Wind Turbine Testing For Safety, Efficiency, and Fault Identification Solutions from Megger Questions? • Dr Ahmed El-Rasheed • Industry Director - Renewables • Ahmed.El-Rasheed@megger.com Introductions • Agenda: • • • • Why test turbines? What are the most common faults? What are the most costly faults? What testing is recommended? • Generally • Electrically • Generator • Control • Protection • Transformer • Cables • How to get the most from testing? • Where to go for additional info? • Questions Dr Ahmed El-Rasheed Industry Director - Renewables • • • • • • PhD in Electrical Engineering from the University of Liverpool, UK Worked at Megger for over 8 years Based in Toronto, Canada Over 14 years in test instrument product development Published several papers on Insulation Testing, Earth/Ground Testing, & using Artificial Intelligence for asset maintenance Sits on several Standards Committees including IEC, SCC, BSi, and IEEE The Rise of Wind Energy and Renewable Energy • Solar & wind energy are the lowest cost and quickest to build sources of electricity • Globally, both solar & wind have experienced exponential growth. • There are already thousands of gigawatts installed. • The International Energy Agency forecasts that the install base of Solar & Wind will double by 2028 Protect your investment. From the very beginning. And throughout its life. The 360° solution for power applications For a complete health assessment of your asset Efficiency & high Return on Investment needs low failure rates • Good commissioning practice will reduce Early “Infant Mortality” failures • Good diagnostic test practice will reduce the Constant Failure Rate • Fast fault-finding practice will reduce downtime • Good O&M practice will extend the lifespan of the installation • EPRI survey shows average O&M Costs per Turbine(WTG) for a 200MW Wind project (using Dec 2009 US$) • The survey shows that each turbine experiences an average of 1 major outage (6hrs+) every 2 years Survey of type and severity of faults on wind turbines: EPRI • The Electrical System has the most frequent faults, and each fault takes 1.6 days to resolve • Gearbox faults are the most severe, causing 6.2 days of lost generation. However, they are less frequent • Based on this survey, the electrical system should be a high priority in Operation & Maintenance procedures O&M General Recommendations Frequency Maintenance Activity Check for abnormal operating temperatures Daily Check for abnormal vibration or noise Check for fluid leaks (oil, hydraulic, etc..) Check power flow & quality (e.g., THD) Check operation of alarms Monthly Check for oil contamination: gearbox & transformer Analysis of power quality Check of protection & control equipment Analysis of oil samples: gearbox & transformer Quarterly Electrical System health check: cables, generator, transformer, etc.. Check lightning protection Annually Mechanical System health check: bearings, gearbox, drivetrain etc.. Site health check 10 Use Toolbox Philosophy – the right tool for the problem in front of you Electrical System Maintenance: Generator • Recommended tests include: • Insulation Resistance testers • Finds faults to ground • Polarization Index test or Dielectric Absorption test • Diagnostic measure of the ground wall insulation • Coil winding resistance test • Indicates health of the conductor(s) in a winding • Inductance of windings • Changes indicated degradation • Step Voltage Test • Tests the ground wall by approximating starting and stopping • Hi-Pot or Withstand test • Demonstrates the ground wall insultation strength • Surge test • Finding winding turn-to-turn faults and weaknesses • Diode test • Partial Discharge Detection and Monitoring Insulation Life Curve BREAKDOWN VOLTAGE Max voltage before damage Insulation Degradation Optimum test voltage range Operating Voltage TIME (Years) Insulation Failure Electrical System Maintenance: Frequency Converters & Power Quality • The frequency and general quality of the electrical energy from Wind Turbines must meet set requirements in order to seamlessly integrate with the wider grid • Turbine generator energy is converted to DC and then back to AC at the power frequency (50Hz or 60Hz) with the correct phase angle and voltage level • At this stage, harmonics can be introduced, and general power quality needs to be controlled and maintained Wind Turbine Lightning Protection n Wind turbines are at an increased risk of being struck by lightning n Statistically, most common cause of damage n Protection must built in to minimise the damage when hit by lightning. n Otherwise… 14 Lightning Damage to Wind Turbines This happens! 15 Electrical Maintenance: Lightning Protection & Earthing/Grounding System • Vestas’ procedures specify these pass limits for the lightning system: • 23m blades: 15mW • 25m blades: 15mW • 32m blades: 20mW • 39m blades: 25mW • 44m blades: 30mW • Earthing/Grounding system needs to be below 1Ohm for each turbine, and some manufacturers specify 900mOhm limit Case Study Ø Recommended by Vestas for turbine lightning protection system Electrical System Maintenance: Transformer • Transformer commissioning and diagnostic tests include: • • • • • • • • • Insulation Resistance Turns Ratio test Excitation Current test Winding Resistance test Short Circuit Impedance test Power Factor (tip-up) test Partial Discharge detection Swept Frequency Response Analysis Transformer oil • Withstand/Breakdown test • Power Factor (Tan-Delta) test • DGA detection Electrical System Maintenance: Protection Relays • Each Wind Turbine has electrical protection systems that can include relays • Protection Relay tests include: • • • • • Under/Over voltage test Under/Over frequency test Vector shift test Rate of Change of Frequency (ROCOF) test Testing protection functions • Some installations use self-powered relays (SPRs), and they have unique challenges for testing and verification Electrical System Maintenance: Circuit Breakers • Circuit breakers are the key disconnection devices that must operate quickly in the event of a fault • Tests of circuit breakers (depending on type) include: • • • • • • • • • • • Timing and Travel Motion Coil current Static Contact Resistance Measurement (SRM) Dynamic Contact Resistance Measurements (DRM) Vibration Motor current Minimum pick-up (minimum voltage to operate) Supply voltage (battery voltage) Power factor/dissipation factor/tan delta Vacuum bottle test for vacuum circuit breakers Electrical System Maintenance: Batteries • The protection devices, like relays, usually operate from battery power. • This makes the supply batteries critical to the electrical safety system • These are essential safety devices and must be tested at commissioning and during regular maintenance work • Battery tests include: • Battery impedance measurement • Battery discharge/capacity test • Ground fault location, in the event of a fault Electrical System Maintenance: Cables AC Cable DC Cable Electrical System Maintenance: Cables • Cable commissioning and diagnostic testing includes: • VLF tests for medium voltage • Mega Ohm test for low voltage • Sheath test • Partial Discharge detection • Fault finding tests include: • TDR (Radar) • Thumping • High-voltage bridge Testing Cables with TDR Technology §A reflectometer (TDR) works on the principle of a radar device and was therefore also called cable radar in the past. §The pulse sent into the cable is partially reflected at every change in impedance and thus returns to the reflectometer. The size of the change in impedance determines the level of reflection. Total reflection occurs at an open end or a short circuit. §The distance can be determined from the time t and the propagation speed v / 2: L = v / 2 * t Wind power and transmission grid Ensuring highest network availability Interconnectors Offshore / Onshore High-voltage onshore and offshore cable fault location container solutions, tailored to very long HV AC and DX underground and submarine cables, rated up to 525 kV and interconnector lengths of up to 900 km Rotor and generator testing in the wind turbine Substations Transform power into appropriate voltage level Offshore HVDC converter platform Converts AC to DC for feeding into the power grid Grid conector AC cable connection at sea 20-72 kV Converter station (converts DC to AC) DC export cable connection at sea DC cable connection on land AC voltage (AC cable) Converter station Transforms AC to DC voltage for low-loss power transmission via HVDC cables, and reserves this from DC to AC back to the distribution grid for households, commerce and industry Transforming voltages and feed-in into the electrical grid Commissioning according to international standards, e.g., IEC, IEEE, and Cenelec Cable fault location, cable diagnostics, earth resistance testing, partial discharge, and dielectric loss diagnostics Cable section station Improves fault location and optimises its availability: main conductor and cable shield access HV AC/DC transmission lines Maintenance Database and Certification • It is necessary to have robust maintenance programs with historical data in order to ensure reliable and efficient electrical power • A testing database is necessary to be able to trend data as well as comply with regulations • Each test must be well planned before, conducted under all safety guidelines, and the results provides using certification documentation Questions? Technical Support Contact Information APACtsg@megger.com Presenter Dr Ahmed El-Rasheed Industry Director - Renewables Ahmed.El-Rasheed@megger.com Marketing meggerhongkong@megger.com