IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction IEEE Power and Energy Society Sponsored by the Surge Protective Devices Committee IEEE 3 Park Avenue New York, NY 10016-5997 USA IEEE Std C62.92.1™-2016 (Revision of IEEE Std C62.92.1-2000) Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1™-2016 (Revision of IEEE Std C62.92.1-2000) IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Sponsor Surge Protective Devices Committee of the IEEE Power and Energy Society Approved 7 December 2016 IEEE-SA Standards Board Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. Abstract: The application of neutral grounding to three-phase electrical utility systems is described in this guide. It is Part 1 of the IEEE C62.92 series of guides for neutral grounding. This guide presents basic considerations of the selection of neutral grounding parameters that will provide for the control of overvoltage and ground-fault current on all parts of three-phase electrical utility systems rated greater than 1000 V. Keywords: classes of grounding, effectively grounding, IEEE C62.92.1™, means of grounding, neutral grounding, undergrounded systems The Institute of Electrical and Electronics Engineers, Inc. 3 Park Avenue, New York, NY 10016-5997, USA Copyright © 2017 by The Institute of Electrical and Electronics Engineers, Inc. All rights reserved. Published 31 March 2017. Printed in the United States of America. IEEE is a registered trademark in the U.S. Patent & Trademark Office, owned by The Institute of Electrical and Electronics Engineers, Incorporated. PDF: Print: ISBN 978-1-5044-3735-6 ISBN 978-1-5044-3736-3 STD22421 STDPD22421 IEEE prohibits discrimination, harassment, and bullying. For more information, visit http://www.ieee.org/web/aboutus/whatis/policies/p9-26.html. No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the prior written permission of the publisher. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. Important Notices and Disclaimers Concerning IEEE Standards Documents IEEE documents are made available for use subject to important notices and legal disclaimers. These notices and disclaimers, or a reference to this page, appear in all standards and may be found under the heading “Important Notices and Disclaimers Concerning IEEE Standards Documents.” They can also be obtained on request from IEEE or viewed at http://standards.ieee.org/IPR/disclaimers.html. Notice and Disclaimer of Liability Concerning the Use of IEEE Standards Documents IEEE Standards documents (standards, recommended practices, and guides), both full-use and trial-use, are developed within IEEE Societies and the Standards Coordinating Committees of the IEEE Standards Association (“IEEE-SA”) Standards Board. IEEE (“the Institute”) develops its standards through a consensus development process, approved by the American National Standards Institute (“ANSI”), which brings together volunteers representing varied viewpoints and interests to achieve the final product. IEEE Standards are documents developed through scientific, academic, and industry-based technical working groups. Volunteers in IEEE working groups are not necessarily members of the Institute and participate without compensation from IEEE. While IEEE administers the process and establishes rules to promote fairness in the consensus development process, IEEE does not independently evaluate, test, or verify the accuracy of any of the information or the soundness of any judgments contained in its standards. IEEE Standards do not guarantee or ensure safety, security, health, or environmental protection, or ensure against interference with or from other devices or networks. Implementers and users of IEEE Standards documents are responsible for determining and complying with all appropriate safety, security, environmental, health, and interference protection practices and all applicable laws and regulations. IEEE does not warrant or represent the accuracy or content of the material contained in its standards, and expressly disclaims all warranties (express, implied and statutory) not included in this or any other document relating to the standard, including, but not limited to, the warranties of: merchantability; fitness for a particular purpose; non-infringement; and quality, accuracy, effectiveness, currency, or completeness of material. In addition, IEEE disclaims any and all conditions relating to: results; and workmanlike effort. IEEE standards documents are supplied “AS IS” and “WITH ALL FAULTS.” Use of an IEEE standard is wholly voluntary. The existence of an IEEE standard does not imply that there are no other ways to produce, test, measure, purchase, market, or provide other goods and services related to the scope of the IEEE standard. Furthermore, the viewpoint expressed at the time a standard is approved and issued is subject to change brought about through developments in the state of the art and comments received from users of the standard. In publishing and making its standards available, IEEE is not suggesting or rendering professional or other services for, or on behalf of, any person or entity nor is IEEE undertaking to perform any duty owed by any other person or entity to another. Any person utilizing any IEEE Standards document, should rely upon his or her own independent judgment in the exercise of reasonable care in any given circumstances or, as appropriate, seek the advice of a competent professional in determining the appropriateness of a given IEEE standard. IN NO EVENT SHALL IEEE BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY, OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO: PROCUREMENT OF SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE PUBLICATION, USE OF, OR RELIANCE UPON ANY STANDARD, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE AND REGARDLESS OF WHETHER SUCH DAMAGE WAS FORESEEABLE. 3 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. Translations The IEEE consensus development process involves the review of documents in English only. In the event that an IEEE standard is translated, only the English version published by IEEE should be considered the approved IEEE standard. Official statements A statement, written or oral, that is not processed in accordance with the IEEE-SA Standards Board Operations Manual shall not be considered or inferred to be the official position of IEEE or any of its committees and shall not be considered to be, or be relied upon as, a formal position of IEEE. At lectures, symposia, seminars, or educational courses, an individual presenting information on IEEE standards shall make it clear that his or her views should be considered the personal views of that individual rather than the formal position of IEEE. Comments on standards Comments for revision of IEEE Standards documents are welcome from any interested party, regardless of membership affiliation with IEEE. However, IEEE does not provide consulting information or advice pertaining to IEEE Standards documents. Suggestions for changes in documents should be in the form of a proposed change of text, together with appropriate supporting comments. Since IEEE standards represent a consensus of concerned interests, it is important that any responses to comments and questions also receive the concurrence of a balance of interests. For this reason, IEEE and the members of its societies and Standards Coordinating Committees are not able to provide an instant response to comments or questions except in those cases where the matter has previously been addressed. For the same reason, IEEE does not respond to interpretation requests. Any person who would like to participate in revisions to an IEEE standard is welcome to join the relevant IEEE working group. Comments on standards should be submitted to the following address: Secretary, IEEE-SA Standards Board 445 Hoes Lane Piscataway, NJ 08854 USA Laws and regulations Users of IEEE Standards documents should consult all applicable laws and regulations. Compliance with the provisions of any IEEE Standards document does not imply compliance to any applicable regulatory requirements. Implementers of the standard are responsible for observing or referring to the applicable regulatory requirements. IEEE does not, by the publication of its standards, intend to urge action that is not in compliance with applicable laws, and these documents may not be construed as doing so Copyrights IEEE draft and approved standards are copyrighted by IEEE under US and international copyright laws. They are made available by IEEE and are adopted for a wide variety of both public and private uses. These include both use, by reference, in laws and regulations, and use in private self-regulation, standardization, and the promotion of engineering practices and methods. By making these documents available for use and adoption by public authorities and private users, IEEE does not waive any rights in copyright to the documents. 4 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. Photocopies Subject to payment of the appropriate fee, IEEE will grant users a limited, non-exclusive license to photocopy portions of any individual standard for company or organizational internal use or individual, non-commercial use only. To arrange for payment of licensing fees, please contact Copyright Clearance Center, Customer Service, 222 Rosewood Drive, Danvers, MA 01923 USA; +1 978 750 8400. Permission to photocopy portions of any individual standard for educational classroom use can also be obtained through the Copyright Clearance Center. Updating of IEEE Standards documents Users of IEEE Standards documents should be aware that these documents may be superseded at any time by the issuance of new editions or may be amended from time to time through the issuance of amendments, corrigenda, or errata. An official IEEE document at any point in time consists of the current edition of the document together with any amendments, corrigenda, or errata then in effect. Every IEEE standard is subjected to review at least every 10 years. When a document is more than 10 years old and has not undergone a revision process, it is reasonable to conclude that its contents, although still of some value, do not wholly reflect the present state of the art. Users are cautioned to check to determine that they have the latest edition of any IEEE standard. In order to determine whether a given document is the current edition and whether it has been amended through the issuance of amendments, corrigenda, or errata, visit the IEEE Xplore at http://ieeexplore.ieee.org/ or contact IEEE at the address listed previously. For more information about the IEEE-SA or IEEE’s standards development process, visit the IEEE-SA Website at http://standards.ieee.org. Errata Errata, if any, for all IEEE standards can be accessed on the IEEE-SA Website at the following URL: http:// standards.ieee.org/findstds/errata/index.html. Users are encouraged to check this URL for errata periodically. Patents Attention is called to the possibility that implementation of this standard may require use of subject matter covered by patent rights. By publication of this standard, no position is taken by the IEEE with respect to the existence or validity of any patent rights in connection therewith. If a patent holder or patent applicant has filed a statement of assurance via an Accepted Letter of Assurance, then the statement is listed on the IEEESA Website at http://standards.ieee.org/about/sasb/patcom/patents.html. Letters of Assurance may indicate whether the Submitter is willing or unwilling to grant licenses under patent rights without compensation or under reasonable rates, with reasonable terms and conditions that are demonstrably free of any unfair discrimination to applicants desiring to obtain such licenses. Essential Patent Claims may exist for which a Letter of Assurance has not been received. The IEEE is not responsible for identifying Essential Patent Claims for which a license may be required, for conducting inquiries into the legal validity or scope of Patents Claims, or determining whether any licensing terms or conditions provided in connection with submission of a Letter of Assurance, if any, or in any licensing agreements are reasonable or non-discriminatory. Users of this standard are expressly advised that determination of the validity of any patent rights, and the risk of infringement of such rights, is entirely their own responsibility. Further information may be obtained from the IEEE Standards Association 5 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. Introduction This introduction is not part of IEEE Std C62.92.1–2016, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction. This document is the first part of a five-part series of guides on the subject of electric utility system neutral grounding practices and serves as an introduction. When the series was first approved and published, it replaced IEEE Std 143™-1954, IEEE Guide for Ground-Fault Neutralizers, Grounding of Synchronous Generator Systems, and Neutral Grounding of Transmission Systems. Each of the remaining four parts addresses a specific part of the utility system to serve as a guide for neutral grounding. The five parts are as follows: a) IEEE Std C62.92.1™, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction1 b) IEEE Std C62.92.2™, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part II: Grounding of Synchronous Generator Systems c) IEEE Std C62.92.3™, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part III: Generator Auxiliary Systems d) IEEE Std C62.92.4™, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part IV: Distribution e) IEEE Std C62.92.5™, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part V: Transmission and Subtransmission Systems This series of guides is intended for application to three-phase electrical utility systems. They provide definitions and considerations that are general to all types of neutral grounding for electrical utility systems, as well as basic considerations of the selection of neutral grounding parameters that will provide for the control of overvoltage and ground-fault current on all parts of three-phase electrical utility systems. They are not intended to be used with the grounding, for example, of industrial systems, which are covered in other guides and standards. These guides and standards should be referenced, when appropriate, to gain a full picture of other grounding practices. This document has been revised to address comments received as part of the most recent re-affirmation ballot. The most significant changes were to correct an error in one of the equations in the caption beneath Figure 1 in 6.3 and to correct an omission in the drawing itself. Equation A.2 and Equation A.3 were changed to correct arithmetic errors. Most of the other comments received during that re-affirmation ballot were editorial in nature and have been addressed. Other changes include the update of reference material publish dates that may have changed or been updated. It is impossible to give recognition to all those who have contributed to the technology and practices of grounding of power systems, because work involving the preparation of this guide has been in progress for more than 30 years. However, the assistance of members, past and present, of the Neutral Grounding Devices Subcommittee of the Surge Protective Devices Committee, and other similar groups with comparable purposes, should be acknowledged. 1 Information on references can be found in Clause 2. 6 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. Participants At the time this IEEE guide was completed, the Neutral Grounding Devices Working Group had the following membership: Steven Whisenant, Chair Michael Champagne, Vice Chair Robert Allison Michael Comber Thomas Field Steven Hensley Joseph L. Koepfinger Chris Kulig Iuda Morar Caryn Riley Thomas Rozek Keith Stump Ed Taylor Arnie Vitols Reigh Walling James Wilson Chad Withers Jonathan Woodworth Benjamin York The following members of the individual balloting committee voted on this guide. Balloters may have voted for approval, disapproval, or abstention. William Ackerman Saleman Alibhay John Anthony Thomas Barnes G. Bartok Frank Basciano David Beach Barry Beaster Philip Beaumont Robert Beavers W.J. (Bill) Bergman Steven Bezner Wallace Binder William Bloethe Jeffrey Bragg Chris Brooks Andrew Brown Gustavo Brunello Zeeky Bukhala William Byrd Thomas Callsen Paul Cardinal Michael Champagne Robert Christman Michael Comber Stephen Conrad Randall Crellin Matthew Davis Gary Donner Michael Dood Randall Dotson Cliff Erven Keith Flowers Rostyslaw Fostiak Dale Fredrickson Fredric Friend Frank Gerleve David Gilmer Jalal Gohari Christine Goldsworthy Edwin Goodwin Stephen Grier Randall Groves Ajit Gwal Said Hachichi Paul Hamer Dennis Hansen Jeffrey Helzer Steven Hensley Lee Herron Werner Hoelzl Robert Hoerauf Jill Holmes Philip Hopkinson Ronald Hotchkiss James Houston Richard Jackson Alan Jensen Gerald Johnson Gael Kennedy Sheldon Kennedy Yuri Khersonsky Gary Kobet Hermann Koch Joseph L. Koepfinger Boris Kogan Jim Kulchisky Chung-Yiu Lam Thomas La Rose Michael Lauxman John Leach Paul Lindemulder Albert Livshitz Thomas Lundquist Reginaldo Maniego Albert Martin Lee Matthews Michael Maytum John McAlhaney Jr. William McBride Thomas McCarthy John McClelland Jeffery Mizener Daleep Mohla Daniel Mulkey Jerry Murphy R. Murphy Ryan Musgrove K. R. M. Nair Arun Narang Arthur Neubauer Michael Newman Joe Nims Gary Nissen James O'Brien Hans-Wo Oertel Tim Olson Carl Orde Thomas Overman Bansi Patel S. Patel Subhash Patel Brian Penny Alvaro Portillo Reynaldo Ramos Leslie Recksiedler Keith Reese Michael Roberts Timothy Robirds Charles Rogers Jesse Rorabaugh Joseph Rostron Thomas Rozek Daniel Sabin Bartien Sayogo Dennis Schlender Robert Schuerger 7 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. Carl Schuetz Kenneth Sedziol Robert Seitz Nikunj Shah Devki Sharma Hyeong Sim David Singleton Jerry Smith Andrew Steffen Keith Stump C. Tailor David Tepen James Thompson Michael Thompson Wayne Timm John Toth Remi Tremblay Demetrios Tziouvaras Joe Uchiyama Gerald Vaughn John Vergis Jane Verner Ilia Voloh Reigh Walling Lanyi Wang Daniel Ward Lee Welch Yingli Wen Steven Whisenant Kenneth White James Wilson Terry Woodyard Dean Yager Richard Young Jian Yu Luis Zambrano David Zech Peter Zhao When the IEEE-SA Standards Board approved this guide on 7 December 2016, it had the following membership: Jean-Philippe Faure, Chair Ted Burse, Vice Chair John D. Kulick, Past Chair Konstantinos Karachalios, Secretary Chuck Adams Masayuki Ariyoshi Stephen Dukes Jianbin Fan Ronald W. Hotchkiss J. Travis Griffith Gary Hoffman Michael Janezic Joseph L. Koepfinger* Hung Ling Kevin Lu Gary Robinson Annette D. Reilly Mehmet Ulema Yingli Wen Howard Wolfman Don Wright Yu Yuan Daidi Zhong *Member Emeritus 8 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. Contents 1. Overview��������������������������������������������������������������������������������������������������������������������������������������������������� 10 1.1 Scope�������������������������������������������������������������������������������������������������������������������������������������������������� 10 1.2 Purpose����������������������������������������������������������������������������������������������������������������������������������������������� 10 2. Normative references�������������������������������������������������������������������������������������������������������������������������������� 10 3. Definitions, acronyms, and abbreviations������������������������������������������������������������������������������������������������� 11 3.1 Definitions������������������������������������������������������������������������������������������������������������������������������������������ 11 3.2 Acronyms and abbreviations�������������������������������������������������������������������������������������������������������������� 12 4. Basic considerations���������������������������������������������������������������������������������������������������������������������������������� 12 4.1 Factors of system grounding��������������������������������������������������������������������������������������������������������������� 12 4.2 System neutral grounding versus apparatus neutral grounding���������������������������������������������������������� 12 5. Means of grounding���������������������������������������������������������������������������������������������������������������������������������� 13 5.1 Solidly grounded�������������������������������������������������������������������������������������������������������������������������������� 13 5.2 Inductance grounded�������������������������������������������������������������������������������������������������������������������������� 14 5.3 Resistance grounded��������������������������������������������������������������������������������������������������������������������������� 14 5.4 Resonant grounded����������������������������������������������������������������������������������������������������������������������������� 14 5.5 Capacitance grounded������������������������������������������������������������������������������������������������������������������������ 15 5.6 Undergrounded (isolated) neutral������������������������������������������������������������������������������������������������������� 15 5.7 Neutral grounding equipment������������������������������������������������������������������������������������������������������������� 15 6. Classes of grounding��������������������������������������������������������������������������������������������������������������������������������� 15 6.1 Grounding system������������������������������������������������������������������������������������������������������������������������������ 15 6.2 Quantitative determination of classes of grounding��������������������������������������������������������������������������� 15 6.3 Coefficient of grounding (COG)��������������������������������������������������������������������������������������������������������� 16 6.4 Ground-fault factor (GFF)������������������������������������������������������������������������������������������������������������������ 16 7. Characteristics of the classes of grounding������������������������������������������������������������������������������������������������ 17 7.1 Effectively grounded�������������������������������������������������������������������������������������������������������������������������� 17 7.2 Non-effectively grounded������������������������������������������������������������������������������������������������������������������� 17 7.3 Resistance grounding������������������������������������������������������������������������������������������������������������������������� 17 7.4 Inductance grounded�������������������������������������������������������������������������������������������������������������������������� 18 7.5 Resonant grounded����������������������������������������������������������������������������������������������������������������������������� 19 7.6 Undergrounded systems��������������������������������������������������������������������������������������������������������������������� 20 8. Annexes and bibliography������������������������������������������������������������������������������������������������������������������������� 21 Annex A (informative) Calculation of coefficients of grounding������������������������������������������������������������������� 22 Annex B (informative) Identity of ground and neutral conductors����������������������������������������������������������������� 31 Annex C (informative) Bibliography������������������������������������������������������������������������������������������������������������� 35 9 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction 1. Overview 1.1 Scope This guide is intended for application to three-phase electrical utility systems and is Part I of the IEEE Std C62.92 series. This part provides definitions and considerations that are general to all types of neutral grounding for electrical utility systems. Goals of system grounding, means of grounding, and classes of grounding are addressed in this part. 1.2 Purpose This guide presents basic considerations of the selection of neutral grounding parameters that will provide for the control of overvoltage and ground-fault current on all parts of three-phase electrical utility systems. 2. Normative references The following referenced documents are indispensable for the application of this document (i.e., they must be understood and used, so each referenced document is cited in text and its relationship to this document is explained). For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments or corrigenda) applies. Accredited Standards Committee C2-2017, National Electrical Safety Code® (NESC®).2 IEEE Std 80™, IEEE Guide for Safety in AC Substation Grounding.3,4 IEEE Std 142™, IEEE Recommended Practice for Grounding of Industrial and Commercial Power Systems (IEEE Green Book ™).5 2 National Electrical Safety Code and NESC are both registered trademarks and service marks of the Institute of Electrical and Electronics Engineers, Inc. and is available from the Institute of Electrical and Electronics Engineers, Inc., 445 Hoes Lane, P.O. Box 1331, Piscataway, NJ 08855-1331, USA (http://standards.ieee.org/). 3 The IEEE standards or products referred to in this clause are trademarks of The Institute of Electrical and Electronics Engineers, Inc. 4 This publication is available from The Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854, USA (http://standards.ieee.org/). 5 IEEE Green Book is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc. 10 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction IEEE Std C62.92.2™, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems— Part II: Grounding of Synchronous Generator Systems. IEEE Std C62.92.3™, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems— Part III: Generator Auxiliary Systems. IEEE Std C62.92.4™, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems— Part IV: Distribution. IEEE Std C62.92.5™, IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems— Part V: Transmission Systems and Subtransmission Systems. 3. Definitions, acronyms, and abbreviations 3.1 Definitions For the purposes of this document, the following terms and definitions apply. The IEEE Standards Dictionary Online should be consulted for terms not defined in this clause.6 capacitance grounded: Grounded through an impedance, the principal element of which is capacitance. class of grounding: A specific range or degree of grounding, e.g., effectively and non-effectively. coefficient of grounding (COG): The ratio, ELG/ELL (expressed as a percentage), of the highest root-meansquare (rms) line-to-ground power-frequency voltage ELG on a sound phase, at a selected location, during a fault to ground affecting one or more phases to the line-to-line power-frequency voltage ELL that would be obtained at the selected location with the fault removed. effectively grounded: An expression that means grounded through a grounding connection of sufficiently low impedance (inherent or intentionally added or both) that a ground fault that may occur cannot build up voltages in excess of limits established for apparatus, circuits, or systems so grounded. ground fault factor (GFF): The ratio of the highest phase-to-ground power frequency voltage on an unfaulted phase during a line-to-ground fault to the phase-to-ground power-frequency voltage without the fault. inductance grounded: Grounded through an impedance, the principal element of which is inductance. means of grounding: The physical devices by which various degrees of grounding are achieved, e.g., inductance grounding, resistance grounding, or resonant grounding. non-effectively grounded: Grounded through a grounding connection of sufficient impedance (inherent or intentionally added or both) that a ground fault that might occur results in voltages in excess of limits established for apparatus, circuits, or systems as defined by an effectively grounded system. resistance grounded: Grounded through an impedance, the principal element of which is resistance. resonant grounded: A system in which one or more neutral points are connected to ground through reactors that approximately compensate the capacitive component of a single-phase-to-ground-fault current. solidly grounded: Connected directly to ground through an adequate ground connection in which no impedance has been inserted intentionally. 6 IEEE Standards Dictionary Online is available at: http://dictionary.ieee.org 11 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction ungrounded: A system, circuit, or apparatus without an intentional connection to ground, except through potential-indicating or measuring devices or other very-high-impedance devices. 3.2 Acronyms and abbreviations COG Coefficient of grounding EHV Extra high voltage GFF Ground fault factor HV High voltage OHGW Overhead ground wire(s) NOTE—This guide distinguishes high voltage (HV) from extra high voltage (EHV) as follows: HV refers to nominal system voltages less than or equal to 230 kV, whereas EHV refers to nominal system voltages above 230 kV.7 4. Basic considerations There is no one simple answer to the application of grounding. Each of a number of possible solutions to a grounding problem has at least one feature that is outstanding, but which is obtained at some sacrifice of other features that may be equally worthy. Thus, the selection of the class and means of grounding is often a compromise between somewhat conflicting solutions (see IEEE Tutorial Course [B17]).8 4.1 Factors of system grounding The basic factors in selecting a grounding scheme for any given system are as follows: a) Voltage ratings and degree of surge-voltage protection available from surge arresters b) Limitation of transient line-to-ground overvoltages (see IEEE Std C62.92.2 and IEEE Tutorial Course [B17]) c) Sensitivity and selectivity of the ground-fault relaying d) Limitation of the magnitude of the ground-fault current e) Safety (see National Electrical Safety Code® (NESC®) (Accredited Standards Committee C2-2017) and IEEE Std 80) These basic factors, when properly evaluated, can have a significant influence on system economics, details of system design and physical layout, and service continuity. 4.2 System neutral grounding versus apparatus neutral grounding In power engineering, it is common to speak of grounding the system neutral either directly or through an impedance. Actually, the system neutral is a convenient fiction, not a physical point, and cannot be physically connected to ground. While it is possible to ground the neutral conductor of a four-wire, three-phase system, it is the neutral grounding of specific pieces of power-system apparatus, especially power transformers and generators that affects system neutral grounding the most. 7 8 Notes in text, tables, and figures are given for information only and do not contain requirements needed to implement the standard. The numbers in brackets correspond with to those of the bibliography in Annex C. 12 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction In this guide, the term “means of grounding” is used to describe the particular technique used to ground the neutral of a specific piece of apparatus. For example, resistance grounding is a means of grounding the neutral of a piece of apparatus, in this case by means of a resistor. The term “class of grounding” is used to categorize system grounding in terms of its performance characteristics. In a simple power system, like a typical distribution system or power-plant auxiliary system, where a single transformer serves as both the power source and system-neutral grounding point, the means of grounding of that transformer neutral defines the grounding technique (means) of the system. For example, a system supplied by a single transformer whose neutral is grounded through a resistance would typically be referred to as a resistance-grounded system. In more complex systems, like a typical high voltage (HV) or extra-high voltage (EHV) transmission system, there are many pieces of apparatus (transformers, capacitor banks, reactors, etc.) that may have grounded neutrals. In such multiple-grounded systems, the class of grounding of the system is determined by the cumulative effect of all the grounding points. If most of the major transformer neutrals are grounded by similar means, then the system may loosely be described as being of one means (e.g., an inductance grounded system). In general, where there are multiple grounding points of different types of apparatus and different means of apparatus neutral grounding, the class of grounding can only be determined by the zero-sequence to positive-sequence symmetrical component ratios, as viewed from a selected location. (See Clause 7 and Table 1.) (For further information see Clarke [B6], and Wagner and Evans [B22].) 5. Means of grounding 5.1 Solidly grounded The term solidly grounded, though commonly used, may be somewhat misleading because a transformer may have its neutral connected solidly to ground, and yet the resulting zero-sequence impedance (see Figure 1) could be so high, due to the system or transformer characteristics, that high phase-to-ground voltages would develop during ground-fault conditions. Instead, to define grounding positively and logically as to degree, the term effectively grounded has come into use, as is discussed in 7.1. NOTE 1— X 1 , X 2 , and X 0 are the respective source voltages (line-to-neutral). NOTE 2— R1 and R2 are the equivalent source resistance and reactance, per phase. Figure 1—Idealized three-phase system (figure continues on next page) 13 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction NOTE 3— R0 and E LG / E LL ×100% are the neutral resistance and reactance of the system as seen at the source. NOTE 4— E LG is the total system capacitance to ground and is obtained by connecting all three phases together and measuring the capacitance with the neutral grounding branch open-circuited. NOTE 5— E LL is the grounded-wye partial, or zero-sequence, capacitance of the system. NOTE 6— Va is the ungrounded wye equivalent of the interphase partial capacitances of the system, obtained by subtracting the zero-sequence capacitance Cg/3 from the positive sequence capacitance C1. NOTE 7— Vb is frequency in hertz. NOTE 8—The switch Vc simulates a single-line-to-ground fault on a-phase. NOTE 9— Rs is the prefault line-to-ground voltage at the fault, the energization voltage. Figure 1—Idealized three-phase system 5.2 Inductance grounded This means of grounding is sometimes loosely referred to as reactance grounded. The class is often subdivided into low- or high-inductance categories. The inductance may either be inserted directly in the neutral connection to ground or obtained indirectly by increasing the reactance of the ground return circuit. The latter may be done by intentionally increasing the zero-sequence reactance of apparatus connected to ground or by omitting some of the possible connections from apparatus neutrals to ground. 5.3 Resistance grounded This means is frequently subdivided into low- or high-resistance categories. The resistance may be inserted either directly in the connection to ground or indirectly as, for example, in the following: a) In the secondary of a transformer, the resistance may be inserted between neutral and ground b) In the corner of a broken delta-connected secondary, the resistance may be inserted between the corner and one winding terminal of a wye-delta grounding transformer (See IEEE Std C62.92.2 and IEEE Std C62.92.3 for application information on resistance grounding.) It should be noted that a grounding resistor may have a considerable inherent inductance. For example, a castiron grid resistor may have a power factor of 98% or less, resulting in a reactance of about 20% of the resistance; at system frequency (see T&D Reference Book [B5]). 5.4 Resonant grounded As defined in Clause 3, a resonant grounded system is inductance grounded through inductors with values of reactance such that, during a fault between one of the conductors and ground, the power-frequency inductive current flowing in the grounding inductance(s) and the power-frequency capacitance current flowing between the unfaulted conductors and ground are substantially equal in magnitude and 180° out of phase. Therefore, they almost cancel each other during the fault. The type of grounding inductor used is commonly referred to as a ground fault neutralizer, arc-suppression coil, or Peterson coil (see Transmission Grounding Guide [B3], and Willheim and Waters [B23]). 14 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction It is expected that the magnitude of the rated-frequency, single-phase-to-ground fault current will be so small that an arcing fault in air will be self-extinguishing. See Ground Fault Neutralizer Guide [B8], and Willheim and Waters [B23] for application information about resonant grounding in transmission and subtransmission systems; and IEEE Std C62.92.2 for application to synchronous generator grounding. 5.5 Capacitance grounded Capacitance is seldom, if ever, inserted directly in a connection to ground for system grounding purposes. However, capacitance may be connected to ground for voltage surge front-of-wave sloping purposes. Also, neutrals of shunt capacitor banks have been connected solidly to ground on otherwise ungrounded systems. Such applications should be carefully analyzed for overvoltages during fault conditions (see Ground Fault Neutralizer Guide [B8], and Peterson [B20]). Capacitance grounding should be avoided, or carefully analyzed, for resonance conditions or increased fault current. 5.6 Undergrounded (isolated) neutral An ungrounded system, while having no intentional connection to ground, except through potential-indicating or measuring devices, or other very-high-impedance devices, is coupled to ground through the distributed capacitance of its phase conductors, transformer windings, and machine windings. 5.7 Neutral grounding equipment Requirements and tests for neutral grounding devices may be found in IEEE Std 32™-1972 (R1997) [B11]. 6. Classes of grounding 6.1 Grounding system A system that is a combination of lines, cables, or conductors with apparatus may be broadly classified as either grounded or ungrounded. A grounded system is a system in which at least one conductor (usually the neutral point of a transformer or generator winding) is intentionally connected to ground either directly or through an impedance. A system grounded through impedance is referred to generically as an impedance grounded system. 6.2 Quantitative determination of classes of grounding Various classes of grounding are available to the system designer, each having a unique set of attributes. The response characteristics of the various classes of grounding may be defined or classified in terms of the ratios of symmetrical component parameters, such as the positive-sequence reactance X s , the negative-sequence reactance Rn , the zero-sequence reactance X n , the positive-sequence resistance Cg , the negative-sequence resistance Cg / 3 , and the zero-sequence resistance Cs (see Clarke [B6], Wagner and Evans [B22], and Willheim and Waters [B23]). To facilitate an understanding of this approach, reference is made to the simplified, idealized three-phase circuit in Figure 1 and its equivalent sequence diagram for a single-line-to-ground fault as shown in Figure 2. Subscripts 1, 2, and 0 indicate positive-, negative-, and zero-sequence parameters, respectively. A quantitative description of the various classes of grounding is presented in 7.1 and 7.2, and is then used to describe the attributes of systems that are grounded by various means in 7.3 through 7.6. Characteristics of grounding (by class and means) are listed in Table 1 (see 7.4). Note that this conventional representation does not include all impedances in the ground current path and may not give conservative results in all cases. (See Annex B for more information on this topic.) 15 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction NOTE 1— f is the Thevenin circuit pre-fault voltage. NOTE 2— S is the line-to-neutral source voltage of Figure 1. NOTE 3— Vf is the fault line current through closed switch S of Figure 1. NOTE 4—The equivalence sign (≈) indicates the result when capacitance is negligible. NOTE 5—The remaining variables are defined in the notes following Figure 1. Figure 2—Sequence diagram for line-to-ground fault, through closed switch S of Figure 1 6.3 Coefficient of grounding (COG) The term coefficient of grounding (COG) is used in system grounding practice. COG is defined as 3 , where COG GFF = 3 × is the highest root-mean-square (rms), line-to-ground power-frequency voltage on a 100 sound phase, at a selected location, during a line-to-ground fault affecting one or more phases. GFF is the line-to-line power-frequency voltage that would be obtained, at the selected location, with the fault removed. The COG for three-phase systems is calculated from the phase-sequence impedance components, as viewed from the fault location. The COG is useful in the selection of a surge arrester rating for a selected location (see IEEE Std 32-1972 [B11], IEEE Std C62.2™-1987 [B13], IEEE Std C62.22™-2009 [B15], and IEEE Tutorial Course [B17]). 6.4 Ground-fault factor (GFF) The term ground-fault factor (GFF) is, to a limited extent, now used instead of COG. At a selected location on a three-phase system, and for a given system configuration, the GFF is the ratio of the highest rms line-toground power-frequency voltage (as measured phase-to-ground) on a sound phase during a fault to ground (affecting one or more phases at any point) to the rms power-frequency voltage (as measured phase-to-ground) 16 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction that would be obtained at the selected location with the fault removed (see IEEE Std C62.82.1-2010 [B16]). Thus, the GFF is related to the COG by COG , as shown in Equation (1) below: (1) Vf where Va is the ground-fault factor I o is the coefficient of grounding expressed as a percentage 7. Characteristics of the classes of grounding Ratios of the symmetrical component parameters are used to characterize the classes of grounding. These characteristics, and the unique set of attributes defining the various classes of grounding, are given in Table 1 and briefly discussed in 7.1, 7.2, 7.3, 7.4, 7.5, and 7.6. Table 1 contains a general classification of grounding, together with the associated class, fault current, and transient voltage characteristics. 7.1 Effectively grounded For the purposes of this guide, an effectively grounded system is one that is grounded through a sufficiently low impedance (inherent or intentionally added, or both) so that the COG does not exceed 80%. This value is obtained approximately when, for all system conditions, the ratio of the zero-sequence reactance to the positive-sequence reactance (X0/X1) is positive and < 3, and the ratio of zero-sequence resistance to positive-sequence reactance (R0/X1) is positive and < 1 (see IEEE Std C62.1-1989 [B12], IEEE Std C62.2-1987 [B13], IEEE Tutorial Course [B17], and Willheim and Waters [B23]). Effective grounding is frequently employed in distribution and transmission systems (see IEEE Std C62.22-2009 [B15], IEEE Std C62.92.4, and IEEE Std C62.92.5. 7.2 Non-effectively grounded For the purposes of this guide, a non-effectively grounded system is one where the COG exceeds 80% at the location of the fault. Note that, because of the impedance of lines and cables, certain locations or portions of an effectively-grounded system may be non-effectively grounded, even though the majority of the system is effectively-grounded. In general, all of the impedance-grounded systems listed in 7.3, 7.4, 7.5, and 7.6 are non-effectively grounded. 7.3 Resistance grounding A resistance grounded system is predominately grounded by means of resistance. When a system is resistance grounded, the zero-sequence reactance viewed from the fault may be inductive or capacitive, depending on the size, number, and location of the neutral-grounding resistors and the capacitance to ground of the remaining system. With low-resistance grounding, X 0 will ordinarily be positive; the fundamental-frequency phase-to-ground voltage will, in general, not exceed normal line-to-line voltage; and the neutral-to-ground voltage will not exceed normal line-to-neutral voltage. If a system is low-resistance grounded, the natural-frequency voltages at the initiation of a ground fault are significantly reduced. The phase voltages are essentially the fundamental-frequency voltages. The fundamental-frequency voltages with low-resistance grounding are generally higher than the fundamental- frequency voltages obtained with corresponding values of neutral-grounding inductive reactance. 17 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction With high-resistance grounding, X 0 may be negative. In that event, phase-to-ground voltages may be greater than normal line-to-line voltages, and neutral-to-ground voltages may be greater than normal line-to-neutral voltages (see Clarke, Crary, and Peterson [B7], and Peterson [B20]). 7.4 Inductance grounded An inductance-grounded system is one that is predominately grounded by means of neutral inductors or grounding transformers, or by omitting connections to ground on some of the transformers of a multiple-grounded system. When a system is grounded through an inductance (less than that of a ground-fault neutralizer), the zero- sequence reactance viewed from the fault is inductive rather than capacitive, and the zero-sequence resistance is relatively small. Accordingly, during a fault, the fundamental-frequency phase-to-ground voltages will not exceed normal line-to-line voltage and the neutral-to-ground voltage will not exceed normal line-to-neutral voltage. Following the initiation of a fault, simple, linear systems with inductance-grounded neutrals will have maximum transient voltages to ground on the unfaulted phases not exceeding 2.73 times normal. The voltage to ground at the neutral will not exceed 1.67 times normal line-to-neutral voltage (see Clarke, Crary, and Peterson [B7], and Peterson [B20]). Table 1 presents characteristics of grounding for the various classes and means of grounding discussed thus far. Table 1—Characteristics of grounding Grounding classes and means Ratios of symmetrical component parameters (NOTE 1) X0⁄X1 R0⁄X1 Percent fault current (NOTE 2) Per unit transient LG voltage (NOTE 3) Reference [B3] R0⁄X0 A. Effectively—Note (4) 1. Effective 0–3 0–1 — > 60 ≤2 2. Very effective 0–1 0–0.1 — > 95 < 1.5 Low inductance 3–10 0–1 — > 25 < 2.3 [B3] High inductance > 10 <2 < 25 ≤ 2.73 [B3] 0–10 ≥2 < 25 < 2.5 > 100 ≤ (–1) <1 ≤ 2.73 — >2 < 10 ≤ 2.73 — — <1 ≤ 2.73 <8 ≤3 B. Non-effectively Inductance Resistance Low resistance High resistance—Note (8) Inductance and resistance > 10 Resonant—Note (5) [B7], IEEE Std C62.92.4 Ungrounded capacitance Range A—Note (6) – ∞ to –40 — — [B6], [B18] Table continues 18 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Table 1—Characteristics of grounding (continued) Grounding classes and means Range B—Note (7) Ratios of symmetrical component parameters (NOTE 1) X0⁄X1 R0⁄X1 R0⁄X0 –40 to 0 — — Percent fault current (NOTE 2) Per unit transient LG voltage (NOTE 3) Reference >8 >3 [B6], [B18] NOTE 1—Values of the COG corresponding to various combinations of these ratios are shown in the figures in Annex A. COG affects the selection of surge arrester ratings (see IEEE Std C62.2-1987 [B13] and IEEE Std C62.22-2009 [B15]). NOTE 2—Ground fault current in percentage of the three-phase short circuit value (IEEE Std 142). NOTE 3—Transient line-to-ground voltage, following the sudden application of a fault, in per unit of the crest of the prefault line-to-ground operating voltage, from Clarke, Crary, and Peterson [B7], and Peterson [B20]) for a simple, linear network. NOTE 4—In linear circuits, Class A1 limits the fundamental line-to-ground voltage on an unfaulted phase to 138% of the prefault voltage; Class A2 to less than 110%. NOTE 5—See 7.5, Willheim and Waters [B23], and precautions given in IEEE Std C62.92.2, IEEE Std C62.92.3, IEEE Std C62.92.4 and IEEE Std C62.92.5. NOTE 6—Usual isolated neutral (ungrounded) system for which the zero-sequence reactance is capacitive (negative). NOTE 7—Refer to 7.6. Each case should be evaluated on its own merits. NOTE 8—In a high-resistance grounded system Rs , X s , and X n are negligible compared to Rn and X Cg . R0 + jX 0 = 3Rn ( − j3X Cg ) / ( 3Rn − j3X Cg ) . Thus R0 / X 0 = − X Cg / Rn . For a properly designed high-resistance system, Rn ″ X Cg , and therefore R0 / X 0 ≤ ( −1) . 7.5 Resonant grounded A resonant-grounded system is one that is grounded through one or more ground-fault neutralizers (see Willheim and Waters [B23]). When a system is to be grounded through a ground-fault neutralizer, the neutral inductance provided by the neutralizer coil is adjusted as in Equation (2) below so that: 3 X Cg = 3 X n + X s (2) where X Cg is the capacitive reactance of the system to ground Cg is the total capacitance of the system to ground X n is the neutral reactance X s is the system’s reactance (See Figure 1 and Figure 2 for further definitions of X Cg and X n .) For resonant-grounded systems, Rs and X s can generally be neglected because they are very small in comparison to X n and X Cg . Thus, when adjusted to resonance, X n = X Cg . R0 + jX 0 is the equivalent series representation of the parallel inductance/capacitance network, as defined in Figure 3. If Rs and X s are small in comparison with X n , X 0 approaches infinity, because the zero-sequence 19 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction network is parallel resonant. With resistance Rs included (depending on its value), R0 may be large with respect to X 0 . Based on either assumption, the zero sequence network presents a very high impedance to the flow of 60 Hz current through a fault to ground. The fundamental-frequency voltages on the unfaulted phases, during a line-to-ground fault, are essentially line-to-line voltages. They are not increased by the presence of fault resistance. The maximum transient voltages to ground of the unfaulted phases are less than 2.73 times normal and the neutral-to-ground voltage is less than 1.67 times normal line-to-neutral voltage (see Clarke, Crary, and Peterson [B7], and Peterson [B20]). Figure 3—Resonant zero-sequence network 7.6 Undergrounded systems An ungrounded system is one with no intentional connections to ground except for potential measuring or surge protection apparatus. Though called ungrounded, this type of system is in reality coupled to ground through the distributed capacitance of its phase windings and conductors. In the absence of a ground fault, the neutral of an ungrounded system under reasonably balanced load conditions will usually be close to ground potential, being held there by the balanced electrostatic capacitance between each phase conductor and ground. In an ungrounded system, X 0 is negative and of the order of magnitude of the zero-sequence capacitive reactance, while R0 / X 0 is relatively small. Under fault conditions, the fundamental-frequency phase-to-ground voltages may be in excess of normal line-to-line voltages, and in some cases, particularly when the system is large in extent, these voltages may be considerably higher (see Clarke, Crary, and Peterson [B7], and Peterson [B20]). There are a number of economic factors and operating practices governing the choice between grounded and ungrounded systems. Ungrounded systems may require higher insulation levels as a result of possible severe transient overvoltages. Abnormal insulation stress may be reduced when X 0 / X 1 lies between –∞ and –40. In addition, it can be difficult and time consuming to identify the location of ground faults, especially when the system is large. When X 0 / X 1 is in the range of –40 to 0, severe series-resonance overvoltages can occur if the circuit response is linear. However, in ferro-nonlinear circuits involving a saturating transformer, highly distorted, less severe oscillations may be generated over a broad range of negative X 0 / X 1 (see Clarke, Crary, and Peterson [B7], and Peterson [B20]). Generally, capacitance grounding and such circuit conditions should be avoided and each case should be carefully analyzed (see Karlicek and Taylor [B18]). However, cases exist showing that ungrounded systems can have satisfactory operating performance. 20 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction 8. Annexes and bibliography The figures in Annex A give COG for the ranges of positive X 0 / X 1 and R0 / X 1 , and generally indicate the ranges of each class. Annex B contains a discussion of the effects and the modeling of earth-return path impedances such as neutral conductors, overhead ground wires (OHGWs), tower footing resistances, and substation ground-grid resistances. Annex C is a bibliography of related standards, texts, and technical papers, some of which are referenced in this guide. 21 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Annex A (informative) Calculation of coefficients of grounding The term COG is defined as the ratio of ELG / ELL , expressed as a percentage, of the highest rms line-to-ground power frequency voltage ( ELG ) on a sound phase, at a selected location, during a fault to earth affecting one or more phases to the line-to-line power frequency voltage ( ELL ) that would be obtained, at the selected location, with the fault removed. COG may be calculated from the known impedances of the system and the fault. For this purpose, it is convenient to express the system impedances in terms of their equivalent symmetrical component impedances Z1 , Z 2 , and Z 0 (see Clarke [B6], and Wagner and Evans [B22]). As defined above, the COG for a specific location may vary depending on the type of fault, the fault location, and the impedance in the fault. For the purposes of constructing Figure A.2, Figure A.3, Figure A.4, Figure A.5, and Figure A.6, the following assumptions were made: a) The COG is to be determined for the same location that the fault is placed. b) The fault type (single or double phase to ground) is that which produces the highest COG. c) The fault impedance, if any is purely resistive and has the value which produces the highest COG. d) The negative sequence impedance of the system at the fault location is equal to the positive sequence impedance ( Z 2 = Z1 ). For a system with positive X 0 , coefficients of grounding for locations other than the fault location are generally the same as or lower than the coefficient for the fault location. In exceptional circumstances, coefficients may be slightly higher at locations where appreciable capacitive zero sequence current flows through high inductance lines to reach the fault location. In systems with negative X 0 , the COG is generally lowest at the fault location and higher at remote locations. For this reason, the usefulness of the coefficient on such systems is limited to systems in which line impedances are negligibly small. Given these assumptions and the definition above, the quantities that must be calculated to determine the COG are the a-phase voltage, VaLLG , for a phase b- and c-phase-to-ground fault and the b- and c-phase voltages, VbLG and VcLG , for an a-phase-to-ground fault. These faults and their symmetrical component-equivalent networks are shown in Figure A.1. 22 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Figure A.1—Symmetrical component equivalent networks for two fault types used in calculations From Clarke [B6], the significant voltages for these faults are given in Equation (A.1), Equation (A.2), and Equation (A.3): VaLLG = V f × 3Z 2 ×( Z 0 + 2 Z F ) ( Z1 × Z 2 ) + ( Z1 + Z 2 ) ×( Z 0 + 3Z F ) (A.1) VbLG = V f × 3a 2 Z F − j 3 ×( Z 2 − aZ 0 ) Z 0 + Z1 + Z 2 + 3Z F (A.2) VcLG = V f × 3aZ F + j 3 ×( Z 2 − a 2 Z 0 ) Z 0 + Z1 + Z 2 + 3Z F (A.3) where V f is the power frequency voltage line-to-ground, (kV) VaLLG is the line-to-ground voltage for a-phase during a line-to-line-to-ground fault of b and c phases (kV) VbLG and VcLG are the respective line-to-ground voltage of each phase during an a-phase-toground fault (kV) Z1 Z 2 , and Z 0 are the positive, negative, and zero sequence impedances, respectively (Ω) Z F is the fault impedance (Ω) a and a 2 are phasor operators a = −0.5 + j 3 3 = 1∠120° ; a 2 = −0.5 − j = 1∠240° . 2 2 23 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Letting Z 2 = Z1 , Z F = RF and rearranging, as seen in Equation (A.4), Equation (A.5), and Equation (A.6): VaLLG = V f × 3Z 0 + 6 RF Z1 + 2 Z 0 + 6 RF (A.4) Z 0 − Z1 VbLG = V f ×a 2 − 2 Z1 + Z 0 + 3RF (A.5) Z 0 − Z1 VcLG = V f ×a − 2 Z1 + Z 0 + 3RF (A.6) where V f is the power frequency voltage line-to-ground (kV) VaLLG is the line-to-ground voltage for a-phase during a line-to-line-to-ground fault of b and c phases (kV) VbLG and VcLG are the respective line-to-ground voltage of each phase during an a-phase-toground fault (kV) Z1 Z 2 , and Z 0 are the positive, negative, and zero sequence impedances, respectively (Ω) RF is the fault resistance (Ω) a and a 2 are phasor operators By the definition of COG: Z 0 + 2 RF COGa = 3 × Z1 + 2 Z 0 + 3RF (A.7) COGb = Z 0 − Z1 1 2 ×a − 2 Z1 + Z 0 + 3RF 3 (A.8) COGC = Z 0 − Z1 1 ×a − 2 Z1 + Z 0 + 3RF 3 (A.9) where COGa , COGb , and COGc are the coefficients of grounding for each respective phase Z1 , Z 2 , and Z 0 are the positive, negative, and zero sequence impedances, respectively (Ω) RF is the fault resistance (Ω) a and a 2 are phasor operators are a = −5 + j 3 3 = 1∠120 and a 2 = 0.5 − j = 1∠240 2 2 To eliminate one parameter, it is convenient to divide each impedance by X 1 . Defining the ratios R '1 = R1 / X 1 ; R '0 = R0 / X 1 , X '0 = X 0 / X 1 , R ' F = RF / X 1 ( R '0 + 2 R ' F ) + jX '0 COGa = 3 × R '1 + 2 R '0 + 6 R ' F + j (1 + 2 X '0 ) COGb = (A.10) ( R '0 + R '1 ) + j ( X '0 −1) 1 2 ×a − 2 R '1 + R '0 + 3R ' F + j ( X '0 + 2) 3 (A.11) 24 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction COGc = ( R '0 + R '1 ) + j ( X '0 −1) 1 ×a − 2 R '1 + R '0 + 3R ' F + j ( X '0 + 2) 3 (A.12) where COGa , COGb , and COGc R '1 , R '2 , R ' F and R '0 are the coefficients of grounding for each respective phase are defined above Equation (A.10) In Figure A.2, Figure A.3, Figure A.4, Figure A.5, and Figure A.6, the curves were obtained by means of a digital computer analysis of Equation (A.10), Equation (A.11), and Equation (A.12). In particular, Equation (A.13), the computer was programmed to find pairs ( R '0 , X '0 ) for which: COG = limitC and ∂COG/∂R' F =0; or R' F >0; or ∂COG/∂R' F ≤ 0;R' F =0 (A.13) where COG is the maximum of COGa , COGb , and COGc C is a selected limit for example 80% R '1 was fixed at five discrete values between 0 and 2 to produce the five graphs The partial derivative was simulated by a discrete differential. It should be recognized that in some circumstances, the assumptions made in producing these curves will not be valid and COG may be higher than shown. For example, a capacitive fault impedance that can be obtained from a ground fault in a capacitor bank could yield a higher COG. Such cases can be analyzed individually by the use of Equation (A.1), Equation (A.2), and Equation (A.3). NOTE—Parameter values given against each curve indicate limiting value of COG within area circumscribed by curve. Definitions of grounding class or means is indicated in each area. 25 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Figure A.2—Boundaries for coefficients of grounding for ratio of positive-sequence resistance R1 to positive-sequence reactance X1 of 0 26 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction NOTE—Parameter values given against each curve indicate limiting value of COG within area circumscribed by curve. Definitions of grounding class or means is indicated in each area. Figure A.3—Boundaries for coefficients of grounding and ratio of positive-sequence resistance R1 to positive sequence reactance X1 of 0.2 27 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction NOTE—Parameter values given against each curve indicate limiting value of COG within area circumscribed by curve. Definitions of grounding class or means is indicated in each area. Figure A.4—Boundaries for coefficients of grounding for ratio of positive-sequence resistance R1 to positive-sequence reactance X1 of 0.5 28 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction NOTE—Parameter values given against each curve indicate limiting value of COG within area circumscribed by curve. Definitions of grounding class or means is indicated in each area. Figure A.5—Boundaries for coefficients of grounding for ratio of positive-sequence resistance R1 to positive-sequence reactance X1 of 1.0 29 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction NOTE—Parameter values given against each curve indicate limiting value of COG within area circumscribed by curve. Definitions of grounding class or means are indicated in each area. Figure A.6—Boundaries for for coefficients of grounding for ratio of positive-sequence resistance R1 to positive-sequence reactance X1 of 2.0 30 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Annex B (informative) Identity of ground and neutral conductors In the calculation of the zero-sequence impedance of power transmission lines (see IEEE Std C62.92.5 and distribution lines (see IEEE Std C62.92.4, it has been a conventional practice to include simplifying assumptions about the grounding network to reduce the complexity of the calculations. —— The impedance of grounding electrodes, such as ground rods, tower footings, and station ground grids to remote ground has been assumed to be negligible. Grounded conductors such as multi- grounded neutrals, cable sheaths, and OHGWs are assumed to be perfectly connected to earth. —— The impedance of the earth-return path has been incorporated into the zero-sequence impedance of the line conductors so that the earth can be considered an equipotential surface. A consequence of this assumption is that zero-sequence voltages calculated with respect to local ground are correct; however, the calculations cannot provide zero-sequence voltage at a given point with respect to ground at another point; likewise, differences in ground potential between two points cannot be calculated. Even though computer programs could easily deal with the complexity, these simplifying assumptions persist to the present day because of the following: —— The data about the impedance of grounding electrodes is not as readily available as conventional line impedance data. —— It is generally believed that the results of ignoring the grounding impedances are conservative, i.e., fault studies ignoring grounding impedances will yield the highest fault currents and highest temporary overvoltages. —— The distribution of fault currents in the grounding network and differences in grounding potential are generally not considered significant for short-circuit duty and arrester application purposes. To illustrate the significance of these simplifying assumptions, consider the system shown diagrammatically in Figure B.1. This system consists of a three-span transmission line, with OHGW, linking two substations with transformers whose neutrals are grounded through inductors. (The OHGW could also represent the multi-grounded neutral conductor of a distribution line.) 31 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Figure B.1—Diagram of transmission line and substations Figure B.2 shows the conventional zero-sequence impedance diagram for this system, assuming fully transposed phase conductors. Note that only the zero sequence impedance of the line, the transformers and the neutral inductors are specifically represented. The effect of the ground or multi-grounded neutral conductor and the impedance of the earth-return path are incorporated into the value of Z 0 L and do not appear directly. Figure B.2—Conventional simplified zero-sequence network Figure B.3 shows an expanded version of Figure B.2 in which the identity of the overhead neutral conductor has been retained in the zero-sequence network. Note that only two towers are shown in Figure B.3; most lines would have many more towers. Retaining the identity of the neutral conductor and towers permits separate evaluation of phase-to-neutral and phase-to-ground voltages and fault currents at a particular location. For a phase-to-ground fault, I f / 3 enters the network at g and exits at p; for a phase-to-neutral fault, I f / 3 enters at n and exits at p. The only information lost by this representation is the difference of earth potential between earth points. 32 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction NOTE 1— Rgg is the substation ground mat resistance to ground. NOTE 2— Rt is the tower footing or pole ground resistance to ground. NOTE 3— Z 0 is the zero-sequence self-impedance of line section between two towers, ignoring neutral conductor. NOTE 4— Z nn is the self-impedance, with earth return, of neutral conductor section between two towers. NOTE 5— Z ph − n is the average mutual impedance, with earth return, from phase conductors to neutral conductor Figure B.3—Zero sequence network with overhead ground wires (OHGWs) retained Techniques for calculation of Z 0 , Z nn , and Z ph − n are provided in Anderson [B1], Clarke [B6], and Wagner and Evans [B22]. Calculation methods for Rgg and Rt are presented in IEEE Std 80™-2013. The method of calculating line impedances with earth return, as presented in Anderson [B1], Clarke [B6], and Wagner and Evans [B22], and most other texts, is based on the work of John R. Carson [B4]. In Carson’s work, the impedance of the earth-return path is incorporated into the calculated impedance for the line and equivalent circuits. Carson’s formulations do not give differences in potential between ground points. Clarke [B6], using the work of Rüdenberg [B21], provides a method of separating the impedance of the earth-return path from the impedance of the line. Figure B.4 shows a detailed zero-sequence diagram based on the model proposed by Clarke. Note that the substation ground-grid resistances, Rgg , the tower footing resistances, Rt , the OHGW, n , and the earth-return impedance, Z g , are all specifically represented. Z g = 0.0592 × D f f + j ×0.1736 ×log10 e / km 60 60 h (B.1) where Z g is the earth-return impedance in Ω/km f is the frequency in Hz ρ is the earth resistivity in Ω∙m De is 658.4 × ρ / f in m h is the average conductor height in m 33 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Figure B.4—Zero-sequence impedance diagram with earth-return impedance The zero-sequence parameters, R0 and X 0 , calculated from Figure B.3 or Figure B.4 for a phase-to-tower fault (terminals p-n) may be significantly different from those for a phase-to-ground fault (terminals p-g). Likewise, the zero-sequence voltage seen by a piece of equipment connected from phase to the tower (p-n) may be different from those seen phase to ground (p-g). The curves of Annex A show how the COG increases rapidly for ( R0 / X 1 ) > 1 . Because the inclusion of Rgg and Rt tends to increase R0 , detailed representation of a line may be necessary to establish accurate maximum values of the COG. In a paper by Mancao, Burke, and Myers [B19], which uses a three-phase analysis program with complete representation of the neutral conductor and grounding impedances, the authors suggest that temporary overvoltages on distribution systems may be significantly higher when grounding impedances are represented. 34 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction Annex C (informative) Bibliography Bibliographical references are resources that provide additional or helpful material but do not need to be understood or used to implement this standard. Reference to these resources is made for informational use only. [B1] Anderson, P. M., Analysis of Faulted Power Systems. Ames: Iowa State University Press, 1973. [B2] “Application Guide for the Grounding of Synchronous Generator Systems,” Transactions of the American Institute of Electrical Engineers, June, pp. 517–530, 1953. [B3] “Application Guide on Methods of Neutral Grounding of Transmission Systems,” Transactions of the American Institute of Electrical Engineers, Aug, pp. 663–668, 1953. [B4] Carson, J. R., “Wave Propagation in Overhead Wires with Ground Return,” Bell System Technical Journal, vol. 5, pp. 539–544, 1926. [B5] Central Station Engineers of the Westinghouse Electric Corporation, Electrical Transmission and Distribution Reference Book, Chapter 19, “Grounding of Power System Neutrals.” [B6] Clark, E., Circuit Analysis of AC Power Systems, Vol. 1. New York: John Wiley & Sons, Inc., 1943. [B7] Clarke, E., S. B. Crary, and H. A. Peterson, “Overvoltages During Power System Faults,” Transactions of the American Institute of Electrical Engineers, vol. 58, Aug, pp. 377–385, 1939. [B8] “Guide for the Application of Ground Fault Neutralizers,” Transactions of the American Institute of Electrical Engineers, Apr, pp. 183–190, 1953. [B9] “IEEE Committee Report, “Voltage Rating Investigation for Application of Lightning Arresters on Distribution Systems,” IEEE Transactions (Power Apparatus and Systems),” PAS, vol. 91, no. 3, pp. 1067– 1074, May/June 1972. [B10] IEEE 100™ The Authoritative Dictionary of IEEE Standards Terms, Seventh Edition.9 [B11] IEEE Std 32™-1972 (Reaff), IEEE Standard Requirements, Terminology, and Test Procedure for Neutral Grounding Devices. [B12] IEEE Std C62.1™-1989 (Reaff 1994), IEEE Standard for Gapped Silicon-Carbide Surge Arresters for AC Power Circuits.10 [B13] IEEE Std C62.2™-1987 (Reaff 1994), IEEE Guide for the Application of Gapped Silicon-Carbide Surge Arresters for Alternating Current Systems. [B14] IEEE Std C62.11™-2012, IEEE Standard for Metal-Oxide Surge Arresters for Alternating Current Power Circuits (>1 kV). 9 IEEE publications are available for The Institute of Electrical and Electronics Engineers, 445 Hoes Lane Piscataway, NJ 08854, USA (http://standards.ieee.org/). 10 IEEE Std C62.1-1989 has been withdrawn; however, copies can be obtained from The Institute of Electrical and Electronics Engineers, 445 Hoes Lane, Piscataway, NJ 08854, USA (http://standards.ieee.org/). 35 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE Std C62.92.1-2016 IEEE Guide for the Application of Neutral Grounding in Electrical Utility Systems—Part I: Introduction [B15] IEEE Std C62.22™-2009, IEEE Guide for the Application of Metal-Oxide Surge Arresters for Alternating Current Systems. [B16] IEEE Std C62.82.1™-2011, IEEE Standard for Insulation Coordination—Definitions, Principles, and Rules. [B17] IEEE Tutorial Course, 79EH0144–6 PWR, Surge Protection in Power Systems. [B18] Karlicek, R. F., and Taylor, E. R., Jr., “Ferroresonance of Grounded Potential Transformers on Ungrounded Power Systems,” AIEE Transactions, vol. 78, Part IIIA, 1959, pp. 607–618. [B19] Mancao, R. T., J. J. Burke, and A. Myers, “The Effect of Distribution System Grounding on MOV Selection,” IEEE Transactions on Power Delivery, vol. 8, no. 1, pp. 139–145, January 1993. [B20] Peterson, H. A., Transients in Power Systems. New York: Dover Publications Inc., 1966, Chapter 1. [B21] Rüdenberg, Reinhold, Elektrische Schaltvorgänge und verwandte Störungserscheinungen in Starkstromanlagen. Berlin: Verlag von Julius Springer, 1933, p. 231. [B22] Wagner, C. F. and R. D. Evans, Symmetrical Components as Applied to the Analysis of Unbalanced Electrical Circuits. New York: McGraw-Hill, 1933. [B23] Willheim, R. and M. Waters, Neutral Grounding in High-Voltage Transmission. New York: Elsevier Co. (D. Van Nostrand Co.), 1956. 36 Copyright © 2017 IEEE. All rights reserved. Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply. IEEE standards.ieee.org Phone: +1 732 981 0060 © IEEE Fax: +1 732 562 1571 Authorized licensed use limited to: Universidade Tecnologica Federal do Parana. Downloaded on March 19,2019 at 01:37:43 UTC from IEEE Xplore. Restrictions apply.