ROTEX AUTOMATION LIMITED
UNIT – II : C-1 B/1501, 4 & 5, G.I.D.C. Vithal Udyognagar, Gujarat – 388 121
PHONE : +91 2692 236224 / 236292 / 236399
FAX
: +91 2692 236442
E-mail
: rotexvun@rotexindia.com
WEBSITE : www.rotexindia.com
CIN NO.:U29259GJ1983PLCOO5831
ASSEMBLY TEST CERTIFICA TE
28-Oct-2019
Certificate No.
: 1Q5922/6
Items Sr.Nos.: 19051587-01/50
Customer
: SURESALES AUTOMATION PVT. LTD.
Purchase Order No.
: SAPL/PO/19-20/-0381
Dated 06/08//2019
Quantity of Valves
: 50 Nos.
Type of Valve: 51424-6-2G-B5-M6+24V DC-16
Working Pressure
: 0- 10 Kg./Sq. Cm
Media: AIR
1. Orifice size
: 6.00 mm
2. Bottom Seating Material : NBR
3. Top Seating Material
: NBR
4. ‘O’ Rings Material
: NBR
5. Threads
: ¼” BSP
6. Pressure of Testing at
: 10 Kg/Sq. Cm (g)
Low Pr. Test at
: 0.1 Kg /Sq. Cm (g)
: 10 Kg./Sq.Cm
Leakage at
: 0.1 Kg/Sq. Cm (g)
:
:
:
(a) Exhaust
(b) Exhaust
(c) Joints
: NIL
: NIL
: NIL
7. Leakage at
(a) Exhaust
(b) Exhaust
(c) Joints
8. Body Material
NIL
NIL
NIL
: B5-SS316
9. Hydrostatic Body test @ 18.00 Kg/Sq. Cm (g)
No Leakage
10. Functionally Tested & Found OK.
Remarks:
ELECTRICALS :
1. Type of Coil
: 24V DC-16 (Terminal Box)
2. Size of Coil
: I
3. Voltage
: 24 V DC
4. + 20 % Voltage
: @ 29.00 Volts OK.
5. – 20 % Voltage
: @ 19.00 Volts OK.
6. High Voltage Test
: OK for 1 Minute at 1,048 Volts
7. Insulation Test
: OK for more than 100 MEGA OHMS at 500 V DC
8. Resistance of Coil
: OK
9. Power of Coil
: 8 Watts
10.Functionaly Tested & Found: OK.
11. Actuation Test
: Ok
Remarks- Above all material tested 100% for functionally & aesthetic quality and found okay.
For ROTEX AUTOMATION LIMITED
ASSEMBLY/TESTING INCHARGE