All About Transformers and Transformer Faults Root Cause Analysis Qazi Arsalan Hamid Power transformer a static piece of apparatus with two or more windings which, by electromagnetic induction, transforms a system of alternating voltage and current in to another system of voltage and current usually of different values and at the same frequency for the purpose of transmitting electrical power [IEV 421-01-01, modified] Auto-transformer ’a transformer in which at least two windings have a common part [IEV 421-01-1 11 Booster transformer a transformer of which one winding is intended to be connected in series with a circuit in order to alter its voltage and/or shift its phase. The other winding is an energizing winding [IEV 42101-12, modified] Oil-immersed type transformer a transformer of which the magnetic circuit and windings are immersed in oil [IEV 421-01-141 NOTE For the purpose of this part any insulating liquid, mineral oil or other product, is regarded as oil. Dry-type transformer a transformer of which the magnetic circuit and windings are not immersed in an insulating liquid [IEV 421 -01 -161 Terminals and neutral point Terminal a conducting element intended for connecting a winding to external conductors line terminal l a terminal intended for connection to a line conductor of a network [IEV 421-02-011 Neutral terminal a) For three-phase transformers and three-phase banks of single-phase transformers: The terminal or terminals connected to the common point( the neutral point) of a star- connected or zigzag connected winding. b) For single-phase transformers: The terminal intended for connection to a neutral point of a network[ IEV4 21-0202, modified] neutral point the point of a symmetrical system of voltages which is normally at zero potential corresponding terminals terminals of different windings of a transformer, marked with the same letter or corresponding symbol [IEV 421 -02-031 Windings winding The assembly of turns forming an electrical circuit associated with one of the voltages assigned to the transformer NOTE For a three-phase transformer, the 'winding' is the combination of the phase windings (see 3.3.3). [IEV 421-03-01, modified] tapped winding a winding in which the effective number of turns can be changed in steps phase winding the assembly of turns forming one phase of a three-phase winding NOTE The term 'phase winding' should not be used for identifying the assembly of all coils on a specific leg. [IEV 421-03-02, modified] high-voltage winding* the winding having the highest rated voltage [IEV 421-03-031 low-voltage winding' the winding having the lowest rated voltage [IEV 421 -03-041 NOTE For a booster transformer, the winding having the lower rated voltage may be that having the higher insulation level. tapping in a transformer having a tapped winding, a specific connection of that winding, representing a definite effective number of turns in the tapped winding and, consequently, a definite turns ratio between this winding and any other winding with fixed number of turns NOTE One of the tapping is the principal tapping, and other tappings are described in relation to the principal tapping by their respective tapping factors. See definitions of these terms below. principal tapping the tapping to which the rated quantities are related [IEV 421-05-021 tapping factor (corresponding to a given tapping) The ratio: rated voltage of the winding / the voltage which would be developed at no-load at the terminals of the winding, at the tapping concerned, by applying rated voltage to an untapped winding. Plus tapping a tapping whose tapping factor is higher than 1 [IEV 421-05-041 minus tapping a tapping whose tapping factor is lower than 1 [IEV 421-05-051 tapping step the difference between the tapping factors, expressed as a percentage, of two adjacent tappings [IEV 421 -05-061 tapping range the variation range of the tapping factor, expressed as a percentage, compared with the value '1 00' NOTE If this factor ranges from 100 + a to 100 - b, the tapping range is said to be: +a %, -b % or +-a %, if a = b. [IEV 421-05-071 tapping voltage ratio (of a pair of windings) the ratio which is equal to the rated voltage ratio: - multiplied by the tapping factor of the tapped winding if this is the high-voltage winding; - divided by the tapping factor of the tapped winding if this is the lowvoltage winding. [IEV 421 -05-081 NOTE While the rated voltage ratio is, by definition, at least equal to 1, the tapping voltage ratio can be lower than 1 for certain tappings when the rated voltage ratio is close to l. tapping duty the numerical values assigned to the quantities, analogous to rated quantities, which refer to tappings other than the principal tapping [ IEV4 21-05-09, modified on-load tap-changer a device for changing the tapping connections of a winding, suitable for operation while the transformer is energized or on load [IEV 421 -1 1-01 Losses and no-load current no-load loss the active power absorbed when rated voltage (tapping voltage) at rated frequency is applied to the terminals of one of the windings, the other winding or windings being open-circuited [IEV 421-06-01, modified] no-load current the r.m.s. value of the current flowing through a line terminal of a winding when rated voltage (tapping voltage) is applied at rated frequency, the other winding or windings being open- circuited NOTE 1 For a three-phase transformer , the value is the arithmetic mean of the values of current in the three phases. NOTE 2 The no-load current of a winding is often expressed as a percentage of the rated current of that winding. For a multi-winding transformer this percentage is referred to the winding with the highest rated power. [IEV 421-06-02, modified] load loss the absorbed active power at rated frequency and reference temperature, associated with a pair of windings when rated current (tapping current) is flowing through the line terminals of one of the windings , and the terminals of the other winding are short- circuited. Further windings, if existing, are opencircuited total losses the sum of the no-load loss and the load loss Temperature rise The difference between the temperature of the part under consideration and the temperature of the external cooling medium. [IEV 421-08-01, modified] star connection Delta Connection zigzag connection (&connection) the winding connection in which one end of each phase winding of a three-phase transformer is connected to a common point (neutral point), and each phase winding consists of two parts in which phase-displaced voltages are induced NOTE These two parts normally have the same number of turns. [IEV 421-10-04, modified] Tests 10.1 General requirements for routine, type and special tests Transformers shall be subjected to tests as specified below. • Tests shall be made at any ambient temperature between 10 "C and 40 "C and with cooling water (if required) at any temperature not exceeding 25 "C. • Tests shall be made at the manufacturer's works, unless otherwise agreed between the manufacturer and the purchaser. • Tapped windings shall be connected on their principal tapping, unless the relevant test clause requires otherwise or unless the manufacturer and the purchaser agree otherwise. • The test basis for all characteristics other than insulation is the rated condition, unless the test clause states otherwise. • All measuring systems used for the tests shall have certified, traceable accuracy and be subjected to periodic calibration, according to the rules of 4.1 1 of IS0 9001, Routine Test • • • • • • Measurement of winding resistance Measurement of voltage ratio and check of phase displacement Measurement of short-circuit impedance and load loss Measurement of no-load loss and current Dielectric routine tests (IEC 60076-3) Tests on on-load tap-changers, where appropriate Type tests a) Temperature-rise test b) Dielectric type tests (IEC 60076-3) Maintenance and inspection of the transformer bushings Six different inspections There are six different inspections to be performed on the bushings of the power transformer: 1.Routine inspection 2.Regular inspection (Once every two years) 3.Inspection due to excessive partial heatings 4.Local damages inspection (fissures) on the bushings 5.Inspection for oil leaks 6.Storage 1. Routine inspection Excessive local heating Pay attention to the clamping section of the terminals. It is convenient to paint this section with heat indicating paint. Pollution When there is much dust and salt, a clean up must be performed and to do so, the transformer must be place out of service and use water, ammonia or carbon tetrachloride. If they are very dirty, use concentrated hydrochloric acid diluted 40 or more times in water. The solution should not be in contact with any metallic part; after the cleaning the porcelain parts, these must be neutralized with water that contains sodium bicarbonate in a proportion of 30 grams by liter. 2. Regular inspection (Once every two years) Evaluation of the deterioration of the insulation The methods to detect the deterioration of the insulation are the measurement of the insulation resistance and tan ∆. The measurement of the tan ∆ is also difficult, since the bushings should be separated from the transformer in most cases. The evaluation of the result of the measurement should not depend solely on the absolute values obtained, but on the values obtained each year and from the variation among them. If there are large discrepancies in the values, special attention is necessary. When the insulation resistance is superior to 1000 MΩ at normal temperatures, it can be considered as good condition, but the value of the tan also must be taken into consideration for the evaluation. 3. Inspection due to excessive partial heating The excessive heating of the terminals in most cases is due to loosening. If this condition is observed, eliminate the dust or dirt from the parts from contact and tighten firmly. 4. Local damages inspection (fissures) on the bushings The cleaning of the bushings must be done according to what was mentioned. If the damages are very serious it must be replaced with new ones. 5. Inspection for oil leaks Check the various pieces of the bushings to see if there is any oil leaks. If oil is leaking through the gasket, tighten it or replace it. If there are bushings of immersed in oil type and the oil leak is through other part of the bushing, report it to the manufacturer. 6. Storage Keep the bushings in a vertical position and in a dry place. It is recommended to keep them in their original packaging. Protection against Over excitation Increase of the magnetizing current Over excitation of a transformer means that the magnetic flux in the core is increased above the normal design level. This will cause an increase of the magnetizing current and the transformer can be damaged if this situation isn’t taken care of. For step-up transformers connected to generators during start-up, over excitation can occur since the flux is dependent of the factor voltage/frequency. This means that the voltage must be gradually increased, with increasing frequency, in order not to overexcite the transformer. The differential protection must therefore be stabilized under these conditions as tripping of transformers and thus load will only mean that the overvoltage condition in the network is becoming worse. The current during over excitation has a lot of fifth harmonic, see figure 1. This fact is utilized in modern transformer protection to stabilize the transformer against unwanted functions during these kind of conditions. If over excitation of the transformer due to overvoltage or under frequency is likely to happen, a separate over excitation protection should be supplied. This protection has inverse characteristics according to the transformers capability to restrain over excitation “V/Hz”. This protection must be connected to a transformer winding with fixed number of turns. Condition Monitoring of Transformer Detecting early signs of deterioration It is possible to provide transformers with measuring devices to detect early signs of degradation in various components and provide warning to the operator in order to avoid a lengthy and expensive outage due to failure. The technique, which can be applied to other plant as well as transformers, is called condition monitoring, as the intent is to provide the operator with regular information on the condition of the transformer. By reviewing the trends in the information provided, the operator can make a better judgment as to the frequency of maintenance, and detect early signs of deterioration that, if ignored, would lead to an internal fault occurring. The extent to which condition monitoring is applied to transformers on a system will depend on many factors, amongst which will be the policy of the asset owner, the suitability of the design (existing transformers may require modifications involving a period out of service – this may be costly and not justified), the importance of the asset to system operation, and the general record of reliability. Therefore, it should not be expected that all transformers would be, or need to be, so fitted. A typical condition monitoring system for an oil immersed transformer is capable of monitoring the condition of various transformer components (bushings, tank, tap changer, coolers and conservators) as shown in Table 1 below. There can be some overlap with the measurements available from a digital/numerical relay. When a Transformer has stomach pain and want to….. About stomach pain During normal operation, transformer internal structures and windings are subjected to mechanical forces due to the magnetic forces. These forces are illustrated in Figure 1. By designing the internal structure very strong to withstand these forces over a long period of time, service life can be extended. However, in a large transformer during a “through fault” (fault current passing through a transformer), forces can reach millions of pounds, pulling the coils up and down and pulling them apart 60/50 times per second. Notice in Figure 1 that the internal low-voltage coil is being pulled downward, while the high-voltage winding is pulled up, in the opposite direction. At the same time, the right-hand part of the figure shows that the high- and low-voltage coils are being forced apart. Keep in mind that these forces are reversing 50/60 times each second. It is obvious why internal structures of transformers must be built incredibly strong. Many times, if fault currents are high, these forces can rip a transformer apart and cause electrical faults inside the transformer itself. This normally results in arcing inside the transformer that can result in explosive failure of the tank, throwing flaming oil over a wide area. There are protective relaying systems to protect against this possibility, although explosive failures do occur occasionally. How to prevent pain Through Fault – Short Circuit withstand considerations The windings are subject to both radial and axial forces related to the current and flux interactions. Radial forces in the inner winding (normally the LV winding) are in compression while the outer winding (normally the HV winding) forces are in tension. Design of the windings and bracing must consider the magnitude of these forces and provide adequate strength to withstand them without significant mechanical deformation which could result in a dielectric failure. The picture below is an example of a free bucking mechanical failure of an inner winding resulting from radial forces in compression on the winding. Note, even though there is mechanical failure, there wasn’t a dielectric failure of this winding. Flux fields are dependent of the balance of the ampere turn distribution of the HV and LV windings. When the ampere turns of the HV and LV windings are equal and balanced, the only forces are radial. DETC taps (De Energized Tap Changer) in the HV windings and LTC (Load Tap Changer) operation result in changes in the ampere turn distribution resulting in axial forces. If the HV and LV windings are not aligned axially or one winding is physically shorter than the other, ampere turn balance is significantly affected and axial forces are magnified. Autotransformers, low impedance, motor starting duty, transformers with multiple voltages by reconnecting the transformer windings in series and parallel configurations, three winding transformers with dual secondary windings for start up or unit auxiliary service at power plants – all can result in increased axial and radial forces during a short circuit and require special consideration. Some Viva Questions Why Delta Star Transformers are used for Lighting Loads? •For lighting loads, neutral conductor is must and hence the secondary must be star winding and this lighting load is always unbalanced in all three phases. •To minimize the current unbalance in the primary we use delta winding in the primary So delta / star transformer is used for lighting loads. How do we select transformers? •Determine primary voltage and frequency. •Determine secondary voltage required. •Determine the capacity required in volt-amperes. This is done by multiplying the load current (amperes) by the load voltage (volts) for single phase. •For example: if the load is 40 amperes, such as a motor, and the secondary voltage is 240 volts, then 240 x 40 equals 9600 VA. A 10 KVA (10,000 volt-amperes) transformer is required. •Always select Transformer Larger than Actual Load. This is done for safety purposes and allows for expansion, in case more loads is added at a later date. For 3 phase KVA, multiply rated volts x load amps x 1.73 (square root of 3) then divide by 1000. •Determine whether taps are required. Taps are usually specified on larger transformers. Why Small Distribution Transformers not used for Industrial Applications? •Industrial control equipment demands a momentary overload capacity of three to eight times’ normal capacity. This is most prevalent in solenoid or magnetic contactor applications where inrush currents can be three to eight times as high as normal sealed or holding currents but still maintain normal voltage at this momentary overloaded condition. •Distribution transformers are designed for good regulation up to 100 percent loading, but their output voltage will drop rapidly on momentary overloads of this type making them unsuitable for high inrush applications. •Industrial control transformers are designed especially for maintaining a high degree of regulation even at eight time’s normal load. This results in a larger and generally more expensive transformer. Can 50 Hz transformers be used at higher frequencies? •Transformers can be used at frequencies above 50 Hz up through 400 Hz with no limitations provided nameplate voltages are not exceeded. • However, 60 Hz transformers will have less voltage regulation at 400 Hz than 50 Hz. What is meant by regulation in a transformer? •Voltage regulation in transformers is the difference between the no load voltage and the full load voltage. This is usually expressed in terms of percentage. •For example: A transformer delivers 100 volts at no load and the voltage drops to 95 volts at full load, the regulation would be 5%. Distribution transformers generally have regulation from 2% to 4%, depending on the size and the application for which they are used. What are taps and when are they used? •Taps are provided on some transformers on the high voltage winding to correct for high or low voltage conditions, and still deliver full rated output voltages at the secondary terminals. Taps are generally set at two and a half and five percent above and below the rated primary voltage. Can Transformers be reverse connected? •Dry type distribution transformers can be reverse connected without a loss of KVA rating, but there are certain limitations. Transformers rated 1 KVA and larger single phase, 3 KVA and larger three phases can be reverse connected without any adverse effects or loss in KVA capacity. •The reason for this limitation in KVA size is, the turns ratio is the same as the voltage ratio. •Example: A transformer with a 480 volt input, 240 volt output— can have the output connected to a 240 volt source and thereby become the primary or input to the transformer, then the original 480 volt primary winding will become the output or 480 volt secondary. •On transformers rated below 1 KVA single phase, there is a turn’s ratio compensation on the low voltage winding. This means the low voltage winding has a greater voltage than the nameplate voltage indicates at no load. •For example, a small single phase transformer having a nameplate voltage of 480 volts primary and 240 volts secondary, would actually have a no load voltage of approximately 250 volts, and a full load voltage of 240 volts. If the 240 volt winding were connected to a 240 volt source, then the output voltage would consequently be approximately 460 volts at no load and approximately 442 volts at full load. As the KVA becomes smaller, the compensation is greater—resulting in lower output voltages. •When one attempts to use these transformers in reverse, the transformer will not be harmed; however, the output voltage will be lower than is indicated by the nameplate. What is the difference between “Insulating”, “Isolating”, and “Shielded Winding” transformers? •Insulating and isolating transformers are identical. These terms are used to describe the separation of the primary and secondary windings. A shielded transformer includes a metallic shield between the primary and secondary windings to attenuate (lessen) transient noise. Will a transformer change Three Phases to Single Phase? •A transformer will not act as a phase changing device when attempting to change three phase to single phase. •There is no way that a transformer will take three phase in and deliver single phase out while at the same time presenting a balanced load to the three phase supply system. •There are, however, circuits available to change three phase to two phase or vice versa using standard dual wound transformers. Please contact the factory for two phase applications. Can 60 Hz transformers be operated at 50 Hz? •Transformers rated below 1 KVA can be used on 50 Hz service. •Transformers 1 KVA and larger, rated at 60 Hz, should not be used on 50 Hz service, due to the higher losses and resultant heat rise. Special designs are required for this service. However, any 50 Hz transformer will operate on a 60 Hz service. Can transformers be used in parallel? •Single phase transformers can be used in parallel only when their impedances and voltages are equal. If unequal voltages are used, a circulating current exists in the closed network between the two transformers, which will cause excess heating and result in a shorter life of the transformer. In addition, impedance values of each transformer must be within 7.5% of each other. •For example: Transformer A has an impedance of 4%, transformer B which is to be parallel to A must have impedance between the limits of 3.7% and 4.3%. When paralleling three phase transformers, the same precautions must be observed as listed above, plus the angular displacement and phasing between the two transformers must be identical. What is Boucholz relay and the significance of it in to the transformer? •Boucholz relay is a device which is used for the protection of transformer from its internal faults, •it is a gas based relay. whenever any internal fault occurs in a transformer, the boucholz relay at once gives a horn for some time, if the transformer is isolated from the circuit then it stop its sound itself otherwise it trips the circuit by its own tripping mechanism. Why we do two types of earthing on transformer (Body earthing & neutral earthing) •The two types of earthing are Familiar as Equipment earthing and system earthing. •In Equipment earthing: body (non conducting part) of the equipment should be earthed to safeguard the human beings. •The System Earthing : In this neutral of the supply source ( Transformer or Generator) should be grounded. With this, in case of unbalanced loading neutral will not be shifted. So that unbalanced voltages will not arise. We can protect the equipment also. With size of the equipment ( transformer or alternator)and selection of relying system earthing will be further classified into directly earthed, Impedance earthing, resistive (NGRs) earthing. Which Point need to be consider while Neutral Earthing of Transformer? •The following points need to check before going for Neutral Grounding Resistance. •Fault current passing through ground, step and touch potential. •Capacity of transformer to sustain ground fault current, w.r.t winding, core burning. •Relay co-ordination and fault clearing time. •Standard practice of limiting earth fault current. In case no data or calculation is possible, go for limiting E/F current to 300A or 500A, depending on sensitivity of relay. Thank You