This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 1 A Novel Fault Identification and Localization Scheme for Bipolar DC Microgrid G. Kesava Rao, Student Member, IEEE, and Premalata Jena, Senior Member, IEEE Abstract— Traditional fault detection and location schemes become ineffective for detecting and locating the fault in DC microgrid systems due to integrating various types of power electronic-based DC loads and generators. To resolve this issue, advanced, intelligent, specialized fault detection and location schemes are necessary. This article suggests a novel fault detection scheme based on the difference in the teager energy available in the DC current wave at sending and receiving ends of lines. After the detection of the fault, the location is calculated by estimating the resistance of the cable up to the fault point as well as the total resistance of the cable, with the help of least square technique. The proposed scheme decides fault is internal if the estimated fault location is less than 1 p.u. Otherwise, the proposed scheme decides fault is external. A DC microgrid with different types of generating units and loads is simulated using MATLAB/SIMULINK to evaluate the developed algorithm. Internal and external faults, pole-to-ground and pole-to-pole faults with changing fault resistance and fault location are some of the fault scenarios that have been simulated. The obtained simulation results prove that the suggested algorithm can discriminate between internal and external faults and locate the fault. The proposed technique is also examined on a DC microgrid hardware testbed and results show the efficiency of the suggested approach. Index Terms— Communication channel, DC microgrid, Fault location, High resistance fault, Self-protection, Teager energy. I. INTRODUCTION D ue to the evolution in power electronic technology and power converter topologies, DC microgrids are an attractive option over AC microgrids [1]. Moreover, the majority of distributed energy resources (DERs), like photovoltaic (PV), fuel cells and energy storage systems (battery) generate power in DC and hence can be easily interfaced with the DC microgrid. Also, most of the loads, electric vehicles (EVs), home appliances, and light-emitting diode (LED) lights operate on DC power [2]. DC microgrids improve the system's overall efficiency, decrease conversion stages, easy to control, more stable, maintain the power quality requirements and reduce conductor weight and size [3] [4]. So far, DC microgrids have been successfully implemented for industrial plants, ships, EV fast charging stations [5], data centers and renewable energy generators such as solar farms [6]. Despite the many benefits of DC microgrids, it remains challenging to implement effective protection schemes for these networks. In DC microgrid, unconventional fault current causes two paramount protection issues. The first one is the discharge This work was supported by the Science and Engineering Research Board, through the Department of Science and Technology, Government of India, under Projects SER-1801-EED and SER-1851-EED. of DC bus capacitor in case of a short circuit, which causes a rapid rise in the fault current and damages any electronic equipment in the fault path if the fault segment is not separated by fast DC protection system [7]. The second issue is that the DC fault current lacks zero crossings, which makes fault current interruption more difficult. It insists on utilizing a special circuit breaker (Solid State Circuit Breaker (SSCB) and distinct converter) to remove the fault [8]. After removing the fault segment, it is essential to restore the fault line to avoid a power outage for end users. The restoration of the faulty segment demands an accurate fault localization algorithm. As a result, fault identification and localization in a DC microgrid are becoming a hotspot for research. Some research articles have exclusively focused on the methods for DC microgrid fault detection [9]–[18]. In case of fault, the rate of rising of current is very high in DC microgrid. Therefore, overcurrent and current derivative protection schemes are more efficient in detecting the DC system's low impedance faults [9], [10]. However, the overcurrent relay coordination is complex because of the DC microgrid low resistance and small cable length. In [11], authors developed a fast protection method for the low voltage DC (LVDC) microgrid depending on the magnitude of current difference of the line segment. However, the magnitude of the current difference is very small when there is a high resistance fault. To minimize synchronization issues in the existing current differential protection scheme, the sign of the fault current is equated at the sending and receiving ends of the cable segment [12]. Nevertheless, the polarity of the current is not changed at the line terminal during a high resistance fault. In [13], [14], the faults in the DC microgrid are detected based on the estimated line parameter sign. In [15], authors suggested a fault identification technique based on the active resistance estimation of DC microgrid up to the fault point. However, this method could fail during a close-in fault. In [16], authors suggest a machine learning-based fault detection and classification scheme for the LVDC microgrid. However, the machine learning method accuracy depends on the dataset quality. Based on the transients monitoring function, a novel fault detection method for DC microgrid is developed in [17]. However, the suggested approach is unable to differentiate internal and external faults. In [18], a novel unit protection scheme is developed based on the adaptive Fano Factor tool based technique. However, the method has not discussed the fault classification in the DC microgrid system. Some research articles have exclusively concentrated on DC microgrid fault location methods [19]-[23]. In [19], a new fault location technique is suggested for the LVDC by connecting the external circuit at both ends of the line. Yet, the technique has Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 2 a limitation on the voltage rating of the DC microgrid. Traveling wave-based fault location algorithm is proposed in [20], [21]. This technique estimates the fault location by using traveling wave reflection laws. Even so, the traveling wave method demands a high sampling frequency transducer. A signal injection-based fault location method is developed in [22]. This method calculates the fault location by introducing a known signal into the faulted DC line. However, the technique necessitates using an external source to introduce an external signal. In [23], a parameter estimation based fault location method is proposed for the mesh type DC microgrid system. However, the fault resistance value affects the estimated fault location accuracy. As discussed above, most of the recent research articles focus on either fault detection or fault location in the DC microgrid. Only a few research articles that addressed fault detection and localization in the DC microgrid are discussed in [24]–[29]. In [24], authors identify faults in the LVDC microgrid by employing the voltage of the current limiting inductor and current flowing through the ground resistor at the relay location. The fault is localized with the help of an iterative method. However, the voltage across the current limiting inductor and current at ground resistance is lower than the threshold during high resistance fault. Depending on the polarities and wave shape of the traveling wave, a novel traveling wave protection technique for the medium-voltage DC (MVDC) microgrid is suggested in [25]. In [26], the fault is identified based on the differential current sample cumulative sum (CUSUM) index and the fault location is estimated using the Moore-Penrose pseudo inverse scheme. Nevertheless, the CUSUM index rises slowly in the case of a high impedance fault. Multi-Criterion System is used to detect a fault in the DC microgrid, and a neural network is employed to estimate the fault distance [27]. Yet, the fault detection time is very high. In [28], the fault in the LVDC microgrid system is detected by using overcurrent protection and the fault location is estimated with the help of probe power unit. Because of the high rate of rising of fault current, coordination of the overcurrent relay is challenging, and the use of probe power unit raises the cost of the protection system. In [29], the fault in the DC microgrid is detected by comparing the transient current signal with the steady state current signal. After that, fault location is estimated by similarity analysis of sampled current and estimated currents. However, the method’s fault detection and location accuracy are altered in case of high resistance faults. To address the issues with the existing fault identification and localization scheme [24]–[29], this article develops a novel unit fault detection and location algorithm for bipolar DC microgrid systems. This article identifies the fault in the DC microgrid by comparing the teager energy available in the current waves at sending and receiving ends of the line. In the case of an external fault, the difference in teager energy at the ends of line segment is close to zero. However, the teager energy difference is not zero at the time of the internal fault. To improve the ruggedness of the suggested fault detection technique, the fault location is also estimated online by using voltage and current available at the ends of the cable segment. If the calculated fault location is less than one per unit, then the fault is internal else fault is external. A radial DC microgrid system is used to validate the proposed scheme. The suggested fault detection and localization technique makes significant contributions. First, it takes less computation time to identify the fault and compute fault location as compared to other existing methods. It also detects the fault up to 50 Ω fault resistance. Second, the technique can estimate the fault location without using an external circuit. Moreover, the proposed fault location technique can estimate the cable fault location even though the cable parameters (resistance and inductance) are unknown. Third, the proposed approach is immune to the noise in the input signal. Finally, the efficiency of the suggested technique is unaffected by the intermittent and variable output of distributed generators. The rest of the paper is articulated as follows: Section II presents the system configuration. Section III contains a description of the proposed algorithm and its flowchart. Section IV presents simulation results and hardware validation, while Section V summarizes the conclusions. II. DESCRIPTION OF THE LVDC SYSTEM A seven-bus bipolar LVDC microgrid system is designed in MATLAB/SIMULINK to check the effectiveness of the suggested unit protection scheme, as illustrated in Fig. 1 [22]. The voltage of the LVDC system is 480 V. The buses present in the LVDC microgrid are associated with the loads (DC fastcharging stations and data centers) and distributed generators (solar, battery) which are connected via a voltage source converter (VSC). The ratings of the parameters of seven bus DC microgrid are provided in Table-IV. Bipolar cables (positive pole, negative pole and neutral line) are used to connect the different types of DERs and loads available at buses in the DC microgrid system. The utility grid is also connected to the LVDC microgrid at bus L via a VSC, LC filter, and transformer. The VSC at the grid and the bidirectional converter at battery are working in grid forming mode. The boost converter at solar panels is set to track the maximum power point. The DC fast chargers are coupled to the LVDC microgrid with the Islanding DC Bus-L protector AC Utility grid Bus-R DC IEDRQ EVcharging station IEDLM 0.5 Km IEDQR 1 Km F2 DC DC Bus-Q IEDQN 0.5 Km IEDML IEDNQ IEDMN 1 Km IEDNM Bus-M Bus-N IEDMO F1 IEDNP Solar Panel DC 1 Km 1 Km IEDOM IEDPN Bus-O Power line Communication line DC DC Data center DC DC EVcharging station Battery DC DC Bus-P DC Load DC DC EVcharging station Fig. 1. DC microgrid with different type of DG’s and EV charging stations. Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 3 unidirectional isolated DC-DC converters [30]. Initially, the mode of charging for the unidirectional, isolated DC-DC converters is constant current, which later shifts to the constant voltage charging mode. The voltage and current at the ends of the line segment are measured using the LV20-P-718331 voltage sensor and the LA25-P-13022 current sensor. Due to unequal load distribution at the positive and negative poles in the bipolar DC microgrid system, voltage unbalance occurs in DC microgrid system. To resolve the voltage unbalance between the positive and negative poles of the bipolar network, a voltage balancer circuit is utilized [31]. The IEDs with the SSCB are mounted at every end of the line segment to protect the line segment from different types of faults [32]. The connection circuit of the digital protection IED used in this article is shown in Fig. 2 [32]. The protection IED receives the voltage and current information through the voltage and current sensor connected at one end of the line segment. It also receives the voltage and current information from the other end of the line through sophisticated communication infrastructure. After receiving the data, IEDs analyze the data and send the corresponding command signal to the SSCB. The precision time protocol (PTP) is considered to synchronize the data in the DC microgrid [33]. A. Communication Latency The development of the smart grid concept can lead to a reduction in the cost of unit protection techniques because the smart grid's communication infrastructure can be employed in such protection schemes [34]. Therefore, this article suggested a novel unit protection technique for LVDC microgrid systems. Using the IEC TR 61850-90-5:2012 communication protocol, the data is transmitted between the two IEDs. In general, the following factors influence the communication latency between the two IEDs. They are (i) processing delay, (ii) propagation delay or queuing delay (iii) transmission delay. The processing delay is influenced by the magnitude of the data packets transmitted and the communication channel bandwidth. For the same data packets, the delay in the high bandwidth channel would be lower. Thus, for data packets of 64 bytes and a channel capacity of 1.5 Mbps, the delay is 0.3 milliseconds, and for a channel capacity of 100 Mbps, it is reduced to 5 microseconds [12]. In DC microgrid systems, the distance between two IEDs is typically small. This will cause a minor propagation delay (1–5 miles, delay ranging from 8.2 to 41 DC BUS SSCB DC line + - Trip + - Current sensor R1 I IED R2 Vn + GND Voltage sensor V Communication from other IED microseconds) [35]. Queuing and transmission delays would be negligible for enhanced communication networks, like fiber optics and high bandwidth communication channels (the latency is about 0.1 millisecond of bandwidth 100–1000 Mbps). As a result, communication latency is low enough to allow the existing unit protection techniques to operate in less than one millisecond. Therefore, the proposed unit protection technique is subjected to a communication latency of up to 1 ms in the relaying operation, as suggested in [12][18]. III. PROPOSED FAULT DETECTION AND LOCATION TECHNIQUE A. Teager Energy Representation of Continuous and Discrete Signal. The teager energy operator has been defined for both continuous (real and complex) and discrete signals. In [36], Kaiser used the following differential equation to understand the teager energy operator. d 2 dt 2 K 0 M (1) The object of the mass M is suspended to the spring constant K, as explained by the preceding second order differential equation. The total energy in the object can be calculated as follows 1 1 2 2 E K Mv 2 2 (2) where v=dχ/dt and χ=Acos(ωt+ϕ), the energy that exists in the objective can be represented as 1 E M 2 A2 (3) 2 As per the preceding equation, the energy is a function of the oscillation amplitude (A) and frequency (ω). According to [36], the amount of teager energy in the continuous signal χ(t) is expressed as (4) c ( (t )) ( '(t )) 2 (t ). ''(t ) where, ' (t ) d ( t ) dt Using equation (4), the amount of teager energy present in the continuous signal χ(t)=Acos(ωt) is given by c ( (t )) A2 2 (5) From (5), the amount of the teager energy present in the continuous signal (χ(t)=Acos(ωt)) is proportional to the square of the oscillation amplitude (A) and frequency (ω). By observing equations (3) and (5), the energy available in the suspended object has the frequency oscillation of Acos(ωt+ϕ) and the teager energy present in signal χ(t)=Acos(ωt) are similar. According to [36], the teager energy available in the discrete signal can be expressed as d [ n] [ n] [ n 1]. [ n 1] 2 (6) where n is the sample number. For calculating the teager energy, three consecutive samples are required. The magnitude of teager energy present in the discrete signal χ[n]=Acos[Ωn+φ] is calculated using the equation (6) and written as Fig. 2. IED connection circuit in DC microgrid. Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 4 d A cos[n ] A 2 2 (7) The relation between the continuous teager energy ψc and discrete teager energy ψd can be calculated using the backward finite approximation. The sampling of the continuous signals generates the discrete signals with the sampling frequency of fs. The discreet signal can represent as (8) [n] (nt ) 1 fs Therefore, by replacing y[n] [n] [n 1] / t where, t '(t ) and and "(t ) in (4) with y[n] y[n 1] / t 2 v (0) 2 (i f (t )) c e( z1 z2 )t iL (0) * z1 z2e( z1 z2 )t L cf v (0) ( z z )t c * iL (0) * e 1 2 z2 z1 Lcf Now, the z1 and z2 parameters present in (15) are expressed in terms of the line parameters up to the fault point. Further, the teager energy can be written as 2 v (0) ( R / L )t 2 1 ( R / L )t ψ(i f (t )) c e cf cf iL (0) * e cf cf Lcf Ccf Lcf respectively, (4) can be written as c ( (t )) 1 (Δt) 2 [n 1] 2 [ n 2]. [ n] (15) (16) v (0) Rcf ( R / L )t c * iL (0) * * e cf cf Lcf Lcf (9) (10) On observing the above equation (10), if we ignore the onesample shift and the scaling by T-2 s then we can transform ψc(χ(t)) into ψd(χ[n]). For the simple representation of the teager energy in the subsequent section, the subscripts c and d from ψ are ignored. In the case of a transient, the DC signal oscillates with the damped resonant frequency (ωd). As a result, the teager energy available in the DC current wave is not equal to zero. From (16), it has been observed that the size of the teager energy (ψ(if(t)) is dependent on the prefault voltage of the DC capacitor, prefault current through inductance, and the fault current path parameters. B. Calculation of Teager Energy in DC Signal During Steady State and Transient (fault) Scenarios. In a DC microgrid system, the steady-state current can be represented as (11) i(t ) A * u(t ) where A is the magnitude of the signal. With the help of equations (4) and (11), during the steady-state, the teager energy available in the DC current wave i(t) can be written as (i(t )) 0 i(t ) 0 0 t 0 (12) In the steady state condition, frequency (ω) of DC current wave is zero. As a result, the teager energy available in the DC current waveform is also zero. When a fault occurs in a DC microgrid, the fault current [9] expression in the frequency domain is written as vc (0) iL (0) Lcf i f (s) (13) Rcf 1 2 s s Lcf Lcf Ccf C. Faulty Line Identification and Fault Location Estimation in LVDC Microgrid 1) Faulty Line Identification in DC Microgrid In this article, the difference in teager energy available in current waves at both ends of the line segment has been used to distinguish the internal and external faults in the DC microgrid. The teager energy difference is calculated as [ n ] 1 [ n ] 2 [ n ] (17) c ( (t )) d ( [n 1]) / (Δt)2 where, vc(0) and iL(0) are the prefault voltage and current across the capacitor and inductor, respectively. Rcf, Lcf, and Ccf signifies the resistance, inductance, and capacitance present in the fault current path. Expression for the fault current [9] in the time domain is expressed as vc (0) i (0) i f (t ) [e z1t e z2t ] L [ z1e z1t z2 e z2t ] (14) Lcf ( z2 z1 ) ( z2 z1 ) Here, z1 =α+ω d , z2 =α-ω d and α denotes the damping factor and is equal to α=Rcf/2Lcf. ωd is the damped resonant frequency and is equivalent to 𝜔𝑑 = √𝛼 2 − 𝜔02 . ω0 is the natural frequency and is equal to ω0 =1/√Lcf Ccf . Hence, during the transient, the teager energy available in the current wave (if(t)) given in (14) is determined using (4) and expressed as where ψ1 and ψ2 are the teager energies of the current waves flowing through both ends of the line segment. They can be estimated using (6) as follows 1[n] ( I1[n])2 { I1[n 1]* I1[n 1]} (18) 2[n] ( I2[n]) { I2[n 1]* I2[n 1]} (19) 2 where I1 and I2 denote the line segments sending and receiving currents, respectively. In the case of an internal fault (F1), the equivalent DC microgrid circuit is depicted in Fig. 3 [16]. Hence, expressions of I1 and I2 [18] of the line segment can be written as vc1 (0) i (0) I1 (t ) [e z1t e z2t ] L1 [ z1e z1t z2 e z2t ] (20) Leq1 ( z2 z1 ) ( z2 z1 ) I 2 (t ) vc 2 (0) i (0) [e z3t e z4t ] L 2 [ z3 e z3t z4 e z4t ] (21) Leq 2 ( z4 z3 ) ( z 4 z3 ) where, z1 =α1 +ω d1 , z2 =α1 -ω d1 here ωd1 =√α21 -ω201 , ω01 = ω d2 here α2 = Req2 Leq2 1 √Leq1 C α1 = Req1 Leq1 ; ; z3 =α2 +ω d2 , z4 =α2 eq1 ; ωd2 =√α22 -ω202 , ω02 = 1 √Leq2 C eq2 The resulting teager energy present in the sending end current signal I1 and receiving end current signal I2 can be derived as Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 5 Leq1/2 Req1/2 Req2/2 Leq2/2 I2 2Ceq2 2Ceq1 I1 VSC-1 vc1(0) vc2(0) Rf Req1/2 Leq2/2 2 ( Req 1 / Leq 1 )t (22) v (0) Req1 ( R / L )t c1 * iL1 (0) * * e eq1 eq1 L L eq1 eq1 2 v (0) ( R / L )t 2 1 2 ( I2(t )) c2 e eq 2 eq 2 iL2(0) * Leq2Ceq2 Leq2 e ( Req 2 / Leq 2 )t VNpp (23) v (0) Req2 ( R / L )t c2 * iL2 (0) * * e eq 2 eq2 L L eq2 eq2 By observing (22) and (23) in case of an internal fault, the teager energy at sending end and receiving end of the line segment is different. Therefore, the difference in teager energy (γ) is greater than the threshold (ξ). However, in the case of external fault, magnitude of current at the sending end and receiving is same I1=I2. Due to this, the teager energy in both current signals I1 and I2 is the same ψ1=ψ2. Therefore, teager energy difference (γ) is less than the ξ. In the bipolar DC microgrid system, the difference of the teager energy present in the positive pole is given as p [n] 1 p [n] 2 p [n] (24) Similarly, the difference of the teager energy present in the negative pole is given as n [ n ] 1 n [ n ] 2n [ n ] (25) 2) Type of Fault Identification In the DC microgrid cables or lines, during the pole to ground fault, the teager energy difference (γ) of the faulted pole is greater than the threshold (ξ). On the other hand, the teager energy difference at the non faulted pole is less than the threshold. By using this concept, the faulted pole in the DC microgrid is identified during the pole to ground fault. In the case of a pole to pole fault, teager energy difference at the positive pole (γp) and negative pole (γn) are greater than the threshold (ξ). As a result, DC microgrid pole to pole and pole to ground faults are easily differentiated using above discussed concept. 3) Fault Location Estimation in LVDC Microgrid: In the suggested fault location scheme, the fault distance is calculated using data at both ends of the line. The distance up to the fault point is calculated by estimating the line resistance up to the fault point and the overall line resistance. As a result, even when the cable parameters are unknown, the suggested method can estimate the fault location. A two-bus equivalent system is considered to understand the proposed fault location algorithm in the case of line to ground fault, as illustrated in Fig. 4. It has two voltage sources, VMpg (bus M pole to ground L R - Req2/2 v (0) ( R / L )t 2 1 1 ( I1 (t )) c1 e eq1 eq1 iL1 (0) * Leq1Ceq1 Leq1 + I2 VNpg RF VMpp Fig. 3. Equivalent DC microgrid circuit during internal fault in line LM. e (1-m)R (1-m)L mL VMpg I1 VSC-2 2Ceq2 2Ceq1 Leq1/2 mR + - Fig. 4. Two bus system during pole to ground fault. voltage) and VNpg (bus N pole to ground voltage). Both voltage sources supply the fault current of I1 and I2, respectively. The voltage at bus M is written in terms of the currents at both ends of the cable MN and written as dI dI VMpg mRI1 mL 1 (1 m)RI2 (1 m)L 2 VNpg (26) dt dt where, m is the fault distance from the bus M, R and L are the DC line segment resistance and inductance. The voltage drop in the line MN can be written as dI dI dI VMpg - VNpg mR I1 I2 mL 1 2 RI2 L 2 (27) dt dt dt During pole-to-pole fault, the corresponding two-bus system model is depicted in Fig. 5. In the occurrence of a pole-to-pole fault, the voltage drop across the line segment (MN) can be expressed as dI dI VMpp - VNpp 2mR( I1 I2 ) 2mL 1 2 2RI2 dt dt dI2 2L dt (28) The line voltages in equation (28) are expressed in terms of the line-to-ground voltage and written as dI dI dI (VMpg - VNpg ) mR( I1 I2 ) mL 1 2 RI2 L 2 (29) dt dt dt By using (27) and (29), the generalized equation for both fault cases is expressed as dI dI dI (VMpg - VNpg ) mR( I1 I2 ) mL 1 2 RI2 L 2 (30) dt dt dt The parameter presented in equation (30) is obtained using Least Square (LS) technique [37] and written as [mR mL R L]T H T H where, H I1 (ti ) I2(ti ) mR -1 H T V1 (ti )- V2(ti ) dI1(ti ) dI 2 (ti ) + I 2 ( ti ) dt dt N×1 (31) dI2 (ti ) dt N 5 (1-m)R (1-m)L mL + + VNpg I2 VMpg I1 RF VMpp mR mL VNpp (1-m)R (1-m)L - I1 I2 Fig. 5. Two bus system during pole to pole fault. Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 6 where the value of N is considered to be 20. mR represents cable resistance up to the fault point. The fault distance m is calculated as m mR R (32) where ℓ denotes the line segment overall length. The estimated percentage error of fault location is expressed as m mact 100 % Error = cal (33) mact When teager energy difference exceeds the threshold (ξ) and the computed fault distance (m) lies in the range 0< m<1, then the proposed scheme detects that the fault is internal and sends a trip signal to the SSCB. Fig. 6 depicts the proposed algorithm flow chart. Initially, IEDs at the ends of line segments receive voltage and current measurements from both ends of the line through measurement sensors and communication links. After that, the IEDs estimate the teager energy available in the current wave using equations (18) and (19). Further, the teager energy difference present in each line segment of positive and negative poles is calculated with the help of equations (24) and (25). When the difference of the teager energy at any pole (γp and γn) is more than the threshold, the proposed technique detects the fault and initiates the fault classification and fault location techniques. If the estimated teager energy difference at both the poles is more than the threshold and the suggested algorithm decides the fault is pole to pole fault. Or else it decides the fault is pole to ground Fault detection Start Measure the value of V1pg, I1p, V2pg, I2p,V1ng, I1n, V2ng and I2n of the line MN Calculate the difference of the teager present in the current signals γp >ξ (or) γn >ξ No Faultclassification classification Fault Yes γp >ξ (and) γn >ξ Yes No Pole to ground fault Pole to pole fault Fault localization Yes Estimate the parameter of mR and R using the equation (30) fault. After fault classification, the suggested method initiates the fault location algorithm. In the fault location technique, the IEDs estimate the line resistance (R) and resistance of the line up to the fault point (mR) using equation (30). Further, the fault distance (m) is estimated using (32). If the estimated fault distance lies in the range of 0<m<1, then the proposed method decides fault is internal or else the fault is external. After detecting the internal fault, the IEDs generate the trip signal to SSCB to isolate the fault section. D. Threshold (ξ) Selection The threshold (ξ) is dependent on the teager energy difference. From equation (17), the teager energy difference in the current signal during internal faults depends on teager energy available at sending and receiving end of the line segment. However, the teager energy in the current signal depends on the iL(0), fault distance and fault resistance. Therefore, to decide the threshold (ξ), a high resistance fault F1 is created with a fault resistance of 50 Ω by varying fault distances and percentage of loading on DC microgrid. During high resistance faults, the teager energy in the current signal is low. Therefore, a high resistance fault is considered to decide the threshold. For all scenarios, the obtained teager energy difference is shown in Fig. 7. By examining Fig. 7, the minimum teager energy difference of 1298 is obtained during a high resistance fault at fault location 0.9 p.u and 50 % loading. Therefore, for detecting an internal fault in the DC microgrid, the threshold magnitude must be less than 1298. In an ideal scenario, the teager energy difference equals zero for external faults and is greater than the threshold during internal faults. However, in the practical scenarios, teager energy difference is not equal to zero in case of external fault and load changes. Generally, in the differential protection scheme, the threshold selection depends on the [38] (i) Measuring error and noise in the signal, (ii) Cable charging current, (iii) Communication delay, (iv) CT saturation. Therefore, to decide the threshold, these factors are also considered. According to the IEC 61869-2 and IEC 61869-3 standards, the measurement error for the voltage and current sensors should be less than 3% [39]. Therefore 3% measurement error in the current signal is considered while deciding the threshold. Also, 35 dB signal-to-noise ratio (SNR) in the current signal and cable charging current during double pole to ground fault is also considered to decide the threshold. Among these, communication delay and CT saturation effects are taken into account for deciding the threshold. Thus, considering the above-mentioned factors, the reliable threshold (ξ=1000) value for the proposed protection technique is decided. In any case, the suggested method initiates the fault Estimate the fault location (m) using mR, and R External fault No 0<m<1 Yes Generate trip signal Fig. 6. Flow chart of suggested fault detection and fault location scheme. Fig. 7. Teager energy difference during high resistance fault. Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 7 × 104 200 150 100 1 0.5 0 VMpg γ 100 0 2 VNpg (a) I1 I2 3.5 Time(s) 3.55 (c) 1 γp γn 20 10 R(mΩ ) 0 × 104 ψ1 4 2 ψ2 0 -2 3.45 (d) 20 10 0 (b) R mR (e) 0.5 d(pu ) ψ ξ 0 0 3.55 3.5 3.45 3.55 3.5 (f) Time(s) Time(s) (c) Fig. 9. Pole to Pole fault. (a) Voltages of line MN. (b) Currents of line MN. (c) Teager energy. (d) Difference of teager energy. (e) Estimated resistance. (f) Fault distance. B. During Pole to Pole Fault In this section, the performance of suggested technique is verified in the case of pole to pole fault. A pole to pole fault is established at the midpoint in the line segment MN with a fault resistance of 0.1 Ω. The simulation results obtained by the suggested technique at the IEDMN and IEDNM are provided in Fig. 9. Fig. 9(c) demonstrates the teager energy available in current wave at the IEDMN is (ψ1) and IEDNM is (ψ2). The magnitude of the teager energy during the pole to pole fault is very high compared to the pole to ground fault. Fig. 9(d) demonstrates the difference in the teager energy of the positive pole and negative pole. By observing Fig. 9(d), it is clear that the difference in the teager energy of the positive and negative poles is more than the threshold. As a result, the suggested technique decides that the fault is line to line. Fig. 9(e) shows the estimated line resistance (R) and resistance of the line up to the fault point (mR). Fig. 9(f) shows that the estimated fault distance during line to line fault is less than 1 p.u. Subsequently, the proposed method classifies the fault as internal and the trip signal is sent to the respective SSCB by the IEDs present at the ends of the line MN. The proposed method dependability is also evaluated during the line to ground (positive pole to ground fault) and line to line faults (F1) by varying the line LM length. The results obtained by the proposed algorithm are provided in Table-I. According to Table-I, during the positive pole to ground fault, the estimated teager energy difference at the positive pole (γP) exceeds the threshold and the fault location (m) is less than 1 p.u for all scenarios. Similarly, during the line to line fault the estimated teager energy difference at the positive pole (γP) and negative pole (γn) are greater than the threshold and the estimated fault location (m) is less than 1 p.u TABLE-I TESTING OF PROPOSED METHOD BY VARYING LINE LENGTH Varying line LM length (km) (d) R mR Parameter 3.5 Time(s) 3.55 (f) Fig. 8. Line to ground fault. (a) Voltages of line MN (b) Currents of line MN. (c) Teager energy. (d) Difference of teager energy. (e) Estimated resistance. (f) Fault distance. LG fault LL-Fault 2 (km) 5 (km) 10(km) 2 (km) 5 (km) 10(km) γP 13817 12942 11715 52706 46544 40739 γn 110.98 63.99 390 52706 46544 40739 R (Ω) 0.0403 0.1006 0.2010 0.0403 0.1005 0.2013 mR (Ω) 0.0204 0.0506 0.0988 0.0199 0.05 0.1005 %Error 1.240 0.59 -1.691 -0.765 -0.497 -0.149 m (p.u) 0.5062 0.5029 0.4915 0.4962 0.4975 0.4992 (e) 0.5 0 3.45 I1 I2 γp γn ξ 0 (b) ψ × 103 5 0 ψ1 -5 ψ2 -10 3.45 4 ×10 0 R(mΩ ) 200 d(pu ) Current(kA) Voltage(V) A. During Pole to Ground Fault To check the selectivity of the suggested protection technique during pole to ground fault, a positive pole to ground fault (F1) is initiated at the midpoint of the line MN with the fault resistance of 0.1 Ω as depicted in Fig. 1. The line to ground voltage and line current variation at the IEDMN and IEDNM are illustrated in Fig. 8. The teager energy of ψ1 and ψ2 present in the current waves at IEDMNp and IEDNMp is provided in Fig. 8(c). By observing Fig. 8(c), the teager available in the current wave during the steady state is zero. During the fault, its magnitude is not equal to zero. The difference in teager energy (γ) available in the current waves of the positive and negative poles of the line MN is illustrated in Fig. 8(d). The difference in the teager energy present in the current wave of the positive pole (γp) is more than the threshold (ξ), as depicted in Fig. 8(d). Therefore, the suggested technique initiated the fault location algorithm at the positive pole IEDs of line MN. After that, by using equation (30), the total line resistance (R) and resistance of the line up to the fault point (mR) are estimated as depicted in Fig. 8(e). The calculated fault distance is less than 1 p.u, as depicted in Fig. 8(f). As a result, the suggested method determines that the fault is internal and sends a trip command to the line segment MN's SSCB. VNpg (a) 2 1 IV. SIMULATION AND EXPERIMENTAL RESULTS A radial LVDC microgrid system is considered to assess the effectiveness of the suggested fault detection and fault localization algorithm, as illustrated in Fig. 1. The LVDC microgrid system is modeled in MATLAB SIMULINK with a 250 µs step size. The suggested fault detection and fault location technique is tested in various fault scenarios, including pole to ground faults, pole to pole faults, noise environments, load switching, high resistance faults, and internal faults by varying fault resistances and fault distances. 5 VMpg γ Current(kA) Voltage(V) location algorithm during the external fault due to the difference of the teager energy being more than the threshold (ξ). In that case, the estimated fault location is more than 1 p.u. Then the suggested fault detection algorithm decides that the fault is external. Therefore, the low value of threshold ξ=1000 is considered to trigger the fault location algorithm for all types of internal faults up to the fault resistance of 50 Ω. Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 500 3.55 (c) 3.5 Time(s) 0 3.45 3.55 (f) 3.5 Time(s) Fig. 10. During external fault. (a) Voltages of line MN, (b) Currents of line MN. (c) Teager energy. (d) Difference of teager energy. (e) Estimated resistance. (f) Fault distance. for all scenarios. As a result, the proposed method does not compromise dependability in line to ground and line to line faults by varying line length. C. During Pole to Ground External Fault To check the security of the suggested fault detection and location algorithm in case of external fault. An external fault (F2) is initiated in the line LM with a fault impedance of 0.1 Ω and fault location of 0.5 p.u from bus L. The corresponding voltage and current at the IEDMN and IEDNM are depicted in Fig. 10(a) and Fig. 10(b). The teager energy available in the current waves at IEDMN and IEDNM is illustrated in Fig. 10(c). It is noticed from Fig. 10(c) that the teager energy available in the current wave at both IEDs is very high during external fault. But the teager energy difference is much lower than the threshold, as depicted in Fig. 10(d). As a result, the suggested method identifies the fault as external. The fault distance is also estimated to check the fault location technique's robustness in this external fault case, as depicted in Fig. 10(f). The estimated fault distance is more than the 1 p.u. As a result, the suggested algorithm retains its security in the case of an external fault. 1 0.5 0 VNpg × 104 5 0 ψ1 -5 ψ2 -10 3.5 3.45 Time(s) 0 (b) 3.55 (c) γp γn ξ (d) 20 10 VMpg 230 1 R mR (a) I2 I1 0 -1 × 103 0 -2 -4 3.45 3.55 (f) Fig. 11. During internal fault in case of noise environment. (a) Voltages of line MN. (b) Currents of line MN. (c) Teager energy. (d) Difference of teager energy. (e) Estimated resistance. (f) Fault distance. R mR (e) 500 ψ1 ψ2 3.5 Time(s) 0 3.45 3.55 (c) 3.5 Time(s) 3.55 (f) Fig. 12. During EV charger switching. (a) Voltages of line MN. (b) Currents of line MN. (c) Teager energy. (d) Difference of teager energy. (e) Estimated resistance. (f) Fault distance. 5 80 200 γn γp 0 10 (a) I1 I2 0 (b) (e) 3.5 Time(s) γp γn (d) 0 -5 -10 -15 (b) -200 0.5 0 3.45 0.5 0 VNpg 140 0 (a) I1 I2 1 × 103 1 250 Ipv(A) γ VMpg F. During Variable Generation in DC Microgrid In order to evaluate the effectiveness of the suggested algorithm in the scenario of variable generation, the irradiation 50 0 -50 ψ1 -100 3.45 ψ ψ 100 0 4 2 × 10 R(mΩ ) 200 d(pu ) Current(kA) Voltage(V) D. In Noise Environment This section evaluates the performance of the suggested protection technique in a noise environment. With a fault location of 0.5 p.u from bus M, a pole to ground fault is initiated in cable MN. After that, a White Gaussian noise is introduced into the voltage and current waves present at the IED MN and IEDNM with signal-to-noise ratio (SNR) of 35 dB, as depicted in Fig. 11. With the help of the suggested technique, the teager E. During EV Charge Switching An EV charger is switched in the DC microgrid bus N to test the suggested algorithm security. The EV's initial state of charge is considered to be 20%. The corresponding voltage and current at the IEDMN and IEDNM are depicted in Fig. 12(a) and Fig. 12(b). The initial current drawn by the EV charger is high, as shown in Fig. 12(b), so overcurrent-based protection schemes are becoming less reliable in detecting the fault in LVDC microgrid systems. However, the proposed method maintains its dependability during the EV charger switching. The difference of the teager is less than the threshold, as depicted in Fig. 12(d). Moreover, the estimated fault distance is more than the 1 p.u, as depicted in Fig. 12(f). Hence, the proposed technique maintains its security when EV charge switching occurs in a LVDC microgrid. γ (e) R(Ω ) (b) d(pu ) ψ × 103 4 ψ1 2 ψ2 0 3.45 R mR d(pu ) -0.2 γ 0 (d) 10 0 -10 -20 I1 I2 R(Ω ) 0.2 ξ ψ2 3.5 Time(s) 5 (d) R mR 0 (e) 500 d(pu ) (a) γp γn Current(kA) Voltage(V) VNpg energy difference in positive pole (γp) and negative pole (γn) are estimated as depicted in Fig. 11(d). By observing Fig. 11(d), the values of γp and γn are before the fault is not equal to zero due to noise in the current signals. However, the values of γp and γn are less than the threshold during the steady state and the value of the γp is greater than the threshold during the fault scenario. Moreover, the estimated fault distance (m) during the fault is less than the 1 pu, as shown in Fig. 11(f). By observing Fig. 11, it is clear that the proposed algorithm does not lose its security due to the measured signal consisting of the noise. ψ γ VMpg 100 0 × 103 Current(A) 200 1.5 1 0.5 0 R(Ω ) Current(kA) Voltage(V) 8 3.55 (c) 0 3.45 3.5 Time(s) 3.55 (f) Fig. 13. During variable generation at bus O. (a) PV output current (b) Currents of line OM. (c) Teager energy. (d) Difference of teager energy. (e) Estimated resistance. (f) Fault distance. Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 9 of the PV panel connected to bus O is increased by 20% at 3.5 seconds. Due to the increase in irradiation, the current supplied by the PV panel is increased at 3.5 sec, as shown in Fig. 13(a). The current measured at both ends of the line segment OM is shown in Fig. 13(b). With the help of the proposed algorithm, the teager energies (ψ1 and ψ2) present in the current signals are estimated at both ends of line segment OM as shown in Fig. 13(c). After that teager energy differences, γ p and γn are calculated as shown in Fig. 13(d). By observing Fig. 13(d), the teager energy difference is small and less than the threshold (ξ=1000). Also, the estimated fault location is greater than 1 p.u, as shown in Fig. 13(f). Therefore, the proposed method does not lose security in the case of variable generation in the DC microgrid. G. Accuracy in Fault Location To check the accuracy of the suggested fault location technique, a pole to ground fault F1 is initiated in the line segment MN for various values of fault distance (m) and fault resistance (Rf). The fault distance is estimated at the IEDMN and IEDNM using the proposed fault location technique for all the above cases. The corresponding estimated error present in fault location is also calculated and provided in Table-II. Table-II shows that the maximum error obtained by the suggested fault distance estimation technique is 3.59 percent. DC DC AC O P IEDPO IEDPQ IEDOP N Q IEDOP IEDQP DC load IEDQL IEDNM F3 IEDMN IEDML IEDLM IEDLQ L M DC DC DC 0 1 0 -1 -2 1 0.5 0 10 5 0 DC (b) 1 γ DC load VMpg VNpg 200 100 0 R(mΩ ) IEDNO d(pu ) DC Bidirectional Islanding converter protector ψ Utility grid DC load Current(kA)Voltage(V) H. Change in Topology and Cable Parameters The proposed scheme is validated for the different DC microgrid topologies by considering a meshed bipolar DC microgrid, as shown in Fig. 14(a). The ratings of the sources and loads presented in the meshed DC microgrid are same as the rating of the sources and loads in the radial DC microgrid, as shown in Fig.1. The cables in the meshed DC microgrid have a resistance of 0.12 Ω/km, an inductance of 300 μH/km, and a capacitance of 0.5 μF/km, respectively. To test the suggested method for the meshed DC microgrid a line to ground fault (f3) is initiated in the line MN has a fault resistance of 0.1 Ω as I1 I2 × 103 × 104 0.5 0 3.45 Solar Panel (a) Battery (c) ψ1 ψ2 (d) γp γn (e) R mR (f) 3.5 Time(s) (g) 3.55 Fig. 14. During a line-to-ground fault in the meshed DC microgrid. (a) Meshed DC microgrid (b) Voltages of line MN. (c) Currents of line MN. (d) Teager energy. (e) Difference of teager energy. (f) Estimated resistance. (g) Fault distance. Rf m 0.1 p.u 0.2 p.u 0.3 p.u 0.4 p.u 0.5 p.u 0.6 p.u 0.7 p.u 0.8 p.u 0.9 p.u TABLE-II FAULT LOCATION ESTIMATION ERROR 0.01 Ω 1Ω 5Ω 10 Ω 15 Ω 0.0845 0.0136 0.0125 0.0997 0.3488 0.7451 1.2792 1.9415 2.7203 0.2575 0.3067 0.0303 0.6868 1.6788 0.3994 1.3357 2.9167 3.5993 0.0481 0.2193 0.2997 0.2815 0.0357 1.2377 1.0254 1.8405 2.8441 0.15 0.1382 0.3406 0.7846 1.0478 1.3783 1.3699 1.4421 1.4535 0.4523 0.0266 0.4972 0.7994 1.1219 1.3783 1.5807 1.7286 1.8275 20 Ω 0.6565 0.0266 0.3792 0.7872 1.1458 1.4321 1.6542 1.8156 1.9183 shown in Fig. 14(a). The line to ground voltage and line current variation at the IEDMN and IEDNM are illustrated in Fig. 14. The difference in the teager energy present in the current wave of the positive pole (γp), is more than the threshold (ξ), as depicted in Fig. 14(e). Therefore, the suggested technique initiated the fault location algorithm at the positive pole IEDs of line MN. After that, by using equation (30), the total line resistance (R) and resistance of the line up to the fault point (mR) are estimated as depicted in Fig. 14(f). The calculated fault distance is less than 1 p.u, as depicted in Fig. 14(g). As a result, the suggested method efficiently detects and locates the fault in the meshed DC microgrid system by varying the cable parameters. I. Comparison Study with Existing Protection Scheme The proposed technique is compared to some sophisticated fault identification and location schemes developed in the DC microgrid. Table-III compares and evaluates the proposed approach with other previous techniques [7] [24], [26], [27], [28] in detail. According to Table-III, the proposed approach takes less time to identify faults than the technique presented in [27], [26]. The proposed approach can identify and locate high resistance faults with a fault resistance of 50 Ω, where existing protection schemes [7] [24], [26], [28] fail to work. The TABLE-III COMPARATIVE ANALYSIS OF THE PROPOSED TECHNIQUE WITH PREVIOUS PROTECTION METHODS Parameters The time it takes for a fault to be detected (ms) The maximum R f is taken into account. Mal operation in the case of temporary fault Fault classification Maximum estimated percentage error in fault distance (%) Fault location accuracy considering SNR of 20 dB (%) For fault detection and location, an external circuit is required. DC microgrid incorporated with the EV charging station Cable information is necessary for fault location calculations. Real-time validation PS 2 [24] 1.25 Various methods [26] [28] 100 1 [27] 19 [7] 1.25 50 Ω 25 Ω 2Ω 2Ω 100 Ω 10Ω No No No Yes Yes No Yes 3.59 Yes 7.1 No 6.42 No 9.75 No 1.6 No 8.7 95.8 94.1 92.6 91.3 1 75.3 No No No Yes No No Yes Yes No No No No No Yes Yes Yes Yes Yes Yes No Yes Yes Yes No PS denotes the proposed algorithm Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 10 (d) γ (a) I1(A) 2 1 0 ×103 (b) (c) I1+I2(A) I2(A) (f) (e) d(pu ) R(mΩ ) 20 10 0 ξ γp γn R mR Fuel cell Boost converter Boost converter Load Bus C Buck converter Load A VC V A IC F2 3 Phase Rectifier Bidbuck I1-6 PVboostGbuck Fboost Mbuck 24 v DC from SMPS Capacitor Bank (20uf, 230V) Half Bridge DO F1 FPGA Board 15V-0 SEIG Simultaneous A/in VB V Va Vb Vc Ia Ib Ic N Vpv IpvVB IB Vcp Speed senscor A IB A DC Motor Bus B R-C Filter & Transformer R B Y N Aux In +15/0/-15 Inverter Load Bidirectional converter ARM 2200uf 190 185 180 175 -173 -174 -175 10 5 0 3.45 Hydrogen gass PV Emulator 1 Phase Rectifier J. Experimental Validation. HIL experimentation is also carried out to validate the result obtained through the MATLAB simulation and test the feasibility of the suggested algorithm in a practical environment. The HIL setup consists of four distributed energy resources solar emulators of the 2 kW, a stack of 8 lead-acid batteries, each with 12 V, 60 Ah, a fuel cell of 1 kW, and a wind emulator of 2 kW. All the distributed generators are interfaced to DC microgrid through the DC to DC converter, as depicted in Fig. 16. The DC microgrid setup is also connected with the utility grid with the help of VSC. The VSC at utility grid maintains DC microgrid voltage of 110 V. VSC plays an important role in synchronizing DC microgrid with the P N Control signal field proposed method produced a maximum of 3.59 percent error in fault location estimation, which is less than existing techniques. The proposed algorithm does not require an external circuit to identify the fault and estimate its location. On the other hand, the methods in [24] require an external circuit for fault identification and location estimation. The proposed algorithm does not require cable information to determine the location of the fault. However, the methods in [7], [24], [26]–[28] need cable information to estimate fault location. Most of the existing fault detection and location methods ignore the effect of EV charging stations in the DC microgrid system when detecting and locating faults. A simulation case study is also conducted to compare the suggested fault detection method with existing differential protection schemes [11],[12]. In this case, a high impedance fault of 50 Ω is initiated at the midpoint of line segment MN. The fault current at the IEDMN and IEDNM are delineated in Fig. 15(a) and Fig. 15(b). The current direction at both IEDs is not changed, as illustrated in Fig. 15(a) and Fig. 15(b), so the differential protection technique depends on the sign of current [12] field to operate in case of a fault with high resistance. The current differential (I1+I2) is also estimated, and its magnitude is very small, as delineated in Fig. 15(c). Therefore the protection technique depends on the magnitude of the current difference [11] and may fail during the high resistance fault. In this case, with the help of the suggested algorithm, the teager energy difference and fault location are calculated as depicted in Fig. 15(d) and Fig. 15(f). From the figures, the calculated teager energy difference is greater than the threshold. Moreover, the calculated fault location is less than 1 p.u, as depicted in Fig. 15(f). According to the case studies discussed above, the suggested protection scheme outperforms all existing protection schemes. P N 1Pole Switch 10A fuse Gate signal 15V-0 10A DC MCB from FPGA Motor Buck converter 2200uf 3 Phase Rectifier Battery Bank 3 Phase Auto trans 4 pole MCB Grid B Y R Grid Fig. 16. Schematic diagram of the DC microgrid hardware setup. conventional grid. HIL experimentation setup can operate gridconnected mode and islanding mode operation. In the gridconnected mode, VSC at the utility grid operates in the grid forming mode remaining all converters operating in grid feeding mode. During islanding condition, bidirectional converter at the battery operations in the grid forming mode remaining converters at DGs operates in grid feeding mode. All the converter control circuits are used in the experimental setup that can be implemented in the LABVIEW platform and interfaced through Field Programmable Gate Array (FPGA). A DC line attached between DC microgrid and the battery bank has a line resistance of 2 Ω and inductance of 0.5 H, as depicted in Fig. 16. The voltage and current of the LVDC microgrid are measured using the LV20-P-718331 voltage sensor and the LA25-P-13022 current sensor. The measured voltage and current waves are sent to the d-SPACE 1104 controller to process further the suggested fault detection and location algorithm depicted in Fig. 17. To test the proposed algorithm in HIL environment, internal fault (line to line and line to ground fault) at F1 location and external fault (line to ground fault) at F2 location are created with a fault resistance of 15 Ω as illustrated in Fig. 16. In all 0.5 3.5 Time(s) 3.55 0 3.45 3.55 3.5 Time(s) Fig. 15. During high resistance fault. (a) Sending end current at line MN. (b) Receiving end current at line MN. (c) Differential current (d) Difference of teager energy. (e) Estimated resistance. (f) Fault distance. Fig. 17. The DERs have been used in the experiment. Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 11 IB 2 A/div 2 A/div 2 A/div 2 A/div 5unit/div γp 0.1 Ω /div mR 2 A/div IC 2 A/div IB IC IC IB γp mR (a) 5unit/div γp 5 unit/div 0.1 Ω /div mR 0.1 Ω /div (c) (b) Fig. 18. The HIL results during fault. (a) Internal line to line fault. (b) Internal line to ground fault (c) External line to ground fault. fault scenarios the current at both ends of the line segments increases rapidly due to the discharge filter capacitor in the converters shown in Fig. 18. By observing the Fig. 18, during internal faults the currents at the line segment increased in same direction. However, in the case of external fault, the currents are increased in opposite directions. In all fault scenarios, the teager energy present in the current waveform at the sending and receiving ends of the line segment is estimated, and the teager difference is calculated using the d-SPACE controller. During internal pole to pole and pole to ground fault, the teager energy difference in the positive pole is greater than the threshold, as shown in Fig. 18(a) and Fig. 18(b). Therefore, proposed initiate the fault location algorithm in the case of an internal pole to pole and pole to ground fault. However, the teager energy difference is less than the threshold during an external fault, as shown in Fig. 18(c). As a result, proposed method decides fault is external and does not initiate fault location algorithm. To compute the fault location during internal faults, the d-SPACE evaluates the line resistance up to the fault point, as depicted in Fig. 18(a) and Fig. 18(b). The estimated fault location during the internal pole to pole and pole to ground faults are 0.4832 p.u and 0.4875 p.u, respectively. As a result, the proposed scheme identifies the faults are internal and d-SPACE generates the trip signal. Observing the HIL and simulation results during an internal fault, the suggested technique computes the teager energy and fault location in less than 1 ms. As a result, the proposed algorithm's overall fault clearing time is 2 ms is considered. Total fault clearing time includes the relay computation time, the operating time for the SSCB of 50 μs [8] and a 1 ms communication delay. V. CONCLUSION This research work focuses on fault detection and localization in LVDC microgrid. Using the IEC 61850 communication protocol, the fault in the DC microgrid is detected by comparing the teager energy available in the current wave at both ends of the line segment. The teager energy available in a DC waveform is zero during a steady state. In the case of a transient, its magnitude is not zero. After the fault has been detected, the fault location is computed by estimating the line resistance up to the fault point and the actual line resistance by using the least square technique. The proposed approach can assess the fault location even though cable parameters are unknown. In 2 ms, the proposed algorithm can detect and locate faults has a fault resistance of up to 50 Ω. The suggested method is robust to the noise environment and loads switching conditions. The comparison studies prove that the suggested technique is superior to the existing fault detection and location methods. APPENDIX A Table III demonstrates the DC microgrid system information in Fig. 1. TABLE-IV TEST SYSTEM PARAMETER Operating voltage 480V Ratted power Grid VSC solar DC to DC converter Battery bidirectional converter PV panel Battery DC Load EV battery capacity DC bus capacitance Cable Resistance(R) Cable Cross-section area Cable Inductance(L) Cable Capacitance 3 MW 1 MW 1*0.5 MW 1*0.5 MW Vmp=54V, Imp=5.58A, Voc=60V Isc=7.8654A Voltage=12 V, capacity=6 AS 1*250 kW 85 kWh 25 mF 10 mΩ/km 240 mm2 100 µH/km 0.67 µF/km REFERENCES [1] [2] [3] [4] [5] [6] [7] [8] [9] T. Dragičević, X. Lu, J. C. Vasquez, and J. M. Guerrero, “DC Microgrids - Part II: A Review of Power Architectures, Applications, and Standardization Issues,” IEEE Trans. Power Electron., vol. 31, no. 5, pp. 3528–3549, 2016. E. M. Committee, IEEE Recommended Practice for Monitoring, vol. 2004. 1992. B. T. Patterson, “DC, Come Home: DC Microgrids and the Birth of the ‘Enernet,’” IEEE Power Energy Mag., vol. 10, no. 6, pp. 60–69, 2012. R. Ayyanar, R. Giri, and N. Mohan, “Active input-voltage and loadcurrent sharing in input-series and output-parallel connected modular dc-dc converters using dynamic input-voltage reference scheme,” IEEE Trans. Power Electron., vol. 19, no. 6, pp. 1462–1473, 2004. S. Srdic and S. Lukic, “Toward Extreme Fast Charging: Challenges and Opportunities in Directly Connecting to Medium-Voltage Line,” IEEE Electrif. Mag., vol. 7, no. 1, pp. 22–31, 2019. M. Babaei, J. Shi, and S. Abdelwahed, “A Survey on Fault Detection, Isolation, and Reconfiguration Methods in Electric Ship Power Systems,” IEEE Access, vol. 6, pp. 9430–9441, 2018. J. Yang, J. E. Fletcher, and J. O’Reilly, “Short-circuit and ground fault analyses and location in VSC-based DC network cables,” IEEE Trans. Ind. Electron., vol. 59, no. 10, pp. 3827–3837, 2012. A. Maqsood and K. Corzine, “DC Microgrid Protection: Using the Coupled-Inductor Solid-State Circuit Breaker,” IEEE Electrif. Mag., vol. 4, no. 2, pp. 58–64, 2016. A. Meghwani, S. C. Srivastava, and S. Chakrabarti, “A Non-unit Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information. This article has been accepted for publication in IEEE Transactions on Industrial Informatics. This is the author's version which has not been fully edited and content may change prior to final publication. Citation information: DOI 10.1109/TII.2023.3252409 12 [10] [11] [12] [13] [14] [15] [16] [17] [18] [19] [20] [21] [22] [23] Protection Scheme for DC Microgrid Based on Local Measurements,” IEEE Trans. Power Deliv., vol. 32, no. 1, pp. 172– 181, 2017. M. E. Baran and N. R. Mahajan, “Overcurrent protection on voltagesource-converter-based multiterminal DC distribution systems,” IEEE Trans. Power Deliv., vol. 22, no. 1, pp. 406–412, 2007. S. D. A. Fletcher, P. J. Norman, K. Fong, S. J. Galloway, and G. M. Burt, “High-speed differential protection for smart DC distribution systems,” IEEE Trans. Smart Grid, vol. 5, no. 5, pp. 2610–2617, 2014. A. A. S. Emhemed, K. Fong, S. Fletcher, and G. M. Burt, “Validation of fast and selective protection scheme for an LVDC distribution network,” IEEE Trans. Power Deliv., vol. 32, no. 3, pp. 1432–1440, 2017. R. Mohanty and A. K. Pradhan, “Protection of Smart DC Microgrid with Ring Configuration using Parameter Estimation Approach,” IEEE Trans. Smart Grid, vol. 3053, no. c, pp. 1–1, 2017. G. K. Rao and P. Jena, “Fault Detection in DC Microgrid Based on the Resistance Estimation,” IEEE Syst. J., pp. 1–12, 2021. P. Cairoli and R. A. Dougal, “Fault detection and isolation in medium-voltage DC microgrids: Coordination between supply power converters and bus contactors,” IEEE Trans. Power Electron., vol. 33, no. 5, pp. 4535–4546, 2018. A. Saxena, N. K. Sharma, and S. R. Samantaray, “An Enhanced Differential Protection Scheme for LVDC Microgrid,” IEEE J. Emerg. Sel. Top. Power Electron., vol. 10, no. 2, pp. 2114–2125, 2022. M. A. Jarrahi, H. Samet, and T. Ghanbari, “Fault Detection in DC Microgrid: A Transient Monitoring Function-Based Method,” IEEE Trans. Ind. Electron., 2022. C. Srivastava and M. Tripathy, “Novel Adaptive Fault Detection Strategy in DC Microgrid Utilizing Statistical-based Method,” IEEE Trans. Ind. Informatics, pp. 1–11, 2022. Y. Yang, C. Huang, and Q. Xu, “A Fault Location Method Suitable for Low-Voltage DC Line,” IEEE Trans. Power Deliv., vol. 35, no. 1, pp. 194–204, 2020. D. Tzelepis, G. Fusiek, A. Dysko, P. Niewczas, C. Booth, and X. Dong, “Novel Fault Location in MTDC Grids with NonHomogeneous Transmission Lines Utilizing Distributed Current Sensing Technology,” IEEE Trans. Smart Grid, vol. 9, no. 5, pp. 5432–5443, 2018. Y. Xi, Z. Li, X. Zeng, X. Tang, X. Zhang, and H. Xiao, “Fault location based on travelling wave identification using an adaptive extended Kalman filter,” IET Gener. Transm. Distrib., vol. 12, no. 6, pp. 1314–1322, 2018. Z. He, J. Zhang, W. H. Li, and X. Lin, “Improved fault-location system for railway distribution system using superimposed signal,” IEEE Trans. Power Deliv., vol. 25, no. 3, pp. 1899–1911, 2010. N. Bayati, H. R. Baghaee, A. Hajizadeh, M. Soltani, Z. Lin, and M. Savaghebi, “Local Fault Location in Meshed DC Microgrids Based On Parameter Estimation Technique,” IEEE Syst. J., vol. 16, no. 1, pp. 1606–1615, 2022. [24] [25] [26] [27] [28] [29] [30] [31] [32] [33] [34] [35] [36] [37] [38] [39] R. Bhargav, B. R. Bhalja, and C. P. Gupta, “Novel Fault Detection and Localization Algorithm for Low-Voltage DC Microgrid,” IEEE Trans. Ind. Informatics, vol. 16, no. 7, pp. 4498–4511, 2020. K. A. Saleh, A. Hooshyar, and E. F. El-Saadany, “Ultra-high-speed traveling-wave-based protection scheme for medium-voltage DC microgrids,” IEEE Trans. Smart Grid, vol. 10, no. 2, pp. 1440–1451, 2019. S. Dhar, R. K. Patnaik, and P. K. Dash, “Fault Detection and Location of Photovoltaic Based DC Microgrid Using Differential Protection Strategy,” IEEE Trans. Smart Grid, vol. 9, no. 5, pp. 4303–4312, 2018. A. Abdali, K. Mazlumi, and R. Noroozian, “High-speed fault detection and location in DC microgrids systems using MultiCriterion System and neural network,” Appl. Soft Comput. J., vol. 79, pp. 341–353, 2019. J. Do Park, J. Candelaria, L. Ma, and K. Dunn, “DC ring-bus microgrid fault protection and identification of fault location,” IEEE Trans. Power Deliv., vol. 28, no. 4, pp. 2574–2584, 2013. L. Kong and H. Nian, “Fault Detection and Location Method for Mesh-Type DC Microgrid Using Pearson Correlation Coefficient,” IEEE Trans. Power Deliv., vol. 36, no. 3, pp. 1428–1439, 2021. W. S. Lee, J. H. Kim, J. Y. Lee, and I. O. Lee, “Design of an Isolated DC/DC Topology with High Efficiency of over 97% for EV Fast Chargers,” IEEE Trans. Veh. Technol., vol. 68, no. 12, pp. 11725– 11737, 2019. X. Zhang and C. Gong, “Dual-buck half-bridge voltage balancer,” IEEE Trans. Ind. Electron., vol. 60, no. 8, pp. 3157–3164, 2013. R. Mohanty and A. K. Pradhan, “Protection of smart DC microgrid with ring configuration using parameter estimation approach,” IEEE Trans. Smart Grid, vol. 9, no. 6, pp. 6328–6337, 2018. R. L. Scheiterer, C. Na, D. Obradovic, and G. Steindl, “B par,” IEEE Trans. Instrum. Meas., vol. 58, no. 6, pp. 1849–1857, 2009. J. W. Heron, J. Jiang, H. Sun, V. Gezerlis, and T. Doukoglou, “Demand-Response Round-Trip Latency of IoT SmartGrid Network Topologies,” IEEE Access, vol. 6, pp. 22930–22937, 2018. V. Nougain, S. Mishra, and A. K. Pradhan, “MVDC Microgrid Protection Using a Centralized Communication With a Localized Backup Scheme of Adaptive Parameters,” IEEE Trans. Power Deliv., vol. 34, no. 3, pp. 869–878, 2019. M. Pineda-Sanchez et al., “Application of the Teager-Kaiser energy operator to the fault diagnosis of induction motors,” IEEE Trans. Energy Convers., vol. 28, no. 4, pp. 1036–1044, 2013. G. Suryanarayana, G. Kesava Rao, S. Sarangi, and P. Raja, “Directional relaying using parameter estimation approach,” Int. J. Electr. Power Energy Syst., vol. 107, no. December 2018, pp. 597– 604, 2019. S. Ward and T. Erwin, “Current differential line protection setting considerations,” Relay Prot. Substation Autom. Mod. Power Syst., pp. 1–28, 2007. International Standard IEC 61869-3, “Instrument transformers Part 3 Additional requirements for inductive voltage transformers,” Int. Electrotech. Comm. (IEC), Geneva, Switz. Authorized licensed use limited to: Motilal Nehru National Institute of Technology. Downloaded on September 02,2023 at 07:55:59 UTC from IEEE Xplore. Restrictions apply. © 2023 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.See https://www.ieee.org/publications/rights/index.html for more information.