
31
Custom Event
#20 Status
CUSTOM EVENT
#20 STATUS
3888
31
Custom Event
#21 Status
CUSTOM EVENT
#21 STATUS
3889
31
Custom Event
#22 Status
CUSTOM EVENT
#22 STATUS
3890
31
Custom Event
#23 Status
CUSTOM EVENT
#23 STATUS
3891
31
Custom Event
#24 Status
CUSTOM EVENT
#24 STATUS
3892
31
Custom Event
#25 Status
CUSTOM EVENT
#25 STATUS
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
3893
31
3894
- 16) - Documentation
Custom Event
#26 Status
CUSTOM EVENT
#26 STATUS
31
Custom Event
#27 Status
CUSTOM EVENT
#27 STATUS
3895
31
Custom Event
#28 Status
CUSTOM EVENT
#28 STATUS
3896
31
Custom Event
#29 Status
CUSTOM EVENT
#29 STATUS
3897
31
Custom Event
#30 Status
CUSTOM EVENT
#30 STATUS
3898
31
Custom Event
#31 Status
CUSTOM EVENT
#31 STATUS
3899
31
Custom Event
#32 Status
CUSTOM EVENT
#32 STATUS
3904
31
Custom Event
#33 Status
CUSTOM EVENT
#33 STATUS
3905
31
Custom Event
#34 Status
CUSTOM EVENT
#34 STATUS
3906
31
Custom Event
#35 Status
CUSTOM EVENT
#35 STATUS
3907
31
Custom Event
#36 Status
CUSTOM EVENT
#36 STATUS
3908
31
Custom Event
#37 Status
CUSTOM EVENT
#37 STATUS
3909
31
Custom Event
#38 Status
CUSTOM EVENT
#38 STATUS
3910
31
Custom Event
#39 Status
CUSTOM EVENT
#39 STATUS
3911
31
Custom Event
#40 Status
CUSTOM EVENT
#40 STATUS
3912
31
Custom Event
#41 Status
CUSTOM EVENT
#41 STATUS
3913
31
Custom Event
#42 Status
CUSTOM EVENT
#42 STATUS
3914
31
Custom Event
#43 Status
CUSTOM EVENT
#43 STATUS
3915
31
Custom Event
#44 Status
CUSTOM EVENT
#44 STATUS
3920
31
Page 18 of 21
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Custom Event
#45 Status
CUSTOM EVENT
#45 STATUS
Page 19 of 21
3921
31
Custom Event
#46 Status
CUSTOM EVENT
#46 STATUS
3922
31
Custom Event
#47 Status
CUSTOM EVENT
#47 STATUS
3923
31
Custom Event
#48 Status
CUSTOM EVENT
#48 STATUS
3924
31
Custom Event
#49 Status
CUSTOM EVENT
#49 STATUS
3925
31
Custom Event
#50 Status
CUSTOM EVENT
#50 STATUS
3926
31
Custom Event
#51 Status
CUSTOM EVENT
#51 STATUS
3927
31
Custom Event
#52 Status
CUSTOM EVENT
#52 STATUS
3928
31
Custom Event
#53 Status
CUSTOM EVENT
#53 STATUS
3929
31
Custom Event
#54 Status
CUSTOM EVENT
#54 STATUS
3930
31
Custom Event
#55 Status
CUSTOM EVENT
#55 STATUS
3931
31
Custom Event
#56 Status
CUSTOM EVENT
#56 STATUS
4000
31
Air Damper
Closed
AIR DAMPER
CLOSED
Digital Input Circuit
Fault
4001
31
ATS in Normal
Position
ATS IN NORMAL
POSITION
Digital Input Circuit
Fault
4002
31
ATS in
Emergency
Position
ATS IN
EMERGENCY
POSITION
Digital Input Circuit
Fault
4003
31
Battery Charger
Failure
BATTERY
CHARGER
FAILURE
Digital Input Circuit
Fault
31
GENERATOR
Generator Circuit
BREAKER
Breaker Closed
CLOSED
31
Utility Circuit
Breaker Closed
4004
4005
UTILITY
BREAKER
CLOSED
Digital Input Circuit
Fault
Digital Input Circuit
Fault
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
4006
4007
4009
4010
4011
-(SEBP5558
31
- 16) - Documentation
Engine in
Cooldown
ENGINE IN
COOLDOWN
Engine Cooldown
Warning
31
Generator
Control Not in
Automatic
Warning
GEN CONTROL
NOT IN AUTO
WARNING
Generator Control
Not In Automatic
Warning
31
Generator
Breaker Failure
to Open
GENERATOR
BREAKER
FAILURE TO
OPEN
31
Utility Breaker
Failure to Open
UTILITY
BREAKER
FAILURE TO
OPEN
31
Generator
Breaker Failure
to Close
GENERATOR
BREAKER
FAILURE TO
CLOSE
UTILITY
BREAKER
FAILURE TO
CLOSE
4012
31
Utility Breaker
Failure to Close
4013
31
Generator Circuit GENERATOR
Breaker Open
BREAKER OPEN
4014
31
Utility Breaker
Open
UTILITY
BREAKER OPEN
0
Utility to
Generator
Transfer Failure
Shutdown
UTIL TO GEN
TRANSFER
FAILURE
SHUTDOWN
15
Utility to
Generator
Transfer Failure
Warning
UTIL TO GEN
TRANSFER
FAILURE
WARNING
4016
15
Generator to
Utility Transfer
Failure Warning
GEN TO UTIL
TRANSFER
FAILURE
WARNING
4017
31
Loss of Utility
LOSS OF UTILITY
4018
31
Generator
Breaker Locked
Out
GENERATOR
BREAKER
LOCKED OUT
4019
31
4015
4015
Page 20 of 21
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14
C18 Generator Set
-(SEBP5558
- 16) - Documentation
Utility Breaker
Locked Out
UTILITY
BREAKER
LOCKED OUT
Page 21 of 21
4028
31
Earth Fault
EARTH FAULT
4029
31
Earth Leakage
EARTH LEAKAGE
17
Low Battery
LOW BATT
Cranking Voltage CRANKING
Warning
VOLTAGE WARN
4256
Copyright 1993 - 2021 Caterpillar Inc.
Wed Jul 14 15:59:44 UTC+0200 2021
All Rights Reserved.
Private Network For SIS Licensees.
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 21/07/14