Equipotential bonding Power busbar PE protective conductor Standards Theory IEC 61439-1 The PE protective conductor contributes to bringing all the switchboard conductive parts to the same potential. Appendix B Example Prisma Schneider Electric proposes a table for choosing the PE derived from the formula provided by the standard: It must be sufficiently sized and secured in the switchboard to withstand heat and electrodynamics stresses generated by a fault current of a duration of between 0.2 s and 5 s. Icw (kA eff/1 s) < 40 40 < Icw < 85 IEC 61439-1 standard gives a method for calculating the cross-section of the PE conductor: In addition to the calculation method, type tests are conducted to ensure the performance of the protective conductor. Profil Linergy Permissible current 630 A 800 A Flat bar cross-section 25 x 5 mm 50 x 5 mm Icw = permissible short-time rated current SP = √I2t/k Where: • SP: is the cross-section of the PE conductor in mm2 • I: is the effective value of the phase-toearth fault current = 60 % of the phase-tophase fault current • t: duration of the fault current in seconds • k: a factor depending on the protective conductor material. Example: k = 143 for a PVC-insulated copper conductor. 2 The cross-section of the PE conductor must be constant throughout the switchboard, in particular from one column to the next.In the case of a switchboard made up of several columns, all the PE busbars must be connected to each other (fish plates, bolts, etc.). Caution: the cross-section of the fish plates must be at least equal to that of the PE conductor. IEC 61439-1 § 8.4.3.2.3 52 3 The PE conductor must never include an insulating device. version: 5.0 Submittal Page 20 How to assemble an electrical switchboard