DCP FIELD SERVICE REPORT CUSTOMER LOCATION/SITE Plant Operator/Supervisor WATER ANALYSIS IFFCO Al Shama Foods Nusrat Ali pH Conductivity TSS T-Alk Ca - Hds Chloride pH Unit mic.siemens ppm ppm CaCO3 ppm CaCO3 ppm Cl 1 22 <10 3 <10 44 1008 <200 - 46 1003 <200 - 89 1940 <700 - Make Up Water 7.91 263 Condenser Loop 1 8.81 5,760 Control Limits <8.20 <1200 Chilled Water 9.72 1,926 Control Limits 8.5 - 10.5 < 3000 TSS - Total suspended solids PLANT OPERATING DATA (check operating logs) CHW Load TONS water inlet temp Deg.C water outlet temp Deg.C Delta T CT#2 Deg.C CT Approach Temp Deg.C Dry | Wet bulb temp Deg.C PRODUCTS PM 3686 Sodium Hypo MS 7501 Unit Dr Dr Dr T-Alk - Total Alkalinity REPORT DATE SAMPLE DATE REPORT NO. T-Iron Nitrite ppm Fe ppm NaNO2 0.01 0.81 <1.0 0.23 <1.0 Hds - Hardness 975 >800 WATER CONSUMPTION T.Phosphate Ca- Balance ppm PO4 % 3.25 99.5% 3.50 - 5.50 90 - 100% - 14-07-2023 14-07-2023 SR-333-2023 COC cycles Zinc 21.90 <2.50 3.25 1.0 - 2.0 ppm C.O.C - Cycles of concentration SCHEDULED CHEMICAL CLEANING (was there any chemical cleaning done) CDW n/a n/a n/a n/a n/a n/a CHEMICAL CONSUMPTION Opening Stock Stock received Condenser makeup meter reading Condenser blowdown meter reading Chilled Water System makeup COC based on MU/BL Closing Stock Consumed m3 m3 m3 Cycle 11,660 50 N/A 21.9 where the Condensers clea was cleaning chemical use No N.A COOLING TOWER CLEANING - MICRO BIOLOGICAL ANALYSIS CONDENSER WATER CHILLED WATER Algae Growth in Cooling tower : Water distribution in cooling tower Dip Slide Value N/A N/A No Alage in entire structure Even distribution Condenser Water System: Very high TSS and conductivity levels noted due to difficulty for the site to drain the water and have a consistent source of makeup water quality. High alkalinity, hardness and chloride levels The dosing system was programmed and set for pulse mode to dose the corrosion inhibitor and daily dose of sodium hypo. High COC noted. Recommendations: Recommend to maintain the system with the blowdown setpoint (1200) to avoid white rusting taking place on the coils. Recommend to have a good constant source of makeup water. Recommend Alternate Office and Residential Cooling Towers more often to minimize stagnation times as it increases the potential of bacterial growth and initiates corrosion. Recommend to clean the CT. Chilled Water System: Currently system has nitrite as corrosion inhibitor. CoolTech has supplied NSF grade Silica based corrosion inhibitor. Recommendations: Recommend to drain the whole CHW network of exsiting water and top it up with MS 7501. Prepared by: Sharath Raju Plant Supervisour / Operator: