OPTIMAL PLACEMENT OF TCSC FOR REACTIVE POWER PLANNING USING GRASSHOPPER OPTIMIZATION ALGORITHM CONSIDERING LINE OUTAGE (N-m) Muhamad Amirul Asyraf Juhari1, Nor Rul Hasma Abdullah1, Ibrahim Haruna Shanono1,2, Mahfuzah Mustafa1, Rosdiyana Samad1 and Dwi Pebrianti1 1Faculty of Electrical & Electronics Engineering, Universiti Malaysia Pahang, Pekan Branch, 26600 Pekan, Pahang, Malaysia. 2Department of Electrical, Faculty of the Engineering, Bayero University Kano, Nigeria Outline • • • • Introduction Methodology Results and Analysis Conclusion Introduction o The increasing number of voltage collapse occurrences due to voltage instability which involves heavy load and contingencies has motivated further research in voltage stability. o The increment in load demands will decrease the reactive power and voltage, which leads to voltage collapse in the system. o Voltage collapse has caused the power utility failed to function which may involve monetary loses. o During contingencies, the operating generators fail to operate and cause the reactive power supply by generator suddenly drop. Introduction cont • Therefore, an efficient voltage stability analysis technique is required in order to perform the voltage stability study. • This phenomenon is a progressing issue, which requires a VSA analysis to be properly conducted especially at the planning stage. • The placement of FACTS controllers has been has suggested as an effective methods to prevent against the voltage collapse by installation of Thyristor Controlled Series Capacitor (TCSC) Methodology Reactive Power Dispatch problem can be formulated mathematically as follows: A. Objective Function where x is the vector of dependent variables, u is the vector of control variables, PL is the real power losses at line-L, NI is the number of transmission lines, PL is losses prevailing in the system, Gij is the conductance of the line joining bus-i and bus-j, δij is the phase difference between the buses, Vi and Vj are the absolute value of voltages the buses i and j. 9/27/2023 TCSC Model By inserting a variable reactance either inductive or capacitive in series with the transmission line, the power flow in the transmission line can be manipulated [2]. Zline xTCSC xline γTCSC = the impedance of the transmission line, = the reactance of the line where TCSC is located, = the reactance of TCSC, and = the coefficient which represents the compensation degree of TCSC. IEEE 30-bus RTS 5 voltage control buses 24 load buses 1 slack bus 41 interconnected lines 5 transformer tap changers. The load bus 25 was selected to perform the test. Line outage No: 1 or 9 The selection for line outage was based on the most severe line in the system [2] back Flow chart for implementation of GOA for TCSC Results And Analysis • Analysis tested on the IEEE 30-bus RTS bus 25 subjected 40 MVAr loading and population of 50. • First part: the results for TCSC installation without contingency (N-1) • Second part: the results for TCSC installation with contingency (N-1): Line outage No. 1 and 9 Table 1. Boundaries setting for control variables for IEEE 30-bus system Control Variable TCSC Location TCSC Sizing (p.u) Lower Bound Upper Bound 1 41 -0.8 0.2 Results and Analysis Table 2: Effect of ORPD with load subjected to bus 26 using PSO (Loading, QL = 25 MVAr) Total Generator % ∆Loss Q g2 Q g5 Q g8 Q g11 Q g13 Loss Outage Analysis SVSI No. (MW) MW Pre 0.3636 22.267 28.085 34.941 54.632 21.586 17.693 0 26.7 Post 0.2113 16.328 77.703 -63.921 229.91 33.723 10.437 Pre 0.3878 22.745 39.272 39.761 53.029 23.895 13 42.5 Post 0.2083 13.087 -18.814 32.093 180.302 64.722 Pre 0.4427 24.176 39.003 36.558 60.293 13, 11 19.5 Post 0.2153 19.457 73.328 -75.648 297.957 Pre 0.4482 25.762 43.633 67.508 13, 11, 2 35.9 Post 0.219 16.516 -25.299 281.201 Vm (p.u) 0.7831 1.0394 0.7564 1.0471 0.7032 1.0295 0.6984 1.0206 • All the SVSI values reduce as compared with pre-ORPD with respect to generator outage number variation. • The voltage profiles in the system are also improved. • The transmission losses are minimized. Table 3. Transmission Losses with manipulated loading condition with line outage 1 Pre Optimization (MW) Post Optimization (MW) 0 8.7550 8.6044 10 9.1019 8.8303 20 9.9514 9.2162 30 11.3487 9.9596 40 13.5580 11.0259 QL (MVAr) Location Line No. 14 1 40 9 2 7 10 40 19 34 2 1 13 5 34 17 2 8 15 34 20 17 33 39 34 Sizing (MVAr) -0.5582 -0.3323 -0.0519 -0.6871 -0.8000 -0.6528 -0.2726 0.5017 0.0635 -0.6432 0.1625 -0.4198 -0.6908 -0.3674 -0.5821 -0.7056 -0.0091 0.1497 -0.8000 -0.5208 -0.2550 -0.0201 -0.0468 0.0755 -0.4904 • All the transmission lossed reduce as compared with pre-opt with respect to loading variation. • The transmission losses are minimized. Conclusion The result indicated that PSO and EP techniques had improved the result ; minimize voltage stability, reduce transmission losses and voltage profile PSO technique outperformed EP in terms of voltage stability improvement and voltage profile. Thank You Q&A