AS 2067/Amdt 1/2010-02-24 STANDARDS AUSTRALIA Amendment No. 1 to AS 2067—2008 Substations and high voltage installations exceeding 1 kV a.c. CORRECTION The 2008 edition of AS 2067 is amended as follows; the amendment(s) should be inserted in the appropriate place(s). SUMMARY: This Amendment applies to the Preface, Clauses 1.2, 1.3.4, 1.3.20, 1.3.30, 1.3.31, 1.3.44, 1.3.51, 1.3.62, 2.1.1, 2.2.4.1, 2.2.6, 3.1, 3.2, 3.3, 3.4, 4.1.1, 4.2.2, 4.2.3, 5.1.4, 5.2.7, 5.5.2.1, 6.7.3, 6.7.4, 6.7.8, 6.7.9, 6.7.13, 6.7.14, 7.3.2, Paragraph B2.1, Appendices C and E, Tables 3.1 and 3.2, 6.1, A1 and Figures 5.1, 5.2, 5.3, 6.7. Published on 24 February 2010. AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 Preface In the fourth paragraph, replace ‘20007’ with ‘2007’. Clause 1.2 In the title of IEC 61936, replace ‘1 V a.c’ with ‘1 kV a.c.’ Clause 1.3.4 Replace the heading ‘busbar’ with ‘Busbar’. Clause 1.3.20 Add the word ‘and’ before ‘appliances’ at the end of the clause. Clause 1.3.30 Replace the heading ‘High voltage’ with ‘High voltage (HV)’. Clause 1.3.31 Replace the heading and clause with— ‘1.3.31 Highest voltage for installation (U m) Highest r.m.s. value of phase-to-phase voltage for which the installation is designed in respect of its insulation.’ Clause 1.3.44 Replace the heading ‘Low voltage’ with ‘Low voltage (LV)’. Clause 1.3.51 Replace the heading ‘Nominal voltage of a system (U)’ with ‘Nominal voltage of a system (U n )’. Clause 1.3.62 In the first line, replace ‘in event of fault’ with ‘in the event of a fault’. ISBN 978 0 7337 9412 4 Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 Clause 2.1.1 In the sixth paragraph, beginning ‘Unless the installation’ insert the word ‘solely’ after ‘operate’. Clause 2.2.4.1 Delete the second NOTE and replace with— ‘2 Where a high voltage installation has on-site generation (co-generation), motors or parallel operation with a transmission or distribution network, allowance shall be made for the increased fault levels.’ Clause 2.2.6 Delete the last paragraph and replace with— ‘When the acceptable value is exceeded, the corona level may be controlled, for example, by the installation of corona rings or the recessing of fasteners on fittings for high voltage suspension insulator assemblies, busbar support assemblies, busbar connections and equipment terminals.’ Clause 3.1 Delete the third paragraph and replace with— ‘For minimum phase-to-phase and phase-to-earth clearances required refer to Table 3.1 for outdoor installations and Table 3.2 for indoor installations.’ Clause 3.2 1 Delete the first paragraph and replace with— ‘The insulation level shall be chosen according to the established highest voltage for equipment U m and/or impulse withstand voltage.’ 2 Delete the fourth paragraph and replace with the following: ‘In installations in which the configuration of the system, due to the adopted method of neutral earthing or the protection by surge arresters, makes it appropriate to lower the level of insulation, the lower alternative values of Table 3.1 and Table 3.2 may be applied.’ AMDT No. 1 FEB 2010 Clause 3.3 1 Delete the second paragraph and replace with— ‘If the minimum clearances in Table 3.1 and Table 3.2 are not maintained the ability to withstand the test voltages of the chosen insulation level shall be established by applying the appropriate dielectric tests in accordance with AS 1931.1 for the withstand voltage values given in Table 3.1 and Table 3.2.’ 2 Delete the third paragraph and replace with the following: ‘If the minimum clearances referenced in Table 3.1 and Table 3.2 are not maintained in parts or areas of an installation, dielectric tests restricted to these parts or areas will be required.’ Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. AMDT No. 1 FEB 2010 AMDT No. 1 FEB 2010 Clause 3.4 Delete the third paragraph and replace with— ‘The minimum clearances in air between phases or between conductors of the same phase that are separable electrically from each other shall be at least 15% greater than the values given in Column 6 of Table 3.1 (for voltages up to and including U m = 245 kV).’ Table 3.1 Delete Table 3.1 and replace with the following: Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. TABLE 3.1 ROD TO STRUCTURE/PLATE GEOMETRY (VOLTAGE RANGE 1 AND VOLTAGE RANGE II) 1 2 Nominal voltage Highest voltage (see note 6) (kV r.m.s) Un Up to 3.3 6.6 11 (kV r.m.s) Um Up to 3.6 7.2 12 22 24 33 36 66 110 72.5 123 132 145 220 245 275 300 330 362 500 550 3 Rated short duration power frequency withstand voltage (kV r.m.s) 10 20 28 28 50 50 70 70 140 185 230 230 275 360 395 460 380 450 450 520 620 680 NOTE: Refer to Notes following Table 3.2. 4 5 6 7 8 9 Rated lightning impulse withstand voltage Rated switching impulse withstand voltage Minimum phase-toearth clearance Minimum phase-tophase clearance Nonflashover distance Ground safety clearance (kV peak) (kV peak) (mm) (mm) (mm) N 65 100 130 175 240 310 350 420 695 990 1210 1210 1430 1800 2015 2225 2015 2545 2545 3075 3605 4345 (mm) G 2440 40 60 75 (95) 125 (145) 170 (200) 325 450 550 550 650 850 950 1050 950 1050 1050 1175 1425 1550 750 850 850 950 1050 1175 60 90 120 (160) 220 (280) 320 (380) 630 900 1100 1100 1300 1700 1900 2100 1900 2400 2400 2900 3400 4100 70 105 140 185 255 325 370 440 725 1035 1265 1265 1495 1955 2185 2415 2185 2760 2760 3335 3910 4715 10 11 12 Safety clearances for operational purposes and maintenance work Vertical Section Horizontal safety work safety work safety clearance clearance clearance (N + G) (N + 1900) (N + 1340) (mm) (mm) (mm) S H V 2505 1965 1405 2540 2000 1440 2570 2030 1470 2615 2075 1515 2680 2140 1580 2750 2210 1650 2790 2250 1690 2860 2320 1760 3135 2595 2035 3430 2890 2330 3650 3110 2550 3650 3110 2550 3870 3330 2770 4240 3700 3140 4455 3915 3355 4665 4125 3565 4455 3915 3355 4985 4445 3885 4985 4445 3885 5515 4975 4415 6045 5505 4945 6785 6245 5685 AMDT No. 1 FEB 2010 Table 3.2 Delete Table 3.2 and the following Notes and replace with the following: Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. TABLE 3.2 CONDUCTOR TO STRUCTURE GEOMETRY, U m >245 kV (VOLTAGE RANGE II) 1 2 Nominal voltage Highest voltage (see note 6) (kV r.m.s) Un 275 (kV r.m.s) Um 300 330 362 500 550 3 Rated short duration power frequency withstand voltage (kV r.m.s) 380 450 450 520 620 680 4 5 6 7 8 9 Rated lightning impulse withstand voltage Rated switching impulse withstand voltage Minimum phase-toearth clearance Minimum phase-tophase clearance Nonflashover distance Ground safety clearance (kV peak) (kV peak) (mm) (mm) (mm) N 1800 2015 2015 2330 2755 3285 (mm) G 2440 950 1050 1050 1175 1425 1550 750 850 850 950 1050 1175 1700 1900 1900 2200 2600 3100 1955 2185 2185 2530 2990 3565 10 11 12 Safety clearances for operational purposes and maintenance work Vertical Section Horizontal safety work safety work safety clearance clearance clearance (N + G) (N + 1900) (N + 1340) (mm) (mm) (mm) S H V 4240 3700 3140 4455 3915 3355 4455 3915 3355 4770 4230 3670 5195 4655 4095 5725 5185 4625 NOTES TO TABLES 3.1 AND 3.2 1 The clearances in Table 3.1 and 3.2 are based on the climatic conditions described in Clause 2.4. 2 The phase-to-earth clearances given in Column 6 of Table 3.1 are for unfavourable configurations of live and earthed parts, i.e. the ‘rod-structure’ arrangement, and may be used for determining clearances to earth from live parts of any configuration. 3 The phase-to-earth clearances given in Column 6 of Table 3.2 for U m >245 kV r.m.s. are for ‘conductor-structure’ configurations normally employed at the higher voltages. (For background information on electrode configurations, refer to CIGRE Technical Brochure 72-1992, Guidelines for the evaluation of dielectric strength of external insulation, and to AS 1824.2.) 4 The higher values shown in parentheses in Column 4 are included to cover those distribution installations that may be exposed to higher than normal overvoltages or where a higher level of safety or withstand is required. For other installations the lower values are preferred. 5 The values shown in parentheses in Column 6 correspond to the rated lightning impulse withstand voltages shown in parentheses in Column 4. 6 For U m <36 kV r.m.s., it may be desirable to increase the phase-to-earth and phase-to-phase clearances where the presence of birds or vermin could cause a hazard or for constructional or other reasons. 7 The non-flashover distances given in Column 8 include a margin of 10% up to an air clearance of 1300 mm in Column 6 and 6% for 1400 mm and above to allow for variations in construction dimensions. This margin may be deleted when the conditions for carrying out the work are adequate to ensure that the minimum phase-to-earth air clearance is observed in all cases. 8 If considered desirable, the section safety clearance given in Column 10 may be increased to 3000 mm as a minimum for air clearances up to 380 mm, in Column 6. AMDT No. 1 FEB 2010 Clause 4.1.1 AMDT No. 1 FEB 2010 Clause 4.2.2 AMDT No. 1 FEB 2010 Clause 4.2.3 AMDT No. 1 FEB 2010 Clause 5.1.4 Delete Item (a) and replace with— ‘(a) Safe physical arrangement when properly assembled, installed and connected to supply.’ Delete the second paragraph and replace with— ‘The main selection criteria for transformers are given in Section 2 and Section 6. Delete the heading and replace with— ‘4.2.3 Gas-insulated metal-enclosed equipment (GIE), metal-enclosed switchgear, insulation-enclosed switchgear and other prefabricated type-tested switchgear and fusegear assemblies’ Delete the entire clause and replace with— ‘Transport routes, their load capacity, height and width shall be adequate for movements of anticipated transport units and shall be agreed upon between the supplier and the user. Within high voltage installations, the passage of vehicles or other mobile equipment beneath or in proximity to live parts (without protective measures) is permitted in accordance with regulatory requirements where they exist. Where no regulatory requirements exist the following conditions shall be met whilst vehicles are in transit (see Figures 5.1, 5.2 and 5.3 and refer to Clause 3.3 and Tables 3.1 and 3.2 for safety clearances): (a) Where vehicles which personnel do not sit or stand upon or within, whilst the vehicle is in transit are used for transporting equipment clearance T = N + 100 (minimum 500 mm) shall apply between the vehicle, and its load and any live part. Section safety clearance (S) shall be provided between the operator’s walkway and any live part at all times. (Refer to Figure 5.1) (b) Where personnel must remain within the cab of the vehicle whilst it is in transit clearance T = N + 100 (minimum 500 mm) shall apply between the vehicle, with open doors, and its load, to live parts, at all times. (Refer Figure 5.2). Personnel may remain in vehicles or mobile equipment only if there are adequate protective measures on the vehicle or mobile equipment, for example the cab roof, to ensure that the danger zone defined above cannot be infringed. (c) Where mobile equipment can be moved whilst being stood or sat upon, the greater of the following clearances shall be applied (Refer Figure 5.3): (i) Section safety clearance (S) is applied from any part of the vehicle or mobile plant where a person would normally sit or stand to live parts. (ii) Clearance X = N + 1900 is applied horizontally from the extremities of the vehicle when against the kerb line or side of the access way to live parts and exposed conductors. Procedures will be required to ensure safe passage of vehicles and mobile plant. Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. AMDT No. 1 FEB 2010 Figure 5.1 Delete the caption and replace with— FIGURE 5.1 MINIMUM APPROACH DISTANCE FOR TRANSPORT IN TRANSIT— TYPICAL INDOOR INSTALLATION WHERE THE VEHICLES CANNOT BE STOOD OR SAT UPON OR SAT WITHIN WHILST IN TRANSIT AMDT No. 1 FEB 2010 Figure 5.2 Delete the caption and replace with— FIGURE 5.2 MINIMUM APPROACH DISTANCE FOR TRANSPORT IN TRANSIT— TYPICAL OUTDOOR INSTALLATION WHERE PERSONNEL MUST REMAIN WITHIN THE CAB WHILST IN TRANSIT AMDT No. 1 FEB 2010 Figure 5.3 Delete the figure and caption and replace with— X S X S X N N FIGURE 5.3 MINIMUM APPROACH DISTANCE FOR TRANSPORT IN TRANSIT— TYPICAL OUTDOOR INSTALLATION WHERE THE VEHICLES CAN BE STOOD OR SAT UPON WHILST IN TRANSIT AMDT No. 1 FEB 2010 Clause 5.2.7 Delete the second paragraph and replace with— ‘Where bare conductors approach buildings that are located within closed electrical operating areas, the following clearances shall be maintained, after allowing for the maximum sag/swing in the case of stranded conductors:’ Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. AMDT No. 1 FEB 2010 Clause 5.5.2.1 AMDT No. 1 FEB 2010 Table 6.1 Delete the last paragraph and replace with— ‘Pipelines and other equipment, if allowed in substations, shall be designed so that the electrical installation is not affected, even in the event of damage to the pipe or other equipment.’ Delete the column headings and replace with— Transformer type AMDT No. 1 FEB 2010 Clause 6.7.3 AMDT No. 1 FEB 2010 Clause 6.7.4 AMDT No. 1 FEB 2010 Clause 6.7.8 Liquid volume Clearance G 1 to other transformers or fire resistant surfaces Clearance G 2 to combustible building surface Delete Item (c) and replace with— ‘(c) Other plant and equipment such as cables, batteries, drainage pipes may catch fire and spread the fire.’ Delete the second sentence of the fifth paragraph and replace with— ‘Transformers insulated with either non-combustible or combustible liquids should have a blast wall between them for additional protection if the separation distance specified in Clause 6.7.2 is not met or determined in accordance with Clause 6.7.13.’ Delete the text and replace with— ‘Distribution kiosk/padmount cubicles and walled high voltage installations (those with no roof and with a single leaf masonry wall) and rating not exceeding 1000 kVA may be installed not closer than 3 m from a Building Codes of Australia Class 1 or Class 10 building in low density residential areas, without extra protective measures, as shown in Appendix C, Figure C1. NOTE: This reduced distance of 3 m will be reviewed for the next edition of this Standard.’ AMDT No. 1 FEB 2010 Clause 6.7.9 AMDT No. 1 FEB 2010 Clause 6.7.13 AMDT No. 1 FEB 2010 Clause 6.7.14 1 In the fifth paragraph, replace ‘--/120/30’ with ‘--/120/120’. 2 In the eighth paragraph, replace ‘self-enclosing dampers’ with ‘self-closing dampers’. Delete the last sentence beginning ‘See also’. Delete the first paragraph (but not the list) and replace with— ‘Typical high voltage installation arrangements to satisfy the minimum fire protection requirements of this Standard, the Building Code of Australia and AS 1940 are provided in Appendix C. The examples in Appendix C are for distribution substations having transformers with less than 1000 L of oil per transformer. The following is to be noted:’ Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. AMDT No. 1 FEB 2010 Figure 6.7 Delete the figure and replace with— AMDT No. 1 FEB 2010 Clause 7.3.2 AMDT No. 1 FEB 2010 Appendix A Delete the text and replace with— ‘For supplies belonging to the essential group, such as the supplies to a computerized control system, liable to process incorrect signals after a transient loss of power, the provision of a suitable UPS (uninterruptible power supply) or automatic changeover to a fully rated back-up supply is recommended.’ 1 Delete Table A1 and replace with the following: TABLE A1 TYPICAL TOUCH VOLTAGE LIMITS Time (msec) 10 20 50 100 150 200 300 400 500 700 1000 2000 5000 10000 Touch voltages C1 C2 355 351 339 319 297 270 205 137 93 67 56 49 45 43 808 790 742 676 619 563 436 306 214 136 109 94 85 82 Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. 2 Delete the text after Table A1 and replace with— ‘The values for the two curves C1 and C2 used in Figure A2 are shown in Table A1. Formulae by which the specified voltage limits may be calculated are as follows: C1 Special locations—High public contact likelihood with negligible additional series impedance Vt = a + ct + et 2 + gt 3 + it 4 + kt 5 1+ bt + dt 2 + ft 3 + ht 4 + jt 5 where t = clearing time in milliseconds a = 358.8444 b = −3.8399e-03 c = −1.7939 d = 3.7036e-06 e = 3.4832e-03 f = 1.4786e-08 g = −2.6211e-06 h = −4.8406e-11 i = −4.4354e-10 j = 5.2568e-14 k = 2.1260e-12 C2 Normal locations—Normal public contact likelihood with typical mix of additional series impedance Vt = a + ct + et 2 + gt 3 + it 4 1+ bt + dt 2 + ft 3 + ht 4 where t = clearing time in milliseconds a = 828.10 b = 8.0916e-04 c = −1.3631 d = −6.2782e-06 e = 6.2308e-04 f = 1.5372e-08 g = 1.5046e-06 h = 1.3723e-11 i = 1.0909e-09’ Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. AMDT No. 1 FEB 2010 Paragraph B2.1 AMDT No. 1 FEB 2010 Appendix C Delete Item (b) and replace with— ‘(b) has combined HV and LV (common) earthing; and’ Delete the entire Appendix and replace with the following: Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. APPENDIX C FIRE RISK ZONES FOR DISTRIBUTION SUBSTATIONS (Informative) For all figures below, the fire protection requirements of the Building Code of Australia apply together with (if combustible liquid-containing electrical equipment is employed) the Appendix H requirements of AS 1940—2004. The examples are for distribution substations having transformers with less than 1000 l of oil per transformer. FIGURE C1 NON-FIRE-RATED KIOSK-TYPE SUBSTATION IN A LOW DENSITY RESIDENTIAL AREA Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. FIGURE C2 NON-FIRE-RATED SUBSTATION IN AN AREA INCORPORATING HV EQUIPMENT WITH COMBUSTIBLE LIQUID DIELECTRIC Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. FIGURE C3 NON-FIRE-RATED SUBSTATION IN AN AREA INCORPORATING DRYTYPE HV EQUIPMENT (SWITCHGEAR AND/OR TRANSFORMERS) OR HV EQUIPMENT WITH NON-COMBUSTIBLE DIELECTRIC Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. FIGURE C4 ADJACENT NON-FIRE-RATED SUBSTATION IN AN AREA INCORPORATING HV EQUIPMENT WITH COMBUSTIBLE DIELECTRIC Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. FIGURE C5 ATTACHED OR ADJACENT SUBSTATION WITH FIRE-RATED WALLS AND ROOF AND NON-FIRE-RATED DOORS AND VENTS Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. FIGURE C6 INDOOR SUBSTATION WITH PUBLIC ACCESS ABOVE Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. FIGURE C7 OPEN TOP SUBSTATION WITH FIRE-RATED WALLS AND NON-FIRERATED DOORS Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited. FIGURE C8 NON-FIRE-RATED SUBSTATION IN A COMMERCIAL/INDUSTRIAL AREA INCORPORATING HV EQUIPMENT WITH COMBUSTIBLE LIQUID DIELECTRIC AND FIRE-RATED BLAST WALL AMDT No. 1 FEB 2010 Appendix E Delete the entire Appendix. Licensed to Rezkhan user. ANSI store order # Free Download. Downloaded 07/10/2023. Single user license only. Copying and networking prohibited.