EGD PHASE-2 ECR REVIEW CHANDRA ASRI Jl. Raya Anyer Km. 123 Ciwandan , Cilegon. Banten 42447, Indonesia DETAIL DESIGN PS-2 has experienced Un-Planned Shutdown due to Spurious Trip Signal from Transmitter that lead to SM production loss. To prevent the spurious trip/ false trip, SMI has road map to increase plant reliability of PS-1 and PS-2 by implement 2 out of 3 (2oo3) interlock configuration. From P1 study, there are 11 instrument tag no will be install during TAM PS2. From 11 tag no, 9 tag no is flow transmitter and the 2 another tag no is level transmitter. For flow transmitter, Differential pressure transmitter (DPT) is proposed. While for level transmitter, Remote diaphragm seal differential pressure transmitter will be used due to material properties that easily polymerize. The following are detail designs for each transmitter: a. 2FT-2051B ~ 2FT-2058B New transmitter will be installed using existing orifice. Existing orifice is flange tap orifice. New tapping point will be provided in existing nipple, so from one nipple will be separate to two transmitter tapping point follow drawing below. Red line is new tapping point. Figure 1 Illustration of 2FT-2051B ~ 2FT-2058B Differential range for new transmitter will follow existing range (0 – 2500 mmH2O) with meter range 0 – 100000 Kg/h. b. 2FT-3001B New transmitter will be installed using existing orifice. Existing orifice is D-D/2 tap orifice. New tapping point will be installed in D-D/2 tap of orifice, but with opposite direction from the existing tapping point location follow drawing below. Red line is new tapping point. Page 1 of 5 ECR No : 513-19-030 Equipment : 2FB-503/507/508 Plant / Area : SMI Prepared by : Ardinda Checked by : F.A Gunawan Approved by : Arief Dharmawan Signed: Signed: Signed: EGD PHASE-2 ECR REVIEW CHANDRA ASRI Jl. Raya Anyer Km. 123 Ciwandan , Cilegon. Banten 42447, Indonesia Figure 2 Illustration of 2FT-3001B Differential range for new transmitter will follow existing range (0 – 2500 mmH2O) with meter range 0 – 50000 Kg/h. c. 2LT-3638B & 2LT-3638C Base on phase 1 study, in 2FA-308 will be installed additional 1 level transmitter and replacement existing level switch to be level transmitter. Figure 3 Illustration 2FA-308 Page 2 of 5 ECR No : 513-19-030 Equipment : 2FB-503/507/508 Plant / Area : SMI Prepared by : Ardinda Checked by : F.A Gunawan Approved by : Arief Dharmawan Signed: Signed: Signed: EGD PHASE-2 ECR REVIEW CHANDRA ASRI Jl. Raya Anyer Km. 123 Ciwandan , Cilegon. Banten 42447, Indonesia Drawing above, is GA drawing of 2FA-308. New level transmitter will be installed with c-c length 800 mm, while existing level switch that will be replaced with new level transmitter has 340 mm c-c length. C.1 Replacement Existing Level Switch For replacement existing level switch, calculation for new level transmitter follow drawing below: Figure 4 Illustration Replacement Existing Level Switch ππ π = π»π − πΏπ = {(ππΊπ π₯ (π − π πππππ‘β)) + ππΊπ ππππππ π₯(ππππππππππ¦)} − {ππΊπ ππππππ π₯((π − π πππππ‘β) + ππππππππππ¦} = {(ππΊπ π₯ (π − π πππππ‘β)) − (ππΊπ ππππππ π₯(π − π πππππ‘β))} = {(0.82π₯340) − (0.934π₯340)} πππ»2 π = 278.8 − 317.56 πππ»2 π = −38.76 πππ»2 π πΏπ π = π»π − πΏπ = {(ππΊπ ππππππ π₯(ππππππππππ¦)} − {ππΊπ ππππππ π₯((π − π πππππ‘β) + ππππππππππ¦)} = {−ππΊπ ππππππ π₯(π − π πππππ‘β)} = {−0.934 π₯ 340} = −317.56 πππ»2 π With ππΆππππππππ¦ ππΊπ ππΊπ ππππππ = height of capillary = specific gravity of fluid inside the tank = specific gravity of silicon oil C.2 New Level Transmitter Page 3 of 5 ECR No : 513-19-030 Equipment : 2FB-503/507/508 Plant / Area : SMI Prepared by : Ardinda Checked by : F.A Gunawan Approved by : Arief Dharmawan Signed: Signed: Signed: EGD PHASE-2 ECR REVIEW CHANDRA ASRI Jl. Raya Anyer Km. 123 Ciwandan , Cilegon. Banten 42447, Indonesia Calculation for new level transmitter follow drawing below: Figure 5 Illustration New Level Transmitter ππ π = π»π − πΏπ = {(ππΊπ π₯ (π − π πππππ‘β)) + ππΊπ ππππππ π₯(ππππππππππ¦)} − {ππΊπ ππππππ π₯((π − π πππππ‘β) + ππππππππππ¦} = {(ππΊπ π₯ (π − π πππππ‘β)) − (ππΊπ ππππππ π₯(π − π πππππ‘β))} = {(0.82π₯800) − (0.934π₯800)} πππ»2 π = 656 − 747.2 πππ»2 π = −91.2 πππ»2 π πΏπ π = π»π − πΏπ = {(ππΊπ ππππππ π₯(ππππππππππ¦)} − {ππΊπ ππππππ π₯((π − π πππππ‘β) + ππππππππππ¦)} = {−ππΊπ ππππππ π₯(π − π πππππ‘β)} = {−0.934 π₯ 800} = −747.2 πππ»2 π With ππΆππππππππ¦ ππΊπ ππΊπ ππππππ = height of capillary = specific gravity of fluid inside the tank = specific gravity of silicon oil From Figure 3 Illustration 2FA-308, new level transmitter and existing tapping point of level switch have different elevation for 0% level and 100% level. To accommodate this situation, need range modification of level transmitter that replace existing level switch in DCS. Page 4 of 5 ECR No : 513-19-030 Equipment : 2FB-503/507/508 Plant / Area : SMI Prepared by : Ardinda Checked by : F.A Gunawan Approved by : Arief Dharmawan Signed: Signed: Signed: EGD PHASE-2 ECR REVIEW CHANDRA ASRI Jl. Raya Anyer Km. 123 Ciwandan , Cilegon. Banten 42447, Indonesia Figure 6 Illustration Elevation New Level Transmitter From drawing above, 205 0% of level transmitter that replace existing level switch = 800 x 100% = 25.625% (range of level transmitter with c-c 800 mm) 100% of level transmitter that replace existing level switch = = 205+340 x 800 545 800 100% x 100% = 68.125% (range of level transmitter with c-c 800 mm) So, DCS range of level transmitter that replace existing level switch will be set from 25.625% to 68.125%. If level below 25.625%, two another transmitter will appear actual level value, while level transmitter that replace existing level switch will always show 25.625%. While if level more than 68.125%, two another transmitter will appear actual level value, while level transmitter that replace existing level switch will always show 68.125%. Page 5 of 5 ECR No : 513-19-030 Equipment : 2FB-503/507/508 Plant / Area : SMI Prepared by : Ardinda Checked by : F.A Gunawan Approved by : Arief Dharmawan Signed: Signed: Signed: