Uploaded by Kyle Magpantay

International Code Council - 2021 International Plumbing Code-International Code Council (2020)

advertisement
IPC
®
INTERNATIONAL
PLUMBING
CODE®
A Member of the International Code Family®
INCLUDES
Plumbing provisions from
ICC A117.1-2017 Standard for Accessible
and Usable Buildings and Facilities
2021 International Plumbing Code®
Date of First Publication: March 6, 2020
First Printing: March 2020
ISBN: 978-1-60983-962-8 (soft-cover edition)
ISBN: 978-1-60983-963-5 (loose-leaf edition)
COPYRIGHT © 2020
by
INTERNATIONAL CODE COUNCIL, INC.
ALL RIGHTS RESERVED. This 2021 International Plumbing Code® is a copyrighted work owned by the International Code
Council, Inc. (“ICC”). Without advance written permission from the ICC, no part of this book may be reproduced, distributed or
transmitted in any form or by any means, including, without limitation, electronic, optical or mechanical means (by way of
example, and not limitation, photocopying or recording by or in an information storage retrieval system). For information on use
rights and permissions, please contact: ICC Publications, 4051 Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888ICCSAFE (422-7233).
Trademarks: “International Code Council,” the “International Code Council” logo, “ICC,” the “ICC” logo, “International
Plumbing Code,” “IPC” and other names and trademarks appearing in this book are registered trademarks of the International
Code Council, Inc., and/or its licensors (as applicable), and may not be used without permission.
The display of the Plumbing-Heating-Cooling Contractors—National Association (PHCC) logo in this publication indicates
PHCC’s support through committee participation of ICC’s open governmental consensus process used to develop the International Codes. This support does not imply any ownership to the copyright to the International Plumbing Code, which is held
solely by the International Code Council, Inc.
Plumbing-Heating-Cooling Contractors—National Association (PHCC): 180 S. Washington Street – Suite 100, Falls Church,
VA 22046; Phone: (703) 237-8100, (800) 533-7694, www.phccweb.org.
T024869
PRINTED IN THE USA
PREFACE
Introduction
The International Plumbing Code® (IPC®) establishes minimum requirements for plumbing systems
using prescriptive and performance-related provisions. It is founded on broad-based principles that
make possible the use of new materials and new plumbing designs. This 2021 edition is fully compatible with all of the International Codes® (I-Codes®) published by the International Code Council® (ICC®),
including the International Building Code®, International Energy Conservation Code®, International
Existing Building Code®, International Fire Code®, International Fuel Gas Code®, International Green
Construction Code®, International Mechanical Code®, International Private Sewage Disposal Code®,
International Property Maintenance Code®, International Residential Code®, International Swimming
Pool and Spa Code®, International Wildland-Urban Interface Code®, International Zoning Code® and
International Code Council Performance Code®.
The I-Codes, including this International Plumbing Code, are used in a variety of ways in both the
public and private sectors. Most industry professionals are familiar with the I-Codes as the basis of
laws and regulations in communities across the US and in other countries. However, the impact of the
codes extends well beyond the regulatory arena, as they are used in a variety of nonregulatory settings, including:
•
Voluntary compliance programs such as those promoting sustainability, energy efficiency and
disaster resistance.
•
The insurance industry, to estimate and manage risk, and as a tool in underwriting and rate
decisions.
•
Certification and credentialing of individuals involved in the fields of building design, construction and safety.
•
Certification of building and construction-related products.
•
US federal agencies, to guide construction in an array of government-owned properties.
•
Facilities management.
•
“Best practices” benchmarks for designers and builders, including those who are engaged in
projects in jurisdictions that do not have a formal regulatory system or a governmental
enforcement mechanism.
•
College, university and professional school textbooks and curricula.
•
Reference works related to building design and construction.
In addition to the codes themselves, the code development process brings together building professionals on a regular basis. It provides an international forum for discussion and deliberation about
building design, construction methods, safety, performance requirements, technological advances
and innovative products.
Development
This 2021 edition presents the code as originally issued, with changes reflected in the 2003 through
2018 editions and with further changes approved by the ICC Code Development Process through 2019.
A new edition such as this is promulgated every 3 years.
This code is founded on principles intended to establish provisions consistent with the scope of a
plumbing code that adequately protects public health, safety and welfare; provisions that do not
unnecessarily increase construction costs; provisions that do not restrict the use of new materials,
products or methods of construction; and provisions that do not give preferential treatment to particular types or classes of materials, products or methods of construction.
2021 INTERNATIONAL PLUMBING CODE®
iii
Maintenance
The International Plumbing Code is kept up to date through the review of proposed changes submitted
by code enforcement officials, industry representatives, design professionals and other interested parties. Proposed changes are carefully considered through an open code development process in which
all interested and affected parties may participate.
The ICC Code Development Process reflects principles of openness, transparency, balance, due process and consensus, the principles embodied in OMB Circular A-119, which governs the federal government’s use of private-sector standards. The ICC process is open to anyone; there is no cost to
participate, and people can participate without travel cost through the ICC’s cloud-based app, cdpAccess®. A broad cross-section of interests are represented in the ICC Code Development Process. The
codes, which are updated regularly, include safeguards that allow for emergency action when
required for health and safety reasons.
In order to ensure that organizations with a direct and material interest in the codes have a voice in
the process, the ICC has developed partnerships with key industry segments that support the ICC’s
important public safety mission. Some code development committee members were nominated by
the following industry partners and approved by the ICC Board:
•
American Institute of Architects (AIA)
•
American Society of Plumbing Engineers (ASPE)
•
National Association of Home Builders (NAHB)
•
Plumbing Heating and Cooling Contractors (PHCC)
The code development committees evaluate and make recommendations regarding proposed
changes to the codes. Their recommendations are then subject to public comment and council-wide
votes. The ICC’s governmental members—public safety officials who have no financial or business
interest in the outcome—cast the final votes on proposed changes.
The contents of this work are subject to change through the code development cycles and by any
governmental entity that enacts the code into law. For more information regarding the code development process, contact the Codes and Standards Development Department of the International Code
Council.
While the I-Code development procedure is thorough and comprehensive, the ICC, its members
and those participating in the development of the codes disclaim any liability resulting from the publication or use of the I-Codes, or from compliance or noncompliance with their provisions. The ICC does
not have the power or authority to police or enforce compliance with the contents of this code.
Code Development Committee Responsibilities
(Letter Designations in Front of Section Numbers)
In each code development cycle, proposed changes to the code are considered at the Committee
Action Hearings by the International Plumbing Code Development Committee, whose action constitutes a recommendation to the voting membership for final action on the proposed change. Proposed
changes to a code section that has a number beginning with a letter in brackets are considered by a
different code development committee. For example, proposed changes to code sections that have
[BS] in front of them (e.g., [BS] 309.2) are considered by the IBC—Structural Code Development Committee at the code development hearings.
The bracketed letter designations for committees responsible for portions of this code are as follows:
[A] = Administrative Code Development Committee
[BE] = IBC—Egress Code Development Committee
[BG] = IBC—General Code Development Committee
[BS] = IBC—Structural Code Development Committee
iv
2021 INTERNATIONAL PLUMBING CODE®
[E] = International Energy Conservation Code Development Committee
[F] = International Fire Code Development Committee
[M] = International Mechanical Code Development Committee
For the development of the 2024 edition of the I-Codes, there will be two groups of code development committees and they will meet in separate years, as shown in the following Code Development
Hearings Table).
Code change proposals submitted for code sections that have a letter designation in front of them
will be heard by the respective committee responsible for such code sections. Because different committees hold Committee Action Hearings in different years, proposals for the IPC will be heard by committees in both the 2021 (Group A) and the 2022 (Group B) code development cycles.
For example, every section of Chapter 1 of this code is designated as the responsibility of the
Administrative Code Development Committee, which is part of the Group B portion of the hearings.
This committee will hold its Committee Action Hearings in 2022 to consider code change proposals for
Chapter 1 of all I-Codes except the International Energy Conservation Code, International Residential
Code and International Green Construction Code. Therefore, any proposals received for Chapter 1 of
this code will be assigned to the Administrative Code Development Committee for consideration in
2022.
It is very important that anyone submitting code change proposals understands which code development committee is responsible for the section of the code that is the subject of the code change
proposal. For further information on the Code Development Committee responsibilities, please visit
the ICC website at https://www.iccsafe.org/products-and-services/i-codes/code-development/current-code-development-cycle.
CODE DEVELOPMENT HEARINGS
Group A Codes
(Heard in 2021, Code Change Proposals
Deadline: January 11, 2021)
International Building Code
– Egress (Chapters 10, 11, Appendix E)
– Fire Safety (Chapters 7, 8, 9, 14, 26)
– General (Chapters 2–6, 12, 27–33,
Appendices A, B, C, D, K, N)
International Fire Code
Group B Codes
(Heard in 2022, Code Change Proposals
Deadline: January 10, 2022)
Administrative Provisions (Chapter 1 of all codes
except IECC, IRC and IgCC, administrative
updates to currently referenced standards, and
designated definitions)
International Building Code
– Structural (Chapters 15–25,
Appendices F, G, H, I, J, L, M)
International Fuel Gas Code
International Existing Building Code
International Mechanical Code
International Energy Conservation Code—Commercial
International Plumbing Code
International Energy Conservation Code—
Residential
– IECC—Residential
– IRC—Energy (Chapter 11)
International Property Maintenance Code
International Green Construction Code
(Chapter 1)
International Private Sewage Disposal Code
International Residential Code
– IRC—Building (Chapters 1–10,
Appendices E, F, H, J, K, L, M, O, Q, R, S, T)
(continued)
2021 INTERNATIONAL PLUMBING CODE®
v
CODE DEVELOPMENT HEARINGS—continued
Group A Codes
(Heard in 2021, Code Change Proposals
Deadline: January 11, 2021)
Group B Codes
(Heard in 2022, Code Change Proposals
Deadline: January 10, 2022)
International Residential Code
– IRC—Mechanical (Chapters 12–23)
– IRC—Plumbing (Chapters 25–33,
Appendices G, I, N, P)
International Swimming Pool and Spa Code
International Wildland-Urban Interface Code
International Zoning Code
Note: Proposed changes to the ICC Performance Code™ will be heard by the code development committee noted in brackets [ ] in the text of the ICC Performance Code™.
Marginal Markings
Solid vertical lines in the margins within the body of the code indicate a technical change from the
requirements of the 2018 edition. Deletion indicators in the form of an arrow ( ) are provided in the
margin where an entire section, paragraph, exception or table has been deleted or an item in a list of
items or a table has been deleted.
A single asterisk [*] placed in the margin indicates that text or a table has been relocated within the
code. A double asterisk [**] placed in the margin indicates that the text or table immediately following
it has been relocated there from elsewhere in the code. The following table indicates such relocations
in the 2021 edition of the International Plumbing Code.
RELOCATIONS
2021 LOCATION
2018 LOCATION
104.8
103.4
104.8.1
103.4.1
107
110
108
107
109
106.6 and 106.6.1
110
106.3.1 and 106.5.6
111
107.5 and 107.5.1
112
107.6 and 107.7
114.2
109.1
115
108
F101.3
109.2
F101.3.1
109.2.1
F101.3.2
109.2.2
F101.3.4
109.2.3
F101.3.5
109.2.5
F101.3.6
109.2.4
(continued)
vi
2021 INTERNATIONAL PLUMBING CODE®
RELOCATIONS—continued
2021 LOCATION
2018 LOCATION
F101.3.7
109.2.6
F101.4
109.4.1
F101.5
109.3
F101.5.1
109.4
F101.5.3
109.5
F101.7
109.6
F101.7.1
109.6.1
F101.7.2
109.6.2
F101.8
109.7
Coordination of the International Codes
The coordination of technical provisions is one of the strengths of the ICC family of model codes. The
codes can be used as a complete set of complementary documents, which will provide users with full
integration and coordination of technical provisions. Individual codes can also be used in subsets or as
stand-alone documents. To make sure that each individual code is as complete as possible, some technical provisions that are relevant to more than one subject area are duplicated in some of the model
codes. This allows users maximum flexibility in their application of the I-Codes.
Italicized Terms
Words and terms defined in Chapter 2, Definitions, are italicized where they appear in code text and
the Chapter 2 definition applies. Where such words and terms are not italicized, common-use definitions apply. The words and terms selected have code-specific definitions that the user should read
carefully to facilitate better understanding of the code.
Adoption
The International Code Council maintains a copyright in all of its codes and standards. Maintaining
copyright allows the ICC to fund its mission through sales of books, in both print and electronic formats. The ICC welcomes adoption of its codes by jurisdictions that recognize and acknowledge the
ICC’s copyright in the code, and further acknowledge the substantial shared value of the public/private
partnership for code development between jurisdictions and the ICC.
The ICC also recognizes the need for jurisdictions to make laws available to the public. All I-Codes
and I-Standards, along with the laws of many jurisdictions, are available for free in a nondownloadable
form on the ICC’s website. Jurisdictions should contact the ICC at adoptions@iccsafe.org to learn how
to adopt and distribute laws based on the International Plumbing Code in a manner that provides necessary access, while maintaining the ICC’s copyright.
To facilitate adoption, several sections of this code contain blanks for fill-in information that needs
to be supplied by the adopting jurisdiction as part of the adoption legislation. For this code, please see:
Section 101.1. Insert: [NAME OF JURISDICTION]
Section 103.1. Insert: [NAME OF DEPARTMENT]
Section 115.4. Insert: [OFFENSE, DOLLAR AMOUNT, NUMBER OF DAYS]
Section 305.4.1. Insert: [NUMBER OF INCHES IN TWO LOCATIONS]
Section 903.1.1. Insert: [NUMBER OF INCHES]
2021 INTERNATIONAL PLUMBING CODE®
vii
Effective use of the International Plumbing Code
The International Plumbing Code (IPC) is a model code that regulates the design and installation of
plumbing systems including the plumbing fixtures in all types of buildings except for detached oneand two-family dwellings and townhouses that are not more than three stories above grade in height.
The regulations for plumbing systems in one- and two-family dwellings and townhouses are covered
by Chapters 25 through 33 of the International Residential Code (IRC). The IPC addresses general
plumbing regulations, fixture requirements, water heater installations and systems for water distribution, sanitary drainage, special wastes, venting, storm drainage and medical gases. The IPC does not
address fuel gas piping systems as those systems are covered by the International Fuel Gas Code
(IFGC). The IPC also does not regulate swimming pool piping systems, process piping systems, or utility-owned piping and systems. The purpose of the IPC is to the establish the minimum acceptable level
of safety to protect life and property from the potential dangers associated with supplying potable
water to plumbing fixtures and outlets and the conveyance of bacteria-laden wastewater from fixtures.
The IPC is primarily a specification-oriented (prescriptive) code with some performance-oriented
text. For example, Section 405.1 is a performance statement but Chapter 6 contains the prescriptive
requirements that will cause Section 405.1 to be satisfied.
Where a building contains plumbing fixtures, those fixtures requiring water must be provided with
an adequate supply of water for proper operation. The number of required plumbing fixtures for a
building is specified by this code and is based upon the anticipated maximum number of occupants for
the building and the type of building occupancy. This code provides prescriptive criteria for sizing piping systems connected to those fixtures. Through the use of code-approved materials and the installation requirements specified in this code, plumbing systems will perform their intended function over
the life of the building. In summary, the IPC sets forth the minimum requirements for providing safe
water to a building as well as a safe manner in which liquidborne wastes are carried away from a building.
viii
2021 INTERNATIONAL PLUMBING CODE®
ARRANGEMENT AND FORMAT OF THE 2021 IPC
The format of the IPC allows each chapter to be devoted to a particular subject with the exception of
Chapter 3, which contains general subject matters that are not extensive enough to warrant their own
independent chapter.
The following table lists those subjects. The ensuing chapter-by-chapter synopsis details the scope
and intent of the provisions of the International Plumbing Code.
CHAPTER TOPICS
Chapters
1–2
3
4
5
6
7
8
9
10
11
12
13
14
15
Appendices A–F
Resource A
Subjects
Administration and Definitions
General Regulations
Fixtures, Faucets and Fixture Fittings
Water Heaters
Water Supply and Distribution
Sanitary Drainage
Indirect/Special Waste
Vents
Traps, Interceptors and Separators
Storm Drainage
Special Piping (Medical Gas)
Nonpotable Water Systems
Subsurface Graywater Soil Absorption
Referenced Standards
Appendices
Plumbing Provisions Excerpted from ICC A117.1–2017
Chapter 1 Scope and Administration
Chapter 1 contains provisions for the application, enforcement and administration of subsequent
requirements of the code. In addition to establishing the scope of the code, Chapter 1 identifies which
buildings and structures come under its purview. Chapter 1 is largely concerned with maintaining “due
process of law” in enforcing the requirements contained in the body of this code. Only through careful
observation of the administrative provisions can the code official reasonably expect to demonstrate
that “equal protection under the law” has been provided.
Chapter 2 Definitions
Chapter 2 is the repository of the definitions of terms used in the body of the code. Codes are technical documents and every word, term and punctuation mark can impact the meaning of the code text
and the intended results. The code often uses terms that have a unique meaning in the code and the
code meaning can differ substantially from the ordinarily understood meaning of the term as used
outside of the code.
The terms defined in Chapter 2 are deemed to be of prime importance in establishing the meaning
and intent of the code text that uses the terms. The user of the code should be familiar with and consult this chapter because the definitions are essential to the correct interpretation of the code and
because the user may not be aware that a term is defined.
Where understanding of a term’s definition is especially key to or necessary for understanding of a
particular code provision, the term is shown in italics. This is true only for those terms that have a
meaning that is unique to the code. In other words, the generally understood meaning of a term or
phrase might not be sufficient or consistent with the meaning prescribed by the code; therefore, it is
essential that the code-defined meaning be known.
Guidance regarding tense, gender and plurality of defined terms as well as guidance regarding
terms not defined in this code is provided.
2021 INTERNATIONAL PLUMBING CODE®
ix
Chapter 3 General Regulations
The content of Chapter 3 is often referred to as “miscellaneous,” rather than general regulations. This
is the only chapter in the code whose requirements do not interrelate. If a requirement cannot be
located in another chapter, it should be located in this chapter. Chapter 3 contains safety requirements for the installation of plumbing and nonplumbing requirements for all types of fixtures. This
chapter also has requirements for the identification of pipe, pipe fittings, traps, fixtures, materials and
devices used in plumbing systems.
The safety requirements of this chapter provide protection for the building’s structural members,
as well as prevent undue stress and strain on pipes. The building’s structural stability is protected by
the regulations for cutting and notching of structural members. Additional protection for the building
occupants includes requirements to maintain the plumbing in a safe and sanitary condition, as well as
privacy for those occupants.
Chapter 4 Fixtures, Faucets and Fixture Fittings
Chapter 4 regulates the minimum number of plumbing fixtures that must be provided for every type
of building. This chapter also regulates the quality of fixtures and faucets by requiring those items to
comply with nationally recognized standards. Because fixtures must be properly installed so that they
are usable by the occupants of the building, this chapter contains the requirements for the installation
of fixtures. Because the requirements for the number of plumbing fixtures affects the design of a
building, Chapter 29 of the International Building Code (IBC) includes, verbatim, many of the requirements listed in Chapter 4 of this code.
Chapter 5 Water Heaters
Chapter 5 regulates the design, approval and installation of water heaters and related safety devices.
The intent is to minimize the hazards associated with the installation and operation of water heaters.
Although this code does not regulate the size of a water heater, it does regulate all other aspects of
the water heater installation, such as temperature and pressure relief valves, safety drip pans, installation and connections. Where a water heater also supplies water for space heating, this chapter regulates the maximum water temperature supplied to the water distribution system.
Chapter 6 Water Supply and Distribution
Chapter 6 regulates the supply of potable water from both public and individual sources to every fixture and outlet so that it remains potable and uncontaminated. Chapter 6 also regulates the design of
the water distribution system, which will allow fixtures to function properly and help prevent backflow
conditions. The unique requirements of the water supply for health care facilities are addressed separately. It is critical that the potable water supply system remain free of actual or potential sanitary hazards by providing protection against backflow.
Chapter 7 Sanitary Drainage
The purpose of Chapter 7 is to regulate the materials, design and installation of sanitary drainage piping systems and connections made to the system. The intent is to design and install sanitary drainage
systems that will function reliably, that are neither undersized nor oversized and that are constructed
from materials, fittings and connections as prescribed herein. This chapter addresses the proper use of
fittings for directing the flow into and within the sanitary drain piping system. Materials and provisions
necessary for servicing the drainage system are also included in this chapter.
Chapter 8 Indirect/Special Waste
Chapter 8 regulates drainage installations that require an indirect connection to the sanitary drainage
system. Fixtures and plumbing appliances, such as those associated with food preparation or handling,
x
2021 INTERNATIONAL PLUMBING CODE®
health care facilities and potable liquids, must be protected from contamination that can result from
connection to the drainage system. An indirect connection prevents sewage from backing up into a fixture or appliance, thus providing protection against potential health hazards. The chapter also regulates special wastes containing hazardous chemicals. Special waste must be treated to prevent any
damage to the sanitary drainage piping and to protect the sewage treatment processes.
Chapter 9 Vents
Chapter 9 covers the requirements for vents and venting. Knowing why venting is required makes it
easier to understand the intent of this chapter. Venting protects every trap against the loss of its seal.
Provisions set forth in this chapter are geared toward limiting the pressure differentials in the drainage
system to a maximum of 1 inch of water column (249 Pa) above or below atmospheric pressure (i.e.,
positive or negative pressures).
Chapter 10 Traps, Interceptors and Separators
Chapter 10 contains design requirements and installation limitations for traps. Prohibited types of
traps are specifically identified. Where fixtures do not frequently replenish the water in traps, a
method is provided to ensure that the water seal of the trap will be maintained. Requirements for the
design and location of various types of interceptors and separators are provided. Specific venting
requirements are given for separators and interceptors, as those requirements are not addressed in
Chapter 9.
Chapter 11 Storm Drainage
Chapter 11 regulates the removal of storm water typically associated with rainfall. The proper installation of a storm drainage system reduces the possibility of structural collapse of a flat roof, prevents
the leakage of water through the roof, prevents damage to the footings and foundation of the building
and prevents flooding of the lower levels of the building.
Chapter 12 Special Piping and Storage Systems
Chapter 12 contains the requirements for the design, installation, storage, handling and use of nonflammable medical gas systems, including inhalation anesthetic and vacuum piping systems, bulk oxygen storage systems and oxygen-fuel gas systems used for welding and cutting operations. The intent
of these requirements is to minimize the potential fire and explosion hazards associated with the
gases used in these systems.
Chapter 13 Nonpotable Water Systems
Chapter 13 regulates the design and installation of nonpotable water systems, including rainwater
havesting systems. The reduction of potable water use in buildings has led building designers in some
jurisdictions to use nonpotable water for flushing of water closets and urinals. This chapter provides
the overall requirements for these systems.
Chapter 14 Subsurface Graywater Soil Absorption Systems
Chapter 14 regulates the design and installation of subsurface graywater soil absorption systems for
the disposal of on-site nonpotable water such as graywater. The reduction of potable water use in
buildings has led building designers in some jurisdictions to use on-site nonpotable water for subsurface irrigation. This chapter provides the overall requirements for these systems.
Chapter 15 Referenced Standards
Chapter 15 contains a comprehensive list of all standards that are referenced in the code. The standards are part of the code to the extent of the reference to the standard. Compliance with the refer2021 INTERNATIONAL PLUMBING CODE®
xi
enced standard is necessary for compliance with this code. By providing specifically adopted
standards, the construction and installation requirements necessary for compliance with the code can
be readily determined. The basis for code compliance is, therefore, established and available on an
equal basis to the code official, contractor, designer and owner.
Chapter 15 is organized in a manner that makes it easy to locate specific standards. It lists all of the
referenced standards, alphabetically, by acronym of the promulgating agency of the standard. Each
agency’s standards are then listed in either alphabetical or numeric order based on the standard identification. The list also contains the title of the standard; the edition (date) of the standard referenced;
any addenda included as part of the ICC adoption; and the section or sections of this code that reference the standard.
Appendix A Plumbing Permit Fee Schedule
Appendix A provides a format for a fee schedule.
Appendix B Rates of Rainfall for Various Cities
Appendix B provides specific rainfall rates for major cities in the United States.
Appendix C Structural Safety
Appendix C is provided so that the user does not have to refer to another code book for limitations for
cutting, notching and boring of sawn lumber and cold-formed steel framing.
Appendix D Degree Day and Design Temperatures
Appendix D provides valuable temperature information for designers and installers of plumbing systems in areas where freezing temperatures might exist.
Appendix E Sizing of Water Piping System
Appendix E provides two recognized methods for sizing the water service and water distribution piping for any structure. The method under Section E103 provides friction loss diagrams that require the
user to “plot” points and read values from the diagrams in order to perform the required calculations
and necessary checks. This method is the most accurate of the two presented in this appendix. The
method under Section E104 is known to be conservative; however, very few calculations are necessary
in order to determine a pipe size that satisfies the flow requirements of any application.
Appendix F Board of Appeals
Appendix F provides a set of regulations for the setup and operation of a Board of Appeals.
Resource A Plumbing Provisions Excerpted from ICC A117.1–2017
Standard for Accessible and Usable Buildings and Facilities
Building accessibility is a fundamental tenet in the International Codes. The codes rely on the provisions contained in ICC A117.1 for the design and construction of accessible buildings. Accessible
plumbing facilities and fixtures play a key role in making sure that all aspects of the building provide
the requisite level of accessibility. ICC A117.1 is referenced in Sections 404.2 and 410.3. For user convenience and in order to provide the information necessary to ensure an accessible plumbing design,
plumbing design-related excerpts from ICC A117.1 have been included in this edition as resource
material after the index. This information is not part of the IPC requirements.
xii
2021 INTERNATIONAL PLUMBING CODE®
TABLE OF CONTENTS
309
Flood Hazard Resistance . . . . . . . . . . . . . . . . . . . . 3-4
310
Washroom and Toilet Room Requirements. . . . . . 3-5
311
Toilet Facilities for Workers . . . . . . . . . . . . . . . . . 3-5
312
Tests and Inspections . . . . . . . . . . . . . . . . . . . . . . . 3-5
313
Equipment Efficiencies . . . . . . . . . . . . . . . . . . . . . 3-6
314
Condensate Disposal . . . . . . . . . . . . . . . . . . . . . . . 3-6
315
Penetrations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
PART 2—ADMINISTRATION
AND ENFORCEMENT . . . . . . . . . . . . . . . . 1-2
316
Alternative Engineered Design . . . . . . . . . . . . . . . 3-7
Section
103 Code Compliance Agency . . . . . . . . . . . . . . . . . . . 1-2
CHAPTER 4 FIXTURES, FAUCETS
AND FIXTURE FITTINGS . . . . . . . . 4-1
CHAPTER 1 SCOPE AND
ADMINISTRATION . . . . . . . . . . . . . . 1-1
PART 1—SCOPE AND APPLICATION. . . . . . . . . . . 1-1
Section
101 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
102
Applicability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
104
Duties and Powers of the Code Official . . . . . . . . . 1-2
105
Approval. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
106
Permits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
107
Temporary Equipment, Systems and Uses. . . . . . . 1-5
108
Inspections and Testing . . . . . . . . . . . . . . . . . . . . . 1-5
109
Fees. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
110
Construction Documents . . . . . . . . . . . . . . . . . . . . 1-6
111
Notice of Approval. . . . . . . . . . . . . . . . . . . . . . . . . 1-7
112
Service Utilities . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
113
Stop Work Order . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
114
Means of Appeals . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
115
Violations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Section
401 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
402
Fixture Materials . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
403
Minimum Plumbing Facilities . . . . . . . . . . . . . . . . 4-1
404
Accessible Plumbing Facilities . . . . . . . . . . . . . . . 4-5
405
Installation of Fixtures . . . . . . . . . . . . . . . . . . . . . . 4-5
406
Automatic Clothes Washers. . . . . . . . . . . . . . . . . . 4-7
407
Bathtubs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
408
Bidets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
409
Dishwashing Machines . . . . . . . . . . . . . . . . . . . . . 4-7
410
Drinking Fountains . . . . . . . . . . . . . . . . . . . . . . . . 4-7
411
Emergency Showers and Eyewash Stations . . . . . 4-8
412
Faucets and Fixture Fittings. . . . . . . . . . . . . . . . . . 4-8
CHAPTER 2 DEFINITIONS . . . . . . . . . . . . . . . . . . . 2-1
413
Floor and Trench Drains . . . . . . . . . . . . . . . . . . . . 4-9
Section
201 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
414
Floor Sinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
415
Flushing Devices for
Water Closets and Urinals . . . . . . . . . . . . . . . . . 4-9
416
Food Waste Disposer Units . . . . . . . . . . . . . . . . . 4-10
CHAPTER 3 GENERAL REGULATIONS . . . . . . . 3-1
417
Garbage Can Washers . . . . . . . . . . . . . . . . . . . . . 4-10
Section
301 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
418
Laundry Trays . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
419
Lavatories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
302
Exclusion of Materials Detrimental
to the Sewer System . . . . . . . . . . . . . . . . . . . . . . 3-1
420
Manual Food and Beverage
Dispensing Equipment. . . . . . . . . . . . . . . . . . . 4-10
303
Materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
421
Showers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
304
Rodentproofing. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
422
Sinks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
305
Protection of Pipes and Plumbing
System Components . . . . . . . . . . . . . . . . . . . . . . 3-2
423
Specialty Plumbing Fixtures . . . . . . . . . . . . . . . . 4-12
424
Urinals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
306
Trenching, Excavation and Backfill . . . . . . . . . . . . 3-2
425
Water Closets . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
307
Structural Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
426
Whirlpool Bathtubs . . . . . . . . . . . . . . . . . . . . . . . 4-12
308
Piping Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
202
General Definitions . . . . . . . . . . . . . . . . . . . . . . . . 2-1
2021 INTERNATIONAL PLUMBING CODE®
xiii
TABLE OF CONTENTS
CHAPTER 5 WATER HEATERS . . . . . . . . . . . . . . . 5-1
Section
501 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
502
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
503
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
504
Safety Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
505
Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
716
717
718
Replacement of Underground Building Sewers
and Building Drains by Pipe-Bursting
Methods. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-12
Relining Building Sewers and
Building Drains . . . . . . . . . . . . . . . . . . . . . . . . 7-13
Rehabilitation of Building Sewers and
Building Drains . . . . . . . . . . . . . . . . . . . . . . . . 7-13
CHAPTER 8 INDIRECT/SPECIAL WASTE . . . . . 8-1
CHAPTER 6 WATER SUPPLY
AND DISTRIBUTION . . . . . . . . . . . . . 6-1
Section
801 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Section
601 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
802
Indirect Wastes. . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
803
Special Wastes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
602
Water Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
603
Water Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
CHAPTER 9 VENTS. . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
604
Design of Building Water
Distribution System . . . . . . . . . . . . . . . . . . . . . . 6-2
Section
901 General. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
605
Materials, Joints and Connections . . . . . . . . . . . . . 6-4
902
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
606
Installation of the Building Water
Distribution System . . . . . . . . . . . . . . . . . . . . . . 6-9
903
Vent Terminals. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-1
904
Outdoor Vent Extensions. . . . . . . . . . . . . . . . . . . . 9-2
905
Vent Connections and Grades . . . . . . . . . . . . . . . . 9-2
906
Vent Pipe Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . 9-2
907
Vents for Stack Offsets . . . . . . . . . . . . . . . . . . . . . 9-4
908
Relief Vents—Stacks of More Than
10 Branch Intervals . . . . . . . . . . . . . . . . . . . . . . 9-4
909
Fixture Vents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
910
Individual Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
911
Common Vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
912
Wet Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-5
913
Waste Stack Vent. . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
914
Circuit Venting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-6
915
Combination Waste and Vent System . . . . . . . . . . 9-7
916
Island Fixture Venting . . . . . . . . . . . . . . . . . . . . . . 9-7
917
Single-Stack Vent System . . . . . . . . . . . . . . . . . . . 9-7
918
Air Admittance Valves . . . . . . . . . . . . . . . . . . . . . 9-8
919
Engineered Vent Systems . . . . . . . . . . . . . . . . . . . 9-9
920
Computerized Vent Design . . . . . . . . . . . . . . . . . . 9-9
607
Hot Water Supply System . . . . . . . . . . . . . . . . . . 6-10
608
Protection of Potable Water Supply . . . . . . . . . . . 6-11
609
Health Care Plumbing . . . . . . . . . . . . . . . . . . . . . 6-17
610
Disinfection of Potable Water System . . . . . . . . . 6-18
611
Drinking Water Treatment Units . . . . . . . . . . . . . 6-18
612
Solar Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-18
613
Temperature Control Devices and Valves . . . . . . 6-18
CHAPTER 7 SANITARY DRAINAGE. . . . . . . . . . . 7-1
Section
701 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
702 Materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
703 Building Sewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3
704 Drainage Piping Installation. . . . . . . . . . . . . . . . . . 7-3
705 Joints. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-4
706 Connections Between Drainage
Piping and Fittings. . . . . . . . . . . . . . . . . . . . . . . 7-6
707 Prohibited Joints and Connections . . . . . . . . . . . . . 7-7
708 Cleanouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-7
709 Fixture Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-8
710 Drainage System Sizing . . . . . . . . . . . . . . . . . . . . 7-10
711 Offsets in Drainage Piping in Buildings
of Five Stories or More . . . . . . . . . . . . . . . . . . 7-10
712 Sumps and Ejectors . . . . . . . . . . . . . . . . . . . . . . . 7-11
713 Computerized Drainage Design . . . . . . . . . . . . . . 7-12
714 Backwater Valves. . . . . . . . . . . . . . . . . . . . . . . . . 7-12
715 Vacuum Drainage Systems . . . . . . . . . . . . . . . . . 7-12
xiv
CHAPTER 10 TRAPS, INTERCEPTORS
AND SEPARATORS . . . . . . . . . . . . 10-1
Section
1001 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-1
1002 Trap Requirements . . . . . . . . . . . . . . . . . . . . . . . 10-1
1003 Interceptors and Separators. . . . . . . . . . . . . . . . . 10-2
1004 Materials, Joints and Connections . . . . . . . . . . . 10-4
2021 INTERNATIONAL PLUMBING CODE®
TABLE OF CONTENTS
CHAPTER 11 STORM DRAINAGE . . . . . . . . . . . . 11-1
Permit Issuance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Section
1101 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
Unit Fee Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Other Inspections and Fees. . . . . . . . . . . . . . . . . . . . . . . . A-1
1102 Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-1
1103 Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
1104 Conductors and Connections. . . . . . . . . . . . . . . . 11-2
1105 Roof Drains . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-2
1106 Size of Conductors, Leaders
and Storm Drains. . . . . . . . . . . . . . . . . . . . . . . 11-3
1107 Siphonic Roof Drainage Systems . . . . . . . . . . . . 11-9
1108 Secondary (Emergency) Roof Drains . . . . . . . . . 11-9
1109 Combined Sanitary and Storm Public Sewer . . . 11-9
1110 Controlled Flow Roof Drain Systems . . . . . . . . . 11-9
APPENDIX B RATES OF RAINFALL
FOR VARIOUS CITIES . . . . . . . . . . B-1
APPENDIX C STRUCTURAL SAFETY . . . . . . . . . C-1
Section
C101 Cutting, Notching and Boring in
Wood Members. . . . . . . . . . . . . . . . . . . . . . . . . C-1
APPENDIX D DEGREE DAY AND
DESIGN TEMPERATURES. . . . . . . D-1
1111 Subsoil Drains . . . . . . . . . . . . . . . . . . . . . . . . . . 11-10
1112 Building Subdrains . . . . . . . . . . . . . . . . . . . . . . 11-10
1113 Sumps and Pumping Systems . . . . . . . . . . . . . . 11-10
CHAPTER 12 SPECIAL PIPING AND
STORAGE SYSTEMS . . . . . . . . . . . 12-1
APPENDIX E SIZING OF WATER
PIPING SYSTEM. . . . . . . . . . . . . . . . E-1
Section
E101 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E-1
E102 Information Required . . . . . . . . . . . . . . . . . . . . . . E-1
Section
1201 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
E103 Selection of Pipe Size . . . . . . . . . . . . . . . . . . . . . . E-1
1202 Medical Gases . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
E105 Determination of Pipe Volumes . . . . . . . . . . . . . E-19
E104 Selection of Pipe Size . . . . . . . . . . . . . . . . . . . . . E-19
1203 Oxygen Systems . . . . . . . . . . . . . . . . . . . . . . . . . 12-1
APPENDIX F BOARD OF APPEALS . . . . . . . . . . . F-1
CHAPTER 13 NONPOTABLE
WATER SYSTEMS . . . . . . . . . . . . . 13-1
Section
F101 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
Section
1301 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13-1
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . INDEX-1
1302 On-site Nonpotable Water Reuse Systems . . . . . 13-3
1303 Nonpotable Rainwater Collection and
Distribution Systems . . . . . . . . . . . . . . . . . . . . 13-5
1304 Reclaimed Water Systems. . . . . . . . . . . . . . . . . . 13-7
CHAPTER 14 SUBSURFACE
GRAYWATER SOIL
ABSORPTION SYSTEMS. . . . . . . . 14-1
Section
1401 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-1
1402 System Design and Sizing. . . . . . . . . . . . . . . . . . 14-1
1403 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14-2
CHAPTER 15 REFERENCED STANDARDS . . . . 15-1
APPENDIX A PLUMBING PERMIT
FEE SCHEDULE . . . . . . . . . . . . . . . A-1
2021 INTERNATIONAL PLUMBING CODE®
RESOURCE A
PLUMBING PROVISIONS EXCERPTED FROM:
ICC A117.1—2017
STANDARD FOR ACCESSIBLE AND USABLE
BUILDINGS AND FACILITIES
CHAPTER 1 APPLICATION AND
ADMINISTRATION . . RESOURCE A-1
101
Title . . . . . . . . . . . . . . . . . . . . . . . . . RESOURCE A-1
102
Purpose. . . . . . . . . . . . . . . . . . . . . . . RESOURCE A-1
103
Human Factor Provisions. . . . . . . . . RESOURCE A-1
104
Compliance Alternatives . . . . . . . . . RESOURCE A-1
105
Conventions . . . . . . . . . . . . . . . . . . . RESOURCE A-1
106
Referenced Documents . . . . . . . . . . RESOURCE A-1
107
Definitions . . . . . . . . . . . . . . . . . . . . RESOURCE A-3
xv
TABLE OF CONTENTS
CHAPTER 3 BUILDING
BLOCKS . . . . . . . . . . . . RESOURCE A-7
301
General . . . . . . . . . . . . . . . . . . . . . . . RESOURCE A-7
302
Floor Surfaces. . . . . . . . . . . . . . . . . . RESOURCE A-7
303
Changes in Level . . . . . . . . . . . . . . . RESOURCE A-7
304
Turning Space. . . . . . . . . . . . . . . . . . RESOURCE A-8
305
Clear Floor Space . . . . . . . . . . . . . . RESOURCE A-10
306
Knee and Toe Clearance. . . . . . . . . RESOURCE A-11
307
Protruding Objects . . . . . . . . . . . . . RESOURCE A-13
308
Reach Ranges . . . . . . . . . . . . . . . . . RESOURCE A-14
309
Operable Parts . . . . . . . . . . . . . . . . RESOURCE A-15
CHAPTER 6 PLUMBING ELEMENTS AND
FACILITIES . . . . . . . RESOURCE A-17
601
General . . . . . . . . . . . . . . . . . . . . . RESOURCE A-17
602
Drinking Fountains and
Bottle Filling Stations. . . . . . . . . RESOURCE A-17
603
Toilet and Bathing Rooms . . . . . . . RESOURCE A-18
604
Water Closets and Toilet
Compartments . . . . . . . . . . . . . . RESOURCE A-19
605
Urinals . . . . . . . . . . . . . . . . . . . . . . RESOURCE A-28
606
Lavatories and Sinks . . . . . . . . . . . RESOURCE A-29
607
Bathtubs . . . . . . . . . . . . . . . . . . . . . RESOURCE A-30
608
Shower Compartments . . . . . . . . . . RESOURCE A-32
609
Grab Bars . . . . . . . . . . . . . . . . . . . . RESOURCE A-37
610
Seats . . . . . . . . . . . . . . . . . . . . . . . . RESOURCE A-39
611
Washing Machines and Clothes
Dryers . . . . . . . . . . . . . . . . . . . . . RESOURCE A-40
612
Saunas and Steam Rooms. . . . . . . . RESOURCE A-42
CHAPTER 8 SPECIAL ROOMS
AND SPACES . . . . . . . RESOURCE A-43
801
General . . . . . . . . . . . . . . . . . . . . . . RESOURCE A-43
804
Kitchens . . . . . . . . . . . . . . . . . . . . . RESOURCE A-43
CHAPTER 11 DWELLING UNITS AND
SLEEPING UNITS . . . RESOURCE A-47
1101 General . . . . . . . . . . . . . . . . . . . . . . RESOURCE A-47
1102 Accessible Units . . . . . . . . . . . . . . . RESOURCE A-47
1103 Type A Units . . . . . . . . . . . . . . . . . RESOURCE A-48
1104 Type B Units . . . . . . . . . . . . . . . . . RESOURCE A-54
1105 Type C (Visitable) Units . . . . . . . . RESOURCE A-63
1106 Units with Communication
Features . . . . . . . . . . . . . . . . . . . RESOURCE A-64
xvi
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 1
SCOPE AND ADMINISTRATION
User note:
About this chapter: Chapter 1 establishes the limits of applicability of this code and describes how the code is to be applied and enforced.
Chapter 1 is in two parts: Part 1—Scope and Application (Sections 101 and 102) and Part 2—Administration and Enforcement (Sections
103–115). Section 101 identifies which buildings and structures come under its purview and references other I-Codes as applicable. Standards and codes are scoped to the extent referenced (see Section 102.8).
This code is intended to be adopted as a legally enforceable document and it cannot be effective without adequate provisions for its administration and enforcement. The provisions of Chapter 1 establish the authority and duties of the code official appointed by the authority
having jurisdiction and also establish the rights and privileges of the design professional, contractor and property owner.
PART 1—SCOPE AND APPLICATION
SECTION 101
SCOPE AND GENERAL REQUIREMENTS
[A] 101.1 Title. These regulations shall be known as the
Plumbing Code of [NAME OF JURISDICTION] hereinafter
referred to as “this code.”
[A] 101.2 Scope. The provisions of this code shall apply to
the erection, installation, alteration, repairs, relocation,
replacement, addition to, use or maintenance of plumbing
systems within this jurisdiction. This code shall regulate
nonflammable medical gas, inhalation anesthetic, vacuum
piping, nonmedical oxygen systems and sanitary and
condensate vacuum collection systems. The installation of
fuel gas distribution piping and equipment, fuel-gas-fired
water heaters and water heater venting systems shall be regulated by the International Fuel Gas Code. Provisions in the
appendices shall not apply unless specifically adopted.
Exception: Detached one- and two-family dwellings and
townhouses not more than three stories above grade plane
in height with a separate means of egress, and their accessory structures not more than three stories above grade
plane in height, shall comply with this code or the International Residential Code.
[A] 101.3 Purpose. The purpose of this code is to establish
minimum requirements to provide a reasonable level of
safety, health, property protection and general welfare by
regulating and controlling the design, construction, installation, quality of materials, location, operation and
maintenance or use of plumbing equipment and systems.
[A] 101.4 Severability. If any section, subsection, sentence,
clause or phrase of this code is for any reason held to be
unconstitutional, such decision shall not affect the validity of
the remaining portions of this code.
SECTION 102
APPLICABILITY
[A] 102.1 General. Where there is a conflict between a
general requirement and a specific requirement, the specific
requirement shall govern. Where, in any specific case,
2021 INTERNATIONAL PLUMBING CODE®
different sections of this code specify different materials,
methods of construction or other requirements, the most
restrictive shall govern.
[A] 102.2 Existing installations. Plumbing systems lawfully
in existence at the time of the adoption of this code shall be
permitted to have their use and maintenance continued if the
use, maintenance or repair is in accordance with the original
design and hazard to life, health or property is not created by
such plumbing system.
[A] 102.2.1 Existing buildings. Additions, alterations,
renovations or repairs related to building or structural
issues shall be regulated by the International Existing
Building Code.
[A] 102.3 Maintenance. Plumbing systems, materials and
appurtenances, both existing and new, and parts thereof,
shall be maintained in proper operating condition in accordance with the original design in a safe and sanitary
condition. Devices or safeguards required by this code shall
be maintained in compliance with the edition of the code
under which they were installed.
The owner or the owner’s authorized agent shall be
responsible for maintenance of plumbing systems. To determine compliance with this provision, the code official shall
have the authority to require any plumbing system to be
reinspected.
[A] 102.4 Additions, alterations or repairs. Additions,
alterations, renovations or repairs to any plumbing system
shall conform to that required for a new plumbing system
without requiring the existing plumbing system to comply
with all of the requirements of this code. Additions, alterations or repairs shall not cause an existing system to
become unsafe, unsanitary or overloaded.
Minor additions, alterations, renovations and repairs to
existing plumbing systems shall meet the provisions for new
construction, unless such work is done in the same manner
and arrangement as was in the existing system, is not hazardous and is approved.
[A] 102.5 Change in occupancy. It shall be unlawful to
make any change in the occupancy of any structure that will
subject the structure to any special provision of this code
applicable to the new occupancy without approval of the
1-1
SCOPE AND ADMINISTRATION
code official. The code official shall certify that such structure meets the intent of the provisions of law governing
building construction for the proposed new occupancy and
that such change of occupancy does not result in any hazard
to the public health, safety or welfare.
the agency shall be the implementation, administration and
enforcement of the provisions of this code.
[A] 102.6 Historic buildings. The provisions of this code
relating to the construction, alteration, repair, enlargement,
restoration, relocation or moving of buildings or structures
shall not be mandatory for existing buildings or structures
identified and classified by the state or local jurisdiction as
historic buildings where such buildings or structures are
judged by the code official to be safe and in the public interest of health, safety and welfare regarding any proposed
construction, alteration, repair, enlargement, restoration,
relocation or moving of buildings.
[A] 103.3 Deputies. In accordance with the prescribed
procedures of this jurisdiction and with the concurrence of
the appointing authority, the code official shall have the
authority to appoint a deputy code official, other related
technical officers, inspectors and other employees. Such
employees shall have powers as delegated by the code
official.
[A] 102.7 Moved buildings. Except as determined by
Section 102.2, plumbing systems that are a part of buildings
or structures moved into or within the jurisdiction shall
comply with the provisions of this code for new installations.
[A] 102.8 Referenced codes and standards. The codes and
standards referenced in this code shall be those that are listed
in Chapter 15 and such codes and standards shall be considered as part of the requirements of this code to the prescribed
extent of each such reference and as further regulated in
Sections 102.8.1 and 102.8.2.
[A] 102.8.1 Conflicts. Where conflicts occur between
provisions of this code and the referenced standards, the
provisions of this code shall apply.
[A] 102.8.2 Provisions in referenced codes and standards. Where the extent of the reference to a referenced
code or standard includes subject matter that is within the
scope of this code, the provisions of this code, as applicable, shall take precedence over the provisions in the
referenced code or standard.
[A] 102.9 Requirements not covered by code. Any requirements necessary for the strength, stability or proper
operation of an existing or proposed plumbing system, or for
the public safety, health and general welfare, not specifically
covered by this code shall be determined by the code
official.
[A] 102.10 Other laws. The provisions of this code shall not
be deemed to nullify any provisions of local, state or federal
law.
[A] 102.11 Application of references. Reference to chapter
section numbers, or to provisions not specifically identified
by number, shall be construed to refer to such chapter,
section or provision of this code.
PART 2—ADMINISTRATION AND ENFORCEMENT
SECTION 103
CODE COMPLIANCE AGENCY
[A] 103.1 Creation of agency. The [INSERT NAME OF
is hereby created and the official in charge
thereof shall be known as the code official. The function of
DEPARTMENT]
1-2
[A] 103.2 Appointment. The code official shall be
appointed by the chief appointing authority of the
jurisdiction.
SECTION 104
DUTIES AND POWERS OF THE CODE OFFICIAL
[A] 104.1 General. The code official is hereby authorized
and directed to enforce the provisions of this code. The code
official shall have the authority to render interpretations of
this code and to adopt policies and procedures in order to
clarify the application of its provisions. Such interpretations,
policies and procedures shall be in compliance with the
intent and purpose of this code. Such policies and procedures
shall not have the effect of waiving requirements specifically
provided for in this code.
[A] 104.2 Applications and permits. The code official shall
receive applications, review construction documents and
issue permits for the installation and alteration of plumbing
systems, inspect the premises for which such permits have
been issued, and enforce compliance with the provisions of
this code.
[A] 104.3 Inspections. The code official shall make all of
the required inspections, or shall accept reports of inspections by approved agencies or individuals. Reports of such
inspections shall be in writing and be certified by a responsible officer of such approved agency or by the responsible
individual. The code official is authorized to engage such
expert opinion as deemed necessary to report on unusual
technical issues that arise, subject to the approval of the
appointing authority.
[A] 104.4 Right of entry. Where it is necessary to make an
inspection to enforce the provisions of this code, or where
the code official has reasonable cause to believe that there
exists in any building or on any premises any conditions or
violations of this code that make the building or premises
unsafe, unsanitary, dangerous or hazardous, the code official
shall have the authority to enter the building or premises at
all reasonable times to inspect or to perform the duties
imposed upon the code official by this code. If such building
or premises is occupied, the code official shall present
credentials to the occupant and request entry. If such building or premises is unoccupied, the code official shall first
make a reasonable effort to locate the owner, the owner’s
authorized agent or other person having charge or control of
the building or premises and request entry. If entry is
refused, the code official shall have recourse to every
remedy provided by law to secure entry.
2021 INTERNATIONAL PLUMBING CODE®
*
SCOPE AND ADMINISTRATION
Where the code official shall have first obtained a proper
inspection warrant or other remedy provided by law to
secure entry, the owner, owner’s authorized agent, occupant
or person having charge, care or control of any building or
premises shall not fail or neglect, after proper request is
made as herein provided, to promptly permit entry therein by
the code official for the purpose of inspection and examination pursuant to this code.
[A] 104.5 Identification. The code official shall carry
proper identification when inspecting structures or premises
in the performance of duties under this code.
[A] 104.6 Notices and orders. The code official shall issue
all necessary notices or orders to ensure compliance with this
code.
[A] 104.7 Department records. The code official shall keep
official records of applications received, permits and certificates issued, fees collected, reports of inspections, and
notices and orders issued. Such records shall be retained in
the official records for the period required for the retention
of public records.
**
[A] 104.8 Liability. The code official, member of the board
of appeals or employee charged with the enforcement of this
code, while acting for the jurisdiction in good faith and without malice in the discharge of the duties required by this
code or other pertinent law or ordinance, shall not thereby be
rendered civilly or criminally liable personally, and is hereby
relieved from all personal liability for any damage accruing
to persons or property as a result of any act or by reason of
an act or omission in the discharge of official duties.
[A] 104.8.1 Legal defense. Any suit or criminal
complaint instituted against any officer or employee
because of an act performed by that officer or employee
in the lawful discharge of duties and under the provisions
of this code shall be defended by the legal representative
of the jurisdiction until the final termination of the
proceedings. The code official or any subordinate shall
not be liable for costs in any action, suit or proceeding
that is instituted in pursuance of the provisions of this
code.
SECTION 105
APPROVAL
[A] 105.1 Modifications. Where there are practical difficulties involved in carrying out the provisions of this code, the
code official shall have the authority to grant modifications
for individual cases, upon application of the owner or
owner’s authorized agent, provided that the code official
shall first find that special individual reason makes the strict
letter of this code impractical and the modification conforms
to the intent and purpose of this code and that such modification does not lessen health, life and fire safety requirements.
The details of action granting modifications shall be
recorded and entered in the files of the plumbing inspection
department.
[A] 105.2 Alternative materials, design and methods of
construction and equipment. The provisions of this code
are not intended to prevent the installation of any material or
2021 INTERNATIONAL PLUMBING CODE®
to prohibit any design or method of construction not specifically prescribed by this code, provided that any such
alternative has been approved. An alternative material or
method of construction shall be approved where the code
official finds that the proposed design is satisfactory and
complies with the intent of the provisions of this code, and
that the material, method or work offered is, for the purpose
intended, not less than the equivalent of that prescribed in
this code in quality, strength, effectiveness, fire resistance,
durability and safety. Where the alternative material, design
or method of construction is not approved, the code official
shall respond in writing, stating the reasons why the alternative was not approved.
[A] 105.2.1 Research reports. Supporting data, where
necessary to assist in the approval of materials or assemblies not specifically provided for in this code, shall
consist of valid research reports from approved sources.
[A] 105.3 Required testing. Where there is insufficient
evidence of compliance with the provisions of this code, or
evidence that a material or method does not conform to the
requirements of this code, or in order to substantiate claims
for alternative materials or methods, the code official shall
have the authority to require tests as evidence of compliance
to be made at no expense to the jurisdiction.
[A] 105.3.1 Test methods. Test methods shall be as specified in this code or by other recognized test standards. In
the absence of recognized and accepted test methods, the
code official shall approve the testing procedures.
[A] 105.3.2 Testing agency. Tests shall be performed by
an approved agency.
[A] 105.3.3 Test reports. Reports of tests shall be
retained by the code official for the period required for
retention of public records.
[A] 105.4 Approved materials and equipment. Materials,
equipment and devices approved by the code official shall be
constructed and installed in accordance with such approval.
[A] 105.4.1 Material and equipment reuse. Materials,
equipment and devices shall not be reused unless such
elements have been reconditioned, tested, placed in good
and proper working condition and approved.
SECTION 106
PERMITS
[A] 106.1 Where required. Any owner, owner’s authorized
agent or contractor who desires to construct, enlarge, alter,
repair, move, demolish or change the occupancy of a building or structure, or to erect, install, enlarge, alter, repair,
remove, convert or replace any plumbing system, the installation of which is regulated by this code, or to cause any
such work to be performed, shall first make application to
the code official and obtain the required permit for the work.
[A] 106.1.1 Annual permit. Instead of an individual
construction permit for each alteration to an already
approved system or equipment or appliance installation,
the code official is authorized to issue an annual permit
upon application therefor to any person, firm or corpora1-3
SCOPE AND ADMINISTRATION
tion regularly employing one or more qualified
tradespersons in the building, structure or on the premises
owned or operated by the applicant for the permit.
[A] 106.1.2 Annual permit records. The person to
whom an annual permit is issued shall keep a detailed
record of alterations made under such annual permit. The
code official shall have access to such records at all times
or such records shall be filed with the code official as
designated.
[A] 106.2 Exempt work. The following work shall be
exempt from the requirement for a permit:
1.
2.
The stopping of leaks in drains, water, soil, waste or
vent pipe provided, however, that if any concealed
trap, drainpipe, water, soil, waste or vent pipe
becomes defective and it becomes necessary to
remove and replace the same with new material, such
work shall be considered as new work and a permit
shall be obtained and inspection made as provided in
this code.
The clearing of stoppages or the repairing of leaks in
pipes, valves or fixtures, and the removal and reinstallation of water closets, provided that such repairs
do not involve or require the replacement or rearrangement of valves, pipes or fixtures.
Exemption from the permit requirements of this code
shall not be deemed to grant authorization for any work to be
done in violation of the provisions of this code or any other
laws or ordinances of this jurisdiction.
*
[A] 106.3 Application for permit. Each application for a
permit, with the required fee, shall be filed with the code
official on a form furnished for that purpose and shall
contain a general description of the proposed work and its
location. The application shall be signed by the owner or
owner’s authorized agent. The permit application shall indicate the proposed occupancy of all parts of the building and
of that portion of the site or lot, if any, not covered by the
building or structure and shall contain such other information required by the code official.
[A] 106.5 Permit issuance. The application, construction
documents and other data filed by an applicant for permit
shall be reviewed by the code official. If the code official
finds that the proposed work conforms to the requirements of
this code and all laws and ordinances applicable thereto, and
that the fees specified in Section 109.1 have been paid, a
permit shall be issued to the applicant.
[A] 106.5.1 Approved construction documents. When
the code official issues the permit where construction
documents are required, the construction documents shall
be endorsed in writing and stamped “APPROVED.” Such
approved construction documents shall not be changed,
modified or altered without authorization from the code
official. Work shall be done in accordance with the
approved construction documents.
The code official shall have the authority to issue a
permit for the construction of a part of a plumbing system
before the entire construction documents for the whole
system have been submitted or approved, provided that
adequate information and detailed statements have been
filed complying with all pertinent requirements of this
code. The holders of such permit shall proceed at their
own risk without assurance that the permit for the entire
plumbing system will be granted.
[A] 106.5.2 Validity. The issuance of a permit or
approval of construction documents shall not be
construed to be a permit for, or an approval of, any violation of any of the provisions of this code or any other
ordinance of the jurisdiction. A permit presuming to give
authority to violate or cancel the provisions of this code
shall not be valid.
The issuance of a permit based on construction documents and other data shall not prevent the code official
from thereafter requiring the correction of errors in said
construction documents and other data or from preventing
building operations being carried on thereunder where in
violation of this code or of other ordinances of this
jurisdiction.
[A] 106.3.2 Time limitation of application. An application for a permit for any proposed work shall be deemed
to have been abandoned 180 days after the date of filing,
unless such application has been pursued in good faith or
a permit has been issued; except that the code official
shall have the authority to grant one or more extensions of
time for additional periods not exceeding 180 days each.
The extension shall be requested in writing and justifiable
cause demonstrated.
[A] 106.5.3 Expiration. Every permit issued by the code
official under the provisions of this code shall expire by
limitation and become null and void if the work authorized by such permit is not commenced within 180 days
from the date of such permit, or if the work authorized by
such permit is suspended or abandoned at any time after
the work is commenced for a period of 180 days. Before
such work can be recommenced, a new permit shall be
first obtained and the fee therefor shall be one-half the
amount required for a new permit for such work, provided
that changes have not been made and will not be made in
the original construction documents for such work, and
provided further that such suspension or abandonment
has not exceeded 1 year.
[A] 106.4 By whom application is made. Application for a
permit shall be made by the person or agent to install all or
part of any plumbing system. The applicant shall meet all
qualifications established by statute, or by rules promulgated
by this code, or by ordinance or by resolution. The full name
and address of the applicant shall be stated in the application.
[A] 106.5.4 Extensions. Any permittee holding an unexpired permit shall have the right to apply for an extension
of the time within which the permittee will commence
work under that permit when work is unable to be
commenced within the time required by this section for
good and satisfactory reasons. The code official shall
[A] 106.3.1 Preliminary inspection. Before a permit is
issued, the code official shall be authorized to inspect and
evaluate the systems, equipment, buildings, devices,
premises and spaces or areas to be used.
1-4
2021 INTERNATIONAL PLUMBING CODE®
SCOPE AND ADMINISTRATION
extend the time for action by the permittee for a period
not exceeding 180 days if there is reasonable cause. A
permit shall not be extended more than once. The fee for
an extension shall be one-half the amount required for a
new permit for such work.
*
*
**
[A] 106.5.5 Suspension or revocation of permit. The
code official shall have the authority to suspend or revoke
a permit issued under the provisions of this code wherever the permit is issued in error or on the basis of
incorrect, inaccurate or incomplete information, or in
violation of any ordinance or regulation or any of the
provisions of this code.
[A] 106.5.6 Previous approvals. This code shall not
require changes in the construction documents, construction or designated occupancy of a structure for which a
lawful permit has been heretofore issued or otherwise
lawfully authorized, and the construction of which has
been pursued in good faith within 180 days after the
effective date of this code and has not been abandoned.
[A] 106.5.7 Posting of permit. The permit or a copy shall
be kept on the site of the work until the completion of the
project.
**
[A] 108.2 Required inspections and testing. The code official, upon notification from the permit holder or the permit
holder’s agent, shall make the following inspections and
such other inspections as necessary, and shall either release
that portion of the construction or shall notify the permit
holder or an agent of any violations that must be corrected.
The holder of the permit shall be responsible for the scheduling of such inspections.
1.
2.
SECTION 107
TEMPORARY EQUIPMENT, SYSTEMS AND USES
[A] 107.1 General. The code official is authorized to issue a
permit for temporary equipment, systems and uses. Such
permits shall be limited as to time of service, but shall not be
permitted for more than 180 days. The code official is authorized to grant extensions for demonstrated cause.
*
inspection purposes until approved. Approval as a result of
an inspection shall not be construed to be an approval of a
violation of the provisions of this code or of other ordinances
of the jurisdiction. Inspections presuming to give authority
to violate or cancel the provisions of this code or of other
ordinances of the jurisdiction shall not be valid. It shall be
the duty of the permit applicant to cause the work to remain
visible and able to be accessed for inspection purposes.
Neither the code official nor the jurisdiction shall be liable
for expenses entailed in the removal or replacement of any
material required to allow inspection.
3.
Underground inspection shall be made after trenches
or ditches are excavated and bedded, piping installed,
and before any backfill is put in place.
Rough-in inspection shall be made after the roof,
framing, fireblocking, firestopping, draftstopping
and bracing is in place and all sanitary, storm and
water distribution piping is roughed-in, and prior to
the installation of wall or ceiling membranes.
Final inspection shall be made after the building is
complete, all plumbing fixtures are in place and
properly connected, and the structure is ready for
occupancy.
[A] 107.2 Conformance. Temporary equipment, systems
and uses shall conform to the structural strength, fire safety,
means of egress, accessibility, light, ventilation and sanitary
requirements of this code as necessary to ensure the public
health, safety and general welfare.
[A] 108.2.1 Other inspections. In addition to the inspections specified in Section 108.2, the code official shall be
authorized to make or require other inspections of any
construction work to ascertain compliance with the provisions of this code and other laws that are enforced.
[A] 107.3 Temporary utilities. The code official is authorized to give permission to temporarily supply utilities
before an installation has been fully completed and the final
certificate of completion has been issued. The part covered
by the temporary certificate shall comply with the requirements specified for temporary lighting, heat or power in the
code.
[A] 108.2.2 Inspection requests. It shall be the duty of
the holder of the permit or their duly authorized agent to
notify the code official when work is ready for inspection.
It shall be the duty of the permit holder to provide access
to and means for inspections of such work that are
required by this code.
[A] 107.4 Termination of approval. The code official is
authorized to terminate such permit for temporary equipment, systems or uses and to order the temporary equipment,
systems or uses to be discontinued.
SECTION 108
INSPECTIONS AND TESTING
[A] 108.1 General. The code official is authorized to
conduct such inspections as are deemed necessary to determine compliance with the provisions of this code.
Construction or work for which a permit is required shall be
subject to inspection by the code official, and such construction or work shall remain visible and able to be accessed for
2021 INTERNATIONAL PLUMBING CODE®
[A] 108.2.3 Approval required. Work shall not be done
beyond the point indicated in each successive inspection
without first obtaining the approval of the code official.
The code official, upon notification, shall make the
requested inspections and shall either indicate the portion
of the construction that is satisfactory as completed, or
notify the permit holder or his or her agent wherein the
same fails to comply with this code. Any portions that do
not comply shall be corrected and such portion shall not
be covered or concealed until authorized by the code
official.
[A] 108.2.4 Approved agencies. The code official is
authorized to accept reports of approved inspection agencies, provided that such agencies satisfy the requirements
as to qualifications and reliability.
1-5
SCOPE AND ADMINISTRATION
[A] 108.2.5 Evaluation and follow-up inspection
services. Prior to the approval of a closed, prefabricated
plumbing system and the issuance of a plumbing permit,
the code official shall require the submittal of an evaluation report on each prefabricated plumbing system
indicating the complete details of the plumbing system,
including a description of the system and its components,
the basis on which the plumbing system is being evaluated, test results and similar information, and other data
as necessary for the code official to determine conformance to this code.
[A] 108.2.5.1 Evaluation service. The code official
shall designate the evaluation service of an approved
agency as the evaluation agency, and review such
agency’s evaluation report for adequacy and conformance to this code.
[A] 108.2.5.2 Follow-up inspection. Except where
ready access is provided to all plumbing systems,
service equipment and accessories for complete
inspection at the site without disassembly or dismantling, the code official shall conduct the frequency of
in-plant inspections necessary to ensure conformance
to the approved evaluation report or shall designate an
independent, approved inspection agency to conduct
such inspections. The inspection agency shall furnish
the code official with the follow-up inspection manual
and a report of inspections on request, and the plumbing system shall have an identifying label permanently
affixed to the system indicating that factory inspections have been performed.
[A] 108.2.5.3 Test and inspection records. Required
test and inspection records shall be available to the
code official at all times during the fabrication of the
plumbing system and the erection of the building, or
such records as the code official designates shall be
filed.
[A] 108.3 Special inspections. Special inspections of alternative engineered design plumbing systems shall be
conducted in accordance with Sections 108.3.1 and 108.3.2.
[A] 108.3.1 Periodic inspection. The registered design
professional or designated inspector shall periodically
inspect and observe the alternative engineered design to
determine that the installation is in accordance with the
approved construction documents. Discrepancies shall be
brought to the immediate attention of the plumbing
contractor for correction. Records shall be kept of all
inspections.
[A] 108.3.2 Written report. The registered design
professional shall submit a final report in writing to the
code official upon completion of the installation, certifying that the alternative engineered design conforms to the
approved construction documents. A notice of approval
for the plumbing system shall not be issued until a written
certification has been submitted.
[A] 108.4 Testing. Plumbing work and systems shall be
tested as required in Section 312 and in accordance with
Sections 108.4.1 through 108.4.3. Tests shall be made by the
permit holder and observed by the code official.
1-6
[A] 108.4.1 New, altered, extended or repaired
systems. New plumbing systems and parts of existing
systems that have been altered, extended or repaired shall
be tested as prescribed herein to disclose leaks and
defects, except that testing is not required in the following
cases:
1.
2.
In any case that does not include addition to,
replacement, alteration or relocation of any water
supply, drainage or vent piping.
In any case where plumbing equipment is set up
temporarily for exhibition purposes.
[A] 108.4.2 Equipment, material and labor for tests.
Equipment, material and labor required for testing a
plumbing system or part thereof shall be furnished by the
permit holder.
[A] 108.4.3 Reinspection and testing. Where any work
or installation does not pass any initial test or inspection,
the necessary corrections shall be made to comply with
this code. The work or installation shall then be resubmitted to the code official for inspection and testing.
SECTION 109
FEES
*
**
[A] 109.1 Payment of fees. A permit shall not be valid until
the fees prescribed by law have been paid. An amendment to
a permit shall not be released until the additional fee, if any,
has been paid.
[A] 109.2 Schedule of permit fees. Where work requires a
permit, a fee for each permit shall be paid as required, in
accordance with the schedule as established by the applicable governing authority.
[A] 109.3 Work commencing before permit issuance. Any
person who commences any work on a plumbing system
before obtaining the necessary permits shall be subject to a
fee established by the code official that shall be in addition to
the required permit fees.
[A] 109.4 Related fees. The payment of the fee for the
construction, alteration, removal or demolition for work
done in connection to or concurrently with the work authorized by a permit shall not relieve the applicant or holder of
the permit from the payment of other fees that are prescribed
by law
[A] 109.5 Refunds. The code official is authorized to establish a refund policy.
*
SECTION 110
CONSTRUCTION DOCUMENTS
[A] 110.1 Construction documents. Construction documents, engineering calculations, diagrams and other such
data shall be submitted in two or more sets, or in a digital
format where allowed by the code official, with each application for a permit. The code official shall require
construction documents, computations and specifications to
be prepared and designed by a registered design professional
where required by state law. Construction documents shall
2021 INTERNATIONAL PLUMBING CODE®
**
SCOPE AND ADMINISTRATION
be drawn to scale and shall be of sufficient clarity to indicate
the location, nature and extent of the work proposed and
show in detail that the work conforms to the provisions of
this code. Construction documents for buildings more than
two stories in height shall indicate where penetrations will be
made for pipes, fittings and components and shall indicate
the materials and methods for maintaining required structural safety, fire-resistance rating and fireblocking.
Exception: The code official shall have the authority to
waive the submission of construction documents, calculations or other data if the nature of the work applied for is
such that the reviewing of construction documents is not
necessary to determine compliance with this code.
**
[A] 110.2 Retention of construction documents. One set of
approved construction documents shall be retained by the
code official for a period of not less than 180 days from date
of completion of the permitted work, or as required by state
or local laws.
One set of approved construction documents shall be
returned to the applicant, and said set shall be kept on the site
of the building or work at all times during which the work
authorized thereby is in progress.
**
SECTION 111
NOTICE OF APPROVAL
[A] 111.1 Approval. After the prescribed tests and inspections indicate that the work complies in all respects with this
code, a notice of approval shall be issued by the code
official.
[A] 111.1.1 Revocation. The code official is authorized
to, in writing, suspend or revoke a notice of approval
issued under the provisions of this code wherever the
notice is issued in error, or on the basis of incorrect information supplied, or where it is determined that the
building or structure, premise or portion thereof is in
violation of any ordinance or regulation or any of the
provisions of this code.
**
SECTION 112
SERVICE UTILITIES
[A] 112.1 Connection of service utilities. A person shall not
make connections from a utility, source of energy, fuel,
power, water system or sewer system to any building or
system that is regulated by this code for which a permit is
required until authorized by the code official.
[A] 112.2 Temporary connection. The code official shall
have the authority to authorize the temporary connection of
the building or system to the utility, source of energy, fuel,
power, water system or sewer system for the purpose of testing plumbing systems or for use under a temporary approval.
[A] 112.3 Authority to disconnect service utilities. The
code official shall have the authority to authorize disconnection of utility service to the building, structure or system
regulated by this code and the referenced codes and stan-
2021 INTERNATIONAL PLUMBING CODE®
dards in case of emergency where necessary to eliminate an
immediate hazard to life or property or where such utility
connection has been made without the approval required by
Section 112.1 or 112.2.
The code official shall notify the serving utility, and
wherever possible the owner or the owner’s authorized agent
and occupant of the building, structure or service system, of
the decision to disconnect prior to taking such action. If not
notified prior to disconnecting, the owner, the owner’s
authorized agent or occupant of the building, structure or
service system shall be notified in writing as soon as practical thereafter.
SECTION 113
STOP WORK ORDER
[A] 113.1 Authority. Where the code official finds any work
regulated by this code being performed in a manner contrary
to the provisions of this code or in a dangerous or unsafe
manner, the code official is authorized to issue a stop work
order.
[A] 113.2 Issuance. The stop work order shall be in writing
and shall be given to the owner of the property, the owner’s
authorized agent or the person performing the work. Upon
issuance of a stop work order, the cited work shall immediately cease. The stop work order shall state the reason for the
order and the conditions under which the cited work is
authorized to resume.
[A] 113.3 Emergencies. Where an emergency exists, the
code official shall not be required to give a written notice
prior to stopping the work.
[A] 113.4 Failure to comply. Any person who shall
continue any work after having been served with a stop work
order, except such work as that person is directed to perform
to remove a violation or unsafe condition, shall be subject to
fines established by the authority having jurisdiction.
SECTION 114
MEANS OF APPEALS
[A] 114.1 General. In order to hear and decide appeals of
orders, decisions or determinations made by the code official
relative to the application and interpretation of this code,
there shall be and is hereby created a board of appeals. The
board of appeals shall be appointed by the applicable
governing authority and shall hold office at its pleasure. The
board shall adopt rules of procedure for conducting its business and shall render all decisions and findings in writing to
the appellant with a duplicate copy to the code official.
[A] 114.2 Limitations on authority. An application for
appeal shall be based on a claim that the true intent of this
code or the rules legally adopted thereunder have been incorrectly interpreted, the provisions of this code do not fully
apply, or an equivalent or better form of construction is
proposed. The board shall not have authority to waive
requirements of this code or interpret the administration of
this code.
1-7
**
SCOPE AND ADMINISTRATION
[A] 114.3 Qualifications. The board of appeals shall consist
of members who are qualified by experience and training
and are not employees of the jurisdiction.
unsafe equipment is hereby declared to be a public nuisance
and shall be abated by repair, rehabilitation, demolition or
removal.
[A] 114.4 Administration. The code official shall take
immediate action in accordance with the decision of the
board.
[A] 115.6.1 Authority to condemn equipment. Where
the code official determines that any plumbing, or portion
thereof, regulated by this code has become hazardous to
life, health or property or has become unsanitary, the code
official shall order in writing that such plumbing either be
removed or restored to a safe or sanitary condition. A
time limit for compliance with such order shall be specified in the written notice. A person shall not use or
maintain defective plumbing after receiving such notice.
**
SECTION 115
VIOLATIONS
[A] 115.1 Unlawful acts. It shall be unlawful for any person,
firm or corporation to erect, construct, alter, repair, remove,
demolish or utilize any plumbing system, or cause same to
be done, in conflict with or in violation of any of the provisions of this code.
[A] 115.2 Notice of violation. The code official shall serve a
notice of violation or order to the person responsible for the
erection, installation, alteration, extension, repair, removal
or demolition of plumbing work in violation of the provisions of this code, or in violation of a detail statement or the
approved construction documents thereunder, or in violation
of a permit or certificate issued under the provisions of this
code. Such order shall direct the discontinuance of the illegal
action or condition and the abatement of the violation.
[A] 115.3 Prosecution of violation. If the notice of violation
is not complied with promptly, the code official shall request
the legal counsel of the jurisdiction to institute the appropriate proceeding at law or in equity to restrain, correct or abate
such violation, or to require the removal or termination of
the unlawful occupancy of the structure in violation of the
provisions of this code or of the order or direction made
pursuant thereto.
[A] 115.4 Violation penalties. Any person who shall violate
a provision of this code or shall fail to comply with any of
the requirements thereof or who shall erect, install, alter or
repair plumbing work in violation of the approved construction documents or directive of the code official, or of a
permit or certificate issued under the provisions of this code,
shall be guilty of a [SPECIFY OFFENSE], punishable by a fine
of not more than [AMOUNT] dollars or by imprisonment not
exceeding [NUMBER OF DAYS], or both such fine and imprisonment. Each day that a violation continues after due notice
has been served shall be deemed a separate offense.
[A] 115.5 Abatement of violation. The imposition of the
penalties herein prescribed shall not preclude the legal officer of the jurisdiction from instituting appropriate action to
prevent unlawful construction or to restrain, correct or abate
a violation, or to prevent illegal occupancy of a building,
structure or premises, or to stop an illegal act, conduct, business or utilization of the plumbing on or about any premises.
Where such plumbing is to be disconnected, written
notice as prescribed in Section 115.2 shall be given. In
cases of immediate danger to life or property, such
disconnection shall be made immediately without such
notice.
[A] 115.6.2 Authority to disconnect service utilities.
The code official shall have the authority to authorize
disconnection of utility service to the building, structure
or system regulated by the technical codes in case of an
emergency, where necessary, to eliminate an immediate
danger to life or property. Where possible, the owner or
the owner’s authorized agent and occupant of the building, structure or service system shall be notified of the
decision to disconnect utility service prior to taking such
action. If not notified prior to disconnecting, the owner,
the owner’s authorized agent or occupant of the building,
structure or service systems shall be notified in writing, as
soon as practical thereafter.
[A] 115.6.3 Connection after order to disconnect. A
person shall not make connections from any energy, fuel,
power supply or water distribution system or supply
energy, fuel or water to any equipment regulated by this
code that has been disconnected or ordered to be disconnected by the code official or the use of which has been
ordered to be discontinued by the code official until the
code official authorizes the reconnection and use of such
equipment.
Where any plumbing is maintained in violation of this
code, and in violation of any notice issued pursuant to the
provisions of this section, the code official shall institute
any appropriate action to prevent, restrain, correct or
abate the violation.
[A] 115.6 Unsafe plumbing. Any plumbing regulated by
this code that is unsafe or that constitutes a fire or health
hazard, insanitary condition, or is otherwise dangerous to
human life is hereby declared unsafe. Any use of plumbing
regulated by this code constituting a hazard to safety, health
or public welfare by reason of inadequate maintenance,
dilapidation, obsolescence, fire hazard, disaster, damage or
abandonment is hereby declared an unsafe use. Any such
1-8
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 2
DEFINITIONS
User note:
About this chapter: Codes, by their very nature, are technical documents. Every word, term and punctuation mark can add to or change
the meaning of a technical requirement. It is necessary to maintain a consensus on the specific meaning of each term contained in the
code. Chapter 2 performs this function by stating clearly what specific terms mean for the purpose of the code.
SECTION 201
GENERAL
201.1 Scope. Unless otherwise expressly stated, the following words and terms shall, for the purposes of this code, have
the meanings shown in this chapter.
201.2 Interchangeability. Words stated in the present tense
include the future; words stated in the masculine gender
include the feminine and neuter; the singular number
includes the plural and the plural the singular.
201.3 Terms defined in other codes. Where terms are not
defined in this code and are defined in the International
Building Code, International Fire Code, International Fuel
Gas Code or the International Mechanical Code, such terms
shall have the meanings ascribed to them as in those codes.
201.4 Terms not defined. Where terms are not defined
through the methods authorized by this section, such terms
shall have ordinarily accepted meanings such as the context
implies.
SECTION 202
GENERAL DEFINITIONS
ACCEPTED ENGINEERING PRACTICE. That which
conforms to accepted principles, tests or standards of nationally recognized technical or scientific authorities.
[M] ACCESS (TO). That which enables a fixture, appliance
or equipment to be reached by ready access or by a means
that first requires the removal or movement of a panel, door
or similar obstruction (see “Ready access”).
ACCESS COVER. A removable plate, usually secured by
bolts or screws, to permit access to a pipe or pipe fitting for
the purposes of inspection, repair or cleaning.
[BE] ACCESSIBLE. A site, building, facility or portion
thereof that complies with Chapter 11 of the International
Building Code.
ADAPTER FITTING. An approved connecting device that
suitably and properly joins or adjusts pipes and fittings that
do not otherwise fit together.
AIR ADMITTANCE VALVE. One-way valve designed to
allow air to enter the plumbing drainage system when negative pressures develop in the piping system. The device shall
close by gravity and seal the vent terminal at zero differential
2021 INTERNATIONAL PLUMBING CODE®
pressure (no-flow conditions) and under positive internal
pressures. The purpose of an air admittance valve is to
provide a method of allowing air to enter the plumbing drainage system without the use of a vent extended to open air and
to prevent sewer gases from escaping into a building.
AIR BREAK (Drainage System). A piping arrangement in
which a drain from a fixture, appliance or device discharges
indirectly into another fixture, receptacle or interceptor at a
point below the flood level rim and above the trap seal.
AIR GAP (Drainage System). The unobstructed vertical
distance through the free atmosphere between the outlet of
the waste pipe and the flood level rim of the receptacle into
which the waste pipe is discharging.
AIR GAP (Water Distribution System). The unobstructed
vertical distance through the free atmosphere between the
lowest opening from any pipe or faucet supplying water to a
tank, plumbing fixture or other device and the flood level rim
of the receptacle.
ALTERNATE ON-SITE NONPOTABLE WATER.
Nonpotable water from other than public utilities, on-site
surface sources and subsurface natural freshwater sources.
Examples of such water are graywater, on-site reclaimed
water, collected rainwater, captured condensate and rejected
water from reverse osmosis systems.
ALTERNATIVE ENGINEERED DESIGN. A plumbing
system that performs in accordance with the intent of Chapters 3 through 14 and provides an equivalent level of
performance for the protection of public health, safety and
welfare. The system design is not specifically regulated by
Chapters 3 through 14.
ANCHORS. See “Supports.”
ANTISIPHON. A term applied to valves or mechanical
devices that eliminate siphonage.
[A] APPROVED. Acceptable to the code official.
[A] APPROVED AGENCY. An established and recognized
agency that is regularly engaged in conducting tests or
furnishing inspection services, or furnishing product certification where such agency has been approved by the code
official.
AREA DRAIN. A receptacle designed to collect surface or
storm water from an open area.
2-1
DEFINITIONS
BACKFLOW. Pressure created by any means in the water
distribution system, which by being in excess of the pressure
in the water supply mains causes a potential backflow
condition.
Backpressure, low head. A pressure less than or equal to
4.33 psi (29.88 kPa) or the pressure exerted by a 10-foot
(3048 mm) column of water.
Backsiphonage. The backflow of potentially contaminated water into the potable water system as a result of the
pressure in the potable water system falling below atmospheric pressure of the plumbing fixtures, pools, tanks or
vats connected to the potable water distribution piping.
Water supply system. The flow of water or other liquids,
mixtures or substances into the distribution pipes of a
potable water supply from any source except the intended
source.
(762 mm) in developed length of pipe beyond the exterior
walls of the building and conveys the drainage to the building
sewer.
Combined. A building drain that conveys both sewage
and storm water or other drainage.
Sanitary. A building drain that conveys sewage only.
Storm. A building drain that conveys storm water or other
drainage, but not sewage.
BUILDING SEWER. That part of the drainage system that
extends from the end of the building drain and conveys the
discharge to a public sewer, private sewer, individual sewage
disposal system or other point of disposal.
Combined. A building sewer that conveys both sewage
and storm water or other drainage.
Sanitary. A building sewer that conveys sewage only.
BACKFLOW, DRAINAGE. A reversal of flow in the
drainage system.
Storm. A building sewer that conveys storm water or
other drainage, but not sewage.
BACKFLOW CONNECTION. Any arrangement whereby
backflow is possible.
BUILDING SUBDRAIN. That portion of a drainage system
that does not drain by gravity into the building sewer.
BACKFLOW PREVENTER. A backflow prevention
assembly, a backflow prevention device or other means or
method to prevent backflow into the potable water supply.
BUILDING TRAP. A device, fitting or assembly of fittings
installed in the building drain to prevent circulation of air
between the drainage system of the building and the building
sewer.
BACKWATER VALVE. A device or valve installed in the
building drain or sewer pipe where a sewer is subject to backflow, and that prevents drainage or waste from backing up
into a lower level or fixtures and causing a flooding
condition.
[BS] BASE FLOOD ELEVATION. A reference point,
determined in accordance with the building code, based on
the depth or peak elevation of flooding, including wave
height, which has a 1-percent (100-year flood) or greater
chance of occurring in any given year.
BATHROOM GROUP. A group of fixtures consisting of a
water closet, lavatory, bathtub or shower, including or
excluding a bidet, an emergency floor drain or both. Such
fixtures are located together on the same floor level.
BRANCH. Any part of the piping system except a riser, main
or stack.
BRANCH INTERVAL. A vertical measurement of
distance, 8 feet (2438 mm) or more in developed length,
between the connections of horizontal branches to a drainage
stack. Measurements are taken down the stack from the highest horizontal branch connection.
BRANCH VENT. A vent connecting one or more individual
vents with a vent stack or stack vent.
[A] BUILDING. Any structure utilized or intended for
supporting or sheltering any occupancy.
BUILDING DRAIN. That part of the lowest piping of a
drainage system that receives the discharge from soil, waste
and other drainage pipes inside and that extends 30 inches
2-2
CIRCUIT VENT. A vent that connects to a horizontal drainage branch and vents two traps to not more than eight traps or
trapped fixtures connected into a battery.
CIRCULATING HOT WATER SYSTEM. A specifically
designed water distribution system where one or more pumps
are operated in the service hot water piping to circulate heated
water from the water-heating equipment to fixture supply and
back to the water-heating equipment.
CISTERN. A small covered tank for storing water for a
home or farm. Generally, this tank stores rainwater to be
utilized for purposes other than in the potable water supply,
and such tank is placed underground in most cases.
CLEANOUT. An access opening in the drainage system
utilized for the removal of obstructions. Types of cleanouts
include a removable plug or cap, and a removable fixture or
fixture trap.
[A] CODE. These regulations, subsequent amendments
thereto or any emergency rule or regulation that the administrative authority having jurisdiction has lawfully adopted.
[A] CODE OFFICIAL. The officer or other designated
authority charged with the administration and enforcement of
this code, or a duly authorized representative.
COLLECTION PIPE. Unpressurized pipe used within the
collection system that drains on-site nonpotable water or rainwater to a storage tank by gravity.
COMBINATION FIXTURE. A fixture combining one sink
and laundry tray or a two- or three-compartment sink or laundry tray in one unit.
2021 INTERNATIONAL PLUMBING CODE®
DEFINITIONS
COMBINATION WASTE AND VENT SYSTEM. A
specially designed system of waste piping embodying the
horizontal wet venting of one or more sinks, lavatories, drinking fountains or floor drains by means of a common waste
and vent pipe adequately sized to provide free movement of
air above the flow line of the drain.
COMBINED BUILDING DRAIN. See “Building drain,
combined.”
COMBINED BUILDING SEWER. See “Building sewer,
combined.”
COMMON VENT. A vent connecting at the junction of two
fixture drains or to a fixture branch and serving as a vent for
both fixtures.
CONCEALED FOULING SURFACE. Any surface of a
plumbing fixture that is not readily visible and is not scoured
or cleansed with each fixture operation.
CONDUCTOR. A pipe inside the building that conveys
storm water from the roof to a storm or combined building
drain.
[A] CONSTRUCTION DOCUMENT. All of the written,
graphic and pictorial documents prepared or assembled for
describing the design, location and physical characteristics of
the elements of the project necessary for obtaining a building
permit. The construction drawings shall be drawn to an
appropriate scale.
CONTAMINATION. An impairment of the quality of the
potable water that creates an actual hazard to the public health
through poisoning or the spread of disease by sewage, industrial fluids or waste.
COPPER ALLOY. A metal alloy where the principle
component is copper.
CRITICAL LEVEL (C-L). An elevation (height) reference
point that determines the minimum height at which a backflow preventer or vacuum breaker is installed above the flood
level rim of the fixture or receptor served by the device. The
critical level is the elevation level below which there is a
potential for backflow to occur. If the critical level marking is
not indicated on the device, the bottom of the device shall
constitute the critical level.
CROSS CONNECTION. Any physical connection or
arrangement between two otherwise separate piping systems,
one of which contains potable water and the other either water
of unknown or questionable safety or steam, gas or chemical,
whereby there exists the possibility for flow from one system
to the other, with the direction of flow depending on the pressure differential between the two systems (see “Backflow”).
DEMAND RECIRCULATION WATER SYSTEM. A
water distribution system where one or more pumps prime the
service hot water piping with heated water upon a demand for
hot water.
DEPTH OF TRAP SEAL. The depth of liquid that would
have to be removed from a full trap before air could pass
through the trap.
2021 INTERNATIONAL PLUMBING CODE®
[BS] DESIGN FLOOD ELEVATION. The elevation of the
“design flood,” including wave height, relative to the datum
specified on the community’s legally designated flood hazard
map. In areas designated as Zone AO, the design flood elevation shall be the elevation of the highest existing grade of the
building’s perimeter plus the depth number (in feet) (mm)
specified on the flood hazard map. In areas designated as Zone
AO where a depth number is not specified on the map, the
depth number shall be taken as being equal to 2 feet (610 mm).
DEVELOPED LENGTH. The length of a pipeline
measured along the centerline of the pipe and fittings.
DISCHARGE PIPE. A pipe that conveys the discharge from
plumbing fixtures or appliances.
DRAIN. Any pipe that carries wastewater or waterborne
wastes in a building drainage system.
DRAINAGE FITTING. The type of fitting or fittings
utilized in the drainage system. Drainage fittings are similar
to cast-iron fittings, except that instead of having a bell and
spigot, drainage fittings are recessed and tapped to eliminate
ridges on the inside of the installed pipe.
DRAINAGE FIXTURE UNIT.
Drainage (dfu). A measure of the probable discharge into
the drainage system by various types of plumbing fixtures.
The drainage fixture-unit value for a particular fixture
depends on its volume rate of drainage discharge, on the
time duration of a single drainage operation and on the
average time between successive operations.
DRAINAGE SYSTEM. Piping within a public or private
premise that conveys sewage, rainwater or other liquid waste
to a point of disposal. A drainage system does not include the
mains of a public sewer system or a private or public sewage
treatment or disposal plant.
Building gravity. A drainage system that drains by gravity into the building sewer.
Sanitary. A drainage system that carries sewage and
excludes storm, surface and ground water.
Storm. A drainage system that carries rainwater, surface
water, subsurface water and similar liquid waste.
DRINKING FOUNTAIN. A plumbing fixture that is
connected to the potable water distribution system and the
drainage system. The fixture allows the user to obtain a drink
directly from a stream of flowing water without the use of any
accessories.
DUAL FLUSHING DEVICE. A feature that allows the user
to flush a water closet with either a reduced or full volume of
water, depending on bowl contents.
EFFECTIVE OPENING. The minimum cross-sectional
area at the point of water supply discharge, measured or
expressed in terms of the diameter of a circle or, if the opening is not circular, the diameter of a circle of equivalent crosssectional area. For faucets and similar fittings, the effective
opening shall be measured at the smallest orifice in the fitting
body or in the supply piping to the fitting.
2-3
DEFINITIONS
EMERGENCY FLOOR DRAIN. A floor drain that does
not receive the discharge of any drain or indirect waste pipe,
and that protects against damage from accidental spills,
fixture overflows and leakage.
ESSENTIALLY NONTOXIC TRANSFER FLUID.
Fluids having a Gosselin rating of 1, including propylene
glycol; mineral oil; polydimethylsiloxane; hydrochlorofluorocarbon, chlorofluorocarbon and carbon refrigerants; and
FDA-approved boiler water additives for steam boilers.
ESSENTIALLY TOXIC TRANSFER FLUID. Soil, waste
or graywater and fluids having a Gosselin rating of 2 or more,
including ethylene glycol, hydrocarbon oils, ammonia refrigerants and hydrazine.
EXISTING INSTALLATION. Any plumbing system regulated by this code that was legally installed prior to the
effective date of this code, or for which a permit to install has
been issued.
FAUCET. A valve end of a water pipe through which water
is drawn from or held within the pipe.
FILL VALVE. A water supply valve, opened or closed by
means of a float or similar device, utilized to supply water to
a tank. An antisiphon fill valve contains an antisiphon device
in the form of an approved air gap or vacuum breaker that is
an integral part of the fill valve unit and that is positioned on
the discharge side of the water supply control valve.
FIXTURE. See “Plumbing fixture.”
FIXTURE BRANCH. A drain serving two or more fixtures
that discharges to another drain or to a stack.
FIXTURE DRAIN. The drain from the trap of a fixture to a
junction with any other drain pipe.
FIXTURE FITTING.
Supply fitting. A fitting that controls the volume, direction of flow or both of water, and is either attached to or
accessed from a fixture, or is used with an open or atmospheric discharge.
Waste fitting. A combination of components that conveys
the sanitary waste from the outlet of a fixture to the
connection to the sanitary drainage system.
FIXTURE SUPPLY. The water supply pipe connecting a
fixture to a branch water supply pipe or directly to a main
water supply pipe.
[BS] FLOOD HAZARD AREA. The greater of the following two areas:
1. The area within a flood plain subject to a 1-percent or
greater chance of flooding in any given year.
2. The area designated as a flood hazard area on a
community’s flood hazard map or as otherwise
legally designated.
FLOOD LEVEL RIM. The edge of the receptacle from
which water overflows.
2-4
FLOW CONTROL (Vented). A device installed upstream
from the interceptor having an orifice that controls the rate of
flow through the interceptor and an air intake (vent) downstream from the orifice that allows air to be drawn into the
flow stream.
FLOW PRESSURE. The pressure in the water supply pipe
near the faucet or water outlet while the faucet or water outlet
is wide open and flowing.
FLUSH TANK. A tank designed with a fill valve and flush
valve to flush the contents of the bowl or usable portion of the
fixture.
FLUSHOMETER TANK. A device integrated within an air
accumulator vessel that is designed to discharge a predetermined quantity of water to fixtures for flushing purposes.
FLUSHOMETER VALVE. A valve attached to a pressurized water supply pipe and designed so that when activated,
the valve opens the line for direct flow into the fixture at a rate
and quantity to operate the fixture properly, and then gradually closes to reseal fixture traps and avoid water hammer.
FULL-OPEN VALVE. A water control or shutoff component in the water supply system piping that, where adjusted
for maximum flow, the flow path through the component’s
closure member is not a restriction in the component’s
through-flow area.
GRAYWATER. Waste discharged from lavatories, bathtubs, showers, clothes washers and laundry trays.
GREASE INTERCEPTOR.
Fats, oils and greases (FOG) disposal system. A plumbing appurtenance that reduces nonpetroleum fats, oils and
greases in effluent by separation or mass and volume
reduction.
Gravity. Plumbing appurtenances of not less than 500
gallons (1893 L) capacity that are installed in the sanitary
drainage system to intercept free-floating fats, oils and
grease from wastewater discharge. Separation is accomplished by gravity during a retention time of not less than
30 minutes.
Hydromechanical. Plumbing appurtenances that are
installed in the sanitary drainage system to intercept freefloating fats, oils and grease from wastewater discharge.
Continuous separation is accomplished by air entrainment,
buoyancy and interior baffling.
GREASE REMOVAL DEVICE, AUTOMATIC (GRD).
A plumbing appurtenance that is installed in the sanitary
drainage system to intercept free-floating fats, oils and grease
from wastewater discharge. Such a device operates on a timeor event-controlled basis and has the ability to remove freefloating fats, oils and grease automatically without intervention from the user except for maintenance.
GREASE-LADEN WASTE. Effluent discharge that is
produced from food processing, food preparation or other
sources where grease, fats and oils enter automatic dishwater
prerinse stations, sinks or other appurtenances.
2021 INTERNATIONAL PLUMBING CODE®
DEFINITIONS
GRIDDED WATER DISTRIBUTION SYSTEM. A water
distribution system where every water distribution pipe is
interconnected so as to provide two or more paths to each
fixture supply pipe.
GROUP WASH FIXTURE. A type of lavatory that allows
more than one person to utilize the fixture at the same time.
The fixture has one or more drains and one or more faucets.
HANGERS. See “Supports.”
HORIZONTAL BRANCH DRAIN. A drainage branch
pipe extending laterally from a soil or waste stack or building
drain, with or without vertical sections or branches, that
receives the discharge from two or more fixture drains or
branches and conducts the discharge to the soil or waste stack
or to the building drain.
HORIZONTAL PIPE. Any pipe or fitting that makes an
angle of less than 45 degrees (0.79 rad) with a horizontal
plane.
HOT WATER. Water at a temperature greater than or equal
to 110°F (43°C).
HOUSE TRAP. See “Building trap.”
INDIRECT WASTE PIPE. A waste pipe that does not
connect directly with the drainage system, but that discharges
into the drainage system through an air break or air gap into
a trap, fixture, receptor or interceptor.
INDIVIDUAL SEWAGE DISPOSAL SYSTEM. A
system for disposal of domestic sewage by means of a septic
tank, cesspool or mechanical treatment, designed for utilization apart from a public sewer to serve a single establishment
or building.
INDIVIDUAL VENT. A pipe installed to vent a fixture trap
and that connects with the vent system above the fixture
served or terminates in the open air.
INDIVIDUAL WATER SUPPLY. A water supply that
serves one or more families, and that is not an approved
public water supply.
INTERCEPTOR. A device designed and installed to separate and retain for removal, by automatic or manual means,
deleterious, hazardous or undesirable matter from normal
wastes, while permitting normal sewage or wastes to
discharge into the drainage system by gravity.
JOINT.
Expansion. A loop, return bend or return offset that
provides for the expansion and contraction in a piping
system and is utilized in tall buildings or where there is a
rapid change of temperature, as in power plants, steam
rooms and similar occupancies.
Flexible. Any joint between two pipes that permits one
pipe to be deflected or moved without movement or
deflection of the other pipe.
Mechanical. See “Mechanical joint.”
Slip. A type of joint made by means of a washer or a
special type of packing compound in which one pipe is
slipped into the end of an adjacent pipe.
2021 INTERNATIONAL PLUMBING CODE®
LEADER. An exterior drainage pipe for conveying storm
water from roof or gutter drains to an approved means of
disposal.
LEAD-FREE SOLDER AND FLUX. Containing not more
than 0.2-percent lead.
MACERATING TOILET SYSTEM. An assembly consisting of a water closet and sump with a macerating pump that
is designed to collect, grind and pump wastes from the water
closet and up to two other fixtures connected to the sump.
MAIN. The principal pipe artery to which branches are
connected.
MANIFOLD. See “Plumbing appurtenance.”
[M] MECHANICAL JOINT. A connection between pipes,
fittings, or pipes and fittings that is not screwed, caulked,
threaded, soldered, solvent cemented, brazed, welded or heat
fused. A joint in which compression is applied along the
centerline of the pieces being joined. In some applications,
the joint is part of a coupling, fitting or adapter.
MEDICAL GAS SYSTEM. The complete system to convey
medical gases for direct patient application from central
supply systems (bulk tanks, manifolds and medical air
compressors), with pressure and operating controls, alarm
warning systems, related components and piping networks
extending to station outlet valves at patient use points.
MEDICAL VACUUM SYSTEM. A system consisting of
central-vacuum-producing equipment with pressure and
operating controls, shutoff valves, alarm-warning systems,
gauges and a network of piping extending to and terminating
with suitable station inlets at locations where patient suction
may be required.
METER. A measuring device used to collect data and indicate water usage.
NONPOTABLE WATER. Water not safe for drinking,
personal or culinary utilization.
NUISANCE. Public nuisance as known in common law or in
equity jurisprudence; whatever is dangerous to human life or
detrimental to health; whatever structure or premises is not
sufficiently ventilated, sewered, drained, cleaned or lighted,
with respect to its intended occupancy; and whatever renders
the air, or human food, drink or water supply unwholesome.
[A] OCCUPANCY. The purpose for which a building or
portion thereof is utilized or occupied.
OFFSET. A combination of approved bends that makes two
changes in direction bringing one section of the pipe out of
line but into a line parallel with the other section.
ON-SITE NONPOTABLE WATER REUSE SYSTEM. A
water system for the collection, treatment, storage, distribution and reuse of nonpotable water generated on site,
including but not limited to a graywater system. This definition does not include a rainwater harvesting system.
OPEN AIR. Outside the structure.
PLUMBING. The practice, materials and fixtures utilized in
the installation, maintenance, extension and alteration of all
piping, fixtures, plumbing appliances and plumbing appurte-
2-5
DEFINITIONS
nances, within or adjacent to any structure, in connection with
sanitary drainage or storm drainage facilities; venting
systems; and public or private water supply systems.
PLUMBING APPLIANCE. Water or drain-connected
devices intended to perform a special function. These devices
have their operation or control dependent on one or more
energized components, such as motors, controls or heating
elements. Such devices are manually adjusted or controlled
by the owner or operator, or are operated automatically
through one or more of the following actions: a time cycle, a
temperature range, a pressure range, a measured volume or
weight.
PLUMBING APPURTENANCE. A manufactured device,
prefabricated assembly or on-the-job assembly of component
parts that is an adjunct to the basic piping system and plumbing fixtures. An appurtenance does not demand additional
water supply and does not add any discharge load to a fixture
or to the drainage system.
PLUMBING FIXTURE. A receptacle or device that is
connected to a water supply system or discharges to a drainage system or both. Such receptacles or devices require a
supply of water; or discharge liquid waste or liquid-borne
solid waste; or require a supply of water and discharge waste
to a drainage system.
PLUMBING SYSTEM. A system that includes the water
distribution pipes; plumbing fixtures and traps; water-treating
or water-using equipment; soil, waste and vent pipes; and
building drains; in addition to their respective connections,
devices and appurtenances within a structure or premises; and
the water service, building sewer and building storm sewer
serving such structure or premises.
POLLUTION. An impairment of the quality of the potable
water to a degree that does not create a hazard to public health
but that does adversely and unreasonably affect the aesthetic
qualities of such potable water for domestic use.
POTABLE WATER. Water free from impurities present in
amounts sufficient to cause disease or harmful physiological
effects and conforming to the bacteriological and chemical
quality requirements of the Public Health Service Drinking
Water Standards or the regulations of the public health
authority having jurisdiction.
[M] PRESS-CONNECT JOINT. A permanent mechanical
joint incorporating an elastomeric seal or an elastomeric seal
and corrosion-resistant grip ring. The joint is made with a
pressing tool and jaw or ring approved by the fitting
manufacturer.
PRIVATE. In the classification of plumbing fixtures,
“private” applies to fixtures that are not public.
PUBLIC OR PUBLIC UTILIZATION. In the classification of plumbing fixtures, “public” applies to fixtures with
unrestricted exposure to walk-in traffic.
PUBLIC SWIMMING POOL. A pool, other than a residential pool, that is intended to be used for swimming or bathing
and is operated by an owner, lessee, operator, licensee or
concessionaire, regardless of whether a fee is charged for use.
2-6
PUBLIC WATER MAIN. A water supply pipe for public
utilization controlled by public authority.
PUSH-FIT FITTING. A mechanical fitting that joins pipes
or tubes and achieves a seal by mating the pipe or tube into
the fitting.
QUICK-CLOSING VALVE. A valve or faucet that closes
automatically when released manually or that is controlled by
a mechanical means for fast-action closing.
RAINWATER. Water from natural precipitation.
[M] READY ACCESS. That which enables a fixture, appliance or equipment to be directly reached without requiring
the removal or movement of any panel, door or similar
obstruction and without the use of a portable ladder, step stool
or similar device.
RECLAIMED WATER. Nonpotable water that has been
derived from the treatment of wastewater by a facility or
system licensed or permitted to produce water meeting the
jurisdiction’s water requirements for its intended uses. Also
known as “recycled water.”
REDUCED PRESSURE PRINCIPLE BACKFLOW
PREVENTION ASSEMBLY. A backflow prevention
device consisting of two independently acting check valves,
internally force-loaded to a normally closed position and
separated by an intermediate chamber (or zone) in which
there is an automatic relief means of venting to the atmosphere, internally loaded to a normally open position between
two tightly closing shutoff valves and with a means for testing for tightness of the checks and opening of the relief
means.
[A] REGISTERED DESIGN PROFESSIONAL. An individual who is registered or licensed to practice their
respective design profession, as defined by the statutory
requirements of the professional registration laws of the state
or jurisdiction in which the project is to be constructed.
RELIEF VALVE.
Pressure relief valve. A pressure-actuated valve held
closed by a spring or other means and designed to relieve
pressure automatically at the pressure at which such valve
is set.
Temperature and pressure relief (T&P) valve. A
combination relief valve designed to function as both a
temperature relief and a pressure relief valve.
Temperature relief valve. A temperature-actuated valve
designed to discharge automatically at the temperature at
which such valve is set.
RELIEF VENT. A vent whose primary function is to
provide circulation of air between drainage and vent systems.
RIM. An unobstructed open edge of a fixture.
RISER. See “Water pipe, riser.”
ROOF DRAIN. A drain installed to receive water collecting
on the surface of a roof and to discharge such water into a
leader or a conductor.
2021 INTERNATIONAL PLUMBING CODE®
DEFINITIONS
ROUGH-IN. Parts of the plumbing system that are installed
prior to the installation of fixtures. This includes drainage,
water supply, vent piping and the necessary fixture supports
and any fixtures that are built into the structure.
SELF-CLOSING FAUCET. A faucet containing a valve
that automatically closes upon deactivation of the opening
means.
SEPARATOR. See “Interceptor.”
SEWAGE. Any liquid waste containing animal or vegetable
matter in suspension or solution, including liquids containing
chemicals in solution.
SEWAGE EJECTOR. A device for lifting sewage by
entraining the sewage in a high-velocity jet of steam, air or
water.
SEWER.
SUMP PUMP. An automatic water pump powered by an
electric motor for the removal of drainage, except raw
sewage, from a sump, pit or low point.
SUMP VENT. A vent from pneumatic sewage ejectors, or
similar equipment, that terminates separately to the open air.
SUPPORTS. Devices for supporting and securing pipe,
fixtures and equipment.
SWIMMING POOL. A permanent or temporary structure
that is intended to be used for swimming, bathing or wading
and that is designed and manufactured or built to be
connected to a circulation system. A swimming pool can be
open to the public regardless of whether a fee is charged for
its use or can be accessory to a residential setting where the
pool is available only to the household and guests of the
household.
Building sewer. See “Building sewer.”
TEMPERED WATER. Water having a temperature range
between 85°F (29°C) and 110°F (43°C).
Public sewer. That part of the drainage system of pipes,
installed and maintained by a city, township, county,
public utility company or other public entity, and located
on public property, in the street or in an approved dedicated easement of public or community use.
THIRD-PARTY CERTIFICATION AGENCY. An
approved agency operating a product or material certification
system that incorporates initial product testing, assessment
and surveillance of a manufacturer’s quality control system.
Sanitary sewer. A sewer that carries sewage and excludes
storm, surface and ground water.
Storm sewer. A sewer that conveys rainwater, surface
water, subsurface water and similar liquid wastes.
SLOPE. The fall (pitch) of a line of pipe in reference to a
horizontal plane. In drainage, the slope is expressed as the fall
in units vertical per units horizontal (percent) for a length of
pipe.
SOIL PIPE. A pipe that conveys sewage containing fecal
matter to the building drain or building sewer.
SPILLPROOF VACUUM BREAKER. An assembly
consisting of one check valve force-loaded closed and an airinlet vent valve force-loaded open to atmosphere, positioned
downstream of the check valve, and located between and
including two tightly closing shutoff valves and a test cock.
STACK. A general term for any vertical line of soil, waste,
vent or inside conductor piping that extends through not
fewer than one story with or without offsets.
STACK VENT. The extension of a soil or waste stack above
the highest horizontal drain connected to the stack.
THIRD-PARTY CERTIFIED. Certification obtained by
the manufacturer indicating that the function and performance characteristics of a product or material have been
determined by testing and ongoing surveillance by an
approved third-party certification agency. Assertion of certification is in the form of identification in accordance with the
requirements of the third-party certification agency.
TOILET FACILITY. A room or space that contains not less
than one water closet and one lavatory.
TRAP. A fitting or device that provides a liquid seal to
prevent the emission of sewer gases without materially
affecting the flow of sewage or wastewater through the trap.
TRAP SEAL. The vertical distance between the weir and the
top of the dip of the trap.
UNSTABLE GROUND. Earth that does not provide a
uniform bearing for the barrel of the sewer pipe between the
joints at the bottom of the pipe trench.
VACUUM. Any pressure less than that exerted by the
atmosphere.
STACK VENTING. A method of venting a fixture or
fixtures through the soil or waste stack.
VACUUM BREAKER. A type of backflow preventer
installed on openings subject to normal atmospheric pressure
that prevents backflow by admitting atmospheric pressure
through ports to the discharge side of the device.
STORM DRAIN. See “Drainage system, storm.”
VENT PIPE. See “Vent system.”
STORM WATER. Natural precipitation, including snowmelt, that has contacted a surface at or below grade.
VENT STACK. A vertical vent pipe installed primarily for
the purpose of providing circulation of air to and from any
part of the drainage system.
[A] STRUCTURE. That which is built or constructed.
SUBSOIL DRAIN. A drain that collects subsurface water or
seepage water and conveys such water to a place of disposal.
SUMP. A tank or pit that receives sewage or liquid waste,
located below the normal grade of the gravity system and that
must be emptied by mechanical means.
2021 INTERNATIONAL PLUMBING CODE®
VENT SYSTEM. A pipe or pipes installed to provide a flow
of air to or from a drainage system, or to provide a circulation
of air within such system to protect trap seals from siphonage
and backpressure.
VERTICAL PIPE. Any pipe or fitting that makes an angle
of 45 degrees (0.79 rad) or more with the horizontal.
2-7
DEFINITIONS
WALL-HUNG WATER CLOSET. A wall-mounted water
closet installed in such a way that the fixture does not touch
the floor.
Drilled. A well constructed by making a hole in the
ground with a drilling machine of any type and installing
a casing and screen.
WASTE. The discharge from any fixture, appliance, area or
appurtenance that does not contain fecal matter.
Driven. A well constructed by driving a pipe in the
ground. The drive pipe is usually fitted with a well point
and screen.
WASTE PIPE. A pipe that conveys only waste.
WASTE RECEPTOR. A floor sink, standpipe, hub drain or
floor drain that receives the discharge of one or more indirect
waste pipes.
WATER COOLER. A drinking fountain that incorporates a
means of reducing the temperature of the water supplied to it
from the potable water distribution system.
WATER DISPENSER. A plumbing fixture that is manually
controlled by the user for the purpose of dispensing potable
drinking water into a receptacle such as a cup, glass or bottle.
Such fixture is connected to the potable water distribution
system of the premises.
Dug. A well constructed by excavating a large-diameter
shaft and installing a casing.
WHIRLPOOL BATHTUB. A plumbing appliance consisting of a bathtub fixture that is equipped and fitted with a
circulating piping system designed to accept, circulate and
discharge bathtub water upon each use.
YOKE VENT. A pipe connecting upward from a soil or
waste stack to a vent stack for the purpose of preventing pressure changes in the stacks.
[M] WATER HEATER. Any heating appliance or equipment that heats potable water and supplies such water to the
potable hot water distribution system.
WATER MAIN. A water supply pipe or system of pipes,
installed and maintained by a city, township, county, public
utility company or other public entity, on public property, in
the street or in an approved dedicated easement of public or
community use.
WATER OUTLET. A discharge opening through which
water is supplied to a fixture, into the atmosphere (except into
an open tank that is part of the water supply system), to a
boiler or heating system, or to any devices or equipment that
require water to operate but are not part of the plumbing
system.
WATER PIPE.
Riser. A water supply pipe that extends one full story or
more to convey water to branches or to a group of fixtures.
Water distribution pipe. A pipe within the structure or on
the premises that conveys water from the water service
pipe, or from the meter when the meter is at the structure,
to the points of utilization.
Water service pipe. The pipe from the water main or
other source of potable water supply, or from the meter
when the meter is at the public right of way, to the water
distribution system of the building served.
WATER SUPPLY SYSTEM. The water service pipe, water
distribution pipes, and the necessary connecting pipes,
fittings, control valves and all appurtenances in or adjacent to
the structure or premises.
WATER-HAMMER ARRESTOR. A device utilized to
absorb the pressure surge (water hammer) that occurs when
water flow is suddenly stopped in a water supply system.
WELL.
Bored. A well constructed by boring a hole in the ground
with an auger and installing a casing.
2-8
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 3
GENERAL REGULATIONS
User note:
About this chapter: Chapter 3 covers general regulations for plumbing installations. As many of these requirements would need to be
repeated in Chapters 3 through 14, placing such requirements in only one location eliminates code development coordination issues associated with the same requirement in multiple locations. These general requirements can be superseded by more specific requirements for
certain applications in Chapters 3 through 14.
SECTION 301
GENERAL
301.1 Scope. The provisions of this chapter shall govern the
general regulations regarding the installation of plumbing
not specific to other chapters.
301.2 System installation. Plumbing shall be installed with
due regard to preservation of the strength of structural
members and prevention of damage to walls and other
surfaces through fixture usage.
301.3 Connections to drainage system. Plumbing fixtures,
drains, appurtenances and appliances used to receive or
discharge liquid waste or sewage shall be directly connected
to the sanitary drainage system of the building or premises,
in accordance with the requirements of this code. This
section shall not be construed to prevent indirect waste
systems required by Chapter 8.
Exception: Bathtubs, showers, lavatories, clothes washers and laundry trays shall not be required to discharge to
the sanitary drainage system where such fixtures
discharge to an approved system in accordance with
Chapters 13 and 14.
301.4 Connections to water supply. Every plumbing
fixture, device or appliance requiring or using water for its
proper operation shall be directly or indirectly connected to
the water supply system in accordance with the provisions of
this code.
301.5 Pipe, tube and fitting sizes. Unless otherwise indicated, the pipe, tube and fitting sizes specified in this code
are expressed in nominal or standard sizes as designated in
the referenced material standards.
301.6 Prohibited locations. Plumbing systems shall not be
located in an elevator shaft or in an elevator equipment
room.
Exception: Floor drains, sumps and sump pumps shall be
permitted at the base of the shaft, provided that they are
indirectly connected to the plumbing system and comply
with Section 1003.4.
301.7 Conflicts. In instances where conflicts occur between
this code and the manufacturer’s installation instructions, the
more restrictive provisions shall apply.
2021 INTERNATIONAL PLUMBING CODE®
SECTION 302
EXCLUSION OF MATERIALS
DETRIMENTAL TO THE SEWER SYSTEM
302.1 Detrimental or dangerous materials. Ashes, cinders
or rags; flammable, poisonous or explosive liquids or gases;
oil, grease or any other insoluble material capable of
obstructing, damaging or overloading the building drainage
or sewer system, or capable of interfering with the normal
operation of the sewage treatment processes, shall not be
deposited, by any means, into such systems.
302.2 Industrial wastes. Waste products from manufacturing or industrial operations shall not be introduced into the
public sewer until it has been determined by the code official
or other authority having jurisdiction that the introduction
thereof will not damage the public sewer system or interfere
with the functioning of the sewage treatment plant.
SECTION 303
MATERIALS
303.1 Identification. Each length of pipe and each pipe
fitting, trap, fixture, material and device utilized in a plumbing system shall bear the identification of the manufacturer
and any markings required by the applicable referenced
standards.
303.2 Installation of materials. Materials used shall be
installed in strict accordance with the standards under which
the materials are accepted and approved. In the absence of
such installation procedures, the manufacturer’s instructions
shall be followed. Where the requirements of referenced
standards or manufacturer’s installation instructions do not
conform to minimum provisions of this code, the provisions
of this code shall apply.
303.3 Plastic pipe, fittings and components. Plastic pipe,
fittings and components shall be third-party certified as
conforming to NSF 14.
303.4 Third-party certification. Plumbing products and
materials required by the code to be in compliance with a
referenced standard shall be listed by a third-party certification agency as complying with the referenced standards.
Products and materials shall be identified in accordance with
Section 303.1.
3-1
GENERAL REGULATIONS
303.5 Cast-iron soil pipe, fittings and components. Castiron soil pipes and fittings, and the couplings used to join
these products together, shall be third-party listed and
labeled. Third-party certifiers or inspectors shall comply
with the minimum inspection requirements of Annex A or
Annex A1 of the ASTM and CISPI product standards indicated in the code for such products.
SECTION 304
RODENTPROOFING
304.1 General. Plumbing systems shall be designed and
installed in accordance with Sections 304.2 through 304.4 to
prevent rodents from entering structures.
304.2 Strainer plates. Strainer plates on drain inlets shall be
designed and installed so that all openings are not greater
than 1/2 inch (12.7 mm) in least dimension.
304.3 Meter boxes. Meter boxes shall be constructed in such
a manner that rodents are prevented from entering a structure
by way of the water service pipes connecting the meter box
and the structure.
304.4 Openings for pipes. In or on structures where openings have been made in walls, floors or ceilings for the
passage of pipes, the annular space between the pipe and the
sides of the opening shall be sealed with caulking materials
or closed with gasketing systems compatible with the piping
materials and locations.
SECTION 305
PROTECTION OF PIPES AND
PLUMBING SYSTEM COMPONENTS
305.1 Protection against contact. Metallic piping, except
for cast iron, ductile iron and galvanized steel, shall not be
placed in direct contact with steel framing members,
concrete or cinder walls and floors or other masonry. Metallic piping shall not be placed in direct contact with corrosive
soil. Where sheathing is used to prevent direct contact, the
sheathing shall have a thickness of not less than 0.008 inch
(8 mil) (0.203 mm) and the sheathing shall be made of plastic. Where sheathing protects piping that penetrates concrete
or masonry walls or floors, the sheathing shall be installed in
a manner that allows movement of the piping within the
sheathing.
305.2 Stress and strain. Piping in a plumbing system shall
be installed so as to prevent strains and stresses that exceed
the structural strength of the pipe. Where necessary, provisions shall be made to protect piping from damage resulting
from expansion, contraction and structural settlement.
freezing temperatures unless adequate provision is made to
protect such pipes from freezing by insulation or heat or
both. Exterior water supply system piping shall be installed
not less than 6 inches (152 mm) below the frost line and not
less than 12 inches (305 mm) below grade.
305.4.1 Sewer depth. Building sewers that connect to
private sewage disposal systems shall be installed not less
than [NUMBER] inches (mm) below finished grade at the
point of septic tank connection. Building sewers shall be
installed not less than [NUMBER] inches (mm) below
grade.
305.5 Waterproofing of openings. Joints at the roof and
around vent pipes shall be made watertight by the use of
lead, copper, galvanized steel, aluminum, plastic or other
approved flashings or flashing material. Exterior wall openings shall be made watertight.
305.6 Protection against physical damage. In concealed
locations where piping, other than cast iron or galvanized
steel, is installed through holes or notches in studs, joists,
rafters or similar members less than 11/4 inches (32 mm)
from the nearest edge of the member, the pipe shall be
protected by steel shield plates. Such shield plates shall have
a thickness of not less than 0.0575 inch (1.463 mm) (No. 16
gage). Such plates shall cover the area of the pipe where the
member is notched or bored, and shall extend not less than 2
inches (51 mm) above sole plates and below top plates.
305.7 Protection of components of plumbing system.
Components of a plumbing system installed along alleyways, driveways, parking garages or other locations exposed
to damage shall be recessed into the wall or otherwise
protected in an approved manner.
SECTION 306
TRENCHING, EXCAVATION AND BACKFILL
306.1 Support of piping. Buried piping shall be supported
throughout its entire length.
306.2 Trenching and bedding. Where trenches are excavated such that the bottom of the trench forms the bed for the
pipe, solid and continuous load-bearing support shall be
provided between joints. Bell holes, hub holes and coupling
holes shall be provided at points where the pipe is joined.
Such pipe shall not be supported on blocks to grade. In
instances where the material manufacturer’s installation
instructions are more restrictive than those prescribed by the
code, the material shall be installed in accordance with the
more restrictive requirement.
305.3 Pipes through foundation walls. Any pipe that
passes through a foundation wall shall be provided with a
relieving arch, or a pipe sleeve pipe shall be built into the
foundation wall. The sleeve shall be two pipe sizes greater
than the pipe passing through the wall.
306.2.1 Overexcavation. Where trenches are excavated
below the installation level of the pipe such that the
bottom of the trench does not form the bed for the pipe,
the trench shall be backfilled to the installation level of
the bottom of the pipe with sand or fine gravel placed in
layers not greater than 6 inches (152 mm) in depth and
such backfill shall be compacted after each placement.
305.4 Freezing. Water, soil and waste pipes shall not be
installed outside of a building, in attics or crawl spaces,
concealed in outside walls, or in any other place subjected to
306.2.2 Rock removal. Where rock is encountered in
trenching, the rock shall be removed to not less than 3
inches (76 mm) below the installation level of the bottom
3-2
2021 INTERNATIONAL PLUMBING CODE®
GENERAL REGULATIONS
of the pipe, and the trench shall be backfilled to the installation level of the bottom of the pipe with sand tamped in
place so as to provide uniform load-bearing support for
the pipe between joints. The pipe, including the joints,
shall not rest on rock at any point.
306.2.3 Soft load-bearing materials. If soft materials of
poor load-bearing quality are found at the bottom of the
trench, stabilization shall be achieved by overexcavating
not less than two pipe diameters and backfilling to the
installation level of the bottom of the pipe with fine
gravel, crushed stone or a concrete foundation. The
concrete foundation shall be bedded with sand tamped
into place so as to provide uniform load-bearing support
for the pipe between joints.
306.3 Backfilling. Backfill shall be free from discarded
construction material and debris. Loose earth free from
rocks, broken concrete and frozen chunks shall be placed in
the trench in 6-inch (152 mm) layers and tamped in place
until the crown of the pipe is covered by 12 inches (305 mm)
of tamped earth. The backfill under and beside the pipe shall
be compacted for pipe support. Backfill shall be brought up
evenly on both sides of the pipe so that the pipe remains
aligned. In instances where the manufacturer’s instructions
for materials are more restrictive than those prescribed by
the code, the material shall be installed in accordance with
the more restrictive requirement.
306.4 Tunneling. Where pipe is to be installed by tunneling,
jacking or a combination of both, the pipe shall be protected
from damage during installation and from subsequent
uneven loading. Where earth tunnels are used, adequate
supporting structures shall be provided to prevent future
settling or caving.
SECTION 307
STRUCTURAL SAFETY
307.1 General. In the process of installing or repairing any
part of a plumbing and drainage installation, the finished
floors, walls, ceilings, tile work or any other part of the
building or premises that must be changed or replaced shall
be left in a safe structural condition in accordance with the
requirements of the International Building Code.
307.2 Cutting, notching or bored holes. A framing
member shall not be cut, notched or bored in excess of
limitations specified in the International Building Code.
307.3 Penetrations of floor/ceiling assemblies and fireresistance-rated assemblies. Penetrations of floor/ceiling
assemblies and assemblies required to have a fire-resistance
rating shall be protected in accordance with the International
Building Code.
[BS] 307.4 Alterations to trusses. Truss members and
components shall not be cut, drilled, notched, spliced or
otherwise altered in any way without written concurrence
and approval of a registered design professional. Alterations
resulting in the addition of loads to any member (such as
HVAC equipment and water heaters) shall not be permitted
without verification that the truss is capable of supporting
such additional loading.
2021 INTERNATIONAL PLUMBING CODE®
307.5 Protection of footings. Trenching installed parallel to
footings and walls shall not extend into the bearing plane of
a footing or wall. The upper boundary of the bearing plane is
a line that extends downward, at an angle of 45 degrees (0.79
rad) from horizontal, from the outside bottom edge of the
footing or wall.
307.6 Piping materials exposed within plenums. Piping
materials exposed within plenums shall comply with the
provisions of the International Mechanical Code.
SECTION 308
PIPING SUPPORT
308.1 General. Plumbing piping shall be supported in accordance with this section.
308.2 Piping seismic supports. Where earthquake loads are
applicable in accordance with the International Building
Code, plumbing piping supports, anchorage, and bracing
shall be designed and installed for seismic forces in accordance with Chapter 16 of the International Building Code.
308.3 Materials. Hangers, anchors and supports shall
support the piping and the contents of the piping. Hangers
and strapping material shall be of approved material that will
not promote galvanic action.
308.4 Structural attachment. Hangers and anchors shall be
attached to the building construction in an approved manner.
308.5 Interval of support. Pipe shall be supported in accordance with Table 308.5.
Exception: The interval of support for piping systems
designed to provide for expansion/contraction shall
conform to the engineered design in accordance with
Section 316.1.
308.6 Sway bracing. Where horizontal pipes 4 inches (102
mm) and larger convey drainage or waste, and where a pipe
fitting in that piping changes the flow direction greater than
45 degrees (0.79 rad), rigid bracing or other rigid support
arrangements shall be installed to resist movement of the
upstream pipe in the direction of pipe flow. A change of flow
direction into a vertical pipe shall not require the upstream
pipe to be braced.
308.7 Anchorage. Anchorage shall be provided to restrain
drainage piping from axial movement.
308.7.1 Location. For pipe sizes greater than 4 inches
(102 mm), restraints shall be provided for drain pipes at
all changes in direction and at all changes in diameter
greater than two pipe sizes. Braces, blocks, rodding and
other suitable methods as specified by the coupling manufacturer shall be utilized.
308.8 Expansion joint fittings. Expansion joint fittings
shall be used only where necessary to provide for expansion
and contraction of the pipes. Expansion joint fittings shall be
of the typical material suitable for use with the type of piping
in which such fittings are installed.
308.9 Parallel water distribution systems. Piping bundles
for manifold systems shall be supported in accordance with
Table 308.5. Support at changes in direction shall be in
3-3
GENERAL REGULATIONS
accordance with the manufacturer’s instructions. Where hot
water piping is bundled with cold water piping, hot water
piping shall be insulated in accordance with Section 607.5.
308.10 Thermal expansion tanks. A thermal expansion
tank shall be supported in accordance with the manufacturer’s instructions. Thermal expansion tanks shall not be
supported by the piping that connects to such tanks.
SECTION 309
FLOOD HAZARD RESISTANCE
309.1 General. Plumbing systems and equipment in structures erected in flood hazard areas shall be constructed in
accordance with the requirements of this section and the
International Building Code.
[BS] 309.2 Flood hazard. For structures located in flood
hazard areas, the following systems and equipment shall be
located and installed as required by Section 1612 of the
International Building Code.
1. Water service pipes.
2. Pump seals in individual water supply systems where
the pump is located below the design flood elevation.
3. Covers on potable water wells shall be sealed, except
where the top of the casing well or pipe sleeve is
elevated to not less than 1 foot (305 mm) above the
design flood elevation.
4. Sanitary drainage piping.
5. Storm drainage piping.
6. Manhole covers shall be sealed, except where
elevated to or above the design flood elevation.
7. Other plumbing fixtures, faucets, fixture fittings,
piping systems and equipment.
8. Water heaters.
9. Vents and vent systems.
Exception: The systems listed in this section are permitted to be located below the elevation required by Section
1612 of the International Building Code for utilities and
attendant equipment, provided that the systems are
designed and installed to prevent water from entering or
accumulating within their components and the systems
are constructed to resist hydrostatic and hydrodynamic
loads and stresses, including the effects of buoyancy,
during the occurrence of flooding up to such elevation.
TABLE 308.5
HANGER SPACING
PIPING MATERIAL
Acrylonitrile butadiene styrene (ABS) pipe
MAXIMUM HORIZONTAL SPACING
(feet)
MAXIMUM VERTICAL SPACING
(feet)
4
10b
Aluminum tubing
10
15
Brass pipe
10
10
Cast-iron pipe
5a
15
Chlorinated polyvinyl chloride (CPVC) pipe and tubing, 1 inch and
smaller
3
10b
Chlorinated polyvinyl chloride (CPVC) pipe and tubing, 11/4 inches and
larger
4
10b
Copper or copper-alloy pipe
12
10
1
Copper or copper-alloy tubing, 1 /4-inch diameter and smaller
6
10
Copper or copper-alloy tubing, 11/2-inch diameter and larger
10
10
2.67 (32 inches)
10b
4
10b
2.67 (32 inches)
4
Cross-linked polyethylene (PEX) pipe, 1 inch and smaller
1
Cross-linked polyethylene (PEX) pipe, 1 /4 inches and larger
Cross-linked polyethylene/aluminum/cross-linked polyethylene
(PEX-AL-PEX) pipe
Lead pipe
Continuous
4
Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe
2.67 (32 inches)
4
Polyethylene of raised temperature (PE-RT) pipe, 1 inch and smaller
2.67 (32 inches)
10b
4
10b
2.67 (32 inches)
10b
Polypropylene (PP) pipe or tubing, 1 /4 inches and larger
4
10b
Polyvinyl chloride (PVC) pipe
4
10b
Stainless steel drainage systems
10
10b
Steel pipe
12
15
Polyethylene of raised temperature (PE-RT) pipe, 11/4 inches and larger
Polypropylene (PP) pipe or tubing, 1 inch and smaller
1
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The maximum horizontal spacing of cast-iron pipe hangers shall be increased to 10 feet where 10-foot lengths of pipe are installed.
b. For sizes 2 inches and smaller, a guide shall be installed midway between required vertical supports. Such guides shall prevent pipe movement in a direction perpendicular to the axis of the pipe.
3-4
2021 INTERNATIONAL PLUMBING CODE®
GENERAL REGULATIONS
[BS] 309.3 Coastal high-hazard areas and coastal A
zones. Structures located in coastal high-hazard areas and
coastal A zones shall meet the requirements of Section
309.2. The plumbing systems, pipes and fixtures shall not be
mounted on or penetrate through walls intended to break
away under flood loads.
SECTION 310
WASHROOM AND TOILET ROOM REQUIREMENTS
310.1 Light and ventilation. Washrooms and toilet rooms
shall be illuminated and ventilated in accordance with the
International Building Code and International Mechanical
Code.
310.2 Location of fixtures and compartments. The location of plumbing fixtures and the requirements for
compartments and partitions shall be in accordance with
Section 405.3.
310.3 Interior finish. Interior finish surfaces of toilet rooms
shall comply with the International Building Code.
SECTION 311
TOILET FACILITIES FOR WORKERS
311.1 General. Toilet facilities shall be provided for
construction workers and such facilities shall be maintained
in a sanitary condition. Construction worker toilet facilities
of the nonsewer type shall conform to PSAI Z4.3.
SECTION 312
TESTS AND INSPECTIONS
312.1 Required tests. The permit holder shall make the
applicable tests prescribed in Sections 312.2 through 312.10
to determine compliance with the provisions of this code.
The permit holder shall give reasonable advance notice to
the code official when the plumbing work is ready for tests.
The equipment, material, power and labor necessary for the
inspection and test shall be furnished by the permit holder
and he or she shall be responsible for determining that the
work will withstand the test pressure prescribed in the
following tests. Plumbing system piping shall be tested with
either water or, for piping systems other than plastic, by air.
After the plumbing fixtures have been set and their traps
filled with water, the entire drainage system shall be submitted to final tests. The code official shall require the removal
of any cleanouts if necessary to ascertain whether the pressure has reached all parts of the system.
312.1.1 Test gauges. Gauges used for testing shall be as
follows:
1. Tests requiring a pressure of 10 pounds per square
inch (psi) (69 kPa) or less shall utilize a testing
gauge having increments of 0.10 psi (0.69 kPa) or
less.
2. Tests requiring a pressure of greater than 10 psi
(69 kPa) but less than or equal to 100 psi (689 kPa)
shall utilize a testing gauge having increments of 1
psi (6.9 kPa) or less.
2021 INTERNATIONAL PLUMBING CODE®
3. Tests requiring a pressure of greater than 100 psi
(689 kPa) shall utilize a testing gauge having
increments of 2 psi (14 kPa) or less.
312.2 Drainage and vent water test. A water test shall be
applied to the drainage system either in its entirety or in
sections. If applied to the entire system, all openings in the
piping shall be tightly closed, except the highest opening,
and the system shall be filled with water to the point of overflow. If the system is tested in sections, each opening shall
be tightly plugged except the highest openings of the section
under test, and each section shall be filled with water, but
sections shall not be tested with less than a 10-foot (3048
mm) head of water. In testing successive sections, not less
than the upper 10 feet (3048 mm) of the next preceding
section shall be tested so that no joint or pipe in the building,
except the uppermost 10 feet (3048 mm) of the system, shall
have been submitted to a test of less than a 10-foot (3048
mm) head of water. This pressure shall be held for not less
than 15 minutes. The system shall then be tight at all points.
312.3 Drainage and vent air test. Plastic piping shall not be
tested using air. An air test shall be made by forcing air into
the system until there is a uniform gauge pressure of 5 psi
(34.5 kPa) or sufficient to balance a 10-inch (254 mm)
column of mercury. This pressure shall be held for a test
period of not less than 15 minutes. Any adjustments to the
test pressure required because of changes in ambient
temperatures or the seating of gaskets shall be made prior to
the beginning of the test period.
312.4 Drainage and vent final test. The final test of the
completed drainage and vent systems shall be visual and in
sufficient detail to determine compliance with the provisions
of this code. Where a smoke test is utilized, it shall be made
by filling all traps with water and then introducing into the
entire system a pungent, thick smoke produced by one or
more smoke machines. When the smoke appears at stack
openings on the roof, the stack openings shall be closed and
a pressure equivalent to a 1-inch water column (248.8 Pa)
shall be held for a test period of not less than 15 minutes.
312.5 Water supply system test. Upon completion of a
section of or the entire water supply system, the system, or
portion completed, shall be tested and proved tight under a
water pressure not less than the working pressure of the
system; or, for piping systems other than plastic, by an air
test of not less than 50 psi (344 kPa). This pressure shall be
held for not less than 15 minutes. The water utilized for tests
shall be obtained from a potable source of supply. The
required tests shall be performed in accordance with this
section and Section 108.
312.6 Gravity sewer test. Gravity sewer tests shall consist
of plugging the end of the building sewer at the point of
connection with the public sewer, filling the building sewer
with water, testing with not less than a 10-foot (3048 mm)
head of water and maintaining such pressure for 15 minutes.
312.7 Forced sewer test. Forced sewer tests shall consist of
plugging the end of the building sewer at the point of
connection with the public sewer and applying a pressure of
5 psi (34.5 kPa) greater than the pump rating, and maintaining such pressure for 15 minutes.
3-5
GENERAL REGULATIONS
312.8 Storm drainage system test. Storm drain systems
within a building shall be tested by water or air in accordance with Section 312.2 or 312.3.
312.9 Shower liner test. Where shower floors and receptors
are made water tight by the application of materials required
by Section 421.5.2, the completed liner installation shall be
tested. The pipe from the shower drain shall be plugged
water tight for the test. The floor and receptor area shall be
filled with potable water to a depth of not less than 2 inches
(51 mm) measured at the threshold. Where a threshold of 2
inches (51 mm) high or greater does not exist, a temporary
threshold shall be constructed to retain the test water in the
lined floor or receptor area to a level not less than 2 inches
(51 mm) deep measured at the threshold. The water shall be
retained for a test period of not less than 15 minutes, and
there shall not be evidence of leakage.
312.10 Inspection and testing of backflow prevention
assemblies. Inspection and testing shall comply with
Sections 312.10.1 and 312.10.2.
312.10.1 Inspections. Annual inspections shall be made
of all backflow prevention assemblies and air gaps to
determine whether the assemblies are operable and air
gaps exist.
312.10.2 Testing. Reduced pressure principle, double
check, pressure vacuum breaker, reduced pressure detector fire protection, double check detector fire protection,
and spill-resistant vacuum breaker backflow preventer
assemblies and hose connection backflow preventers
shall be tested at the time of installation, immediately
after repairs or relocation and at least annually. The testing procedure shall be performed in accordance with one
of the following standards: ASSE 5013, ASSE 5015,
ASSE 5020, ASSE 5047, ASSE 5048, ASSE 5052, ASSE
5056, CSA B64.10 or CSA B64.10.1. Test gauges shall
comply with ASSE 1064.
SECTION 313
EQUIPMENT EFFICIENCIES
313.1 General. Equipment efficiencies shall be in accordance with the International Energy Conservation Code.
SECTION 314
CONDENSATE DISPOSAL
[M] 314.1 Fuel-burning appliances. Liquid combustion
byproducts of condensing appliances shall be collected and
discharged to an approved plumbing fixture or disposal area
in accordance with the manufacturer’s instructions. Condensate piping shall be of approved corrosion-resistant material
and shall not be smaller than the drain connection on the
appliance. Such piping shall maintain a horizontal slope in
the direction of discharge of not less than one-eighth unit
vertical in 12 units horizontal (1-percent slope).
[M] 314.1.1 Identification. The termination of concealed
condensate piping shall be marked to indicate whether the
piping is connected to the primary or secondary drain.
3-6
[M] 314.2 Evaporators and cooling coils. Condensate drain
systems shall be provided for equipment and appliances
containing evaporators or cooling coils. Condensate drain
systems shall be designed, constructed and installed in
accordance with Sections 314.2.1 through 314.2.5.
[M] 314.2.1 Condensate disposal. Condensate from all
cooling coils and evaporators shall be conveyed from the
drain pan outlet to an approved place of disposal. Such
piping shall maintain a horizontal slope in the direction of
discharge of not less than one-eighth unit vertical in 12
units horizontal (1-percent slope). Condensate shall not
discharge into a street, alley or other areas so as to cause a
nuisance.
[M] 314.2.1.1 Condesate discharge. Condensate
drains shall not directly connect to any plumbing
drain, waste or vent pipe. Condensate drains shall not
discharge into a plumbing fixture other than a floor
sink, floor drain, trench drain, mop sink, hub drain,
standpipe, utility sink or laundry sink. Condensate
drain connections to a lavatory wye branch tailpiece or
to a bathtub overflow pipe shall not be considered as
discharging to a plumbing fixture. Except where
discharging to grade outdoors, the point of discharge
of condensate drains shall be located within the same
occupancy, tenant space or dwelling unit as the source
of the condensate.
[M] 314.2.2 Drain pipe materials and sizes. Components of the condensate disposal system shall be ABS,
cast-iron, copper and copper-alloy, CPVC, cross-linked
polyethylene, galvanized steel, PE-RT, polyethylene,
polypropylene, PVC, or PVDF pipe or tubing. Components shall be selected for the pressure and temperature
rating of the installation. Joints and connections shall be
made in accordance with the applicable provisions of
Chapter 7 relative to the material type. Condensate waste
and drain line size shall be not less than 3/4-inch (19.1
mm) pipe size and shall not decrease in size from the
drain pan connection to the place of condensate disposal.
Where the drain pipes from more than one unit are manifolded together for condensate drainage, the pipe or
tubing shall be sized in accordance with Table 314.2.2.
[M] TABLE 314.2.2
CONDENSATE DRAIN SIZING
EQUIPMENT CAPACITY
MINIMUM CONDENSATE
PIPE DIAMETER (inch)
3
Up to 20 tons of refrigeration
/4 inch
Over 20 tons to 40 tons of refrigeration
1 inch
1
Over 40 tons to 90 tons of refrigeration
1 /4 inches
Over 90 tons to 125 tons of refrigeration
11/2 inches
Over 125 tons to 250 tons of refrigeration
2 inches
For SI: 1 inch = 25.4 mm, 1 ton of capacity = 3.517 kW.
[M] 314.2.3 Auxiliary and secondary drain systems. In
addition to the requirements of Section 314.2.1, where
damage to any building components could occur as a
result of overflow from the equipment primary condensate removal system, one of the following auxiliary
2021 INTERNATIONAL PLUMBING CODE®
GENERAL REGULATIONS
protection methods shall be provided for each cooling
coil or fuel-fired appliance that produces condensate:
support the appliance or equipment shall be water
resistant and approved.
1. An auxiliary drain pan with a separate drain shall
be provided under the coils on which condensation
will occur. The auxiliary pan drain shall discharge
to a conspicuous point of disposal to alert occupants in the event of a stoppage of the primary
drain. The pan shall have a depth of not less than
11/2 inches (38 mm), shall be not less than 3 inches
(76 mm) larger than the unit or the coil dimensions
in width and length, and shall be constructed of
corrosion-resistant material. Galvanized sheet
metal pans shall have a thickness of not less than
0.0236-inch (0.6010 mm) (No. 24 gage) galvanized sheet metal. Nonmetallic pans shall have a
thickness of not less than 0.0625 inch (1.6 mm).
2. A separate overflow drain line shall be connected
to the drain pan provided with the equipment.
Such overflow drain shall discharge to a conspicuous point of disposal to alert occupants in the
event of a stoppage of the primary drain. The overflow drain line shall connect to the drain pan at a
higher level than the primary drain connection.
3. An auxiliary drain pan without a separate drain
line shall be provided under the coils on which
condensate will occur. Such pan shall be equipped
with a water-level detection device conforming to
UL 508 that will shut off the equipment served
prior to overflow of the pan. The auxiliary drain
pan shall be constructed in accordance with Item 1
of this section.
4. A water-level detection device conforming to UL
508 shall be provided that will shut off the equipment served in the event that the primary drain is
blocked. The device shall be installed in the
primary drain line, the overflow drain line or in the
equipment-supplied drain pan, located at a point
higher than the primary drain line connection and
below the overflow rim of such pan.
[M] 314.2.3.3 Identification. The termination of
concealed condensate piping shall be marked to indicate whether the piping is connected to the primary or
secondary drain.
Exception: Fuel-fired appliances that automatically
shut down operation in the event of a stoppage in the
condensate drainage system.
[M] 314.2.3.1 Water-level monitoring devices. On
down-flow units and all other coils that do not have a
secondary drain or provisions to install a secondary or
auxiliary drain pan, a water-level monitoring device
shall be installed inside the primary drain pan. This
device shall shut off the equipment served in the event
that the primary drain becomes restricted. Devices
installed in the drain line shall not be permitted.
[M] 314.2.3.2 Appliance, equipment and insulation
in pans. Where appliances, equipment or insulation
are subject to water damage when auxiliary drain pans
fill such portions of the appliances, equipment and
insulation shall be installed above the flood level rim
of the pan. Supports located inside of the pan to
2021 INTERNATIONAL PLUMBING CODE®
[M] 314.2.4 Traps. Condensate drains shall be trapped as
required by the equipment or appliance manufacturer.
[M] 314.2.4.1 Ductless mini-split system traps.
Ductless mini-split equipment that produces condensation shall be provided with an in-line check valve
located in the drain line or a trap.
[M] 314.2.5 Drain line maintenance. Condensate drain
lines shall be configured to permit the clearing of blockages and performance of maintenance without requiring
the drain line to be cut.
SECTION 315
PENETRATIONS
315.1 Sealing of annular spaces. The annular space
between the outside of a pipe and the inside of a pipe sleeve
or between the outside of a pipe and an opening in a building
envelope wall, floor, or ceiling assembly penetrated by a
pipe shall be sealed in an approved manner with caulking
material, foam sealant or closed with a gasketing system.
The caulking material, foam sealant or gasketing system
shall be designed for the conditions at the penetration location and shall be compatible with the pipe, sleeve and
building materials in contact with the sealing materials.
Annular spaces created by pipes penetrating fire-resistancerated assemblies or membranes of such assemblies shall be
sealed or closed in accordance with Section 714 of the International Building Code.
SECTION 316
ALTERNATIVE ENGINEERED DESIGN
316.1 Alternative engineered design. The design, documentation, inspection, testing and approval of an alternative
engineered design plumbing system shall comply with
Sections 316.1.1 through 316.1.6.
316.1.1 Design criteria. An alternative engineered
design shall conform to the intent of the provisions of this
code and shall provide an equivalent level of quality,
strength, effectiveness, fire resistance, durability and
safety. Material, equipment or components shall be
designed and installed in accordance with the manufacturer’s instructions.
316.1.2 Submittal. The registered design professional
shall indicate on the permit application that the plumbing
system is an alternative engineered design. The permit
and permanent permit records shall indicate that an alternative engineered design was part of the approved
installation.
3-7
GENERAL REGULATIONS
316.1.3 Technical data. The registered design professional shall submit sufficient technical data to
substantiate the proposed alternative engineered design
and to prove that the performance meets the intent of this
code.
316.1.4 Construction documents. The registered design
professional shall submit to the code official two
complete sets of signed and sealed construction documents for the alternative engineered design. The
construction documents shall include floor plans and a
riser diagram of the work. Where appropriate, the
construction documents shall indicate the direction of
flow, all pipe sizes, grade of horizontal piping, loading
and location of fixtures and appliances.
316.1.5 Design approval. Where the code official determines that the alternative engineered design conforms to
the intent of this code, the plumbing system shall be
approved. If the alternative engineered design is not
approved, the code official shall notify the registered
design professional in writing, stating the reasons thereof.
316.1.6 Inspection and testing. The alternative engineered design shall be tested and inspected in accordance
with the requirements of Sections 108 and 312.
3-8
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 4
FIXTURES, FAUCETS AND FIXTURE FITTINGS
User note:
About this chapter: Plumbing fixtures are required to be installed for nearly every building as toilet facilities (water closets and lavatories)
are needed by the occupants of a building. Additional fixtures for washing, bathing and culinary purposes are also necessary where occupants dwell in buildings. Chapter 4 specifies the minimum number and type of plumbing fixtures for buildings based on the description of
use of the building. Because fixture design and quality are paramount to ensure that plumbing fixtures operate properly, this chapter also
specifies numerous product and material standards for plumbing fixtures.
SECTION 401
GENERAL
enameled surfaces on plumbing fixtures shall be acid
resistant.
401.1 Scope. This chapter shall govern the materials, design
and installation of plumbing fixtures, faucets and fixture
fittings in accordance with the type of occupancy, and shall
provide for the minimum number of fixtures for various
types of occupancies.
402.2 Materials for specialty fixtures. Materials for
specialty fixtures not otherwise covered in this code shall be
of stainless steel, soapstone, chemical stoneware or plastic,
or shall be lined with lead, copper-base alloy, nickel-copper
alloy, corrosion-resistant steel or other material especially
suited to the application for which the fixture is intended.
401.2 Prohibited fixtures and connections. Water closets
having a concealed trap seal or an unventilated space or
having walls that are not thoroughly washed at each
discharge in accordance with ASME A112.19.2/CSA B45.1
shall be prohibited. Any water closet that permits siphonage
of the contents of the bowl back into the tank shall be prohibited. Trough urinals shall be prohibited.
402.3 Sheet copper. Sheet copper for general applications
shall conform to ASTM B152 and shall not weigh less than
12 ounces per square foot (3.7 kg/m2).
402.4 Sheet lead. Sheet lead for pans shall not weigh less
than 4 pounds per square foot (19.5 kg/m2) and shall be
coated with an asphalt paint or other approved coating.
401.3 Water conservation. The maximum water flow rates
and flush volume for plumbing fixtures and fixture fittings
shall comply with Section 604.4.
SECTION 402
FIXTURE MATERIALS
402.1 Quality of fixtures. Plumbing fixtures shall be
constructed of approved materials, with smooth, impervious
surfaces, free from defects and concealed fouling surfaces,
and shall conform to standards cited in this code. Porcelain
SECTION 403
MINIMUM PLUMBING FACILITIES
403.1 Minimum number of fixtures. Plumbing fixtures
shall be provided in the minimum number as shown in Table
403.1, based on the actual use of the building or space. Uses
not shown in Table 403.1 shall be considered individually by
the code official. The number of occupants shall be determined by the International Building Code.
TABLE 403.1
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa (See Sections 403.1.1 and 403.2)
WATER CLOSETS
(URINALS: SEE SECTION 424.2)
NO. CLASSIFICATION
1
Assembly
BATHTUBS/
SHOWERS
DRINKING
FOUNTAIN
(SEE
SECTION
410)
OTHER
LAVATORIES
DESCRIPTION
MALE
FEMALE
MALE
FEMALE
Theaters and other buildings
for the performing arts and
motion picturesd
1 per 125
1 per 65
1 per 200
—
1 per 500
1
service
sink
Nightclubs, bars, taverns,
dance halls and buildings for
similar purposesd
1 per 40
1 per 40
1 per 75
—
1 per 500
1
service
sink
Restaurants, banquet halls and
food courtsd
1 per 75
1 per 75
1 per 200
—
1 per 500
1
service
sink
(continued)
2021 INTERNATIONAL PLUMBING CODE®
4-1
FIXTURES, FAUCETS AND FIXTURE FITTINGS
TABLE 403.1—continued
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa (See Sections 403.1.1 and 403.2)
WATER CLOSETS
(URINALS: SEE SECTION 424.2)
NO.
CLASSIFICATION
DESCRIPTION
Assembly
(cont.)
DRINKING
FOUNTAIN
(SEE
OTHER
SECTION
410)
1
1 per 1,000 service
sink
MALE
FEMALE
MALE FEMALE
1 per 100 for the
first 400 and 1 per
250 for the
remainder
exceeding 400
1 per 50 for the
first 400 and 1 per
150 for the
remainder
exceeding 400
1 per 250 for the
first 750 and
1 per 500 for the
remainder
exceeding 750
—
Auditoriums without
permanent seating, art
galleries, exhibition halls,
museums, lecture halls,
libraries, arcades and
gymnasiumsd
1 per 125
1 per 65
1 per 200
—
Passenger terminals and
transportation facilitiesd
1 per 500
1 per 500
1 per 750
—
Places of worship and other
religious servicesd
1 per 150
1 per 75
1 per 200
—
Casino gaming areas
1
BATHTUBS/
SHOWERS
LAVATORIES
1 per 75 for the
1 per 40 for the
first 1,500 and
first 1,520 and
1 per 120 for the
1 per 60 for the
remainder
remainder
exceeding 1,500
exceeding 1,520
1 per 75 for the
1 per 40 for the
Stadiums, amusement
first 1,500 and
first 1,520 and
parks, bleachers and grand1 per 120 for the
1 per 60 for the
stands for outdoor sporting
remainder
remainder
events and activitiesf
exceeding 1,500
exceeding 1,520
Buildings for the
transaction of business,
professional services, other
services involving
1 per 25 for the first 50 and 1 per 50
merchandise, office build- for the remainder exceeding 50
ings, banks, ambulatory
care, light industrial and
similar uses
Coliseums, arenas, skating
rinks, pools and tennis
courts for indoor sporting
events and activities
1 per 500
1
service
sink
1
1 per 1,000 service
sink
1
1 per 1,000 service
sink
1 per
200
1 per
150
—
1
1 per 1,000 service
sink
1 per
200
1 per
150
—
1
1 per 1,000 service
sink
1 per 40 for the
first 80 and
1 per 80 for the
remainder
exceeding 80
—
1 per 100
1
service
sinke
2
Business
3
Educational
Educational facilities
1 per 50
1 per 50
—
1 per 100
1
service
sink
4
Factory and
industrial
Structures in which occupants are engaged in work
fabricating, assembly or
processing of products or
materials
1 per 100
1 per 100
—
1 per 400
1
service
sink
Custodial care facilities
1 per 10
1 per 10
1 per 8
1 per 100
1 per roomc
1 per roomc
1 per 15
1 per 100
1 per 25
1 per 35
—
1 per 100
—
1 per 75
1 per 100
—
1 per 500
—
Prisonsb
1 per cell
1 per cell
1 per 15
1 per 100
Reformitories, detention
centers, and correctional
centersb
1 per 15
1 per 15
1 per 15
1 per 100
Medical care recipients in
hospitals and nursing
homes
5
Institutional
Employees in hospitals and
nursing homesb
Visitors in hospitals and
nursing homes
1
service
sink
1
service
sink per
floor
1
service
sink
1
service
sink
(continued)
4-2
2021 INTERNATIONAL PLUMBING CODE®
FIXTURES, FAUCETS AND FIXTURE FITTINGS
TABLE 403.1—continued
MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURESa (See Sections 403.1.1 and 403.2)
WATER CLOSETS
(URINALS: SEE SECTION 424.2)
NO.
CLASSIFICATION
DESCRIPTION
MALE
5
(cont.)
6
Institutional
Mercantile
Employees in reformatories, detention centers and
correctional centersb
Adult day care and child
day care
Retail stores, service
stations, shops, salesrooms, markets and
shopping centers
Hotels, motels, boarding
houses (transient)
Dormitories, fraternities,
sororities and boarding
houses (not transient)
Apartment house
7
Residential
Congregate living facilities with 16 or fewer
persons
One- and two-family
dwellings and lodging
houses with five or fewer
guestrooms
8
Storage
Congregate living facilities with 16 or fewer
persons
Structures for the storage
of goods, warehouses,
storehouse and freight
depots. Low and Moderate
Hazard.
FEMALE
BATHTUBS/
SHOWERS
DRINKING
FOUNTAIN
(SEE
SECTION
410)
OTHER
LAVATORIES
MALE FEMALE
1 per 25
1 per 35
—
1 per 100
—
1 per 15
1 per 15
1
1 per 100
1
service sink
1 per 500
1 per 750
—
1 per 1,000
1
service sinke
1 per
sleeping unit
1 per
sleeping unit
1 per
sleeping unit
—
1
service sink
1 per 10
1 per 10
1 per 8
1 per 100
1
service sink
1 per dwelling unit
1 per
dwelling unit
1 per
dwelling unit
—
1 kitchen sink
per dwelling
unit; 1 automatic clothes
washer
connection per
20 dwelling
units
1 per 10
1 per 10
1 per 8
1 per 100
1 service sink
1 per dwelling unit
1 per
dwelling unit
1 per
dwelling unit
—
1 kitchen sink
per dwelling
unit; 1 automatic clothes
washer
connection per
dwelling unit
1 per 10
1 per 10
1 per 8
1 per 100
1
service sink
1 per 100
1 per 100
—
1 per 1,000
1
service sink
a. The fixtures shown are based on one fixture being the minimum required for the number of persons indicated or any fraction of the number of persons indicated. The number of occupants shall be determined by the International Building Code.
b. Toilet facilities for employees shall be separate from facilities for inmates or care recipients.
c. A single-occupant toilet room with one water closet and one lavatory serving not more than two adjacent patient sleeping units shall be permitted provided
that each patient sleeping unit has direct access to the toilet room and provision for privacy for the toilet room user is provided.
d. The occupant load for seasonal outdoor seating and entertainment areas shall be included when determining the minimum number of facilities required.
e. For business and mercantile classifications with an occupant load of 15 or fewer, service sinks shall not be required.
f. The required number and type of plumbing fixtures for outdoor public swimming pools shall be in accordance with Section 609 of the International Swimming Pool and Spa Code.
2021 INTERNATIONAL PLUMBING CODE®
4-3
FIXTURES, FAUCETS AND FIXTURE FITTINGS
403.1.1 Fixture calculations. To determine the occupant
load of each sex, the total occupant load shall be divided
in half. To determine the required number of fixtures, the
fixture ratio or ratios for each fixture type shall be applied
to the occupant load of each sex in accordance with Table
403.1. Fractional numbers resulting from applying the
fixture ratios of Table 403.1 shall be rounded up to the
next whole number. For calculations involving multiple
occupancies, such fractional numbers for each occupancy
shall first be summed and then rounded up to the next
whole number.
Exceptions:
1. The total occupant load shall not be required to
be divided in half where approved statistical
data indicate a distribution of the sexes of other
than 50 percent of each sex.
2. Where multiple-user facilities are designed to
serve all genders, the minimum fixture count
shall be calculated 100 percent, based on total
occupant load. In such multiple-user facilities,
each fixture type shall be in accordance with
ICC A117.1 and each urinal that is provided
shall be located in a stall.
3. Distribution of the sexes is not required where
single-user water closets and bathing room
fixtures are provided in accordance with
Section 403.1.2.
403.1.2 Single-user toilet and bathing room fixtures.
The plumbing fixtures located in single-user toilet and
bathing rooms, including family or assisted-use toilet and
bathing rooms that are required by Section 1109.2.1 of
the International Building Code, shall contribute toward
the total number of required plumbing fixtures for a
building or tenant space. Single-user toilet and bathing
rooms, and family or assisted-use toilet rooms and bathing rooms shall be identified as being available for use by
all persons regardless of their sex.
The total number of fixtures shall be permitted to be
based on the required number of separate facilities or
based on the aggregate of any combination of single-user
or separate facilities.
403.1.3 Lavatory distribution. Where two or more toilet
rooms are provided for each sex, the required number of
lavatories shall be distributed proportionately to the
required number of water closets.
403.2 Separate facilities. Where plumbing fixtures are
required, separate facilities shall be provided for each sex.
Exceptions:
1. Separate facilities shall not be required for dwelling units and sleeping units.
2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load,
including both employees and customers, of 15 or
fewer.
4-4
3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant
load is 100 or fewer.
4. Separate facilities shall not be required in business
occupancies in which the maximum occupant load
is 25 or fewer.
5. Separate facilities shall not be required to be
designated by sex where single-user toilet rooms
are provided in accordance with Section 403.1.2.
6. Separate facilities shall not be required where
rooms having both water closets and lavatory
fixtures are designed for use by both sexes and
privacy for water closets is provided in accordance
with Section 405.3.4. Urinals shall be located in an
area visually separated from the remainder of the
facility or each urinal that is provided shall be
located in a stall.
403.2.1 Family or assisted-use toilet facilities serving
as separate facilities. Where a building or tenant space
requires a separate toilet facility for each sex and each
toilet facility is required to have only one water closet,
two family or assisted-use toilet facilities shall be permitted to serve as the required separate facilities. Family or
assisted-use toilet facilities shall not be required to be
identified for exclusive use by either sex as required by
Section 403.4.
403.3 Employee and public toilet facilities. For structures
and tenant spaces intended for public utilization, customers,
patrons and visitors shall be provided with public toilet facilities. Employees associated with structures and tenant spaces
shall be provided with toilet facilities. The number of plumbing fixtures located within the required toilet facilities shall
be provided in accordance with Section 403 for all users.
Employee toilet facilities shall be either separate or
combined employee and public toilet facilities.
Exception: Public toilet facilities shall not be required
for:
1. Parking garages operated without parking
attendants.
2. Structures and tenant spaces intended for quick
transactions, including takeout, pickup and dropoff, having a public access area less than or equal
to 300 square feet (28 m2).
403.3.1 Access. The route to the public toilet facilities
required by Section 403.3 shall not pass through kitchens,
storage rooms or closets. Access to the required facilities
shall be from within the building or from the exterior of
the building. The public shall have access to the required
toilet facilities at all times that the building is occupied.
403.3.2 Prohibited toilet room location. Toilet rooms
shall not open directly into a room used for the preparation of food for service to the public.
403.3.3 Location of toilet facilities in occupancies
other than malls. In occupancies other than covered and
2021 INTERNATIONAL PLUMBING CODE®
FIXTURES, FAUCETS AND FIXTURE FITTINGS
Exceptions:
1. The location and maximum distances of travel
to required employee facilities in factory and
industrial occupancies shall be permitted to
exceed that required by this section, provided
that the location and maximum distances of
travel are approved.
2. The location and maximum distances of travel
to required public and employee facilities in
Group S occupancies shall be permitted to
exceed that required by this section, provided
that the location and maximum distances of
travel are approved.
403.3.4 Location of toilet facilities in malls. In covered
and open mall buildings, the required public and
employee toilet facilities shall be located not more than
one story above or below the space required to be
provided with toilet facilities, and the path of travel to
such facilities shall not exceed a distance of 300 feet (91
m). In mall buildings, the required facilities shall be based
on total square footage within a covered mall building or
within the perimeter line of an open mall building, and
facilities shall be installed in each individual store or in a
central toilet area located in accordance with this section.
The maximum distance of travel to central toilet facilities
in mall buildings shall be measured from the main
entrance of any store or tenant space. In mall buildings,
where employees’ toilet facilities are not provided in the
individual store, the maximum distance of travel shall be
measured from the employees’ work area of the store or
tenant space.
403.3.5 Pay facilities. Where pay facilities are installed,
such facilities shall be in excess of the required minimum
facilities. Required facilities shall be free of charge.
403.3.6 Door locking. Where a toilet room is provided
for the use of multiple occupants, the egress door for the
room shall not be lockable from the inside of the room.
This section does not apply to family or assisted-use toilet
rooms.
403.4 Signage. Required public facilities shall be provided
with signs that designate the sex, as required by Section
403.2. Signs shall be readily visible and located near the
entrance to each toilet facility. Signs for accessible toilet
facilities shall comply with Section 1111 of the International
Building Code.
403.4.1 Directional signage. Directional signage indicating the route to the required public toilet facilities shall be
posted in a lobby, corridor, aisle or similar space, such
that the sign can be readily seen from the main entrance to
the building or tenant space.
403.5 Drinking fountain location. Drinking fountains shall
not be required to be located in individual tenant spaces
2021 INTERNATIONAL PLUMBING CODE®
provided that public drinking fountains are located within a
distance of travel of 500 feet (152 m) of the most remote
location in the tenant space and not more than one story
above or below the tenant space. Where the tenant space is in
a covered or open mall, such distance shall not exceed 300
feet (91 m).
403.6 Service sink location. Service sinks shall not be
required to be located in individual tenant spaces in a
covered mall provided that service sinks are located within a
distance of travel of 300 feet (91 m) of the most remote location in the tenant space and not more than one story above or
below the tenant space. Service sinks shall be located on an
accessible route.
SECTION 404
ACCESSIBLE PLUMBING FACILITIES
404.1 Where required. Accessible plumbing facilities and
fixtures shall be provided in accordance with Chapter 11 of
the International Building Code.
404.2 Accessible fixture requirements. Accessible plumbing fixtures shall be installed in accordance with ICC
A117.1.
SECTION 405
INSTALLATION OF FIXTURES
405.1 Water supply protection. The supply lines and
fittings for every plumbing fixture shall be installed so as to
prevent backflow.
405.2 Access for cleaning. Plumbing fixtures shall be
installed so as to afford easy access for cleaning both the
fixture and the area around the fixture.
405.3 Setting. Fixtures shall be set level and in proper alignment with reference to adjacent walls.
405.3.1 Water closets, urinals, lavatories and bidets. A
water closet, urinal, lavatory or bidet shall not be set
closer than 15 inches (381 mm) from its center to any side
wall, partition, vanity or other obstruction. Where partitions or other obstructions do not separate adjacent water
closets, urinals, or bidets, the fixtures shall not be set
closer than 30 inches (762 mm) center to center between
adjacent fixtures or adjacent water closets, urinals, or
bidets. There shall be not less than a 21-inch (533 mm)
clearance in front of a water closet, urinal, lavatory or
bidet to any wall, fixture or door. Water closet compartments shall be not less than 30 inches (762 mm) in width
and not less than 60 inches (1524 mm) in depth for floormounted water closets and not less than 30 inches (762
mm) in width and 56 inches (1422 mm) in depth for wallhung water closets.
Exception: An accessible children’s water closet shall
be set not closer than 12 inches (305 mm) from its
center to the required partition or to the wall on one side.
405.3.2 Public lavatories. In employee and public toilet
rooms, the required lavatory shall be located in the same
room as the required water closet.
4-5

open mall buildings, the required public and employee
toilet facilities shall be located not more than one story
above or below the space required to be provided with
toilet facilities, and the path of travel to such facilities
shall not exceed a distance of 500 feet (152 m).
FIXTURES, FAUCETS AND FIXTURE FITTINGS
405.3.3 Location of fixtures and piping. Piping, fixtures
or equipment shall not be located in such a manner as to
interfere with the normal operation of windows, doors or
other means of egress openings.
thick for copper alloy, 0.25 inch (6.4 mm) thick for plastic
and 0.25 inch (6.4 mm) thick and not less than a 2-inch
(51 mm) caulking depth for cast iron or galvanized
malleable iron.
405.3.4 Water closet compartment. Each water closet
utilized by the public or employees shall occupy a separate compartment with walls or partitions and a door
enclosing the fixtures to ensure privacy.
Floor flanges of hard lead shall weigh not less than 1
pound, 9 ounces (0.7 kg) and shall be composed of lead
alloy with not less than 7.75-percent antimony by weight.
Closet screws and bolts shall be of copper alloy. Flanges
shall be secured to the building structure with corrosionresistant screws or bolts.
Exceptions:
1. Water closet compartments shall not be
required in a single-occupant toilet room with a
lockable door.
2. Toilet rooms located in child day care facilities
and containing two or more water closets shall
be permitted to have one water closet without
an enclosing compartment.
3. This provision is not applicable to toilet areas
located within Group I-3 housing areas.
405.3.5 Urinal partitions. Each urinal utilized by the
public or employees shall occupy a separate area with
walls or partitions to provide privacy. The horizontal
dimension between walls or partitions at each urinal shall
be not less than 30 inches (762 mm). The walls or partitions shall begin at a height not greater than 12 inches
(305 mm) from and extend not less than 60 inches (1524
mm) above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the
urinal not less than 18 inches (457 mm) or to a point not
less than 6 inches (152 mm) beyond the outermost front
lip of the urinal measured from the finished backwall
surface, whichever is greater.
Exceptions:
1. Urinal partitions shall not be required in a
single occupant or family/assisted-use toilet
room with a lockable door.
2. Toilet rooms located in child day care facilities
and containing two or more urinals shall be
permitted to have one urinal without partitions.
405.4 Floor and wall drainage connections. Connections
between the drain and floor outlet plumbing fixtures shall be
made with a floor flange or a waste connector and sealing
gasket. The waste connector and sealing gasket joint shall
comply with the joint tightness test of ASME A112.4.3 and
shall be installed in accordance with the manufacturer’s
instructions. The flange shall be attached to the drain and
anchored to the structure. Connections between the drain and
wall-hung water closets shall be made with an approved
extension nipple or horn adaptor. The water closet shall be
bolted to the hanger with corrosion-resistant bolts or screws.
Joints shall be sealed with an approved elastomeric gasket,
flange-to-fixture connection complying with ASME
A112.4.3 or an approved setting compound.
405.4.1 Floor flanges. Floor flanges for water closets or
similar fixtures shall be not less than 0.125 inch (3.2 mm)
4-6
405.4.2 Securing floor outlet fixtures. Floor outlet
fixtures shall be secured to the floor or floor flanges by
screws or bolts of corrosion-resistant material.
405.4.3 Securing wall-hung water closet bowls. Wallhung water closet bowls shall be supported by a
concealed metal carrier that is attached to the building
structural members so that strain is not transmitted to the
fixture connector or any other part of the plumbing
system. The carrier shall conform to ASME A112.6.1M
or ASME A112.6.2.
405.5 Plumbing fixtures with a pumped waste. Plumbing
fixtures with a pumped waste shall comply with ASME
A112.3.4/CSA B45.9. The plumbing fixture with a pumped
waste shall be installed in accordance with the manufacturer’s instructions.
405.6 Watertight joints. Joints formed where fixtures come
in contact with walls or floors shall be sealed.
405.7 Plumbing in mental health centers. In mental health
centers, pipes or traps shall not be exposed, and fixtures shall
be bolted through walls.
405.8 Design of overflows. Where any fixture is provided
with an overflow, the waste shall be designed and installed
so that standing water in the fixture will not rise in the overflow when the stopper is closed, and water will not remain in
the overflow when the fixture is empty.
405.8.1 Connection of overflows. The overflow from
any fixture shall discharge into the drainage system on the
inlet or fixture side of the trap.
Exception: The overflow from a flush tank serving a
water closet or urinal shall discharge into the fixture
served.
405.9 Slip-joint connections. Slip joints shall be made with
an approved elastomeric gasket and shall only be installed
on the trap outlet, trap inlet and within the trap seal. Fixtures
with concealed slip-joint connections shall be provided with
an access panel or utility space not less than 12 inches (305
mm) in its smallest dimension or other approved arrangement so as to provide access to the slip-joint connections for
inspection and repair.
405.10 Design and installation of plumbing fixtures. Integral fixture fitting mounting surfaces on manufactured
plumbing fixtures or plumbing fixtures constructed on site
shall meet the design requirements of ASME
A112.19.2/CSA B45.1 or ASME A112.19.3/CSA B45.4.
2021 INTERNATIONAL PLUMBING CODE®
FIXTURES, FAUCETS AND FIXTURE FITTINGS
SECTION 406
AUTOMATIC CLOTHES WASHERS
406.1 Water connection. The water supply to an automatic
clothes washer shall be protected against backflow by an air
gap that is integral with the machine or a backflow preventer
shall be installed in accordance with Section 608. Air gaps
shall comply with ASME A112.1.2 or A112.1.3.
406.2 Waste connection. The waste from an automatic
clothes washer shall discharge through an air break into a
standpipe in accordance with Section 802.3.3 or into a laundry sink. The trap and fixture drain for an automatic clothes
washer standpipe shall be not less than 2 inches (51 mm) in
diameter. The fixture drain for the standpipe serving an automatic clothes washer shall connect to a 3-inch (76 mm) or
larger diameter fixture branch or stack. Automatic clothes
washers that discharge by gravity shall be permitted to drain
to a waste receptor or an approved trench drain.
SECTION 407
BATHTUBS
407.1 Approval. Bathtubs shall conform to ASME
A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1,
ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.
407.2 Bathtub waste outlets and overflows. Bathtubs shall
be equipped with a waste outlet that is not less than 11/2
inches (38 mm) in diameter. The waste outlet shall be
equipped with a watertight stopper. Where an overflow is
installed, the overflow shall be not less than 11/2 inches (38
mm) in diameter.
407.3 Glazing. Windows and doors within a bathtub enclosure shall conform to the safety glazing requirements of the
International Building Code.
407.4 Bathtub enclosure. Doors in a bathtub enclosure shall
conform to ASME A112.19.15.
SECTION 408
BIDETS
408.1 Approval. Bidets shall conform to ASME
A112.19.2/CSA B45.1 or ASME A112.19.3/CSA B45.4.
408.2 Water connection. The water supply to a bidet shall
be protected against backflow by an air gap or backflow
preventer in accordance with Section 608.14.1, 608.14.2,
608.14.3, 608.14.5, 608.14.6 or 608.14.8.
408.3 Bidet water temperature. The discharge water
temperature from a bidet fitting shall be limited to not
greater than 110°F (43°C) by a water-temperature-limiting
device conforming to ASSE 1070/ASME A112.1070/CSA
B125.70.
SECTION 409
DISHWASHING MACHINES
409.1 Approval. Commercial dishwashing machines shall
conform to ASSE 1004 and NSF 3. Residential dishwashers
shall conform to NSF 184.
2021 INTERNATIONAL PLUMBING CODE®
409.2 Water connection. The water supply to a dishwashing
machine shall be protected against backflow by an air gap
that is integral with the machine or a backflow preventer
shall be installed in accordance with Section 608. Air gaps
shall comply with ASME A112.1.2 or A112.1.3.
409.3 Waste connection. The waste connection of a
commercial dishwashing machine shall comply with Section
802.1.6.
409.4 Residential dishwasher waste connection. The waste
connection of a residential dishwasher shall connect directly
to a wye branch fitting on the tailpiece of the kitchen sink,
directly to the dishwasher connection of a food waste
disposer, or through an air break to a standpipe. The waste
line of a residential dishwasher shall rise and be securely
fastened to the underside of the sink rim or countertop.
SECTION 410
DRINKING FOUNTAINS
410.1 Approval. Drinking fountains shall conform to ASME
A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1 or
ASME A112.19.3/CSA B45.4, and water coolers shall
conform to ASHRAE 18. Drinking fountains, water coolers
and water dispensers shall conform to NSF 61, Section 9.
Electrically operated, refrigerated drinking water coolers
and water dispensers shall be listed and labeled in accordance with UL 399.
410.2 Small occupancies. Drinking fountains shall not be
required for an occupant load of 15 or fewer.
410.3 High and low drinking fountains. Where drinking
fountains are provided on an exterior site, on a floor or
within a secured area, the drinking fountains shall be
provided in accordance with Sections 410.3.1 and 410.3.2.
[BE] 410.3.1 Minimum number. Not fewer than two
drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who
use a wheelchair and one drinking fountain shall comply
with the requirements for standing persons.
Exceptions:
1. A single drinking fountain with two separate
spouts that complies with the requirements for
people who use a wheelchair and standing
persons shall be permitted to be substituted for
two separate drinking fountains.
2. Where drinking fountains are primarily for
children’s use, the drinking fountains for
people using wheelchairs shall be permitted to
comply with the children’s provisions in ICC
A117.1 and drinking fountains for standing
children shall be permitted to provide the spout
at 30 inches (762 mm) minimum above the
floor.
[BE] 410.3.2 More than the minimum number. Where
more than the minimum number of drinking fountains
specified in Section 410.3.1 is provided, 50 percent of the
total number of drinking fountains provided shall comply
with the requirements for persons who use a wheelchair
4-7
FIXTURES, FAUCETS AND FIXTURE FITTINGS
and 50 percent of the total number of drinking fountains
provided shall comply with the requirements for standing
persons.
Exceptions:
1. Where 50 percent of the drinking fountains
yields a fraction, 50 percent shall be permitted
to be rounded up or down, provided that the
total number of drinking fountains complying
with this section equals 100 percent of the
drinking fountains.
2. Where drinking fountains are primarily for
children’s use, drinking fountains for people
using wheelchairs shall be permitted to comply
with the children’s provisions in ICC A117.1
and drinking fountains for standing children
shall be permitted to provide the spout at 30
inches (762 mm) minimum above the floor.
410.4 Substitution. Where restaurants provide drinking
water in a container free of charge, drinking fountains shall
not be required in those restaurants. In other occupancies
where three or more drinking fountains are required, water
dispensers shall be permitted to be substituted for not more
than 50 percent of the required number of drinking
fountains.
410.5 Prohibited location. Drinking fountains, water coolers and water dispensers shall not be installed in public
restrooms.
SECTION 411
EMERGENCY SHOWERS
AND EYEWASH STATIONS
411.1 Approval. Emergency showers and eyewash stations
shall conform to ISEA Z358.1.
411.2 Waste connection. Waste connections shall not be
required for emergency showers and eyewash stations.
411.3 Water supply. Where hot and cold water is supplied
to an emergency shower or eyewash station, the temperature
of the water supply shall only be controlled by a temperature-actuated mixing valve complying with ASSE 1071.
Where water is supplied directly to an emergency shower or
eyewash station from a water heater, the water heater shall
comply with ASSE 1085.
SECTION 412
FAUCETS AND FIXTURE FITTINGS
412.1 Approval. Faucets and fixture fittings shall conform
to ASME A112.18.1/CSA B125.1. Faucets and fixture
fittings that supply drinking water for human ingestion shall
conform to the requirements of NSF 61, Section 9. Flexible
water connectors exposed to continuous pressure shall
conform to the requirements of Section 605.6.
412.1.1 Faucets and supply fittings. Faucets and supply
fittings shall conform to the water consumption requirements of Section 604.4.
4-8
412.1.2 Waste fittings. Waste fittings shall conform to
ASME A112.18.2/CSA B125.2, ASTM F409 or to one of
the standards listed in Tables 702.1 and 702.4 for
aboveground drainage and vent pipe and fittings.
412.2 Hand showers. Hand-held showers shall conform to
ASME A112.18.1/CSA B125.1. Hand-held showers shall
provide backflow protection in accordance with ASME
A112.18.1/CSA B125.1 or shall be protected against backflow by a device complying with ASME A112.18.3.
412.3 Individual shower valves. Individual shower and tubshower combination valves shall be balanced-pressure, thermostatic or combination balanced-pressure/thermostatic
valves that conform to the requirements of ASSE
1016/ASME A112.1016/CSA B125.16 or ASME
A112.18.1/CSA B125.1. Such valves shall be installed at the
point of use. Shower control valves shall be rated for the
flow rate of the installed shower head. Shower and tubshower combination valves required by this section shall be
equipped with a means to limit the maximum setting of the
valve to 120°F (49°C), which shall be field adjusted in
accordance with the manufacturer’s instructions to provide
water at a temperature not to exceed 120°F (49°C). In-line
thermostatic valves shall not be utilized for compliance with
this section.
412.4 Multiple (gang) showers. Multiple (gang) showers
supplied with a single, tempered water supply pipe shall
have the water supply for such showers controlled by an
approved automatic temperature control mixing valve that
conforms to ASSE 1069 or CSA B125.3, or each shower
head shall be individually controlled by a balanced-pressure,
thermostatic or combination balanced-pressure/thermostatic
valve that conforms to ASSE 1016/ASME A112.1016/CSA
B125.16 or ASME A112.18.1/CSA B125.1 and that is
installed at the point of use. Where a shower head is individually controlled, shower control valves shall be rated for the
flow rate of the installed shower head. Such valves shall be
equipped with a means to limit the maximum setting of the
valve to 120°F (49°C), which shall be field adjusted in
accordance with the manufacturer’s instructions to provide
water at a temperature not to exceed 120°F (49°C). Access
shall be provided to an ASSE 1069 or CSA B125.3 valve.
412.5 Bathtub and whirlpool bathtub valves. Bathtubs and
whirlpool bathtub valves shall have or be supplied by a
water-temperature-limiting device that conforms to ASSE
1070/ASME A112.1070/CSA B125.70 or by a water heater
complying with ASSE 1082 or ASSE 1084, except where
such valves are combination tub/shower valves in accordance with Section 412.3. The water-temperature-limiting
device required by this section shall be equipped with a
means to limit the maximum setting of the device to 120°F
(49°C), and, where adjustable, shall be field adjusted in
accordance with the manufacturer’s instructions to provide
hot water at a temperature not to exceed 120°F (49°C).
Access shall be provided to water-temperature-limiting
devices that conform to ASSE 1070/ASME A112.1070/CSA
B125.70.
Exception: Access shall not be required for nonadjustable
water-temperature-limiting devices that conform to ASSE
2021 INTERNATIONAL PLUMBING CODE®
FIXTURES, FAUCETS AND FIXTURE FITTINGS
1070/ASME A112.1070/CSA B125.70 and are integral
with a fixture fitting, provided that the fixture fitting itself
can be accessed for replacement.
412.6 Hose-connected outlets. Faucets and fixture fittings
with hose-connected outlets shall conform to ASME
A112.18.3 or ASME A112.18.1/CSA B125.1.
412.7 Temperature-actuated, flow-reduction devices for
individual fixture fittings. Temperature-actuated, flowreduction devices, where installed for individual fixture
fittings, shall conform to ASSE 1062. A temperature-actuated, flow-reduction device shall be an approved method for
limiting the water temperature to not greater than 120° F
(49° C) at the outlet of a faucet or fixture fitting. Such
devices shall not be used alone as a substitute for the
balanced-pressure, thermostatic or combination shower
valves required in Section 412.3 or as a substitute for bathtub
or whirlpool tub water-temperature-limiting valves required
in Section 412.5.
412.8 Transfer valves. Deck-mounted bath/shower transfer
valves containing an integral atmospheric vacuum breaker
shall conform to the requirements of ASME A112.18.1/CSA
B125.1.
412.9 Water closet personal hygiene devices. Personal
hygiene devices integral to water closets or water closet seats
shall conform to the requirements of ASME A112.4.2/CSA
B45.16.
412.10 Head shampoo sink faucets. Head shampoo sink
faucets shall be supplied with hot water that is limited to not
more than 120°F (49°C). Each faucet shall have integral
check valves to prevent crossover flow between the hot and
cold water supply connections. The means for regulating the
maximum temperature shall be one of the following:
1.
2.
3.
A limiting device conforming to ASSE 1070/ASME
A112.1070/CSA B125.70.
A water heater conforming to ASSE 1082.
A temperature-actuated, flow-reduction device conforming to ASSE 1062.
412.11 Prerinse spray valve. Prerinse spray valves for
commercial food service shall conform to ASME
A112.18.1/CSA B125.1.
413.4 Public laundries and central washing facilities. In
public coin-operated laundries and in the central washing
facilities of multiple-family dwellings, the rooms containing
automatic clothes washers shall be provided with floor
drains located to readily drain the entire floor area. Such
drains shall have an outlet of not less than 3 inches (76 mm)
in diameter.
SECTION 414
FLOOR SINKS
414.1 Approval. Sanitary floor sinks shall conform to the
requirements of ASME A112.6.7.
SECTION 415
FLUSHING DEVICES FOR
WATER CLOSETS AND URINALS
415.1 Flushing devices required. Each water closet, urinal,
clinical sink and any plumbing fixture that depends on trap
siphonage to discharge the fixture contents to the drainage
system shall be provided with a flushometer valve, flushometer tank or a flush tank designed and installed to supply
water in quantity and rate of flow to flush the contents of the
fixture, cleanse the fixture and refill the fixture trap.
415.1.1 Separate for each fixture. A flushing device
shall not serve more than one fixture.
415.2 Flushometer valves and tanks. Flushometer valves
and tanks shall comply with ASSE 1037/ASME
A112.1037/CSA B125.37 or CSA B125.3. Vacuum breakers
on flushometer valves shall conform to the performance
requirements of ASSE 1001 or CSA B64.1.1. Access shall be
provided to vacuum breakers. Flushometer valves shall be of
the water-conservation type and shall not be used where the
water pressure is lower than the minimum required for
normal operation. When operated, the valve shall automatically complete the cycle of operation, opening fully and
closing positively under the water supply pressure. Each
flushometer valve shall be provided with a means for regulating the flow through the valve. The trap seal to the fixture
shall be automatically refilled after each flushing cycle.
413.1 Approval. Floor drains shall conform to ASME
A112.3.1, ASME A112.6.3 or CSA B79. Trench drains shall
comply with ASME A112.6.3.
415.3 Flush tanks. Flush tanks equipped for manual flushing shall be controlled by a device designed to refill the tank
after each discharge and to shut off completely the water
flow to the tank when the tank is filled to operational capacity. The trap seal to the fixture shall be automatically refilled
after each flushing. The water supply to flush tanks equipped
for automatic flushing shall be controlled with a timing
device or sensor control devices.
413.2 Floor drains. Floor drains shall have removable
strainers. The floor drain shall be constructed so that the
drain is capable of being cleaned. Access shall be provided to
the drain inlet. Ready access shall be provided to floor
drains.
415.3.1 Fill valves. Flush tanks shall be equipped with an
antisiphon fill valve conforming to ASSE 1002/ASME
A112.1002/CSA B125.12 or CSA B125.3. The fill valve
backflow preventer shall be located not less than 1 inch
(25 mm) above the full opening of the overflow pipe.
Exception: Floor drains serving refrigerated display
cases shall be provided with access.
415.3.2 Overflows in flush tanks. Flush tanks shall be
provided with overflows discharging to the water closet
or urinal connected thereto and shall be sized to prevent
flooding the tank at the maximum rate at which the tanks
SECTION 413
FLOOR AND TRENCH DRAINS
413.3 Size of floor drains. Floor drains shall have a drain
outlet not less than 2 inches (51 mm) in diameter.
2021 INTERNATIONAL PLUMBING CODE®
4-9
FIXTURES, FAUCETS AND FIXTURE FITTINGS
are supplied with water according to the manufacturer’s
design conditions. The opening of the overflow pipe shall
be located above the flood level rim of the water closet or
urinal or above a secondary overflow in the flush tank.
415.3.3 Sheet copper. Sheet copper utilized for flush
tank linings shall conform to ASTM B152 and shall not
weigh less than 10 ounces per square foot (0.03 kg/m2).
415.3.4 Access required. All parts in a flush tank shall be
provided with access for repair and replacement.
415.4 Flush pipes and fittings. Flush pipes and fittings shall
be of nonferrous material and shall conform to ASME
A112.19.5/CSA B45.15.
SECTION 416
FOOD WASTE DISPOSER UNITS
416.1 Approval. Domestic food waste disposers shall
conform to ASSE 1008 and shall be listed and labeled in
accordance with UL 430. Commercial food waste disposers
shall be listed and labeled in accordance with UL 430. Food
waste disposers shall not increase the drainage fixture unit
load on the sanitary drainage system.
416.2 Domestic food waste disposer waste outlets. Domestic food waste disposers shall be connected to a drain of not
less than 11/2 inches (38 mm) in diameter.
416.3 Commercial food waste disposer waste outlets.
Commercial food waste disposers shall be connected to a
drain not less than 11/2 inches (38 mm) in diameter.
Commercial food waste disposers shall be connected and
trapped separately from any other fixtures or sink
compartments.
416.4 Water supply required. Food waste disposers shall
be provided with a supply of cold water. The water supply
shall be protected against backflow by an air gap or backflow preventer in accordance with Section 608.
SECTION 417
GARBAGE CAN WASHERS
417.1 Water connection. The water supply to a garbage can
washer shall be protected against backflow by an air gap or a
backflow preventer in accordance with Section 608.14.1,
608.14.2, 608.14.3, 608.14.5, 608.14.6 or 608.14.8.
418.2 Waste outlet. Each compartment of a laundry tray
shall be provided with a waste outlet not less than 11/2 inches
(38 mm) in diameter and a strainer or crossbar to restrict the
clear opening of the waste outlet.
SECTION 419
LAVATORIES
419.1 Approval. Lavatories shall conform to ASME
A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1,
ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.
Group wash fixtures shall conform to the requirements of
Section 402. For determining the number of lavatories
required by Table 403.1, every 20 inches (508 mm) of rim
space of a group wash fixture shall be considered as one
lavatory.
419.2 Cultured marble lavatories. Cultured marble vanity
tops with an integral lavatory shall conform to CSA
B45.5/IAPMO Z124.
419.3 Lavatory waste outlets. Lavatories and group wash
fixtures shall have a waste outlet not less than 11/4 inches (32
mm) in diameter. A strainer, pop-up stopper, crossbar or
other device shall be provided to restrict the clear opening of
the waste outlet.
419.4 Movable lavatory systems. Movable lavatory
systems shall comply with ASME A112.19.12.
419.5 Tempered water for public hand-washing facilities.
Tempered water shall be delivered from lavatories and group
wash fixtures located in public toilet facilities provided for
customers, patrons and visitors. Tempered water shall be
delivered through an approved water-temperature limiting
device that conforms to ASSE 1070/ASME A112.1070/CSA
B125.70.
SECTION 420
MANUAL FOOD AND
BEVERAGE DISPENSING EQUIPMENT
420.1 Approval. Manual food and beverage dispensing
equipment shall conform to the requirements of NSF 18.
SECTION 421
SHOWERS
417.2 Waste connection. Garbage can washers shall be
trapped separately. The receptacle receiving the waste from
the washer shall have a removable basket or strainer to
prevent the discharge of large particles into the drainage
system.
421.1 Approval. Prefabricated showers and shower
compartments shall conform to ASME A112.19.1/CSA
B45.2,
ASME
A112.19.2/CSA
B45.1,
ASME
A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.
Shower valves for individual showers shall conform to the
requirements of Section 412.3.
SECTION 418
LAUNDRY TRAYS
421.2 Water supply riser. Water supply risers from the
shower valve to the shower head outlet, whether exposed or
concealed, shall be attached to the structure. The attachment
to the structure shall be made by the use of support devices
designed for use with the specific piping material or by
fittings anchored with screws.
418.1 Approval. Laundry trays shall conform to ASME
A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1,
ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.
4-10
2021 INTERNATIONAL PLUMBING CODE®
FIXTURES, FAUCETS AND FIXTURE FITTINGS
421.3 Shower waste outlet. Waste outlets serving showers
shall be not less than 11/2 inches (38 mm) in diameter and,
for other than waste outlets in bathtubs, shall have removable strainers not less than 3 inches (76 mm) in diameter
with strainer openings not less than 1/4 inch (6.4 mm) in least
dimension. Where each shower space is not provided with an
individual waste outlet, the waste outlet shall be located and
the floor pitched so that waste from one shower does not
flow over the floor area serving another shower. Waste
outlets shall be fastened to the waste pipe in an approved
manner.
421.3.1 Waste fittings. Waste fittings shall conform to
ASME A112.18.2/CSA B125.2.
421.4 Shower compartments. Shower compartments shall
be not less than 900 square inches (0.58 m2) in interior crosssectional area. Shower compartments shall be not less than
30 inches (762 mm) in least dimension as measured from the
finished interior dimension of the compartment, exclusive of
fixture valves, showerheads, soap dishes and safety grab bars
or rails. Except as required in Section 404, the minimum
required area and dimension shall be measured from the
finished interior dimension at a height equal to the top of the
threshold and at a point tangent to its centerline and shall be
continued to a height not less than 70 inches (1778 mm)
above the shower drain outlet.
Exception: Shower compartments having not less than
25 inches (635 mm) in minimum dimension measured
from the finished interior dimension of the compartment,
provided that the shower compartment has not less than
1,300 square inches (0.838 m2) of cross-sectional area.
421.4.1 Floor and wall area. Bathtub floors, shower
floors, wall areas above built-in tubs that have installed
shower heads and walls in shower compartments shall be
constructed of smooth, corrosion-resistant and nonabsorbent waterproof materials. Wall materials shall extend to
a height of not less than 6 feet (1829 mm) above the room
floor level, and not less than 70 inches (1778 mm) above
the drain of the tub or shower. Such walls shall form a
watertight joint with each other and with either the tub or
shower floor.
421.4.2 Access. The shower compartment access and
egress opening shall have a clear and unobstructed
finished width of not less than 22 inches (559 mm).
Shower compartments required to be designed in conformance to accessibility provisions shall comply with
Section 404.1.
421.5 Shower floors or receptors. Floor surfaces shall be
constructed of impervious, noncorrosive, nonabsorbent and
waterproof materials.
421.5.1 Support. Floors or receptors under shower
compartments shall be laid on, and supported by, a
smooth and structurally sound base.
421.5.2 Shower lining. Floors under shower compartments, except where prefabricated receptors have been
provided, shall be lined and made watertight utilizing
material complying with Sections 421.5.2.1 through
2021 INTERNATIONAL PLUMBING CODE®
421.5.2.6. Such liners shall turn up on all sides not less
than 2 inches (51 mm) above the finished threshold level.
Liners shall be recessed and fastened to an approved
backing so as not to occupy the space required for wall
covering, and shall not be nailed or perforated at any
point less than 1 inch (25 mm) above the finished threshold. Liners shall be pitched one-fourth unit vertical in 12
units horizontal (2-percent slope) and shall be sloped
toward the fixture drains and be securely fastened to the
waste outlet at the seepage entrance, making a watertight
joint between the liner and the outlet. The completed liner
shall be tested in accordance with Section 312.9.
Exceptions:
1. Floor surfaces under shower heads provided for
rinsing laid directly on the ground are not
required to comply with this section.
2. Where a sheet-applied, load-bearing, bonded,
waterproof membrane is installed as the shower
lining, the membrane shall not be required to be
recessed.
421.5.2.1 PVC sheets. Plasticized polyvinyl chloride
(PVC) sheets shall meet the requirements of ASTM
D4551. Sheets shall be joined by solvent welding in
accordance with the manufacturer’s installation
instructions.
421.5.2.2 Chlorinated polyethylene (CPE) sheets.
Nonplasticized chlorinated polyethylene sheet shall
meet the requirements of ASTM D4068. The liner
shall be joined in accordance with the manufacturer’s
installation instructions.
421.5.2.3 Sheet lead. Sheet lead shall weigh not less
than 4 pounds per square foot (19.5 kg/m2) and shall be
coated with an asphalt paint or other approved coating.
The lead sheet shall be insulated from conducting
substances other than the connecting drain by 15pound (6.80 kg) asphalt felt or an equivalent. Sheet
lead shall be joined by burning.
421.5.2.4 Sheet copper. Sheet copper shall conform to
ASTM B152 and shall weigh not less than 12 ounces
per square foot (3.7 kg/m2). The copper sheet shall be
insulated from conducting substances other than the
connecting drain by 15-pound (6.80 kg) asphalt felt or
an equivalent. Sheet copper shall be joined by brazing
or soldering.
421.5.2.5 Sheet-applied, load-bearing, bonded,
waterproof membranes. Sheet-applied, load-bearing, bonded, waterproof membranes shall meet the
requirements of ANSI A118.10 and shall be applied in
accordance with the manufacturer’s installation
instructions.
421.5.2.6 Liquid-type, trowel-applied, load-bearing,
bonded waterproof materials. Liquid-type, trowelapplied, load-bearing, bonded waterproof materials
shall meet the requirements of ANSI A118.10 and
shall be applied in accordance with the manufacturer’s
instructions.
4-11
FIXTURES, FAUCETS AND FIXTURE FITTINGS
421.6 Glazing. Windows and doors within a shower enclosure shall conform to the safety glazing requirements of the
International Building Code.
SECTION 422
SINKS
422.1 Approval. Sinks shall conform to ASME
A112.19.1/CSA B45.2, ASME A112.19.2/CSA B45.1,
ASME A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.
422.2 Sink waste outlets. Sinks shall be provided with
waste outlets having a diameter not less than 11/2 inches (38
mm). A strainer or crossbar shall be provided to restrict the
clear opening of the waste outlet.
422.3 Movable sink systems. Movable sink systems shall
comply with ASME A112.19.12.
SECTION 423
SPECIALTY PLUMBING FIXTURES
423.1 Water connections. Baptisteries, ornamental and lily
pools, aquariums, ornamental fountain basins, swimming
pools, and similar constructions, where provided with water
supplies, shall be protected against backflow in accordance
with Section 608.
423.2 Approval. Specialties requiring water and waste
connections shall be submitted for approval.
423.3 Footbaths and pedicure baths. The water supplied to
specialty plumbing fixtures, such as pedicure chairs having
an integral foot bathtub and footbaths, shall be limited to not
greater than 120ºF (49ºC) by a water-temperature-limiting
device that conforms to ASSE 1070/ASME A112.1070/CSA
B125.70 or by a water heater complying with ASSE 1082.
SECTION 424
URINALS
424.1 Approval. Urinals shall conform to ASME
A112.19.2/CSA B45.1, ASME A112.19.19 or CSA
B45.5/IAPMO Z124. Urinals shall conform to the water
consumption requirements of Section 604.4. Water-supplied
urinals shall conform to the hydraulic performance requirements of ASME A112.19.2/CSA B45.1 or CSA
B45.5/IAPMO Z124.
424.2 Substitution for water closets. In each bathroom or
toilet room, urinals shall not be substituted for more than 67
percent of the required water closets in assembly and educational occupancies. Urinals shall not be substituted for more
than 50 percent of the required water closets in all other
occupancies.
SECTION 425
WATER CLOSETS
425.1 Approval. Water closets shall conform to the water
consumption requirements of Section 604.4 and shall
4-12
conform to ASME A112.19.2/CSA B45.1, ASME
A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.
425.1.1 Hydraulic performance. Water closets shall
conform to the hydraulic performance requirements of
ASME A112.19.2/CSA B45.1.
425.1.2 Water closet tanks. Water closet tanks shall
conform to ASME A112.19.2/CSA B45.1, ASME
A112.19.3/CSA B45.4 or CSA B45.5/IAPMO Z124.
425.1.3 Dual flush water closets. Water closets equipped
with a dual flushing device shall comply with ASME
A112.19.14.
425.2 Water closets for public or employee toilet facilities. Water closet bowls for public or employee toilet
facilities shall be of the elongated type.
425.3 Water closet seats. Water closets shall be equipped
with seats of smooth, nonabsorbent material. Seats of water
closets provided for public or employee toilet facilities shall
be of the hinged open-front type. Integral water closet seats
shall be of the same material as the fixture. Water closet
seats shall be sized for the water closet bowl type.
425.4 Water closet connections. A 4-inch by 3-inch (102
mm by 76 mm) closet bend shall be acceptable. Where a 3inch (76 mm) bend is utilized on water closets, a 4-inch by 3inch (102 mm by 76 mm) flange shall be installed to receive
the fixture horn.
SECTION 426
WHIRLPOOL BATHTUBS
426.1 Approval. Whirlpool bathtubs shall comply with
ASME A112.19.7/CSA B45.10 and shall be listed and
labeled in accordance with UL 1795.
426.2 Installation. Whirlpool bathtubs shall be installed and
tested in accordance with the manufacturer’s instructions.
The pump shall be located above the weir of the fixture trap.
426.3 Drain. The pump drain and circulation piping shall be
sloped to drain the water in the volute and the circulation
piping when the whirlpool bathtub is empty.
426.4 Suction fittings. Suction fittings for whirlpool bathtubs shall comply with ASME A112.19.7/CSA B45.10.
426.5 Access to pump. Access shall be provided to circulation pumps in accordance with the fixture or pump
manufacturer’s installation instructions. Where the manufacturer’s instructions do not specify the location and minimum
size of field-fabricated access openings, an opening not less
than 12 inches by 12 inches (305 mm by 305 mm) shall be
installed to provide access to the circulation pump. Where
pumps are located more than 2 feet (609 mm) from the
access opening, an opening not less than 18 inches by 18
inches (457 mm by 457 mm) shall be installed. A door or
panel shall be permitted to close the opening. In all cases, the
access opening shall be unobstructed and of the size necessary to permit the removal and replacement of the circulation
pump.
426.6 Whirlpool enclosure. Doors within a whirlpool
enclosure shall conform to ASME A112.19.15.
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 5
WATER HEATERS
User note:
About this chapter: Chapter 5 contains regulations concerning the safety of water heating units and hot water storage tanks. Heated (hot
or tempered) potable water is needed for plumbing fixtures that are associated with handwashing, bathing, culinary activities and building
maintenance. Heated water is commonly stored in large pressurized storage tanks that must be protected against explosion by pressure
and temperature relief valves specified in this chapter. This chapter also covers the access requirements to water heaters and hot water
storage tanks to allow for the maintenance and replacement of that equipment.
SECTION 501
GENERAL
SECTION 502
INSTALLATION
501.1 Scope. The provisions of this chapter shall govern the
materials, design and installation of water heaters and the
related safety devices and appurtenances.
502.1 General. Water heaters shall be installed in accordance with the manufacturer’s instructions. Oil-fired water
heaters shall conform to the requirements of this code and
the International Mechanical Code. Electric water heaters
shall conform to the requirements of this code and provisions
of NFPA 70. Gas-fired water heaters shall conform to the
requirements of the International Fuel Gas Code. Solar thermal water heating systems shall conform to the requirements
of the International Mechanical Code and ICC 900/SRCC
300.
501.2 Water heater as space heater. Where a combination
potable water heating and space heating system requires
water for space heating at temperatures greater than 140°F
(60°C), a temperature-actuated mixing valve complying with
ASSE 1017 shall be provided to limit the water supplied to
the potable hot water distribution system to a temperature of
140°F (60°C) or less. The potability of the water shall be
maintained throughout the system. Requirements for combination potable water heating and space heating systems shall
be in accordance with the International Mechanical Code.
501.3 Drain valves. Drain valves for emptying shall be
installed at the bottom of each tank-type water heater and hot
water storage tank. The drain valve inlet shall be not less
than 3/4-inch (19 mm) nominal iron pipe size and the outlet
shall be provided with male garden hose threads.
501.4 Location. Water heaters and storage tanks shall be
located and connected so as to provide access for observation, maintenance, servicing and replacement.
501.5 Water heater labeling. Water heaters shall be thirdparty certified.
501.6 Water temperature control in piping from tankless
heaters. The temperature of water from tankless water heaters shall be not greater than 140°F (60°C) where intended for
domestic uses. This provision shall not supersede the
requirement for protective shower valves in accordance with
Section 412.3.
501.7 Pressure marking of storage tanks. Storage tanks
and water heaters installed for domestic hot water shall have
the maximum allowable working pressure clearly and indelibly stamped in the metal or marked on a plate welded thereto
or otherwise permanently attached. Such markings shall be
in a position with access on the outside of the tank so as to
make inspection or reinspection readily possible.
501.8 Temperature controls. Hot water supply systems
shall be equipped with automatic temperature controls capable of adjustments from the lowest to the highest acceptable
temperature settings for the intended temperature operating
range.
2021 INTERNATIONAL PLUMBING CODE®
502.1.1 Elevation and protection. Elevation of water
heater ignition sources and mechanical damage protection
requirements for water heaters shall be in accordance
with the International Mechanical Code and the International Fuel Gas Code.
502.2 Rooms used as a plenum. Water heaters using solid,
liquid or gas fuel shall not be installed in a room containing
air-handling machinery where such room is used as a
plenum.
502.3 Water heaters installed in attics. Attics containing a
water heater shall be provided with an opening and unobstructed passageway large enough to allow removal of the
water heater. The passageway shall be not less than 30
inches (762 mm) in height and 22 inches (559 mm) in width
and not more than 20 feet (6096 mm) in length when
measured along the centerline of the passageway from the
opening to the water heater. The passageway shall have
continuous solid flooring not less than 24 inches (610 mm)
in width. A level service space not less than 30 inches (762
mm) in length and 30 inches (762 mm) in width shall be
present at the front or service side of the water heater. The
clear access opening dimensions shall be not less than 20
inches by 30 inches (508 mm by 762 mm) where such
dimensions are large enough to allow removal of the water
heater.
502.4 Seismic supports. Where earthquake loads are applicable in accordance with the International Building Code,
water heater supports shall be designed and installed for the
seismic forces in accordance with the International Building
Code.
502.5 Clearances for maintenance and replacement.
Appliances shall be provided with access for inspection,
5-1
WATER HEATERS
service, repair and replacement without disabling the function of a fire-resistance-rated assembly or removing
permanent construction, other appliances or any other piping
or ducts not connected to the appliance being inspected,
serviced, repaired or replaced. A level working space not
less than 30 inches in length and 30 inches in width (762 mm
by 762 mm) shall be provided in front of the control side to
service an appliance.
SECTION 503
CONNECTIONS
503.1 Cold water line valve. The cold water branch line
from the main water supply line to each hot water storage
tank or water heater shall be provided with a valve, located
near the equipment and serving only the hot water storage
tank or water heater. The valve shall not interfere or cause a
disruption of the cold water supply to the remainder of the
cold water system. The valve shall be provided with access
on the same floor level as the water heater served.
503.2 Water circulation. The method of connecting a circulating water heater to the tank shall provide proper
circulation of water through the water heater. The pipe or
tubes required for the installation of appliances that will
draw from the water heater or storage tank shall comply with
the provisions of this code for material and installation.
SECTION 504
SAFETY DEVICES
504.1 Antisiphon devices. An approved means, such as a
cold water “dip” tube with a hole at the top or a vacuum
relief valve installed in the cold water supply line above the
top of the heater or tank, shall be provided to prevent siphoning of any storage water heater or tank.
504.2 Vacuum relief valve. Bottom fed water heaters and
bottom fed tanks connected to water heaters shall have a
vacuum relief valve installed. The vacuum relief valve shall
comply with ANSI Z21.22.
504.3 Shutdown. A means for disconnecting an electric hot
water supply system from its energy supply shall be
provided in accordance with NFPA 70. A separate valve
shall be provided to shut off the energy fuel supply to all
other types of hot water supply systems.
504.4 Relief valve. Storage water heaters operating above
atmospheric pressure shall be provided with an approved,
self-closing (levered) pressure relief valve and temperature
relief valve or combination thereof. The relief valve shall
conform to ANSI Z21.22. The relief valve shall not be used
as a means of controlling thermal expansion.
504.4.1 Installation. Such valves shall be installed in the
shell of the water heater tank. Temperature relief valves
shall be located in the tank so as to be actuated by the
water in the top 6 inches (152 mm) of the tank served. For
installations with separate storage tanks, the approved,
self-closing (levered) pressure relief valve and temperature relief valve or combination thereof conforming to
ANSI Z21.22 valves shall be installed on both the storage
5-2
water heater and storage tank. There shall not be a check
valve or shutoff valve between a relief valve and the
heater or tank served.
504.5 Relief valve approval. Temperature and pressure
relief valves, or combinations thereof, and energy cutoff
devices shall bear the label of an approved agency and shall
have a temperature setting of not more than 210°F (99°C)
and a pressure setting not exceeding the tank or water heater
manufacturer’s rated working pressure or 150 psi (1035
kPa), whichever is less. The relieving capacity of each pressure relief valve and each temperature relief valve shall
equal or exceed the heat input to the water heater or storage
tank.
504.6 Requirements for discharge piping. The discharge
piping serving a pressure relief valve, temperature relief
valve or combination thereof shall:
1. Not be directly connected to the drainage system.
2. Discharge through an air gap located in the same
room as the water heater.
3. Not be smaller than the diameter of the outlet of the
valve served and shall discharge full size to the air
gap.
4. Serve a single relief device and shall not connect to
piping serving any other relief device or equipment.
5. Discharge to the floor, to the pan serving the water
heater or storage tank, to a waste receptor or to the
outdoors.
6. Discharge in a manner that does not cause personal
injury or structural damage.
7. Discharge to a termination point that is readily
observable by the building occupants.
8. Not be trapped.
9. Be installed so as to flow by gravity.
10. Terminate not more than 6 inches (152 mm) above
and not less than two times the discharge pipe diameter above the floor or flood level rim of the waste
receptor.
11. Not have a threaded connection at the end of such
piping.
12. Not have valves or tee fittings.
13. Be constructed of those materials listed in Section
605.4 or materials tested, rated and approved for such
use in accordance with ASME A112.4.1.
14. Be one nominal size larger than the size of the relief
valve outlet, where the relief valve discharge piping
is installed with insert fittings. The outlet end of such
tubing shall be fastened in place.
504.7 Required pan. Where a storage tank-type water
heater or a hot water storage tank is installed in a location
where water leakage from the tank will cause damage, the
tank shall be installed in a pan constructed of one of the
following:
1. Galvanized steel or aluminum of not less than 0.0236
inch (0.6010 mm) in thickness.
2021 INTERNATIONAL PLUMBING CODE®
WATER HEATERS
2. Plastic not less than 0.036 inch (0.9 mm) in
thickness.
3. Other approved materials.
A plastic pan shall not be installed beneath a gas-fired
water heater.
504.7.1 Pan size and drain. The pan shall be not less
than 11/2 inches (38 mm) in depth and shall be of sufficient size and shape to receive all dripping or condensate
from the tank or water heater. The pan shall be drained by
an indirect waste pipe having a diameter of not less than
3
/4 inch (19 mm). Piping for safety pan drains shall be of
those materials listed in Table 605.4.
504.7.2 Pan drain termination. The pan drain shall
extend full size and terminate over a suitably located indirect waste receptor or floor drain or extend to the exterior
of the building and terminate not less than 6 inches (152
mm) and not more than 24 inches (610 mm) above the
adjacent ground surface. Where a pan drain was not
previously installed, a pan drain shall not be required for a
replacement water heater installation.
SECTION 505
INSULATION
[E] 505.1 Unfired vessel insulation. Unfired hot water storage tanks shall be insulated to R-12.5 (h × ft2 × °F)/Btu (R2.2 m2 × K/W).
2021 INTERNATIONAL PLUMBING CODE®
5-3
5-4
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 6
WATER SUPPLY AND DISTRIBUTION
User note:
About this chapter: Many plumbing fixtures require a supply of potable water. Other fixtures could be supplied with nonpotable water such
as reclaimed water. Chapter 6 covers the requirements for water distribution piping systems to and within buildings. The regulations include
the types of materials and the connection methods for such systems. The prevention of backflow of contaminated or polluted water into any
potable water system is critical for protection of users of potable water. This chapter regulates the assemblies, devices and methods that
are used for this purpose.
SECTION 601
GENERAL
601.1 Scope. This chapter shall govern the materials, design
and installation of water supply systems, both hot and cold,
for utilization in connection with human occupancy and
habitation and shall govern the installation of individual
water supply systems.
601.2 Solar energy utilization. Solar energy systems used
for heating potable water or using an independent medium
for heating potable water shall comply with the applicable
requirements of this code. The use of solar energy shall not
compromise the requirements for cross connection or protection of the potable water supply system required by this
code.
601.3 Existing piping used for grounding. Existing metallic water service piping used for electrical grounding shall
not be replaced with nonmetallic pipe or tubing until other
approved means of grounding is provided.
601.4 Tests. The potable water distribution system shall be
tested in accordance with Section 312.5.
602.3.1 Sources. Dependent on geological and soil conditions and the amount of rainfall, individual water supplies
are of the following types: drilled well, driven well, dug
well, bored well, spring, stream or cistern. Surface bodies
of water and land cisterns shall not be sources of individual water supply unless properly treated by approved
means to prevent contamination. Individual water
supplies shall be constructed and installed in accordance
with the applicable state and local laws. Where such laws
do not address all of the requirements set forth in NGWA01, individual water supplies shall comply with NGWA01 for those requirements not addressed by state and local
laws.
602.3.2 Minimum quantity. The combined capacity of
the source and storage in an individual water supply
system shall supply the fixtures with water at rates and
pressures as required by this chapter.
602.3.3 Water quality. Water from an individual water
supply shall be approved as potable by the authority
having jurisdiction prior to connection to the plumbing
system.
601.5 Rehabilitation of piping systems. Where pressure
piping systems are rehabilitated using an epoxy lining
system, such lining system shall comply with ASTM F2831.
602.3.4 Disinfection of system. After construction, the
individual water supply system shall be purged of deleterious matter and disinfected in accordance with Section
610.
SECTION 602
WATER REQUIRED
602.3.5 Pumps. Pumps shall be rated for the transport of
potable water. Pumps in an individual water supply
system shall be constructed and installed so as to prevent
contamination from entering a potable water supply
through the pump units. Pumps intended to supply drinking water shall conform to NSF 61. Pumps shall be sealed
to the well casing or covered with a watertight seal.
Pumps shall be designed to maintain a prime and installed
such that ready access is provided to the pump parts of
the entire assembly for repairs.
602.1 General. Structures equipped with plumbing fixtures
and utilized for human occupancy or habitation shall be
provided with a potable supply of water in the amounts and
at the pressures specified in this chapter.
602.2 Potable water required. Only potable water shall be
supplied to plumbing fixtures that provide water for drinking, bathing or culinary purposes, or for the processing of
food, medical or pharmaceutical products. Unless otherwise
provided in this code, potable water shall be supplied to all
plumbing fixtures.
602.3 Individual water supply. Where a potable public
water supply is not available, individual sources of potable
water supply shall be utilized.
2021 INTERNATIONAL PLUMBING CODE®
602.3.5.1 Pump enclosure. The pump room or enclosure around a well pump shall be drained and protected
from freezing by heating or other approved means.
Where pumps are installed in basements, such pumps
shall be mounted on a block or shelf not less than 18
inches (457 mm) above the basement floor. Well pits
shall be prohibited.
6-1
WATER SUPPLY AND DISTRIBUTION
SECTION 603
WATER SERVICE
603.1 Size of water service pipe. The water service pipe
shall be sized to supply water to the structure in the quantities and at the pressures required in this code. The water
service pipe shall be not less than 3/4 inch (19.1 mm) in
diameter.
603.2 Separation of water service and building sewer.
Where water service piping is located in the same trench
with the building sewer, such sewer shall be constructed of
materials listed in Table 702.2. Where the building sewer
piping is not constructed of materials listed in Table 702.2,
the water service pipe and the building sewer shall be horizontally separated by not less than 5 feet (1524 mm) of
undisturbed or compacted earth. The required separation
distance shall not apply where a water service pipe crosses a
sewer pipe, provided that the water service is sleeved to a
point not less than 5 feet (1524 mm) horizontally from the
sewer pipe centerline on both sides of such crossing. The
sleeve shall be of pipe materials listed in Table 605.3, 702.2
or 702.3. The required separation distance shall not apply
where the bottom of the water service pipe, located within 5
feet (1524 mm) of the sewer, is not less than 12 inches (305
mm) above the highest point of the top of the building sewer.
603.2.1 Water service near sources of pollution. Potable water service pipes shall not be located in, under or
above cesspools, septic tanks, septic tank drainage fields
or seepage pits. Where soil or ground water causes
contaminated conditions for piping, analysis shall be
required in accordance with Section 605.1.
SECTION 604
DESIGN OF BUILDING WATER
DISTRIBUTION SYSTEM
604.1 General. The design of the water distribution system
shall conform to accepted engineering practice. Methods
utilized to determine pipe sizes shall be approved.
604.2 System interconnection. At the points of interconnection between the hot and cold water supply piping systems
and the individual fixtures, appliances or devices, provisions
shall be made to prevent flow between such piping systems.
604.3 Water distribution system design criteria. The
water distribution system shall be designed, and pipe sizes
shall be selected such that under conditions of peak demand,
the capacities at the fixture supply pipe outlets shall be not
less than shown in Table 604.3. The minimum flow rate and
flow pressure provided to fixtures and appliances not listed
in Table 604.3 shall be in accordance with the manufacturer’s installation instructions.
604.4 Maximum flow and water consumption. The maximum water consumption flow rates and quantities for all
6-2
plumbing fixtures and fixture fittings shall be in accordance
with Table 604.4.
Exceptions:
1.
2.
3.
4.
5.
Blowout design water closets having a water
consumption not greater than 31/2 gallons (13 L)
per flushing cycle.
Vegetable sprays.
Clinical sinks having a water consumption not
greater than 41/2 gallons (17 L) per flushing cycle.
Service sinks.
Emergency showers.
TABLE 604.3
WATER DISTRIBUTION SYSTEM DESIGN CRITERIA
REQUIRED CAPACITY AT FIXTURE SUPPLY PIPE OUTLETS
FLOW
RATEa
(gpm)
FLOW
PRESSURE
(psi)
4
20
Bidet, thermostatic mixing valve
2
20
Combination fixture
4
8
Dishwasher, residential
2.75
8
Drinking fountain
0.75
8
FIXTURE SUPPLY OUTLET SERVING
Bathtub, balanced-pressure, thermostatic
or combination balanced-pressure/
thermostatic mixing valve
Laundry tray
4
8
Lavatory, private
0.8
8
Lavatory, private, mixing valve
0.8
8
Lavatory, public
0.4
8
Shower
2.5
8
Shower, balanced-pressure, thermostatic
or combination balanced-pressure/
thermostatic mixing valve
2.5b
20
5
8
1.75
8
Sillcock, hose bibb
Sink, residential
Sink, service
3
8
Urinal, valve
12
25
Water closet, blow out, flushometer valve
25
45
Water closet, flushometer tank
1.6
20
Water closet, siphonic, flushometer valve
25
35
Water closet, tank, close coupled
3
20
Water closet, tank, one piece
6
20
For SI:1 pound per square inch = 6.895 kPa, 1 gallon per minute = 3.785 L/m.
a. For additional requirements for flow rates and quantities, see Section
604.4.
b. Where the shower mixing valve manufacturer indicates a lower flow
rating for the mixing valve, the lower value shall be applied.
2021 INTERNATIONAL PLUMBING CODE®
WATER SUPPLY AND DISTRIBUTION
TABLE 604.4
MAXIMUM FLOW RATES AND CONSUMPTION FOR
PLUMBING FIXTURES AND FIXTURE FITTINGS
PLUMBING FIXTURE OR
FIXTURE FITTING
Lavatory, private
Lavatory, public (metering)
Lavatory, public
(other than metering)
a
MAXIMUM FLOW
RATE OR QUANTITYb
2.2 gpm at 60 psi
0.25 gallon per metering cycle
0.5 gpm at 60 psi
Shower head
2.5 gpm at 80 psi
Sink faucet
2.2 gpm at 60 psi
Urinal
1.0 gallon per flushing cycle
Water closet
1.6 gallons per flushing cycle
For SI: 1 gallon = 3.785 L, 1 gallon per minute = 3.785 L/m,
1 pound per square inch = 6.895 kPa.
a. A hand-held shower spray is a shower head.
b. Consumption tolerances shall be determined from referenced standards.
604.5 Size of fixture supply. The minimum size of a fixture
supply pipe shall be as shown in Table 604.5. The fixture
supply pipe shall terminate not more than 30 inches (762
mm) from the point of connection to the fixture. A reducedsize flexible water connector installed between the supply
pipe and the fixture shall be of an approved type. The supply
pipe shall extend to the floor or wall adjacent to the fixture.
The minimum size of individual distribution lines utilized in
gridded or parallel water distribution systems shall be as
shown in Table 604.5.
604.6 Variable street pressures. Where street water main
pressures fluctuate, the building water distribution system
shall be designed for the minimum pressure available.
604.7 Inadequate water pressure. Wherever water pressure
from the street main or other source of supply is insufficient
to provide flow pressures at fixture outlets as required under
Table 604.3, a water pressure booster system conforming to
Section 606.5 shall be installed on the building water supply
system.
604.8 Water pressure-reducing valve or regulator. Where
water pressure within a building exceeds 80 psi (552 kPa)
static, an approved water pressure-reducing valve conforming to ASSE 1003 or CSA B356 with strainer shall be
installed to reduce the pressure in the building water distribution piping to not greater than 80 psi (552 kPa) static.
Exception: Service lines to sill cocks and outside
hydrants, and main supply risers where pressure from the
mains is reduced to 80 psi (552 kPa) or less at individual
fixtures.
604.8.1 Valve design. The pressure-reducing valve shall
be designed to remain open to permit uninterrupted water
flow in case of valve failure.
604.8.2 Repair and removal. Water pressure-reducing
valves, regulators and strainers shall be so constructed
and installed as to permit repair or removal of parts without breaking a pipeline or removing the valve and strainer
from the pipeline.
2021 INTERNATIONAL PLUMBING CODE®
TABLE 604.5
MINIMUM SIZES OF FIXTURE WATER SUPPLY PIPES
MINIMUM PIPE SIZE
(inch)
FIXTURE
Bathtubsa (60″ × 32″ and smaller)
a
1
/2
Bathtubs (larger than 60″ × 32″)
1
Bidet
3
Combination sink and tray
1
/2
/8
/2
a
Dishwasher, domestic
1
Drinking fountain
3
Hose bibbs
1
Kitchen sink
/2
/8
/2
a
1
/2
a
Laundry, 1, 2 or 3 compartments
1
Lavatory
3
Shower, single heada
1
Sinks, flushing rim
3
Sinks, service
1
Urinal, flush tank
1
Urinal, flushometer valve
3
Wall hydrant
1
Water closet, flush tank
3
Water closet, flushometer tank
3
Water closet, flushometer valve
Water closet, one piecea
/2
/8
/2
/4
/2
/2
/4
/2
/8
/8
1
1
/2
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm,
1 pound per square inch = 6.895 kPa.
a. Where the developed length of the distribution line is 50 feet or less, and
the available pressure at the meter is 35 psi or greater, the minimum size
of an individual distribution line supplied from a manifold and installed
as part of a parallel water distribution system shall be one nominal tube
size smaller than the sizes indicated.
604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of
water hammer. A water-hammer arrestor shall be installed
where quick-closing valves are utilized. Water-hammer
arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform
to ASSE 1010.
604.10 Gridded and parallel water distribution system
manifolds. Hot water and cold water manifolds installed
with gridded or parallel connected individual distribution
lines to each fixture or fixture fitting shall be designed in
accordance with Sections 604.10.1 through 604.10.3.
604.10.1 Manifold sizing. Hot water and cold water
manifolds shall be sized in accordance with Table
604.10.1. The total gallons per minute is the demand of
all outlets supplied.
6-3
WATER SUPPLY AND DISTRIBUTION
TABLE 604.10.1
MANIFOLD SIZING
NOMINAL SIZE
INTERNAL DIAMETER
(inches)
MAXIMUM DEMAND (gpm)
Velocity at
4 feet per second
Velocity at
8 feet per second
1
2
5
3
/4
1
6
10
11
20
11/4
11/2
15
22
31
44
/2
For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m,
1 foot per second = 0.305 m/s.
and ground water contaminated with solvents, fuels, organic
compounds or other detrimental materials causing permeation, corrosion, degradation or structural failure of the
piping material. Where detrimental conditions are suspected,
a chemical analysis of the soil and ground water conditions
shall be required to ascertain the acceptability of the water
service or water distribution piping material for the specific
installation. Where detrimental conditions exist, approved
alternative materials or routing shall be required.
605.2 Lead content of water supply pipe and fittings. Pipe
and pipe fittings, including valves and faucets, utilized in the
water supply system shall have not more than 8-percent lead
content.
604.10.2 Valves. Individual fixture shutoff valves
installed at the manifold shall be identified as to the
fixture being supplied.
605.2.1 Lead content of drinking water pipe and
fittings. Pipe, pipe fittings, joints, valves, faucets and
fixture fittings utilized to supply water for drinking or
cooking purposes shall comply with NSF 372 and shall
have a weighted average lead content of 0.25 percent or
less.
604.10.3 Access. Access shall be provided to manifolds
with integral factory- or field-installed valves.
604.11 Individual pressure balancing in-line valves for
individual fixture fittings. Where individual pressure
balancing in-line valves for individual fixture fittings are
installed, such valves shall comply with ASSE 1066. Such
valves shall be installed in a location with access. The valves
shall not be utilized alone as a substitute for the balanced
pressure, thermostatic or combination shower valves
required in Section 412.3.
SECTION 605
MATERIALS, JOINTS AND CONNECTIONS
605.1 Soil and ground water. The installation of a water
service or water distribution pipe shall be prohibited in soil
605.3 Water service pipe. Water service pipe shall conform
to NSF 61 and shall conform to one of the standards listed in
Table 605.3. Water service pipe or tubing, installed underground and outside of the structure, shall have a working
pressure rating of not less than 160 psi (1100 kPa) at 73.4ºF
(23ºC). Where the water pressure exceeds 160 psi (1100
kPa), piping material shall have a working pressure rating
not less than the highest available pressure. Water service
piping materials not third-party certified for water distribution shall terminate at or before the full open valve located at
the entrance to the structure. Ductile iron water service
piping shall be cement mortar lined in accordance with
AWWA C104/A21.4.
TABLE 605.3
WATER SERVICE PIPE
MATERIAL
Acrylonitrile butadiene styrene (ABS) plastic pipe
Chlorinated polyvinyl chloride (CPVC) plastic pipe
Chlorinated polyvinyl chloride/aluminum/chlorinated polyvinyl chloride
(CPVC/AL/CPVC)
Copper or copper-alloy pipe
Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM)
Cross-linked polyethylene (PEX) plastic pipe and tubing
Cross-linked polyethylene/aluminum/cross-linked polyethylene
(PEX-AL-PEX) pipe
Cross-linked polyethylene/aluminum/high-density polyethylene
(PEX-AL-HDPE)
Ductile iron water pipe
Galvanized steel pipe
Polyethylene (PE) plastic pipe
Polyethylene (PE) plastic tubing
Polyethylene/aluminum/polyethylene (PE-AL-PE) pipe
Polyethylene of raised temperature (PE-RT) plastic tubing
Polypropylene (PP) plastic pipe or tubing
Polyvinyl chloride (PVC) plastic pipe
Stainless steel pipe (Type 304/304L)
Stainless steel pipe (Type 316/316L)
6-4
STANDARD
ASTM D1527; ASTM D2282
ASTM D2846; ASTM F441; ASTM F442; CSA B137.6
ASTM F2855
ASTM B42; ASTM B43; ASTM B302
ASTM B75; ASTM B88; ASTM B251; ASTM B447
ASTM F876; AWWA C904; CSA B137.5
ASTM F1281; ASTM F2262; CSA B137.10
ASTM F1986
AWWA C151/A21.51; AWWA C115/A21.15
ASTM A53
ASTM D2239; ASTM D3035; AWWA C901; CSA B137.1
ASTM D2737; AWWA C901; CSA B137.1
ASTM F1282; CSA B137.9
ASTM F2769; CSA B137.18
ASTM F2389; CSA B137.11
ASTM D1785; ASTM D2241; ASTM D2672; CSA B137.3
ASTM A269/A269M; ASTM A312; ASTM A778
ASTM A269/A269M; ASTM A312; ASTM A778
2021 INTERNATIONAL PLUMBING CODE®
WATER SUPPLY AND DISTRIBUTION
605.5.1.1 Full flow assurance. Branch tubes shall not
restrict the flow in the run tube. A dimple serving as a
depth stop shall be formed in the branch tube to ensure
that penetration into the collar is of the correct depth.
For inspection purposes, a second dimple shall be
placed 1/4 inch (6.4 mm) above the first dimple.
Dimples shall be aligned with the tube run.
605.3.1 Dual check-valve-type backflow preventer.
Dual check-valve backflow preventers installed on the
water supply system shall comply with ASSE 1024 or
CSA B64.6.
605.4 Water distribution pipe. Water distribution pipe and
tubing shall conform to NSF 61 and shall conform to one of
the standards listed in Table 605.4. Hot water distribution
pipe and tubing shall have a pressure rating of not less than
100 psi (690 kPa) at 180ºF (82ºC).
605.5 Fittings. Pipe fittings shall be approved for installation with the piping material installed and shall comply with
the applicable standards listed in Table 605.5. Pipe fittings
utilized in water supply systems shall also comply with NSF
61. Ductile and gray iron pipe and pipe fittings utilized in
water service piping systems shall be cement mortar lined in
accordance with AWWA C104/A21.4.
605.5.1 Mechanically formed tee fittings. Mechanically
extracted outlets shall have a height not less than three
times the thickness of the branch tube wall.
605.5.1.2 Brazed joints. Mechanically formed tee
fittings shall be brazed in accordance with Section
605.14.1.
605.6 Flexible water connectors. Flexible water connectors
exposed to continuous pressure shall conform to ASME
A112.18.6/CSA B125.6. Access shall be provided to all flexible water connectors.
605.7 Valves. Valves shall be compatible with the type of
piping material installed in the system. Valves shall conform
to one of the standards listed in Table 605.7 or shall be
approved. Valves intended to supply drinking water shall
meet the requirements of NSF 61.
TABLE 605.4
WATER DISTRIBUTION PIPE
MATERIAL
STANDARD
Chlorinated polyvinyl chloride (CPVC) plastic pipe and tubing
ASTM D2846; ASTM F441; ASTM F442; CSA B137.6
Chlorinated polyvinyl chloride/aluminum/chlorinated polyvinyl chloride
(CPVC/AL/CPVC)
ASTM F2855
Copper or copper-alloy pipe
ASTM B42; ASTM B43; ASTM B302
Copper or copper-alloy tubing (Type K, WK, L, WL, M or WM)
ASTM B75; ASTM B88; ASTM B251; ASTM B447
Cross-linked polyethylene (PEX) plastic tubing
ASTM F876; CSA B137.5
Cross-linked polyethylene/aluminum/cross-linked polyethylene
(PEX-AL-PEX) pipe
ASTM F1281; ASTM F2262; CSA B137.10
Cross-linked polyethylene/aluminum/high-density polyethylene
(PEX-AL-HDPE)
ASTM F1986
Ductile iron pipe
AWWA C115/A21.15; AWWA C151/A21.51
Galvanized steel pipe
ASTM A53
Polyethylene/aluminum/polyethylene (PE-AL-PE) composite pipe
ASTM F1282
Polyethylene of raised temperature (PE-RT) plastic tubing
ASTM F2769; CSA B137.18
Polypropylene (PP) plastic pipe or tubing
ASTM F2389; CSA B137.11
Stainless steel pipe (Type 304/304L)
ASTM A312; ASTM A778
Stainless steel pipe (Type 316/316L)
ASTM A312; ASTM A778
TABLE 605.7
VALVES
MATERIAL
STANDARD
Chlorinated polyvinyl chloride (CPVC) plastic
ASME A112.4.14; ASME A112.18.1/CSA B125.1; ASTM F1970;
CSA B125.3; IAPMO Z1157; MSS SP-122
Copper or copper alloy
ASME A112.4.14; ASME A112.18.1/CSA B125.1; ASME B16.34;
CSA B125.3; IAPMO Z1157; MSS SP-67; MSS SP-80;
MSS SP-110; MSS SP-139
Cross-linked polyethylene (PEX) plastic
ASME A112.4.14; ASME A112.18.1/CSA B125.1; CSA B125.3;
IAPMO Z1157; NSF 359
Gray iron and ductile iron
AWWA C500; AWWA C504; AWWA C507; IAPMO Z1157;
MSS SP-67; MSS SP-70; MSS SP-71; MSS SP-72; MSS SP-78
Polypropylene (PP) plastic
ASME A112.4.14; ASTM F2389; IAPMO Z1157
Polyvinyl chloride (PVC) plastic
ASME A112.4.14; ASTM F1970; IAPMO Z1157; MSS SP-122
2021 INTERNATIONAL PLUMBING CODE®
6-5
WATER SUPPLY AND DISTRIBUTION
TABLE 605.5
PIPE FITTINGS
MATERIAL
STANDARD
Acrylonitrile butadiene styrene (ABS) plastic
Cast iron
ASTM D2468
ASME B16.4
ASSE 1061; ASTM D2846; ASTM F437; ASTM F438;
ASTM F439; CSA B137.6
ASME B16.15; ASME B16.18; ASME B16.22;
ASME B16.26; ASME B16.51; ASSE 1061; ASTM F1476;
ASTM F1548; ASTM F3226
Chlorinated polyvinyl chloride (CPVC) plastic
Copper or copper alloy
Cross-linked polyethylene/aluminum/high-density polyethylene
(PEX-AL-HDPE)
ASTM F1986
ASSE 1061; ASTM F877; ASTM F1807; ASTM F1960;
ASTM F2080; ASTM F2098; ASTM F2159; ASTM F2434;
ASTM F2735; CSA B137.5
ASSE 1061; ASTM D3261; ASTM F1807; ASTM F2098;
ASTM F2159; ASTM F2735; ASTM F2769; CSA B137.18
ASTM F1476; ASTM F1548; AWWA C110/A21.10;
AWWA C153/A21.53;
Fittings for cross-linked polyethylene (PEX) plastic tubing
Fittings for polyethylene of raised temperature (PE-RT) plastic tubing
Gray iron and ductile iron
Insert fittings for polyethylene/aluminum/polyethylene (PE-AL-PE) and
cross-linked polyethylene/aluminum/cross-linked polyethylene
(PEX-AL-PEX)
Malleable iron
Metal (brass) insert fittings for polyethylene/aluminum/polyethylene
(PE-AL-PE) and cross-linked polyethylene/aluminum/cross-linked polyethylene (PEX-AL-PEX)
ASME B16.3
ASTM F1974
ASTM D2609; ASTM D2683; ASTM D3261; ASTM F1055;
CSA B137.1
ASTM F2389; CSA B137.11
ASTM D2464; ASTM D2466; ASTM D2467; CSA B137.2;
CSA B137.3
ASTM A312; ASTM A778; ASTM F1476; ASTM F1548;
ASTM F3226
ASTM A312; ASTM A778; ASTM F1476; ASTM F1548;
ASTM F3226
ASME B16.9; ASME B16.11; ASME B16.28; ASTM F1476;
ASTM F1548
Polyethylene (PE) plastic pipe
Polypropylene (PP) plastic pipe or tubing
Polyvinyl chloride (PVC) plastic
Stainless steel (Type 304/304L)
Stainless steel (Type 316/316L)
Steel
605.8 Manufactured pipe nipples. Manufactured pipe
nipples shall conform to one of the standards listed in Table
605.8.
TABLE 605.8
MANUFACTURED PIPE NIPPLES
MATERIAL
STANDARD
Copper, copper alloy, and chromium-plated
ASTM B687
Steel
ASTM A733
605.9 Prohibited joints and connections. The following
types of joints and connections shall be prohibited:
1. Cement or concrete joints.
2. Joints made with fittings not approved for the
specific installation.
3. Solvent-cement joints between different types of
plastic pipe.
4. Saddle-type fittings.
6-6
ASTM F1281; ASTM F1282; ASTM F1974; CSA B137.9;
CSA B137.10
605.10 ABS plastic. Joints between ABS plastic pipe and
fittings shall comply with Sections 605.10.1 through
605.10.3.
605.10.1 Mechanical joints. Mechanical joints on water
pipes shall be made with an elastomeric seal conforming
to ASTM D3139. Mechanical joints shall only be
installed in underground systems, unless otherwise
approved. Joints shall be installed only in accordance
with the manufacturer’s instructions.
605.10.2 Solvent cementing. Joint surfaces shall be clean
and free from moisture. Solvent cement that conforms to
ASTM D2235 shall be applied to all joint surfaces. The
joint shall be made while the cement is wet. Joints shall
be made in accordance with ASTM D2235. Solventcement joints shall be permitted above or below ground.
605.10.3 Threaded joints. Threads shall conform to
ASME B1.20.1. Where pipe is to be threaded, the pipe
shall have a wall thickness of not less than Schedule 80.
Pipe threads shall be made with dies specifically designed
2021 INTERNATIONAL PLUMBING CODE®
WATER SUPPLY AND DISTRIBUTION
for plastic pipe. Approved thread lubricant or tape shall be
applied on the male threads only.
605.11 Gray iron and ductile iron joints. Joints for gray
and ductile iron pipe and fittings shall comply with AWWA
C111/A21.11 and shall be installed in accordance with the
manufacturer’s instructions.
cleaned. The tube shall be fully inserted into the pressconnect fitting. Press-connect joints shall be pressed with
a tool certified by the manufacturer.
605.12.1 Brazed joints. Joint surfaces shall be cleaned.
An approved flux shall be applied where required. The
joint shall be brazed with a filler metal conforming to
AWS A5.8.
605.13.6 Solder joints. Solder joints shall be made in
accordance with the methods of ASTM B828. Cut tube
ends shall be reamed to the full inside diameter of the
tube end. Joint surfaces shall be cleaned. A flux conforming to ASTM B813 shall be applied. The joint shall be
soldered with a solder conforming to ASTM B32. The
joining of water supply piping shall be made with leadfree solder and flux. “Lead free” shall mean a chemical
composition equal to or less than 0.2-percent lead. Solder
and flux joining pipe or fittings intended to supply drinking water shall conform to NSF 61.
605.12.2 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
605.13.7 Push-fit fitting joints. Push-fit fittings shall
conform to ASSE 1061 and shall be installed in accordance with the manufacturer’s instructions.
605.12.3 Solder joints. Solder joints shall be made in
accordance with ASTM B828. Cut tube ends shall be
reamed to the full inside diameter of the tube end. Joint
surfaces shall be cleaned. A flux conforming to ASTM
B813 shall be applied. The joint shall be soldered with a
solder conforming to ASTM B32. The joining of water
supply piping shall be made with lead-free solder and
fluxes. “Lead free” shall mean a chemical composition
equal to or less than 0.2-percent lead. Solder and flux
joining pipe or fittings intended to supply drinking water
shall conform to NSF 61.
605.14 CPVC plastic. Joints between CPVC plastic pipe
and fittings shall comply with Sections 605.14.1 through
605.14.4.
605.12 Copper pipe. Joints between copper or copper-alloy
pipe and fittings shall comply with Sections 605.12.1
through 605.12.5.
605.12.4 Threaded joints. Threads shall conform to
ASME B1.20.1. Pipe-joint compound or tape shall be
applied on the male threads only.
605.12.5 Welded joints. Joint surfaces shall be cleaned.
The joint shall be welded with an approved filler metal.
605.13 Copper tubing. Joints between copper or copperalloy tubing and fittings shall comply with Sections 605.13.1
through 605.13.7.
605.13.1 Brazed joints. Joint surfaces shall be cleaned.
An approved flux shall be applied where required. The
joint shall be brazed with a filler metal conforming to
AWS A5.8.
605.13.2 Flared joints. Flared joints for water pipe shall
be made by a tool designed for that operation.
605.13.3 Grooved and shouldered mechanical joints.
Grooved and shouldered mechanical joints shall comply
with ASTM F1476, shall be made with an approved elastomeric seal and shall be installed in accordance with the
manufacturer’s instructions. Such joints shall be exposed
or concealed.
605.13.4 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
605.13.5 Press-connect joints. Press-connect joints shall
conform to one of the standards indicated in Table 605.5,
and shall be installed in accordance with the manufacturer’s instructions. Cut tube ends shall be reamed to the
full inside diameter of the tube end. Joint surfaces shall be
2021 INTERNATIONAL PLUMBING CODE®
605.14.1 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
605.14.2 Solvent cementing. Joint surfaces shall be clean
and free from moisture. Joints shall be made in accordance with the pipe manufacturer’s installation
instructions. Where such instructions require that a primer
be used, the primer shall be applied to the joint surfaces
and a solvent cement orange in color and conforming to
ASTM F493 shall be applied to the joint surfaces. Where
such instructions allow for a one-step solvent cement,
yellow in color and conforming to ASTM F493, to be
used, the joint surfaces shall not require application of a
primer before the solvent cement is applied. The joint
shall be made while the cement is wet and in accordance
with ASTM D2846 or ASTM F493. Solvent-cement
joints shall be permitted above or below ground.
605.14.3 Threaded joints. Threads shall conform to
ASME B1.20.1. Where pipe is to be threaded, the pipe
shall have a wall thickness of not less than Schedule 80.
Pipe threads shall be made with dies specifically designed
for plastic pipe. The pressure rating of threaded pipe shall
be reduced by 50 percent. Thread-by-socket molded
fittings shall be permitted. Approved thread lubricant or
tape shall be applied on the male threads only.
605.14.4 Push-fit joints. Push-fit joints shall conform to
ASSE 1061 and shall be installed in accordance with the
manufacturer’s instructions.
605.15 Chlorinated polyvinyl chloride/aluminum/chlorinated polyvinyl chloride (CPVC/AL/CPVC) pipe and
tubing. Joints between CPVC/AL/CPVC plastic pipe or
CPVC fittings shall comply with Sections 605.15.1 and
605.15.2.
605.15.1 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
6-7
WATER SUPPLY AND DISTRIBUTION
605.15.2 Solvent cementing. Joint surfaces shall be clean
and free from moisture, and an approved primer shall be
applied. Solvent cement, orange in color and conforming
to ASTM F493, shall be applied to joint surfaces. The
joint shall be made while the cement is wet, and in accordance with ASTM D2846 or ASTM F493. Solvent
cement joints shall be permitted above or below ground.
Exception: A primer is not required where all of the
following conditions apply:
1.
2.
3.
4.
The solvent cement used is third-party certified
as conforming to ASTM F493.
The solvent cement used is yellow in color.
The solvent cement is used only for joining 1/2inch (12.7 mm) through 2-inch-diameter (51
mm) CPVC/AL/CPVC pipe and CPVC fittings.
The CPVC fittings are manufactured in accordance with ASTM D2846.
605.16 PEX plastic. Joints between cross-linked polyethylene plastic tubing and fittings shall comply with Sections
605.16.1 through 605.16.3.
605.16.1 Flared joints. Flared pipe ends shall be made by
a tool designed for that operation.
605.16.2 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s instructions. Fittings for cross-linked polyethylene (PEX) plastic
tubing shall comply with the applicable standards listed in
Table 605.5 and shall be installed in accordance with the
manufacturer’s instructions. PEX tubing shall be factory
marked with the appropriate standards for the fittings that
the PEX manufacturer specifies for use with the tubing.
605.16.3 Push-fit joints. Push-fit joints shall conform to
ASSE 1061 and shall be installed in accordance with the
manufacturer’s instructions.
605.17 Steel. Joints between galvanized steel pipe and
fittings shall comply with Sections 605.17.1 through
605.17.3.
605.17.1 Threaded joints. Threads shall conform to
ASME B1.20.1. Pipe-joint compound or tape shall be
applied on the male threads only.
605.17.2 Mechanical joints. Joints shall be made with an
approved elastomeric seal. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
605.17.3 Grooved and shouldered mechanical joints.
Grooved and shouldered mechanical joints shall comply
with ASTM F1476, shall be made with an approved elastomeric seal and shall be installed in accordance with the
manufacturer’s instructions. Such joints shall be exposed
or concealed.
605.18 PE plastic. Joints between polyethylene plastic pipe
or tubing and fittings shall comply with Sections 605.18.1
through 605.18.4.
605.18.1 Flared joints. Flared joints shall be permitted
where so indicated by the pipe manufacturer. Flared joints
shall be made by a tool designed for that operation.
6-8
605.18.2 Heat-fusion joints. Joint surfaces shall be clean
and free from moisture. Joint surfaces shall be heated to
melt temperature and joined. The joint shall be undisturbed until cool. Joints shall be made in accordance with
ASTM D2657.
605.18.3 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
605.18.4 Installation. Polyethylene pipe shall be cut
square, with a cutter designed for plastic pipe. Except
where joined by heat fusion, pipe ends shall be chamfered
to remove sharp edges. Kinked pipe shall not be installed.
The minimum pipe bending radius shall be not less than
30 pipe diameters, or the minimum coil radius, whichever
is greater. Piping shall not be bent beyond straightening
of the curvature of the coil. Bends shall be prohibited
within 10 pipe diameters of any fitting or valve. Stiffener
inserts installed with compression-type couplings and
fittings shall not extend beyond the clamp or nut of the
coupling or fitting.
605.19 Polypropylene (PP) plastic. Joints between PP plastic pipe and fittings shall comply with Section 605.19.1 or
605.19.2.
605.19.1 Heat-fusion joints. Heat-fusion joints for polypropylene pipe and tubing joints shall be installed with
socket-type heat-fused polypropylene fittings, butt-fusion
polypropylene fittings or electrofusion polypropylene
fittings. Joint surfaces shall be clean and free from moisture. The joint shall be undisturbed until cool. Joints shall
be made in accordance with ASTM F2389.
605.19.2 Mechanical and compression sleeve joints.
Mechanical and compression sleeve joints shall be
installed in accordance with the manufacturer’s
instructions.
605.20 Polyethylene/aluminum/polyethylene (PE-AL-PE)
and cross-linked polyethylene/aluminum/cross-linked
polyethylene (PEX-AL-PEX). Joints between PE-AL-PE
or PEX-AL-PEX pipe and fittings shall comply with Section
605.20.1.
605.20.1 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s instructions. Fittings for PE-AL-PE and PEX-AL-PEX as
described in ASTM F1281, ASTM F1282, ASTM F1974,
CSA B137.9 and CSA B137.10 shall be installed in
accordance with the manufacturer’s instructions.
605.21 PVC plastic. Joints between PVC plastic pipe and
fittings shall comply with Sections 605.21.1 through
605.21.3.
605.21.1 Mechanical joints. Mechanical joints on water
pipe shall be made with an elastomeric seal conforming to
ASTM D3139. Mechanical joints shall not be installed in
above-ground systems unless otherwise approved. Joints
shall be installed in accordance with the manufacturer’s
instructions.
605.21.2 Grooved and shouldered mechanical joints.
Grooved and shouldered mechanical joints shall comply
with ASTM F1476, shall be made with an approved elas2021 INTERNATIONAL PLUMBING CODE®
WATER SUPPLY AND DISTRIBUTION
tomeric seal and shall be installed in accordance with the
manufacturer’s instructions. Such joints shall be exposed
or concealed.
605.24 PE-RT plastic. Joints between polyethylene of
raised temperature plastic tubing and fittings shall be in
accordance with Section 605.24.1.
605.21.3 Solvent cementing. Joint surfaces shall be clean
and free from moisture. A purple primer that conforms to
ASTM F656 shall be applied. Solvent cement not purple
in color and conforming to ASTM D2564 or CSA B137.3
shall be applied to all joint surfaces. The joint shall be
made while the cement is wet and shall be in accordance
with ASTM D2855. Solvent-cement joints shall be
permitted above or below ground.
605.24.1 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s instructions. Fittings for polyethylene of raised temperature
plastic tubing shall comply with the applicable standards
indicated in Table 605.5 and shall be installed in accordance with the manufacturer’s instructions. Polyethylene
of raised temperature plastic tubing shall be factory
marked with the applicable standards for the fittings that
the manufacturer of the tubing specifies for use with the
tubing.
605.21.4 Threaded joints. Threads shall conform to
ASME B1.20.1. Where pipe is to be threaded, the pipe
shall have a wall thickness of not less than Schedule 80.
Pipe threads shall be made with dies specifically designed
for plastic pipe. The pressure rating of threaded pipe shall
be reduced by 50 percent. Thread-by-socket molded
fittings shall be permitted. Approved thread lubricant or
tape shall be applied on the male threads only.
605.22 Stainless steel. Joints between stainless steel pipe
and fittings shall comply with Sections 605.22.1 through
605.22.3.
605.22.1 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
SECTION 606
INSTALLATION OF THE
BUILDING WATER DISTRIBUTION SYSTEM
606.1 Location of full-open valves. Full-open valves shall
be installed in the following locations:
1.
2.
605.22.2 Welded joints. Joint surfaces shall be cleaned.
The joint shall be welded autogenously or with an
approved filler metal as referenced in ASTM A312.
605.22.3 Grooved and shouldered mechanical joints.
Grooved and shouldered mechanical joints shall comply
with ASTM F1476, shall be made with an approved elastomeric seal and shall be installed in accordance with the
manufacturer’s instructions. Such joints shall be exposed
or concealed.
605.23 Joints between different materials. Joints between
different piping materials shall be made with a mechanical
joint of the compression or mechanical-sealing type, or shall
be made in accordance with Section 605.23.1, 605.23.2 or
605.23.3. Connectors or adapters shall have an elastomeric
seal conforming to ASTM F477. Joints shall be installed in
accordance with the manufacturer’s instructions.
605.23.1 Copper or copper-alloy tubing to galvanized
steel pipe. Joints between copper pipe or tubing and
galvanized steel pipe shall be made with a copper-alloy or
dielectric fitting or a dielectric union conforming to
ASSE 1079. The copper tubing shall be soldered to the
fitting in an approved manner, and the fitting shall be
screwed to the threaded pipe
605.23.2 Plastic pipe or tubing to other piping material. Joints between different types of plastic pipe or
between plastic pipe and other piping material shall be
made with approved adapters or transition fittings.
605.23.3 Stainless steel. Joints between stainless steel
and different piping materials shall be made with a
mechanical joint of the compression or mechanical sealing type or a dielectric fitting or a dielectric union
conforming to ASSE 1079.
2021 INTERNATIONAL PLUMBING CODE®
3.
4.
5.
6.
7.
8.
On the building water service pipe from the public
water supply near the curb.
On the water distribution supply pipe at the entrance
into the structure.
2.1. In multiple-tenant buildings, where a
common water supply piping system is
installed to supply other than one- and twofamily dwellings, a main shutoff valve shall
be provided for each tenant.
On the discharge side of every water meter.
On the base of every water riser pipe in occupancies
other than multiple-family residential occupancies
that are two stories or less in height and in one- and
two-family residential occupancies.
On the top of every water down-feed pipe in occupancies other than one- and two-family residential
occupancies.
On the entrance to every water supply pipe to a
dwelling unit, except where supplying a single
fixture equipped with individual stops.
On the water supply pipe to a gravity or pressurized
water tank.
On the water supply pipe to every water heater.
606.2 Location of shutoff valves. Shutoff valves shall be
installed in the following locations:
1.
On the fixture supply to each plumbing fixture other
than bathtubs and showers in one- and two-family
residential occupancies, and other than in individual
sleeping units that are provided with unit shutoff
valves in hotels, motels, boarding houses and similar
occupancies.
2. On the water supply pipe to each sillcock.
3. On the water supply pipe to each appliance or
mechanical equipment.
6-9
WATER SUPPLY AND DISTRIBUTION
606.3 Access to valves. Access shall be provided to all fullopen valves and shutoff valves.
suction side of the pump when a positive pressure of 10 psi
(68.94 kPa) or less occurs on the suction side of the pump.
606.4 Valve identification. Service and hose bibb valves
shall be identified. Other valves installed in locations that are
not adjacent to the fixture or appliance shall be identified,
indicating the fixture or appliance served.
606.5.6 Potable water inlet control and location. Potable water inlets to gravity tanks shall be controlled by a
fill valve or other automatic supply valve installed so as
to prevent the tank from overflowing. The inlet shall be
terminated so as to provide an air gap not less than 4
inches (102 mm) above the overflow.
606.5.1 Water pressure booster systems required.
Where the water pressure in the public water main or
individual water supply system is insufficient to supply
the minimum pressures and quantities specified in this
code, the supply shall be supplemented by an elevated
water tank, a hydropneumatic pressure booster system or
a water pressure booster pump installed in accordance
with Section 606.5.5.
606.5.2 Support. Water supply tanks shall be supported
in accordance with the International Building Code.
606.5.3 Covers. Water supply tanks shall be covered to
keep out unauthorized persons, dirt and vermin. The
covers of gravity tanks shall be vented with a return bend
vent pipe with an area not less than the area of the downfeed riser pipe, and the vent shall be screened with a
corrosion-resistant screen of not less than 16 by 20 mesh
per inch (630 by 787 mesh per m).
606.5.4 Overflows for water supply tanks. A gravity or
suction water supply tank shall be provided with an overflow with a diameter not less than that shown in Table
606.5.4. The overflow outlet shall discharge at a point not
less than 6 inches (152 mm) above the roof or roof drain;
floor or floor drain; or over an open water-supplied
fixture. The overflow outlet shall be covered with a corrosion-resistant screen of not less than 16 by 20 mesh per
inch (630 by 787 mesh per m) and by 1/4-inch (6.4 mm)
hardware cloth or shall terminate in a horizontal angle
seat check valve. Drainage from overflow pipes shall be
directed so as not to freeze on roof walks.
TABLE 606.5.4
SIZES FOR OVERFLOW PIPES FOR WATER SUPPLY TANKS
MAXIMUM CAPACITY OF WATER
SUPPLY LINE TO TANK (gpm)
0 – 50
DIAMETER OF OVERFLOW PIPE
(inches)
2
50 – 150
21/2
150 – 200
3
200 – 400
4
400 – 700
5
700 – 1,000
6
Over 1,000
8
For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m.
606.5.5 Low-pressure cutoff required on booster
pumps. A low-pressure cutoff shall be installed on all
booster pumps in a water pressure booster system to
prevent creation of a vacuum or negative pressure on the
6-10
606.5.7 Tank drain pipes. A drain pipe with a valve
shall be provided at the lowest point of each tank to
permit emptying of the tank. The tank drain pipe shall
discharge as required for overflow pipes and shall not be
smaller in size than specified in Table 606.5.7.
TABLE 606.5.7
SIZE OF DRAIN PIPES FOR WATER TANKS
TANK CAPACITY (gallons)
Up to 750
DRAIN PIPE (inches)
1
11/2
751 to 1,500
1,501 to 3,000
2
3,001 to 5,000
21/2
5,000 to 7,500
3
Over 7,500
4
For SI: 1 inch = 25.4 mm, 1 gallon = 3.785 L.
606.5.8 Prohibited location of potable supply tanks.
Potable water gravity tanks or manholes of potable water
pressure tanks shall not be located directly under any soil
or waste piping or any source of contamination.
606.5.9 Pressure tanks, vacuum relief. Water pressure
tanks shall be provided with a vacuum relief valve at the
top of the tank that will operate up to a maximum water
pressure of 200 psi (1380 kPa) and up to a maximum
temperature of 200ºF (93ºC). The size of such vacuum
relief valve shall be not less than 1/2 inch (12.7 mm).
Exception: This section shall not apply to pressurized
captive air diaphragm/bladder tanks.
606.5.10 Pressure relief for tanks. Every pressure tank
in a hydropneumatic pressure booster system shall be
protected with a pressure relief valve. The pressure relief
valve shall be set at a maximum pressure equal to the
rating of the tank. The relief valve shall be installed on the
supply pipe to the tank or on the tank. The relief valve
shall discharge by gravity to a safe place of disposal.
606.6 Water supply system test. Upon completion of a
section of or the entire water supply system, the system, or
portion completed, shall be tested in accordance with
Section 312.
SECTION 607
HOT WATER SUPPLY SYSTEM
607.1 Where required. In residential occupancies, hot
water shall be supplied to plumbing fixtures and equipment
utilized for bathing, washing, culinary purposes, cleansing,
laundry or building maintenance. In nonresidential occupan-
2021 INTERNATIONAL PLUMBING CODE®

606.5 Water pressure booster systems. Water pressure
booster systems shall be provided as required by Sections
606.5.1 through 606.5.10.
WATER SUPPLY AND DISTRIBUTION
cies, hot water shall be supplied for culinary purposes,
cleansing, laundry or building maintenance purposes. In
nonresidential occupancies, hot water or tempered water
shall be supplied for bathing and washing purposes.
607.1.1 Temperature limiting means. A thermostat
control for a water heater shall only serve as the temperature limiting means for the purposes of complying with
the requirements of this code for maximum allowable hot
or tempered water delivery temperature at fixtures where
the water heater complies with ASSE 1082 or ASSE
1085.
607.1.2 Tempered water temperature control.
Tempered water shall be controlled by one the following:
1.
2.
3.
4.
A limiting device conforming to ASSE
1070/ASME A112.1070/CSA B125.70 and set to
not greater than 110ºF (43ºC).
A thermostatic mixing valve conforming to ASSE
1017.
A water heater conforming to ASSE 1082.
A water heater conforming to ASSE 1084.
This provision shall not supersede the requirement for
protective shower valves in accordance with Section
412.3.
607.2 Hot or tempered water supply to fixtures. The
developed length of hot or tempered water piping, from the
source of hot water to the fixtures that require hot or
tempered water, shall not exceed 50 feet (15 240 mm).
Recirculating system piping and heat-traced piping shall be
considered to be sources of hot or tempered water.
607.2.1 Circulation systems and heat trace systems for
maintaining heated water temperature in distribution
systems. For Group R2, R3 and R4 occupancies that are
three stories or less in height above grade plane, the
installation of heated water circulation and temperature
maintenance systems shall be in accordance with Section
R403.5.1 of the International Energy Conservation Code.
For other than Group R2, R3 and R4 occupancies that are
three stories or less in height above grade plane, the
installation of heated water circulation and heat trace
systems shall be in accordance with Section C404.6 of the
International Energy Conservation Code.
607.2.1.1 Pump controls for hot water storage
systems. The controls on pumps that circulate water
between a water heater and a storage tank for heated
water shall limit operation of the pump from heating
cycle startup to not greater than 5 minutes after the end
of the cycle.
607.2.1.2 Demand recirculation controls for distribution systems. A water distribution system having
one or more recirculation pumps that pump water from
a heated water supply pipe back to the heated water
source through a cold water supply pipe shall be a
demand recirculation water system. Pumps shall have
controls that comply with both of the following:
1.
The control shall start the pump upon receiving
a signal from the action of a user of a fixture or
2021 INTERNATIONAL PLUMBING CODE®
2.
appliance, sensing the presence of a user of a
fixture, or sensing the flow of hot or tempered
water to a fixture fitting or appliance.
The control shall limit the temperature of the
water entering the cold water piping to 104°F
(40°C).
607.2.2 Piping for recirculation systems having
temperature-actuated mixing valves. Where a temperature-actuated mixing valve is used in a system with a hot
water recirculating pump, the hot water or tempered
water return line shall be routed to the cold water inlet
pipe of the water heater and the cold water inlet pipe or
the hot water return connection of the temperature-actuated mixing valve.
607.3 Thermal expansion control. Where a storage water
heater is supplied with cold water that passes through a
check valve, pressure reducing valve or backflow preventer,
a thermal expansion control device shall be connected to the
water heater cold water supply pipe at a point that is downstream of all check valves, pressure reducing valves and
backflow preventers. Thermal expansion tanks shall be sized
in accordance with the tank manufacturer’s instructions and
shall be sized such that the pressure in the water distribution
system shall not exceed that required by Section 604.8.
607.4 Flow of hot water to fixtures. Fixture fittings, faucets
and diverters shall be installed and adjusted so that the flow
of hot water from the fittings corresponds to the left-hand
side of the fixture fitting.
Exception:
conforming
B125.16 or
flow of hot
device.
Shower and tub/shower mixing valves
to ASSE 1016/ASME A112.1016/CSA
ASME A112.18.1/CSA B125.1, where the
water corresponds to the markings on the
[E] 607.5 Insulation of piping. For other than Group R2, R3
and R4 occupancies that are three stories or less in height
above grade plane, piping to the inlet of a water heater and
piping conveying water heated by a water heater shall be
insulated in accordance with Section C404.4 of the International Energy Conservation Code. For Group R2, R3 and R4
occupancies that are three stories or less in height above
grade plane, piping to the inlet of a water heater and piping
conveying water heated by a water heater shall be insulated
in accordance with Section R403.5.3 of the International
Energy Conservation Code.
SECTION 608
PROTECTION OF POTABLE WATER SUPPLY
608.1 General. A potable water supply system shall be
designed, installed and maintained in such a manner so as to
prevent contamination from nonpotable liquids, solids or
gases being introduced into the potable water supply through
cross connections or any other piping connections to the
system. Backflow preventer applications shall conform to
Table 608.1, except as specifically stated in Sections 608.2
through 608.17.10.
6-11
WATER SUPPLY AND DISTRIBUTION
TABLE 608.1
APPLICATION OF BACKFLOW PREVENTERS
DEGREE OF HAZARDa
DEVICE
APPLICATIONb
APPLICABLE STANDARDS
Backflow prevention assemblies:
Double check backflow prevention assembly
and double check fire protection backflow
prevention assembly
Low hazard
Backpressure or backsiphonage
Sizes 3/8˝–16˝
ASSE 1015; AWWA C510;
CSA B64.5; CSA B64.5.1
Double check detector fire protection backflow
Low hazard
prevention assemblies
Backpressure or backsiphonage
Sizes 2˝–16˝
ASSE 1048
Pressure vacuum breaker assembly
High or low hazard
Backsiphonage only Sizes 1/2˝–2˝
ASSE 1020; CSA B64.1.2
Reduced pressure principle backflow
prevention assembly and reduced
pressure principle fire protection backflow
assembly
High or low hazard
Backpressure or backsiphonage
Sizes 3/8˝–16˝
ASSE 1013; AWWA C511;
CSA B64.4; CSA B64.4.1
Reduced pressure detector fire protection backHigh or low hazard
flow prevention assemblies
Backsiphonage or backpressure
(automatic sprinkler systems)
ASSE 1047
Spill-resistant vacuum breaker assembly
High or low hazard
Backsiphonage only Sizes 1/4˝–2˝
ASSE 1056; CSA B64.1.3
Antisiphon-type fill valves for gravity water
closet flush tanks
High hazard
Backsiphonage only
ASSE 1002/ASME
A112.1002/CSA B125.12;
CSA B125.3
Backflow preventer for carbonated beverage
machines
Low hazard
Backpressure or backsiphonage
Sizes 1/4˝–3/8˝
ASSE 1022
Backflow preventer with intermediate
atmospheric vents
Low hazard
Backpressure or backsiphonage
Sizes 1/4˝–3/4˝
ASSE 1012; CSA B64.3
Backflow preventer with intermediate
atmospheric vent and pressure-reducing valve.
Low hazard
Backpressure or backsiphonage
Sizes 1/4˝–3/4˝
ASSE 1081
Dual-check-valve-type backflow preventer
Low hazard
Backpressure or backsiphonage
Sizes 1/4˝–1˝
ASSE 1024; CSA B64.6
Hose connection backflow preventer
High or low hazard
Low head backpressure, rated
ASME A112.21.3;
working pressure, backpressure or
ASSE 1052; CSA B64.2.1.1
1
backsiphonage Sizes /2˝–1˝
Hose connection vacuum breaker
High or low hazard
Low head backpressure or
backsiphonage Sizes 1/2˝, 3/4˝, 1˝
ASME A112.21.3;
ASSE 1011; CSA B64.2;
CSA B64.2.1
Laboratory faucet backflow preventer
High or low hazard
Low head backpressure and
backsiphonage
ASSE 1035; CSA B64.7
Backflow preventer plumbing devices:
Pipe-applied atmospheric-type vacuum breaker High or low hazard
Backsiphonage only Sizes 1/4˝–4˝
ASSE 1001; CSA B64.1.1
Vacuum breaker wall hydrants, frostresistant, automatic-draining-type
High or low hazard
Low head backpressure or
backsiphonage Sizes 3/4˝, 1˝
ASME A112.21.3;
ASSE 1019; CSA B64.2.2
High or low hazard
Backsiphonage or backpressure
ASME A112.1.2
Air gap fittings for use with plumbing fixtures,
High or low hazard
appliances and appurtenances
Backsiphonage or backpressure
ASME A112.1.3
Barometric loop
Backsiphonage only
(See Section 608.14.4)
Other means or methods:
Air gap
High or low hazard
For SI: 1 inch = 25.4 mm.
a. Low hazard—See Pollution (Section 202).
High hazard—See Contamination (Section 202).
b. See Backpressure, low head (Section 202, Backflow).
See Backsiphonage (Section 202, Backflow).
6-12
2021 INTERNATIONAL PLUMBING CODE®
WATER SUPPLY AND DISTRIBUTION
608.2 Plumbing fixtures. The supply lines and fittings for
plumbing fixtures shall be installed so as to prevent backflow. Plumbing fixture fittings shall provide backflow
protection in accordance with ASME A112.18.1/CSA
B125.1.
608.3 Devices, appurtenances, appliances and apparatus.
Devices, appurtenances, appliances and apparatus intended
to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that
connect to the water supply system, shall be provided with
protection against backflow and contamination of the water
supply system.
608.3.1 Special equipment, water supply protection.
The water supply for hospital fixtures shall be protected
against backflow with a reduced pressure principle backflow prevention assembly, an atmospheric or spillresistant vacuum breaker assembly, or an air gap.
Vacuum breakers for bedpan washer hoses shall not be
located less than 5 feet (1524 mm) above the floor.
Vacuum breakers for hose connections in health care or
laboratory areas shall be not less than 6 feet (1829 mm)
above the floor.
the nonpotable water shall be identified either by color marking, metal tags or tape in accordance with Sections 608.9.1
through 608.9.2.3.
608.9.1 Signage required. Nonpotable water outlets,
such as hose connections, open-ended pipes and faucets,
shall be identified with signage that reads as follows:
“Nonpotable water is utilized for [application name].
CAUTION: NONPOTABLE WATER – DO NOT
DRINK.” The words shall be legibly and indelibly printed
on a tag or sign constructed of corrosion-resistant waterproof material or shall be indelibly printed on the fixture.
The letters of the words shall be not less than 0.5 inch
(12.7 mm) in height and in colors in contrast to the background on which they are applied. In addition to the
required wordage, the pictograph shown in Figure 608.9.1
shall appear on the required signage.
608.4 Potable water handling and treatment equipment.
Water pumps, filters, softeners, tanks and other appliances
and devices that handle or treat potable water to be supplied
to the potable water distribution system shall be located to
prevent contamination from entering the appliances and
devices. Overflow, relief valve and waste discharge pipes
from such appliances and devices shall terminate through an
air gap.
608.5 Water service piping. Water service piping shall be
protected in accordance with Sections 603.2 and 603.2.1.
608.6 Chemicals and other substances. Chemicals and
other substances that produce either toxic conditions, taste,
odor or discoloration in a potable water system shall not be
introduced into, or utilized in, such systems.
608.7 Cross connection control. Cross connections shall be
prohibited, except where approved backflow prevention
assemblies, backflow prevention devices or other means or
methods are installed to protect the potable water supply.
608.7.1 Private water supplies. Cross connections
between a private water supply and a potable public
supply shall be prohibited.
608.8 Valves and outlets prohibited below grade. Potable
water outlets and combination stop-and-waste valves shall
not be installed underground or below grade. A freezeproof
yard hydrant that drains the riser into the ground shall be
considered as having a stop-and-waste valve below grade.
Exception: Freezeproof yard hydrants that drain the riser
into the ground shall be permitted to be installed,
provided that the potable water supply to such hydrants is
protected in accordance with Section 608.14.2 or
608.14.5, and the hydrants and the piping from the backflow preventer to the hydrant are identified in accordance
with Section 608.9.
FIGURE 608.9.1
PICTOGRAPH—DO NOT DRINK
608.9.2 Distribution pipe labeling and marking. Nonpotable distribution piping shall be purple in color and
shall be embossed, or integrally stamped or marked, with
the words: “CAUTION: NONPOTABLE WATER – DO
NOT DRINK” or the piping shall be installed with a
purple identification tape or wrap. Pipe identification
shall include the contents of the piping system and an
arrow indicating the direction of flow. Hazardous piping
systems shall also contain information addressing the
nature of the hazard. Pipe identification shall be repeated
at intervals not exceeding 25 feet (7620 mm) and at each
point where the piping passes through a wall, floor or
roof. Lettering shall be readily observable within the
room or space where the piping is located.
608.9.2.1 Color. The color of the pipe identification
shall be discernable and consistent throughout the
building. The color purple shall be used to identify
reclaimed, rain and graywater distribution systems.
608.9.2.2 Lettering size. The size of the background
color field and lettering shall comply with Table
608.9.2.2.
608.9 Identification of nonpotable water systems. Where
nonpotable water systems are installed, the piping conveying
2021 INTERNATIONAL PLUMBING CODE®
6-13
WATER SUPPLY AND DISTRIBUTION
TABLE 608.9.2.2
SIZE OF PIPE IDENTIFICATION
PIPE DIAMETER
(inches)
3
LENGTH BACKGROUND
COLOR FIELD
(inches)
SIZE OF LETTERS
(inches)
8
0.5
/4 to 11/4
11/2 to 2
8
0.75
21/2 to 6
12
1.25
8 to 10
24
2.5
over 10
32
3.5
For SI: 1 inch = 25.4 mm.
608.9.2.3 Identification tape. Where used, identification tape shall be not less than 3 inches (76 mm) wide
and have white or black lettering on a purple field stating “CAUTION: NONPOTABLE WATER – DO
NOT DRINK.” Identification tape shall be installed on
top of nonpotable rainwater distribution pipes,
fastened not less than every 10 feet (3048 mm) to each
pipe length and run continuously the entire length of
the pipe.
608.10 Reutilization prohibited. Water utilized for the
heating or cooling of equipment or other processes shall not
be returned to the potable water system. Such water shall be
discharged into a drainage system through an air gap or shall
be utilized for nonpotable purposes.
608.11 Reuse of piping. Piping that has been utilized for any
purpose other than conveying potable water shall not be
utilized for conveying potable water.
608.12 Potable water tanks. Where in contact with potable
water intended for drinking water, water tanks, coatings for
the inside of tanks and liners for water tanks shall conform to
NSF 61. The interior surface of a potable water tank shall not
be lined, painted or repaired with any material that changes
the taste, odor, color or potability of the water supply when
the tank is placed in, or returned to, service.
608.13 Pumps and other appliances. Water pumps, filters,
softeners, tanks and other devices that handle or treat potable
water shall be protected against contamination.
608.14 Backflow protection. Means of protection against
backflow shall be provided in accordance with Sections
609.14.1 through 608.14.9.
608.14.1 Air gap. The minimum required air gap shall be
measured vertically from the lowest end of a potable
water outlet to the flood level rim of the fixture or receptacle into which such potable water outlet discharges. Air
gaps shall comply with ASME A112.1.2 and air gap
fittings shall comply with ASME A112.1.3. Products that
are listed and labeled to ASME A112.1.2 or ASME
A112.1.3 shall be considered to be in compliance with
this section.
608.14.2 Reduced pressure principle backflow prevention assemblies. Reduced pressure principle backflow
prevention assemblies shall conform to ASSE 1013,
AWWA C511, CSA B64.4 or CSA B64.4.1. Reduced
pressure detector assembly backflow preventers shall
conform to ASSE 1047. These devices shall be permitted
6-14
to be installed where subject to continuous pressure
conditions. The relief opening shall discharge by air gap
and shall be prevented from being submerged.
608.14.3 Backflow preventer with intermediate atmospheric vent. Backflow preventers with intermediate
atmospheric vents shall conform to ASSE 1012, ASSE
1081 or CSA B64.3. These devices shall be permitted to
be installed where subject to continuous pressure conditions. The relief opening shall discharge by air gap and
shall be prevented from being submerged.
608.14.4 Barometric loop. Barometric loops shall
precede the point of connection and shall extend vertically to a height of 35 feet (10 668 mm). A barometric
loop shall only be utilized as an atmospheric-type or pressure-type vacuum breaker.
608.14.5 Pressure vacuum breaker assemblies. Pressure vacuum breaker assemblies shall comply with ASSE
1020 or CSA B64.1.2. Spill-resistant vacuum breaker
assemblies shall comply with ASSE 1056 or CSA
B64.1.3. These assemblies shall be installed with the critical level of the assembly located not less than 12 inches
(305 mm) above all downstream piping and outlets. Pressure vacuum breaker assemblies shall not be installed in
locations where spillage could cause damage to the
structure.
608.14.6 Atmospheric-type vacuum breakers. Pipeapplied atmospheric-type vacuum breakers shall conform
to ASSE 1001 or CSA B64.1.1. Hose-connection vacuum
breakers shall conform to ASME A112.21.3, ASSE 1011,
ASSE 1019, ASSE 1035, ASSE 1052, CSA B64.2, CSA
B64.2.1, CSA B64.2.1.1, CSA B64.2.2 or CSA B64.7.
These devices shall operate under normal atmospheric
pressure when the critical level is installed at the required
height.
608.14.7 Double check backflow prevention assemblies. Double check backflow prevention assemblies shall
conform to ASSE 1015, CSA B64.5, CSA B64.5.1 or
AWWA C510. Double check detector fire protection
backflow prevention assemblies shall conform to ASSE
1048. These assemblies shall be capable of operating
under continuous pressure conditions.
608.14.8 Chemical dispenser backflow devices. Backflow devices for chemical dispensers shall comply with
ASSE 1055 or shall be equipped with an air gap fitting.
608.14.9 Dual check backflow preventer. Dual check
backflow preventers shall conform to ASSE 1024 or CSA
B64.6.
608.15 Location of backflow preventers. Access shall be
provided to backflow preventers as specified by the manufacturer’s instructions.
608.15.1 Outdoor enclosures for backflow prevention
devices. Outdoor enclosures for backflow prevention
devices shall comply with ASSE 1060.
608.15.2 Protection of backflow preventers. Backflow
preventers shall not be located in areas subject to freezing
except where they can be removed by means of unions or
are protected from freezing by heat, insulation or both.
2021 INTERNATIONAL PLUMBING CODE®
WATER SUPPLY AND DISTRIBUTION
608.15.2.1 Relief port piping. The termination of the
piping from the relief port or air gap fitting of a backflow preventer shall discharge to an approved indirect
waste receptor or to the outdoors where it will not
cause damage or create a nuisance. The indirect waste
receptor and drainage piping shall be sized to drain the
maximum discharge flow rate from the relief port as
published by the backflow preventer manufacturer.
608.16.4.1 Deck-mounted and integral vacuum
breakers. Approved deck-mounted or equipmentmounted vacuum breakers and faucets with integral
atmospheric vacuum breakers or spill-resistant
vacuum breaker assemblies shall be installed in accordance with the manufacturer’s instructions and the
requirements for labeling with the critical level not less
than 1 inch (25 mm) above the flood level rim.
608.16 Protection of potable water outlets. Potable water
openings and outlets shall be protected against backflow in
accordance with Section 608.16.1, 608.16.2, 608.16.3,
608.16.4, 608.16.4.1 or 608.16.4.2.
608.16.4.2 Hose connections. Sillcocks, hose bibbs,
wall hydrants and other openings with a hose connection shall be protected by an atmospheric-type or
pressure-type vacuum breaker or a permanently
attached hose connection vacuum breaker.
608.16.1 Protection by air gap. Openings and outlets
shall be protected by an air gap between the opening and
the fixture flood level rim as specified in Table 608.16.1.
Openings and outlets equipped for hose connection shall
be protected by means other than an air gap.
608.16.2 Protection by reduced pressure principle
backflow prevention assembly. Openings and outlets
shall be protected by a reduced pressure principle backflow prevention assembly or a reduced pressure principle
fire protection backflow prevention assembly on potable
water supplies.
608.16.3 Protection by a backflow preventer with
intermediate atmospheric vent. Openings and outlets
shall be protected by a backflow preventer with an intermediate atmospheric vent.
608.16.4 Protection by a vacuum breaker. Openings
and outlets shall be protected by atmospheric-type or
pressure-type vacuum breakers. The critical level of the
vacuum breaker shall be set not less than 6 inches (152
mm) above the flood level rim of the fixture or device. Fill
valves shall be set in accordance with Section 415.3.1.
Vacuum breakers shall not be installed under exhaust
hoods or similar locations that will contain toxic fumes or
vapors. Pipe-applied vacuum breakers shall be installed
not less than 6 inches (152 mm) above the flood level rim
of the fixture, receptor or device served.
Exceptions:
1. This section shall not apply to water heater
and boiler drain valves that are provided
with hose connection threads and that are
intended only for tank or vessel draining.
2. This section shall not apply to water supply
valves intended for connection of clothes
washing machines where backflow prevention is otherwise provided or is integral with
the machine.
608.17 Connections to the potable water system. Connections to the potable water system shall conform to Sections
608.17.1 through 608.17.10.
608.17.1 Beverage dispensers. The water supply connection to beverage dispensers shall be protected against
backflow in accordance with Sections 608.17.1.1 and
608.17.1.2.
608.17.1.1 Carbonated beverage dispensers. The
water supply connection to each carbonated beverage
dispenser shall be protected against backflow by a
backflow preventer conforming to ASSE 1022 or by
an air gap. The portion of the backflow preventer
device downstream from the second check valve of the
device and the piping downstream therefrom shall not
be affected by carbon dioxide gas.
TABLE 608.16.1
MINIMUM REQUIRED AIR GAPS
MINIMUM AIR GAP
FIXTURE
Away from a walla (inches)
Close to a wall (inches)
1
11/2
Sinks, laundry trays, gooseneck back faucets and other fixtures with
effective openings not greater than 3/4 inch in diameter
11/2
21/2
Over-rim bath fillers and other fixtures with effective openings not
greater than 1 inch in diameter
2
3
1
11/2
Two times the diameter of the
effective opening
Three times the diameter of the
effective opening
Lavatories and other fixtures with effective openings not greater
than 1/2 inch in diameter
7
Drinking water fountains, single orifice not greater than /16 inch in
diameter or multiple orifices with a total area of 0.150 square inch
(area of circle 7/16 inch in diameter)
Effective openings greater than 1 inch
For SI:1 inch = 25.4 mm, 1 square inch = 645 mm2.
a. Applicable where walls or obstructions are spaced from the nearest inside-edge of the spout opening a distance greater than three times the diameter of the
effective opening for a single wall, or a distance greater than four times the diameter of the effective opening for two intersecting walls.
2021 INTERNATIONAL PLUMBING CODE®
6-15
WATER SUPPLY AND DISTRIBUTION
608.17.1.2 Coffee machines and noncarbonated
drink dispensers. The water supply connection to
each coffee machine and each noncarbonated beverage
dispenser shall be protected against backflow by a
backflow preventer conforming to ASSE 1022 or
ASSE 1024, or protected by an air gap.
608.17.2 Connections to boilers. The potable supply to
the boiler shall be equipped with a backflow preventer
with an intermediate atmospheric vent complying with
ASSE 1012, ASSE 1081 or CSA B64.3. Where conditioning chemicals are introduced into the system, the
potable water connection shall be protected by an air gap
or a reduced pressure principle backflow preventer,
complying with ASSE 1013, AWWA C511 or CSA
B64.4.
608.17.3 Heat exchangers. Heat exchangers utilizing an
essentially toxic transfer fluid shall be separated from the
potable water by double-wall construction. An air gap
open to the atmosphere shall be provided between the two
walls. Heat exchangers utilizing an essentially nontoxic
transfer fluid shall be permitted to be of single-wall
construction.
608.17.4 Connections to automatic sprinkler systems
and standpipe systems. The potable water supply to
automatic sprinkler systems and standpipe systems shall
be protected against backflow by a double check backflow prevention assembly, a double check fire protection
backflow prevention assembly or a reduced pressure principle fire protection backflow prevention assembly.
Exceptions:
6-16
pressure, the potable water supply shall be protected
against backflow by an air gap or an atmospheric
vacuum breaker conforming to ASSE 1001 or CSA
B64.1.1.
608.17.5 Connections to lawn irrigation systems. The
potable water supply to lawn irrigation systems shall be
protected against backflow by an atmospheric vacuum
breaker, a pressure vacuum breaker assembly or a
reduced pressure principle backflow prevention assembly. Valves shall not be installed downstream from an
atmospheric vacuum breaker. Where chemicals are introduced into the system, the potable water supply shall be
protected against backflow by a reduced pressure principle backflow prevention assembly.
608.17.6 Connections subject to backpressure. Where a
potable water connection is made to a nonpotable line,
fixture, tank, vat, pump or other equipment subject to
high-hazard backpressure, the potable water connection
shall be protected by a reduced pressure principle backflow prevention assembly.
608.17.7 Chemical dispensers. Where chemical dispensers connect to the potable water distribution system, the
water supply system shall be protected against backflow
in accordance with Section 608.14.1, 608.14.2, 608.14.5,
608.14.6, or 608.14.8.
608.17.8 Portable cleaning equipment. Where the
portable cleaning equipment connects to the water distribution system, the water supply system shall be protected
against backflow in accordance with Section 608.14.1,
608.14.2, 608.14.3, 608.14.7 or 608.14.8.
1. Where systems are installed as a portion of the
water distribution system in accordance with
the requirements of this code and are not
provided with a fire department connection,
isolation of the water supply system shall not
be required.
2. Isolation of the water distribution system is not
required for deluge, preaction or dry pipe
systems.
608.17.9 Dental pumping equipment. The water supply
connection to each dental pumping equipment system, the
water supply system shall be protected against backflow
in accordance with Section 608.14.1, 608.14.2, 608.14.5,
608.14.6 or 608.14.8.
608.17.4.1 Additives or nonpotable source. Where
systems under continuous pressure contain chemical
additives or antifreeze, or where systems are
connected to a nonpotable secondary water supply, the
potable water supply shall be protected against backflow by a reduced pressure principle backflow
prevention assembly or a reduced pressure principle
fire protection backflow prevention assembly. Where
chemical additives or antifreeze are added to only a
portion of an automatic sprinkler system or standpipe
system, the reduced pressure principle backflow
prevention assembly or the reduced pressure principle
fire protection backflow prevention assembly shall be
permitted to be located so as to isolate that portion of
the system. Where systems are not under continuous
608.18 Protection of individual water supplies. An individual water supply shall be located and constructed so as to
be safeguarded against contamination in accordance with
Sections 608.18.1 through 608.18.8.
608.17.10 Humidifiers. The water supply connection to
humidifiers that do not have internal backflow protection
shall be protected against backflow by a backflow
preventer conforming to ASSE 1012 or by an air gap.
608.18.1 Well locations. A potable ground water source
or pump suction line shall not be located closer to potential sources of contamination than the distances shown in
Table 608.18.1. In the event the underlying rock structure
is limestone or fragmented shale, the local or state health
department shall be consulted on well site location. The
distances in Table 608.18.1 constitute minimum separation and shall be increased in areas of creviced rock or
limestone, or where the direction of movement of the
ground water is from sources of contamination toward the
well.
2021 INTERNATIONAL PLUMBING CODE®
WATER SUPPLY AND DISTRIBUTION
TABLE 608.18.1
DISTANCE FROM CONTAMINATION TO
PRIVATE WATER SUPPLIES AND PUMP SUCTION LINES
SOURCE OF CONTAMINATION
Barnyard
DISTANCE (feet)
100
Farm silo
25
Pasture
100
Pumphouse floor drain of cast iron draining
to ground surface
2
Seepage pits
50
Septic tank
25
Sewer
10
Subsurface disposal fields
50
Subsurface pits
50
For SI: 1 foot = 304.8 mm.
608.18.2 Elevation. Well sites shall be positively drained
and shall be at higher elevations than potential sources of
contamination.
608.18.3 Depth. Private potable well supplies shall not be
developed from a water table less than 10 feet (3048 mm)
below the ground surface.
608.18.4 Watertight casings. Each well shall be
provided with a watertight casing extending to not less
than 10 feet (3048 mm) below the ground surface.
Casings shall extend not less than 6 inches (152 mm)
above the well platform. Casings shall be large enough to
permit installation of a separate drop pipe. Casings shall
be sealed at the bottom in an impermeable stratum or
extend several feet (mm) into the water-bearing stratum.
608.18.5 Drilled or driven well casings. Drilled or
driven well casings shall be of steel or other approved
material. Where drilled wells extend into a rock formation, the well casing shall extend to and set firmly in the
formation. The annular space between the earth and the
outside of the casing shall be filled with cement grout to a
depth of not less than 10 feet (3048 mm) below the
ground surface. In an instance of casing to rock installation, the grout shall extend to the rock surface.
608.18.6 Dug or bored well casings. Dug or bored well
casings shall be of watertight concrete, tile or galvanized
or corrugated metal pipe extending to not less than 10 feet
(3048 mm) below the ground surface. Where the water
table is more than 10 feet (3048 mm) below the ground
surface, the watertight casing shall extend below the table
surface. Well casings for dug wells or bored wells
constructed with sections of concrete, tile or galvanized
or corrugated metal pipe shall be surrounded by 6 inches
(152 mm) of grout poured into the hole between the
outside of the casing and the ground and extending not
less than 10 feet (3048 mm) below the ground surface.
608.18.7 Cover. Potable water wells shall be equipped
with an overlapping watertight cover at the top of the well
casing or pipe sleeve such that contaminated water or
other substances are prevented from entering the well
through the annular opening at the top of the well casing,
2021 INTERNATIONAL PLUMBING CODE®
wall or pipe sleeve. Covers shall extend downward not
less than 2 inches (51 mm) over the outside of the well
casing or wall. A dug well cover shall be provided with a
pipe sleeve permitting the withdrawal of the pump
suction pipe, cylinder or jet body without disturbing the
cover. Where pump sections or discharge pipes enter or
leave a well through the side of the casing, the circle of
contact shall be watertight.
608.18.8 Drainage. Potable water wells and springs shall
be constructed such that surface drainage will be diverted
away from the well or spring.
SECTION 609
HEALTH CARE PLUMBING
609.1 Scope. This section shall govern those aspects of
health care plumbing systems that differ from plumbing
systems in other structures. Health care plumbing systems
shall conform to the requirements of this section in addition
to the other requirements of this code. The provisions of this
section shall apply to the special devices and equipment
installed and maintained in the following occupancies:
Group I-1, Group I- 2, Group B ambulatory care facilities,
medical offices, research and testing laboratories, and Group
F facilities manufacturing pharmaceutical drugs and
medicines.
609.2 Water service for Group I-2, Condition 2 facilities.
Group I-2, Condition 2 facilities shall have not fewer than
two water service pipes sized such that with the loss of the
largest service pipe, the remaining service pipes will meet
the water demand for the entire facility. Each water service
shall have a shutoff valve in the building and a shutoff valve
at the utility-provided point of connection to the water main
or other source of potable water.
609.2.1 Tracer wire for nonmetallic piping. An insulated tracer wire listed for the purpose or other approved
conductor shall be installed adjacent to underground
nonmetallic piping serving as a water service for a hospital. Access shall be provided to the tracer wire or the
tracer wire shall terminate above ground at each end of
the nonmetalic piping. The tracer wire size shall be not
less than 18 AWG and the wire insulation type shall be
suitable for direct burial.
609.3 Hot water. Hot water shall be provided to supply all
of the hospital fixture, kitchen and laundry requirements.
Special fixtures and equipment shall have hot water supplied
at a temperature specified by the manufacturer. The hot
water system shall be installed in accordance with Section
607.
609.4 Vacuum breaker installation. Vacuum breakers shall
be installed not less than 6 inches (152 mm) above the flood
level rim of the fixture or device in accordance with Section
608. The flood level rim of hose connections shall be the
maximum height at which any hose is utilized.
609.5 Prohibited water closet and clinical sink supply.
Jet- or water-supplied orifices, except those supplied by the
flush connections, shall not be located in or connected with a
6-17
WATER SUPPLY AND DISTRIBUTION
water closet bowl or clinical sink. This section shall not
prohibit an approved bidet installation.
drainage system through an air gap or an air gap device that
meets the requirements of CSA B483.1 or NSF 58.
609.6 Clinical, hydrotherapeutic and radiological equipment. Clinical, hydrotherapeutic, radiological or any
equipment that is supplied with water or that discharges to
the waste system shall conform to the requirements of this
section and Section 608.
611.3 Connection tubing. The tubing to and from drinking
water treatment units shall be of a size and material as
recommended by the manufacturer. The tubing shall comply
with NSF 14, NSF 42, NSF 44, NSF 53, NSF 58 or NSF 61.
609.7 Condensate drain trap seal. A water supply shall be
provided for cleaning, flushing and resealing the condensate
trap, and the trap shall discharge through an air gap in accordance with Section 608.
609.8 Valve leakage diverter. Each water sterilizer filled
with water through directly connected piping shall be
equipped with an approved leakage diverter or bleed line on
the water supply control valve to indicate and conduct any
leakage of unsterile water away from the sterile zone.
SECTION 610
DISINFECTION OF POTABLE WATER SYSTEM
610.1 General. New potable water systems shall be purged
of deleterious matter and disinfected prior to utilization. The
method to be followed shall be that prescribed by the health
authority or water purveyor having jurisdiction or, in the
absence of a prescribed method, the procedure described in
either AWWA C651 or AWWA C652, or as described in
this section. This requirement shall apply to “on-site” or “inplant” fabrication of a system or to a modular portion of a
system.
SECTION 612
SOLAR SYSTEMS
612.1 Solar systems. The construction, installation, alterations and repair of systems, equipment and appliances
intended to utilize solar energy for space heating or cooling,
domestic hot water heating, swimming pool heating or
process heating shall be in accordance with the International
Mechanical Code.
SECTION 613
TEMPERATURE CONTROL DEVICES AND VALVES
613.1 Temperature-actuated mixing valves. Temperatureactuated mixing valves, which are installed to reduce water
temperatures to defined limits, shall comply with ASSE
1017. Such valves shall be installed at the hot water source.
1. The pipe system shall be flushed with clean, potable
water until dirty water does not appear at the points
of outlet.
2. The system or part thereof shall be filled with a
water/chlorine solution containing not less than 50
parts per million (50 mg/L) of chlorine, and the
system or part thereof shall be valved off and allowed
to stand for 24 hours; or the system or part thereof
shall be filled with a water/chlorine solution containing not less than 200 parts per million (200 mg/L) of
chlorine and allowed to stand for 3 hours.
3. Following the required standing time, the system
shall be flushed with clean potable water until the
chlorine is purged from the system.
4. The procedure shall be repeated where shown by a
bacteriological examination that contamination
remains present in the system.
SECTION 611
DRINKING WATER TREATMENT UNITS
611.1 Design. Point-of-use reverse osmosis drinking water
treatment units shall comply with CSA B483.1 or NSF 58.
Drinking water treatment units shall meet the requirements
of CSA B483.1, NSF 42, NSF 44, NSF 53 or NSF 62.
611.2 Reverse osmosis systems. The discharge from a
reverse osmosis drinking water treatment unit shall enter the
6-18
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 7
SANITARY DRAINAGE
User note:
About this chapter: Chapter 7 regulates the methods and piping systems that remove water that has served a purpose such as flushing
water closets, bathing, culinary activities and equipment discharges. The types of materials, drainage fitting and the connection methods
are covered for these systems that begin at the receiving fixtures and end at the point of disposal for the liquid waste. A design method for
a gravity flow system of vertical and horizontal piping is provided based on the probability of flows from specific fixtures. Vacuum and
pumped types of liquid waste removal methods are also regulated by this chapter.
SECTION 701
GENERAL
701.1 Scope. The provisions of this chapter shall govern the
materials, design, construction and installation of sanitary
drainage systems.
701.2 Connection to sewer required. Sanitary drainage
piping from plumbing fixtures in buildings and sanitary
drainage piping systems from premises shall be connected to
a public sewer. Where a public sewer is not available, the
sanitary drainage piping and systems shall be connected to a
private sewage disposal system in compliance with state or
local requirements. Where state or local requirements do not
exist for private sewage disposal systems, the sanitary drainage piping and systems shall be connected to an approved
private sewage disposal system that is in accordance with the
International Private Sewage Disposal Code.
Exception: Sanitary drainage piping and systems that
convey only the discharge from bathtubs, showers, lavatories, clothes washers and laundry trays shall not be
required to connect to a public sewer or to a private
sewage disposal system provided that the piping or
systems are connected to a system in accordance with
Chapter 13 or 14.
701.3 Separate sewer connection. A building having
plumbing fixtures installed and intended for human habitation, occupancy or use on premises abutting on a street, alley
or easement in which there is a public sewer shall have a
separate connection with the sewer. Where located on the
same lot, multiple buildings shall not be prohibited from
connecting to a common building sewer that connects to the
public sewer.
701.4 Sewage treatment. Sewage or other waste from a
plumbing system that is deleterious to surface or subsurface
waters shall not be discharged into the ground or into any
waterway unless it has first been rendered innocuous through
subjection to an approved form of treatment.
701.5 Damage to drainage system or public sewer. Waste
detrimental to the public sewer system or to the functioning
of the sewage-treatment plant shall be treated and disposed
of in accordance with Section 1003 as directed by the code
official.
701.7 Engineered systems. Engineered sanitary drainage
systems shall conform to the provisions of Sections 316 and
713.
SECTION 702
MATERIALS
702.1 Above-ground sanitary drainage and vent pipe.
Above-ground soil, waste and vent pipe shall conform to one
of the standards listed in Table 702.1.
TABLE 702.1
ABOVE-GROUND DRAINAGE AND VENT PIPE
MATERIAL
STANDARD
Acrylonitrile butadiene styrene
(ABS) plastic pipe in IPS diameASTM D2661;
ters, including Schedule 40,
ASTM F628; ASTM F1488;
DR 22 (PS 200) and DR 24
CSA B181.1
(PS 140); with a solid, cellular core
or composite wall
Cast-iron pipe
ASTM A74; ASTM A888;
CISPI 301
Copper or copper-alloy pipe
ASTM B42; ASTM B43;
ASTM B302
Copper or copper-alloy tubing
(Type K, L, M or DWV)
ASTM B75; ASTM B88;
ASTM B251; ASTM B306
Galvanized steel pipe
ASTM A53
Glass pipe
ASTM C1053
Polyolefin pipe
ASTM F1412; CSA B181.3
Polyvinyl chloride (PVC) plastic
pipe in IPS diameters, including
Schedule 40, DR 22 (PS 200), and
DR 24 (PS 140); with a solid,
cellular core or composite wall
ASTM D2665;
ASTM F891; ASTM F1488;
CSA B181.2
Polyvinyl chloride (PVC) plastic
pipe with a 3.25-inch O.D. and a
solid, cellular core or composite
wall
ASTM D2949;
ASTM F1488
Polyvinylidene fluoride (PVDF)
plastic pipe
ASTM F1673; CSA B181.3
Stainless steel drainage systems,
Types 304 and 316L
ASME A112.3.1
701.6 Tests. The sanitary drainage system shall be tested in
accordance with Section 312.
2021 INTERNATIONAL PLUMBING CODE®
7-1
SANITARY DRAINAGE
702.2 Underground building sanitary drainage and vent
pipe. Underground building sanitary drainage and vent pipe
shall conform to one of the standards listed in Table 702.2.
TABLE 702.2
UNDERGROUND BUILDING DRAINAGE AND VENT PIPE
MATERIAL
STANDARD
TABLE 702.3
BUILDING SEWER PIPE
MATERIAL
STANDARD
Acrylonitrile butadiene styrene
(ABS) plastic pipe in IPS diameters, including Schedule 40,
DR 22 (PS 200) and DR 24
(PS 140); with a solid, cellular
core or composite wall
ASTM D2661;
ASTM D2680;
ASTM F628;
ASTM F1488;
CSA B181.1
Acrylonitrile butadiene styrene
(ABS) plastic pipe in sewer and
drain diameters, including
SDR 42 (PS 20), PS 35, SDR 35
(PS 45), PS 50, PS 100, PS 140,
SDR 23.5 (PS 150) and PS 200;
with a solid, cellular core or
composite wall
ASTM D2751; ASTM F1488
Acrylonitrile butadiene styrene
(ABS) plastic pipe in IPS diameters, including Schedule 40,
DR 22 (PS 200) and
DR 24 (PS 140); with a solid,
cellular core or composite wall
ASTM D2661; ASTM F628;
ASTM F1488; CSA B181.1
Cast-iron pipe
ASTM A74; ASTM A888;
CISPI 301
Copper or copper-alloy tubing
(Type K, L, M or DWV)
ASTM B75; ASTM B88;
ASTM B251; ASTM B306
Polyethylene (PE) plastic pipe
(SDR-PR)
ASTM F714
Cast-iron pipe
ASTM A74; ASTM A888;
CISPI 301
Polyolefin pipe
ASTM F714;
ASTM F1412; CSA B181.3
Concrete pipe
ASTM C14; ASTM C76;
CSA A257.1; CSA A257.2
Polyvinyl chloride (PVC) plastic
pipe in IPS diameters, including
ASTM D2665; ASTM F891;
Schedule 40, DR 22 (PS 200) and
ASTM F1488; CSA B181.2
DR 24 (PS 140); with a solid,
cellular core or composite wall
Copper or copper-alloy tubing
(Type K or L)
ASTM B75; ASTM B88;
ASTM B251
Polyethylene (PE) plastic pipe
(SDR-PR)
ASTM F714
Polyvinyl chloride (PVC) plastic
pipe with a 3.25-inch O.D. and a
solid, cellular core or composite
wall
Polypropylene (PP) plastic pipe
ASTM F2736; ASTM F2764;
CSA B182.13
ASTM D2949; ASTM F1488
Polyvinylidene fluoride (PVDF)
plastic pipe
ASTM F1673; CSA B181.3
ASTM D2665; ASTM F891;
ASTM F1488
Stainless steel drainage systems,
Type 316L
Polyvinyl chloride (PVC) plastic
pipe in IPS diameters, including
Schedule 40, DR 22 (PS 200) and
DR 24 (PS 140); with a solid,
cellular core or composite wall
ASME A112.3.1
For SI: 1 inch = 25.4 mm.
702.3 Building sewer pipe. Building sewer pipe shall
conform to one of the standards listed in Table 702.3.
702.4 Fittings. Pipe fittings shall be approved for installation with the piping material installed and shall comply with
the applicable standards listed in Table 702.4.
702.5 Temperature rating. Where the wastewater temperature will be greater than 140°F (60°C), the sanitary drainage
piping material shall be rated for the highest temperature of
the wastewater.
702.6 Chemical waste system. A chemical waste system
shall be completely separated from the sanitary drainage
system. The chemical waste shall be treated in accordance
with Section 803.2 before discharging to the sanitary drainage system. Separate drainage systems for chemical wastes
and vent pipes shall be of an approved material that is resistant to corrosion and degradation for the concentrations of
chemicals involved.
Polyvinyl chloride (PVC) plastic
pipe in sewer and drain diameters, including PS 25, SDR 41 (PS
ASTM F891; ASTM F1488;
28), PS 35, SDR 35 (PS 46), PS
ASTM D3034;
50, PS 100, SDR 26
CSA B182.2; CSA B182.4
(PS 115), PS 140 and PS 200; with
a solid, cellular core or composite
wall
Polyvinyl chloride (PVC) plastic
pipe with a 3.25-inch O.D. and a
solid, cellular core or composite
wall
ASTM D2949; ASTM F1488
Polyvinylidene fluoride (PVDF)
plastic pipe
ASTM F1673; CSA B181.3
Stainless steel drainage systems,
Types 304 and 316L
ASME A112.3.1
Vitrified clay pipe
ASTM C4; ASTM C700
For SI: 1 inch = 25.4 mm.
702.7 Lead bends and traps. The wall thickness of lead
bends and traps shall be not less than 1/8 inch (3.2 mm).
7-2
2021 INTERNATIONAL PLUMBING CODE®
SANITARY DRAINAGE
TABLE 702.4
PIPE FITTINGS
MATERIAL
Acrylonitrile butadiene styrene
(ABS) plastic pipe in IPS
diameters
Acrylonitrile butadiene styrene
(ABS) plastic pipe in sewer and
drain diameters
Cast iron
Copper or copper alloy
Glass
Gray iron and ductile iron
Polyethylene
Polyolefin
Polyvinyl chloride (PVC) plastic in IPS diameters
Polyvinyl chloride (PVC) plastic pipe in sewer and drain
diameters
Polyvinyl chloride (PVC) plastic pipe with a 3.25-inch O.D.
Polyvinylidene fluoride (PVDF)
plastic pipe
Stainless steel drainage systems,
Types 304 and 316L
STANDARD
ASME A112.4.4;
ASTM D2661; ASTM F628;
CSA B181.1
ASTM D2751
ASME B16.4; ASME B16.12;
ASTM A74; ASTM A888;
CISPI 301
ASME B16.15; ASME B16.18;
ASME B16.22;
ASME B16.23;
ASME B16.26;
ASME B16.29
ASTM C1053
AWWA C110/A21.10
ASTM D2683
ASTM F1412; CSA B181.3
ASME A112.4.4;
ASTM D2665; ASTM F1866
Vitrified clay
703.5 Cleanouts on building sewers. Cleanouts on building
sewers shall be located as indicated in Section 708.
703.6 Combined sanitary and storm public sewer. Where
the public sewer is a combined system for both sanitary and
storm water, the sanitary sewer shall be connected independently to the public sewer.
SECTION 704
DRAINAGE PIPING INSTALLATION
704.1 Slope of horizontal drainage piping. Horizontal
drainage piping shall be installed in uniform alignment at
uniform slopes. The slope of a horizontal drainage pipe shall
be not less than that indicated in Table 704.1 except that
where the drainage piping is upstream of a grease interceptor, the slope of the piping shall be not less than 1/4 inch per
foot (2-percent slope).
TABLE 704.1
SLOPE OF HORIZONTAL DRAINAGE PIPE
ASTM D3034
SIZE (inches)
ASTM D2949
ASTM F1673; CSA B181.3
ASME A112.3.1
ASME B16.9; ASME B16.11;
ASME B16.28
ASTM C700
Steel
slabs and existing building sewers that will serve the new
system shall be internally examined to verify that the piping
is sloping in the correct direction, is not broken, is not
obstructed and is sized for the drainage load of the new
plumbing drainage system to be installed.
For SI: 1 inch = 25.4 mm.
SECTION 703
BUILDING SEWER
703.1 Building sewer pipe near the water service. The
proximity of a sewer to a water service shall comply with
Section 603.2.
703.2 Drainage pipe in filled ground. Where a building
sewer or building drain is installed on filled or unstable
ground, the drainage pipe shall conform to one of the standards for ABS plastic pipe, cast-iron pipe, copper or copperalloy tubing, PVC plastic pipe or polypropylene plastic pipe
indicated in Table 702.3.
703.3 Sanitary and storm sewers. Where separate systems
of sanitary drainage and storm drainage are installed in the
same property, the sanitary and storm building sewers or
drains shall be permitted to be laid side by side in one trench.
703.4 Existing building sewers and building drains.
Where the entire sanitary drainage system of an existing
building is replaced, existing building drains under concrete
2021 INTERNATIONAL PLUMBING CODE®
MINIMUM SLOPE (inch per foot)
21/2 or less
1 a
4
3 to 6
1 a
8
8 or larger
1
/
/
/16a
For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.33 mm/m.
a. Slopes for piping draining to a grease interceptor shall comply with
Section 704.1.
704.2 Reduction in pipe size in the direction of flow. The
size of the drainage piping shall not be reduced in the direction of the flow. The following shall not be considered as a
reduction in size in the direction of flow:
1. A 4-inch by 3-inch (102 mm by 76 mm) water closet
flange.
2. A water closet bend fitting having a 4-inch (102 mm)
inlet and a 3-inch (76 mm) outlet provided that the 4inch leg of the fitting is upright and below, but not
necessarily directly connected to, the water closet
flange.
3. An offset closet flange.
704.3 Connections to offsets and bases of stacks. Horizontal branches shall connect to the bases of stacks at a point
located not less than 10 times the diameter of the drainage
stack downstream from the stack. Horizontal branches shall
connect to horizontal stack offsets at a point located not less
than 10 times the diameter of the drainage stack downstream
from the upper stack.
704.4 Future fixtures. Drainage piping for future fixtures
shall terminate with an approved cap or plug.
7-3
SANITARY DRAINAGE
SECTION 705
JOINTS
705.1 General. This section contains provisions applicable
to joints specific to sanitary drainage piping.
705.2 ABS plastic. Joints between ABS plastic pipe or
fittings shall comply with Sections 705.2.1 through 705.2.3.
705.5 Copper pipe. Joints between copper or copper-alloy
pipe or fittings shall comply with Sections 705.5.1 through
705.5.5.
705.2.1 Mechanical joints. Mechanical joints on drainage pipes shall be made with an elastomeric seal
conforming to ASTM C1173, ASTM D3212 or CSA
B602. Mechanical joints shall be installed only in underground systems unless otherwise approved. Joints shall
be installed in accordance with the manufacturer’s
instructions.
705.5.1 Brazed joints. Joint surfaces shall be cleaned. An
approved flux shall be applied where required. The joint
shall be brazed with a filler metal conforming to AWS
A5.8.
705.2.2 Solvent cementing. Joint surfaces shall be clean
and free from moisture. Solvent cement that conforms to
ASTM D2235 or CSA B181.1 shall be applied to all joint
surfaces. The joint shall be made while the cement is wet.
Joints shall be made in accordance with ASTM D2235,
ASTM D2661, ASTM F628 or CSA B181.1. Solventcement joints shall be permitted above or below ground.
705.5.3 Solder joints. Solder joints shall be made in
accordance with the methods of ASTM B828. Cut tube
ends shall be reamed to the full inside diameter of the
tube end. Joint surfaces shall be cleaned. A flux conforming to ASTM B813 shall be applied. The joint shall be
soldered with a solder conforming to ASTM B32.
705.2.3 Threaded joints. Threads shall conform to
ASME B1.20.1. Schedule 80 or heavier pipe shall be
permitted to be threaded with dies specifically designed
for plastic pipe. Approved thread lubricant or tape shall be
applied on the male threads only.
705.2.4 Push-fit joints. Push-fit DWV fittings shall be
listed and labeled to ASME A112.4.4 and shall be
installed in accordance with the manufacturer’s
instructions.
705.3 Cast iron. Joints between cast-iron pipe or fittings
shall comply with Sections 705.3.1 through 705.3.3.
705.5.2 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
705.5.4 Threaded joints. Threads shall conform to
ASME B1.20.1. Pipe-joint compound or tape shall be
applied on the male threads only.
705.5.5 Welded joints. Joint surfaces shall be cleaned.
The joint shall be welded with an approved filler metal.
705.6 Copper tubing. Joints between copper or copperalloy tubing or fittings shall comply with Sections 705.6.1
through 705.6.3.
705.6.1 Brazed joints. Joint surfaces shall be cleaned. An
approved flux shall be applied where required. The joint
shall be brazed with a filler metal conforming to AWS
A5.8.
705.3.1 Caulked joints. Joints for hub and spigot pipe
shall be firmly packed with oakum or hemp. Molten lead
shall be poured in one operation to a depth of not less than
1 inch (25 mm). The lead shall not recede more than 1/8
inch (3.2 mm) below the rim of the hub and shall be
caulked tight. Paint, varnish or other coatings shall not be
permitted on the jointing material until after the joint has
been tested and approved. Lead shall be run in one pouring and shall be caulked tight. Acid-resistant rope and
acidproof cement shall be permitted.
705.6.2 Mechanical joints. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
705.3.2 Compression gasket joints. Compression
gaskets for hub and spigot pipe and fittings shall conform
to ASTM C564 and shall be tested to ASTM C1563.
Gaskets shall be compressed when the pipe is fully
inserted.
705.7 Borosilicate glass joints. Glass-to-glass connections
shall be made with a bolted compression-type, 300 series
stainless steel coupling with contoured acid-resistant elastomeric compression ring and a fluorocarbon polymer inner
seal ring; or with caulked joints in accordance with Section
705.7.1.
705.3.3 Mechanical joint coupling. Mechanical joint
couplings for hubless pipe and fittings shall consist of an
elastomeric sealing sleeve and a metallic shield that
comply with CISPI 310, ASTM C1277 or ASTM C1540.
The elastomeric sealing sleeve shall conform to ASTM
C564 or CSA B602 and shall be provided with a center
stop. Mechanical joint couplings shall be installed in
accordance with the manufacturer’s instructions.
7-4
705.4 Concrete joints. Joints between concrete pipe and
fittings shall be made with an elastomeric seal conforming to
ASTM C443, ASTM C1173, CSA A257.3M or CSA B602.
705.6.3 Solder joints. Solder joints shall be made in
accordance with the methods of ASTM B828. Cut tube
ends shall be reamed to the full inside diameter of the
tube end. Joint surfaces shall be cleaned. A flux conforming to ASTM B813 shall be applied. The joint shall be
soldered with a solder conforming to ASTM B32.
705.7.1 Caulked joints. Lead-caulked joints for hub and
spigot soil pipe shall be firmly packed with oakum or
hemp and filled with molten lead not less than 1 inch (25
mm) in depth and not to recede more than 1/8 inch (3.2
mm) below the rim of the hub. Paint, varnish or other
coatings shall not be permitted on the jointing material
until after the joint has been tested and approved. Lead
shall be run in one pouring and shall be caulked tight.
Acid-resistant rope and acidproof cement shall be
permitted.
2021 INTERNATIONAL PLUMBING CODE®
SANITARY DRAINAGE
705.8 Steel. Joints between galvanized steel pipe or fittings
shall comply with Sections 705.8.1 and 705.8.2.
705.8.1 Threaded joints. Threads shall conform to
ASME B1.20.1. Pipe-joint compound or tape shall be
applied on the male threads only.
705.8.2 Mechanical joints. Joints shall be made with an
approved elastomeric seal. Mechanical joints shall be
installed in accordance with the manufacturer’s
instructions.
705.9 Lead. Joints between lead pipe or fittings shall comply
with Sections 705.9.1 and 705.9.2.
705.9.1 Burned. Burned joints shall be uniformly fused
together into one continuous piece. The thickness of the
joint shall be not less than the thickness of the lead being
joined. The filler metal shall be of the same material as
the pipe.
705.9.2 Wiped. Joints shall be fully wiped, with an
exposed surface on each side of the joint not less than 3/4
inch (19.1 mm). The joint shall be not less than 3/8 inch
(9.5 mm) thick at the thickest point.
705.10 PVC plastic. Joints between PVC plastic pipe or
fittings shall comply with Sections 705.10.1 through
705.10.3.
705.10.1 Mechanical joints. Mechanical joints on drainage pipe shall be made with an elastomeric seal
conforming to ASTM C1173, ASTM D3212 or CSA
B602. Mechanical joints shall not be installed in aboveground systems, unless otherwise approved. Joints shall
be installed in accordance with the manufacturer’s
instructions.
705.10.2 Solvent cementing. Joint surfaces shall be clean
and free from moisture. A purple primer that conforms to
ASTM F656 shall be applied. Solvent cement not purple
in color and conforming to ASTM D2564, CSA B137.3,
CSA B181.2 or CSA B182.1 shall be applied to all joint
surfaces. The joint shall be made while the cement is wet
and shall be in accordance with ASTM D2855. Solventcement joints shall be permitted above or below ground.
Exception: A primer is not required where both of the
following conditions apply:
1. The solvent cement used is third-party certified
as conforming to ASTM D2564.
2. The solvent cement is used only for joining
PVC drain, waste and vent pipe and fittings in
nonpressure applications in sizes up to and
including 4 inches (102 mm) in diameter.
705.10.3 Threaded joints. Threads shall conform to
ASME B1.20.1. Where pipe is to be threaded, the pipe
shall have a wall thickness of not less than Schedule 80.
Pipe threads shall be made with dies specifically designed
for plastic pipe. Approved thread lubricant or tape shall be
applied on the male threads only.
705.10.4 Push-fit joints. Push-fit joints shall conform to
ASME A112.4.4 and shall be installed in accordance with
the manufacturer’s instructions.
2021 INTERNATIONAL PLUMBING CODE®
705.11 Vitrified clay. Joints between vitrified clay pipe or
fittings shall be made with an elastomeric seal conforming to
ASTM C425, ASTM C1173 or CSA B602.
705.12 Polyethylene plastic pipe. Joints between polyethylene plastic pipe and fittings shall be underground and shall
comply with Section 705.12.1 or 705.12.2.
705.12.1 Heat-fusion joints. Joint surfaces shall be clean
and free from moisture. Joint surfaces shall be cut, heated
to melting temperature and joined using tools specifically
designed for the operation. Joints shall be undisturbed
until cool. Joints shall be made in accordance with ASTM
D2657 and the manufacturer’s instructions.
705.12.2 Mechanical joints. Mechanical joints in drainage piping shall be made with an elastomeric seal
conforming to ASTM C1173, ASTM D3212 or CSA
B602. Mechanical joints shall be installed in accordance
with the manufacturer’s instructions.
705.13 Polyolefin plastic. Joints between polyolefin plastic
pipe and fittings shall comply with Sections 705.13.1 and
705.13.2.
705.13.1 Heat-fusion joints. Heat-fusion joints for polyolefin pipe and tubing joints shall be installed with
socket-type heat-fused polyolefin fittings or electrofusion
polyolefin fittings. Joint surfaces shall be clean and free
from moisture. The joint shall be undisturbed until cool.
Joints shall be made in accordance with ASTM F1412 or
CSA B181.3.
705.13.2 Mechanical and compression sleeve joints.
Mechanical and compression sleeve joints shall be
installed in accordance with the manufacturer’s
instructions.
705.14 Polyvinylidene fluoride plastic. Joints between
polyvinylidene plastic pipe and fittings shall comply with
Sections 705.14.1 and 705.14.2.
705.14.1 Heat-fusion joints. Heat-fusion joints for polyvinylidene fluoride pipe and tubing joints shall be
installed with socket-type heat-fused polyvinylidene fluoride fittings or electrofusion polyvinylidene fittings and
couplings. Joint surfaces shall be clean and free from
moisture. The joint shall be undisturbed until cool. Joints
shall be made in accordance with ASTM F1673.
705.14.2 Mechanical and compression sleeve joints.
Mechanical and compression sleeve joints shall be
installed in accordance with the manufacturer’s
instructions.
705.15 Polypropylene plastic. The joint between polypropylene plastic pipe and fittings shall incorporate an
elastomeric seal. The joint shall conform to ASTM D3212.
Mechanical joints shall not be installed above ground.
705.16 Joints between different materials. Joints between
different piping materials shall be made with a mechanical
joint of the compression or mechanical-sealing type
conforming to ASTM C1173, ASTM C1460 or ASTM
C1461. Connectors and adapters shall be approved for the
application and such joints shall have an elastomeric seal
7-5
SANITARY DRAINAGE
conforming to ASTM C425, ASTM C443, ASTM C564,
ASTM C1440, ASTM F477, CSA A257.3M or CSA B602,
or as required in Sections 705.16.1 through 705.16.7. Joints
between glass pipe and other types of materials shall be
made with adapters having a TFE seal. Joints shall be
installed in accordance with the manufacturer’s instructions.
705.16.1 Copper pipe or tubing to cast-iron hub pipe.
Joints between copper pipe or tubing and cast-iron hub
pipe shall be made with a copper or copper-alloy ferrule
or compression joint. The copper pipe or tubing shall be
soldered to the ferrule in an approved manner, and the
ferrule shall be joined to the cast-iron hub by a caulked
joint or a mechanical compression joint.
705.16.2 Copper or copper-alloy pipe or tubing to
galvanized steel pipe. Joints between copper or copperalloy pipe or tubing and galvanized steel pipe shall be
made with a copper-alloy fitting or dielectric fitting. The
copper tubing shall be soldered to the fitting in an
approved manner, and the fitting shall be screwed to the
threaded pipe.
705.16.3 Cast-iron pipe to galvanized steel pipe. Joints
between cast iron and galvanized steel shall be made by
either caulked or threaded joints or with an approved
adapter fitting.
705.16.4 Plastic pipe or tubing to other piping material. Joints between different types of plastic pipe shall be
made with an approved adapter fitting, or by a solventcement joint only where a single joint is made between
ABS and PVC pipes at the end of a building drainage pipe
and the beginning of a building sewer pipe using a solvent
cement complying with ASTM D3138. Joints between
plastic pipe and other piping material shall be made with
an approved adapter fitting. Joints between plastic pipe
and cast-iron hub pipe shall be made by a caulked joint or
a mechanical compression joint.
705.16.5 Lead pipe to other piping material. Joints
between lead pipe and other piping material shall be made
by a wiped joint to a caulking ferrule, soldering nipple or
bushing or shall be made with an approved adapter
fitting.
705.16.6 Borosilicate glass to other materials. Joints
between glass pipe and other types of materials shall be
made with adapters having a TFE seal and shall be
installed in accordance with the manufacturer’s
instructions.
705.16.7 Stainless steel drainage systems to other
materials. Joints between stainless steel drainage systems
and other piping materials shall be made with approved
mechanical couplings.
705.17 Drainage slip joints. Slip joints shall comply with
Section 405.9.
705.18 Caulking ferrules. Caulking ferrules shall be of
copper alloy and shall be in accordance with Table 705.18.
TABLE 705.18
CAULKING FERRULE SPECIFICATIONS
PIPE SIZES
(inches)
INSIDE DIAMETER
(inches)
LENGTH
(inches)
MINIMUM
WEIGHT EACH
2
21/4
41/2
1 pound
3
31/4
41/2
1 pound
12 ounces
4
41/4
41/2
2 pounds
8 ounces
For SI: 1 inch = 25.4 mm, 1 ounce = 28.35 g, 1 pound = 0.454 kg.
705.19 Soldering bushings. Soldering bushings shall be of
copper or copper alloy and shall be in accordance with Table
705.19.
TABLE 705.19
SOLDERING BUSHING SPECIFICATIONS
PIPE SIZES (inches)
11/4
1
MINIMUM WEIGHT EACH
6 ounces
1 /2
8 ounces
2
14 ounces
21/2
1 pound 6 ounces
3
2 pounds
4
3 pounds 8 ounces
For SI: 1 inch = 25.4 mm, 1 ounce = 28.35 g, 1 pound = 0.454 kg.
705.20 Stainless steel drainage systems. O-ring joints for
stainless steel drainage systems shall be made with an
approved elastomeric seal.
SECTION 706
CONNECTIONS BETWEEN
DRAINAGE PIPING AND FITTINGS
706.1 Connections and changes in direction. Connections
and changes in direction of the sanitary drainage system
shall be made with approved drainage fittings. Connections
between drainage piping and fixtures shall conform to
Section 405.
706.2 Obstructions. The fittings shall not have ledges,
shoulders or reductions capable of retarding or obstructing
flow in the piping. Threaded drainage pipe fittings shall be
of the recessed drainage type. This section shall not be applicable to tubular waste fittings used to convey vertical flow
upstream of the trap seal liquid level of a fixture trap.
706.3 Installation of fittings. Fittings shall be installed to
guide sewage and waste in the direction of flow. Change in
direction shall be made by fittings installed in accordance
with Table 706.3. Change in direction by combination
fittings, side inlets or increasers shall be installed in accordance with Table 706.3 based on the pattern of flow created
by the fitting. Double sanitary tee patterns shall not receive
the discharge of back-to-back water closets and fixtures or
appliances with pumping action discharge.
Exception: Back-to-back water closet connections to
double sanitary tees shall be permitted where the horizon-
7-6
2021 INTERNATIONAL PLUMBING CODE®
SANITARY DRAINAGE
tal developed length between the outlet of the water closet
and the connection to the double sanitary tee pattern is 18
inches (457 mm) or greater.
TABLE 706.3
FITTINGS FOR CHANGE IN DIRECTION
TYPE OF FITTING
PATTERN
CHANGE IN DIRECTION
Horizontal to
vertical
Vertical to
horizontal
Horizontal to
horizontal
Sixteenth bend
X
X
X
Eighth bend
X
X
X
Sixth bend
X
X
X
Quarter bend
X
Xa
Xa
Short sweep
X
Xa,b
Xa
Long sweep
X
X
X
Sanitary tee
Xc
—
—
Wye
X
X
X
Combination wye and
eighth bend
X
X
X
For SI: 1 inch = 25.4 mm.
a. The fittings shall only be permitted for a 2-inch or smaller fixture drain.
b. Three inches or larger.
c. For a limitation on double sanitary tees, see Section 706.3.
706.4 Heel- or side-inlet quarter bends. Heel-inlet quarter
bends shall be an acceptable means of connection, except
where the quarter bend serves a water closet. A low-heel
inlet shall not be used as a wet-vented connection. Side-inlet
quarter bends shall be an acceptable means of connection for
drainage, wet venting and stack venting arrangements.
SECTION 707
PROHIBITED JOINTS AND CONNECTIONS
707.1 Prohibited joints. The following types of joints and
connections shall be prohibited:
1. Cement or concrete joints.
2. Mastic or hot-pour bituminous joints.
3. Joints made with fittings not approved for the
specific installation.
4. Joints between different diameter pipes made with
elastomeric rolling O-rings.
5. Solvent-cement joints between different types of
plastic pipe except where provided for in Section
705.16.4.
6. Saddle-type fittings.
SECTION 708
CLEANOUTS
708.1 Cleanouts required. Cleanouts shall be provided for
drainage piping in accordance with Sections 708.1.1 through
708.1.12.
708.1.1 Horizontal drains and building drains. Horizontal drainage pipes in buildings shall have cleanouts
located at intervals of not more than 100 feet (30 480
2021 INTERNATIONAL PLUMBING CODE®
mm). Building drains shall have cleanouts located at
intervals of not more than 100 feet (30 480 mm) except
where manholes are used instead of cleanouts, the
manholes shall be located at intervals of not more than
400 feet (122 m). The interval length shall be measured
from the cleanout or manhole opening, along the developed length of the piping to the next drainage fitting
providing access for cleaning, the end of the horizontal
drain or the end of the building drain.
Exception: Horizontal fixture drain piping serving a
nonremovable trap shall not be required to have a cleanout for the section of piping between the trap and the
vent connection for such trap.
708.1.2 Building sewers. Building sewers smaller than 8
inches (203 mm) shall have cleanouts located at intervals
of not more than 100 feet (30 480 mm). Building sewers 8
inches (203 mm) and larger shall have a manhole located
not more than 200 feet (60 960 mm) from the junction of
the building drain and building sewer and at intervals of
not more than 400 feet (122 m). The interval length shall
be measured from the cleanout or manhole opening, along
the developed length of the piping to the next drainage
fitting providing access for cleaning, a manhole or the end
of the building sewer.
708.1.3 Building drain and building sewer junction.
The junction of the building drain and the building sewer
shall be served by a cleanout that is located at the junction
or within 10 feet (3048 mm) of the developed length of
piping upstream of the junction. For the requirements of
this section, the removal of the water closet shall not be
required to provide cleanout access.
708.1.4 Changes of direction. Where a horizontal drainage pipe, a building drain or a building sewer has a
change of horizontal direction greater than 45 degrees
(0.79 rad), a cleanout shall be installed at the change of
direction. Where more than one change of horizontal
direction greater than 45 degrees (0.79 rad) occurs within
40 feet (12 192 mm) of developed length of piping, the
cleanout installed for the first change of direction shall
serve as the cleanout for all changes in direction within
that 40 feet (12 192 mm) of developed length of piping.
708.1.5 Cleanout size. Cleanouts shall be the same size
as the piping served by the cleanout, except that cleanouts
for piping larger than 4 inches (102 mm) need not be
larger than 4 inches (102 mm).
Exceptions:
1. A removable P-trap with slip or ground joint
connections can serve as a cleanout for drain
piping that is one size larger than the P-trap
size.
2. Cleanouts located on stacks can be one size
smaller than the stack size.
3. The size of cleanouts for cast-iron piping can
be in accordance with the referenced standards
for cast-iron fittings as indicated in Table
702.4.
7-7
SANITARY DRAINAGE
for such purposes and shall be approved. Trim cover
fasteners that thread into cleanout plugs shall be corrosion resistant. Cleanout plugs shall not be covered with
mortar, plaster or any other permanent material.
708.1.6 Cleanout equivalent. A fixture trap or a fixture
with integral trap, removable without altering concealed
piping, shall be acceptable as a cleanout equivalent.
708.1.7 Cleanout plugs. Cleanout plugs shall be of
copper-alloy, plastic or other approved materials. Cleanout plugs for borosilicate glass piping systems shall be
of borosilicate glass. Copper-alloy cleanout plugs shall
conform to ASTM A74 and shall be limited for use only
on metallic piping systems. Plastic cleanout plugs shall
conform to the referenced standards for plastic pipe
fittings, as indicated in Table 702.4. Cleanout plugs shall
have a raised square head, a countersunk square head or a
countersunk slot head. Where a cleanout plug will have a
trim cover screw installed into the plug, the plug shall be
manufactured with a blind end threaded hole for such
purpose.
708.1.8 Manholes. Manholes and manhole covers shall
be of an approved type. Manholes located inside of a
building shall have gas-tight covers that require tools for
removal.
708.1.9 Installation arrangement. The installation
arrangement of a cleanout shall enable cleaning of drainage piping only in the direction of drainage flow.
Exceptions:
1. Test tees serving as cleanouts.
2. A two-way cleanout installation that is
approved for meeting the requirements of
Section 708.1.3.
708.1.10 Required clearance. Cleanouts for 6-inch (153
mm) and smaller piping shall be provided with a clearance of not less than 18 inches (457 mm) from, and
perpendicular to, the face of the opening to any obstruction. Cleanouts for 8-inch (203 mm) and larger piping
shall be provided with a clearance of not less than 36
inches (914 mm) from, and perpendicular to, the face of
the opening to any obstruction.
708.1.11 Cleanout access. Required cleanouts shall not be
installed in concealed locations. For the purposes of this
section, concealed locations include, but are not limited to,
the inside of plenums, within walls, within floor/ceiling
assemblies, below grade and in crawl spaces where the
height from the crawl space floor to the nearest obstruction along the path from the crawl space opening to the
cleanout location is less than 24 inches (610 mm). Cleanouts with openings at a finished wall shall have the face of
the opening located within 11/2 inches (38 mm) of the
finished wall surface. Cleanouts located below grade shall
be extended to grade level so that the top of the cleanout
plug is at or above grade. A cleanout installed in a floor or
walkway that will not have a trim cover installed shall
have a countersunk plug installed so the top surface of the
plug is flush with the finished surface of the floor or
walkway.
708.1.11.1 Cleanout plug trim covers. Trim covers
and access doors for cleanout plugs shall be designed
7-8
708.1.11.2 Floor cleanout assemblies. Where it is
necessary to protect a cleanout plug from the loads of
vehicular traffic, cleanout assemblies in accordance
with ASME A112.36.2M shall be installed.
708.1.12 Prohibited use. The use of a threaded cleanout
opening to add a fixture or to extend piping shall be
prohibited except where another cleanout of equal size is
installed with the required access and clearance.
SECTION 709
FIXTURE UNITS
709.1 Values for fixtures. Drainage fixture unit values as
given in Table 709.1 designate the relative load weight of
different kinds of fixtures that shall be employed in estimating the total load carried by a soil or waste pipe, and shall be
used in connection with Tables 710.1(1) and 710.1(2) of
sizes for soil, waste and vent pipes for which the permissible
load is given in terms of fixture units.
709.2 Fixtures not listed in Table 709.1. Fixtures not listed
in Table 709.1 shall have a drainage fixture unit load based
on the outlet size of the fixture in accordance with Table
709.2. The minimum trap size for unlisted fixtures shall be
the size of the drainage outlet but not less than 11/4 inches (32
mm).
TABLE 709.2
DRAINAGE FIXTURE UNITS FOR FIXTURE DRAINS OR TRAPS
FIXTURE DRAIN OR TRAP SIZE
(inches)
DRAINAGE FIXTURE UNIT VALUE
11/4
1
11/2
2
2
3
1
2 /2
4
3
5
4
6
For SI: 1 inch = 25.4 mm.
709.3 Conversion of gpm flow to dfu values. Where
discharges to a waste receptor or to a drainage system are
only known in gallons per minute (liters per second) values,
the drainage fixture unit values for those flows shall be
computed on the basis that 1 gpm (0.06 L/s) of flow is equivalent to two drainage fixture units.
709.4 Values for indirect waste receptor. The drainage
fixture unit load of an indirect waste receptor receiving the
discharge of indirectly connected fixtures shall be the sum of
the drainage fixture unit values of the fixtures that discharge
to the receptor, but not less than the drainage fixture unit
value given for the indirect waste receptor in Table 709.1 or
709.2.
2021 INTERNATIONAL PLUMBING CODE®
SANITARY DRAINAGE
TABLE 709.1
DRAINAGE FIXTURE UNITS FOR FIXTURES AND GROUPS
FIXTURE TYPE
Automatic clothes washers, commerciala,g
Automatic clothes washers, residential
g
Bathroom group as defined in Section 202 (1.6 gpf water closet)f
DRAINAGE FIXTURE UNIT
VALUE AS LOAD FACTORS
MINIMUM SIZE OF TRAP
(inches)
3
2
2
2
5
—
Bathroom group as defined in Section 202 (water closet flushing greater than 1.6 gpf)f
6
—
Bathtubb (with or without overhead shower or whirlpool attachments)
2
11/2
Bidet
1
11/4
Combination sink and tray
2
11/2
Dental lavatory
1
11/4
Dental unit or cuspidor
1
11/4
2
11/2
Dishwashing machinec, domestic
Drinking fountain
1
/2
11/4
Emergency floor drain
0
2
Floor drainsh
2h
2
Floor sinks
Note h
2
Kitchen sink, domestic
2
11/2
Kitchen sink, domestic with food waste disposer, dishwasher or both
2
11/2
Laundry tray (1 or 2 compartments)
2
11/2
Lavatory
1
11/4
Shower (based on the total flow rate through showerheads and body sprays)
flow rate:
5.7 gpm or less
Greater than 5.7 gpm to 12.3 gpm
Greater than 12.3 gpm to 25.8 gpm
Greater than 25.8 gpm to 55.6 gpm
2
3
5
6
11/2
2
3
4
Service sink
2
11/2
Sink
2
11/2
Urinal
4
Note d
e
Note d
/2
Note d
2
11/2
Urinal, 1 gallon per flush or less
2
Urinal, nonwater supplied
1
Wash sink (circular or multiple) each set of faucets
4
e
Note d
Water closet, private (1.6 gpf)
3
e
Note d
Water closet, private (flushing greater than 1.6 gpf)
4e
Note d
Water closet, public (1.6 gpf)
e
4
Note d
Water closet, public (flushing greater than 1.6 gpf)
6e
Note d
Water closet, flushometer tank, public or private
For SI: 1 inch = 25.4 mm, 1 gallon = 3.785 L, gpf = gallon per flushing cycle, 1 gallon per minute (gpm) = 3.785 L/m.
a. For traps larger than 3 inches, use Table 709.2.
b. A showerhead over a bathtub or whirlpool bathtub attachment does not increase the drainage fixture unit value.
c. See Sections 709.2 through 709.4.1 for methods of computing unit value of fixtures not listed in this table or for rating of devices with intermittent flows.
d. Trap size shall be consistent with the fixture outlet size.
e. For the purpose of computing loads on building drains and sewers, water closets and urinals shall not be rated at a lower drainage fixture unit unless the
lower values are confirmed by testing.
f. For fixtures added to a bathroom group, add the dfu value of those additional fixtures to the bathroom group fixture count.
g. See Section 406.2 for sizing requirements for fixture drain, branch drain and drainage stack for an automatic clothes washer standpipe.
h. See Sections 709.4 and 709.4.1.
2021 INTERNATIONAL PLUMBING CODE®
7-9
SANITARY DRAINAGE
709.4.1 Clear-water waste receptors. Where waste
receptors such as floor drains, floor sinks and hub drains
receive only clear-water waste from display cases, refrigerated display cases, ice bins, coolers and freezers, such
receptors shall have a drainage fixture unit value of onehalf.
TABLE 710.1(1)
BUILDING DRAINS AND SEWERS
DIAMETER
OF PIPE
(inches)
MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS
CONNECTED TO ANY PORTION OF THE BUILDING
DRAIN OR THE BUILDING SEWER, INCLUDING
BRANCHES OF THE BUILDING DRAINa
Slope per foot
1
SECTION 710
DRAINAGE SYSTEM SIZING
710.1 Maximum fixture unit load. The maximum number
of drainage fixture units connected to a given size of building sewer, building drain or horizontal branch of the
building drain shall be determined using Table 710.1(1). The
maximum number of drainage fixture units connected to a
given size of horizontal branch or vertical soil or waste stack
shall be determined using Table 710.1(2).
710.1.1 Horizontal stack offsets. Horizontal stack
offsets shall be sized as required for building drains in
accordance with Table 710.1(1), except as required by
Section 711.3.
710.1.2 Vertical stack offsets. Vertical stack offsets shall
be sized as required for straight stacks in accordance with
Table 710.1(2), except where required to be sized as a
building drain in accordance with Section 711.1.1.
710.2 Future fixtures. Where provision is made for the
future installation of fixtures, those provided for shall be
considered in determining the required sizes of drain pipes.
/16 inch
1
/8 inch
1
/4 inch
1
/2 inch
1
1 /4
—
—
1
1 /2
—
—
3
3
2
—
—
21
26
21/2
—
—
24
31
3
—
36
42
50
4
—
180
216
250
5
—
390
480
575
6
—
700
840
1,000
8
1,400
1,600
1,920
2,300
10
2,500
2,900
3,500
4,200
1
1
12
3,900
4,600
5,600
6,700
15
7,000
8,300
10,000
12,000
For SI: 1 inch = 25.4 mm, 1 inch per foot = 83.3 mm/m.
a. The minimum size of any building drain serving a water closet shall be 3
inches.
TABLE 710.1(2)
HORIZONTAL FIXTURE BRANCHES AND STACKSa
MAXIMUM NUMBER OF DRAINAGE FIXTURE UNITS (dfu)
SECTION 711
OFFSETS IN DRAINAGE PIPING
IN BUILDINGS OF FIVE STORIES OR MORE
711.1 Horizontal branch connections above or below
vertical stack offsets. If a horizontal branch connects to the
stack within 2 feet (610 mm) above or below a vertical stack
offset, and the offset is located more than four branch intervals below the top of the stack, the offset shall be vented in
accordance with Section 907.
711.1.1 Omission of vents for vertical stack offsets.
Vents for vertical offsets required by Section 711.1 shall
not be required where the stack and its offset are sized as
a building drain [see Table 710.1(1)].
711.2 Horizontal stack offsets. A stack with a horizontal
offset located more than four branch intervals below the top
of the stack shall be vented in accordance with Section 907
and sized as follows:
1. The portion of the stack above the offset shall be
sized as for a vertical stack based on the total number
of drainage fixture units above the offset.
2. The offset shall be sized in accordance with Section
710.1.1.
3. The portion of the stack below the offset shall be
sized as for the offset or based on the total number of
drainage fixture units on the entire stack, whichever
is larger [see Table 710.1(2), Column 5].
7-10
Stacksb
DIAMETER
OF PIPE
(inches)
11/2
Total for
horizontal
branch
Total
discharge
into one
branch
interval
3
2
Total for
Total for
stack of
stack greater
three branch
than three
intervals or
branch
less
intervals
4
8
2
6
6
10
24
21/2
12
9
20
42
3
20
20
48
72
4
160
90
240
500
5
360
200
540
1,100
6
620
350
960
1,900
8
1,400
600
2,200
3,600
10
2,500
1,000
3,800
5,600
12
3,900
1,500
6,000
8,400
15
7,000
Note c
Note c
Note c
For SI:1 inch = 25.4 mm.
a. Does not include branches of the building drain. Refer to Table 710.1(1).
b. Stacks shall be sized based on the total accumulated connected load at
each story or branch interval. As the total accumulated connected load
decreases, stacks are permitted to be reduced in size. Stack diameters
shall not be reduced to less than one-half of the diameter of the largest
stack size required.
c. Sizing load based on design criteria.
2021 INTERNATIONAL PLUMBING CODE®
This File is Uploaded By
4MechEngineer.com
WIKIMEP.com
You can Follow US
Facebook/4MechEngineer
Linked-in/4MechEngineer
Instagram/4MechEngineer
YouTube/4MechEngineer
Google+/4MechEngineer
Twitter/4MechEngineer
SANITARY DRAINAGE
711.2.1 Omission of vents for horizontal stack offsets.
Vents for horizontal stack offsets required by Section
711.2 shall not be required where the stack and its offset
are one pipe size larger than required for a building drain
[see Table 710.1(1)] and the entire stack and offset are not
less in cross-sectional area than that required for a straight
stack plus the area of an offset vent as provided for in
Section 907.
711.3 Offsets below lowest branch. Where a vertical offset
occurs in a soil or waste stack below the lowest horizontal
branch, a change in diameter of the stack because of the
offset shall not be required. If a horizontal offset occurs in a
soil or waste stack below the lowest horizontal branch, the
required diameter of the offset and the stack below it shall be
determined as for a building drain in accordance with Table
710.1(1).
pated loads in the area of use. The sump pit shall be
vented in accordance with Chapter 9.
712.3.3 Discharge pipe and fittings. Discharge pipe and
fittings serving sump pumps and ejectors shall be
constructed of materials in accordance with Sections
712.3.3.1 and 712.3.3.2.
712.3.3.1 Materials. Pipe and fitting materials shall be
constructed of copper or copper-alloy, CPVC, ductile
iron, PE, or PVC.
712.3.3.2 Ratings. Pipe and fittings shall be rated for
the maximum system operating pressure and temperature. Pipe fitting materials shall be compatible with the
pipe material. Where pipe and fittings are buried in the
earth, they shall be suitable for burial.
SECTION 712
SUMPS AND EJECTORS
712.3.4 Maximum effluent level. The effluent level
control shall be adjusted and maintained to at all times
prevent the effluent in the sump from rising to within 2
inches (51 mm) of the invert of the gravity drain inlet into
the sump.
712.1 Building subdrains. Building subdrains that cannot
be discharged to the sewer by gravity flow shall be
discharged into a tightly covered and vented sump from
which the liquid shall be lifted and discharged into the building gravity drainage system by automatic pumping
equipment or other approved method. In other than existing
structures, the sump shall not receive drainage from any
piping within the building capable of being discharged by
gravity to the building sewer.
712.3.5 Pump connection to the drainage system.
Pumps connected to the drainage system shall connect to
a building sewer, building drain, soil stack, waste stack or
horizontal branch drain. Where the discharge line
connects into horizontal drainage piping, the connection
shall be made through a wye fitting into the top of the
drainage piping and such wye fitting shall be located not
less than 10 pipe diameters from the base of any soil
stack, waste stack or fixture drain.
712.2 Valves required. A check valve and a full open valve
located on the discharge side of the check valve shall be
installed in the pump or ejector discharge piping between the
pump or ejector and the gravity drainage system. Access
shall be provided to such valves. Such valves shall be
located above the sump cover required by Section 712.1 or,
where the discharge pipe from the ejector is below grade, the
valves shall be accessibly located outside the sump below
grade in an access pit with a removable access cover.
712.4 Sewage pumps and sewage ejectors. A sewage pump
or sewage ejector shall automatically discharge the contents
of the sump to the building drainage system.
712.3 Sump design. The sump pump, pit and discharge
piping shall conform to the requirements of Sections 712.3.1
through 712.3.5.
712.3.1 Sump pump. The sump pump capacity and head
shall be appropriate to anticipated use requirements.
712.3.2 Sump pit. The sump pit shall be not less than 18
inches (457 mm) in diameter and not less than 24 inches
(610 mm) in depth, unless otherwise approved. The pit
shall be provided with access and shall be located such
that all drainage flows into the pit by gravity. The sump
pit shall be constructed of tile, concrete, steel, plastic or
other approved materials. The pit bottom shall be solid
and provide permanent support for the pump. The sump
pit shall be fitted with a gastight removable cover that is
installed not more than 2 inches (51 mm) below grade or
floor level. The cover shall be adequate to support antici-
2021 INTERNATIONAL PLUMBING CODE®
712.4.1 Macerating toilet systems. Macerating toilet
systems shall comply with ASME A112.3.4/CSA B45.9
and shall be installed in accordance with the manufacturer’s instructions.
712.4.2 Capacity. A sewage pump or sewage ejector
shall have the capacity and head for the application
requirements. Pumps or ejectors that receive the
discharge of water closets shall be capable of handling
spherical solids with a diameter of up to and including 2
inches (51 mm). Other pumps or ejectors shall be capable
of handling spherical solids with a diameter of up to and
including 1/2 inch (13 mm). The capacity of a pump or
ejector based on the diameter of the discharge pipe shall
be not less than that indicated in Table 712.4.2.
Exceptions:
1. Grinder pumps or grinder ejectors that receive
the discharge of water closets shall have a
discharge opening of not less than 11/4 inches
(32 mm).
2. Macerating toilet assemblies that serve single
water closets shall have a discharge opening of
not less than 3/4 inch (19.1 mm).
7-11
SANITARY DRAINAGE
TABLE 712.4.2
MINIMUM CAPACITY OF
SEWAGE PUMP OR SEWAGE EJECTOR
DIAMETER OF
THE DISCHARGE PIPE (inches)
CAPACITY OF PUMP
OR EJECTOR (gpm)
2
21
21/2
30
3
46
For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m.
SECTION 713
COMPUTERIZED DRAINAGE DESIGN
713.1 Design of drainage system. The sizing, design and
layout of the drainage system shall be permitted to be
designed by approved computer design methods.
713.2 Load on drainage system. The load shall be
computed from the simultaneous or sequential discharge
conditions from fixtures, appurtenances and appliances or
the peak usage design condition.
713.2.1 Fixture discharge profiles. The discharge
profiles for flow rates versus time from fixtures and appliances shall be in accordance with the manufacturer’s
specifications.
SECTION 715
VACUUM DRAINAGE SYSTEMS
715.1 Scope. Vacuum drainage systems shall be in accordance with Sections 715.2 through 715.4.
715.2 System design. Vacuum drainage systems shall be
designed in accordance with the vacuum drainage system
manufacturer’s instructions. The system layout, including
piping layout, tank assemblies, vacuum pump assembly and
other components necessary for proper function of the
system shall be in accordance with the manufacturer’s
instructions. Plans, specifications and other data for such
systems shall be submitted to the code official for review and
approval prior to installation.
715.2.1 Fixtures. Gravity-type fixtures installed in
vacuum drainage systems shall comply with Chapter 4.
715.2.2 Drainage fixture units. Drainage fixture units
for gravity drainage systems that discharge into, or
receive discharge from, vacuum drainage systems shall be
based on the values in this chapter.
715.2.3 Water supply fixture units. Water supply
fixture units shall be based on the values in Chapter 6 of
this code, except that the water supply fixture unit for a
vacuum-type water closet shall be 1.
713.3 Selections of drainage pipe sizes. Pipe shall be sized
to prevent full-bore flow.
715.2.4 Traps and cleanouts. Gravity drainage fixtures
shall be provided with traps and cleanouts in accordance
with this chapter and Chapter 10.
713.3.1 Selecting pipe wall roughness. Pipe size calculations shall be conducted with the pipe wall roughness
factor (ks), in accordance with the manufacturer’s specifications and as modified for aging roughness factors with
deposits and corrosion.
715.2.5 Materials. Vacuum drainage pipe, fitting and
valve materials shall be in accordance with the vacuum
drainage system manufacturer’s instructions and the
requirements of this chapter.
713.3.2 Slope of horizontal drainage piping. Horizontal
drainage piping shall be designed and installed at slopes
in accordance with Table 704.1.
SECTION 714
BACKWATER VALVES
714.1 Sewage backflow. Where plumbing fixtures are
installed on a floor with a finished floor elevation below the
elevation of the manhole cover of the next upstream manhole
in the public sewer, such fixtures shall be protected by a
backwater valve installed in the building drain, or horizontal
branch serving such fixtures. Plumbing fixtures installed on
a floor with a finished floor elevation above the elevation of
the manhole cover of the next upstream manhole in the
public sewer shall not discharge through a backwater valve.
Exception: In existing buildings, fixtures above the
elevation of the manhole cover of the next upstream
manhole in the public sewer shall not be prohibited from
discharging through a backwater valve.
714.2 Material. Backwater valves shall comply with ASME
A112.14.1, CSA B181.1 or CSA B181.2.
714.3 Location. Backwater valves shall be installed so that
access is provided to the working parts.
7-12
715.3 Testing and demonstrations. After completion of the
entire system installation, the system shall be subjected to a
vacuum test of 19 inches (483 mm) of mercury and shall be
operated to function as required by the code official and the
manufacturer of the vacuum drainage system. Recorded
proof of all tests shall be submitted to the code official.
715.4 Written instructions. Written instructions for the
operation, maintenance, safety and emergency procedures
shall be provided to the building owner. The code official
shall verify that the building owner is in receipt of such
instructions.
SECTION 716
REPLACEMENT OF UNDERGROUND
BUILDING SEWERS AND BUILDING
DRAINS BY PIPE-BURSTING METHODS
716.1 General. This section shall govern the replacement of
existing building sewer and building drain piping by pipebursting methods.
716.2 Applicability. The replacement of building sewer and
building drain piping by pipe-bursting methods shall be
limited to gravity drainage piping of sizes 6 inches (152 mm)
and smaller. The replacement piping shall be of the same
nominal size as the existing piping.
2021 INTERNATIONAL PLUMBING CODE®
SANITARY DRAINAGE
716.3 Pre-installation inspection. The existing piping
sections to be replaced shall be inspected internally by a
recorded video camera survey. The survey shall include
notations of the position of cleanouts and the depth of
connections to the existing piping.
716.4 Pipe. The replacement pipe shall be made of highdensity polyethylene (HDPE) and shall have a standard
dimension ratio (SDR) of 17. The pipe shall be in compliance with ASTM F714.
716.5 Pipe fittings. Pipe fittings to be connected to the
replacement pipe shall be made of high-density polyethylene
(HDPE) and shall be in compliance with ASTM D2683.
716.6 Cleanouts. Where the existing building sewer or
building drain did not have cleanouts meeting the requirements of this code, cleanout fittings shall be installed as
required by this code.
716.7 Post-installation inspection. The completed replacement piping section shall be inspected internally by a
recorded video camera survey. The video survey shall be
reviewed and approved by the code official prior to pressure
testing of the replacement piping system.
716.8 Pressure testing. The replacement piping system as
well as the connections to the replacement piping shall be
tested in accordance with Section 312.
SECTION 717
RELINING BUILDING SEWERS
AND BUILDING DRAINS
717.1 General. This section shall govern the relining of
existing building sewers and building drainage piping.
717.2 Applicability. The relining of existing building
sewers and building drainage piping shall be limited to gravity drainage piping 4 inches (102 mm) in diameter and
larger. The relined piping shall be of the same nominal size
as the existing piping.
717.3 Preinstallation requirements. Prior to commencement of the relining installation, the existing piping sections
to be relined shall be descaled and cleaned. After the cleaning process has occurred and water has been flushed through
the system, the piping shall be inspected internally by a
recorded video camera survey.
717.3.1 Preinstallation recorded video camera survey.
The video survey shall include verification of the project
address location. The video shall include notations of the
cleanout and fitting locations, and the approximate depth
of the existing piping. The video shall also include notations of the length of piping at intervals not greater than
25 feet (7620 mm).
717.4 Permitting. Prior to permit issuance, the code official
shall review and evaluate the preinstallation recorded video
camera survey to determine if the piping system is able to be
relined in accordance with the proposed lining system manufacturer’s installation requirements and applicable
referenced standards.
2021 INTERNATIONAL PLUMBING CODE®
717.5 Prohibited applications. Where review of the preinstallation recorded video camera survey reveals that piping
systems are not installed correctly or defects exist, relining
shall not be permitted. The defective portions of piping shall
be exposed and repaired with pipe and fittings in accordance
with this code. Defects include, but are not limited to, backgrade or insufficient slope, complete pipe wall deterioration
or complete separations such as from tree root invasion or
improper support.
717.6 Relining materials. The relining materials shall be
manufactured in compliance with applicable standards and
certified as required in Section 303. Fold-and-form pipe
reline materials shall be manufactured in compliance with
ASTM F1504 or ASTM F1871.
717.7 Installation. The installation of relining materials
shall be performed in accordance with the manufacturer's
installation instructions, applicable referenced standards and
this code.
717.7.1 Material data report. The installer shall record
the data as required by the relining material manufacturer
and applicable standards. The recorded data shall include
but is not limited to the location of the project, relining
material type, amount of product installed and conditions
of the installation. A copy of the data report shall be
provided to the code official prior to final approval.
717.8 Post-installation recorded video camera survey.
The completed, relined piping system shall be inspected
internally by a recorded video camera survey after the
system has been flushed and flow-tested with water. The
video survey shall be submitted to the the code official prior
to finalization of the permit. The video survey shall be
reviewed and evaluated to provide verification that no
defects exist. Any defects identified shall be repaired and
replaced in accordance with this code.
717.9 Certification. A certification shall be provided in
writing to the code official, from the permit holder, that the
relining materials have been installed in accordance with the
manufacturer’s installation instructions, the applicable standards and this code.
717.10 Approval. Upon verification of compliance with the
requirements of Sections 717.1 through 717.9, the code official shall approve the installation.
SECTION 718
REHABILITATION OF
BUILDING SEWERS AND BUILDING DRAINS
718.1 Cure-in-place. Sectional cure-in-place rehabilitation
of building sewer piping and sewer service lateral piping
shall be in accordance with ASTM F2599. Main and lateral
cure-in-place rehabilitation of building sewer and sewer
service lateral pipe and their connections to the main sewer
pipe shall be in accordance with ASTM F2561. Hydrophilic
rings or gaskets in cure-in-place rehabilitation of building
sewer piping and sewer service laterals shall be in accordance with ASTM F3240 to ensure water tightness and
elimination of ground water penetration.
7-13
7-14
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 8
INDIRECT/SPECIAL WASTE
User note:
About this chapter: There are drainage applications in buildings where a backup of liquid waste in a drainage system could contaminate
equipment and appliances. Chapter 8 covers the applications that require an indirect discharge connection to the building’s drainage
system. The chapter has provisions for the types of indirect connections and waste receptor configurations.
SECTION 801
GENERAL
801.1 Scope. This chapter shall govern matters concerning
indirect waste piping and special wastes. This chapter shall
further control matters concerning food-handling establishments, sterilizers, humidifiers, clear-water waste, swimming
pools, methods of providing air breaks or air gaps, and
neutralizing devices for corrosive wastes.
801.2 Protection. Devices, appurtenances, appliances and
apparatus intended to serve some special function, such as
sterilization, humidification, distillation, processing, cooling, or storage of ice or foods, and that discharge to the
drainage system, shall be provided with protection against
backflow, flooding, fouling, contamination and stoppage of
the drain.
SECTION 802
INDIRECT WASTES
802.1 Where required. Food-handling equipment, in other
than dwelling units, clear-water waste, humidifiers, dishwashing machines and utensils, pots, pans and dishwashing
sinks shall discharge through an indirect waste pipe as specified in Sections 802.1.1 through 802.1.7. Fixtures not
required to be indirectly connected by this section and the
exception to Section 301.6 shall be directly connected to the
plumbing system in accordance with Chapter 7.
802.1.1 Food handling. Equipment and fixtures utilized
for the storage, preparation and handling of food shall
discharge through an indirect waste pipe by means of an
air gap. Each well of a multiple-compartment sink shall
discharge independently to a waste receptor.
802.1.2 Floor drains in food storage areas. Floor drains
located within walk-in refrigerators or freezers in food
service and food establishments shall be indirectly
connected to the sanitary drainage system by means of an
air gap. Where a floor drain is located within an area
subject to freezing, the waste line serving the floor drain
shall not be trapped and shall indirectly discharge into a
waste receptor located outside of the area subject to
freezing.
Exception: Where protected against backflow by a
backwater valve, such floor drains shall be indirectly
connected to the sanitary drainage system by means of
an air break or an air gap.
2021 INTERNATIONAL PLUMBING CODE®
802.1.3 Potable clear-water waste. Where devices and
equipment, such as sterilizers and relief valves, discharge
potable water to the building drainage system, the
discharge shall be through an indirect waste pipe by
means of an air gap.
802.1.4 Swimming pools. Where wastewater from swimming pools, backwash from filters and water from pool
deck drains discharge to the building drainage system, the
discharge shall be through an indirect waste pipe by
means of an air gap.
802.1.5 Nonpotable clear-water waste. Where devices
and equipment such as process tanks, filters, drips and
boilers discharge nonpotable water to the building drainage system, the discharge shall be through an indirect
waste pipe by means of an air break or an air gap.
802.1.6 Commercial dishwashing machines. The
discharge from a commercial dishwashing machine shall
be through an air gap or air break into a waste receptor in
accordance with Section 802.3.
802.1.7 Food utensils, dishes, pots and pans sinks.
Sinks, in other than dwelling units, used for the washing,
rinsing or sanitizing of utensils, dishes, pots, pans or
service ware used in the preparation, serving or eating of
food shall discharge indirectly through an air gap or an
air break to the drainage system.
802.2 Material, joints and connections. The materials,
joints, connections and methods utilized for the construction
and installation of indirect waste piping systems shall
comply with the applicable provisions of Chapter 7.
802.3 Installation. Indirect waste piping shall discharge
through an air gap or air break into a waste receptor. Waste
receptors shall be trapped and vented and shall connect to the
building drainage system. Indirect waste piping that exceeds
30 inches (762 mm) in developed length measured horizontally, or 54 inches (1372 mm) in total developed length, shall
be trapped.
Exception: Where a waste receptor receives only clearwater waste and does not directly connect to a sanitary
drainage system, the receptor shall not require a trap.
802.3.1 Air gap. The air gap between the indirect waste
pipe and the flood level rim of the waste receptor shall be
not less than twice the effective opening of the indirect
waste pipe.
8-1
INDIRECT/SPECIAL WASTE
802.3.2 Air break. An air break shall be provided
between the indirect waste pipe and the trap seal of the
waste receptor.
802.4 Waste receptors. For other than hub drains that
receive only clear-water waste and standpipes, a removable
strainer or basket shall cover the outlet of waste receptors.
Waste receptors shall not be installed in concealed spaces.
Waste receptors shall not be installed in plenums, crawl
spaces, attics, interstitial spaces above ceilings and below
floors. Ready access shall be provided to waste receptors.
802.4.1 Size of receptors. A waste receptor shall be sized
for the maximum discharge of all indirect waste pipes
served by the receptor. Receptors shall be installed to
prevent splashing or flooding.
802.4.2 Hub drains. A hub drain shall be in the form of a
hub or a pipe extending not less than 1 inch (25 mm)
above a water-impervious floor.
802.4.3 Standpipes. Standpipes shall be individually
trapped. Standpipes shall extend not less than 18 inches
(457 mm) but not greater than 42 inches (1067 mm)
above the trap weir. Access shall be provided to standpipes and drains for rodding.
802.4.3.1 Connection of laundry tray to standpipe.
As an alternative for a laundry tray fixture connecting
directly to a drainage system, a laundry tray waste line
without a fixture trap shall connect to a standpipe for
an automatic clothes washer drain. The standpipe shall
extend not less than 30 inches (762 mm) above the
weir of the standpipe trap and shall extend above the
flood level rim of the laundry tray. The outlet of the
laundry tray shall not be greater than 30 inches (762
mm) horizontal distance from the side of the
standpipe.
SECTION 803
SPECIAL WASTES
803.1 Neutralizing device required for corrosive wastes.
Corrosive liquids, spent acids or other harmful chemicals
that destroy or injure a drain, sewer, soil or waste pipe, or
create noxious or toxic fumes or interfere with sewage treatment processes shall not be discharged into the plumbing
system without being thoroughly diluted, neutralized or
treated by passing through an approved dilution or neutralizing device. Such devices shall be automatically provided
with a sufficient supply of diluting water or neutralizing
medium so as to make the contents noninjurious before
discharge into the drainage system. The nature of the corrosive or harmful waste and the method of its treatment or
dilution shall be approved prior to installation.
803.2 System design. A chemical drainage and vent system
shall be designed and installed in accordance with this code.
Chemical drainage and vent systems shall be completely
separated from the sanitary systems. Chemical waste shall
not discharge to a sanitary drainage system until such waste
has been treated in accordance with Section 803.1.
8-2
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 9
VENTS
User note:
About this chapter: Chapter 9 regulates connection locations, various venting system arrangements and the sizing of piping for vent
systems. The proper operation of a gravity flow drainage system (Chapter 7) depends on maintaining an air path throughout the system to
prevent waste and odor “blow back” into fixtures and siphoning of the trap seal in fixture traps (Chapter 10).
SECTION 901
GENERAL
SECTION 903
VENT TERMINALS
901.1 Scope. The provisions of this chapter shall govern the
materials, design, construction and installation of vent
systems.
903.1 Vent terminal required. The vent pipe shall terminate by extending to the outdoors through the roof or the side
wall in accordance with one of the methods identified in
Sections 903.1.1 through 903.1.4.
901.2 Trap seal protection. The plumbing system shall be
provided with a system of vent piping that will permit the
admission or emission of air so that the seal of any fixture
trap shall not be subjected to a pressure differential of more
than 1 inch of water column (249 Pa).
901.2.1 Venting required. Traps and trapped fixtures
shall be vented in accordance with one of the venting
methods specified in this chapter.
901.3 Chemical waste vent systems. The vent system for a
chemical waste system shall be independent of the sanitary
vent system and shall terminate separately through the roof
to the outdoors or to an air admittance valve that complies
with ASSE 1049. Air admittance valves for chemical waste
systems shall be constructed of materials approved in accordance with Section 702.6 and shall be tested for chemical
resistance in accordance with ASTM F1412.
901.4 Use limitations. The plumbing vent system shall not
be utilized for purposes other than the venting of the plumbing system.
901.5 Tests. The vent system shall be tested in accordance
with Section 312.
901.6 Engineered systems. Engineered venting systems
shall conform to the provisions of Section 919.
SECTION 902
MATERIALS
902.1 Vents. The materials and methods utilized for the
construction and installation of venting systems shall comply
with the applicable provisions of Section 702.
902.2 Sheet copper. Sheet copper for vent pipe flashings
shall conform to ASTM B152 and shall weigh not less than 8
ounces per square foot (2.5 kg/m2).
902.3 Sheet lead. Sheet lead for vent pipe flashings shall
weigh not less than 3 pounds per square foot (15 kg/m2) for
field-constructed flashings and not less than 21/2 pounds per
square foot (12 kg/m2) for prefabricated flashings.
2021 INTERNATIONAL PLUMBING CODE®
903.1.1 Roof extension unprotected. Open vent pipes
that extend through a roof shall be terminated not less
than [NUMBER] inches (mm) above the roof.
903.1.2 Roof used for recreational or assembly
purposes. Where a roof is to be used as a promenade,
restaurant, bar, or sunbathing deck, as an observation
deck, or for similar purposes, open vent pipes shall terminate not less than 7 feet (2134 mm) above the roof.
903.1.3 Protected vent terminal. Where an open vent
pipe terminates above a sloped roof and is covered by
either a roof-mounted panel (such as a solar collector or
photovoltaic panel mounted over the vent opening) or a
roof element (such as an architectural feature or a decorative shroud), the vent pipe shall terminate not less than 2
inches (51 mm) above the roof surface. Such roof
elements shall be designed to prevent the adverse effects
of snow accumulation and wind on the function of the
vent. The placement of a panel over a vent pipe and the
design of a roof element covering the vent pipe shall
provide for an open area for the vent pipe to the outdoors
that is not less than the area of the pipe, as calculated from
the inside diameter of the pipe. Such vent terminals shall
be protected by a method that prevents birds and rodents
from entering or blocking the vent pipe opening.
903.1.4 Sidewall vent terminal. Vent terminals extending through the wall shall terminate not less than 10 feet
(3048 mm) from the lot line and 10 feet (3048 mm) above
the highest adjacent grade within 10 feet (3048 mm) horizontally of the vent terminal. Vent terminals shall not
terminate under the overhang of a structure with soffit
vents. Sidewall vent terminals shall be protected to
prevent birds and rodents from entering or blocking the
vent opening.
903.2 Frost closure. Where the 97.5-percent value for
outdoor design temperature is 0°F (-18°C) or less, vent
extensions through a roof or wall shall be not less than 3
inches (76 mm) in diameter. Any increase in the size of the
vent shall be made not less than 1 foot (305 mm) inside the
thermal envelope of the building.
9-1
VENTS

903.3 Flashings. The juncture of each vent pipe with the
roof line shall be made watertight by an approved flashing.
SECTION 905
VENT CONNECTIONS AND GRADES
903.4 Prohibited use. A vent terminal shall not be used for
any purpose other than a vent terminal.
905.1 Connection. Individual, branch and circuit vents shall
connect to a vent stack, stack vent, air admittance valve or
extend to the open air.
903.5 Location of vent terminal. An open vent terminal
from a drainage system shall not be located directly beneath
any door, openable window, or other air intake opening of
the building or of an adjacent building, and any such vent
terminal shall not be within 10 feet (3048 mm) horizontally
of such an opening unless it is 3 feet (914 mm) or more
above the top of such opening.
903.6 Extension outside a structure. In climates where the
97.5-percent value for outside design temperature is less
than 0°F (-18°C), vent pipes installed on the exterior of the
structure shall be protected against freezing by insulation,
heat or both.
SECTION 904
OUTDOOR VENT EXTENSIONS
904.1 Required vent extension. The vent system serving
each building drain shall have not less than one vent pipe
that extends to the outdoors.
904.1.1 Installation. The required vent shall be a dry vent
that connects to the building drain or an extension of a
drain that connects to the building drain. Such vent shall
not be an island fixture vent as allowed by Section 916.
904.1.2 Size. The required vent shall be sized in accordance with Section 906.2 based on the required size of the
building drain.
904.2 Vent stack required. A vent stack shall be required
for every drainage stack that has five branch intervals or
more.
Exception: Drainage stacks installed in accordance with
Section 913.
904.3 Vent termination. Vent stacks or stack vents shall
terminate outdoors to the open air or to a stack-type air
admittance valve in accordance with Section 918.
904.4 Vent connection at base. Vent stacks shall connect to
the base of the drainage stack. The vent stack shall connect
at or below the lowest horizontal branch. Where the vent
stack connects to the building drain, the connection shall be
located downstream of the drainage stack and within a
distance of 10 times the diameter of the drainage stack.
904.5 Vent headers. Stack vents and vent stacks connected
into a common vent header at the top of the stacks and
extending to the open air at one point shall be sized in accordance with the requirements of Section 906.1. The number
of fixture units shall be the sum of all fixture units on all
stacks connected thereto, and the developed length shall be
the longest vent length from the intersection at the base of
the most distant stack to the vent terminal in the open air, as
a direct extension of one stack.
9-2
905.2 Grade. Vent and branch vent pipes shall be so graded
and connected as to drain back to the drainage pipe by
gravity.
905.3 Vent connection to drainage system. Every dry vent
connecting to a horizontal drain shall connect above the
centerline of the horizontal drain pipe.
905.4 Vertical rise of vent. Every dry vent shall rise vertically to a point not less than 6 inches (152 mm) above the
flood level rim of the highest trap or trapped fixture being
vented.
Exception: Vents for interceptors located outdoors.
905.5 Height above fixtures. A connection between a vent
pipe and a vent stack or stack vent shall be made at not less
than 6 inches (152 mm) above the flood level rim of the highest fixture served by the vent. Horizontal vent pipes forming
branch vents, relief vents or loop vents shall be located not
less than 6 inches (152 mm) above the flood level rim of the
highest fixture served.
905.6 Vent for future fixtures. Where the drainage piping
has been roughed-in for future fixtures, a rough-in connection for a vent shall be installed. The vent size shall be not
less than one-half the diameter of the rough-in drain to be
served. The vent rough-in shall connect to the vent system,
or shall be vented by other means as provided for in this
chapter. The connection shall be identified to indicate that it
is a vent.
SECTION 906
VENT PIPE SIZING
906.1 Size of stack vents and vent stacks. The minimum
required diameter of stack vents and vent stacks shall be
determined from the developed length and the total of drainage fixture units connected thereto in accordance with Table
906.1, but in no case shall the diameter be less than one-half
the diameter of the drain served or less than 11/4 inches (32
mm).
906.2 Vents other than stack vents or vent stacks. The
diameter of individual vents, branch vents, circuit vents and
relief vents shall be not less than one-half the required diameter of the drain served. The required size of the drain shall
be determined in accordance with Table 710.1(2). Vent pipes
shall be not less than 11/4 inches (32 mm) in diameter. Vents
exceeding 40 feet (12 192 mm) in developed length shall be
increased by one nominal pipe size for the entire developed
length of the vent pipe. Relief vents for soil and waste stacks
in buildings having more than 10 branch intervals shall be
sized in accordance with Section 908.2.
2021 INTERNATIONAL PLUMBING CODE®
VENTS
TABLE 906.1
SIZE AND DEVELOPED LENGTH OF STACK VENTS AND VENT STACKS
DIAMETER OF
SOIL OR WASTE STACK
(inches)
MAXIMUM DEVELOPED LENGTH OF VENT (feet)a DIAMETER OF VENT (inches)
TOTAL FIXTURE
UNITS BEING VENTED
(dfu)
11/4
11/2
2
21/2
3
4
5
6
8
10
12
30
50
30
—
150
100
—
—
—
—
—
—
—
—
—
11/2
2
8
10
2
2
21/2
12
20
42
—
30
26
75
50
30
200
150
100
—
—
300
—
—
—
—
—
—
—
3
3
3
10
21
53
—
42
32
27
150
110
94
360
270
230
1,040
810
680
—
—
—
—
—
—
3
4
4
102
43
140
—
25
—
—
86
35
27
210
85
65
620
250
200
—
980
750
—
—
—
—
—
4
4
5
320
540
190
—
—
23
21
—
55
50
28
170
150
82
640
580
320
—
—
990
—
—
—
—
5
5
5
490
940
1,400
—
—
—
21
18
16
63
53
49
250
210
190
760
670
590
—
—
—
—
6
6
6
500
1,100
2,000
—
—
—
—
33
26
22
130
100
84
400
310
260
1,000
780
660
—
—
—
6
8
8
2,900
1,800
3,400
—
—
—
—
20
—
—
77
31
24
240
95
73
600
240
190
—
940
729
—
—
8
8
10
5,600
7,600
4,000
—
—
—
—
—
20
18
—
62
56
31
160
140
78
610
560
310
—
—
960
—
10
10
10
7,200
11,000
15,000
—
—
—
—
—
—
24
20
18
60
51
46
240
200
180
740
630
571
—
12
12
12
7,300
13,000
20,000
—
—
—
—
—
—
—
31
24
20
120
94
79
380
300
250
940
720
610
12
15
15
26,000
15,000
25,000
—
—
—
—
—
—
—
18
—
—
72
40
31
230
130
96
500
310
240
15
15
38,000
50,000
—
—
—
—
—
—
—
—
26
24
81
74
200
180
1
1 /4
11/2
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
a. The developed length shall be measured from the vent connection to the open air.
2021 INTERNATIONAL PLUMBING CODE®
9-3
VENTS
906.3 Developed length. The developed length of individual, branch, circuit and relief vents shall be measured from
the farthest point of vent connection to the drainage system
to the point of connection to the vent stack, stack vent or
termination outside of the building.
906.4 Multiple branch vents. Where multiple branch vents
are connected to a common branch vent, the common
branch vent shall be sized in accordance with this section
based on the size of the common horizontal drainage branch
that is or would be required to serve the total drainage
fixture unit load being vented.
906.5 Sump vents. Sump vent sizes shall be determined in
accordance with Sections 906.5.1 and 906.5.2.
906.5.1 Sewage pumps and sewage ejectors other than
pneumatic. Drainage piping below sewer level shall be
vented in the same manner as that of a gravity system.
Building sump vent sizes for sumps with sewage pumps
or sewage ejectors, other than pneumatic, shall be determined in accordance with Table 906.5.1.
906.5.2 Pneumatic sewage ejectors. The air pressure
relief pipe from a pneumatic sewage ejector shall be
connected to an independent vent stack terminating as
required for vent extensions through the roof. The relief
pipe shall be sized to relieve air pressure inside the ejector
to atmospheric pressure, but shall be not less than 11/4
inches (32 mm) in size.
SECTION 907
VENTS FOR STACK OFFSETS
or more branch intervals are located above the offset. The
offset shall be vented by venting the upper section of the
drainage stack and the lower section of the drainage stack.
907.2 Upper section. The upper section of the drainage
stack shall be vented as a separate stack with a vent stack
connection installed in accordance with Section 904.4. The
offset shall be considered to be the base of the stack.
907.3 Lower section. The lower section of the drainage
stack shall be vented by a yoke vent connecting between the
offset and the next lower horizontal branch. The yoke vent
connection shall be permitted to be a vertical extension of
the drainage stack. The size of the yoke vent and connection
shall be not less than the size required for the vent stack of
the drainage stack.
SECTION 908
RELIEF VENTS—STACKS OF
MORE THAN 10 BRANCH INTERVALS
908.1 Where required. Soil and waste stacks in buildings
having more than 10 branch intervals shall be provided with
a relief vent at each tenth interval installed, beginning with
the top floor.
908.2 Size and connection. The size of the relief vent shall
be equal to the size of the vent stack to which it connects.
The lower end of each relief vent shall connect to the soil or
waste stack through a wye below the horizontal branch serving the floor, and the upper end shall connect to the vent
stack through a wye not less than 3 feet (914 mm) above the
floor.
907.1 Vent for horizontal offset of drainage stack. Horizontal offsets of drainage stacks shall be vented where five
TABLE 906.5.1
SIZE AND LENGTH OF SUMP VENTS
DISCHARGE
CAPACITY OF PUMP
(gpm)
MAXIMUM DEVELOPED LENGTH OF VENT (feet)a
Diameter of vent (inches)
11/4
b
11/2
2
21/2
3
4
No limit
No limit
No limit
No limit
10
No limit
No limit
20
270
No limit
No limit
No limit
No limit
No limit
40
72
160
No limit
No limit
No limit
No limit
60
31
75
270
No limit
No limit
No limit
80
16
41
150
380
No limit
No limit
100
10c
25
97
250
No limit
No limit
150
Not permitted
10c
44
110
370
No limit
200
Not permitted
Not permitted
20
60
210
No limit
250
Not permitted
Not permitted
10
36
132
No limit
c
300
Not permitted
Not permitted
10
22
88
380
400
Not permitted
Not permitted
Not permitted
10c
44
210
500
Not permitted
Not permitted
Not permitted
Not permitted
24
130
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
a. Developed length plus an appropriate allowance for entrance losses and friction due to fittings, changes in direction and diameter. Suggested allowances
shall be obtained from NBS Monograph 31 or other approved sources. An allowance of 50 percent of the developed length shall be assumed if a more
precise value is not available.
b. Actual values greater than 500 feet.
c. Less than 10 feet.
9-4
2021 INTERNATIONAL PLUMBING CODE®
VENTS
SECTION 909
FIXTURE VENTS
TABLE 911.3
COMMON VENT SIZES
909.1 Distance of trap from vent. Each fixture trap shall
have a protecting vent located so that the slope and the developed length in the fixture drain from the trap weir to the vent
fitting are within the requirements set forth in Table 909.1.
Exception: The developed length of the fixture drain
from the trap weir to the vent fitting for self-siphoning
fixtures, such as water closets, shall not be limited.
TABLE 909.1
MAXIMUM DISTANCE OF FIXTURE TRAP FROM VENT
SIZE OF TRAP (inches) SLOPE (inch per foot)
DISTANCE FROM
TRAP (feet)
11/4
1
5
11/2
1
6
2
1
8
3
1
12
4
1
16
/4
/4
/4
/8
/8
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 inch per foot = 83.3 mm/m.
909.2 Venting of fixture drains. The total fall in a fixture
drain due to pipe slope shall not exceed the diameter of the
fixture drain, nor shall the vent connection to a fixture drain,
except for water closets, be below the weir of the trap.
909.3 Crown vent. A vent shall not be installed within two
pipe diameters of the trap weir.
SECTION 910
INDIVIDUAL VENT
910.1 Individual vent permitted. Each trap and trapped
fixture is permitted to be provided with an individual vent.
The individual vent shall connect to the fixture drain of the
trap or trapped fixture being vented.
SECTION 911
COMMON VENT
911.1 Individual vent as common vent. An individual vent
is permitted to vent two traps or trapped fixtures as a
common vent. The traps or trapped fixtures being common
vented shall be located on the same floor level.
911.2 Connection at the same level. Where the fixture
drains being common vented connect at the same level, the
vent connection shall be at the interconnection of the fixture
drains or downstream of the interconnection.
911.3 Connection at different levels. Where the fixture
drains connect at different levels, the vent shall connect as a
vertical extension of the vertical drain. The vertical drain
pipe connecting the two fixture drains shall be considered to
be the vent for the lower fixture drain, and shall be sized in
accordance with Table 911.3. The upper fixture shall not be
a water closet.
2021 INTERNATIONAL PLUMBING CODE®
PIPE SIZE
(inches)
MAXIMUM DISCHARGE
FROM UPPER FIXTURE DRAIN
(dfu)
11/2
1
2
4
21/2 to 3
6
For SI: 1 inch = 25.4 mm.
SECTION 912
WET VENTING
912.1 Horizontal wet vent permitted. Any combination of
fixtures within two bathroom groups located on the same
floor level is permitted to be vented by a horizontal wet vent.
The wet vent shall be considered to be the vent for the
fixtures and shall extend from the connection of the dry vent
along the direction of the flow in the drain pipe to the most
downstream fixture drain connection to the horizontal
branch drain. Each wet-vented fixture drain shall connect
independently to the horizontal wet vent. Only the fixtures
within the bathroom groups shall connect to the wet-vented
horizontal branch drain. Any additional fixtures shall
discharge downstream of the horizontal wet vent.
912.1.1 Vertical wet vent permitted. Any combination
of fixtures within two bathroom groups located on the
same floor level is permitted to be vented by a vertical
wet vent. The vertical wet vent shall be considered to be
the vent for the fixtures and shall extend from the connection of the dry vent down to the lowest fixture drain
connection. Each wet-vented fixture shall connect independently to the vertical wet vent. Water closet drains
shall connect at the same elevation. Other fixture drains
shall connect above or at the same elevation as the water
closet fixture drains. The dry-vent connection to the vertical wet vent shall be an individual or common vent
serving one or two fixtures.
912.2 Dry vent connection. The required dry-vent connection for wet-vented systems shall comply with Sections
912.2.1 and 912.2.2.
912.2.1 Horizontal wet vent. The dry-vent connection
for a horizontal wet-vent system shall be an individual
vent or a common vent for any bathroom group fixture,
except an emergency floor drain. Where the dry-vent
connects to a water closet fixture drain, the drain shall
connect horizontally to the horizontal wet-vent system.
Not more than one wet-vented fixture drain shall
discharge upstream of the dry-vented fixture drain
connection.
912.2.2 Vertical wet vent. The dry-vent connection for a
vertical wet-vent system shall be an individual vent or
common vent for the most upstream fixture drain.
9-5
VENTS
912.3 Size. The dry vent serving the wet vent shall be sized
based on the largest required diameter of pipe within the
wet-vent system served by the dry vent. The wet vent shall
be of a size not less than that specified in Table 912.3, based
on the fixture unit discharge to the wet vent.
TABLE 912.3
WET VENT SIZE
WET VENT PIPE SIZE
(inches)
DRAINAGE FIXTURE UNIT LOAD
(dfu)
11/2
1
2
4
21/2
6
3
12
914.2 Vent connection. The circuit vent connection shall be
located between the two most upstream fixture drains. The
vent shall connect to the horizontal branch and shall be
installed in accordance with Section 905. The circuit vent
pipe shall not receive the discharge of any soil or waste.
SECTION 913
WASTE STACK VENT
913.1 Waste stack vent permitted. A waste stack shall be
considered to be a vent for all of the fixtures discharging to
the stack where installed in accordance with the requirements of this section.
913.2 Stack installation. The waste stack shall be vertical,
and both horizontal and vertical offsets shall be prohibited
between the lowest fixture drain connection and the highest
fixture drain connection. Fixture drains shall connect separately to the waste stack. The stack shall not receive the
discharge of water closets or urinals.
913.3 Stack vent. A stack vent shall be provided for the
waste stack. The size of the stack vent shall be not less than
the size of the waste stack. Offsets shall be permitted in the
stack vent, shall be located not less than 6 inches (152 mm)
above the flood level of the highest fixture and shall be in
accordance with Section 905.2. The stack vent shall be
permitted to connect with other stack vents and vent stacks in
accordance with Section 904.5.
913.4 Waste stack size. The waste stack shall be sized based
on the total discharge to the stack and the discharge within a
branch interval in accordance with Table 913.4. The waste
stack shall be the same size throughout its length.
TABLE 913.4
WASTE STACK VENT SIZE
MAXIMUM NUMBER OF
DRAINAGE FIXTURE UNITS (dfu)
Total discharge into
one branch interval
914.1 Circuit vent permitted. Not more than eight fixtures
connected to a horizontal branch drain shall be permitted to
be circuit vented. Each fixture drain shall connect horizontally to the horizontal branch being circuit vented. The
horizontal branch drain shall be classified as a vent from the
most downstream fixture drain connection to the most
upstream fixture drain connection to the horizontal branch.
914.1.1 Multiple circuit-vented branches. Circuitvented horizontal branch drains are permitted to be
connected together. Each group of not more than eight
fixtures shall be considered to be a separate circuit vent
and shall conform to the requirements of this section.
For SI: 1 inch = 25.4 mm.
STACK SIZE
(inches)
SECTION 914
CIRCUIT VENTING
Total discharge
for stack
11/2
1
2
2
2
4
21/2
No limit
8
3
No limit
24
4
No limit
50
5
No limit
75
6
No limit
100
914.3 Slope and size of horizontal branch. The slope of the
vent section of the horizontal branch drain shall be not
greater than one unit vertical in 12 units horizontal (8.3percent slope). The entire length of the vent section of the
horizontal branch drain shall be sized for the total drainage
discharge to the branch.
914.3.1 Size of multiple circuit vent. Each separate
circuit-vented horizontal branch that is interconnected
shall be sized independently in accordance with Section
914.3. The downstream circuit-vented horizontal branch
shall be sized for the total discharge into the branch,
including the upstream branches and the fixtures within
the branch.
914.4 Relief vent. A relief vent shall be provided for circuitvented horizontal branches receiving the discharge of four or
more water closets and connecting to a drainage stack that
receives the discharge of soil or waste from upper horizontal
branches.
914.4.1 Connection and installation. The relief vent
shall connect to the horizontal branch drain between the
stack and the most downstream fixture drain of the circuit
vent. The relief vent shall be installed in accordance with
Section 905.
914.4.2 Fixture drain or branch. The relief vent is
permitted to be a fixture drain or fixture branch for
fixtures located within the same branch interval as the
circuit-vented horizontal branch. The maximum
discharge to a relief vent shall be four fixture units.
914.5 Additional fixtures. Fixtures, other than the circuitvented fixtures, are permitted to discharge to the horizontal
branch drain. Such fixtures shall be located on the same
floor as the circuit-vented fixtures and shall be either individually or common vented.
For SI: 1 inch = 25.4 mm.
9-6
2021 INTERNATIONAL PLUMBING CODE®
VENTS
SECTION 915
COMBINATION WASTE AND VENT SYSTEM
915.1 Type of fixtures. A combination waste and vent
system shall not serve fixtures other than floor drains, sinks,
lavatories and drinking fountains. Combination waste and
vent systems shall not receive the discharge from a clinical
sink.
915.2 Installation. The only vertical pipe of a combination
waste and vent system shall be the connection between the
fixture drain and the horizontal combination waste and vent
pipe. The vertical distance shall not exceed 8 feet (2438
mm).
915.2.1 Slope. The slope of a horizontal combination
waste and vent pipe shall not exceed one-half unit vertical
in 12 units horizontal (4-percent slope) and shall be not
less than that indicated in Table 704.1.
915.2.2 Size and length. The size of a combination waste
and vent pipe shall be not less than that indicated in Table
915.2.2. The horizontal length of a combination waste
and vent system shall be unlimited.
TABLE 915.2.2
SIZE OF COMBINATION WASTE AND VENT PIPE
DIAMETER PIPE
(inches)
MAXIMUM NUMBER OF
DRAINAGE FIXTURE UNITS (dfu)
Connecting to a
Connecting to a building
horizontal branch or stack drain or building subdrain
2
3
4
21/2
6
26
3
12
31
4
20
50
5
160
250
6
360
575
For SI: 1 inch = 25.4 mm.
915.2.3 Connection. The combination waste and vent
system shall be provided with a dry vent connected at any
point within the system or the system shall connect to a
horizontal drain that serves vented fixtures located on the
same floor. Combination waste and vent systems connecting to building drains receiving only the discharge from
one or more stacks shall be provided with a dry vent. The
vent connection to the combination waste and vent pipe
shall extend vertically to a point not less than 6 inches
(152 mm) above the flood level rim of the highest fixture
being vented before offsetting horizontally.
915.2.4 Vent size. The vent shall be sized for the total
drainage fixture unit load in accordance with Section
906.2.
2021 INTERNATIONAL PLUMBING CODE®
915.2.5 Fixture branch or drain. The fixture branch or
fixture drain shall connect to the combination waste and
vent within a distance specified in Table 909.1. The
combination waste and vent pipe shall be considered to be
the vent for the fixture.
SECTION 916
ISLAND FIXTURE VENTING
916.1 Limitation. Island fixture venting shall not be permitted for fixtures other than sinks and lavatories. Residential
kitchen sinks with a dishwasher waste connection, a food
waste disposer, or both, in combination with the kitchen sink
waste, shall be permitted to be vented in accordance with
this section.
916.2 Vent connection. The island fixture vent shall connect
to the fixture drain as required for an individual or common
vent. The vent shall rise vertically to above the drainage
outlet of the fixture being vented before offsetting horizontally or vertically downward. The vent or branch vent for
multiple island fixture vents shall extend to a point not less
than 6 inches (152 mm) above the highest island fixture
being vented before connecting to the outside vent terminal.
916.3 Vent installation below the fixture flood level rim.
The vent located below the flood level rim of the fixture
being vented shall be installed as required for drainage
piping in accordance with Chapter 7, except for sizing. The
vent shall be sized in accordance with Section 906.2. The
lowest point of the island fixture vent shall connect full size
to the drainage system. The connection shall be to a vertical
drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit
rodding of all vent piping located below the flood level rim
of the fixtures. Rodding in both directions shall be permitted
through a cleanout.
SECTION 917
SINGLE-STACK VENT SYSTEM
917.1 Single-stack vent system permitted. A drainage
stack shall serve as a single-stack vent system where sized
and installed in accordance with Sections 917.2 through
917.9. The drainage stack and branch piping shall be the
vents for the drainage system. The drainage stack shall have
a stack vent.
917.2 Stack size. Drainage stacks shall be sized in accordance with Table 917.2. Stacks shall be uniformly sized
based on the total connected drainage fixture unit load. The
stack vent shall be the same size as the drainage stack. A 3inch (76 mm) stack shall serve not more than two water
closets.
9-7
VENTS
TABLE 917.2
SINGLE STACK SIZE
MAXIMUM CONNECTED DRAINAGE FIXTURE UNITS
STACK SIZE
(inches)
Stacks less than
75 feet in height
3
24
4
5
Stacks 75 feet to
Stacks 160 feet and
less than 160
greater in height
feet in height
NP
NP
225
24
NP
480
225
24
6
1,015
480
225
8
2,320
1,015
480
10
4,500
2,320
1,015
12
8,100
4,500
2,320
15
13,600
8,100
4,500
NP = Not permitted.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
917.3 Branch size. Horizontal branches connecting to a
single-stack vent system shall be sized in accordance with
Table 710.1(2). Not more than one water closet shall
discharge into a 3-inch (76 mm) horizontal branch at a point
within a developed length of 18 inches (457 mm) measured
horizontally from the stack.
Where a water closet is within 18 inches (457 mm)
measured horizontally from the stack and not more than one
fixture with a drain size of not more than 11/2 inches (38 mm)
connects to a 3-inch (76 mm) horizontal branch, the branch
drain connection to the stack shall be made with a sanitary tee.
917.4 Length of horizontal branches. The length of horizontal branches shall conform to the requirements of
Sections 917.4.1 through 917.4.3.
917.4.1 Water closet connection. Water closet connections shall be not greater than 4 feet (1219 mm) in
developed length measured horizontally from the stack.
Exception: Where the connection is made with a sanitary tee, the maximum developed length shall be 8 feet
(2438 mm).
917.4.2 Fixture connections. Fixtures other than water
closets shall be located not greater than 12 feet (3657
mm) in developed length, measured horizontally from the
stack.
917.4.3 Vertical piping in branch. The length of vertical
piping in a fixture drain connecting to a horizontal branch
shall not be considered in computing the fixture’s
distance in developed length measured horizontally from
the stack.
917.5 Minimum vertical piping size from fixture. The
vertical portion of piping in a fixture drain to a horizontal
branch shall be 2 inches (51 mm). The minimum size of the
vertical portion of piping for a water-supplied urinal or
standpipe shall be 3 inches (76 mm). The maximum vertical
drop shall be 4 feet (1219 mm). Fixture drains that are not
increased in size, or have a vertical drop in excess of 4 feet
(1219 mm), shall be individually vented.
917.6 Additional venting required. Additional venting
shall be provided where more than one water closet
9-8
discharges to a horizontal branch and where the distance
from a fixture trap to the stack exceeds the limits in Section
917.4. Where additional venting is required, the fixture(s)
shall be vented by individual vents, common vents, wet
vents, circuit vents, or a combination waste and vent pipe.
The dry vent extensions for the additional venting shall
connect to a branch vent, vent stack, stack vent, air admittance valve, or shall terminate outdoors.
917.7 Stack offsets. Where fixture drains are not connected
below a horizontal offset in a stack, a horizontal offset shall
not be required to be vented. Where horizontal branches or
fixture drains are connected below a horizontal offset in a
stack, the offset shall be vented in accordance with Section
907. Fixture connections shall not be made to a stack within
2 feet (610 mm) above or below a horizontal offset.
917.8 Prohibited lower connections. Stacks greater than 2
branch intervals in height shall not receive the discharge of
horizontal branches on the lower two floors. There shall not
be connections to the stack between the lower two floors and
a distance of not less than 10 pipe diameters downstream
from the base of the single stack vented system.
917.9 Sizing building drains and sewers. The building
drain and building sewer receiving the discharge of a single
stack vent system shall be sized in accordance with Table
710.1(1).
SECTION 918
AIR ADMITTANCE VALVES
918.1 General. Vent systems utilizing air admittance valves
shall comply with this section. Stack-type air admittance
valves shall conform to ASSE 1050. Individual and branchtype air admittance valves shall conform to ASSE 1051.
918.2 Installation. The valves shall be installed in accordance with the requirements of this section and the
manufacturer’s instructions. Air admittance valves shall be
installed after the DWV testing required by Section 312.2 or
312.3 has been performed.
918.3 Where permitted. Individual, branch and circuit
vents shall be permitted to terminate with a connection to an
individual or branch-type air admittance valve in accordance
with Section 918.3.1. Stack vents and vent stacks shall be
permitted to terminate to stack-type air admittance valves in
accordance with Section 918.3.2.
918.3.1 Horizontal branches. Individual and branchtype air admittance valves shall vent only fixtures that are
on the same floor level and connect to a horizontal
branch drain. Where the horizontal branch is located
more than four branch intervals from the top of the stack,
the horizontal branch shall be provided with a relief vent
that shall connect to a vent stack or stack vent, or extend
outdoors to the open air. The relief vent shall connect to
the horizontal branch drain between the stack and the
most downstream fixture drain connected to the horizontal branch drain. The relief vent shall be sized in
accordance with Section 906.2 and installed in accordance with Section 905. The relief vent shall be permitted
to serve as the vent for other fixtures.
2021 INTERNATIONAL PLUMBING CODE®
VENTS
919.2 Individual branch fixture and individual fixture
header vents. The maximum developed length of individual
fixture vents to vent branches and vent headers shall be
determined in accordance with Table 919.2 for the minimum
pipe diameters at the indicated vent airflow rates.
918.3.2 Stack. Stack-type air admittance valves shall be
prohibited from serving as the vent terminal for vent
stacks or stack vents that serve drainage stacks having
more than six branch intervals.
918.4 Location. Individual and branch-type air admittance
valves shall be located not less than 4 inches (102 mm)
above the horizontal branch drain or fixture drain being
vented. Stack-type air admittance valves shall be located not
less than 6 inches (152 mm) above the flood level rim of the
highest fixture being vented. The air admittance valve shall
be located within the maximum developed length permitted
for the vent. The air admittance valve shall be installed not
less than 6 inches (152 mm) above insulation materials.
The individual vent airflow rate shall be determined in
accordance with the following:
Qh,b = Nn,b Q
(Equation 9-1)
For SI: Qh,b = Nn,b Q (0.4719 L/s)
where:
Nn,b= Number of fixtures per header (or vent branch) ÷ total
number of fixtures connected to vent stack.
Qh,b= Vent branch or vent header airflow rate (cfm).
Q = Total vent stack airflow rate (cfm).
918.5 Access and ventilation. Access shall be provided to
all air admittance valves. Such valves shall be installed in a
location that allows air to enter the valve.
Q (gpm) = 27.8 rs 2/3 (1 – rs) D 8/3
918.6 Size. The air admittance valve shall be rated in accordance with the standard for the size of the vent to which the
valve is connected.
Q (cfm) = 0.134 Q (gpm)
where:
D = Drainage stack diameter (inches).
Qw = Design discharge load (gpm).
918.7 Vent required. Within each plumbing system, not
less than one stack vent or vent stack shall extend outdoors to
the open air.
918.8 Prohibited installations. Air admittance valves shall
not be installed in nonneutralized special waste systems as
described in Chapter 8 except where such valves are in
compliance with ASSE 1049, are constructed of materials
approved in accordance with Section 702.5, and are tested
for chemical resistance in accordance with ASTM F1412.
Air admittance valves shall not be located in spaces utilized
as supply or return air plenums. Air admittance valves shall
not be used to vent sumps or tanks except where the vent
system for the sump or tank has been designed by an engineer. Air admittance valves shall not be installed on outdoor
vent terminals for the sole purpose of reducing clearances to
gravity air intakes or mechanical air intakes.
rs = Wastewater flow area to total area.
Qw
= ----------------------83
27.8 D
Individual vent airflow rates are obtained by equally
distributing Qh,b into one-half the total number of fixtures on
the branch or header for more than two fixtures; for an odd
number of total fixtures, decrease by one; for one fixture,
apply the full value of Qh,b.
Individual vent developed length shall be increased by 20
percent of the distance from the vent stack to the fixture vent
connection on the vent branch or header.
SECTION 919
ENGINEERED VENT SYSTEMS
SECTION 920
COMPUTERIZED VENT DESIGN
919.1 General. Engineered vent systems shall comply with
this section and the design, submittal, approval, inspection
and testing requirements of Section 316.
920.1 Design of vent system. The sizing, design and layout
of the vent system shall be permitted to be determined by
approved computer program design methods.
TABLE 919.2
MINIMUM DIAMETER AND MAXIMUM LENGTH OF INDIVIDUAL
BRANCH FIXTURE VENTS AND INDIVIDUAL FIXTURE HEADER VENTS FOR SMOOTH PIPES
DIAMETER
OF VENT PIPE
(inches)
INDIVIDUAL VENT AIRFLOW RATE (cubic feet per minute)
Maximum developed length of vent (feet)
1
2
3
1
95
25
13
8
5
4
3
2
1
1
1
1
1
1
1
1
1
1
1
1
3
/4
100
88
47
30
20
15
10
9
7
6
5
4
3
3
3
2
2
2
2
1
1
—
—
100
94
65
48
37
29
24
20
17
14
12
11
9
8
7
7
6
6
11/4
—
—
—
—
—
—
—
100
87
73
62
53
46
40
36
32
29
26
23
21
11/2
—
—
—
—
—
—
—
—
—
—
—
100
96
84
75
65
60
54
49
45
2
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
100
/2
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
For SI: 1 inch = 25.4 mm, 1 cubic foot per minute = 0.4719 L/s, 1 foot = 304.8 mm.
2021 INTERNATIONAL PLUMBING CODE®
9-9
VENTS
920.2 System capacity. The vent system shall be based on
the air capacity requirements of the drainage system under a
peak load condition.
9-10
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 10
TRAPS, INTERCEPTORS AND SEPARATORS
User note:
About this chapter: Chapter 10 regulates the design of fixture traps, methods for preventing evaporation of trap seals in traps and the
required locations for interceptors and separators. The trap seal of a trap is an essential feature of a drainage system to prevent odors from
the drainage piping from entering the building. The discharge of various processes, such as cooking and laundry, creates the need for
equipment to retain detrimental greases and solids from entering the drainage systems.
SECTION 1001
GENERAL
1001.1 Scope. This chapter shall govern the material and
installation of traps, interceptors and separators.
SECTION 1002
TRAP REQUIREMENTS
1002.1 Fixture traps. Each plumbing fixture shall be separately trapped by a liquid-seal trap, except as otherwise
permitted by this code. The vertical distance from the fixture
outlet to the trap weir shall not exceed 24 inches (610 mm),
and the horizontal distance shall not exceed 30 inches (610
mm) measured from the centerline of the fixture outlet to the
centerline of the inlet of the trap. The height of a clothes
washer standpipe above a trap shall conform to Section
802.4.3. A fixture shall not be double trapped.
Exceptions:

1. This section shall not apply to fixtures with integral traps.
2. A combination plumbing fixture is permitted to be
installed on one trap, provided that one compartment is not more than 6 inches (152 mm) deeper
than the other compartment and the waste outlets
are not more than 30 inches (762 mm) apart.
3. Floor drains in multilevel parking structures that
discharge to a building storm sewer shall not be
required to be individually trapped. Where floor
drains in multilevel parking structures are required
to discharge to a combined building sewer system,
the floor drains shall not be required to be individually trapped provided that they are connected to a
main trap in accordance with Section 1103.1.
1002.2 Design of traps. Fixture traps shall be self-scouring.
Fixture traps shall not have interior partitions, except where
such traps are integral with the fixture or where such traps
are constructed of an approved material that is resistant to
corrosion and degradation. Slip joints shall be made with an
approved elastomeric gasket and shall be installed only on
the trap inlet, trap outlet and within the trap seal.
1002.3 Prohibited traps. The following types of traps are
prohibited:
1. Traps that depend on moving parts to maintain the
seal.
2021 INTERNATIONAL PLUMBING CODE®
2. Bell traps.
3. Crown-vented traps.
4. Traps not integral with a fixture and that depend on
interior partitions for the seal, except those traps
constructed of an approved material that is resistant
to corrosion and degradation.
5. “S” traps.
6. Drum traps.
Exception: Drum traps used as solids interceptors
and drum traps serving chemical waste systems shall
not be prohibited.
1002.4 Trap seals. Each fixture trap shall have a liquid seal
of not less than 2 inches (51 mm) and not more than 4 inches
(102 mm), or deeper for special designs relating to accessible fixtures.
1002.4.1 Trap seal protection. Trap seals of emergency
floor drain traps and trap seals subject to evaporation
shall be protected by one of the methods in Sections
1002.4.1.1 through 1002.4.1.5.
1002.4.1.1 Potable water-supplied trap seal primer
valve. A potable water-supplied trap seal primer valve
shall supply water to the trap. Water-supplied trap seal
primer valves shall conform to ASSE 1018. The
discharge pipe from the trap seal primer valve shall
connect to the trap above the trap seal on the inlet side
of the trap.
1002.4.1.2 Reclaimed or graywater-supplied trap
seal primer valve. A reclaimed or graywater-supplied
trap seal primer valve shall supply water to the trap.
Water-supplied trap seal primer valves shall conform
to ASSE 1018. The quality of reclaimed or graywater
supplied to trap seal primer valves shall be in accordance with the requirements of the manufacturer of the
trap seal primer valve. The discharge pipe from the
trap seal primer valve shall connect to the trap above
the trap seal, on the inlet side of the trap.
1002.4.1.3 Wastewater-supplied trap primer
device. A wastewater-supplied trap primer device
shall supply water to the trap. Wastewater-supplied
trap primer devices shall conform to ASSE 1044. The
discharge pipe from the trap seal primer device shall
connect to the trap above the trap seal on the inlet side
of the trap.
10-1
TRAPS, INTERCEPTORS AND SEPARATORS
1002.4.1.4 Barrier-type trap seal protection device.
A barrier-type trap seal protection device shall protect
the floor drain trap seal from evaporation. Barrier-type
floor drain trap seal protection devices shall conform
to ASSE 1072. The devices shall be installed in accordance with the manufacturer’s instructions.
1002.4.1.5 Fixture drain connection for trap priming. A fixture drain from a lavatory or hand sink shall
serve as a method of providing trap seal protection for
an emergency floor drain, a trench drain, or a floor
sink where such fixtures are located in the same room.
A fixture drain from a drinking fountain shall serve as
a method of providing trap seal protection for an emergency floor drain, a trench drain, or a floor sink where
such fixtures are in the same room or in a room adjacent to the room having the drinking fountain. The
fixture drain shall not be routed on or above the
surface of the floor and shall connect to the floor drain,
trench drain, or floor sink at a point that is below the
flood level rim and above the inlet to the trap of the
receiving fixture.
1002.5 Size of fixture traps. Fixture trap size shall be sufficient to drain the fixture rapidly and not less than the size
indicated in Table 709.1. A trap shall not be larger than the
drainage pipe into which the trap discharges.
1002.6 Building traps. Building (house) traps shall be
prohibited.
1002.7 Trap setting and protection. Traps shall be set level
with respect to the trap seal and, where necessary, shall be
protected from freezing.
1002.8 Recess for trap connection. A recess provided for
connection of the underground trap, such as one serving a
bathtub in slab-type construction, shall have sides and a
bottom of corrosion-resistant, insect- and verminproof
construction.
1002.9 Acid-resisting traps. Where a vitrified clay or other
brittleware, acid-resisting trap is installed underground, such
trap shall be embedded in concrete extending 6 inches (152
mm) beyond the bottom and sides of the trap.
1002.10 Plumbing in mental health centers. In mental
health centers, pipes and traps shall not be exposed.
SECTION 1003
INTERCEPTORS AND SEPARATORS
1003.1 Where required. Interceptors and separators shall be
provided to prevent the discharge of oil, grease, sand and
other substances harmful or hazardous to the public sewer,
the private sewage system or the sewage treatment plant or
processes.
1003.2 Approval. The size, type and location of each interceptor and of each separator shall be designed and installed
in accordance with the manufacturer’s instructions and the
requirements of this section based on the anticipated conditions of use. Wastes that do not require treatment or
separation shall not be discharged into any interceptor or
separator.
10-2
1003.3 Grease interceptors. Grease interceptors shall
comply with the requirements of Sections 1003.3.1 through
1003.3.8.
1003.3.1 Grease interceptors and automatic grease
removal devices required. A grease interceptor or automatic grease removal device shall be required to receive
the drainage from fixtures and equipment with greaseladen waste located in food preparation areas, such as in
restaurants, hotel kitchens, hospitals, school kitchens,
bars, factory cafeterias and clubs. Fixtures and equipment
shall include pot sinks, prerinse sinks; soup kettles or
similar devices; wok stations; floor drains or sinks into
which kettles are drained; automatic hood wash units and
dishwashers without prerinse sinks. Grease interceptors
and automatic grease removal devices shall receive waste
only from fixtures and equipment that allow fats, oils or
grease to be discharged. Where lack of space or other
constraints prevent the installation or replacement of a
grease interceptor, one or more grease interceptors shall
be permitted to be installed on or above the floor and
upstream of an existing grease interceptor.
1003.3.2 Food waste disposers restriction. A food waste
disposer shall not discharge to a grease interceptor.
1003.3.3 Additives to grease interceptors. Dispensing
systems that dispense interceptor performance additives
to grease interceptors shall not be installed except where
such systems dispense microbes for the enhancement of
aerobic bioremediation of grease and other organic material, or for inhibiting growth of pathogenic organisms by
anaerobic methods. Such microbial dispensing systems
shall be installed only where the grease interceptor manufacturer’s instructions allow such systems and the
systems conform to ASME A112.14.6. Systems that
discharge emulsifiers, chemicals or enzymes to grease
interceptors shall be prohibited.
1003.3.4 Grease interceptors and automatic grease
removal devices not required. A grease interceptor or an
automatic grease removal device shall not be required for
individual dwelling units or any private living quarters.
1003.3.5 Hydromechanical grease interceptors, fats,
oils and greases disposal systems and automatic grease
removal devices. Hydromechanical grease interceptors;
fats, oils, and greases disposal systems and automatic
grease removal devices shall be sized in accordance with
ASME A112.14.3, ASME A112.14.4, ASME A112.14.6,
CSA B481.3 or PDI G101. Hydromechanical grease
interceptors; fats, oils, and greases disposal systems and
automatic grease removal devices shall be designed and
tested in accordance with ASME A112.14.3, ASME
A112.14.4, CSA B481.1, PDI G101 or PDI G102. Hydromechanical grease interceptors; fats, oils, and greases
disposal systems and automatic grease removal devices
shall be installed in accordance with the manufacturer’s
instructions. Where manufacturer’s instructions are not
provided, hydromechanical grease interceptors; fats, oils,
and greases disposal systems and automatic grease
removal devices shall be installed in compliance with
2021 INTERNATIONAL PLUMBING CODE®
TRAPS, INTERCEPTORS AND SEPARATORS
ASME A112.14.3, ASME A112.14.4, ASME A112.14.6,
CSA B481.3 or PDI G101.
1003.3.5.1 Grease interceptor capacity. Grease interceptors shall have the grease retention capacity
indicated in Table 1003.3.5.1 for the flow-through
rates indicated.
TABLE 1003.3.5.1
CAPACITY OF GREASE INTERCEPTORSa
TOTAL FLOW-THROUGH RATING
(gpm)
GREASE RETENTION CAPACITY
(pounds)
4
8
6
12
7
14
9
18
10
20
12
24
14
28
15
30
18
36
20
40
25
50
35
70
50
100
75
150
100
200
For SI: 1 gallon per minute = 3.785 L/m, 1 pound = 0.454 kg.
a. For total flow-through ratings greater than 100 (gpm), double the flowthrough rating to determine the grease retention capacity (pounds).
1003.3.5.2 Rate of flow controls. Grease interceptors
shall be equipped with devices to control the rate of
water flow so that the water flow does not exceed the
rated flow. The flow-control device shall be vented
and terminate not less than 6 inches (152 mm) above
the flood rim level or be installed in accordance with
the manufacturer’s instructions.
1003.3.6 Automatic grease removal devices. Where
automatic grease removal devices are installed, such
devices shall be located downstream of each fixture or
multiple fixtures in accordance with the manufacturer’s
instructions. The automatic grease removal device shall
be sized to pretreat the measured or calculated flows for
all connected fixtures or equipment. Ready access shall
be provided for inspection and maintenance.
1003.3.7 Gravity grease interceptors and gravity
grease interceptors with fats, oils, and greases disposal
systems. The required capacity of gravity grease interceptors and gravity grease interceptors with fats, oils, and
greases disposal systems shall be determined by multiplying the peak drain flow into the interceptor in gallons per
minute by a retention time of 30 minutes. Gravity grease
interceptors shall be designed and tested in accordance
with IAPMO/ANSI Z1001. Gravity grease interceptors
with fats, oils, and greases disposal systems shall be
designed and tested in accordance with ASME A112.14.6
2021 INTERNATIONAL PLUMBING CODE®
and IAPMO/ANSI Z1001. Gravity grease interceptors
and gravity grease interceptors with fats, oils, and greases
disposal systems shall be installed in accordance with
manufacturer’s instructions. Where manufacturer’s
instructions are not provided, gravity grease interceptors
and gravity grease interceptors with fats, oils, and greases
disposal systems shall be installed in compliance with
ASME A112.14.6 and IAPMO/ANSI Z1001.
1003.3.8 Direct connection. The discharge piping from a
grease interceptor shall be directly connected to the sanitary drainage system.
1003.4 Oil separators required. At repair garages where
floor or trench drains are provided, car washing facilities,
factories where oily and flammable liquid wastes are
produced and hydraulic elevator pits, oil separators shall be
installed into which oil-bearing, grease-bearing or flammable wastes shall be discharged before emptying into the
building drainage system or other point of disposal.
Exception: An oil separator is not required in hydraulic
elevator pits where an approved alarm system is installed.
Such alarm systems shall not terminate the operation of
pumps utilized to maintain emergency operation of the
elevator by fire fighters.
1003.4.1 Separation of liquids. A mixture of treated or
untreated light and heavy liquids with various specific
gravities shall be separated in an approved receptacle.
1003.4.2 Oil separator design. Oil separators shall be
listed and labeled, or designed in accordance with
Sections 1003.4.2.1 and 1003.4.2.2.
1003.4.2.1 General design requirements. Oil separators shall have a depth of not less than 2 feet (610 mm)
below the invert of the discharge drain. The outlet
opening of the separator shall have not less than an 18inch (457 mm) water seal.
1003.4.2.2 Garages and service stations. Where
automobiles are serviced, greased, repaired or washed
or where gasoline is dispensed, oil separators shall
have a capacity of not less than 6 cubic feet (0.168 m3)
for the first 100 square feet (9.3 m2) of area to be
drained, plus 1 cubic foot (0.028 m3) for each additional 100 square feet (9.3 m2) of area to be drained
into the separator. Parking garages in which servicing,
repairing or washing is not conducted, and in which
gasoline is not dispensed, shall not require a separator.
Areas of commercial garages utilized only for storage
of automobiles are not required to be drained through a
separator.
1003.5 Sand interceptors in commercial establishments.
Sand and similar interceptors for heavy solids shall be
designed and located so as to be provided with ready access
for cleaning, and shall have a water seal of not less than 6
inches (152 mm).
1003.6 Clothes washer discharge interceptor. Clothes
washers shall discharge through an interceptor that is
provided with a wire basket or similar device, removable for
cleaning, that prevents passage into the drainage system of
solids 1/2 inch (12.7 mm) or larger in size, string, rags,
10-3
TRAPS, INTERCEPTORS AND SEPARATORS
buttons or other materials detrimental to the public sewage
system.
Exceptions:
1. Clothes washers in individual dwelling units shall
not be required to discharge through an
interceptor.
2. A single clothes washer designed for use in individual dwelling units and installed in a location
other than an individual dwelling unit shall not be
required to discharge through an interceptor.
1003.7 Bottling establishments. Bottling plants shall
discharge process wastes into an interceptor that will provide
for the separation of broken glass or other solids before
discharging waste into the drainage system.
1003.8 Slaughterhouses. Slaughtering room and dressing
room drains shall be equipped with approved separators. The
separator shall prevent the discharge into the drainage
system of feathers, entrails and other materials that cause
clogging.
1003.9 Venting of interceptors and separators. Interceptors and separators shall be designed so as not to become air
bound. Interceptors and separators shall be vented in accordance with one of the methods in Chapter 9.
1003.10 Access and maintenance of interceptors and
separators. Access shall be provided to each interceptor and
separator for service and maintenance. Interceptors and
separators shall be maintained by periodic removal of accumulated grease, scum, oil, or other floating substances and
solids deposited in the interceptor or separator.
SECTION 1004
MATERIALS, JOINTS AND CONNECTIONS
1004.1 General. The materials and methods utilized for the
construction and installation of traps, interceptors and separators shall comply with this chapter and the applicable
provisions of Chapters 4 and 7. The fittings shall not have
ledges, shoulders or reductions capable of retarding or
obstructing flow of the piping.
10-4
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 11
STORM DRAINAGE
User note:
About this chapter: Rainfall onto buildings must be removed and directed to a location that can accommodate storm water. Chapter 11
specifies the design rainfall event for the geographic area and provides sizing methods for piping and gutter systems to convey the storm
water away from the building. Included in this chapter are regulations for piping materials and subsoil drainage systems.
SECTION 1101
GENERAL
SECTION 1102
MATERIALS
1101.1 Scope. The provisions of this chapter shall govern
the materials, design, construction and installation of storm
drainage.
1102.1 General. The materials and methods utilized for the
construction and installation of storm drainage systems shall
comply with this section and the applicable provisions of
Chapter 7.
1101.2 Disposal. Rainwater from roofs and storm water
from paved areas, yards, courts and courtyards shall drain to
an approved place of disposal. For one- and two-family
dwellings, and where approved, storm water is permitted to
discharge onto flat areas, such as streets or lawns, provided
that the storm water flows away from the building.
1101.3 Prohibited drainage. Storm water shall not be
drained into sewers intended for sewage only.
1102.2 Inside storm drainage conductors. Inside storm
drainage conductors installed above ground shall conform to
one of the standards listed in Table 702.1.
1102.3 Underground building storm drain pipe. Underground building storm drain pipe shall conform to one of the
standards listed in Table 702.2.
1101.4 Tests. The conductors and the building storm drain
shall be tested in accordance with Section 312.
1102.4 Building storm sewer pipe. Building storm sewer
pipe shall conform to one of the standards listed in Table
1102.4.
1101.5 Change in size. The size of a drainage pipe shall not
be reduced in the direction of flow.
TABLE 1102.4
BUILDING STORM SEWER PIPE
1101.6 Fittings and connections. Connections and changes
in direction of the storm drainage system shall be made with
approved drainage-type fittings in accordance with Table
706.3. The fittings shall not obstruct or retard flow in the
system.
[BS] 1101.7 Roof design. Roofs shall be designed for the
maximum possible depth of water that will pond thereon as
determined by the relative levels of roof deck and overflow
weirs, scuppers, edges or serviceable drains in combination
with the deflected structural elements. In determining the
maximum possible depth of water, all primary roof drainage
means shall be assumed to be blocked. The maximum possible depth of water on the roof shall include the height of the
water required above the inlet of the secondary roof drainage
means to achieve the required flow rate of the secondary
drainage means to accommodate the design rainfall rate as
required by Section 1106.
1101.8 Cleanouts required. Cleanouts shall be installed in
the storm drainage system and shall comply with the provisions of this code for sanitary drainage pipe cleanouts.
Exception: Subsurface drainage system.
1101.9 Backwater valves. Storm drainage systems shall be
provided with backwater valves as required for sanitary
drainage systems in accordance with Section 714.
2021 INTERNATIONAL PLUMBING CODE®
MATERIAL
STANDARD
Acrylonitrile butadiene styrene
(ABS) plastic pipe in IPS diameASTM D2661; ASTM F628;
ters, including Schedule 40, DR
ASTM F1488; CSA B181.1;
22 (PS 200) and DR 24 (PS 140);
CSA B182.1
with a solid, cellular core or
composite wall
Cast-iron pipe
Concrete pipe
Copper or copper-alloy tubing
(Type K, L, M or DWV)
Polyethylene (PE) plastic pipe
Polypropylene (PP) pipe
Polyvinyl chloride (PVC) plastic
pipe (Type DWV, SDR26,
SDR35, SDR41, PS50 or
PS100) in IPS diameters, including Schedule 40, DR 22 (PS
200) and DR 24 (PS 140); with a
solid, cellular core or composite
wall
ASTM A74; ASTM A888;
CISPI 301
ASTM C14; ASTM C76;
CSA A257.1; CSA A257.2
ASTM B75; ASTM B88;
ASTM B251; ASTM B306
ASTM F667;
ASTM F2306/F2306M;
ASTM F2648/F2648M
ASTM F2881; CSA B182.13
ASTM D2665; ASTM D3034;
ASTM F891; ASTM F1488;
CSA B181.2; CSA B182.2;
CSA B182.4
Stainless steel drainage systems,
ASME A112.3.1
Type 316L
Vitrified clay pipe
ASTM C4; ASTM C700
11-1
STORM DRAINAGE
1102.5 Subsoil drain pipe. Subsoil drains shall be openjointed, horizontally split or perforated pipe conforming to
one of the standards listed in Table 1102.5.
TABLE 1102.5
SUBSOIL DRAIN PIPE
MATERIAL
STANDARD
Cast-iron pipe
ASTM A74; ASTM A888;
CISPI 301
Polyethylene (PE) plastic pipe
ASTM F405; ASTM F667;
CSA B182.1; CSA B182.6;
CSA B182.8
Polyvinyl chloride (PVC) plastic pipe (type sewer pipe,
SDR35, PS25, PS50 or PS100)
ASTM D2729; ASTM D3034;
ASTM F891; CSA B182.2;
CSA B182.4
Stainless steel drainage
systems, Type 316L
ASME A112.3.1
Vitrified clay pipe
ASTM C4; ASTM C700
1102.6 Roof drains. Roof drains shall conform to ASME
A112.3.1 or ASME A112.6.4. Roof drains, other than
siphonic roof drains, shall be tested and rated in accordance
with ASME A112.6.4 or ASPE/IAPMO Z1034.
1102.7 Fittings. Pipe fittings shall be approved for installation with the piping material installed, and shall conform to
the respective pipe standards or one of the standards listed in
Table 1102.7. The fittings shall not have ledges, shoulders or
reductions capable of retarding or obstructing flow in the
piping. Threaded drainage pipe fittings shall be of the
recessed drainage type.
SECTION 1103
TRAPS
1103.1 Main trap. Leaders and storm drains connected to a
combined sewer shall be trapped. Individual storm water
traps shall be installed on the storm water drain branch serving each conductor, or a single trap shall be installed in the
main storm drain just before its connection with the
combined building sewer or the public sewer. Leaders and
storm drains connected to a building storm sewer shall not
be required to be trapped.
1103.2 Material. Storm water traps shall be of the same
material as the piping system to which they are attached.
1103.3 Size. Traps for individual conductors shall be the
same size as the horizontal drain to which they are
connected.
1103.4 Cleanout. A cleanout shall be installed on the building side of the trap and shall be provided with access.
SECTION 1104
CONDUCTORS AND CONNECTIONS
1104.1 Prohibited use. Conductor pipes shall not be used as
soil, waste or vent pipes, and soil, waste or vent pipes shall
not be used as conductors.
11-2
TABLE 1102.7
PIPE FITTINGS
MATERIAL
STANDARD
Acrylonitrile butadiene styrene
(ABS) plastic
ASTM D2661; ASTM D3311;
CSA B181.1
Cast iron
ASME B16.4; ASME B16.12;
ASTM A74; ASTM A888;
CISPI 301
Coextruded composite ABS and
drain DR-PS in PS35, PS50,
ASTM D2751
PS100, PS140, PS200
Coextruded composite ABS
DWV Schedule 40 IPS pipe
(solid or cellular core)
ASTM D2661; ASTM D3311;
ASTM F628
Coextruded composite PVC
DWV Schedule 40 IPS-DR,
PS140, PS200
(solid or cellular core)
ASTM D2665; ASTM D3311;
ASTM F891
Coextruded composite PVC
sewer and drain DR-PS in
PS35, PS50, PS100, PS140,
PS200
ASTM D3034
Copper or copper alloy
ASME B16.15; ASME B16.18;
ASME B16.22;
ASME B16.23;
ASME B16.26;
ASME B16.29
Gray iron and ductile iron
AWWA C110/A21.10
Malleable iron
ASME B16.3
Plastic, general
ASTM F409
Polyethylene (PE) plastic pipe
ASTM F2306/F2306M
Polyvinyl chloride (PVC)
plastic
ASTM D2665; ASTM D3311;
ASTM F1866
Stainless steel drainage
systems, Type 316L
ASME A112.3.1
Steel
ASME B16.9; ASME B16.11;
ASME B16.28
1104.2 Floor drains. Floor drains shall not be connected to a
storm drain.
SECTION 1105
ROOF DRAINS
1105.1 General. Roof drains shall be installed in accordance
with the manufacturer’s instructions. The inside opening for
the roof drain shall not be obstructed by the roofing
membrane material.
1105.2 Roof drain flow rate. The published roof drain flow
rate, based on the head of water above the roof drain, shall be
used to size the storm drainage system in accordance with
Section 1106. The flow rate used for sizing the storm drainage piping shall be based on the maximum anticipated
ponding at the roof drain.
2021 INTERNATIONAL PLUMBING CODE®
STORM DRAINAGE
SECTION 1106
SIZE OF CONDUCTORS,
LEADERS AND STORM DRAINS
TABLE 1106.3
VERTICAL LEADER SIZING
SIZE OF LEADER (inches)
CAPACITY (gpm)
1106.1 General. The size of the vertical conductors and
leaders, building storm drains, building storm sewers and
any horizontal branches of such drains or sewers shall be
based on the 100-year hourly rainfall rate indicated in
Figures 1106.1(1) through 1106.1(5) or on other rainfall
rates determined from approved local weather data.
2
30
2×2
30
11/2 × 21/2
30
1106.2 Size of storm drain piping. Vertical and horizontal
storm drain piping shall be sized based on the flow rate
through the roof drain. The flow rate, as calculated in accordance with Section 1106.2.1, shall be checked against the
roof drain manufacturer’s published flow rate for the specific
roof drain model and size to verify that the selected roof
drain will handle the anticipated flow. The flow rate in storm
drain piping shall not exceed that specified in Table 1106.2.
1
2 /2
54
21/2 × 21/2
54
3
92
2×4
92
1
2 /2 × 3
92
4
192
3 × 41/4
192
31/2 × 4
192
5
360
1106.2.1 Rainfall rate conversion method. The rainfall
rate falling on a roof surface shall be converted to a gallon
per minute (L/m) flow rate in accordance with Equation
11-1.
4×5
360
41/2 × 41/2
360
6
563
GPM = R × A × 0.0104
5×6
563
51/2 × 51/2
563
(Equation 11-1)
where:
R = Rainfall intensity in inches (mm) per hour.
A = Roof area in square feet (m2).
1106.3 Vertical leader sizing. Vertical leaders shall be sized
based on the flow rate from horizontal gutters or the maximum flow rate through roof drains. The flow rate through
vertical leaders shall not exceed that specified in Table
1106.3.
1106.4 Vertical walls. In sizing roof drains and storm drainage piping, one-half of the area of any vertical wall that
diverts rainwater to the roof shall be added to the projected
roof area for inclusion in calculating the required size of
vertical conductors, leaders and horizontal storm drainage
piping.
8
1208
6×8
1208
For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m.
1106.5 Parapet wall scuppers. Where scuppers are used for
primary roof drainage or for secondary (emergency overflow) roof drainage or both, the quantity, size, location and
inlet elevation of the scuppers shall be chosen to prevent the
depth of ponding water on the roof from exceeding the maximum water depth that the roof was designed for as
determined by Section 1611.1 of the International Building
Code. Scupper openings shall be not less than 4 inches (102
mm) in height and have a width that is equal to or greater
than the circumference of a roof drain sized for the same roof
area. The flow through the primary system shall not be
considered when locating and sizing secondary scuppers.
TABLE 1106.2
STORM DRAIN PIPE SIZING
CAPACITY (gpm)
PIPE SIZE (inches)
2
VERTICAL DRAIN
34
SLOPE OF HORIZONTAL DRAIN
1
/16 inch per foot
15
1
/8 inch per foot
22
1
/4 inch per foot
31
1
/2 inch per foot
44
3
87
39
55
79
111
4
180
81
115
163
231
5
311
117
165
234
331
6
538
243
344
487
689
8
1,117
505
714
1,010
1,429
10
2,050
927
1,311
1,855
2,623
12
3,272
1,480
2,093
2,960
4,187
15
5,543
2,508
3,546
5,016
7,093
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
2021 INTERNATIONAL PLUMBING CODE®
11-3
STORM DRAINAGE
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington D.C.
FIGURE 1106.1(1)
100-YEAR, 1-HOUR RAINFALL (INCHES) WESTERN UNITED STATES
11-4
2021 INTERNATIONAL PLUMBING CODE®
STORM DRAINAGE
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington D.C.
FIGURE 1106.1(2)
100-YEAR, 1-HOUR RAINFALL (INCHES) CENTRAL UNITED STATES
2021 INTERNATIONAL PLUMBING CODE®
11-5
STORM DRAINAGE
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington D.C.
FIGURE 1106.1(3)
100-YEAR, 1-HOUR RAINFALL (INCHES) EASTERN UNITED STATES
11-6
2021 INTERNATIONAL PLUMBING CODE®
STORM DRAINAGE
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington D.C.
FIGURE 1106.1(4)
100-YEAR, 1-HOUR RAINFALL (INCHES) ALASKA
2021 INTERNATIONAL PLUMBING CODE®
11-7
11-8
FIGURE 1106.1(5)
100-YEAR, 1-HOUR RAINFALL (INCHES) HAWAII
For SI: 1 inch = 25.4 mm.
Source: National Weather Service, National Oceanic and Atmospheric Administration, Washington D.C.
STORM DRAINAGE
2021 INTERNATIONAL PLUMBING CODE®
STORM DRAINAGE
1108.3 Sizing of secondary drains. Secondary (emergency)
roof drain systems shall be sized in accordance with Section
1106 based on the rainfall rate for which the primary system
is sized. Scuppers shall be sized to prevent the depth of
ponding water from exceeding that for which the roof was
designed as determined by Section 1101.7. Scuppers shall
have an opening dimension of not less than 4 inches (102
mm) in height and have an opening width equal to the
circumference of the roof drain required for the area served.
The flow through the primary system shall not be considered
when sizing the secondary roof drain system.
1106.6 Size of roof gutters. Horizontal gutters shall be sized
based on the flow rate from the roof surface. The flow rate in
horizontal gutters shall not exceed that specified in Table
1106.6.
SECTION 1107
SIPHONIC ROOF DRAINAGE SYSTEMS
1107.1 General. Siphonic roof drains and drainage systems
shall be designed in accordance with ASME A112.6.9 and
ASPE 45.
SECTION 1109
COMBINED SANITARY AND
STORM PUBLIC SEWER
SECTION 1108
SECONDARY (EMERGENCY) ROOF DRAINS
1108.1 Secondary (emergency overflow) drains or scuppers. Where roof drains are required, secondary (emergency
overflow) roof drains or scuppers shall be provided where
the roof perimeter construction extends above the roof in
such a manner that water will be entrapped if the primary
drains allow buildup for any reason. Where primary and
secondary roof drains are manufactured as a single assembly, the inlet and outlet for each drain shall be independent.
1109.1 General. Where the public sewer is a combined
system for both sanitary and storm water, the storm sewer
shall be connected independently to the public sewer.
SECTION 1110
CONTROLLED FLOW ROOF DRAIN SYSTEMS
1110.1 General. The roof of a structure shall be designed for
the storage of water where the storm drainage system is engineered for controlled flow. The controlled flow roof drain
system shall be an engineered system in accordance with this
section and the design, submittal, approval, inspection and
testing requirements of Section 316.1. The controlled flow
1108.2 Separate systems required. Secondary roof drain
systems shall have the end point of discharge separate from
the primary system. Discharge shall be above grade, in a
location that would normally be observed by the building
occupants or maintenance personnel.
TABLE 1106.6
HORIZONTAL GUTTER SIZING
GUTTER DIMENSIONSa (inches)
1
1
SLOPE (inch per foot)
CAPACITY (gpm)
1 /2 × 2 /2
1
/4
26
11/2 × 21/2
1
/2
40
4
1
/8
39
21/4 × 3
1
/4
55
2 /4 × 3
1
/2
87
5
1
/8
74
4 × 2 /2
1
/4
106
3 × 31/2
1
/2
156
6
1
/8
110
3×5
1
/4
157
3×5
1
/2
225
8
1
/16
172
8
1
/8
247
41/2 × 6
1
/4
348
1
4 /2 × 6
1
/2
494
10
1
/16
331
10
1
/8
472
5×8
1
/4
651
4 × 10
1
/2
1055
1
1
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m, 1 inch per foot = 83.3 mm/m.
a. Dimensions are width by depth for rectangular shapes. Single dimensions are diameters of a semicircle.
2021 INTERNATIONAL PLUMBING CODE®
11-9
STORM DRAINAGE
system shall be designed based on the required rainfall rate
in accordance with Section 1106.1.
1113.1.3 Electrical. Electrical service outlets, where
required, shall meet the requirements of NFPA 70.
1110.2 Control devices. The control devices shall be
installed so that the rate of discharge of water per minute
shall not exceed the values for continuous flow as indicated
in Section 1110.1.
1113.1.4 Piping. Discharge piping shall meet the requirements of Section 1102.2, 1102.3 or 1102.4 and shall
include a gate valve and a full flow check valve. Pipe and
fittings shall be the same size as, or larger than, the pump
discharge tapping.
1110.3 Installation. Runoff control shall be by control
devices. Control devices shall be protected by strainers.
1110.4 Minimum number of roof drains. Not less than two
roof drains shall be installed in roof areas 10,000 square feet
(929 m2) or less and not less than four roof drains shall be
installed in roofs over 10,000 square feet (929 m2) in area.
Exception: In one- and two-family dwellings, only a
check valve shall be required, located on the discharge
piping from the pump or ejector.
SECTION 1111
SUBSOIL DRAINS
1111.1 Subsoil drains. Subsoil drains shall be open-jointed,
horizontally split or perforated pipe conforming to one of the
standards listed in Table 1102.5. Such drains shall be not less
than 4 inches (102 mm) in diameter. Where the building is
subject to backwater, the subsoil drain shall be protected by
an accessibly located backwater valve. Subsoil drains shall
discharge to a trapped area drain, sump, dry well or
approved location above ground. The subsoil sump shall not
be required to have either a gastight cover or a vent. The
sump and pumping system shall comply with Section
1113.1.
SECTION 1112
BUILDING SUBDRAINS
1112.1 Building subdrains. Building subdrains located
below the public sewer level shall discharge into a sump or
receiving tank, the contents of which shall be automatically
lifted and discharged into the drainage system as required for
building sumps. The sump and pumping equipment shall
comply with Section 1113.1.
SECTION 1113
SUMPS AND PUMPING SYSTEMS
1113.1 Pumping system. The sump pump, pit and discharge
piping shall conform to Sections 1113.1.1 through 1113.1.4.
1113.1.1 Pump capacity and head. The sump pump
shall be of a capacity and head appropriate to anticipated
use requirements.
1113.1.2 Sump pit. The sump pit shall be not less than 18
inches (457 mm) in diameter and not less than 24 inches
(610 mm) in depth, unless otherwise approved. The pit
shall be provided with access and shall be located such
that all drainage flows into the pit by gravity. The sump
pit shall be constructed of tile, steel, plastic, cast iron,
concrete or other approved material, with a removable
cover adequate to support anticipated loads in the area of
use. The pit floor shall be solid and provide permanent
support for the pump.
11-10
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 12
SPECIAL PIPING AND STORAGE SYSTEMS
User note:
About this chapter: Chapter 12 specifies the standards covering the installation of nonflammable medical gas piping systems and
nonmedical oxygen piping systems.
SECTION 1201
GENERAL
1201.1 Scope. The provisions of this chapter shall govern
the design and installation of piping and storage systems for
nonflammable medical gas systems and nonmedical oxygen
systems. All maintenance and operations of such systems
shall be in accordance with the International Fire Code.
SECTION 1202
MEDICAL GASES
[F] 1202.1 Nonflammable medical gases. Nonflammable
medical gas systems, inhalation anesthetic systems and
vacuum piping systems shall be installed, tested and labeled
in accordance with NFPA 99.
Exceptions:
1. This section shall not apply to portable systems or
cylinder storage.
2. Vacuum system exhaust terminations shall comply
with the International Mechanical Code.
SECTION 1203
OXYGEN SYSTEMS
[F] 1203.1 Design and installation. Nonmedical oxygen
systems shall be designed and installed in accordance with
NFPA 51 and NFPA 55.
2021 INTERNATIONAL PLUMBING CODE®
12-1
12-2
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 13
NONPOTABLE WATER SYSTEMS
User note:
About this chapter: Storm water and some liquid waste from a building can be a source of nonpotable water that can be used to reduce
the volume of potable water supplied to the building. Chapter 13 provides the requirements for storage, treatment and distribution of this
resource. This chapter also regulates the piping systems for reclaimed water supplied by a wastewater treatment facility.
SECTION 1301
GENERAL
1301.1 General. The provisions of Chapter 13 shall govern
the materials, design, construction and installation of
systems for the collection, storage, treatment and distribution
of nonpotable water. For nonpotable rainwater systems, the
provisions of CSA B805/ICC 805 shall be an alternative for
regulating the materials, design, construction and installation
of systems for rainwater collection, storage, treatment and
distribution of nonpotable water. The use and application of
nonpotable water shall comply with laws, rules and ordinances applicable in the jurisdiction.
1301.2 Water quality. Nonpotable water for each end use
application shall meet the minimum water quality requirements as established for the intended application by the laws,
rules and ordinances applicable in the jurisdiction. Where
nonpotable water from different sources is combined in a
system, the system shall comply with the most stringent of
the requirements of this code that are applicable to such
sources.
1301.2.1 Residual disinfectants. Where chlorine is used
for disinfection, the nonpotable water shall contain not
more than 4 ppm (4 mg/L) of chloramines or free chlorine
when tested in accordance with ASTM D1253. Where
ozone is used for disinfection, the nonpotable water shall
not contain gas bubbles having elevated levels of ozone at
the point of use.
Exception: Reclaimed water sources shall not be
required to comply with these requirements.
1301.2.2 Filtration required. Nonpotable water utilized
for water closet and urinal flushing applications shall be
filtered by a 100-micron (0.1 mm) or finer filter.
Exception: Reclaimed water sources shall not be
required to comply with these requirements.
1301.3 Signage required. Nonpotable water outlets such as
hose connections, open-ended pipes and faucets shall be
identified at the point of use for each outlet with signage that
reads as follows: “Nonpotable water is utilized for [application name]. CAUTION: NONPOTABLE WATER – DO
NOT DRINK.” The words shall be legibly and indelibly
printed on a tag or sign constructed of corrosion-resistant
waterproof material or shall be indelibly printed on the
fixture. The letters of the words shall be not less than 0.5
inch (12.7 mm) in height and in colors in contrast to the
2021 INTERNATIONAL PLUMBING CODE®
background on which they are applied. In addition to the
required wordage, the pictograph shown in Figure 1301.3
shall appear on the signage required by this section.
FIGURE 1301.3
PICTOGRAPH—DO NOT DRINK
1301.4 Permits. Permits shall be required for the construction, installation, alteration and repair of nonpotable water
systems. Construction documents, engineering calculations,
diagrams and other such data pertaining to the nonpotable
water system shall be submitted with each permit
application.
1301.5 Potable water connections. Where a potable system
is connected to a nonpotable water system, the potable water
supply shall be protected against backflow in accordance
with Section 608.
1301.6 Components and materials. Piping, plumbing
components and materials used in collection and conveyance
systems shall be of material approved by the manufacturer
for the intended application.
1301.7 Insect and vermin control. The system shall be
protected to prevent the entrance of insects and vermin into
storage tanks and piping systems. Screen materials shall be
compatible with contacting system components and shall not
accelerate the corrosion of system components.
1301.8 Freeze protection. Where sustained freezing
temperatures occur, provisions shall be made to keep storage
tanks and the related piping from freezing.
13-1
NONPOTABLE WATER SYSTEMS
1301.9 Nonpotable water storage tanks. Nonpotable water
storage tanks shall comply with Sections 1301.9.1 through
1301.9.10.
1301.9.1 Location. Any storage tank or portion thereof
that is above grade shall be protected from direct exposure to sunlight by one of the following methods:
1. Tank construction using opaque, UV-resistant
materials such as heavily tinted plastic, fiberglass,
lined metal, concrete, wood, or painted to prevent
algae growth.
2. Specially constructed sun barriers.
3. Installation in garages, crawl spaces or sheds.
1301.9.2 Materials. Where collected on site, water shall
be collected in an approved tank constructed of durable,
nonabsorbent and corrosion-resistant materials. The storage tank shall be constructed of materials compatible with
any disinfection systems used to treat water upstream of
the tank and with any systems used to maintain water
quality in the tank. Wooden storage tanks that are not
equipped with a makeup water source shall be provided
with a flexible liner.
1301.9.3 Foundation and supports. Storage tanks shall
be supported on a firm base capable of withstanding the
weight of the storage tank when filled to capacity. Storage
tanks shall be supported in accordance with the International Building Code.
1301.9.3.1 Ballast. Where the soil can become saturated, an underground storage tank shall be ballasted,
or otherwise secured, to prevent the tank from floating
out of the ground when empty. The combined weight
of the tank and hold-down ballast shall meet or exceed
the buoyancy force of the tank. Where the installation
requires a foundation, the foundation shall be flat and
shall be designed to support the weight of the storage
tank when full, consistent with the bearing capability
of adjacent soil.
1301.9.3.2 Structural support. Where installed below
grade, storage tank installations shall be designed to
withstand earth and surface structural loads without
damage and with minimal deformation when empty or
filled with water.
1301.9.4 Makeup water. Where an uninterrupted supply
is required for the intended application, potable or
reclaimed water shall be provided as a source of makeup
water for the storage tank. The makeup water supply shall
be protected against backflow in accordance with Section
608. A full-open valve located on the makeup water
supply line to the storage tank shall be provided. Inlets to
the storage tank shall be controlled by fill valves or other
automatic supply valves installed to prevent the tank from
overflowing and to prevent the water level from dropping
below a predetermined point. Where makeup water is
provided, the water level shall not be permitted to drop
below the source water inlet or the intake of any attached
pump.
1301.9.5 Overflow. The storage tank shall be equipped
with an overflow pipe having a diameter not less than that
13-2
shown in Table 606.5.4. The overflow pipe shall be
protected from insects or vermin and shall discharge in a
manner consistent with storm water runoff requirements
of the jurisdiction. The overflow pipe shall discharge at a
sufficient distance from the tank to avoid damaging the
tank foundation or the adjacent property. Drainage from
overflow pipes shall be directed to prevent freezing on
roof walkways. The overflow drain shall not be equipped
with a shutoff valve. A cleanout shall be provided on each
overflow pipe in accordance with Section 708.
1301.9.6 Access. Not less than one access opening shall
be provided to allow inspection and cleaning of the tank
interior. Access openings shall have an approved locking
device or other approved method of securing access.
Below-grade storage tanks, located outside of the building, shall be provided with a manhole either not less than
24 inches (610 mm) square or with an inside diameter not
less than 24 inches (610 mm). Manholes shall extend not
less than 4 inches (102 mm) above ground or shall be
designed to prevent water infiltration. Finished grade
shall be sloped away from the manhole to divert surface
water. Manhole covers shall be secured to prevent unauthorized access. Service ports in manhole covers shall be
not less than 8 inches (203 mm) in diameter and shall be
not less than 4 inches (102 mm) above the finished grade
level. The service port shall be secured to prevent unauthorized access.
Exception: Treated-water storage tanks that are less
than 800 gallons (3028 L) in volume and installed
below grade shall not be required to be equipped with
a manhole provided that the tank has a service port of
not less than 8 inches (203 mm) in diameter.
1301.9.7 Venting. Storage tanks shall be provided with a
vent sized in accordance with Chapter 9 and based on the
aggregate diameter of all tank influent pipes. The reservoir vent shall not be connected to sanitary drainage
system vents. Vents shall be protected from contamination by means of an approved cap or U-bend installed
with the opening directed downward. Vent outlets shall
extend not less than 4 inches (102 mm) above grade or as
necessary to prevent surface water from entering the storage tank. Vent openings shall be protected against the
entrance of vermin and insects in accordance with the
requirements of Section 1301.7.
1301.9.8 Draining of tanks. Tanks shall be provided
with a means of emptying the contents for the purpose of
service or cleaning. Tanks shall be drained by using a
pump or by a drain located at the lowest point in the tank.
The tank drain pipe shall discharge as required for overflow pipes and shall not be smaller in size than specified
in Table 606.5.7. Not less than one cleanout shall be
provided on each drain pipe in accordance with Section
708.
1301.9.9 Marking and signage. Each nonpotable water
storage tank shall be labeled with its rated capacity. The
contents of storage tanks shall be identified with the
words “CAUTION: NONPOTABLE WATER – DO
NOT DRINK.” Where an opening is provided that could
2021 INTERNATIONAL PLUMBING CODE®
NONPOTABLE WATER SYSTEMS
allow the entry of personnel, the opening shall be marked
with the words, “DANGER – CONFINED SPACE.”
Markings shall be indelibly printed on the tank or on a tag
or sign constructed of corrosion-resistant waterproof
material that is mounted on the tank. The letters of the
words shall be not less than 0.5 inch (12.7 mm) in height
and shall be of a color in contrast with the background on
which they are applied.
1301.9.10 Storage tank tests. Storage tanks shall be
tested in accordance with the following:
Storage tanks shall be filled with water to the overflow
line prior to and during inspection. Seams and joints shall
be left exposed and the tank shall remain watertight without leakage for a period of 24 hours.
1. After 24 hours, supplemental water shall be introduced for a period of 15 minutes to verify proper
drainage of the overflow system and that there are
no leaks.
2. The tank drain shall be observed for proper
operation.
3. The makeup water system shall be observed for
proper operation and successful automatic shutoff
of the system at the refill threshold shall be
verified.
1301.10 System abandonment. If the owner of an on-site
nonpotable water reuse system or rainwater collection and
conveyance system elects to cease use of, or fails to properly
maintain such system, the system shall be abandoned and
shall comply with the following:
1. All system piping connecting to a utility-provided
water system shall be removed or disabled.
2. The distribution piping system shall be replaced with
an approved potable water supply piping system.
Where an existing potable pipe system is already in
place, the fixtures shall be connected to the existing
system.
3. The storage tank shall be secured from accidental
access by sealing or locking tank inlets and access
points, or filling with sand or equivalent.
1301.11 Trenching requirements for nonpotable water
piping. Nonpotable water collection and distribution piping
and reclaimed water piping shall be separated from the
building sewer and potable water piping underground by 5
feet (1524 mm) of undisturbed or compacted earth. Nonpotable water collection and distribution piping shall not be
located in, under or above cesspools, septic tanks, septic tank
drainage fields or seepage pits. Buried nonpotable water
piping shall comply with the requirements of Section 306.
Exceptions:
1. The required separation distance shall not apply
where the bottom of the nonpotable water pipe
within 5 feet (1524 mm) of the sewer is not less
than 12 inches (305 mm) above the top of the
highest point of the sewer and the pipe materials
conform to Table 702.3.
2021 INTERNATIONAL PLUMBING CODE®
2. The required separation distance shall not apply
where the bottom of the potable water service pipe
within 5 feet (1524 mm) of the nonpotable water
pipe is not less than 12 inches (305 mm) above the
top of the highest point of the nonpotable water
pipe and the pipe materials comply with the
requirements of Table 605.4.
3. Nonpotable water pipe is permitted to be located
in the same trench with a building sewer, provided
that such sewer is constructed of materials that
comply with the requirements of Table 702.2.
4. The required separation distance shall not apply
where a nonpotable water pipe crosses a sewer
pipe, provided that the pipe is sleeved to not less
than 5 feet (1524 mm) horizontally from the sewer
pipe centerline on both sides of such crossing, with
pipe materials that comply with Table 702.2.
5. The required separation distance shall not apply
where a potable water service pipe crosses a
nonpotable water pipe, provided that the potable
water service pipe is sleeved for a distance of not
less than 5 feet (1524 mm) horizontally from the
centerline of the nonpotable pipe on both sides of
such crossing, with pipe materials that comply
with Table 702.2.
6. Irrigation piping located outside of a building and
downstream of the backflow preventer is not
required to meet the trenching requirements where
nonpotable water is used for outdoor applications.
1301.12 Outdoor outlet access. Sillcocks, hose bibbs, wall
hydrants, yard hydrants and other outdoor outlets supplied
by nonpotable water shall be located in a locked vault or
shall be operable only by means of a removable key.
SECTION 1302
ON-SITE NONPOTABLE WATER REUSE SYSTEMS
1302.1 General. The provisions of ASTM E2635 and
Section 1302 shall govern the construction, installation,
alteration and repair of on-site nonpotable water reuse
systems for the collection, storage, treatment and distribution
of on-site sources of nonpotable water as permitted by the
jurisdiction.
1302.2 Sources. On-site nonpotable water reuse systems
shall collect waste discharge from only the following
sources: bathtubs, showers, lavatories, clothes washers and
laundry trays. Where approved and as appropriate for the
intended application, water from other nonpotable sources
shall be collected for reuse by on-site nonpotable water reuse
systems.
1302.2.1 Prohibited sources. Wastewater containing
urine or fecal matter shall not be diverted to on-site
nonpotable water reuse systems and shall discharge to the
sanitary drainage system of the building or premises in
accordance with Chapter 7. Reverse osmosis system
reject water, water softener discharge water, kitchen sink
13-3
NONPOTABLE WATER SYSTEMS
wastewater, dishwasher wastewater and wastewater
discharged from wet-hood scrubbers shall not be
collected for reuse in an on-site nonpotable water reuse
system.
1302.3 Traps. Traps serving fixtures and devices discharging wastewater to on-site nonpotable water reuse systems
shall comply with Section 1002.4.
1302.4 Collection pipe. On-site nonpotable water reuse
systems shall utilize drainage piping approved for use in
plumbing drainage systems to collect and convey untreated
water for reuse. Vent piping approved for use in plumbing
venting systems shall be utilized for vents in the graywater
system. Collection and vent piping materials shall comply
with Section 702.
1302.4.1 Installation. Collection piping conveying
untreated water for reuse shall be installed in accordance
with Section 704.
1302.4.2 Joints. Collection piping conveying untreated
water for reuse shall utilize joints approved for use with
the distribution piping and appropriate for the intended
applications as specified in Section 705.
1302.4.3 Size. Collection piping conveying untreated
water for reuse shall be sized in accordance with drainage
sizing requirements specified in Section 710.
1302.4.4 Marking. Additional marking of collection
piping conveying untreated water for reuse shall not be
required beyond that required for sanitary drainage, waste
and vent piping by Chapter 7.
1302.5 Filtration. Untreated water collected for reuse shall
be filtered as required for the intended end use. Filters shall
be provided with access for inspection and maintenance.
Filters shall utilize a pressure gauge or other approved
method to provide indication when a filter requires servicing
or replacement. Filters shall be installed with shutoff valves
immediately upstream and downstream to allow for isolation
during maintenance.
1302.6 Disinfection and treatment. Where the intended
application for nonpotable water collected on site for reuse
requires disinfection or other treatment or both, it shall be
disinfected as needed to ensure that the required water quality is delivered at the point of use. Nonpotable water
collected on site containing untreated graywater shall be
retained in collection reservoirs for not longer than 24 hours.
1302.6.1 Graywater used for fixture flushing. Graywater used for flushing water closets and urinals shall be
disinfected and treated by an on-site water reuse treatment system complying with NSF 350.
1302.7 Storage tanks. Storage tanks utilized in on-site
nonpotable water reuse systems shall comply with Sections
1301.9, 1302.7.1 and 1302.7.2.
1302.7.1 Location. Storage tanks shall be located with a
minimum horizontal distance between various elements
as indicated in Table 1302.7.1.
1302.7.2 Outlets. Outlets shall be located not less than 4
inches (102 mm) above the bottom of the storage tank and
shall not skim water from the surface.
1302.8 Valves. Valves shall be supplied on on-site nonpotable water reuse systems in accordance with Sections
1302.8.1 and 1302.8.2.
1302.8.1 Bypass valve. One three-way diverter valve
listed and labeled to NSF 50 or other approved device
shall be installed on collection piping upstream of each
storage tank, or drainfield, as applicable, to divert
untreated on-site reuse sources to the sanitary sewer to
allow servicing and inspection of the system. Bypass
valves shall be installed downstream of fixture traps and
vent connections. Bypass valves shall be marked to indicate the direction of flow, connection and storage tank or
drainfield connection. Bypass valves shall be provided
with access that allows for removal. Two shutoff valves
shall not be installed to serve as a bypass valve.
1302.8.2 Backwater valve. One or more backwater
valves shall be installed on each overflow and tank drain
pipe. Backwater valves shall be in accordance with
Section 714.
1302.9 Pumping and control system. Mechanical equipment including pumps, valves and filters shall be easily
accessible and removable in order to perform repair, maintenance and cleaning. The minimum flow rate and flow
pressure delivered by the pumping system shall be appropriate for the application and in accordance with Section 604.
TABLE 1302.7.1
LOCATION OF NONPOTABLE
WATER REUSE STORAGE TANKS
ELEMENT
Critical root zone (CRZ) of protected trees
MINIMUM HORIZONTAL DISTANCE FROM STORAGE TANK (feet)
2
Lot line adjoining private lots
5
Public water main
10
Seepage pits
5
Septic tanks
5
Streams and lakes
50
Water service
5
Water wells
50
For SI: 1 foot = 304.8 mm.
13-4
2021 INTERNATIONAL PLUMBING CODE®
NONPOTABLE WATER SYSTEMS
1302.10 Water pressure-reducing valve or regulator.
Where the water pressure supplied by the pumping system
exceeds 80 psi (552 kPa) static, a pressure-reducing valve
shall be installed to reduce the pressure in the nonpotable
water distribution system piping to 80 psi (552 kPa) static or
less. Pressure-reducing valves shall be specified and
installed in accordance with Section 604.8.
1302.11 Distribution piping. Distribution piping utilized in
on-site nonpotable water reuse systems shall comply with
Sections 1302.11.1 through 1302.11.3.
Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.
1302.11.1 Materials, joints and connections. Distribution piping shall conform to the standards and
requirements specified in Section 605.
1302.11.2 Design. On-site nonpotable water reuse distribution piping systems shall be designed and sized in
accordance with Section 604 for the intended application.
1302.11.3 Labeling and marking. On-site nonpotable
water distribution piping labeling and marking shall
comply with Section 608.9.
1302.12 Tests and inspections. Tests and inspections shall
be performed in accordance with Sections 1302.12.1 through
1302.12.6.
1302.12.1 Collection pipe and vent test. Drain, waste
and vent piping used for on-site water reuse systems shall
be tested in accordance with Section 312.
1302.12.2 Storage tank test. Storage tanks shall be tested
in accordance with Section 1301.9.10.
1302.12.3 Water supply system test. The testing of
makeup water supply piping and distribution piping shall
be conducted in accordance with Section 312.5.
1302.12.4 Inspection and testing of backflow prevention assemblies. The testing of backflow preventers and
backwater valves shall be conducted in accordance with
Section 312.10.
1302.12.5 Inspection of vermin and insect protection.
Inlets and vents to the system shall be inspected to verify
that each is protected to prevent the entrance of insects
and vermin into the storage tank and piping systems in
accordance with Section 1301.7.
1302.12.6 Water quality test. The quality of the water
for the intended application shall be verified at the point
of use in accordance with the requirements of the
jurisdiction.
1302.13 Operation and maintenance manuals. Operation
and maintenance materials shall be supplied with nonpotable
on-site water reuse systems in accordance with Sections
1302.13.1 through 1302.13.4.
1302.13.1 Manual. A detailed operations and maintenance manual shall be supplied in hardcopy form with all
systems.
1302.13.2 Schematics. The manual shall include a
detailed system schematic, and the locations and a list of
2021 INTERNATIONAL PLUMBING CODE®
all system components, including manufacturer and
model number.
1302.13.3 Maintenance procedures. The manual shall
provide a schedule and procedures for all system components requiring periodic maintenance. Consumable parts,
including filters, shall be noted along with part numbers.
1302.13.4 Operations procedures. The manual shall
include system startup and shutdown procedures. The
manual shall include detailed operating procedures for the
system.
SECTION 1303
NONPOTABLE RAINWATER
COLLECTION AND DISTRIBUTION SYSTEMS
1303.1 General. The provisions of Section 1303 shall
govern the construction, installation, alteration and repair of
rainwater collection and conveyance systems for the collection, storage, treatment and distribution of rainwater for
nonpotable applications, as permitted by the jurisdiction.
1303.1.1 Fire protection systems. The storage, treatment
and distribution of nonpotable water to be used for fire
protection systems shall be in accordance with the International Fire Code.
1303.2 Collection surface. Rainwater shall be collected
only from above-ground impervious roofing surfaces
constructed from approved materials and where approved,
vehicular parking or pedestrian walking surfaces.
1303.3 Debris excluders. Downspouts and leaders shall be
connected to a debris excluder or equivalent device that is
designed to remove leaves, sticks, pine needles and similar
debris to prevent such from entering the storage tank.
1303.4 First-flush diverter. First-flush diverters shall operate automatically and shall not rely on manually operated
valves or devices. Diverted rainwater shall not be drained to
the roof surface, and shall be discharged in a manner consistent with the storm water runoff requirements of the
jurisdiction. First-flush diverters shall be provided with
access for maintenance and service.
1303.5 Roof gutters and downspouts. Gutters and downspouts shall be constructed of materials that are compatible
with the collection surface and the rainwater quality for the
desired end use. Joints shall be watertight.
1303.5.1 Slope. Roof gutters, leaders and rainwater
collection piping shall slope continuously toward collection inlets. Gutters and downspouts shall have a slope of
not less than 1/8 inch per foot (10.4 mm/m) along their
entire length, and shall not permit the collection or pooling of water at any point.
Exception: Siphonic drainage systems installed in
accordance with the manufacturer’s instructions shall
not be required to have a slope.
1303.5.2 Size. Gutters and downspouts shall be installed
and sized in accordance with Section 1106.6 and local
rainfall rates.
13-5
NONPOTABLE WATER SYSTEMS
1303.5.3 Cleanouts. Cleanouts shall be provided in the
water conveyance system to allow access to all filters,
flushes, pipes and downspouts.
1303.6 Drainage. Water drained from the roof washer or
debris excluder shall not be drained to the sanitary sewer.
Such water shall be diverted from the storage tank and
discharge in a location that will not cause erosion or damage
to property in accordance with the International Building
Code. Roof washers and debris excluders shall be provided
with an automatic means of self-draining between rain
events, and shall not drain onto roof surfaces.
TABLE 1303.10.1
LOCATION OF RAINWATER STORAGE TANKS
MINIMUM HORIZONTAL DISTANCE
FROM STORAGE TANK (feet)
ELEMENT
Critical root zone (CRZ) of
protected trees
2
Lot line adjoining private lots
5
Seepage pits
5
Septic tanks
5
For SI: 1 foot = 304.8 mm.
1303.7 Collection pipe. Rainwater collection and conveyance systems shall utilize drainage piping approved for use
within plumbing drainage systems to collect and convey
captured rainwater. Vent piping approved for use within
plumbing venting systems shall be utilized for vents within
the rainwater system. Collection and vent piping materials
shall comply with Section 702.
1303.10.2 Inlets. Storage tank inlets shall be designed to
introduce collected rainwater into the tank with minimum
turbulence, and shall be located and designed to avoid
agitating the contents of the storage tank.
1303.7.1 Installation. Collection piping conveying
captured rainwater shall be installed in accordance with
Section 704.
1303.11 Valves. Valves shall be supplied on rainwater
collection and conveyance systems in accordance with
Section 1303.11.1.
1303.7.2 Joints. Collection piping conveying captured
rainwater shall utilize joints approved for use with the
distribution piping and appropriate for the intended applications as specified in Section 705.
1303.11.1 Backwater valve. Backwater valves shall be
installed on each overflow and tank drain pipe. Backwater
valves shall be in accordance with Section 714.
1303.7.3 Size. Collection piping conveying captured rainwater shall be sized in accordance with drainage sizing
requirements specified in Section 710.
1303.7.4 Marking. Additional marking of collection
piping conveying captured rainwater for reuse shall not
be required beyond that required for sanitary drainage,
waste and vent piping by Chapter 7.
1303.8 Filtration. Collected rainwater shall be filtered as
required for the intended end use. Filters shall be provided
with access for inspection and maintenance. Filters shall
utilize a pressure gauge or other approved method to provide
indication when a filter requires servicing or replacement.
Filters shall be installed with shutoff valves installed immediately upstream and downstream to allow for isolation
during maintenance.
1303.9 Disinfection. Where the intended application for
rainwater requires disinfection or other treatment or both, it
shall be disinfected as needed to ensure that the required
water quality is delivered at the point of use. Where chlorine
is used for disinfection or treatment, water shall be tested for
residual chlorine in accordance with ASTM D1253. The
levels of residual chlorine shall not exceed that allowed for
the intended use in accordance with the requirements of the
jurisdiction.
1303.10 Storage tanks. Storage tanks utilized in nonpotable
rainwater collection and conveyance systems shall comply
with Sections 1301.9 and 1303.10.1 through 1303.10.3.
1303.10.1 Location. Storage tanks shall be located with a
minimum horizontal distance between various elements
as indicated in Table 1303.10.1.
13-6
1303.10.3 Outlets. Outlets shall be located not less than 4
inches (102 mm) above the bottom of the storage tank and
shall not skim water from the surface.
1303.12 Pumping and control system. Mechanical equipment including pumps, valves and filters shall be provided
with access that allows for removal in order to perform
repair, maintenance and cleaning. The minimum flow rate
and flow pressure delivered by the pumping system shall be
appropriate for the application and in accordance with
Section 604.
1303.13 Water pressure-reducing valve or regulator.
Where the water pressure supplied by the pumping system
exceeds 80 psi (552 kPa) static, a pressure-reducing valve
shall be installed to reduce the pressure in the rainwater
distribution system piping to 80 psi (552 kPa) static or less.
Pressure-reducing valves shall be specified and installed in
accordance with Section 604.8.
1303.14 Distribution piping. Distribution piping utilized in
rainwater collection and conveyance systems shall comply
with Sections 1303.14.1 through 1303.14.3.
Exception: Irrigation piping located outside of the building and downstream of a backflow preventer.
1303.14.1 Materials, joints and connections. Distribution piping shall conform to the standards and
requirements specified in Section 605 for nonpotable
water.
1303.14.2 Design. Distribution piping systems shall be
designed and sized in accordance with Section 604 for the
intended application.
1303.14.3 Labeling and marking. Nonpotable rainwater
distribution piping labeling and marking shall comply
with Section 608.9.
2021 INTERNATIONAL PLUMBING CODE®
NONPOTABLE WATER SYSTEMS
1303.15 Tests and inspections. Tests and inspections shall
be performed in accordance with Sections 1303.15.1 through
1303.15.9.
1303.15.1 Roof gutter inspection and test. Roof gutters
shall be inspected to verify that the installation and slope
are in accordance with Section 1303.5.1. Gutters shall be
tested by pouring not less than 1 gallon (3.8 L) of water
into the end of the gutter opposite the collection point.
The gutter being tested shall not leak and shall not retain
standing water.
1303.15.2 First-flush diverter test. First-flush diverters
shall be tested by introducing water into the collection
system upstream of the diverter. Proper diversion of the
first amount of water shall be in accordance with the
requirements of Section 1303.4.
1303.15.3 Collection pipe and vent test. Drain, waste
and vent piping used for rainwater collection and conveyance systems shall be tested in accordance with Section
312.
1303.15.4 Storage tank test. Storage tanks shall be tested
in accordance with Section 1301.9.10.
1303.15.5 Water supply system test. The testing of
makeup water supply piping and distribution piping shall
be conducted in accordance with Section 312.5.
1303.15.6 Inspection and testing of backflow prevention assemblies. The testing of backflow preventers and
backwater valves shall be conducted in accordance with
Section 312.10.
1303.15.7 Inspection of vermin and insect protection.
Inlets and vents to the system shall be inspected to verify
that each is protected to prevent the entrance of insects
and vermin into the storage tank and piping systems in
accordance with Section 1301.7.
1303.15.8 Water quality test. The quality of the water
for the intended application shall be verified at the point
of use in accordance with the requirements of the
jurisdiction.
1303.15.9 Collected raw rainwater quality. ASTM
E2727 shall be used to determine what, if any, site conditions impact the quality of collected raw rainwater and
whether those site conditions require treatment of the raw
water for the intended end use or make the water unsuitable for specific end uses.
1303.16 Operation and maintenance manuals. Operation
and maintenance manuals shall be supplied with rainwater
collection and conveyance systems in accordance with
Sections 1303.16.1 through 1303.16.4.
1303.16.1 Manual. A detailed operations and maintenance manual shall be supplied in hardcopy form with all
systems.
1303.16.3 Maintenance procedures. The manual shall
provide a maintenance schedule and procedures for all
system components requiring periodic maintenance.
Consumable parts, including filters, shall be noted along
with part numbers.
1303.16.4 Operations procedures. The manual shall
include system startup and shutdown procedures, as well
as detailed operating procedures.
SECTION 1304
RECLAIMED WATER SYSTEMS
1304.1 General. The provisions of this section shall govern
the construction, installation, alteration and repair of systems
supplying nonpotable reclaimed water.
1304.2 Water pressure-reducing valve or regulator.
Where the reclaimed water pressure supplied to the building
exceeds 80 psi (552 kPa) static, a pressure-reducing valve
shall be installed to reduce the pressure in the reclaimed
water distribution system piping to 80 psi (552 kPa) static or
less. Pressure-reducing valves shall be specified and
installed in accordance with Section 604.8.
1304.3 Reclaimed water systems. The design of the
reclaimed water systems shall conform to accepted engineering practice.
1304.3.1 Distribution piping. Distribution piping shall
comply with Sections 1304.3.1.1 through 1304.3.1.3.
Exception: Irrigation piping located outside of the
building and downstream of a backflow preventer.
1304.3.1.1 Materials, joints and connections. Distribution piping conveying reclaimed water shall
conform to standards and requirements specified in
Section 605 for nonpotable water.
1304.3.1.2 Design. Distribution piping systems shall
be designed and sized in accordance with Section 604
for the intended application.
1304.3.1.3 Labeling and marking. Nonpotable distribution piping labeling and marking shall comply with
Section 608.9.
1304.4 Tests and inspections. Tests and inspections shall be
performed in accordance with Sections 1304.4.1 and
1304.4.2.
1304.4.1 Water supply system test. The testing of
makeup water supply piping and reclaimed water distribution piping shall be conducted in accordance with
Section 312.5.
1304.4.2 Inspection and testing of backflow prevention
assemblies. The testing of backflow preventers shall be
conducted in accordance with Section 312.10.
1303.16.2 Schematics. The manual shall include a
detailed system schematic, and the locations and a list of
all system components, including manufacturer and
model number.
2021 INTERNATIONAL PLUMBING CODE®
13-7
13-8
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 14
SUBSURFACE GRAYWATER SOIL ABSORPTION SYSTEMS
User note:
About this chapter: Chapter 14 provides regulations for disposing of nonpotable water to underground landscape irrigation piping. Testing
procedures are provided to assess the capability of the soil to accept the volume of flow. This chapter covers the regulations, types and
material standards for the piping of these systems.
SECTION 1401
GENERAL
Commercial—Number of occupants shall be determined by
the International Building Code.
1401.1 Scope. The provisions of this chapter shall govern
the materials, design, construction and installation of subsurface graywater soil absorption systems connected to
nonpotable water from on-site water reuse systems.
B
= Estimated flow demands for each occupant:
1401.2 Materials. Above-ground drain, waste and vent
piping for subsurface graywater soil absorption systems shall
conform to one of the standards listed in Table 702.1.
Subsurface graywater soil absorption systems, underground
building drainage and vent pipe shall conform to one of the
standards listed in Table 702.2.
Commercial—Based on type of fixture or water use records
minus the discharge of fixtures other than those discharging
graywater.
Residential—25 gallons per day (94.6 Lpd) per occupant for
showers, bathtubs and lavatories and 15 gallons per day
(56.7 Lpd) per occupant for clothes washers or laundry trays.
C
= Estimated graywater discharge based on the total
number of occupants.
1401.3 Tests. Drain, waste and vent piping for subsurface
graywater soil absorption systems shall be tested in accordance with Section 312.
1402.2 Percolation tests. The permeability of the soil in the
proposed absorption system shall be determined by percolation tests or permeability evaluation.
1401.4 Inspections. Subsurface graywater soil absorption
systems shall be inspected in accordance with Section 108.
1402.2.1 Percolation tests and procedures. Not fewer
than three percolation tests in each system area shall be
conducted. The holes shall be spaced uniformly in relation to the bottom depth of the proposed absorption
system. More percolation tests shall be made where
necessary, depending on system design.
1401.5 Disinfection. Disinfection shall not be required for
on-site nonpotable water reuse for subsurface graywater soil
absorption systems.
1401.6 Coloring. On-site nonpotable water reuse for subsurface graywater soil absorption systems shall not be required
to be dyed.
SECTION 1402
SYSTEM DESIGN AND SIZING
1402.1 Sizing. The system shall be sized in accordance with
the sum of the output of all water sources connected to the
subsurface graywater soil absorption system. Where graywater collection piping is connected to subsurface landscape
irrigation systems, graywater output shall be calculated
according to the gallons-per-day-per-occupant number based
on the type of fixtures connected. The graywater discharge
shall be calculated by the following equation:
C=A×B
(Equation 14-1)
where:
A = Number of occupants:
Residential—Number of occupants shall be determined by
the actual number of occupants, but not less than two occupants for one bedroom and one occupant for each additional
bedroom.
2021 INTERNATIONAL PLUMBING CODE®
1402.2.1.1 Percolation test hole. The test hole shall
be dug or bored. The test hole shall have vertical sides
and a horizontal dimension of 4 inches to 8 inches (102
mm to 203 mm). The bottom and sides of the hole
shall be scratched with a sharp-pointed instrument to
expose the natural soil. Loose material shall be
removed from the hole and the bottom shall be covered
with 2 inches (51 mm) of gravel or coarse sand.
1402.2.1.2 Test procedure, sandy soils. The hole
shall be filled with clear water to not less than 12
inches (305 mm) above the bottom of the hole for tests
in sandy soils. The time for this amount of water to
seep away shall be determined, and this procedure
shall be repeated if the water from the second filling of
the hole seeps away in 10 minutes or less. The test
shall proceed as follows: Water shall be added to a
point not more than 6 inches (152 mm) above the
gravel or coarse sand. Thereupon, from a fixed reference point, water levels shall be measured at 10minute intervals for a period of 1 hour. Where 6 inches
(152 mm) of water seeps away in less than 10 minutes,
a shorter interval between measurements shall be used,
but in no case shall the water depth exceed 6 inches
14-1
SUBSURFACE GRAYWATER SOIL ABSORPTION SYSTEMS
texture in accordance with accepted soil evaluation practices. Borings shall be made in accordance with Section
1402.2.1.1 for evaluating the soil.
(152 mm). Where 6 inches (152 mm) of water seeps
away in less than 2 minutes, the test shall be stopped
and a rate of less than 3 minutes per inch (7.2 s/mm)
shall be reported. The final water level drop shall be
used to calculate the percolation rate. Soils not meeting the requirements of this section shall be tested in
accordance with Section 1402.2.1.3.
1402.3 Subsurface graywater soil absorption site location. The surface grade of all soil absorption systems shall
be located at a point lower than the surface grade of any
water well or reservoir on the same or adjoining lot. Where
this is not possible, the site shall be located so surface water
drainage from the site is not directed toward a well or reservoir. The soil absorption system shall be located with a
minimum horizontal distance between various elements as
indicated in Table 1402.3. Private sewage disposal systems
in compacted areas, such as parking lots and driveways, are
prohibited. Surface water shall be diverted away from any
soil absorption site on the same or neighboring lots.
1402.2.1.3 Test procedure, other soils. The hole shall
be filled with clear water, and a minimum water depth
of 12 inches (305 mm) shall be maintained above the
bottom of the hole for a 4-hour period by refilling
whenever necessary or by use of an automatic siphon.
Water remaining in the hole after 4 hours shall not be
removed. Thereafter, the soil shall be allowed to swell
not less than 16 hours or more than 30 hours. Immediately after the soil swelling period, the measurements
for determining the percolation rate shall be made as
follows: any soil sloughed into the hole shall be
removed and the water level shall be adjusted to 6
inches (152 mm) above the gravel or coarse sand.
Thereupon, from a fixed reference point, the water
level shall be measured at 30-minute intervals for a
period of 4 hours, unless two successive water level
drops do not vary by more than 1/16 inch (1.59 mm).
Not fewer than three water level drops shall be
observed and recorded. The hole shall be filled with
clear water to a point not more than 6 inches (152 mm)
above the gravel or coarse sand whenever it becomes
nearly empty. Adjustments of the water level shall not
be made during the three measurement periods except
to the limits of the last measured water level drop.
Where the first 6 inches (152 mm) of water seeps away
in less than 30 minutes, the time interval between
measurements shall be 10 minutes and the test run for
1 hour. The water depth shall not exceed 5 inches (127
mm) at any time during the measurement period. The
drop that occurs during the final measurement period
shall be used in calculating the percolation rate.
SECTION 1403
INSTALLATION
1403.1 Installation. Absorption systems shall be installed in
accordance with Sections 1403.1.1 through 1403.1.5.
1403.1.1 Absorption area. The total absorption area
required shall be computed from the estimated daily graywater discharge and the design-loading rate based on the
percolation rate for the site. The required absorption area
equals the estimated graywater discharge divided by the
design-loading rate from Table 1403.1.1.
TABLE 1403.1.1
DESIGN LOADING RATE
PERCOLATION RATE
(minutes per inch)
DESIGN LOADING FACTOR
(gallons per square foot per day)
0 to less than 10
1.2
10 to less than 30
0.8
30 to less than 45
0.72
45 to 60
0.4
For SI: 1 minute per inch = min/25.4 mm,
1 gallon per square foot = 40.7 L/m2.
1402.2.1.4 Mechanical test equipment. Mechanical
percolation test equipment shall be of an approved
type.
1403.1.2 Seepage trench excavations. Seepage trench
excavations shall be not less than 1 foot (305 mm) in
width and not greater than 5 feet (1524 mm) in width.
Trench excavations shall be spaced not less than 2 feet
1402.2.2 Permeability evaluation. Soil shall be evaluated for estimated percolation based on structure and
TABLE 1402.3
LOCATION OF SUBSURFACE GRAYWATER SOIL ABSORPTION SYSTEM
ELEMENT
Buildings
MINIMUM HORIZONTAL DISTANCE
Storage tank (feet)
Absorption field (feet)
5
2
Lot line adjoining private property
5
5
Public water main
10
10
Seepage pits
5
5
Septic tanks
0
5
Streams and lakes
50
50
Water service
5
5
Water wells
50
100
For SI: 1 foot = 304.8 mm.
14-2
2021 INTERNATIONAL PLUMBING CODE®
SUBSURFACE GRAYWATER SOIL ABSORPTION SYSTEMS
(610 mm) apart. The soil absorption area of a seepage
trench shall be computed by using the bottom of the
trench area (width) multiplied by the length of pipe. Individual seepage trenches shall be not greater than 100 feet
(30 480 mm) in developed length.
1403.1.3 Seepage bed excavations. Seepage bed excavations shall be not less than 5 feet (1524 mm) in width and
have more than one distribution pipe. The absorption area
of a seepage bed shall be computed by using the bottom
of the trench area. Distribution piping in a seepage bed
shall be uniformly spaced not greater than 5 feet (1524
mm) and not less than 3 feet (914 mm) apart, and greater
than 3 feet (914 mm) and not less than 1 foot (305 mm)
from the sidewall or headwall.
1403.1.4 Excavation and construction. The bottom of a
trench or bed excavation shall be level. Seepage trenches
or beds shall not be excavated where the soil is so wet that
such material rolled between the hands forms a soil wire.
Smeared or compacted soil surfaces in the sidewalls or
bottom of seepage trench or bed excavations shall be
scarified to the depth of smearing or compaction and the
loose material removed. Where rain falls on an open
excavation, the soil shall be left until sufficiently dry so a
soil wire will not form when soil from the excavation
bottom is rolled between the hands. The bottom area shall
then be scarified and loose material removed.
1403.1.5 Aggregate and backfill. Not less than 6 inches
(152 mm) in depth of aggregate, ranging in size from 1/2
to 21/2 inches (12.7 mm to 64 mm), shall be laid into the
trench below the distribution piping elevation. The aggregate shall be evenly distributed not less than 2 inches (51
mm) in depth over the top of the distribution pipe. The
aggregate shall be covered with approved synthetic materials or 9 inches (229 mm) of uncompacted marsh hay or
straw. Building paper shall not be used to cover the aggregate. Not less than 9 inches (229 mm) of soil backfill shall
be provided above the covering.
1403.2 Distribution piping. Distribution piping shall be not
less than 3 inches (76 mm) in diameter. Materials shall
comply with Table 1403.2. The top of the distribution pipe
shall be not less than 8 inches (203 mm) below the original
surface. The slope of the distribution pipes shall be not less
than 2 inches (51 mm) and not greater than 4 inches (102
mm) per 100 feet (30 480 mm).
TABLE 1403.2
DISTRIBUTION PIPE
MATERIAL
Polyethylene (PE) plastic pipe
STANDARD
ASTM F405
Polyvinyl chloride (PVC) plastic pipe
ASTM D2729
Polyvinyl chloride (PVC) plastic pipe with a
3.5-inch O.D. and solid cellular core or
composite wall
ASTM F1488
For SI: 1 inch = 25.4 mm.
1403.2.1 Joints. Joints in distribution pipe shall be made
in accordance with Section 705.
2021 INTERNATIONAL PLUMBING CODE®
14-3
14-4
2021 INTERNATIONAL PLUMBING CODE®
CHAPTER 15
REFERENCED STANDARDS
User note:
About this chapter: This code contains numerous references to standards that are used to provide requirements for materials and methods of
construction. Chapter 15 contains a comprehensive list of all standards that are referenced in this code. These standards, in essence, are part of
this code to the extent of the reference to the standard.
This chapter lists the standards that are referenced in various sections of this document. The standards are listed herein by the promulgating
agency of the standard, the standard identification, the effective date and title, and the section or sections of this document that reference the
standard. The application of the referenced standards shall be as specified in Section 102.8.
ANSI
American National Standards Institute
25 West 43rd Street, 4th Floor
New York, NY 10036
A118.10—14: Specifications for Load Bearing, Bonded, Waterproof Membranes for Thin Set Ceramic Tile and Dimension Stone
Installation
421.5.2.5, 421.5.2.6
Z21.22—99 (R2003): Relief Valves for Hot Water Supply Systems with Addenda Z21.22a—2000 (R2003) and Z21.22b—2001 (R2003)
504.2, 504.4, 504.4.1
ASHRAE
ASHRAE
1791 Tullie Circle NE
Atlanta, GA 30329
ASHRAE 18—2008 (RA13): Method of Testing for Rating Drinking-Water Coolers with Self-contained Mechanical Refrigeration
(ANSI/ASHRAE Approved)
410.1
ASME
American Society of Mechanical Engineers
Two Park Avenue
New York, NY 10016-5990
A112.1.2—2022: Air Gaps in Plumbing Systems (For Plumbing Fixtures and Water Connection Receptors)
406.1, 409.2, Table 608.1, 608.14.1
A112.1.3—2000 (R2020): Air Gap Fittings for Use with Plumbing Fixtures, Appliances and Appurtenances
406.1, 409.2, Table 608.1, 608.14.1, 1102.6
A112.3.1—2007 (R2022): Stainless Steel Drainage Systems for Sanitary, DWV, Storm and Vacuum Applications Above and Below
Ground
413.1, Table 702.1, Table 702.2, Table 702.3, Table 702.4, Table 1102.4, Table 1102.5, 1102.6, Table
1102.7
A112.4.1—2009 (R2019): Water Heater Relief Valve Drain Tubes
504.6
A112.4.2—2020/CSA B45.16—20: Water Closet Personal Hygiene Devices
412.9
A112.4.3—1999 (R2020): Plastic Fittings for Connecting Water Closets to the Sanitary Drainage System
405.4
A112.4.4—2017: Plastic Push-Fit Drain, Waste, and Vent (DWV) Fittings
705.2.4
A112.4.14—2004 (R2019): Manually Operated, Quarter-Turn Shutoff Valves for Use in Plumbing Systems
Table 605.7
A112.6.1M —1997(R2017): Floor Affixed Supports for Off-the-Floor Plumbing Fixtures for Public Use
405.4.3
2021 INTERNATIONAL PLUMBING CODE®
15-1
REFERENCED STANDARDS
ASME—continued
A112.6.2—2022: Framing-Affixed Supports for Off-the-Floor Water Closets with Concealed Tanks
405.4.3
A112.6.3—2019: Floor and Trench Drains
413.1
A112.6.4—2003 (R2020): Roof, Deck, and Balcony Drains
1102.6
A112.6.7—2010 (R2020): Sanitary Floor Sinks
414.1
A112.6.9—2005 (R2020): Siphonic Roof Drains
1107.1
A112.14.1—2003 (R2022): Backwater Valves
714.2
A112.14.3—2021: Grease Interceptors
1003.3.5
A112.14.4—2001 (R2022): Grease Removal Devices
1003.3.5
A112.14.6—2010 (R2020): FOG (Fats, Oils and Greases) Disposal Systems
1003.3, 1003.3.5, 1003.3.7
A112.18.1—2020/CSA B125.1—2020: Plumbing Supply Fittings
412.1, 412.2, 412.3, 412.4, 412.6, 412.8, Table 605.7, 607.4, 608.2
A112.18.2—2019/CSA B125.2—19: Plumbing Waste Fittings
412.1.2, 421.3.1
A112.18.3—2002 (R2020): Performance Requirements for Backflow Protection Devices and Systems in Plumbing Fixture Fittings
412.2, 412.6
A112.18.6—2021/CSA B125.6—21: Flexible Water Connectors
605.6
A112.19.1—2020/CSA B45.2—20: Enameled Cast Iron and Enameled Steel Plumbing Fixtures
407.1, 410.1, 418.1, 419.1, 421.1, 422.1
A112.19.2—2020/CSA B45.1—20: Ceramic Plumbing Fixtures
401.2, 405.10, 407.1, 408.1, 410.1, 418.1, 419.1, 421.1, 422.1, 424.1, 425.1
A112.19.3—2021/CSA B45.4—2021: Stainless Steel Plumbing Fixtures
405.9, 407.1, 408.1, 410.1, 418.1, 419.1, 421.1, 425.1
A112.19.5—2021/CSA B45.15—2021: Flush Valves and Spuds for Water Closets, Urinals, and Tanks
415.4
A112.19.7—2012/CSA B45.10—2012 (R2021): Hydromassage Bathtub Systems
426.1, 426.4
A112.19.12—2019: Wall Mounted and Pedestal Mounted, Adjustable, Elevating, Tilting and Pivoting Lavatory, Sink and Shampoo Bowl
Carrier Systems and Drain Waste Systems
419.4
A112.19.14—2013 (R2018): Six-liter Water Closets Equipped with a Dual Flushing Device
425.1
A112.19.15—2012 (R2017): Bathtub/Whirlpool Bathtubs with Pressure Sealed Doors
407.4, 426.6
A112.19.19—2021: Vitreous China Nonwater Urinals
424.1
A112.21.3—1985 (R2017): Hydrants for Utility and Maintenance Use
Table 608.1, 608.14.6
A112.36.2M—1991 (R2017): Cleanouts
708.1.11.2
ASME A112.3.4—2020/CSA B45.9—20: Macerating Toilet Systems and Waste Pumping Systems for Plumbing Fixtures
405.5, 712.4.1
15-2
2021 INTERNATIONAL PLUMBING CODE®
REFERENCED STANDARDS
ASME—continued
ASSE 1002—2020/ASME A112.1002—2020/CSA B125.12—2020: Anti-Siphon Fill Valves for Water Closet Tanks
415.3.1, Table 608.1
ASSE 1016—2020/ASME A112.1016—2020/CSA B125.16—2020: Performance Requirements for Automatic Compensating Valves for
Individual Showers and Tub/Shower Combinations
412.3, 412.4, 607.4
ASSE 1037—2015/ASME A112.1037—2015/CSA B125.37—2015: Pressurized Flushing Devices for Plumbing Fixtures
415.2
ASSE 1070—2020/ASME A112.1070—2020/CSA B125.1070—20: Water Temperature Limiting Devices
408.3, 412.5, 412.10, 419.5, 423.3, 607.1.2
B1.20.1—2019: Pipe Threads, General Purpose (inch)
605.10.3, 605.12.4, 605.14.3, 605.17.1, 705.2.3, 705.5.4, 705.8.1, 705.10.3
B16.3—2021: Malleable Iron Threaded Fittings Classes 150 and 300
Table 1102.7
B16.4—2021: Gray Iron Threaded Fittings Classes 125 and 250
Table 605.5, Table 702.4, Table 1102.7
B16.9—2018: Factory-Made Wrought Steel Buttwelding Fittings
Table 605.5, Table 702.4, Table 1102.7
B16.11—2021: Forged Fittings, Socket-Welding and Threaded
Table 605.5, Table 702.4, Table 1102.7
B16.12—2009 (R2019): Cast Iron Threaded Drainage Fittings
Table 702.4, Table 1102.7
B16.15—2018: Cast Alloy Threaded Fittings: Class 125 and 250
Table 605.5, Table 702.4, Table 1102.7
B16.18—2018: Cast Copper Alloy Solder Joint Pressure Fittings
Table 605.5, Table 702.4, Table 1102.7
B16.22—2018: Wrought Copper and Copper Alloy Solder Joint Pressure Fittings
Table 605.5, Table 702.4, Table 1102.7
B16.23—2021: Cast Copper Alloy Solder Joint Drainage Fittings DWV
Table 702.4, Table 1102.7
B16.26—2018: Cast Copper Alloy Fittings for Flared Copper Tubes
Table 605.5, Table 702.4, Table 1102.7
B16.28—1994: Wrought Steel Buttwelding Short Radius Elbows and Returns
Table 605.5, Table 702.4, Table 1102.7
B16.29—2017: Wrought Copper and Wrought Copper Alloy Solder Joint Drainage Fittings (DWV)
Table 702.4, Table 1102.7
B16.34—2020: Valves—Flanged, Threaded and Welding End
Table 605.7
B16.51—2018: Copper and Copper Alloy Press-Connect Pressure Fittings
Table 605.5
ASPE
American Society of Plumbing Engineers
6400 Shafer Ct., Suite 350
Rosemont, IL 60018-4914
45—2013: Siphonic Roof Drainage Systems
1107.1
ASPE/IAPMO Z1034—2015: Test Method for Evaluating Roof Drain Performance
1102.6
2021 INTERNATIONAL PLUMBING CODE®
15-3
REFERENCED STANDARDS
ASSE
ASSE International
18927 Hickory Creek Drive, Suite 220
Mokena, IL 60448
1001—2017: Performance Requirements for Atmospheric Type Vacuum Breakers
415.2, Table 608.1, 608.14.6, 608.17.4.1
1003—09: Performance Requirements for Water Pressure Reducing Valves
604.8
1004—2016: Performance Requirements for Commercial Dishwashing Machines
409.1
1005—99: Performance Requirements for Water Heater Drain Valves
501.3
1008—06: Performance Requirements for Plumbing Aspects of Food Waste Disposer Units
413.1
1010—04: Performance Requirements for Water Hammer Arresters
604.9
1011—2016: Performance Requirements for Hose Connection Vacuum Breakers
Table 608.1, 608.14.6
1012—09: Performance Requirements for Backflow Preventers with Intermediate Atmospheric Vent
Table 608.1, 608.14.3, 608.17.2, 608.17.10
1013—2011: Performance Requirements for Reduced Pressure Principle Backflow Preventers and Reduced Pressure Principle Fire
Protection Backflow Preventers
Table 608.1, 608.14.2, 608.17.2
1015—2017: Performance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection
Backflow Prevention Assemblies
607.1.2, Table 608.1, 608.14.7
1017—2009: Performance Requirements for Temperature Actuated Mixing Valves for Hot Water Distribution Systems
501.2, 613.1
1018—2001: Performance Requirements for Trap Seal Primer Valves; Potable Water Supplied
1002.4.1.2
1019—2011 (R2016): Performance Requirements for Vacuum Breaker Wall Hydrants, Freeze Resistant, Automatic Draining Type
Table 608.1, 608.14.6
1020—04: Performance Requirements for Pressure Vacuum Breaker Assembly
Table 608.1, 608.14.5
1022—2017: Performance Requirements for Backflow Preventer for Beverage Dispensing Equipment
Table 608.1, 608.17.1.1, 608.17.1.2
1024—2017: Performance Requirements for Dual Check Valve Type Backflow Preventers, Anti-siphon-type, Residential Applications
605.3.1, Table 608.1, 608.14.9, 608.17.1.2
1035—08: Performance Requirements for Laboratory Faucet Backflow Preventers
Table 608.1, 608.14.6
1044—2015: Performance Requirements for Trap Seal Primer Devices—Drainage Types and Electronic Design Types
1002.4.1.3
1047—2011: Performance Requirements for Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies
Table 608.1, 608.14.2
1048—2011: Performance Requirements for Double Check Detector Fire Protection Backflow Prevention Assemblies
Table 608.1, 608.14.7
1049—2009: Performance Requirements for Individual and Branch Type Air Admittance Valves for Chemical Waste Systems
901.3, 918.8
1050—2009: Performance Requirements for Stack Air Admittance Valves for Sanitary Drainage Systems
918.1
1051—2009: Performance Requirements for Individual and Branch Type Air Admittance Valves for Sanitary Drainage Systems
918.1
15-4
2021 INTERNATIONAL PLUMBING CODE®
REFERENCED STANDARDS
ASSE—continued
1052—2016: Performance Requirements for Hose Connection Backflow Preventers
Table 608.1, 608.14.6
1055—2018: Performance Requirements for Chemical Dispensing Systems
608.14.8
1056—2013: Performance Requirements for Spill Resistant Vacuum Breaker
Table 608.1, 608.14.5
1060—2017: Performance Requirements for Outdoor Enclosures for Fluid Conveying Components
608.15.1
1061—2015: Performance Requirements for Push Fit Fittings
Table 605.5, 605.14.4, 605.16.3
1062—2017: Performance Requirements for Temperature Actuated, Flow Reduction (TAFR) Valves to Individual Supply Fittings
412.7
1064—2006 (R2011): Performance Requirements for Backflow Prevention Assembly Field Test Kits
312.10.2
1066—1997: Performance Requirements for Individual Pressure Balancing In-line Valves for Individual Fixture Fittings
604.11
1069—05: Performance Requirements for Automatic Temperature Control Mixing Valves
412.4
1071—2012: Performance Requirements for Temperature Actuated Mixing Valves for Plumbed Emergency Equipment
411.3, 412.10, 412.5, 419.5, 423.3, 607.1.2
1072—07: Performance Requirements for Barrier Type Floor Drain Tap Seal Protection Devices
1002.4.1.4
1079—2005: Performance Requirements for Dielectric Pipe Unions
605.23.1, 605.23.3
1081—2014: Performance Requirements for Backflow Preventers with Integral Pressure Reducing Boiler Feed Valve and Intermediate
Atmospheric Vent Style for Domestic and Light Commercial Water Distribution Systems
608.14.3, 608.17.2
1082—2018: Performance Requirements for Water Heaters with Integral Temperature Control Devices for Hot Water Distribution
Systems.
412.10, 607.1.1
1084—2018: Performance Requirements for Water Heaters with Temperature Limiting Capacity
412.5, 607.1.2
1085—2018: Performance Requirements for Water Heaters for Emergency Equipment
411.3, 607.1.1, 607.1.2
5013—2015: Performance Requirements for Testing Reduced Pressure Principle Backflow Prevention Assembly (RPA) and Reduced
Pressure Fire Protection Backflow Preventers (RFP)
312.10.2
5015—2015: Performance Requirements for Testing Double Check Valve Backflow Prevention Assemblies (DC) and Double Check Fire
Protection Backflow Prevention Assemblies (DCF)
312.10.2
5020—2015: Performance Requirements for Testing Pressure Vacuum Breaker Assemblies (PVBA)
312.10.2
5047—2015: Performance Requirements for Testing Reduced Pressure Detector Fire Protection Backflow Prevention Assemblies
(RPDA)
312.10.2
5048—2015: Performance Requirements for Testing Double Check Valve Detector Assembly (DCDA)
312.10.2
5052—98: Performance Requirements for Testing Hose Connection Backflow Preventers
312.10.2
5056—2015: Performance Requirements for Testing Spill Resistant Vacuum Breaker (SRVB)
312.10.2
ASSE 1002—2020/ASME A112.1002—2020/CSA B125.12—2020: Anti-Siphon Fill Valves for Water Closet Tanks
415.3.1, Table 608.1
2021 INTERNATIONAL PLUMBING CODE®
15-5
REFERENCED STANDARDS
ASSE—continued
ASSE 1016—2020/ASME A112.1016—2020/CSA B125.16—2020: Performance Requirements for Automatic Compensating Valves for
Individual Showers and Tub/Shower Combinations
412.3, 412.4, 607.4
ASSE 1037—2015/ASME A112.1037—2015/CSA B125.37—15: Pressurized Flushing Devices for Plumbing Fixtures
415.2
ASSE 1070—2020/ASME A112.1070—2020/CSA B125.1070—20: Water Temperature Limiting Devices
408.3, 412.5, 412.10, 419.5, 423.3, 607.1.2
ASTM
ASTM International
100 Barr Harbor Drive, P.O. Box C700
West Conshohocken, PA 19428-2959
A53/A53M—2018: Specification for Pipe, Steel, Black and Hot-dipped, Zinc-coated Welded and Seamless
Table 605.3, Table 605.4, Table 702.1
A74—17: Specification for Cast-iron Soil Pipe and Fittings
Table 702.1, Table 702.2, Table 702.3, Table 702.4, 708.1.6, Table 1102.4, Table 1102.5, Table 1102.7
A269/A269M-15a: Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service
Table 605.3
A312/A312M—2018: Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes
Table 605.3, Table 605.4, Table 605.5, 605.22.2
A733—16: Specification for Welded and Seamless Carbon Steel and Austenitic Stainless Steel Pipe Nipples
Table 605.8
A778/A778M—16: Specification for Welded Unannealed Austenitic Stainless Steel Tubular Products
Table 605.3, Table 605.4, Table 605.5
A888—2018: Specification for Hubless Cast-iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste, and Vent Piping
Application
Table 702.1, Table 702.2, Table 702.3, Table 702.4, Table 1102.4, Table 1102.5, Table 1102.7
B32—08(2014): Specification for Solder Metal
605.12.3, 605.13.6, 705.5.3, 705.6.1
B42—15a: Specification for Seamless Copper Pipe, Standard Sizes
Table 605.3, Table 605.4, Table 702.1
B43—15: Specification for Seamless Red Brass Pipe, Standard Sizes
Table 605.4, Table 702.1
B75/B75M—11: Specification for Seamless Copper Tube
Table 605.3, Table 605.4, Table 702.1, Table 702.2, Table 702.3, Table 1102.4
B88—2016: Specification for Seamless Copper Water Tube
Table 605.3, Table 605.4, Table 702.1, Table 702.2, Table 702.3, Table 1102.4
B152/B152M—13: Specification for Copper Sheet, Strip Plate and Rolled Bar
402.3, 415.3.3, 902.2
B251/B251M—2017: Specification for General Requirements for Wrought Seamless Copper and Copper-alloy Tube
Table 605.3, Table 605.4, Table 702.1, Table 702.2, Table 702.3, Table 1102.4
B302—17: Specification for Threadless Copper Pipe, Standard Sizes
Table 605.3, Table 605.4, Table 702.1
B306—13: Specification for Copper Drainage Tube (DWV)
Table 702.1, Table 702.2, Table 1102.4
B447—12a: Specification for Welded Copper Tube
Table 605.3, Table 605.4
B687—1999(2016): Specification for Brass, Copper and Chromium-plated Pipe Nipples
Table 605.8
B813—16: Specification for Liquid and Paste Fluxes for Soldering of Copper and Copper Alloy Tube
605.12.3, 605.13.6, 705.5.3, 705.6.1
B828—2016: Practice for Making Capillary Joints by Soldering of Copper and Copper Alloy Tube and Fittings
605.12.3, 605.13.6, 705.5.3, 705.6.1
15-6
2021 INTERNATIONAL PLUMBING CODE®
REFERENCED STANDARDS
ASTM—continued
C4—04(2018): Specification for Clay Drain Tile and Perforated Clay Drain Tile
Table 702.3, Table 1102.4, Table 1102.5
C14—15a: Specification for Nonreinforced Concrete Sewer, Storm Drain and Culvert Pipe
Table 702.3, Table 1102.4
C76—2018A: Specification for Reinforced Concrete Culvert, Storm Drain and Sewer Pipe
Table 702.3, Table 1102.4
C425—2004(2018): Specification for Compression Joints for Vitrified Clay Pipe and Fittings
705.11, 705.16
C443—2012(2017): Specification for Joints for Concrete Pipe and Manholes, Using Rubber Gaskets
705.4, 705.16
C564—14: Specification for Rubber Gaskets for Cast-iron Soil Pipe and Fittings
705.3.2, 705.3.3, 705.16
C700—2018: Specification for Vitrified Clay Pipe, Extra Strength, Standard Strength, and Perforated
Table 702.3, Table 702.4, Table 1102.4, Table 1102.5
C1053—2000(2015): Specification for Borosilicate Glass Pipe and Fittings for Drain, Waste, and Vent (DWV) Applications
Table 702.1, Table 702.4
C1173—2018: Specification for Flexible Transition Couplings for Underground Piping System
705.2.1, 705.5, 705.10.1, 705.11, 705.12.2, 705.16
C1277—2018: Specification for Shielded Coupling Joining Hubless Cast-iron Soil Pipe and Fittings
705.3.3
C1440—2017: Specification for Thermoplastic Elastomeric (TPE) Gasket Materials for Drain, Waste, and Vent (DWV), Sewer, Sanitary
and Storm Plumbing Systems
705.16
C1460—2017: Specification for Shielded Transition Couplings for Use with Dissimilar DWV Pipe and Fittings Above Ground
705.16
C1461—2008(2017): Specification for Mechanical Couplings Using Thermoplastic Elastomeric (TPE) Gaskets for Joining Drain, Waste
and Vent (DWV) Sewer, Sanitary and Storm Plumbing Systems for Above and Below Ground Use
705.19
C1540—2018: Specification for Heavy Duty Shielded Couplings Joining Hubless Cast-iron Soil Pipe and Fittings
705.3.3
C1563—2008(2017): Standard Test Method for Gaskets for Use in Connection with Hub and Spigot Cast Iron Soil Pipe and Fittings for
Sanitary Drain, Waste, Vent and Storm Piping Applications
705.3.2
D1253—14: Standard Test Method For Residual Chlorine in Water
1301.2.1, 1303.9
D1527—99(2005): Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe, Schedules 40 and 80
Table 605.3
D1785—2015E1: Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe, Schedules 40, 80 and 120
Table 605.3
D2235—2004(2016): Specification for Solvent Cement for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe and Fittings
605.10.2, 705.2.2
D2239—12a: Specification for Polyethylene (PE) Plastic Pipe (SIDR-PR) Based on Controlled Inside Diameter
Table 605.3
D2241—15: Specification for Poly (Vinyl Chloride) (PVC) Pressure-rated Pipe (SDR-Series)
Table 605.3
D2282—99(2005): Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe (SDR-PR)
Table 605.3
D2464—15: Specification for Threaded Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
Table 605.5, 605.21.3
D2466—2017: Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 40
Table 605.5
D2467—15: Specification for Poly (Vinyl Chloride) (PVC) Plastic Pipe Fittings, Schedule 80
Table 605.5
2021 INTERNATIONAL PLUMBING CODE®
15-7
REFERENCED STANDARDS
ASTM—continued
D2468—96a: Specification for Acrylonitrile-Butadiene-Styrene (ABS) Plastic Pipe Fittings, Schedule 40
Table 605.5
D2564—2012(2018): Specification for Solvent Cements for Poly (Vinyl Chloride) (PVC) Plastic Piping Systems
605.21.3, 705.10.2, 705.14.2
D2609—15: Specification for Plastic Insert Fittings for Polyethylene (PE) Plastic Pipe
Table 605.5
D2657—2007(2015): Practice for Heat Fusion-joining of Polyolefin Pipe and Fitting Waste, and Vent Pipe and Fittings
605.18.2, 705.12.1
D2661—14E1: Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe and Fittings
Table 702.1, Table 702.2, Table 702.3, Table 702.4, 705.2.2, Table 1102.4, Table 1102.7
D2665—2014: Specification for Poly (Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings
Table 702.1, Table 702.2, Table 702.3, Table 702.4, Table 1102.4, Table 1102.7
D2672—14: Specification for Joints for IPS PVC Pipe Using Solvent Cement
Table 605.3
D2680―01(2014): Standard Specification for Acrylonitrile-Butadiene-Styrene (ABS) and Poly(Vinyl Chloride) (PVC) Composite Sewer
Piping
Table 702.3
D2683—14: Standard Specification for Socket-type Polyethylene Fittings for Outside Diameter-controlled Polyethylene Pipe and Tubing
Table 605.5, Table 702.4, 716.5
D2729—2017: Specification for Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings
Table 1102.5, Table 1403.2
D2737—2012a: Specification for Polyethylene (PE) Plastic Tubing
Table 605.3
D2751—05: Specification for Acrylonitrile-Butadiene-Styrene (ABS) Sewer Pipe and Fittings
Table 702.3, Table 702.4, Table 1102.7
D2846/D2846M—2017BE1: Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Hot- and Cold-Water Distribution
Systems
Table 605.3, Table 605.4, Table 605.5, 605.14.2, 605.15.2
D2855—2015: Standard Practice for Making Solvent-cemented Joints with Poly (Vinyl Chloride) (PVC) Pipe and Fittings
605.21.3, 705.10.2
D2949—10: Specification for 3.25-in. Outside Diameter Poly (Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings
Table 702.1, Table 702.2, Table 702.3, Table 702.4, Table 1102.7
D3034—2016: Specification for Type PSM Poly (Vinyl Chloride) (PVC) Sewer Pipe and Fittings
Table 702.3, Table 702.4, Table 1102.4, Table 1102.5, Table 1102.7
D3035—15: Standard Specification for Polyethylene (PE) Plastic Pipe (DR-PR) Based on Controlled Outside Diameter
Table 605.3
D3138—2016: Standard Specification for Solvent Cements for Transition Joints Between Acrylonitrile-Butadiene-Styrene (ABS) and
Poly (Vinyl Chloride) (PVC) Non-pressure Piping Components
705.16.4
D3139—98(2011): Specification for Joints for Plastic Pressure Pipes Using Flexible Elastomeric Seals
605.10.1, 605.22.1
D3212—07(2013): Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals
705.2.1, 705.10.1, 705.12.2, 705.15
D3261—2016: Specification for Butt Heat Fusion Polyethylene (PE) Plastic Fittings for Polyethylene (PE) Plastic Pipe and Tubing
Table 605.5
D3311—2017: Specification for Drain, Waste and Vent (DWV) Plastic Fittings Patterns
Table 1102.7
D4068—2017: Specification for Chlorinated Polyethlene (CPE) Sheeting for Concealed Water-containment Membrane
421.5.2.2
D4551—2017: Specification for Poly (Vinyl Chloride) (PVC) Plastic Flexible Concealed Water-containment Membrane
421.5.2.1
E2635—14: Standard Practice for Water Conservation Through In-Situ Water Reclamation
1302.1
15-8
2021 INTERNATIONAL PLUMBING CODE®
REFERENCED STANDARDS
ASTM—continued
E2727—2018: Standard Practice for the Assessment of Rainwater Quality
1303.15.9
F405—05: Specification for Corrugated Polyethylene (PE) Pipe and Fittings
Table 1102.5, Table 1403.2
F409—2017: Specification for Thermoplastic Accessible and Replaceable Plastic Tube and Tubular Fittings
412.1.2, Table 1102.7
F437—15: Specification for Threaded Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80
Table 605.5
F438—2017: Specification for Socket-type Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 40
Table 605.5
F439—13: Standard Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe Fittings, Schedule 80
Table 605.5
F441/F441M—15: Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe,Schedules 40 and 80
Table 605.3, Table 605.4
F442/F442M—13e1: Specification for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe (SDR-PR)
Table 605.3, Table 605.4
F477—14: Specification for Elastomeric Seals (Gaskets) for Joining Plastic Pipe
605.23, 705.16
F493—14: Specification for Solvent Cements for Chlorinated Poly (Vinyl Chloride) (CPVC) Plastic Pipe and Fittings
605.14.2, 605.15.2
F628—2012E2: Specification for Acrylonitrile-Butadiene-Styrene (ABS) Schedule 40 Plastic Drain, Waste, and Vent Pipe with a Cellular
Core
Table 702.1, Table 702.2, Table 702.3, Table 702.4, 705.2.2, Table 1102.4, Table 1102.7
F656—2015: Specification for Primers for Use in Solvent Cement Joints of Poly (Vinyl Chloride) (PVC) Plastic Pipe and Fittings
605.21.3, 705.10.2, 705.14.2
F667/F667M—2016: Standard Specification for 3 through 24 in. Corrugated Polyethylene Pipe and Fittings
Table 1102.4, Table 1102.5
F714—2013: Specification for Polyethylene (PE) Plastic Pipe (SDR-PR) Based on Outside Diameter
Table 702.3
F876—2017: Specification for Cross-linked Polyethylene (PEX) Tubing
Table 605.3, Table 605.4
F877—2018A: Specification for Cross-linked Polyethylene (PEX) Hot- and Cold-water Distribution Systems
Table 605.5
F891—2016: Specification for Coextruded Poly (Vinyl Chloride) (PVC) Plastic Pipe with a Cellular Core
Table 702.1, Table 702.2, Table 702.3, Table 1102.4, Table 1102.5, Table 1102.7
F1055—2016A: Standard Specification for Electrofusion Type Polyethylene Fittings for Outside Diameter Controlled Polyethylene and
Cross-linked Polyethylene Pipe and Tubing
Table 605.5
F1281—2017: Specification for Cross-linked Polyethylene/Aluminum/ Cross-linked Polyethylene (PEX-AL-PEX) Pressure Pipe
Table 605.3, Table 605.4, Table 605.5, 605.20.1, Table E105.1
F1282—2017: Specification for Polyethylene/Aluminum/Polyethylene (PE-AL-PE) Composite Pressure Pipe
Table 605.3, Table 605.4, Table 605.5, 605.20.1
F1412—2016: Specification for Polyolefin Pipe and Fittings for Corrosive Waste Drainage
Table 702.1, Table 702.2, Table 702.4, 705.13.1, 901.3
F1476—07(2013): Standard Specification for Performance of Gasketed Mechanical Couplings for Use in Piping Applications
Table 605.5, 605.13.3, 605.17.3, 605.22.2, 605.22.3
F1488—2014E1: Specification for Coextruded Composite Pipe
Table 702.1, Table 702.2, Table 702.3, Table 1102.4, Table 1403.2
F1504—2014: Standard Specification for Folded Poly (Vinyl Chloride) (PVC) for Existing Sewer and Conduit Rehabilitation
717.6
2021 INTERNATIONAL PLUMBING CODE®
15-9
REFERENCED STANDARDS
ASTM—continued
F1548—2001(2018): Standard Specification for the Performance of Fittings for Use with Gasketed Mechanical Couplings Used in Piping
Applications
Table 605.5
F1673—2010(2016): Standard Specification for Polyvinylidene Fluoride (PVDF) Corrosive Waste Drainage Systems
Table 702.1, Table 702.2, Table 702.3, Table 702.4, 705.14.1
F1807—2018: Specification for Metal Insert Fittings Utilizing a Copper Crimp Ring for SDR9 Cross-linked Polyethylene (PEX) Tubing
and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing
Table 605.5
F1866—2018: Specification for Poly (Vinyl Chloride) (PVC) Plastic Schedule 40 Drainage and DWV Fabricated Fittings
Table 702.4, Table 1102.7
F1871—2011: Standard Specification for Folded/Formed Poly (Vinyl Chloride) Pipe Type A for Existing Sewer and Conduit
Rehabilitation
717.6
F1960—2018: Specification for Cold Expansion Fittings with PEX Reinforcing Rings for Use with Cross-linked Polyethylene (PEX)
Tubing
Table 605.5
F1970—2018: Special Engineered Fittings, Appurtenances or Valves for Use in Poly (Vinyl Chloride) (PVC) OR Chlorinated Poly (Vinyl
Chloride) (CPVC) Systems
Table 605.7
F1974—09(2015): Specification for Metal Insert Fittings for Polyethylene/Aluminum/Polyethylene and Cross-linked Polyethylene/
Aluminum/Cross-linked Polyethylene Composite Pressure Pipe
Table 605.5, 605.20.1
F1986—2001(2011): Specification for Multilayer Pipe, Type 2, Compression Fittings and Compression Joints for Hot and Cold Drinking
Water Systems
Table 605.3, Table 605.4, Table 605.5
F2080—2016: Specifications for Cold-expansion Fittings with Metal Compression-sleeves for Cross-linked Polyethylene (PEX) Pipe
Table 605.5
F2098—2015: Standard Specification for Stainless Steel Clamps for Securing SDR9 Cross-linked Polyethylene (PEX) Tubing to Metal
Insert and Plastic Fittings
Table 605.5
F2159—2018: Specification for Plastic Insert Fittings Utilizing a Copper Crimp Ring for SDR9 Cross-linked Polyethylene (PEX) Tubing
and SDR9 Polyethylene of Raised Temperature (PE-RT) Tubing
Table 605.5
F2262—09: Specification for Cross-linked Polyethylene/Aluminum/Cross-linked Polyethylene Tubing OD Controlled SDR9
Table 605.3, Table 605.4
F2306/F2306M—2018: 12″ to 60″ Annular Corrugated Profile-wall Polyethylene (PE) Pipe and Fittings for Gravity Flow Storm Sewer
and Subsurface Drainage Applications
Table 1102.4, Table 1102.7
F2389—2017A: Specification for Pressure-rated Polypropylene (PP) Piping Systems
Table 605.3, Table 605.4, Table 605.5, Table 605.7, 605.19.1
F2434—14: Standard Specification for Plastic Insert Fittings Utilizing a Copper Crimp Ring for SDR9 Cross-linked Polyethylene (PEX)
Tubing and SDR9 Cross-linked Polyethylene/Aluminum/ Cross-linked Polyethylene (PEX AL-PEX) Tubing
Table 605.5
F2561—17: Standard Practice for Rehabilitation of a Sewer Service Lateral and its Connection to the Main Using a One Piece Main and
Lateral Cured-in-Place Liner
718.1
F2599—16: Standard Practice for The Sectional Repair of Damaged Pipe by Means of an Inverted Cured-in-Place Liner
718.1
F2648/F2648M—2017: Standard Specification for 2 to 60 inch [50 to 1500 mm] Annular Corrugated Profile Wall Polyethylene (PE) Pipe
and Fittings for Land Drainage Applications
Table 1102.4
F2735—2009(2016): Standard Specification for Plastic Insert Fittings for SDR9 Cross-linked Polyethylene (PEX) and Polyethylene of
Raised Temperature (PE-RT) Tubing
Table 605.5
15-10
2021 INTERNATIONAL PLUMBING CODE®
REFERENCED STANDARDS
ASTM—continued
F2736—13e1: Standard Specification for 6 to 30 in. [152 to 762 mm] Polypropylene (PP) Corrugated Single Wall Pipe and Double Wall
Pipe
Table 702.3
F2764/F2764M—2018: Standard Specification for 30 to 60 in. [750 to 1500 mm] Polypropylene (PP) Triple Wall Pipe and Fittings for
Non-pressure Sanitary Sewer Applications
Table 702.3
F2769—2018: Polyethylene or Raised Temperature (PE-RT) Plastic Hot- and Cold-water Tubing and Distribution Systems
Table 605.3, Table 605.4, Table 605.5
F2831—2012(2017): Standard Practice for Internal Non Structural Epoxy Barrier Coating Material Used in Rehabilitation of Metallic
Pressurized Piping Systems
601.5
F2855—12: Standard Specification for Chlorinated Poly (Vinyl Chloride)/Aluminum/Chlorinated Poly (Vinyl Chloride) (CPVC/AL/
CPVC) Composite Pressure Tubing
Table 605.3, Table 605.4
F2881/F2881M—2018: Standard Specification for 12 to 60 in. [300 to 1500 mm] Polypropylene (PP) Dual Wall Pipe and Fittings for Nonpressure Storm Sewer Applications
Table 1102.4
F3226/F3226M—16: Standard Specification for Metallic Press-Connect Fittings for Piping and Tubing Systems
Table 605.5
F3240—17: Standard Practice for Installation of Seamless Molded Hydrophilic Gaskets (SMHG) for Long Term Watertightness of
Cured-in-Place Rehabilitation of Main and Lateral Pipelines
718.1
AWS
American Welding Society
8669 NW 36 Street, #130
Miami, FL 33166
A5.8M/A5.8—2011-AMD1: Specifications for Filler Metals for Brazing and Braze Welding
605.12.1, 605.13.1, 705.5.1, 705.6.1
AWWA
American Water Works Association
6666 West Quincy Avenue
Denver, CO 80235
C104/A21.4—16: Cement-mortar Lining for Ductile-iron Pipe and Fittings
605.3, 605.5
C110/A21.10—12: Ductile-iron and Gray-iron Fittings
Table 605.5, Table 702.4, Table 1102.7
C111/A21.11—17: Rubber-gasket Joints for Ductile-iron Pressure Pipe and Fittings
605.11
C115/A21.15—11: Flanged Ductile-iron Pipe with Ductile-iron or Gray-iron Threaded Flanges
Table 605.3, Table 605.4
C151/A21.51—17: Ductile-iron Pipe, Centrifugally Cast for Water
Table 605.3, Table 605.4
C153—00/A21.53—11: Ductile-iron Compact Fittings for Water Service
Table 605.5
C500—09: Standard for Metal-seated Gate Valves for Water Supply Service
Table 605.7
C504—15: Standard for Rubber-Seated Butterfly Valves
Table 605.7
C507—15: Standard for Ball Valves, 6 In. Through 60 in. (150 mm through 1,500 mm).
Table 605.7
C510—17: Double Check Valve Backflow Prevention Assembly
Table 608.1, 608.14.7
2021 INTERNATIONAL PLUMBING CODE®
15-11
REFERENCED STANDARDS
AWWA—continued
C511—17: Reduced-pressure Principle Backflow Prevention Assembly
Table 608.1, 608.14.2, 608.17.2
C651—14: Disinfecting Water Mains
610.1
C652—11: Disinfection of Water-storage Facilities
610.1
C901—16: Polyethylene (PE) Pressure Pipe and Tubing 3/4 inch (19 mm) Through 3 inch (76 mm) for Water Service
Table 605.3
C904—16: Cross-linked Polyethylene (PEX) Pressure Tubing 1/2 inch (13 mm) Through 3 inch (76 mm) for Water Service
Table 605.3
CISPI
Cast Iron Soil Pipe Institute
2401 Fieldcrest Dr.
Mundelein, IL 60060
301—18: Specification for Hubless Cast-iron Soil Pipe and Fittings for Sanitary and Storm Drain, Waste and Vent Piping Applications
Table 702.1, Table 702.2, Table 702.3, Table 702.4, Table 1102.4, Table 1102.5, Table 1102.7
310—18: Specification for Coupling for Use in Connection with Hubless Cast-iron Soil Pipe and Fittings for Sanitary and Storm Drain,
Waste and Vent Piping Applications
705.3.3
CSA
CSA Group
8501 East Pleasant Valley Road
Cleveland, OH 44131-5516
A257.1—14: Non-reinforced Circular Concrete Culvert, Storm Drain, Sewer Pipe and Fittings
Table 702.3, Table 1102.4
A257.2—14: Reinforced Circular Concrete Culvert, Storm Drain, Sewer Pipe and Fittings
Table 702.3, Table 1102.4
A257.3—14: Joints for Circular Concrete Sewer and Culvert Pipe, Manhole Sections and Fittings Using Rubber Gaskets
705.4, 705.16
ASME A112.3.4—2020/CSA B45.9—20: Macerating Systems and Waste Pumping Systems for Plumbing Fixtures
405.5, 712.4.1
ASME A112.4.2—2020/CSA B45.16—20: Water Closet Personal Hygiene Devices
412.9
ASME A112.18.1—2018/CSA B125.1—18: Plumbing Supply Fittings
412.1, 412.2, 412.3, 412.4, 412.6, 412.8, Table 605.7, 607.4, 608.2
ASME A112.18.2—2015/CSA B125.2—2015: Plumbing Waste Fittings
412.1.2, 421.3.1
ASME A112.18.6—2021/CSA B125.6—21: Flexible Water Connectors
605.6
ASME A112.19.1—2020/CSA B45.2—20: Enameled Cast-iron and Enameled Steel Plumbing Fixtures
407.1, 410.1, 418.1, 419.1, 421.1, 422.1
ASME A112.19.2—2020/B45.1—2020: Ceramic Plumbing Fixtures
401.2, 405.10, 407.1, 408.1, 410.1, 418.1, 419.1, 421.1, 422.1, 424.1, 425.1
ASME A112.19.3—2021/CSA B45.4—2021: Stainless-steel Plumbing Fixtures
405.9, 407.1, 418.1, 419.1, 421.1, 425.1
ASME A112.19.5—2021/CSA B45.15—2021: Flush Valves and Spuds for Water Closets, Urinals and Tanks
415.4
ASME A112.19.7—2012/CSA B45.10—2012(R2021): Hydromassage Bathtub Systems
426.1, 426.4
ASSE 1002—2020/ASME A112.1002—2020/CSA B125.12—2020: Anti-Siphon Fill Valves for Water Closet Tanks
415.3.1, Table 608.1
15-12
2021 INTERNATIONAL PLUMBING CODE®
REFERENCED STANDARDS
CSA—continued
ASSE 1016—2020/ASME A112.1016—2020/CSA B125.16—2020: Performance Requirements for Automatic Compensating Valves for
Individual Showers and Tub/Shower Combinations
412.3, 412.4, 607.4
ASSE 1037—2015/ASME A112.1037—2015/CSA B125.37—15: Pressurized Flushing Devices for Plumbing Fixtures
415.2
ASSE 1070—2020/ASME A112.1070—2020/CSA B125.1070—20: Water Temperature Limiting Devices
408.3, 412.5, 412.10, 419.5, 423.3, 607.1.2
B64.1.1—11(R2016): Vacuum Breakers, Atmospheric Type (AVB)
415.2, Table 608.1, 608.14.6, 608.17.4.1
B64.1.2—11(R2016): Pressure Vacuum Breakers, (PVB)
Table 608.1, 608.14.5
B64.1.3—11(R2016): Spill Resistant Pressure Vacuum Breakers (SRPVB)
Table 608.1, 608.14.5
B64.2—11(R2016): Vacuum Breakers, Hose Connection Type (HCVB)
Table 608.1, 608.14.6
B64.2.1—11(2016): Vacuum Breakers, Hose Connection (HCVB) with Manual Draining Feature
Table 608.1, 608.14.6
B64.2.1.1—11(2016): Hose Connection Dual Check Vacuum Breakers (HCDVB)
Table 608.1, 608.14.6
B64.2.2—11(2016): Vacuum Breakers, Hose Connection Type (HCVB) with Automatic Draining Feature
Table 608.1, 608.14.6
B64.3—11(R2016): Backflow Preventers, Dual Check Valve Type with Atmospheric Port (DCAP)
Table 608.1, 608.14.3, 608.17.2
B64.4—11(R2016): Backflow Preventers, Reduced Pressure Principle Type (RP)
Table 608.1, 608.14.2, 608.17.2
B64.4.1—11(R2016): Reduced Pressure Principle for Fire Sprinklers (RPF)
Table 608.1, 608.14.2
B64.5—11(R2016): Double Check Backflow Preventers (DCVA)
Table 608.1, 608.14.7
B64.5.1—11(R2016): Double Check Valve Backflow Preventer for Fire Systems (DCVAF)
Table 608.1, 608.14.7
B64.6—11(R2016): Dual Check Valve (DuC) Backflow Preventers
605.3.1, Table 608.1, 608.14.9
B64.7—11(R2016): Laboratory Faucet Vacuum Breakers (LFVB)
Table 608.1, 608.14.6
B64.10—17: Manual for the Selection and Installation of Backflow Prevention Devices
312.10.2
B64.10.1—17: Maintenance and Field Testing of Backflow Preventers
312.10.2
B79—08(R2018): Commercial and Residential Drains and Cleanouts
413.1
B125.3—2018: Plumbing Fittings
408.3, 412.4, 412.5, 415.2, 415.3.1, 423.3, Table 605.7, Table 608.1
B137.1—17: Polyethylene (PE) Pipe, Tubing and Fittings for Cold-water Pressure Services
Table 605.3, Table 605.5
B137.2—17: Polyvinylchloride, PVC, Injection-moulded Gasketed Fittings for Pressure Applications
Table 605.5
B137.3—17: Rigid Poly (Vinyl Chloride) (PVC) Pipe for Pressure Applications
Table 605.3, Table 605.5, 605.21.3, 705.10.2, 705.14.2
B137.5—17: Cross-linked Polyethylene (PEX) Tubing Systems for Pressure Applications
Table 605.3, Table 605.4, Table 605.5
2021 INTERNATIONAL PLUMBING CODE®
15-13
REFERENCED STANDARDS
CSA—continued
B137.6—17: CPVC Pipe, Tubing and Fittings for Hot- and Cold-water Distribution Systems
Table 605.3, Table 605.4, Table 605.5
B137.9—17: Polyethylene Aluminum/Polyethylene (PE-AL-PE) Composite Pressure-pipe Systems
Table 605.3, Table 605.5, 605.20.1
B137.10—17: Cross-linked Polyethylene/Aluminum/Cross-linked Polyethylene (PEX-AL-PEX) Composite Pressure-pipe Systems
Table 605.3, Table 605.4, Table 605.5, 605.20.1
B137.11—17: Polypropylene (PP-R) Pipe and Fittings for Pressure Applications
Table 605.3, Table 605.4, Table 605.5
B137.18—17: Polyethylene of Raised Temperature Resistance (PE-RT) Tubing Systems for Pressure Applications
Table 605.3, Table 605.4, Table 605.5
B181.1—18: Acrylonitrile-Butadiene-Styrene ABS Drain, Waste and Vent Pipe and Pipe Fittings
Table 702.1, Table 702.2, Table 702.3, Table 702.4, 705.2.2, 714.2, Table 1102.4, Table 1102.7
B181.2—18: Polyvinylchloride PVC and Chlorinated Polyvinylchloride (CPVC) Drain, Waste, and Vent Pipe and Pipe Fittings
Table 702.1, Table 702.2, 705.10.2, 705.14.2, 714.2
B181.3—18: Polyolefin and Polyvinylidene Fluoride (PVDF) Laboratory Drainage Systems
Table 702.1, Table 702.2, Table 702.3, Table 702.4, 705.13.1
B182.1—18: Plastic Drain and Sewer Pipe and Pipe Fittings
705.10.2, 705.14.2, Table 1102.4, Table 1102.5
B182.2—18: PSM Type Polyvinylchloride PVC Sewer Pipe and Fittings
Table 702.3, Table 1102.4, Table 1102.5
B182.4—18: Profile Polyvinylchloride PVC Sewer Pipe and Fittings
Table 702.3, Table 1102.4, Table 1102.5
B182.6—18: Profile Polyethylene (PE) Sewer Pipe and Fittings for Leak-proof Sewer Applications
Table 1102.5
B182.8—18: Profile Polyethylene (PE) Storm Sewer and Drainage Pipe and Fittings
Table 1102.5
B182.13—18: Profile Polypropylene (PP) Sewer Pipe and Fittings for Leak-proof Sewer Applications
Table 702.3, Table 1102.4
B356—10(R2015): Water Pressure Reducing Valves for Domestic Water Systems
604.8
B481.1—12(R2017): Testing and Rating of Grease Interceptors Using Lard
1003.3.4
B481.3—12(R2017): Sizing, Selection, Location and Installation of Grease Interceptors
1003.3.5
B483.1—07(R2017): Drinking Water Treatment Systems
611.1, 611.2
B602—16: Mechanical Couplings for Drain, Waste and Vent Pipe and Sewer Pipe
705.2.1, 705.3.3, 705.5, 705.10.1, 705.11, 705.12.2, 705.16
CSA B45.5—17/IAPMO Z124—2017 with errata dated August 2017: Plastic Plumbing Fixtures
407.1, 418.1, 419.1, 419.2, 421.1, 422.1, 424.1, 425.1, 425.1.2
CSA B805-18/ICC 805-2018: Rainwater Harvesting Systems
1301.1
IAPMO
IAPMO Group
4755 E. Philadelphia Street
Ontario, CA 91761 USA
ASPE/IAPMO Z1034—2015: Test Method for Evaluating Roof Drain Performance
1102.6
CSA B45.5—17/IAPMO Z124—2017 with errata dated August 2017: Plastic Plumbing Fixtures
407.1, 418.1, 419.1, 419.2, 421.1, 422.1, 424.1, 425.1, 425.1.2
15-14
2021 INTERNATIONAL PLUMBING CODE®
REFERENCED STANDARDS
IAPMO—continued
IAPMO/ANSI Z1157—2014e1: Ball Valves
Table 605.7
Z1001—2016: Prefabricated Gravity Grease Interceptors
1003.3.7
ICC
International Code Council, Inc.
500 New Jersey Ave, NW 6th Floor
Washington, DC 20001
CSA B805—18/ICC 805—2018: Rainwater Harvesting Systems
1301.1
IBC—21: International Building Code®
201.3, 202, 307.1, 307.2, 307.3, 308.2, 309.1, 309.2, 310.1, 310.3, 315.1, 403.1, Table 403.1, 403.1.2,
403.3.1, 403.4, 404.1, 407.3, 421.6, 502.4, 606.5.2, 1106.5, 1301.9.3, 1303.6, 1402.1
ICC 900/SRCC 300—2020: Solar Thermal System Standard
502.1
ICC A117.1—17: Accessible and Usable Buildings and Facilities
404.2, 410.3
IEBC—21: International Existing Building Code®
102.2.1
IECC—21: International Energy Conservation Code®
313.1, 607.2.1, 607.5
IFC—21: International Fire Code®
201.3, 1201.1
IFGC—21: International Fuel Gas Code®
101.2, 201.3, 502.1, 502.1.1
IMC—21: International Mechanical Code®
201.3, 307.6, 310.1, 502.1, 502.1.1, 612.1, 1202.1
IPSDC—21: International Private Sewage Disposal Code®
701.2
IRC—21: International Residential Code®
101.2
ISEA
International Safety Equipment Association
1901 N. Moore Street, Suite 808
Arlington, VA 22209
ANSI/ISEA Z358.1—2014: Emergency Eyewash and Shower Equipment
411.1
MSS
Manufacturers Standardization Society of the Valve and Fittings Industry, Inc.
127 Park St. NE
Vienna, VA 22180-4602
SP-67—2011: Butterfly Valves
Table 605.7
SP-70—2013: Gray Iron Gate Valves, Flanged and Threaded Ends
Table 605.7
SP-71—2018: Gray Iron Swing Check Valves, Flanged and Threaded Ends
Table 605.7
SP-72—2010a: Ball Valves with Flanged or Butt-welding Ends for General Service
Table 605.7
SP-78—2011: Cast Iron Plug Valves, Flanged and Threaded Ends
Table 605.7
2021 INTERNATIONAL PLUMBING CODE®
15-15
REFERENCED STANDARDS
MSS—continued
SP-80—2013: Bronze Gate, Globe, Angle and Check Valves
Table 605.7
SP-110—2010: Ball Valves, Threaded, Socket Welding, Solder Joint, Grooved and Flared Ends (incl. a 2010 Errata Sheet)
Table 605.7
SP-122—2017: Plastic Industrial Ball Valves
Table 605.7
SP-139—2014: Copper Alloy Gate, Globe, Angle and Check Valves for Low Pressure/Low Temperature Plumbing Applications
Table 605.7
NFPA
National Fire Protection Association
1 Batterymarch Park
Quincy, MA 02169-7471
51—18: Design and Installation of Oxygen-fuel Gas Systems for Welding, Cutting and Allied Processes
1203.1
55—19: Compressed Gases and Cryogenic Fluids Code
1203.1
70—20: National Electrical Code
502.1, 504.3, 1113.1.3
99—21: Health Care Facilities Code
1202.1
NGWA
National Ground Water Association
601 Dempsey Road
Westerville, OH 43081
NGWA/ANSI 01—14: Water Well Construction Standard
602.3.1
NSF
NSF International
789 N. Dixboro Road P.O. Box 130140
Ann Arbor, MI 48105
3—2017: Commercial Warewashing Equipment
409.1
14—2018: Plastic Piping System Components and Related Materials
303.3, 611.3
18—2016: Manual Food and Beverage Dispensing Equipment
426.1
42—2018: Drinking Water Treatment Units-Aesthetic Effects
611.1, 611.3
44—2018: Residential Cation Exchange Water Softeners
611.1, 611.3
50—2017: Equipment for Swimming Pools, Spas, Hot Tubs and Other Recreational Facilities
1302.8.1
53—2017: Drinking Water Treatment Units—Health Effects
611.1, 611.3
58—2017: Reverse Osmosis Drinking Water Treatment Systems
611.1, 611.2, 611.3
61—2018: Drinking Water System Components—Health Effects
410.1, 412.1, 605.3, 605.4, 605.5, 605.7, 605.12.3, 605.13.6, 608.12, 611.3
62—2017: Drinking Water Distillation Systems
611.1
15-16
2021 INTERNATIONAL PLUMBING CODE®
REFERENCED STANDARDS
NSF—continued
184—2014: Residential Dishwashers
409.1
350—2017a: Onsite Residential and Commercial Water Reuse Treatment Systems
1302.6.1
359—2018: Valves for Cross-linked Polyethylene (PEX) Water Distribution Tubing Systems
Table 605.7
372—2016: Drinking Water Systems Components—Lead Content
605.2.1
PDI
Plumbing and Drainage Institute
800 Turnpike Street, Suite 300
North Andover, MA 01845
PDI G101 (2012): Testing and Rating Procedure for Grease Interceptors with Appendix of Sizing and Installation Data
1003.3.5
PDI G102 (2009): Testing and Certification for Grease Interceptors with Fog Sensing and Alarm Devices
1003.3.5
PSAI
Portable Sanitation Association International
2626 E. 82nd Street, Suite 175
Bloomington, MN 55425
PSAI/ANSI Z4.3—16: Minimum Requirements for Nonsewered Waste-disposal Systems
311.1
UL
UL LLC
333 Pfingsten Road
Northbrook, IL 60062-2096
399—2017: Drinking-Water Coolers—with revisions through August 2018
410.1
430—2015: Waste Disposers—with revisions through February 2018
416.1
508—2018: Industrial Control Equipment
314.2.3
1795—2016: Hydromassage Bathtubs—with revisions through December 2017
426.1
2021 INTERNATIONAL PLUMBING CODE®
15-17
15-18
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX A
PLUMBING PERMIT FEE SCHEDULE
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
User note:
About this appendix: Appendix A provides an example of a permit fee schedule that can be used by a jurisdiction.
TABLE A101
EXAMPLE OF PERMIT FEE SCHEDULE
Permit Issuance
1. For issuing each permit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . $ ______
2. For issuing each supplemental permit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
Unit Fee Schedule
1. For each plumbing fixture or trap or set of fixtures on one trap
(including water, drainage piping and backflow protection thereof). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
2. For each building sewer and each trailer park sewer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
3. Rainwater systems—per drain (inside building) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
4. For each cesspool (where permitted) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
5. For each private sewage disposal system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
6. For each water heater and/or vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
7. For each industrial waste pretreatment interceptor including its trap and vent,
excepting kitchen-type grease interceptors functioning as fixture traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
8. For installation, alteration or repair of water-piping and/or water-treating equipment, each . . . . . . . . . . . . . . _______
9. For repair or alteration of drainage or vent piping, each fixture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
10. For each lawn sprinkler system on any one meter including backflow protection devices therefor . . . . . . . . . _______
11. For atmospheric-type vacuum breakers not included in Item 2:
1 to 5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
over 5, each . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
12. For each backflow protective device other than atmospheric-type vacuum breakers:
2 inches (51 mm) and smaller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
Over 2 inches (51 mm). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _______
Other Inspections and Fees
1. Inspections outside of normal business hours (minimum charge 2 hours) . . . . . . . . . . . . . . . . . . . . . . . _____ per hour
2. Reinspection fee assessed under provisions of Section 108.4.3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _____ each
3. Inspections for which no fee is specifically indicated (minimum charge one-half hour) . . . . . . . . . . . . _____ per hour
4. Additional plan review required by changes, additions or revisions to approved plans
(minimum charge one-half hour) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . _____ per hour
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX A-1
APPENDIX A-2
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX B
RATES OF RAINFALL FOR VARIOUS CITIES
This appendix is informative and is not part of the code.
User note:
About this appendix: The design of storm water drainage systems (Chapter 11) requires determination of the design rainfall event for the
geographic location of the building. Appendix B provides a list of major cities in the U.S. along with the 1-hour duration, 100-year occurrence rainfall rate.
TABLE B101
RATES OF RAINFALL FOR VARIOUS CITIESa
Alabama:
Birmingham
3.8
Huntsville
3.6
Mobile
4.6
Montgomery
4.2
Alaska:
Fairbanks
1.0
Juneau
0.6
Arizona:
Flagstaff
2.4
Nogales
3.1
Phoenix
2.5
Yuma
1.6
Connecticut:
3.7
Texarkana
3.8
1.4
Crescent City
1.5
Fresno
1.1
Los Angeles
2.1
Needles
1.6
Placerville
1.5
San Fernando
2.3
San Francisco
1.5
Yreka
1.4
1.5
Denver
2.4
Durango
1.8
Grand Junction
1.7
Lamar
3.0
Pueblo
2.5
2.6
Georgetown
3.0
Wilmington
3.1
3.2
Florida:
Jacksonville
4.3
Key West
4.3
Miami
4.7
Pensacola
4.6
Tampa
4.5
Georgia:
Atlanta
3.7
Dalton
3.4
Macon
3.9
Savannah
4.3
Thomasville
4.3
Hawaii:
Hilo
6.2
Honolulu
3.0
Wailuku
3.0
Idaho:
Colorado:
Craig
Putnam
Washington
California:
Barstow
2.8
District of Columbia:
3.6
Little Rock
2.7
New Haven
Delaware:
Arkansas:
Fort Smith
Hartford
Boise
0.9
Lewiston
1.1
Pocatello
1.2
Illinois:
Cairo
3.3
Chicago
3.0
Peoria
3.3
Rockford
3.2
Springfield
3.3
(continued)
2021 INTERNATIONAL PLUMBING CODE
®
APPENDIX B-1
APPENDIX B—RATES OF RAINFALL FOR VARIOUS CITIES
TABLE B101—continued
RATES OF RAINFALL FOR VARIOUS CITIESa
Indiana:
Minnesota:
Evansville
3.2
Duluth
2.8
Fort Wayne
2.9
Grand Marais
2.3
Indianapolis
3.1
Minneapolis
3.1
Moorhead
3.2
Worthington
3.5
Iowa:
Davenport
3.3
Des Moines
3.4
Dubuque
3.3
Biloxi
4.7
Sioux City
3.6
Columbus
3.9
Corinth
3.6
Natchez
4.4
Vicksburg
4.1
Kansas:
Atwood
3.3
Dodge City
3.3
Topeka
3.7
Wichita
3.7
Kentucky:
Mississippi:
Missouri:
Columbia
3.2
Kansas City
3.6
Ashland
3.0
Springfield
3.4
Lexington
3.1
St. Louis
3.2
Louisville
3.2
Montana:
Middlesboro
3.2
Ekalaka
Paducah
3.3
Havre
1.6
Helena
1.5
Louisiana:
2.5
Alexandria
4.2
Kalispell
1.2
Lake Providence
4.0
Missoula
1.3
New Orleans
4.8
Nebraska:
Shreveport
3.9
Maine:
Bangor
2.2
Houlton
2.1
Portland
2.4
Maryland:
North Platte
3.3
Omaha
3.8
Scottsbluff
3.1
Valentine
3.2
Nevada:
Elko
1.0
3.2
Ely
1.1
Hagerstown
2.8
Las Vegas
1.4
Oakland
2.7
Reno
1.1
Salisbury
3.1
Baltimore
Massachusetts:
New Hampshire:
Berlin
2.5
Boston
2.5
Concord
2.5
Pittsfield
2.8
Keene
2.4
Worcester
2.7
Michigan:
New Jersey:
Atlantic City
2.9
Alpena
2.5
Newark
3.1
Detroit
2.7
Trenton
3.1
Grand Rapids
2.6
Lansing
2.8
Albuquerque
2.0
Marquette
2.4
Hobbs
3.0
Sault Ste. Marie
2.2
Raton
2.5
New Mexico:
(continued)
APPENDIX B-2
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX B—RATES OF RAINFALL FOR VARIOUS CITIES
TABLE B101—continued
RATES OF RAINFALL FOR VARIOUS CITIESa
New Mexico: (continued)
South Carolina:
Roswell
2.6
Charleston
4.3
Silver City
1.9
Columbia
4.0
Greenville
4.1
New York:
Albany
2.5
Binghamton
2.3
Buffalo
Buffalo
2.3
Huron
3.3
Kingston
2.7
Pierre
3.1
New York
3.0
Rapid City
2.9
Rochester
2.2
Yankton
3.6
North Carolina:
Asheville
South Dakota:
2.8
Tennessee:
4.1
Chattanooga
Charlotte
3.7
Knoxville
3.2
Greensboro
3.4
Memphis
3.7
Wilmington
4.2
Nashville
3.3
North Dakota:
3.5
Texas:
Bismarck
2.8
Abilene
3.6
Devils Lake
2.9
Amarillo
3.5
Fargo
3.1
Brownsville
4.5
Williston
2.6
Dallas
4.0
Ohio:
Del Rio
4.0
2.9
El Paso
2.3
Cleveland
2.6
Houston
4.6
Columbus
2.8
Lubbock
3.3
Toledo
2.8
Odessa
3.2
Pecos
3.0
San Antonio
4.2
Cincinnati
Oklahoma:
Altus
3.7
Boise City
3.3
Utah:
Durant
3.8
Brigham City
1.2
Oklahoma City
3.8
Roosevelt
1.3
Oregon:
Baker
0.9
Salt Lake City
1.3
St. George
1.7
Coos Bay
1.5
Vermont:
Eugene
1.3
Barre
Portland
1.2
Bratteboro
2.7
Burlington
2.1
2.5
Pennsylvania:
2.3
Erie
2.6
Rutland
Harrisburg
2.8
Virginia:
Philadelphia
3.1
Bristol
2.7
Pittsburgh
2.6
Charlottesville
2.8
Scranton
2.7
Lynchburg
3.2
Norfolk
3.4
3.3
Rhode Island:
Block Island
2.75
Richmond
Providence
2.6
Washington:
Omak
1.1
(continued)
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX B-3
APPENDIX B—RATES OF RAINFALL FOR VARIOUS CITIES
TABLE B101—continued
RATES OF RAINFALL FOR VARIOUS CITIESa
Washington: (continued)
Port Angeles
1.1
Seattle
1.4
Spokane
1.0
Yakima
1.1
West Virginia:
Charleston
2.8
Morgantown
2.7
Wisconsin:
Ashland
2.5
Eau Claire
2.9
Green Bay
2.6
La Crosse
3.1
Madison
3.0
Milwaukee
3.0
Wyoming:
Cheyenne
2.2
Fort Bridger
1.3
Lander
1.5
New Castle
2.5
Sheridan
1.7
Yellowstone Park
1.4
a. Rainfall rates, in inches per hour, are based on a storm of 1-hour duration
and a 100-year return period. The rainfall rates shown in the appendix are
derived from Figures 1106.1(1) through 1106.1(5).
APPENDIX B-4
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX C
STRUCTURAL SAFETY
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
User note:
About this appendix: The installation of plumbing systems frequently requires piping to pass through building framing members. Appendix
C provides the regulations for limits on the sizes and locations of holes that can be drilled or punched in various types of framing members.
SECTION C101
CUTTING, NOTCHING AND BORING IN WOOD
MEMBERS
[BS] C101.1 Joist notching. Notches on the ends of joists
shall not exceed one-fourth the joist depth. Holes bored in
joists shall not be within 2 inches (51 mm) of the top or
bottom of the joist, and the diameter of any such hole shall
not exceed one-third the depth of the joist. Notches in the top
or bottom of joists shall not exceed one-sixth the depth and
shall not be located in the middle third of the span.
not be cut or notched. Holes in webs of nonstructural coldformed steel wall studs shall be permitted along the centerline of the web of the framing member, shall not exceed 11/2
inches (38 mm) in width or 4 inches (102 mm) in length, and
the holes shall not be spaced less than 24 inches (610 mm)
center to center from another hole or less than 10 inches (254
mm) from the bearing end.
[BS] C101.2 Stud cutting and notching. In exterior walls
and bearing partitions, a wood stud shall not be cut or
notched in excess of 25 percent of its depth. In nonbearing
partitions that do not support loads other than the weight of
the partition, a stud shall not be cut or notched in excess of
40 percent of its depth.
[BS] C101.3 Bored holes. The diameter of bored holes in
wood studs shall not exceed 40 percent of the stud depth.
The diameter of bored holes in wood studs shall not exceed
60 percent of the stud depth in nonbearing partitions. The
diameter of bored holes in wood studs shall not exceed 60
percent of the stud depth in any wall where each stud is
doubled, provided that not more than two such successive
doubled studs are so bored. The edge of the bored hole shall
be not closer than 5/8 inch (15.9 mm) to the edge of the stud.
Bored holes shall not be located at the same section of stud
as a cut or notch.
[BS] C101.4 Cutting, notching and boring holes in structural steel framing. The cutting, notching and boring of
holes in structural steel framing members shall be as
prescribed by the registered design professional.
[BS] C101.5 Cutting, notching and boring holes in coldformed steel framing. Flanges and lips of load-bearing
cold-formed steel framing members shall not be cut or
notched. Holes in webs of load-bearing cold-formed steel
framing members shall be permitted along the centerline of
the web of the framing member and shall not exceed the
dimensional limitations, penetration spacing or minimum
hole edge distance as prescribed by the registered design
professional. Cutting, notching and boring holes of steel
floor/roof decking shall be as prescribed by the registered
design professional.
[BS] C101.6 Cutting, notching and boring holes in
nonstructural cold-formed steel wall framing. Flanges
and lips of nonstructural cold-formed steel wall studs shall
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX C-1
APPENDIX C-2
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX D
DEGREE DAY AND DESIGN TEMPERATURES
This appendix is informative and is not part of the code.
User note:
About this appendix: This code refers to the 97.5-percent winter design temperature for directing the code user to requirements for design
of the plumbing system. Appendix D provides such temperatures for many major cities in the United States.
TABLE D101
DEGREE DAY AND DESIGN TEMPERATURESa FOR CITIES IN THE UNITED STATES
DESIGN TEMPERATURES
STATE
AL
AK
AZ
HEATING DEGREE
DAYS (yearly total)
STATIONb
CA
Summer
1
1
DEGREES NORTH
LATITUDEc
97 /2%
Dry bulb 2 /2%
Wet bulb 2 /2%
2,551
21
94
77
33°30′
Huntsville
3,070
16
96
77
34°40′
Mobile
1,560
29
93
79
30°40′
Montgomery
2,291
25
95
79
32°20′
Anchorage
10,864
-18
68
59
61°10′
Fairbanks
14,279
-47
78
62
64°50′
Juneau
9,075
1
70
59
58°20′
Nome
14,171
-27
62
56
64°30′
Flagstaff
7,152
4
82
60
35°10′
Phoenix
1,765
34
107
75
33°30′
Tucson
1,800
32
102
71
33°10′
974
39
109
78
32°40′
Fort Smith
3,292
17
98
79
35°20′
Little Rock
3,219
20
96
79
34°40′
Texarkana
2,533
23
96
79
33°30′
Fresno
2,611
30
100
71
36°50′
Long Beach
1,803
43
80
69
33°50′
Los Angeles
2,061
43
80
69
34°00′
Los Angelesd
1,349
40
89
71
34°00′
Oakland
2,870
36
80
64
37°40′
Sacramento
2,502
32
98
71
38°30′
San Diego
1,458
44
80
70
32°40′
San Francisco
3,015
38
77
64
37°40′
d
CO
1
Birmingham
Yuma
AR
Winter
San Francisco
3,001
40
71
62
37°50′
Alamosa
8,529
-16
82
61
37°30′
Colorado Springs
6,423
2
88
62
38°50′
Denver
6,283
1
91
63
39°50′
Grand Junction
5,641
7
94
63
39°10′
Pueblo
5,462
0
95
66
38°20′
Bridgeport
5,617
9
84
74
41°10′
CT
Hartford
6,235
7
88
75
41°50′
New Haven
5,897
7
84
75
41°20′
DE
Wilmington
4,930
14
89
76
39°40′
DC
Washington
4,224
17
91
77
38°50′
(continued)
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX D-1
APPENDIX D—DEGREE DAY AND DESIGN TEMPERATURES
TABLE D101—continued
DEGREE DAY AND DESIGN TEMPERATURESa FOR CITIES IN THE UNITED STATES
DESIGN TEMPERATURES
STATE
STATIONb
Daytona
FL
IL
IN
IA
KS
Summer
1
1
DEGREES NORTH
LATITUDEc
97 /2%
Dry bulb 2 /2%
Wet bulb 2 /2%
35
90
79
29°10′
442
44
92
79
26°40′
1,239
32
94
79
30°30′
Key West
108
57
90
79
24°30′
Miami
214
47
90
79
25°50′
Orlando
766
38
93
78
28°30′
Pensacola
1,463
29
93
79
30°30′
Tallahassee
1,485
30
92
78
30°20′
683
40
91
79
28°00′
253
45
91
79
26°40′
2,929
22
92
77
34°00′
Athens
ID
1
Jacksonville
West Palm Beach
HI
879
Winter
Fort Myers
Tampa
GA
HEATING DEGREE
DAYS (yearly total)
Atlanta
2,961
22
92
76
33°40′
Augusta
2,397
23
95
79
33°20′
Columbus
2,383
24
93
78
32°30′
Macon
2,136
25
93
78
32°40′
Rome
3,326
22
93
78
34°20′
Savannah
1,819
27
93
79
32°10′
Hilo
0
62
83
74
19°40′
Honolulu
0
63
86
75
21°20′
Boise
5,809
10
94
66
43°30′
Lewiston
5,542
6
93
66
46°20′
Pocatello
7,033
-1
91
63
43°00′
Chicago
(Midway)
6,155
0
91
75
41°50′
Chicago (O’Hare)
6,639
-4
89
76
42°00′
d
Chicago
5,882
2
91
77
41°50′
Moline
6,408
-4
91
77
41°30′
Peoria
6,025
-4
89
76
40°40′
Rockford
6,830
-4
89
76
42°10′
Springfield
5,429
2
92
77
39°50′
Evansville
4,435
9
93
78
38°00′
Fort Wayne
6,205
1
89
75
41°00′
Indianapolis
5,699
2
90
76
39°40′
South Bend
6,439
1
89
75
41°40′
Burlington
6,114
-3
91
77
40°50′
Des Moines
6,588
-5
91
77
41°30′
Dubuque
7,376
-7
88
75
42°20′
Sioux City
6,951
-7
92
77
42°20′
Waterloo
7,320
-10
89
77
42°30′
Dodge City
4,986
5
97
73
37°50′
Goodland
6,141
0
96
70
39°20′
Topeka
5,182
4
96
78
39°00′
Wichita
4,620
7
98
76
37°40′
(continued)
APPENDIX D-2
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX D—DEGREE DAY AND DESIGN TEMPERATURES
TABLE D101—continued
DEGREE DAY AND DESIGN TEMPERATURESa FOR CITIES IN THE UNITED STATES
DESIGN TEMPERATURES
STATE
STATIONb
HEATING DEGREE
DAYS (yearly total)
Covington
KY
LA
ME
MD
MA
MI
MN
MS
MO
MT
5,265
Winter
1
Summer
1
1
97 /2%
Dry bulb 2 /2%
Wet bulb 2 /2%
6
90
75
DEGREES NORTH
LATITUDEc
39°00′
Lexington
4,683
8
91
76
38°00′
Louisville
4,660
10
93
77
38°10′
Alexandria
1,921
27
94
79
31°20′
Baton Rouge
1,560
29
93
80
30°30′
Lake Charles
1,459
31
93
79
30°10′
New Orleans
1,385
33
92
80
30°00′
Shreveport
2,184
25
96
79
32°30′
Caribou
9,767
-13
81
69
46°50′
Portland
7,511
-1
84
72
43°40′
Baltimore
4,654
13
91
77
39°10′
d
Baltimore
4,111
17
89
78
39°20′
Frederick
5,087
12
91
77
39°20′
Boston
5,634
9
88
74
42°20′
Pittsfield
7,578
-3
84
72
42°30′
Worcester
6,969
4
84
72
42°20′
Alpena
8,506
-6
85
72
45°00′
Detroit (City)
6,232
6
88
74
42°20′
Escanabad
8,481
-7
83
71
45°40′
Flint
7,377
1
87
74
43°00′
Grand Rapids
6,894
5
88
74
42°50′
Lansing
6,909
1
87
74
42°50′
Marquetted
8,393
-8
81
70
46°30′
Muskegon
6,696
6
84
73
43°10′
Sault Ste. Marie
9,048
-8
81
70
46°30′
Duluth
10,000
-16
82
70
46°50′
Minneapolis
8,382
-12
89
5
44°50′
Rochester
8,295
-12
87
75
44°00′
Jackson
2,239
25
95
78
32°20′
Meridian
2,289
23
95
79
32°20′
Vicksburgd
2,041
26
95
80
32°20′
Columbia
5,046
4
94
77
39°00′
Kansas City
4,711
6
96
77
39°10′
St. Joseph
5,484
2
93
79
39°50′
St. Louis
4,900
6
94
77
38°50′
St. Louisd
4,484
8
94
77
38°40′
Springfield
4,900
9
93
77
37°10′
Billings
7,049
-10
91
66
45°50′
Great Falls
7,750
-15
88
62
47°30′
Helena
8,129
-16
88
62
46°40′
Missoula
8,125
-6
88
63
46°50′
(continued)
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX D-3
APPENDIX D—DEGREE DAY AND DESIGN TEMPERATURES
TABLE D101—continued
DEGREE DAY AND DESIGN TEMPERATURESa FOR CITIES IN THE UNITED STATES
DESIGN TEMPERATURES
STATIONb
STATE
Grand Island
d
NE
NV
NH
NJ
NM
NY
NC
ND
HEATING DEGREE
DAYS (yearly total)
6,530
Winter
1
Summer
1
1
97 /2%
Dry bulb 2 /2%
Wet bulb 2 /2%
-3
94
74
DEGREES NORTH
LATITUDEc
41°00′
Lincoln
5,864
-2
95
77
40°50′
Norfolk
6,979
-4
93
77
42°00′
North Platte
6,684
-4
94
72
41°10′
Omaha
6,612
-3
91
77
41°20′
Scottsbluff
6,673
-3
92
68
41°50′
Elko
7,433
-2
92
62
40°50′
Ely
7,733
-4
87
59
39°10′
Las Vegas
2,709
28
106
70
36°10′
Reno
6,332
10
92
62
39°30′
Winnemucca
6,761
3
94
62
40°50′
Concord
7,383
-3
87
73
43°10′
Atlantic City
4,812
13
89
77
39°30′
Newark
4,589
14
91
76
40°40′
Trentond
4,980
14
88
76
40°10′
Albuquerque
4,348
16
94
65
35°00′
Raton
6,228
1
89
64
36°50′
Roswell
3,793
18
98
70
33°20′
Silver City
3,705
10
94
64
32°40′
Albany
6,875
-1
88
74
42°50′
Albanyd
6,201
1
88
74
42°50′
Binghamton
7,286
1
83
72
42°10′
Buffalo
7,062
6
85
73
43°00′
NY (Central
Park)d
4,871
15
89
75
40°50′
NY (Kennedy)
5,219
15
87
75
40°40′
NY(LaGuardia)
4,811
15
89
75
40°50′
Rochester
6,748
5
88
73
43°10′
Schenectadyd
6,650
1
87
74
42°50′
Syracuse
6,756
2
87
73
43°10′
Charlotte
3,181
22
93
76
35°10′
Greensboro
3,805
18
91
76
36°10′
Raleigh
3,393
20
92
77
35°50′
Winston-Salem
3,595
20
91
75
36°10′
Bismarck
8,851
-19
91
71
46°50′
Devils Laked
9,901
-21
88
71
48°10′
Fargo
9,226
-18
89
74
46°50′
Williston
9,243
-21
88
70
48°10′
(continued)
APPENDIX D-4
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX D—DEGREE DAY AND DESIGN TEMPERATURES
TABLE D101—continued
DEGREE DAY AND DESIGN TEMPERATURESa FOR CITIES IN THE UNITED STATES
DESIGN TEMPERATURES
STATIONb
STATE
HEATING DEGREE
DAYS (yearly total)
Akron-Canton
d
OH
OK
OR
PA
SC
SD
TN
1
Summer
1
1
97 /2%
Dry bulb 2 /2%
Wet bulb 2 /2%
6
86
73
DEGREES NORTH
LATITUDEc
41°00′
Cincinnati
4,410
6
90
75
39°10′
Cleveland
6,351
5
88
74
41°20′
Columbus
5,660
5
90
75
40°00′
Dayton
5,622
4
89
75
39°50′
Mansfield
6,403
5
87
74
40°50′
Sanduskyd
5,796
6
91
74
41°30′
Toledo
6,494
1
88
75
41°40′
Youngstown
6,417
4
86
73
41°20′
Oklahoma City
3,725
13
97
77
35°20′
Tulsa
3,860
13
98
78
36°10′
Eugene
4,726
22
89
67
44°10′
Medford
5,008
23
94
68
42°20′
Portland
4,635
23
85
67
45°40′
Portlandd
4,109
24
86
67
45°30′
Salem
4,754
23
88
68
45°00′
Allentown
5,810
9
88
75
40°40′
Erie
6,451
9
85
74
42°10′
Harrisburg
5,251
11
91
76
40°10′
Philadelphia
5,144
14
90
76
39°50′
Pittsburgh
5,987
5
86
73
40°30′
d
RI
6,037
Winter
Pittsburgh
5,053
7
88
73
40°30′
Readingd
4,945
13
89
75
40°20′
Scranton
6,254
5
87
73
41°20′
Williamsport
5,934
7
89
74
41°10′
Providence
5,954
9
86
74
41°40′
Charleston
2,033
27
91
80
32°50′
Charlestond
1,794
28
92
80
32°50′
Columbia
2,484
24
95
78
34°00′
Huron
8,223
-14
93
75
44°30′
Rapid City
7,345
-7
92
69
44°00′
Sioux Falls
7,839
-11
91
75
43°40′
Bristol
4,143
14
89
75
36°30′
Chattanooga
3,254
18
93
77
35°00′
Knoxville
3,494
19
92
76
35°50′
Memphis
3,232
18
95
79
35°00′
Nashville
3,578
14
94
77
36°10′
(continued)
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX D-5
APPENDIX D—DEGREE DAY AND DESIGN TEMPERATURES
TABLE D101—continued
DEGREE DAY AND DESIGN TEMPERATURESa FOR CITIES IN THE UNITED STATES
DESIGN TEMPERATURES
STATE
TX
STATIONb
HEATING DEGREE
DAYS (yearly total)
Winter
1
Summer
1
1
DEGREES NORTH
LATITUDEc
97 /2%
Dry bulb 2 /2%
Wet bulb 2 /2%
Abilene
2,624
20
99
74
32°30′
Austin
1,711
28
98
77
30°20′
Dallas
2,363
22
100
78
32°50′
El Paso
2,700
24
98
68
31°50′
Houston
1,396
32
94
79
29°40′
Midland
2,591
21
98
72
32°00′
San Angelo
2,255
22
99
74
31°20′
San Antonio
1,546
30
97
76
29°30′
Waco
2,030
26
99
78
31°40′
Wichita Falls
2,832
18
101
76
34°00′
UT
Salt Lake City
6,052
8
95
65
40°50′
VT
Burlington
8,269
-7
85
72
44°30′
Lynchburg
4,166
16
90
76
37°20′
Norfolk
3,421
22
91
78
36°50′
Richmond
3,865
17
92
78
37°30′
Roanoke
4,150
16
91
74
37°20′
Olympia
5,236
22
83
66
47°00′
Seattle-Tacoma
5,145
26
80
64
47°30′
Seattled
4,424
27
82
67
47°40′
VA
WA
WV
WI
WY
a.
b.
c.
d.
Spokane
6,655
2
90
64
47°40′
Charleston
4,476
11
90
75
38°20′
Elkins
5,675
6
84
72
38°50′
Huntington
4,446
10
91
77
38°20′
Parkersburgd
4,754
11
90
76
39°20′
Green Bay
8,029
-9
85
74
44°30′
La Crosse
7,589
-9
88
75
43°50′
Madison
7,863
-7
88
75
43°10′
Milwaukee
7,635
-4
87
74
43°00′
Casper
7,410
-5
90
61
42°50′
Cheyenne
7,381
-1
86
62
41°10′
Lander
7,870
-11
88
63
42°50′
Sheridan
7,680
-8
91
65
44°50′
All data were extracted from the 1985 ASHRAE Handbook, Fundamentals Volume.
Design data developed from airport temperature observations unless noted.
Latitude is given to the nearest 10 minutes. For example, the latitude for Miami, Florida, is given as 25°50′, or 25 degrees 50 minutes.
Design data developed from office locations within an urban area, not from airport temperature observations.
APPENDIX D-6
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E
SIZING OF WATER PIPING SYSTEM
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
User note:
About this appendix: The sizing of water service and water distribution piping is not specified in Chapter 6 as it is left up to the designer of
the system with the code official approving the design method. Appendix E provides several methods that could be used by a system
designer.
SECTION E101
GENERAL
E101.1 Scope.
E101.1.1 Two procedures. This appendix outlines two
procedures for sizing a water piping system (see Sections
E103.3 and E104.1). The design procedures are based on
the minimum static pressure available from the supply
source, the head changes in the system caused by friction
and elevation, and the rates of flow necessary for operation of various fixtures.
E101.1.2 Variable conditions. Because of the variable
conditions encountered in hydraulic design, it is impractical to specify definite and detailed rules for sizing of the
water piping system. Accordingly, other sizing or design
methods conforming to good engineering practice standards are acceptable alternatives to those presented
herein.
SECTION E102
INFORMATION REQUIRED
E102.1 Preliminary. Obtain the necessary information
regarding the minimum daily static service pressure in the
area where the building is to be located. If the building
supply is to be metered, obtain information regarding friction loss relative to the rate of flow for meters in the range of
sizes likely to be used. Friction loss data can be obtained
from most manufacturers of water meters.
the highest fixture in the supply system. If the highest group
of fixtures contains flushometer valves, the pressure for the
group should be not less than 15 pounds per square inch (psi)
(103.4 kPa) flowing. For flush tank supplies, the available
pressure should be not less than 8 psi (55.2 kPa) flowing,
except blowout action fixtures must be not less than 25 psi
(172.4 kPa) flowing.
E103.2 Pipe sizing.
E103.2.1 Pipe size selection. Pipe sizes can be selected
according to the following procedure or by other design
methods conforming to acceptable engineering practice
and approved by the administrative authority. The sizes
selected must not be less than the minimum required by
this code.
E103.2.2 Pressures and losses. Water pipe sizing procedures are based on a system of pressure requirements and
losses, the sum of which must not exceed the minimum
pressure available at the supply source. These pressures
are as follows:
1.
2.
Example: Assume that the highest fixture
supply outlet is 20 feet (6096 mm) above or
below the supply source. This produces a
static pressure differential of 20 feet by 0.433
psi/foot (2096 mm by 9.8 kPa/m) and an 8.66
psi (59.8 kPa) loss.
E102.2 Demand load.
E102.2.1 Fixture demand. Estimate the supply demand
of the building main and the principal branches and risers
of the system by totaling the corresponding demand from
the applicable part of Table E103.3(3).
E102.2.2 Continuous demand. Estimate continuous
supply demands in gallons per minute (L/m) for items
such as lawn sprinklers and air conditioners, and add the
sum to the total demand for fixtures. The result is the estimated supply demand for the building supply.
3.
4.
5.
6.
SECTION E103
SELECTION OF PIPE SIZE
E103.1 General. Decide from Table 604.3 what is the desirable minimum residual pressure that should be maintained at
2021 INTERNATIONAL PLUMBING CODE®
Pressure required at fixture to produce required
flow. See Sections 604.3 and 604.5.
Static pressure loss or gain (due to head) is
computed at 0.433 psi per foot (9.8 kPa/m) of
elevation change.
7.
Loss through water meter. The friction or pressure
loss can be obtained from meter manufacturers.
Loss through taps in water main.
Losses through special devices such as filters,
softeners, backflow prevention devices and pressure regulators. These values must be obtained
from the manufacturers.
Loss through valves and fittings. Losses for these
items are calculated by converting to equivalent
length of piping and adding to the total pipe
length.
Loss due to pipe friction can be calculated where
the pipe size, the pipe length and the flow through
APPENDIX E-1
APPENDIX E—SIZING OF WATER PIPING SYSTEM
8.
the pipe are known. With these three items, the
friction loss can be determined. For piping flow
charts not included, use manufacturers’ tables and
velocity recommendations.
For the purposes of all examples, the following
metric conversions are applicable:
1 cubic foot per minute = 0.4719 L/s
1 square foot = 0.0929 m2
1 degree = 0.0175 rad
1 pound per square inch = 6.895 kPa
1 inch = 25.4 mm
1 foot = 304.8 mm
1 gallon per minute = 3.785 L/m
E103.3 Segmented loss method. The size of water service
mains, branch mains and risers by the segmented loss
method must be determined according to water supply
demand [gpm (L/m)], available water pressure [psi (kPa)]
and friction loss caused by the water meter and developed
length of pipe [feet (m)], including equivalent length of
fittings. The design procedure is based on the following
parameters:
•
•
•
Calculated friction loss through each length of the
pipe.
A system of pressure losses, the sum of which must
not exceed the minimum pressure available at the
street main or other source of supply.
The estimated peak demand, total pressure losses
caused by difference in elevation, equipment, developed length and pressure required at most remote
fixture, loss through taps in water main, losses
through fittings, filters, backflow prevention devices,
valves and pipe friction.
Because of the variable conditions encountered in hydraulic design, it is impractical to specify definite and detailed
rules for sizing of the water piping system. Current sizing
methods do not address the differences in the probability of
use and flow characteristics of fixtures between types of
occupancies. Creating an exact model of predicting the
demand for a building is impossible and final studies assessing the impact of water conservation on demand are not yet
complete. The following steps are necessary for the
segmented loss method.
1. Preliminary. Obtain the necessary information
regarding the minimum daily static service pressure
in the area where the building is to be located. If the
building supply is to be metered, obtain information
regarding friction loss relative to the rate of flow for
meters in the range of sizes to be used. Friction loss
data can be obtained from manufacturers of water
meters. It is essential that enough pressure be available to overcome all system losses caused by friction
and elevation so that plumbing fixtures operate properly. Section 604.6 requires the water distribution
system to be designed for the minimum pressure
available taking into consideration pressure fluctuations. The lowest pressure must be selected to
APPENDIX E-2
guarantee a continuous, adequate supply of water.
The lowest pressure in the public main usually occurs
in the summer because of lawn sprinkling and
supplying water for air-conditioning cooling towers.
Future demands placed on the public main as a result
of large growth or expansion should be considered.
The available pressure will decrease as additional
loads are placed on the public system.
2. Demand load. Estimate the supply demand of the
building main and the principal branches and risers of
the system by totaling the corresponding demand
from the applicable part of Table E103.3(3) . When
estimating peak demand sizing methods typically use
water supply fixture units (w.s.f.u.) [see Table
E103.3(2) ]. This numerical factor measures the loadproducing effect of a single plumbing fixture of a
given kind. The use of such fixture units can be
applied to a single basic probability curve (or table),
found in the various sizing methods [Table
E103.3(3)]. The fixture units are then converted into
gallons per minute (L/m) flow rate for estimating
demand.
2.1. Estimate continuous supply demand in
gallons per minute (L/m) for items such as
lawn sprinklers and air conditioners, and
add the sum to the total demand for
fixtures. The result is the estimated supply
demand for the building supply. Fixture
units cannot be applied to constant use
fixtures such as hose bibbs, lawn sprinklers and air conditioners. These types of
fixtures must be assigned the gallon per
minute (L/m) value.
3. Selection of pipe size. This water pipe sizing procedure is based on a system of pressure requirements
and losses, the sum of which must not exceed the
minimum pressure available at the supply source.
These pressures are as follows:
3.1. Pressure required at the fixture to produce
required flow. See Sections 604.3 and
604.5.
3.2. Static pressure loss or gain (because of
head) is computed at 0.433 psi per foot
(9.8 kPa/m) of elevation change.
3.3. Loss through a water meter. The friction or
pressure loss can be obtained from the
manufacturer.
3.4. Loss through taps in water main [see Table
E103.3(4)].
3.5. Losses through special devices such as
filters, softeners, backflow prevention
devices and pressure regulators. These
values must be obtained from the
manufacturers.
3.6. Loss through valves and fittings [see
Tables E103.3(5) and E103.3(6)]. Losses
for these items are calculated by convert-
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E—SIZING OF WATER PIPING SYSTEM
ing to equivalent length of piping and
adding to the total pipe length.
3.7. Loss caused by pipe friction can be calculated where the pipe size, the pipe length
and the flow through the pipe are known.
With these three items, the friction loss
can be determined using Figures
E103.3(2) through E103.3(7). When using
charts, use pipe inside diameters. For
piping flow charts not included, use manufacturers’
tables
and
velocity
recommendations. Before attempting to
size any water supply system, it is necessary to gather preliminary information that
includes available pressure, piping material, select design velocity, elevation
differences and developed length to most
remote fixture. The water supply system is
divided into sections at major changes in
elevation or where branches lead to fixture
groups. The peak demand must be determined in each part of the hot and cold
water supply system that includes the
corresponding water supply fixture unit
and conversion to gallons per minute
(L/m) flow rate to be expected through
each section. Sizing methods require the
determination of the “most hydraulically
remote” fixture to compute the pressure
loss caused by pipe and fittings. The
hydraulically remote fixture represents the
most downstream fixture along the circuit
of piping requiring the most available
pressure to operate properly. Consideration must be given to all pressure
demands and losses, such as friction
caused by pipe, fittings and equipment,
elevation and the residual pressure
required by Table 604.3. The two most
common and frequent complaints about
the water supply system operation are lack
of adequate pressure and noise.
E103.3.1 Sample problem. What size Type L copper
water pipe, service and distribution will be required to
serve a two-story factory building having on each floor,
back-to-back, two toilet rooms each equipped with hot
and cold water? The highest fixture is 21 feet (6401 mm)
above the street main, which is tapped with a 2-inch (51
mm) corporation cock at which point the minimum pressure is 55 psi (379.2 kPa). In the building basement, a 2inch (51 mm) meter with a maximum pressure drop of 11
psi (75.8 kPa) and 3-inch (76 mm) reduced pressure principle backflow preventer with a maximum pressure drop
of 9 psi (621 kPa) are to be installed. The system is shown
by Figure E103.3(1) . To be determined are the pipe sizes
for the service main and the cold and hot water distribution pipes.
Problem Solution: A tabular arrangement such as
shown in Table E103.3(1) should first be constructed.
2021 INTERNATIONAL PLUMBING CODE®
The steps to be followed are indicated by the tabular
arrangement itself as they are in sequence, Columns 1
through 10 and Lines A through L.
Step 1
Columns 1 and 2: Divide the system into sections
breaking at major changes in elevation or where
branches lead to fixture groups. After point B [see
Figure E103.3(1)], separate consideration will be
given to the hot and cold water piping. Enter the
sections to be considered in the service and cold water
piping in Column 1 of the tabular arrangement.
Column 1 of Table E103.3(1) provides a line-by-line
recommended tabular arrangement for use in solving
pipe sizing.
The objective in designing the water supply system
is to ensure an adequate water supply and pressure to
all fixtures and equipment. Column 2 provides the
pounds per square inch (psi) to be considered separately from the minimum pressure available at the
main. Losses to take into consideration are the following: the differences in elevation between the water
supply source and the highest water supply outlet,
meter pressure losses, the tap in main loss, special
fixture devices such as water softeners and backflow
prevention devices and the pressure required at the
most remote fixture outlet. The difference in elevation
can result in an increase or decrease in available pressure at the main. Where the water supply outlet is
located above the source, this results in a loss in the
available pressure and is subtracted from the pressure
at the water source. Where the highest water supply
outlet is located below the water supply source, there
will be an increase in pressure that is added to the
available pressure of the water source.
Column 3: According to Table E103.3(3) , determine
the gpm (L/m) of flow to be expected in each section
of the system. These flows range from 28.6 to 108
gpm. Load values for fixtures must be determined as
water supply fixture units and then converted to a
gallon-per-minute (gpm) rating to determine peak
demand. When calculating peak demands, the water
supply fixture units are added and then converted to
the gallon-per-minute rating. For continuous flow
fixtures such as hose bibbs and lawn sprinkler systems,
add the gallon-per-minute demand to the intermittent
demand of fixtures. For example, a total of 120 water
supply fixture units is converted to a demand of 48
gallons per minute. Two hose bibbs × 5 gpm demand =
10 gpm. Total gpm rating = 48.0 gpm + 10 gpm = 58.0
gpm demand.
Step 2
Line A: Enter the minimum pressure available at the
main source of supply in Column 2. This is 55 psi
(379.2 kPa). The local water authorities generally keep
records of pressures at different times of day and year.
The available pressure can be checked from nearby
buildings or from fire department hydrant checks.
APPENDIX E-3
APPENDIX E—SIZING OF WATER PIPING SYSTEM
Line B: Determine from Table 604.3 the highest pressure required for the fixtures on the system, which is
15 psi (103.4 kPa), to operate a flushometer valve. The
most remote fixture outlet is necessary to compute the
pressure loss caused by pipe and fittings, and
represents the most downstream fixture along the
circuit of piping requiring the available pressure to
operate properly as indicated by Table 604.3.
Line C: Determine the pressure loss for the meter size
given or assumed. The total water flow from the main
through the service as determined in Step 1 will serve
to aid in the meter selected. There are three common
types of water meters; the pressure losses are determined by the American Water Works Association
Standards for displacement type, compound type and
turbine type. The maximum pressure loss of such
devices takes into consideration the meter size, safe
operating capacity (gpm) and maximum rates for
continuous operations (gpm). Typically, equipment
imparts greater pressure losses than piping.
Line D: Select from Table E103.3(4) and enter the
pressure loss for the tap size given or assumed. The
loss of pressure through taps and tees in pounds per
square inch (psi) is based on the total gallon-perminute flow rate and size of the tap.
Line E: Determine the difference in elevation between
the main and source of supply and the highest fixture
on the system. Multiply this figure, expressed in feet,
by 0.43 psi (2.9 kPa). Enter the resulting psi loss on
Line E. The difference in elevation between the water
supply source and the highest water supply outlet has a
significant impact on the sizing of the water supply
system. The difference in elevation usually results in a
loss in the available pressure because the water supply
outlet is generally located above the water supply
source. The loss is caused by the pressure required to
lift the water to the outlet. The pressure loss is
subtracted from the pressure at the water source.
Where the highest water supply outlet is located below
the water source, there will be an increase in pressure
that is added to the available pressure of the water
source.
Lines F, G and H: The pressure losses through filters,
backflow prevention devices or other special fixtures
must be obtained from the manufacturer or estimated
and entered on these lines. Equipment such as backflow prevention devices, check valves, water
softeners, instantaneous or tankless water heaters,
filters and strainers can impart a much greater pressure
loss than the piping. The pressure losses can range
from 8 psi to 30 psi.
Step 3
Line I: The sum of the pressure requirements and
losses that affect the overall system (Lines B through
H) is entered on this line. Summarizing the steps, all of
the system losses are subtracted from the minimum
water pressure. The remainder is the pressure available
for friction, defined as the energy available to push the
APPENDIX E-4
water through the pipes to each fixture. This force can
be used as an average pressure loss, as long as the
pressure available for friction is not exceeded. Saving
a certain amount for available water supply pressures
as an area incurs growth, or because of aging of the
pipe or equipment added to the system is
recommended.
Step 4
Line J: Subtract Line I from Line A. This gives the
pressure that remains available from overcoming friction losses in the system. This figure is a guide to the
pipe size that is chosen for each section, incorporating
the total friction losses to the most remote outlet
(measured length is called developed length ).
Exception: Where the main is above the highest
fixture, the resulting psi must be considered a pressure gain (static head gain) and omitted from the
sums of Lines B through H and added to Line J.
The maximum friction head loss that can be tolerated in the system during peak demand is the
difference between the static pressure at the highest
and most remote outlet at no-flow conditions and the
minimum flow pressure required at that outlet. If the
losses are within the required limits, then every run of
pipe will be within the required friction head loss.
Static pressure loss is the most remote outlet in feet ×
0.433 = loss in psi caused by elevation differences.
Step 5
Column 4: Enter the length of each section from the
main to the most remote outlet (at Point E). Divide the
water supply system into sections breaking at major
changes in elevation or where branches lead to fixture
groups.
Step 6
Column 5: When selecting a trial pipe size, the length
from the water service or meter to the most remote
fixture outlet must be measured to determine the
developed length. However, in systems having a flushometer valve or temperature controlled shower at the
topmost floors the developed length would be from the
water meter to the most remote flushometer valve on
the system. A rule of thumb is that size will become
progressively smaller as the system extends farther
from the main source of supply. The following
formula is an acceptable method to determine trial pipe
size:
Line J: (Pressure available to overcome pipe friction)
× 100/equivalent length of run total developed length
to most remote fixture × percentage factor of 1.5
(Note: a percentage factor is used only as an estimate
for friction losses imposed for fittings for initial trial
pipe size) = psi (average pressure drops per 100 feet of
pipe).
For trial pipe size, see Figure E103.3(3) (Type L
copper) based on 2.77 psi and a 108 gpm = 21/2 inches.
To determine the equivalent length of run to the most
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E—SIZING OF WATER PIPING SYSTEM
Total friction loss is determined by multiplying the
friction loss per 100 feet (30 480 mm) for each pipe
section in the total developed length by the pressure
loss in fittings expressed as equivalent length in feet.
Note: Section C-F should be considered in the total
pipe friction losses only if greater loss occurs in
Section C-F than in pipe section D-E. Section C-F is
not considered in the total developed length. Total friction loss in equivalent length is determined in Table
E103.3.1(3).
remote outlet, the developed length is determined and
added to the friction losses for fittings and valves. The
developed lengths of the designated pipe sections are
shown in Table E103.3.1(1) .
The equivalent length of the friction loss in fittings
and valves must be added to the developed length
(most remote outlet). Where the size of fittings and
valves is not known, the added friction loss should be
approximated. A general rule that has been used is to
add 50 percent of the developed length to allow for
fittings and valves. For example, the equivalent length
of run equals the developed length of run (225 ft × 1.5
= 338 ft). The total equivalent length of run for determining a trial pipe size is 338 feet.
Example: 9.36 (pressure available to overcome pipe
friction) × 100/338 (equivalent length of run = 225
× 1.5) = 2.77 psi (average pressure drop per 100 feet
of pipe).
Step 11
Line K: Enter the sum of the values in Column 9. The
value is the total friction loss in equivalent length for
each designated pipe section.
Step 12
Line L: Subtract Line J from Line K and enter in
Column 10.
The result should always be a positive or plus
figure. If it is not, repeat the operation using Columns
5, 6, 8 and 9 until a balance or near balance is
obtained. If the difference between Lines J and K is a
high positive number, it is an indication that the pipe
sizes are too large and should be reduced, thus saving
materials. In such a case, the operations using
Columns 5, 6, 8 and 9 should again be repeated.
Step 7
Column 6: Select from Table E103.3(6) the equivalent lengths for the trial pipe size of fittings and valves
on each pipe section. Enter the sum for each section in
Column 6. (The number of fittings to be used in this
example must be an estimate.) The equivalent length
of piping is the developed length plus the equivalent
lengths of pipe corresponding to friction head losses
for fittings and valves. Where the size of fittings and
valves is not known, the added friction head losses
must be approximated. An estimate for this example is
found in Table E103.3.1(2).
The total friction losses are determined and
subtracted from the pressure available to overcome
pipe friction for trial pipe size. This number is critical
as it provides a guide to whether the pipe size selected
is too large and the process should be repeated to
obtain an economically designed system.
Step 8
Column 7: Add the figures from Column 4 and
Column 6, and enter in Column 7. Express the sum in
hundreds of feet.
Answer: The final figures entered in Column 5
become the design pipe size for the respective
sections. Repeating this operation a second time using
the same sketch but considering the demand for hot
water, it is possible to size the hot water distribution
piping. This has been worked up as a part of the overall problem in the tabular arrangement used for sizing
the service and water distribution piping. Note that
consideration must be given to the pressure losses
from the street main to the water heater (Section A-B)
in determining the hot water pipe sizes.
Step 9
Column 8: Select from Figure E103.3(3) the friction
loss per 100 feet (30 480 mm) of pipe for the gallonper-minute flow in a section (Column 3) and trial pipe
size (Column 5). Maximum friction head loss per 100
feet is determined on the basis of total pressure available for friction head loss and the longest equivalent
length of run. The selection is based on the gallon-perminute demand, the uniform friction head loss and the
maximum design velocity. Where the size indicated by
hydraulic table indicates a velocity in excess of the
selected velocity, a size must be selected that produces
the required velocity.
Step 10
Column 9: Multiply the figures in Columns 7 and 8
for each section and enter in Column 9.
TABLE E103.3.1(1)
SUMMATION OF DEVELOPED PIPE LENGTHS
SEGMENT
A-B
LENGTHa (feet)
54
B-C
8
C-D
13
D-E
150
For SI: 1 foot = 304.8 mm.
a. Total developed length = 225 feet.
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E-5
APPENDIX E—SIZING OF WATER PIPING SYSTEM
TABLE E103.3.1(2)
FITTING PRESSURE LOSSES EXPRESSED IN EQUIVALENT LENGTHS (formerly Table E1)
COLD WATER
PIPE SECTION
A-B
B-C
C-F
FITTINGS/VALVES
PRESSURE LOSS
EXPRESSED AS
EQUIVALENT
LENGTH OF TUBE
(feet)
HOT WATER
PIPE SECTION
FITTINGS/VALVES
PRESSURE LOSS
EXPRESSED AS
EQUIVALENT OF TUBE
(feet)
(3) 21/2˝ Gate valves
3
A-B
(3) 21/2˝ Gate valves
3
1
1
(1) 2 /2˝ Side branch tee
12
—
(1) 2 /2˝ Side branch tee
12
(1) 21/2˝ Straight run tee
0.5
B-C
(1) 2˝ Straight run tee
7
—
—
—
(1) 2˝ 90-degree elbow
0.5
(1) 21/2˝ Side branch tee
12
C-F
(1) 11/2˝ Side branch tee
7
1
1
C-D
(1) 2 /2˝ 90-degree elbow
7
C-D
(1) 1 /2˝ 90-degree elbow
4
D-E
(1) 21/2˝ Side branch tee
12
D-E
(1) 11/2˝ Side branch tee
7
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
TABLE E103.3.1(3)
TOTAL FRICTION LOSS EQUIVALENT PIPING LENGTH (formerly Table E2)
PIPE SECTION
FRICTION LOSS EQUIVALENT LENGTH (feet)
Cold Water
Hot Water
A-B
0.69 × 3.2 = 2.21
0.69 × 3.2 = 2.21
B-C
0.085 × 3.1 = 0.26
0.16 × 1.4 = 0.22
C-D
0.20 × 1.9 = 0.38
0.17 × 3.2 = 0.54
D-E
1.62 × 1.9 = 3.08
1.57 × 3.2 = 5.02
5.93
7.99
Total pipe friction losses (Line K)
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gallon per minute = 3.785 L/m.
APPENDIX E-6
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E—SIZING OF WATER PIPING SYSTEM
HOT WATER
COLD WATER
M = METER
BFP = BACKFLOW PREVENTER
= 90 DEGREE ELBOW
= “T”
= VALVE
150 FT.
132 fu, 77 gpm
D
D′
FLOOR 2
E′
13 FT.
13 FT.
12 fu, 28.6 gpm
132 fu,
77 gpm
E
132 fu, 77 gpm
C
288 fu, 108 gpm
8 FT.
FLOOR 1
264 fu,
104.5 gpm
C′
B
M
MAIN
BFP
12 fu, 28.6 gpm
F′
24 fu, 38 gpm
B′
WATER HEATER
54 FT.
For SI: 1 foot = 304.8 mm, 1 gpm = 3.785 L/m.
FIGURE E103.3(1)
EXAMPLE—SIZING
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E-7
APPENDIX E—SIZING OF WATER PIPING SYSTEM
TABLE E103.3(1)
RECOMMENDED TABULAR ARRANGEMENT FOR USE IN SOLVING PIPE SIZING PROBLEMS
1
COLUMN
Line
2
A
Minimum pressure
available at main
55.00
B
Highest pressure required at
a fixture (Table 604.3)
15.00
C
Meter loss 2″ meter
11.00
D
Tap in main loss 2″ tap
[Table E103.3(4)]
1.61
E
Static head loss 21 × 43 psi
9.03
Special fixture loss
backflow preventer
9.00
Special fixture loss—Filter
0.00
H
Special fixture loss—Other
0.00
I
Total overall losses and
requirements
45.64
(Sum of Lines B through H)
J
Pressure available to overcome pipe friction (Line A
minus Lines B to H)
F
G
Pipe section (from
diagram)
Cold water distribution piping
4
5
6
7
8
Friction
Equivalent
Total
Lb per Gal. per Length
Trial
loss per
length of equivalent
square
min
of
pipe
100 feet
fittings and length col.
inch through section
size
of trial
valves
4 and col.
(psi) section (feet) (inches)
size pipe
(feet)
6 (100 feet)
(psi)
Description
Service
and cold
water
distribution
pipinga
3
9
10
Friction
loss in
equivalent
length col.
8 × col. 7
(psi)
Excess
pressure
over
friction
losses
(psi)
9.36
FU
264
AB
288
108.0
54
21/2
15.00
0.69
3.2
2.21
—
BC
264
104.5
8
21/2
0.5
0.20
1.9
0.26
—
1
CD
132
77.0
13
2 /2
7.00
0.20
1.9
0.38
—
CF b
132
77.0
150
21/2
12.00
1.62
1.9
3.08
—
DE b
132
77.0
150
21/2
12.00
1.62
1.9
3.08
—
—
—
—
—
—
—
5.93
—
K
Total pipe friction losses (cold)
L
Difference (Line J minus Line K)
—
—
—
—
—
—
—
3.43
A′B′
288
108.0
54
12.00
0.69
3.3
2.21
—
Pipe section
(from diagram)
21/2
B′C′
24
38.0
8
2
7.5
0.16
1.4
0.22
—
Hot water distribution piping
C′D′
12
28.6
13
11/2
4.0
0.17
3.2
0.54
—
C′F′ b
12
28.6
150
11/2
7.00
1.57
3.2
5.02
—
12
28.6
150
11/2
7.00
1.57
3.2
5.02
—
D′E′
b
K
Total pipe friction losses (hot)
—
—
—
—
—
—
7.99
—
L
Difference (Line J minus Line K)
—
—
—
—
—
—
—
1.37
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 psi = 6.895 kPa, 1 gpm = 3.785 L/m.
a. To be considered as pressure gain for fixtures below main (to consider separately, omit from “I” and add to “J”).
b. To consider separately, in K use C-F only if greater loss than above.
APPENDIX E-8
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E—SIZING OF WATER PIPING SYSTEM
TABLE E103.3(2)
LOAD VALUES ASSIGNED TO FIXTURESa
LOAD VALUES, IN WATER SUPPLY FIXTURE UNITS (wsfu)
OCCUPANCY
TYPE OF SUPPLY
CONTROL
Cold
Hot
Total
Private
Flush tank
2.7
1.5
3.6
Bathroom group
Private
Flushometer valve
6.0
3.0
8.0
Bathtub
Private
Faucet
1.0
1.0
1.4
FIXTURE
Bathroom group
Bathtub
Public
Faucet
3.0
3.0
4.0
Bidet
Private
Faucet
1.5
1.5
2.0
Combination fixture
Private
Faucet
2.25
2.25
3.0
Dishwashing machine
Private
Automatic
—
1.4
1.4
3
/8″ valve
0.25
—
0.25
Kitchen sink
Private
Faucet
1.0
1.0
1.4
Kitchen sink
Drinking fountain
Offices, etc.
Hotel, restaurant
Faucet
3.0
3.0
4.0
Laundry trays (1 to 3)
Private
Faucet
1.0
1.0
1.4
Lavatory
Private
Faucet
0.5
0.5
0.7
Lavatory
Public
Faucet
1.5
1.5
2.0
Service sink
Offices, etc.
Faucet
2.25
2.25
3.0
Shower head
Public
Mixing valve
3.0
3.0
4.0
Shower head
Private
Mixing valve
1.0
1.0
1.4
Urinal
Public
1″ flushometer valve
10.0
—
10.0
Urinal
Public
/4″ flushometer valve
5.0
—
5.0
Urinal
Public
Flush tank
3.0
—
3.0
Washing machine (8 lb)
Private
Automatic
1.0
1.0
1.4
Washing machine (8 lb)
Public
Automatic
2.25
2.25
3.0
3
Washing machine (15 lb)
Public
Automatic
3.0
3.0
4.0
Water closet
Private
Flushometer valve
6.0
—
6.0
Water closet
Private
Flush tank
2.2
—
2.2
Water closet
Public
Flushometer valve
10.0
—
10.0
Water closet
Public
Flush tank
5.0
—
5.0
Water closet
Public or private
Flushometer tank
2.0
—
2.0
For SI: 1 inch = 25.4 mm, 1 pound = 0.454 kg.
a. For fixtures not listed, loads should be assumed by comparing the fixture to one listed using water in similar quantities and at similar rates. The assigned
loads for fixtures with both hot and cold water supplies are given for separate hot and cold water loads and for total load. The separate hot and cold water
loads being three-fourths of the total load for the fixture in each case.
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E-9
APPENDIX E—SIZING OF WATER PIPING SYSTEM
TABLE E103.3(3)
TABLE FOR ESTIMATING DEMAND
SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS
Load
SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSHOMETER VALVES
Demand
Load
Demand
(Water supply fixture units) (Gallons per minute) (Cubic feet per minute) (Water supply fixture units) (Gallons per minute) (Cubic feet per minute)
1
3.0
0.04104
—
—
—
2
5.0
0.0684
—
—
—
3
6.5
0.86892
—
—
—
4
8.0
1.06944
—
—
—
5
9.4
1.256592
5
15.0
2.0052
6
10.7
1.430376
6
17.4
2.326032
7
11.8
1.577424
7
19.8
2.646364
8
12.8
1.711104
8
22.2
2.967696
9
13.7
1.831416
9
24.6
3.288528
10
14.6
1.951728
10
27.0
3.60936
11
15.4
2.058672
11
27.8
3.716304
12
16.0
2.13888
12
28.6
3.823248
13
16.5
2.20572
13
29.4
3.930192
14
17.0
2.27256
14
30.2
4.037136
15
17.5
2.3394
15
31.0
4.14408
16
18.0
2.90624
16
31.8
4.241024
17
18.4
2.459712
17
32.6
4.357968
18
18.8
2.513184
18
33.4
4.464912
19
19.2
2.566656
19
34.2
4.571856
20
19.6
2.620128
20
35.0
4.6788
25
21.5
2.87412
25
38.0
5.07984
30
23.3
3.114744
30
42.0
5.61356
35
24.9
3.328632
35
44.0
5.88192
40
26.3
3.515784
40
46.0
6.14928
45
27.7
3.702936
45
48.0
6.41664
50
29.1
3.890088
50
50.0
6.684
60
32.0
4.27776
60
54.0
7.21872
70
35.0
4.6788
70
58.0
7.75344
80
38.0
5.07984
80
61.2
8.181216
90
41.0
5.48088
90
64.3
8.595624
100
43.5
5.81508
100
67.5
9.0234
120
48.0
6.41664
120
73.0
9.75864
140
52.5
7.0182
140
77.0
10.29336
160
57.0
7.61976
160
81.0
10.82808
180
61.0
8.15448
180
85.5
11.42964
200
65.0
8.6892
200
90.0
12.0312
225
70.0
9.3576
225
95.5
12.76644
250
75.0
10.026
250
101.0
13.50168
275
80.0
10.6944
275
104.5
13.96956
(continued)
APPENDIX E-10
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E—SIZING OF WATER PIPING SYSTEM
TABLE E103.3(3)—continued
TABLE FOR ESTIMATING DEMAND
SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSH TANKS
Load
SUPPLY SYSTEMS PREDOMINANTLY FOR FLUSHOMETER VALVES
Demand
Load
Demand
(Water supply fixture units) (Gallons per minute) (Cubic feet per minute) (Water supply fixture units) (Gallons per minute) (Cubic feet per minute)
300
85.0
11.3628
300
108.0
14.43744
400
105.0
14.0364
400
127.0
16.97736
500
124.0
16.57632
500
143.0
19.11624
750
170.0
22.7256
750
177.0
23.66136
1,000
208.0
27.80544
1,000
208.0
27.80544
1,250
239.0
31.94952
1,250
239.0
31.94952
1,500
269.0
35.95992
1,500
269.0
35.95992
1,750
297.0
39.70296
1,750
297.0
39.70296
2,000
325.0
43.446
2,000
325.0
43.446
2,500
380.0
50.7984
2,500
380.0
50.7984
3,000
433.0
57.88344
3,000
433.0
57.88344
4,000
525.0
70.182
4,000
525.0
70.182
5,000
593.0
79.27224
5,000
593.0
79.27224
3
For SI: 1 inch = 25.4 mm, 1 gallon per minute = 3.785 L/m, 1 cubic foot per minute = 0.28 m per minute.
TABLE E103.3(4)
LOSS OF PRESSURE THROUGH TAPS AND TEES IN POUNDS PER SQUARE INCH (psi)
GALLONS PER
MINUTE
SIZE OF TAP OR TEE (inches)
5
3
1
11/4
11/2
2
3
10
1.35
0.64
0.18
0.08
—
—
—
20
5.38
2.54
0.77
0.31
0.14
—
—
30
12.10
5.72
1.62
0.69
0.33
0.10
—
40
—
10.20
3.07
1.23
0.58
0.18
—
50
—
15.90
4.49
1.92
0.91
0.28
—
60
—
—
6.46
2.76
1.31
0.40
—
/8
/4
70
—
—
8.79
3.76
1.78
0.55
0.10
80
—
—
11.50
4.90
2.32
0.72
0.13
90
—
—
14.50
6.21
2.94
0.91
0.16
100
—
—
17.94
7.67
3.63
1.12
0.21
120
—
—
25.80
11.00
5.23
1.61
0.30
140
—
—
35.20
15.00
7.12
2.20
0.41
150
—
—
—
17.20
8.16
2.52
0.47
160
—
—
—
19.60
9.30
2.92
0.54
180
—
—
—
24.80
11.80
3.62
0.68
200
—
—
—
30.70
14.50
4.48
0.84
225
—
—
—
38.80
18.40
5.60
1.06
250
—
—
—
47.90
22.70
7.00
1.31
275
—
—
—
—
27.40
7.70
1.59
300
—
—
—
—
32.60
10.10
1.88
For SI: 1 inch = 25.4 mm, 1 pound per square inch = 6.895 kPa, 1 gallon per minute = 3.785 L/m.
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E-11
APPENDIX E—SIZING OF WATER PIPING SYSTEM
TABLE E103.3(5)
ALLOWANCE IN EQUIVALENT LENGTHS OF PIPE FOR FRICTION LOSS IN VALVES AND THREADED FITTINGS (feet)
FITTING OR VALVE
PIPE SIZE (inches)
1
3
1
11/4
11/2
2
21/2
45-degree elbow
1.2
3
1.5
1.8
2.4
3.0
4.0
5.0
6.0
90-degree elbow
Tee, run
2.0
2.5
3.0
4.0
5.0
7.0
8.0
10.0
0.6
0.8
0.9
1.2
1.5
2.0
2.5
3.0
Tee, branch
3.0
4.0
5.0
6.0
7.0
10.0
12.0
15.0
Gate valve
0.4
0.5
0.6
0.8
1.0
1.3
1.6
2.0
/2
/4
Balancing valve
0.8
1.1
1.5
1.9
2.2
3.0
3.7
4.5
Plug-type cock
0.8
1.1
1.5
1.9
2.2
3.0
3.7
4.5
Check valve, swing
5.6
8.4
11.2
14.0
16.8
22.4
28.0
33.6
Globe valve
15.0
20.0
25.0
35.0
45.0
55.0
65.0
80.0
Angle valve
8.0
12.0
15.0
18.0
22.0
28.0
34.0
40.0
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
TABLE E103.3(6)
PRESSURE LOSS IN FITTINGS AND VALVES EXPRESSED AS EQUIVALENT LENGTH OF TUBEa (feet)
NOMINAL OR
STANDARD
SIZE (inches)
FITTINGS
Standard EII
90 Degree
VALVES
90-Degree Tee
45 Degree
Side Branch
Straight Run
Coupling
Ball
Gate
Butterfly
Check
3
0.5
—
1.5
—
—
—
—
—
1.5
1
1
0.5
2
—
—
—
—
—
2
5
1.5
0.5
2
—
—
—
—
—
2.5
3
2
0.5
3
—
—
—
—
—
3
1
2.5
1
4.5
—
—
0.5
—
—
4.5
3
1
5.5
0.5
0.5
0.5
—
—
5.5
/8
/2
/8
/4
11/4
11/2
4
1.5
7
0.5
0.5
0.5
—
—
6.5
5.5
2
9
0.5
0.5
0.5
0.5
7.5
9
2 /2
7
2.5
12
0.5
0.5
—
1
10
11.5
3
9
3.5
15
1
1
—
1.5
15.5
14.5
2
1
1
3 /2
9
3.5
14
1
1
—
2
—
12.5
4
12.5
5
21
1
1
—
2
16
18.5
5
16
6
27
1.5
1.5
—
3
11.5
23.5
6
19
7
34
2
2
—
3.5
13.5
26.5
8
29
11
50
3
3
—
5
12.5
39
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 degree = 0.0175 rad.
a. Allowances are for streamlined soldered fittings and recessed threaded fittings. For threaded fittings, double the allowances shown in the table. The equivalent lengths presented above are based on a C factor of 150 in the Hazen-Williams friction loss formula. The lengths shown are rounded to the nearest halffoot.
APPENDIX E-12
2021 INTERNATIONAL PLUMBING CODE®
″
″
10
8″
6″
5″
4″
″
3½
10
3″
ITY
OC
EL
.V
″
1¼
5 8
½″
ITY
OC
/″
EL
.V
ITY
OC
EL
.V
¾″
EC
S
T./
5F
EC
1″
1.2
./S
FT
ITY
OC
EL
2.5
.V
″
1½
EC
S
T./
2″
5F
EC
./S
FT
″
2½
3 8
/″
¼″
10
EC
./S
FT
ITY
ITY
OC
EL
.V
EC
OC
EL
S
T./
.V
5F
EC
ITY
./S
FT
OC
EL
ITY
.V
EC
OC
EL
S
T./
.V
5F
2.5
1.2
Note: Fluid velocities in excess of 5 to 8 feet/second are not usually recommended.
APPENDIX E—SIZING OF WATER PIPING SYSTEM
9000
9000
5000
4000
5000
4000
3000
12
2000
3000
″
10
2000
″
8″
1000
1000
5″
400
400
4″
300
300
″
3½
./S
FT
30
1″
.V
20
¾″
.V
ITY
EC
OC
EL
S
T./
EL
10
50
40
″
1¼
ITY
OC
EC
5F
20
″
1½
EL
./S
FT
30
ITY
.V
EC
OC
EL
2″
S
T./
2.5
50
40
100
.V
5F
EC
″
2½
100
200
10
3″
200
1.2
ITY
OC
10
½″
5
5
3 /8″
4
3
4
3
100
40
50
30
10
5
4
3
2
1.0
0.4
0.5
1
0.3
1
0.2
2
0.1
2
20
WATER FLOW RATE, GALLONS PER MINUTE
6″
PRESSURE DROP PER 100 FEET OF TUBE, POUNDS PER SQUARE INCH
Note: Fluid velocities in excess of 5 to 8 feet/second are not usually recommended.
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa, 1 foot per second = 0.305 m/s.
a. This chart applies to smooth new copper tubing with recessed (streamline) soldered joints and to the actual sizes of types indicated on the diagram.
FIGURE E103.3(4)
FRICTION LOSS IN SMOOTH PIPEa (TYPE M, ASTM B88 COPPER TUBING)
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E-15
APPENDIX E—SIZING OF WATER PIPING SYSTEM
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa, 1 foot per second = 0.305 m/s.
a. This chart applies to smooth new steel (fairly smooth) pipe and to actual diameters of standard-weight pipe.
FIGURE E103.3(5)
FRICTION LOSS IN FAIRLY SMOOTH PIPEa
APPENDIX E-16
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E—SIZING OF WATER PIPING SYSTEM
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa, 1 foot per second = 0.305 m/s.
a. This chart applies to fairly rough pipe and to actual diameters, which in general will be less than the actual diameters of the new pipe of the same kind.
FIGURE E103.3(6)
FRICTION LOSS IN FAIRLY ROUGH PIPEa
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E-17
APPENDIX E—SIZING OF WATER PIPING SYSTEM
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 gpm = 3.785 L/m, 1 psi = 6.895 kPa, 1 foot per second = 0.305 m/s.
a. This chart applies to very rough pipe and existing pipe and to their actual diameters.
FIGURE E103.3(7)
FRICTION LOSS IN ROUGH PIPEa
APPENDIX E-18
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E—SIZING OF WATER PIPING SYSTEM
SECTION E104
SELECTION OF PIPE SIZE
E104.1 Size of water service mains, branch mains and
risers. The minimum size water service pipe shall be 3/4 inch
(19.1 mm). The size of water service mains, branch mains
and risers shall be determined according to water supply
demand [gpm (L/m)], available water pressure [psi (kPa)]
and friction loss due to the water meter and developed length
of pipe [feet (m)], including equivalent length of fittings.
The size of each water distribution system shall be determined according to the procedure outlined in this section or
by other design methods conforming to acceptable engineering practice and approved by the code official:
1.
2.
3.
Supply load in the building water distribution system
shall be determined by total load on the pipe being
sized, in terms of water-supply fixture units
(w.s.f.u.), as shown in Table E103.3(2). For fixtures
not listed, choose a w.s.f.u. value of a fixture with
similar flow characteristics.
Obtain the minimum daily static service pressure [psi
(kPa)] available (as determined by the local water
authority) at the water meter or other source of
supply at the installation location. Adjust this minimum daily static pressure [psi (kPa)] for the
following conditions:
2.1. Determine the difference in elevation
between the source of supply and the highest water supply outlet. Where the highest
water supply outlet is located above the
source of supply, deduct 0.5 psi (3.4 kPa)
for each foot (0.3 m) of difference in
elevation. Where the highest water supply
outlet is located below the source of
supply, add 0.5 psi (3.4 kPa) for each foot
(0.3 m) of difference in elevation.
2.2. Where a water pressure-reducing valve is
installed in the water distribution system,
the minimum daily static water pressure
available is 80 percent of the minimum
daily static water pressure at the source of
supply or the set pressure downstream of
the pressure-reducing valve, whichever is
smaller.
2.3. Deduct all pressure losses due to special
equipment such as a backflow preventer,
water filter and water softener. Pressure
loss data for each piece of equipment shall
be obtained through the manufacturer of
such devices.
2.4. Deduct the pressure in excess of 8 psi (55
kPa) due to installation of the special
plumbing fixture, such as temperature
controlled shower and flushometer tank
water closet. Using the resulting minimum
available pressure, find the corresponding
pressure range in Table E104.1.
The maximum developed length for water piping is
the actual length of pipe between the source of
2021 INTERNATIONAL PLUMBING CODE®
4.
5.
supply and the most remote fixture, including either
hot (through the water heater) or cold water branches
multiplied by a factor of 1.2 to compensate for pressure loss through fittings. Select the appropriate
column in Table E104.1 equal to or greater than the
calculated maximum developed length.
To determine the size of water service pipe, meter
and main distribution pipe to the building using the
appropriate table, follow down the selected “maximum developed length” column to a fixture unit
equal to, or greater than the total installation demand
calculated by using the “combined” water supply
fixture unit column of Table E103.3(2). Read the
water service pipe and meter sizes in the first lefthand column and the main distribution pipe to the
building in the second left-hand column on the same
row.
To determine the size of each water distribution pipe,
start at the most remote outlet on each branch (either
hot or cold branch) and, working back toward the
main distribution pipe to the building, add up the
water supply fixture unit demand passing through
each segment of the distribution system using the
related hot or cold column of Table E103.3(2).
Knowing demand, the size of each segment shall be
read from the second left-hand column of the same
table and maximum developed length column
selected in Steps 1 and 2, under the same or next
smaller size meter row. The size of any branch or
main does not need to be larger than the size of the
main distribution pipe to the building established in
Step 4.
SECTION E105
DETERMINATION OF PIPE VOLUMES
E105.1 Determining volume of piping systems. Where
required for engineering design purposes, Table E105.1 shall
be used to determine the approximate internal volume of
water distribution piping.
APPENDIX E-19
APPENDIX E—SIZING OF WATER PIPING SYSTEM
TABLE E104.1
MINIMUM SIZE OF WATER METERS, MAINS AND DISTRIBUTION
PIPING BASED ON WATER SUPPLY FIXTURE UNIT VALUES (w.s.f.u.)
METER AND
SERVICE PIPE
(inches)
DISTRIBUTION PIPE
(inches)
Pressure Range 30 to 39 psi
MAXIMUM DEVELOPMENT LENGTH (feet)
40
60
80
100
150
200
250
300
400
500
3
1 a
2
/
2.5
2
1.5
1.5
1
1
0.5
0.5
0
0
3
3
/4
9.5
7.5
6
5.5
4
3.5
3
2.5
2
1.5
1
32
25
20
16.5
11
9
7.8
6.5
5.5
4.5
/4
/4
3
/4
1
1
32
32
27
21
13.5
10
8
7
5.5
5
3
/4
11/4
32
32
32
32
30
24
20
17
13
10.5
1
11/4
80
80
70
61
45
34
27
22
16
12
11/4
80
80
80
75
54
40
31
25
17.5
13
1
1 /2
1
1
1 /2
87
87
87
87
84
73
64
56
45
36
11/2
11/2
151
151
151
151
117
92
79
69
54
43
2
11/2
151
151
151
151
128
99
83
72
56
45
1
2
87
87
87
87
87
87
87
87
87
86
1 /2
2
275
275
275
275
258
223
196
174
144
122
2
2
365
365
365
365
318
266
229
201
160
134
2
1
533
533
533
533
533
495
448
409
353
311
1
2 /2
METER AND
SERVICE PIPE
(inches)
DISTRIBUTION PIPE
(inches)
Pressure Range 40 to 49 psi
MAXIMUM DEVELOPMENT LENGTH (feet)
40
60
80
100
150
200
250
300
400
500
3
1 a
2
/
3
2.5
2
1.5
1.5
1
1
0.5
0.5
0.5
3
3
/4
9.5
9.5
8.5
7
5.5
4.5
3.5
3
2.5
2
3
/4
1
32
32
32
26
18
13.5
10.5
9
7.5
6
1
1
32
32
32
32
21
15
11.5
9.5
7.5
6.5
3
/4
11/4
32
32
32
32
32
32
32
27
21
16.5
1
11/4
80
80
80
80
65
52
42
35
26
20
1 /2
1
1 /4
80
80
80
80
75
59
48
39
28
21
1
11/2
87
87
87
87
87
87
87
78
65
55
1 /2
1
1 /2
151
151
151
151
151
130
109
93
75
63
2
11/2
151
151
151
151
151
139
115
98
77
64
/4
/4
1
1
1
2
87
87
87
87
87
87
87
87
87
87
11/2
2
275
275
275
275
275
275
264
238
198
169
2
2
365
365
365
365
365
349
304
270
220
185
2
21/2
533
533
533
533
533
533
533
528
456
403
(continued)
APPENDIX E-20
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E—SIZING OF WATER PIPING SYSTEM
TABLE E104.1—continued
MINIMUM SIZE OF WATER METERS, MAINS AND DISTRIBUTION
PIPING BASED ON WATER SUPPLY FIXTURE UNIT VALUES (w.s.f.u.)
METER AND
SERVICE PIPE
(inches)
DISTRIBUTION PIPE
(inches)
MAXIMUM DEVELOPMENT LENGTH (feet)
40
60
80
100
150
200
250
300
400
500
/4
Pressure Range 50 to 60 psi
1 a
2
/
3
3
2.5
2
1.5
1
1
1
0.5
0.5
3
/4
3
/4
9.5
9.5
9.5
8.5
6.5
5
4.5
4
3
2.5
3
/4
8
3
1
32
32
32
32
25
18.5
14.5
12
9.5
1
1
32
32
32
32
30
22
16.5
13
10
8
3
11/4
32
32
32
32
32
32
32
32
29
24
1
11/4
80
80
80
80
80
68
57
48
35
28
11/2
11/4
80
80
80
80
80
75
63
53
39
29
1
1 /2
87
87
87
87
87
87
87
87
82
70
1 /2
1
1 /2
151
151
151
151
151
151
139
120
94
79
2
11/2
151
151
151
151
151
151
146
126
97
81
1
2
87
87
87
87
87
87
87
87
87
87
1 /2
2
275
275
275
275
275
275
275
275
247
213
2
2
365
365
365
365
365
365
365
329
272
232
2
21/2
533
533
533
533
533
533
533
533
533
486
/4
1
1
1
METER AND
SERVICE PIPE
(inches)
DISTRIBUTION PIPE
(inches)
MAXIMUM DEVELOPMENT LENGTH (feet)
Pressure Range Over 60
40
60
80
100
150
200
250
300
400
500
3
1 a
2
/
3
3
3
2.5
2
1.5
1.5
1
1
0.5
3
3
/4
/4
9.5
9.5
9.5
9.5
7.5
6
5
4.5
3.5
3
3
/4
/4
1
32
32
32
32
32
24
19.5
15.5
11.5
9.5
1
1
32
32
32
32
32
28
28
17
12
9.5
3
/4
1
1 /4
32
32
32
32
32
32
32
32
32
30
1
11/4
80
80
80
80
80
80
69
60
46
36
1
80
80
80
80
80
80
76
65
50
38
1
1 /2
1 /4
1
1
1 /2
87
87
87
87
87
87
87
87
87
84
11/2
11/2
151
151
151
151
151
151
151
144
114
94
2
11/2
151
151
151
151
151
151
151
151
118
97
1
2
87
87
87
87
87
87
87
87
87
87
11/2
2
275
275
275
275
275
275
275
275
275
252
2
2
365
368
368
368
368
368
368
368
318
273
2
1
533
533
533
533
533
533
533
533
533
533
2 /2
For SI: 1 inch = 25.4, 1 foot = 304.8 mm.
a. Minimum size for building supply is 3/4-inch pipe.
2021 INTERNATIONAL PLUMBING CODE®
APPENDIX E-21
APPENDIX E—SIZING OF WATER PIPING SYSTEM
TABLE E105.1
INTERNAL VOLUME OF VARIOUS WATER DISTRIBUTION TUBING
OUNCES OF WATER PER FOOT OF TUBE
Copper
Type M
Copper
Type L
Copper
Type K
CPVC CTS
SDR 11
CPVC
SCH 40
CPVC
SCH 80
PE-RT
SDR 9
Composite
ASTM F1281
PEX CTS
SDR 9
3
1.06
0.97
0.84
N/A
1.17
—
0.64
0.63
0.64
1
1.69
1.55
1.45
1.25
1.89
1.46
1.18
1.31
1.18
3
3.43
3.22
2.90
2.67
3.38
2.74
2.35
3.39
2.35
Size Nominal, Inch
/8
/2
/4
1
5.81
5.49
5.17
4.43
5.53
4.57
3.91
5.56
3.91
11/4
8.70
8.36
8.09
6.61
9.66
8.24
5.81
8.49
5.81
11/2
12.18
11.83
11.45
9.22
13.20
11.38
8.09
13.88
8.09
2
21.08
20.58
20.04
15.79
21.88
19.11
13.86
21.48
13.86
N/A = applicable.
For SI: 1 inch = 25.4 mm, 1 ounce = 0.030 L.
APPENDIX E-22
2021 INTERNATIONAL PLUMBING CODE®
[A] APPENDIX F
BOARD OF APPEALS
The provisions contained in this appendix are not mandatory unless specifically referenced in the adopting ordinance.
User Note:
About this appendix: Appendix F provides criteria for Board of Appeals members. Also provided are procedures by which the Board of
Appeals should conduct its business. Code development reminder: Code change proposals to this appendix will be considered by the
Administrative Code Development Committee during the 2022 (Group B) Code Development Cycle. See explanation on page iv.
[A] SECTION F101
GENERAL
[A] F101.1 Scope. A board of appeals shall be established
within the jurisdiction for the purpose of hearing applications for modification of the requirements of this code
pursuant to the provisions of Section 114. The board shall be
established and operated in accordance with this section, and
shall be authorized to hear evidence from appellants and the
code official pertaining to the application and intent of this
code for the purpose of issuing orders pursuant to these
provisions.
[A] F101.2 Application for appeal. Any person shall have
the right to appeal a decision of the code official to the
board. An application for appeal shall be based on a claim
that the intent of this code or the rules legally adopted hereunder have been incorrectly interpreted, the provisions of
this code do not fully apply or an equally good or better form
of construction is proposed. The application shall be filed on
a form obtained from the code official within 20 days after
the notice was served.
[A] F101.2.1 Limitation of authority. The board shall
not have authority to waive requirements of this code or
interpret the administration of this code.
**
[A] F101.2.2 Stays of enforcement. Appeals of notice
and orders, other than Imminent Danger notices, shall
stay the enforcement of the notice and order until the
appeal is heard by the board.
[A] F101.3 Membership of board. The board shall consist
of five voting members appointed by the chief appointing
authority of the jurisdiction. Each member shall serve for
[INSERT NUMBER OF YEARS] years or until a successor has
been appointed. The board members’ terms shall be staggered at intervals, so as to provide continuity. The code
official shall be an ex officio member of said board but shall
not vote on any matter before the board.
[A] F101.3.1 Qualifications. The board shall consist of
five individuals, who are qualified by experience and
training to pass on matters pertaining to building construction and are not employees of the jurisdiction.
[A] F101.3.2 Alternate members. The chief appointing
authority is authorized to appoint two alternate members
who shall be called by the board chairperson to hear
appeals during the absence or disqualification of a
member. Alternate members shall possess the qualifica2021 INTERNATIONAL PLUMBING CODE®
tions required for board membership, and shall be
appointed for the same term or until a successor has been
appointed.
[A] F101.3.3 Vacancies. Vacancies shall be filled for an
unexpired term in the same manner in which original
appointments are required to be made.
[A] F101.3.4 Chairperson. The board shall annually
select one of its members to serve as chairperson.
[A] F101.3.5 Secretary. The chief appointing authority
shall designate a qualified clerk to serve as secretary to
the board. The secretary shall file a detailed record of all
proceedings, which shall set forth the reasons for the
board’s decision, the vote of each member, the absence of
a member and any failure of a member to vote.
[A] F101.3.6 Conflict of member interest. A member
with any personal, professional or financial interest in a
matter before the board shall declare such interest and
refrain from participating in discussions, deliberations
and voting on such matters.
[A] F101.3.7 Compensation of members. Compensation
of members shall be determined by law.
[A] F101.3.8 Removal from the board. A member shall
be removed from the board prior to the end of their term
only for cause. Any member with continued absence from
regular meeting of the board may be removed at the
discretion of the chief appointing authority.
[A] F101.4 Rules and procedures. The board shall establish
policies and procedures necessary to carry out its duties
consistent with the provisions of this code and applicable
state law. The procedures shall not require compliance with
strict rules of evidence, but shall mandate that only relevant
information be presented.
[A] F101.5 Notice of meeting. The board shall meet upon
notice from the chairperson, within 10 days of the filing of
an appeal or at stated periodic intervals.
[A] F101.5.1 Open hearing. All hearings before the
board shall be open to the public. The appellant, the
appellant’s representative, the code official and any
person whose interests are affected shall be given an
opportunity to be heard.
[A] F101.5.2 Quorum. Three members of the board shall
constitute a quorum.
APPENDIX F-1
**
**
APPENDIX F—BOARD OF APPEALS
[A] F101.5.3 Postponed hearing. When five members
are not present to hear an appeal, either the appellant or
the appellant’s representative shall have the right to
request a postponement of the hearing.
**
[A] F101.6 Legal counsel. The jurisdiction shall furnish
legal counsel to the board to provide members with general
legal advice concerning matters before them for consideration. Members shall be represented by legal counsel at the
jurisdiction’s expense in all matters arising from service
within the scope of their duties.
[A] F101.7 Board decision. The board shall only modify or
reverse the decision of the code official by a concurring vote
of three or more members.
[A] F101.7.1 Resolution. The decision of the board shall
be by resolution. Every decision shall be promptly filed in
writing in the office of the code official within three days
and shall be open to the public for inspection. A certified
copy shall be furnished to the appellant or the appellant’s
representative and to the code official.
[A] F101.7.2 Administration. The code official shall
take immediate action in accordance with the decision of
the board.
[A] F101.8 Court review. Any person, whether or not a
previous party of the appeal, shall have the right to apply to
the appropriate court for a writ of certiorari to correct errors
of law. Application for review shall be made in the manner
and time required by law following the filing of the decision
in the office of the chief administrative officer.
APPENDIX F-2
2021 INTERNATIONAL PLUMBING CODE®
INDEX
A
ABS PIPE
Approved standards . . . . . . .Table 605.3, Table 605.5,
Table 702.1, Table 702.2,
Table 702.3, Table 702.4,
Table 1102.4, Table 1102.7
Support . . . . . . . . . . . . . . . . . . . . . . . . . . . .Table 308.5
ACCEPTED
ENGINEERING PRACTICE . . . . . . . . . . . . 202, 604.1,
1304.3
ACCESS COVER . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
ACCESS TO
Air admittance valve . . . . . . . . . . . . . . . . . . . . . . .918.5
Appliances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .502.5
Backflow preventers . . . . . . . . . . . . . . . . . . . . . .608.14
Backwater valve . . . . . . . . . . . . . . . . . . . . . . . . . .714.3
Cleanouts . . . . . . . . . . . . . . . . . . . . . .708.1.11, 1103.4
Filters . . . . . . . . . . . . 1302.5, 1302.9, 1303.8, 1303.12
First-flush diverter . . . . . . . . . . . . . . . . . . . . . . . .1303.4
Fixtures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .405.2
Flexible water connectors . . . . . . . . . . . . . . . . . . .605.6
Floor drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .413.2
Flush tank components. . . . . . . . . . . . . . . . . . . 415.3.4
Grease removal devices . . . . . . . . . . . . . . . . . 1003.3.6
Interceptors and separators . . . . . . . . 1003.10, 1003.5
Manifolds . . . . . . . . . . . . . . . . . . . . . . . . . . . . 604.10.3
Pumps. . . . . . . . . . . . . . . . . . . . . . . . . .602.3.5, 1302.9
Reservoir or interior . . . . . . . . . . . . . . . . . . . . 1301.9.6
Shower compartment . . . . . . . . . . . . . . . . . . . . 421.4.2
Slip joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .405.9
Standpipes . . . . . . . . . . . . . . . . . . . . . . . . . . . . 802.4.3
Sump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 712.3.2
Vacuum breakers . . . . . . . . . . . . . . . . . . . . . . . . .415.2
Valves . . . . . . . . . . . . . . . .503.1, 604.11, 606.3, 712.2,
918.5, 1302.8.1, 1302.9, 1303.12
Waste receptors . . . . . . . . . . . . . . . . . . . . . . . . . .802.4
Water heaters . . . . . . . . . . . . . . . . . . . . . . 502.3, 502.5
Whirlpool pump. . . . . . . . . . . . . . . . . . . . . . . . . . .426.5
ACCESSIBLE . . . . . . . . . . . . . . .202, 403.4, 403.6, 404,
405.3.1, 1002.4
ACCESSIBLE PLUMBING FACILITIES
Clearances . . . . . . . . . . . . . . . . . . . . . . .404.2, 405.3.1
Protection required . . . . . . . . . . . . . . . . . . . . . . .404.3
Route . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .403.5
Signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .403.4
Where required . . . . . . . . . . . . . . . . . . . . . . . . . .404.1
2021 INTERNATIONAL PLUMBING CODE®
ADAPTER FITTING . . . . . . . . . . . . . . . . . 202, 705.16.3,
705.16.4, 705.16.5
ADMINISTRATION
Applicability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102
Approval . . . . . . . . . . . . . . . . . . . . 105, 106.5.6, 111.1
Inspections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108
Intent . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101.3, 114.2
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102.3
Means of appeal . . . . . . . . . . . . . . . . . . . . . . . . . . .114
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101.2
Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106.5.2
Violations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .115
AIR ADMITTANCE VALVE
Chemical waste . . . . . . . . . . . . . . . . . . . . . . . . . 901.3
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Where permitted . . . . . . . . . . . . . . . .905.1, 917.6, 918
AIR BREAK
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Method of providing . . . . . . .802.1.5, 802.1.6, 802.1.7
Where required . . . . . . . . . . . . . . . . . . .406.2, 802.1.2,
802.1.5, 802.3.2
AIR BREAK (Drainage System)
AIR GAP
Annual inspection of . . . . . . . . . . . . . . . . . . . .312.10.1
Application of . . . . . . . . . . . . . . . . . . . . . . . Table 608.1
Bidet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408.2
Clothes washer . . . . . . . . . . . . . . . . . . . . . . . . . . 406.1
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Dishwasher . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 409.2
Drainage . . . . . . . . . . . . . . . . . . . . . . . . . . . 202, 801.1
Method of providing . . . . . . . . . . . . . .608.16.1, 802.3.1
Required . . . . . . . . . . . . .416.4, 417.1, 504.6, 606.5.6,
608.10, 608.3.1, 608.4, 608.14.1,
608.14.2, 608.14.3, 608.14.8,
608.15.2.1, 608.17.1.1, 608.17.1.2,
608.17.2, 608.17.3, 608.17.4.1, 608.17.10,
609.7, 611.2, 802.1.1, 802.1.2,
802.1.3, 802.1.4, 802.1.5,
802.1.6, 802.1.7,
802.3, 802.3.1
AIR GAP (Drainage System) . . . . .202, 801.1, 802.1.2,
802.1.3, 802.1.4, 802.1.5,
802.1.6, 802.1.7, 802.3, 802.3.1
AIR GAP
(Water Distribution System) . . . . . . . . . . . . . . . . 202,
312.10.1, 406.1, 408.2,
409.2, 416.4, 417.1
AIR TEST . . . . . . . . . . . . . . . . . . . . . 312.3, 312.5, 312.8
INDEX-1
INDEX
ALTERATIONS AND REPAIRS . . . . . . . . . . . . 102.2.1,
102.4, 307.4, 612.1
ALTERNATE ON-SITE NONPOTABLE WATER
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1302
ALTERNATIVE ENGINEERED DESIGN
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Requirements for . . . . . . . . . . . . . . . . . . . . . . . . . . 316
Special inspections of . . . . . . . . . . . . . . . . . . . . . 108.3
ALTERNATIVE MATERIALS AND
EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . 105.2, 605.1
ANCHORS . . . . . . . . . . . . . . . . . . . . . . 202, 308.3, 308.4
ANTISIPHON . . . . . . . . 202, 405.3.1, 504.1, Table 608.1
APPLYING THE CODE . . . . . . . . . . . . . . . . . . . . . . . 102
APPROVAL OF ALTERNATIVES . . . . . . . . . . . . . . . 105
APPROVED
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
APPROVED AGENCY . . . 104.3, 105.3.2, 108.2.5.1, 202
AREA DRAIN . . . . . . . . . . . . . . . . . . . . . . . . 202, 1111.1
ATMOSPHERIC VACUUM BREAKER . . . . . . . . . 412.8,
Table 608.1, 608.3.1, 608.14.4,
608.14.6, 608.16.4, 608.16.4.1,
608.16.4.2, 608.17.4.1, 608.17.5
AUTOMATIC CLOTHES WASHER. . . . . . . . . . . . 301.3,
Table 403.1, 406, 413.4,
608.16.4.2, Table 709.1,
802.4.3.1, 1003.6, 1302.2, 1402.1
B
BACKFILLING . . . . . . . . 108.2, 306.2.3, 306.3, 1403.1.5
BACKFLOW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
BACKFLOW, DRAINAGE . . . . . . . . . . . . . . . 202, 714.1
BACKFLOW CONNECTION . . . . . . . 202, 608.7, 608.17
BACKFLOW PREVENTER
Access to. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 608.15
Boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 608.17.2
Carbonated beverage dispenser . . . . . . . . . 608.17.1.1
Coffee and noncarbonated
beverage dispenser . . . . . . . . . . . . . . . . . 608.17.1.2
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Effect of installation . . . . . . . . . . . . . . . . . . . . . . . 607.3
Fire sprinkler system . . . . . . . . . . . . . . . . . . . . 608.17.4
Humidifier . . . . . . . . . . . . . . . . . . . . . . . . . . . 608.17.10
Irrigation system . . . . . . . . . . . . . . . 608.17.5, 1301.11,
1302.11, 1303.14, 1304.3.1
Location of. . . . . . . . . . . . . 608.14.5, 608.15, 608.16.4
Relief port piping from . . . . . . . . . . . . . . . . . 608.15.2.1
Required . . . . 406.1, 408.2, 409.2, 416.4, 417.1, 608.1
Standards . . . . . . . . . . . . . . . . . . . . . . . . . Table 608.1
Testing. . . . . 312.10.2, 1302.12.4, 1303.15.6, 1304.4.2
INDEX-2
BACKFLOW PROTECTION . . . . . . . . . . . . . . . . . 608.1
BACKWATER VALVE
Where required . . . . . . . . . . . . 714.1, 802.1.2, 1101.9,
1111.1, 1302.8.2, 1303.11.1
BAROMETRIC LOOP . . . . . . . . . Table 608.1, 608.14.4
BASE FLOOD ELEVATION . . . . . . . . . . . . . . . 202, 309
BATHING ROOM . . . . . . . . . . . . . . . . . 403.1.1, 403.1.2
BATHROOM GROUP . . . . . . . . . . . . . 202, Table 709.1,
912.1, 912.2.1, E103
BATHTUB
Discharge from . . . . . . . . . . . . . . . . . . . 301.3, 1302.2
Doors in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407.4
Drainage fixture unit . . . . . . . . . . . . . . . . . . . . . . 709.1
Faucet for . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 412
Foot (pedicure bathtub) . . . . . . . . . . . . . . . . . . . . 423.3
Glazing nearby . . . . . . . . . . . . . . . . . . . . . . . . . . 407.3
Outlet and overflow for . . . . . . . . . . . . . . . . . . . . 407.2
Recessed area for trap below slab . . . . . . . . . . 1002.8
Required . . . . . . . . . . . . . . . . . . . . . . . . . . Table 403.1
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 407.1
Walls around built-in type . . . . . . . . . . . . . . . . 421.4.1
Water temperature supplied to . . . . . . . . 412.5, 412.7
Whirlpool . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202, 426
BEVERAGE DISPENSER . . . . . . . . . . . . . . . . 608.17.1
BIDET
Backflow protection . . . . . . . . . . . . . . . . . . . . . . . 408.2
Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408.1
Water temperature supplied to . . . . . . . . . . . . . . 408.3
BOOSTER SYSTEM . . . 604.7, 606.5, 606.5.1. 606.5.5
BOTTLING ESTABLISHMENT . . . . . . . . . . . . . . 1003.7
BRACING, SWAY . . . . . . . . . . . . . . . . . . . . . . . . . 308.6
BRANCH. . . . . . . . . . . . . . . . . 202, 406.2, 503.1, 704.3,
Table 709.1, 710.1, Table 710.1(1),
711.1, 712.3.5, 905.2, 905.5, 906.2,
906.3, 906.4, 907.3, 908.2, 913.4,
914.1, 914.1.1, 914.2, 914.3.1, 914.4,
914.4.1, 914.4.2, 915.2.5, 916.2, 917.1,
917.3, 917.4, 917.4.3, 917.5, 917.6,
917.7, 917.8, 918.3.1, 918.3.2, 919.2,
Table 919.2, 1103.1, 1106.1,
E103, E104
BRANCH INTERVAL . . . . . . . . . . . 202, Table 710.1(2),
711.1, 711.2, 904.2, 906.2,
907.1, 908, 908.1, Table 913.4,
914.4.2, 917.8, 918.3.1, 918.3.2
BRANCH VENT . . . . . . . . . . . . 202, 906.4, 916.2, 917.6
BRASS (See COPPER ALLOY)
BUILDING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
BUILDING DRAIN
Branches of . . . . . . . . . . . . . . . . . . . . . . Table 710.1(2)
Cleanouts for . . . . . . . . . . . . 708.1.1, 708.1.3, 708.1.4
Connection to building sewer . . . . . . . . . . . . 705.16.4
2021 INTERNATIONAL PLUMBING CODE®
INDEX
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Existing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .703.4
Material, above-ground . . . . . . . . . . . . . . .Table 702.1
Material, below ground . . . . . . . . . . . . . . .Table 702.2
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . Table 710.1(1)
BUILDING DRAINAGE SYSTEM
Below sewer level . . . . . . . . . . . . . . . . . . . . . . . . .712.1
Definition (See DRAINAGE SYSTEM) . . . . . . . . . . 202
Excluding detrimental materials from . . . . . . . . . .302.1
Oil Separators for . . . . . . . . . . . . . . . . . . . . . . . .1003.4
BUILDING SEWER
Cleanouts . . . . . . . . . . . . . . . . . . . . . . 708.1.2, 708.1.4
Connection to building drain . . . . . . . . . . . . . . 708.1.3
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
In same trench as nonpotable water piping . . .1301.11
In same trench as storm sewer . . . . . . . . . . . . . .703.3
Material . . . . . . . . . . . . . . . . . . . . . . . . . . .Table 702.3
Reuse of existing . . . . . . . . . . . . . . . . . . . . . . . . .703.4
Separation from water service . . . . . . . . . . . . . . .603.2
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . Table 710.1(1)
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
BUILDING SUBDRAIN . . . . . . . . . . . . . . . . . 202, 712.1,
Table 915.2.2, 1112, 1112.1
BUILDING TRAP
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Prohibition of . . . . . . . . . . . . . . . . . . . . . . . . . . .1002.6
BUNDLED WATER PIPING . . . . . . . . . . . . . . . . . .606.7
C
CAST-IRON PIPE
Approved standards . . . . . . .Table 702.1, Table 702.2,
Table 702.3, Table 702.4,
Table 1102.4, Table 1102.5,
Table 1102.7
Joints . . . . . . . . . . . . . . . . . .705.3, 705.16.1, 705.16.3
Support of . . . . . . . . . . . . . . . . . . . . . . . . . .Table 308.5
CAULKING FERRULES . . . . . . . . . . . . . . . . . . . .705.18
CHANGE IN DIRECTION OF DRAINAGE
Anchorage for . . . . . . . . . . . . . . . . . . . . . . . . . . . .308.7
Cleanouts for . . . . . . . . . . . . . . . . . . . . . . . . . . 708.1.4
Support against sway . . . . . . . . . . . . . . . . . . . . . .308.6
CHEMICAL WASTE
Exclusion from the sewer . . . . . . . . . . . . . . . . . . .803.1
Neutralizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . .803.1
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .702.6
System venting . . . . . . . . . . . . . . . . . . . . . . . . . .901.3
CIRCUIT VENT
Connection of . . . . . . . . . . . . . . . . . . . . . . . . . . . .905.1
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Requirements for system . . . . . . . . . . . . . . . . . . . . 914
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .906.2
2021 INTERNATIONAL PLUMBING CODE®
CIRCULATING HOT WATER SYSTEM
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 607.2
CISTERN . . . . . . . . . . . . . . . . . . . . . . . . . . .202, 602.3.1
CLAY PIPE
Approved standards . . . . . . . . . . . . . . . . .Table 702.3,
Table 1102.4, Table 1102.5
Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 705.11
CLEANOUT
Building drain . . . . . . . . . . . . . . . . . . . . . . . . . . .708.1.1
Change of direction . . . . . . . . . . . . . . . . . . . . . .708.1.4
Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . .708.1.10
Condensate drain . . . . . . . . . . . . . . . . . . . . . . .314.2.5
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Direction of flow . . . . . . . . . . . . . . . . . . . . . . . . .708.1.8
Floor accessed . . . . . . . . . . . . . . . . . . . . . . 708.1.11.2
Horizontal drains . . . . . . . . . . . . . . . . . . . . . . . .708.1.1
Location of . . . . . . . . . . . . . . . . . . . . . . . . . . . .708.1.11
Manholes . . . . . . . . . . . . . . . .708.1.1, 708.1.2, 708.1.7
On stacks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .708.1.5
Plugs, materials for . . . . . . . . . . . . . . . . . . . . . .708.1.6
Prohibited use of . . . . . . . . . . . . . . . . . . . . . . .708.1.12
Sewers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .708.1.2
Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .708.1.5
Trim covers for plugs . . . . . . . . . . . . . . . . . . 708.1.11.1
Where required . . . . . . . . . . . . . . . . . . . . . . . . . . 708.1
CLEAR WATER WASTE . . . . . . . . . . . . . . . . . . .802.1.5
CLEARANCES . . . . . . . . . 404.2, 405.3.1, 502.5, 918.8
CLOTHES WASHER
(See AUTOMATIC CLOTHES WASHER)
CODE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
CODE COMPLIANCE AGENCY . . . . . . . . . . . . . . . .103
CODE OFFICIAL
Application for permit . . . . . . . . . . . . . . . . . . . . . 106.3
Appointment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103.2
Approval of modifications . . . . . . . . . . . . . . . . . . . .105
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Department records . . . . . . . . . . . . . . . . . . . . . . 104.7
Duties and powers . . . . . . . . . . . . . . . . . . . . . . . . .104
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104.1
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104.5
Inspections . . . . . . . . . . . . . . . . . . . . . . . . . 104.3, 108
COFFEE MACHINE . . . . . . . . . . . . . . . . . . . . 608.17.1.2
COLLECTION PIPE
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
On-site nonpotable water reuse system . . . . . . 1302.4
Testing of . . . . . . . . . . . . . . . . . .1302.12.1, 1303.15.3
COMBINATION FIXTURE . . . . . 202, Table 604.3, E103
COMBINATION WASTE AND VENT SYSTEM
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . .915
INDEX-3
INDEX
COMBINED BUILDING DRAIN . . . . . . . . . . . . . . . . . 202
COMBINED BUILDING SEWER . . . . . . . . . . . . . . . . 202
COMMON VENT . . . . . . . . . . . . . . . . . . . . . . . . 202, 911
COMPARTMENT, WATER CLOSET . . . . . . . . 405.3.1,
405.3.4
CONCEALED FOULING SURFACE . . . . . . . 202, 402.1
CONCRETE PIPE
Approved standards . . . . . . Table 702.3, Table 1102.4
CONDENSATE DISCHARGE
Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314.2.1.1
CONDENSATE DRAIN
Configured for clearing blockages. . . . . . . . . . . 314.2.5
Mini-split systems . . . . . . . . . . . . . . . . . . . . . 314.2.4.1
Piping material. . . . . . . . . . . . . . . . . . . . . . . . . . 314.2.2
Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 314.2.4
Termination identification . . . . . . . . . . 314.1.1, 314.2.3
CONDUCTOR
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
CONFLICTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301.7
CONNECTION TO PUBLIC SEWER . . . . . . . . . . 701.2
CONNECTIONS TO SUMPS AND EJECTORS
Below sewer level . . . . . . . . . . . . . . . . . . . . . . . . 712.1
CONSERVATION, WATER AND ENERGY
Fixtures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 604.4
Flow rates . . . . . . . . . . . . . . . . . . . . . . . . . Table 604.3
Insulation . . . . . . . . . . . . . . . . . . . 505, 607.2.1, 607.5
CONSTRUCTION DOCUMENTS . . . . . . . . . . . . . . . 110
CONTAMINATION . . . . . . . . . . . . 202, 602.3.1, 602.3.5,
606.5.8, 608.1, Table 608.1,
608.3, 608.4, 608.13, 608.18,
608.18.1, Table 608.18.1,
608.18.2, 610.1
CONTROLLED FLOW STORM DRAINAGE . . . . . 1110
COPPER ALLOY . . . . . . . . . . . . . 202, 314.2.2, 405.4.1,
Table 605.5, Table 605.7,
Table 605.8, Table 702.4,
705.16.1, 705.18, 705.19,
Table 1102.7
COPPER OR COPPER-ALLOY
PIPE OR TUBING
Approved standards . . . . . . Table 605.3, Table 605.4,
Table 702.1, Table 702.2,
Table 702.3
COPPER SHEET (See SHEET COPPER)
CPVC PIPE OR TUBING
Approved standards . . . . . . . Table 605.3, Table 605.4
CRITICAL LEVEL (C-L). . . . . . . . . . 608.14.5, 608.14.6,
608.16.4
CROSS CONNECTION . . . . . . . . . . . 202, 601.2, 608.1,
608.7, 608.7.1
INDEX-4
CUTTING OR NOTCHING,
STRUCTURAL MEMBERS . . . . . . . . . . 307.2, 307.4,
Appendix C
D
DEMAND RECIRCULATION WATER SYSTEM
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 607.2.1.2
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
DEPTH OF TRAP SEAL. . . . . . . . . . . . . . . . 202, 1002.4
DESIGN FLOOD ELEVATION . . . . . . . . . . . . 202, 309.2
DESIGN PROFESSIONAL . . . . . . . . 108.3.2, F101.3.1,
307.4, 316.1
DETRIMENTAL WASTES . . . . . . . . . . . . . . 302, 1003.1
DEVELOPED LENGTH . . . . . . . . . . . 202, Table 604.5,
607.2, 706.3, 708.1.1, 708.1.2,
708.1.3, 708.1.4, 802.3, 904.5,
906.1, Table 906.1, 906.2, 906.3,
Table 906.5.1, 909.1, 917.3, 917.4.1,
917.4.2, 917.4.3, 918.4, 919.2, Table 919.2,
1002.1, 1403.1.2, E103.3, E103.3.1,
Table E103.3.1(1), E104.1
DISCHARGE PIPE . . . . . . . . . . . . . . . 202, 504.6, 608.4
DISHWASHING MACHINE . . . . . . . . . . . . 409, 802.1.6
DISINFECTION OF
POTABLE WATER SYSTEM . . . . . . . . . . . . . . . . 610
DISTANCE OF TRAP FROM VENT . . . . . . Table 909.1
DISTRIBUTION SYSTEM (See WATER)
DRAIN
Roof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1105
Storm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1106
DRAINAGE FITTING . . . . . . . . . 706.1, 708.1.1, 708.1.2
DRAINAGE FIXTURE UNITS
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Values for continuous flow . . . . . . . . . . . . . . . . . . 709.3
Values for fixtures . . . . . . . . . . . . . . . . . . . Table 709.1
DRAINAGE SYSTEM
Connection to sewer or private disposal system . 701.2
Determining size . . . . . . . . . . . . . . . . . . . . . . . . . 710.1
Fixture units . . . . . . . . . . . . . . . . . . Table 709.1, 709.3
Indirect waste . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 802
Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 705
Material detrimental to . . . . . . . . . . . . . . . . . . . . . . 302
Materials. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 702
Obstructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 706.2
Offset sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 711
Provisions for future fixtures. . . . . . . . . . . . . . . . . 710.2
Sizing . . . . . . . . . . . . . . Table 710.1(1), Table 710.1(2)
Slope of piping . . . . . . . . . . . . . . . . . . . . . . Table 704.1
Sumps and ejectors . . . . . . . . . . . . . . . . . . . . . . . . 712
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312
2021 INTERNATIONAL PLUMBING CODE®
INDEX
DRINKING FOUNTAIN
Accessibility requirements . . . . . . . . . 410.3.1, 410.3.2
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .410.1
Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .403.5
Number required . . . . . . . . . . . . . . . Table 403.1, 410.1
Prohibited location . . . . . . . . . . . . . . . . . . . . . . . .410.5
Small occupancies . . . . . . . . . . . . . . . . . . . . . . . .410.2
Substitution for . . . . . . . . . . . . . . . . . . . . . . . . . . .410.4
DRINKING WATER TREATMENT UNIT . . . . . . . . . 611
DUAL FLUSHING DEVICE . . . . . . . . . . . . . 202, 425.1.3
E
EFFECTIVE OPENING . . . . . . . . . . . . . . . . . . . . . . .202,
Table 608.16.1, 802.3.1
EJECTOR, SEWAGE . . . . . . . . . . . . . . . . . . . . . . . . 712
EJECTOR CONNECTION . . . . . . . . . . . . . . . . . 712.3.5
ELEVATOR SHAFT . . . . . . . . . . . . . . . . . . . . . . . .301.6
EMERGENCY FLOOR DRAIN . . . . . . 202, Table 709.1,
912.2.1, 1002.4.1, 1002.4.1.5
EMERGENCY SHOWER . . . . . . . . . . . . . . . . . . . . . 411
EMPLOYEE TOILET FACILITIES . . . . . . . . . . . . .403.3
ENGINEERED DESIGN, ALTERNATIVE . . . . . . . . 316
ESSENTIALLY NONTOXIC
TRANSFER FLUID. . . . . . . . . . . . . . . . . 202, 608.17.3
ESSENTIALLY TOXIC
TRANSFER FLUID. . . . . . . . . . . . . . . . . 202, 608.17.3
EXCAVATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
EXISTING BUILDING . . . . . . . . . . . . . . . . . . . . . 102.2.1
EXISTING BUILDING
PLUMBING SYSTEMS . . . . . . . . . . . . .102.2, 102.2.1
EXISTING INSTALLATION . . . . . . . . . . . . . . .102.2, 202
EYEWASH STATION . . . . . . . . . . . . . . . . . . . . . . . . 411
F
FACILITIES, TOILET . . . . . . . . . . . . . . . . . . . . . . . . 403
FAMILY AND ASSISTED USE . . . . . . . 403.1.2, 403.2.1
FAUCET . . . . . . . . . . . . . . . . . . .202, 309.2, 401.1, 412,
412.1, 412.1.1, 412.6, 412.7,
Table 604.4, 605.2, 605.2.1,
607.4, Table 608.1, 608.9.1,
Table 608.16.1, 608.16.4.1,
Table 709.1, 1301.3,
Table E103.3(2)
FEES . . . . . . . . . . . . . . . . . . . . . . . . . . 104.7, 106.5, 109
FERRULE . . . . . . . . . . . . . . . . . . . . .705.16.1, 705.16.5,
705.18, Table 705.18
FILL VALVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 415.3.1
FITTINGS
Approved standards . . . . . . . Table 605.5, Table 702.4
Drainage system . . . . . . . . . . . . . . . . . . . . . . . . . . 706
2021 INTERNATIONAL PLUMBING CODE®
FIXTURE
Definition (See PLUMBING FIXTURE) . . . . . . . . . .202
FIXTURE CALCULATIONS . . . . . . . . . . . . . . . .403.1.1
FIXTURE FITTING . . . . . . . . . . . . . . . . . . . . . . .202, 412
FIXTURE LOCATION . . . . . . . . . . . . . . . . . . . . .405.3.1
FIXTURE SUPPLY . . . . . . . . . . 202, 604.3, Table 604.3,
604.5, 606.2, E103.2.2
FIXTURE TRAPS . . . . . . . . . . . . . . . . . . . . . . . . . .1002
Acid-resisting . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.9
Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.6
Design of . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.2
For each fixture . . . . . . . . . . . . . . . . . . . . . . . . . 1002.1
Prohibited . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.3
Seal protection . . . . . . . . . . . . . . . . . . . . . . . .1002.4.1
Seals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.4
Setting and protection . . . . . . . . . . . . . . . . . . . . 1002.7
Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.5
FIXTURE UNITS, DRAINAGE
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Values for continuous flow . . . . . . . . . . . . . . . . . 709.3
Values for fixtures . . . . . . . . . . . . . .709.1, Table 709.1
FLOOD HAZARD AREA . . . . . . . . . . .202, 309.1, 309.2
FLOOD LEVEL RIM . . . . . . . . . . . . . . . . . . . . . . . . .202
FLOOD-RESISTANT CONSTRUCTION
Design flood elevation . . . . . . . . . . . . . . . . . . . . . .202
Flood hazard area . . . . . . . . . . . . . . . . . . . . . . . . .202
Flood hazard resistance . . . . . . . . . . . . . . . . . . . . .309
FLOOR DRAINS . . . . . . . . . . . . . . . . . 412, Table 709.1
FLOOR DRAINS, EMERGENCY . . . . 202, Table 709.1
FLOOR FLANGES . . . . . . . . . . . . . . . .405.4.1, 405.4.2
FLOW CONTROL (Vented) . . . . . . . . . . 202, 1003.3.5.2
FLOW PRESSURE. . . . . . . . . . . . . . .Table 604.3, 604.7
FLOW RATES . . . . . . . . . . . . . . . . . 604.3, Table 604.3,
Table 604.4, 604.10
FLUSHING DEVICES
Dual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425.1
Flush tanks . . . . . . . . 415.2, Table 604.3, Table 604.5
Flushometer tanks . . . . . . . . . . . . . 415.2, 604.3, 604.5
Flushometer valves . . 415.2, Table 604.3, Table 604.5
Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .415
FOOD HANDLING DRAINAGE . . . . . .802.1.1, 802.1.7
FOOD WASTE DISPOSER . . . . . . . . . . . . . . . . . . . .416
FOOTBATHS (PEDICURE BATHS) . . . . . . . . . . . 423.3
FOOTINGS, PROTECTION OF . . . . . . . . . . . . . . . 307.5
FREEZING, PROTECTION OF
BACKFLOW DEVICES . . . . . . . . . . . . . . . . .608.15.2
FREEZING, PROTECTION OF PIPES . . . . . . . . . 305.4
FROST CLOSURE . . . . . . . . . . . . . . . . . . . . . . . . 903.2
FULL OPEN VALVE
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 605.3
INDEX-5
INDEX
FUTURE FIXTURES . . . . . . . . . . . . . . . . . . . . . . . 704.4
G
GALVANIZED STEEL PIPE . . . . . . . . . . . . Table 605.3,
Table 605.4, 605.17
GARBAGE CAN WASHERS . . . . . . . . . . . . . . . . . . 417
GARBAGE DISPOSAL
(See FOOD WASTE DISPOSER)
GENERAL REGULATIONS . . . . . . . . . . . . . . . . . . . 301
Conflicts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 301.7
Connection to plumbing system . . . . . . . . . . . . . 301.3
Connection to public water and sewer . . . 301.3, 301.4
Elevator machinery rooms . . . . . . . . . . . . . . . . . 301.6
Health and safety . . . 115.6, 115.6.1, 115.6.2, 115.6.3
Materials detrimental . . . . . . . . . . . . 302, 302.1, 302.2
Piping sizes indicated . . . . . . . . . . . . . . . . . . . . . 301.5
Protection of pipes . . . . . . . . . . . . . . . . . . . . . . . . . 305
Rodentproofing . . . . . . 304, 304.1, 304.2, 304.3, 304.4
Sleeves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305.3
Strains and stresses in pipe . . . . . . . . . . . . . . . . 305.2
Toilet facilities for workers . . . . . . . . . . . . . . . . . . . 311
Trenching, excavation and backfill . . . . . . . . . . . . . 306
Washroom requirements . . . . . . . . . . . . . . . . . . . . 310
GRAYWATER (See also ALTERNATE
ON-SITE NONPOTABLE WATER) . . . . . . . . . . . 202,
1302.6.1, 1401.1, 1401.2,
1401.3, 1401.4, 1401.5,
1401.6, 1402.1, 1402.3,
Table 1402.3, 1403.1.1
GREASE INTERCEPTORS . . . . . . . . . . . . . . 202, 1003
Additives to . . . . . . . . . . . . . . . . . . . . . . . . . . . 1003.3.3
Approved standards . . . . . . . . . . . . 1003.3.5, 1003.3.7
Capacity . . . Table 1003.3.5.1, 1003.4.2.1, 1003.4.2.2
Discharge . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1003.3.8
Food waste disposers to . . . . . . . . . . . . . . . . 1003.3.2
Gravity-type . . . . . . . . . . . . . . . . . . . . . . . . . . 1003.3.7
Hydromechanical-type . . . . . . . . . . . . . . . . . . 1003.3.5
Not required . . . . . . . . . . . . . . . . . . . . . . . . . . 1003.3.4
Piping leading to . . . . . . . . . . . . . . . . . . . . . . . . . 704.1
Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1003.3.1
GREASE REMOVAL DEVICE,
AUTOMATIC (GRD) . . . . . . . . . . . . . . . 202, 1003.3.1,
1003.3.4, 1003.3.5, 1003.3.6
GREASE-LADEN WASTE. . . . . . . . . . . . . 202, 1003.3.1
GRIDDED WATER
DISTRIBUTION SYSTEM . . . . . . . . . . . . . . 202, 604.2
GROUP WASH FIXTURE . . . . 202, 419.1, 419.3, 419.5
GUTTERS . . . . . . . . . . . . . . . . . . . 1106.6, Table 1106.6
INDEX-6
H
HANGERS AND SUPPORTS
Attachment to buildings . . . . . . . . . . . . . . . . . . . . 308.4
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308.3
Seismic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308.2
Spacing . . . . . . . . . . . . . . . . . . . . . . . . . . . Table 308.5
HEALTH AND SAFETY . . . . . . . . . . . . . . . . . . . . . 101.3
HEALTH CARE PLUMBING . . . . . . . . . . . . . . . . . . 609
HEAT EXCHANGERS . . . . . . . . . . . . . . . . . . . 608.17.3
HORIZONTAL PIPE
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Slope for drainage . . . . . . . . . . . . . . . . . . . . . . . . 704.1
HOT WATER
Circulating system . . . . . . . . . . . . . . . . . . 202, 607.2.1
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Demand recirculation water system . . . . . . . 607.2.1.2
Flow of hot water from fixtures . . . . . . . . . . . . . . 607.4
Heaters and tanks . . . . . . . . . . . . . . . . . . . . .Chapter 5
Pipe insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . 607.5
Pumps for water heaters . . . . . . . . . . . . . . . . . 607.2.1
Recirculating systems with
thermostatic mixing valves . . . . . . . . . . . . . 607.2.2
Supply system . . . . . . . . . . . . . . . . . . . . . . . . . . . . 607
Temperature maintenance (Heat trace) . . . . . 607.2.1
HOUSE TRAP (See BUILDING TRAP)
HUMIDIFIER . . . . . . . . . . . . . . . . . . . . . . . . . 608.17.10
I
INDIRECT WASTE . . . . . . . . . . . . . . . . . . . . . . . . . 802
Air gap or break . . . . . . . . . . . . . . . . . 802.3.1, 802.3.2
Food handling establishment . . . . . . . . . . . . . 802.1.1
Receptors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 802.4
Special wastes . . . . . . . . . . . . . . . . . . . . . . . . . . . 803
Wastewater temperature . . . . . . . . . . . . . . . . . . . 702.5
Where required . . . . . . . . . . . . . . . . . . . . . . . . . . 802.1
INDIRECT WASTE PIPE . . . . . . . . . . . . . . . . .Chapter 8
INDIVIDUAL VENT . . . . . . . . . . . . . . . . . . . . . . . . . 910
INDIVIDUAL WATER SUPPLY
INSPECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108.1
Final . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108.2
Reinspection . . . . . . . . . . . . . . . . . . . . . . . . . . 108.4.3
Required. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108.2
Rough-in. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108.2
Scheduling of . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108.2
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108.4
2021 INTERNATIONAL PLUMBING CODE®
INDEX
INSPECTOR (See CODE OFFICIAL)
INSULATION . . . . . . . . . . . . . . . . . . . . . . . . . .505, 607.5
INTERCEPTORS AND SEPARATORS . . . . . . . . . 1003
Access to . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1003.10
Additives to . . . . . . . . . . . . . . . . . . . . . . . . . . . 1003.3.3
Approved standards . . . . . . . . . . . . 1003.3.5, 1003.3.7
Bottling establishments. . . . . . . . . . . . . . . . . . . .1003.7
Clothes washers . . . . . . . . . . . . . . . . . . . . . . . . .1003.6
Connection of discharge . . . . . . . . . . . . . . . . . 1003.3.8
Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Fats, oils and greases systems . . . . . . . . . . . 1003.3.7
Not required . . . . . . . . . . . . . . . . . . . . . . . . . . 1003.3.4
Oil and flammable liquids separators . . . . . . . . .1003.4
Rate of flow control for grease interceptors .1003.3.5.2
Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1003.1
Slaughterhouses . . . . . . . . . . . . . . . . . . . . . . . . .1003.8
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . 905.4, 1003.9
IRRIGATION, LAWN . . . . . . . . . . . . . . . . . . . . 608.17.5
ISLAND FIXTURE VENT . . . . . . . . . . . . . . . . . . . . . 916
J
JOINTS AND CONNECTIONS . . . . . . . . . . . . . 605, 705
ABS plastic pipe . . . . . . . . . . . . . . . . . . . 605.10, 705.2
Between different materials . . . . . . . . . 605.23, 705.16
Brazed joints . . . . 605.12.1, 605.13.1, 705.5.1, 705.6.1
Building drain to
building sewer (ABS/PVC) . . . . . . . . . . . . . 705.16.4
Cast-iron pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . .705.3
Caulked joint . . . . . . . . . . . . . . . . . . . . 705.3.1, 705.7.1
Concrete pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . .705.4
Copper or copper-alloy pipe . . . . . . . . . . 605.12, 705.5
Copper or copper-alloy tubing . . . . . . . . 605.13, 705.6
CPVC plastic pipe. . . . . . . . . . . . . . . . . 605.14, 605.15
Expansion joints . . . . . . . . . . . . . . . . . . . . . . . . . .308.8
Flared . . . . . . . . . . . . . . . 605.13.2, 605.16.1, 605.18.1
Galvanized steel pipe . . . . . . . . . . . . . . . . . . . . .605.17
Grooved and shouldered . . . . . . . .605.13.3, 605.17.3,
605.21.2, 605.22.3
Heat fusion . . . . . . . . . . . . . . . . . . .605.18.2, 605.19.1,
705.12.1, 705.13.1, 705.14.1
Mechanical joints . . . . . . . . . . . . . . . . . . . . . . 605, 705
Polyethylene of raised temperature (PE-RT) . . .605.24
Polyethylene plastic pipe or tubing (PE) . . . . . . .605.18
Polypropylene plastic pipe or tubing (PP) . . . . . .605.19
Press-connect. . . . . . . . . . . . . . . . . . . . . 202, 605.13.5
Prohibited . . . . . . . . . . . . . . . . . . . . . . . . . . .605.9, 707
Push-fit . . . . . . . . . . . . . . 605.13.7, 605.14.4, 605.16.3
PVC plastic pipe . . . . . . . . . . . . . . . . . . 605.21, 705.10
Screwed together . . . . . . . . . . . . . . 605.23.1, 705.16.2
Slip joints . . . . . . . . . . . . . . . . . . . . . . . . 405.9, 1002.2
2021 INTERNATIONAL PLUMBING CODE®
Soldered joints . . . . . . . . . . . . . . . . 605.12.3, 605.13.6,
705.5.3, 705.6.3
Solvent cemented . . . . . 605.10.2, 605.14.2, 605.15.2,
605.21.2, 705.2.2,
705.10.2, 705.16.4
Stainless steel . . . . . . . . . . . . . . . . . . . . . . . . . . 605.22
Threaded . . . . . . . . . . . . 605.10.3, 605.12.4, 605.14.3,
605.17.1, 605.21.4, 705.2.3,
705.5.4, 705.8.1, 705.10.3,
705.16.2, 705.16.3
Vitrified clay pipe . . . . . . . . . . . . . . . . . . . . . . . . 705.11
Welded . . . . . . . . . . . . . . .605.12.5, 605.22.2, 705.5.5
K
KITCHEN
Grease interceptor . . . . . . . . . . . . . . . . . . . . .1003.3.1
Hot water for . . . . . . . . . . . . . . . . . . . . . . . . . . . . 609.3
Island sink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 916.1
Passage through . . . . . . . . . . . . . . . . . . . . . . .403.3.1
Sink drainage fixture unit . . . . . . . . . . . . . Table 709.1
Sink requirement . . . . . . . . . . . . . . . . . . . Table 403.1
Sink standards . . . . . . . . . . . . . . . . . . . . . . . . . . . .422
L
LABELS FOR BUNDLED WATER PIPING . . . . . 606.7
LAUNDRY TRAY . . . . . . . . . . . . . . . . . . . . . . . . . . . .418
LAVATORY . . . . . . . . . . . . . . . . . . . . . . . . .403.1.3, 419
LEADER
Connecting to combined sewer . . . . . . . . . . . . . .1103
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
For rainwater collection systems . . . . . . . . . . . 1303.3
Sizing . . . . . . . . . . . . . . 1106.1, 1106.3, Table 1106.3
Slope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1303.5.1
LEAD-FREE SOLDER AND FLUX . . . . . . . . . . . . . 202,
605.12.3, 605.13.6
LIGHT AND VENTILATION REQUIREMENT . . . . 310.1
LOADING, SANITARY DRAINAGE SYSTEM . . . . .709
LOCATION
Anchorage for drain piping . . . . . . . . . . . . . . . .308.7.1
Drinking fountain . . . . . . . . . . . . . . . . . . . .403.5, 410.5
Fixture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 405.3
Fixtures, obstruction . . . . . . . . . . . . . . . . . . . . .405.3.3
Potable water supply tank . . . . . . . . . . . . . . . .606.5.8
Prohibited, drinking fountain . . . . . . . . . . . . . . . . 410.5
Secondary roof drain discharge . . . . . . . . . . . . 1108.2
Storage tank . . .1302.7.1, 1303.10.1, Table 1303.10.1
Subsoil irrigation site . . . . . . . . . . . . . . . . . . . . 1402.3
Toilet facilities, malls . . . . . . . . . . . . . . . . . . . . .403.3.4
Toilet facilities, other than in malls . . . . . . . . . .403.3.3
Toilet room and kitchen . . . . . . . . . . . . . . . . . .403.3.2
INDEX-7
INDEX
Trench . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307.5
Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . 606.1, 606.2
Vent terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . 903.5
Water heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . 501.4
Wells . . . . . . . . . . . . . . . . . . . 608.18.8, Table 1302.7.1
M
MAIN . . . . . . . . . . . . . . . . . . . . 202, 501.2, 604.6, 604.7,
604.8, 604.8.1, 606.1, 606.5.1,
607.2.1, 608.1, 609.1, 609.2,
715.4, 718.1, 1003.4, 1103.1,
1301.10, Table 1302.7.1, 1303.12,
1303.16, Table 1402.3, E102.2.1,
E103.2.2, E103.3, Table E103.3(1),
E103.3.1, E104.1, Table E104.1
MANHOLE . . . . . . . . . . . . . . . . . . . . . 708.1.1, 708.1.2,
708.1.7, 714.1, 1301.9.6
MANIFOLD. . . . . . . . . . . . . . . . . . . . Table 604.5, 604.10
MATERIAL
Above-ground drainage and vent pipe . . . Table 702.1
Alternative . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105.2
Approved . . . . . . . . . . . . . 105.4, 108.2.3, 308.3, 316,
402.1, 504.7, 608.18.5, 702.6.
708.1.6, 712.3.2, 1002.2,
1002.3, 1113.1.2, 1303.2
Building sewer pipe . . . . . . . . . . . . . . . . . . . . . . 702.3
Building storm sewer pipe . . . . . . . . . . . . . . . . 1102.4
Chemical waste system . . . . . . . . . . . . . . . . . . . 702.6
Fittings . . . . . Table 605.5, Table 702.4, Table 1102.7
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303.1
Joint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 605, 705
Roof drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1102.6
Sewer pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 702.3
Standards for . . . . . . . . . . . . . . . . . . . . . . . Chapter 15
Storm sewer pipe . . . . . . . . . . . . . . . . . . Table 1102.4
Subsoil drain pipe . . . . . . . . . . . . . . . . . . . . . . . 1102.5
Underground building drainage and
vent pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 702.2
Vent pipe . . . . . . . . . . . . . . . . . . . . . . . . . 702.1, 702.2
Water distribution pipe . . . . . . . . . . . . . . . Table 605.4
Water service pipe . . . . . . . . . . . . . . . . . . Table 605.3
MATERIAL, FIXTURE
Quality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 402.1
Special use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 402.2
MATERIAL, SPECIAL
Caulking ferrules . . . . . . . . . . . . . . . . . . . . . . . 705.18
Cleanout plugs . . . . . . . . . . . . . . . . . . . . . . . . . 708.1.6
Sheet copper . . . . . . . . . . . . . . . . . . . . . . . . . . . 402.3
Sheet lead . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 402.4
Soldering bushings . . . . . . . . . . . . . . . . . . . . . . 705.19
MECHANICAL JOINTS . . . . . . . . . . . . . . . . . . 605, 705
INDEX-8
MEDICAL GAS, NONFLAMMABLE . . . . . . . . . . 1202.1
N
NONPOTABLE WATER REUSE SYSTEMS . . . . 1302
NONPOTABLE WATER SYSTEMS
Disinfection . . . . . . . . . . . . . . . . . . . . . . . . . . 1301.2.1
Distribution piping color . . . . . . . . . . . . . . . . . 608.9.2.1
Filtration . . . . . . . . . . . . . . . 1301.2.2, 1302.5, 1303.8
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 608.9
Protection of potable water from . . . . . . 608.1, 1301.5
Requirements for . . . . . . . . . . . . . . . . . . . . .Chapter 13
Signage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1301.3
Tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1301.9
O
OFFSET
Closet flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . 704.2
Definition, piping . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Drainage . . . . . . . . . . . . . 704.3, 710.1.1, 710.1.2, 711
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 907, 917.7
OPENINGS
Through walls or roofs . . . . . . . . . . . 304.4, 305.5, 315
OVERFLOW . . . . . . . . . . . . . . . . . 405.8, 407.2, 415.3.1,
415.3.2, 606.5.4, 1101.7, 1108.1
OXYGEN SYSTEMS . . . . . . . . . . . . . . . . . . . . . . 1203.1
P
PAN
Auxiliary (condensate) . . . . . . . . . . . . . . . . . . . 314.2.3
Water heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . 504.7
PARKING GARAGE . . . . . . . . . . . . . . . . . . 305.7, 403.3,
1002.1, 1003.4.2.2
PARTITION
Fixture . . . . . . . . . . . . . . . . . 405.3.1, 405.3.4, 405.3.5
Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.2, 1002.3
PEDICURE BATHS . . . . . . . . . . . . . . . . . . . . . . . . 423.3
PENETRATIONS . . . . . . . . . . . . . . . . . . . . . . 307.3, 315
PERMIT
Application for . . . . . . . . . . . . . . . . . . . . . . . . . . . 106.3
Conditions of . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106.5
Fees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Posting of . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106.5.7
Suspension of . . . . . . . . . . . . . . . . . . . . . . . . . 106.5.5
PIPE BURSTING . . . . . . . . . . . . . . . . . . . . . . . . . . . 716
PIPING
Bundled . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 308.9
Construction documents . . . . . . . . . . . . . 104.2, 110.1
Drainage, horizontal slope . . . . . . . . . . . . . . . . . . 704.1
2021 INTERNATIONAL PLUMBING CODE®
INDEX
Drainage piping installation. . . . . . . . . . . . . . . . . . . 704
Drainage piping offset, size . . .710.1.1, 710.1.2, 711.2
Joints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 605, 705
Rehabilitation of the inside of . . . . . . . . . . . . . . . .601.5
PIPING PROTECTION
Backfilling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .306.3
Bedding . . . . . . . . . . . . . . . . . . . . . . . . . . 306.1, 306.2
Corrosion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .305.1
Expansion and contraction . . . . . . . . . . . . . . . . .305.2
Exposed locations . . . . . . . . . . . . . . . . . . . . . . . .305.6
Foundation wall . . . . . . . . . . . . . . . . . . . . . . . . . .305.3
Freezing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .305.4
Impact by vehicles . . . . . . . . . . . . . . . . . . . . . . . .305.7
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .305.2
Penetration by fasteners . . . . . . . . . . . . . . . . . . .305.6
Slabs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .305.1
Structural settlement . . . . . . . . . . . . . . . . . . . . . .305.2
Tunneling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .306.4
PLUMBING FACILITIES . . . . . . . . . . . . . . . . . . . . . 403
PLUMBING FIXTURES
Accessible. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 404
Automatic clothes washers . . . . . . . . . . . . . . . . . . . 406
Bidet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 408
Clearances . . . . . . . . . . . . . . . .404.2, 405.3.1, 405.3.5
Definition. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Dishwashing machine . . . . . . . . . . . . . . . . . . . . . . . 409
Drainage fixture unit values . . . . . . . . . . . .Table 709.1
Drinking fountain . . . . . . . . . . . . . . . . . . . . . . . . . . . 410
Emergency showers . . . . . . . . . . . . . . . . . . . . . . . . 411
Eyewash stations . . . . . . . . . . . . . . . . . . . . . . . . . . 411
Floor and trench drains. . . . . . . . . . . . . . . . . . . . . . 413
Floor sinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 414
Food waste disposer. . . . . . . . . . . . . . . . . . . . . . . . 416
Future fixtures . . . . . . . . . . . . . . . . . . . . . . . . . . . .704.4
Garbage can washer . . . . . . . . . . . . . . . . . . . . . . . 417
Installation of. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 405
Joints at wall or floor . . . . . . . . . . . . . . . . . . . . . . .405.6
Kitchen sink . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
Laundry tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 418
Lavatories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 419
Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .402.1
Minimum number of . . . . . . . . . . . . . . . . . . . . . . .403.1
Ornamental pools . . . . . . . . . . . . . . . . . . . . . . . . .423.1
Quality of. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .402.1
Separate facilities for . . . . . . . . . . . . . . . . . . . . . .403.2
Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .405.3
Showers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421
Sinks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 422
Urinals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 424
Water closets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 425
2021 INTERNATIONAL PLUMBING CODE®
Water coolers . . . . . . . . . . . . . . . . . . . . . . . . .202, 410
Water supply protection . . . . . . . . . . . . . . . . . . . . 608.2
PNEUMATIC (SEWAGE) EJECTORS . . . . . . . . . . .712
POLYETHYLENE PIPE OR TUBING
PE approved standards . . . . . . . . . . . . . . .Table 702.2,
Table 1102.4, Table 1102.5
PE-AL-PE approved standards . . . . . . . . .Table 605.3,
Table 605.4
PE-RT approved standards . . . . . . . . . . . .Table 605.3,
Table 605.4
PEX approved standards. . . .Table 605.3, Table 605.4
PEX-AL-PEX approved standards. . . . . . .Table 605.3,
Table 605.4
POLYPROPYLENE (PP) PIPE OR TUBING
Approved standards . . . . . . . . . . . . . . . . .Table 605.3,
Table 605.4, Table 702.3
POTABLE WATER, PROTECTION OF . . . . . . . . . .608
POTABLE WATER HANDLING EQUIPMENT . . . 608.4
POWERS OF CODE OFFICAL . . . . . . . . . . . . . . . . .104
PRESSURE OF WATER
DISTRIBUTION SYSTEM . . . . . . 604.6, 604.7, 604.8
PROHIBITED
Air admittance valve use . . . . . . . . . . . 918.3.2, 918.8
Bends in tubing . . . . . . . . . . . . . . . . . . . . . . . .605.18.4
Building traps . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.6
Cleanout opening use . . . . . . . . . . . . . . . . . . .708.1.12
Conductor use . . . . . . . . . . . . . . . . . . . . . . . . . . .1104
Cross connections . . . . . . . . . . . . . . . . . . . . . . . 608.7
Discharge to water reuse system . . . . . . . . . .1302.2.1
Drinking fountain location . . . . . . . . . . . . . . . . . . 410.5
Fixture design . . . . . . . . . . . . . . . . . . . . . . . . . . . 401.2
Joints and connections . . . . . . . . . . . . . . . . 605.9, 707
Offset in waste stack . . . . . . . . . . . . . . . . . . . . . 913.2
Piping reutilization . . . . . . . . . . . . . . . . . . . . . . 608.10
Plumbing systems location . . . . . . . . . . . . . . . . . 301.6
Stack connections . . . . . . . . . . . . . . . . . . . . . . . 917.8
Storm water into sanitary sewer . . . . . . . . . . . . 1101.3
Tank location . . . . . . . . . . . . . . . . . . . . . . . . . .606.5.8
Toilet facility location . . . . . . . . . . . . . . . . . . . .403.3.2
Trap design . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.3
Valve location . . . . . . . . . . . . . . . . . . . . . . . . . . . 608.8
Vent terminal use . . . . . . . . . . . . . . . . . . . . . . . . 903.4
Water cooler location . . . . . . . . . . . . . . . . . . . . . 410.5
Water dispenser locations . . . . . . . . . . . . . . . . . 410.5
Well pits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 602.3.5.1
Yard hydrant . . . . . . . . . . . . . . . . . . . . . . . . . . . . 608.8
PROTECTION OF POTABLE WATER . . . . . 603.2, 608
PUBLIC SWIMMIMG POOL . . . . . . . . 202, Table 403.1
PUBLIC WATER MAIN . . . . . . . . . . . . . . . 202, 606.5.1,
Table 1302.7.1, Table 1402.3
INDEX-9
INDEX
PUMPED WASTE FIXTURE . . . . . . . . . . . . . . . . . 405.5
PUMPING EQUIPMENT . . . . . . . . . . . . . 608.17.9, 712,
1113, 1303.12
PURPOSE OF CODE. . . . . . . . . . . . . . . . . . . . . . . 101.3
PUSH-FIT FITTING . . . . . . . . . . . . . . . . . . . . . . . . . . 202
DWV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 705.2.4
PUSH-FIT JOINT . . . . . . . . . . . . . . . . . 705.2.4, 705.10.4
PVC PIPE . . . . . . . . . . . . . . . . . . . . 314.2.2, Table 605.3,
Table 605.4, Table 702.1,
Table 702.2, Table 702.3, 703.2,
712.3.3.1, Table 1102.4, Table 1102.5,
Table 1102.7, Table 1403.2
Q
QUALITY OF WATER
General . . . . . . . . . . . . . . . 602.3.3, 608.1, 1002.4.1.2,
1301.2, 1301.9.2, 1302.6,
1302.12.6, 1303.5, 1303.9,
1303.15.8, 1303.15.9
QUICK CLOSING VALVE
Causing water hammer . . . . . . . . . . . . . . . . . . . 604.9
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
R
RAINWATER (STORM WATER)
DRAINAGE . . . . . . . . . . . . . . . . . . . . . . . . Chapter 11
RAINWATER COLLECTION AND
DISTRIBUTION SYSTEMS . . . . . . . . . . . . . . . . . 1303
RAINWATER QUAILITY . . . . . . . . . . . . . . . . . 1303.15.9
RECLAIMED WATER SYSTEMS . . . . . . . . . . . . . . 1304
REDUCED PRESSURE PRINCIPLE
BACKFLOW PREVENTER . . . . . .608.17.2, E103.3.1
Boiler potable water supply . . . . . . . . . . . . . . . 608.17.2
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Freeze protection of . . . . . . . . . . . . . . . . . . . . 608.15.2
Installation of . . . . . . . . . . . . . . . . . . . . . . . . . . 608.14.2
Periodic inspections . . . . . . . . . . . . . . . . . . . . . 312.10
Relief port piping from . . . . . . . . . . . . . . . . . 608.15.2.1
Standards . . . . . . . . . . . . . . . . . . . . . . . . . Table 608.1
Where required . . . . . . . . . . . . . . . 608.17.2, 608.17.4,
608.17.4.1, 608.17.5, 608.17.6
REFERENCED STANDARDS . . . . . . . . . . . Chapter 15
RELIEF VALVE, PRESSURE . . . . . . . . . . . 504.4, 504.5
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
RELIEF VALVE DISCHARGE PIPING . . . . . . . . . 504.6
RELIEF VENT . . . . . . . . . . . . . . . . . 905.5, 906.2, 906.3,
908, 914.4, 914.4.2, 918.3.1
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
INDEX-10
ROOF DRAIN
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Flow rating for water height above . . . 1101.7, 1105.2
Installation of . . . . . . . . . . . . . . . . . . . . . . . . . . . 1105.1
Standards for . . . . . . . . . . . . . . . . . . . . . . . . . . . 1106.2
ROUGH-IN INSPECTION . . . . . . . . . . . . . . . . . . . 108.2
S
SANITARY TEE . . . . . . . . . . . 706.3, Table 706.3, 917.3
SCOPE OF CODE . . . . . . . . . . . . . . . . . . . . . . . . . 101.2
SCUPPERS. . . . . . . . . . . . . . . . . . . . . . . 1106.5, 1108.1
SEISMIC (Earthquakes). . . . . . . . . . . . . . . . . . . . . 308.2
SEPARATE (TOILET) FACILITIES . . . . . . . . . . . . 403.2
SERVICE SINKS . . . . . . . . . . . . . . . . Table 403.1, 422,
604.4, Table 709.1
SHAMPOO SINKS . . . . . . . . . . . . . . . . . . . . . . . . 412.10
SHEET COPPER . . . . . . 305.5, 402.3, 421.5.2.4, 902.2
SHEET LEAD . . . . . . . . . . . . . . . 402.4, 421.5.2.3, 902.3
SHOWER LINER
Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 421.5.2
Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312.9
SHOWERS
Approvals for prefabricated types . . . . . . . . . . . . 421.1
Compartment size . . . . . . . . . . . . . . . . . . . . . . . . 421.4
Emergency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 411
Required number . . . . . . . . . . . . . . . . . . . . . . . . 403.1
Wall protection for . . . . . . . . . . . . . . . . . . . . . . 421.4.1
Water supply riser for . . . . . . . . . . . . . . . . . . . . . 421.2
SILL COCK . . . . . . . . 412.6, Table 604.3, 604.8, 606.2,
608.16.4.2, 1301.12
SINGLE-STACK VENT SYSTEM . . . . . . . . . . . . . . 917
SINKS . . . . . . . . . . . . . . . . . . . . . Table 403.1, 414, 422
SIPHONIC ROOF DRAINAGE SYSTEMS . . . . . . 1107
SIZING
Drainage system . . . . . . . . . . . . . . . . . . . . . . . . . . 710
Fixture drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 709
Fixture water supply . . . . . . . . . . . . . . . . . . . . . . 604.5
Vent system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 906
Water distribution system . . . . . . . . . . . . . . . . . . . 604
Water service . . . . . . . . . . . . . . . . . . . . . . . . . . . 603.1
SLAUGHTERHOUSES. . . . . . . . . . . . . . . . . . . . . 1003.8
SLEEVES IN FOUNDATION WALLS . . . . . . . . . . 305.3
SLOPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
SLOPE, PIPING . . . . . . . . . . . . . . . . . . . . . . Table 709.1
SOIL PIPE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
SOLAR HEATING SYSTEM . . . . . . . . . . . . . . . . . 502.1
SOLDERING BUSHINGS . . . . . . . . . . . . . . . . . . 705.19
2021 INTERNATIONAL PLUMBING CODE®
INDEX
SOLVENT CEMENTING
(See JOINTS AND CONNECTIONS
SPECIAL WASTES . . . . . . . . . . . . . . . . . . . . . . . . . 803
SPECIALTY PLUMBING FIXTURES . . . . . . . . . . . . 423
STAINLESS STEEL DRAINAGE SYSTEMS
Approved standards for
drainage systems . . . . . . .Table 702.1, Table 702.2,
Table 702.3, Table 702.4,
Table 1102.4, Table 1102.5,
Table 1102.7
Joints for drainage systems . . . . . . . .705.16.7, 705.20
STAINLESS STEEL PIPE
Approved standards for
water systems . . . . . . . . . Table 605.3, Table 605.4
Joints for . . . . . . . . . . . . . . . . . . . . . . . 605.22, 605.23
STANDPIPE (FIXTURE) . . . . . . . . . . . . . . . . . . . . .802.4
STORM DRAIN
Area drain definition . . . . . . . . . . . . . . . . . . . . . . . . 202
Building size . . . . . . . . . . . . . . . . . . . . . . . . . . . .1106.1
Building subdrains . . . . . . . . . . . . . . . . . . . . . . .1112.1
Building subsoil drains . . . . . . . . . . . . . . . . . . . .1111.1
Conductors and connections . . . . . . . . . . . . . . . . 1104
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1101
Inspection of . . . . . . . . . . . . . . . . . . . . . . . . . . . .108.2
Prohibited drainage . . . . . . . . . . . . . . . . . . . . . .1101.3
Roof drains . . . . . . . . . . . . . . . . . . . . . . .1102.6, 1105
Secondary roof drains . . . . . . . . . . . . . . . . . . . . . 1108
Sizing of conductors, leaders and
storm drains . . . . . . . . . . . . . . . . . . . . . . . . . . . 1106
Sizing of roof gutters . . . . . . . . . . . . . . . . . . . . .1106.6
Sizing of vertical conductors and leaders . . . . .1106.2
Traps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1103
Where required . . . . . . . . . . . . . . . . . . . . . . . . .1101.2
STRUCTURAL SAFETY . . . . . . . . . . . 307, Appendix C
SUBDRAIN BUILDING . . . . . . . . . . . . . . . . . . . . .1112.1
SUBSOIL DRAIN PIPE . . . . . . . . . . . . . . . . . . . .1111.1
SUBSOIL LANDSCAPE
IRRIGATION SYSTEMS . . . . . . . . . . . . . . Chapter 14
SUMP PUMP DISCHARGE PIPE . . . . . . .301.6, 712.3.3
SUMP VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .906.5
SUMPS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1113
SUPPORTS . . . . . . . . . . . . . . . .202, 308.3, Table 308.5,
314.2.3.2, 1301.9.3
Seismic (Earthquake) . . . . . . . . . . . . . . . . 308.2, 502.4
SWIMMING POOL
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Public . . . . . . . . . . . . . . . . . . . . . . . . .202, Table 403.1
Solar heating of . . . . . . . . . . . . . . . . . . . . . . . . . .612.1
Waste connections . . . . . . . . . . . . . . . . . . . . . . . . 801
Water connections to . . . . . . . . . . . . . . . . . . . . . .423.1
2021 INTERNATIONAL PLUMBING CODE®
SWIMMING POOL DRAINAGE . . . . . . . . . . . . .802.1.4
T
TEMPERATURE AND
PRESSURE RELIEF VALVE . . . . . . . . . . . . . . . . .504
TEMPERATURE CONTROL
Mixing valves . . . . . . . . . . 411.3, 412.3, 412.4, 412.5,
Table 604.3, 607.2.2,
607.4, 613.1
TEMPERATURE OF WASTEWATER . . . . . . . . . 702.5
TEMPERATURE-ACTUATED FLOW
REDUCTION VALVE . . . . . . . . . . . . . . . . . . . . . 412.7
TEMPERED WATER . . . . . 202, 419.5, 607.1.1, 607.1.2
TEST
Drainage and vent air test . . . . . . . . . . . . . . . . . . 312.3
Drainage and vent final test. . . . . . . . . . . . . . . . . 312.4
Drainage and vent water test. . . . . . . . . . . . . . . . 312.2
Forced sewer test . . . . . . . . . . . . . . . . . . . . . . . . 312.7
Gravity sewer test . . . . . . . . . . . . . . . . . . . . . . . . 312.6
Percolation test . . . . . . . . . . . . . . . . . . . . . . . . . 1402.2
Required tests . . . . . . . . . . . . . . . . . . . . . . . . . . . 312.1
Shower liner. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 312.9
Test gauges . . . . . . . . . . . . . . . . . . . .312.1.1, 312.10.2
Test of backflow prevention devices . . . . . . . . . 312.10
Test of conductors . . . . . . . . . . . . . . . . . . . . . . . . 312.8
THERMAL EXPANSION CONTROL . . . . . . . . . . 607.3
THERMAL EXPANSION TANK, SUPPORT . . . . 308.10
THIRD-PARTY CERTIFICATION . . . 202, 303.3, 303.4,
303.5, 501.5, 605.3,
605.15.2, 705.10.2
TOILET FACILITY
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .202
Multiple-user (serving all genders) . . . . 403.1.1, 403.2
Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .403
Signs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 403.4
Single-user . . . . . . . . . . . . . . . . . . . . . . 403.1.2, 403.2
Travel distance . . . . . . . . . . . . . . . . . .403.3.3, 403.3.4
Workers’ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .311
TOILET ROOM DOOR LOCKING . . . . . . . . . . . .403.3.6
TRAP SEAL PROTECTION . . . . . . . . . . . . . . .1002.4.1
TRAPS
Acid-resisting . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.9
Building . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.6
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.2
Prohibited types . . . . . . . . . . . . . . . . . . . . . . . . 1002.3
Seal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1002.4
Separate for each fixture . . . . . . . . . . . . . . . . . 1002.1
Size . . . . . . . . . . . . . . . . . . . .Table 709.1, Table 709.2
TRENCH DRAINS . . . . . . . . . . . . . . . . . . . . . . . . . . .413
TRENCHING, EXCAVATION AND BACKFILL . . . .306
INDEX-11
INDEX
TUNNELING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306.4
U
UNDERGROUND DRAINAGE AND
VENT PIPE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 702.2
URINAL PARTITIONS . . . . . . . . . . . . . . . . . . . . 405.3.5
URINALS . . . . . . . . . . . . . . . . . . . . . . . Table 403.1, 424
V
VACUUM BREAKER . . . . . . . . . . 202, 312.10.2, 412.8,
415.2, Table 608.1, 608.3.1,
608.14.5, 608.14.6, 608.16.4,
608.16.4.1, 608.16.4.2, 609.4
VACUUM DRAINAGE SYSTEMS . . . . . . . . . . . . . . 715
VACUUM RELIEF VALVE . . . . . . . . . . . . . 504.1, 504.2
VACUUM SYSTEM, MEDICAL . . . . . . . . . . . . . . 1202.1
VALVE
Air admittance . . . . . . . . . . . . . . . . . . . . . . . . 202, 918
Approved standards . . . . . . . . . . . . Table 605.7, 714.2
Backwater . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202, 714
Full-open . . . . . . . . . . . . . . . . . . . . . . . . . . 202, 605.3
Pressure reducing . . . . . . . . . . . . . . . . . . . . . . . 604.8
Relief . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202, 504.4
Stop and waste . . . . . . . . . . . . . . . . . . . . . . . . . . 608.8
Temperature-actuated flow reduction . . . . . . . . . 412.7
Transfer valves . . . . . . . . . . . . . . . . . . . . . . . . . . 412.8
VENT
Individual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 910
Sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 906
VENT, RELIEF . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 908
VENT STACK
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 904.2
VENT SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
VENTS AND VENTING
Branch vents . . . . . . . . . . . . . . . . . . . . . . . . . . . 906.4
Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 914
Combination waste . . . . . . . . . . . . . . . . . . . . . . . . . 915
Common . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 911
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Distance from trap . . . . . . . . . . . . . Table 909.1, 909.2
Engineered systems . . . . . . . . . . . . . . . . . . . . . . . . 919
Island fixture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 916
Required vent . . . . . . . . . . . . . . . . . . . . . . . . . . . 904.1
Single stack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 917
Vent stack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 904.2
Vent terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 903
Waste stack . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 913
Wet vent . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 912
INDEX-12
W
WALL-HUNG WATER CLOSET . . . . . . . . . . . . . . . 425
WASTE
Indirect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 802
Special . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 803
WASTE RECEPTORS
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
WASTE STACK . . . . . . . . . . . . . . . . . . . . . . . . . . . . 913
WASTEWATER TEMPERATURE . . . . . . . . . . . . . 702.5
WATER
Cross connection . . . . . . . . . . . . . . . . . . . . . . . . 608.7
Distribution piping material . . . . . . . . . . . . Table 605.4
Distribution system design . . . . . . . . . . . . . . . . . . 604
Excessive pressure . . . . . . . . . . . . . . . . . . . . . . . 604.8
Hammer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 604.9
Pressure booster . . . . . . . . . . . . . . . . . . . . . . . . . 606.5
Rain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Reclaimed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 603
Service piping material . . . . . . . . . . . . . . . Table 605.3
Storm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
WATER CLOSET COMPARTMENTS . . . . . . . . 405.3.4
WATER CLOSET
PERSONAL HYGIENE DEVICE . . . . . . . . . . . . . 412.9
WATER CLOSETS . . . . . . . . . . . . . . . . . . . . . . . . . . 425
WATER CONSERVATION
Fixtures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 604.4
Flow rates . . . . . . . . . . . . . . . . . . . . . . . . . Table 604.4
WATER COOLER
Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 410.1
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Prohibited location . . . . . . . . . . . . . . . . . . . . . . . . 410.5
WATER DISPENSER
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Prohibited location . . . . . . . . . . . . . . . . . . . . . . . . 410.5
Substitution for drinking fountain . . . . . . . . . . . . . 410.4
WATER HAMMER . . . . . . . . . . . . . . . . . . . . . . . . . 604.9
WATER HEATER
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Requirements for . . . . . . . . . . . . . . . . . . . . . .Chapter 5
WATER HEATER PAN . . . . . . . . . . . . . . . . . . . . . 504.7
WATER TREATMENT
Drinking water systems . . . . . . . . . . . . . . . . . . . . . 611
Softeners . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 608.4
WELL WATER . . . . . . . . . . . . . . . . . . . . . . . . . . 602.3.1
WET VENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 912
WIPED JOINTS . . . . . . . . . . . . . . . . . . . . . . . . . 705.9.2
WORKERS’ TOILET FACILITIES . . . . . . . . . . . . . . 311
2021 INTERNATIONAL PLUMBING CODE®
RESOURCE A
PLUMBING PROVISIONS EXCERPTED FROM:
ICC A117.1–2017 STANDARD FOR ACCESSIBLE
AND USABLE BUILDINGS AND FACILITIES
User note:
About this resource: Sections 404.2 and 410.3 reference ICC A117.1 for accessible plumbing facilities and fixtures. Key to these references
are provisions which state, “Accessible plumbing fixtures shall be installed in accordance with ICC A117.1” (Section 404.2) and “where drinking fountains are primarily for children’s use, the drinking fountains for people using wheelchairs shall be permitted to comply with the
children’s provisions in ICC A117.1 and drinking fountains for standing children shall be permitted to provide the spout at 30 inches (762 mm)
minimum above the floor” (Exception 2 to Section 410.3).
For user convenience and in order to ensure an accessible plumbing design, plumbing design-related excerpts from ICC A117.1—2017 have
been included in this new Resource A. Marginal markings indicate changes from the 2009 edition. This resource material is not part of the IPC
requirements.
ICC A117.1 is an approved American National Standard (ANS) developed in accordance with ANSI’s requirements for ANS standard
development.
Plumbing Provisions Excerpted from:
ICC A117.1-2017
Standard for Accessible
and Usable Buildings
and Facilities
International Code Council
500 New Jersey Avenue, NW, 6th Floor
Washington, D.C. 20001
ICC A117.1-2017
Standard for Accessible and Usable Buildings and Facilities
(Plumbing Provisions)
ISBN: 978-1-60983-758-7
COPYRIGHT ® 2017
By
INTERNATIONAL CODE COUNCIL, INC.
ALL RIGHTS RESERVED. The 2017 ICC Standard for Accessible and Usable Buildings and Facilities (ICC
A117.1-2017) is a copyrighted work owned by the International Code Council, Inc (“ICC”). Without advance written
permission from the ICC, no part of this book may be reproduced, distributed, or transmitted in any form or by any
means, including, without limitation, electronic, optical or mechanical means (by way of example, and not limitation,
photocopying, or recording by or in an information storage retrieval system). For information on use rights and permissions, please contact: ICC Publications, 4051 Flossmoor Road, Country Club Hills, IL 60478. Phone 1-888-ICCSAFE (422-7233).
Trademarks: “International Code Council,” the “International Code Council” logo, “ICC,” the “ICC” logo, and other
names and trademarks appearing in this book are registered trademarks of the International Code Council, Inc.,
and/or its licensors (as applicable), and may not be used without permission.
T024869
PRINTED IN THE USA
Table of Contents
CHAPTER 1 APPLICATION AND
ADMINISTRATION . . RESOURCE A-1
CHAPTER 8 SPECIAL ROOMS
AND SPACES . . . . . . . RESOURCE A-43
101
Title. . . . . . . . . . . . . . . . . . . . . . . . RESOURCE A-1
801
General . . . . . . . . . . . . . . . . . . . . RESOURCE A-43
102
Purpose . . . . . . . . . . . . . . . . . . . . . RESOURCE A-1
804
Kitchens . . . . . . . . . . . . . . . . . . . RESOURCE A-43
103
Human Factor Provisions . . . . . . . RESOURCE A-1
104
Compliance Alternatives . . . . . . . RESOURCE A-1
105
Conventions . . . . . . . . . . . . . . . . . RESOURCE A-1
106
Referenced Documents. . . . . . . . . RESOURCE A-1
107
Definitions . . . . . . . . . . . . . . . . . . RESOURCE A-3
CHAPTER 11 DWELLING UNITS AND
SLEEPING UNITS. . . RESOURCE A-47
1101
General . . . . . . . . . . . . . . . . . . . . RESOURCE A-47
1102
Accessible Units. . . . . . . . . . . . . RESOURCE A-47
1103
Type A Units . . . . . . . . . . . . . . . RESOURCE A-48
CHAPTER 3 BUILDING
BLOCKS . . . . . . . . . . . . RESOURCE A-7
1104
Type B Units . . . . . . . . . . . . . . . RESOURCE A-54
1105
Type C (Visitable) Units . . . . . . RESOURCE A-63
301
General . . . . . . . . . . . . . . . . . . . . . RESOURCE A-7
1106
302
Floor Surfaces. . . . . . . . . . . . . . . . RESOURCE A-7
Units with Communication
Features . . . . . . . . . . . . . . . . . RESOURCE A-64
303
Changes in Level . . . . . . . . . . . . . RESOURCE A-7
304
Turning Space. . . . . . . . . . . . . . . . RESOURCE A-8
305
Clear Floor Space . . . . . . . . . . . . RESOURCE A-10
306
Knee and Toe Clearance. . . . . . . RESOURCE A-11
307
Protruding Objects . . . . . . . . . . . RESOURCE A-13
308
Reach Ranges . . . . . . . . . . . . . . . RESOURCE A-14
309
Operable Parts . . . . . . . . . . . . . . RESOURCE A-15
CHAPTER 6 PLUMBING ELEMENTS AND
FACILITIES . . . . . . . RESOURCE A-17
601
General . . . . . . . . . . . . . . . . . . . RESOURCE A-17
602
Drinking Fountains and
Bottle Filling Stations. . . . . . . RESOURCE A-17
603
Toilet and Bathing Rooms . . . . . RESOURCE A-18
604
Water Closets and Toilet
Compartments. . . . . . . . . . . . . RESOURCE A-19
605
Urinals . . . . . . . . . . . . . . . . . . . . RESOURCE A-28
606
Lavatories and Sinks. . . . . . . . . . RESOURCE A-29
607
Bathtubs . . . . . . . . . . . . . . . . . . . RESOURCE A-30
608
Shower Compartments . . . . . . . . RESOURCE A-32
609
Grab Bars . . . . . . . . . . . . . . . . . . RESOURCE A-37
610
Seats . . . . . . . . . . . . . . . . . . . . . . RESOURCE A-39
611
Washing Machines and Clothes
Dryers . . . . . . . . . . . . . . . . . . . RESOURCE A-40
612
Saunas and Steam Rooms. . . . . . RESOURCE A-42
PLUMBING PROVISIONS FROM: ICC A117.1—2017
RESOURCE A-v
RESOURCE A-vi
PLUMBING PROVISIONS FROM: ICC A117.1—2017
CHAPTER 1
APPLICATION AND ADMINISTRATION
SECTION 101
TITLE
This document shall be known as the standard for Accessible
and Usable Buildings and Facilities, hereinafter referred to as
“this standard.”
SECTION 102
PURPOSE
102.1 General. The technical criteria in Chapters 3 through
10, Sections 1102, 1103 and 1106 of this standard make sites,
facilities, buildings and elements accessible to and usable by
people with such physical disabilities as the inability to walk,
difficulty walking, reliance on walking aids, blindness and
visual impairment, deafness and hearing impairment, incoordination, reaching and manipulation disabilities, lack of
stamina, difficulty interpreting and reacting to sensory information, and extremes of physical size. The intent of these
sections is to allow a person with a physical disability to independently get to, enter, and use a site, facility, building or element.
Section 1104 of this standard provides criteria for Type B
units. These criteria are intended to be consistent with the
intent of the criteria of the U.S. Department of Housing and
Urban Development (HUD) Fair Housing Accessibility
Guidelines. The Type B units are intended to supplement, not
replace, Accessible units or Type A units as specified in this
standard.
Section 1105 of this standard provides criteria for minimal
accessibility features for one and two family dwelling units
and townhouses which are not covered by the U.S. Department of Housing and Urban Development (HUD) Fair Housing Accessibility Guidelines.
This standard is intended for adoption by government
agencies and by organizations setting model codes to achieve
uniformity in the technical design criteria in building codes
and other regulations.
102.2 Applicability. Sites, facilities, buildings, and elements
required to be accessible by the scoping provisions adopted
by the administrative authority shall comply with the applicable provisions of Chapters 3 through 10. Dwelling units and
sleeping units shall comply with the applicable provisions of
Chapter 11.
SECTION 103
HUMAN FACTOR PROVISIONS
The technical criteria in this standard are based on body sizes
and functional abilities of adults and, in those sections where
specifically noted, children.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
SECTION 104
COMPLIANCE ALTERNATIVES
Nothing in this standard is intended to prevent the use of
designs, products or technologies as alternatives to those prescribed by this standard, provided they result in equivalent or
greater accessibility and such equivalency is approved by the
administrative authority adopting this standard.
SECTION 105
CONVENTIONS
105.1 General. Where specific criteria of this standard differ
from the general criteria of this standard, the specific criteria
shall apply.
105.2 Calculation of percentages. Where the determination
of the required size or dimension of an element or facility
involves ratios or percentages, rounding down for values less
than one half shall be permitted.
105.3 Dimension tolerances. All dimensions are subject to
conventional industry tolerances except where the requirement is a range with stated minimum and maximum end
points.
105.4 Figures. Unless specifically stated, figures included
herein are provided for informational purposes only and are
not considered part of the standard.
105.5 Floor or floor surface. The terms floor or floor surface
refer to the finish floor surface or ground surface, as applicable.
105.6 Referenced sections. Unless specifically stated otherwise, a reference to another section or subsection within this
standard includes all subsections of the referenced section or
subsection.
SECTION 106
REFERENCED DOCUMENTS
106.1 General. The documents listed in Section 106.2 shall
be considered part of this standard to the prescribed extent of
each such reference. Where criteria in this standard differ
from those of these referenced documents, the criteria of this
standard shall apply.
106.2 Documents.
106.2.1 Americans with Disabilities Act (ADA) Accessibility Guidelines for Transportation Vehicles. 36 CFR
1192 published in 56 Federal Register 45558, September
6, 1991 (United States Access Board, 1331 F Street, NW,
Suite 1000, Washington, DC 20004-1111).
RESOURCE A-1
APPLICATION AND ADMINISTRATION
Convention
36
915
Description
dimension showing English units (in inches unless otherwise
specified) above the line and SI units (in millimeters unless
otherwise specified) below the line
6
150
dimension for small measurements
33 - 36
840 - 915
dimension showing a range with minimum - maximum
min
minimum
max
maximum
greater than
greater than or equal to
less than
less than or equal to
boundary of clear floor space or maneuvering clearance
C
L
centerline
a permitted element or its extension
direction of travel or approach
a wall, floor, ceiling or other element cut in section or plan
a highlighted element in elevation or plan
location zone of element, control or feature
FIGURE 105.4
GRAPHIC CONVENTION FOR FIGURES
106.2.2 Hearing aids – Magnetic field strength in
audio-frequency induction loops for hearing aids operating with an induction pickup coil. IEC 60118.4-2014
(International Electrotechnical Commission, 3 rue de
Varenbe, PO Box 131, 1211 Geneva 20, Switzerland.)
106.2.3 Manual on Uniform Traffic Control Devices.
MUTCD-2009 with Revisions 1 and 2 incorporated, May
2012 (The Federal Highway Administration, Office of
Transportation Operations, Room 3408, 400 7th Street,
S.W., Washington, DC 20590).
106.2.4 National Fire Alarm and Signaling Code.
NFPA 72-2016 (National Fire Protection Association, 1
Batterymarch Park, Quincy, MA 02269-9101).
106.2.5 Performance Criteria for Accessible Communications Entry Systems. DASMA 303-2006. (Door and
RESOURCE A-2
Access Systems Manufacturers Association, 1300 Sumner
Avenue, Cleveland, OH 44115-2851).
106.2.6 Power Assist and Low Energy Power Operated
Doors. BHMA A156.19-2013 (Builders Hardware Manufacturers’ Association, 355 Lexington Avenue, 15th Floor,
New York, NY 10017).
106.2.7 Power Operated Pedestrian Doors. ANSI/
BHMA A156.10-2011 (Builders Hardware Manufacturers’ Association, 355 Lexington Avenue, 15th Floor, New
York, NY 10017).
106.2.8 Safety Code for Elevators and Escalators.
ASME A17.1-2013/CSA B44-16 (American Society of
Mechanical Engineers International, Three Park Avenue,
New York, NY 10016-5990).
PLUMBING PROVISIONS FROM: ICC A117.1—2017
APPLICATION AND ADMINISTRATION
106.2.9 Safety Standard for Platform Lifts and Stairway Chairlifts. ASME A18.1-2014 (American Society of
Mechanical Engineers International, Three Park Avenue,
New York, NY 10016-5990).
106.2.10 Standard Consumer Safety Performance
Specification for Playground Equipment for Public
Use. ASTM F 1487-01 (ASTM International, 100 Barr
Harbor Drive, PO Box C700, West Conshohocken, PA,
19428-2959).
106.2.11 Standard Laboratory Test Method for Determination of Forces and Motions Required to Activate
Operable Parts of Operable Windows and Doors in
Accessible Spaces. AAMA 513-14 (AAMA, 1827
Walden Office Square, Suite 550, Schaumburg, IL 601734268).
106.2.12 Standard Specification for Impact Attenuation of Surfacing Materials Within the Use Zone of
Playground Equipment. ASTM F 1292-13 (ASTM International, 100 Barr Harbor Drive, PO Box C700, West
Conshohocken, PA, 19428-2959).
106.2.13 Standard Test Method for Determination of
Decay Rates for Use in Sound Insulation Test Methods.
ASTM E 2235-04 (2012) (ASTM International, 100 Barr
Harbor Drive, PO Box C700, West Conshohocken, PA
19428-2959).
SECTION 107
DEFINITIONS
107.1 General. For the purpose of this standard, the terms
listed in Section 107.5 have the indicated meaning.
107.2 Terms defined in referenced documents. Terms specifically defined in a referenced document, and not defined in
this section, shall have the specified meaning from the referenced document.
107.3 Undefined terms. The meaning of terms not specifically defined in this standard or in a referenced document
shall be as defined by collegiate dictionaries in the sense that
the context implies.
107.4 Interchangeability. Words, terms and phrases used in
the singular include the plural, and those used in the plural
include the singular.
107.5 Defined terms.
accessible: Describes a site, building, facility or portion
thereof that complies with this standard.
administrative authority: A jurisdictional body that adopts
or enforces regulations and standards for the design, construction or operation of buildings and facilities.
amusement attraction: Any facility, or portion of a facility,
located within an amusement park or theme park which provides amusement without the use of an amusement device.
Amusement attractions include, but are not limited to, fun
houses, barrels and other attractions without seats.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
amusement ride: A system that moves persons through a
fixed course within a defined area for the purpose of amusement.
amusement ride seat: A seat that is built-in or mechanically
fastened to an amusement ride intended to be occupied by
one or more passengers.
area of sport activity: That portion of a room or space where
the play or practice of a sport occurs.
assembly area: A building or facility, or portion thereof,
used for the purpose of entertainment, worship, educational
or civic gatherings, or similar purposes. For the purposes of
these requirements, assembly areas include, but are not limited to, classrooms, lecture halls, courtrooms, public meeting
rooms, public hearing rooms, legislative chambers, spaces
utilized for viewing motion picture projections, auditoria,
theaters, playhouses, dinner theaters, concert halls, centers
for the performing arts, amphitheaters, arenas, stadiums,
grandstands, places of religious worship or convention centers.
assistive listening system (ALS): An amplification system
utilizing transmitters, receivers and coupling devices to
bypass the acoustical space between a sound source and a listener by means of induction loop, radio frequency, infrared,
or direct-wired equipment.
blended transition: A raised pedestrian street crossing,
depressed corner or similar connection between the pedestrian access route at the level of the sidewalk and the level of
the pedestrian street crossing that has a grade of 1:20 or less.
boarding pier: A portion of a pier where a boat is temporarily secured for the purpose of embarking or disembarking.
boat launch ramp: A sloped surface designed for launching
and retrieving trailered boats and other water craft to and
from a body of water.
boat slip: That portion of a pier, main pier, finger pier or
float where a boat is moored for the purpose of berthing,
embarking, or disembarking.
catch pool: A pool or designated section of a pool used as a
terminus for water slide flumes.
characters: Letters, numbers, punctuation marks and typographic symbols.
children’s use: Spaces and elements specifically designed
for use primarily by people 12 years old and younger.
circulation path: An exterior or interior way of passage provided for pedestrian travel, including but not limited to,
walks, hallways, courtyards, elevators, platform lifts, ramps,
stairways and landings.
common use: Interior or exterior circulation paths, rooms,
spaces or elements that are not for public use and are made
available for the shared use of two or more people.
counter slope: Any slope opposing the running slope of a
curb ramp.
cross slope: The slope that is perpendicular to the direction
of travel (see running slope).
RESOURCE A-3
APPLICATION AND ADMINISTRATION
curb ramp: A short ramp cutting through a curb or built up
to it.
destination-oriented elevator system: An elevator system
that provides lobby controls for the selection of destination
floors, lobby indicators designating which elevator to board
and a car indicator designating the floors at which the car will
stop.
detectable warning: A standardized surface feature built in
or applied to floor surfaces to warn of hazards on a circulation path.
dwelling unit: A single unit providing complete, independent
living facilities for one or more persons including permanent
provisions for living, sleeping, eating, cooking and sanitation.
element: An architectural or mechanical component of a
building, facility, space or site.
elevated play component: A play component that is
approached above or below grade and that is part of a composite play structure consisting of two or more play components attached or functionally linked to create an integrated
unit providing more than one play activity.
elevator car call sequential step scanning: A technology
used to enter a car call by means of an up or down floor selection button.
employee work area: All or any portion of a space used only
by employees and used only for work. Corridors, toilet
rooms, kitchenettes and break rooms are not employee work
areas.
existing building: A building erected prior to the date of
adoption of this standard, or one for which a legal building
permit has been issued.
existing facility: A facility completed prior to the date of
adoption of this standard, or one for which a legal permit has
been issued.
facility: All or any portion of a building, structure, site
improvements, elements and pedestrian routes or vehicular
ways located on a site.
gangway: A variable-sloped pedestrian walkway that links a
fixed structure or land with a floating structure. Gangways
that connect to vessels are not addressed by this document.
golf car passage: A continuous passage on which a motorized golf car can operate.
grade break: The line where two surface planes with different grades meet.
ground level play component: A play component that is
approached and exited at the ground level.
habitable: A space in a building for living, sleeping, eating
or cooking. Bathrooms, toilet rooms, closets, halls, storage or
utility spaces and similar areas are not considered habitable
spaces.
key surface: The surface or plane of any key or button that
must be touched to activate or deactivate an operable part or a
machine function or enter data.
RESOURCE A-4
marked crossing: A crosswalk or other identified path
intended for pedestrian use in crossing a vehicular way.
operable part: A component of an element used to insert or
withdraw objects, or to activate, deactivate or adjust the element.
pictogram: A pictorial symbol that represents activities,
facilities or concepts.
play area: A portion of a site containing play components
designed and constructed for children.
play component: An element intended to generate specific
opportunities for play, socialization or learning. Play components are manufactured or natural; and are stand-alone or part
of a composite play structure.
ramp: A walking surface that has a running slope steeper
than 1:20.
running slope: The slope that is parallel to the direction of
travel (see cross slope).
sign: An architectural element composed of displayed textual, symbolic, tactile or pictorial information.
site: A parcel of land bounded by a property line or a designated portion of a public right-of-way.
sleeping unit: A room or space in which people sleep that
can also include permanent provisions for living, sleeping,
eating and either sanitation or kitchen facilities but not both.
Such rooms and spaces that are also part of a dwelling unit
are not sleeping units.
soft contained play structure: A play structure made up of
one or more play components where the user enters a fully
enclosed play environment that utilizes pliable materials,
such as plastic, netting or fabric.
teeing ground: In golf, the starting place for the hole to be
played.
transfer device: Equipment designed to facilitate the transfer
of a person from a wheelchair or other mobility aide to and
from an amusement ride seat.
transition plate: A sloping pedestrian walking surface
located at the ends of a gangway.
TTY: An abbreviation for teletypewriter. Equipment that
employs interactive, text-based communications through the
transmission of coded signals across the standard telephone
network. The term TTY also refers to devices known as text
telephones and TDDs.
use zone: The ground level area beneath and immediately
adjacent to a play structure or play equipment that is designated by ASTM F 1487 listed in Section 106.2.10, for unrestricted circulation around the play equipment and where it is
predicted that a user would land when falling from or exiting
the play equipment.
variable message signs (VMS): Electronic signs that have a
message with the capacity to change by means of scrolling,
streaming or paging across a background.
variable message sign (VMS) characters: Characters of an
electronic sign are composed of pixels in an array. High reso-
PLUMBING PROVISIONS FROM: ICC A117.1—2017
APPLICATION AND ADMINISTRATION
lution VMS characters have vertical pixel counts of 16 rows
or greater. Low resolution VMS characters have vertical pixel
counts of 7 to 15 rows.
vehicular way: A route provided for vehicular traffic, such
as in a street, driveway or parking facility.
walk: An exterior pathway with a prepared surface for pedestrian use.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
wheelchair charging area: A clear floor area where people
with disabilities can recharge their wheelchair batteries.
wheelchair space: A space for a single wheelchair and its
occupant.
wheelchair space locations: A space for a minimum of a single wheelchair and the associated companion seating. Wheelchair space locations can contain multiple wheelchair spaces
and associated companion seating.
RESOURCE A-5
RESOURCE A-6
PLUMBING PROVISIONS FROM: ICC A117.1—2017
CHAPTER 3
BUILDING BLOCKS
SECTION 301
GENERAL
301.1 Scope. The provisions of Chapter 3 shall apply where
required by the scoping provisions adopted by the administrative authority or by Chapters 4 through 11.
301.2 Overlap. Unless otherwise specified, clear floor
spaces, clearances at fixtures, maneuvering clearances at
doors, and turning spaces shall be permitted to overlap.
SECTION 302
FLOOR SURFACES
302.1 General. Floor surfaces shall be stable, firm, and slip
resistant, and shall comply with Section 302. Changes in
level in floor surfaces shall comply with Section 303.
FIGURE 302.3
OPENINGS IN FLOOR SURFACES
302.2 Carpet. Carpet or carpet tile shall be securely attached
and shall have a firm cushion, pad, or backing or no cushion
or pad. Carpet or carpet tile shall have a level loop, textured
loop, level cut pile, or level cut/uncut pile texture. The pile
shall be 1/2 inch (13 mm) maximum in height. Exposed edges
of carpet shall be fastened to the floor and shall have trim
along the entire length of the exposed edge. Carpet edge trim
shall comply with Section 303.
¼ max
6.4
FIGURE 303.2
VERTICAL CHANGE IN LEVEL
¼
6.4
½
13
FIGURE 302.2
CARPET ON FLOOR SURFACES
302.3 Openings. Openings in floor surfaces shall be of a size
that does not permit the passage of a 1/2-inch (13 mm) diameter sphere, except as allowed in Sections 407.4.3, 408.4.3,
409.4.3, 410.4 and 805.10. Elongated openings shall be
placed so that the long dimension is perpendicular to the predominant direction of travel.
¼
6.4
(A)
¼–½
6.4 – 13
SECTION 303
CHANGES IN LEVEL
303.1 General. Changes in level in floor surfaces shall comply with Section 303.
(B)
303.2 Vertical. Changes in level of 1/4 inch (6.4 mm) maximum in height shall be permitted to be vertical.
FIGURE 303.3
BEVELED CHANGES IN LEVEL
303.3 Beveled. Changes in level greater than 1/4 inch (6.4
mm) in height and not more than 1/2 inch (13 mm) maximum
in height shall be beveled with a slope not steeper than 1:2.
303.4 Ramps. Changes in level greater than 1/2 inch (13 mm)
in height shall be by a ramp complying with Section 405 or
by a curb ramp complying with Section 406.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
RESOURCE A-7
BUILDING BLOCKS
SECTION 304
TURNING SPACE
304.2 Floor surface. Floor surfaces of a turning space shall
comply with Section 302. Changes in level shall not be permitted within the turning space.
Exception: Slopes not steeper than 1:48 shall be permitted.
25 max
635
per
306.2.2
304.1 General. A turning space shall comply with Section
304.
60 min
1525
304.3 Size. Turning spaces shall comply with Section 304.3.1
or 304.3.2.
304.3.1 Circular space.
304.3.1.1 New buildings and facilities. In new
buildings and facilities, the turning space shall be a
circular space with a 67-inch (1700 mm) minimum
diameter.
304.3.1.1.1 Overlap. Turning spaces shall be
permitted to include knee and toe clearance complying with Section 306. Where the turning space
includes knee and toe clearances under an
obstruction, the overlap shall comply with all of
the following:
1.
The depth of the overlap shall not be
more than 10 inches (255 mm), and
2.
The depth shall not exceed the depth of
the knee and toe clearances provided, and
The overlap shall be permitted only
within the turning circle area shown
shaded in Figure 304.3.1.
3.
Overlap of knee and toe clearance
FIGURE 304.3.1.2
CIRCULAR TURNING SPACE - EXISTING BUILDINGS - SIZE
AND OVERLAP
304.3.2 T-Shaped space.
304.3.2.1 New buildings and facilities. In new
buildings and facilities, the turning space shall be a
T–shaped space complying with one of the following:
1. A T-shaped space, clear of obstruction, that
fits within an area 68 inches (1725 mm) wide
and 60 inches (1525 mm) deep, with two
arms and one base that are all 36 inches (915
mm) minimum in width. Each arm shall
extend 16 inches (405 mm) minimum from
each side of the base located opposite the
other, and the base shall extend 24 inches
(610 mm) minimum from the arms. At the
intersection of each arm and the base, the
interior corners shall be chamfered for 8
inches (205 mm) minimum along both the
arm and along the base.
8 min
205
67 min
1700
Overlap of knee and toe clearance
36 min
915
60 min
1525
10 max
255
68 min
1725
24 min
610
FIGURE 304.3.1.1
CIRCULAR TURNING SPACE - NEW BUILDINGS
SIZE AND OVERLAP
304.3.1.2 Existing buildings and facilities. In
existing buildings and facilities, the turning space
shall be a circular space with a 60-inch (1525 mm)
minimum diameter.
304.3.1.2.1 Overlap. Turning spaces shall be
permitted to include knee and toe clearance complying with Section 306.
RESOURCE A-8
16
min
405
36 min
915
16
min
405
FIGURE 304.3.2.1(A)
T-SHAPED TURNING SPACE
NEW BUILDINGS - OPTION 1
PLUMBING PROVISIONS FROM: ICC A117.1—2017
BUILDING BLOCKS
arm shall extend 12 inches (305 mm) minimum from each side of the base and the base
shall extend 20 inches (510 mm) minimum
from each arm.
2. A T-shaped space, clear of obstruction, that
fits within an area 64 inches (1625 mm) wide
and 60 inches (1525 mm) deep, with two
arms 38 inches (965 mm) minimum in width
and a base 42 inches (1065 mm) minimum in
width. Each arm shall extend 11 inches (280
mm) minimum from each side of the base,
located opposite the other, and the base shall
extend 22 inches (560 mm) minimum from
each arm.
22 min
660
11
min
280
42 min
1065
20 min
510
60 min
1525
38 min
965
64 min
1625
60 min
1525
40 min
1015
64 min
1625
12
min
305
40 min
1015
12
min
305
FIGURE 304.3.2.1(C)
T-SHAPED TURNING SPACE
NEW BUILDINGS - OPTION 3
11
min
280
FIGURE 304.3.2.1(B)
T-SHAPED TURNING SPACE
NEW BUILDINGS - OPTION 2
304.3.2.1.1 Overlap. Turning spaces shall be
permitted to include knee and toe clearance complying with Section 306 of either the base or one
arm. For Option 1, the base or arm is the portion
beyond the chamfer.
3. A T-shaped space, clear of obstruction, 64
inches (1625 mm) wide and 60 inches (1525
mm) deep, with two arms and one base 40
inches (1015 mm) minimum in width. Each
arm
base
base
arm
Overlap of knee and toe clearance
FIGURE 304.3.2.1.1
T-SHAPED TURNING SPACE
NEW BUILDINGS - OVERLAP
PLUMBING PROVISIONS FROM: ICC A117.1—2017
RESOURCE A-9
BUILDING BLOCKS
304.3.2.2 Existing buildings and facilities. In
existing buildings and facilities, the turning space
shall be a T-shaped space within a 60-inch (1525
mm) minimum square, with arms and base 36 inches
(915 mm) minimum in width. Each arm of the T
shall be clear of obstructions 12 inches (305 mm)
minimum in each direction, and the base shall be
clear of obstructions 24 inches (610 mm) minimum.
SECTION 305
CLEAR FLOOR SPACE
305.1 General. A clear floor space shall comply with Section
305.
305.2 Floor surfaces. Floor surfaces of a clear floor space
shall comply with Section 302. Changes in level shall not be
permitted within the clear floor space.
Exception: Slopes not steeper than 1:48 shall be permitted.
60 min
1525
60 min
1525
36 min
915
305.3 Size.
24 min
610
305.3.1 New buildings and facilities. In new buildings
and facilities, the clear floor space shall be 52 inches
(1320 mm) minimum in length and 30 inches (760 mm)
minimum in width.
12 min
305
36 min
915
30 min
760
52 min
1320
12 min
305
FIGURE 304.3.2.2
T-SHAPED TURNING SPACE
EXISTING BUILDINGS - SIZE
304.3.2.2.1 Overlap. Turning spaces shall be permitted to include knee and toe clearance complying
with Section 306 only at the end of either the base or
one arm.
FIGURE 305.3.1
SIZE OF CLEAR FLOOR SPACE - NEW BUILDINGS
305.3.2 Existing buildings and facilities. In existing
buildings and facilities, the clear floor space shall be 48
inches (1220 mm) minimum in length and 30 inches (760
mm) minimum in width.
base
30 min
760
48 min
1220
Overlap of knee and toe clearance
FIGURE 304.3.2.2.1
T-SHAPED TURNING SPACE - EXISTING BUILDINGS
OVERLAP
304.4 Door swing. Unless otherwise specified, doors shall be
permitted to swing into turning spaces.
RESOURCE A-10
FIGURE 305.3.2
SIZE OF CLEAR FLOOR SPACE - EXISTING BUILDINGS
305.4 Knee and toe clearance. Unless otherwise specified,
clear floor space shall be permitted to include knee and toe
clearance complying with Section 306.
305.5 Position. Unless otherwise specified, clear floor spaces
shall be positioned for either forward or parallel approach to
an element.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
BUILDING BLOCKS
x > 24
x > 610
305.7.2 Forward approach. Where a clear floor space
is positioned for a forward approach, the alcove shall
be 36 inches (915 mm) minimum in width where the
depth exceeds 24 inches (610 mm).
FIGURE 305.5(A)
POSITION OF CLEAR FLOOR SPACE - FORWARD
36 min
915
FIGURE 305.5(B)
POSITION OF CLEAR FLOOR SPACE - PARALLEL
305.6 Approach. One full, unobstructed side of a clear floor
space shall adjoin or overlap an accessible route or adjoin
another clear floor space.
305.7 Alcoves. If a clear floor space is in an alcove or otherwise confined on all or part of three sides, additional maneuvering clearances complying with Sections 305.7.1 and
305.7.2 shall be provided, as applicable.
x > 15
x > 380
305.7.1 Parallel approach. Where a clear floor space
is positioned for a parallel approach, the alcove shall be
60 inches (1525 mm) minimum in width where the
depth exceeds 15 inches (380 mm).
FIGURE 305.7.2
MANEUVERING CLEARANCE IN AN ALCOVE
FORWARD APPROACH
SECTION 306
KNEE AND TOE CLEARANCE
306.1 General. Where space beneath an element is included
as part of the clear floor space at an element, clearance at an
element, or a turning space, the space shall comply with Section 306. Additional space shall not be prohibited beneath an
element, but shall not be considered as part of the clear floor
space or turning space.
306.2 Toe clearance.
306.2.1 General. Space beneath an element between
the floor and 9 inches (230 mm) above the floor shall
be considered toe clearance and shall comply with Section 306.2.
306.2.2 Maximum depth. Toe clearance shall be permitted to extend 25 inches (635 mm) maximum under
an element.
60 min
1525
FIGURE 305.7.1
MANEUVERING CLEARANCE IN AN ALCOVE
PARALLEL APPROACH
PLUMBING PROVISIONS FROM: ICC A117.1—2017
306.2.3 Minimum depth. Where toe clearance is
required at an element as part of a clear floor space
complying with Section 305, the toe clearance shall
extend 17 inches (430 mm) minimum beneath the element.
306.2.4 Additional clearance. Space extending greater
than 6 inches (150 mm) beyond the available knee
clearance at 9 inches (230 mm) above the floor shall
not be considered toe clearance.
306.2.5 Width. Toe clearance shall be 30 inches (760
mm) minimum in width.
RESOURCE A-11
(B)
>20 – 25
510 – 635
BUILDING BLOCKS
10. Emergency aid devices, such as fire department
hose connections, valve controls, gauges, police
call boxes and annunciator panels shall not be
required to comply with this section provided that
they are used only for emergencies by emergency
personnel acting in their official capacity.
ing of the wrist. The force required to activate operable parts
shall be 5.0 pounds (22.2 N) maximum.
Exception: Gas pump nozzles shall not be required to provide operable parts that have an activating force of 5.0
pounds (22.2 N) maximum.
309.2 Clear floor space. A clear floor space complying with
Section 305 shall be provided.
309.3 Height. Operable parts shall be placed within one or
more of the reach ranges specified in Section 308.
Work
surface
Co
un
a
<= re ter t
9 as op
sq
.f
t.
309.4 Operation. Operable parts shall be operable with one
hand and shall not require tight grasping, pinching, or twist-
FIGURE 309.1
OPERABLE PARTS - EXCEPTION 3
RESOURCE A-16
PLUMBING PROVISIONS FROM: ICC A117.1—2017
CHAPTER 6
PLUMBING ELEMENTS AND FACILITIES
FIGURE 602.2.1(B)
CLEAR FLOOR SPACE AT WHEELCHAIR DRINKING
FOUNTAINS - PRIMARILY FOR CHILDREN’S USE
EXCEPTION
602.2.3 Spout outlet height. Spout outlets of drinking
fountains shall be 36 inches (915 mm) maximum above
the floor.
Exception: At drinking fountains primarily for children's use, the spout outlet shall be 30 inches (760 mm)
maximum above the floor.
Children
CL
36 max
915
0
30 max
760
SECTION 602
DRINKING FOUNTAINS AND BOTTLE FILLING
STATIONS
602.1 General. Drinking fountains for persons using wheelchairs shall comply with Sections 602.2 and 307. Drinking
fountains for persons who are standing shall comply with
Section 602.3 and 307.
602.2 Drinking fountains for persons using wheelchairs.
Drinking fountains for persons using wheelchairs shall comply with Sections 602.2.1 through 602.2.5.
602.2.1 Clear floor space. A clear floor space positioned
for a forward approach to the drinking fountain shall be
provided. Knee and toe space complying with Section 306
shall be provided. The clear floor space shall be centered
on the drinking fountain.
Exception: Drinking fountains primarily for children’s
use shall be permitted where a clear floor space provides a parallel approach and is centered on the drinking fountain.
602.2.2 Operable parts. Operable parts shall comply with
Section 309.
C
L
Adult
SECTION 601
GENERAL
601.1 Scope. Plumbing elements and facilities required to be
accessible by scoping provisions adopted by the administrative authority shall comply with the applicable provisions of
Chapter 6.
FIGURE 602.2.3
WHEELCHAIR DRINKING FOUNTAIN SPOUT
HEIGHT AND LOCATION
FIGURE 602.2.1(A)
CLEAR FLOOR SPACE AT WHEELCHAIR DRINKING
FOUNTAINS
PLUMBING PROVISIONS FROM: ICC A117.1—2017
602.2.4 Spout location. The spout shall be located 15
inches (380 mm) minimum from the vertical support and 5
inches (125 mm) maximum from the front edge of the
drinking fountain, including bumpers.
Exception: At drinking fountains primarily for children’s use, the spout shall be located 31/2 inches (90
mm) maximum from the front edge of the drinking
fountain, including bumpers.
RESOURCE A-17
PLUMBING ELEMENTS AND FACILITIES
15 min – adult
380
5 max
125
602.3.3 Spout location. The spout shall be located 5
inches (125 mm) maximum from the front edge of the
drinking fountain, including bumpers.
5 max
125
FIGURE 602.2.4
WHEELCHAIR DRINKING FOUNTAIN SPOUT LOCATION
602.2.5 Water flow. The spout shall provide a flow of
water 4 inches (100 mm) minimum in height. The angle of
the water stream from spouts within 3 inches (75 mm) of
the front of the drinking fountain shall be 30 degrees maximum, and from spouts between 3 inches (75 mm) and 5
inches (125 mm) from the front of the drinking fountain
shall be 15 degrees maximum, measured horizontally relative to the front face of the drinking fountain.
602.3 Drinking fountains for persons who are standing.
Drinking fountains for persons who are standing shall comply
with Sections 602.3.1 through 602.3.4.
602.3.1 Operable parts. Operable parts shall comply with
Sections 309.3 and 309.4.
602.3.2 Spout outlet height. Spout outlets of drinking
fountains shall be 38 inches (965 mm) minimum and 43
inches (1090 mm) maximum above the floor.
Exception: Drinking fountains primarily for children’s
use shall be permitted where the spout outlet is 30
inches (760 mm) minimum and 43 inches (1090 mm)
maximum above the floor.
38 – 43 max
965 – 1090
Standing use
adult
Standing use
children
30 – 43 max
760 – 1090
0
FIGURE 602.3.3
STANDING USE DRINKING FOUNTAIN SPOUT LOCATION
602.3.4 Water flow. The spout shall provide a flow of
water 4 inches (100 mm) minimum in height. The angle of
the water stream from spouts within 3 inches (75 mm) of
the front of the drinking fountain shall be 30 degrees maximum, and from spouts between 3 inches (75 mm) and 5
inches (125 mm) from the front of the drinking fountain
shall be 15 degrees maximum, measured horizontally relative to the front face of the drinking fountain.
602.4 Bottle filling stations. Bottle filling stations shall comply with Sections 602.4.1 and 602.4.2.
Exception: Where bottle filling stations are part of the
drinking fountain for persons who are standing, the bottle
filling station is not required to comply with this section
provided a bottle filling station is located at the drinking
fountain for persons using wheelchairs.
602.4.1 Clear floor space. A clear floor space positioned
for a forward or side approach shall be provided.
602.4.2 Controls. Controls for bottle filling stations shall
be hand operated or automatic. Hand operated controls
shall comply with Section 309.
SECTION 603
TOILET AND BATHING ROOMS
603.1 General. Toilet and bathing rooms shall comply with
Section 603.
603.2 Clearances.
603.2.1 Turning space. A turning space shall be provided
within the room. The required turning space shall not be
provided within a toilet compartment.
603.2.2 Door swing. Doors shall not swing into the clear
floor space or clearance for any fixture.
FIGURE 602.3.2
STANDING USE DRINKING FOUNTAIN SPOUT
HEIGHT AND LOCATION
RESOURCE A-18
PLUMBING PROVISIONS FROM: ICC A117.1—2017
PLUMBING ELEMENTS AND FACILITIES
Exceptions:
1. Doors to a toilet or bathing room for a single
occupant, accessed only through a private office
and not for common use or public use shall be
permitted to swing into the clear floor space, provided the swing of the door can be reversed to
comply with Section 603.2.2.
2. Where the room is for individual use and a clear
floor space complying with Section 305.3 is provided within the room beyond the arc of the door
swing, the door shall not be required to comply
with Section 603.2.2.
603.3 Mirrors. Where mirrors are located above lavatories, a
mirror shall be located over the lavatory complying with Section 606 and shall be mounted with the bottom edge of the
reflecting surface 40 inches (1015 mm) maximum above the
floor. Where mirrors are located above counters that do not
contain lavatories, the mirror shall be mounted with the bottom edge of the reflecting surface 40 inches (1015 mm) maximum above the floor.
Exception: Other than within Accessible dwelling or
sleeping units, mirrors shall not be required over the lavatories or counters if a mirror is located within the same toilet or bathing room and mounted with the bottom edge of
the reflecting surface 35 inches (890 mm) maximum
above the floor.
603.4 Coat hooks and shelves. Coat hooks shall be located
within one of the reach ranges specified in Section 308.
Shelves shall be 40 inches (1015 mm) minimum and 48
inches (1220 mm) maximum above the floor.
603.5 Diaper changing tables. Diaper changing tables shall
comply with Sections 309 and 902
603.6 Operable parts. Operable parts on towel dispensers
and hand dryers serving lavatories complying with Section
606 shall comply with Table 603.6.
SECTION 604
WATER CLOSETS AND TOILET COMPARTMENTS
604.1 General. Water closets and toilet compartments shall
comply with Section 604. Compartments containing more
than one plumbing fixture shall comply with Section 603.
Wheelchair accessible compartments shall comply with Section 604.9. Ambulatory accessible compartments shall comply with Section 604.10.
Exception: Water closets and toilet compartments primarily for children’s use shall be permitted to comply with
Section 604.11 as applicable.
604.2 Location. The water closet shall be located with a wall
or partition to the rear and to one side. The centerline of the
water closet shall be 16 inches (405 mm) minimum and 18
inches (455 mm) maximum from the side wall or partition.
Water closets located in ambulatory accessible toilet compartments specified in Section 604.10 shall have the centerline of the water closet 17 inches (430 mm) minimum and 19
inches (485 mm) maximum from the side wall or partition.
TABLE 603.6
MAXIMUM REACH DEPTH AND HEIGHT
Maximum
Reach Depth
Maximum
Reach Height
0.5 inch
(13 mm)
48 inches
(1220 mm)
2 inches
(51 mm)
46 inches
(1170 mm)
5 inches
(125 mm)
42 inches
(1065 mm)
6 inches
(150 mm)
40 inches
(1015 mm)
CL
11 inches
(280 mm)
34 inches
(865 mm)
CL
17 − 19
430 − 485
16 − 18
405 − 455
(A)Accessible Water
Closets
9 inches
(230 mm)
36 inches
(915 mm)
(B) Ambulatory
Accessible Water Closets
FIGURE 604.2
WATER CLOSET LOCATION
PLUMBING PROVISIONS FROM: ICC A117.1—2017
RESOURCE A-19
PLUMBING ELEMENTS AND FACILITIES
604.3 Clearance.
604.3.1 Clearance width. Clearance around a water closet
shall be 60 inches (1525 mm) minimum in width, measured perpendicular from the sidewall.
604.3.2 Clearance depth. Clearance around the water
closet shall be 56 inches (1420 mm) minimum in depth,
measured perpendicular from the rear wall.
604.3.3 Clearance overlap. The required clearance
around the water closet shall be permitted to overlap
the water closet, associated grab bars, paper dispensers,
sanitary napkin receptacles, coat hooks, shelves, accessible routes, clear floor space at other fixtures and the
turning space. No other fixtures or obstructions shall be
within the required water closet clearance.
Seat height
17 − 19
430 − 485
Note: For children’s dimensions see Fig. 604.11.4
56 min
1420
Other fixtures not allowed
within this area
60 min
1525
FIGURE 604.3
SIZE OF CLEARANCE FOR WATER CLOSET
604.4 Height. The height of water closet seats shall be 17
inches (430 mm) minimum and 19 inches (485 mm) maximum above the floor, measured to the top of the seat. Seats
shall not be sprung to return to a lifted position.
Exceptions:
1. A water closet which is adjustable in height by the
user is permitted provided that at least one adjustment setting provides a seat within the range specified in this section.
2. A water closet in a toilet room for a single occupant, accessed only through a private office and not
for common use or public use, shall not be required
to comply with this section.
RESOURCE A-20
FIGURE 604.4
WATER CLOSET SEAT HEIGHT
604.5 Grab bars. Grab bars for water closets shall comply
with Section 609 and shall be provided in accordance with
Sections 604.5.1 and 604.5.2. Grab bars shall be provided on
the rear wall and on the side wall closest to the water closet.
Exceptions:
1. Grab bars shall not be required to be installed in a
toilet room for a single occupant, accessed only
through a private office and not for common use or
public use, provided reinforcement has been
installed in walls and located so as to permit the
installation of grab bars complying with Section
604.5.
2. In detention or correction facilities, grab bars shall
not be required to be installed in housing or holding
cells or rooms that are specially designed without
protrusions for purposes of suicide prevention.
604.5.1 Fixed side-wall grab bars. Fixed side-wall grab
bars shall include a horizontal bar complying with Section
604.5.1.1 and a vertical grab bar complying with Section
604.5.1.2. The vertical grab bar at water closets primarily
for children’s use shall comply with Section 609.4.2.
604.5.1.1 Horizontal grab bar. A horizontal grab bar
42 inches (1065 mm) minimum in length shall be
located 12 inches (305 mm) maximum from the rear
wall and extend 54 inches (1370 mm) minimum from
the rear wall.
604.5.1.2 Vertical grab bar. A vertical grab bar 18
inches (455 mm) minimum in length shall be mounted
with the bottom of the bar located 39 inches (990 mm)
minimum and 41 inches (1040 mm) maximum above
the floor, and with the center line of the bar located 39
inches (990 mm) minimum and 41 inches (1040 mm)
maximum from the rear wall.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
PLUMBING ELEMENTS AND FACILITIES
36 min
915
CL
33 − 36
840 − 915
Section 609.4.1
39 − 41
990 − 1040
39 − 41
990 − 1040
6 max
150
33 − 36
840 − 915
Section 609.4.1
42 min
1065
42 min
1065
18 min
455
12
max
305
54 min
1370
Note: For children’s dimensions see Fig. 609.4.2
FIGURE 604.5.2
REAR-WALL GRAB BAR FOR WATER CLOSET
Note: For children’s dimensions see Fig. 609.4.2
FIGURE 604.5.1
SIDE-WALL GRAB BAR FOR WATER CLOSET
604.5.2 Rear-wall grab bars. The fixed rear-wall grab
bar shall
1. Be 36 inches (915 mm) minimum in length,
2. Be located 6 inches maximum (150 mm) from the
side wall, and
3. Extend 42 inches (1065 mm) minimum from the
side wall.
Exceptions:
1. The rear grab bar shall be permitted to be 24
inches (610 mm) minimum in length, centered on
the water closet, where wall space does not permit a grab bar 36 inches (915 mm) minimum in
length due to the location of a recessed fixture
adjacent to the water closet.
2. Where an administrative authority requires flush
controls for flush valves to be located in a position that conflicts with the location of the rear
grab bar, that grab bar shall be permitted to be
split or shifted to the open side of the toilet area.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
604.6 Flush controls. Flush controls shall be hand operated
or automatic. Hand operated flush controls shall comply with
Section 309. Flush controls shall be located on the open side
of the water closet.
Exception: In ambulatory accessible toilet compartments
complying with Section 604.10, flush controls shall be
permitted to be located on either side of the water closet.
604.7 Dispensers. Toilet paper dispensers shall comply with
Sections 309.4 and 609.3. Dispensers shall not be of a type
that control delivery or do not allow continuous paper flow.
604.7.1 Location. Where the dispenser is located above the
grab bar, the outlet of the dispenser shall be located within an
area 24 inches (610 mm) minimum and 36 inches (915 mm)
maximum from the rear wall. Where the dispenser is located
below the grab bar, the outlet of the dispenser shall be located
18 inches (455 mm) minimum and 48 inches (1220 mm)
maximum above the floor.
Exception: Toilet paper dispensers that accommodate a
maximum of 2 toilet paper rolls of not more than 5-inch
(125 mm) diameter each shall be permitted to be located 7
inches (180 mm) minimum and 9 inches (230 mm) maximum in front the of the water closet measured to the centerline of the dispenser. The outlet of the dispenser shall be
15 inches (380 mm) minimum and 48 inches (1220 mm)
maximum above the floor.
RESOURCE A-21
PLUMBING ELEMENTS AND FACILITIES
42 max
1070
FIGURE 604.7.1(A)
DISPENSER OUTLET LOCATION - PROTRUDING DISPENSER
BELOW GRAB BAR
48 max
1220
18 min
455
1½ min
38
Section 609.3
24 min
610
36 max
915
24 min
610
12 min
305
Section 609.3
FIGURE 604.7.1(B)
DISPENSER OUTLET LOCATION
PROTRUDING DISPENSER ABOVE GRAB BAR
42 max
1070
18min
455
48 max
1220
36 max
915
24 min
610
Note: For children’s dimensions see Fig. 604.11.7 dispenser
outlet location
FIGURE 604.7.1(C)
DISPENSER OUTLET LOCATION
RECESSED DISPENSER
RESOURCE A-22
PLUMBING PROVISIONS FROM: ICC A117.1—2017
PLUMBING ELEMENTS AND FACILITIES
FIGURE 604.7.1(D)
DISPENSER OUTLET LOCATION
DISPENSER IN FRONT OF WATER CLOSET - EXCEPTION
604.8 Coat hooks and shelves. Coat hooks provided within
toilet compartments shall be 48 inches (1220 mm) maximum
above the floor. Shelves shall be 40 inches (1015 mm) minimum and 48 inches (1220 mm) maximum above the floor.
604.9 Wheelchair accessible toilet compartments.
604.9.1 General. Wheelchair accessible toilet compartments shall comply with Section 604.9.
604.9.2 Size. Wheelchair accessible toilet compartments
shall comply with Section 604.9.2.1, 604.9.2.2 or
604.9.2.3 as applicable.
604.9.2.1 Minimum area. The minimum area of a
wheelchair accessible toilet compartment shall be 60
inches (1525 mm) minimum in width measured perpendicular to the side wall, and 56 inches (1420 mm) minimum in depth for wall hung water closets, and 59
inches (1500 mm) minimum in depth for floor mounted
water closets measured perpendicular to the rear wall.
604.9.2.2 Compartment for children’s use. The minimum area of a wheelchair accessible toilet compartment primarily for children’s use shall be 60 inches
(1525 mm) minimum in width measured perpendicular
to the side wall, and 59 inches (1500 mm) minimum in
depth for wall hung and floor mounted water closets
measured perpendicular to the rear wall.
604.9.2.3 Alternate wheelchair accessible toilet compartments. Where an alternate wheelchair accessible
toilet compartment is provided, the minimum area of
the compartment shall be 60 inches (1525 mm) minimum in width, measured perpendicular to the side wall,
and 84 inches (2135 mm) minimum in depth, measured
perpendicular to the rear wall.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
60 min
1525
FIGURE 604.9.2(A)
WHEELCHAIR TOILET COMPARTMENTS
WALL HUNG CLOSET, ADULT
59 min
1500
7–9
180 –
230
15 min
380
48 max
1220
56 min
1420
C
L
60 min
1525
FIGURE 604.9.2(B)
WHEELCHAIR TOILET COMPARTMENTS
FLOOR MOUNTED WATER CLOSET, ADULT - WALL HUNG
AND FLOOR MOUNTED WATER CLOSET, CHILDREN
RESOURCE A-23
84 min
2085
PLUMBING ELEMENTS AND FACILITIES
60 min
1525
FIGURE 604.9.2.3
WHEELCHAIR TOILET COMPARTMENTS
ALTERNATE WHEELCHAIR TOILET COMPARTMENT
604.9.3 Doors. Wheelchair accessible toilet compartment
doors, including door hardware, shall comply with Section
404. The door shall be self-closing. A door pull complying
with Section 404.2.6 shall be placed on both sides of the
door near the latch. Wheelchair accessible toilet compartment doors shall not swing into the required minimum
area of the compartment.
Exceptions:
1. Outside of the compartment, where the approach
is to the latch side of the wheelchair accessible
toilet compartment, door clearance between the
door side of the compartment and any obstruction
shall be 42 inches (1065 mm) minimum.
2. Within the wheelchair accessible toilet compartment, maneuvering clearances at the door shall
not be required to comply with Section 404.
3. In an alternate wheelchair accessible toilet compartment, the door shall be permitted to swing
into the stall where a clear floor space complying
with Section 305.3 is provided within the stall
beyond the arc of the door swing.
604.9.3.1 Door opening location. The farthest edge of
the wheelchair accessible toilet compartment door
opening shall be located in the front wall or partition or
in the side wall or partition as required by Table
604.9.3.1.
60 min*
1525
Door shall not swing
into the required
minimum area of the
compartment.
56 min*
1420
(Wall mounted W.C.) - Adult
59 min*
1500
(Floor mounted W.C.) - Adult
Wall and floor mounted W.C. - Children
* Toliet compartment size per
Sections 604.9.2.1 and 604.9.2.2
FIGURE 604.9.3(A)
WHEELCHAIR TOILET COMPARTMENT DOORS
DOOR SWINGING INTO THE WHEELCHAIR TOILET COMPARTMENT
RESOURCE A-24
PLUMBING PROVISIONS FROM: ICC A117.1—2017
PLUMBING ELEMENTS AND FACILITIES
TABLE 604.9.3.1—DOOR OPENING LOCATION
Door Opening Location
Measured From
Dimension
From the side wall or
partition closest to the water closet
56 inches (1420 mm) minimum
Front Wall or Partition
or
From the side wall or
partition farthest from the water closet
From the rear wall
Side Wall or Partition
Wall-Hung Water Closet
52 inches (1320 mm) minimum
or
From the front wall or partition
From the rear wall
Side Wall or Partition
Floor-Mounted Water Closet
4 inches (100 mm) maximum
55 inches (1395 mm) minimum
or
From the front wall or partition
604.9.4 Approach. Wheelchair accessible toilet compartments shall be arranged for left-hand or right-hand
approach to the water closet.
604.9.5 Toe clearance. Toe clearance for wheelchair
accessible toilet compartments primarily for children’s use
shall comply with Section 604.9.5.2. Toe clearance for
other wheelchair accessible toilet compartments shall
comply with Section 604.9.5.1.
Partition
8
205
12 min
305
FIGURE 604.9.5(A)
TOE CLEARANCE - ELEVATION
8
205
8
205
FIGURE 604.9.5(B)
TOE CLEARANCE - PLAN
RESOURCE A-26
4 inches (100 mm) maximum
4 inches (100 mm) maximum
604.9.5.1 Toe clearance at wheelchair accessible toilet compartments. The front partition and at least one
side partition of wheelchair accessible toilet compartments shall provide a toe clearance of 12 inches (305
mm) minimum above the floor and extending 8 inches
(205 mm) beyond the compartment side face of the partition, exclusive of partition support members.
Exceptions:
1. Toe clearance at the front partition is not
required in a wheelchair accessible toilet compartment greater than 64 inches (1625 mm) in
depth with a wall-hung water closet, or greater
than 67 inches (1700 mm) in depth with a
floor-mounted water closet.
2. Toe clearance at the side partition is not
required in a wheelchair accessible toilet compartment greater than 68 inches (1725 mm) in
width.
604.9.5.2 Toe clearance at wheelchair accessible toilet compartments for children’s use. The front partition and at least one side partition of wheelchair
accessible toilet compartments primarily for children’s
use shall provide a toe clearance of 12 inches (305 mm)
minimum above the floor and extending 8 inches (205
mm) beyond the wheelchair accessible toilet compartment side face of the partition, exclusive of partition
support members.
Exceptions:
1. Toe clearance at the front partition is not
required in a wheelchair accessible toilet compartment greater than 67 inches (1700 mm) in
depth.
2. Toe clearance at the side partition is not
required in a wheelchair accessible toilet compartment greater than 68 inches (1725 mm) in
width.
604.9.6 Grab bars. Grab bars shall comply with Section
609. Side wall grab bars complying with Section 604.5.1
located on the wall closest to the water closet, and a rear
wall grab bar complying with Section 604.5.2, shall be
provided.
604.10 Ambulatory accessible toilet compartments.
604.10.1 General. Ambulatory accessible toilet compartments shall comply with Section 604.10.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
PLUMBING ELEMENTS AND FACILITIES
Note: For adult dimensions see Fig. 604.7
FIGURE 604.11.7(A)
CHILDREN’S DISPENSER OUTLET - LOCATION
RESOURCE A-28
19 max
485
14 min
355
FIGURE 604.11.7(B)
CHILDREN’S DISPENSER OUTLET - EXCEPTION
604.11.8 Toilet compartments. Wheelchair and ambulatory accessible toilet compartments shall comply with Sections 604.9 and 604.10, as applicable.
SECTION 605
URINALS
605.1 General. Urinals shall comply with Section 605.
605.2 Height and depth. Urinals shall be of the stall type or
shall be of the wall hung type with the rim at 17 inches (430
mm) maximum above the floor. Urinals shall be 131/2 inches
(345 mm) minimum in depth measured from the outer face of
the urinal rim to the finished wall surface.
14 min
355
19 max
485
24 min
610
7-9
180-230
Section 609.3
1½ min
38
42 max
1070
C
L
Section 609.3
1½ min
38
maximum above the floor, measured to the top of the seat.
Seats shall not be sprung to return to a lifted position.
604.11.5 Grab bars. Grab bars for water closets shall
comply with Section 604.5.
604.11.6 Flush controls. Flush controls shall be hand
operated or automatic. Hand operated flush controls shall
comply with Sections 309.2 and 309.4 and shall be
installed 36 inches (915 mm) maximum above the floor.
Flush controls shall be located on the open side of the
water closet.
Exception: In ambulatory accessible toilet compartments complying with Section 604.10, flush controls
shall be permitted to be located on either side of the
water closet.
604.11.7 Dispensers. Toilet paper dispensers shall comply
with Section 309.4. Dispensers shall not be of a type that
control delivery or do not allow continuous paper flow.
604.11.7.1 Location. The outlet of toilet paper dispensers shall be located within an area 24 inches (610 mm)
minimum and 42 inches (1065 mm) maximum from the
rear wall. The outlet of the dispenser shall be 14 inches
(355 mm) minimum and 19 inches (485 mm) maximum
above the floor.
Exception: Toilet paper dispensers that accommodate a maximum of 2 toilet paper rolls of not more
than 5-inch diameter each shall be permitted to be
located 7 inches minimum and 9 inches maximum in
front of the of the water closet measured to the centerline of the dispenser. The outlet of the dispenser
shall be 14 inches (355 mm) minimum and 19
inches (485 mm) maximum above the floor.
17 max
430
13½ min
345
FIGURE 605.2(A)
HEIGHT AND DEPTH OF URINAL
WALL HUNG TYPE
PLUMBING PROVISIONS FROM: ICC A117.1—2017
34 max
865
30 min
760
Controlend wall
Head end wall
Back wall
Length of bathtub
FIGURE 607.2(A)
CLEARANCE FOR BATHTUBS WITH
REMOVABLE IN TUB SEATS
30 min
760
Controlend wall
Head end wall
Back wall
Length of bathtub and seat
12 min
305
FIGURE 607.2(B)
CLEARANCE FOR BATHTUBS WITH
SEAT AT HEAD END OF TUB
−
840 − 915
Section 609.4.1
3−6
75 − 150
18 min
455
PLUMBING ELEMENTS AND FACILITIES
12 max
305
24 min
610
24 max
610
Head end
wall
Control
end wall
24 min
610
Back wall
12 min
305
4 max
100
FIGURE 607.4.2(B)
GRAB BARS FOR BATHTUBS WITH REMOVABLE SEATS - PLAN
607.5 Controls. Controls, other than drain stoppers, shall be
provided on an end wall, located between the bathtub rim and
grab bar, and between the open side of the bathtub and the
centerline of the width of the bathtub. Controls shall comply
with Section 309.4.
Control
end
C
L wall
SECTION 608
SHOWER COMPARTMENTS
608.1 General. Shower compartments shall comply with
Section 608.
608.2 Size, clearance and seat. Shower compartments shall
have sizes, clearances and seats complying with Section
608.2.
608.2.1 Transfer-type shower compartments. Transfertype shower compartments shall comply with Section
608.2.1.
608.2.1.1 Size. Transfer-type shower compartments
shall have a clear inside dimension of 36 inches (915
mm) in width and 36 inches (915 mm) in depth, measured at the center point of opposing sides. An entry 36
inches (915 mm) minimum in width shall be provided.
FIGURE 607.5
LOCATION OF BATHTUB CONTROLS
607.6 Hand shower. A hand shower with a hose 59 inches
(1500 mm) minimum in length, that can be used as both a
fixed shower head and as a hand shower, shall be provided.
The hand shower shall have a control with a nonpositive shutoff feature. Where provided, an adjustable-height hand
shower mounted on a vertical bar shall be installed so as to
not obstruct the use of grab bars.
607.7 Bathtub enclosures. Enclosures for bathtubs shall not
obstruct controls, faucets, shower and spray units or obstruct
transfer from wheelchairs onto bathtub seats or into bathtubs.
Enclosures on bathtubs shall not have tracks installed on the
rim of the bathtub.
607.8 Water temperature. Bathtubs shall deliver water that
is 120°F (49°C) maximum.
RESOURCE A-32
Control
CL wall
Seat C
wall L
36 min
915
36
915
36
915
Back wall
CL
Entrance
Note: inside finished dimensions measured
at the center points of opposing sides
FIGURE 608.2.1.1
TRANSFER-TYPE SHOWER COMPARTMENT SIZE
608.2.1.2 Clearance.
608.2.1.2.1 New buildings and facilities. In new
buildings and facilities, a clearance of 52 inches
(1320 mm) minimum in length and 36 inches (915
PLUMBING PROVISIONS FROM: ICC A117.1—2017
PLUMBING ELEMENTS AND FACILITIES
Back wall
mm) minimum in depth shall be provided adjacent
to the open face of the compartment. The length of
the clear floor space shall be measured perpendicular from either the control wall or from 4 inches (100
mm) behind the control wall.
Control
wall
Seat
wall
Seat
36min
915
Back wall
Control
wall
52min
1320
FIGURE 608.2.1.2(A)
TRANSFER-TYPE SHOWER COMPARTMENT CLEARANCES
NEW BUILDINGS - OPTION 1
608.2.1.2.2 Existing buildings and facilities. In
existing buildings and facilities, a clearance of 48
inches (1220 mm) minimum in length measured perpendicular from the control wall, and 36 inches (915
mm) minimum in depth shall be provided adjacent
to the open face of the compartment.
Back wall
Seat
wall
48min
1220
FIGURE 608.2.1.2(C)
TRANSFER-TYPE SHOWER COMPARTMENT CLEARANCES
EXISTING BUILDINGS
608.2.1.3 Seat. A folding or non-folding seat complying with Section 610 shall be provided on the wall
opposite the control wall.
Exception: A seat is not required to be installed in a
shower for a single occupant, accessed only through
a private office and not for common use or public
use, provided reinforcement has been installed in
walls and located so as to permit the installation of a
shower seat.
608.2.2 Standard roll-in-type shower compartments.
Standard roll-in-type shower compartments shall comply
with Section 608.2.2.
608.2.2.1 Size. Standard roll-in-type shower compartments shall have a clear inside dimension of 60 inches
(1525 mm) minimum in width and 30 inches (760 mm)
minimum in depth, measured at the center point of
opposing sides. An entry 60 inches (1525 mm) minimum in width shall be provided.
Control
wall
36min
915
4 max
100
CL
Side
wall
C
L
Control
wall
Seat
wall
C
L
30 min
760
36min
915
wall
60 min
1525
52min
1320
FIGURE 608.2.1.2(B)
TRANSFER-TYPE SHOWER COMPARTMENT CLEARANCES
NEW BUILDINGS - OPTION 2
PLUMBING PROVISIONS FROM: ICC A117.1—2017
Note: inside finished dimensions measured
at the center points of opposing sides
FIGURE 608.2.2.1
STANDARD ROLL-IN-TYPE SHOWER COMPARTMENT SIZE
RESOURCE A-33
PLUMBING ELEMENTS AND FACILITIES
18
min
455
3–6
75 –
150
3 – 6 18 min
75 –
455
150
18
455
33 – 36
840 – 915
Section 609.4.1
33 – 36
840 – 915
Section 609.4.1
Back
wall
FIGURE 608.3.1(A)
GRAB BARS IN TRANSFER-TYPE SHOWER - ELEVATION
Seat
wall
FIGURE 608.3.2(A)
GRAB BARS IN STANDARD ROLL-IN-TYPE SHOWER
ELEVATION
18
455
6 max
150
Edge
of
seat
Control wall
Control
wall
4 max
102
FIGURE 608.3.1(B)
GRAB BARS IN TRANSFER-TYPE SHOWER - PLAN
608.3.2 Standard roll-in-type showers. Grab bars in
standard roll-in showers shall comply with Sections
608.3.2.1 through 608.3.2.3.
608.3.2.1 Back-wall grab bar. In standard roll-in type
showers, a grab bar shall be provided on the back wall
beginning at the edge of the seat. The grab bars shall
not be provided above the seat. The back-wall grab bar
shall extend the length of the wall and extend within 6
inches (150 mm) maximum from the adjacent side wall
opposite the seat.
Exceptions:
1. The back wall grab bar shall not be required to
exceed 48 inches (1220 mm) in length.
2. The back-wall grab bar is not required to
extend within 6 inches (150 mm) of the adjacent side wall opposite the seat if it would
require the grab bar length to exceed 48 inches
(1220 mm) in length.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
6 max
150
Back wall
Control wall
Side
wall
Seat
wall
4 max
100
FIGURE 608.3.2(B)
GRAB BARS IN STANDARD ROLL-IN-TYPE SHOWER
PLAN
608.3.2.2 Side-wall grab bars. Where a side wall is
provided opposite the seat within 72 inches (1830 mm)
of the seat wall, a grab bar shall be provided on the
side-wall opposite the seat. The side wall grab bar shall
extend the length of the wall and extend within 6 inches
(150 mm) maximum from the adjacent back wall.
Exception: The side-wall grab bar shall not be
required to exceed 30 inches (760 mm) in length.
608.3.2.3 Vertical grab bar. Where a side wall is provided opposite the seat within 72 inches (1830 mm) of
the seat wall a vertical grab bar shall be provided. A
vertical grab bar 18 inches (455 mm) minimum in
length shall be provided on the end wall 3 inches (75
mm) minimum and 6 inches (150 mm) maximum
above the horizontal grab bar, and 4 inches (100 mm)
maximum inward from the front edge of the shower.
608.3.3 Alternate roll-in-type showers. In alternate roll-in
type showers, grab bars shall be provided on the back wall
and the side wall adjacent to the seat. Grab bars shall not be
provided above the seat. Grab bars shall be 6 inches (150
mm) maximum from the adjacent wall.
RESOURCE A-35
PLUMBING ELEMENTS AND FACILITIES
CL
33 – 36
840 – 915
Section 609.4.1
15 max
380
38 min
965
48 max
1220
Back wall
Control
wall
FIGURE 608.3.3(A)
GRAB BARS IN ALTERNATE ROLL-IN-TYPE
SHOWER - ELEVATION
FIGURE 608.4.1
TRANSFER-TYPE SHOWER CONTROLS AND
HAND SHOWER LOCATION
Side
wall
Side
wall
of seat
6 max
Edge 150
Back wall
608.4.2 Standard roll-in showers. In standard roll-in
showers, the controls and hand shower shall not be located
above the seat. Controls and hand showers shall be located
according to the following:
1. On the back wall,
2. At a height of 38 inches (965 mm) minimum and
48 inches (1220 mm) maximum above the shower
floor and
3. 16 inches (405 mm) minimum and 27 inches (685
mm) maximum from the wall behind the seat.
27 max
685
Seat wall
FIGURE 608.3.3(B)
GRAB BARS IN ALTERNATE ROLL-IN-TYPE
SHOWER - PLAN
Control wall
38 min
965
608.4 Controls and hand showers. Controls and hand showers shall comply with Sections 608.4 and 309.4.
608.4.1 Transfer-type showers. In transfer-type showers,
the controls and hand shower shall be located:
1. On the control wall opposite the seat.
2. At a height of 38 inches (965 mm) minimum and
48 inches (1220 mm) maximum above the shower
floor, and
3. 15 inches (380 mm) maximum, from the centerline
of the control wall toward the shower opening.
16 min
405
48 max
1220
6 max
150
6 max
150
FIGURE 608.4.2
STANDARD ROLL-IN-TYPE SHOWER CONTROLS AND
HAND SHOWER LOCATION
608.4.3 Alternate roll-in showers. In alternate roll-in
showers, the controls and hand shower shall be located
1. At a height of 38 inches (965 mm) minimum and
48 inches (1220 mm) maximum above the shower
floor, and
RESOURCE A-36
PLUMBING PROVISIONS FROM: ICC A117.1—2017
PLUMBING ELEMENTS AND FACILITIES
2. Where the controls and hand shower are located on
the end wall adjacent to the seat, the controls and
hand shower shall be 16 inches (405 mm) minimum and 27 inches (685 mm) maximum from the
wall behind the seat wall, or
3. Where the controls and hand shower are located on
the back wall opposite the seat, the controls and
hand shower shall be located within 15 inches (380
mm) maximum from the centerline of the seat
toward the transfer space.
38 min
965
48 max
1220
27 max
685
16 min
405
Side
wall
FIGURE 608.4.3(A)
ALTERNATE ROLL-IN-TYPE SHOWER CONTROLS AND HAND
SHOWER LOCATION - END WALL - ELEVATION
15 max
380
Back wall
38 min
965
48 max
1220
CL
FIGURE 608.4.3(B)
ALTERNATE ROLL-IN-TYPE SHOWER CONTROLS AND HAND
SHOWER LOCATION - CONTROL WALL - ELEVATION
608.5 Hand showers. A hand shower with a hose 59 inches
(1500 mm) minimum in length, that can be used both as a
fixed shower head and as a hand shower, shall be provided.
The hand shower shall have a control with a nonpositive shutoff feature. Where provided, an adjustable-height hand
PLUMBING PROVISIONS FROM: ICC A117.1—2017
shower mounted on a vertical bar shall be installed so as to
not obstruct the use of grab bars. A means to hold the hand
shower wand while in the on or off position shall be located
at a height of 38 inches (965 mm) minimum and 48 inches
(1220 mm) maximum above the shower finish floor.
Exception: In other than Accessible units and Type A
units, a fixed shower head located 48 inches (1220 mm)
maximum above the shower floor shall be permitted in
lieu of a hand shower.
608.6 Thresholds. Thresholds in roll-in-type shower compartments shall be 1/2 inch (13 mm) maximum in height in
accordance with Section 303. In transfer-type shower compartments, thresholds 1/2 inch (13 mm) maximum in height
shall be beveled, rounded, or vertical.
Exception: In existing facilities, in transfer-type shower
compartments where provision of a threshold 1/2 inch (13
mm) in height would disturb the structural reinforcement
of the floor slab, a threshold 2 inches (51 mm) maximum
in height shall be permitted.
608.7 Shower enclosures. Shower compartment enclosures
for shower compartments shall not obstruct controls or
obstruct transfer from wheelchairs onto shower seats.
608.8 Water temperature. Showers shall deliver water that
is 120°F (49°C) maximum.
SECTION 609
GRAB BARS
609.1 General. Grab bars in toilet or bathing facilities shall
comply with Section 609.
609.2 Cross section. Grab bars shall have a cross section
complying with Section 609.2.1 or 609.2.2.
609.2.1 Circular cross section. Grab bars with a circular
cross section shall have an outside diameter of 11/4 inch
(32 mm) minimum and 2 inches (51 mm) maximum.
609.2.2 Noncircular cross section. Grab bars with a noncircular cross section shall have a cross section dimension
of 2 inches (51 mm) maximum, and a perimeter dimension
of 4 inches (100 mm) minimum and 4.8 inches (120 mm)
maximum.
609.3 Spacing. The space between the wall and the grab bar
shall be 11/2 inches (38 mm). The space between the grab bar
and projecting objects below and at the ends of the grab bar
shall be 11/2 inches (38 mm) minimum. The space between
the grab bar and projecting objects above the grab bar shall be
12 inches (305 mm) minimum.
Exceptions:
1. The space between the grab bars and shower controls, shower fittings, and other grab bars above the
grab bar shall be permitted to be 11/2 inches (38 mm)
minimum.
2. Recessed dispensers projecting from the wall 1/4 inch
(6.4 mm) maximum measured from the face of the
dispenser and complying with Section 604.7 shall be
permitted within the 12-inch (305 mm) space above
and the 11/2-inch (38 mm) spaces below and at the
ends of the grab bar.
RESOURCE A-37
PLUMBING ELEMENTS AND FACILITIES
4 to 4.8 perimeter
100 − 120
1¼ − 2
32 − 51
(A) Circular
2 max
51
(B) Noncircular
(C)
2. Vertical grab bars shall comply with Sections
604.5.1.2, 607.4.1.2.2, 607.4.2.2 and 608.3.1.2.
3. Grab bars at water closets primarily for children’s
use shall comply with Section 609.4.2.
609.4.2 Position of children’s grab bars. At water closets primarily for children's use complying with Section
604.11, grab bars shall be installed in a horizontal position
18 inches (455 mm) minimum and 27 inches (685 mm)
maximum above the floor measured to the top of the gripping surface. A vertical grab bar shall be mounted with the
bottom of the bar located between 21 inches (535 mm)
minimum and 30 inches (760 mm) maximum above the
floor and with the centerline of the bar located between 34
inches (865 mm) minimum and 36 inches (915 mm) maximum from the rear wall.
FIGURE 609.2
SIZE OF GRAB BARS
FIGURE 609.3
SPACING OF GRAB BARS
609.4 Position of grab bars.
609.4.1 General. Grab bars shall be installed in a horizontal position, 33 inches (840 mm) minimum and 36 inches
(915 mm) maximum above the floor measured to the top
of the gripping surface or shall be installed as required by
Items 1 through 3.
1. The lower grab bar on the back wall of a bathtub
shall comply with Section 607.4.1.1 or 607.4.2.1.
RESOURCE A-38
18 – 27
455 – 685
Section 604.5.1
21 – 30
535 – 760
34 – 36
865 – 915
18 min
455
12 min
305
54 min
1370
42 min
1065
Note: For adult dimensions see Fig. 604.5.1
FIGURE 609.4.2(A)
POSITIONS OF CHILDREN’S GRAB BARS
SIDE-WALL VIEW
PLUMBING PROVISIONS FROM: ICC A117.1—2017
PLUMBING ELEMENTS AND FACILITIES
42 min
1065
36 min
915
6 max
150
18 − 27
455 − 685
17 − 19
430 − 485
Section 604.5.2
15 − 16
380 − 405
Note: For adult dimensions see Fig. 604.5.2
Control end wall
15 min
380
Head end w all
Back wall
Control end wall
SECTION 610
SEATS
610.1 General. Seats in bathtubs and shower compartments
shall comply with Section 610.
610.2 Bathtub seats. The height of bathtub seats shall be 17
inches (430 mm) minimum and 19 inches (485 mm) maximum above the bathroom floor, measured to the top of the
seat. Removable in-tub seats shall be 15 inches (380 mm)
minimum and 16 inches (405 mm) maximum in depth.
Removable in-tub seats shall be capable of secure placement.
Permanent seats shall be 15 inches (380 mm) minimum in
depth and shall extend from the back wall to or beyond the
outer edge of the bathtub. Permanent seats shall be positioned
at the head end of the bathtub.
FIGURE 610.2(A)
BATHTUB SEATS
REMOVABLE IN-TUB SEATS
430 − 485
17 − 19
609.5 Surface hazards. Grab bars and any wall or other surfaces adjacent to grab bars shall be free of sharp or abrasive
elements. Edges shall be rounded.
609.6 Fittings. Grab bars shall not rotate within their fittings.
609.7 Installation and configuration. Grab bars shall be
installed in any manner that provides a gripping surface at the
locations specified in this standard and does not obstruct the
clear floor space. Horizontal and vertical grab bars shall be
permitted to be separate bars, a single piece bar, or combination thereof.
609.8 Structural strength. Allowable stresses shall not be
exceeded for materials used where a vertical or horizontal
force of 250 pounds (1112 N) is applied at any point on the
grab bar, fastener mounting device, or supporting structure.
Head end wall
Back wall
FIGURE 609.4.2(B)
POSITIONS OF CHILDREN’S GRAB BARS
REAR-WALL VIEW
FIGURE 610.2(B)
BATHTUB SEATS
SEAT PROVIDED AT HEAD END OF TUB
PLUMBING PROVISIONS FROM: ICC A117.1—2017
RESOURCE A-39
PLUMBING ELEMENTS AND FACILITIES
CL
Centered on the
appliance
FIGURE 611.2(A)
CLEAR FLOOR SPACE - TOP LOADING
36 max
915
611.3 Operable parts. Operable parts, including doors, lint
screens, detergent and bleach compartments, shall comply
with Sections 308 and 309.
Exception: The height of the obstruction in Section
308.3.2 shall be permitted to be 36 inches (915 mm) maximum above the floor.
611.4 Height. Top loading machines shall have the door to
the laundry compartment 36 inches (915 mm) maximum
above the floor. Front loading machines shall have the bottom
of the opening to the laundry compartment 15 inches (380
mm) minimum and 36 inches (915 mm) maximum above the
floor.
CL
C
L
Offset 24 inches (610 mm)
maximum from center of
door opening
15 – 36
380 – 915
FIGURE 611.4(A)
HEIGHT OF LAUNDRY EQUIPMENT - TOP LOADING
FIGURE 611.2(B)
CLEAR FLOOR SPACE - FRONT LOADING
FIGURE 611.4(B)
HEIGHT OF LAUNDRY EQUIPMENT - FRONT LOADING
PLUMBING PROVISIONS FROM: ICC A117.1—2017
RESOURCE A-41
PLUMBING ELEMENTS AND FACILITIES
SECTION 612
SAUNAS AND STEAM ROOMS
612.1 General. Saunas and steam rooms shall comply with
Section 612.
612.2 Bench. Where seating is provided in saunas and steam
rooms, at least one bench shall comply with Section 903.
Doors shall not swing into the clear floor space required by
Section 903.2.
Exception: Where the room is for individual use and a
clear floor space complying with Section 305.3 is provided within the room beyond the arc of the door swing,
the door shall not be required to comply with this section.
612.3 Turning space. A turning space shall be provided
within saunas and steam rooms.
RESOURCE A-42
PLUMBING PROVISIONS FROM: ICC A117.1—2017
CHAPTER 8
SPECIAL ROOMS AND SPACES
SECTION 801
GENERAL
801.1 Scope. Special rooms and spaces required to be accessible by the scoping provisions adopted by the administrative
authority shall comply with the applicable provisions of
Chapter 8.
SECTION 804
KITCHENS
804.1 General. Kitchens shall comply with Section 804.
804.2 Clearance. Where a pass-through kitchen is provided,
clearances shall comply with Section 804.2.1. Where a Ushaped kitchen is provided, clearances shall comply with Section 804.2.2. Kitchens where a cook top or conventional
range is not provided shall comply with Section 804.2.3.
804.2.1 Pass-through kitchens. In pass-through kitchens
where counters, appliances or cabinets are on two opposing sides, or where counters, appliances or cabinets are
opposite a parallel wall, clearance between all opposing
base cabinets, countertops, appliances, or walls within
kitchen work areas shall be 40 inches (1015 mm) minimum. Pass-through kitchens shall have two entries.
804.2.2 U-shaped kitchens. In kitchens enclosed on three
contiguous sides, clearance between all opposing base
cabinets, countertops, appliances, or walls within kitchen
work areas shall be 60 inches (1525 mm) minimum.
Exception: U-shaped kitchens with an island complying with Section 804.2.1.
804.2.3 Spaces where a cook top or conventional range
is not provided. In a kitchen space where a cooktop or
conventional range is not provided, clearance between all
opposing base cabinets, countertops, appliances and walls
within kitchen work areas shall be 40-inch (1015 mm)
minimum.
804.3 Work surface. At least one accessible work surface 30
inches minimum in length shall be provided in accordance
with Section 902. The work surface shall be located in accordance with Section 804.5.5.2 or 804.5.5.3.
Exception: Spaces that do not provide a cooktop or conventional range shall not be required to provide an accessible work surface.
804.4 Sinks. The sink shall comply with Section 606.
804.5 Appliances. Where provided, kitchen appliances shall
comply with Section 804.5.
804.5.1 Clear floor space. A clear floor space shall be
provided at each kitchen appliance.
804.5.2 Operable parts. All appliance controls shall comply with Section 309.
Exceptions:
1. Appliance doors and door latching devices shall
not be required to comply with Section 309.4.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
2. Bottom-hinged appliance doors, when in the
open position, shall not be required to comply
with Section 309.3.
804.5.3 Dishwasher. A clear floor space positioned adjacent to the dishwasher door, shall be provided. The dishwasher door in the open position shall not obstruct the
clear floor space for the dishwasher or an adjacent sink.
804.5.4 Cooktop. Cooktops shall comply with Section
804.5.4.
804.5.4.1 Approach. A clear floor space, positioned
for a parallel or forward approach to the cooktop, shall
be provided.
804.5.4.2 Forward approach. Where the clear floor
space is positioned for a forward approach, knee and
toe clearance complying with Section 306 shall be provided. The underside of the cooktop shall be insulated
or otherwise configured to prevent burns, abrasions, or
electrical shock.
804.5.4.3 Parallel approach. Where the clear floor
space is positioned for a parallel approach, the clear
floor space shall be centered on the appliance.
804.5.4.4 Controls. The location of controls shall not
require reaching across burners.
804.5.5 Oven. Ovens shall comply with Section 804.5.5.
804.5.5.1 Clear floor space. A clear floor space shall
be provided. The oven door in the open position shall
not obstruct the clear floor space for the oven.
804.5.5.2 Side-hinged door ovens. Side-hinged door
ovens shall have a work surface complying with Section 804.3 positioned adjacent to the latch side of the
oven door.
804.5.5.3 Bottom-hinged door ovens. Bottom-hinged
door ovens shall have a work surface complying with
Section 804.3 positioned adjacent to one side of the
door.
804.5.5.4 Controls. The location of controls shall not
require reaching across burners.
804.5.6 Refrigerator/freezer. Combination refrigerators and
freezers shall have at least 50 percent of the freezer compartment shelves, including the bottom of the freezer, 54 inches
(1370 mm) maximum above the floor when the shelves are
installed at the maximum heights possible in the compartment. A clear floor space, positioned for a parallel approach
to the refrigerator/freezer, shall be provided. The centerline
of the clear floor space shall be offset 24 inches (610 mm)
maximum from the centerline of the appliance.
RESOURCE A-43
SPECIAL ROOMS AND SPACES
Work
surface
Work
surface
DW
Ref
Ref
40 min
1015
40 min
1015
FIGURE 804.2.1(A)
PASS-THROUGH KITCHEN CLEARANCE
FIGURE 804.2.1(B)
PASS-THROUGH KITCHEN CLEARANCE
Work
surface
Work
surface
DW
DW
Ref
60 min
1525
FIGURE 804.2.2(A)
U-SHAPED KITCHEN CLEARANCE
RESOURCE A-44
Ref
60 min
1525
FIGURE 804.2.2(B)
U-SHAPED KITCHEN CLEARANCE
PLUMBING PROVISIONS FROM: ICC A117.1—2017
40 min
1015
SPECIAL ROOMS AND SPACES
40 mn
1015
40 min
1015
40 mn
1015
40 min
1015
FIGURE 804.2.2(C)
U-SHAPED KITCHEN CLEARANCE - EXCEPTION
PLUMBING PROVISIONS FROM: ICC A117.1—2017
RESOURCE A-45
RESOURCE A-46
PLUMBING PROVISIONS FROM: ICC A117.1—2017
CHAPTER 11
DWELLING UNITS AND SLEEPING UNITS
SECTION 1101
GENERAL
1101.1 Scoping. Dwelling units and sleeping units required
by the scoping provisions adopted by the administrative
authority to be Accessible units, Type A units, Type B units,
Type C (Visitable) units or units with accessible communication features shall comply with the applicable provisions of
Chapter 11.
SECTION 1102
ACCESSIBLE UNITS
1102.1 General. Accessible units shall comply with Section
1102.
1102.2 Primary entrance. The primary entrance shall be on
an accessible route from public and common areas. The primary entrance shall not be to a bedroom unless it is the only
entrance.
1102.3 Accessible route. Accessible routes within Accessible units shall comply with Section 1102.3.
1102.3.1 Location. At least one accessible route shall connect all spaces and elements that are a part of the unit.
Accessible routes shall coincide with or be located in the
same area as a general circulation path.
Exception: An accessible route is not required to
unfinished attics and unfinished basements that are part
of the unit.
1102.3.2 Turning space. All rooms served by an accessible route shall provide a turning space.
Exceptions:
1. A turning space shall not be required in toilet
rooms and bathrooms that are not required to
comply with Section 1102.11.2.
2. A turning space is not required within closets or
pantries that are 48 inches (1220 mm) maximum
in depth.
1102.3.3 Components. Accessible routes shall consist of
one or more of the following elements: walking surfaces
with a slope not steeper than 1:20, doors and doorways,
ramps, elevators, and platform lifts.
1102.4 Walking surfaces. Walking surfaces that are part of
an accessible route shall comply with Section 403.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
1102.5 Doors and doorways. The primary entrance door to
the unit, and all other doorways intended for user passage,
shall comply with Section 404.
Exceptions:
1. Existing doors to hospital patient sleeping rooms
shall be exempt from the requirement for space at
the latch side provided the door is 44 inches (1120
mm) minimum in width.
2. In toilet rooms and bathrooms not required to comply with Section 1102.11.2, maneuvering clearances
required by Section 404.2.3 shall not be required on
the toilet room or bathroom side of the door.
3. A turning space between doors in a series as
required by Section 404.2.5 is not required.
4. Storm and screen doors shall not be required to comply with Section 404.2.5.
5. Communicating doors between individual sleeping
units shall not be required to comply with Section
404.2.5.
6. At other than the primary entrance door, where exterior space dimensions of balconies are less than the
required maneuvering clearance, door maneuvering
clearance is not required on the exterior side of the
door.
7. The maneuvering clearances required by Section
404 shall not be required within a closet or pantry
complying with Exception 2 of Section 1102.3.2.
1102.6 Ramps. Ramps shall comply with Section 405.
1102.7 Elevators. Elevators within the unit shall comply
with Section 407, 408, or 409.
1102.8 Platform lifts. Platform lifts within the unit shall
comply with Section 410.
1102.9 Operable parts. Lighting controls, electrical panelboards, electrical switches and receptacle outlets, environmental controls, appliance controls, plumbing fixture controls
and user controls for security or intercom systems shall comply with Section 309.
1102.10 Laundry equipment. Washing machines and
clothes dryers shall comply with Section 611.
1102.11 Toilet and bathing facilities. At least one toilet and
bathing facility shall comply with Section 1102.11.2. All
other toilet and bathing facilities shall comply with Section
1102.11.1
RESOURCE A-47
DWELLING UNITS AND SLEEPING UNITS
1102.11.1 Grab bars and shower seat reinforcement. At
fixtures in toilet and bathing facilities not required to comply with Section 1102.11.2, reinforcement in accordance
with Section 1104.11.1 shall be provided.
Exception: Reinforcement is not required where Type
B units are not provided in the structure.
1102.11.2 Toilet and bathing facility. At least one toilet
and bathing facility shall comply with Section 603. At
least one lavatory, one water closet and either a bathtub or
shower within the unit shall comply with Sections 604
through 610. These toilet and bathing fixtures shall be in a
single toilet/bathing area, such that travel between fixtures
does not require travel through other parts of the unit.
1102.11.2.1 Vanity countertop space. If vanity countertop space is provided in dwelling or sleeping units
not required to be Accessible units within the same
facility, equivalent vanity countertop space, in terms of
size and proximity to the lavatory, shall also be provided in Accessible units.
1102.11.2.2 Mirrors. Mirrors above lavatories
required to comply with Section 606 shall have the bottom edge of the reflecting surface 40 inches (1015 mm)
maximum above the floor.
1102.12 Kitchens. Kitchens shall comply with Section 804.
1102.13 Windows. Operable windows shall comply with
Section 506.1.
Exceptions:
1. Windows in kitchens shall not be required to comply
with Section 1102.13.
2. Windows in bathrooms shall not be required to comply with Section 1102.13.
1102.14 Storage facilities. Where storage facilities are provided, at least one of each type shall comply with Section
905.
Exception: Kitchen cabinets shall not be required to comply with Section 1102.14.
1102.15 Beds. In at least one sleeping area, a minimum of
five percent, but not less than one bed shall comply with Section 1102.15.
1102.15.1 Clear floor space. A clear floor space shall be
provided on both sides of the bed. The clear floor space
shall be positioned for parallel approach to the side of the
bed.
Exception: Where a single clear floor space positioned
for parallel approach is provided between two beds, a
clear floor space shall not be required on both sides of
the bed.
1102.15.2 Bed frames. At least one bed shall be provided
with an open bed frame.
1102.15.3 Bed height. At least one bed shall measure 17
to 23 inches (430 to 585 mm) high from the floor to the
top of the uncompressed mattress.
1102.15.4 Wheelchair charging area. The clear floor
space required by Section 1102.15.1 shall also serve as a
wheelchair charging area complying with Section 906.
RESOURCE A-48
SECTION 1103
TYPE A UNITS
1103.1 General. Type A units shall comply with Section
1103.
1103.2 Primary entrance. The primary entrance shall be on
an accessible route from public and common areas. The primary entrance shall not be to a bedroom unless it is the only
entrance.
1103.3 Accessible route. Accessible routes within Type A
units shall comply with Section 1103.3.
1103.3.1 Location. At least one accessible route shall connect all spaces and elements that are a part of the unit.
Accessible routes shall coincide with or be located in the
same area as a general circulation path.
Exception: An accessible route is not required to
unfinished attics and unfinished basements that are part
of the unit.
1103.3.2 Turning space. All rooms served by an accessible route shall provide a turning space.
Exceptions:
1. A turning space is not required in toilet rooms
and bathrooms that are not required to comply
with Section 1103.11.2.
2. A turning space is not required within closets or
pantries that are 48 inches (1220 mm) maximum
in depth.
1103.3.3 Components. Accessible routes shall consist of
one or more of the following elements: walking surfaces
with a slope not steeper than 1:20, doors and doorways,
ramps, elevators, and platform lifts.
1103.4 Walking surfaces. Walking surfaces that are part of
an accessible route shall comply with Section 403.
1103.5 Doors and doorways. The primary entrance door to
the unit, and all other doorways intended for user passage,
shall comply with Section 404.
Exceptions:
1. Thresholds at exterior sliding doors shall be permitted to be 3/4 inch (19 mm) maximum in height, provided they are beveled with a slope not greater than
1:2.
2. In toilet rooms and bathrooms not required to comply with Section 1103.11.2, maneuvering clearances
required by Section 404.2.3 shall not be required on
the toilet room or bathroom side of the door.
3. A turning space between doors in a series as
required by Section 404.2.5 is not required.
4. Storm and screen doors shall not be required to comply with Section 404.2.5.
5. Communicating doors between individual sleeping
units shall not be required to comply with Section
404.2.5.
6. At other than the primary entrance door, where exterior space dimensions of balconies are less than the
required maneuvering clearance, door maneuvering
PLUMBING PROVISIONS FROM: ICC A117.1—2017
DWELLING UNITS AND SLEEPING UNITS
clearance is not required on the exterior side of the
door.
7. The maneuvering clearances required by Section
404 shall not be required within a closet or pantry
complying with Exception 2 of Section 1103.3.2.
1103.6 Ramps. Ramps shall comply with Section 405.
1103.7 Elevators. Elevators within the unit shall comply
with Section 407, 408, or 409.
1103.8 Platform lifts. Platform lifts within the unit shall
comply with Section 410.
1103.9 Operable parts. Lighting controls, electrical panelboards, electrical switches and receptacle outlets, environmental controls, appliance controls, plumbing fixture
controls, and user controls for security or intercom systems
shall comply with Section 309.
1103.10 Laundry equipment. Washing machines and
clothes dryers shall comply with Section 611.
1103.11 Toilet and bathing facilities. At least one toilet and
bathing facility shall comply with Section 1103.11.2. All toilet and bathing facilities shall comply with Section 1103.11.1.
1103.11.1 Grab bar and shower seat reinforcement.
Reinforcement shall be provided for the future installation
of grab bars complying with Section 604.5 at water closets; grab bars complying with Section 607.4 at bathtubs;
and for grab bars and shower seats complying with Sections 608.3, 608.2.1.3, 608.2.2.3 and 608.2.3.2 at shower
compartments.
Exceptions:
1. At fixtures not required to comply with Section
1103.11.2, reinforcement in accordance with
Section 1104.11.1 shall be permitted.
2. Reinforcement is not required in a room containing only a lavatory and a water closet, provided
the room does not contain the only lavatory or
water closet on the accessible level of the dwelling unit.
3. Reinforcement for the water closet side wall vertical grab bar component required by Section
604.5 is not required.
4. Where the lavatory overlaps the water closet
clearance in accordance with the exception to
Section 1103.11.2.4.4 reinforcement at the water
closet rear wall for a 24-inch (610 mm) minimum
length grab bar, centered on the water closet,
shall be provided.
1103.11.2 General. At least one toilet and bathing facility
shall comply with Section 1103.11.2. At least one lavatory, one water closet and either a bathtub or shower
within the unit shall comply with Section 1103.11.2.
These toilet and bathing fixtures shall be in a single toilet/
bathing area, such that travel between fixtures does not
require travel through other parts of the unit.
1103.11.2.1 Doors. Doors shall not swing into the clear
floor space or clearance for any fixture.
Exception: Where a clear floor space is provided
within the room beyond the arc of the door swing.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
1103.11.2.2 Lavatory. Lavatories shall comply with
Section 606.
Exception: Cabinetry shall be permitted under the
lavatory, provided the following criteria are met:
1. The cabinetry can be removed without
removal or replacement of the lavatory;
2. The floor finish extends under the cabinetry;
and
3. The walls behind and surrounding the cabinetry are finished.
1103.11.2.3 Mirrors. Mirrors above lavatories
required to comply with Section 1103.11.2.2 shall have
the bottom edge of the reflecting surface 40 inches
(1015 mm) maximum above the floor.
1103.11.2.4 Water closet. Water closets shall comply
with Section 1103.11.2.4.
1103.11.2.4.1 Location. The water closet shall be
positioned with a wall to the rear and to one side.
The centerline of the water closet shall be 16 inches
(405 mm) minimum and 18 inches (455 mm) maximum from the sidewall.
1103.11.2.4.2 Clearance width. Clearance around
the water closet shall be 60 inches (1525 mm) minimum in width, measured perpendicular from the
side wall.
1103.11.2.4.3 Clearance depth. Clearance around
the water closet shall be 56 inches (1420 mm) minimum in depth, measured perpendicular from the rear
wall.
1103.11.2.4.4 Clearance overlap. The required
clearance around the water closet shall be permitted
to overlap the water closet, associated grab bars,
paper dispensers, coat hooks, shelves, accessible
routes, clear floor space required at other fixtures,
and the wheelchair turning space. No other fixtures
or obstructions shall be located within the required
water closet clearance.
CL
16 −18
405 − 455
FIGURE 1103.11.2.4(A)
WATER CLOSETS IN TYPE A UNITS - WATER CLOSET
LOCATION
RESOURCE A-49
60 min
1525
FIGURE 1103.11.2.4(B)
WATER CLOSETS IN TYPE A UNITS - MINIMUM CLEARANCE
inches (485 mm) maximum above the floor, measured to the top of the seat.
1103.11.2.4.6 Flush controls. Flush controls shall
be hand-operated or automatic. Hand operated flush
controls shall comply with Section 309. Hand-operated flush controls shall be located on the open side
of the water closet.
1103.11.2.5 Bathing fixtures. The bathing fixture shall
be a bathtub complying with Section 1103.11.2.5.1 or a
shower compartment complying with Section
1103.11.2.5.2.
1103.11.2.5.1 Bathtub. Bathtubs shall comply with
Section 607.
Back wall
66 min
1675
30 min
760
Control end wall
18 min
455
Head end
wall
56 min
1420
DWELLING UNITS AND SLEEPING UNITS
CL
60 min
1525
FIGURE 1103.11.2.5.1(A)
CLEARANCE FOR BATHTUBS IN TYPE A UNITS
WITH REMOVABLE SEAT
Back wall
30 min
760
Head end
wall
15 −19
380 − 485
Length of bath tub
Control end wall
FIGURE 1103.11.2.4(C)
WATER CLOSETS IN TYPE A UNITS - CLEARANCE WITH
LAVATORY (OVERLAP EXCEPTION)
FIGURE 1103.11.2.4(D)
WATER CLOSETS IN TYPE A UNITS - WATER CLOSET SEAT
HEIGHT
Exception: A lavatory measuring 24 inches (610
mm) maximum in depth and complying with Section 1103.11.2.2 shall be permitted on the rear
wall 18 inches (455 mm) minimum from the centerline of the water closet to the side edge of the
lavatory where the clearance at the water closet is
66 inches (1675 mm) minimum measured perpendicular from the rear wall.
1103.11.2.4.5 Height. The top of the water closet
seat shall be 15 inches (380 mm) minimum and 19
RESOURCE A-50
12 min
305
Length of bath tub and seat
FIGURE 1103.11.2.5.1(B)
CLEARANCE FOR BATHTUBS IN TYPE A UNITS
WITH PERMANENT SEAT
PLUMBING PROVISIONS FROM: ICC A117.1—2017
DWELLING UNITS AND SLEEPING UNITS
30 min
760
Exception: Countertops and cabinetry shall be
permitted at one end of the clearance, provided
the following criteria are met:
1. The countertop and cabinetry can be
removed;
2. The floor finish extends under the countertop and cabinetry; and
3. The walls behind and surrounding the
countertop and cabinetry are finished.
1103.11.2.5.2 Shower. Showers shall comply with
Section 608.
Exception: At standard roll-in shower compartments complying with Section 608.2.2, lavato-
60 min
1525
Note: Lavatory permitted per
Section 608.2.2
FIGURE 1103.11.2.5.2
STANDARD ROLL-IN-TYPE SHOWER COMPARTMENT IN
TYPE A UNITS
ries, countertops and cabinetry shall be permitted
at one end of the clearance, provided the following criteria are met:
1. The countertop and cabinetry can be
removed;
2. The floor finish extends under the countertop and cabinetry; and
3. The walls behind and surrounding the
countertop and cabinetry are finished.
1103.12 Kitchens. Kitchens shall comply with Section
1103.12.
1103.12.1 Clearance. Clearance complying with Section
1103.12.1 shall be provided.
1103.12.1.1 Minimum clearance. Clearance between
all opposing base cabinets, countertops, appliances, or
walls within kitchen work areas shall be 40 inches
(1015 mm) minimum.
1103.12.1.2 U-shaped kitchens. In kitchens with
counters, appliances, or cabinets on three contiguous
sides, clearance between all opposing base cabinets,
countertops, appliances, or walls within kitchen work
areas shall be 60 inches (1525 mm) minimum.
Exception: U-shaped kitchens with an island complying with Section 1103.12.1.1.
1103.12.2 Clear floor space. Clear floor spaces required
by Sections 1103.12.3 through 1103.12.5 shall comply
with Section 305.
Work
surface
Work
surface
DW
Ref
Ref
40 min
1015
40 min
1015
(B)
(A)
FIGURE 1103.12.1.1
MINIMUM KITCHEN CLEARANCE IN TYPE A UNITS
PLUMBING PROVISIONS FROM: ICC A117.1—2017
RESOURCE A-51
DWELLING UNITS AND SLEEPING UNITS
DW
Ref
60 min
1525
FIGURE 1103.12.1.2(A)
U-SHAPED KITCHEN CLEARANCE IN TYPE A UNITS
1103.12.3.1 Clear floor space. A clear floor space,
positioned for a forward approach to the work surface,
shall be provided. Knee and toe clearance complying
with Section 306 shall be provided.
Exception: Cabinetry shall be permitted under the
work surface, provided the following criteria are
met:
1. The cabinetry can be removed without
removal or replacement of the work surface,
2. The floor finish extends under the cabinetry,
and
3. The walls behind and surrounding the cabinetry are finished.
1103.12.3.2 Height. The work surface shall be 34
inches (865 mm) maximum above the floor.
Exception: A counter that is adjustable to provide a
work surface at variable heights 29 inches (735 mm)
minimum and 36 inches (915 mm) maximum above
the floor, or that can be relocated within that range
without cutting the counter or damaging adjacent
cabinets, walls, doors, and structural elements, shall
be permitted.
1103.12.3.3 Exposed surfaces. There shall be no sharp
or abrasive surfaces under the exposed portions of work
surface counters.
40 min
1015
30 min*
760
40 mn
1015
40 min
1015
40 mn
1015
34 max
865
40 min
1015
* 36 min. (915) if part of T-shaped turning
space per Sections 304.3.2 and 1003.3.2
FIGURE 1103.12.3
WORK SURFACE IN KITCHEN FOR TYPE A UNITS
1103.12.3 Work surface. At least one section of counter
shall provide an accessible work surface 30 inches (760
mm) minimum in length complying with Section
1103.12.3.
Exception: Spaces that do not provide a cooktop or
conventional range shall not be required to provide an
accessible work surface.
RESOURCE A-52
1103.12.4 Sink. Sinks shall comply with Section
1103.12.4.
1103.12.4.1 Clear floor space. A clear floor space,
positioned for a forward approach to the sink, shall be
provided. Knee and toe clearance complying with Section 306 shall be provided.
Exceptions:
1. The requirement for knee and toe clearance
shall not apply to more than one bowl of a
multi-bowl sink.
2. Cabinetry shall be permitted to be added under
the sink, provided the following criteria are
met:
2.1. The cabinetry can be removed without
removal or replacement of the sink,
PLUMBING PROVISIONS FROM: ICC A117.1—2017

FIGURE 1103.12.1.2(B)
U-SHAPED KITCHEN CLEARANCE IN TYPE A UNITS
EXCEPTION
DWELLING UNITS AND SLEEPING UNITS
2.2. The floor finish extends under the cabinetry, and
2.3. The walls behind and surrounding the
cabinetry are finished.
3. A clear floor space providing a parallel
approach and centered on the sink shall be
permitted at a kitchen sink in a space where a
cook top or conventional range is not provided.
4. A clear floor space providing a parallel
approach and centered on the sink shall be
permitted at wet bars.
1103.12.4.2 Height. The front of the sink shall be 34
inches (865 mm) maximum above the floor, measured
to the higher of the rim or counter surface.
Exception: A sink and counter that is adjustable to
variable heights 29 inches (735 mm) minimum and
36 inches (915 mm) maximum above the floor, or
that can be relocated within that range without cutting the counter or damaging adjacent cabinets,
walls, doors and structural elements, provided
rough-in plumbing permits connections of supply
and drain pipes for sinks mounted at the height of 29
inches (735 mm), shall be permitted.
1103.12.4.3 Faucets. Faucets shall comply with Section 309.
1103.12.4.4 Exposed pipes and surfaces. Water supply and drain pipes under sinks shall be insulated or
otherwise configured to protect against contact. There
shall be no sharp or abrasive surfaces under sinks.
34 max
865
30 min*
760
* 36 in. (915 mm) min. if part of T-shaped turning
space in accordance with Sections 304.3.2
and 1003.3.2
FIGURE 1103.12.4
KITCHEN SINK FOR TYPE A UNITS
1103.12.5 Appliances. Where provided, kitchen appliances shall comply with Section 1103.12.5.
1103.12.5.1 Operable parts. All appliance controls
shall comply with Section 1103.9.
Exceptions:
1. Appliance doors and door latching devices
shall not be required to comply with Section
309.4.
2. Bottom-hinged appliance doors, when in the
open position, shall not be required to comply
with Section 309.3.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
1103.12.5.2 Clear floor space. A clear floor space,
positioned for a parallel or forward approach, shall be
provided at each kitchen appliance.
1103.12.5.3 Dishwasher. A clear floor space, positioned adjacent to the dishwasher door, shall be provided. The dishwasher door in the open position shall
not obstruct the clear floor space for the dishwasher or
an adjacent sink.
1103.12.5.4 Cooktop. Cooktops shall comply with
Section 1103.12.5.4.
1103.12.5.4.1 Approach. A clear floor space, positioned for a parallel or forward approach to the
cooktop, shall be provided.
1103.12.5.4.2 Forward approach. Where the clear
floor space is positioned for a forward approach,
knee and toe clearance complying with Section 306
shall be provided. The underside of the cooktop
shall be insulated or otherwise configured to protect
from burns, abrasions or electrical shock.
1103.12.5.4.3 Parallel approach. Where the clear
floor space is positioned for a parallel approach, the
clear floor space shall be centered on the appliance.
1103.12.5.4.4 Controls. The location of controls
shall not require reaching across burners.
1103.12.5.5 Oven. Ovens shall comply with Section
1103.12.5.5.
1103.12.5.5.1 Clear floor space. A clear floor space
shall be provided. The oven door in the open position shall not obstruct the clear floor space for the
oven.
1103.12.5.5.2 Side-hinged door ovens. Side-hinged
door ovens shall have a countertop positioned adjacent to the latch side of the oven door.
1103.12.5.5.3 Bottom-hinged door ovens. Bottomhinged door ovens shall have a countertop positioned adjacent to one side of the door.
1103.12.5.5.4 Controls. The location of controls
shall not require reaching across burners.
1103.12.5.6 Refrigerator/freezer. Combination refrigerators and freezers shall have at least 50 percent of the
freezer compartment shelves, including the bottom of
the freezer 54 inches (1370 mm) maximum above the
floor when the shelves are installed at the maximum
heights possible in the compartment. A clear floor
space, positioned for a parallel approach to the refrigerator/freezer, shall be provided. The centerline of the
clear floor space shall be offset 24 inches (610 mm)
maximum from the centerline of the appliance.
1103.13 Windows. Operable windows shall comply with
Section 1103.13.
Exceptions:
1. Windows in kitchens shall not be required to comply
with Section 1103.13.
2. Windows in bathrooms shall not be required to comply with Section 1103.13.
RESOURCE A-53
30 min
760
48 min
1220
FIGURE 1104.1.1
CLEAR FLOOR SPACE FOR TYPE B UNITS
DWELLING UNITS AND SLEEPING UNITS
PLUMBING PROVISIONS FROM: ICC A117.1—2017
36 max
915
Exceptions:
1. Receptacle outlets serving a dedicated use.
2. In a kitchen where two or more receptacle outlets
are provided above a length of countertop that is
uninterrupted by a sink or appliance, only one
receptacle outlet shall be required to comply with
this section.
3. In a kitchen where a clear floor space for a parallel
approach cannot be located at a countertop in a
corner between appliances, receptacle outlets over
the countertop shall not be required to comply
with this section provided that the countertop area
does not exceed 9 square feet (0.835 m2) maximum.
4. Floor receptacle outlets.
5. HVAC diffusers.
6. Controls mounted on ceiling fans.
7. Controls or switches mounted on appliances.
8. Plumbing fixture controls.
9. Reset buttons and shut-offs serving appliances,
piping and plumbing fixtures.
10. Where redundant controls other than light
switches are provided for a single element, one
control in each space shall not be required to comply with this section.
11. Within kitchens and bathrooms, lighting controls,
electrical switches and receptacle outlets are permitted to be located over cabinets with countertops
36 inches (915 mm) maximum in height and 251/2
inches (650 mm) maximum in depth.
46 max
1170
Exceptions:
1. Storm and screen doors serving individual dwelling or sleeping units shall not be required to comply with Section 404.2.5.
2. For the maneuvering clearance at swinging doors
for the front approach direction on the push side,
the dimension perpendicular to the door shall be
48 inches (1220 mm) minimum.
3. For the maneuvering clearance at sliding and
folding doors for the front approach direction, the
dimension perpendicular to the door shall be 48
inches (1220 mm) minimum.
4. For doorways without doors, the dimension perpendicular to the doorway for the front direction
shall be 48 inches (1220 mm) minimum.
1104.5.2 User passage doorways. Doorways intended for
user passage shall comply with Section 1104.5.2.
Exception: Doors that are part of a shower door assembly shall not be required to comply with this section.
1104.5.2.1 Clear width. Doorways shall have a clear
opening of 313/4 inches (805 mm) minimum. Clear
opening of swinging doors shall be measured between
the face of the door and stop, with the door open 90
degrees.
1104.5.2.1.1 Double leaf doorways. Where the
operable parts on an inactive leaf of a double leaf
doorway are located more than 48 inches (1220 mm)
or less than 15 inches (380 mm) above the floor, the
active leaf shall provide the clearance required by
Section 1104.5.2.1.
1104.5.2.2 Thresholds. Thresholds shall comply with
Section 303.
Exception: Thresholds at exterior sliding doors
shall be permitted to be 3/4 inch (19 mm) maximum
in height, provided they are beveled with a slope not
steeper than 1:2.
1104.5.2.3 Automatic doors. Automatic doors shall
comply with Section 404.3.
1104.6 Ramps. Ramps shall comply with Section 405.
1104.7 Elevators. Elevators serving the unit shall comply
with Sections 407, 408 or 409.
Exception: In private residence elevators, the inside
dimensions of elevator cars shall provide a clear floor
length of 48 inches (1220 mm) minimum and a clear floor
width of 36 inches (760 mm) minimum.
1104.8 Platform lifts. Platform lifts within the unit shall
comply with Section 410.
Exception: Platform lifts with a single door or with doors
on opposite ends shall provide a clear floor width of 36
inches (915 mm) minimum and a clear floor length of 48
inches (1220 mm) minimum.
1104.9 Operable parts. Lighting controls, electrical switches
and receptacle outlets, environmental controls, electrical panelboards, and user controls for security or intercom systems
shall comply with Sections 309.3 and 1104.1.1.
>10 – 25½
255 – 650
FIGURE 1104.9
REACH OVER A KITCHEN OR BATHROOM CABINET
1104.10 Laundry equipment. Washing machines and
clothes dryers shall comply with Section 1104.10.
1104.10.1 Clear floor space. A clear floor space shall be
provided for each washing machine and clothes dryer. A
parallel approach shall be provided for a top loading
machine. A forward or parallel approach shall be provided
for a front loading machine.
RESOURCE A-55
CL
15¾
400 CL
28 min
710
CL
18 min
455
18 min
455
FIGURE 1104.11.1.1
SWING-UP GRAB BARS FOR WATER CLOSETS
DWELLING UNITS AND SLEEPING UNITS
through other parts of the unit, not more than
one lavatory is required to comply with Section 1104.11.3.1.
2. A lavatory and a water closet in a room containing only a lavatory and water closet, provided the room does not contain the only
lavatory or water closet on the accessible level
of the unit.
1104.11.3.1.1 Lavatory. A clear floor space positioned for a parallel approach shall be provided at a
lavatory. The clear floor space shall be centered on
the lavatory.
Exception: A lavatory complying with Sections
606.3, 606.4 and 1104.1.1 shall be permitted.
Cabinetry shall be permitted under the lavatory
provided the following criteria are met:
1. The cabinetry can be removed without
removal or replacement of the lavatory, and
2. The floor finish extends under the cabinetry, and
3. The walls behind and surrounding the cabinetry are finished.
1104.11.3.1.2.2.1 Clearance width. Clearance around the water closet shall be 48 inches
(1220 mm) minimum in width, measured perpendicular from the side of the clearance that
is 16 inches (405 mm) minimum and 18
inches (455 mm) maximum from the water
closet centerline.
1104.11.3.1.2.2.2 Clearance depth. Clearance around the water closet shall be 56 inches
(1420 mm) minimum in depth, measured perpendicular from the rear wall.
1104.11.3.1.2.2.3 Increased clearance depth
at forward approach. Where a forward
approach is provided, the clearance shall be 66
inches (1675 mm) minimum in depth, measured perpendicular from the rear wall.
CL
Edge of
clearance,
wall, fixture
or other
obstruction
C
L
24 min
610
16-18
405-455
FIGURE 1104.11.3.1.2(A)
CLEARANCE AT WATER CLOSETS IN TYPE B UNITS
WATER CLOSET LOCATION
CL
FIGURE 1104.11.3.1.1
LAVATORY IN TYPE B UNITS - OPTION A BATHROOMS
1104.11.3.1.2 Water closet. The water closet shall
comply with Section 1104.11.3.1.2.
1104.11.3.1.2.1 Location. The centerline of the
water closet shall be 16 inches (405 mm) minimum and 18 inches (455 mm) maximum from
one side of the required clearance.
1104.11.3.1.2.2 Clearance. Clearance around the
water closet shall comply with Sections
1104.11.3.1.2.2.1 through 1104.11.3.1.2.2.3.
Exception: Clearance complying with Sections 1103.11.2.4.2 through 1103.11.2.4.4.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
56 min
1420
Clear floor space
16 – 18
405 – 455
48 min
1220
FIGURE 1104.11.3.1.2(B)
CLEARANCE AT WATER CLOSETS IN TYPE B UNITS
CLEARANCE WIDTH AND DEPTH
RESOURCE A-57
DWELLING UNITS AND SLEEPING UNITS
66 min
1675
CL
16 – 18
405 – 455
48 min
1220
FIGURE 1104.11.3.1.2(C)
CLEARANCE AT WATER CLOSETS IN TYPE B UNITS
INCREASED CLEARANCE DEPTH - FORWARD
APPROACH
1104.11.3.1.2.2.4 Clearance overlap. A vanity or other obstruction 24 inches (610 mm)
maximum in depth, measured perpendicular
from the rear wall, shall be permitted to overlap the required clearance, provided the width
of the remaining clearance at the water closet
is 33 inches (840 mm) minimum.
24 max
610
CL
1104.11.3.1.3 Bathing fixtures. Where provided, a
bathtub shall comply with Section 1104.11.3.1.3.1
or 1104.11.3.1.3.2 and a shower compartment shall
comply with Section 1104.11.3.1.3.3.
1104.11.3.1.3.1 Parallel approach bathtubs. A
clearance 60 inches (1525 mm) minimum in
length and 30 inches (760 mm) minimum in
width shall be provided in front of bathtubs with
a parallel approach. Lavatories complying with
Section 606 shall be permitted in the clearance. A
lavatory complying with Section 1104.11.3.1.1
shall be permitted at one end of the bathtub if a
clearance 48 inches (1220 mm) minimum in
length and 30 inches (760 mm) minimum in
width is provided in front of the bathtub.
1104.11.3.1.3.2 Forward approach bathtubs. A
clearance 60 inches (1525 mm) minimum in
length and 48 inches (1220 mm) minimum in
width shall be provided in front of bathtubs with
a forward approach. A water closet and a lavatory
shall be permitted in the clearance at one end of
the bathtub.
1104.11.3.1.3.3 Shower compartment. If a
shower compartment is the only bathing facility,
the shower compartment shall have dimensions
of 36 inches (915 mm) minimum in width and 36
inches (915 mm) minimum in depth. A clearance
of 48 inches (1220 mm) minimum in length,
measured perpendicular from the control wall,
and 30 inches (760 mm) minimum in depth, measured from the face of the shower compartment,
shall be provided.
Exceptions:
1. A shower compartment with dimensions of 30 inches (760 mm) minimum
in depth and 44 inches (1120 mm)
minimum in width shall be permitted.
2. A shower door assembly shall be permitted where the assembly can be
removed without removal or replacement of the surrounding walls and
floor to which it is affixed.
16 – 18
405 – 455
33 min
840
FIGURE 1104.11.3.1.2(D)
CLEARANCE AT WATER CLOSETS IN TYPE B UNITS
CLEARANCE WITH LAVATORY OVERLAP
RESOURCE A-58
PLUMBING PROVISIONS FROM: ICC A117.1—2017
(B)
Control
end wall
Seat
wall
30 min
760
Control
wall
36 min
915
36 min
915
Back wall
48 min
1220
DWELLING UNITS AND SLEEPING UNITS
30 inches (760 mm) minimum in width shall be
provided in front of bathtubs.
1104.11.3.2.3.2 Shower compartment. A
shower compartment shall comply with Section
1104.11.3.1.3.3.
30 min
760
Head end wall
Controlend wall
Back wall
1104.12 Kitchens. Kitchens shall comply with Section
1104.12.
1104.12.1 Clearance. Clearance complying with Section
1104.12.1 shall be provided.
1104.12.1.1 Minimum clearance. Clearance between
all opposing base cabinets, countertops, appliances, or
walls within kitchen work areas shall be 40 inches
(1015 mm) minimum.
1104.12.1.2 U-shaped kitchens. In kitchens with
counters, appliances or cabinets on three contiguous
sides, clearance between all opposing base cabinets,
countertops, appliances, or walls within kitchen work
areas shall be 60 inches (1525 mm) minimum.
Exception: U-shaped kitchens with an island complying with Section 1104.12.1.1.
48 min
1220
FIGURE 1104.11.3.2.3.1
BATHROOM CLEARANCE IN TYPE B UNITS
OPTION B BATHROOM
DW
Ref
Ref
40 min
1015
40 min
1015
(B)
(A)
FIGURE 1104.12.1.1
MINIMUM CLEARANCE IN TYPE B UNITS
PLUMBING PROVISIONS FROM: ICC A117.1—2017
RESOURCE A-61
DWELLING UNITS AND SLEEPING UNITS
DW
Ref
60 min
1525
40 min
1015
FIGURE 1104.12.1.2(A)
U-SHAPED KITCHEN CLEARANCE IN TYPE B UNITS
40 mn
1015
40 mn
1015
40 min
1015
40 min
1015
FIGURE 1104.12.1.2(B)
U-SHAPED KITCHEN CLEARANCE IN TYPE B UNITS - EXCEPTION
RESOURCE A-62
PLUMBING PROVISIONS FROM: ICC A117.1—2017
DWELLING UNITS AND SLEEPING UNITS
1104.12.2 Clear floor space. Clear floor spaces at appliances shall comply with Sections 1104.12.2 and 1104.1.1.
1104.12.2.1 Sink. A clear floor space, positioned for a
parallel approach to the sink, shall be provided. The
clear floor space shall be centered on the sink bowl.
Exception: A sink with a forward approach complying with Section 1103.12.4.1.
1104.12.2.2 Dishwasher. A clear floor space, positioned for a parallel or forward approach to the dishwasher, shall be provided. The dishwasher door in the
open position shall not obstruct the clear floor space for
the dishwasher.
1104.12.2.3 Cooktop. Cooktops shall comply with
Section 1104.12.2.3.
1104.12.2.3.1 Approach. A clear floor space, positioned for a parallel or forward approach to the
cooktop, shall be provided.
1104.12.2.3.2 Forward approach. Where the clear
floor space is positioned for a forward approach,
knee and toe clearance complying with Section 306
shall be provided. The underside of the cooktop
shall be insulated or otherwise configured to prevent
burns, abrasions, or electrical shock.
1104.12.2.3.3 Parallel approach. Where the clear
floor space is positioned for a parallel approach, the
clear floor space shall be centered on the appliance.
1104.12.2.4 Oven. A clear floor space, positioned for a
parallel or forward approach adjacent to the oven shall
be provided. The oven door in the open position shall
not obstruct the clear floor space for the oven.
1104.12.2.5 Refrigerator/freezer. The refrigerator/
freezer shall comply with Section 1104.12.2.5.
1104.12.2.5.1 Approach. A clear floor space positioned for a parallel or forward approach to the
refrigerator/freezer shall be provided.
1104.12.2.5.2 Forward approach. Where the clear
floor space is positioned for a forward approach, the
centerline of the clear floor space shall be offset 15
inches (380 mm) maximum from the centerline of
the appliance.
1104.12.2.5.3 Parallel approach. Where the clear
floor space is positioned for a parallel approach, the
centerline of the clear floor space shall be offset 24
inches (610 mm) maximum from the centerline of
the appliance.
1104.12.2.6 Trash compactor. A clear floor space,
positioned for a parallel or forward approach to the
trash compactor, shall be provided.
SECTION 1105
TYPE C (VISITABLE) UNITS
1105.1 General. Type C (Visitable) dwelling units shall
comply with Section 1105.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
1105.2 Unit entrance. At least one unit entrance shall be on a
circulation path complying with Section 1105.5 from a public
street or sidewalk, a dwelling unit driveway, or a garage.
1105.3 Connected spaces. A circulation path complying
with Section 1105.5 shall connect the unit entrance complying with Section 1105.2 and with the spaces specified in Section 1105.4.
1105.4 Interior spaces. The entrance level shall include a
toilet room or bathroom complying with Section 1105.6 and
one habitable space with an area 70 square feet (6.5 m2) minimum. Where a food preparation area is provided on the
entrance level, it shall comply with Section 1105.7.
Exception: A toilet room or bathroom shall not be
required on an entrance level with less than 120 square
feet (11.2 m2) of habitable space.
1105.5 Circulation path. Circulation paths shall comply
with Section 1105.5.
1105.5.1 Components. The circulation path shall consist
of one or more of the following elements: walking surfaces with a slope not steeper that 1:20, doors and doorways, ramps, elevators complying with Sections 407
through 409, and wheelchair (platform) lifts complying
with Section 410.
1105.5.2 Walking surfaces. Walking surfaces with slopes
not steeper than 1:20 shall comply with Section 303.
1105.5.2.1 Clear width. The clear width of the circulation path shall be 36 inches (915 mm) minimum.
1105.5.3 Doors and doorways. Doors and doorways shall
comply with Section 1105.5.3
1105.5.3.1 Clear width. Doorways shall have a clear
opening of 313/4 inches (805 mm) minimum. Clear
opening of swinging doors shall be measured between
the face of the door and stop, with the door open 90
degrees.
1105.5.3.2 Thresholds. Thresholds shall comply with
Section 303.
Exception: Thresholds at exterior sliding doors
shall be permitted to be 3/4 inch (19 mm) maximum
in height, provided they are beveled with a slope not
steeper than 1:2.
1105.5.4 Ramps. Ramps shall comply with Section 405.
Exception: Handrails, intermediate landings and edge
protection shall not be required where the sides of ramp
runs have a vertical drop off of 1/2 inch (13 mm) maximum within 10 inches (255 mm) horizontally of the
ramp run.
1105.5.4.1 Clear width. The clear width of the circulation path shall comply with Section 403.5.
1105.6 Toilet room or bathroom. At a minimum, the toilet
room or bathroom required by Section 1105.4 shall include a
lavatory and a water closet. Reinforcement shall be provided
for the future installation of grab bars at water closets. Clearances at the water closet shall comply with Section
1104.11.3.1.2.
1105.7 Food preparation area. At a minimum, the food
preparation area shall include a sink, a cooking appliance,
RESOURCE A-63
DWELLING UNITS AND SLEEPING UNITS
and a refrigerator. Clearances between all opposing base cabinets, counter tops, appliances or walls within the food preparation area shall be 40 inches (1015 mm) minimum.
Exception: Spaces that do not provide a cooktop or conventional range shall be permitted to provide a clearance
of 36 inches (915 mm) minimum.
1105.8 Lighting controls and receptacle outlets. Receptacle outlets and operable parts of lighting controls shall be
located 15 inches (380 mm) minimum and 48 inches (1220
mm) maximum above the floor.
Exception: The following shall not be required to comply
with Section 1105.8.
1. Receptacle outlets serving a dedicated use.
2. Controls mounted on ceiling fans and ceiling
lights.
3. Floor receptacle outlets.
4. Lighting controls and receptacle outlets over
countertops.
SECTION 1106
UNITS WITH COMMUNICATION FEATURES
1106.1 General. Units required to have communication features shall comply with Section 1106.
1106.2 Unit smoke detection. Where provided, unit smoke
detection shall include audible notification complying with
NFPA 72 listed in Section 106.2.4.
1106.3 Building fire alarm system. Where a building fire
alarm system is provided, the system wiring shall be extended
to a point within the unit in the vicinity of the unit smoke
detection system.
1106.4 Visible notification appliances. Visible notification
appliances, where provided within the unit as part of the unit
smoke detection system or the building fire alarm system,
shall comply with Section 1106.4.
1106.4.1 Appliances. Visible notification appliances shall
comply with Section 702.
1106.4.2 Activation. All visible notification appliances
provided within the unit for smoke detection notification
shall be activated upon smoke detection. All visible notification appliances provided within the unit for building fire
RESOURCE A-64
alarm notification shall be activated upon activation of the
building fire alarm in the portion of the building containing the unit.
1106.4.3 Interconnection. The same visible notification
appliances shall be permitted to provide notification of
unit smoke detection and building fire alarm activation.
1106.4.4 Prohibited use. Visible notification appliances
used to indicate unit smoke detection or building fire
alarm activation shall not be used for any other purpose
within the unit.
1106.5 Unit primary entrance. Communication features
shall be provided at the unit primary entrance complying with
Section 1106.5.
1106.5.1 Notification. A hard-wired electric doorbell
shall be provided. A button or switch shall be provided on
the public side of the unit primary entrance. Activation of
the button or switch shall initiate an audible tone within
the unit. Where visible doorbell signals are located in
sleeping areas, controls shall be provided to deactivate the
signal.
1106.5.2 Identification. A means for visually identifying
a visitor without opening the unit entry door shall be provided. Peepholes, where used, shall provide a minimum
180-degree range of view.
1106.6 Site, building or floor entrance. Where a system
permitting voice communication between a visitor and the
occupant of the unit is provided at a location other than the
unit entry door, the system shall comply with Section 1106.6.
1106.6.1 Public or common-use interface. The public or
common-use system interface shall include the capability
of supporting voice and TTY communication with the unit
interface.
1106.6.2 Unit interface. The unit system interface shall
include a telephone jack capable of supporting voice and
TTY communication with the public or common-use system interface.
1106.7 Closed-circuit communication systems. Where a
closed-circuit communication system is provided, the public
or common-use system interface shall comply with Section
1106.6.1, and the unit system interface in units required to
have communication features shall comply with Section
1106.6.2.
PLUMBING PROVISIONS FROM: ICC A117.1—2017
Look no further than ICC-ES PMG® The Leading provider of
product evaluations in plumbing, mechanical and fuel gas,
with excellent customer service and the highest acceptability
by code officials at the price you’re looking for.
We certify:
Faucets
Showerheads
Bathtubs
Sink products
Toilets & Urinals
Ceramic Fixtures
Resins and Linear
Drain products
and many more!
Benefits of having an ICC-ES PMG Listing
· ICC-ES PMG offers a lower cost for
certification than competitors
· ICC-ES will accept test reports from other
entities
· Expedited certification for all client listings
·N
o fee for EPA WaterSense listings and lead
law listings
· ICC-ES PMG does not conduct warehouse
inspections
∙ ICC-ES PMG does not charge for additional
company listings
· No separate file for NSF 61 listings
· A2LA, ANSI, SCC and EMA
www.icc-es-pmg.org
800-423-6587 x7643
19-17625
This File is Uploaded By
4MechEngineer.com
WIKIMEP.com
You can Follow US
Facebook/4MechEngineer
Linked-in/4MechEngineer
Instagram/4MechEngineer
YouTube/4MechEngineer
Google+/4MechEngineer
Twitter/4MechEngineer
LIVE WEB SESSION
· IPC Webinar Series
· IMC Webinar Series
· IPMC Webinar Series
· IFGC Webinar Series
ONLINE Online learning is available 24/7 and features topics such as exam study,
code training, management, and leadership.
HIRE ICC TO TEACH ICC will bring the training to you. We can customize the
training to meet the needs of your organization.
Subject matter examples include:
· IPC® Design, Installation and Inspection Principles
· IMC® Design, Installation and Inspection Principles
· IFGC® Design Installation and Inspection Principles
20-18376
People Helping People Build a Safer World
®
Get FREE access to hundreds of
ICC resources and view the largest
collection of code titles
ICC’s Digital Codes Library (codes.iccsafe.org) conveniently
provides access to the latest code text while on the go, at home
or in the office, in an easy-to-navigate format.
NEVER MISS A CODE UPDATE
Available anywhere 24/7
Use on any mobile or
digital device
View over 800+ ICC titles
19-17447
Learn how to use this powerful tool at codes.iccsafe.org
ICC Membership
An Essential Tool to advance your Building Safety Career!
Training
Networking
Code
Opinions
Product
Savings
Join our
64,000+
members
today!
Put the benefits of ICC Membership to work for you and your career!
Visit www.iccsafe.org/memnow or
call 1-888-ICC-SAFE (422-7233), ext. 33804 to learn more.
19-17662
Download