General Lighting and Receptacle Loads Small-Appliances Branch Circuits Laundry Branch Circuit(s) Connected Load First 3000 VA Succeding 3000 VA to 120000 VA Excess of 120,000 VA Demand Factor Quantity 42 5 2 Design Exercise 2.1 (6 Unit) Multifamily Dwelling Unit Voltage Ampere Voltage Ampere/Quantity 230 4.383 24 230 32.609 1500 230 13.043 1500 3000 66048 0 UNITS 6 6 6 Total Voltage Ampere 6048 45000 18000 69048 3000 23116.8 0 26116.8 VA VA VA VA VA VA VA VA 6 6 6 6 6 VA VA VA VA VA VA VA VA 100% 35% 25% Water Heater Disposer Compactor Diswasher Three Attic Fans Connected Load Demand Factor Clothes Dryer 1 1 1 1 3 230 230 230 230 230 Fastened Appliances In Place 4000 8 230 8 230 9 230 12 2760 75% 1 230 6000 6 24000 11040 11040 12420 16560 75060 5629500% 27000 Range Oven 1 Cooker Unit 1 1 1 230 230 230 0 8000 9000 0 6 6 0 48000 54000 VA VA VA 102000 VA 0 20640 21000 41,640 VA VA VA VA 0 VA Cooking Appliances Connected Load A B C Demand Load Air Handler 0 1 1 0% 43% 100 0 8000 21000 1 Cooling and Heating Appliances 230 0 0 6 6 AC Compressor Compressor Fan Connected Load Electric Heater Air Handler Connected Load Demand Load Largest Motor Total Demand Load System Voltage Service Rating No. of Parallel Conductors Adjustment Factor (3.10.2.6(B)(3)(a) Minimum Ampacity per Conductor Copper Conductor Size at 75°C Total Neutral Conductor Neutral Conductor calculated Neutral Conductor size GEC EGC 1 1 230 230 18 4 4140 920 6 6 1 1 230 230 5 15000 1150 6 6 25% 400 1840 Phase 3 Full Load Current 24840 16560 41400 90000 6900 96900 96900 460 24841180% 359 400 1 100% 400 250 22781980.0% 329 250 50 50 VA VA VA VA VA VA VA VA VA A A SET A mm² CU mm² CU mm² CU mm² CU