Uploaded by Dalton Ngwashi

Manual de Wago 750

advertisement
Modular I/O System
DeviceNet
750-306, 750-806
Manual
Technical Description,
Installation and
Configuration
Version 1.0.0
ii • General
Copyright © 2007 by WAGO Kontakttechnik GmbH & Co. KG
All rights reserved.
WAGO Kontakttechnik GmbH & Co. KG
Hansastraße 27
D-32423 Minden
Phone: +49 (0) 571/8 87 – 0
Fax:
+49 (0) 571/8 87 – 1 69
E-Mail: info@wago.com
Web:
http://www.wago.com
Technical Support
Phone: +49 (0) 571/8 87 – 5 55
Fax:
+49 (0) 571/8 87 – 85 55
E-Mail: support@wago.com
Every conceivable measure has been taken to ensure the correctness and completeness of this documentation. However, as errors can never be fully excluded we would appreciate any information or ideas at any time.
E-Mail: documentation@wago.com
We wish to point out that the software and hardware terms as well as the
trademarks of companies used and/or mentioned in the present manual are
generally trademark or patent protected.
WAGO-I/O-SYSTEM 750
DeviceNet
Table of Contents
• iii
TABLE OF CONTENTS
1 Important Notes .......................................................................................... 7
1.1 Legal Principles........................................................................................ 7
1.1.1
Copyright ............................................................................................. 7
1.1.2
Personnel Qualification ....................................................................... 7
1.1.3
Conforming Use of Series 750 ............................................................ 8
1.1.4
Technical Condition of the Devices .................................................... 8
1.2 Standards and Regulations for Operating the 750 Series ......................... 8
1.3 Symbols .................................................................................................... 9
1.4 Safety Information.................................................................................. 10
1.5 Font Conventions ................................................................................... 11
1.6 Number Notation .................................................................................... 11
1.7 Scope ...................................................................................................... 12
1.8 Abbreviation........................................................................................... 12
2 The WAGO-I/O-SYSTEM 750 ................................................................ 13
2.1 System Description................................................................................. 13
2.2 Technical Data........................................................................................ 14
2.3 Manufacturing Number .......................................................................... 20
2.4 Component Update................................................................................. 21
2.5 Storage, Assembly and Transport .......................................................... 21
2.6 Mechanical Setup ................................................................................... 22
2.6.1
Installation Position ........................................................................... 22
2.6.2
Total Expansion................................................................................. 22
2.6.3
Assembly onto Carrier Rail ............................................................... 23
2.6.3.1
Carrier rail properties.................................................................... 23
2.6.3.2
WAGO DIN Rail .......................................................................... 24
2.6.4
Spacing .............................................................................................. 24
2.6.5
Plugging and Removal of the Components ....................................... 25
2.6.6
Assembly Sequence ........................................................................... 26
2.6.7
Internal Bus/Data Contacts................................................................ 27
2.6.8
Power Contacts .................................................................................. 28
2.6.9
Wire connection................................................................................. 29
2.7 Power Supply ......................................................................................... 30
2.7.1
Isolation ............................................................................................. 30
2.7.2
System Supply ................................................................................... 31
2.7.2.1
Connection .................................................................................... 31
2.7.2.2
Alignment ..................................................................................... 32
2.7.3
Field Supply....................................................................................... 34
2.7.3.1
Connection .................................................................................... 34
2.7.3.2
Fusing............................................................................................ 35
2.7.4
Supplementary power supply regulations.......................................... 38
2.7.5
Supply example ................................................................................. 39
2.7.6
Power Supply Unit............................................................................. 40
2.8 Grounding............................................................................................... 41
2.8.1
Grounding the DIN Rail .................................................................... 41
2.8.1.1
Framework Assembly ................................................................... 41
2.8.1.2
Insulated Assembly....................................................................... 41
WAGO-I/O-SYSTEM 750
DeviceNet
iv • Table of Contents
2.8.2
Grounding Function........................................................................... 42
2.8.3
Grounding Protection ........................................................................ 43
2.9 Shielding (Screening) ............................................................................. 44
2.9.1
General............................................................................................... 44
2.9.2
Bus Conductors.................................................................................. 44
2.9.3
Signal Conductors.............................................................................. 44
2.9.4
WAGO Shield (Screen) Connecting System..................................... 45
2.10 Assembly Guidelines/Standards............................................................. 45
3 Fieldbus Coupler/Controller .................................................................... 46
3.1 Fieldbus Coupler 750-306 ...................................................................... 46
3.1.1
Description......................................................................................... 46
3.1.2
Hardware............................................................................................ 47
3.1.2.1
View .............................................................................................. 47
3.1.2.2
Device Supply ............................................................................... 48
3.1.2.3
Fieldbus Connection ..................................................................... 49
3.1.2.4
Display Elements .......................................................................... 50
3.1.2.5
Configuration Interface................................................................. 51
3.1.2.6
Hardware Address (MAC ID)....................................................... 51
3.1.2.7
Setting the Baud Rate.................................................................... 52
3.1.3
Operating System............................................................................... 52
3.1.4
Process Image .................................................................................... 53
3.1.5
Data Exchange ................................................................................... 54
3.1.5.1
Communication Interfaces ............................................................ 55
3.1.5.2
Memory Areas .............................................................................. 55
3.1.5.3
Addressing .................................................................................... 56
3.1.6
Configuration Software ..................................................................... 58
3.1.7
Starting up DeviceNet Fieldbus Nodes ............................................. 58
3.1.7.1
Connecting the PC and Fieldbus Node ......................................... 59
3.1.7.2
Setting the MAC ID and Baud Rate ............................................. 59
3.1.7.3
Configuration with Static Assembly............................................. 60
3.1.8
LED Display ...................................................................................... 64
3.1.8.1
Node status – Blink code from the 'I/O' LED ............................... 65
3.1.8.2
Supply voltage status .................................................................... 72
3.1.9
Technical Data ................................................................................... 73
3.2 Fieldbus Controller 750-806 .................................................................. 74
3.2.1
Description......................................................................................... 74
3.2.2
Hardware............................................................................................ 75
3.2.2.1
View .............................................................................................. 75
3.2.2.2
Device Supply ............................................................................... 76
3.2.2.3
Fieldbus Connection ..................................................................... 77
3.2.2.4
Display Elements .......................................................................... 78
3.2.2.5
Configuration and Programming Interface ................................... 79
3.2.2.6
Operating Mode Switch ................................................................ 79
3.2.2.7
Hardware Address (MAC ID)....................................................... 80
3.2.2.8
Setting the Baud Rate.................................................................... 81
3.2.3
Operating System............................................................................... 82
3.2.3.1
Start-up.......................................................................................... 82
3.2.3.2
PLC Cycle ..................................................................................... 82
3.2.4
Process Image .................................................................................... 84
WAGO-I/O-SYSTEM 750
DeviceNet
Table of Contents
• v
3.2.5
Data Exchange ................................................................................... 85
3.2.5.1
Communication Interfaces ............................................................ 86
3.2.5.2
Memory Areas .............................................................................. 86
3.2.5.3
Addressing .................................................................................... 89
3.2.6
Programming the PFC with WAGO-I/O-PRO 32 ............................. 93
3.2.6.1
WAGO-I/O-PRO 32 Library Elements ........................................ 93
3.2.6.2
IEC 61131-3 Program Transfer .................................................... 94
3.2.7
Special DeviceNet Features of the Controller ................................... 97
3.2.7.1
Connection via the UCMM port ................................................... 97
3.2.7.2
Offline Connection Set ................................................................. 97
3.2.7.3
DeviceNet Shutdown .................................................................... 97
3.2.7.4
Dynamic Assembly ....................................................................... 97
3.2.7.5
Change MAC ID by SW ............................................................... 98
3.2.7.6
Heartbeat ....................................................................................... 98
3.2.7.7
Bit-Strobe...................................................................................... 98
3.2.8
Configuration Software ..................................................................... 99
3.2.9
Starting-up DeviceNet Fieldbus Nodes ............................................. 99
3.2.9.1
Connecting the PC and Fieldbus Node ......................................... 99
3.2.9.2
Setting the MAC ID and Baud Rate ............................................. 99
3.2.9.3
Configuration with Static and Dynamic Assembly .................... 100
3.2.10 LED Display .................................................................................... 111
3.2.10.1 Node status – Blink code from the 'I/O' LED ............................. 112
3.2.10.2 Supply voltage status .................................................................. 119
3.2.11 Technical Data ................................................................................. 120
4 DeviceNet ................................................................................................. 122
4.1 Description ........................................................................................... 122
4.2 Network Architecture ........................................................................... 123
4.2.1
Transmission Media ........................................................................ 123
4.2.1.1
Type of Cable.............................................................................. 123
4.2.1.2
Cable Types ................................................................................ 123
4.2.1.3
Maximum Bus Length ................................................................ 124
4.2.2
Cabling............................................................................................. 124
4.2.3
Network Topology........................................................................... 126
4.2.4
Network Grounding ......................................................................... 127
4.2.5
Interface Modules ............................................................................ 127
4.3 Network Communication ..................................................................... 128
4.3.1
Objects, Classes, Instances and Attributes ...................................... 128
4.4 Module Characteristics......................................................................... 129
4.4.1
Communication Model .................................................................... 129
4.4.1.1
Message Groups.......................................................................... 129
4.4.1.2
Message Types............................................................................ 129
4.4.2
I/O Messaging Connections............................................................. 130
4.5 Process data and Diagnostic Status ...................................................... 130
4.5.1
Process Image .................................................................................. 130
4.5.1.1
Assembly Instances..................................................................... 131
4.6 Configuration / Parametering with the Object Model .......................... 133
4.6.1
EDS Files ......................................................................................... 133
4.6.2
Object Model ................................................................................... 134
4.6.2.1
Object Model for Coupler 750-306 and Controller 750-806...... 135
WAGO-I/O-SYSTEM 750
DeviceNet
vi • Table of Contents
4.6.2.2
Supplement to the Object Model for Controller 750-806........... 151
5 I/O Modules ............................................................................................. 158
5.1 Overview .............................................................................................. 158
5.1.1
Digital Input Modules...................................................................... 158
5.1.2
Digital Output Modules ................................................................... 160
5.1.3
Analog Intput Modules .................................................................... 161
5.1.4
Analog Output Modules .................................................................. 162
5.1.5
Special Modules .............................................................................. 163
5.1.6
System Modules............................................................................... 164
5.2 Process Data Architecture for DeviceNet ............................................ 165
5.2.1
Digital Input Modules...................................................................... 165
5.2.2
Digital Output Modules ................................................................... 167
5.2.3
Analog Input Modules ..................................................................... 171
5.2.4
Analog Output Modules .................................................................. 173
5.2.5
Specialty Modules ........................................................................... 174
5.2.6
System Modules............................................................................... 186
6 Use in Hazardous Environments ........................................................... 187
6.1 Foreword .............................................................................................. 187
6.2 Protective measures .............................................................................. 187
6.3 Classification meeting CENELEC and IEC ......................................... 187
6.3.1
Divisions .......................................................................................... 187
6.3.2
Explosion protection group ............................................................. 188
6.3.3
Unit categories ................................................................................. 189
6.3.4
Temperature classes......................................................................... 189
6.3.5
Types of ignition protection ............................................................ 190
6.4 Classifications meeting the NEC 500................................................... 191
6.4.1
Divisions .......................................................................................... 191
6.4.2
Explosion protection groups ............................................................ 191
6.4.3
Temperature classes......................................................................... 192
6.5 Identification ........................................................................................ 193
6.5.1
For Europe ....................................................................................... 193
6.5.2
For America ..................................................................................... 194
6.6 Installation regulations ......................................................................... 195
7 Glossary.................................................................................................... 197
8 Literature List ......................................................................................... 198
9 Index ......................................................................................................... 199
WAGO-I/O-SYSTEM 750
DeviceNet
Important Notes
Legal Principles
• 7
1 Important Notes
This section provides only a summary of the most important safety requirements and notes which will be mentioned in the individual sections. To protect
your health and prevent damage to the devices, it is essential to read and carefully follow the safety guidelines.
1.1 Legal Principles
1.1.1 Copyright
This manual including all figures and illustrations contained therein is subject
to copyright. Any use of this manual which infringes the copyright provisions
stipulated herein, is not permitted. Reproduction, translation and electronic
and phototechnical archiving and amendments require the written consent of
WAGO Kontakttechnik GmbH & Co. KG, Minden. Non-observance will entail the right of claims for damages.
WAGO Kontakttechnik GmbH & Co. KG reserves the right of changes serving technical progress.
All rights developing from the issue of a patent or the legal protection of utility patents are reserved to WAGO Kontakttechnik GmbH & Co. KG. Thirdparty products are always indicated without any notes concerning patent
rights. Thus, the existence of such rights must not be excluded.
1.1.2 Personnel Qualification
The use of the product described in this manual requires special qualifications,
as shown in the following table:
Activity
Electrical specialist
Assembly
X
Commissioning
X
Instructed personnel*)
X
X
Programming
*)
Specialists**) having
qualifications in PLC
programming
X
Maintenance
X
Troubleshooting
X
Disassembly
X
X
X
Instructed persons have been trained by qualified personnel or electrical specialists.
**) A specialist is someone who, through technical training, knowledge and experience,
demonstrates the ability to meet the relevant specifications and identify potential dangers in
the mentioned field of activity.
All personnel must be familiar with the applicable standards.
WAGO Kontakttechnik GmbH & Co. KG declines any liability resulting from
WAGO-I/O-SYSTEM 750
DeviceNet
8 •
Important Notes
Standards and Regulations for Operating the 750 Series
improper action and damage to WAGO products and third party products due to
non-observance of the information contained in this manual.
1.1.3 Conforming Use of Series 750
The couplers and controllers of the modular I/O System 750 receive digital
and analog signals from the I/O modules and sensors and transmit them to the
actuators or higher level control systems. Using the WAGO controllers, the
signals can also be (pre-)processed.
The device is designed for IP20 protection class. It is protected against finger
touch and solid impurities up to 12.5mm diameter, but not against water penetration. Unless otherwise specified, the device must not be operated in wet and
dusty environments.
1.1.4 Technical Condition of the Devices
For each individual application, the components are supplied from the factory
with a dedicated hardware and software configuration. Changes in hardware,
software and firmware are only admitted within the framework of the possibilities documented in the manuals. All changes to the hardware or software
and the non-conforming use of the components entail the exclusion of liability
on the part of WAGO Kontakttechnik GmbH & Co. KG.
Please direct any requirements pertaining to a modified and/or new hardware
or software configuration directly to WAGO Kontakttechnik GmbH & Co.
KG.
1.2 Standards and Regulations for Operating the 750 Series
Please observe the standards and regulations that are relevant to your installation:
• The data and power lines must be connected and installed in compliance
with the standards to avoid failures on your installation and eliminate any
danger to personnel.
• For installation, startup, maintenance and repair, please observe the accident prevention regulations of your machine (e.g. BGV A 3, "Electrical Installations and Equipment").
• Emergency stop functions and equipment must not be made ineffective.
See relevant standards (e.g. DIN EN 418).
• Your installation must be equipped in accordance to the EMC guidelines so
that electromagnetic interferences can be eliminated.
• Operating 750 Series components in home applications without further
measures is only permitted if they meet the emission limits (emissions of
interference) according to EN 61000-6-3. You will find the relevant information in the section on "WAGO-I/O-SYSTEM 750" å "System Description" å "Technical Data".
WAGO-I/O-SYSTEM 750
DeviceNet
Important Notes
Symbols
• 9
• Please observe the safety measures against electrostatic discharge according to DIN EN 61340-5-1/-3. When handling the modules, ensure that the
environment (persons, workplace and packing) is well grounded.
• The relevant valid and applicable standards and guidelines concerning the
installation of switch cabinets are to be observed.
1.3 Symbols
Danger
Always observe this information to protect persons from injury.
Warning
Always observe this information to prevent damage to the device.
Attention
Marginal conditions that must always be observed to ensure smooth and efficient operation.
ESD (Electrostatic Discharge)
Warning of damage to the components through electrostatic discharge. Observe the precautionary measure for handling components at risk of electrostatic discharge.
Note
Make important notes that are to be complied with so that a trouble-free and
efficient device operation can be guaranteed.
Additional Information
References to additional literature, manuals, data sheets and INTERNET
pages.
WAGO-I/O-SYSTEM 750
DeviceNet
10 •
Important Notes
Safety Information
1.4 Safety Information
When connecting the device to your installation and during operation, the following safety notes must be observed:
Danger
The WAGO-I/O-SYSTEM 750 and its components are an open system. It
must only be assembled in housings, cabinets or in electrical operation
rooms. Access is only permitted via a key or tool to authorized qualified personnel.
Danger
All power sources to the device must always be switched off before carrying
out any installation, repair or maintenance work.
Warning
Replace defective or damaged device/module (e.g. in the event of deformed
contacts), as the functionality of fieldbus station in question can no longer be
ensured on a long-term basis.
Warning
The components are not resistant against materials having seeping and insulating properties. Belonging to this group of materials is: e.g. aerosols, silicones, triglycerides (found in some hand creams). If it cannot be ruled out
that these materials appear in the component environment, then the components must be installed in an enclosure that is resistant against the above mentioned materials. Clean tools and materials are generally required to operate
the device/module.
Warning
Soiled contacts must be cleaned using oil-free compressed air or with ethyl
alcohol and leather cloths.
Warning
Do not use contact sprays, which could possibly impair the functioning of the
contact area.
Warning
Avoid reverse polarity of data and power lines, as this may damage the devices.
ESD (Electrostatic Discharge)
The devices are equipped with electronic components that may be destroyed
by electrostatic discharge when touched.
WAGO-I/O-SYSTEM 750
DeviceNet
Important Notes
Font Conventions
• 11
1.5 Font Conventions
italic
Names of paths and files are marked in italic.
e.g.: C:\Programs\WAGO-IO-CHECK
italic
Menu items are marked in bold italic.
e.g.: Save
\
A backslash between two names characterizes the selection of a menu point from a menu.
e.g.: File \ New
END
Press buttons are marked as bold with small capitals
e.g.: ENTER
<>
Keys are marked bold within angle brackets
e.g.: <F5>
Courier
The print font for program codes is Courier.
e.g.: END_VAR
1.6 Number Notation
Number code
Example
Note
Decimal
100
Normal notation
Hexadecimal
0x64
C notation
Binary
'100'
'0110.0100'
Within ',
Nibble separated with dots
WAGO-I/O-SYSTEM 750
DeviceNet
12 •
Important Notes
Scope
1.7 Scope
Item no.
Description
750-306
fieldbus Coupler DeviceNet; 125 – 500 kBaud
750-806
prog. Fieldbus Controller DeviceNet; 125 – 500 kBaud
1.8 Abbreviation
AI
Analog Input
AO
Analog Output
BC
BusCoupler
CAL
CAN Application Layer
CAN
Controller Area Network
DI
Digital Input
DIP
Dual In-line Package
DO
Digital Output
EDS
Electronic Data Sheets
I/O
Input/Output
ID
Identifier, Identification
Idx
Index
ISO/ OSI
International Organization for Standardization / Open Systems Interconnection (model)
M
Master
MAC ID
Media Access Control Identifier (nodeaddress)
MS
Module Status
NMT
Network Management
NS
Network Status
PFC
Programmable fieldbus Controller
RO
Read Only
RW
Read/Write
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
System Description
• 13
2 The WAGO-I/O-SYSTEM 750
2.1 System Description
The WAGO-I/O-SYSTEM 750 is a modular, fieldbus independent I/O system.
It is comprised of a fieldbus coupler/controller (1) and connected fieldbus
modules (2) for any type of signal. Together, these make up the fieldbus node.
The end module (3) completes the node.
Fig. 2-1: Fieldbus node
g0xxx00x
Couplers/controllers for fieldbus systems such as PROFIBUS, INTERBUS,
ETHERNET TCP/IP, CAN (CANopen, DeviceNet, CAL), MODBUS, LON
and others are available.
The coupler/controller contains the fieldbus interface, electronics and a power
supply terminal. The fieldbus interface forms the physical interface to the relevant fieldbus. The electronics process the data of the bus modules and make it
available for the fieldbus communication. The 24 V system supply and the
24 V field supply are fed in via the integrated power supply terminal.
The fieldbus coupler communicates via the relevant fieldbus. The programmable fieldbus controller (PFC) enables the implementation of additional PLC
functions. Programming is done with the WAGO-I/O-PRO 32 in accordance
with IEC 61131-3.
Bus modules for diverse digital and analog I/O functions as well as special
functions can be connected to the coupler/controller. The communication between the coupler/controller and the bus modules is carried out via an internal
bus.
The WAGO-I/O-SYSTEM 750 has a clear port level with LEDs for status indication, insertable mini WSB markers and pullout group marker carriers. The
3-wire technology supplemented by a ground wire connection allows for direct sensor/actuator wiring.
WAGO-I/O-SYSTEM 750
DeviceNet
14 •
The WAGO-I/O-SYSTEM 750
Technical Data
2.2 Technical Data
Mechanic
Material
Polycarbonate, Polyamide 6.6
Dimensions W x H* x L
* from upper edge of DIN 35 rail
- Coupler/Controller (Standard)
- Coupler/Controller (ECO)
- Coupler/Controller (FireWire)
- I/O module, single
- I/O module, double
- I/O module, fourfold
- 51 mm x 65 mm x 100 mm
- 50 mm x 65 mm x 100 mm
- 62 mm x 65 mm x 100 mm
- 12 mm x 64 mm x 100 mm
- 24 mm x 64 mm x 100 mm
- 48 mm x 64 mm x 100 mm
Installation
on DIN 35 with interlock
modular by
double featherkey-dovetail
Mounting position
any position
Marking
marking label type 247 and 248
paper marking label 8 x 47 mm
Connection
Connection type
CAGE CLAMP®
Wire range
0.08 mm² ... 2.5 mm², AWG 28-14
Stripped length
8 – 9 mm,
9 – 10 mm for components with pluggable wiring
(753-xxx)
Contacts
Power jumpers contacts
blade/spring contact
self-cleaning
Current via power contactsmax
10 A
Voltage drop at Imax
< 1 V/64 modules
Data contacts
slide contact, hard gold plated
1.5 µm, self-cleaning
Climatic environmental conditions
Operating temperature
0 °C ... 55 °C,
-20 °C … +60 °C for components with extended
temperature range (750-xxx/025-xxx)
Storage temperature
-20 °C ... +85 °C
Relative humidity
5 % to 95 % without condensation
Resistance to harmful substances
acc. to IEC 60068-2-42 and IEC 60068-2-43
Special conditions
Ensure that additional measures for components are
taken, which are used in an environment involving:
– dust, caustic vapors or gasses
– ionization radiation.
Maximum pollutant concentration at SO2 ≤ 25 ppm
relative humidity < 75%
H2S ≤ 10 ppm
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Technical Data
• 15
Safe electrical isolation
Air and creepage distance
acc. to IEC 60664-1
Degree of pollution
acc. To IEC 61131-2
2
Degree of protection
Degree of protection
IP 20
Electromagnetic compatibility
Immunity to interference for industrial areas acc. to EN 61000-6-2 (2001)
Test specification
Test values
Strength
class
Evaluation
criteria
EN 61000-4-2 ESD
4 kV/8 kV (contact/air)
2/3
B
EN 61000-4-3
electromagnetic fields
10 V/m 80 MHz ... 1 GHz
3
A
EN 61000-4-4 burst
1 kV/2 kV (data/supply)
2/3
B
EN 61000-4-5 surge
Data:
EN 61000-4-6
RF disturbances
-/- (line/line)
B
1 kV (line/earth)
2
DC supply:
0.5 kV (line/line)
1
0.5 kV (line/earth)
1
AC supply:
1 kV (line/line)
2
2 kV (line/earth)
3
10 V/m 80 % AM (0.15 ... 80
MHz)
3
B
B
A
Emission of interference for industrial areas acc. to EN 61000-6-4 (2001)
Test specification
Limit values/[QP]*) Frequency range
Distance
EN 55011 (AC supply,
conducted)
79 dB (µV)
150 kHz ... 500 kHz
73 dB (µV)
500 kHz ... 30 MHz
EN 55011 (radiated)
40 dB (µV/m)
30 MHz ... 230 MHz
10 m
47 dB (µV/m)
230 MHz ... 1 GHz
10 m
Emission of interference for residential areas acc. to EN 61000-6-3 (2001)
Test specification
Limit values/[QP]*) Frequency range
EN 55022 (AC supply,
conducted)
66 ... 56 dB (µV)
150 kHz ... 500 kHz
56 dB (µV)
500 kHz ... 5 MHz
60 dB (µV)
5 MHz ... 30 MHz
EN 55022 (DC supply/data,
conducted)
40 ... 30 dB (µA)
150 kHz ... 500 kHz
30 dB (µA)
500 kHz ... 30 MHz
EN 55022 (radiated)
30 dB (µV/m)
30 MHz ... 230 MHz
10 m
37 dB (µV/m)
230 MHz ... 1 GHz
10 m
WAGO-I/O-SYSTEM 750
DeviceNet
Distance
16 •
The WAGO-I/O-SYSTEM 750
Technical Data
Mechanical strength acc. to IEC 61131-2
Test specification
IEC 60068-2-6 vibration
Frequency range
5 Hz ≤ f < 9 Hz
9 Hz ≤ f < 150 Hz
Limit value
1.75 mm amplitude (permanent)
3.5 mm amplitude (short term)
0.5 g (permanent)
1 g (short term)
Note on vibration test:
a) Frequency change: max. 1 octave/minute
b) Vibration direction: 3 axes
IEC 60068-2-27 shock
15 g
Note on shock test:
a) Type of shock: half sine
b) Shock duration: 11 ms
c) Shock direction: 3x in positive and 3x in negative direction for each of the three mutually perpendicular axes of the
test specimen
IEC 60068-2-32 free fall
1m
(module in original packing)
*) QP: Quasi Peak
Note:
If the technical data of components differ from the values described here, the
technical data shown in the manuals of the respective components shall be
valid.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Technical Data
• 17
For Products of the WAGO-I/O-SYSTEM 750 with ship specific approvals,
supplementary guidelines are valid:
Electromagnetic compatibility
Immunity to interference acc. to Germanischer Lloyd (2003)
Test specification
Test values
Strength
class
Evaluation
criteria
IEC 61000-4-2 ESD
6 kV/8 kV (contact/air)
3/3
B
IEC 61000-4-3
electromagnetic fields
10 V/m 80 MHz ... 2 GHz
3
A
IEC 61000-4-4 burst
1 kV/2 kV (data/supply)
2/3
A
IEC 61000-4-5 surge
AC/DC
Supply:
0.5 kV (line/line)
1
A
1 kV (line/earth)
2
10 V/m 80 % AM (0.15 ... 80
MHz)
3
A
Type test AF disturbances 3 V, 2 W
(harmonic waves)
-
A
Type test high voltage
-
-
IEC 61000-4-6
RF disturances
755 V DC
1500 V AC
Emission of interference acc. to Germanischer Lloyd (2003)
Test specification
Limit values
Type test
96 ... 50 dB (µV)
(EMC1, conducted)
allows for ship bridge control 60 ... 50 dB (µV)
applications
50 dB (µV)
Type test
80 ... 52 dB (µV/m)
(EMC1, radiated)
52 ... 34 dB (µV/m)
allows for ship bridge control
applications
54 dB (µV/m)
außer für: 24 dB (µV/m)
Frequency range
Distance
10 kHz ... 150 kHz
150 kHz ... 350 kHz
350 kHz ... 30 MHz
150 kHz ... 300 kHz
3m
300 kHz ... 30 MHz
3m
30 MHz ... 2 GHz
3m
156 MHz ... 165 MHz
3m
Mechanical strength acc. to Germanischer Lloyd (2003)
Test specification
IEC 60068-2-6 vibration
(category A – D)
Frequency range
2 Hz ≤ f < 25 Hz
25 Hz ≤ f < 100 Hz
Limit value
± 1.6 mm amplitude (permanent)
4 g (permanent)
Note on vibration test:
a) Frequency change: max. 1 octave/minute
b) Vibration direction: 3 axes
WAGO-I/O-SYSTEM 750
DeviceNet
18 •
The WAGO-I/O-SYSTEM 750
Technical Data
Range of
application
Required specification
emission of interference
Required specification
immunity to interference
Industrial areas
EN 61000-6-4 (2001)
EN 61000-6-2 (2001)
Residential areas
EN 61000-6-3 (2001)*)
EN 61000-6-1 (2001)
*) The system meets the requirements on emission of interference in residential areas with
the fieldbus coupler/controller for:
ETHERNET 750-342/-841/-842/-860
LonWorks
750-319/-819
CANopen
750-337/-837
DeviceNet
750-306/-806
MODBUS
750-312/-314/ -315/ -316
750-812/-814/ -815/ -816
With a special permit, the system can also be implemented with other fieldbus couplers/controllers in residential areas (housing, commercial and business areas, small-scale
enterprises). The special permit can be obtained from an authority or inspection office. In
Germany, the Federal Office for Post and Telecommunications and its branch offices
issues the permit.
It is possible to use other field bus couplers/controllers under certain boundary conditions. Please contact WAGO Kontakttechnik GmbH & Co. KG.
Maximum power dissipation of the components
Bus modules
0.8 W / bus terminal (total power dissipation, system/field)
Fieldbus coupler/controller
2.0 W / coupler/controller
Warning
The power dissipation of all installed components must not exceed the maximum conductible power of the housing (cabinet).
When dimensioning the housing, care is to be taken that even under high external temperatures, the temperature inside the housing does not exceed the
permissible ambient temperature of 55 °C.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Technical Data
• 19
Dimensions
01 02
A
A
A
C
C
B
B
A
C
B
D
D
A
C
C
B
D
B
D
D
24V 0V
100
+ +
-
35
-
12
24
64
65
51
Side view
Fig. 2-2: Dimensions
Dimensions in mm
g01xx05e
Note:
The illustration shows a standard coupler. For detailed dimensions, please
refer to the technical data of the respective coupler/controller.
WAGO-I/O-SYSTEM 750
DeviceNet
20 •
The WAGO-I/O-SYSTEM 750
Manufacturing Number
2.3 Manufacturing Number
The manufacturing number indicates the delivery status directly after production.
This number is part of the lateral marking on the component.
In addition, starting from calender week 43/2000 the manufacturing number is
also printed on the cover of the configuration and programming interface of
the fieldbus coupler or controller.
PROFIBUS
72072
GL
NO
DS
SW
HW
FWL
0 1 0 3 0 0 0 2 0 3 - B 0 60 0 60 0 60
24V DC
AWG 28-14
55°C max ambient
LISTED 22ZA AND 22XM
750-333
WAGO - I/O - SYSTEM
ITEM-NO.:750-333
PROFIBUS DP 12 MBd /DPV1
Hansastr. 27
D-32423 Minden
-
+
Power Supply
Field
II 3 GD
DEMKO 02 ATEX132273 X
EEx nA II T4
24 V
0V
Power Supply
Electronic
PATENTS PENDING
Manufacturing Number
0 1 0 3 0 0 0 2 0 3 - B 0 6 0 6 0 6
01030002
03-B
060606
72072
Calendar
week
Year
Software
version
Hardware Firmware Loader Internal
version
version
Number
Fig. 2-3: Example: Manufacturing Number of a PROFIBUS fieldbus coupler 750-333
g01xx15e
The manufacturing number consists of the production week and year, the software version (if available), the hardware version of the component, the firmware loader (if available) and further internal information for
WAGO Kontakttechnik GmbH.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Component Update
• 21
2.4 Component Update
For the case of an Update of one component, the lateral marking on each component contains a prepared matrix.
This matrix makes columns available for altogether three updates to the entry
of the current update data, like production order number (NO; starting from
calendar week 13/2004), update date (DS), software version (SW), hardware
version (HW) and the firmware loader version (FWL, if available).
Update Matrix
Current Version data for:
Production Order
Number
NO
Datestamp
DS
Software index
SW
Hardware index
HW
1. Update 2. Update 3. Update
Firmware loader index FWL
ä Only starting from
calendar week 13/2004
ä Only for coupler/ controller
If the update of a component took place, the current version data are registered
into the columns of the matrix.
Additionally with the update of a fieldbus coupler or controller also the cover
of the configuration and programming interface of the coupler or controller is
printed on with the current manufacturing and production order number.
The original manufacturing data on the housing of the component remain
thereby.
2.5 Storage, Assembly and Transport
Wherever possible, the components are to be stored in their original packaging. Likewise, the original packaging provides optimal protection during
transport.
When assembling or repacking the components, the contacts must not be
soiled or damaged. The components must be stored and transported in appropriate containers/packaging. Thereby, the ESD information is to be regarded.
Statically shielded transport bags with metal coatings are to be used for the
transport of open components for which soiling with amine, amide and silicone has been ruled out, e.g. 3M 1900E.
WAGO-I/O-SYSTEM 750
DeviceNet
22 •
The WAGO-I/O-SYSTEM 750
Mechanical Setup
2.6 Mechanical Setup
2.6.1 Installation Position
Along with horizontal and vertical installation, all other installation positions
are allowed.
Attention
In the case of vertical assembly, an end stop has to be mounted as an additional safeguard against slipping.
WAGO item 249-116
End stop for DIN 35 rail, 6 mm wide
WAGO item 249-117
End stop for DIN 35 rail, 10 mm wide
2.6.2 Total Expansion
The length of the module assembly (including one end module of 12mm
width) that can be connected to the coupler/controller is 780mm. When assembled, the I/O modules have a maximum length of 768mm.
Examples:
• 64 I/O modules of 12mm width can be connected to one coupler/controller.
• 32 I/O modules of 24mm width can be connected to one coupler/controller.
Exception:
The number of connected I/O modules also depends on which type of coupler/controller is used. For example, the maximum number of I/O modules
that can be connected to a Profibus coupler/controller is 63 without end module.The maximum total expansion of a node is calculated as follows:
Warning
The maximum total length of a node without coupler/controller must not exceed 780mm. Furthermore, restrictions made on certain types of couplers/controllers must be observed (e.g. for Profibus).
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Mechanical Setup
• 23
2.6.3 Assembly onto Carrier Rail
2.6.3.1 Carrier rail properties
All system components can be snapped directly onto a carrier rail in accordance with the European standard EN 50022 (DIN 35).
Warning
WAGO supplies standardized carrier rails that are optimal for use with the
I/O system. If other carrier rails are used, then a technical inspection and approval of the rail by WAGO Kontakttechnik GmbH should take place.
Carrier rails have different mechanical and electrical properties. For the optimal system setup on a carrier rail, certain guidelines must be observed:
• The material must be non-corrosive.
• Most components have a contact to the carrier rail to ground electromagnetic disturbances. In order to avoid corrosion, this tin-plated carrier
rail contact must not form a galvanic cell with the material of the carrier
rail which generates a differential voltage above 0.5 V (saline solution of
0.3% at 20°C) .
• The carrier rail must optimally support the EMC measures integrated into
the system and the shielding of the bus module connections.
• A sufficiently stable carrier rail should be selected and, if necessary, several mounting points (every 20 cm) should be used in order to prevent
bending and twisting (torsion).
• The geometry of the carrier rail must not be altered in order to secure the
safe hold of the components. In particular, when shortening or mounting
the carrier rail, it must not be crushed or bent.
• The base of the I/O components extends into the profile of the carrier rail.
For carrier rails with a height of 7.5 mm, mounting points are to be riveted
under the node in the carrier rail (slotted head captive screws or blind rivets).
WAGO-I/O-SYSTEM 750
DeviceNet
24 •
The WAGO-I/O-SYSTEM 750
Mechanical Setup
2.6.3.2 WAGO DIN Rail
WAGO carrier rails meet the electrical and mechanical requirements.
Item Number
Description
210-113 /-112
35 x 7.5; 1 mm; steel yellow chromated; slotted/unslotted
210-114 /-197
35 x 15; 1.5 mm; steel yellow chromated; slotted/unslotted
210-118
35 x 15; 2.3 mm; steel yellow chromated; unslotted
210-198
35 x 15; 2.3 mm; copper; unslotted
210-196
35 x 7.5; 1 mm; aluminum; unslotted
2.6.4 Spacing
The spacing between adjacent components, cable conduits, casing and frame
sides must be maintained for the complete field bus node.
Fig. 2-4: Spacing
g01xx13x
The spacing creates room for heat transfer, installation or wiring. The spacing
to cable conduits also prevents conducted electromagnetic interferences from
influencing the operation.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Mechanical Setup
• 25
2.6.5 Plugging and Removal of the Components
Warning
Before work is done on the components, the voltage supply must be turned
off.
In order to safeguard the coupler/controller from jamming, it should be fixed
onto the carrier rail with the locking disc To do so, push on the upper groove
of the locking disc using a screwdriver.
To pull out the fieldbus coupler/controller, release the locking disc by pressing
on the bottom groove with a screwdriver and then pulling the orange colored
unlocking lug.
Fig. 2-5: Coupler/Controller and unlocking lug
g01xx12e
It is also possible to release an individual I/O module from the unit by pulling
an unlocking lug.
Fig. 2-6: removing bus terminal
p0xxx01x
Danger
Ensure that an interruption of the PE will not result in a condition which
could endanger a person or equipment!
For planning the ring feeding of the ground wire, please see chapter 2.6.3.
WAGO-I/O-SYSTEM 750
DeviceNet
26 •
The WAGO-I/O-SYSTEM 750
Mechanical Setup
2.6.6 Assembly Sequence
All system components can be snapped directly on a carrier rail in accordance
with the European standard EN 50022 (DIN 35).
The reliable positioning and connection is made using a tongue and groove
system. Due to the automatic locking, the individual components are securely
seated on the rail after installing.
Starting with the coupler/controller, the bus modules are assembled adjacent
to each other according to the project planning. Errors in the planning of the
node in terms of the potential groups (connection via the power contacts) are
recognized, as the bus modules with power contacts (male contacts) cannot be
linked to bus modules with fewer power contacts.
Attention
Always link the bus modules with the coupler/controller, and always plug
from above.
Warning
Never plug bus modules from the direction of the end terminal. A ground
wire power contact, which is inserted into a terminal without contacts, e.g. a
4-channel digital input module, has a decreased air and creepage distance to
the neighboring contact in the example DI4.
Always terminate the fieldbus node with an end module (750-600).
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Mechanical Setup
• 27
2.6.7 Internal Bus/Data Contacts
Communication between the coupler/controller and the bus modules as well as
the system supply of the bus modules is carried out via the internal bus. It is
comprised of 6 data contacts, which are available as self-cleaning gold spring
contacts.
Fig. 2-7: Data contacts
p0xxx07x
Warning
Do not touch the gold spring contacts on the I/O modules in order to avoid
soiling or scratching!
ESD (Electrostatic Discharge)
The modules are equipped with electronic components that may be destroyed
by electrostatic discharge. When handling the modules, ensure that the environment (persons, workplace and packing) is well grounded. Avoid touching
conductive components, e.g. gold contacts.
WAGO-I/O-SYSTEM 750
DeviceNet
28 •
The WAGO-I/O-SYSTEM 750
Mechanical Setup
2.6.8 Power Contacts
Self-cleaning power contacts , are situated on the side of the components
which further conduct the supply voltage for the field side. These contacts
come as touchproof spring contacts on the right side of the coupler/controller
and the bus module. As fitting counterparts the module has male contacts on
the left side.
Danger
The power contacts are sharp-edged. Handle the module carefully to prevent
injury.
Attention
Please take into consideration that some bus modules have no or only a few
power jumper contacts. The design of some modules does not allow them to
be physically assembled in rows, as the grooves for the male contacts are
closed at the top.
Fig. 2-8: Example for the arrangement of power contacts
g0xxx05e
Recommendation
With the WAGO ProServe® Software smartDESIGNER, the assembly of a
fieldbus node can be configured. The configuration can be tested via the integrated accuracy check.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Mechanical Setup
• 29
2.6.9 Wire connection
All components have CAGE CLAMP® connections.
The WAGO CAGE CLAMP® connection is appropriate for solid, stranded
and fine–stranded conductors. Each clamping unit accommodates one conductor.
Fig. 2-9: CAGE CLAMP® Connection
g0xxx08x
The operating tool is inserted into the opening above the connection. This
opens the CAGE CLAMP®. Subsequently the conductor can be inserted into
the opening. After removing the operating tool, the conductor is safely
clamped.
More than one conductor per connection is not permissible. If several conductors have to be made at one connection point, then they should be made away
from the connection point using WAGO Terminal Blocks. The terminal blocks
may be jumpered together and a single wire brought back to the I/O module
connection point.
Attention
If it is unavoidable to jointly connect 2 conductors, then a ferrule must be
used to join the wires together.
Ferrule:
Length
8 mm
Nominal cross sectionmax.
1 mm2 for 2 conductors with 0.5 mm2
each
WAGO Product
216-103
or products with comparable properties
WAGO-I/O-SYSTEM 750
DeviceNet
30 •
The WAGO-I/O-SYSTEM 750
Power Supply
2.7 Power Supply
2.7.1 Isolation
Within the fieldbus node, there are three electrically isolated potentials.
• Operational voltage for the fieldbus interface.
• Electronics of the couplers/controllers and the bus modules (internal bus).
• All bus modules have an electrical isolation between the electronics (internal bus, logic) and the field electronics. Some digital and analog input
modules have each channel electrically isolated, please see catalog.
Fig. 2-10: Isolation
g0xxx01e
Attention
The ground wire connection must be present in each group. In order that all
protective conductor functions are maintained under all circumstances, it is
recommended that a ground wire be connected at the beginning and end of a
potential group. (ring format, please see chapter "2.8.3"). Thus, if a bus module comes loose from a composite during servicing, then the protective conductor connection is still guaranteed for all connected field devices.
When using a joint power supply unit for the 24 V system supply and the
24 V field supply, the electrical isolation between the internal bus and the
field level is eliminated for the potential group.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Power Supply
• 31
2.7.2 System Supply
2.7.2.1 Connection
The WAGO-I/O-SYSTEM 750 requires a 24 V direct current system supply
(-15% or +20 %). The power supply is provided via the coupler/controller and,
if necessary, in addition via the internal system supply modules (750-613).
The voltage supply is reverse voltage protected.
Attention
The use of an incorrect supply voltage or frequency can cause severe damage
to the component.
Fig. 2-11: System Supply
g0xxx02e
The direct current supplies all internal system components, e.g. coupler/controller electronics, fieldbus interface and bus modules via the internal
bus (5 V system voltage). The 5 V system voltage is electrically connected to
the 24 V system supply.
Fig. 2-12: System Voltage
WAGO-I/O-SYSTEM 750
DeviceNet
g0xxx06e
32 •
The WAGO-I/O-SYSTEM 750
Power Supply
Attention
Resetting the system by switching on and off the system supply, must take
place simultaneously for all supply modules (coupler/controller and
750-613).
2.7.2.2 Alignment
Recommendation
A stable network supply cannot be taken for granted always and everywhere.
Therefore, regulated power supply units should be used in order to guarantee
the quality of the supply voltage.
The supply capacity of the coupler/controller or the internal system supply
module (750-613) can be taken from the technical data of the components.
Internal current consumption*)
Current consumption via system voltage:
5 V for electronics of the bus modules and coupler/controller
Residual current for bus terminals*)
Available current for the bus modules. Provided by
the bus power supply unit. See coupler/controller
and internal system supply module (750-613)
*) cf. catalogue W4 Volume 3, manuals or Internet
Example
Coupler 750-301:
internal current consumption:350 mA at 5V
residual current for
bus modules:
1650 mA at 5V
2000 mA at 5V
sum I(5V) total :
The internal current consumption is indicated in the technical data for each
bus terminal. In order to determine the overall requirement, add together the
values of all bus modules in the node.
Attention
If the sum of the internal current consumption exceeds the residual current
for bus modules, then an internal system supply module (750-613) must be
placed before the module where the permissible residual current was exceeded.
Example:
A node with a PROFIBUS Coupler 750-333 consists of 20 relay modules (750-517) and 10 digital input modules (750-405).
Current consumption:
20* 90 mA = 1800 mA
10* 2 mA =
Sum
1820 mA
20 mA
The coupler can provide 1650 mA for the bus modules. Consequently,
an internal system supply module (750-613), e.g. in the middle of the
node, should be added.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Power Supply
• 33
Recommendation
With the WAGO ProServe® Software smartDESIGNER, the assembly of a
fieldbus node can be configured. The configuration can be tested via the integrated accuracy check.
The maximum input current of the 24 V system supply is 500 mA. The exact
electrical consumption (I(24 V)) can be determined with the following formulas:
Coupler/Controller
I(5 V) total =
Sum of all the internal current consumption of the connected
bus modules
+ internal current consumption coupler/controller
750-613
I(5 V) total =
Input current I(24 V) =
Sum of all the internal current consumption of the connected
bus modules
5 V / 24 V * I(5 V) total / η
η = 0.87 (at nominal load)
Note
If the electrical consumption of the power supply point for the 24 V-system
supply exceeds 500 mA, then the cause may be an improperly aligned node
or a defect.
During the test, all outputs, in particular those of the relay modules, must be
active.
WAGO-I/O-SYSTEM 750
DeviceNet
34 •
The WAGO-I/O-SYSTEM 750
Power Supply
2.7.3 Field Supply
2.7.3.1 Connection
Sensors and actuators can be directly connected to the relevant channel of the
bus module in 1-/4 conductor connection technology. The bus module supplies
power to the sensors and actuators. The input and output drivers of some bus
modules require the field side supply voltage.
The coupler/controller provides field side power (DC 24V). In this case it is a
passive power supply without protection equipment.
Power supply modules are available for other potentials, e.g. AC 230 V. Likewise, with the aid of the power supply modules, various potentials can be set
up. The connections are linked in pairs with a power contact.
Fig. 2-13: Field Supply (Sensor/Actuator)
g0xxx03e
The supply voltage for the field side is automatically passed to the next module via the power jumper contacts when assembling the bus modules .
The current load of the power contacts must not exceed 10 A on a continual
basis. The current load capacity between two connection terminals is identical
to the load capacity of the connection wires.
By inserting an additional power supply module, the field supply via the
power contacts is disrupted. From there a new power supply occurs which
may also contain a new voltage potential.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Power Supply
• 35
Attention
Some bus modules have no or very few power contacts (depending on the I/O
function). Due to this, the passing through of the relevant potential is disrupted. If a field supply is required for subsequent bus modules, then a power
supply module must be used.
Note the data sheets of the bus modules.
In the case of a node setup with different potentials, e.g. the alteration from
DC 24 V to AC 230V, a spacer module should be used. The optical separation of the potentials acts as a warning to heed caution in the case of wiring
and maintenance works. Thus, the results of wiring errors can be prevented.
2.7.3.2 Fusing
Internal fusing of the field supply is possible for various field voltages via an
appropriate power supply module.
750-601
24 V DC, Supply/Fuse
750-609
230 V AC, Supply/Fuse
750-615
120 V AC, Supply/Fuse
750-610
24 V DC, Supply/Fuse/Diagnosis
750-611
230 V AC, Supply/Fuse/Diagnosis
Fig. 2-14: Supply module with fuse carrier (Example 750-610)
WAGO-I/O-SYSTEM 750
DeviceNet
g0xxx09x
36 •
The WAGO-I/O-SYSTEM 750
Power Supply
Warning
In the case of power supply modules with fuse holders, only fuses with a
maximum dissipation of 1.6 W (IEC 127) must be used.
For UL approved systems only use UL approved fuses.
In order to insert or change a fuse, or to switch off the voltage in succeeding
bus modules, the fuse holder may be pulled out. In order to do this, use a
screwdriver for example, to reach into one of the slits (one on both sides) and
pull out the holder.
Fig. 2-15: Removing the fuse carrier
p0xxx05x
Lifting the cover to the side opens the fuse carrier.
Fig. 2-16: Opening the fuse carrier
p0xxx03x
Fig. 2-17: Change fuse
p0xxx04x
After changing the fuse, the fuse carrier is pushed back into its original position.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Power Supply
• 37
Alternatively, fusing can be done externally. The fuse modules of the WAGO
series 281 and 282 are suitable for this purpose.
Fig. 2-18: Fuse modules for automotive fuses, Series 282
pf66800x
Fig. 2-19: Fuse modules with pivotable fuse carrier, Series 281
pe61100x
Fig. 2-20: Fuse modules, Series 282
pf12400x
WAGO-I/O-SYSTEM 750
DeviceNet
38 •
The WAGO-I/O-SYSTEM 750
Power Supply
2.7.4 Supplementary power supply regulations
The WAGO-I/O-SYSTEM 750 can also be used in shipbuilding or offshore
and onshore areas of work (e.g. working platforms, loading plants). This is
demonstrated by complying with the standards of influential classification
companies such as Germanischer Lloyd and Lloyds Register.
Filter modules for 24-volt supply are required for the certified operation of the
system.
Item No.
Name
Description
750-626
Supply filter
Filter module for system supply and field supply (24 V,
0 V), i.e. for field bus coupler/controller and bus power
supply (750-613)
750-624
Supply filter
Filter module for the 24 V- field supply
(750-602, 750-601, 750-610)
Therefore, the following power supply concept must be absolutely complied
with.
Fig. 2-21: Power supply concept
g01xx11e
Note
Another potential power terminal 750-601/602/610 must only be used behind
the filter terminal 750-626 if the protective earth conductor is needed on the
lower power contact or if a fuse protection is required.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Power Supply
• 39
2.7.5 Supply example
Note
The system supply and the field supply should be separated in order to ensure
bus operation in the event of a short-circuit on the actuator side.
L1
L2
L3
N
PE
a)
b)
750-400
750-410
750-401
750-613
2)
1)
750-616
1) d)
c)
750-612
750-512
750-512
750-513
750-616
750-610
750-552
750-630
750-600
2)
Shield (screen) bus
10 A
Main ground bus
System
Supply
230V
24V
Field
Supply
230V
24V
Field
Supply
10 A
1) Separation module
recommended
2) Ring-feeding
recommended
a) Power Supply
on coupler / controller
via external Supply
Module
b) Internal System
Supply Module
c) Supply Module
passive
d) Supply Module
with fuse carrier/
diagnostics
Fig. 2-22: Supply example
WAGO-I/O-SYSTEM 750
DeviceNet
g0xxx04e
40 •
The WAGO-I/O-SYSTEM 750
Power Supply
2.7.6 Power Supply Unit
The WAGO-I/O-SYSTEM 750 requires a 24 V direct current system supply
with a maximum deviation of -15% or +20 %.
Recommendation
A stable network supply cannot be taken for granted always and everywhere.
Therefore, regulated power supply units should be used in order to guarantee
the quality of the supply voltage.
A buffer (200 µF per 1 A current load) should be provided for brief voltage
dips. The I/O system buffers for approx 1 ms.
The electrical requirement for the field supply is to be determined individually
for each power supply point. Thereby all loads through the field devices and
bus modules should be considered. The field supply as well influences the bus
modules, as the inputs and outputs of some bus modules require the voltage of
the field supply.
Note
The system supply and the field supply should be isolated from the power
supplies in order to ensure bus operation in the event of short circuits on the
actuator side.
WAGO products
Article No.
Description
787-903
Primary switched - mode, DC 24 V, 5 A
wide input voltage range AC 85-264 V
PFC (Power Factor Correction)
787-904
Primary switched - mode, DC 24 V, 10 A
wide input voltage range AC 85-264 V
PFC (Power Factor Correction)
787-912
Primary switched - mode, DC 24 V, 2 A
wide input voltage range AC 85-264 V
PFC (Power Factor Correction)
Rail-mounted modules with universal mounting carrier
288-809
288-810
288-812
288-813
AC 115 V / DC 24 V; 0,5 A
AC 230 V / DC 24 V; 0,5 A
AC 230 V / DC 24 V; 2 A
AC 115 V / DC 24 V; 2 A
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Grounding
• 41
2.8 Grounding
2.8.1 Grounding the DIN Rail
2.8.1.1 Framework Assembly
When setting up the framework, the carrier rail must be screwed together with
the electrically conducting cabinet or housing frame. The framework or the
housing must be grounded. The electronic connection is established via the
screw. Thus, the carrier rail is grounded.
Attention
Care must be taken to ensure the flawless electrical connection between the
carrier rail and the frame or housing in order to guarantee sufficient grounding.
2.8.1.2 Insulated Assembly
Insulated assembly has been achieved when there is constructively no direct
conduction connection between the cabinet frame or machine parts and the
carrier rail. Here the earth must be set up via an electrical conductor.
The connected grounding conductor should have a cross section of at least
4 mm2.
Recommendation
The optimal insulated setup is a metallic assembly plate with grounding connection with an electrical conductive link with the carrier rail.
The separate grounding of the carrier rail can be easily set up with the aid of
the WAGO ground wire terminals.
Article No.
Description
283-609
Single-conductor ground (earth) terminal block make an automatic
contact to the carrier rail; conductor cross section: 0.2 -16 mm2
Note: Also order the end and intermediate plate (283-320)
WAGO-I/O-SYSTEM 750
DeviceNet
42 •
The WAGO-I/O-SYSTEM 750
Grounding
2.8.2 Grounding Function
The grounding function increases the resistance against disturbances from
electro-magnetic interferences. Some components in the I/O system have a
carrier rail contact that dissipates electro-magnetic disturbances to the carrier
rail.
Fig. 2-23: Carrier rail contact
g0xxx10e
Attention
Care must be taken to ensure the direct electrical connection between the
carrier rail contact and the carrier rail.
The carrier rail must be grounded.
For information on carrier rail properties, please see chapter 2.6.3.2.
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Grounding
• 43
2.8.3 Grounding Protection
For the field side, the ground wire is connected to the lowest connection terminals of the power supply module. The ground connection is then connected
to the next module via the Power Jumper Contact (PJC). If the bus module has
the lower power jumper contact, then the ground wire connection of the field
devices can be directly connected to the lower connection terminals of the bus
module.
Attention
Should the ground conductor connection of the power jumper contacts within
the node become disrupted, e.g. due to a 4-channel bus terminal, the ground
connection will need to be re-established.
The ring feeding of the grounding potential will increase the system safety.
When one bus module is removed from the group, the grounding connection
will remain intact.
The ring feeding method has the grounding conductor connected to the beginning and end of each potential group.
Fig. 2-24: Ring-feeding
g0xxx07e
Attention
The regulations relating to the place of assembly as well as the national regulations for maintenance and inspection of the grounding protection must be
observed.
WAGO-I/O-SYSTEM 750
DeviceNet
44 •
The WAGO-I/O-SYSTEM 750
Shielding (Screening)
2.9 Shielding (Screening)
2.9.1 General
The shielding of the data and signal conductors reduces electromagnetic interferences thereby increasing the signal quality. Measurement errors, data transmission errors and even disturbances caused by overvoltage can be avoided.
Attention
Constant shielding is absolutely required in order to ensure the technical
specifications in terms of the measurement accuracy.
The data and signal conductors should be separated from all high-voltage
cables.
The cable shield should be potential. With this, incoming disturbances can be
easily diverted.
The shielding should be placed over the entrance of the cabinet or housing in
order to already repel disturbances at the entrance.
2.9.2 Bus Conductors
The shielding of the bus conductor is described in the relevant assembly
guidelines and standards of the bus system.
2.9.3 Signal Conductors
Bus modules for most analog signals along with many of the interface bus
modules include a connection for the shield.
Note
For better shield performance, the shield should have previously been placed
over a large area. The WAGO shield connection system is suggested for such
an application.
This suggestion is especially applicable when the equipment can have even
current or high impulse formed currents running through it (for example
through atmospheric end loading).
WAGO-I/O-SYSTEM 750
DeviceNet
The WAGO-I/O-SYSTEM 750
Assembly Guidelines/Standards
• 45
2.9.4 WAGO Shield (Screen) Connecting System
The WAGO Shield Connecting system includes a shield clamping saddle, a
collection of rails and a variety of mounting feet. Together these allow many
dfferent possibilities. See catalog W4 volume 3 chapter 10.
Fig. 2-25: WAGO Shield (Screen) Connecting System
p0xxx08x, p0xxx09x, and p0xxx10x
Fig. 2-26: Application of the WAGO Shield (Screen) Connecting System
p0xxx11x
2.10 Assembly Guidelines/Standards
DIN 60204,
Electrical equipping of machines
DIN EN 50178
Equipping of high-voltage systems with electronic
components (replacement for VDE 0160)
EN 60439
Low voltage – switch box combinations
WAGO-I/O-SYSTEM 750
DeviceNet
46 •
Fieldbus Coupler 750-306
Description
3 Fieldbus Coupler/Controller
3.1 Fieldbus Coupler 750-306
3.1.1 Description
The fieldbus Coupler 750-306 displays the peripheral data of all I/O modules
in the WAGO-I/O-SYSTEM 750 on DeviceNet Feldbus. The data is transmitted with objects.
The bus Coupler determines the physical structure of the node and creates a
process image from this with all inputs and outputs. This could involve a
mixed arrangement of analog (word by word data exchange) and digital (byte
by byte data exchange) modules.
The local process image is subdivided into an input and output data area. The
process data can be read in via the DeviceNet bus and further processed in a
control system. The process output data is sent via the DeviceNet bus.
The data of the analog modules are mapped into the automatical created process image according to the order of their position downstream of the bus Coupler. The bits of the digital modules are compiled to form bytes and also
mapped into the process image attached to the data of the analog modules.
Should the number of digital I/Os exceed 8 bits, the Coupler automatically
starts another byte.
The fieldbus Coupler supports the DeviceNet function Bit-Strobe, whereby the
function is insofar restricted, that only the status byte will be delivered.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Hardware
• 47
3.1.2 Hardware
3.1.2.1 View
01 02
DeviceNet
OVERFL
MS
RUN
Fieldbus
connection
Series 231
(MCS)
C
B
D
BUS OFF 24V 0V
NS
CONNECT
+
+
Ñ
Ñ
ON
1 2 3 4 5 6 7 8
750-306
I/O
DIP switch
for MAC ID
and baud rate
A
Status
voltage supply
-Power jumper
contacts
-System
Data contacts
Supply
24V
0V
Supply via
power jumper
contacts
24V
0V
PE PE
Power jumper
contacts
Configuration
interface
flap
opened
Fig. 3-1: Fieldbus Coupler 750-306 DeviceNet
g030600e
The fieldbus Coupler comprises of:
• Supply module with Internal system supply module for the system supply
as well as power jumper contacts for the field supply via I/O module assemblies.
• Fieldbus interface with the bus connection
• DIP switch for baud rate and MAC ID
• Display elements (LED's) for status display of the operation, the bus communication, the operating voltages as well as for fault messages and diagnosis
• Configuration interface
• Electronics for communication with the I/O modules (internal bus) and the
fieldbus interface
WAGO-I/O-SYSTEM 750
DeviceNet
48 •
Fieldbus Coupler 750-306
Hardware
3.1.2.2 Device Supply
The supply is made via terminal blocks with CAGE CLAMP® connection.
The device supply is intended both for the system and the field units.
24V
5
1
24V/0V
10nF
DC
Bus
modules
DC
24V
ELECTRONICS
FIELDBUS INTERFACE
0V
6
2
24V
ELECTRONICS
FIELDBUS
INTERFACE
7
3
0V
1)
2)
0V
10nF
8
4
1) 1MW
2) 10nF/500V
750-306
Fig. 3-2: Device supply
g030601e
The integrated internal system supply module generates the necessary voltage
to supply the electronics and the connected I/O modules.
The fieldbus interface is supplied with electrically isolated voltage from the
internal system supply module.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Hardware
• 49
3.1.2.3 Fieldbus Connection
For the field bus connection, the DeviceNet interface is equipped with a 5 pole
header, its counter-piece being a plug connector (Open Style Connector).
The scope of delivery includes the plug connector 231-305/010-000/050-000
from the WAGO MULTI CONNECTION SYSTEM. The connector has gold
plated contacts and has the signal designations printed at its clamping units.
The table shows the connection diagram, the colours resulting in accordance
with the DeviceNet specification and are identical to the conductor colours of
the DeviceNet cables.
V+
Fieldbus
connection
Series 231
(MCS)
CAN_High
drain
CAN_Low
Pin
Signal
Code
Description
5
V+
red
11 ... 25 V
4
CAN_H
white
CAN Signal High
3
Shield
2
CAN_L
blue
CAN Signal Low
1
V-
black
0V
Shield connection
V-
Fig. 3-3: Fieldbus connection, MCS
g012500e
For the connection of small conductor cross sections, we recommend to insert
an insulation stop from series 231-670 (white), 231-671 (light grey) or 231672 (dark grey) due to the low kink resistance. This insulation stop prevents a
conductor from kinking when it hits the conductor contact point, and as such
the conductor insulation from being also entered into and clamped in the connection point. Connector marking, housing components, test connectors including cables and header connectors for cable extensions are available.
The connection point is lowered in such a way that after a connector is inserted, installation in an 80 mm high switchbox is possible.
The electrical isolation between the fieldbus system and the electronics is
made via the DC/DC converter and the optoCoupler in the fieldbus.
WAGO-I/O-SYSTEM 750
DeviceNet
50 •
Fieldbus Coupler 750-306
Hardware
3.1.2.4 Display Elements
The operating condition of the fieldbus Coupler or node is signalled via light
diodes (LED).
Four LEDs, specific for DeviceNet (OVERFL, RUN, BUSOFF, CONNECT),
indicate the module status (MS) and the network status (NS).
DeviceNet
OVERFL
MS
RUN
DeviceNet
A
C
B
D
C
A
OVERFL
MS
RUN
BUS OFF 24V 0V
NS
CONNECT
BUS OFF
NS
CONNECT
I/O
I/O
+
+
A
C
B
D
A
B
24V 0V
+
+
Fig. 3-4: Display elements 750-306
LED
Color
Meaning
OVERFL
red
Errors or faults at the fieldbus Coupler.
RUN
green
Fieldbus Coupler is ready for operation.
BUS OFF
red
Error or malfunction at network
g012555x
CONNECT green
Fieldbus Coupler is ready for network communication.
I/O
red/
green/
orange
The ‚I/O‘-LED indicates the operation of the node and signals faults
encountered.
A
green
Status of the operating voltage system
B or C
green
Status of the operating voltage – power jumper contacts
(LED position is manufacturing dependent)
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Hardware
• 51
3.1.2.5 Configuration Interface
The configuration interface used for the communication with
WAGO-I/O-CHECK or for firmware transfer is located behind the cover flap.
open
flap
Configuration
interface
Fig. 3-5: Configuration interface
g01xx06e
The communication cable (750-920) is connected to the 4-pole header.
Warning
The communication cable 750-920 must not be connected or disconnected
while the coupler/controller is powered on!
3.1.2.6 Hardware Address (MAC ID)
The DIP switch is used both for parametrizing (setting the baud rate) of the
fieldbus Coupler and for setting the MAC ID.
The MAC-ID (node address) is set with the DIP switches 1 to 6 by 'sliding' the
desired DIP switch to 'ON'.
The binary significance of the individual DIP switches increases according to
the switch number. DIP switch 1 being the lowest bit with the value 20 and
switch 6 the highest bit with the value 25. Therefore the MAC ID 1 is set with
DIP1 = ON, the MAC ID 8 with DIP4 = ON, etc.
For the DeviceNet fieldbus nodes, the node address can be set within the range
from 0 to 63.
ON
1 2 3 4 5
ON
6 7 8
1
2
3
4
5
6
7
8
Fig. 3-6: Example: Setting of station (node) address MAC ID 1 (DIP 1 = ON)
g012540x
The configuration is only read during the power up sequence. Changing the
switch position during operation does not change the configuration of the bus-
WAGO-I/O-SYSTEM 750
DeviceNet
52 •
Fieldbus Coupler 750-306
Operating System
coupler. Turn off and on the power supply for the fieldbus coupler to accept
the DIP switch change.
The default setting is MAC ID 1.
3.1.2.7 Setting the Baud Rate
The fieldbus coupler supports 3 different Baud rates, 125 kBaud, 250 kBaud
and 500 kBaud. DIP switches 7 and 8 are used to set the baud rate.
ON
1 2 3 4 5
ON
6 7 8
1
2
3
4
5
6
7
8
g012541x
Fig. 3-7: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) on a
station (node) with the address MAC
ID 1.
Baud rate
DIP7
DIP8
125 kBaud*)
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not allowed
ON
ON
*)
Presetting
The configuration is only read during the power up sequence. Changing the
switch position during operation does not change the configuration of the buscoupler. Turn off and on the power supply for the fieldbus Coupler to accept
the DIP switch change.
The default setting is Baud rate 125 kB.
3.1.3 Operating System
Following is the configuration of the master activation and the electrical installation of the fieldbus station.
After switching on the supply voltage, the Coupler performs a self-test of all
functions of its devices, the I/O module and the fieldbus interface. Following
this, the I/O modules and the present configuration is determined, whereby an
external, not visible list is generated.
In the event of a fault, the Coupler changes to the "Stop" condition. The "I/O"
LED flashes red. After clearing the fault and cycling power, the Coupler
changes to the "Fieldbus start" status and the "I/O" LED lights up green.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Process Image
Fig. 3-8: Operating system 750-306
• 53
g012113e
3.1.4 Process Image
After powering up, the Coupler recognizes all I/O modules plugged into the
node which supply or wait for data (data width/bit width > 0). In the nodes,
analog and digital I/O modules can be mixed.
The Coupler produces an internal process image from the data width and the
type of I/O module as well as the position of the I/O modules in the node. It is
divided into an input and an output data area.
The data of the digital I/O modules is bit orientated, i.e. the data exchange is
made bit for bit. The analog I/O modules are all byte orientated I/O modules,
i.e. modules where the data exchange is made byte for byte. These I/O modules include, for example, the counter modules, I/O modules for angle and
path measurement as well as the communication modules.
Note
For the number of input and output bits or bytes of the individual I/O modules, please refer to the corresponding I/O module description.
The data of the I/O modules is separated for the local input and output process
image in the sequence of their position after the Coupler in the individual
process image.
In the respective I/O area, analog modules are mapped first, then all digital
modules, even if the order of the connected analog and digital modules does
not comply with this order. The digital channels are grouped, each of these
groups having a data width of 1 byte. Should the number of digital I/Os exceed 8 bits, the Coupler automatically starts another byte.
Note
A process image restructuring may result if a node is changed or extended. In
this case, the process data addresses also change in comparison with earlier
ones. In the event of adding a module, take the process data of all previous
modules into account.
WAGO-I/O-SYSTEM 750
DeviceNet
54 •
Fieldbus Coupler 750-306
Data Exchange
3.1.5 Data Exchange
With DeviceNet, the transmission and exchange of data is made using objects.
For a network access on the single objects of the Coupler, it is necessary to
create a connection between the desired participants and to allocate connection objects.
For an easy and quick set-up of a connection, the DeviceNet fieldbus Coupler
750-306 uses the "Predefined Master/Slave Connection Set", which contains 4
pre-defined connections. For the access on the Coupler the connections only
need to be allocated. The "Predefined Master/Slave Connection Set" confines
itself to pure Master/Slave relationships.
The DeviceNet fieldbus Coupler 750-306 can only communicate via its assigned client and it is a so-called "Group 2 Only Server". The Group 2 Only
Server communicating is only possible via the Group 2 Only Unconnected
Explicit Message Port. These slaves exclusively receive messages defined in
message group 2.
The object configuration for the data transmission is defined by an Assembly
Object. The Assembly Object can be used to group data (e.g. I/O data) into
blocks (mapping) and send this data via one single communication connection.
This mapping results in a reduced number of accesses to the network.
A differentiation is made between "Input-Assemblies" and "OutputAssemblies".
An Input-Assembly reads in data from the application via the network or produces data on the network respectively.
An Output-Assembly writes data to the application or consumes data from the
network respectively.
Various Assembly instances are permanently programmed (static assembly) in
the fieldbus Coupler.
Further information
The Assembly instances for the static assembly are described in chapter
4.5.1.1 "Assembly Instance".
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Data Exchange
• 55
3.1.5.1 Communication Interfaces
For a data exchange, the DeviceNet fieldbus Coupler is equipped with two interfaces:
• the interface to fieldbus (-master) and
• the interface to the bus modules.
Data exchange takes place between the fieldbus master and the bus modules.
Access from the fieldbus side is fieldbus specific.
3.1.5.2 Memory Areas
The Coupler uses a memory space of 256 words (word 0 ... 255) for the physical input and output data.
The division of the memory spaces is identical with all WAGO fieldbus Couplers.
fieldbus coupler
fieldbus
memory area
for input data
word 0
1
I/O modules
input
modules
word 255
memory area
for output data
word 0
2
output
modules
I
O
word 255
Fig. 3-9: Memory areas and data exchange for a fieldbus Coupler
g012433e
The Coupler process image contains the physical data of the bus modules in a
storage area for input data and in a storage area for output data (word 0 ... 255
each).
1
The input module data can be read from the fieldbus side.
2
In the same manner, writing to the output modules is possible from the
fieldbus side.
WAGO-I/O-SYSTEM 750
DeviceNet
56 •
Fieldbus Coupler 750-306
Data Exchange
3.1.5.3 Addressing
3.1.5.3.1 Fieldbus Specific
Once the supply voltage is applied, the Assembly Object maps data from the
process image. As soon as a connection is established, a DeviceNet-Master
(Scanner) can address and access the data by "Class", "Instance" and "Attribute".
Data mapping depends on the selected Assembly Instance of the static Assembly.
Further information
The Assembly Instances of the static Assembly are described in chapter
4.5.1.1 "Assembly Instance".
Fieldbus coupler
memory area
for input data
word 0
Connection
Object
Producer
fieldbus
master
Assembly
Object
I/O modules
1
input
modules
Application
Object
InputAssemly
word 255
Consumer
OutputAssemly
memory area
for output data
word 0
2
output
modules
I
O
word 255
Fig. 3-1: Fieldbus specific data exchange for a DeviceNet fieldbus Coupler
g012531e
Note
For the number of input and output bits or bytes of the individual I/O modules,
please refer to the corresponding I/O module description.
Note
A process image restructuring may result if a node is changed or extended. In
this case the process data addresses also change in comparison with earlier
ones. In the event of adding a module, take the process data of all previous
modules into account.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Data Exchange
• 57
Example for static assembly (default assembly):
The default assembly is:
Output1
Input1
(I/O Assembly Instance 1)
(I/O Assembly Instance 4)
In this example, the fieldbus node arrangement looks like this:
1) 1 fieldbus coupler DeviceNet (750-306),
2) 1 digital 4-channel input module (i. e. 750-402),
3) 1 digital 4- channel output module (i. e. 750-504),
4) 1 analog 2- channel output module with 2 bytes per channel (i. e. 750-552),
5) 1 analog 2- channel input module with 2 bytes per channel (i. e. 750-456),
6) 1 End module (750-600).
Input process image:
Default process data, input image (Assembly Class, Instance 4)
Byte
.7
.6
.5
.4
.3
0
low byte channel 1
1
high byte channel 1
2
low byte channel 2
3
high byte channel 2
not used
4
2)
.1
.0
DI031)
DI021)
DI011)
DS08 2) DS07 2) DS06 2) DS05 2) DS04 2) DS03 2) DS02 2) DS01 2)
5
1)
DI041)
.2
DI = Digital Input
DS = Diagnostic Status (The last byte in the input process image is the Diagnostic
Status Byte, DS01...DS08, see also: Object 0x64/Instance 1/Attr. 5)
DS01 =1: internal bus error (0x01)
DS02 =1: module communication error (0x02)
DS04 =1: module diagnostic (0x08)
DS08 =1: fieldbus error (0x80)
WAGO-I/O-SYSTEM 750
DeviceNet
58 •
Fieldbus Coupler 750-306
Configuration Software
Output process image:
Default process data, output image (Assembly Class, Instance 1)
Byte
.7
.6
.5
.4
.3
0
low byte channel 1
1
high byte channel 1
2
low byte channel 2
3
high byte channel 2
not used
4
1)
DO041)
.2
.1
.0
DO031)
DO021)
DO011)
DO = Digital Output
3.1.6 Configuration Software
To enable a connection between the PLC and the fieldbus devices, the interface modules have to be configured with the individual station data.
To this effect, the scope of delivery of WAGO-I/O-SYSTEM 758 includes the
WAGO NETCON software intended for design and configuration, start-up and
diagnosis.
Further configuration software of different manufacturers include, for instance, RSNetWorx.
3.1.7 Starting up DeviceNet Fieldbus Nodes
This chapter shows the step-by-step procedure for starting up a
WAGO DeviceNet fieldbus node.
Attention
This description is given as an example and is limited to the execution of a
local start-up of an individual DeviceNet fieldbus node.
The procedure contains the following steps:
1. Connecting the PC and fieldbus node
2. Setting the MAC ID and baud rate
3. Configuration with static Assembly
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Starting up DeviceNet Fieldbus Nodes
• 59
3.1.7.1 Connecting the PC and Fieldbus Node
4. Connect the fitted DeviceNet fieldbus node to the DeviceNet fieldbus PCB in
your PC via a fieldbus cable.
The 24 V field bus supply is fed by an external fieldbus network power supply
over the connections V+, V- of the 5-pin fieldbus connector (MCS Series 231).
5. Start your PC.
3.1.7.2 Setting the MAC ID and Baud Rate
6. Use the DIP switches 1...6 to set the desired node address (MAC ID). The binary significance of the individual DIP switches increases according to the
switch number.
1 2 3 4 5
ON
DIP switch
6 7 8
1
2
3
4
5
6
g012443x
Fig. 3-10: Example: Setting the
MAC ID 4 (DIP 3 = ON).
Value
20
21
22
23
24
25
7. DIP switches 7 and 8 are used to set the desired baud rate.
ON
1 2 3 4 5
ON
6 7 8
1
2
3
4
5
6
7
8
g012541x
Fig. 3-11: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) of the
station with MAC ID 1.
Baud rate
DIP7
DIP8
125 kBaud*)
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not allowed
ON
ON
*)
Presetting
8. Then switch on the Coupler supply voltage.
WAGO-I/O-SYSTEM 750
DeviceNet
60 •
Fieldbus Coupler 750-306
Starting up DeviceNet Fieldbus Nodes
3.1.7.3 Configuration with Static Assembly
In this example, the software WAGO NETCON is used for the configuration.
The node in the example consists of the following I/O modules:
2
DI DI
402
402
3
4
5
6
DODO DODO DODO AI AI
7
8
AO AO
750-306
1
DI DI
516
516
516
Fig. 3-12: Example for a fieldbus node
467
550
600
g012552x
1. Starting Software and EDS file load
1. Start the configuration software WAGO NETCON.
2. Load an EDS file for the fieldbus Coupler in WAGO NETCON, i. e. "4.EDS".
For this click on "File/ Copy EDS" and choose the EDS-file to load.
Note
You can download the EDS files for the fieldbus Coupler from the Internet under: www.wago.com.
Upon downloading the EDS file into WAGO NETCON, you can create a
new project and start configuring your network.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Starting up DeviceNet Fieldbus Nodes
• 61
2. Create a new project
3. Enter the "File" menu and click on menu point "New".
4. Select "DeviceNet" as the fieldbus system and confirm your selection by clicking on the "OK" button.
Fig. 3-13: Select fieldbus
p112501d
3. Enter Master
5. Enter a fieldbus master on the surface by clicking on the „Master“ menu point
in the "Insert" menu.
A dialog window opens in which you can select the DeviceNet fieldbus card in
your PC.
Fig. 3-14: Select the DeviceNet fieldbus PCB / Insert Master
p1x2602d
6. For the DeviceNet Master interface card, click in the left-hand selection window on the corresponding entry to mark it.
7. Take the Master into the right-hand window by clicking on the "Add" button
and confirm by clicking on the "OK" button.
Now the fieldbus master is shown on the surface as a graphic.
WAGO-I/O-SYSTEM 750
DeviceNet
62 •
Fieldbus Coupler 750-306
Starting up DeviceNet Fieldbus Nodes
4. Add a slave
8. Enter a fieldbus slave on the surface by clicking on the “Device” menu point in
the "Insert" menu.
The mouse pointer changes to the letter D with an arrow.
9. Move this mouse pointer to the graphic display of the fieldbus, then click on
the left-hand mouse key.
A dialog window opens permitting you to select a DeviceNet device.
Fig. 3-15: Insert slave
p012501d
10.For the fieldbus Coupler 750-306 click in the left-hand selection window on
the corresponding entry to mark it.
11.Take this into the right-hand window by clicking on the "Add" button and confirm by clicking on the "OK" button.
The configuration is displayed on the surface as a graphic.
Fig. 3-16: Configuration
p012502d
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Starting up DeviceNet Fieldbus Nodes
• 63
5. Device configuration
12.To configure the device, click on its graphic to mark it, then click on the menu
point “Device configuration” in the "Settings" menu.
A dialog window opens permitting you to proceed with the desired settings.
Fig. 3-17: Device Configuration
p112505d
6. Load configuration
13.To load the set configuration in the interface card, click on the master’s graphic
to mark it, then click on the “Download” menu point in the "Online" menu.
WAGO-I/O-SYSTEM 750
DeviceNet
64 •
Fieldbus Coupler 750-306
LED Display
3.1.8 LED Display
The Coupler possesses several LEDs for on site display of the Coupler operating status or the complete node.
01 02
DeviceNet
OVERFL
A
RUN
B
MS
C
D
BUS OFF 24V 0V
NS
C
A
CONNECT
I/O
Fig. 3-18: Display elements 750-306
g030602x
The module status (MS) and the network status (NS) can be displayed by the
top 4 LED’s. They react as described in the table.
Module status (MS)
OVERFL RUN
(red)
(green)
State of device
Meaning
off
off
off
off
on
blinking
no power
device operational
device in standby
blinking
on
off
off
minor fault
unrecoverable fault
blinking
blinking
device self testing
No power supply to the device.
The device operates correctly.
The device needs to be configured or has been partly
configured.
A minor fault has occurred. It exists a diagnostics.
The device is defective, needs to be serviced or
replaced.
The device performs a built-in check.
Table 3-1: Fault and status displays: MS
Network status (NS)
BUSOFF
(red)
CONNECT
(green)
State of device
Meaning
off
off
not powered, not online
off
blinking
online, not connected
off
on
link ok online, connected
blinking
off
connection time out
on
off
critical link failure
No power supply to the device / fieldbus supply /
DeviceNet cable not connected and „Duplicate MAC
ID detection“ is not yet completed.
The device operates correctly at the fieldbus. However, it has not yet been integrated by a scanner.
The device operates correctly at the fieldbus. At least
one connection to another device has been established.
A minor fault has occurred (e.g. EPR is unequal 0
during a polling connection, slave is not polled any
longer).
The device has detected a fault (duplicated MAC ID
check error). It is unable to perform any more functions in the network.
Table 3-2: Fault and status displays: NS
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
LED Display
• 65
3.1.8.1 Node status – Blink code from the 'I/O' LED
The ‘I/O‘-LED displays the communication status of the internal bus. Additionally, this LED is used to display fault codes (blink codes) in the event of a
system error.
LED
Meaning
Trouble shooting
I/O
Green
Off
Red
Red
Fieldbus coupler operating perfectly, Data cycle on the
internal bus
No data cycle on the internal bus
a) During startup of fieldbus coupler:
Internal bus being initialized,
Startup displayed by LED flashing fast for approx.
1-2 seconds
b) After startup of fieldbus coupler:
Errors, which occur, are indicated by three consecutive flashing sequences. There is a short pause
between each sequential flash.
Evaluate the fault message (fault code and
fault argument).
The coupler starts up after switching on the supply voltage. The "I/O" LED
blinks. The "I/O" LED has a steady light following a fault free start-up.
In the case of a fault the "I/O" LED continues blinking. The fault is cyclically
displayed by the blink code.
Detailed fault messages are displayed with the aid of a blink code. A fault is
cyclically displayed with up to 3 blink sequences.
•
•
•
WAGO-I/O-SYSTEM 750
DeviceNet
The first blink sequence (approx. 10 Hz) starts the fault display.
The second blink sequence (approx. 1 Hz) following a pause. The
number of blink pulses indicates the fault code.
The third blink sequence (approx. 1 Hz) follows after a further pause.
The number of blink pulses indicates the fault argument.
66 •
Fieldbus Coupler 750-306
LED Display
Switching on
the power supply
Coupler/Controller starts up
“I/O”-LED is blinking
No
Test o.k.?
Yes
“I/O” LED
1st flash sequence
(Introduction of the
error indication)
1st break
“I/O” LED
2nd flash sequence
Error code
(Number of flash cycles)
2nd break
“I/O” LED
3rd flash sequence
Error argument
“I/O”-LED is shining
(Number of flash cycles)
ready for operation
Fig. 3-19: Signalling of the LED for indication of the node status
g012111e
After clearing a fault, restart the coupler by cycling the power.
I/O
Meaning
green
Data cycle on the internal bus
off
No data cycle on the internal bus
red
Hardware of fieldbus coupler is defect
red
flashing
During startup of fieldbus coupler: Internal bus being initialized,
After startup of fieldbus coupler: Errors, which occur, are indicated by
three consecutive flashing sequences
cyclic
red flashing
Fault message during internal bus reset or internal error. The evaluation
is made by the three consecutive flashing sequences (fault code and
fault argument).
Fault message of the ‘I/O‘-LED
1 st flash sequence: Start of the Fault message
2 nd flash sequence: Fault code
3 rd flash sequence: Fault argument
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
LED Display
• 67
Fault code 1: "Hardware and Configuration fault"
Fault argument
Fault description
Trouble shooting
-
Invalid checksum within the
parameter range of fieldbus coupler
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
1
Overflow of the internal buffer
memory for the inline code
Turn off the power supply of the
node, reduce number of I/O modules and turn the power supply on
again. If the error still exists,
exchange the bus coupler.
2
I/O module(s) with unsupported
data type
3
Unknown program module type
of the flash program memory
4
Fault when writing data within
the flash memory
5
Fault when deleting a flash sector
6
Changed I/O module configuration determined after
AUTORESET
Fault when writing data in the
serial EEPROM
Detect faulty I/O module as follows: turn off the power supply.
Place the end module in the middle of the fieldbus node. Turn the
power supply on again.
– If the LED is still blinking, turn
off the power supply and place
the end module in the middle of
the first half of the node (towards
the coupler).
– If the LED doesn’t blink, turn
off the power supply and place
the end module in the middle of
the second half of the node (away
from the coupler).
Turn the power supply on again.
Repeat this procedure until the
faulty I/O module is detected.
Replace the faulty I/O module.
Ask about a firmware update for
the fieldbus coupler.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
Restart the fieldbus coupler by
turning the power supply off and
on again.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
7
8
WAGO-I/O-SYSTEM 750
DeviceNet
Invalid Hardware Firmware
combination
68 •
Fieldbus Coupler 750-306
LED Display
9
10
11
12
13
14
Invalid checksum within the
serial EEPROM
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
serial EEPROM initialization
Turn off the power supply of the
fault
node, exchange the bus coupler
and turn the power supply on
again.
Fault when reading out data from Turn off the power supply of the
the EEPROM
node, exchange the bus coupler
and turn the power supply on
again.
Timeout when writing data in the Turn off the power supply of the
EEPROM
node, exchange the bus coupler
and turn the power supply on
again.
- not used Maximum number of Gateway or Turn off the power supply of the
Mailbox I/O modules exceeded
node, reduce number of Gateway
or Mailbox I/O modules and turn
the power supply on again.
Fault code 2 -not usedFault argument
-
Fault description
Trouble shooting
not used
-
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
LED Display
• 69
Fault code 3: "Internal bus protocol fault"
Fault argument
-
WAGO-I/O-SYSTEM 750
DeviceNet
Fault description
Trouble shooting
Internal bus communication
malfunction; faulty device can’t
be detected
If the fieldbus node comprises
internal system supply modules
(750-613), make sure first that the
power supply of these modules is
functioning. This is indicated by
the status LEDs. If all I/O modules
are connected correctly or if the
fieldbus node doesn’t comprise
750-613 modules you can detect
the faulty I/O module as follows:
turn off the power supply of the
node. Place the end module in the
middle of the fieldbus node. Turn
the power supply on again.
– If the LED is still blinking, turn
off the power supply and place the
end module in the middle of the
first half of the node (towards the
coupler).
– If the LED doesn’t blink, turn off
the power supply and place the end
module in the middle of the second
half of the node (away from the
coupler).
Turn the power supply on again.
Repeat this procedure until the
faulty I/O module is detected.
Replace the faulty I/O module. If
there is only one I/O module left
but the LED is still blinking, then
this I/O module or the coupler is
defective. Replace defective component.
70 •
Fieldbus Coupler 750-306
LED Display
Fault code 4: "Internal bus physical fault"
Fault argument
-
n*
Fault description
Trouble shooting
Error in internal bus data communication or interruption of the
internal bus at the coupler
Turn off the power supply of the
node. Place an I/O module with
process data behind the coupler
and note the error argument after
the power supply is turned on. If
no error argument is given by the
I/O LED, replace the coupler.
Otherwise detect faulty I/O module as follows: turn off the power
supply. Place the end module in
the middle of the fieldbus node.
Turn the power supply on again.
– If the LED is still blinking, turn
off the power supply and place the
end module in the middle of the
first half of the node (towards the
coupler).
– If the LED doesn’t blink, turn off
the power supply and place the end
module in the middle of the second
half of the node (away from the
coupler).
Turn the power supply on again.
Repeat this procedure until the
faulty I/O module is detected.
Replace the faulty I/O module.
If there is only one I/O module left
but the LED is still blinking, then
this I/O module or the coupler is
defective. Replace defective component.
Interruption of the internal bus
Turn off the power supply of the
after the nth process data module. node, exchange the (n+1)th process
data module and turn the power
supply on again.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
LED Display
• 71
Fault code 5: "Internal bus initialization fault"
Fault argument
n*
Fault description
Trouble shooting
Error in register communication
during internal bus initialization
Turn off the power supply of the
node and replace nth process data
module and turn the power supply
on again.
Fault code 6 -not usedFault argument
-
Fault description
Trouble shooting
not used
-
Fault code 7 -not usedFault argument
-
Fault description
Trouble shooting
not used
-
Fault code 8 -not usedFault argument
-
Fault description
Trouble shooting
not used
-
Fault code 9 "CPU Trap Error"
Fault argument
Fault description
Trouble shooting
1
Illegal Opcode
2
Stack overflow
Error in the program sequence.
Contact the WAGO I/O-Support
3
Stack underflow
4
NMI
Fault code 10 -not usedFault argument
-
Fault description
Trouble shooting
not used
-
Fault code 11: "Gateway-/Mailbox I/O module fault"
Fault argument
Fault description
Trouble shooting
1
Maximum number of Gateway
modules exceeded
Turn off the power supply of the
node, reduce number of Gateway
modules and turn the power supply
on again.
2
Maximum size of Mailbox exceeded
Reduce the Mailbox size.
3
Maximum size of process image Reduce the data width of the
exceeded due to the put Gateway Gateway modules.
modules
* The number of blink pulses (n) indicates the position of the I/O module. I/O modules
without data are not counted (e.g. supply module without diagnosis)
WAGO-I/O-SYSTEM 750
DeviceNet
72 •
Fieldbus Coupler 750-306
LED Display
Example for a fault message; Fault: The 13th I/O module has been removed
1.
The "I/O" LED starts the fault display with the first blink sequence (approx. 10
flashes/second).
2.
The second blink sequence (1 flash/second) follows the first pause. The "I/O" LED
blinks four times and thus signals the fault code 4 (internal bus data fault).
3.
The third blink sequence follows the second pause. The "I/O " LED blinks twelve
times. The fault argument 12 means that the internal bus is interrupted after the 12th
I/O module.
3.1.8.2 Supply voltage status
The two green LED’s in the coupler supply section, display the status of the
supply voltage. The left LED (A) indicates the status of the 24 V supply for
the coupler. The right hand LED (‘B‘ or ‘C‘) displays the status of the field
side supply (i.e., the power jumper contacts).
LED
Meaning
Trouble shooting
A
Green
Operating voltage for the system exists.
OFF
No operating voltage for the system.
Check the supply voltage (24V
and 0V).
B or C
Green
Operating voltage for the power jumper
contacts exists.
OFF
No operating voltage for the the power
jumper contacts.
Check the supply voltage (24V
and 0V).
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Coupler 750-306
Technical Data
• 73
3.1.9 Technical Data
System data
Max. no. of nodes
Max. no. of I/O points
Transmission medium
Max. length of bus line
Baud rate
BusCoupler connection
64 with scanner
ca. 6000 (depends on master)
shielded Cu cable,
trunk line: AWG 15, 18 (2x 0.82mm2 +2x1.7mm2)
drop line: AWG 22, 24 (2x0.2mm2 +2x0.32mm2)
100 m ... 500 m
(depends on baud rate / on the cable)
125 kBaud, 250 kBaud, 500 kBaud
5-pole male connector, series 231 (MCS)
female connector 231-305/010-000/050-000
is included
Standards and approvals
UL
KEMA
Certification
Conformity marking
E175199, UL508
E198726, UL1604
Clas I Div2 ABCD T4A
01ATEX1024 X
Eex nA II T4
ODVA
CE
Accessories
EDS files
Download: www.wago.com
Miniature WSB quick marking system
Technical data
Max. number of I/O modules
Input process image
Output process image
Configuration
Voltage supply
Current consumption
- via power supply terminal
- via CAN interface
Efficiency of the power supply
Internal power consumption
Total current for I/O modules
Isolation
Voltage via power jumper contacts
Current via power jumper contactmax
Dimensions (mm) W x H x L
Weight
EMC interference resistance
EMC interference transmission
WAGO-I/O-SYSTEM 750
DeviceNet
64
max. 512 bytes
max. 512 bytes
via PC or PLC
DC 24 V (-15 % / + 20 %)
< 500 mA at 24 V
< 120 mA at 11 V
87 %
350 mA at 5 V
1650 mA at 5 V
500 V system/supply
DC 24 V (-15 % / + 20 %)
DC 10 A
51 x 65* x 100 (*from top edge of mounting rail)
ca. 195 g
acc. EN 50082-2 (96)
acc. EN 50081-2 (94)
74 •
Fieldbus Controller 750-806
Description
3.2 Fieldbus Controller 750-806
3.2.1 Description
The programmable fieldbus Controller 750-806 (short: PFC) combines the
DeviceNet functions of the fieldbus Coupler 750-306 with that of a programmable logic control (PLC).
The application program is created with WAGO-I/O-PRO 32 in accordance
with IEC 61131-3.
All input signals of the sensors are grouped in the Controller.
According to the IEC 61131-3 programming, data processing occurs locally in
the PFC. The link results created in this manner can be put out directly to the
actuators or transmitted to the higher ranking control system via the bus.
The programmer has access to all fieldbus and I/O data.
In the initialization phase, the fieldbus Controller determines the physical
structure of the node and creates a process image from this with all inputs and
outputs. This could involve a mixed arrangement of analog (word by word
data exchange) and digital (byte by byte data exchange) modules.
The local process image is subdivided into an input and output data area.
The data of the analog modules are mapped into the PDOs according to the
order of their position downstream of the bus Coupler. The bits of the digital
modules are compiled to form bytes and also mapped into PDOs. Should the
number of digital I/Os exceed 8 bits, the Coupler automatically starts another
byte.
In addition to the functions of the fieldbus Coupler, the fieldbus Controller
supports the following DeviceNet functions:
• Create Connection via UCMM-Port
• Offline Connection Set
• DeviceNet Shutdown
• Dynamic assembly
• Change MAC ID by SW
• Heartbeat
• Bit-Strobe
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Hardware
• 75
3.2.2 Hardware
3.2.2.1 View
01 02
DeviceNet
OVERFL
MS
RUN
Fieldbus
connection
Series 231
(MCS)
C
B
D
Data contacts
Supply
24V
0V
Supply via
power jumper
contacts
24V
+
+
Ñ
Ñ
ON
1 2 3 4 5 6 7 8
750-806
USR
Configuration
and programming
interface
A
BUS OFF 24V 0V
NS
CONNECT
I/O
DIP switch
for MAC ID
and baud rate
Status
voltage supply
-Power jumper
contacts
-System
flap
opened
0V
Power jumper
contacts
operating
mode switch
Fig. 3-20: Fieldbus Controller 750-806 DeviceNet
g080600e
The fieldbus Controller is comprised of:
• Device supply with an internal system supply module as well as power
jumper contacts for the field supply via assembled I/O modules
• Fieldbus interface with the bus connection
• DIP switch for baud rate and node ID
• Display elements (LEDs) for status display of the operation, the bus communication, the operating voltages as well as for fault messages and diagnosis
• Configuration and programming interface and operating mode switch
• Electronics for communication with the I/O modules (internal bus) and the
fieldbus interface
WAGO-I/O-SYSTEM 750
DeviceNet
76 •
Fieldbus Controller 750-806
Hardware
3.2.2.2 Device Supply
The voltage supply is fed in via the terminals with the CAGE CLAMP® connection. Device supply is intended for system supply and field side supply.
I/O Modules
1/2
24 V
24 V
Electronic
10 nF
Fieldbus
Interface
Electronic
3/4
5V
0V
24 V
5V
Fieldbus
Interface
10 nF
24 V
1
2
1)
0V
3
1) 1M
2) 10nF/500V
4
750-806
Fig. 3-21: Device supply
g080601e
The integrated internal system supply module generates the necessary voltage
to supply the electronics and the connected I/O modules.
The fieldbus interface is supplied with electrically isolated voltage from the
internal system supply module.
WAGO-I/O-SYSTEM 750
DeviceNet
2)
Fieldbus Controller 750-806
Hardware
• 77
3.2.2.3 Fieldbus Connection
The scope of delivery includes the plug connector 231-305/010-000/050-000
from the WAGO MULTI CONNECTION SYSTEM. The connector has gold
plated contacts and has the signal designations printed at it clamping units.
The connection diagram shows the table, the colours resulting in accordance
with the DeviceNet specification and are identical to the conductor colours of
the DeviceNet cables.
V+
Fieldbus
connection
Series 231
(MCS)
CAN_High
drain
CAN_Low
Pin
Signal
Code
Description
5
V+
red
11 ... 25 V
4
CAN_H
white
CAN Signal High
3
Shield
2
CAN_L
blue
CAN Signal Low
1
V-
black
0V
Shield connection
V-
Fig. 3-22: Fieldbus connection, MCS
g012500e
For the connection of small conductor cross sections, we recommend to insert
an insulation stop from series 231-670 (white), 231-671 (light grey) or 231672 (dark grey) due to the low kink resistance. This insulation stop prevents a
conductor from kinking when it hits the conductor contact point, and as such,
the conductor insulation from being also entered into and clamped in the connection point. Connector marking, housing components, test connectors including cables and heater connectors for cable extensions, are available.
The connection point is lowered in such a way that after a connector is inserted, installation in an 80 mm high switchbox is possible.
The electrical isolation between the fieldbus system and the electronics is
made via the DC/DC converter and the optocoupler in the fieldbus.
WAGO-I/O-SYSTEM 750
DeviceNet
78 •
Fieldbus Controller 750-806
Hardware
3.2.2.4 Display Elements
The operating condition of the fieldbus controller or node is signalled via light
diodes (LED).
Four LED’s, specific for DeviceNet (OVERFL, RUN, BUSOFF, CONNECT),
indicate the module status (MS) or the network status (NS).
DeviceNet
OVERFL
MS
RUN
DeviceNet
A
C
B
D
C
A
OVERFL
MS
RUN
BUS OFF 24V 0V
NS
CONNECT
BUS OFF
NS
CONNECT
I/O
I/O
USR
+
+
USR
A
C
B
D
A
B
24V 0V
+
+
Fig. 3-23: Display elements 750-806
LED
Color
Meaning
OVERFL
red
Errors or faults at the fieldbus Coupler.
RUN
green
Fieldbus Coupler is ready for operation.
BUS OFF
red
Error or malfunction at network
g012556x
CONNECT green
Fieldbus Coupler is ready for network communication.
IO
red
/green /
orange
The 'I/O'-LED indicates the operation of the node and signals faults
encountered.
USR
red
/green /
orange
The 'USR' LED can be selected by a user program in a programmable fieldbus Controller
A
green
Status of the operating voltage system
B or C
green
Status of the operating voltage – power jumper contacts
(LED position is manufacturing dependent)
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Hardware
• 79
3.2.2.5 Configuration and Programming Interface
The configuration and programming interface is located behind the cover flap.
This is used to communicate with WAGO-I/O-CHECK and
WAGO-I/O-PRO 32 as well as for firmware transfer.
open
flap
Configuration and
programming interface
Fig. 3-24: Configuration and programming interface
g01xx07e
The communication cable (750-920) is connected to the 4-pole header.
Warning
The communication cable 750-920 must not be connected or disconnected
while the coupler/controller is powered on!
3.2.2.6 Operating Mode Switch
The operating mode switch is located behind the cover flap beside the configuration and programming interface.
open
flap
Run
Stop
Update firmware
Reset
(pushing down)
mode switch
Fig. 3-25: Operating mode switch
g01xx10e
The switch is a push/slide switch with 3 settings and a hold-to-run function.
WAGO-I/O-SYSTEM 750
DeviceNet
80 •
Fieldbus Controller 750-806
Hardware
Operating mode switch
Function
From middle to top position
Activate program processing (RUN)
From top to middle position
Stop program processing (STOP)
Lower position, bootstrap
For original loading of firmware,
not necessary for user
Push down
(i.e.with a screwdriver)
Hardware reset
All outputs are reset; variables are set to 0 or to FALSE
or to an initial value.
The hardware reset can be performed with STOP as well
as RUN in any position of the operating mode switch!
An operating mode is internally changed at the end of a PLC cycle.
Attention
If outputs are set when switching over the operating mode switch from RUN
to STOP, they remain set! Switching off the software side i.e. by initiators,
are ineffective, because the program is no longer processed.
Note
With "GET_STOP_VALUE" (library "System.lib") WAGO-I/O-PRO 32
provides a function which serves to recognize the last cycle prior to a program stop giving the user the possibility to program the behavior of the Controller in case of a STOP. With the aid of this function the Controller outputs
can be switched to a safe condition.
3.2.2.7 Hardware Address (MAC ID)
The DIP switch is used both for parametrizing (setting the baud rate) of the
fieldbus controller and for setting the MAC ID.
The MAC-ID (node address) is set with the DIP switches 1 to 6 by 'sliding' the
desired DIP switch to 'ON'.
The binary significance of the individual DIP switches increases according to
the switch number. DIP switch 1 being the lowest bit with the value 20 and
switch 6 the highest bit with the value 25. Therefore the MAC ID 1 is set with
DIP1 = ON, the MAC ID 8 with DIP4 = ON, etc.
For the DeviceNet fieldbus nodes the node address can be set within the range
from 0 to 63.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Hardware
ON
1 2 3 4 5
ON
6 7 8
1
2
3
4
5
6
7
8
• 81
Fig. 3-26: Example: Setting of station (node) address MAC ID 1 (DIP 1 = ON)
g012540x
The configuration is only read during the power up sequence. Changing the
switch position during operation does not change the configuration of the buscoupler. Turn off and on the power supply for the fieldbus controller to accept
the DIP switch change.
The default setting is MAC ID 1.
3.2.2.8 Setting the Baud Rate
The fieldbus controller supports 3 different Baud rates, 125 kBaud, 250 kBaud
and 500 kBaud. DIP switches 7 and 8 are used to set the baud rate.
Baudrate
ON
1 2 3 4 5
DIP7
DIP8
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not allowed
ON
ON
125 kBaud
ON
6 7 8
1
2
3
4
5
6
7
8
g012541x
Fig. 3-27: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) on a
station (node) with the address MAC
ID 1.
*)
*)
Presetting
The configuration is only read during the power up sequence. Changing the
switch position during operation does not change the configuration of the buscoupler. Turn off and on the power supply for the fieldbus controller to accept
the changing.
The default setting is Baud rate 125 kB.
WAGO-I/O-SYSTEM 750
DeviceNet
82 •
Fieldbus Controller 750-806
Operating System
3.2.3 Operating System
3.2.3.1 Start-up
The Controller starts-up after switching on the supply voltage or after a hardware reset. The PLC program in the flash memory is transferred to the RAM.
This is followed by the initialization of the system. The Controller determines
the I/O modules and the present configuration. The variables are set to 0 or to
FALSE or to an initialization value given by the PLC program. The flags retain their status. The "I/O" LED blinks red during this phase.
Following an error free start-up, the Controller changes over to the "RUN"
mode. The "I/O" LED lights up green.
A PLC program does not yet exist in the flash memory when delivered. The
Controller start-up is described without initializing the system. It then behaves
as a Coupler.
3.2.3.2 PLC Cycle
The PLC cycle starts following an error free start-up when the operating mode
switch is in the top position or by a start command from the
WAGO-I/O-PRO 32. The input and output data of the fieldbus and the I/O
modules as well as the times are read. Subsequently, the PLC program in the
RAM is processed followed by the output data of the fieldbus and the I/O
modules in the process image. Operating system functions, amongst others, for
diagnosis and communication are performed and the times are updated at the
end of the PLC cycle. The cycle starts again with the reading in of the input
and output data and the times.
The change of the operating mode (STOP/RUN) is made at the end of a PLC
cycle.
The cycle time is the time from the start of the PLC program to the next start.
If a loop is programmed within a PLC program, the PLC running time and
thus the PLC cycle are extended correspondingly.
The inputs, outputs and times are not updated during the processing of the
PLC program. This update occurs in a defined manner only at the end of the
PLC program. For this reason it is not possible to wait for an event from the
process or the elapse of a time within a loop.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Operating System
• 83
Switching on the
supply voltage
“I/O” LED
is blinking
orange
Is a PLC
program in the Flash
memory ?
No
Yes
PLC program transfer
from the flash memory to RAM
Determination of the I/O modules
and the configuration
Variables are set to 0 or FALSE
or to their initial value,
flags remain in the same status.
Initialization
of the system
“I/O” LED
is blinking
red
Test o.k.?
Determination of the I/O modules
and the configuration
No
Yes
Operating mode
STOP
Stop
No
Test o.k.?
operating mode switch
is in the top position or
start command in
WAGO-IO-PRO 32:
Online/Start or Online/Stop
Yes
RUN
PLC cycle
Reading inputs, outputs and times
Fieldbus data,
data of I/O modules
PLC program in the RAM
is processed
“I/O” LED
is shining
green
Writing outputs
Fieldbus start
behaviour as a coupler
Fieldbus data,
data of I/O modules
Operating system functions,
updating times
operating mode switch
Operating mode
RUN
Fig. 3-28: Controller operating system
WAGO-I/O-SYSTEM 750
DeviceNet
STOP is in the top position or
start command in
WAGO-IO-PRO 32:
Online/Start or Online/Stop
g012941d
84 •
Fieldbus Controller 750-806
Process Image
3.2.4 Process Image
After switching on, the Controller recognizes all I/O modules plugged into the
node which supply or wait for data (data width/bit width > 0). In nodes, analog
and digital I/O modules can be mixed.
The Controller produces an internal process image from the data width and the
type of I/O module as well as the position of the I/O modules in the node. It is
divided into an input and an output data area.
The data of the digital I/O modules is bit orientated, i.e. the data exchange is
made bit for bit. The analog I/O modules are all byte orientated I/O modules,
i.e. those where the data exchange is made byte for byte. These I/O modules
include, for example, the counter modules, I/O modules for angle and path
measurement as well as the communication modules.
Note
For the number of input and output bits or bytes of the individually activated
on I/O modules please refer to the corresponding I/O module description.
The data of the I/O modules is separated from the local input and output process image in the sequence of their position after the controller in the individual
process image.
In the respective I/O area, first of all analog modules are mapped, then all
digital modules, even if the order of the connected analog and digital modules
does not comply with this order. The digital channels are grouped, each of
these groups having a data width of 1 byte. Should the number of digital I/Os
exceed 8 bits, the Controller automatically starts another byte.
Note
A process image restructuring may result if a node is changed or extended. In
this case, the process data addresses also change in comparison with earlier
ones. In the event of adding modules, take the process data of all previous
modules into account.
The process image for the physical bus module data is identical with that of
the WAGO DeviceNet fieldbus Coupler.
With the Controller, the data of the PFC variables are filled into the process
image, separated according to input and output data.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Data Exchange
• 85
3.2.5 Data Exchange
With DeviceNet, the transmission and exchange of data is made using objects.
For a network access on the single objects, it is necessary to create a connection between the desired participants and to allocate connection objects.
The DeviceNet fieldbus Controller 750-806 can communicate via the UCMMPort (Unconnected Message Manager Port).
The UCMM-Port permits a dynamic connection via one or several connections from one or more clients.
The object configuration for the data transmission is defined by the Assembly
Object. The Assembly Object can be used to group data (e.g.: I/O data) to
form blocks (mapping) and send this data via one single communication connection. This mapping results in a reduced number of accesses to the network.
A differentiation is made between input and output assemblies.
An Input Assembly reads data from the application via the network or produces data on the network respectively.
An Output Assembly writes data to the application or consumes data from the
network respectively.
Various Assembly instances are permanently programmed (static assembly) in
the fieldbus Controller.
Further information
The Assembly instances for the static Assembly are described in chapter
4.5.1.1 "Assembly Instance".
In addition to the static assembly, dynamic assembly can also be used with the
fieldbus Controller. The dynamic assembly can be used to set up Assembly Instances in which process data from various application objects can be configured as required.
Further information
For information regarding the dynamic Assembly, please refer to chapter
3.2.7.4 "Dynamic Assembly".
WAGO-I/O-SYSTEM 750
DeviceNet
86 •
Fieldbus Controller 750-806
Data Exchange
3.2.5.1 Communication Interfaces
For a data exchange, the DeviceNet fieldbus Controller is equipped with three
interfaces:
• the interface to fieldbus (-master),
• the PLC functionality of the PFC (CPU) and
• the interface to the bus modules
Data exchange takes place between the fieldbus master and the bus modules,
between the PLC functionality of the PFC (CPU) and the bus modules as well
as between the fieldbus master and the PLC functionality of the PFC (CPU).
Data access of the PLC functionality of the PFC (CPU) is via an application related IEC 61131-3 program and independent on the fieldbus system.
Access from the fieldbus side is fieldbus specific.
3.2.5.2 Memory Areas
The Controller uses a memory space of 256 words (word 0 ... 255) for the
physical input and output data.
The Controller is assigned an additional memory space for mapping the PFC
variables defined according to IEC 61131-3. This extended memory space
(word 256 ... 511 each) is used to map the PFC variables behind the physical
process image.
The division of the memory spaces and the access of the PLC functionality
(CPU) to the process data is identical with all WAGO fieldbus Controllers.
Access is via an application related IEC 61131-3 program and independent on
the fieldbus system.
Access from the fieldbus side is fieldbus specific.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Data Exchange
• 87
programmable fieldbus controller
memory area
for input data
word 0
fieldbus
1
I/O modules
input
modules
word 255
word 256
3
PFC
input
variables
word 511
IEC 61131
program
CPU
memory area
for output data
word 0
2
output
modules
word 255
word 256
4
I
O
PFC
output
variables
word 511
Fig. 3-29: Memory areas and data exchange for a fieldbus Controller
g012434d
In its memory space word 0 ... 255, the Controller process image contains the
physical data of the bus modules.
1
The data of the input modules can be read by the CPU and from the fieldbus side.
2
In the same manner, writing to the output modules is possible from the
CPU and from the fieldbus side. The value of the last is written to the output while concurrent writing on an output.
Note
A concurrent writing on an output must be avoided.
Either by using instance 11 of the static assembly (see chapter 0 "
Additional Assembly Instances 10 and 11") or by using the dynamic assembly (see chapter 3.2.7.4 "Dynamic Assembly").
The PFC variables are filled in the memory space word 256 ... 511 of the process image.
3 The PFC input variables are written in the input memory space from the
fieldbus side and read by the CPU for further processing.
4 The variables processed by the CPU via the IEC 61131-3 program are filled
in the output memory space and can be read out by the master.
WAGO-I/O-SYSTEM 750
DeviceNet
88 •
Fieldbus Controller 750-806
Data Exchange
In addition, the Controller offers further memory spaces which, however, cannot be accessed from the fieldbus side:
RAM
The RAM memory is used to create variables not required for communication with the interfaces but for internal processing, such as
computation of results.
Retain
The retain memory is a non-volatile memory, i.e. all values are retained following a voltage failure. The memory management is automatic. In this memory area, flags for the IEC 61131-3 program are
filed together with variables without memory space addressing or
variables which are explicitly defined with "var retain".
Note
The automatic memory management can cause a data overlap. For
this reason, we recommend not to use a mix of flags and retain variables.
Code
memory
The IEC 61131-3 program is filed in the code memory. The code
memory is a flash ROM. Once the supply voltage is applied, the program is transmitted from the flash to the RAM memory. After an
error-free start-up, the PFC cycle starts when the operating mode
switch is turned to its upper position or by a start command from
WAGO-I/O-PRO 32.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Data Exchange
• 89
3.2.5.3 Addressing
3.2.5.3.1 Fieldbus Specific
Once the supply voltage is applied, the Assembly Object maps data from the
process image. As soon as a connection is established, a DeviceNet Master
(scanner) can address and access the data by "Class", "Instance" and "Attribute" or read and/or write the data using I/O connections.
Data mapping depends on the selected Assembly instance of the static assembly or on the application specific determination with the dynamic Assembly.
Further information
The Assembly Instances of the static Assembly are described in chapter
4.5.1.1 "Assembly Instance".
Further information
For information regarding the dynamic Assembly, please refer to chapter
3.2.7.4 "Dynamic Assembly".
Programmable fieldbus controller
memory area
for input data
Object directory()
word 0
1
I/O modules
input
modules
Connection
Object
Producer
fieldbus
master
Assembly
Object
Application
Object
InputAssemly
Digital I/O,
Analog I/O
Consumer
OutputAssemly
word 255
word 256
3
PFC
input
variables
IEC 61131
program
CPU
word 511
memory area
for output data
word 0
2
output
modules
word 255
word 256
4
I
O
PFC
output
variables
word 511
Fig. 3-2: Fieldbus specific data exchange for a DeviceNet fieldbus Controller
g012532d
Note
For the number of input and output bits or bytes of the individual I/O modules,
please refer to the corresponding I/O module description.
Note
A process image restructuring may result if a node is changed or extended. In
this case, the process data addresses also change in comparison with earlier
ones. In the event of adding a module, take the process data of all previous
modules into account.
WAGO-I/O-SYSTEM 750
DeviceNet
90 •
Fieldbus Controller 750-806
Data Exchange
Example for static assembly (default assembly):
The default assembly is:
Output1
(I/O Assembly Instance 1)
Input1
(I/O Assembly Instance 4)
In this example, the fieldbus node arrangement looks like this:
1) 1 fieldbus Controller DeviceNet (750-806)
2) 1 digital 4-channel input module (i. e. 750-402),
3) 1 digital 4- channel output module (z. B. 750-504),
4) 1 analog 2- channel output module with 2 bytes per channel (i. e. 750-552),
5) 1 analog 2- channel input module with 2 bytes per channel (i. e. 750-456),
6) 1 End module (750-600).
Input process image:
Default process data, input image (Assembly Class, Instance 4)
Byte
.7
.6
.5
.4
.3
0
low byte channel 1
1
high byte channel 1
2
low byte channel 2
3
high byte channel 2
2)
.1
.0
DI031)
DI021)
DI011)
DS08 2) DS07 2) DS06 2) DS05 2) DS04 2) DS03 2) DS02 2) DS01 2)
5
1)
DI041)
not used
4
.2
DI = Digital Input
DS = Diagnostic Status (The last byte in the input process image is the Diagnostic
Status Byte, DS01...DS08, see also: Object 0x64/Instance 1/Attr. 5)
DS01 =1: internal bus error (0x01)
DS02 =1: module communication error (0x02)
DS04 =1: module diagnostic (0x08)
DS08 =1: fieldbus error (0x80)
Output process image:
Default process data, output image (Assembly Class, Instance 1)
Byte
.7
.6
.5
.4
.3
0
low byte channel 1
1
high byte channel 1
2
low byte channel 2
3
high byte channel 2
not used
4
1)
DO041)
.2
.1
.0
DO031)
DO021)
DO011)
DO = Digital Output
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Data Exchange
• 91
3.2.5.3.2 Absolute Addressing
The CPU has direct access to the bus terminal data through absolute addresses. Addressing begins with the address 0 both with inputs and outputs.
The corresponding addresses for bits, bytes and double words (DWord) are
derived from the word addresses.
The structure of the process image is described in chapter 3.2.4 Process Image.
Addressing is done in this structure.
%IW0
|
%IWn
%In+1
|
%In+m
%QW0
|
%QWn
%Qn+1
|
%Qn+m
Input data
Output data
word-orientated data
bit-orientated data
word-orientated data
bit-orientated data
3.2.5.3.3 Calculate Addresses
The word address is the basis for calculation (word).
Bit Address
Word address .0 to .15
Byte Address
1st byte:
2nd byte:
DWord Address
lower section: Word address (even numbers) / 2
upper section: Word address (odd numbers) / 2, rounded off
2 x Word address
2 x Word address + 1
3.2.5.3.4 Address Range for I/O Module Data
Data size
Bit
0.0
...
0.7
0.8
...
0.15
1.0
...
1.7
1.8
...
1.15
...
254.0
...
254.7
254.8
...
254.15
255.0
...
255.7
255.8
...
255.15
Byte
0
1
2
3
...
508
509
510
511
Word
DWord
WAGO-I/O-SYSTEM 750
DeviceNet
Address range I/O module data
0
1
0
...
...
254
255
127
92 •
Fieldbus Controller 750-806
Data Exchange
3.2.5.3.5 Address Range for Fieldbus Variables
Data size
Address range fieldbus variables
Bit
256.0
...
256.7
256.8
...
256.15
257.0
...
257.7
257.8
...
257.15
...
510.0
...
510.7
510.8
...
510.15
511.0
...
511.7
511.8
...
511.15
Byte
512
513
514
515
...
1020
1021
1022
1023
Word
256
257
DWord
...
128
510
511
...
255
3.2.5.3.6 Address Range for Flags
Data size
Address range flags
Bit
0.0
...
0.7
0.8
...
0.15
1.0
...
1.7
1.8
...
1.15
...
4094.0
...
4094.7
4094.8
...
4094.15
4095.0
...
4095.7
4095.8
...
4095.15
Byte
0
1
2
3
...
8188
8189
8190
8191
Word
0
DWord
1
0
...
4094
...
4095
2047
All flags are non volatile (retain).
3.2.5.3.7 Example for Absolute Addresses
Data size
Inputs:
Bit
Byte
%IX14.0 ... 15
%IB28
Word
%IB29
%IB31
%IW15
%ID7
Outputs:
Bit
Byte
%IB30
%IW14
DWord
Data size
%IX15.0 ... 15
%QX5.0 ... 15
%QB10
%QB11
%QX6.0 ... 15
%QB12
%QB13
Word
%QW5
%QW6
DWord
%QD2 (oberer Teil)
%QD3 (unterer Teil)
%MX11.0 ... 15
%MX12.0 ... 15
Data size
Bit
Byte
Flags:
%MB22
%MB23
%MB24
%MB25
Word
%MW11
%MW12
DWord
%MD5 (upper part)
%MD6 (lower part)
The character 'X' for single bits can be deleted, e.g.%I14.0, %Q6.10, %M11.7
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Programming the PFC with WAGO-I/O-PRO 32
• 93
3.2.6 Programming the PFC with WAGO-I/O-PRO 32
Due to the IEC 61131 programming of the DeviceNet fieldbus Controller
750-806 you have the option to use the functionality of a PLC beyond the
functions of fieldbus Coupler 750-306.
An application program according to IEC 61131-3 is created using the programming tool WAGO-I/O-PRO 32 (order No.: 759-332/000-002).
This manual, however, does not include a description of how to program with
WAGO-I/O-PRO 32. In contrast, the following chapters are to describe the
special modules for WAGO-I/O-PRO 32 for you to utilize explicitly for programming the DeviceNet fieldbus Controller.
The description also explains transmitting the IEC 61131-3 program into the
Controller and loading a suitable communication driver.
More information
For a detailed description of how to use the software, please refer to the
WAGO-I/O-PRO 32 manual (order No.: 759-122 / 000-002).
3.2.6.1 WAGO-I/O-PRO 32 Library Elements
You are offered various libraries for different IEC 61131-3 programming applications in WAGO-I/O-PRO 32. They contain modules for universal use
and can, thereby, facilitate and speed up the creation of your program. As
standard, the library 'standard.lib' is available to you.
The library described in the following is specifically intended for DeviceNet
projects with WAGO-I/O-PRO 32:
• "DevNet. lib"
This library extends the fieldbus Controller 750-806 by the master function.
As a result, it can be programmed in the network as a DeviceNet Master.
Several libraries are loaded on the WAGO-I/O-PRO CD.
Having integrated this library, you have access to its POUs, data types and
global variables which can be used in the same manner as those defined by
yourself.
More information
For a detailed description of the POUs and the software operation, please
refer to the WAGO-I/O-PRO 32 manual (order No.: 759-122 / 000-002).
WAGO-I/O-SYSTEM 750
DeviceNet
94 •
Fieldbus Controller 750-806
Programming the PFC with WAGO-I/O-PRO 32
3.2.6.2 IEC 61131-3 Program Transfer
Program transfer from the PC to the Controller following programming of the
desired IEC 61131 application can be made in two different ways:
• via the serial interface or
• via the fieldbus.
One suitable communication driver each is required for both types.
More information
For information on the installation of the communication drivers as well as
details regarding the use of the software, please refer to the
WAGO-I/O-PRO 32 manual (order No.: 759-122 / 000-002).
3.2.6.2.1 Transmission via the Serial Interface
Use the WAGO communication cable to produce a physical connection via the
serial interface. This is contained in the scope of delivery of the programming
tool IEC 61131-3, order No.: 759-332/000-002, or can be purchased as an accessory under order No.: 750-920.
Connect the COMX port of your PC with the communication interface of your
Controller via the WAGO communication cable.
Warning
The communication cable 750-920 must not be connected or disconnected
while the coupler/controller is powered on!
A communication driver is required for serial data transmission. In WAGOI/O-PRO 32, this driver and its parameters are entered in the "Communication parameters" dialog.
1. Start the WAGO-I/O-PRO 32 software via ’Start/Programs’ or by double
clicking on the WAGO-I/O-PRO-32 symbol on your desk top.
2. In the "Online" menu click on the "Communication parameters" menu
point.
The dialog "Communication parameters" opens. The basic setting of this
dialog has not yet any entries.
3. In the selection window mark the desired driver on the right-hand dialog
side (i.e. "Serial RS232"), to configure the serial connection between PC
and the Controller).
4. In the center window of the dialog, the following entries have to appear:
- Parity:
Even
- Stop bits: 1
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Programming the PFC with WAGO-I/O-PRO 32
• 95
If necessary, change the entries accordingly.
You can now commence testing the Controller.
Note
To be able to access the Controller, ensure that the operating mode switch of
the Controller is set to the center or the top position.
5. Under "Online" click on the "Log-on" menu point to log into the Controller.
(The WAGO-I/O-PRO 32 server is active during online operation. The
communication parameters cannot be polled.)
6. If there is not a program in the Controller, a window appears asking
whether or not the program is to be loaded.
Confirm with "Yes".
Subsequently the current program will be loaded.
7. As soon as the program is loaded, you can start program via the "Online"
menu, menu point "Start".
At the right-hand end of the status bar, the system signals "ONLINE
RUNNING"."
8. To terminate the online operation, return via the "Online" menu and click
on the "Log-off" menu point.
3.2.6.2.2 Transmission via the Fieldbus
The field bus cable is the physical connection between the PC and the Controller. It is necessary to have a suitable communication driver for data transmission. This driver and how it is parametered is entered in
WAGO-I/O-PRO 32 in the "communication parameter" dialog.
Note
Transmission via the fieldbus is supported by UCMM. Here, for the download of the PFC program, WAGO-I/O-PRO 32 counts as a subscriber.
1. Start the WAGO-I/O-PRO 32 software via ’Start/Programs’ or by double
clicking on the WAGO-I/O-PRO-32 symbol on your desk top.
2. In the "Online" menu click on the "Communication parameters" menu
point.
The "Communication parameters" dialog opens.
3. Click on the “New” button to define a driver in the "Communication parameter" dialog
4. Enter any name and mark the driver "Hilscher PA Interface standard" in
the selection window of the dialog.
Subsequently confirm with "OK".
WAGO-I/O-SYSTEM 750
DeviceNet
96 •
Fieldbus Controller 750-806
Programming the PFC with WAGO-I/O-PRO 32
5. If necessary, change the entry accordingly in the center window of the dialog.
Note
Prerequisite for the access to the Controller is that the operating mode switch
of the Controller is in the center or top position.
6. Under "Online" click on the "Log-on" menu point to log into the Controller.
(During online operation, the WAGO-I/O-PRO 32 server is active. The
communication parameters cannot be polled.)
7. If there is not a program contained in the Controller, a window appears asking whether or not the program is to be loaded.
Confirm with "Yes".
Subsequently the current program is loaded.
8. As soon as the program is loaded, you can start the program via the "Online" menu, menu point "Start".
At the right-hand end of the status bar, the system signals "ONLINE
RUNNING".
9. To terminate the online operation, return via the "Online" menu and click
on the "Log-off" menu point.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Special DeviceNet Features of the Controller
• 97
3.2.7 Special DeviceNet Features of the Controller
3.2.7.1 Connection via the UCMM port
In contrast to the fieldbus Coupler 750-306 as a Group 2 Only Server, the DeviceNet Controller supports the dynamic connection via the UCMM port (Unconnected Message Manager Port).
For the Controller, the simultaneous set-up of 5 explicit and 5 dynamic I/O
connections, i.e. the connection with 5 subscribers, is possible.
3.2.7.2 Offline Connection Set
Due to the Offline Connection Set, the fieldbus node can be addressed via the
network when this node has been switched off because of a double MAC ID
and is in a Communication Fault status. After being addressed, the MAC ID of
the fieldbus Controller can be changed using the software.
3.2.7.3 DeviceNet Shutdown
The Device Shutdown allows the fieldbus node to log out from a control in a
defined manner if the node is switched off due to internal faults. This function
can be used in a targeted way in DeviceNet networks subject to very high
safety requirements, such as e.g. in the chemical industry or in semi-conductor
production.
3.2.7.4 Dynamic Assembly
An Assembly Object is used to group data (e.g. I/O data) to form blocks to be
sent as a single message. The static Assembly allows the user to access permanently pre-programmed Assembly Instances in the fieldbus Controller. The
dynamic Assembly, on the other hand, offers the possibility to set up Assembly Instances in which process data from various application objects can be
configured as required.
In addition to the I/O data transmission, the dynamic assembly can also be
used for a targeted selection of data which are to be transmitted explicitly via
the fieldbus, or those which are explicitly not to be transmitted via the fieldbus.
Attention
To set the pysical outputs with the PFC either use the dynamic assembly or
the instance 11 of the static assemblies. With this, you do not enter the physical outputs into the mapping in order to prevent the output data from being
transmitted and temporary overwritten by the fieldbus.
Further information
You can find more details in chapter 4.6.2.2.2 "Dynamic Assembly".
WAGO-I/O-SYSTEM 750
DeviceNet
98 •
Fieldbus Controller 750-806
Special DeviceNet Features of the Controller
3.2.7.5 Change MAC ID by SW
The MAC ID of the Controller can be changed via the network using the software (e.g. WAGO NETCON, RS NetWorx). For this purpose, the node address is stored in non-volatile memory. Should the address set at the DIP
switch differ from the one set via the network using the software, the I/O LED
changes its colour to orange.
To reset the software default address, the invalid address 64 is entered in class
3, instance 1, attribute 1.
Subsequently, the Controller has its MAC ID that is set at the DIP switch.
3.2.7.6 Heartbeat
The heartbeat function permits a node to cyclically transmit a so-called heartbeat message and, in this manner, to signal its communication ability to all
members in the network.
If a responsible heartbeat consumer does not receive a message within a predefined time (Heartbeat Consuming Time), this is registered as a heartbeat
fault. The relationship between producer and consumer of a Heartbeatmessage can be configured by entries in the object directory, so the time between two Heartbeat messages can be entered in Class 0x01, Instance 1, Attribut ID 10 (0x0A).
3.2.7.7 Bit-Strobe
The bit strobe I/O connection is always a 1 to n multicast connection.
In other words, a master can reach with its message all slaves supporting the
bit strobe command. The transfer takes place at the same time. In this manner
it is possible to synchronize the slaves.
The length of this master message is limited to 8 bytes. Each node address in
the net is assigned a bit within the 8 data bytes. The reaction of the slave
which bit is set is specific to the application. The reaction has to be defined
and it has to be known by the PLC. With its answer, each slave can return 8
bytes of data. The order of the answers depends on the reaction time of the
single slave and, in addition, it depends on the particular node address. If all
slaves would reply to the Bit-Strobe command at the same time, the order of
sending on the CAN bus would be determined by the node address (bit arbitration).
Further information
You can find more details in chapter 4.6.2.2.1 "Bit-Strobe".
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Configuration Software
• 99
3.2.8 Configuration Software
To allow a connection between the PLC and the fieldbus devices, the interface
modules have to be configured with the individual station file.
To this effect, the scope of the WAGO-I/O-SYSTEM 758 includes the
WAGO NETCON software intended for design and configuration, start-up and
diagnosis.
Further configuration software of different manufacturers include, for instance, RSNetWorx.
3.2.9 Starting-up DeviceNet Fieldbus Nodes
This chapter shows the step-by-step procedure for starting up a
WAGO DeviceNet fieldbus node.
Following this will be information for programming the PFC with WAGOI/O-PRO 32.
Attention
This description is given as an example and is limited to the execution of a
local start-up of an individual DeviceNet fieldbus node.
The procedure contains the following steps:
14.Connecting the PC and fieldbus node
15.Setting the MAC ID and baud rate
16.Configuration with static and dynamic Assembly
3.2.9.1 Connecting the PC and Fieldbus Node
1. Connect the assembled DeviceNet fieldbus node to the DeviceNet fieldbus PCB in your PC
via a fieldbus cable and start your PC.
The 24 V field bus supply is fed by an external fieldbus network power supply over the connections V+, V- of the 5-pin fieldbus connector (MCS Series 231).
2. Start your PC.
3.2.9.2 Setting the MAC ID and Baud Rate
1. Use the DIP switches 1...6 to set the desired node address (MAC ID). The binary significance
of the individual DIP switches increases according to the switch number.
ON
1 2 3 4 5
DIP switch
6 7 8
g012443x
Fig. 3-30 Example: Setting the MAC
ID 4 (DIP 3 = ON).
Value
1
2
3
4
5
20
6
25
21
22
23
24
DIP switches 7 and 8 are used to set the desired baud rate.
WAGO-I/O-SYSTEM 750
DeviceNet
100 • Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
Baud rate
ON
1 2 3 4 5
DIP7
DIP8
OFF
OFF
250 kBaud
ON
OFF
500 kBaud
OFF
ON
not allowed
ON
ON
125 kBaud
ON
6 7 8
1
2
3
4
5
6
7
8
g012541x
Fig. 3-31: Example: Setting the baud
rate 250 kBaud (DIP 7 = ON) of the
station with MAC ID 1.
*)
*)
Presetting
2. Then switch on the Controller supply voltage.
3.2.9.3 Configuration with Static and Dynamic Assembly
In this example, the software RSNetWorx Rev:3.00.00 of Allan-Bradley and
SLC500 with a 1747-SDN Scanner Module is used.
The inputs are mapped using the static Assembly and the outputs are mapped
with the dynamic Assembly.
The node in the example consists of the following I/O modules:
2
DI DI
402
402
3
4
5
6
DODO DODO DODO AI AI
7
8
AO AO
750-806
1
DI DI
516
516
516
467
550
600
Fig. 3-32: Example for a fieldbus node
g012553x
1. Starting Software and EDS file load
1. Start the configuration software RSNetWorx.
2. Load the EDS file "750-806_1.EDS" for the fieldbus Controller in RSNetWorx.
For this click on "Tools/ EDS Wizard" and choose the EDS-file to load.
Note
You can download the EDS file 750-806_1.EDS from the Internet under:
www.wago.com
3. Now follow the Wizard instructions.
2. Create a New Network
1. After the EDS file has been loaded in RSNetWorx, you can start establishing your network.
For this purpose, click in the tree structure located in the left-hand screen
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
• 101
window on the "Communication Adapter" folder.
A list of various sub-folders appears.
2. From the list of sub-folders, select the corresponding scanner available in
your network (for the present example, select "1747 SDN Scanner Module").
3. Take over the selected scanner into the right-hand graphics window with a
double-click or drag&drop.
The selected scanner is displayed in the right-hand screen window as a
symbol.
4. Now select the DeviceNet Controller 806 in the tree structure in the
"Communication Adapter" folder.
5. Also take this over into the right-hand graphic window with a double-click
or drag&drop.
The Controller is added to the right-hand screen window as a second symbol.
3. RX/TX Calculation for the Mapping
The correct setting of the TX/RX configuration is a prerequisite for the perfect
running of the DeviceNet network. For this purpose, the TX/RX configuration
must coincide with the node configuration.
For the entry into the RX and TX fields in RSNetworx, all input bit/bytes
count as a whole, as well as all output bits/bytes.
Here, individual bits are always grouped to form full bytes.
From the fieldbus master standpoint, the example node has the following data
configuration:
I/O module
RX
750-806 DeviceNet PFC
1 byte input status
750-402 4-channel input
4 bits input
750-402 4- channel input
4 bits input
TX
750-516 4- channel output
4 bits output
750-516 4- channel output
4 bits output
750-516 4- channel output
4 bits output
750-467 2 channel analog input
4 bytes input
750-550 2 channel analog output
750-600 end module
4 bytes output
-
PFC fieldbus input variables
PFC fieldbus output variables
WAGO-I/O-SYSTEM 750
DeviceNet
0 bytes input
4 bytes output
102 • Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
10 bytes
Sum
6 bytes
Note
PFC output variables are defined from the point of view of the programmable
fieldbus Controller. These are input variables from the point of view of the
fieldbus DeviceNet, which are added to the RX Settings. Accordingly, PFC
input variables are output variables for IEC 61131-3 access of the field bus.
For that reason they will be added to the TX Settings:
IEC 61131-3 input variable
= PFC output variable
PFC input variable
= IEC 61131-3 output variable
fieldbus
PLC
input
variables
PLC
output
variables
Programmable
fieldbus controller
PFC
input
variables
PFC
output
variables
Fig. 3-33: Zusammenhang SPS-Variablen and PFC-Variablen
g012444d
4. Static assembly for inputs
In the present example, the master/scanner is to have access to the physical inputs and to the 4 bytes PFC output variables.
The number of input data is complemented by 4 bytes of the PFC output variables during the static assembly for the TX configuration of the scanner.
1. To be able to parameterize the Controller, double-click on the graphic
symbol of the fieldbus node 750-806.
2. In the "General" register, you can assign the Controller any desired address.
To this effect, click in the input window for the address and enter the address in accordance with the address set at the Controller DIP switch.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
• 103
3. The RX/TX configuration can be entered in the "Parameters" register. For
this purpose, move to the "Groups" dialog box, down along the scroll bar,
and select "PLC fieldbus variables".
4. Do not change the value for the ID#37 "PLC fieldbus Input variables"
which is 0. Enter 4 for the ID#38 "PLC fieldbus Output variables".
5. Confirm the setting by clicking on the "OK" button.
6. Double-click on the scanner icon to start the configuration.
The dialog window "1797-SDN Scanner Module" opens.
7. Select the "Scanlist" register card.
8. Click on the button with the arrow to the right in order to take over the
DeviceNet Controller 750-806 in the left-hand window "Available Devices" into the "Scanlist" window.
9. Click on the "Edit I/O Parameters..." button.
10. Activate the poll function by clicking on the field located in front of
"Polled".
The field is now ticked which permits the entry for TX and RX.
11. Enter 6 bytes in the "TX-Size" dialog box. They are receipt bytes for the
inputs.
Enter 4 bytes for the PFC input variables in the "RX-Size" dialog box. The
number of these bytes results from the following determinations in the dynamic assembly for the outputs. This simultaneously defines that only the
PFC input variables and no physical outputs are to be written by the master.
12. Then click on the "OK" button to take over the parameters.
A window appears indicating that several I/O data will not be mapped.
Confirm the question of whether or not you wish to continue by clicking
on the "Yes" button.
WAGO-I/O-SYSTEM 750
DeviceNet
104 • Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
13. In the "1797-SDN Scanner Module" dialog window, select the "Input" register card. All inputs are mapped as digital inputs.
Mapped Inputs
I:1.0
1 Word Reserved for Scanner Module
I:1.1
1 Word Analog Input Channel 1
I:1.2
1 Word Analog Input Channel 2
I:1.3
1 Byte Status
I:1.4
1 Word IEC 61131-3 input variable 1
(or PFC output variable 1)
I:1.5
1 Word IEC 61131-3 input variable 2
(or PFC output variable 2)
| 1 Byte Digital Inputs
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
• 105
14. In the "1797-SDN Scaner Module" dialog window, select the "Output"
register card. All outputs are mapped as digital outputs.
Mapped Outputs
O:1.0
1 Word Reserved for Scanner Module
O:1.1
1 Word IEC 61131-3 output variable 1
(or PFC input variable 1)
O:1.2
1 Word IEC 61131-3 output variable 2
(or PFC input variable 2)
WAGO-I/O-SYSTEM 750
DeviceNet
106 • Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
5. Dynamic assembly for the outputs
The dynamic assembly is used to map those data which are to be transmitted
via the fieldbus. They are stored as classes, instances and attributes.
17.In the graphical display, click on the symbol of the fieldbus Controller 750-806
so that the symbol is marked.
18.Then click on the “Class Instance Editor...” menu point in the "Device" menu.
A window displaying a warning appears:
Note
This editor changes parameters in the Controller.
For this reason, ensure that all data is entered consistently either as hexadecimal or decimal. If the data number format is not consistent, data loss can result
up to a total functional failure of the Controller.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
• 107
19.Confirm the warning information by clicking on the "Yes" button.
The dialog window "Service Class Instance Attribute Editor" appears.
20.In the "Description" dialog box select the "Create" utility and enter the following values in the dialog boxes for the "Object Address":
- "Class": 4
– "Instance":
0
– "Attribute":
1.
Note
Do not click on the "ENTER" key, because this will close the dialog window
so that it has to be reopened.
21.Click on the "Execute" button to create the instance for the dynamic assembly.
If the setting was successful, the fieldbus node will send the instance number =
100 0.
If a fault has occurred, you will receive a fault message.
In this case, check the entries for class, instance and attribute, the DeviceNet
connection and the configuration.
22.In the "Description" dialog box, select the "Set Single Attribute" utility and enter the following values in the "Object Address" dialog boxes:
- "Class": 4
– "Instance":
64 (64 hexadecimal = 100 decimal)
– "Attribute":
2.
23.Click in the " Data Sent to the device" dialog box and enter the following values in hexadecimal:
10 00 06 00 20 A6 24 01 30 01 10 00 06 00 20 A6 24 02 30 01
WAGO-I/O-SYSTEM 750
DeviceNet
108 • Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
The path is described by:
0x20 CC (Class) 0x24 II (Instance) 0x30 AA (Attribute)
24.Click on the "Execute" button to define the mapping.
If the mapping was successful, the fieldbus node sends a “performance” confirmation.
If a fault has occurred, you will receive a fault message.
In the event of a communication or reply fault, check the DeviceNet connection
and whether or not the instance was correctly set.
25.Click on the "Close" button.
The dialog window is closed.
26.To parameterize the Controllers, double-click on the graphic symbol of the
fieldbus node 750-806.
27.Select the "Parameters" register and “All parameters” in the "Groups" dialog
box.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
• 109
1. Use the scroll bar to move down to the ID#13 and #ID14 addresses.
ID#13 is a pointer for the inputs (Default = 4).
This parameter is changed when the inputs are mapped for the master. This is not required
due to the fact that the inputs are only read and not written.
ID#14 is a pointer for the outputs (Default = 1).
This parameter is changed in order to point on the dynamic mapping of the
outputs that are mapped in the dynamic assembly instance 100dec.
(0x64hex).
2. Do not change the pre-set standard value 4 of the ID#13.
Enter 25604 decimal for the ID#14 to direct the pointer on the dynamic assembly output
mapping.
WAGO-I/O-SYSTEM 750
DeviceNet
110 • Fieldbus Controller 750-806
Starting-up DeviceNet Fieldbus Nodes
The value 25604 corresponds to the hexadecimal writing 0x6404.
04 (Low Byte) = Class type
64 (High Byte) = 100 decimal instance number
3. Change the value for the ID#39. Select "Dynamic created instances are stored in non volatile
memory", to retain the storage of the configuration for the Dynamic Assembly even following a voltage failure of the Controller.
4. To take over the pre-set parameters into the Controller, select the following parameter in the
right-hand control box in the "Parameters" register:
"All Values", then click on the "Download parameters to the device" symbol which is located
on the far right next to the dialog box.
5. Confirm the setting by clicking on the "OK" button.
The dialog window is closed.
6. Then switch the supply voltage of the Controller off and on again.
Now the fieldbus node is ready for networked communication.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
LED Display
• 111
3.2.10 LED Display
The Controller possesses several LEDs for on site display of the Controller
operating status or the complete node.
01 02
DeviceNet
OVERFL
A
RUN
B
MS
C
D
C
A
BUS OFF 24V 0V
NS
CONNECT
I/O
USR
Fig. 3-34: Display elements 750-806
g080602x
The module status (MS) and the network status (NS) can be displayed by the
top 4 LED’s. They react as described in the following tables.
Module status (MS)
OVERFL RUN
(red)
(green)
State of device
Meaning
off
off
off
off
on
blinking
no power
device operational
device in standby
blinking
on
off
off
minor fault
unrecoverable fault
blinking
blinking
device self testing
No power supply to the device.
The device operates correctly.
The device needs to be configured or has been partly
configured.
A minor fault has occurred. It exists a diagnostics.
The device is defective, needs to be serviced or
replaced.
The device performs a built-in check.
Table 3-3: Fault and status displays: MS
Network status (NS)
BUSOFF
(red)
CONNECT
(green)
State of device
Meaning
off
off
not powered, not online
off
blinking
online, not connected
off
on
link ok online, connected
blinking
off
connection time out
on
off
critical link failure
No power supply to the device / fieldbus supply /
DeviceNet cable not connected and „Duplicate MAC
ID detection“ is not yet completed.
The device operates correctly at the fieldbus. However, it has not yet been integrated by the scanner.
The device operates correctly at the fieldbus. At least
one connection to another device has been established.
A minor fault has occurred (e.g. EPR is unequal 0
during a polling connection, slave is not polled any
longer).
The device has detected a fault (duplicated MAC ID
check error). It is unable to perform any more functions in the network.
Table 3-4: Fault and status displays: NS
WAGO-I/O-SYSTEM 750
DeviceNet
112 • Fieldbus Controller 750-806
LED Display
3.2.10.1
Node status – Blink code from the 'I/O' LED
The ‘I/O‘-LED displays the communication status of the internal bus. Additionally, this LED is used to display fault codes (blink codes) in the event of a
system error.
LED
Meaning
Trouble shooting
I/O
Green
Off
Red
Red
Fieldbus coupler operating perfectly, Data cycle on the
internal bus
No data cycle on the internal bus
a) During startup of fieldbus controller:
Internal bus being initialized,
Startup displayed by LED flashing fast for approx.
1-2 seconds
b) After startup of fieldbus controller:
Errors, which occur, are indicated by three consecutive flashing sequences. There is a short pause
between each sequential flash.
Evaluate the fault message (fault code and
fault argument).
The controller starts up after switching on the supply voltage. The "I/O" LED
blinks. The "I/O" LED has a steady light following a fault free start-up.
In the case of a fault the "I/O" LED continues blinking. The fault is cyclically
displayed by the blink code.
Detailed fault messages are displayed with the aid of a blink code. A fault is
cyclically displayed with up to 3 blink sequences.
•
•
•
The first blink sequence (approx. 10 Hz) starts the fault display.
The second blink sequence (approx. 1 Hz) following a pause. The
number of blink pulses indicates the fault code.
The third blink sequence (approx. 1 Hz) follows after a further pause.
The number of blink pulses indicates the fault argument.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
LED Display
• 113
Switching on
the power supply
Coupler/Controller starts up
“I/O”-LED is blinking
No
Test o.k.?
Yes
“I/O” LED
1st flash sequence
(Introduction of the
error indication)
1st break
“I/O” LED
2nd flash sequence
Error code
(Number of flash cycles)
2nd break
“I/O” LED
3rd flash sequence
Error argument
“I/O”-LED is shining
(Number of flash cycles)
ready for operation
Fig. 3-35: Signalling the LED's node status
g012111e
After clearing a fault, restart the coupler by cycling the power.
I/O
Meaning
green
Data cycle on the internal bus
off
No data cycle on the internal bus
red
Controller hardware defective
red
blinks
When starting: internal bus is initialized
During operation: general internal bus fault
red
blinks cyclically
Fault message during internal bus reset and internal fault:
orange
MAC-ID is changed via SW and is different to the DIP switch setting
Fault message of the ‘I/O‘-LED
1 st flash sequence: Start of the Fault message
2 nd flash sequence: Fault code
3 rd flash sequence: Fault argument
WAGO-I/O-SYSTEM 750
DeviceNet
114 • Fieldbus Controller 750-806
LED Display
Fault code 1: "Hardware and Configuration fault"
Fault argument
Fault description
Trouble shooting
-
Invalid checksum within the
parameter range of fieldbus coupler
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
1
Overflow of the internal buffer
memory for the inline code
Turn off the power supply of the
node, reduce number of I/O modules and turn the power supply on
again. If the error still exists,
exchange the bus coupler.
2
I/O module(s) with unsupported
data type
3
Unknown program module type
of the flash program memory
4
Fault when writing data within
the flash memory
5
Fault when deleting a flash sector
6
Changed I/O module configuration determined after
AUTORESET
Fault when writing data in the
serial EEPROM
Detect faulty I/O module as follows: turn off the power supply.
Place the end module in the middle of the fieldbus node. Turn the
power supply on again.
– If the LED is still blinking, turn
off the power supply and place
the end module in the middle of
the first half of the node (towards
the coupler).
– If the LED doesn’t blink, turn
off the power supply and place
the end module in the middle of
the second half of the node (away
from the coupler).
Turn the power supply on again.
Repeat this procedure until the
faulty I/O module is detected.
Replace the faulty I/O module.
Ask about a firmware update for
the fieldbus coupler.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
Restart the fieldbus coupler by
turning the power supply off and
on again.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
7
8
Invalid Hardware Firmware
combination
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
LED Display
9
10
11
12
13
14
Invalid checksum within the
serial EEPROM
Turn off the power supply of the
node, exchange the bus coupler
and turn the power supply on
again.
serial EEPROM initialization
Turn off the power supply of the
fault
node, exchange the bus coupler
and turn the power supply on
again.
Fault when reading out data from Turn off the power supply of the
the EEPROM
node, exchange the bus coupler
and turn the power supply on
again.
Timeout when writing data in the Turn off the power supply of the
EEPROM
node, exchange the bus coupler
and turn the power supply on
again.
- not used Maximum number of Gateway or Turn off the power supply of the
Mailbox I/O modules exceeded
node, reduce number of Gateway
or Mailbox I/O modules and turn
the power supply on again.
Fault code 2 -not usedFault argument
-
WAGO-I/O-SYSTEM 750
DeviceNet
• 115
Fault description
Trouble shooting
not used
-
116 • Fieldbus Controller 750-806
LED Display
Fault code 3: "Internal bus protocol fault"
Fault argument
-
Fault description
Trouble shooting
Internal bus communication
malfunction; faulty device can’t
be detected
If the fieldbus node comprises
internal system supply modules
(750-613), make sure first that the
power supply of these modules is
functioning. This is indicated by
the status LEDs. If all I/O modules
are connected correctly or if the
fieldbus node doesn’t comprise
750-613 modules you can detect
the faulty I/O module as follows:
turn off the power supply of the
node. Place the end module in the
middle of the fieldbus node. Turn
the power supply on again.
– If the LED is still blinking, turn
off the power supply and place the
end module in the middle of the
first half of the node (towards the
coupler).
– If the LED doesn’t blink, turn off
the power supply and place the end
module in the middle of the second
half of the node (away from the
coupler).
Turn the power supply on again.
Repeat this procedure until the
faulty I/O module is detected.
Replace the faulty I/O module. If
there is only one I/O module left
but the LED is still blinking, then
this I/O module or the coupler is
defective. Replace defective component.
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
LED Display
• 117
Fault code 4: "Internal bus physical fault"
Fault argument
-
n*
WAGO-I/O-SYSTEM 750
DeviceNet
Fault description
Trouble shooting
Error in internal bus data communication or interruption of the
internal bus at the coupler
Turn off the power supply of the
node. Place an I/O module with
process data behind the coupler
and note the error argument after
the power supply is turned on. If
no error argument is given by the
I/O LED, replace the coupler.
Otherwise detect faulty I/O module as follows: turn off the power
supply. Place the end module in
the middle of the fieldbus node.
Turn the power supply on again.
– If the LED is still blinking, turn
off the power supply and place the
end module in the middle of the
first half of the node (towards the
coupler).
– If the LED doesn’t blink, turn off
the power supply and place the end
module in the middle of the second
half of the node (away from the
coupler).
Turn the power supply on again.
Repeat this procedure until the
faulty I/O module is detected.
Replace the faulty I/O module.
If there is only one I/O module left
but the LED is still blinking, then
this I/O module or the coupler is
defective. Replace defective component.
Turn off the power supply of the
Interruption of the internal bus
after the nth process data module. node, exchange the (n+1)th process
data module and turn the power
supply on again.
118 • Fieldbus Controller 750-806
LED Display
Fault code 5: "Internal bus initialization fault"
Fault argument
n*
Fault description
Trouble shooting
Error in register communication
during internal bus initialization
Turn off the power supply of the
node and replace nth process data
module and turn the power supply
on again.
Fault code 6 -not usedFault argument
-
Fault description
Trouble shooting
not used
-
Fault code 7 -not usedFault argument
-
Fault description
Trouble shooting
not used
-
Fault code 8 -not usedFault argument
-
Fault description
Trouble shooting
not used
-
Fault code 9 "CPU Trap Error"
Fault argument
Fault description
Trouble shooting
1
Illegal Opcode
2
Stack overflow
Error in the program sequence.
Contact the WAGO I/O-Support
3
Stack underflow
4
NMI
Fault code 10: "PLC program fault "
Fault argument
Fault description
Trouble shooting
1
Invalid Offset address for digital
inputs
Correct the Offset address in the
associated function block.
2
Invalid Offset address for digital
outputs
Correct the Offset address in the
associated function block.
Fault code 11: "Gateway-/Mailbox I/O module fault"
Fault argument
Fault description
Trouble shooting
1
Maximum number of Gateway
modules exceeded
Turn off the power supply of the
node, reduce number of Gateway
modules and turn the power supply
on again.
2
Maximum size of Mailbox exceeded
Reduce the Mailbox size.
3
Maximum size of process image Reduce the data width of the
exceeded due to the put Gateway Gateway modules.
modules
* The number of blink pulses (n) indicates the position of the I/O module. I/O modules
without data are not counted (e.g. supply module without diagnosis)
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
LED Display
• 119
Example for a fault message; Fault: The 13th I/O module has been removed
3.2.10.2
1.
The "I/O" LED starts the fault display with the first blink sequence (approx. 10
flashes/second).
2.
The second blink sequence (1 flash/second) follows the first pause. The "I/O" LED
blinks four times and thus signals the fault code 4 (internal bus data fault).
3.
The third blink sequence follows the second pause. The "I/O " LED blinks twelve
times. The fault argument 12 means that the internal bus is interrupted after the 12th
I/O module.
Supply voltage status
The two green LED’s in the coupler supply section, display the status of the
supply voltage. The left LED (A) indicates the status of the 24 V supply for
the coupler. The right hand LED (‘B‘ or ‘C‘) displays the status of the field
side supply (i.e., the power jumper contacts).
LED
Meaning
Trouble shooting
A
Green
Operating voltage for the system exists.
OFF
No operating voltage for the system.
Check the supply voltage (24V
and 0V).
B or C
Green
Operating voltage for the power jumper
contacts exists.
OFF
No operating voltage for the the power
jumper contacts.
WAGO-I/O-SYSTEM 750
DeviceNet
Check the supply voltage (24V
and 0V).
120 • Fieldbus Controller 750-806
Technical Data
3.2.11 Technical Data
System data
Max. no. of nodes
64 with scanner
Max. no. of I/O points
ca. 6000 (depends on master)
Transmission medium
shielded Cu cable,
trunk line: AWG 15, 18 (2x 0.82mm2 +2x1.7mm2)
drop line: AWG 22, 24 (2x0.2mm2 +2x0.32mm2)
Max. length of bus line
100 m ... 500 m
(baud rate dependent / cable dependent)
Baud rate
125 kBaud, 250 kBaud, 500 kBaud
Bus coupler connection
5-pole male connector, series 231 (MCS)
female connector 231-305/010-000/050-000
is included
Programming
WAGO-I/O-PRO 32
IEC 61131-3
IL, LD, FBD, ST, FC
Standards and approvals
UL
E175199, UL 508
E198726, UL 1604
Clas I Div2 ABCD T4A (applied for)
DEMKO
02ATEX132273 X
II 3 GD EEx nA II T4
Conformity marking
CE
Accessories
EDS-Dateien
Download: www.wago.com
Miniature WSB quick marking system
Technical data
Max. number of I/O modules
64
Fieldbus
Input process image
max. 1024 Byte
Output process image
max. 1024 Byte
Input variables
max. 512 Byte
Output variables
max. 512 Byte
Program memory
128 kByte
Data memory
64 kByte
Non-volatile memory
8 kByte (retain)
Cycle time
< 3 ms for 1,000 statements /256 dig. I/Os
Configuration
via PC or control
WAGO-I/O-SYSTEM 750
DeviceNet
Fieldbus Controller 750-806
Technical Data
• 121
DeviceNet features
Polled I/O Message Connection
Strobed I/O Message Connection
Change of State / Cyclic Message Connection
UCMM Device, expandable to master with DevNet.lib
Voltage via power jumper contacts
DC 24 V (-15 % / + 20 %)
Current consumption
- via power supply terminal
- via CAN interface
< 500 mA at 24 V
< 120 mA at 11 V
Efficiency of the power supply
87 %
Internal power consumption
350 mA at 5 V
Total current for I/O modules
1650 mA at 5 V
Isolation
500 V system/supply
Voltage via power jumper contacts
DC 24 V (-15 % / + 20 %)
Current via power jumper contactmax
DC 10 A
Dimensions (mm) W x H x L
51 x 65* x 100 (*from top edge of mounting rail)
Weight
ca. 195 g
EMC interference resistance
acc. to EN 50082-2 (96)
EMC interference transmission
acc. to EN 50081-2 (94)
WAGO-I/O-SYSTEM 750
DeviceNet
122 • Description
Technical Data
4 DeviceNet
4.1 Description
DeviceNet is a networking concept in the device level based on the serial bus
system CAN (Controller Area Network). It is particularly distinguished by the
problem-free addition and removal of devices, from simple light barriers up to
complex motor controls during operation. DeviceNet is mainly used in industrial automation and for robot controls.
The Data Link Layer, i.e. the physical and data storage layer, is defined in the
CAN specification. The telegram architecture is described. However, there is
no information about the application layer.
This is where DeviceNet comes into play. It describes the defined meaning of
the data transmitted in the application layer.
The Open DeviceNet Vendor Association (abridged: ODVA) is the user organisation for DeviceNet. In a specification, the ODVA DeviceNet is defined
as a uniform application layer and it lays down technical and functional features for device networking.
A maximum of 64 fieldbus nodes can be operated in one DeviceNet network.
The extension of the network depends on the selected baud rate (125 kBaud,
250 kBaud or 500 kBaud).
In contrast to other fieldbus systems, CAN does not address the modules connected to the bus but identifies the messages. Whenever the bus is free, subscribers are allowed to send messages. Each bus subscriber decides on its own
when it wants to send data or instigate other bus subscribers to send data. This
permits a communication without a bus master assembly group.
Bus conflicts are solved in that the messages are assigned a certain priority.
This priority is defined by the CAN identifier, called Connection ID in DeviceNet. The following rule applies: the smaller the identifier, the higher the
priority.
A general distinction between high priority process messages (I/O Messages)
and low priority management messages (Explicit Messages) is done before.
Messages having a data length of more than 8 bytes can be fragmented.
The communication with DeviceNet occurs always connection-referenced
(connection based). All data and functions of a device are described by means
of an object model. Therefore, for a message exchange directly after switching
on a device, the connections to the desired subscriber have to be established
first and communication objects be created or allocated. Message distribution
is according to the broadcast system, data exchange according to the producer
consumer model.
A transmitting DeviceNet node produces data that is either consumed via a
point-to-point connection (1 to 1) by one receiving node, or via a multicast
connection (1 to n) by several receiving nodes.
WAGO-I/O-SYSTEM 750
DeviceNet
Network Architecture
Transmission Media
• 123
Further information
The Open DeviceNet Vendor Association (ODVA) provides further documents in the Internet under: http://www.odva.org
4.2 Network Architecture
4.2.1 Transmission Media
4.2.1.1 Type of Cable
A bus medium forms the basis for the physical realization of a network using
DeviceNet.
According to the line specification, a double 2-conductor twisted pair cable
(twisted pair, screened cable) is recommended to be used as a medium.
It consists of two screened twisted pair cables with a wire in the middle of the
cable. Further screening extended at the outside.
The blue and the white twisted pair cable is used for signal transmission, the
black and red one for the supply voltage.
4.2.1.2 Cable Types
The DeviceNet bus is configured using a remote bus cable as the trunk line
and several drop lines.
For this purpose, the DeviceNet specification distinguishes between 2 cable
types:
• Thick Cable
For the trunk line of maximum 8 A or for networks extending over more
than 100 m.
The trunk line topology is linear, i.e. the remote bus cables are not further
branched. On each end of the remote bus cable, terminating resistors are
required.
• Thin Cable
For drop lines with maximum 3 A or for networks extending less than
100 m.
One or more nodes can be connected to the drop lines, in other words,
branching is permitted here. The length of the individual drop lines is
measured from the branching point of the node and can be up to 6 m. The
entire length of the drop line depends on the Baud rate.
WAGO-I/O-SYSTEM 750
DeviceNet
124 • Network Architecture
Cabling
Note
If possible, route the data line separately from all high current carrying cables.
Further information
For a detailed specification regarding the cable types, please refer to the
INTERNET under: http://www.odva.org.
4.2.1.3 Maximum Bus Length
In the following table, the permitted cable length is represented in dependence of the Baud
rate. Here, a differentiation is made between the maximum length for a transmission using a
thick and a thin cable.
Baud rate
Bus length
Thick + Thin Cable
LThin ≤ 100 m (328 ft)
500 kbit/s
LTick +
250 kbit/s
LTick + 2,5 • LThin ≤ 250 m (820,2 ft)
125 kbit/s
LTick + 5 • LThin ≤ 500 m (1640,4 ft)
Tap line length
only
Thick
Cable
only
Thin
Cable
maximal
cumulated
100 m
(328 ft)
250 m
(820,2 ft)
500 m
(1640,4 ft)
100 m
(328 ft)
100 m
(328 ft)
100 m
(328 ft)
6 m (19,6 ft)
39 m (127,9 ft)
6 m (19,6 ft)
78 m (255,9 ft)
6 m (19,6 ft)
156 m (511,8 ft)
Tab. 4-1: Maximum bus length dependent on the set Baud rate
When specifying the maximum cable lengths, it is made sure that communication is possible between two nodes located at maximum distance to each other
(worst case).
4.2.2 Cabling
The connection of a WAGO fieldbus node to the DeviceNet bus cable is made
by the supplied 5-pole plug (Multi Connector 231).
V+
Fieldbus
connection
Series 231
(MCS)
CAN_High
drain
CAN_Low
V-
Fig. 4-1: Plug assignment for the fieldbus connection
For wiring using a screened cable, the plus is assigned the connections V+, Vfor the voltage supply and with CAN_High, CAN_Low for data transmission.
The 24 V field bus supply is fed by an external fieldbus network power supply.
WAGO-I/O-SYSTEM 750
DeviceNet
Network Architecture
Cabling
• 125
CAN_High and CAN_Low are two physically different bus levels.
The cable screen is connected to the drain connection.
This is terminated with a 1 MΩ resistor to the DIN rail via the clip on the bottom of the Coupler/Controller. The DIN rail must then be directly connected
to the Grounding Stud that must be connected to Earth Ground. We strongly
recommend a central Earth Ground for the entire DeviceNet Bus conductor
screening. A low Ohm connection of the screening on PE terminal can only be
made externally.
Note
WAGO offers the screen connection system (series 790) for an optimum connection between fieldbus cable screening and functional earth.
Each DeviceNet node forms the differential voltage UDiff with: UDiff =
UCAN_High - UCAN_Low. using the bus levels CAN_High and CAN_Low.
Differential signal transmission offers the advantage of an insensitivity compared to common mode malfunctions and ground offset between the nodes.
Note
At its conductor ends, the bus cable must always be connected with a matching resistor of 120 Ohm to avoid reflections and, as a result, transmission
problems.
This is also required for very short conductor lengths.
The CAN bus is a 2-wire bus and bus error management can detect a cable
break or a short-circuit by the asymmetric operation.
Further information
The CiA provides documents regarding specifications, especially cable specifications on the Internet under:
http://www.can-cia.de
WAGO-I/O-SYSTEM 750
DeviceNet
126 • Network Architecture
Network Topology
4.2.3 Network Topology
To build a simple DeviceNet network, you need a scanner (PC with a DeviceNet fieldbus PCB card), a connection cable and a DC 24 V power pack to
ensure the power supply in addition to a DeviceNet fieldbus node.
The CANopen network is constructed as a line structure with matching resistors (120 Ohm).
120
Termination
120
Termination
WAGO
I/ O
Scanner
Busnetzteil
In systems accommodating more than two stations, all subscribers are wired in
parallel. Node connection to the remote bus cable (trunk line) is made by
means of drop lines. For this purpose, the bus cable has to be looped without
interruption. A maximum length of 6 m for a drop line should not be exceeded.
The following is a topology example:
Power Supply
WAGO-I/O-SYSTEM 750
DeviceNet
Network Architecture
Network Grounding
• 127
WAGO Kontakttechnik GmbH has developed a Multi-Port DeviceNet Tap to
connect the nodes to permit the connection of remote bus cables and drop lines
using the CAGE CLAMP® technology. This achieves a reliable, fast and vibration and corrosion resistant connection.
The DeviceNet taps are available in 2 designs.
Article
Description
810-900/000-001
Enclosed design with connection possibilities for 6 lines.
The housing provides a protection in difficult environmental conditions.
810-901/000-001
Open design to which 2 drop lines and 2 remote bus lines
(trunk lines) can be connected.
All subscribers in the network communicate at the same Baud rate. The bus
structure permits the interference-free connection and disconnection of stations or a stepped start-up of the system.
Future extensions have no influence on the stations already in operation.
Should a subscriber fail or be added to the network as a new one, it is automatically deteced by the system.
4.2.4 Network Grounding
The devices can either be power supplied via the DevicNet bus or have their
own power supply.
Prerequisite being, however, that the network is only grounded at one point.
Preferably, grounding is in the network center (V and screen drain with round
media) to optimize the capacity and minimize interference.
Not permitted are ground loops via devices that are not disconnected from the
power supply. The device must either be insulated or, if this is not possible,
the power must be correspondingly disconnected in the device.
4.2.5 Interface Modules
In a network, all WAGO DeviceNet fieldbus nodes are delivered to operate as
slaves. The master operation is taken over by a central control system, such as
PLC, NC or RC.
Note
The programmable fieldbus Controller 750-806 can assume the master operation when being extended by the "DevNet.lib" library.
The connection to fieldbus devices is made via interface modules.
As an interface module, WAGO offers the PC interface PCBs for DeviceNet,
ISA DeviceNet Master 7KByte (order No. 758-340), PC104 DeviceNet Master 7KByte D-Sub,straight, angled (order No. 758-341) and PCI DeviceNet
Master 7 Kbyte (order No. 758-342) from the WAGO-I/O-SYSTEM 758 Series.
WAGO-I/O-SYSTEM 750
DeviceNet
128 • Network Communication
Objects, Classes, Instances and Attributes
Other interface modules for programmable logic controls (PLCs) are also offered by other manufacturers.
4.3 Network Communication
4.3.1 Objects, Classes, Instances and Attributes
Protocol processing of DeviceNet is object oriented. Each node in the network
is represented as a collection of objects. In the following, several terms connected with them are defined:
• Object:
Object is an abstract representation of individual components within a device belonging to each other. It is defined by its data or attributes, its external functions or services available, and by its defined behaviour.
• Class:
A class includes objects of a product belonging together, it is organized in
instances, e.g. Identity Class, DeviceNet Class.
• Instance:
An instance is composed of various variables (attributes). Differing instances of a class have the same services, the same behaviour and the same
variables (attributes). However, they can have different variable values,
e.g. different connection instances: Expilict Message, Poll I/O or BitStrobe connection instance.
• Attributes:
The attributes represent data provided by a device via DeviceNet. They
contain the current values, e.g. a configuration of an input, such as, for instance Vendor ID, Device Type or Product Name.
• Service:
Services can be applied to classes and attributes. They perform defined actions, e.g. reading of variables (attributes) or resetting a class.
• Behaviour:
The behaviour defines how a device reacts as a consequence of external
events, such as changed process data, or as a consequence of internal
events, such as expiring timers.
WAGO-I/O-SYSTEM 750
DeviceNet
Module Characteristics
Communication Model
• 129
4.4 Module Characteristics
The I/O module is defined by vendor ID and device type.
Vendor ID
0x28 (40)
Device Type
0x0C (12), Communication Adapter
4.4.1 Communication Model
4.4.1.1 Message Groups
CAN messages are divided into several groups in order to achieve different
priorities.
• message group 1 serves to exchange I/O data via I/O messages
• message group 2 is reserved for Master/Slave applications
• message group 3 serves to exchange configurations data via explicit messages
• message group 4 is reserved for system administration (i. e. Offline Connection Set)
The CAN Identifier (Connection ID) and with it the priority is built via different message groups and the MAC ID.
4.4.1.2 Message Types
DeviceNet has 2 types of messages:
• I/O Messages and
• Explicite Messages
4.4.1.2.1 I/O Messaging
I/O messages are sent by a node and can be received by one or several other
nodes. Only I/O data is transmitted and no protocol data is specified by this
way.
4.4.1.2.2 Explicit Messaging
Explicit messages are sent directly from one node to another. They consist of a
request and an answer. Therefore services can be requested directly from another node. The data field consists of the service identification and the destination address. The format of the explicit messages is defined. Via explicit messages devices can be configured or a dynamic built-up of message connections
can be made.
WAGO-I/O-SYSTEM 750
DeviceNet
130 • Process data and Diagnostic Status
I/O Messaging Connections
4.4.2 I/O Messaging Connections
The transfer or exchange of process data between the scanner and the I/O device is made via a „Polled I/O Connection“, „Change of State/Cyclic“ or „Bit
Strobe“.
Polled I/O Connection
Slaves are cyclically polled by the master.
Strobe Function
All slaves are polled by the master by means of
a command.
Change of State
Messages are transmitted either cyclically by
the master or the slave, or in the event of a state
change.
4.5 Process data and Diagnostic Status
The data is transmitted between master and slave in the form of objects, a differentiation being made between input and output objects. The object architecture is defined by assembly objects which serve to group attributes of differing
application objects. I/O data of different objects can, for this reason, be
grouped to form a data block and transmitted by a message connection.
4.5.1 Process Image
The process image is differentiated according to input and output process images. The assembly object makes a statically configured process image available in the instances 1 ... 9.
The desired process image can be selected by setting the Produced Connection
Path and the Consumed Connection Path of the individual I/O connections
(Poll, Bit Strobe, Change of State or Change of Value).
The architecture of the individual instances of the assembly object is described
in the following.
WAGO-I/O-SYSTEM 750
DeviceNet
Process data and Diagnostic Status
Process Image
• 131
4.5.1.1 Assembly Instances
Permanently pre-programmed (static) assemblies in the device permit an easy
and rapid transmission of input and output images from the fieldbus Coupler/Controller to the master. For this purpose, various assembly instances are
provided in the fieldbus Coupler/Controller:
Output 1 (I/O Assembly Instance 1):
The entire output data image is transmitted from the master to the Controller
via the corresponding I/O message connection. In this case, the data length
corresponds to the number of output data in bytes. Analog output data come
before digital output data.
Output 2 (I/O Assembly Instance 2):
The digital output data image is transmitted from the master to the Controller
via the corresponding I/O message connection. The data length is equivalent
to the number of digital output data and is rounded up to full bytes.
Output 3 (I/O Assembly Instance 3):
The analog output data image is transmitted from the master to the Controller
via the corresponding I/O message connection. The data length is equivalent
to the number of analog output data in bytes.
Input 1 (I/O Assembly Instance 4):
The entire input data image and one status byte are transmitted to the master
via the corresponding I/O message connection. The data length is equivalent
to the number of input data in bytes and one status byte.
Input 2 (I/O Assembly Instance 5):
The digital input data image and one status byte are transmitted to the master
via the corresponding I/O message connection. The data length is equivalent
to the number of digital input data and rounded up to full bytes. In addition, a
status byte is inserted.
Input 3 (I/O Assembly Instance 6):
The analog input data image and one status byte are transmitted to the master
via the corresponding I/O message connection. The data length is equivalent
to the number of analog input data in bytes and one status byte.
Input 1 (I/O Assembly Instance 7):
The entire input data image is transmitted to the master via the corresponding
I/O message connection. The data length is equivalent to the number of input
data in byte.
WAGO-I/O-SYSTEM 750
DeviceNet
132 • Process data and Diagnostic Status
Process Image
Input 2 (I/O Assembly Instance 8):
The digital input data image is transmitted to the master via the corresponding
I/O message connection. The data length is equivalent to the number of digital
input data and is rounded up to full bytes.
Input 3 (I/O Assembly Instance 9):
The analog input data image is transmitted to the master via the corresponding
I/O message connection. The data length is equivalent to the number of analog
input data in bytes.
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
EDS Files
• 133
4.6 Configuration / Parametering with the Object Model
4.6.1 EDS Files
In DeviceNet, the capacity characteristics of the devices are documented by
the manufacturers in the form of an EDS file (Electronic Data Sheet) and
made available to the user.
Architecture, contents and coding of the EDS files are standardized which
permits design and configuration with devices of different manufacturers.
EDS file for I/O module 750-806
750-806_1.EDS *)
*) _1 indicates that this EDS file is valid for Controllers with firmware major version 1.
The EDS file is read by the configuration software and corresponding settings
transmitted. For required entries and handling steps for this purpose, please refer to the software user manuals.
Further information
ODVA informs about the EDS files of all listed manufacturers.
http://www.odva.org
EDS and symbol files to configure the I/O modules are available under the
order numberr 750-912 on a floppy disk or on the WAGO INTERNET homepage.
http://www.wago.com
WAGO-I/O-SYSTEM 750
DeviceNet
134 • Configuration / Parametering with the Object Model
Object Model
4.6.2 Object Model
For network communication, DeviceNet uses an object model describing all
device functions and data.
System Support Objects (general Management Objects)
•
•
Identity Object
Message Router Object
Communication Objects (Communications Objects for Data Exchange)
•
•
DeviceNet Object
Connection Object
Application Objects
(Application Objects, to determine device function and/or configuration)
•
•
•
Application Object(s)
Assembly Object
Parameter Object
Tabelle 4-1: Object model
Communication can be made exclusively connection oriented. For access by
the network to the individual objects, first of all make connections between
the desired subscribers and provide, or allocate, connection objects.
Data Type
USINT
Unsigned Short INTeger (8 Bit)
UINT
Unsigned INTeger (16 Bit)
USINT
Unsigned Short INTeger (8 Bit)
UDINT
Unsigned Double INTeger (32 Bit)
BOOL
Boolean, True (1) or False (0)
STRUCT
Structure of ...
ARRAY
Array of ...
Note
In the following, the object model for the fieldbus Coupler 750-306 and the
fieldbus Controller 750-806 are listed. The explicit supplements to the fieldbus
Controller 750-806 can be taken from the following chapter.
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
• 135
4.6.2.1 Object Model for Coupler 750-306 and Controller 750-806
4.6.2.1.1 Classes of Coupler and Controller:
Object
Identity
Message Router
DeviceNet
Class
0x01
0x02
0x03
Instance
1
1
1
Assembly
0x04
9
Connection class
Acknowledge handler
0x05
0x2B
3
1
Coupler configuration
object
Discrete input point
Discrete output point
Analog input point
Analog output point
0x64
1
Description
Device type, vendor ID, serial number etc.
Routes explicit messages to the proper destination.
Maintains the physical connection to DeviceNet. This object
also allocates/deallocates the Master/Slave connection set.
Allows Data transmission of different objects over a single
connection, by binding attributes of multiple objects.
Allows explicit messages to be conducted.
The Acknowledge Handler Object is used to manage the
reception of messages acknowledgements. This object communicates with a message producing application object
within a device. The Acknowledge Handler Object notifies
the producing application of acknowledge reception, acknowledge timeouts amd production retry limit.
Coupler and module configuration
0x65
0x66
0x67
0x68
0...255
0...255
0...255
0...255
Digital input channel objects
Digital output channel objects
Analog input channel objects
Analog output channel objects
4.6.2.1.2 Identity Class (0x01):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
Name
Data type
Description
Value
Revision
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation
is based.
0x01
Name
Data type
Description
Vendor
Device
Type
Product
Code
UINT
UINT
Identification of vendor
Indication of general type of
product
Identification of particular
product of an individual vendor
Default
Value
40 (0x28)
12 (0x0C)
Revision
Major/
Minor
Status
Serial_
number
Product
name
Stuct:
USINT,
USINT
WORD
UDINT
Revision of the item the Identity
object represents
SHORT_
STRING
(num,char
char...)
Human readable identification
Instance 1:
Attribute
ID
1
2
Used in
buscoupler
required
required
Access
rule
get
get
3
required
get
4
required
get
5
6
required
required
get
get
7
required
get
UINT
status of device
Serial number of device
i. e. 306
(0x132)
for the
750-306
i. e. {3;0}
for the
750-306
i. e.
„WAGO
750-306 V
3.0)“
for the
750-306
Services:
Service Code
0x0E
0x05
WAGO-I/O-SYSTEM 750
DeviceNet
Service Name
Get_Attribute_Single
Reset
Description
Returns the contents of the specified attribute
Invokes the reset service for the device
136 • Configuration / Parametering with the Object Model
Object Model
4.6.2.1.3 Message Router (0x02):
no attribute, no services
4.6.2.1.4 DeviceNet Object (0x03):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
Name
Data type
Description
Revision
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation
is based.
Name
Data type
Description
MAC ID
Baud Rate
BOI
Bus-Off
Counter
Allocation
Information
Allocation
Choice
Byte
Master`s
ID
USINT
USINT
BOOL
USINT
Node address
Baud rate
Bus-off Interrupt
Number of times CAN went to
the bus-off state
s. MAC ID of Master (from
Allocate)
Default
Value
0x02
Instance 1:
Attribute
ID
1
2
3
4
Used in
buscoupler
Optional
Optional
Optional
Optional
Access
rule
get/set
get
get/set
get/set
5
Optional
get
Struct of:
BYTE,
USINT
Default
Value
0 - 63
0-2
0/1
0 - 255
0 - 63, 255
Services:
Service Code
0x0E
0x10
0x4B
Service Name
Get_Attribute_Single
Set_Attribute_Single
Allocate_Master/Slave_Connection
0x4C
Release_Group_2_Identifier_Set
Description
Used to read a DeviceNet Object attribute value
Used to modify a DeviceNet object attribute value
Requests the use of the predefined Master/Slave
connection
Indicates that the specified connections within the
predefined Master/Slave connection set are no
longer desired. These connections are to be released
(deleted)
4.6.2.1.5 Assembly Object (0x04):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
Name
Data type
Description
Value
Revision
UINT
Revision of the Assembly Object,
Range 1-65535, class definition
upon which the implementation is
based.
0x02
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
• 137
Description of the instances:
Instance
ID
1
2
3
4
5
6
7
8
9
12
13
14
Description
References to the process image containing analog and digital output data.
References to the process image containing only digital output data.
References to the process image containing only analog output data.
References to the process image containing containing analog and digital input data plus status.
References to the process image containing only digital input data plus status.
References to the process image containing only analog input data plus status.
References to the process image containing analog and digital input data.
References to the process image containing only analog input data.
References to the process image containing only analog input data.
References to the process image: analog and digital input data plus Error Code
References to the process image: analog and digital input data plus Error Code and Error Argument
References to the process image: analog and digital input data plus Error Code and Error Argument,
Status
Instance 1:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get/set
Name
Data type
Description
Process
image
Array of
Byte
process image, collection of all
modules process output data.
Access
rule
get/set
Name
Data type
Description
Process
image
Array of
Byte
process image, collection of all
modules process output data.
Access
rule
get/set
Name
Data type
Description
Process
image
Array of
Byte
process image, collection of all
analog modules process output
data.
Access
rule
get
Name
Data type
Description
Process
image
Array of
Byte
process image, collection of all
modules process input data plus
status byte.
Name
Data type
Description
Process
image
Array of
Byte
process image, collection of all
digital modules process input data
plus status byte.
Name
Data type
Description
Process
image
Array of
Byte
process image, collection of all
analog modules process input data
plus status byte.
Value
Instance 2:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Value
Instance 3:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Value
Instance 4:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Value
Instance 5:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get
Value
Instance 6:
Attribute
ID
3
WAGO-I/O-SYSTEM 750
DeviceNet
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get
Value
138 • Configuration / Parametering with the Object Model
Object Model
Instance 7:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get
Name
Data type
Description
Value
Process
image
Array of
Byte
process image, collection of all
modules process input data
Name
Data type
Description
Process
image
Array of
Byte
process image, collection of all
digital modules process input data
Name
Data type
Description
Process
image
Array of
Byte
process image, collection of all
analog modules process input data
Name
Data type
Description
Process
image +
Error
Code
Array of
Byte
process image, collection of all
analog modules process input data
plus Error Code (Cl. 100/Inst. 1/
Attr. 45)
Name
Data type
Description
Process
image +
Error
Code +
Error
Argument
Array of
Byte
process image, collection of all
analog modules process input data
plus Error Code (Cl. 100/Inst. 1/
Attr. 45)
plus Error Argument (Cl. 100/Inst.
1/ Attr. 46)
Instance 8:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get
Value
Instance 9:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get
Value
Instance 12:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get
Value
Instance 13:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get
Value
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
• 139
Instance 14:
Attribute
ID
3
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get
Name
Data type
Description
Process
image +
Error
Code +
Error
Argument
+ Status
Array of
Byte
process image, collection of all
analog modules process input data
plus Error Code (Cl. 100/Inst. 1/
Attr. 45)
plus Error Argument (Cl. 100/Inst.
1/ Attr. 46)
plus Status (Cl. 100/Inst. 1/Attr. 5)
Plus Terminal diagnostic *) (Cl.
100/Inst. 1/Attr. 6)
plus Diagnostic value*) (Cl. 100/
Inst. 1/Attr. 47), the diagnostic
value is only valid, if in the Status
is indicated, that a diagnostic
message lies close
*) Diagnostic is only possible for
the Controller 750-806
Value
Services:
Service Code
0x0E
0x10
Service Name
Get_Attribute_Single
Set_Attribute_Single
Description
Used to read a DeviceNet Object attribute value
Used to modify a DeviceNet object attribute value
4.6.2.1.6 Connection Object (0x05):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
Name
Data type
Description
Revision
UINT
Revision of the Connection
Object, Range 1-65535, class
definition upon which the implementation is based.
Default
Value
0x01
Description of the instances:
Instance ID
1
2
3
4
5
Description
References the Explicit Messaging Connection into the Server
References the Poll I/O Connection
References Bit-Strobe I/O Connection
References the Slave´s Change of State or Cyclic I/O Connection
Reserved for „Reserved Identifier“, Message ID 1
Instance 1 (explicit messaging):
Attribute
ID
1
2
Used in
buscoupler
available
required
Access
rule
get
get
3
required
get
4
required
get
5
required
get
WAGO-I/O-SYSTEM 750
DeviceNet
Name
Data type
Description
state
instance_
type
transportClass_
trigger
produced_
connection_id
consumed_co
nnec-
USINT
USINT
State of the object
Indicates either I/O or Messaging Connection
USINT
defines behaviour of the connection
UINT
CAN Identifier field when the connection
transmits
UINT
CAN Identifier field value that denotes message to be received
140 • Configuration / Parametering with the Object Model
Object Model
6
required
get
7
required
get
8
required
get
9
required
get/set
10-11
12
N/A
required
get
get
13
required
get
14
required
get/set
15
required
get
16
required
get
17
required
get
tion_id
initial_comm
_characteri
stics
produced_con
nection_size
consumed_co
nnection_size
expected_pa
cket_rate
N/A
watchdog_timeout_action
produced_con
nection_path_
length
produced_con
nection_path
consumed_co
nnection_path_
length
consumed_co
nnection_path
production_inhibi
t_time
USINT
Defines the message groups across which
productions and consumptions associated with
this connection occur
UINT
maximum number of Bytes transmitted across
this connection
UINT
maximum number of Bytes transmitted across
this connection
UINT
defines timing associated with this connnection
N/A
USINT
not used
defines how to handle inactivity/watchdog
timeouts
UINT
number of Bytes in produced_connection_path attribute
Array of
USINT
specifies the application objects which data is
to be produced by this connection object
UINT
number of Bytes in consumed_connection_path attribute
Array of
USINT
specifies the application objects that are to
receive the data consumed by this connection
object
USINT
defines minimum time between new data
production
Name
Data type
Description
state
instance_
type
transportClass_
trigger
produced_
connection_id
consumed_co
nnection_id
initial_comm
_characteri
stics
produced_con
nection_size
con-
USINT
USINT
State of the object
Indicates either I/O or Messaging Connection
USINT
defines behaviour of the connection
UINT
CAN Identifier field when the connection
transmits
UINT
CAN Identifier field value that denotes message to be received
USINT
Defines the message groups across which
productions and consumptions associated with
this connection occur
UINT
maximum number of Bytes transmitted across
this connection
UINT
maximum number of Bytes received across
Instance 2 (Poll I/O Connection):
Attribute
ID
1
2
Used in
buscoupler
available
required
Access
rule
get
get
3
required
get
4
required
get
5
required
get
6
required
get
7
required
get
8
required
get
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
9
required
get/set
10-11
12
N/A
required
get
get
13
required
get
14
required
get/set
15
required
get
16
required
get/set
17
required
get
sumed_co
nnection_size
expected_pa
cket_rate
N/A
watchdog_timeout_action
produced_con
nection_path_
length
produced_con
nection_path
consumed_co
nnection_path_
length
consumed_co
nnection_path
production_inhibi
t_time
• 141
this connection
UINT
defines timing associated with this connnection
N/A
USINT
not used
defines how to handle inactivity/watchdog
timeouts
UINT
number of Bytes in produced_connection_path attribute
Array of
USINT
specifies the application objects which data is
to be produced by this connection object
UINT
number of Bytes in consumed_connection_path attribute
Array of
USINT
specifies the application objects that are to
receive the data consumed by this connection
object
USINT
defines minimum time between new data
production
Instance 3 (Bit-Strobe I/O Connection):
Attribute
ID
1
2
Used in
buscoupler
available
required
Access
rule
get
get
3
required
get
4
required
get
5
required
get
6
required
get
7
required
get
8
required
get
9
required
get/set
10-11
12
N/A
required
get
get
WAGO-I/O-SYSTEM 750
DeviceNet
Name
Data type
Description
state
instance_
type
transportClass_
trigger
produced_
connection_id
consumed_co
nnection_id
initial_comm
_characteri
stics
produced_con
nection_size
consumed_co
nnection_size
expected_pa
cket_rate
N/A
watchdog_timeout_action
USINT
USINT
State of the object
Indicates either I/O or Messaging Connection
USINT
defines behaviour of the connection
UINT
CAN Identifier field when the connection
transmits
UINT
CAN Identifier field value that denotes message to be received
USINT
Defines the message groups across which
productions and consumptions associated with
this connection occur
UINT
maximum number of Bytes transmitted across
this connection
UINT
maximum number of Bytes received across
this connection
UINT
defines timing associated with this connnection
N/A
USINT
not used
defines how to handle inactivity/watchdog
timeouts
142 • Configuration / Parametering with the Object Model
Object Model
13
required
get
14
required
get
15
required
get
16
required
get
17
required
get
produced_con
nection_path_
length
produced_con
nection_path
consumed_co
nnection_path_
length
consumed_co
nnection_path
production_inhibi
t_time
UINT
number of Bytes in produced_connection_path attribute
Array of
USINT
specifies the application objects which data is
to be produced by this connection object
UINT
number of Bytes in consumed_connection_path attribute
Array of
USINT
specifies the application objects that are to
receive the data consumed by this connection
object
USINT
defines minimum time between new data
production
Instance 4 (Change of State and Cyclic I/O Connection):
Attribute
ID
1
2
Used in
buscoupler
available
required
Access
rule
get
get
3
required
get
4
required
get
5
required
get
6
required
get
7
required
get
8
required
get
9
required
get/set
10-11
12
N/A
required
get
get
13
required
get
14
required
get/set
15
required
get
Name
Data type
Description
state
instance_
type
transportClass_
trigger
produced_
connection_id
consumed_co
nnection_id
initial_comm
_characteri
stics
produced_con
nection_size
consumed_co
nnection_size
expected_pa
cket_rate
N/A
watchdog_timeout_action
produced_con
nection_path_
length
produced_con
nection_path
con-
USINT
USINT
State of the object
Indicates either I/O or Messaging Connection
USINT
defines behaviour of the connection
UINT
CAN Identifier field when the connection
transmits
UINT
CAN Identifier field value that denotes message to be received
USINT
Defines the message groups across which
productions and consumptions associated with
this connection occur
UINT
maximum number of Bytes transmitted across
this connection
UINT
maximum number of Bytes received across
this connection
UINT
defines timing associated with this connnection
N/A
USINT
not used
defines how to handle inactivity/watchdog
timeouts
UINT
number of Bytes in produced_connection_path attribute
Array of
USINT
specifies the application objects which data is
to be produced by this connection object
UINT
number of Bytes in con-
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
16
required
get
17
required
get/set
sumed_co
nnection_path_
length
conArray of
sumed_co USINT
nnection_path
USINT
production_inhibi
t_time
• 143
sumed_connection_path attribute
specifies the application objects that are to
receive the data consumed by this connection
object
defines minimum time between new data
production
Services:
Service Code
0x0E
0x10
0x05
Service Name
Get_Attribute_Single
Set_Attribute_Single
Reset
Description
Used to read a DeviceNet Object attribute value
Used to modify a DeviceNet object attribute value
Restores connection default values.
The instances are not available if the connection is in state „non existent“.
I/O Connection Object State
Non-Existent
Delete from any state
Create
Get_Atribute/
Set_Attribute/
Apply_Attributes
Get_Atribute/Set_Attribute
Configuring
Apply_Atributes
Waiting for
Connection ID
Apply Atributes
Apply_Atributes
Get_Atribute/
Set_Attribute/
Apply_Attributes/
Reset/Message
Produced/Consumed
Established
Inactivity/Watchdog
Timeout & watchdog_timeout_action =
Transition to Time Out
Reset
Delete
Timed Out
4.6.2.1.7 Acknowledge Handler Object (0x2B):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
2
required
get
Instance 1:
WAGO-I/O-SYSTEM 750
DeviceNet
Name
Data type
Description
Value
Revision
UINT
0x01
Max
instance
UINT
Revision of the Acknowledge
Handler Object, Range 1-65535,
class definition upon which the
implementation is based.
maximum instance number of an
object currently created in this
class level of device
0x01
144 • Configuration / Parametering with the Object Model
Object Model
Attribute
ID
1
Used in
buscoupler
Name
Data type
Description
required
Access
rule
get/set
Acknowledge timer
UINT
2
required
get/set
Retry limit USINT
3
required
get
COS
Producing
Connection
Instance
time to wait for acknowledge before resending range 1-65,535 ms (0 invalid), default 16
ms
number of ack timeouts to wait before informing the producing application of a RetryLimit_Reached event default=1, range 0255; default 16 ms
0x04, connection instance which contains the
path of the producing I/O application object
which will be notified of ack handler objects
UINT
Value
Services:
Service Code
0x0E
Service Name
Get_Attribute_Single
0x10
Set_Attribute_Single
Description
Used to read a DeviceNet Object attribute
value
Used to modify a DeviceNet object attribute
value
4.6.2.1.8 Coupler configuration object (0x64):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
Name
Data type
Description
Value
Revision
UINT
0x01
2
required
get
Max
instance
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
maximum instance number of an
object currently created in this
class level of device
Name
0x01
Instance 1:
Attribute
ID
1
Used in
buscoupler
specific
Access
rule
get/set
2
3
specific
specific
get/set
get/set
4
5
specific
specific
get/set
get
6
specific
get
Bk_Module
No
Bk_TableNo
Bk_Register
No
Bk_Data
ProcessState
DNS_i_Trmnl
dia (**)
Data
type
USINT
USINT
USINT
UINT
USINT
UINT
Description
module number: 0-Coupler, 1- first module, 22.module
table number: 0 ... 256; not all existing
Register number: 0...255 for the Coupler
(0...63 for modules)
Register data , Status
Coupler status: 0x01 module communication
error, 0x02 internal bus error , 0x08: module
diagnostic , 0x80 fieldbus error
Module diagnostic, 0x8000 to decode a
message, High Byte (Bit14...8): channel
number, Low Byte (Bit7..0) Module number
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
7
8
9
10
11
12
13
14
15
WAGO-I/O-SYSTEM 750
DeviceNet
• 145
(**) Object 100 (0x64) Instance 1 Attribute 6
The attribute DNS_i_Trmndia is set depending on the state of the node, i. e.it will be execute a diagnostic evaluation. This word will only supply valid data, if bit 3 (count up from 0) in ProcessState
(class 100/Inst1/Attr.5) is set. This bit indicates, that a new diagnostic notification is present (see
description ProcessState).
The diagnostic evaluation is done by bit 15 in the attribute DNS_i_Trmndia.
If a diagnostic error appears, bit 15 is set.
If an error is rectifyed, bit 15 is reset.
As long as at least one diagnostic error is present, the MS LED is blinking red.
If there are a lot of diagnostic notifications at the same time, with every readout of this attribute you
get the next diagnostic notification. If DNS_i_Trmndia = 0, there is current no new diagnostic notification. The MS LED changes on green again, not until the readout of the last diagnostic notification
(only if the diagnostic reason is solved).
specific
get
CnfLen.
UINT
number of I/O Bits for analog output data
AnalogOut
words
specific
get
CnfLen.
UINT
number of I/O Bits for analog input data
AnalogInp
words
specific
get
CnfLen.
UINT
number of I/O Bits for digital output data bits
DigitalOut
specific
get
CnfLen.
UINT
number of I/O Bits for digital input data bits
DigitalInp
specific
get/set
BK_FAULT USINT An enumerator used to specify fieldbus error
_REACTIO
handling
N
0: stop local I/O cycles (default)
1: switch all outputs to 0
2: do nothing
specific
get/set
BK_SEL_S UINT
Non volatile power up value for the polled I/O
TORED_PO
produced connection path. The attribute is
LL_P_PAT
used to hold an enumerator for the assembly
H
path and the class and instance for the modules object (discrete input point...) paths.
Write only instance values that are available
for couplers present module configuration.
(e.g. do not use analog input points if only
digital modules are fixed to the coupler.)
4:analog and digital input data,status
5: only digital input data plus status
6: only analog input data plus status
7: analog and digital input data
8: only digital input data
9: only analog input data
12: analog and digital input data plus
BK_LED_ERR_CODE (C 100, I 1, A45)
13: analog and digital input data plus
BK_LED_ERR_CODE (C 100, I 1, A45) plus
BK_LED_ERR_ARG (C 100, I 1, A46)
14: analog and digital input data plus
BK_LED_ERR_CODE (C 100, I 1, A45) plus
BK_LED_ERR_ARG (C 100, I 1, A46) plus
Status (C 100, I 1 A 5) plus DNS_i_Trmnldia
(C 100, I 1, A6) plus BK_DIAG_VALUE
(C 100, I 1, A47)
specific
get/set
BK_SEL_S UINT
Non volatile power up value for the polled I/O
TORED_PO
consumed connection path. The attribute is
LL_C_PAT
used to hold an enumerator for the assembly
H
path and the class and instance for modules
object (discrete input point ...) paths. Write
only instance values that are available for
Couplers present module configuration (e.g.
do not use analog input points if only digital
modules are fixed to the Coupler.
specific
get/set
BK_SEL_S UINT
Non volatile power up value for the change of
TORED_CO
state and cyclic connection path. The attribute
SCYC_C_P
is used to hold an enumerator for the assemATH
bly path and the class and instance for modules object (discrete input point...) paths.
Write only instance values that are available
for Couplers present module configuration
(e.g Digital Ausgang not use analog input
points if only digital modules are fixed to the
Coupler.
BK_EM_ex UINT
specific
get/set
Defines the default timing associated with
146 • Configuration / Parametering with the Object Model
Object Model
pected_pac
ket_rate
BK_EM_wa
tchdog_tim
eout_action
BK_PIO_ex
pected_pac
ket_rate
BK_PIO_w
atchdog_timeou
t_action
BK_BS_ex
pected_pac
ket_rate
BK_BS_wa
tchdog_tim
eout_action
BK_COS_e
xpected_pa
cket_rate
BK_COS_w
atchdog_timeou
t_action
BK_BOI
this Explicit Messaging Connection
USINT
Defines how to handle Inactivity/Watchdog
Explicit Messaging Connection timeouts
UINT
Defines the default timing associated with
this Poll I/O Connection Connection
USINT
Defines how to handle Inactivity/Watchdog
Poll I/O Connection Connection timeouts
UINT
Defines the default timing associated with
this Bit–Strobe I/O Connection Connection
USINT
Defines how to handle Inactivity/Watchdog
Bit–Strobe I/O Connection Connection timeouts
Defines the default timing associated with
this Change of State and Cyclic I/O Connection
Defines how to handle Inactivity/Watchdog
Change of State and Cyclic I/O Connection
timeouts
16
specific
get/set
17
specific
get/set
18
specific
get/set
19
specific
get/set
20
specific
get/set
21
specific
get/set
22
specific
get/set
23
specific
get/set
24
specific
get/set
25
specific
get/set
26
specific
get/set
BK_DO_FA USINT
ULT_REAC
TION_ON_
RELEASE_
ST
Defines the behavior after de allocation the
strobed Connection
0: (default) do nothing
1: Process the Coupler fault reaction
40
specific
get/set
BK_static_ UINT
analog_digital_i
nput_mappi
ng
Defines how to calculate the values for the
number of analog and digital input bits.
0000: All bits are digital
0016: One word is analog remaining bits are
digital
0032: Two words are analog remaining bits
are digital
...
0xFFFF: All bits are handled like module type
(default)
41
specific
get/set
BK_static_ UINT
analog_digital_
output_mappin
g
Defines how to calculate the values for the
number of analog and digital input bits.
0000: All bits are digital
0016: One word is analog remaining bits are
digital
0032: Two words are analog remaining bits
are digital
...
0xFFFF: All bits are handled like module type
(default)
(If the number of analog bits exceeds the size
UINT
USINT
USINT
BK_DO_FA USINT
ULT_REAC
TION_ON_
RELEASE_
PIO
BK_DO_FA USINT
ULT_REAC
TION_ON_
RELEASE_
COS
Defines the default value for BOI(Obj0x3
Inst. 1 Att. 3. It handles the CAN Bus-Off
situation.
0: Hold the CAN chip in its bus-off (reset)
state upon detection of a bus-off indication
1: If possible, fully reset the CAN chip and
continue communicating upon detectionof a
bus-off indication
Defines the behavior after de allocation the
polled I/O connection
0: (default) do nothing
1: Process the Coupler fault reaction
Defines the behavior after de allocation the
Change of State and Cyclic I/O Connection
0: (default) do nothing
1: Process the Coupler fault reaction
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
• 147
UINT
of the process image all bits are mapped to
analog bits.
Defines the Couplers functionality.
0xFFFF: All possible functions are enabled.
(resetting a bit to 0 disables the assigned
functionality).
It is only possible to reduce the functionality.
Resetting to „1“ is ignored.
Defines the Couplers major and minor revision attribute.
0xFFFF: The major and minor revison Attributes are set by the firmware.
(This is the default behavior).
0x??00: The minor revison is set to 0.
0x03??: The mjor revison is set to 3.
All other values are valid to.
I/O LED Error Code
UINT
I/O LED Error Argument
42
specific
get/set
BK_specific UINT
_Coupler_b
ehavior
43
specific
get/set
BK_revisio
n_setting
45
specific
get
46
specific
get
BK_Led_Err_
Code
BK_Led_Err_
Arg
UINT
Services:
Service Code
0x0E
Service Name
Get_Attribute_Single
0x10
Set_Attribute_Single
Description
Used to read a DeviceNet Object attribute
value
Used to modify a DeviceNet object attribute
value
4.6.2.1.9 Discrete Input Point Object (0x65):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
Name
Data type
Description
Value
Revision
UINT
0x01
2
optional
get
Max
instance
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
maximum number of instances of
an object currently created in this
class level of the device
0x256
Description of the instances:
Instance ID
1
2
...
255
Description
Reference to the first digital input point
Reference to the next digital input point
Reference to the last possible digital input point
Instance 1 to 255:
Attribute
ID
1
WAGO-I/O-SYSTEM 750
DeviceNet
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get
Name
Data type
Description
Value
DIPOBJ_
VALUE
BIT
digital input bit
0:off
1:on
148 • Configuration / Parametering with the Object Model
Object Model
Services:
Service Code
0x0E
4.6.2.1.10
Service Name
Get_Attribute_Single
Description
Used to read an object attribute value.
Discrete Output Point Object (0x66):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
Name
Data type
Description
Value
Revision
UINT
0x01
2
optional
get
Max
instance
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
maximum instance number of an
object currently created in this
class level of device
0x256
Description of the instances:
Instance ID
1
2
...
255
Description
Reference to the first digital output point
Reference to the next digital output point
Reference to the last possible digital output point
Instance 1 to 255:
Attribute
ID
1
Used in
buscoupler
dep. on kind
of connected
modules
Access
rule
get/set
Name
Data type
Description
Value
DOPOBJ_
VALUE
BIT
digital output bit
0:off
1:on
Services:
4.6.2.1.11
Service Code
0x0E
Service Name
Get_Attribute_Single
0x10
Set_Attribute_Single
Description
Used to read a DeviceNet Object attribute
value
Used to modify a DeviceNet object attribute
value
Analog Input Point Object (0x67):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
Name
Data type
Description
Value
Revision
UINT
01
2
optional
get
Max
instance
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
maximum instance number of an
object currently created in this
class level of device
256
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
• 149
Description of the instances:
Instance ID
1
2
...
255
Description
reference to the first analog input point
reference to the next analog input point
reference to the last possible analog input point
Instance 1 to 255:
Attribute
ID
1
2
Used in
buscoupler
dep. on kind
of connected
modules
dep. on kind
of connected
modules
Access
rule
get
Name
Data type
Description
Value
AIPOBJ_
VALUE
Array of
Byte
Input data
get
AIPOBJ_
VALUE
USINT
Input data length
aktual
input
Values
Number
of Bytes
Services:
4.6.2.1.12
Service Code
0x0E
Service Name
Get_Attribute_Single
0x10
Set_Attribute_Single
Description
Used to read a DeviceNet Object attribute
value
Used to modify a DeviceNet object attribute
value
Analog Output Point Object (0x68):
Instance 0:
Attribute
ID
1
Used in
buscoupler
required
Access
rule
get
Name
Data type
Description
Value
Revision
UINT
01
2
optional
get
Max
instance
UINT
Revision of the Identity Object,
Range 1-65535, class definition
upon which the implementation is
based.
maximum instance number of an
object currently created in this
class level of device
256
Description of the instances:
Instance ID
1
2
...
255
Description
reference to the first analog output point
reference to the next analog output point
reference to the last possible analog output point
Instance 1 to 255:
Attribute
ID
1
2
WAGO-I/O-SYSTEM 750
DeviceNet
Used in
buscoupler
dep. on kind
of connected
modules
dep. on kind
of connected
Access
rule
get
get
Name
Data type
Description
Value
AOPOBJ_
VALUE
Array of
Byte
output data
AOPOBJ_
VALUE
USINT
output data length
actual
output
value
number
of Bytes
150 • Configuration / Parametering with the Object Model
Object Model
modules
Services:
Service Code
0x0E
Service Name
Get_Attribute_Single
0x10
Set_Attribute_Single
Description
Used to read a DeviceNet Object attribute
value
Used to modify a DeviceNet object attribute
value
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
• 151
4.6.2.2 Supplement to the Object Model for Controller 750-806
4.6.2.2.1 Bit-Strobe
• Consumed Path changeable (Discrete Output Point (class 0x66) or 0 valid)
• Produced-Path changeable like a poll connection (if data size more than 8
bytes, only the first 8 bytes are transmitted)
4.6.2.2.2 Dynamic Assembly
• Two dynamic assembly instances possible (instance 100 and 101)
Attribute ID
1
Used in
Acces
buscoupler Rule
Required
Get
2
Required
3
Required
Name
Get/Set
Number of
Members in
List
Member List
Get/Set
Member Data
Description
Member Path
Size
Member Path
(**)
Data
DeviceNet data Description of attribute
type
UINT
Max.51 members possible
Array of Struct
UINT
The member list is an array
of DeviceNet paths
Size of member data
UINT
Size of member path
Semantics
of values
Size in
bits
Size in
bytes
EPATH
Array of Byte
(**)
Descrition of the MemberPath:
0x20 CC 0x24 II 0x30 AA
CC:
class
II:
instance
AA:
attribute
The following classes / instances / attributes are possible:
class:100 instance 1 attribute 5 (ProcessState)
class:100 instance 1 attribute 6 (DNS_i_Trmnldia)
class:101 (Discrete Input Point Object)
class:102 (Discrete Output Point Object)
class:103 (Analog Input Point Object)
class:104 (Analog Output Point Object)
class:160-173 (PLC variables)
Class Services
Service code
0x0Eh
0x08h
Service name
Get_Attribute_Single
Create
Service description
Used to read an Object attribute value
Instantiates an Assembly object within a
specified class. Response contains instance number.
Service name
Get_Attribute_Single
Set_Attribute_Single
Delete
Service description
Used to read an Object attribute value
Modifies an attribute value
Deletes an assembly object and releases
all associated resources
Instance Services
Service code
0x0Eh
0x10h
0x09h
WAGO-I/O-SYSTEM 750
DeviceNet
152 • Configuration / Parametering with the Object Model
Object Model
4.6.2.2.3 New Classes for the PLC Fieldbus Variables
7 new classes for each input and output.
All 7 input / output classes are overlapped, e.g.:
1st and 2nd USINT (class 160 / instance 1 and 2)
= 1st UINT (class166 / instance 1), or
1st and 2nd UINT (class166 / instance 1 and 2)
= 1st UDINT (class170 / instance 1) etc.
4.6.2.2.4 Class 160 (0xA0) Input PLC Fieldbus Variable USINT
Instance 0:
Attribute ID
Used in buscoupler
1
Required
Acces
Rule
Get
2
Optional
Get
Name
Revision
Max.
instance
DeviceNet
data type
UINT
Description of attribute
UINT
Max. instance number of
255
an object currently created
in this class level of the
device
DeviceNet
data type
USINT
Description of attribute
Revision of this object
Semantics of
values
0x01
Description for the object instance Ids
Instance ID
1
2
…
255
Description
Reference to the1. input PLC byte
Reference to the 2. input PLC byte
Reference to the 255. input PLC byte
Instance 1 to instance 255
Attribute ID
Used in buscoupler
1
Optional
Acces
Rule
Get/Set
Name
FB_IN_
VAR
Input data
Semantics of
values
Actual input
data
Services:
Service code
0x0Eh
0x10h
Service name
Get_Attribute_Single
Set_Attribute_Single
Service description
Used to read an Object attribute value
Used to write an Object attribute value
4.6.2.2.5 Class 161 (0xA1) Input Fieldbus Variable USINT
PLC input byte 256 … 510
Max. instance: 255
4.6.2.2.6 Class 162 (0xA2) Input Fieldbus Variable USINT
PLC input byte 511 … 512
Max. instance: 2
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
• 153
4.6.2.2.7 Class 163 (0xA3) Output Fieldbus Variable USINT
Attribute ID
Used in buscoupler
Acces Rule
Name
1
2
Required
Optional
Get
Get
Revision
Max. instance
DeviceNet data Description of attribute
type
UINT
Revision of this object
UINT
Max. instance number
of an object currently
created in this class
level of the device
Semantics
of values
0x01
255
DeviceNet data Description of attribute
type
USINT
Output data
Semantics
of values
Actual
output
data
Description for the object instance Ids
Instance ID
1
2
…
255
Description
Reference to the 1. PLC output byte
Reference to the 2. PLC output byte
Reference to the 255. PLC output byte
Instance 1 to instance 255:
Attribute
ID
1
Used in buscoupler
Acces Rule
Name
Optional
Get
FB_OUT_VA
R
Services:
Service code
0x0Eh
Service name
Get_Attribute_Single
Service description
Used to read an Object attribute value
4.6.2.2.8 Class 164 (0xA4) Output Fieldbus Variable USINT
PLC output byte 256 … 510
Max. instance: 255
4.6.2.2.9 Class 165 (0xA5) Output Fieldbus Variable USINT
PLC output byte 511 … 512
Max. instance: 2
4.6.2.2.10
Class 166 (0xA6) Input Fieldbus Variable UINT
PLC input byte 1..255
Max. instance: 255
4.6.2.2.11
Class 167 (0xA7) Input Fieldbus Variable UINT
PLC input byte 256
Max. instance: 1
WAGO-I/O-SYSTEM 750
DeviceNet
154 • Configuration / Parametering with the Object Model
Object Model
4.6.2.2.12
Class 168 (0xA8) Output Fieldbus Variable UINT
PLC output byte 1..255
Max. instance: 255
4.6.2.2.13
Class 169 (0xA9) Output Fieldbus Variable UINT
PLC output byte 256
Max. instance: 1
4.6.2.2.14
Class 170 (0xAA) Input Fieldbus Variable UDINT
PLC input byte 1..128
Max. instance: 128
4.6.2.2.15
Class 171 (0xAB) Input Fieldbus Variable UDINT
PLC input byte 1..128
Max. instance: 128
Starts with 2 bytes offset
(the 2nd and 3rd UINT (class166 / instance 2 and 3)
= 1st UDINT (class171 / instance 1) etc.)
4.6.2.2.16
Class 172 (0xAC) Output Fieldbus Variable UDINT
PLC output byte 1..128
Max. instance: 128
4.6.2.2.17
Class 173 (0xAD) Output Fieldbus Variable UDINT
PLC output byte 1..128
Max. instance: 128
Starts with 2 bytes offset
(the 2nd and 3rd UINT (class168 / instance 2 and 3)
= 1st UDINT (class173 / instance 1) etc.)
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
4.6.2.2.18
• 155
Class 100 (0x64) - Attribute 44/100/101
Attribut ID
Used in Coupler
Access rule
Attribute
name
BK_SAVE_
DYN_ASS_
INST
Data type
Brief description of the attribute
44
(0x2C)
Specific
Get/Set
UINT
Save dynamic created instances in non
volatile memory (after power up all
saved instances are automatically
created )
0: save no dynamic instances
1: save dynamic instances
Defines the number of bytes from the
PLC-fieldbus-variables (inputs) which
will be added to the assembly object
(this count will be added to the consumed path – assembly instances 1..3)
Defines the number of bytes from the
PLC-fieldbus-variables (outputs)
which will be added to the assembly
object (this count will be added to the
produced path – assembly instances
4..9)
100 (0x64)
Specific
Get/Set
BK_FBINP_ UINT
VAR_CNT
101 (0x65)
Specific
Get/Set
BK_FBOUT
_VAR_CNT
UINT
(For PLCs with Software version starting with SW 01.06):
102 (0x66)
Specific
get/set
103 (0x67)
Specific
get/set
104 (0x66)
Specific
get/set
105 (0x67)
Specific
get/set
BK_FBIN
P_PLCON
LY_VAR_
CNT
BK_FBIN
P_START
PLC_VAR
_CNT
BK_FBO
UT_PLCO
NLY_VA
R_CNT
BK_FBIN
P_START
PLC_VAR
_CNT
UINT
Defines the number of bytes from the PLCfieldbus-variables (inputs) which will be
assigned to the Assembly Object Instance 11.
UINT
Defines the Offset of the first PLC-input
variable (from this variable, the number of the
PLC input variables, which is specified in
Attribute 102, will be transferred.
Defines the number of bytes from the PLCfieldbus-variables (outputs) which will be
assigned to the Assembly Object Instance 10.
UINT
UINT
Defines the Offset of the first PLC-output
variable (from this variable, the number of the
PLC output variables, which is specified in
Attribute 104, will be transferred.
Example:
The example comes from the DeviceNet Coupler point of view:
-> Configuration Coupler:
input process image 12 byte,
output process image 10 byte
-> BK_FBINP_VAR_CNT = 0; BK_FBOUT_VAR_CNT = 0
poll connection: -> 12 byte produced
-> 10 byte consumed
-> BK_FBINP_VAR_CNT = 4; BK_FBOUT_VAR_CNT = 3
poll connection:
-> 15 byte produced
(12 byte input process image + 3 byte PLC output fieldbus variables)
-> 14 byte consumed
(10 byte output process image + 4 byte PLC input fieldbus variables)
WAGO-I/O-SYSTEM 750
DeviceNet
156 • Configuration / Parametering with the Object Model
Object Model
4.6.2.2.19
Identity Class 1 (0x01)
Instance 1:
4.6.2.2.20
Attribut ID
Used in Coupler
Access rule
Attribute name
Data type
Description of the attribute
10 (0x0A)
required
Get/Set
Heartbeat
Interval
USINT
Interval between 2 Heartbeat messages in seconds
Default
Value
0
Connection Object (0x05)
Description of the instances:
Instance ID
1 ... 4
5
6
7
8
9
10
11
12
13
14
4.6.2.2.21
Description
...
References dynamic Connection
References I/O Connection
Additional Assembly Instances 10 and 11
In addition to the (static) assemblies (1 ... 9) that are permanently preprogrammed in the device, the Controller has the assembly instances 10 and
11.
These simplify and speed up the transmission of the input and output image of
the PLC variable from the fieldbus Controller to the master.
Description of the instances:
Instance
ID
1 ... 9
10
11
Description
....
References to the process image containing PLC output variables.
References to the process image containing PLC input variables.
Instance 10:
Attribute
ID
3
Used in
buscoupler
optional
Access
rule
get
Name
Data type
Description
Value
PLC
output
variables
Array of
Byte
process image, collection of all
PLC output variables
Name
Data type
Description
PLC input
variables
Array of
Byte
process image, collection of all
PLC input variables
Instance 11:
Attribute
ID
3
Used in
buscoupler
optional
Access
rule
get
Value
WAGO-I/O-SYSTEM 750
DeviceNet
Configuration / Parametering with the Object Model
Object Model
• 157
(For PLCs with software version before SW 01.06):
PLC Output (I/O Assembly Instance 10):
Only the PLC output variables are transmitted via the corresponding I/O message connection. The data length is equivalent to the value in class 100 / instance 1 / attribute 101 (BK_FBOUT_ VAR_CNT).
PLC Input (I/O Assembly Instance 11):
Only the PLC input variables are transmitted via the corresponding I/O message connection. The data length is equivalent to the value in class 100 / instance 1 / attribute 100 (BK_FBIN_ VAR_CNT).
(For PLCs from software version SW 01.06):
PLC Output (I/O Assembly Instance 10):
Only the PLC output variables are transmitted via the corresponding I/O message connection. The data length is equivalent to the value in class 100 / instance 1 / attribute 104 (BK_FBOUT_ PLCONLY_VAR_CNT).
The first PLC transfer byte is defined by the value in class 100 / instance 1 /
attribute 105 (BK_FBOUT_STARTPLC_VAR_CNT).
PLC Input (I/O Assembly Instance 11):
Only the PLC input variables are transmitted via the corresponding I/O message connection. The data length is equivalent to the value in class 100 / instance 1 / attribute 102 (BK_FBINP_PLCONLY_ VAR_CNT).
The first PLC transfer byte is defined by the value in class 100 / instance 1 /
attribute 103 (BK_FBIN_STARTPLC_VAR_CNT).
WAGO-I/O-SYSTEM 750
DeviceNet
158 •
I/O Modules
5 I/O Modules
5.1 Overview
All listed bus modules, in the overview below, are available for modular applications with the WAGO-I/O-SYSTEM 750.
For detailed information on the I/O modules and the module variations, please
refer to the manuals for the I/O modules.
You will find these manuals on CD ROM „ELECTRONICC Tools and Docs“
(Item-no.: 0888-0412) or on the web pages:
www.wago.com å Service å Download å Documentation.
More Information
Current information on the modular WAGO-I/O-SYSTEM is available in the
Internet under:
www.wago.com
5.1.1 Digital Input Modules
DI DC 5 V
750-414
4 Channel, DC 5 V, 0.2 ms, 2- to 3-conductor connection,
high-side switching
DI DC 5(12) V
753-434
8 Channel, DC 5(12) V, 0.2 ms, 1-conductor connection,
high-side switching
DI DC 24 V
750-400, 753-400
2 Channel, DC 24 V, 3.0 ms, 2- to 4-conductor connection;
high-side switching
750-401, 753-401
2 Channel, DC 24 V, 0.2 ms, 2- to 4-conductor connection;
high-side switching
750-410, 753-410
2 Channel, DC 24 V, 3.0 ms, 2- to 4-conductor connection;
high-side switching
750-411, 753-411
2 Channel, DC 24 V, 0.2 ms, 2- to 4-conductor connection;
high-side switching
750-418, 753-418
2 Channel, DC 24 V, 3.0 ms, 2- to 3-conductor connection;
high-side switching; diagnostic
750-419
2 Channel, DC 24 V, 3.0 ms, 2- to 3-conductor connection;
high-side switching; diagnostic
750-421, 753-421
2 Channel, DC 24 V, 3.0 ms, 2- to 3-conductor connection;
high-side switching; diagnostic
750-402, 753-402
4 Channel, DC 24 V, 3.0 ms, 2- to 3-conductor connection;
high-side switching
750-432, 753-432
4 Channel, DC 24 V, 3.0 ms, 2-conductor connection;
high-side switching
750-403, 753-403
4 Channel, DC 24 V, 0.2 ms, 2- to 3-conductor connection;
high-side switching
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
750-433, 753-433
4 Channel, DC 24 V, 0.2 ms, 2-conductor connection;
high-side switching
750-422, 753-422
4 Channel, DC 24 V, 2- to 3-conductor connection;
high-side switching; 10 ms pulse extension
750-408, 753-408
4 Channel, DC 24 V, 3.0 ms, 2- to 3-conductor connection;
low-side switching
750-409, 753-409
4 Channel, DC 24 V, 0.2 ms, 2- to 3-conductor connection;
low-side switching
750-430, 753-430
8 Channel, DC 24 V, 3.0 ms, 1-conductor connection;
high-side switching
750-431, 753-431
8 Channel, DC 24 V, 0.2 ms, 1-conductor connection;
high-side switching
750-436
8 Channel, DC 24 V, 3.0 ms, 1-conductor connection;
lowside switching
750-437
8 Channel, DC 24 V, 0.2 ms, 1-conductor connection;
low-side switching
• 159
DI AC/DC 24 V
750-415, 753-415
4 Channel, AC/DC 24 V, 2-conductor connection
750-423, 753-423
4 Channel, AC/DC 24 V, 2- to 3-conductor connection;
with power jumper contacts
DI AC/DC 42 V
750-428, 753-428
4 Channel, AC/DC 42 V, 2-conductor connection
DI DC 48 V
750-412, 753-412
2 Channel, DC 48 V, 3.0ms, 2- to 4-conductor connection;
high-side switching
DI DC 110 V
750-427, 753-427
2 Channel, DC 110 V, Configurable high-side or low-side switching
DI AC 120 V
750-406, 753-406
2 Channel, AC 120 V, 2- to 4-conductor connection;
high-side switching
DI AC 120(230) V
753-440
4 Channel, AC 120(230) V, 2-conductor connection;
high-side switching
DI AC 230 V
750-405, 753-405
2 Channel, AC 230 V, 2- to 4-conductor connection;
high-side switching
DI NAMUR
750-435
1 Channel, NAMUR EEx i, Proximity switch acc. to DIN EN 50227
750-425, 753-425
2 Channel, NAMUR, Proximity switch acc. to DIN EN 50227
750-438
2 Channel, NAMUR EEx i, Proximity switch acc. to DIN EN 50227
DI Intruder Detection
750-424, 753-424
WAGO-I/O-SYSTEM 750
DeviceNet
2 Channel, DC 24 V, Intruder Detection
160 •
I/O Modules
5.1.2 Digital Output Modules
DO DC 5 V
750-519
4 Channel, DC 5 V, 20mA, short-circuit-protected; high-side switching
DO DC 12(14) V
753-534
8 Channel, DC 12(14) V, 1A, short-circuit-protected; high-side switching
DO DC 24 V
750-501, 753-501
2 Channel, DC 24 V, 0.5 A, short-circuit-protected; high-side switching
750-502, 753-502
2 Channel, DC 24 V, 2.0 A, short-circuit-protected; high-side switching
750-506, 753-506
2 Channel, DC 24 V, 0.5 A, short-circuit-protected;
high-side switching; with diagnostics
750-507, 753-507
2 Channel, DC 24 V, 2.0 A, short-circuit-protected;
high-side switching; with diagnostics; No longer available, replaced by
750-508
750-508
2 Channel, DC 24 V, 2.0 A, short-circuit-protected;
high-side switching; with diagnostics; Replacement for 750-508
750-535
2 Channel, DC 24 V, EEx i, short-circuit-protected;
PNP-positive switching
750-504, 753-504
4 Channel, DC 24 V, 0.5 A, short-circuit-protected; high-side switching
750-531, 753-531
4 Channel, DC 24 V, 0.5 A, short-circuit-protected; high-side switching
750-516, 753-516
4 Channel, DC 24 V, 0.5 A, short-circuit-protected; low-side switching
750-530, 753-530
8 Channel, DC 24 V, 0.5 A, short-circuit-protected; high-side switching
750-537
8 Channel, DC 24 V, 0.5 A, short-circuit-protected; high-side switching;
with diagnostics
750-536
8 Channel, DC 24 V, 0.5 A, short-circuit-protected; low-side switching
DO AC 120(230) V
753-540
4 Channel, AC 120(230) V, 0.25 A, short-circuit-protected;
high-side switching
DO AC/DC 230 V
750-509, 753-509
2 Channel Solid State Relay, AC/DC 230 V, 300 mA
750-522
2 Channel Solid State Relay, AC/DC 230 V, 500 mA, 3 A (< 30 s)
DO Relay
750-523
1 Channel, AC 230 V, AC 16 A, isolated output, 1 make contact, bistable, manual operation
750-514, 753-514
2 Channel, AC 125 V , AC 0.5 A , DC 30 V, DC 1 A,
isolated outputs, 2 changeover contacts
750-517, 753-517
2 Channel, AC 230 V, 1 A, isolated outputs, 2 changeover contacts
750-512, 753-512
2 Channel, AC 230 V, DC 30 V, AC/DC 2 A, non-floating, 2 make contacts
750-513, 753-513
2 Channel, AC 230 V, DC 30 V, AC/DC 2 A, isolated outputs, 2 make
contacts
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
5.1.3 Analog Intput Modules
AI 0 - 20 mA
750-452, 753-452
2 Channel, 0 - 20 mA, Differential Inputs
750-465, 753-465
2 Channel, 0 - 20 mA, single-ended (S.E.)
750-472, 753-472
2-channel, 0 - 20 mA, 16 Bit, single-ended (S.E.)
750-480
2-channel, 0 - 20 mA ,Differential Inputs
750-453, 753-453
4 Channel, 0 - 20 mA, single-ended (S.E.)
AI 4 - 20 mA
750-454, 753-454
2 Channel, 4 - 20 mA,Differential Inputs
750-474, 753-474
2 Channel, 4 - 20 mA, 16 Bit, single-ended (S.E.)
750-466, 753-466
2 Channel, 4 - 20 mA, single ended (S.E.)
750-485
2 Channel, 4 - 20 mA, EEx i, single ended (S.E.)
750-492, 753-492
2 Channel, 4 - 20 mA, Isolated Differential Inputs
750-455, 753-455
4 Channel, 4 - 20 mA, single ended (S.E.)
AI 0 - 1 A
750-475, 753-475
2-channel, 0 - 1 A AC/DC ,Differential Inputs
AI 0 - 5 A
750-475/020-000,
753-475/020-000
2-channel, 0 - 5 A AC/DC ,Differential Inputs
AI 0 - 10 V
750-467, 753-467
2 Channel, DC 0 - 10 V, single-ended (S.E.)
750-477, 753-477
2 Channel, AC/DC 0 - 10 V,Differential Inputs
750-478, 753-478
2 Channel, DC 0 - 10 V, single-ended (S.E.)
750-459, 753-459
4 Channel, DC 0 - 10 V, single-ended (S.E.)
750-468
4 Channel, DC 0 - 10 V, single-ended (S.E.)
AI DC ± 10 V
750-456, 753-456
2 Channel, DC ± 10 V,Differential Inputs
750-479, 753-479
2 Channel, DC ± 10 V,Differential Measurement Input
750-476, 753-476
2 Channel, DC ± 10 V, single-ended (S.E.)
750-457, 753-457
4 Channel, DC ± 10 V, single-ended (S.E.)
AI DC 0 - 30 V
750-483, 753-483
2 Channel, DC 0 -30 V,Differential Measurement Input
AI Resistance Sensors
750-461, 753-461
2 Channel, Resistance Sensors, PT100 / RTD
750-481/003-000
2 Channel, Resistance Sensors, PT100 / RTD, EEx i
750-460
4 Channel, Resistance Sensors, PT100 / RTD
AI Thermocouples
WAGO-I/O-SYSTEM 750
DeviceNet
• 161
162 •
I/O Modules
750-462
2 Channel, thermocouples with diagnostics
Sensor types: J, K, B, E, N, R, S, T, U
750-469, 753-469
2 Channel, thermocouples with diagnostics
Sensor types: J, K, B, E, N, R, S, T, U, L
AI Others
750-491
1 Channel for Resistor Bridges (Strain Gauge)
5.1.4 Analog Output Modules
AO 0 - 20 mA
750-552, 753-552
2 Channel, 0 - 20 mA
750-585
2 Channel, 0 - 20 mA, EEx i
750-553, 753-553
4 Channel, 0 - 20 mA
AO 4 - 20 mA
750-554, 753-554
2-channel, 4 - 20 mA
750-554, 753-554
4-channel, 4 - 20 mA
AO DC 0 - 10 V
750-550, 753-550
2 Channel, DC 0 - 10 V
750-560
2 Channel, DC 0 - 10 V, 10 Bit, 100 mW, 24 V
750-559, 753-559
4 Channel, DC 0 - 10 V
AO DC ± 10 V
750-556, 753-556
2 Channel, DC ± 10 V
750-557, 753-557
4 Channel, DC ± 10 V
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
• 163
5.1.5 Special Modules
Counter Modules
750-404, 753-404
Up / Down Counter, DC 24 V, 100 kHz
750-638, 753-638
2 Channel, Up / Down Counter, DC 24 V/ 16Bit / 500 Hz
Frequency Measuring
750-404/000-003,
753-404/000-003
Frequency Measuring
Pulse Width Module
750-511
2-channel Pulse Width Module, DC 24 V,
short-circuit-protected, high-side switching
Distance and Angle Measurement Modules
750-630
SSI Transmitter Interface
750-631
Incremental Encor Interface, TTL level squarewave
750-634
Incremental Encor Interface, DC 24 V
750-637
Incremental Encor Interface RS 422, cam outputs
750-635, 753-635
Digital Pulse Interface
Serial Interfaces
750-650, 753
Serial Interface RS 232 C
750-653, 753
Serial Interface RS 485
750-651
TTY-Serial Interface, 20 mA Current Loop
750-654
Data Exchange Module
DALI / DSI Master Module
750-641
DALI / DSI Master Module
AS interface Master Module
750-655
AS interface Master Module
Radio Receiver Module
750-642
Radio Receiver EnOcean
MP Bus Master Module
750-643
MP Bus (Multi Point Bus) Master Module
Vibration Monitoring
750-645
2-Channel Vibration Velocity / Bearing Condition Monitoring VIB I/O
PROFIsafe Modules
750-660/000-001
8FDI 24V DC PROFIsafe
750-665/000-001
4FDO 0.5A / 4FDI 24V DC PROFIsafe
750-666/000-001
1FDO 10A / 2FDO 0.5A / 2FDI 24V PROFIsafe
RTC Module
750-640
WAGO-I/O-SYSTEM 750
DeviceNet
RTC Module
164 •
I/O Modules
5.1.6 System Modules
Module Bus Extension
750-627
Module Bus Extension, End Module
750-628
Module Bus Extension, Coupler Module
DC 24 V Power Supply Modules
750-602
DC 24 V, passiv
750-601
DC 24 V, max. 6.3 A,without diagnostics, with fuse-holder
750-610
DC 24 V, max. 6.3 A, with diagnostics, with fuse-holder
750-625
DC 24 V, EEx i, with fuse-holder
DC 24 V Power Supply Modules with bus power supply
750-613
Bus power supply, 24 V DC
AC 120 V Power Supply Modules
750-615
AC 120 V, max. 6.3 A without diagnostics, with fuse-holder
AC 230 V Power Supply Modules
750-612
AC/DC 230 V without diagnostics, passiv
750-609
AC 230 V, max. 6.3 A without diagnostics, with fuse-holder
750-611
AC 230 V, max. 6.3 A with diagnostics, with fuse-holder
Filter Modules
750-624
Filter Module for field side power supply
750-626
Filter Module for system and field side power supply
Field Side Connection Module
750-603, 753-603
Field Side Connection Module, DC 24 V
750-604, 753-604
Field Side Connection Module, DC 0 V
750-614, 753-614
Field Side Connection Module, AC/DC 0 ... 230 V
Separation Modules
750-616
Separation Module
750-621
Separation Module with Power Contacts
Binary Spacer Module
750-622
Binary Spacer Module
End Module
750-600
End Module, to loop the internal bus
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
• 165
5.2 Process Data Architecture for DeviceNet
With some I/O modules, the structure of the process data is fieldbus specific.
In the case of a DeviceNet coupler/controller, the process image uses a byte
structure (without word alignment). The internal mapping method for data
greater than one byte conforms to the Intel format.
The following section describes the process image for various
WAGO-I/O-SYSTEM 750 and 753 I/O modules when using a DeviceNet coupler/controller.
Note
Depending on the specific position of an I/O module in the fieldbus node,
the process data of all previous byte or bit-oriented modules must be
taken into account to determine its location in the process data map.
For the PFC process image of the programmable fieldbus controller is the
structure of the process data mapping identical.
5.2.1 Digital Input Modules
Digital input modules supply one bit of data per channel to specify the signal
state for the corresponding channel. These bits are mapped into the Input
Process Image.
When analog input modules are also present in the node, the digital data is always appended after the analog data in the Input Process Image, grouped into
bytes.
Some digital modules have an additional diagnostic bit per channel in the Input Process Image. The diagnostic bit is used for detecting faults that occur
(e.g., wire breaks and/or short circuits).
Each input channel seizes one Instance in the Discrete Input Point Object
(Class 0x65).
1 Channel Digital Input Module with Diagnostics
750-435
Bit 7
Bit 6
Bit 5
Input Process Image
Bit 4
Bit 3
Bit 2
The input modules seize 2 Instances in Class (0x65).
WAGO-I/O-SYSTEM 750
DeviceNet
Bit 1
Bit 0
Diagnostic bit Data bit
S1
DI 1
166 •
I/O Modules
Process Data Architecture for DeviceNet
2 Channel Digital Input Modules
750-400, -401, -405, -406, -410, -411, -412, -427, -438, (and all variations),
753-400, -401, -405, -406, -410, -411, -412, -427
Bit 7
Bit 6
Bit 5
Input Process Image
Bit 4
Bit 3
Bit 2
Bit 1
Data bit
DI 2
Channel
2
Bit 0
Data bit
DI 1
Channel
1
Bit 1
Data bit
DI 2
Channel
2
Bit 0
Data bit
DI 1
Channel
1
The input modules seize 2 Instances in Class (0x65).
2 Channel Digital Input Modules with Diagnostics
750-419, -421, -424, -425, 753-421, -424, -425
Bit 7
Bit 6
Bit 5
Bit 4
Input Process Image
Bit 3
Bit 2
Diagnostic
Diagnostic
bit S 2
bit S 1
Channel 2
Channel 1
The input modules seize 4 Instances in Class (0x65).
2 Channel Digital Input Module with Diagnostics and Output Process
Data
750-418, 753-418
The 750-418, 753-418 digital input module supplies a diagnostic and acknowledge bit for each input channel. If a fault condition occurs, the diagnostic bit is set. After the fault condition is cleared, an acknowledge bit must be
set to re-activate the input. The diagnostic data and input data bit is mapped in
the Input Process Image, while the acknowledge bit is in the Output Process
Image.
Bit 7
Bit 6
Bit 5
Bit 4
Input Process Image
Bit 3
Bit 2
Diagnostic
Diagnostic
bit S 2
bit S 1
Channel 2
Channel 1
Bit 1
Data bit
DI 2
Channel
2
Bit 0
Data bit
DI 1
Channel
1
Bit 1
Bit 0
0
0
The input modules seize 4 Instances in Class (0x65).
Bit 7
Bit 6
Bit 5
Output Process Image
Bit 4
Bit 3
Bit 2
AcknowlAcknowledgement bit edgement bit
Q2
Q1
Channel 2
Channel 1
And the input modules seize 4 Instances in Class (0x66).
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
• 167
4 Channel Digital Input Modules
750-402, -403, -408, -409, -414, -415, -422, -423, -428, -432, -433,
753-402, -403, -408, -409, -415, -422, -423, -428, -432, -433, -440
Bit 7
Bit 6
Bit 5
Input Process Image
Bit 4
Bit 3
Bit 2
Data bit Data bit
DI 4
DI 3
Channel Channel
4
3
Bit 1
Data bit
DI 2
Channel
2
Bit 0
Data bit
DI 1
Channel
1
Bit 1
Data bit
DI 2
Channel
2
Bit 0
Data bit
DI 1
Channel
1
The input modules seize 4 Instances in Class (0x65).
8 Channel Digital Input Modules
750-430, -431, -436, -437, 753-430, -431, -434
Bit 7
Data bit
DI 8
Channel
8
Bit 6
Data bit
DI 7
Channel
7
Bit 5
Data bit
DI 6
Channel
6
Input Process Image
Bit 4
Bit 3
Bit 2
Data bit Data bit Data bit
DI 5
DI 4
DI 3
Channel Channel Channel
5
4
3
The input modules seize 8 Instances in Class (0x65).
5.2.2 Digital Output Modules
Digital output modules use one bit of data per channel to control the output of
the corresponding channel. These bits are mapped into the Output Process Image.
When analog output modules are also present in the node, the digital image
data is always appended after the analog data in the Output Process Image,
grouped into bytes.
Each output channel seizes one Instance in the Discrete Output Point Object
(Class 0x66).
1 Channel Digital Output Module with Input Process Data
750-523
Bit 7
Bit 6
Bit 5
Input Process Image
Bit 4
Bit 3
Bit 2
Bit 1
not
used
The output modules seize 2 Instances in Class (0x65).
WAGO-I/O-SYSTEM 750
DeviceNet
Bit 0
Status bit
„Manual
Operation“
168 •
I/O Modules
Process Data Architecture for DeviceNet
Bit 7
Bit 6
Bit 5
Output Process Image
Bit 4
Bit 3
Bit 2
Bit 1
not
used
Bit 0
controls
DO 1
Channel 1
And the output modules seize 2 Instances in Class (0x66).
2 Channel Digital Output Modules
750-501, -502, -509, -512, -513, -514, -517, -535, (and all variations),
753-501, -502, -509, -512, -513, -514, -517
Bit 7
Bit 6
Bit 5
Output Process Image
Bit 4
Bit 3
Bit 2
Bit 1
controls
DO 2
Channel
2
Bit 0
controls
DO 1
Channel
1
The output modules seize 2 Instances in Class (0x66).
2 Channel Digital Input Modules with Diagnostics and Input Process
Data
750-507 (-508), -522, 753-507
The 750-507 (-508), -522 and 753-507 digital output modules have a diagnostic bit for each output channel. When an output fault condition occurs (i.e.,
overload, short circuit, or broken wire), a diagnostic bit is set. The diagnostic
data is mapped into the Input Process Image, while the output control bits are
in the Output Process Image.
Bit 7
Bit 6
Bit 5
Input Process Image
Bit 4
Bit 3
Bit 2
Bit 1
Diagnostic
bit S 2
Channel 2
Bit 0
Diagnostic
bit S 1
Channel 1
The output modules seize 2 Instances in Class (0x65).
Bit 7
Bit 6
Bit 5
Output Process Image
Bit 4
Bit 3
Bit 2
Bit 1
controls
DO 2
Channel 2
Bit 0
controls
DO 1
Channel 1
And the output modules seize 2 Instances in Class (0x66).
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
• 169
750-506, 753-506
The 750-506, 753-506 digital output module has 2-bits of diagnostic information for each output channel. The 2-bit diagnostic information can then be decoded to determine the exact fault condition of the module (i.e., overload, a
short circuit, or a broken wire). The 4-bits of diagnostic data are mapped into
the Input Process Image, while the output control bits are in the Output Process Image.
Bit 7
Bit 6
Bit 5
Input Process Image
Bit 4
Bit 3
Bit 2
Diagnostic Diagnostic
bit S 3
bit S 2
Channel 2 Channel 2
Bit 1
Diagnostic
bit S 1
Channel 1
Bit 0
Diagnostic
bit S 0
Channel 1
The output modules seize 4 Instances in Class (0x65).
Bit 7
Bit 6
Bit 5
Output Process Image
Bit 4
Bit 3
Bit 2
not used
not used
Bit 1
controls
DO 2
Channel 2
Bit 0
controls
DO 1
Channel 1
And the output modules seize 4 Instances in Class (0x66).
4 Channel Digital Output Modules
750-504, -516, -519, -531, 753-504, -516, -531, -540
Bit 7
Bit 6
Bit 5
Output Process Image
Bit 4
Bit 3
Bit 2
controls controls
DO 4
DO 3
Channel Channel
4
3
Bit 1
controls
DO 2
Channel
2
Bit 0
controls
DO 1
Channel
1
The output modules seize 4 Instances in Class (0x66).
4 Channel Digital Output Modules with Diagnostics and Input Process
Data
750-532
The 750-532 digital output modules have a diagnostic bit for each output
channel. When an output fault condition occurs (i.e., overload, short circuit, or
broken wire), a diagnostic bit is set. The diagnostic data is mapped into the
Input Process Image, while the output control bits are in the Output Process
Image.
WAGO-I/O-SYSTEM 750
DeviceNet
170 •
I/O Modules
Process Data Architecture for DeviceNet
Bit 7
Bit 6
Diagnostic bit S = '0'
Diagnostic bit S = '1'
Bit 5
Input Process Image
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Diagnos- Diagnos- DiagnosDiagnostic bit S tic bit S tic bit S
tic bit S 0
3
2
1
Channel
Channel Channel Channel
1
4
3
2
no Error
overload, short circuit, or broken wire
The output modules seize 4 Instances in Class (0x65).
Bit 7
Bit 6
Bit 5
Output Process Image
Bit 4
Bit 3
Bit 2
controls controls
DO 4
DO 3
Channel Channel
4
3
Bit 1
controls
DO 2
Channel
2
Bit 0
controls
DO 1
Channel
1
And the output modules seize 4 Instances in Class (0x66).
8 Channel Digital Output Module
750-530, -536, 753-530, -434
Bit 7
controls
DO 8
Channel
8
Bit 6
controls
DO 7
Channel
7
Output Process Image
Bit 5
Bit 4
Bit 3
Bit 2
controls controls controls controls
DO 6
DO 5
DO 4
DO 3
Channel Channel Channel Channel
6
5
4
3
Bit 1
controls
DO 2
Channel
2
Bit 0
controls
DO 1
Channel
1
The output modules seize 8 Instances in Class (0x66).
8 Channel Digital Output Modules with Diagnostics and Input Process
Data
750-537
The 750-537 digital output modules have a diagnostic bit for each output
channel. When an output fault condition occurs (i.e., overload, short circuit, or
broken wire), a diagnostic bit is set. The diagnostic data is mapped into the
Input Process Image, while the output control bits are in the Output Process
Image.
Input Process Image
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Diagnos- Diagnos- Diagnos- Diagnos- Diagnos- DiagnosDiagnosDiagnostic bit S tic bit S tic bit S tic bit S tic bit S tic bit S
tic bit S 7
tic bit S 0
6
5
4
3
2
1
Channel
Channel
Channel Channel Channel Channel Channel Channel
8
1
7
6
5
4
3
2
Bit 7
Diagnostic bit S = ‘0’
Diagnostic bit S = ‘1’
no Error
overload, short circuit, or broken wire
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
• 171
The output modules seize 8 Instances in Class (0x65).
Bit 7
controls
DO 8
Channel
8
Output Process Image
Bit 5
Bit 4
Bit 3
Bit 2
controls controls controls controls
DO 6
DO 5
DO 4
DO 3
Channel Channel Channel Channel
6
5
4
3
Bit 6
controls
DO 7
Channel
7
Bit 1
controls
DO 2
Channel
2
Bit 0
controls
DO 1
Channel
1
And the output modules seize 8 Instances in Class (0x66).
5.2.3 Analog Input Modules
The hardware of an analog input module has 16 bits of measured analog data
per channel and 8 bits of control/status. However, the DeviceNet coupler/controller does not have access to the 8 control/status bits. Therefore, the
DeviceNet coupler/controller can only access the 16 bits of analog input data
per channel mapped in Intel format in the Input Process Image.
When digital input modules are also present in the node, the analog input data
is always mapped into the Input Process Image in front of the digital data.
Each input channel seizes one Instance in the Analog Input Point Object
(Class 0x67).
1 Channel Analog Input Module
750-491, (and all variations)
Instance
n
Input Process Image
Byte Destination
D0
D1
n+1
D2
D3
Remark
Measured Value UD
Measured Value Uref
The input modules represent 2x2 bytes and seize 2 Instances in Class (0x67).
WAGO-I/O-SYSTEM 750
DeviceNet
172 •
I/O Modules
Process Data Architecture for DeviceNet
2 Channel Analog Input Modules
750-452, -454, -456, -461, -462, -465, -466, -467, -469, -472, -474, -475, -476,
-477, -478, -479, -480, -481, -483, -485, -492, (and all variations),
753-452, -454, -456, -461, -465, -466, -467, -469, -472, -474, -475, -476, -477,
-478, -479, -483, -492, (and all variations)
Instance
n
Input Process Image
Byte Destination
D0
Remark
Measured Value Channel 1
D1
n+1
D2
Measured Value Channel 2
D3
The input modules represent 2x2 bytes and seize 2 Instances in Class (0x67).
4 Channel Analog Input Modules
750-453, -455, -457, -459, -460, -468, (and all variations),
753-453, -455, -457, -459
Instance
n
Input Process Image
Byte Destination
D0
Remark
Measured Value Channel 1
D1
n+1
D2
Measured Value Channel 2
D3
n+2
D4
Measured Value Channel 3
D5
n+3
D6
Measured Value Channel 4
D7
The input modules represent 4x2 bytes and seize 4 Instances in Class (0x67).
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
• 173
5.2.4 Analog Output Modules
The hardware of an analog output module has 16 bits of measured analog data
per channel and 8 bits of control/status. However, the DeviceNet coupler/controller does not have access to the 8 control/status bits. Therefore, the
DeviceNet coupler/controller can only access the 16 bits of analog output data
per channel mapped in Intel format in the Output Process Image.
When digital output modules are also present in the node, the analog output
data is always mapped into the Output Process Image in front of the digital
data.
Each output channel seizes one Instance in the Analog Output Point Object
(Class 0x68).
2 Channel Analog Output Modules
750-550, -552, -554, -556, -560, -585, (and all variations),
753-550, -552, -554, -556
Instance
n
Output Process Image
Byte Destination
D0
Remark
Output Value Channel 1
D1
n+1
D2
Output Value Channel 2
D3
The output modules represent 2x2 bytes and seize 2 Instances in Class (0x68).
4 Channel Analog Output Modules
750-553, -555, -557, -559, 753-553, -555, -557, -559
Instance
n
Output Process Image
Byte Destination
D0
Remark
Output Value Channel 1
D1
n+1
D2
Output Value Channel 2
D3
n+2
D4
Output Value Channel 3
D5
n+3
D6
Output Value Channel 4
D7
The output modules represent 4x2 bytes and seize 4 Instances in Class (0x68).
WAGO-I/O-SYSTEM 750
DeviceNet
174 •
I/O Modules
Process Data Architecture for DeviceNet
5.2.5 Specialty Modules
WAGO has a host of Specialty I/O modules that perform various functions.
With individual modules beside the data bytes also the control/status byte is
mapped in the process image. The control/status byte is required for the bidirectional data exchange of the module with the higher-ranking control system. The control byte is transmitted from the control system to the module and
the status byte from the module to the control system.
This allows, for example, setting of a counter with the control byte or displaying of overshooting or undershooting of the range with the status byte.
Further information
For detailed information about the structure of a particular module’s control/status byte, please refer to that module’s manual. Manuals for each
module can be found on the Internet under:
http://www.wago.com.
The Specialty Modules represent as analog modules.
For this, the process input data of the Specialty Modules seize one Instance
per channel in the Analog Input Point Object (Class 0x67) and the process
output data seize one Instance seize one Instance in the Analog Input Point
Object (Class 0x67) per channel in the Analog Output Point Object (Class
0x68).
Counter Modules
750-404, (and all variations except of /000-005),
753-404, (and variation /000-003)
The above Counter Modules have a total of 5 bytes of user data in both the Input and Output Process Image (4 bytes of counter data and 1 byte of control/status). The counter value is supplied as 32 bits. The following tables illustrate the Input and Output Process Image, which has a total of 6 bytes
mapped into each image.
Instance
n
Input Process Image
Byte Destination
Remark
S
Status byte
-
not used
D0
D1
Counter Value
D2
D3
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
Instance
Output Process Image
Byte Destination
• 175
Remark
C
Control byte
-
not used
D0
n
D1
Counter Setting Value
D2
D3
And the specialty modules represent 1x6 bytes output data and seize 1 Instance in Class (0x68).
750-404/000-005
The above Counter Modules have a total of 5 bytes of user data in both the Input and Output Process Image (4 bytes of counter data and 1 byte of control/status). The two counter values are supplied as 16 bits. The following tables illustrate the Input and Output Process Image, which has a total of 6 bytes
mapped into each image.
Instance
n
Input Process Image
Byte Destination
Remark
S
Status byte
-
not used
D0
Counter Value of Counter 1
D1
D2
Counter Value of Counter 2
D3
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).
Instance
n
Output Process Image
Byte Destination
Remark
C
Control byte
-
not used
D0
Counter Setting Value of Counter 1
D1
D2
Counter Setting Value of Counter 2
D3
And the specialty modules represent 1x6 bytes output data and seize 1 Instance in Class (0x68).
WAGO-I/O-SYSTEM 750
DeviceNet
176 •
I/O Modules
Process Data Architecture for DeviceNet
750-638, 753-638
The above Counter Modules have a total of 6 bytes of user data in both the Input and Output Process Image (4 bytes of counter data and 2 bytes of control/status). The two counter values are supplied as 16 bits. The following tables illustrate the Input and Output Process Image, which has a total of 6 bytes
mapped into each image.
Instance
Input Process Image
Byte Destination
S0
n
D0
Remark
Status byte of Counter 1
Counter Value of Counter 1
D1
S1
n+1
D2
Status byte of Counter 2
Counter Value of Counter 2
D3
The specialty modules represent 2x3 bytes input data and seize 2 Instances in
Class (0x67).
Instance
Output Process Image
Byte Destination
C0
n
D0
Remark
Control byte of Counter 1
Counter Setting Value of Counter 1
D1
S1
n+1
D2
Control byte of Counter 2
Counter Setting Value of Counter 2
D3
And the specialty modules represent 2x3 bytes output data and seize 2 Instances in Class (0x68).
Pulse Width Modules
750-511, (and all variations)
The above Pulse Width modules have a total of 6 bytes of user data in both the
Input and Output Process Image (4 bytes of channel data and 2 bytes of control/status). The two channel values are supplied as 16 bits. Each channel has
its own control/status byte. The following table illustrates the Input and Output Process Image, which has a total of 6 bytes mapped into each image.
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
Instance
Input and Output Process Image
Byte Destination
Remark
C0/S0
n
• 177
D0
Control/Status byte of Channel 1
Data Value of Channel 1
D1
C1/S1
n+1
D2
Control/Status byte of Channel 2
Data Value of Channel 2
D3
The specialty modules represent 2x3 bytes input and output data and seize 2
Instances in Class (0x67) and 2 Instances in Class (0x68).
Serial Interface Modules with alternative Data Format
750-650, (and the variations /000-002, -004, -006, -009, -010, -011, -012,
-013)
750-651, (and the variations /000-002, -003)
750-653, (and the variations /000-002, -007)
Note:
With the freely parametrizable variations /003 000 of the serial interface
modules, the desired operation mode can be set. Dependent on it, the
process image of these modules is then the same, as from the appropriate
variation.
The above Serial Interface Modules with alternative data format have a total
of 4 bytes of user data in both the Input and Output Process Image (3 bytes of
serial data and 1 byte of control/status). The following table illustrates the Input and Output Process Image, which have a total of 4 bytes mapped into each
image.
Instance
n
Input and Output Process Image
Byte Destination
Remark
C/S
Control/Status byte
D0
n+1
D1
Data bytes
D2
The specialty modules represent 2x2 bytes input and output data and seize 2
Instances in Class (0x67) and 2 Instances in Class (0x68).
WAGO-I/O-SYSTEM 750
DeviceNet
178 •
I/O Modules
Process Data Architecture for DeviceNet
Serial Interface Modules with Standard Data Format
750-650/000-001, -014, -015, -016
750-651/000-001
750-653/000-001, -006
The above Serial Interface Modules with Standard Data Format have a total of
6 bytes of user data in both the Input and Output Process Image (5 bytes of serial data and 1 byte of control/status). The following table illustrates the Input
and Output Process Image, which have a total of 6 bytes mapped into each image.
Instance
Input and Output Process Image
Byte Destination
Remark
C/S
Control/Status byte
D0
n
D1
D2
Data bytes
D3
D4
The specialty modules represent 1x6 bytes input and output data and seize 1
Instance in Class (0x67) and 1 Instance in Class (0x68).
Data Exchange Module
750-654, (and the variation /000-001)
The Data Exchange modules have a total of 4 bytes of user data in both the
Input and Output Process Image. The following tables illustrate the Input and
Output Process Image, which has a total of 4 bytes mapped into each image.
Instance
n
Input and Output Process Image
Byte Destination
Remark
D0
D1
n+1
Data bytes
D2
D3
The specialty modules represent 2x2 bytes input and output data and seize 2
Instances in Class (0x67) and 2 Instances in Class (0x68).
SSI Transmitter Interface Modules
750-630 (and the variations /000-001, -002, -006, -008, -009, -011, -012,
-013)
The above SSI Transmitter Interface modules have a total of 4 bytes of user
data in the Input Process Image, which has 4 bytes mapped into the image.
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
Instance
n
Input Process Image
Byte Destination
Remark
D0
D1
n+1
• 179
Data bytes
D2
D3
The specialty modules represent 2x2 bytes input data and seize 2 Instances in
Class (0x67).
750-630/000-004, -005, -007
The above SSI Transmitter Interface modules with status have a total of 5
bytes of user data in the Input Process Image, which has 6 bytes mapped into
the image.
Instance
n
Input Process Image
Byte Destination
Remark
S
Status byte
-
not used
D0
D1
Data bytes
D2
D3
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).
Incremental Encoder Interface Modules
750-631
The above Incremental Encoder Interface modules have 5 bytes of input data
and 3 bytes of output data. The following tables illustrate the Input and Output
Process Image, which have 6 bytes into each image.
Instance
Input Process Image
Byte Destination
S
D0
n
Remark
Status byte
Counter word
D1
D2
not used
Latch word
D3
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).
WAGO-I/O-SYSTEM 750
DeviceNet
180 •
I/O Modules
Process Data Architecture for DeviceNet
Instance
Output Process Image
Byte Destination
C
D0
n
Remark
Control byte
Counter Setting word
D1
not used
-
And the specialty modules represent 1x6 bytes output data and seize 1 Instance in Class (0x68).
750-634
The above Incremental Encoder Interface module has 5 bytes of input data (6
bytes in cycle duration measurement mode) and 3 bytes of output data. The
following tables illustrate the Input and Output Process Image, which has 6
bytes mapped into each image.
Instance
Input Process Image
Byte Destination
Remark
S
Status byte
D0
n
Counter word
D1
(D2)*)
(Periodic time)
D3
Latch word
D4
*) If cycle duration measurement mode is enabled in the control byte, the cycle
duration is given as a 24-bit value that is stored in D2 together with D3/D4.
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).
Instance
Output Process Image
Byte Destination
C
D0
n
Remark
Control byte
Counter Setting word
D1
-
not used
-
And the specialty modules represent 1x6 bytes output data and seize 1 Instance in Class (0x68).
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
• 181
750-637
The above Incremental Encoder Interface Module has a total of 6 bytes of user
data in both the Input and Output Process Image (4 bytes of encoder data and
2 bytes of control/status). The following table illustrates the Input and Output
Process Image, which have 6 bytes mapped into each image.
Instance
Input and Output Process Image
Byte Destination
Remark
C0/S0
n
D0
Control/Status byte of Channel 1
Data Value of Channel 1
D1
C1/S1
n+1
D2
Control/Status byte of Channel 2
Data Value of Channel 2
D3
The specialty modules represent 2x3 bytes input and output data and seize 2
Instances in Class (0x67) and 2 Instances in Class (0x68).
750-635, 753-635
The above Digital Pulse Interface module has a total of 4 bytes of user data in
both the Input and Output Process Image (3 bytes of module data and 1 byte of
control/status). The following table illustrates the Input and Output Process
Image, which have 4 bytes mapped into each image.
Instance
Input and Output Process Image
Byte Destination
Remark
C0/S0
n
Control/Status byte
D0
D1
Data bytes
D2
The specialty modules represent 1x4 bytes input and output data and seize 1
Instance in Class (0x67) and 1 Instance in Class (0x68).
RTC Module
750-640
The above RTC module has a total of 6 bytes of user data in both the Input
and Output Process Image (4 bytes of module data and 1 byte of control/status
and 1 byte ID for command). The following table illustrates the Input and
Output Process Image, which have 6 bytes mapped into each image.
WAGO-I/O-SYSTEM 750
DeviceNet
182 •
I/O Modules
Process Data Architecture for DeviceNet
Instance
n
Input and Output Process Image
Byte Destination
Remark
C/S
Control/Status byte
ID
Command byte
D0
D1
Data bytes
D2
D3
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).and seize 1 Instance in Class (0x68).
DALI/DSI Master Module
750-641
The DALI/DSI Master module has a total of 6 bytes of user data in both the
Input and Output Process Image (5 bytes of module data and 1 byte of control/status). The following tables illustrate the Input and Output Process Image, which have 6 bytes mapped into each image.
Instance
n
Input Process Image
Byte Destination
Remark
S
Status byte
D0
DALI response
D1
DALI address
D2
Message 3
D3
Message 2
D4
Message 1
The specialty modules represent 1x6 bytes input data and seize 1 Instance in
Class (0x67).
Instance
n
Output Process Image
Byte Destination
Remark
C
Control byte
D0
DALI command, DSI dimming value
D1
DALI address
D2
Parameter 2
D3
Parameter 1
D4
Command-Extension
And the specialty modules represent 1x6 bytes output data and seize 1
Instance in Class (0x68).
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
• 183
EnOcean Radio Receiver
750-642
The EnOcean radio receiver has a total of 4 bytes of user data in both the Input
and Output Process Image (3 bytes of module data and 1 byte of control/status). The following tables illustrate the Input and Output Process Image, which have 4 bytes mapped into each image.
Instance
n
Input Process Image
Byte Destination
S
Remark
Status byte
D0
n+1
D1
Data bytes
D2
Instance
n
Output Process Image
Byte Destination
C
Remark
Control byte
n+1
-
Not used
-
The specialty modules represent 2x2 bytes input and output data and seize 2
Instances in Class (0x67) and 2 Instances in Class (0x68).
MP Bus Master Module
750-643
The MP Bus Master Module has a total of 8 bytes of user data in both the Input and Output Process Image (6 bytes of module data and 2 bytes of control/status). The following table illustrates the Input and Output Process Image, which have 8 bytes mapped into each image.
WAGO-I/O-SYSTEM 750
DeviceNet
184 •
I/O Modules
Process Data Architecture for DeviceNet
Instance
Input and Output Process Image
Byte Destination
Remark
C0/S0
Control/Status byte
C1/S1
extended Control/Status byte
D0
n
D1
D2
Data bytes
D3
D4
D5
The specialty modules represent 1x8 bytes input and output data and seize 1
Instance in Class (0x67) and 1 Instance in Class (0x68).
Vibration Velocity/Bearing Condition Monitoring VIB I/O
750-645
The Vibration Velocity/Bearing Condition Monitoring VIB I/O has a total of
12 bytes of user data in both the Input and Output Process Image (8 bytes of
module data and 4 bytes of control/status). The following table illustrates the
Input and Output Process Image, which have 12 bytes mapped into each image.
Instance
n
Input and Output Process Image
Byte Destination
Remark
C0/S0
Control/Status byte
(log. Channel 1, Sensor input 1)
D0
Data bytes
(log. Channel 1, Sensor input 1)
D1
n+1
C1/S1
Control/Status byte
(log. Channel 2, Sensor input 2)
D2
Data bytes
(log. Channel 2, Sensor input 2)
D3
n+2
C2/S2
Control/Status byte
(log. Channel 3, Sensor input 1)
D4
Data bytes
(log. Channel 3, Sensor input 1)
D5
n+3
C3/S3
Control/Status byte
(log. Channel 4, Sensor input 2)
D6
Data bytes
(log. Channel 4, Sensor input 2)
D7
WAGO-I/O-SYSTEM 750
DeviceNet
I/O Modules
Process Data Architecture for DeviceNet
• 185
The specialty modules represent 4x3 bytes input and output data and seize 4
Instances in Class (0x67) and 4 Instances in Class (0x68).
AS-interface Master Module
750-655
The length of the process image of the AS-interface master module can be set
to fixed sizes of 12, 20, 24, 32, 40 or 48 bytes.
It consists of a control or status byte, a mailbox with a size of 0, 6, 10, 12 or
18 bytes and the AS-interface process data, which can range from 0 to 32
bytes.
The AS-interface master module has a total of 12 to maximally 48 bytes data
in both the Input and Output Process Image.
The first Input and output byte, which is assigned to an AS-interface master
module, contains the status / control byte, the second byte is one empty byte.
Subsequently the mailbox data are mapped, when the mailbox is permanently
superimposed (Mode 1).
In the operating mode with suppressable mailbox (Mode 2), the mailbox and
the cyclical process data are mapped next.
The following bytes contain the remaining process data.
Instance
Input and Output Process Image
Byte Destination
Remark
C0/S0
Control/Status byte
-
Not used
D0
n
D1
D2
Mailbox (0,6, 10, 12 or 18 bytes) /
Process data (0-32 bytes)
...
D46
The specialty modules represent 1x 12...48 bytes input and output data and
seize 1 Instance in Class (0x67) and 1 Instance in Class (0x68).
WAGO-I/O-SYSTEM 750
DeviceNet
186 •
I/O Modules
Process Data Architecture for DeviceNet
5.2.6 System Modules
System Modules with Diagnostics
750-610, -611
The 750-610 and 750-611 Supply Modules provide 2 bits of diagnostics in the
Input Process Image for monitoring of the internal power supply.
Bit 7
Bit 6
Bit 5
Bit 4
Input Process Image
Bit 3 Bit 2
Bit 1
Diagnostic bit S 2
Fuse
Bit 0
Diagnostic bit S 1
Voltage
The system modules seize 2 Instances in Class (0x65).
Binary Space Module
750-622
The Binary Space Modules 750-622 behave alternatively like 2 channel digital
input modules or output modules and occupy depending upon the selected settings 1, 2, 3 or 4 bits per channel. According to this, 2, 4, 6 or 8 bits are occupied then either in the process input or the process output image.
Input or Output Process Image
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
(Data bit (Data bit (Data bit (Data bit (Data bit (Data bit
DI 8)
DI 7)
DI 6)
DI 5)
DI 4)
DI 3)
Bit 1
Data bit
DI 2
Bit 0
Data bit
DI 1
The Binary Space Modules seize 2, 4, 6 or 8 Instances in class (0x65) or in
class (0x66).
WAGO-I/O-SYSTEM 750
DeviceNet
Use in Hazardous Environments
Foreword
• 187
6 Use in Hazardous Environments
6.1 Foreword
Today’s development shows that many chemical and petrochemical companies have production plants, production, and process automation machines in
operation which use gas-air, vapor-air and dust-air mixtures which can be explosive. For this reason, the electrical components used in such plants and systems must not pose a risk of explosion resulting in injury to persons or damage
to property. This is backed by law, directives or regulations on a national and
international scale. WAGO-I/O-SYSTEM 750 (electrical components) is designed for use in zone 2 explosive environments. The following basic explosion protection related terms have been defined.
6.2 Protective measures
Primarily, explosion protection describes how to prevent the formation of an
explosive atmosphere. For instance by avoiding the use of combustible liquids, reducing the concentration levels, ventilation measures, to name but a
few. But there are a large number of applications, which do not allow the implementation of primary protection measures. In such cases, the secondary explosion protection comes into play. Following is a detailed description of such
secondary measures.
6.3 Classification meeting CENELEC and IEC
The specifications outlined here are valid for use in Europe and are based on
the following standards: EN50... of CENELEC (European Committee for
Electrotechnical Standardization). On an international scale, these are reflected by the IEC 60079-... standards of the IEC (International Electrotechnical Commission).
6.3.1 Divisions
Explosive environments are areas in which the atmosphere can potentially become explosive. The term explosive means a special mixture of ignitable substances existing in the form of air-borne gases, fumes, mist or dust under atmospheric conditions which, when heated beyond a tolerable temperature or
subjected to an electric arc or sparks, can produce explosions. Explosive zones
have been created to describe the concentrations level of an explosive atmosphere. This division, based on the probability of an explosion occurring, is of
great importance both for technical safety and feasibility reasons. Knowing
that the demands placed on electrical components permanently employed in an
explosive environment have to be much more stringent than those placed on
electrical components that are only rarely and, if at all, for short periods, subject to a dangerous explosive environment.
WAGO-I/O-SYSTEM 750
DeviceNet
188 • Use in Hazardous Environments
Classification meeting CENELEC and IEC
Explosive areas resulting from gases, fumes or mist:
Zone 0 areas are subject to an explosive atmosphere
(> 1000 h /year) continuously or for extended periods.
Zone 1 areas can expect the occasional occurrence of an explosive atmosphere (> 10 h ≤ 1000 h /year).
Zone 2 areas can expect the rare or short-term occurrence of an explosive atmosphere (> 0 h ≤ 10 h /year).
Explosive areas subject to air-borne dust:
Zone 20 areas are subject to an explosive atmosphere
(> 1000 h /year) continuously or for extended periods.
Zone 21 areas can expect the occasional occurrence of an explosive atmosphere (> 10 h ≤ 1000 h /year).
Zone 22 areas can expect the rare or short-term occurrence of an explosive
atmosphere (> 0 h ≤ 10 h /year).
6.3.2 Explosion protection group
In addition, the electrical components for explosive areas are subdivided into
two groups:
Group I:
Group I includes electrical components for use in fire-damp
endangered mine structures.
Group II:
Group II includes electrical components for use in all other
explosive environments. This group is further subdivided by
pertinent combustible gases in the environment.
Subdivision IIA, IIB and IIC takes into account that different materials/substances/gases have various ignition energy
characteristic values. For this reason the three sub-groups
are assigned representative types of gases:
IIA – Propane
IIB – Ethylene
IIC – Hydrogen
Minimal ignition energy of representative types of gases
Explosion group
I
IIA
IIB
IIC
Gases
Methane
Propane
Ethylene
Hydrogen
Ignition energy (µJ)
280
250
82
16
WAGO-I/O-SYSTEM 750
DeviceNet
Use in Hazardous Environments
Classification meeting CENELEC and IEC
• 189
Hydrogen being commonly encountered in chemical plants, frequently the explosion group IIC is requested for maximum safety.
6.3.3 Unit categories
Moreover, the areas of use (zones) and the conditions of use (explosion
groups) are subdivided into categories for the electrical operating means:
Unit
categories
Explosion
group
Area of use
M1
I
Fire-damp protection
M2
I
Fire-damp protection
1G
II
Zone 0 Explosive environment by gas, fumes or mist
2G
II
Zone 1 Explosive environment by gas, fumes or mist
3G
II
Zone 2 Explosive environment by gas, fumes or mist
1D
II
Zone 20 Explosive environment by dust
2D
II
Zone 21 Explosive environment by dust
3D
II
Zone 22 Explosive environment by dust
6.3.4 Temperature classes
The maximum surface temperature for electrical components of explosion protection group I is 150 °C (danger due to coal dust deposits) or 450 °C (if there
is no danger of coal dust deposit).
In line with the maximum surface temperature for all ignition protection types,
the electrical components are subdivided into temperature classes, as far as
electrical components of explosion protection group II are concerned. Here the
temperatures refer to a surrounding temperature of 40 °C for operation and
testing of the electrical components. The lowest ignition temperature of the
existing explosive atmosphere must be higher than the maximum surface temperature.
Temperature classes
Maximum surface
temperature
Ignition temperature
of the combustible materials
T1
450 °C
> 450 °C
T2
300 °C
> 300 °C to 450 °C
T3
200 °C
> 200 °C to 300 °C
T4
135 °C
> 135 °C to 200 °C
T5
100 °C
>100 °C to 135 °C
T6
85°C
> 85 °C to 100 °C
WAGO-I/O-SYSTEM 750
DeviceNet
190 • Use in Hazardous Environments
Classification meeting CENELEC and IEC
The following table represents the division and attributes of the materials to
the temperature classes and material groups in percent:
Temperature classes
T1
T2
T3
26.6 %
42.8 %
25.5 %
94.9 %
T4
T5
T6
Total*
4.9 %
0%
0.2 %
432
Explosion group
IIA
85.2 %
IIB
13.8 %
Total*
501
IIC
1.0 %
*
Number of classified materials
6.3.5 Types of ignition protection
Ignition protection defines the special measures to be taken for electrical components in order to prevent the ignition of surrounding explosive atmospheres.
For this reason a differentiation is made between the following types of ignition protection:
Identification
CENELEC standard
IEC standard
Explanation
Application
EEx o
EN 50 015
IEC 79-6
Oil encapsulation
Zone 1 + 2
EEx p
EN 50 016
IEC 79-2
Overpressure encapsu- Zone 1 + 2
lation
EEx q
EN 50 017
IEC 79-5
Sand encapsulation
Zone 1 + 2
EEx d
EN 50 018
IEC 79-1
Pressure resistant
encapsulation
Zone 1 + 2
EEx e
EN 50 019
IEC 79-7
Increased safety
Zone 1 + 2
EEx m
EN 50 028
IEC 79-18
Cast encapsulation
Zone 1 + 2
EEx i
EN 50 020 (unit)
EN 50 039 (system)
IEC 79-11
Intrinsic safety
Zone 0 + 1 + 2
EEx n
EN 50 021
IEC 79-15
Electrical components Zone 2
for zone 2 (see below)
Ignition protection “n" describes exclusively the use of explosion protected
electrical components in zone 2. This zone encompasses areas where explosive atmospheres can only be expected to occur rarely or short-term. It represents the transition between the area of zone 1, which requires an explosion
protection and safe area in which for instance welding is allowed at any time.
Regulations covering these electrical components are being prepared on a
world-wide scale. The standard EN 50 021 allows electrical component manufacturers to obtain certificates from the corresponding authorities for instance
KEMA in the Netherlands or the PTB in Germany, certifying that the tested
components meet the above mentioned standards draft.
WAGO-I/O-SYSTEM 750
DeviceNet
Use in Hazardous Environments
Classifications meeting the NEC 500
• 191
Type “n” ignition protection additionally requires electrical components to be
marked with the following extended identification:
A – non spark generating (function modules without relay /without switches)
AC – spark generating, contacts protected by seals (function modules with relays / without switches)
L – limited energy (function modules with switch)
Further information
For more detailed information please refer to the national and/or international
standards, directives and regulations!
6.4 Classifications meeting the NEC 500
The following classifications according to NEC 500 (National Electric Code)
are valid for North America.
6.4.1 Divisions
The "Divisions" describe the degree of probability of whatever type of dangerous situation occurring. Here the following assignments apply:
Explosion endangered areas due to combustible gases, fumes, mist and dust:
Division 1
Encompasses areas in which explosive atmospheres are to be expected
occasionally (> 10 h ≤ 1000 h /year) as well as continuously and long-term
(> 1000 h /year).
Division 2
Encompasses areas in which explosive atmospheres can be expected rarely
and short-term (>0 h ≤ 10 h /year).
6.4.2 Explosion protection groups
Electrical components for explosion endangered areas are subdivided in three
danger categories:
Class I (gases and fumes):
Group A (Acetylene)
Group B (Hydrogen)
Group C (Ethylene)
Group D (Methane)
Class II (dust):
Group E (Metal dust)
Group F (Coal dust)
Group G (Flour, starch and cereal dust)
Class III (fibers):
No sub-groups
WAGO-I/O-SYSTEM 750
DeviceNet
192 • Use in Hazardous Environments
Classifications meeting the NEC 500
6.4.3 Temperature classes
Electrical components for explosive areas are differentiated by temperature
classes:
Temperature classes
Maximum
surface temperature
Ignition temperature
of the combustible materials
T1
450 °C
> 450 °C
T2
300 °C
> 300 °C to 450 °C
T2A
280 °C
> 280 °C to 300 °C
T2B
260 °C
> 260 °C to 280 °C
T2C
230 °C
>230 °C to 260 °C
T2D
215 °C
>215 °C to 230 °C
T3
200 °C
>200 °C to 215 °C
T3A
180 °C
>180 °C to 200 °C
T3B
165 °C
>165 °C to 180 °C
T3C
160 °C
>160 °C to 165 °C
T4
135 °C
>135 °C to 160 °C
T4A
120 °C
>120 °C to 135 °C
T5
100 °C
>100 °C to 120 °C
T6
85 °C
> 85 °C to 100 °C
WAGO-I/O-SYSTEM 750
DeviceNet
Use in Hazardous Environments
Identification
• 193
6.5 Identification
6.5.1 For Europe
According to CENELEC and IEC
Unit category
Explosion protection group
Community symbol for
explosion protected
electrical components
II 3 G
KEMA 01ATEX1024 X
EEx nA II T4
Temperature class
Approval body and/or number of
the examination certificate
Explosion protection group
E = conforming with European standards
Ex = explosion protected component
Extended identification
n = Type of ignition
2DI 24V DC 3.0ms
0.08-2.5mm
0V
24V
24246
2101--02----03
CL I DIV 2
24V DC
Grp. A B C D
AWG 28-14
op temp code T4A
55°C max ambient
LISTED 22ZA AND 22XM
ITEM-NO.:750-400
Hansastr. 27
D-32423 Minden
2
DI1
Di2
II 3 G
KEMA 01ATEX1024 X
EEx nA II T4
PATENTS PENDING
Fig. 6.5.1-1: Example for lateral labeling of bus modules
(750-400, 2 channel digital input module 24 V DC)
WAGO-I/O-SYSTEM 750
DeviceNet
g01xx03e
194 • Use in Hazardous Environments
Identification
6.5.2 For America
According to NEC 500
Area of application (zone)
Explosion protection group
(condition of use category)
CL I DIV 2
Grp. ABCD
optemp code T4A
Explosion group
(gas group)
Temperature class
2DI 24V DC 3.0ms
0.08-2.5mm
0V
24V
24246
4100--02----03
CL I DIV 2
24V DC
Grp. A B C D
AWG 28-14
op temp code T4A
55°C max ambient
LISTED 22ZA AND 22XM
ITEM-NO.:750-400
Hansastr. 27
D-32423 Minden
2
DI1
Di2
II 3 G
KEMA 01ATEX1024 X
EEx nA II T4
PATENTS PENDING
Fig. 6.5.2-1: Example for lateral labeling of bus modules
(750-400, 2 channel digital input module 24 V DC)
g01xx04e
WAGO-I/O-SYSTEM 750
DeviceNet
Use in Hazardous Environments
Installation regulations
• 195
6.6 Installation regulations
In the Federal Republic of Germany, various national regulations for the installation in explosive areas must be taken into consideration. The basis being
the ElexV complemented by the installation regulation DIN VDE 0165/2.91.
The following are excerpts from additional VDE regulations:
DIN VDE 0100
Installation in power plants with rated voltages up to
1000 V
DIN VDE 0101
Installation in power plants with rated voltages above
1 kV
DIN VDE 0800
Installation and operation in telecommunication plants
including information processing equipment
DIN VDE 0185
lightning protection systems
The USA and Canada have their own regulations. The following are excerpts
from these regulations:
NFPA 70
National Electrical Code Art. 500 Hazardous Locations
ANSI/ISA-RP
12.6-1987
Recommended Practice
C22.1
Canadian Electrical Code
WAGO-I/O-SYSTEM 750
DeviceNet
196 • Use in Hazardous Environments
Installation regulations
Danger
When using the WAGO-I/O SYSTEM 750 (electrical operation) with Ex approval, the following points are mandatory:
The fieldbus independent I/O System Modules Type 750-xxx are to be installed in enclosures that provide for the degree of ingress protection of at
least IP54.
For use in the presence of combustible dust, the above mentioned modules
are to be installed in enclosures that provide for the degree of ingress protection of at least IP64.
The fieldbus independent I/O system may only be installed in hazardous areas
(Europe: Group II, Zone 2 or America: Class I, Division 2, Group A, B, C,
D) or in non-hazardous areas!
Installation, connection, addition, removal or replacement of modules, fieldbus connectors or fuses may only take place when the system supply and
the field supply are switched off, or when the area is known to be
non-hazardous.
Ensure that only approved modules of the electrical operating type will be
used. The Substitution or Replacement of modules can jeopardize the suitability of the system in hazardous environments!
Operation of intrinsically safe EEx i modules with direct connection to sensors/actuators in hazardous areas of Zone 0 + 1 and Division 1 type requires the use of a 24 V DC Power Supply EEx i module!
DIP switches and potentiometers are only to be adjusted when the area is
know to be non-hazardous.
Further Information
Proof of certification is available on request. Also take note of the information given on the module technical information sheet.
WAGO-I/O-SYSTEM 750
DeviceNet
Glossary
• 197
7 Glossary
Bit
Smallest information unit. Its value can either be 1 or
0.
Bitrate
Number of bits transmitted within a time unit.
Bootstrap
Operating mode of the fieldbus Coupler / Controllers.
Device expects a firmware upload.
Bus
A structure used to transmit data. There are two
types, serial and parallel. A serial bus transmits data
bit by bit, whereas a parallel bus transmits many bits
at one time.
Byte
Binary Yoked Transfer Element. A byte generally
contains 8 bits.
Data bus
see Bus.
Fieldbus
System for serial information transmission between
devices of automation technology in the processrelated field area.
Hardware
Electronic, electrical and mechanic components of a
module/subassembly.
Operating system
Software which links the application programs to the
hardware.
Segment
Typically, a network is divided up into different
physical network segments by way of routers or repeaters.
Server
Device providing services within a client/server system. The service is requested by the Client.
Subnet
A portion of a network that shares the same network
address as the other portions. These subnets are distinguished through the subnet mask.
WAGO-I/O-SYSTEM 750
DeviceNet
198 •
Literature List
8 Literature List
Controller-Area-Network
Grundlagen, Protokolle, Bausteine, Anwendungen
Konrad Etschberger
2., völlig überarbeitete Auflage
2000 Carl Hanser Verlag München Wien
ISBN 3-4446-19431-2
Further information on web pages:
The ODVA provides further documentation on DeviceNet.
www.odva.org
CAN in Automation (CiA) provides further documentation on CAN.
can-cia.de
WAGO-I/O-SYSTEM 750
DeviceNet
Index
9 Index
C
O
carrier rail · 16, 19
contacts
data- · 20
power- · 27
Controller · 8
Coupler · 8
Cycle time · 72
Operating mode
RUN · 69
STOP · 69
Operating mode switch · 69, 72, 78, 86
D
data contacts · 20
E
P
PFC cycle · 78
PLC cycle · 72
PLC program · 72
Power contacts · 21, 27
not carried out · 28
power jumper contacts · 44
Process image · 47, 62, 72, 105
Electrical isolation · 43, 67
F
Fieldbus interface · 72
Fieldbus node · 111
Fieldbus start · 72
Flag · 72
Flags · 82
Flash memory · 72
H
Hardware reset · 69
I
I/O modules
Address range · 81
IEC 61131-3 · 105
Internal bus · 65, 72, 103
R
RAM · 72
RUN · 72
S
Start-up · 72
STOP · 72
Subnet · 156
T
Times · 72
U
unlocking lug · 18
V
L
Variables · 69
Light diodes · 44, 68
locking disc · 18
Loop · 72
W
WAGO-I/O-SYSTEM 750
DeviceNet
WAGO-I/O-PRO 32 · 70, 85, 89
• 199
200 •
Index
WAGO Kontakttechnik GmbH & Co. KG
Postfach 2880 • D-32385 Minden
Hansastraße 27 • D-32423 Minden
Phone:
05 71/8 87 – 0
Fax: 05 71/8 87 – 1 69
E-Mail:
info@wago.com
Web: http://www.wago.com
WAGO-I/O-SYSTEM 750
DeviceNet
Related documents
Download