Copyright © 2020 NR. All rights reserved. NR, the NR logo are either registered trademarks or trademarks of NR Electric Co., Ltd. No NR trademarks may be used without written permission. NR products appearing in this document may be covered by P.R. China and foreign patents. NR Electric Co., Ltd. reserves all rights and benefits afforded under P.R. China and international copyright and patent laws in its products, including but not limited to software, firmware and documentation. NR Engineering Co., Ltd. is licensed to use this document as well as all intellectual property rights owned or held by NR Electric Co., Ltd, including but not limited to copyright, rights in inventions, patents, know-how, trade secrets, trademarks and trade names, service marks, design rights, database rights and rights in data, utility models, domain names and all similar rights. The information in this document is provided for informational use only and does not constitute a legal contract between NR and any person or entity unless otherwise specified. Information in this document is subject to change without prior notice. To the extent required the products described herein meet applicable IEC and IEEE standards, but no such assurance is given with respect to local codes and ordinances because they vary greatly. Although every reasonable effort is made to present current and accurate information, this document does not purport to cover all details or variations in equipment nor provide for every possible contingency to be met in connection with installation, operation, or maintenance. Should further information be desired or should particular problems arise which are not covered sufficiently for your purposes, please do not hesitate to contact us. Preface Preface About This Manual The technical manual describes the protection, automation, control, and supervision functions of PCS-9613S differential relay, and contains operation principle descriptions, and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data, sorted per function, as well as the hardware of the device. The manual can be used as a technical reference during the engineering phase and during normal service. In addition, the manual also includes a glossary that lists and defines technical terms used throughout the manual. Safety Information This manual is not a complete index of all safety measures required for operation of the equipment (module or device). However, it comprises important information that must be followed for personal safety, as well as to avoid material damage. Information is highlighted and illustrated as follows according to the degree of danger: Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury or equipment damage. Indicates that property damage can result if the measures specified are not taken. Important information about the device, product handling or a certain section of the documentation which must be given particular attention. Instructions and Warnings The following hazard statements apply to this device. Disconnect or de-energize all external connections BEFORE opening this device. Contact with hazardous voltages and currents inside this device PCS-9613S Differential Relay I Date: 2020-09-02 Preface can cause electrical shock resulting in injury or death. Contact with instrument terminals can cause electrical shock that can result in injury or death. Use of this equipment in a manner other than specified in this manual can impair operator safety safeguards provided by this equipment. Have only qualified personnel service this equipment. If you are not qualified to service this equipment, you can injure yourself or others, or cause equipment damage. This device is shipped with default passwords. Default passwords should be changed to private passwords at installation. Failure to change each default password to a private password may allow unauthorized access. NR shall not be responsible for any damage resulting from unauthorized access. DO NOT look into the fiber (laser) ports/connectors. DO NOT look into the end of an optical cable connected to an optical output. DO NOT perform any procedures or adjustments that this instruction manual does not describe. During installation, maintenance, or testing of the optical ports, ONLY use the test equipment qualified for Class 1 laser products! PCS-9613S Differential Relay II Date: 2020-09-02 Preface Incorporated components, such as LEDs, transceivers, and laser emitters, are NOT user serviceable. Return units to NR for repair or replacement. Equipment components are SENSITIVE to electrostatic discharge (ESD). Undetectable permanent damage can result if you do not use proper ESD procedures. Ground yourself, your work surface, and this equipment BEFORE removing any cover from this equipment. If your facility is not equipped to work with these components, contact NR about returning this device and related NR equipment for service. Insufficiently rated insulation can deteriorate under abnormal operating conditions and cause equipment damage. For external circuits, use wiring of SUFFICIENTLY RATED insulation that will not break down under abnormal operating conditions. SEVERE power and ground problems can occur on the communications ports of this equipment as a result of using non-standard cables. Please use the wiring method recommended in the manual for communication terminals. DO NOT connect power to the relay until you have completed these procedures and receive instruction to apply power. Equipment damage can result otherwise. Use of controls or adjustments, or performance of procedures other than those specified herein, may RESULT IN hazardous radiation exposure. The firmware may be upgraded to add new features or enhance/modify existing features, please MAKE SURE that the version of this manual is compatible with the product in your hand. PCS-9613S Differential Relay III Date: 2020-09-02 Preface Document Conventions ⚫ The abbreviations and acronyms in this manual are explained in “Appendix A Glossary”. The Glossary also contains definitions of important terms. ⚫ Menu path is connected with the arrow "→" and bold. For example: the access path of protection settings is: MainMenu→Settings→Protection Settings ⚫ Settings not in the table should be placed in brackets. For example: the system setting [Opt_SysFreq] ⚫ Cross-references are presented in italics. For example: refer to Figure 1.1-1, refer to Table 1.1-1, reference to Section 1.1 ⚫ Binary input signals, binary output signals, analogs, LED lights, buttons, and other fixed meanings, should be written in double quotes and bold. For example: press the button "ENT". Symbols ⚫ AND Gate & ⚫ & & >=1 >=1 OR Gate >=1 ⚫ Comparator ⚫ Signal input SIG ⚫ xxx Setting input SET xxx PCS-9613S Differential Relay IV Date: 2020-09-02 Preface ⚫ Enable input EN ⚫ xxx Timer Optional definite-time or inverse-time characteristics Timer t t ⚫ Timer Fixed delay pickup (10ms), fixed delay dropout (2ms) 10ms ⚫ 2ms Timer Settable delay pickup, fixed delay dropout [Tset1] ⚫ 0ms Timer Fixed delay pickup, settable delay dropout 0ms ⚫ [Tset2] Timer Settable delay pickup, settable delay dropout [Tset1] ⚫ [Tset2] Generator G ⚫ Transformer PCS-9613S Differential Relay V Date: 2020-09-02 Preface ⚫ Reactor ⚫ Motor M ⚫ Capacitor C ⚫ Busbar ⚫ Circuit breaker 52 ⚫ Current transformer 3CT * ⚫ Voltage transformer 3VT ⚫ Disconnector ⚫ Earth PCS-9613S Differential Relay VI Date: 2020-09-02 Preface Three-phase Corresponding Relationship Basic A, B, C L1, L2, L3 R, Y, B AN, BN, CN L1N, L2N, L3N RN, YN, BN ABC L123 RYB U (voltage) V U Example Ia, Ib, Ic, I0 IL1, IL2, IL3, IN IR, IY, IB, IN Ua, Ub, Uc VL1, VL2, VL3 UR, UY, UB Uab, Ubc, Uca VL12, VL23, VL31 URY, UYB, UBR U0, U1, U2 VN, V1, V2 UN, U1, U2 Warranty This product is covered by the standard NR 10-year warranty. For warranty details, please consult the manufacturer or agent for warranty information. Document Structure This manual is a comprehensive work covering the theories of protection, control, supervision, measurement, etc. and the structure & technical data of relevant hardware. Read the sections that pertain to your application to gain valuable information about using this device. To concentrate on the target sections of this manual as your job needs and responsibilities dictate. An overview of each manual section and section topics follows. 1 Introduction Introduces the features of this device, summarizes functions and applications of the device. 2 Technical Data Lists device specifications, type tests, and ratings. 3 Protection Functions Describes the function of various protection elements, gives detailed specifics on protection scheme logic, and provides the relevant logic diagrams. 4 Control Functions Describes the logic for the control of disconnectors and circuit breakers. 5 Measurement Provides information on viewing fundamental and metering quantities for voltages and currents, as well as power and energy metering data. 6 Supervision PCS-9613S Differential Relay VII Date: 2020-09-02 Preface Describes self-supervision technique to help diagnose potential difficulties should these occur and includes the list of status notification messages. Provides a troubleshooting chart for common device operation problems. 7 System Functions Describes how to perform fundamental operations such as clock synchronization, communicating with the device, switching active setting group, checking relay status, reading event reports and SER (Sequential Events Recorder) records. 8 Hardware Describes the hardware of the PCS S series device family and provides general information on the product structure and the modules’ information. 9 Settings Provides a list of all PCS-9611S settings and their ranges, unit, steps, defaults. The organization of the settings is similar to the settings organization in the device and in the PCS-Studio configuration tool. Appendix A Glossary Describes the abbreviations adopted in this manual. Document Revision History PN: ZL_PCS-9613S_X_Technical Manual_EN_Overseas General_X Current version: R1.10 Corresponding Version Date Document Software R1.00 R1.00 2019-07-29 R1.01 R1.11 2019-10-17 Description of change ⚫ Form the original manual. ⚫ Capacitive current compensation function for current differential protection is deleted. PCS-9613S Differential Relay VIII Date: 2020-09-02 Preface R1.10 R1.12 ⚫ Measurement scope and accuracy are modified ⚫ The logic of the direction element of phase overcurrent protection, earth fault overcurrent protection, negative-sequence overcurrent protection and sensitive earth fault protection are modified; ⚫ The operation characteristic and dropout characteristic of RMS overcurrent protection are modified; ⚫ The VT circuit supervision function is modified ⚫ The logic diagram of enabling/disabling phase overvoltage protection, residual overvoltage protection, negative-sequence overvoltage protection, positive-sequence overvoltage protection and under voltage protection is modified; ⚫ Switch-on-to-fault protection is modified; ⚫ Broken conductor protection is added; ⚫ Thermal overload protection is added; ⚫ The control function is modified; ⚫ The NR6661A module is added. ⚫ The NR6663A module is added; 2020-09-02 PCS-9613S Differential Relay IX Date: 2020-09-02 Introduction 1 Introduction 1 Table of Contents 1.1 Application ....................................................................................................... 1-1 1.2 Functions ......................................................................................................... 1-1 1.3 Features............................................................................................................ 1-6 List of Figures Figure 1.1-1 Functional diagram of PCS-9613S ....................................................................... 1-1 PCS-9613S Differential Relay 1-a Date: 2020-09-02 1 Introduction 1 PCS-9613S Differential Relay 1-b Date: 2020-09-02 Introduction 1.1 Application The PCS-9613S relay can provide current differential protection, measurement, control and monitoring functions for the feeder line in all systems of which the neutral point is effectively grounded or not effectively grounded. Many auxiliary functions such as fault location, fault recording, event recording, communication functions and etc. are also integrated into the device. This relay is suitable for wall surface mounted indoors or outdoors or flush mounted into a control panel. The function diagram of this relay is shown in Figure 1.1-1. Busbar 3VTs 52 27P 59P 59Q VTS 59G 81U 81R 81O 25 79 1 VT 67P * 3 CTs 87L * 32R 50P 51P 50G 51G 46BC CTS 51Q 37 FR 49 1CT SOTF 67G Data exchange Load Figure 1.1-1 Functional diagram of PCS-9613S 1.2 Functions 1 Protection functions ANSI 87 Protection Functions Current differential protection Remark Steady-state current differential element (2 stages) CT saturation detection PCS-9613S Differential Relay 1-1 Date: 2020-09-02 1 1 Introduction 1 67P 50/51P Phase overcurrent protection Up to 6 stages with independent logic Voltage control element for each stage Optional direction element for each stage, including forward direction, reverse direction and non-direction Optional definite-time characteristic and inverse-time characteristic for each stage Selectable trip purpose or alarm purpose for each stage Harmonic control element for each stage Up to 6 stages with independent logic Optional direction element for each stage, including forward direction, reverse direction and non-direction 67G 50/51G Earth fault protection Optional measured zero-sequence current or calculated zero-sequence current Optional definite-time characteristic and inverse-time characteristic for each stage 50/51Q Negative-sequence Selectable trip purpose or alarm purpose for each stage Harmonic control element for each stage Up to 2 stages with independent logic Optional direction element for each stage, including overcurrent forward direction, reverse direction and non-direction protection Optional definite-time characteristic and inverse-time characteristic for each stage 50/51R 46BC RMS overcurrent protection Selectable trip purpose or alarm purpose for each stage Up to 2 stages with independent logic Full-current RMS value includes 2nd~11th harmonic components Selectable trip purpose or alarm purpose for each stage Adopt the ratio of negative-sequence current to positive-sequence current (Ι2/Ι1) to detect the broken Broken conductor protection conductor. 59P 59G 59Q 59Pos Overvoltage protection Residual overvoltage protection Negative-sequence overvoltage protection Positive-sequence protection overvoltage Up to 2 stages with independent logic Optional definite-time characteristic and inverse-time characteristic for each stage Optional phase voltage or phase-to-phase voltage Optional “1-out-of-3” logic or “3-out-of-3” logic Selectable trip purpose or alarm purpose for each stage Up to 2 stages with independent logic Selectable trip purpose or alarm purpose for each stage Up to 2 stages with independent logic Selectable trip purpose or alarm purpose for each stage One stage of positive-sequence overvoltage protection Selectable trip purpose or alarm purpose PCS-9613S Differential Relay 1-2 Date: 2020-09-02 Introduction Up to 2 stages with independent logic Optional definite-time characteristic and inverse-time 1 characteristic for each stage 27P Undervoltage protection Optional phase voltage or phase-to-phase voltage Optional “1-out-of-3” logic or “3-out-of-3” logic Check mode using circuit breaker position and current criterion 81O Overfrequency protection 81U Underfrequency protection 81R 32R 37 Frequency rate-of-change protection Reverse power protection Undercurrent protection Blocked by instantaneous VT circuit failure Selectable trip purpose or alarm purpose for each stage Up to 6 stages with independent logic Voltage control element Up to 6 stages with independent logic Voltage control element Up to 6 stages with independent logic Voltage control element Up to 2 stages with independent logic Selectable trip purpose or alarm purpose for each stage Optional blocking condition, including circuit breaker position and current criterion Optional “1-out-of-3” logic or “3-out-of-3” logic Selectable trip purpose or alarm purpose for each stage Breaker failure protection and re-trip function Optional current criterion (phase overcurrent element, zero-sequence overcurrent element, negative-sequence 50BF Breaker failure protection overcurrent element) It can be initiated by current, circuit breaker position or external binary input 50PSOTF 50GSOTF Switch-on-to-fault protection Two time delays One stage of phase overcurrent SOTF protection One stage of earth fault overcurrent SOTF protection Harmonic control element Voltage control element for phase overcurrent SOTF protection 49 Thermal overload protection 25 Synchro-check 79 Auto-reclosing Two stages of thermal overload protection, one stage for alarm purpose and the other stage for trip purpose Independent logic for auto-reclosing and manually closing One shot or multi-shot 3-pole AR It can be triggered by protection operation signal or external binary input signal VTS Voltage transformer supervision CTS Current transformer supervision FL Supports synchronism check or dead charge check Fault location function PCS-9613S Differential Relay 1-3 Date: 2020-09-02 1 Introduction TCS 1 2 3 4 5 Tripping circuit supervision Control functions ⚫ Circuit breaker & disconnector control (Remote/Local) ⚫ Synchronism check for remote and manual closing Measurement functions ⚫ Energy metering (active and reactive energy are calculated in import and export direction respectively) ⚫ Power (Apparent/Active/Reactive) ⚫ Power factor ⚫ Frequency ⚫ Event recorder including 1024 disturbance items, 1024 binary events, 1024 supervision events, 256 control logs and 1024 device logs. ⚫ Disturbance recorder including 64 disturbance records with waveforms (The file format of disturbance recorder is compatible with international COMTRADE file). Supervision functions ⚫ VT circuit supervision ⚫ CT circuit supervision ⚫ Trip/Close coil supervision ⚫ Self-diagnostic ⚫ DC power supply supervision ⚫ System frequency supervision Communication functions ⚫ Up to four 10Base-T/100Base-TX copper Ethernet ports using IEC 61850, DNP3 or IEC 60870-5-103 over TCP/IP ⚫ Up to four 100Base-FX optical Ethernet ports using IEC 61850, DNP3 or IEC 60870-5-103 over TCP/IP ⚫ Two RS-485 serial ports using IEC 60870-5-103 or Modbus ⚫ One RS-485 serial port for clock synchronization ⚫ Support GOOSE communication module using IEC 61850-8-1 GOOSE ⚫ Full compatibility between IEC 61850 Editions 1 and 2 ⚫ Redundancy protocols PRP and HSR PCS-9613S Differential Relay 1-4 Date: 2020-09-02 Introduction ⚫ 6 7 8 One front RJ45 port for debugging Digital interface ⚫ Support IEC 61850 MMS Server via extendable electrical or optical Ethernet port ⚫ Support IEC 61850-8-1 GOOSE via extendable electrical or optical Ethernet port ⚫ Support IEC 61850-9-2LE SV via extendable electrical or optical Ethernet port 1 User Interfaces ⚫ Friendly HMI interface with LCD, easy-to-use keypad aids simple navigation and set-point adjustment ⚫ Push buttons for open/close, switch for selection between local and remote control, and user's login and logout authority management ⚫ 4 Programmable operator pushbuttons with user-configurable labels ⚫ Up to 15/18 (6U, 1/3 × 19" or 6U, 1/2 × 19" chassis) programmable target LEDs with user-configurable labels ⚫ 1 RS-232 rear port for printer (by iumper) ⚫ Language switchover—English+ selected language ⚫ Configuration tool—PCS-Studio Additional functions ⚫ User programmable logic ⚫ Fault location ⚫ Fault phase selection ⚫ System phase sequences rotation function (ABC or ACB) ⚫ Clock synchronization ⚫ IRIG-B: IRIG-B via RS-485 differential level or TTL level PPS: Pulse per second (PPS) via RS-485 differential level or binary input PPM: Pulse per minute (PPM) via RS-485 differential level or binary input IEEE1588: Clock message based on IEEE1588 via Ethernet network SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network SNTP (BC): Broadcast SNTP mode via Ethernet network Message (IEC103/Modbus/DNP3): Clock messages through IEC103 protocol, Modbus protocol and DNP3 protocol Cyber security PCS-9613S Differential Relay 1-5 Date: 2020-09-02 1 Introduction 1 NERC CIP IEC 62351 IEC 62443 IEEE 1686 1.3 Features ⚫ Unified software and hardware platform, comprehensive power grid solutions of protection, control, measurement and monitoring, easy to use and maintain. ⚫ High reliability and redundancy design for drive systems of the sampling circuit and the output circuit ensure that overall reliability of the device is high. Real-time sampling based on dual AD can mutually check and detect the potential abnormality in the sampling circuit in time. The control power supply of the output relay is independent with the control circuit of trigger signals, which can prevent from undesired operation caused by the abnormality of drive circuit of output relays. ⚫ Various function modules can satisfy various situations according to the different requirements of users. Flexible and universal logic programming, user-defined configuration of BI/BOs, buttons and LEDs and powerful analogue programming are supported. ⚫ Modularized hardware design makes the device be easily upgraded or repaired by a qualified service person. It can be combined with different I/O modules, with online self-check and monitoring function, and the device can be restored from abnormal operation only need to replace a single abnormal module. ⚫ Support memory check and error correction function, ensure high reliability and safety. ⚫ Support the internet communication protocol of native PRP/HSR and RSTP. ⚫ Fully compatible with IEC 61850 edition 1 & edition 2, support MMS service, IEC 62351 communication service, GOOSE communication in station level & process level, SV communication with multi-sampling rate. ⚫ Fully comply with cyber security standards, including IEC62443, IEC62351, IEEE1686, NERC-CIP, support role based access control (RBAC), security audit, security encryption communication and security tool, improve the cyber security capability of devices. ⚫ Powerful COMTRADE fault and disturbance recording function is supported. The whole recording time is automatically configurable by the fault duration, which is convenient to fault analysis and replay. The recording sample rate is up to 9.6kHz. ⚫ Settable secondary rated current (1A/5A) and settable voltage threshold of binary input ⚫ Support small size and large size LCD, control and multifunction button ⚫ Support flush mounting, semi-flush mounting, surface mounting, wall mounting and other mounting methods. PCS-9613S Differential Relay 1-6 Date: 2020-09-02 Introduction ⚫ Cross screw IO, CT/VT terminals can support AWG12 specification connector and 4mm 2 lead ⚫ Multiple variants with case size 6U, 1/3 × 19" or 6U, 1/2 × 19" ⚫ Protection class of front side is up to IP54 ⚫ PCS-Studio engineering tool is the application software on the user's PC for the interface with PCS S series devices providing all the related functionality. It ranges from device configuration to entire substation design of bay integration. ⚫ Support IEEE1588, IRIG-B clock synchronization ⚫ Support actual system phase sequence, either ABC or ACB, incorrect connection of actual phase sequence can automatically be verified and relevant protection functions can be blocked. ⚫ Equipped with high-speed large capacity output relay, its operation speed is less than 1ms and its break capacity is up to 10A. The real-time supervision for output drive circuit can detect the abnormality in advance. ⚫ Support setup up to 40 users and allow each user to own different password and access authority. ⚫ Fully integrates multi functions into one device and can realize the protection and monitoring 1 function of feeder line. ⚫ Current differential protection Two-terminal transmission line application. Phase-segregated differential protection employs steady quantities as protection criteria, easy to set, quick to clear the fault, high sensitivity and immune to power swing and load fluctuation. Current differential protection has the excellent resistance to CT saturation when external fault. As long as the correct transfer time is no less than 3ms, current differential protection will ensure fast clearance of internal fault and non-operation of external fault. Current differential protection supports double fiber channel, parallel and independent, either can be selected as main channel and seamlessly switched to standby channel when main channel is abnormal. Unique and reliable differential logic and it can be set non-operation when CT circuit failure under normal conditions. ⚫ Both dedicated fiber channel and multiplexing fiber channel are supported, and single mode and multi-mode channel combination operation mode is enable. Communication rate supports 64kbit/s and 2Mbit/s, and communication protocol supports C37.94 and G.703. ⚫ Comprehensive functionality includes phase overcurrent protection, earth fault overcurrent protection, negative-sequence overcurrent protection, overvoltage protection, undervoltage PCS-9613S Differential Relay 1-7 Date: 2020-09-02 1 Introduction protection, frequency protection, reverse power protection, breaker failure protection, undercurrent protection etc. The breaker failure, reclosing, measuring, monitoring and control function are supported. 1 ⚫ The overcurrent protection is combined with harmonic blocking logic, which can prevent mal-operation affected by inrush current while the transformer is no-load energized. ⚫ Selectable IEC, ANSI inverse-time characteristic curves that can be defined by users, and the inverse-time drop-out curve selection is supported. ⚫ Overvoltage and undervoltage protection support single phase and three phase operation criteria setting, phase voltage and phase-to-phase voltage measurement mode are selectable, which can be for various applications. ⚫ Complete event recording function is provided: 64 latest protection operation reports, 1024 latest supervision records, 1024 latest control operation records, 1024 latest user operation records and 1024 latest records of time tagged sequence of event (SOE) can be recorded. PCS-9613S Differential Relay 1-8 Date: 2020-09-02 2 Technical Data 2 Technical Data Table of Contents 2.1 Electrical Specifications ................................................................................. 2-1 2.1.1 AC Current Input ................................................................................................................... 2-1 2.1.2 AC Voltage Input................................................................................................................... 2-1 2.1.3 Power Supply ....................................................................................................................... 2-2 2.1.4 Binary Input .......................................................................................................................... 2-2 2.1.5 Binary Output........................................................................................................................ 2-4 2.2 Mechanical Specifications .............................................................................. 2-5 2.3 Ambient Temperature and Humidity Range .................................................. 2-6 2.4 Communication Port ....................................................................................... 2-6 2.4.1 EIA-485 Port ......................................................................................................................... 2-6 2.4.2 Ethernet Port ........................................................................................................................ 2-6 2.4.3 Optical Fiber Port ................................................................................................................. 2-7 2.4.4 Print Port............................................................................................................................... 2-7 2.4.5 Clock Synchronization Port .................................................................................................. 2-7 2.5 Type Tests ........................................................................................................ 2-8 2.5.1 Environmental Tests ............................................................................................................. 2-8 2.5.2 Mechanical Tests .................................................................................................................. 2-8 2.5.3 Electrical Tests...................................................................................................................... 2-8 2.5.4 Electromagnetic Compatibility .............................................................................................. 2-8 2.6 Certifications.................................................................................................. 2-10 2.7 Liquid Crystal Display (LCD) .........................................................................2-11 2.8 Terminals .........................................................................................................2-11 2.8.1 Ring Ferrule ........................................................................................................................ 2-11 2.8.2 Pin Ferrule .......................................................................................................................... 2-11 2.9 Measurement Scope and Accuracy ..............................................................2-11 2.10 Management Function ................................................................................. 2-12 PCS-9613S Differential Relay 2-a Date: 2020-09-02 2 2 Technical Data 2.10.1 Control Performance ........................................................................................................ 2-12 2.10.2 Clock Performance ........................................................................................................... 2-12 2.10.3 Fault and Disturbance Recording..................................................................................... 2-12 2.10.4 Binary Input Signal ........................................................................................................... 2-12 2 2.11 Protective Functions ................................................................................... 2-13 2.11.1 Fault Detector (FD) ........................................................................................................... 2-13 2.11.2 Current Differential Protection (87L) ................................................................................. 2-13 2.11.3 Phase Overcurrent Protection (50/51P) ........................................................................... 2-13 2.11.4 Earth Fault Protection (50/51G) ....................................................................................... 2-14 2.11.5 Negative-sequence Overcurrent Protection (50/51Q)...................................................... 2-15 2.11.6 RMS Overcurrent Protection (50/51R) ............................................................................. 2-16 2.11.7 Broken Conductor Protection (46BC) ............................................................................... 2-16 2.11.8 Phase Overvoltage Protection (59P) ................................................................................ 2-16 2.11.9 Residual Overvoltage Protection (59G) ........................................................................... 2-17 2.11.10 Negative-sequence Overvoltage Protection (59Q) ........................................................ 2-17 2.11.11 Positive-sequence Overvoltage Protection (59Pos) ....................................................... 2-17 2.11.12 Phase Undervoltage Protection (27P) ............................................................................ 2-17 2.11.13 Overfrequency Protection (81O) .................................................................................... 2-18 2.11.14 Underfrequency Protection (81U)................................................................................... 2-18 2.11.15 Frequency Rate-of-change Protection (81R) ................................................................. 2-18 2.11.16 Reverse Power Protection (32R).................................................................................... 2-18 2.11.17 Undercurrent Protection (37) .......................................................................................... 2-19 2.11.18 Breaker Failure Protection (50BF).................................................................................. 2-19 2.11.19 Switch-on-to-Fault Protection (SOTF) ............................................................................ 2-19 2.11.20 Thermal Overload Protection (49) .................................................................................. 2-20 2.11.21 Auto-reclosing (79) ......................................................................................................... 2-20 2.11.22 Transient Overreach ....................................................................................................... 2-20 2.11.23 Fault Locator ................................................................................................................... 2-20 2.12 Communication Functions ......................................................................... 2-20 2.12.1 GOOSE ............................................................................................................................ 2-20 PCS-9613S Differential Relay 2-b Date: 2020-09-02 2 Technical Data 2.12.2 SV ..................................................................................................................................... 2-21 2 PCS-9613S Differential Relay 2-c Date: 2020-09-02 2 Technical Data 2 PCS-9613S Differential Relay 2-d Date: 2020-09-02 2 Technical Data 2.1 Electrical Specifications “System phase sequence”, which can be set by PCS-Studio, this setting informs the device of the actual system phase sequence, either ABC or ACB. CT and VT inputs on the device, labelled as A, B and C, must be connected to system phase A, B and C for correct operation. 2.1.1 AC Current Input Phase rotation ABC or ACB Nominal frequency (fn) 50Hz, 60Hz Rated current (In) 1A/5A (Settable) Linear to 0.05In~40In Thermal withstand -continuously 4In -for 10s 30In -for 1s 100In -for half a cycle 250In Burden <0.05VA/phase @1A, <0.25VA/phase @5A Number Up to 4 current inputs according to various applications 2.1.2 AC Voltage Input Phase rotation ABC or ACB Nominal frequency (fn) 50Hz, 60Hz Rated voltage (Un) 100V~130V Linear to 1V~300V Thermal withstand Phase-to-ground Phase-to-phase -continuously 300V 519V -10s 600V 1038V -1s 660V 1141V Burden at rated <0.10VA/phase @100V PCS-9613S Differential Relay 2-1 Date: 2020-09-02 2 2 Technical Data Number Up to 4 voltage inputs according to various applications 2.1.3 Power Supply 100Vac/110Vac/115Vac 110Vdc/125Vdc 2 24Vdc/30Vdc Rated voltage 120Vac/127Vac/220Vac 220Vdc/250Vdc 48Vdc/60Vdc 230Vac/240Vac/250Vac IEC 61000-4-11:2017 IEC 61000-4-29:2000 Permissible voltage range 88~300Vdc 80~275Vac 18~72Vdc IEC 60255-26:2013 Permissible AC ripple voltage ≤15% of the nominal auxiliary voltage Quiescent condition Additional for <15W (Default hardware configuration) each 0.25W ~ 0.35W energized SFP Quiescent condition: <1W 0.004W @ 24VDC Additional for each BI 0.015W @ 48VDC Additional for each energized Burden module 0.08W @ 110VDC binary input 0.32W @ 220VDC 0.41W @ 250VDC Additional for each BO module Quiescent condition: <0.1W Additional for each energized relay: <0.44W Additional module for SV <7W sampling 2.1.4 Binary Input Settable pickup voltage and dropout voltage Rated voltage 110Vdc 125Vdc 220Vdc 250Vdc Rated current drain 0.73mA 0.83mA 1.47mA 1.67mA On value (default set) 69.3~132Vdc 78.75~160Vdc 138.6~264Vdc 157.5~300Vdc PCS-9613S Differential Relay 2-2 Date: 2020-09-02 2 Technical Data Off value (default set) <55Vdc <62.5Vdc Maximum permissible voltage 300Vdc Withstand voltage 2000Vac, 2800Vdc (1 min) <110Vdc <125Vdc Up to 34 (6U, 1/3 × 19", ring ferrule), 41 (6U, 1/3 × 19", pin ferrule), 84 Number (6U, 1/2 × 19", ring ferrule) or 105 (6U, 1/2 × 19", pin ferrule) binary inputs according to various hardware configurations Settable pickup voltage and dropout voltage Rated voltage 110Vac 220Vac Rated current drain 0.73mA 1.47mA On value (default set) 69.3~132Vac 138.6~264Vac Off value (default set) <55Vac <110Vac Maximum permissible voltage 300Vac Withstand voltage 2000Vac, 2800Vdc (1 min) Up to 34 (6U, 1/3 × 19", ring ferrule), 41 (6U, 1/3 × 19", pin ferrule), 84 Number (6U, 1/2 × 19", ring ferrule) or 105 (6U, 1/2 × 19", pin ferrule) binary inputs according to various hardware configurations Settable pickup voltage and dropout voltage Rated voltage 24Vdc 48Vdc Rated current drain 0.16mA 0.32mA On value (default set) 15.12~28.8Vdc 30.24~57.6Vdc Off value (default set) <12V <24V Maximum permissible voltage 300Vdc Withstand voltage 2000Vac, 2800Vdc (1 min) Up to 34 (6U, 1/3 × 19", ring ferrule), 41 (6U, 1/3 × 19", pin ferrule), 84 Number (6U, 1/2 × 19", ring ferrule) or 105 (6U, 1/2 × 19", pin ferrule) binary inputs according to various hardware configurations PCS-9613S Differential Relay 2-3 Date: 2020-09-02 2 2 Technical Data 2.1.5 Binary Output Tripping/signalling contact 2 Output mode Potential free contact Maximum system voltage 250Vac, 300Vdc Continuous carry 10A Pickup time (Typical value) <5ms Drop-off time (Resistive load) <6ms 0.5A@48Vdc 0.35A@110Vdc Breaking capacity (L/R=40ms) 0.30A@125Vdc 0.20A@220Vdc 0.15A@250Vdc 0.5A@48Vdc 0.35A@110Vdc Cyclic capacity (2.5 cycle/second, 0.30A@125Vdc L/R=40ms) 0.20A@220Vdc 0.15A@250Vdc 30A@3s Short duration current 50A@1s Durability (Loaded contact) 10000 operations Up to 18 (6U, 1/3 × 19", ring ferrule), 22 (6U, 1/3 × 19", pin ferrule), 44 Number (6U, 1/2 × 19", ring ferrule) or 56 (6U, 1/2 × 19", pin ferrule) binary outputs according to various hardware configurations Heavy-capacity tripping contact Output mode Potential free contact MOV Protection (Maximum voltage) 350Vdc, 275Vac Continuous carry 10A Pickup time (Typical value) <1ms PCS-9613S Differential Relay 2-4 Date: 2020-09-02 2 Technical Data Dropout time (Resistive load) <10ms 10A@48V L/R=40ms 10A@110V L/R=40ms Breaking capacity 10A@125V L/R=40ms 2 10A@220V L/R=20ms 10A@250V L/R=20ms 10A@48V L/R=40ms Cyclic Capacity (4cycles in 1 second, 10A@110V L/R=40ms followed by 2 minutes idle for thermal 10A@125V L/R=40ms dissipation) 10A@220V L/R=20ms 10A@250V L/R=20ms 30A@3s Short duration current 50A@1s Durability (Loaded contact) 10000 operations Up to 4 (6U, 1/3 × 19", ring ferrule) or 12 (6U, 1/2 × 19", ring ferrule) Number heavy-capacity binary outputs according to various hardware configurations 2.2 Mechanical Specifications Chassis color Silver grey Approx. 8.66kg (6U, 1/2 × 19") Weight per device Approx. 6.93kg (6U, 1/3 × 19") Chassis material Aluminum alloy Location of terminal Rear panel of the device Device structure Plug-in modular type @ rear side, integrated front plate Protection Class Standard IEC 60529-2013 IP52 Front side IP54 (valid for surface mounting mode of 6U, 1/3 × 19" or 6U, 1/2 × 19" PCS-9613S Differential Relay 2-5 Date: 2020-09-02 2 Technical Data case with sealing strip) 2 Other sides IP50 Rear side, connection terminals IP20 2.3 Ambient Temperature and Humidity Range Standard IEC 60255-1:2009 -40°C to +80°C (Readability of display may be impaired below -20°C Operating temperature and above 70°C) Transport and storage temperature -40°C to +80°C range Permissible humidity 5%~95%, without condensation Pollution degree Ⅱ Altitude <3000m 2.4 Communication Port 2.4.1 EIA-485 Port Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s Protocol IEC 60870-5-103:1997 or Modbus Maximum capacity 32 Maximum transmission distance 500m Safety level Isolation to ELV level Twisted pair Screened twisted pair cable 2.4.2 Ethernet Port Connector type RJ-45 LC Transmission rate 100Mbit/s Transmission standard 100Base-TX 100Base-FX Maximum transmission distance 100m 2km (1310nm) Protocol IEC 60870-5-103:1997, DNP 3.0 or IEC 61850 PCS-9613S Differential Relay 2-6 Date: 2020-09-02 2 Technical Data Safety level Isolation to ELV level 2.4.3 Optical Fiber Port For Station Level and Process Level Characteristic Glass optical fiber Connector type LC Fiber type Multi mode Maximum transmission distance 2km Wave length 1310nm Minimum transmission power 50μm: -24dBm Minimum receiving power -31dBm Margin 50μm: -7dBm 2 62.5μm: -20dBm 62.5μm: -9dBm For Differential Communications Characteristics Glass optical fiber Connector type ST or FC Fibre type Single mode Wave length 1310nm 1550nm 850nm Transmission power -11.0dBm~-7.0dBm 0dBm~5dBm 62.5μm: -20dBm~-12dBm Minimum receiving power -38dBm -36dBm 62.5μm: -32dBm Maximum transmission distance 60km 120km 62.5μm: 2km Multi mode 2.4.4 Print Port Type RS-232 Baud rate 4.8kbit/s, 9.6kbit/s, 19.2kbit/s, 38.4kbit/s, 57.6kbit/s, 115.2kbit/s Printer type EPSON® 300K printer Safety level Isolation to ELV level 2.4.5 Clock Synchronization Port Type RS-485 serial port Input Demodulated IRIG-B or PPS PCS-9613S Differential Relay 2-7 Date: 2020-09-02 2 Technical Data Nominal voltage 5Vdc+10% Maximum voltage 5.5Vdc Input impedance 2.5kΩ Isolation 500Vdc 2 2.5 Type Tests 2.5.1 Environmental Tests Dry cold test IEC60068-2-1:2007 Dry heat test IEC60068-2-2:2007 Damp heat test, cyclic IEC60068-2-30:2005 2.5.2 Mechanical Tests Vibration IEC 60255-21-1:1988 Class Ⅰ Shock and bump IEC 60255-21-2:1988 Class Ⅰ 2.5.3 Electrical Tests Standard IEC 60255-27:2013 Dielectric tests Test voltage 2kV, 50Hz, 1min Impulse voltage tests Test voltage 5kV Overvoltage category Ⅲ Insulation resistance measurements Isolation resistance >100MΩ@500VDC 2.5.4 Electromagnetic Compatibility IEC 60255-26:2013 1MHz burst disturbance test Common mode: class Ⅲ 2.5kV Differential mode: class Ⅲ 1.0kV IEC 61000-4-2:2008 class Ⅳ Electrostatic discharge test For contact discharge: 8kV For air discharge: 15kV Radio frequency interference tests IEC 60255-26:2013 class Ⅲ PCS-9613S Differential Relay 2-8 Date: 2020-09-02 2 Technical Data Frequency sweep Radiated amplitude-modulated 10V/m (rms), f=80~1000MHz, 1400~2700MHz Spot frequency 2 Radiated amplitude-modulated 10V/m (rms), f=80MHz/160MHz/450MHz/900MHz IEC 60255-26:2013 Power supply, I/O, Earth: class Ⅳ, 4kV, 5kHz, 5/50ns Fast transient disturbance tests Communication terminals: class Ⅳ, 2kV, 5kHz, 5/50ns IEC 60255-26:2013 Power supply, AC input, I/O port: class Ⅳ, 1.2/50μs Surge immunity test Common mode: 4kV Differential mode: 2kV IEC 60255-26:2013 Power supply, AC, I/O, Comm. Terminal: Class Ⅲ, 10V (rms), 150 Conducted RF electromagnetic kHz~80MHz disturbance Spot frequency 10V (rms), f=27MHz/68MHz Power frequency magnetic field immunity IEC 61000-4-8: 2009 class Ⅴ, 100A/m for 1min, 1000A/m for 3s IEC 61000-4-9:2016 Pulse magnetic field immunity class Ⅴ, 6.4/16μs, 1000A/m for 3s Damped oscillatory magnetic field IEC 61000-4-10:2016 immunity class Ⅴ, 100kHz & 1MHz–100A/m IEC 60255-26:2013 Conducted emission 0.15MHz~0.50MHz: 79dB (μV) quasi peak, 66dB (μV) average 0.50MHz~30MHz: 73dB (μV) quasi peak, 60dB (μV) average IEC 60255-26:2013 Radiated emission Below 1GHz 30MHz~230MHz: 40dB (μV/m) quasi peak @10m, PCS-9613S Differential Relay 2-9 Date: 2020-09-02 2 Technical Data 50dB (μV/m) quasi peak @3m 230MHz~1000MHz: 47dB (μV/m) quasi peak @10m, 57dB (μV/m) quasi peak @3m 1GHz~3GHz: 56dB (μV/m) average, 76dB (μV/m) 2 peak @3m Above 1GHz 3GHz~6GHz: 60dB (μV/m) average, 80dB (μV/m) peak @3m IEC 60255-26:2013 Auxiliary power supply performance Up to 200ms for dips to 40% of rated voltage without reset - Voltage dips 50ms for interruption without rebooting without energy storage board -Voltage short interruptions (Typical configuration) 500ms for interruption without rebooting with energy storage board (Typical configuration) 2.6 Certifications ⚫ ISO9001:2015 ⚫ ISO14001:2015 ⚫ ISO45001:2018 ⚫ ISO/IEC27001:2013 ⚫ CMMI L5 ⚫ EMC: 2014/30/EU, EN60255-26:2013 ⚫ Products safety (LVD): 2014/35/EU, EN60255-27:2014 ⚫ IEC 61850: Edition 2, Parts 6, 7-1, 7-2, 7-3,7-4 and 8-1 ⚫ IEC 61850: Edition 2, GOOSE Performance Class P1 (3ms) ⚫ IEEE 1588: IEEE Std C37.238TM-2017 ⚫ DNP: DNP 3.0 ⚫ PRP: IEC 62439-3 Ed.3 (IS 2016) ⚫ HSR: IEC 62439-3 Ed.3 (IS 2016) PCS-9613S Differential Relay 2-10 Date: 2020-09-02 2 Technical Data 2.7 Liquid Crystal Display (LCD) Type Resolution Large size (6U 1/2 × 19" case) 320x240 pixels Small size (6U 1/3 × 19" case) 240x160 pixels 2 2.8 Terminals 2.8.1 Ring Ferrule Connection Type Wire Size Screw Type Torque AC current Screw terminals, 1.5~4mm2 lead M4 1.6~1.8 N⋅m AC voltage Screw terminals, 0.8~4mm2 lead M4 1.6~1.8 N⋅m Power supply Screw terminals, 0.8~4mm2 lead M4 0.8~1.4 N⋅m Contact I/O Screw terminals, 0.8~4mm2 lead M4 0.8~1.4 N⋅m Grounding (Earthing) connection BVR type, 0.8~4mm2 lead M3 0.6~0.8 N⋅m 2.8.2 Pin Ferrule Connection Type Wire Size Screw Type Torque Power supply Screw terminals, 0.3~3.3mm2 lead M2.5 0.4~0.6 N⋅m Contact I/O Screw terminals, 0.3~3.3mm2 lead M2.5 0.4~0.6 N⋅m 2.9 Measurement Scope and Accuracy Item Range Phase range 0°~ 360° Accuracy ±0.2° (0.2×In<I<4.0×In) ±0.5° (0.1×In<I<0.2×In) Frequency Fn±5 Hz ≤ 0.002Hz Currents from protection measurement current transformers ≤ 0.6% of rating (0.06In~0.2In) Current 0.06~4.00In ≤ 0.2% of applied quantities (0.2In~4.00In) Voltage 0.05~1.50Un ≤ 0.2% of applied quantities (0.05Un~1.50Un) PCS-9613S Differential Relay 2-11 Date: 2020-09-02 2 Technical Data 0.05~1.50Un ≤ 1.0% of rating (0.06~0.1In) 0.06~4.00In ≤ 0.5% of applied quantities (0.1~4.00In) 0.05~1.50Un ≤ 1.0% of rating (0.06~0.1In) 0.06~4.00In ≤ 0.5% of applied quantities (0.1~4.00In) 0.05~1.50Un ≤ 1.0% of rating (0.06~0.1In) 0.06~4.00In ≤ 0.5% of applied quantities (0.1~4.00In) 0.05~1.50Un ≤ 1.0% of rating (0.06~0.1In) 0.06~4.00In ≤ 0.5% of applied quantities (0.1~4.00In) 0.05~1.50Un ≤ 1.0% of rating (0.06~0.1In) 0.06~4.00In ≤ 0.5% of applied quantities (0.1~4.00In) Active power (W) Reactive power (VAr) 2 Apparent power (VA) Energy (Wh) Energy (VAh) 2.10 Management Function 2.10.1 Control Performance Control mode Local or remote Response time of local control ≤1s Response time of remote control ≤3s 2.10.2 Clock Performance Real time clock accuracy ≤1s/day Accuracy of GPS synchronization ≤1ms External time synchronization IRIG-B (200-98), PPS, IEEE1588 or SNTP protocol 2.10.3 Fault and Disturbance Recording Duration & Recording position Sampling rate Settable pre-disturbance, post-disturbance and maximum recorded duration Up to 9.6kHz 2.10.4 Binary Input Signal Resolution of binary input signal ≤1ms Binary input mode Potential-free contact PCS-9613S Differential Relay 2-12 Date: 2020-09-02 2 Technical Data 2.11 Protective Functions 2.11.1 Fault Detector (FD) 2.11.1.1 DPFC Current Element 2 ≤2.5%×Setting or 0.02In, whichever is greater Current setting accuracy 2.11.1.2 Residual Current Element ≤2.5%×Setting or 0.02In, whichever is greater Current setting accuracy 2.11.2 Current Differential Protection (87L) Current setting accuracy ≤2.5%×Setting or 0.01In, whichever is greater Pickup time ≤30ms (at 2 times current setting) Maximum operating time (at 4 times <30ms (Steady-state current differential element) current setting) Minimum operating time (at 4 times <20ms (Steady-state current differential element) current setting) Dropout time <30ms 2.11.3 Phase Overcurrent Protection (50/51P) Without direction controlled element Pickup current 1.0×Setting Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤25ms (at 2 times current setting) Operating time delay accuracy (Definite-time characteristics) Operating time delay accuracy (Inverse-time characteristics) Dropout time accuracy (Definite-time characteristics) Dropout time accuracy (Inverse-time characteristics) Dropout ratio ≤1%×Setting or 25ms (at 2 times current setting) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30) ≤1%×Setting or 30ms ≤5% of calculated value or 30ms 0.95 PCS-9613S Differential Relay 2-13 Date: 2020-09-02 2 Technical Data With direction controlled element 2 Pickup current 1.0×Setting Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤40ms (at 2 times current setting) Operating time delay accuracy (Definite-time characteristics) Operating time delay accuracy (Inverse-time characteristics) Dropout time accuracy (Definite-time characteristics) Dropout time accuracy (Inverse-time characteristics) ≤1%×Setting or 40ms (at 2 times current setting) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30) ≤1%×Setting or 30ms ≤5% of calculated value or 30ms Dropout ratio 0.95 Phase angel accuracy ≤3° 2.11.4 Earth Fault Protection (50/51G) Without direction controlled element Pickup current 1.0×Setting Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater Pickup time ≤25ms (at 2 times current setting) Operating time delay accuracy (Definite-time characteristics) Operating time delay accuracy (Inverse-time characteristics) Dropout time accuracy (Definite-time characteristics) Dropout time accuracy (Inverse-time characteristics) Dropout ratio ≤1%×Setting or 25ms (at 2 times current setting) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30) ≤1%×Setting or 30ms ≤5% of calculated value or 30ms 0.95 With direction controlled element Pickup current 1.0×Setting Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater PCS-9613S Differential Relay 2-14 Date: 2020-09-02 2 Technical Data Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤40ms (at 2 times current setting) Operating time delay accuracy (Definite-time characteristics) Operating time delay accuracy (Inverse-time characteristics) Dropout time accuracy (Definite-time characteristics) Dropout time accuracy (Inverse-time characteristics) ≤1%×Setting or 40ms (at 2 times current setting) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30) ≤1%×Setting or 30ms ≤5% of calculated value or 30ms Dropout ratio 0.95 Phase angel accuracy ≤3° 2.11.5 Negative-sequence Overcurrent Protection (50/51Q) Without direction controlled element Pickup current 1.0×Setting Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater Pickup time ≤25ms (at 2 times current setting) Operating time delay accuracy (Definite-time characteristics) Operating time delay accuracy (Inverse-time characteristics) Dropout time accuracy (Definite-time characteristics) Dropout time accuracy (Inverse-time characteristics) Dropout ratio ≤1%×Setting or 25ms (at 2 times current setting) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30) ≤1%×Setting or 30ms ≤5% of calculated value or 30ms 0.95 With direction controlled element Pickup current 1.0×Setting Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤40ms (at 2 times current setting) Operating time delay accuracy (Definite-time characteristics) Operating time delay accuracy ≤1%×Setting or 40ms (at 2 times current setting) ≤5% of calculated value + 1% current tolerance or 35ms (1.2≤I/Ip≤30) PCS-9613S Differential Relay 2-15 Date: 2020-09-02 2 2 Technical Data (Inverse-time characteristics) Dropout time accuracy (Definite-time characteristics) Dropout time accuracy (Inverse-time characteristics) 2 ≤1%×Setting or 30ms ≤5% of calculated value or 30ms Dropout ratio 0.95 Phase angel accuracy ≤3° 2.11.6 RMS Overcurrent Protection (50/51R) Pickup current 1.0×Setting Current setting accuracy ≤2.5%×Setting or 0.01In, whichever is greater Pickup time ≤25ms (at 2 times current setting) Operating time delay accuracy ≤1%×Setting or 25ms (at 2 times current setting) Dropout time accuracy ≤1%×Setting or 30ms Dropout ratio 0.95 2.11.7 Broken Conductor Protection (46BC) Pickup current 1.0×Setting Current setting Accuracy ≤1%×Setting or 0.01In, whichever is greater Operating time delay accuracy ≤1%×Setting or 30ms (at 2 times current setting) Dropout ratio 0.97 2.11.8 Phase Overvoltage Protection (59P) Pickup voltage 1.0×Setting Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤35ms (at 1.1 times voltage setting) Operating time delay accuracy (Definite-time characteristics) Operating time (Inverse-time characteristics) accuracy ≤1%×Setting or 35ms (at 1.1 times voltage setting) ≤5% of calculated value + 1% voltage tolerance or 40ms (1.1≤U/Up≤2) Dropout time accuracy ≤1%×Setting or 30ms Dropout ratio Settable 0.93~1.00, default value: 0.98 PCS-9613S Differential Relay 2-16 Date: 2020-09-02 2 Technical Data 2.11.9 Residual Overvoltage Protection (59G) Pickup voltage 1.0×Setting Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤35ms (at 1.1 times voltage setting) Operating time delay accuracy ≤1%×Setting or 35ms (at 1.1 times voltage setting) Dropout time accuracy ≤1%×Setting or 30ms Dropout ratio Settable 0.93~1.00, default value: 0.98 2 2.11.10 Negative-sequence Overvoltage Protection (59Q) Pickup voltage 1.0×Setting Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤35ms (at 1.1 times voltage setting) Operating time delay accuracy ≤1%×Setting or 35ms (at 1.1 times voltage setting) Dropout time accuracy ≤1%×Setting or 30ms Dropout ratio Settable 0.93~1.00, default value: 0.98 2.11.11 Positive-sequence Overvoltage Protection (59Pos) Pickup voltage 1.0×Setting Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤35ms (at 1.1 times voltage setting) Operating time delay accuracy ≤1%×Setting or 35ms (at 1.1 times voltage setting) Dropout time accuracy ≤1%×Setting or 30ms Dropout ratio Settable 0.93~1.00, default value: 0.98 2.11.12 Phase Undervoltage Protection (27P) Pickup voltage 1.0×Setting Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤35ms (at 0.9 times voltage setting) Operating time delay accuracy (Definite-time characteristics) Operating time (Inverse-time characteristics) accuracy ≤1%×Setting or 35ms (at 0.9 times voltage setting) ≤5% of calculated value + 1% voltage tolerance or 50ms (U/Up≤0.9) PCS-9613S Differential Relay 2-17 Date: 2020-09-02 2 Technical Data Dropout time accuracy ≤1%×Setting or 30ms Dropout ratio Settable 1.00~1.20, default value: 1.03 2.11.13 Overfrequency Protection (81O) 2 Pickup frequency 1.0×Setting Frequency setting accuracy ≤ 0.01Hz Pickup time ≤70ms Time delay accuracy ≤1%×Setting+70ms Dropout time accuracy ≤40ms Dropout frequency 1.0×Setting 2.11.14 Underfrequency Protection (81U) Pickup frequency 1.0×Setting Frequency setting accuracy ≤ 0.01Hz Pickup time ≤70ms Time delay accuracy ≤1%×Setting+70ms Dropout time accuracy ≤40ms Dropout frequency 1.0×Setting 2.11.15 Frequency Rate-of-change Protection (81R) Pickup frequency Frequency rate-of-change accuracy 1.0×Setting setting ≤ 0.02Hz Data window 4 cycles Pickup time ≤70ms Time delay accuracy ≤1%×Setting+70ms Dropout time accuracy ≤40ms Dropout frequency 1.0×Setting 2.11.16 Reverse Power Protection (32R) Pickup power 1.0×Setting Power setting accuracy ≤2%×Setting or 0.01pu, whichever is greater PCS-9613S Differential Relay 2-18 Date: 2020-09-02 2 Technical Data Current setting accuracy ≤1%×Setting or 0.01pu, whichever is greater Voltage setting accuracy ≤1%×Setting or 0.1V, whichever is greater Pickup time ≤30ms (at 2 times power setting) Operating time delay accuracy ≤1%×Setting or 30ms (at 2 times power setting) Dropout time accuracy ≤30ms Dropout ratio 0.95 2 2.11.17 Undercurrent Protection (37) Pickup current 1.0×Setting Current setting Accuracy ≤1%×Setting or 0.01In, whichever is greater Pickup time ≤30ms (at 0.5 times current setting) Operating time delay accuracy ≤1%×Setting or 30ms (at 0.5 times current setting) Drop-out time accuracy ≤30ms Dropout ratio 1.1 2.11.18 Breaker Failure Protection (50BF) Pickup current 1.0×Setting Current setting Accuracy ≤1%×Setting or 0.01In, whichever is greater Operating time delay accuracy ≤1%×Setting or 20ms (at 2 times current setting) Pickup time ≤20ms Dropout time <20ms Dropout ratio 1 2.11.19 Switch-on-to-Fault Protection (SOTF) Pickup current 1.0×Setting Current setting accuracy ≤1%×Setting or 0.01In, whichever is greater Voltage setting accuracy ≤1%×Setting or 0.01V, whichever is greater Pickup time accuracy ≤25ms (at 2 times current setting) Operating time delay accuracy ≤1%×Setting or 35ms (at 2 times current setting) Drop-out time ≤30ms PCS-9613S Differential Relay 2-19 Date: 2020-09-02 2 Technical Data Drop-out ratio 0.95 2.11.20 Thermal Overload Protection (49) ≤2.5% of operating time or 30ms, whichever is greater (for current Operating time 2 between 1.2 and 20 multiples of pickup) ≤30ms Reset time 2.11.21 Auto-reclosing (79) Phase angel accuracy (synchronism check) Voltage setting accuracy (synchronism check) Frequency setting accuracy (synchronism check) Time delay accuracy (synchronism check) ≤2° ≤1%×Setting or 0.1V, whichever is greater 0.01Hz ≤1%×Setting+20ms Time delay accuracy (Reclaim) ≤1%×Setting+20ms Time delay accuracy (Reclosing) ≤1%×Setting+20ms 2.11.22 Transient Overreach Accuracy for all high-speed protection ≤2% 2.11.23 Fault Locator Accuracy for multi-phase faults with < ±2.5% single end feed Tolerance will be higher in case of single-phase fault with high ground resistance. 2.12 Communication Functions 2.12.1 GOOSE Receiving Control Block (RCB) Max. 64 (Typical configuration: 50×FCD+200×BOOL+16×FLOAT) Sending Control Block (SCB) Max. 16 (Typical configuration: 100×BOOL) Receiving route delay Max. 2ms Sending route delay Max. 3ms The capacity of GOOSE receiving and sending is determined by the number of configured boards and control & protection functions. PCS-9613S Differential Relay 2-20 Date: 2020-09-02 2 Technical Data 2.12.2 SV Receiving Control Block (RCB) Max. 12 Receiving route delay Max. 2ms The capacity of SV receiving is determined by the number of configured boards and control & protection functions. PCS-9613S Differential Relay 2-21 Date: 2020-09-02 2 2 Technical Data 2 PCS-9613S Differential Relay 2-22 Date: 2020-09-02 3 Protection Functions 3 Protection Functions Table of Contents 3.1 Three-phase Current Element (TCUR3P) ....................................................... 3-1 3.1.1 Function Description............................................................................................................. 3-1 3.1.2 Function Block Diagram ....................................................................................................... 3-2 3.1.3 I/O Signals ............................................................................................................................ 3-2 3.1.4 Settings................................................................................................................................. 3-3 3.2 Three-phase Voltage Element (TVOL3P)........................................................ 3-3 3.2.1 Function Description............................................................................................................. 3-3 3.2.2 Function Block Diagram ....................................................................................................... 3-4 3.2.3 I/O Signals ............................................................................................................................ 3-4 3.2.4 Settings ................................................................................................................................. 3-5 3.3 One-phase Current Element (TCUR1P).......................................................... 3-5 3.3.1 Function Description............................................................................................................. 3-5 3.3.2 Function Block Diagram ....................................................................................................... 3-5 3.3.3 I/O Signals ............................................................................................................................ 3-6 3.3.4 Settings ................................................................................................................................. 3-6 3.4 One-phase Voltage Element (TVOL1P) .......................................................... 3-6 3.4.1 Function Description............................................................................................................. 3-6 3.4.2 Function Block Diagram ....................................................................................................... 3-7 3.4.3 I/O Signals ............................................................................................................................ 3-7 3.4.4 Settings ................................................................................................................................. 3-7 3.5 Fault Detector (FD) .......................................................................................... 3-7 3.5.1 Function Description............................................................................................................. 3-7 3.5.2 Function Block Diagram ..................................................................................................... 3-10 3.5.3 I/O Signals .......................................................................................................................... 3-10 3.5.4 Logic ................................................................................................................................... 3-10 3.5.5 Settings ............................................................................................................................... 3-11 PCS-9613S Differential Relay 3-a Date: 2020-09-02 3 3 Protection Functions 3.6 Optical Pilot Channel (FO) .............................................................................3-11 3.6.1 Function Description........................................................................................................... 3-11 3.6.2 Function Block Diagram ..................................................................................................... 3-16 3.6.3 I/O Signals .......................................................................................................................... 3-16 3.6.4 Logic ................................................................................................................................... 3-17 3.6.5 Settings ............................................................................................................................... 3-17 3.7 Current Differential Protection (87L) ............................................................ 3-18 3 3.7.1 Functions Description ......................................................................................................... 3-18 3.7.2 Function Block Diagram ..................................................................................................... 3-37 3.7.3 I/O Signals .......................................................................................................................... 3-38 3.7.4 Settings ............................................................................................................................... 3-38 3.8 Phase Overcurrent Protection (50/51P) ....................................................... 3-39 3.8.1 Function Description........................................................................................................... 3-39 3.8.2 Function Block Diagram ..................................................................................................... 3-51 3.8.3 I/O Signal ............................................................................................................................ 3-52 3.8.4 Logic ................................................................................................................................... 3-53 3.8.5 Settings ............................................................................................................................... 3-53 3.9 Earth Fault Overcurrent Protection (50/51G) ............................................... 3-69 3.9.1 Function Description........................................................................................................... 3-69 3.9.2 Function Block Diagram ..................................................................................................... 3-78 3.9.3 I/O Signal ............................................................................................................................ 3-78 3.9.4 Logic ................................................................................................................................... 3-79 3.9.5 Settings ............................................................................................................................... 3-79 3.10 Negative-sequence Overcurrent Protection (50/51Q) ............................... 3-95 3.10.1 Function Description......................................................................................................... 3-95 3.10.2 Function Block Diagram ................................................................................................. 3-104 3.10.3 I/O Signal ........................................................................................................................ 3-104 3.10.4 Logic ............................................................................................................................... 3-105 3.10.5 Settings........................................................................................................................... 3-105 3.11 RMS Overcurrent Protection (50/51R) .......................................................3-110 PCS-9613S Differential Relay 3-b Date: 2020-09-02 3 Protection Functions 3.11.1 Function Description ....................................................................................................... 3-110 3.11.2 Function Block Diagram ................................................................................................. 3-117 3.11.3 I/O Signal ........................................................................................................................ 3-117 3.11.4 Logic ............................................................................................................................... 3-118 3.11.5 Settings ........................................................................................................................... 3-118 3.12 Broken Conductor Protection (46BC) ...................................................... 3-122 3.12.1 Function Description....................................................................................................... 3-122 3.12.2 Function Block Diagram ................................................................................................. 3-123 3.12.3 I/O Signals ...................................................................................................................... 3-123 3.12.4 Logic ............................................................................................................................... 3-124 3.12.5 Settings........................................................................................................................... 3-124 3.13 Phase Overvoltage Protection (59P) ........................................................ 3-124 3.13.1 Function Description....................................................................................................... 3-125 3.13.2 Function Block Diagram ................................................................................................. 3-129 3.13.3 I/O Signal ........................................................................................................................ 3-130 3.13.4 Logic ............................................................................................................................... 3-131 3.13.5 Settings........................................................................................................................... 3-131 3.14 Residual Overvoltage Protection (59G) ................................................... 3-135 3.14.1 Function Description....................................................................................................... 3-135 3.14.2 Function Block Diagram ................................................................................................. 3-137 3.14.3 I/O Signal ........................................................................................................................ 3-137 3.14.4 Logic ............................................................................................................................... 3-138 3.14.5 Settings........................................................................................................................... 3-138 3.15 Negative-sequence Overvoltage Protection (59Q).................................. 3-139 3.15.1 Function Description....................................................................................................... 3-139 3.15.2 Function Block Diagram ................................................................................................. 3-142 3.15.3 I/O Signals ...................................................................................................................... 3-142 3.15.4 Logic ............................................................................................................................... 3-143 3.15.5 Settings........................................................................................................................... 3-143 3.16 Positive-sequence Overvoltage Protection (59Pos) ............................... 3-144 PCS-9613S Differential Relay 3-c Date: 2020-09-02 3 3 Protection Functions 3.16.1 Function Description....................................................................................................... 3-144 3.16.2 Function Block Diagram ................................................................................................. 3-147 3.16.3 I/O Signals ...................................................................................................................... 3-147 3.16.4 Logic ............................................................................................................................... 3-147 3.16.5 Settings........................................................................................................................... 3-147 3.17 Phase Undervoltage Protection (27P) ...................................................... 3-148 3.17.1 Function Description....................................................................................................... 3-148 3 3.17.2 Function Block Diagram ................................................................................................. 3-154 3.17.3 I/O Signal ........................................................................................................................ 3-155 3.17.4 Logic ............................................................................................................................... 3-156 3.17.5 Settings........................................................................................................................... 3-157 3.18 Overfrequency Protection (81O)............................................................... 3-161 3.18.1 Function Description....................................................................................................... 3-161 3.18.2 Function Block Diagram ................................................................................................. 3-163 3.18.3 I/O Signals ...................................................................................................................... 3-163 3.18.4 Logic ............................................................................................................................... 3-164 3.18.5 Settings........................................................................................................................... 3-164 3.19 Underfrequency Protection (81U)............................................................. 3-165 3.19.1 Function Description....................................................................................................... 3-165 3.19.2 Function Block Diagram ................................................................................................. 3-167 3.19.3 I/O Signals ...................................................................................................................... 3-167 3.19.4 Logic ............................................................................................................................... 3-168 3.19.5 Settings........................................................................................................................... 3-168 3.20 Frequency Rate-of-change Protection (81R) ........................................... 3-169 3.20.1 Function Description....................................................................................................... 3-169 3.20.2 Function Block Diagram ................................................................................................. 3-171 3.20.3 I/O Signals ...................................................................................................................... 3-171 3.20.4 Logic ............................................................................................................................... 3-172 3.20.5 Settings........................................................................................................................... 3-172 3.21 Reverse Power Protection (32R) .............................................................. 3-173 PCS-9613S Differential Relay 3-d Date: 2020-09-02 3 Protection Functions 3.21.1 Function Description....................................................................................................... 3-173 3.21.2 Function Block Diagram ................................................................................................. 3-176 3.21.3 I/O Signals ...................................................................................................................... 3-176 3.21.4 Logic ............................................................................................................................... 3-176 3.21.5 Settings........................................................................................................................... 3-177 3.22 Undercurrent Protection (37) .................................................................... 3-177 3.22.1 Function Description....................................................................................................... 3-178 3.22.2 Function Block Diagram ................................................................................................. 3-180 3.22.3 I/O Signals ...................................................................................................................... 3-181 3.22.4 Logic ............................................................................................................................... 3-182 3.22.5 Settings........................................................................................................................... 3-182 3.23 Breaker Failure Protection (50BF) ............................................................ 3-183 3.23.1 Function Description....................................................................................................... 3-183 3.23.2 Function Block Diagram ................................................................................................. 3-185 3.23.3 I/O Signals ...................................................................................................................... 3-185 3.23.4 Logic ............................................................................................................................... 3-186 3.23.5 Settings........................................................................................................................... 3-187 3.24 Switch-on-to-Fault Protection (SOTF) ...................................................... 3-188 3.24.1 Function Description....................................................................................................... 3-188 3.24.2 Function Block Diagram ................................................................................................. 3-189 3.24.3 I/O Signals ...................................................................................................................... 3-189 3.24.4 Logic ............................................................................................................................... 3-190 3.24.5 Settings........................................................................................................................... 3-192 3.25 Thermal Overload Protection (49) ............................................................ 3-193 3.25.1 Function Description....................................................................................................... 3-193 3.25.2 Function Block Diagram ................................................................................................. 3-197 3.25.3 I/O Signals ...................................................................................................................... 3-197 3.25.4 Logic ............................................................................................................................... 3-198 3.25.5 Settings........................................................................................................................... 3-198 3.26 Transfer Trip (TT) ....................................................................................... 3-199 PCS-9613S Differential Relay 3-e Date: 2020-09-02 3 3 Protection Functions 3.26.1 Function Description....................................................................................................... 3-199 3.26.2 Function Block Diagram ................................................................................................. 3-199 3.26.3 I/O Signals ...................................................................................................................... 3-199 3.26.4 Logic ............................................................................................................................... 3-200 3.26.5 Settings........................................................................................................................... 3-200 3.27 Automatic Reclosure (79).......................................................................... 3-201 3.27.1 Function Description....................................................................................................... 3-201 3 3.27.2 Function Block Diagram ................................................................................................. 3-210 3.27.3 I/O Signals ...................................................................................................................... 3-210 3.27.4 Settings........................................................................................................................... 3-211 3.28 VT Circuit Supervision (VTS) .................................................................... 3-213 3.28.1 General Application ........................................................................................................ 3-213 3.28.2 Function Description....................................................................................................... 3-214 3.28.3 Function Block ................................................................................................................ 3-214 3.28.4 I/O Signals ...................................................................................................................... 3-214 3.28.5 Logic ............................................................................................................................... 3-215 3.28.6 Settings........................................................................................................................... 3-216 3.29 CT Circuit Supervision (CTS).................................................................... 3-216 3.29.1 Function Description....................................................................................................... 3-216 3.29.2 Function Block Diagram ................................................................................................. 3-217 3.29.3 I/O Signals ...................................................................................................................... 3-217 3.29.4 Logics ............................................................................................................................. 3-217 3.29.5 Settings........................................................................................................................... 3-218 3.30 Fault Location (FL) .................................................................................... 3-218 3.30.1 Function Description....................................................................................................... 3-218 3.30.2 Function Block Diagram ................................................................................................. 3-220 3.30.3 I/O Signals ...................................................................................................................... 3-221 3.30.4 Settings........................................................................................................................... 3-221 List of Figures PCS-9613S Differential Relay 3-f Date: 2020-09-02 3 Protection Functions Figure 3.5-1 Logic diagram of fault detector .......................................................................... 3-10 Figure 3.6-1 Direct optical link up to 2km with 850nm .......................................................... 3-12 Figure 3.6-2 Direct optical link up to 60km with 1310nm ...................................................... 3-12 Figure 3.6-3 Connect to a communication network via communication convertor........... 3-12 Figure 3.6-4 Connect to a communication network via MUX-64 .......................................... 3-13 Figure 3.6-5 Connect to a communication network via MUX-2M ......................................... 3-13 Figure 3.6-6 Schematic diagram of communication channel time ...................................... 3-15 Figure 3.6-7 Logic of receiving signal i ................................................................................... 3-17 Figure 3.6-8 Logic of sending signal i ..................................................................................... 3-17 Figure 3.6-9 Logic of channel alarm ........................................................................................ 3-17 Figure 3.7-1 Logic of enabling current differential protection ............................................. 3-19 Figure 3.7-2 Inconsistent enabling status of current differential protection ...................... 3-20 Figure 3.7-3 Common condition of current differential protection ...................................... 3-20 Figure 3.7-4 Operating characteristics of steady-state current differential element ......... 3-21 Figure 3.7-5 Operating characteristics of steady-state current differential element ......... 3-22 Figure 3.7-6 Logic of steady-state current differential element (stage 1) ........................... 3-23 Figure 3.7-7 Logic of steady-state current differential element (stage 2) ........................... 3-24 Figure 3.7-8 Connection mode ................................................................................................. 3-25 Figure 3.7-9 Schematic diagram of communication channel time ...................................... 3-27 Figure 3.7-10 Relation between CT saturation differential current and restraint current . 3-28 Figure 3.7-11 Logic of differential current supervision ......................................................... 3-29 Figure 3.7-12 CT circuit failure blocking current differential protection ............................. 3-30 Figure 3.7-13 Weak infeed logic of current differential protection ...................................... 3-31 Figure 3.7-14 Sending permissive signal of current differential protection ....................... 3-32 Figure 3.7-15 Logic of differential inter-trip element ............................................................. 3-34 Figure 3.7-16 CT schematic ...................................................................................................... 3-35 Figure 3.7-17 Equivalent circuit ............................................................................................... 3-35 Figure 3.7-18 Core's Magnetizing curve ................................................................................. 3-36 Figure 3.8-1 The enabling and blocking logic of phase overcurrent protection ................ 3-40 Figure 3.8-2 The fault detector element of phase overcurrent protection .......................... 3-40 PCS-9613S Differential Relay 3-g Date: 2020-09-02 3 3 Protection Functions Figure 3.8-3 The voltage control element of phase overcurrent protection ....................... 3-41 Figure 3.8-4 The direction element operation characteristics when phase A voltage is polarized ..................................................................................................................................... 3-42 Figure 3.8-5 Logic diagram of forward and reverse direction element of phase overcurrent protection ................................................................................................................................... 3-45 Figure 3.8-6 Logic diagram of harmonic control element of phase overcurrent protection3-46 Figure 3.8-7 Definite-time operation characteristic curve of phase overcurrent protection3-47 3 Figure 3.8-8 Inverse-time operation characteristic curve of phase overcurrent protection3-48 Figure 3.8-9 Definite-time dropout characteristic of phase overcurrent protection .......... 3-49 Figure 3.8-10 Inverse-time dropout characteristic curve of phase overcurrent protection3-50 Figure 3.8-11 Inverse-time dropout characteristic of phase overcurrent protection ......... 3-51 Figure 3.8-12 Logic diagram of phase overcurrent protection ............................................ 3-53 Figure 3.9-1 The enabling and blocking logic of earth fault overcurrent protection ......... 3-70 Figure 3.9-2 Logic diagram of the fault detector element of earth fault overcurrent protection ................................................................................................................................... 3-70 Figure 3.9-3 The direction element operation characteristics when zero-sequence voltage is polarized ................................................................................................................................. 3-71 Figure 3.9-4 Logic diagram of forward and reverse direction element of earth fault overcurrent protection .............................................................................................................. 3-72 Figure 3.9-5 Logic diagram of harmonic control element of earth fault overcurrent protection ................................................................................................................................... 3-73 Figure 3.9-6 Definite-time operation characteristic curve of earth fault overcurrent protection ................................................................................................................................... 3-74 Figure 3.9-7 Inverse-time operation characteristic curve of earth fault overcurrent protection ................................................................................................................................... 3-75 Figure 3.9-8 Definite-time dropout characteristic of earth fault overcurrent protection ... 3-76 Figure 3.9-9 Inverse-time dropout characteristic curve of earth fault overcurrent protection3-77 Figure 3.9-10 Inverse-time dropout characteristic of earth fault overcurrent protection . 3-78 Figure 3.9-11 Logic diagram of earth fault overcurrent protection...................................... 3-79 Figure 3.10-1 The enabling and blocking logic of negative-sequence overcurrent protection ..................................................................................................................................................... 3-95 Figure 3.10-2 Logic diagram of the fault detector element of negative-sequence overcurrent protection ................................................................................................................................... 3-96 PCS-9613S Differential Relay 3-h Date: 2020-09-02 3 Protection Functions Figure 3.10-3 The direction element operation characteristics of negative-sequence overcurrent protection .............................................................................................................. 3-96 Figure 3.10-4 Logic diagram of forward and reverse direction element of negative-sequence overcurrent protection ............................................................................ 3-98 Figure 3.10-5 Definite-time operation characteristic curve of negative-sequence overcurrent protection ............................................................................................................ 3-100 Figure 3.10-6 Inverse-time operation characteristic curve of negative-sequence overcurrent protection ............................................................................................................ 3-101 Figure 3.10-7 Definite-time dropout characteristic of negative-sequence overcurrent protection ................................................................................................................................. 3-102 Figure 3.10-8 Inverse-time dropout characteristic curve of negative-sequence overcurrent protection ................................................................................................................................. 3-103 Figure 3.10-9 Inverse-time dropout characteristic of negative-sequence overcurrent protection ................................................................................................................................. 3-104 Figure 3.10-10 Logic diagram of negative-sequence overcurrent protection .................. 3-105 Figure 3.11-1 The enabling and blocking logic of RMS overcurrent protection................3-111 Figure 3.11-2 Logic diagram of the fault detector element of RMS overcurrent protection3-111 Figure 3.8-3 Definite-time operation characteristic curve of RMS overcurrent protection3-112 Figure 3.8-4 Inverse-time operation characteristic curve of RMS overcurrent protection3-113 Figure 3.8-5 Definite-time dropout characteristic of RMS overcurrent protection .......... 3-114 Figure 3.8-6 Inverse-time dropout characteristic curve of RMS overcurrent protection 3-116 Figure 3.8-7 Inverse-time dropout characteristic of RMS overcurrent protection ........... 3-116 Figure 3.11-5 Logic diagram of RMS overcurrent protection ............................................. 3-118 Figure 3.9-1 Logic of broken conductor protection ............................................................ 3-124 Figure 3.12-1 The enabling and blocking logic of phase overvoltage protection ............ 3-125 Figure 3.12-2 Logic diagram of the fault detector element of phase overvoltage protection3-126 Figure 3.12-3 Definite-time operation characteristic curve of phase overvoltage protection3-127 Figure 3.12-4 Inverse-time operation characteristic curve of phase overvoltage protection3-128 Figure 3.12-5 Definite-time dropout characteristic of phase overvoltage protection...... 3-129 Figure 3.12-6 Logic diagram of phase overvoltage protection .......................................... 3-131 Figure 3.13-1 The enabling and blocking logic of residual overvoltage protection ........ 3-135 Figure 3.13-2 Logic diagram of the fault detector element of residual overvoltage PCS-9613S Differential Relay 3-i Date: 2020-09-02 3 3 Protection Functions protection ................................................................................................................................. 3-136 Figure 3.13-3 Definite-time operation characteristic curve of residual overvoltage protection ................................................................................................................................. 3-136 Figure 3.13-4 Definite-time dropout characteristic of residual overvoltage protection .. 3-137 Figure 3.13-5 Logic diagram of residual overvoltage protection ....................................... 3-138 Figure 3.14-1 Logic diagram of enabling/disabling negative-sequence overvoltage protection ................................................................................................................................. 3-140 3 Figure 3.14-2 Logic diagram of the fault detector of negative-sequence overvoltage protection ................................................................................................................................. 3-140 Figure 3.14-3 Operation characteristic curve of negative-sequence overvoltage protection3-141 Figure 3.14-4 Definite-time dropout characteristic of negative-sequence overvoltage protection ................................................................................................................................. 3-142 Figure 3.14-5 Logic diagram of negative-sequence overvoltage protection .................... 3-143 Figure 3.15-1 Logic diagram of enabling/disabling positive-sequence overvoltage protection ................................................................................................................................. 3-144 Figure 3.15-2 Logic diagram of the fault detector of positive-sequence overvoltage protection ................................................................................................................................. 3-145 Figure 3.15-3 Operation characteristic curve of positive-sequence overvoltage protection3-145 Figure 3.15-4 Definite-time dropout characteristic of positive-sequence overvoltage protection ................................................................................................................................. 3-146 Figure 3.15-5 Logic diagram of positive-sequence overvoltage protection ..................... 3-147 Figure 3.16-1 The enabling and blocking logic of phase undervoltage protection ......... 3-149 Figure 3.16-2 Logic diagram of the fault detector element of phase undervoltage protection ................................................................................................................................................... 3-151 Figure 3.16-3 Definite-time operation characteristic curve of phase undervoltage protection ................................................................................................................................................... 3-152 Figure 3.16-4 Inverse-time operation characteristic curve of phase undervoltage protection ................................................................................................................................................... 3-153 Figure 3.16-5 Definite-time dropout characteristic of undervoltage protection ............... 3-154 Figure 3.16-6 Logic diagram of phase undervoltage protection ........................................ 3-156 Figure 3.17-1 Logic diagram of enabling/disabling overfrequency protection ................ 3-162 Figure 3.17-2 Logic diagram of the fault detector of overfrequency protection .............. 3-162 Figure 3.17-3 Operation characteristic curve of overfrequency protection ..................... 3-163 PCS-9613S Differential Relay 3-j Date: 2020-09-02 3 Protection Functions Figure 3.17-4 Logic diagram of overfrequency protection ................................................. 3-164 Figure 3.18-1 Logic diagram of enabling/disabling underfrequency protection .............. 3-166 Figure 3.18-2 Logic diagram of the fault detector of underfrequency protection ............ 3-166 Figure 3.18-3 Operation characteristic curve of underfrequency protection ................... 3-167 Figure 3.18-4 Logic diagram of underfrequency protection ............................................... 3-168 Figure 3.19-1 Logic diagram of enabling/disabling frequency rate-of-change protection3-170 Figure 3.19-2 Logic diagram of the fault detector of frequency rate-of-change protection3-170 Figure 3.19-3 Operation characteristic curve of frequency rate-of-change protection ... 3-171 Figure 3.19-4 Logic diagram of frequency rate-of-change protection............................... 3-172 Figure 3.20-1 Logic diagram of enabling/disabling reverse power protection ................ 3-174 Figure 3.20-2 Logic diagram of the fault detector of reverse power protection .............. 3-174 Figure 3.20-3 Operation characteristic curve of reverse power protection ...................... 3-175 Figure 3.20-4 Logic diagram of reverse power protection.................................................. 3-176 Figure 3.21-1 Logic diagram of enabling/disabling undercurrent protection................... 3-178 Figure 3.21-2 Logic diagram of the fault detector of undercurrent protection ................ 3-179 Figure 3.21-3 Operation characteristic curve of undercurrent protection ........................ 3-180 Figure 3.21-4 Logic diagram of undercurrent protection.................................................... 3-182 Figure 3.22-1 Logic of enabling breaker failure protection ................................................ 3-186 Figure 3.22-2 Logic of breaker failure initiating signal abnormality .................................. 3-186 Figure 3.22-3 Logic of breaker failure protection ................................................................ 3-186 Figure 3.23-1 The enabling and blocking logic of SOTF protection .................................. 3-188 Figure 3.23-2 Logic of auto-reclosing signal........................................................................ 3-190 Figure 3.23-3 Logic of manual closing signal ...................................................................... 3-190 Figure 3.23-4 Logic of phase overcurrent SOTF protection ............................................... 3-191 Figure 3.23-5 Logic of earth fault overcurrent SOTF protection ........................................ 3-191 Figure 3.25-1 The operation characteristic curve of thermal overload protection .......... 3-194 Figure 3.25-2 Logic diagram of enabling/disabling thermal overload protection ............ 3-196 Figure 3.25-3 Logic diagram of the fault detector of thermal overload protection (method 1) ................................................................................................................................................... 3-196 Figure 3.25-4 Logic diagram of thermal overload protection (method 1) ......................... 3-198 PCS-9613S Differential Relay 3-k Date: 2020-09-02 3 3 Protection Functions Figure 3.24-1 Logic of transfer trip ........................................................................................ 3-200 Figure 3.25-1 Logic of enabling AR ....................................................................................... 3-202 Figure 3.30-2 Logic of synchronism check mode selection for AR................................... 3-202 Figure 3.25-2 Logic of AR block............................................................................................. 3-203 Figure 3.25-3 Logic of AR ready ............................................................................................ 3-204 Figure 3.25-4 Tripping initiating AR ....................................................................................... 3-205 Figure 3.25-5 CB state initiating AR ...................................................................................... 3-205 3 Figure 3.25-6 One-shot AR ..................................................................................................... 3-205 Figure 3.25-7 Reclosing output logic .................................................................................... 3-206 Figure 3.25-8 Reclosing failure and success ....................................................................... 3-207 Figure 3.25-9 Transient fault................................................................................................... 3-208 Figure 3.25-10 Permanent fault ([79.Num]=2) ....................................................................... 3-209 Figure 3.30-1 VT circuit supervision logic diagram ............................................................. 3-215 Figure 3.27-1 Logic of CT circuit failure................................................................................ 3-217 Figure 3.28-1 Equivalent circuit of single-phase fault with fault resistance..................... 3-219 List of Tables Table 3.1-1 Input/Output signals of three-phase current element ......................................... 3-2 Table 3.1-2 Settings of three-phase current element............................................................... 3-3 Table 3.2-1 Input/Output signals of three-phase voltage element ......................................... 3-4 Table 3.2-2 Settings of three-phase voltage element .............................................................. 3-5 Table 3.3-1 Input/Output signals of one-phase current element ............................................ 3-6 Table 3.3-2 Settings of one-phase current element ................................................................. 3-6 Table 3.4-1 Input/Output signals of one-phase voltage element ............................................ 3-7 Table 3.4-2 Settings of one-phase voltage element ................................................................. 3-7 Table 3.5-1 Output signals of fault detector ........................................................................... 3-10 Table 3.5-2 Settings of fault detector ...................................................................................... 3-11 Table 3.6-1 Input signals of optical pilot channel .................................................................. 3-16 Table 3.6-2 Settings of optical pilot channel .......................................................................... 3-17 Table 3.7-1 Protection transmission data format for 64kbit/s .............................................. 3-25 PCS-9613S Differential Relay 3-l Date: 2020-09-02 3 Protection Functions Table 3.7-2 Protection transmission data format for 2Mbit/s ............................................... 3-26 Table 3.7-3 Input/Output signals of current differential protection ..................................... 3-38 Table 3.7-4 Settings of current differential protection .......................................................... 3-38 Table 3.8-1 Input/output signals of phase overcurrent protection ...................................... 3-52 Table 3.8-2 Settings of phase overcurrent protection ........................................................... 3-53 Table 3.9-1 Input/output signals of earth fault overcurrent protection ............................... 3-78 Table 3.9-2 Settings of earth fault overcurrent protection .................................................... 3-79 Table 3.10-1 Input/output signals of negative-sequence overcurrent protection ............ 3-104 Table 3.10-2 Settings of negative-sequence overcurrent protection................................. 3-105 Table 3.11-1 Input/output signals of RMS overcurrent protection ..................................... 3-117 Table 3.11-2 Settings of RMS overcurrent protection.......................................................... 3-118 Table 3.9-1 Input/Output signals of broken conductor protection..................................... 3-123 Table 3.9-2 Settings of broken conductor protection .......................................................... 3-124 Table 3.12-1 Input/output signals of phase overvoltage protection .................................. 3-130 Table 3.12-2 Settings of phase overvoltage protection ....................................................... 3-132 Table 3.13-1 Input/output signals of residual overvoltage protection ............................... 3-137 Table 3.13-2 Settings of residual overvoltage protection ................................................... 3-138 Table 3.14-1 Input/output signals of negative-sequence overvoltage protection ............ 3-142 Table 3.14-2 Settings of negative-sequence overvoltage protection ................................ 3-143 Table 3.15-1 Input/output signals of positive-sequence overvoltage protection ............. 3-147 Table 3.15-2 Settings of positive-sequence overvoltage protection ................................. 3-148 Table 3.16-1 Input/output signals of phase undervoltage protection ................................ 3-155 Table 3.16-2 Settings of phase undervoltage protection .................................................... 3-157 Table 3.17-1 Input/output signals of overfrequency protection ......................................... 3-163 Table 3.17-2 Settings of overfrequency protection.............................................................. 3-164 Table 3.18-1 Input/output signals of underfrequency protection ....................................... 3-167 Table 3.18-2 Settings of underfrequency protection ........................................................... 3-168 Table 3.19-1 Input/output signals of frequency rate-of-change protection ...................... 3-171 Table 3.19-2 Settings of frequency rate-of-change protection ........................................... 3-172 Table 3.20-1 Input/output signals of reverse power protection.......................................... 3-176 PCS-9613S Differential Relay 3-m Date: 2020-09-02 3 3 Protection Functions Table 3.20-2 Settings of reverse power protection .............................................................. 3-177 Table 3.21-1 Input/output signals of undercurrent protection............................................ 3-181 Table 3.21-2 Settings of undercurrent protection ................................................................ 3-182 Table 3.22-1 Input/output signals of breaker failure protection ......................................... 3-185 Table 3.22-2 Settings of breaker failure protection.............................................................. 3-187 Table 3.23-1 Input/output signals of SOTF protection ........................................................ 3-189 Table 3.23-2 Settings of SOTF protection ............................................................................. 3-192 3 Table 3.25-1 Input/output signals of thermal overload protection ..................................... 3-197 Table 3.25-2 Settings of thermal overload protection ......................................................... 3-198 Table 3.24-1 Input/Output signals of transfer trip ................................................................ 3-199 Table 3.24-2 Settings of transfer trip ..................................................................................... 3-200 Table 3.25-1 Input/Output signals of AR ............................................................................... 3-210 Table 3.25-2 Settings of AR .................................................................................................... 3-211 Table 3.30-1 Input/output signals of VT circuit supervision ............................................... 3-214 Table 3.30-2 Settings of VT circuit supervision ................................................................... 3-216 Table 3.27-1 Input/output signals of CT circuit supervision ............................................... 3-217 Table 3.27-2 Settings of CT circuit supervision ................................................................... 3-218 Table 3.28-1 Output signals of fault location ........................................................................ 3-221 Table 3.28-2 Settings of fault location ................................................................................... 3-221 PCS-9613S Differential Relay 3-n Date: 2020-09-02 3 Protection Functions 3.1 Three-phase Current Element (TCUR3P) Three-phase current element is responsible for pre-processing three phase currents and calculating sequence components, amplitudes and phase angles of three phase currents, etc. All calculated information of three-phase current element is used for protection logic calculation. Three-phase current element is a basic element, for a specific application, the displayed signals and settings may have different prefixes in front of them. 3.1.1 Function Description Three-phase current element has following functions: 1. Pre-process three phase currents 2. Calculate information related to three-phase current When any phase current is greater than 0.04In, the input current signals are valid and the valid signal will be outputted for programmable logic application. CT circuit supervision of three-phase current is carried out by the CTS element, which can refer to Section 3.29 for details. PCS-9613S Differential Relay 3-1 Date: 2020-09-02 3 3 Protection Functions 3.1.2 Function Block Diagram TCUR3P in_ia I3P in_ib Ia_Sec in_ic Ib_Sec Ic_Sec I1_Sec 3 I2_Sec 3I0_Cal_Sec Ang(Ia-Ib) Ang(Ib-Ic) Ang(Ic-Ia) Ang(Ia) Ang(Ib) Ang(Ic) Ang(3I0_Cal) Alm_CTS Flg_OnLoad 3.1.3 I/O Signals Table 3.1-1 Input/Output signals of three-phase current element No. Input Signal Description 1 in_ia Sampled value of phase-A current 2 in_ib Sampled value of phase-B current 3 in_ic Sampled value of phase-C current No. Output Signal Description 1 I3P A current data set 2 Ia_Sec Amplitude of secondary phase-A current 3 Ib_Sec Amplitude of secondary phase-B current 4 Ic_Sec Amplitude of secondary phase-C current 5 I1_Sec Amplitude of secondary positive-sequence current 6 I2_Sec Amplitude of secondary negative-sequence current 7 3I0_Cal_Sec Amplitude of calculated secondary residual current 8 Ang(Ia-Ib) Phase angle between phase A and phase B currents 9 Ang(Ib-Ic) Phase angle between phase B and phase C currents PCS-9613S Differential Relay 3-2 Date: 2020-09-02 3 Protection Functions 10 Ang(Ic-Ia) Phase angle between phase C and phase A currents 11 Ang(Ia) Phase angle of phase-A current 12 Ang(Ib) Phase angle of phase-B current 13 Ang(Ic) Phase angle of phase-C current 14 Ang(3I0_Cal) Phase angle of calculated residual current 15 Alm_CTS CT secondary circuit failure 16 Flg_OnLoad A flag indicating that the load current is detected 3.1.4 Settings ⚫ Access path: 3 MainMenu Settings Global Settings System Settings Table 3.1-2 Settings of three-phase current element No. Item Range Step Unit Default 1 Prot.I1n 0~9999 1 A 1000 2 Prot.I2n 1 or 5 - A 1 3 Prot.En_RevCT - - Disabled Enabled, Disabled Description Primary current value of the three-phase CT Secondary current value of the three-phase CT Logic setting of enabling/disabling the current polarity of the three-phase CT reversed 3.2 Three-phase Voltage Element (TVOL3P) Three-phase voltage element is responsible for pre-processing three phase voltages and calculating sequence components, amplitudes and phases of three phase voltages, etc. All calculated information of three-phase voltage element is used for the protection logic calculation. 3.2.1 Function Description Three-phase voltage element has following functions: 1. Pre-process three phase voltages 2. Calculate information related to three phase voltages VT circuit failure supervision of three-phase voltage is carried out by the VTS element, which can refer to Section 3.28 for details. PCS-9613S Differential Relay 3-3 Date: 2020-09-02 3 Protection Functions 3.2.2 Function Block Diagram TVOL3P in_ua U3P in_ub Ua_Sec in_uc Ub_Sec BI_En_VT Uc_Sec U1_Sec 3 U2_Sec 3U0_Cal_Sec Ang(Ua-Ub) Ang(Ub-Uc) Ang(Uc-Ua) Ang(Ua) Ang(Ub) Ang(Uc) Ang(3U0_Cal) Alm_VTS 3.2.3 I/O Signals Table 3.2-1 Input/Output signals of three-phase voltage element No. Input signal Description 1 in_ua Sampled value of phase-A voltage 2 in_ub Sampled value of phase-B voltage 3 in_uc Sampled value of phase-C voltage 4 BI_En_VT Input signal of indicating VT in service No. Output signal Description 1 U3P A voltage data set 2 Ua_Sec Amplitude of phase-A secondary voltage 3 Ub_Sec Amplitude of phase-B secondary voltage 4 Uc_Sec Amplitude of phase-C secondary voltage 5 U1_Sec Amplitude of positive-sequence secondary voltage 6 U2_Sec Amplitude of negative-sequence secondary voltage 7 3U0_Cal_Sec Amplitude of calculated residual secondary voltage 8 Ang(Ua-Ub) Phase angle between phase A and phase B voltages 9 Ang(Ub-Uc) Phase angle between phase B and phase C voltages PCS-9613S Differential Relay 3-4 Date: 2020-09-02 3 Protection Functions 10 Ang(Uc-Ua) Phase angle between phase C and phase A voltages 11 Ang(Ua) Phase angle of phase-A voltage 12 Ang(Ub) Phase angle of phase-B voltage 13 Ang(Uc) Phase angle of phase-C voltage 14 Ang(3U0_Cal) Phase angle of calculated residual voltage 15 Alm_VTS VT secondary circuit abnormality 3.2.4 Settings ⚫ Access path: MainMenu Settings Global Settings System Settings 3 Table 3.2-2 Settings of three-phase voltage element No. Item Range Step Unit Default 1 Prot.U1n 1~1100 0.001 kV 10 Rated value of primary voltage of the three-phase VT 2 Prot.U2n 1~120 0.001 V 100 Rated value of secondary voltage of the three-phase VT 3 En_VT - - Enabled Logic setting to put the three-phase VT into service Enabled, Disabled Description 3.3 One-phase Current Element (TCUR1P) One-phase current element is responsible for pre-processing measured one-phase current and calculating the magnitude and the phase angle of the one-phase current, etc. All calculated information of one-phase current element is used for the protection logic calculation. 3.3.1 Function Description One-phase current element has following functions: 1. Pre-process measured one-phase current 2. Calculate information related to the one-phase current 3.3.2 Function Block Diagram TCUR1P in_ip I1P Neu.I Neu.Ang(I) Flg_OnLoad PCS-9613S Differential Relay 3-5 Date: 2020-09-02 3 Protection Functions 3.3.3 I/O Signals Table 3.3-1 Input/Output signals of one-phase current element No. 1 in_ip No. 3 Input signal Description Measured one-phase current (external residual current) Output signal Description 1 I1P A current data set 2 Neu.I Amplitude of external residual secondary current 3 Neu.Ang(I) Phase angle of external residual current 4 Flg_OnLoad A flag indicating there is load current 3.3.4 Settings ⚫ Access path: MainMenu Settings Global Settings System Settings Table 3.3-2 Settings of one-phase current element No. Item Range Step Unit Default 1 Neu.I1n 0~9999 1 A 1000 2 Neu.I2n 1 or 5 - A 1 3 Neu.En_RevCT - - Disabled Enabled, Disabled Description Primary rated current of the external residual current CT Secondary rated current of the external residual current CT Logic setting of enabling/disabling the current polarity of the external residual current CT 3.4 One-phase Voltage Element (TVOL1P) One-phase voltage element is responsible for pre-processing one-phase voltage and calculating the magnitude and the phase angle of the one-phase voltage, etc. All calculated information of one-phase voltage element is used for the protection logic calculation. 3.4.1 Function Description One-phase voltage element has following functions: 1. Pre-process measured one-phase voltage 2. Calculate information related to one-phase voltage PCS-9613S Differential Relay 3-6 Date: 2020-09-02 3 Protection Functions 3.4.2 Function Block Diagram TVOL1P in_up U1P Syn.U BI_En_VT Syn.Ang(U) 3.4.3 I/O Signals 3 Table 3.4-1 Input/Output signals of one-phase voltage element No. Input signal Description 1 in_up Measured one-phase voltage (synchronism voltage) 2 BI_En_VT Input signal of indicating VT in service No. Output signal Description 1 U1P A voltage data set 2 Syn.U Amplitude of the one-phase voltage (secondary value) 3 Syn.Ang(U) Phase angle of the one-phase voltage 3.4.4 Settings ⚫ Access path: MainMenu Settings Global Settings System Settings Table 3.4-2 Settings of one-phase voltage element No. Item Range Step Unit Default 1 Syn.U1n 0~1100 0.001 kV - 2 Syn.U2n 1~200 0.001 V - Description Primary rated voltage of the one-phase VT (synchronism voltage) Secondary rated voltage of the one-phase VT (synchronism voltage) 3.5 Fault Detector (FD) Fault detector is responsible to determine fault appearance on the protected power system. The device will switch to protection calculation after the fault detector picks up. If the fault is within the protected zone, the device will issue tripping command. 3.5.1 Function Description The current amplitude is calculated based on the injected analog quantities. The fault detector continuously detects the change of phase-to-phase power frequency current and the calculated zero-sequence and negative-sequence currents. The fault detector includes: 1. Fault detector based on DPFC current: DPFC current is greater than the setting value PCS-9613S Differential Relay 3-7 Date: 2020-09-02 3 Protection Functions 3 2. Fault detector based on zero-sequence current: Zero-sequence current is greater than the setting value 3. Fault detector based on negative-sequence current: Negative-sequence current is greater than the setting value 4. Fault detector based on weak infeed logic or inter-trip logic of current differential protection: Weak infeed logic or inter-trip logic of current differential protection pickup If any of the above conditions is satisfied, the fault detector will operate to start protection calculation. The fault detector based on DPFC current and the fault detector based on zero-sequence current are always enabled, and fault detector based on negative-sequence current could be enabled or disabled by the setting. Current differential protection is controlled by these fault detector. 3.5.1.1 Fault Detector Based on DPFC Current DPFC phase-to-phase current is obtained by subtracting the phase-to-phase current from that of a cycle before. I(k) is the current sampling point. I(k-24) is the value of the sampling point before a cycle, 24 is the sampling points cycle. 200 100 0 -100 -200 0 20 40 60 Original Current 80 100 120 0 20 40 60 DPFC current 80 100 120 100 50 0 -50 -100 From above figures, it is concluded that DPFC can reflect the sudden change of current at the initial stage of a fault and has a perfect performance of fault detection. It is used to determine whether this pickup condition is met according to Equation 3.5-1. For multi-phase short-circuit fault, DPFC phase-to-phase current has high sensitivity to ensure the pickup of protection device. For usual single-phase earth fault, it also has sufficient sensitivity to pick up except the earth fault with very large fault resistance. Under this condition, DPFC current may be very small and the sensitivity is reduced, however, zero-sequence current is used to PCS-9613S Differential Relay 3-8 Date: 2020-09-02 3 Protection Functions remedy the reduction of the sensitivity. This element adopts adaptive floating threshold varied with the change of load current continuously. The change of load current is small and steady under normal or power swing condition, the adaptive floating threshold with the ΔI Set is higher than the change of current under these conditions and hence maintains the element stability. The criterion is: ΔIΦΦMAX>1.25ΔITh+ΔISet Equation 3.5-1 Where: ΔIΦΦMAX: The maximum half-wave integration value of phase-to-phase current (ΦΦ=AB, BC, CA) ΔISet: The fixed threshold value (i.e. the setting [FD.DPFC.I_Set]) ΔITh: The floating threshold value The coefficient, 1.25, is an empirical value which ensures that the threshold is always higher than the unbalance current of the system. If operation condition is satisfied, the fault detector based on DPFC current will operate. The pickup signal will maintain 5s after the fault detector based on DPFC current drops off. 3.5.1.2 Fault Detector Based on Zero-sequence Current The operation condition will be satisfied when zero-sequence current (3I0) is greater than the setting [FD.ROC.3I0_Set]. The fault detector based on zero-sequence current is always in service. (3I0: zero-sequence current is calculated from the vector sum of Ia, Ib and Ic) If operation condition is satisfied, the fault detector based on zero-sequence current will operate. The pickup signal will maintain 5s after the fault detector based on zero-sequence current drops off. 3.5.1.3 Fault Detector Based on Negative-sequence Current The operation condition will be satisfied when negative-sequence current (I2) is greater than the setting [FD.NOC.I2_Set]. It can be enabled or disabled by the setting [FD.NOC.En]. If operation condition is satisfied, the fault detector based on negative-sequence current will operate. The pickup signal will maintain 5s after the fault detector based on negative-sequence current drops off. 3.5.1.4 Fault Detector Based on Weak Infeed Logic or Inter-trip Logic For an internal fault, current fault detector may not operate at weak end. If permissive signal of current differential protection from the remote end and weak infeed logic of current differential protection meets operation condition, the fault detector based on weak infeed logic will operate. The pickup signal will maintain 500ms after the fault detector based on weak infeed logic drops off. When any protection (such as overcurrent protection and etc.) of local end operates, inter-trip PCS-9613S Differential Relay 3-9 Date: 2020-09-02 3 3 Protection Functions signal of corresponding phase will be sent to the remote end. If differential current meets the criterion and the device receives the inter-trip signal from the remote end, the fault detector based on inter-trip logic will operate. The pickup signal will maintain 500ms after the fault detector based on inter-trip logic drops off. 3.5.2 Function Block Diagram FD FD.Pkp FD.DPFC.Pkp 3 FD.ROC.Pkp FD.NOC.Pkp Alm_Pkp_FD 3.5.3 I/O Signals Table 3.5-1 Output signals of fault detector No. Output Signal Description 1 FD.Pkp The device picks up 2 FD.DPFC.Pkp DPFC current fault detector element operates. 3 FD.ROC.Pkp Zero-sequence current fault detector element operates. 4 FD.NOC.Pkp Negative-sequence fault detector element operates. 5 Alm_Pkp_FD Fault detector element operates for more than 50s. 3.5.4 Logic SIG Ia SIG Ib SIG Ic Calculate DPFC phase-tophase current: ΔIab=Δ(Ia-Ib) ΔIbc=Δ(Ib-Ic) ΔIca=Δ(Ic-Ia) ΔIab>[FD.DPFC.I_Set] >=1 ΔIbc>[FD.DPFC.I_Set] FD.DPFC.Pkp ΔIca>[FD.DPFC.I_Set] >=1 0s Calculate residual current: 3I0=Ia+Ib+Ic 3I0>[FD.ROC.3I0_Set] Calculate negativesequence current: I2 I2>[FD.NOC.I2_Set] 5s FD.Pkp FD.ROC.Pkp & FD.NOC.Pkp EN FD.NOC.En SIG FD.Pkp 50s 10s Alm_Pkp_FD Figure 3.5-1 Logic diagram of fault detector PCS-9613S Differential Relay 3-10 Date: 2020-09-02 3 Protection Functions 3.5.5 Settings ⚫ Access path: MainMenu Settings Protection Settings FD Settings Table 3.5-2 Settings of fault detector No. Settings Range Default value Unit Step 1 FD.DPFC.I_Set (0.050~40.000)×In 0.100 A 0.001 2 FD.ROC.3I0_Set (0.050~40.000)×In 0.100 A 0.001 Description Current setting of DPFC current fault detector element Current FD.NOC.I2_Set (0.050~40.000)×In 0.100 A 0.001 of residual current fault detector element Current 3 setting setting of negative-sequence current fault detector element 4 FD.NOC.En Disabled Enabled Enabling/disabling Disabled - - negative-sequence current fault detector element 3.6 Optical Pilot Channel (FO) The devices can transmit analog quantities and Boolean quantities such as current quantities, blocking signal and transfer trip signal to the remote end via optical fibre channel. Up to 2 optical fibre channels are supported, which can be dedicated optical fibre channel or multiplex channel, the channel mode could be selected as single-mode or multi-mode. The communication rate can be 64kbit/s or 2048kbit/s, and G.703 or C37.94 are optional for communication protocol. 3.6.1 Function Description Besides current and voltage, 8 digital bits are integrated in each frame of transmission message for various applications, and 8 binary signals are configurable. Each received message frame via fibre optical channel will pass through security check to ensure the integrity of the message consistently. 3.6.1.1 Channel Interface The device can adopt dedicated optical fibre channel or multiplex channel. The dedicated fibre channel is usually recommended unless the received power does not meet the requirement if the transmission line is very long. The channel connections with two kinds of communication rate, 64kbit/s or 2048kbit/s, via dedicated optical fibre channel is shown in Figure 3.6-1 and Figure 3.6-2. PCS-9613S Differential Relay 3-11 Date: 2020-09-02 3 3 Protection Functions Max 2km for 62.5/125um multi-mode FO (C37.94) TX RX RX TX IED1 IED2 ST connectors ST connectors Figure 3.6-1 Direct optical link up to 2km with 850nm 3 Max 60km for 9/125um single-mode FO TX RX RX TX IED1 IED2 FC connectors FC connectors Figure 3.6-2 Direct optical link up to 60km with 1310nm The channel connections with two kinds of communication rate, 64kbit/s or 2048kbit/s, via single channel or multiplex channel is shown in Figure 3.6-3, Figure 3.6-4 and Figure 3.6-5. C37.94 (n*64kbit/s) Multi-mode FO IED1 Communication convertor TX RX RX TX ST connectors E O Interface Link to communicate device ST connectors Figure 3.6-3 Connect to a communication network via communication convertor PCS-9613S Differential Relay 3-12 Date: 2020-09-02 3 Protection Functions G.703 (64kbit/s) MUX-64 Single-mode FO IED1 TX RX RX TX FC connectors E Interface Link to communicate device O FC connectors 3 Figure 3.6-4 Connect to a communication network via MUX-64 G.703-E1 (2048kbit/s) MUX-2M Single-mode FO IED1 TX RX RX TX FC connectors E Interface O Link to communicate device FC connectors Figure 3.6-5 Connect to a communication network via MUX-2M The data format of protection transmission is shown as following table. Bit High low Data Frame Description Start bit The header data of transmission data format, 7E (hexadecimal) Data information Including currents and binary signals CRC CRC Stop bit The ender of transmission data format, 7E (hexadecimal) 3.6.1.2 Communication Clock The device transmits and receives messages based on respective clocks, which are called transmit clock (i.e. clock TX) and receive clock (i.e. clock RX) respectively. Clock RX is fixed to be extracted from message frame, which can ensure no slip frame and no error message received. Clock TX has two options: 1. Use internal crystal clock, which is called internal clock. (master clock) 2. Use external clock. (slave clock) Depend on the clock used by the device at both ends, there are three modes. 1. Master-master mode Both ends use internal clock. PCS-9613S Differential Relay 3-13 Date: 2020-09-02 3 Protection Functions 2. Slave-slave mode Both ends use external clock. 3. Master-slave mode One of them uses internal clock, the other uses external clock The logic setting [FOx.Opt_ClkSrc] is used to select the communication clock. The internal clock is enabled automatically when the logic setting [FOx.Opt_ClkSrc] is set as “Int”. Contrarily, the external clock is enabled automatically when the logic setting [FOx.Opt_ClkSrc] is set to “Ext”. 3 If the device uses multiplex PCM channel, logic setting [FOx.Opt_ClkSrc] at both ends should be set as “Ext” (Mode 2). If the device uses dedicated optical fibre channel, clock Mode 1 and Mode 3 can be used. Mode 1 is recommended in considering simplification to user, i.e. logic setting [FOx.Opt_ClkSrc] at both ends should be set as “Int”. 3.6.1.3 Identity Code In order to ensure reliability of the device when digital communication channel is applied, settings [LocID] and [RmtID] are provided as identity code to distinguish uniquely the device at remote end using same channel. Under normal conditions, the identity code of the device at local end should be different with that at remote end. In addition, it is recommended that the identity code of all devices, i.e., the setting [LocID], should be unique in the power grid. The setting range is from 0 to 65535. Only for loop test, they are set as the same. The setting [LocID] of the device at an end should be as same as the setting [RmtID] of the device at opposite end and the greater [LocID] between them is chosen as the master end for sampling synchronism, the smaller [LocID] is the slave end. If the setting [LocID] is set as same as the setting [RmtID], that means the device in loopback testing mode. The setting [LocID] is packaged in the message frame and transmitted to the remote end. When the [LocID] of the device at remote end received by local device is same to the setting [RmtID] of local device, the message received from the remote end is valid, and data information involved in message is considered in protection calculation. When these settings are not matched, the message is considered as invalid and data information involved in message is ignored, corresponding alarms will be issued. 3.6.1.4 Channel Statistics The device has the function of on-line channel monitoring and channel statistics. It can produce channel statistic report automatically at 9:00 every day and the report can be printed for operator to check the channel quality. The monitoring contents of channel status are shown as follows, and they can be viewed by the menu Main Menu→"Test"→"Counter"→"Pilot Ch Counter". 1. FOx.StartTime (starting time) It shows the starting time of the channel status statistics of the device at local end. 2. 87L.Equip_Local PCS-9613S Differential Relay 3-14 Date: 2020-09-02 3 Protection Functions It shows the local device is master or slaver. 3. RmtID (ID code of the remote end) It shows the ID information received by the device at local end now. 4. FOx.t_ChLag (propagation delay of channel x) It shows the calculated communication channel time delay of the device at local end now (unit: us). The calculation is based on the assumption that the sending and receiving channel paths are same. The device measures propagation delay of communication channel based on the below principle. Side S transmits a frame of message to side M, and meanwhile records the transmitting time “tss” on the basis of clock on side S. When side M receives the message, it will record receiving time “tmr” of the message with its own clock, and return a frame of message to side S at next fixed transmitting time, meanwhile data of “tms-tmr” is included in the frame of message. Side S will receive the message from side M at the time “tsr” and obtain the data of “tms-tmr”. Therefore, the propagation delay of the channel “Td” is obtained through calculation: Td = (t sr − t ss ) − (t ms − t mr ) 2 By using the above calculated “Td”, the device automatically compensate time synchronization of sampling data at each end and transmission time lag. T1 tss tsr tmr Td tms "S" "M" T2 Figure 3.6-6 Schematic diagram of communication channel time 5. FOx.N_CRCFail (total number of error frame of channel x) It shows the total number of the error frames of the device at local end from starting time of channel statistics until now. Error frame means that this frame fails in CRC check. 6. FOx.N_FramErr (total number of abnormal messages of channel x) It shows the total number of abnormal messages of the device at local end from starting time of PCS-9613S Differential Relay 3-15 Date: 2020-09-02 3 3 Protection Functions channel statistics until now. 7. FOx.N_FramLoss (total number of lost frames of channel x) It shows the total number of the lost frames of the device at local end from starting time of channel statistics until now. 8. FOx.N_RmtAbnor (total number of abnormal messages from the remote end of channel x) It shows the total number of abnormal messages received from the remote end from starting time of channel statistics until now. 3 9. FOx.N_CRCFailSec (total number of serious error frames of channel x) It shows the total number of serious error frame seconds of the device at local end from starting time of the channel statistics until now. 10. FOx.N_SynLoss (total number of loss synchronous of channel x) It shows the total number of loss synchronous of the device at local end from starting time of the channel statistics until now. 3.6.2 Function Block Diagram FOx FOx.Enable FOx.On FOx.Sendi FOx.Recvi FOx.Alm FOx.Alm_ID FOx.Alm_87L_Unmatched 3.6.3 I/O Signals Table 3.6-1 Input signals of optical pilot channel No. Input Signal Description 1 FOx.Enable Enabling channel x 2 FOx.Sendi Sending signal i of channel x (i=1, 2, 3, ......, 8) No. Output Signal Description 1 FOx.On Channel x is enabled. 2 FOx.Recvi Receiving signal i of channel x (i=1, 2, 3, ......, 8) 3 FOx.Alm Channel x is abnormal. 4 FOx.Alm_ID 5 FOx.Alm_87L_Unmatched Received ID from the remote end is not as same as the setting [RmtID] of the device in local end. The status of differential protection of channel x between local end and remote end is inconsistent. PCS-9613S Differential Relay 3-16 Date: 2020-09-02 3 Protection Functions 3.6.4 Logic SIG Receiving transfer signal i from remote side & FOx.Recvi SIG FOx.Alm >=1 SIG FOx.Alm_ID SIG FOx.Enable & FOx.On EN [FOx.En] 3 Figure 3.6-7 Logic of receiving signal i SIG FOx.Sendi & Sending to the opposite end SIG FOx.On Figure 3.6-8 Logic of sending signal i i can be 1~8 SIG FOx.Alm_ID SIG FOx.Alm_NoValFram SIG FOx.Alm_CRC SIG FOx.Alm_Connect & FOx.Alm >=1 Figure 3.6-9 Logic of channel alarm 3.6.5 Settings ⚫ Access path: MainMenu Settings Protection Settings Rmt CommCh Settings Table 3.6-2 Settings of optical pilot channel No. Settings Range Default Unit value Step 1 LocID 0~65535 1 - 1 2 RmtID 0~65535 2 - 1 3 BaudRate 2048 kbps - 64 2048 PCS-9613S Differential Relay Description Identity code of the device at local end Identity code of the device at remote end Baud rate of optical pilot channel 3-17 Date: 2020-09-02 3 Protection Functions No. Settings Range Default Unit value Step G.703 4 Protocol C37.94 - - 12 - 1 C37.94 Description It is used to select protocol type, G.703 or C37.94 The setting for the times of 64kbit/s, 5 FOx.Nx64k_C37.94 1~12 which is an N*64kbit/s standard defined by IEEE C37.94 standard Option of internal clock or external 6 FOx.Opt_ClkSrc 3 Ext Int Int - - clock Ext: external clock Int: internal clock 7 FOx.En Disabled Enabled Enabled - - Enabling/disabling channel x 3.7 Current Differential Protection (87L) Current differential protection refers to the phase-segregated steady-state current differential element, and it provides CT saturation detection for external fault. Current differential protection can be used as the main protection of overhead line or cable with various voltage levels, and it is applied for single CB 2-terminal transmission line. 3.7.1 Functions Description Current differential protection includes two stages of phase-segregated steady-state current differential protection. The device adopts the asynchronous method and the restrained current floating threshold technology to identify whether there is CT saturation during external fault, which can effectively prevent current differential protection from maloperation during external fault with serious CT saturation. Based on differential current abnormality discrimination, current differential protection can be selected to be blocked according to the specific requirements. Current differential protection exchanges required analog quantities and binary signals via optical fibre channel. The optical fibre channel can be dedicated optical fibre or multiplex channel, its communication rate can be 64kbit/s or 2048kbit/s, and supports G.703 and C37.94. The device calculates channel propagation delay in real-time, and adjust sampling instant to ensure synchronization of sampled values at each end. The maximum tolerable channel propagation delay is 20ms. Based on the Kirchhoff theory, the magnitude is same and the phase is reverse between the currents which flowing in and flowing out the protected zone under normal conditions, or during power swing, or external fault. The differential current which comes from CT error at both sides and capacitive current due to line capacitive reactance is very small. When an internal fault appears in the protected zone, a large differential current will be generated. Hence, the distinction between internal fault and external fault is very explicit. PCS-9613S Differential Relay 3-18 Date: 2020-09-02 3 Protection Functions 3.7.1.1 Current Differential Protection Enable/Disable Current differential protection receives information quantities from other ends, and current differential protection is not enabled unless all current differential protections of two ends are enabled. The logic scheme is shown as below. SIG 87L.FOx.Enable EN [87L.En] SIG 87L.FOx.Block SIG 87L.FOx.Enable EN [87L.En] & & FOx.Enable DIFF (Local end) 3 & & FOx.Enable DIFF (Remote end) SIG 87L.FOx.Block Setting by the remote end SIG FO1.Enable DIFF (Local end) & 87L.FO1.On SIG FO1.Enable DIFF (Remote end) >=1 87L.On SIG FO2.Enable DIFF (Local end) & 87L.FO2.On SIG FO2.Enable DIFF (Remote end) SIG FOx.Enable DIFF (Local end) SIG 87L.FOx.Block >=1 SIG 87L.FOx.On & 87L.FOx.Valid >=1 SIG Fail_Device SIG Alm_Invalid_I & >=1 87L.FOx.Blocked SIG FOx.Alm Figure 3.7-1 Logic of enabling current differential protection Where: FOx.Enable DIFF (Local end): local current differential protection is enabled corresponding to channel x FOx.Enable DIFF (Remote end): remote current differential protection is enabled corresponding PCS-9613S Differential Relay 3-19 Date: 2020-09-02 3 Protection Functions to channel x SIG FOx.Enable DIFF (Local end) & >=1 SIG FOx.Enable DIFF (Remote end) & & 10s 10s FOx.Alm_87L_Unmatched SIG FOx.Alm 3 Figure 3.7-2 Inconsistent enabling status of current differential protection 3.7.1.2 Basic Differential Current Condition SIG 87L.CT_Blk & SIG 87L.On SET IDiffA >[87L.I_Pkp] & 87L.Low_Slop_StA & SET IDiffA >0.15×IBiasA SIG 87L.CT_Blk & SIG 87L.On SET IDiffB >[87L.I_Pkp] & 87L.Low_Slop_StB & SET IDiffB >0.15×IBiasB SIG 87L.CT_Blk & SIG 87L.On SET IDiffC >[87L.I_Pkp] & & 87L.Low_Slop_StC SET IDiffC >0.15×IBiasC Figure 3.7-3 Common condition of current differential protection Where: IDiffA, IDiffB, IDiffC: differential current of phase A, phase B and phase C. IBiasA, IBiasB, IBiasC: restraint current of phase A, phase B and phase C. 87L.CT_Blk: CT circuit failure blocks current differential protection. PCS-9613S Differential Relay 3-20 Date: 2020-09-02 3 Protection Functions 3.7.1.3 Steady-state Current Differential Element 1. Stage 1 The steady-state current differential element comprises pickup threshold, low slope characteristics and high slope characteristics. The calculation of steady-state restraint current and differential current is phase-segregated. The first section is a low slope characteristics, which is sensitive to slight internal faults. The second section is a high slope characteristics, which mainly prevents from unbalance current due to large current. Its criterion is: 3 I DiffΦ I ( H I BiasΦ Knee1) I DiffΦ I H + K 1 ( I BiasΦ - Knee1) ( Knee1 I BiasΦ Knee2) IDiffΦ IH + K1 ( Knee2 − Knee1)+ K 2 (IBiasΦ − Knee2) (IBiasΦ Knee2) Equation 3.7-1 I DiffΦ = IMΦ + INΦ I BiasΦ = IMΦ + INΦ Where: I DiffΦ : The phase differential current I BiasΦ : The phase restraint current IH : 1.5×[87L.I_Pkp] IDiffΦ k=1 k2 k1 IH Knee2 Knee1 IBiasΦ Figure 3.7-4 Operating characteristics of steady-state current differential element Where: K1 and K2 are respectively the setting [87L.Slope1] and the setting [87L.Slope2]. PCS-9613S Differential Relay 3-21 Date: 2020-09-02 3 Protection Functions Knee1 are Knee2 are respectively the setting [87L.I_Knee1] and the setting [87L.Knee2]. 2. Stage 2 Due to exist transient components, the time delay of stage 2 of steady-state current differential element is fixed as 1¼ cycles, which can avoid stage 2 of steady-state current differential element is affected by transient components. Its criterion is: I DiffΦ I M(I BiasΦ Knee1) 3 I DiffΦ I M + K 1 ( I BiasΦ - Knee1) ( Knee1 I BiasΦ Knee2) Equation 3.7-2 IDiffΦ IM + K1 ( Knee2 − Knee1)+ K 2 (IBiasΦ − Knee2) (IBiasΦ Knee2) Where: IM : i.e. the setting [87L.I_Pkp]; I DiffΦ and I BiasΦ are the same as those mentioned above. IDiffΦ k=1 k2 k1 IM knee2 knee1 IBiasΦ Figure 3.7-5 Operating characteristics of steady-state current differential element Where: K1 and K2 are respectively the setting [87L.Slope1] and the setting [87L.Slope2]. Knee1 are Knee2 are respectively the setting [87L.I_Knee1] and the setting [87L.Knee2]. The logic of steady-state current differential element is: PCS-9613S Differential Relay 3-22 Date: 2020-09-02 3 Protection Functions SIG Steady-state DIFF1 SIG FD.Pkp SIG 87L.Low_Slop_StA EN [87L.En_Biased1] SIG CT saturation & & >=1 & 87L.OpA_Biased1 SIG 87L.CT_Blk SIG Permissive signal (phase-A) EN [87L.En_LocDiff] SIG Steady-state DIFF1 SIG FD.Pkp SIG 87L.Low_Slop_StB EN [87L.En_Biased1] SIG CT saturation >=1 3 & & >=1 & 87L.OpB_Biased1 SIG 87L.CT_Blk SIG Permissive signal (phase-B) EN [87L.En_LocDiff] SIG Steady-state DIFF1 SIG FD.Pkp SIG 87L.Low_Slop_StC EN [87L.En_Biased1] SIG CT saturation >=1 & & >=1 & 87L.OpC_Biased1 SIG 87L.CT_Blk SIG Permissive signal (phase-C) EN [87L.En_LocDiff] SIG 87L.OpA_Biased1 SIG 87L.OpB_Biased1 SIG 87L.OpC_Biased1 >=1 >=1 87L.Op_Biased1 Figure 3.7-6 Logic of steady-state current differential element (stage 1) PCS-9613S Differential Relay 3-23 Date: 2020-09-02 3 Protection Functions 3 SIG Steady-state DIFF2 SIG FD.Pkp SIG 87L.Low_Slop_StA EN [87L.En_Biased2] SIG CT saturation SIG 87L.CT_Blk SIG Permissive signal (phase-A) EN [87L.En_LocDiff] SIG Steady-state DIFF2 SIG FD.Pkp SIG 87L.Low_Slop_StB EN [87L.En_Biased2] SIG CT saturation SIG 87L.CT_Blk SIG Permissive signal (phase-B) EN [87L.En_LocDiff] SIG Steady-state DIFF2 SIG FD.Pkp SIG 87L.Low_Slop_StC EN [87L.En_Biased2] SIG CT saturation SIG 87L.CT_Blk SIG Permissive signal (phase-C) EN [87L.En_LocDiff] SIG 87L.OpA_Biased2 SIG 87L.OpB_Biased2 SIG 87L.OpC_Biased2 & & >=1 & 1¼ cycles 0 87L.OpA_Biased2 1¼ cycles 0 87L.OpB_Biased2 1¼ cycles 0 87L.OpC_Biased2 >=1 & & >=1 & >=1 & & >=1 & >=1 >=1 87L.Op_Biased2 Figure 3.7-7 Logic of steady-state current differential element (stage 2) Where: Steady-state DIFF1: Stage 1 of steady-state current differential element meet the operating PCS-9613S Differential Relay 3-24 Date: 2020-09-02 3 Protection Functions equation. Steady-state DIFF2: Stage 2 of steady-state current differential element meet the operating equation. 3.7.1.4 Data Exchange Based on the information transmitted from each end of transmission line via communication channel, current differential protection can discriminate the fault. For 2-terminal transmission line, current differential protections at both ends send the current sampling value to the opposite end and receive the current sampling value from the opposite end. After finishing synchronization, they calculate differential current and restrained current respectively. I1 I2 89 89 52 52 i1 87L i2 87L Figure 3.7-8 Connection mode The detailed channel status can be viewed by LCD, including channel delay, current at the opposite end and differential current, etc. Table 3.7-1 Protection transmission data format for 64kbit/s Bit High Data Frame Description Format The header of transmission data format LocID The identity code of local device Ia Ib Three phase current Ic low Time Time for synchronizing FOx.Send1~FOx.Send8 The eight signals sent by channel No.x Inter-trip (phase A/B/C) Phase-segregated inter-tripping signal Permissive signal (phase A/B/C) Permissive signal of current differential protection operating Enable DIFF Differential protection at both sides are enabled CRC The device supports 64kbit/s and 2Mbit/s communication rate. When 64kbit/s was adopted, the device transmits once sampling data every 5ms, and the data contents transmitted is as shown in Table 3.7-1. When 2Mbit/s was adopted, the device transmits once sampling data every sampling interval, and the data contents transmitted is as shown in Table 3.7-2. PCS-9613S Differential Relay 3-25 Date: 2020-09-02 3 3 Protection Functions Table 3.7-2 Protection transmission data format for 2Mbit/s Bit High Data Frame Description Format The header of transmission data format LocID The identity code of local device Ia Ib Three phase current Ic Ua Ub Three phase voltage Uc 3 low Time Time for synchronizing FOx.Send1~FOx.Send8 The eight signals sent by channel No.x Inter-trip (phase A/B/C) Phase-segregated inter-tripping signal Permissive signal (phase A/B/C) Permissive signal of current differential protection operating Enable DIFF Differential protection at both sides are enabled CRC 1. Clock synchronization Valid messages exchange is key factor for current differential protection. The device sends and receives messages based on respective clocks, which are called transmit clock (i.e. clock TX) and receive clock (i.e. clock RX) respectively. Clock RX is fixed to be extracted from message frame, which can ensure no slip frame and no error message received. The device adopts the synchronization mode based on symmetric channel, and the propagation delay between the sending route and the receiving route of the channel shall be equivalent (<1ms). It should be ensured that the sending and receiving channels are of same route. If the propagation delay between the sending route and the receiving route of the channel meets the requirement, the device adopts clock source in the device (i.e., internal crystal clock, , which is also called internal clock or master clock) or clock source in the communication network (i.e., clock source provided by PCM or SDH) as clock TX. Depend on the clock used by the device at both ends, there are three modes. 1) Master-master mode Both ends use internal crystal clock. 2) Slave-slave mode Both ends use the clock of the communication network. 3) Master-slave mode One of them uses internal crystal clock, the other uses the clock of the communication network. PCS-9613S Differential Relay 3-26 Date: 2020-09-02 3 Protection Functions T1 tss tsr tmr Td tms "IED1" 3 "IED2" T2 Figure 3.7-9 Schematic diagram of communication channel time For example, IED1 sends a frame of message to IED2, and meanwhile records the sending time “tss”. When IED2 receives the message, it will record receiving time “tmr”. IED2 sends a frame of message to IED1 at next sampling interval, meanwhile data of “tms-tmr” is included in the frame of message. IED1 will receive the message from IED2 at the time “tsr” and obtain the data of “tms-tmr”. Therefore, the propagation delay of the channel “Td” is obtained through calculation: Td = (t sr − t ss ) − (t ms − t mr ) 2 By using the above calculated “Td”, the device automatically compensate time synchronization of sampling data at each end and transmission time lag. 3.7.1.5 CT Saturation Discrimination Two detectors are used to prevent undesired tripping caused by severe CT saturation during external close up fault. If the differential current is determined to be caused by CT saturation, the device will block differential protection to prevent mal-operation. ⚫ High restraint coefficient and self-adaptive floating restraint threshold Due to high slope of DPFC percent differential protection, differential protection has higher ability of anti-CT saturation. For external fault as shown in figure below, the restraint current will be able to reflect the real quantity of system for a short time after current cross zero point and can be used as the restraint current after CT enters into saturation status by the use of self-adaptive floating threshold technology. PCS-9613S Differential Relay 3-27 Date: 2020-09-02 3 Protection Functions Fault-Current-SideA 10 A 5 0 -5 -10 0 20 40 60 80 100 120 140 80 100 120 140 80 100 120 140 Fault-Current-SideB 20 A 10 0 -10 0 20 40 60 Diff-Current 20 A 10 0 3 -10 0 20 40 60 Restraint-Current 20 CT A 10 0 -10 -20 0 20 40 60 80 100 120 140 Figure 3.7-10 Relation between CT saturation differential current and restraint current ⚫ Asynchronous method The asynchronous method is realized according to the the condition that the differential current and the restraint current change differently. As shown in Figure 3.7-10, there is a short time before CT is saturated after fault current cross zero point, during the period, CT can convert fault current accurately, so there is restraint current but no differential current, the congruent relationship between increased differential current and increased restraint current is used to judge if there is a internal or external fault, strong anti-saturation ability can be gained based on this method. The discrimination of external fault is only effective for percentage current differential element. 3.7.1.6 Differential Abnormality Supervision When the propagation delay of the channel is uncertain, no GPS and unreliable GPS source make that the device cannot detect the propagation delay of the channel, so the currents at both ends cannot accurately be synchronized. For large load current, larger differential current may be generated so as to lead to undesired operation of current differential protection. Hence, differential current needs to be supervised. According to unbalance differential current under load conditions, if differential current is greater than the threshold value, the device will issue an alarm to indicate that differential current is abnormal. The threshold of discriminating differential current abnormality needs to cooperate with pickup setting of current differential protection, at the same time it should be greater than unbalance current under normal conditions (including unbalance current due to CT error at both ends and capacitive current not compensated). In addition to discriminate inconsistent channel route, continuous differential current can also be used to detect CT circuit failure, an alarm will be issued with a time delay for CT circuit failure of any end under on-load conditions. PCS-9613S Differential Relay 3-28 Date: 2020-09-02 3 Protection Functions The logic of differential current abnormality supervision is SET IDiffA>[87L.I_Alm] SET IDiffB>[87L.I_Alm] SET IDiffC>[87L.I_Alm] SIG & 10s 10s 10s 10s 10s 10s & >=1 87L.FOx.Alm_Diff & 3 87L.FOx.On Figure 3.7-11 Logic of differential current supervision Where: IdiffA, IdiffB, IdiffC are respectively differential current of phase A, B, C 3.7.1.7 CT Circuit Supervision When CT circuit failure occurs at one end, FD and current differential protection on the end might operate. However, FD on another end will not operate and not send any permissive signal of current differential protection. Therefore, the current differential protection will not maloperate. Meanwhile the healthy end will issue alarm signal [87L.Alm_Diff] which will be treated as the same as the alarm [CTS.Alm]. However, if CT circuit failure associated with internal fault or pickup due to system disturbance is detected, the device will show two kinds of behaviour. 1) If logic setting [87L.En_CTS_Blk] (differential protection being blocked during CT circuit failure) is set as “Enabled”, the current differential protection will be blocked. 2) If logic setting [87L.En_CTS_Blk] is set as “Disabled” and the current differential current of the faulty phase is more than the differential current setting [87L.I_Pkp_CTS] during CT circuit failure, the current differential protection will operate with alarm signal being issued at the same time. The logic of CT circuit failure blocking current differential protection is: PCS-9613S Differential Relay 3-29 Date: 2020-09-02 3 Protection Functions SET IDiff >[87L.I_Pkp_CTS] EN >=1 [87L.En_CTS_Blk] SIG CTS.Alm & >=1 & SIG 87L.FOx.Alm_Diff 87L.CT_Blk SIG 87L.On Figure 3.7-12 CT circuit failure blocking current differential protection 3 3.7.1.8 Weak Infeed For some special fault, such as the high-impedance fault, internal fault at weak end, etc., the sensitivity of fault detector element does not meet the requirements, so as that current differential protection cannot operate. Hence, the independent mandatory fault detector element is provided for these cases. 1) When the voltage is valid, if there is an asymmetric voltage element or phase voltage or phase-to-phase voltage is lower than the setting, and there is differential current and permissive signal from the opposite end is received, the independent fault detector element for weak infeed operate. The device picks up. 2) When the voltage is invalid, if the current of the opposite end is more than four times that of the local end, and there is differential current and permissive signal from the opposite end is received, the independent fault detector element for weak infeed operate. The device picks up. The independent fault detector element for weak infeed will be automatically disabled when CT circuit fails, or differential current is abnormal or three phases of the circuit breaker are all open position. The logic of independent fault detector element for weak infeed is: PCS-9613S Differential Relay 3-30 Date: 2020-09-02 3 Protection Functions SIG 3U0>1V >=1 30ms 0 SIG 3U2>6V SIG UA<0.65UN >=1 >=1 SIG UB<0.65UN & SIG UC<0.65UN SIG UAB<0.65UNN >=1 SIG UBC<0.65UNN 3 SIG UCA<0.65UNN SIG VTS.Alm SIG 4Ia<Ia_Rmt >=1 SIG 4Ib<Ib_Rmt & SIG 4Ic<Ic_Rmt >=1 SIG Permissive signal SIG 87L.FOx.Alm_Diff Weak infeed logic & 30ms >=1 0 SIG CTS.Alm Figure 3.7-13 Weak infeed logic of current differential protection Where: Ia, Ib, Ic are three phases current of local end; Ia_Rmt, Ib_Rmt, Ic_Rmt are three phases current of remote end; Ua, Ub, Uc are three phases voltage of local end; Uab, Ubc, Uca are three phase-to-phase voltage of local end. 3.7.1.9 Permissive Signal Differential permissive signal is fault discrimination signal, which is sent to the other ends of current differential protection and used as an auxiliary condition of current differential protection operation. The setting [87L.En_LocDiff] can determine whether local current differential protection is controlled by permissive signal from other ends. For some abnormal conditions, such as CT circuit failure or abnormal sampling, a large differential current will be produced under non-fault conditions. Taking CT circuit failure as an example, when CT circuit fails, the differential current maybe is larger than the setting and current differential protection mal-operates if load current is very large. In order to prevent from undesired operation, permissive signal from other ends is used as auxiliary criterion of local current differential protection. PCS-9613S Differential Relay 3-31 Date: 2020-09-02 3 Protection Functions The logic of sending permissive signal is: SIG 87L.Low_Slop_StA & SIG 87L.Low_Slop_StB & SIG 87L.Low_Slop_StC 3 SIG 52b_PhA & Send permissive signal (phase A) Send permissive signal (phase B) Send permissive signal (phase C) & SIG 52b_PhB SIG 52b_PhC >=1 SIG Weak infeed logic SIG FD.Pkp Figure 3.7-14 Sending permissive signal of current differential protection 3.7.1.10 CT Ratio Adjustment If CTs' ratio at two ends of the transmission line is different, the currents must be corrected to one reference value. Regarding local end as the referenced end, differential current and restraint current can be calculated since the current of the opposite end is corrected by the setting. [87L.K_Cr_CT]. Setting principle: Suppose CT ratio, Terminal M: kM=IM1n : IM2n; Terminal N: kN=IN1n : IN2n IM1n: primary rated current of terminal M, IM2n: secondary rated current of terminal M IN1n: primary rated current of terminal N, IN2n: secondary rated current of terminal N If IM1n>= IN1n Terminal M: [87L.K_Cr_CT]=1.00 Terminal N: [87L.K_Cr_CT]=IN1n / IM1n For example: Terminal M: CT ratio=1250 : 5, the setting [87L.K_Cr_CT] is set as “0.5” Terminal N: CT ratio=2500 : 1, the setting [87L.K_Cr_CT] is set as “1.0” If current of terminal M is IM, current of terminal N is IN, the differential current and restraint current calculated on terminal M is: I DiffΦ = IMΦ + INΦ [87L.K_Corr_CT] PCS-9613S Differential Relay 3-32 Date: 2020-09-02 3 Protection Functions I BiasΦ = IMΦ − INΦ [87L.K_Corr_CT] 3.7.1.11 Differential Inter-trip When a fault associated with high resistance occurs in the outlet of long transmission line, the device of local end, which is near the fault, can pick up immediately, but, considering the influence of a considerable power source, the device of the remote end, which is far from the fault, cannot pick up due to unapparent fault component. In order to avoid this case, any protection (such as overcurrent protection and etc.) of local end operates, inter-trip signal of corresponding phase will be sent to the remote end. In addition, for some special faults, the sensitivity of current differential protection is not enough, so backup protection (for example, earth fault protection) will operate to clear the fault. In order to ensure reliable operation at both ends, inter-tripping signal can be configured to send to the opposite end. Inter-trip signal is phase-segregated signal and is sent to the opposite end via optical fibre channel, which can be configured by PCS-Studio. After receiving the inter-trip signal, the device of the opposite end can pick up, when the setting [87L.En_InterTrp] is set as “Enabled”, the corresponding phase will be inter-tripped if the differential current meets the operating condition. When the circuit breaker of any end is in open position and there is no current, the tripping will be blocked. The logic of differential inter-trip element is: PCS-9613S Differential Relay 3-33 Date: 2020-09-02 3 3 Protection Functions SIG 87L.Low_Slop_StA & SIG Inter-trip element (phase A) & & SIG 52b_PhA EN 87L.OpB_InterTrp 10ms 0 87L.OpC_InterTrp & & SIG 52b_PhB [87L.En_InterTrp] SIG 87L.Low_Slop_StC & SIG Inter-trip element (phase C) & & SIG 52b_PhC EN 10ms 0 & SIG Inter-trip element (phase B) EN 87L.OpA_InterTrp [87L.En_InterTrp] SIG 87L.Low_Slop_StB 3 10ms 0 [87L.En_InterTrp] SIG 87L.OpA_InterTrp SIG 87L.OpB_InterTrp >=1 87L.Op_InterTrp SIG 87L.OpC_InterTrp Figure 3.7-15 Logic of differential inter-trip element Where: Inter-trip element: the tripping signal from the opposite end is received and basic differential current condition is met when the device picks up. 3.7.1.12 CT Requirement for Current Differential Protection The current transformer converts large current at primary side into small current at secondary side based on electromagnetic induction principle. The current transformer is composed of a closed core and windings. Its primary windings is less and connected with the measured loop in series. Its secondary windings is more and connected with the protection loop in series. When the current transformer is working, its secondary loop is always closed and is close to short-circuit. PCS-9613S Differential Relay 3-34 Date: 2020-09-02 3 Protection Functions Figure 3.7-16 CT schematic There are three kinds of current transformer, including high remnant magnetism, low remnant magnetism and non remnant magnetism. ⚫ High remnant magnetism There is no gap in the core with high remnant magnetism. The typical type of current transformer with high remnant magnetism includes TPX, TPS, P and PX. The rate of remnant magnetism can be up to 95%. ⚫ Low remnant magnetism There is a small gap in the core with low remnant magnetism. The typical type of current transformer with low remnant magnetism includes TPY and PR. The rate of remnant magnetism cannot be more than 10% saturation flux. ⚫ Non remnant magnetism There is a large gap in the core with non remnant magnetism. The typical type of current transformer with non remnant magnetism is TPZ. Its remnant magnetism can be neglected. Choosing the current transformer used by the protection, it is necessary that the transferring error of steady-state symmetric short-circuit current should not exceed the specified value. The aperiodic component of short-circuit current and transient impact of remnant magnetism should be considered reasonably according to the severity of the system transient state, the protection characteristics, the transient saturation, etc,. According to the basic electromagnetic relationship, the equivalent circuit of current transformer is shown is shown as below. Figure 3.7-17 Equivalent circuit When other parameters is unchanged and the current is less than the rated value, the smaller the PCS-9613S Differential Relay 3-35 Date: 2020-09-02 3 3 Protection Functions current, the smaller the permeability (μ). The excitation impedance is small, and the excitation current is large, so the error is larger relatively. When the current increases, the permeability increases, the excitation impedance becomes larger and the excitation current becomes smaller, so the error becomes smaller. However, if the current continually increases, the excitation impedance becomes smaller, the excitation current increases, and the error increases again. The B-H curve is shown as below. 3 Figure 3.7-18 Core's Magnetizing curve The current transformer can be verified whether it meets the requirements by calculating the secondary limit electromotive force of current transformer. 1) The rated secondary limit electromotive force of the current transformer: ESl = Kalf×Ie×(Rct+Rbn) Where: Kalf is accuracy limit factor (Kalf=Ipal/Ipn) Ipal is rated accuracy limit primary current. Ipn is rated primary current. Ie is rated secondary current. Rct is secondary windings of the current transformer. Rbn is rated resistance burden. 2) The actual secondary limit electromotive force of the current transformer: Es = Ktd×Kpcf×Isn×(Rct+Rb) Ktd is steady-state coefficient. Kpcf is protective checking factor current. (Kpcf=Ipcf/Ipn) Ipcf is actual maximal primary faulty current. Isn is rated secondary current. PCS-9613S Differential Relay 3-36 Date: 2020-09-02 3 Protection Functions Ipn is rated primary current. Rb is actual resistance burden. 3) Verification criterion: ESl>ES The rated secondary limit electromotive force of current transformer should be greater than the actual second limit electromotive force. The steady-state coefficient (Ktd) should be set complying with the followings. Considering a completed process (CO-CO) and the worst conditions: ⚫ High remnant magnetism CT (P, PX) Ktd=(2+K2), K2=2 ⚫ Low remnant magnetism CT (TPX, TPY, PR) Ktd=(1+K2), K2=1 ⚫ Non remnant magnetism CT (TPZ) Ktd=(0.6+K2), K2=0.6 System primary time constant: K2=0.8 (<60ms), K3=1 (60-120ms), K3=1.5 (120-200ms), K3=2 (>200ms) 3.7.2 Function Block Diagram 87L 87L. FOx.Enable 87L.On 87L. FOx. Block 87L. FOx.On 87L. FOx. Valid 87L. FOx. Blocked 87L.Op 87L.Op_A 87L.Op_B 87L.Op_C 87L.Op_ Biased1 87L.Op_ Biased2 87L.Op_ InterTrp 87L. FOx.Alm_Diff PCS-9613S Differential Relay 3-37 Date: 2020-09-02 3 3 Protection Functions 3.7.3 I/O Signals Table 3.7-3 Input/Output signals of current differential protection No. Input Signal 1 87L.FOx.Enable 2 87L.FOx.Block No. Description Current differential protection enabling input, it is triggered from binary input or programmable logic etc. Current differential protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 87L.On Current differential protection is enabled. 2 87L.FOx.On Current differential protection of channel No.x is enabled. 3 87L.FOx.Valid Current differential protection of channel No.x is valid. 4 87L.FOx.Blocked Current differential protection of channel No.x is blocked. 5 87L.Op 6 87L.Op_A Current differential protection operates. (Phase A) 7 87L.Op_B Current differential protection operates. (Phase B) 8 87L.Op_C Current differential protection operates. (Phase C) 9 87L.Op_Biased1 Stage 1 of steady-stage current differential element operates. 10 87L.Op_Biased2 Stage 2 of steady-stage current differential element operates. 11 87L.Op_InterTrp Differential inter-trip element operates. 12 87L.FOx.Alm_Diff The differential current of channel No.x is abnormal. 3 Current differential protection operates, if any of them “[87L.Op_Biased1], [87L.Op_Biased2], [87L.Op_InterTrp]” operates, then [87L.Op] will operate. 3.7.4 Settings ⚫ Access path: MainMenu Settings Protection Settings Diff Settings Table 3.7-4 Settings of current differential protection No. Settings Range Default Unit value Step 1 87L.I_Pkp (0.05~40)×In 0.300 A 0.001 2 87L.I_Alm (0.05~40)×In 0.300 A 0.001 3 87L.I_Pkp_CTS (0.05~40)×In 1.0×In A 0.001 4 87L.K_Cr_CT 0.2~10 1.0 - 0.001 5 87L.I_Knee1 (0.05~40)×In 1.0×In A 0.001 6 87L.I_Knee2 (0.05~40)×In 3.0×In A 0.001 7 87L.Slope1 0.3~0.75 0.500 - 0.01 Description Minimum pickup current setting of current differential protection Current setting of differential current abnormality alarm Current setting of differential protection when CT circuit failure The factor of CT ratio Current setting of knee point 1 for current differential protection Current setting of knee point 2 for current differential protection Slope 1 of steady-state current differential element PCS-9613S Differential Relay 3-38 Date: 2020-09-02 3 Protection Functions No. Settings 8 87L.Slope2 9 87L.En 10 11 12 87L.En_Biased1 87L.En_Biased2 87L.InterTrp Range 0.3~0.75 Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Default Unit value Step 0.700 - 0.01 Enabled - - Description Slope 2 of steady-state current differential element Enabling/disabling differential protection Enabling/disabling Enabled - - current stage 1 of steady-state current differential element Enabling/disabling Enabled - - stage 2 of steady-state current differential element Enabled - - Enabling/disabling inter-tripping element Enabling/disabling local independent current differential 13 87L.En_LocDiff Disabled Enabled protection (independent current Enabled - - differential protection means local current differential protection can operate without permissive signal from remote end) 14 87L.En_CTS_Blk Disabled Enabled Enabling/disabling Disabled - - differential protection current blocked during CT circuit failure 3.8 Phase Overcurrent Protection (50/51P) Phase overcurrent protection is the most widely used type of protection element in power systems. It can be used as the main protection of the feeder, and can also be used as the backup protection for power equipment such as transformers, reactors, and motors. When a fault occurs in the system, a fault current will be generated and the phase overcurrent protection can reflect the increase of the fault current. 3.8.1 Function Description The device can provide six stages of phase overcurrent protection with independent logic. Each stage can be independently set as definite-time characteristics or inverse-time characteristics. The dropout characteristics can be set as instantaneous dropout, definite-time dropout or inverse-time dropout. Users can choose whether it is blocked by the voltage control element, direction control element, or harmonic control element, users can also choose whether it is controlled by cold load pickup. The direction control element can be set as no direction, forward direction and reverse direction. The phase overcurrent protection picks up when the current exceeds the current threshold value, and operates after a certain time delay, once the fault disappears, the phase overcurrent protection will dropout. Phase overcurrent protection can be enabled or disabled via the settings or binary input signals, PCS-9613S Differential Relay 3-39 Date: 2020-09-02 3 3 Protection Functions for some specific applications, overcurrent protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block overcurrent protection. The enabling and blocking logic of phase overcurrent protection is shown in the figure below: EN 50/51Px.En SI G 50/51Px.Enable SI G 50/51Px.Block SI G Fail_Device & 50/51Px.On & ≥1 50/51Px.Blocked & 3 50/51Px.Valid Figure 3.8-1 The enabling and blocking logic of phase overcurrent protection The logic diagram of the fault detector element of phase overcurrent protection is as follows: SET Ia>0.95×[50/51Px.I_Set] SET Ib>0.95×[50/51Px.I_Set] SET Ic>0.95×[50/51Px.I_Set] SIG 50/51Px.On SIG 50/51Px.Valid SET [50/51Px.Opt_Trp/Alm]=Alm >=1 & 0 500ms & 50/51Px.Pkp & FD.Pkp Figure 3.8-2 The fault detector element of phase overcurrent protection 3.8.1.1 Voltage Control Element When a fault occurs at the remote end of a feeder, the fault current is relatively small, so the voltage control element can be adopted to increase the sensitivity for this kind of fault. Users can enable or disable the voltage control element via the setting [50/51Px.En_Volt_Blk] (x=1~6). If the VT circuit supervision function is enabled for the device, and the setting [50/51P.En_VTS_Blk] is set as “Enabled”, when VT circuit failure happens, the device will issue a VT circuit failure alarm signal [VTS.Alm], and the voltage controlled phase overcurrent protection will be blocked. If the voltage control element of phase overcurrent protection is not enabled, phase overcurrent protection will not be affected by VT circuit failure. The corresponding relationship between the phase-segregated overcurrent element and the voltage control element is as follows. Voltage control criterion Phase A Phase B Phase C Phase-to-phase Uab<[50/51P.VCE.Upp] Uab<[50/51P.VCE.Upp] Ubc<[50/51P.VCE.Upp] criterion Uca<[50/51P.VCE.Upp] Ubc<[50/51P.VCE.Upp] Uca<[50/51P.VCE.Upp] U2>[50/51P.VCE.U2] U2>[50/51P.VCE.U2] U2>[50/51P.VCE.U2] Negative-sequence criterion PCS-9613S Differential Relay 3-40 Date: 2020-09-02 3 Protection Functions Zero-sequence U0_Cal>[50/51P.VCE.3U0] criterion U0_Cal>[50/51P.VCE.3U0] U0_Cal>[50/51P.VCE.3U0] The relationship between the phase-to-phase criterion, the negative-sequence criterion and the zero-sequence criterion is "or". The logic diagram of the voltage control element action is shown below: EN [50/51P.En_VTS_Blk] & >=1 SIG VTS.Alm SIG U2, U0_Cal SIG Prot.BI_En_VT EN Voltage criterion SIG Uab, Ubc, Uca & 3 & 50/51P.VCE.Op & [En_VT] Figure 3.8-3 The voltage control element of phase overcurrent protection 3.8.1.2 Direction Control Element In order to ensure the selectivity of phase overcurrent protection, direction control element is introduced. The setting [50/51Px.Opt_Dir] (x=1~6) is used for users to select the directional mode of each stage of phase overcurrent protection: no direction, forward direction and reverse direction are selectable. Takes the phase A fault as an example, the polarization mode is set as “Up”, its operation characteristics are shown in the figure below. The principle of phase B and phase C is the same. If the positive-sequence voltage or the phase-to-phase voltage is polarized, the operation characteristics are the same. The operation boundary of the forward direction element can be set by [50/51P.DIR.phi_Min_Fwd] and [50/51P.DIR.phi_Max_Fwd]. The operation boundary of the reverse direction element can be set by [50/51P.DIR.phi_Min_Rev] and [50/51P.DIR.phi_Max_Rev]. PCS-9613S Differential Relay 3-41 Date: 2020-09-02 3 Protection Functions Ua [50/51P.DIR.phi_Min_Fwd] Non-operating area Ia Operating area in forward direction [50/51P.DIR.phi_Max_Rev] [50/51P.DIR.RCA] 3 Operating area in reverse direction [50/51P.DIR.phi_Max_Fwd] [50/51P.DIR.phi_Min_Rev] Non-operating area Figure 3.8-4 The direction element operation characteristics when phase A voltage is polarized Where: The sensitivity angle of the direction control element (RCA) can be set by the setting [50/51P.DIR.RCA]. The selection of the polarization voltage can be set by the setting [50/51P.DIR.Opt_PolarizedVolt]. The following table shows the relationship between the operating current, the polarized voltage and the polarization mode. Direction criterion (for “ABC” system phase sequence) Polarization Faulty Operating mode phase current Phase A Positive-sequence voltage polarized Phase B Phase C Phase A Phase-to-phase voltage polarized Phase B Phase C Phase-to-ground Phase A Polarized voltage Phase-A Positive-sequence current Ia voltage Phase-B Positive-sequence current Ib voltage Phase-C Positive-sequence current Ic voltage Phase-A Phase-to-phase current Ia voltage Ubc Phase-B Phase-to-phase current Ib voltage Uca Phase-C Phase-to-phase current Ic voltage Uab Phase-A Phase-to-ground Angle difference Angle_A=Angle(U1)-Angle(Ia)-RCA Angle_B=Angle(U1)-Angle(Ib)-RCA-120º Angle_C=Angle(U1)-Angle(Ic)-RCA+120º Angle_A=Angle(Ubc)-Angle(Ia)-RCA+90º Angle_B=Angle(Uca)-Angle(Ib)-RCA+90º Angle_C=Angle(Uab)-Angle(Ic)-RCA+90º Angle_A=Angle(Ua)-Angle(Ia)-RCA PCS-9613S Differential Relay 3-42 Date: 2020-09-02 3 Protection Functions voltage polarized Phase B Phase C current Ia voltage Ua Phase-B Phase-to-ground current Ib voltage Ub Phase-C Phase-to-ground current Ic voltage Uc Angle_B=Angle(Ub)-Angle(Ib)-RCA Angle_C=Angle(Uc)-Angle(Ic)-RCA In order to improve the reliability of the direction control element, the direction control element with the above three polarization modes must be used in conjunction with the negative-sequence direction criterion. The negative-sequence direction criterion is shown in the table below. Negative-sequence direction criterion Operating current Polarized voltage Negative-sequence current 3 Angle difference Negative-sequence voltage Angle_I2=Angle(U2)-Angle(I2)-RCA+180º For the “ACB” system phase sequence, the angle difference under positive-sequence voltage polarization mode and phase-to-phase voltage polarization mode is different from that of the “ABC” system phase sequence, as shown in the following table: Direction criterion (for “ACB” system phase sequence) Polarization Faulty Operating mode phase current Phase A Positive-sequence voltage polarized Phase B Phase C Phase A Phase-to-phase voltage polarized Phase B Phase C Polarized voltage Phase-A Positive-sequence current Ia voltage Phase-B Positive-sequence current Ib voltage Phase-C Positive-sequence current Ic voltage Phase-A Phase-to-phase current Ia voltage Ubc Phase-B Phase-to-phase current Ib voltage Uca Phase-C Phase-to-phase current Ic voltage Uab Angle difference Angle_A=Angle(U1)-Angle(Ia)-RCA Angle_B=Angle(U1)-Angle(Ib)-RCA+120º Angle_C=Angle(U1)-Angle(Ic)-RCA-120º Angle_A=Angle(Ubc)-Angle(Ia)-RCA+270º Angle_B=Angle(Uca)-Angle(Ib)-RCA+270º Angle_C=Angle(Uab)-Angle(Ic)-RCA+270º Therefore, the criterion for the three-phase direction control element is as follows: Three-phase direction control element Direction element Phase A forward direction Phase A reverse direction Phase B forward direction Operating condition Angle_A forward direction operates and Angle_I2 reverse direction does not operate. Angle_A reverse direction operates and Angle_I2 forward direction does not operate. Angle_B forward direction operates and Angle_I2 reverse direction does not PCS-9613S Differential Relay 3-43 Date: 2020-09-02 3 Protection Functions operate. Phase B reverse direction Phase C forward direction Phase C reverse direction 3 Angle_B reverse direction operates and Angle_I2 forward direction does not operate. Angle_C forward direction operates and Angle_I2 reverse direction does not operate. Angle_C reverse direction operates and Angle_I2 forward direction does not operate. The direction element calculation needs to judge the current threshold and voltage threshold. The corresponding phase operating current must be greater than the minimum operating current setting [50/51P.DIR.I_Min], otherwise the direction element can not operate. For the voltage, it has memory function that can eliminate the dead zone of the direction element when the close up three-phase short circuit fault occurs. When the polarized voltage is less than the minimum operating voltage setting [50/51P.DIR.U_Min], the polarized voltage will not be used to judge the direction, the positive-sequence voltage before two cycles is used to judge the direction. Polarized voltage Operating current Phase-to-phase voltage Phase current Phase-to-ground voltage Phase current Positive-sequence voltage Phase current Negative-sequence voltage Negative-sequence current EN [50/51P.En_VTS_Blk] SIG VTS.Alm SIG Three-phase currents SIG Three-phase voltages SIG Memorized U1 SET [50/51P.DIR.Opt_PolarizedVolt] SIG Prot.BI_En_VT EN [En_VT] SET Iop>[50/51P.DIR.I_Min] & & >=1 & Forward direction criterion 50/51P.FwdDir.Op & PCS-9613S Differential Relay 3-44 Date: 2020-09-02 3 Protection Functions EN [50/51P.En_VTS_Blk] SIG VTS.Alm SIG Three-phase currents SIG Three-phase voltages SIG Memorized U1 SET [50/51P.DIR.Opt_PolarizedVolt] SIG Prot.BI_En_VT EN [En_VT] SET Iop>[50/51P.DIR.I_Min] & & >=1 & Reverse direction criterion 50/51P.RevDir.Op 3 & Figure 3.8-5 Logic diagram of forward and reverse direction element of phase overcurrent protection Where: Memorized U1: the positive-sequence memory voltage, it refers to the positive-sequence voltage of two cycles before the polarized voltage is less than the minimum operating voltage setting [50/51P.DIR.U_Min], and it is calculated from the three-phase voltage. Iop: the operating current. 3.8.1.3 Harmonic Control Element When transformer and other equipment are energized without any load, the inrush current may be generated, which may cause the mal-operation of the phase overcurrent protection. According to the characteristics of high secondary harmonic component in the inrush current and low secondary harmonic component in common fault current, the secondary harmonic control element is added to prevent the phase overcurrent protection from mal-operation due to inrush current. For the harmonic control element, the harmonic blocking mode can be selected through the setting [50/51P.HMB.Opt_Blk], it can support phase locking, cross locking, and maximum phase locking. The correspondences are shown in the following table: Harmonic blocking criterion Setting Value Phase A Phase B Phase C Ib2/Ib1>[50/51P.HMB.K_Hm2] Ic2/Ic1>[50/51P.HMB.K_Hm2] 1 PhaseBlk Ia2/Ia1>[50/51P.HMB.K_Hm2] 2 CrossBlk (Ia2/Ia1) or (Ib2/Ib1) or (Ic2/Ic1)> [50/51P.HMB.K_Hm2] 3 MaxPhaseBlk Max(Ia2, Ib2, Ic2)/Ia1> [50/51P.HMB.K_Hm2] Max(Ia2, Ib2, Ic2)/Ib1> [50/51P.HMB.K_Hm2] Max(Ia2, Ib2, Ic2)/Ic1> [50/51P.HMB.K_Hm2] Where: Ia1, Ib1, Ic1: the fundamental current; Ia2, Ib2, Ic2: the secondary harmonic component of the current. PCS-9613S Differential Relay 3-45 Date: 2020-09-02 3 Protection Functions When the fundamental current is greater than the setting [50/51P.HMB.I_Rls], the harmonic blocking element of the corresponding phase is released. The following figure shows the logic diagram of the harmonic control element of phase overcurrent protection. SET Imax>[50/51P.HMB.I_Rls] & SIG Ia1, Ib1, Ic1 Harmonic criterion 50/51P.HMB.Op SIG Ia2, Ib2, Ic2 SET [50/51P.HMB.Opt_Blk] 3 Figure 3.8-6 Logic diagram of harmonic control element of phase overcurrent protection Where: Ia1, Ib1, Ic1: the fundamental current Ia2, Ib2, Ic2: the 2nd harmonic current Imax: the maximum phase current 3.8.1.4 Operation Characteristic Phase overcurrent protection can operate without time delay or operate with a definite-time limit, it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards. Phase overcurrent protection can support definite-time limit, IEC & ANSI standard inverse time limit and user-defined inverse-time limit, users can select the wanted operating curve by the setting [50/51Px.Opt_Curve] (x=1~6), the relationship between the value of the setting and the curve is shown in the table below. 50/51Px.Opt_Curve Time Characteristic k α c tr ANSIE ANSI Extremely Inverse 28.2 2.0 0.1217 29.1 ANSIV ANSI Very inverse 19.61 2.0 0.491 21.6 ANSIN ANSI Normal Inverse 0.0086 0.02 0.0185 0.46 ANSIM ANSI Moderately Inverse 0.0515 0.02 0.114 4.85 ANSIDefTime ANSI Definite Time - - - - ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30 ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46 ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6 IECN IEC Normal Inverse 0.14 0.02 0 - IECV IEC Very inverse 13.5 1.0 0 - IEC IEC Inverse 0.14 0.02 0 - IECE IEC Extremely inverse 80.0 2.0 0 - IECST IEC Short-time inverse 0.05 0.04 0 - IECLT IEC Long-time inverse 120.0 1.0 0 - IECDefTime IEC Definite Time - - - - UserDefine Programmable PCS-9613S Differential Relay 3-46 Date: 2020-09-02 3 Protection Functions Only when the setting [50/51Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time characteristic is selected, the settings [50/51Px.K], [50/51Px.C] and [50/51Px.Alpha] are useful, the inverse-time operating curve is determined by the three settings. ⚫ Without time delay When I > Ip , phase overcurrent protection operates immediately. ⚫ Definite-time characteristic When I > Ip , the protection operates with a time delay of top (i.e. the value of the setting [50/51Px.t_Op]), and the operation characteristic curve is shown in the following figure: 3 t t op IP I Figure 3.8-7 Definite-time operation characteristic curve of phase overcurrent protection ⚫ Inverse-time characteristic When I > Ip , the inverse-time accumulator begins to accumulate, and the operating time is affected by the applied current I . The operating time will decrease with the current increasing, but the operating time shall not less than tmin , i.e. the setting [50/51Px.tmin] (x=1~6). The inverse-time operation characteristic equation is: k t= + c TMS (I / I P ) −1 Where: Ip is the current setting [50/51Px.I_Set]; TMS is the inverse-time time multiplier, i.e. the setting [50/51Px.TMS]; k is the inverse-time coefficient K, i.e. the setting [50/51Px.K]; c is the inverse-time coefficient C, i.e. the setting [50/51Px.C]; is the inverse-time coefficient Alpha, i.e. the setting [50/51Px.Alpha]; PCS-9613S Differential Relay 3-47 Date: 2020-09-02 3 Protection Functions I is the measured current. The inverse-time operation characteristic curve is shown as below: t 3 t min IP ID I Figure 3.8-8 Inverse-time operation characteristic curve of phase overcurrent protection When the applied current is not a fixed value, but changes with time, the operating behaviour of the protection is shown in the following equation: T0 1 t ( I )dt =1 0 Where: T0 is the operating time of the protection element; t(I) is the theoretical operating time when the current is I. 3.8.1.5 Dropout Characteristic The supported dropout characteristics of the phase overcurrent protection include instantaneous dropout, definite-time dropout and ANSI inverse-time dropout. When the operating curve is selected as definite-time, IEC inverse-time or user-defined inverse-time characteristic, the dropout characteristic can only be selected as instantaneous dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal "Fail_Settings" will be issued and the device will be blocked. When the operating curve is selected as ANSI inverse-time characteristic, the dropout characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI inverse-time dropout. ⚫ Instantaneous dropout PCS-9613S Differential Relay 3-48 Date: 2020-09-02 3 Protection Functions When I <0.95* Ip , the protection drops out immediately. ⚫ Definite-time dropout When I <0.95* Ip , the protection drops out with a time delay of tdr (i.e. the value of the setting [50/51Px.t_DropOut]), and the dropout characteristic curve is shown in the following figure: Start time I>Ip 3 Start signal Operating signal Protection operate Operating threshold Operating counter t dr Dropout time setting t dr t dr Dropout time Dropout time Figure 3.8-9 Definite-time dropout characteristic of phase overcurrent protection ⚫ Inverse-time dropout When I > Ip , the inverse-time operating accumulator begins to accumulate, the accumulated value after t p (Assuming t p is less than the theoretical operating time) is calculated according to the following equation: tp 1 dt t ( I ) 0 I tp = At this time, if I <0.95* Ip , the protection element starts dropout, and the dropout characteristic meets the following equation: TR 1 dt = 0 t ( I ) R 0 I tp − Where: PCS-9613S Differential Relay 3-49 Date: 2020-09-02 3 Protection Functions T R is the dropout time; tR( I ) is the dropout characteristic equation When I <0.95* Ip , the inverse-time dropout characteristic equation is as follows: tr tR = TMS 2 1 − ( I / I P ) Where: 3 Ip is the current setting [50/51Px.I_Set]; TMS is the inverse-time factor, i.e. the setting [50/51Px.TMS]; tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after the protection operates. I is the measured current. When 0.95* Ip < I < Ip , the accumulator will neither accumulate nor drop out The inverse time dropout characteristic curve is shown in the figure below. t tr IP I Figure 3.8-10 Inverse-time dropout characteristic curve of phase overcurrent protection The correspondence between the start signal, operating signal, and operating accumulator in the inverse-time dropout characteristic is shown in the figure below: PCS-9613S Differential Relay 3-50 Date: 2020-09-02 3 Protection Functions Start time I>Ip Start signal Operating signal Protection operate Operating threshold 3 Operating counter tr Dropout time coefficient Dropout time Dropout time Figure 3.8-11 Inverse-time dropout characteristic of phase overcurrent protection 3.8.2 Function Block Diagram 50/51P 50/51Px.Enable 50/51Px.Block 50/51Px.On 50/51Px.Blocked 50/51Px.Valid 50/51Px.St 50/51Px.StA 50/51Px.StB 50/51Px.StC 50/51Px.Op 50/51Px.Op.PhA 50/51Px.Op.PhB 50/51Px.Op.PhC 50/51P.FwdDir.Op 50/51P.RevDir.Op 50/51Px.Alm PCS-9613S Differential Relay 3-51 Date: 2020-09-02 3 Protection Functions 3.8.3 I/O Signal Table 3.8-1 Input/output signals of phase overcurrent protection No. 1 50/51Px.Enable 2 50/51Px.Block No. 3 Input signal Description Stage x of phase overcurrent protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~6) Stage x of phase overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~6) Output signal Description 1 50/51Px.On Stage x of phase overcurrent protection is enabled 2 50/51Px.Blocked Stage x of phase overcurrent protection is blocked 3 50/51Px.Valid Stage x of phase overcurrent protection is valid 4 50/51Px.St Stage x of phase overcurrent protection starts 5 50/51Px.StA Stage x of phase overcurrent protection starts (Phase A) 6 50/51Px.StB Stage x of phase overcurrent protection starts (Phase B) 7 50/51Px.StC Stage x of phase overcurrent protection starts (Phase C) 8 50/51Px.Op Stage x of phase overcurrent protection operates 9 50/51Px.Op.PhA Stage x of phase overcurrent protection operates (Phase A) 10 50/51Px.Op.PhB Stage x of phase overcurrent protection operates (Phase B) 11 50/51Px.Op.PhC Stage x of phase overcurrent protection operates (Phase C) 12 50/51Px.Alm Stage x of phase overcurrent protection alarms 13 50/51P.FwdDir.Op The forward direction element of phase overcurrent protection operates 14 50/51P.RevDir.Op The reverse direction element of phase overcurrent protection operates PCS-9613S Differential Relay 3-52 Date: 2020-09-02 3 Protection Functions 3.8.4 Logic SET Ia>[50/51Px.I_Set] SIG 50/51P.VCE.Op_A EN [50/51Px.En_Volt_Blk] SIG 50/51P.FwdDir.Op_A SIG 50/51P.RevDir.Op_A SIG [50/51Px.Opt_Dir] SIG 50/51P.HMB.Op_A EN [50/51Px.En_Hm_Blk] SIG 50/51Px.Pkp SET [50/51Px.Opt_Trp/Alm]=Trp SET [50/51Px.Opt_Trp/Alm]=Alm SIG 50/51Px.StA SIG 50/51Px.StB SIG 50/51Px.StC SIG 50/51Px.Op.PhA SIG 50/51Px.Op.PhB SIG 50/51Px.Op.PhC SIG 50/51Px.Alm.PhA SIG 50/51Px.Alm.PhB SIG 50/51Px.Alm.PhC >=1 & Direction selection 50/51Px.StA & & Timer t & 3 & t 50/51Px.Op.PhA & 50/51Px.Alm.PhA >=1 50/51Px.St >=1 50/51Px.Op >=1 50/51Px.Alm Figure 3.8-12 Logic diagram of phase overcurrent protection 3.8.5 Settings ⚫ Access path: MainMenu Settings Protection Settings OC Settings Table 3.8-2 Settings of phase overcurrent protection No. Settings Default Range value Unit Step Description The low voltage blocking setting 1 50/51P.VCE.Upp 10~100 70 V 0.001 of the voltage control element of phase overcurrent protection PCS-9613S Differential Relay 3-53 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The negative-sequence voltage 2 50/51P.VCE.U2 2~57 8 V 0.001 blocking setting of the voltage control element of phase overcurrent protection The residual voltage setting (set 3 50/51P.VCE.3U0 2~57 8 V 0.001 according to 3U0) of voltage control element of phase overcurrent protection 3 The relay characteristic angle of 4 50/51P.DIR.RCA -180~179 45 deg 1 the direction control element of phase overcurrent protection The relay negative-sequence 5 50/51P.DIR.RCA_N egOC -180~179 45 deg 1 characteristic direction angle control of element the of phase overcurrent protection 6 7 8 9 50/51P.DIR.phi_Min _Fwd 50/51P.DIR.phi_Ma x_Fwd 50/51P.DIR.phi_Min _Rev 50/51P.DIR.phi_Ma x_Rev The minimum boundary of the 10~90 90 deg 1 forward direction element of phase overcurrent protection The maximum boundary of the 10~90 90 deg 1 forward direction element of phase overcurrent protection The minimum boundary of the 10~90 90 deg 1 reverse direction element of phase overcurrent protection The maximum boundary of the 10~90 90 deg 1 reverse direction element of phase overcurrent protection The voltage polarization mode for direction control element of phase overcurrent protection 10 50/51P.DIR.Opt_Pol arizedVolt Upp; Up; Upp: Upp - - U1 phase-to-phase voltage polarized Up: phase-to-ground voltage polarized U1: positive-sequence voltage polarized The minimum operating current 11 50/51P.DIR.I_Min (0.05~1)In 0.05 - 0.001 setting for the direction control element of phase overcurrent protection PCS-9613S Differential Relay 3-54 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The minimum operating voltage 12 50/51P.DIR.U_Min 1~10 4 V 0.001 setting for the direction control element of phase overcurrent protection Logic setting to determine the behaviour of phase overcurrent protection when VT circuit supervision function is enabled and VT circuit failure happens. 13 50/51P.En_VTS_Blk Disabled; Enabled Disabled - - Disabled: phase overcurrent protection will not affected by VT circuit failure Enabled: voltage controlled phase overcurrent protection will be blocked by VT circuit failure signal 14 50/51P.HMB.K_Hm 2 The 0.1~1 0.2 - 0.001 percent setting of the harmonic control element of phase overcurrent protection The current setting for releasing 15 50/51P.HMB.I_Rls 2~150 20 A 0.001 the harmonic control element of phase overcurrent protection The setting used to select the harmonic 16 50/51P.HMB.Opt_Bl k PhaseBlk CrossBlk blocking mode of phase overcurrent protection PhaseBlk - - MaxPhaseBlk PhaseBlk: phase blocking CrossBlk: cross blocking MaxPhaseBlk: maximum phase blocking 17 50/51P1.I_Set 0.05~200 15 A 0.001 The current setting of stage 1 of phase overcurrent protection The operating time setting of 18 50/51P1.t_Op 0 ~100 0.1 s 0.001 stage 1 of phase overcurrent protection The dropout time setting of 19 50/51P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase overcurrent protection PCS-9613S Differential Relay 3-55 Date: 2020-09-02 3 3 Protection Functions No. Settings Range Default value Unit Step Description The logic setting for enabling/disabling the voltage control element of stage 1 of phase overcurrent protection Disabled: stage 1 of phase 20 50/51P1.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element 3 Enabled: stage 1 of phase overcurrent protection is controlled by the voltage control element Non_Directional 21 50/51P1.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 1 of phase overcurrent protection. The logic setting for enabling/disabling the harmonic control element of stage 1 of phase overcurrent protection Disabled: stage 1 of phase 22 50/51P1.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 1 of phase overcurrent controlled protection by the is harmonic control element 23 50/51P1.En Disabled; Enabled The Enabled - - logic setting for enabling/disabling the stage 1 of phase overcurrent protection Enabling stage 1 of phase 24 50/51P1.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 3-56 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 25 50/51P1.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime - - IECV; inverse-time operation characteristic curve of stage 1 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 26 50/51P1.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 1 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 27 50/51P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase overcurrent protection The minimum operating time 28 50/51P1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of phase overcurrent protection The 29 50/51P1.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 1 of phase overcurrent protection The 30 50/51P1.Alpha 0.01 ~3 0.02 - 0.000 1 constant customized “α” of the inverse-time operation characteristic of stage 1 of phase overcurrent protection PCS-9613S Differential Relay 3-57 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range value Unit Step Description The 31 50/51P1.C 0 ~1 0 - 0.000 1 “C” constant customized of the inverse-time operation characteristic of stage 1 of phase overcurrent protection 32 50/51P2.I_Set 0.05~200 15 A 0.001 The current setting of stage 2 of phase overcurrent protection The operating time setting of 3 33 50/51P2.t_Op 0 ~100 0.1 s 0.001 stage 2 of phase overcurrent protection The dropout time setting of 34 50/51P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase overcurrent protection The logic setting for enabling/disabling the voltage control element of stage 2 of phase overcurrent protection Disabled: stage 2 of phase 35 50/51P2.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 2 of phase overcurrent protection is controlled by the voltage control element Non_Directional 36 50/51P2.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 2 of phase overcurrent protection. The logic setting for enabling/disabling the harmonic control element of stage 2 of phase overcurrent protection Disabled: stage 2 of phase 37 50/51P2.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 2 of phase overcurrent controlled protection by the is harmonic control element PCS-9613S Differential Relay 3-58 Date: 2020-09-02 3 Protection Functions No. 38 Settings 50/51P2.En Default Range Disabled; Enabled value Unit Step Description The Enabled - - logic setting for enabling/disabling the stage 2 of phase overcurrent protection Enabling stage 2 of phase 39 50/51P2.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 3 ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 40 50/51P2.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime - - IECV; inverse-time operation characteristic curve of stage 2 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 41 50/51P2.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 2 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 42 50/51P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase overcurrent protection The minimum operating time 43 50/51P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase overcurrent protection The 44 50/51P2.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 2 of phase overcurrent protection PCS-9613S Differential Relay 3-59 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The 45 50/51P2.Alpha 0.01 ~3 0.02 - 0.000 1 constant “α” customized of the inverse-time operation characteristic of stage 2 of phase overcurrent protection The 46 50/51P2.C 0 ~1 0 - 3 0.000 1 constant “C” customized of the inverse-time operation characteristic of stage 2 of phase overcurrent protection 47 50/51P3.I_Set 0.05~200 15 A 0.001 The current setting of stage 3 of phase overcurrent protection The operating time setting of 48 50/51P3.t_Op 0 ~100 0.1 s 0.001 stage 3 of phase overcurrent protection The dropout time setting of 49 50/51P3.t_DropOut 0 ~100 0 s 0.001 stage 3 of phase overcurrent protection The logic setting for enabling/disabling the voltage control element of stage 3 of phase overcurrent protection Disabled: stage 3 of phase 50 50/51P3.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 3 of phase overcurrent protection is controlled by the voltage control element Non_Directional 51 50/51P3.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 3 of phase overcurrent protection. PCS-9613S Differential Relay 3-60 Date: 2020-09-02 3 Protection Functions No. Settings Range Default value Unit Step Description The logic setting for enabling/disabling the harmonic control element of stage 3 of phase overcurrent protection Disabled: stage 3 of phase 52 50/51P3.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 3 of phase overcurrent controlled protection by the is harmonic control element 53 50/51P3.En Disabled; Enabled The Enabled - - logic setting for enabling/disabling the stage 3 of phase overcurrent protection Enabling stage 3 of phase 54 50/51P3.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 55 50/51P3.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime IECV; - - inverse-time operation characteristic curve of stage 3 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine PCS-9613S Differential Relay 3-61 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range value Unit Step Description The setting for selecting the inverse-time 56 50/51P3.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 3 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 3 57 50/51P3.TMS 0.04~ 20 1 - 0.001 stage 3 of phase overcurrent protection The minimum operating time 58 50/51P3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of phase overcurrent protection The 59 50/51P3.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 3 of phase overcurrent protection The 60 50/51P3.Alpha 0.01 ~3 0.02 - 0.000 1 constant customized “α” of the inverse-time operation characteristic of stage 3 of phase overcurrent protection The 61 50/51P3.C 0 ~1 0 - 0.000 1 constant customized “C” of the inverse-time operation characteristic of stage 3 of phase overcurrent protection 62 50/51P4.I_Set 0.05~200 15 A 0.001 The current setting of stage 4 of phase overcurrent protection The operating time setting of 63 50/51P4.t_Op 0 ~100 0.1 s 0.001 stage 4 of phase overcurrent protection The dropout time setting of 64 50/51P4.t_DropOut 0 ~100 0 s 0.001 stage 4 of phase overcurrent protection PCS-9613S Differential Relay 3-62 Date: 2020-09-02 3 Protection Functions No. Settings Range Default value Unit Step Description The logic setting for enabling/disabling the voltage control element of stage 4 of phase overcurrent protection Disabled: stage 4 of phase 65 50/51P4.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 4 of phase overcurrent protection is controlled by the voltage control element Non_Directional 66 50/51P4.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 4 of phase overcurrent protection. The logic setting for enabling/disabling the harmonic control element of stage 4 of phase overcurrent protection Disabled: stage 4 of phase 67 50/51P4.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 4 of phase overcurrent controlled protection by the is harmonic control element 68 50/51P4.En Disabled; Enabled The Enabled - - logic setting for enabling/disabling the stage 4 of phase overcurrent protection Enabling stage 4 of phase 69 50/51P4.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 3-63 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range value Unit Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 3 70 50/51P4.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime - - IECV; inverse-time operation characteristic curve of stage 4 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 71 50/51P4.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 4 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 72 50/51P4.TMS 0.04~ 20 1 - 0.001 stage 4 of phase overcurrent protection The minimum operating time 73 50/51P4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of phase overcurrent protection The 74 50/51P4.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 4 of phase overcurrent protection The 75 50/51P4.Alpha 0.01 ~3 0.02 - 0.000 1 constant customized “α” of the inverse-time operation characteristic of stage 4 of phase overcurrent protection PCS-9613S Differential Relay 3-64 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The 76 50/51P4.C 0 ~1 0 - 0.000 1 constant “C” customized of the inverse-time operation characteristic of stage 4 of phase overcurrent protection 77 50/51P5.I_Set 0.05~200 15 A 0.001 The current setting of stage 5 of phase overcurrent protection The operating time setting of 78 50/51P5.t_Op 0 ~100 0.1 s 0.001 stage 5 of phase overcurrent protection The dropout time setting of 79 50/51P5.t_DropOut 0 ~100 0 s 0.001 stage 5 of phase overcurrent protection The logic setting for enabling/disabling the voltage control element of stage 5 of phase overcurrent protection Disabled: stage 5 of phase 80 50/51P5.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 5 of phase overcurrent protection is controlled by the voltage control element Non_Directional 81 50/51P5.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 5 of phase overcurrent protection. The logic setting for enabling/disabling the harmonic control element of stage 5 of phase overcurrent protection Disabled: stage 5 of phase 82 50/51P5.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 5 of phase overcurrent controlled protection by the is harmonic control element PCS-9613S Differential Relay 3-65 Date: 2020-09-02 3 3 Protection Functions No. 83 Settings 50/51P5.En Default Range Disabled; Enabled value Unit Step Description The Enabled - - logic setting for enabling/disabling the stage 5 of phase overcurrent protection Enabling stage 5 of phase 84 50/51P5.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 3 ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 85 50/51P5.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime - - IECV; inverse-time operation characteristic curve of stage 5 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 86 50/51P5.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 5 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 87 50/51P5.TMS 0.04~ 20 1 - 0.001 stage 5 of phase overcurrent protection The minimum operating time 88 50/51P5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of phase overcurrent protection The 89 50/51P5.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 5 of phase overcurrent protection PCS-9613S Differential Relay 3-66 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The 90 50/51P5.Alpha 0.01 ~3 0.02 - 0.000 1 constant “α” customized of the inverse-time operation characteristic of stage 5 of phase overcurrent protection The 91 50/51P5.C 0 ~1 0 - 0.000 1 constant “C” customized of the inverse-time operation characteristic of stage 5 of phase overcurrent protection 92 50/51P6.I_Set 0.05~200 15 A 0.001 The current setting of stage 6 of phase overcurrent protection The operating time setting of 93 50/51P6.t_Op 0 ~100 0.1 s 0.001 stage 6 of phase overcurrent protection The dropout time setting of 94 50/51P6.t_DropOut 0 ~100 0 s 0.001 stage 6 of phase overcurrent protection The logic setting for enabling/disabling the voltage control element of stage 6 of phase overcurrent protection Disabled: stage 6 of phase 95 50/51P6.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 6 of phase overcurrent protection is controlled by the voltage control element Non_Directional 96 50/51P6.Opt_Dir Forward Reverse Non_Directio nal PCS-9613S Differential Relay The setting used to select the - - directional mode of stage 6 of phase overcurrent protection. 3-67 Date: 2020-09-02 3 3 Protection Functions No. Settings Range Default value Unit Step Description The logic setting for enabling/disabling the harmonic control element of stage 6 of phase overcurrent protection Disabled: stage 6 of phase 97 50/51P6.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element 3 Enabled: stage 6 of phase overcurrent controlled protection by the is harmonic control element 98 50/51P6.En Disabled; Enabled The Enabled - - logic setting for enabling/disabling the stage 6 of phase overcurrent protection Enabling stage 6 of phase 99 50/51P6.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 100 50/51P6.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime IECV; - - inverse-time operation characteristic curve of stage 6 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine PCS-9613S Differential Relay 3-68 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The setting for selecting the inverse-time 101 50/51P6.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 6 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 102 50/51P6.TMS 0.04~ 20 1 - 0.001 stage 6 of phase overcurrent protection The minimum operating time 103 50/51P6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of phase overcurrent protection The 104 50/51P6.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 6 of phase overcurrent protection The 105 50/51P6.Alpha 0.01 ~3 0.02 - 0.000 1 constant customized “α” of the inverse-time operation characteristic of stage 6 of phase overcurrent protection The 106 50/51P6.C 0 ~1 0 - 0.000 1 constant customized “C” of the inverse-time operation characteristic of stage 6 of phase overcurrent protection 3.9 Earth Fault Overcurrent Protection (50/51G) The normal operating power system is three-phase symmetrical, its zero-sequence current and voltage are theoretically zero. Most of the faults are three-phase asymmetrical, according to the asymmetry of the fault, various protections reflect sequence component principle can be constituted. Earth fault overcurrent protection has been widely used in power systems, it can be used for the fault conditions that zero-sequence fault current flows into the earth, including single-phase earth fault and phase-to-phase short-circuit earth fault etc.. 3.9.1 Function Description The device can provide six stages of earth fault overcurrent protection with independent logic. Each stage can be independently set as definite-time characteristics or inverse-time characteristics. The dropout characteristics can be set as instantaneous dropout, definite-time PCS-9613S Differential Relay 3-69 Date: 2020-09-02 3 3 Protection Functions dropout or inverse-time dropout. Users can choose whether it is blocked by the direction control element or the harmonic control element, users can also choose whether it is controlled by cold load pickup. The direction control element can be set as no direction, forward direction and reverse direction. The zero-sequence current used by earth fault overcurrent protection can be calculated zero-sequence current or the measured zero-sequence current, it can operate to trip or alarm, it can be enabled or blocked by the external binary input. 3 Earth fault overcurrent protection can be enabled or disabled via the settings or binary input signals, for some specific applications, the protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block earth fault overcurrent protection. The enabling and blocking logic of earth fault overcurrent protection is shown in the figure below: EN 50/51Gx.En SIG 50/51Gx.Enable SIG 50/51Gx.Block SIG Fail_Device & 50/51Gx.On & ≥1 50/51Gx.Blocked & 50/51Gx.Valid Figure 3.9-1 The enabling and blocking logic of earth fault overcurrent protection The logic diagram of the fault detector element of earth fault overcurrent protection is as follows: SET 3I0>0.95*[50/51Gx.3I0_Set] & 0 SIG 50/51Gx.On SIG 50/51Gx.Valid EN [50/51Gx.Opt_Trp/Alm]=Alm 500ms 50/51Gx.Pkp & & FD.Pkp Figure 3.9-2 Logic diagram of the fault detector element of earth fault overcurrent protection 3.9.1.1 Direction Control Element In order to ensure the selectivity of earth fault overcurrent protection, direction control element is introduced. The setting [50/51Gx.Opt_Dir] (x=1~6) is used for users to select the directional mode of each stage of earth fault overcurrent protection: no direction, forward direction and reverse direction are selectable. The operation boundary of the forward direction element can be set by [50/51G.DIR.phi_Min_Fwd] and [50/51G.DIR.phi_Max_Fwd]. The operation boundary of the reverse direction element can be set by [50/51G.DIR.phi_Min_Rev] and [50/51G.DIR.phi_Max_Rev]. PCS-9613S Differential Relay 3-70 Date: 2020-09-02 3 Protection Functions -U0 [50/51G.DIR.phi_Min_Fwd] Non-operating area I0 Operating area in forward direction [50/51G.DIR.phi_Max_Rev] [50/51G.DIR.RCA] 3 Operating area in reverse direction [50/51G.DIR.phi_Max_Fwd] [50/51G.DIR.phi_Min_Rev] Non-operating area Figure 3.9-3 The direction element operation characteristics when zero-sequence voltage is polarized Where: The sensitivity angle of the direction control element (RCA) can be set by the setting [50/51G.DIR.RCA]. The forward direction characteristic is: -[50/51G.DIR.phi_Min_Fwd]<angle<[50/51G.DIR.phi_Max_Fwd] The reverse direction characteristic is: 180-[50/51G.DIR.phi_Min_Rev]<angle<180+[50/51G.DIR.phi_Max_Rev] The following table shows the relationship between the operating current, the polarized voltage and the polarization mode. Polarization mode Operating current Polarized voltage Angle difference Zero-sequence Calculated residual current 3I0_Cal -3U0 angle=angle(-3U0)-angle(3I0_Cal)-RCA voltage polarized Measured residual current 3I0_Ext -3U0 angle=angle(-3U0)-angle(3I0_Ext)-RCA The direction element calculation needs to judge the current threshold and voltage threshold. The corresponding operating current must be greater than the minimum operating current setting [50/51G.DIR.3I0_Min], otherwise the direction element can not operate. The polarized voltage must be greater than the minimum operating voltage setting [50/51G.DIR.3U0_Min], otherwise the direction element can not operate. The logic diagram of the forward direction element and reverse direction element is as follows. PCS-9613S Differential Relay 3-71 Date: 2020-09-02 3 Protection Functions EN [50/51G.En_VTS_Blk] & SIG VTS.Alm SIG 3U0_Cal EN 3 [En_VT] >=1 & Forward direction criterion SIG 3I0_Ext, 3I0_Cal & 50/51G.FwdDir.Op & SIG Prot.BI_En_VT SET Iop>[50/51G.DIR.3I0_Min] SET Upo>[50/51G.DIR.3U0_Min] EN [50/51G.En_VTS_Blk] & SIG VTS.Alm SIG 3U0_Cal EN [En_VT] Reverse direction criterion SIG 3I0_Ext, 3I0_Cal & >=1 & 50/51G.RevDir.Op & SIG Prot.BI_En_VT SET Iop>[50/51G.DIR.3I0_Min] SET Upo>[50/51G.DIR.3U0_Min] Figure 3.9-4 Logic diagram of forward and reverse direction element of earth fault overcurrent protection Where: 3I0_Ext is the measured residual current. 3I0_Cal is the calculated residual current. 3U0_Cal: the calculated residual voltage Iop: the operating current. Upo: the polarized voltage. 3.9.1.2 Harmonic Control Element Zero-sequence harmonic control element can be used together with earth fault overcurrent protection when harmonic blocking is required, the zero-sequence current can be the calculated zero-sequence current or the measured zero-sequence current. PCS-9613S Differential Relay 3-72 Date: 2020-09-02 3 Protection Functions When the percentage of the second harmonic component to fundamental component of residual current is greater than the setting [50/51G.HMB.K_Hm2], harmonic blocking element operates to block stage x of earth fault protection if corresponding logic setting [50/51Gx.En_Hm_Blk] is enabled. When the fundamental zero-sequence current is greater than the setting [50/51G.HMB.I_Rls], the harmonic blocking element is released. The following figure shows the logic diagram of the harmonic control element of earth fault overcurrent protection. SET 3 3I0>[50/51G.HMB.I_Rls] & SIG 3I0_Ext or 3I0_Cal 50/51G.Hm_Op Harmonic blocking logi c SET 3I02/3I0>[50/51G.HMB.K_Hm2] Figure 3.9-5 Logic diagram of harmonic control element of earth fault overcurrent protection Where: 3I0_Ext, 3I0_Cal: the measured residual current and the calculated residual current 3I02: the 2nd harmonic residual current 3.9.1.3 Operation Characteristic Earth fault overcurrent protection can operate without time delay or operate with a definite-time limit, it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards. Earth fault overcurrent protection can support definite-time limit, IEC & ANSI standard inverse time limit and user-defined inverse-time limit, users can select the wanted operating curve by the setting [50/51Gx.Opt_Curve], the relationship between the value of the setting and the curve is shown in the table below. 50/51Gx.Opt_Curve Time Characteristic α k c tr ANSIE ANSI Extremely Inverse 28.2 2.0 0.1217 29.1 ANSIV ANSI Very inverse 19.61 2.0 0.491 21.6 ANSIN ANSI Normal Inverse 0.0086 0.02 0.0185 0.46 ANSIM ANSI Moderately Inverse 0.0515 0.02 0.114 4.85 ANSIDefTime ANSI Definite Time - - - - ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30 ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46 ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6 IECN IEC Normal Inverse 0.14 0.02 0 - IECV IEC Very inverse 13.5 1.0 0 - IEC IEC Inverse 0.14 0.02 0 - IECE IEC Extremely inverse 80.0 2.0 0 - IECST IEC Short-time inverse 0.05 0.04 0 - PCS-9613S Differential Relay 3-73 Date: 2020-09-02 3 Protection Functions 50/51Gx.Opt_Curve Time Characteristic α k c tr IECLT IEC Long-time inverse 120.0 1.0 0 - IECDefTime IEC Definite Time - - - - UserDefine Programmable Only when the setting [50/51Gx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time characteristic is selected, the settings [50/51Gx.K], [50/51Gx.C] and [50/51Gx.Alpha] are useful, the inverse-time operating curve is determined by the three settings. ⚫ 3 Without time delay When I 0 > I 0 p , the protection operates immediately. ⚫ Definite-time characteristic When I 0 > I 0 p , the protection operates with a time delay of top (i.e. the value of the setting [50/51Gx.t_Op]), and the operation characteristic curve is shown in the following figure: t t op I0p I0 Figure 3.9-6 Definite-time operation characteristic curve of earth fault overcurrent protection ⚫ Inverse-time characteristic When I 0 > I 0 p , the inverse-time accumulator begins to accumulate, and the operating time is affected by the applied current I 0 . The larger current is, the smaller the operating time is, but not unlimited. When the current is large enough to a certain threshold ( I 0 p ), the inverse-time operating time will not continue to decrease, then the operation characteristic becomes the definite-time characteristic, and the operating time is tmin , i.e. the setting [50/51Gx.tmin]. The inverse-time operation characteristic equation is: + c TMS (I 0 / I 0P ) − 1 t = k Where: I 0 p is the current setting [50/51Gx.3I0_Set]; PCS-9613S Differential Relay 3-74 Date: 2020-09-02 3 Protection Functions TMS is the inverse-time time multiplier, i.e. the setting [50/51Gx.TMS]; k is the inverse-time coefficient K, i.e. the setting [50/51Gx.K]; c is the inverse-time coefficient C, i.e. the setting [50/51Gx.C]; is the inverse-time coefficient Alpha, i.e. the setting [50/51Gx.Alpha]; I 0 is the measured zero-sequence current. The inverse-time operation characteristic curve is shown as below: t 3 t min I0P ID I0 Figure 3.9-7 Inverse-time operation characteristic curve of earth fault overcurrent protection When the applied zero-sequence current I 0 is not a fixed value, but changes with time, the operating behaviour of the protection is shown in the following equation: T0 1 t ( I )dt 0 =1 0 Where: T0 is the operating time of the protection element; t(I0) is the theoretical operating time when the current is I 0 . 3.9.1.4 Dropout Characteristic The supported dropout characteristics of the earth fault overcurrent protection include instantaneous dropout, definite-time dropout and ANSI inverse-time dropout. When the operating curve is selected as definite-time, IEC inverse-time or user-defined inverse-time characteristic, the dropout characteristic can only be selected as instantaneous dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal "Fail_Settings" will be issued and the device will be blocked. PCS-9613S Differential Relay 3-75 Date: 2020-09-02 3 Protection Functions When the operating curve is selected as ANSI inverse-time characteristic, the dropout characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI inverse-time dropout. ⚫ Instantaneous dropout When I 0 <0.95* I 0 p , the protection drops out immediately. ⚫ Definite-time dropout When I 0 <0.95* I 0 p , the protection drops out with a time delay of tdr (i.e. the value of the setting [50/51Gx.t_DropOut]), the dropout characteristic curve is shown in the following figure: 3 Start time I0>I0p Start signal Operating signal Protection operate Operating threshold Operating counter t dr Dropout time setting t dr t dr Dropout time Dropout time Figure 3.9-8 Definite-time dropout characteristic of earth fault overcurrent protection ⚫ Inverse-time dropout When I 0 > I 0 p , the inverse-time operating accumulator begins to accumulate, the accumulated value after t p (Assuming t p is less than the theoretical operating time) is calculated according to the following equation: tp Itp = 1 t(I 0 dt 0 ) At this time, if I 0 <0.95* I 0 p , the protection element starts dropout, and the dropout characteristic meets the following equation: PCS-9613S Differential Relay 3-76 Date: 2020-09-02 3 Protection Functions TR 1 dt = 0 t ( I ) R 0 I tp − Where: T R is the dropout time; tR( I ) is the dropout characteristic equation When I 0 <0.95* I 0 p , the inverse-time dropout characteristic equation is as follows: 3 tr tR = TMS 2 1 − ( I 0 / I 0 P ) Where: I0P is the current setting [50/51Gx.3I0_Set]; TMS is the inverse-time factor, i.e. the setting [50/51Gx.TMS]; tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after the protection operates. I 0 is the measured current. When 0.95* I 0 p < I 0 < I 0 p , the accumulator will neither accumulate nor drop out The inverse time dropout characteristic curve is shown in the figure below. t tr I0 P I0 Figure 3.9-9 Inverse-time dropout characteristic curve of earth fault overcurrent protection The correspondence between the start signal, operating signal, and operating accumulator in the PCS-9613S Differential Relay 3-77 Date: 2020-09-02 3 Protection Functions inverse-time dropout characteristic is shown in the figure below: Start time I0>I0p Start signal Operating signal 3 Protection operate Operating threshold Operating counter tr Dropout time coefficient Dropout time Dropout time Figure 3.9-10 Inverse-time dropout characteristic of earth fault overcurrent protection 3.9.2 Function Block Diagram 50/51G 50/51Gx.On 50/51Gx.Enable 50/51Gx.Block 50/51Gx.Blocked 50/51Gx.Valid 50/51Gx.St 50/51Gx.Op 50/51Gx.Alm 50/51Gx.FwdDir.Op 50/51Gx.RevDir.Op 3.9.3 I/O Signal Table 3.9-1 Input/output signals of earth fault overcurrent protection No. Input signal 1 50/51Gx.Enable 2 50/51Gx.Block Description Stage x of earth fault overcurrent protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~6) Stage x of earth fault overcurrent protection blocking input, it is triggered from PCS-9613S Differential Relay 3-78 Date: 2020-09-02 3 Protection Functions binary input or programmable logic etc. (x=1~6) No. Output signal Description 1 50/51Gx.On Stage x of earth fault overcurrent protection is enabled 2 50/51Gx.Blocked Stage x of earth fault overcurrent protection is blocked 3 50/51Gx.Valid Stage x of earth fault overcurrent protection is valid 4 50/51Gx.St Stage x of earth fault overcurrent protection starts 5 50/51Gx.Op Stage x of earth fault overcurrent protection operates 6 50/51Gx.Alm Stage x of earth fault overcurrent protection alarms 7 50/51G.FwdDir.Op The forward direction element of earth fault overcurrent protection operates 8 50/51G.RevDir.Op The reverse direction element of earth fault overcurrent protection operates 3.9.4 Logic 3I0>[50/51Gx.3I0_Set] SIG 50/51G.FwdDir.Op SIG 50/51G.RevDir.Op SET [50/51Gx.Opt_Dir] SIG 50/51G.HMB.Op EN [50/51Gx.En_Hm_Blk] SIG 50/51Gx.Pkp SET [50/51Gx.Opt_Trp/Alm]=Trp Direction selection SET 50/51Gx.St & Timer t & t & & 50/51Gx.Op & 50/51Gx.Alm SET [50/51Gx.Opt_Trp/Alm]=Alm Figure 3.9-11 Logic diagram of earth fault overcurrent protection 3.9.5 Settings ⚫ Access path: MainMenu Settings Protection Settings ROC Settings Table 3.9-2 Settings of earth fault overcurrent protection No. Settings Range Default Unit value Step Description The relay characteristic angle 1 50/51G.DIR.RCA -180~179 45 deg 1 of the element direction of earth control fault overcurrent protection PCS-9613S Differential Relay 3-79 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range Unit value Step Description The minimum boundary of the 2 50/51G.DIR.phi_Min_ Fwd 10~90 90 deg 1 forward direction element of earth fault overcurrent protection The maximum boundary of the 3 50/51G.DIR.phi_Max_ Fwd 10~90 90 deg 1 forward direction element of earth fault overcurrent protection 3 The minimum boundary of the 4 50/51G.DIR.phi_Min_ Rev 10~90 90 deg 1 reverse direction element of earth fault overcurrent protection The maximum boundary of the 5 50/51G.DIR.phi_Max_ Rev 10~90 90 deg 1 reverse direction element of earth fault overcurrent protection The 6 50/51G.DIR.3I0_Min (0.05~1)In 0.05 - 0.001 minimum operating current setting for the direction control element of earth fault overcurrent protection The 7 50/51G.DIR.3U0_Min 1~10 4 V 0.001 minimum operating voltage setting for the direction control element of earth fault overcurrent protection Logic setting to determine the behaviour of earth fault overcurrent protection when VT circuit supervision function is enabled and VT circuit 8 50/51G.En_VTS_Blk Disabled; Enabled failure happens. Disabled - - Disabled: earth fault overcurrent protection will not affected by VT circuit failure Enabled: earth voltage controlled fault overcurrent protection will be blocked by VT circuit failure signal The percent setting of the 9 50/51G.HMB.K_Hm2 0.1~1 0.2 - 0.001 harmonic control element of earth fault overcurrent protection PCS-9613S Differential Relay 3-80 Date: 2020-09-02 3 Protection Functions No. Settings Default Range Unit value Step Description The 10 50/51G.HMB.I_Rls 2~150 20 A 0.001 current setting for releasing the harmonic control element of earth fault overcurrent protection The setting used to select the residual current that used for stage 11 50/51G1.Opt_3I0 Ext; Cal Ext - - 1 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 1 12 50/51G1.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection The operating time setting of 13 50/51G1.t_Op 0 ~100 0.1 s 0.001 stage 1 of earth fault overcurrent protection The dropout time setting of 14 50/51G1.t_DropOut 0 ~100 0 s 0.001 stage 1 of earth fault overcurrent protection Non_Direction 15 50/51G1.Opt_Dir The setting used to select the al; Non_Direct Forward; ional - - Reverse directional mode of stage 1 of earth fault overcurrent protection. The logic setting enabling/disabling for the harmonic control element of the stage 1 of earth fault overcurrent protection 16 50/51G1.En_Hm_Blk Disabled; Enabled Disabled: stage 1 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 1 of earth fault overcurrent protection is controlled by the harmonic control element The 17 50/51G1.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 1 of earth fault overcurrent protection PCS-9613S Differential Relay 3-81 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range Unit value Step Description Enabling stage 1 earth fault 18 50/51G1.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; 3 ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 19 50/51G1.Opt_Curve ANSILT; IECDefTim IECN; e inverse-time - - characteristic curve of stage 1 of IECV; operation earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 20 50/51G1.Opt_Curve_ DropOut characteristic curve of stage 1 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 21 50/51G1.TMS 0.04~ 20 1 - 0.001 stage 1 of earth fault overcurrent protection The minimum operating time 22 50/51G1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of earth fault overcurrent protection The constant customized 23 50/51G1.K 0.001~120 0.14 - 0.0001 “k” of operation characteristic stage of 1 the inverse-time earth of fault overcurrent protection PCS-9613S Differential Relay 3-82 Date: 2020-09-02 3 Protection Functions No. Settings Default Range Unit value Step Description The constant customized 24 50/51G1.Alpha 0.01 ~3 0.02 - 0.0001 “α” of inverse-time operation characteristic stage of 1 the earth of fault overcurrent protection The constant customized 25 50/51G1.C 0 ~1 0 - 0.0001 “C” of inverse-time operation characteristic stage of 1 the earth of fault overcurrent protection The setting used to select the residual current that used for stage 26 50/51G2.Opt_3I0 Ext; Cal Ext - - 2 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 2 27 50/51G2.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection The operating time setting of 28 50/51G2.t_Op 0 ~100 0.1 s 0.001 stage 2 of earth fault overcurrent protection The dropout time setting of 29 50/51G2.t_DropOut 0 ~100 0 s 0.001 stage 2 of earth fault overcurrent protection Non_Direction 30 50/51G2.Opt_Dir The setting used to select the al; Non_Direct Forward; ional - Reverse - directional mode of stage 2 of earth fault overcurrent protection. PCS-9613S Differential Relay 3-83 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range Unit value Step Description The logic setting enabling/disabling for the harmonic control element of the stage 2 of earth fault overcurrent protection 31 50/51G2.En_Hm_Blk Disabled; Enabled Disabled: stage 2 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic 3 control element Enabled: stage 2 of earth fault overcurrent protection is controlled by the harmonic control element The 32 50/51G2.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 2 of earth fault overcurrent protection Enabling stage 2 earth fault 33 50/51G2.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 34 50/51G2.Opt_Curve ANSILT; IECDefTim IECN; e inverse-time - IECV; - operation characteristic curve of stage 2 of earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine PCS-9613S Differential Relay 3-84 Date: 2020-09-02 3 Protection Functions No. Settings Default Range Unit value Step Description The setting for selecting the inverse-time 35 50/51G2.Opt_Curve_ DropOut characteristic curve of stage 2 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 36 50/51G2.TMS 0.04~ 20 1 - 0.001 stage 2 of earth fault overcurrent protection The minimum operating time 37 50/51G2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of earth fault overcurrent protection The constant customized 38 50/51G2.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 2 the earth of fault overcurrent protection The constant customized 39 50/51G2.Alpha 0.01 ~3 0.02 - 0.0001 “α” of inverse-time operation characteristic stage of 2 the earth of fault overcurrent protection The constant customized 40 50/51G2.C 0 ~1 0 - 0.0001 “C” of operation characteristic stage of 2 the inverse-time earth of fault overcurrent protection The setting used to select the residual current that used for stage 41 50/51G3.Opt_3I0 Ext; Cal Ext - - 3 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 3 42 50/51G3.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection PCS-9613S Differential Relay 3-85 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range Unit value Step Description The operating time setting of 43 50/51G3.t_Op 0 ~100 0.1 s 0.001 stage 3 of earth fault overcurrent protection The dropout time setting of 44 50/51G3.t_DropOut 0 ~100 0 s 0.001 stage 3 of earth fault overcurrent protection Non_Direction 3 45 50/51G3.Opt_Dir The setting used to select the al; Non_Direct Forward; ional - - Reverse directional mode of stage 3 of earth fault overcurrent protection. The logic setting enabling/disabling for the harmonic control element of the stage 3 of earth fault overcurrent protection 46 50/51G3.En_Hm_Blk Disabled; Enabled Disabled: stage 3 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 3 of earth fault overcurrent protection is controlled by the harmonic control element The 47 50/51G3.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 3 of earth fault overcurrent protection Enabling stage 3 earth fault 48 50/51G3.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 3-86 Date: 2020-09-02 3 Protection Functions No. Settings Default Range Unit value Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 49 50/51G3.Opt_Curve ANSILT; IECDefTim IECN; e inverse-time - - characteristic curve of stage 3 of IECV; operation earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 50 50/51G3.Opt_Curve_ DropOut characteristic curve of stage 3 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 51 50/51G3.TMS 0.04~ 20 1 - 0.001 stage 3 of earth fault overcurrent protection The minimum operating time 52 50/51G3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of earth fault overcurrent protection The constant customized 53 50/51G3.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 3 the earth of fault overcurrent protection The constant customized 54 50/51G3.Alpha 0.01 ~3 0.02 - 0.0001 “α” of operation characteristic stage of 3 the inverse-time earth of fault overcurrent protection PCS-9613S Differential Relay 3-87 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range Unit value Step Description The constant “C” customized 55 50/51G3.C 0 ~1 0 - 0.0001 of the inverse-time operation characteristic stage of 3 earth of fault overcurrent protection The setting used to select the residual current that used for stage 3 56 50/51G4.Opt_3I0 Ext; Cal Ext - - 4 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 4 57 50/51G4.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection The operating time setting of 58 50/51G4.t_Op 0 ~100 0.1 s 0.001 stage 4 of earth fault overcurrent protection The dropout time setting of 59 50/51G4.t_DropOut 0 ~100 0 s 0.001 stage 4 of earth fault overcurrent protection Non_Direction 60 50/51G4.Opt_Dir The setting used to select the al; Non_Direct Forward; ional - - Reverse directional mode of stage 4 of earth fault overcurrent protection. The logic setting enabling/disabling for the harmonic control element of the stage 4 of earth fault overcurrent protection 61 50/51G4.En_Hm_Blk Disabled; Enabled Disabled: stage 4 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 4 of earth fault overcurrent protection is controlled by the harmonic control element PCS-9613S Differential Relay 3-88 Date: 2020-09-02 3 Protection Functions No. Settings Default Range Unit value Step Description The 62 50/51G4.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 4 of earth fault overcurrent protection Enabling stage 4 earth fault 63 50/51G4.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose 3 Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 64 50/51G4.Opt_Curve ANSILT; IECDefTim IECN; e inverse-time - - characteristic curve of stage 4 of IECV; operation earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 65 50/51G4.Opt_Curve_ DropOut characteristic curve of stage 4 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 66 50/51G4.TMS 0.04~ 20 1 - 0.001 stage 4 of earth fault overcurrent protection The minimum operating time 67 50/51G4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of earth fault overcurrent protection PCS-9613S Differential Relay 3-89 Date: 2020-09-02 3 Protection Functions No. Settings Default Range Unit value Step Description The constant customized 68 50/51G4.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 4 the earth of fault overcurrent protection The constant customized 69 50/51G4.Alpha 0.01 ~3 0.02 - 0.0001 3 “α” of inverse-time operation characteristic stage of 4 the earth of fault overcurrent protection The constant customized 70 50/51G4.C 0 ~1 0 - 0.0001 “C” of operation characteristic stage of 4 the inverse-time earth of fault overcurrent protection The setting used to select the residual current that used for stage 71 50/51G5.Opt_3I0 Ext; Cal Ext - - 5 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 5 72 50/51G5.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection The operating time setting of 73 50/51G5.t_Op 0 ~100 0.1 s 0.001 stage 5 of earth fault overcurrent protection The dropout time setting of 74 50/51G5.t_DropOut 0 ~100 0 s 0.001 stage 5 of earth fault overcurrent protection Non_Direction 75 50/51G5.Opt_Dir The setting used to select the al; Non_Direct Forward; ional - Reverse - directional mode of stage 5 of earth fault overcurrent protection. PCS-9613S Differential Relay 3-90 Date: 2020-09-02 3 Protection Functions No. Settings Default Range Unit value Step Description The logic setting enabling/disabling for the harmonic control element of the stage 5 of earth fault overcurrent protection 76 50/51G5.En_Hm_Blk Disabled; Enabled Disabled: stage 5 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 5 of earth fault overcurrent protection is controlled by the harmonic control element The 77 50/51G5.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 5 of earth fault overcurrent protection Enabling stage 5 earth fault 78 50/51G5.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 79 50/51G5.Opt_Curve ANSILT; IECDefTim IECN; e inverse-time - IECV; - operation characteristic curve of stage 5 of earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine PCS-9613S Differential Relay 3-91 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range Unit value Step Description The setting for selecting the inverse-time 80 50/51G5.Opt_Curve_ DropOut characteristic curve of stage 5 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout 3 The time multiplier setting of 81 50/51G5.TMS 0.04~ 20 1 - 0.001 stage 5 of earth fault overcurrent protection The minimum operating time 82 50/51G5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of earth fault overcurrent protection The constant customized 83 50/51G5.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 5 the earth of fault overcurrent protection The constant customized 84 50/51G5.Alpha 0.01 ~3 0.02 - 0.0001 “α” of inverse-time operation characteristic stage of 5 the earth of fault overcurrent protection The constant customized 85 50/51G5.C 0 ~1 0 - 0.0001 “C” of operation characteristic stage of 5 the inverse-time earth of fault overcurrent protection The setting used to select the residual current that used for stage 86 50/51G6.Opt_3I0 Ext; Cal Ext - - 6 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 6 87 50/51G6.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection PCS-9613S Differential Relay 3-92 Date: 2020-09-02 3 Protection Functions No. Settings Default Range Unit value Step Description The operating time setting of 88 50/51G6.t_Op 0 ~100 0.1 s 0.001 stage 6 of earth fault overcurrent protection The dropout time setting of 89 50/51G6.t_DropOut 0 ~100 0 s 0.001 stage 6 of earth fault overcurrent protection Non_Direction 90 50/51G6.Opt_Dir The setting used to select the al; Non_Direct Forward; ional - - Reverse directional mode of stage 6 of earth fault overcurrent protection. The logic setting enabling/disabling for the harmonic control element of the stage 6 of earth fault overcurrent protection 91 50/51G6.En_Hm_Blk Disabled; Enabled Disabled: stage 6 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 6 of earth fault overcurrent protection is controlled by the harmonic control element The 92 50/51G6.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 6 of earth fault overcurrent protection Enabling stage 6 earth fault 93 50/51G6.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 3-93 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range Unit value Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 3 94 50/51G6.Opt_Curve ANSILT; IECDefTim IECN; e inverse-time - - characteristic curve of stage 6 of IECV; operation earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 95 50/51G6.Opt_Curve_ DropOut characteristic curve of stage 6 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 96 50/51G6.TMS 0.04~ 20 1 - 0.001 stage 6 of earth fault overcurrent protection The minimum operating time 97 50/51G6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of earth fault overcurrent protection The constant customized 98 50/51G6.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 6 the earth of fault overcurrent protection The constant customized 99 50/51G6.Alpha 0.01 ~3 0.02 - 0.0001 “α” of operation characteristic stage of 6 the inverse-time earth of fault overcurrent protection PCS-9613S Differential Relay 3-94 Date: 2020-09-02 3 Protection Functions No. Settings Default Range Unit value Step Description The constant customized 100 50/51G6.C 0 ~1 0 - 0.0001 “C” of inverse-time operation characteristic stage of 6 the earth of fault overcurrent protection 3.10 Negative-sequence Overcurrent Protection (50/51Q) When a phase-to-phase fault occurs in the system, the fault current is small, and the phase current criterion may not be able to detect the fault. At this time, the negative-sequence overcurrent protection with higher sensitivity can be used. Negative-sequence overcurrent protection can also be used to detect the broken phase operation or load unbalance. 3.10.1 Function Description The device can provide two stages of negative-sequence overcurrent protection with independent logic. Each stage can be independently set as definite-time characteristics or inverse-time characteristics. The dropout characteristics can be set as instantaneous dropout, definite-time dropout or inverse-time dropout. For a double-circuit or a ring network line, the negative-sequence fault current may have different flow direction. Considering the protection selectivity, the negative-sequence overcurrent protection can be blocked by the direction control element. Negative-sequence overcurrent protection can operate to trip or alarm, it can be enabled or blocked by the external binary input. Negative-sequence overcurrent protection can be enabled or disabled via the settings or binary input signals, for some specific applications, the protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block negative-sequence overcurrent protection. The enabling and blocking logic of negative-sequence overcurrent protection is shown in the figure below: EN [50/51Qx.En] SIG 50/51Qx.Enable SIG 50/51Qx.Block SIG Fail_Device & 50/51Qx.On & ≥1 50/51Qx.Blocked & 50/51Qx.Valid Figure 3.10-1 The enabling and blocking logic of negative-sequence overcurrent protection The logic diagram of the fault detector element of negative-sequence overcurrent protection is as follows: PCS-9613S Differential Relay 3-95 Date: 2020-09-02 3 3 Protection Functions SET I2>0.95×[50/51Qx.I2_Set] & 0 500ms & SIG 50/51Qx.On 50/51Qx.Pkp & FD.Pkp SIG 50/51Qx.Valid SET [50/51Qx.Opt_Trp/Alm]=Alm Figure 3.10-2 Logic diagram of the fault detector element of negative-sequence overcurrent protection 3.10.1.1 Direction Control Element 3 In order to ensure the selectivity of negative-sequence overcurrent protection, direction control element is introduced. The setting [50/51Qx.Opt_Dir] (x=1 and 2) is used for users to select the directional mode of each stage of negative-sequence overcurrent protection: no direction, forward direction and reverse direction are selectable. The operation boundary of the forward direction element can be set by [50/51Q.DIR.phi_Min_Fwd] and [50/51Q.DIR.phi_Max_Fwd]. The operation boundary of the reverse direction element can be set by [50/51Q.DIR.phi_Min_Rev] and [50/51Q.DIR.phi_Max_Rev]. For the direction control element of negative-sequence overcurrent protection, negative-sequence voltage is polarized, the operation characteristic is shown as below. the -U2 [50/51Q.DIR.phi_Min_Fwd] Non-operating area I2 [50/51Q.DIR.phi_Max_Rev] Operating area in forward direction [50/51Q.DIR.RCA] Operating area in reverse direction [50/51Q.DIR.phi_Max_Fwd] Non-operating area [50/51Q.DIR.phi_Min_Rev] Figure 3.10-3 The direction element operation characteristics of negative-sequence overcurrent protection Where: The sensitivity angle of the direction control element (RCA) can be set by the setting PCS-9613S Differential Relay 3-96 Date: 2020-09-02 3 Protection Functions [50/51Q.DIR.RCA]. The forward direction characteristic is: -[50/51Q.DIR.phi_Min_Fwd]<angle<[50/51Q.DIR.phi_Max_Fwd] The reverse direction characteristic is: 180-[50/51Q.DIR.phi_Min_Rev]<angle<180+[50/51Q.DIR.phi_Max_Rev] The following table shows the relationship between the operating current, the polarized voltage and the polarization mode. Polarization mode Negative-sequence voltage polarized Operating current Negative-sequence current I2 Polarized voltage -U2 Angle difference 3 Angle=Angle(-U2)-Angle(I2)-RCA The direction element calculation needs to judge the current threshold and voltage threshold. The operating current must be greater than the minimum operating current setting [50/51Q.DIR.I2_Min], otherwise the direction element can not operate. The polarized voltage must be greater than the minimum operating voltage setting [50/51Q.DIR.U2_Min], otherwise the direction element can not operate. The logic diagram of the forward direction element and reverse direction element is as follows. PCS-9613S Differential Relay 3-97 Date: 2020-09-02 3 Protection Functions EN [50/51Q.En_VTS_Blk] & SIG VTS.Alm SIG U2 EN 3 [En_VT] >=1 & Forward direction criterion SIG I2 & 50/51Q.FwdDir.Op & SIG Prot.BI_En_VT SET Iop>[50/51Q.DIR.I_Min] SET Upo>[50/51Q.DIR.U_Min] EN [50/51Q.En_VTS_Blk] & SIG VTS.Alm SIG U2 EN [En_VT] >=1 & Reverse direction criterion SIG I2 & 50/51Q.RevDir.Op & SIG Prot.BI_En_VT SET Iop>[50/51Q.DIR.I2_Min] SET Upo>[50/51Q.DIR.U2_Min] Figure 3.10-4 Logic diagram of forward and reverse direction element of negative-sequence overcurrent protection Where: I2: the negative-sequence current. U2: the negative-sequence voltage. Iop: the operating current. Upo: the polarized voltage. 3.10.1.2 Operation Characteristic Negative-sequence overcurrent protection can operate instantaneously or operate with a definite-time limit, it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards. Negative-sequence overcurrent protection can support definite-time limit, IEC & ANSI standard inverse time limit and user-defined inverse-time limit, PCS-9613S Differential Relay 3-98 Date: 2020-09-02 3 Protection Functions users can select the wanted operating curve by the setting [50/51Qx.Opt_Curve] (x=1 or 2), the relationship between the value of the setting and the curve is shown in the table below. 50/51Qx.Opt_Curve Time Characteristic α k c tr ANSIE ANSI Extremely Inverse 28.2 2.0 0.1217 29.1 ANSIV ANSI Very inverse 19.61 2.0 0.491 21.6 ANSIN ANSI Normal Inverse 0.0086 0.02 0.0185 0.46 ANSIM ANSI Moderately Inverse 0.0515 0.02 0.114 4.85 ANSIDefTime ANSI Definite Time - - - - ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30 ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46 ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6 IECN IEC Normal Inverse 0.14 0.02 0 - IECV IEC Very inverse 13.5 1.0 0 - IEC IEC Inverse 0.14 0.02 0 - IECE IEC Extremely inverse 80.0 2.0 0 - IECST IEC Short-time inverse 0.05 0.04 0 - IECLT IEC Long-time inverse 120.0 1.0 0 - IECDefTime IEC Definite Time - - - - UserDefine Programmable Only when the setting [50/51Qx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time characteristic is selected, the settings [50/51Qx.K], [50/51Qx.C] and [50/51Qx.Alpha] are useful, the inverse-time operating curve is determined by the three settings. ⚫ Without time delay (Instantaneously) When ⚫ I 2 > I 2 p , the protection operates immediately. Definite-time characteristic When I 2 > I 2 p , the protection operates with a time delay of top (i.e. the value of the setting [50/51Qx.t_Op]), and the operation characteristic curve is shown in the following figure: PCS-9613S Differential Relay 3-99 Date: 2020-09-02 3 3 Protection Functions t t op 3 I2p I2 Figure 3.10-5 Definite-time operation characteristic curve of negative-sequence overcurrent protection ⚫ Inverse-time characteristic When I 2 > I 2 p , the inverse-time accumulator begins to accumulate, and the operating time is affected by the applied current I 2 . The operating time will decrease with the current increasing, but the operating time shall not less than tmin , i.e. the setting [50/51Qx.tmin]. The inverse-time operation characteristic equation is: k t={ + c} × TMS α (I2 ⁄I2p ) − 1 Where: I 2 p is the current setting [50/51Qx.I2_Set]; TMS is the inverse-time time multiplier, i.e. the setting [50/51Qx.TMS]; k is the inverse-time coefficient K, i.e. the setting [50/51Qx.K]; c is the inverse-time coefficient C, i.e. the setting [50/51Qx.C]; is the inverse-time coefficient Alpha, i.e. the setting [50/51Qx.Alpha]; I 2 is the measured negative-sequence current. The inverse-time operation characteristic curve is shown as below: PCS-9613S Differential Relay 3-100 Date: 2020-09-02 3 Protection Functions t 3 t min ID I2P I2 Figure 3.10-6 Inverse-time operation characteristic curve of negative-sequence overcurrent protection When the applied negative-sequence overcurrent current I 2 is not a fixed value, but changes with time, the operating behaviour of the protection is shown in the following equation: T0 ∫ 0 1 dt = 1 t(I2 ) Where: T0 is the operating time of the protection element; t(I2) is the theoretical operating time when the current is I2 . 3.10.1.3 Dropout Characteristic The supported dropout characteristics of the negative-sequence overcurrent protection include instantaneous dropout, definite-time dropout and ANSI inverse-time dropout. When the operating curve is selected as definite-time, IEC inverse-time or user-defined inverse-time characteristic, the dropout characteristic can only be selected as instantaneous dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal "Fail_Settings" will be issued and the device will be blocked. When the operating curve is selected as ANSI inverse-time characteristic, the dropout characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI inverse-time dropout. ⚫ Instantaneous dropout When I 2 <0.95* I 2 p , the protection drops out immediately. PCS-9613S Differential Relay 3-101 Date: 2020-09-02 3 Protection Functions ⚫ Definite-time dropout When I 2 <0.95* I 2 p , the protection drops out with a time delay of tdr (i.e. the value of the setting [50/51Qx.t_DropOut]), and the dropout characteristic curve is shown in the following figure: Start time I2>I2p 3 Start signal Operating signal Protection operate Operating threshold Operating counter t dr Dropout time setting t dr t dr Dropout time Dropout time Figure 3.10-7 Definite-time dropout characteristic of negative-sequence overcurrent protection ⚫ Inverse-time dropout When I 2 > I 2 p , the inverse-time operating accumulator begins to accumulate, the accumulated value after t p (Assuming t p is less than the theoretical operating time) is calculated according to the following equation: tp I tp = 0 1 dt t(I2 ) At this time, if I 2 <0.95* I 2 p , the protection element starts dropout, and the dropout characteristic meets the following equation: TR I tp − 0 1 dt = 0 tR ( I 2 ) PCS-9613S Differential Relay 3-102 Date: 2020-09-02 3 Protection Functions Where: T R is the dropout time; tR( I 2 ) is the dropout characteristic equation When I 2 <0.95* I 2 p , the inverse-time dropout characteristic equation is as follows: t R (I2 ) = { tr 1 − (I2 /I2p ) 2} × TMS 3 Where: I 2 p is the current setting [50/51Qx.I2_Set]; TMS is the inverse-time factor, i.e. the setting [50/51Qx.TMS]; tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after the protection operates. I 2 is the measured negative-sequence current. When 0.95* I 2 p < I 2 < I 2 p , the accumulator will neither accumulate nor drop out The inverse time dropout characteristic curve is shown in the figure below. t tr Figure 3.10-8 Inverse-time dropout characteristic curve of negative-sequence overcurrent protection The correspondence between the start signal, operating signal, and operating accumulator in the inverse-time dropout characteristic is shown in the figure below: PCS-9613S Differential Relay 3-103 Date: 2020-09-02 3 Protection Functions Start time I2>I2p Start signal Operating signal 3 Protection operate Operating threshold Operating counter tr Dropout time coefficient Dropout time Dropout time Figure 3.10-9 Inverse-time dropout characteristic of negative-sequence overcurrent protection 3.10.2 Function Block Diagram 50/51Q 50/51Qx.On 50/51Qx.Enable 50/51Qx.Block 50/51Qx.Blocked 50/51Qx.Valid 50/51Qx.St 50/51Qx.Op 50/51Qx.Alm 50/51Q.FwdDir.Op 50/51Q.RevDir.Op 3.10.3 I/O Signal Table 3.10-1 Input/output signals of negative-sequence overcurrent protection No. Input signal 1 50/51Qx.Enable 2 50/51Qx.Block No. 1 Description Stage x of negative-sequence overcurrent protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~2) Stage x of negative-sequence overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~2) Output signal 50/51Qx.On Description Stage x of negative-sequence overcurrent protection is enabled PCS-9613S Differential Relay 3-104 Date: 2020-09-02 3 Protection Functions 2 50/51Qx.Blocked Stage x of negative-sequence overcurrent protection is blocked 3 50/51Qx.Valid Stage x of negative-sequence overcurrent protection is valid 4 50/51Qx.St Stage x of negative-sequence overcurrent protection starts 5 50/51Qx.Op Stage x of negative-sequence overcurrent protection operates 6 50/51Qx.Alm Stage x of negative-sequence overcurrent protection alarms 7 50/51Q.FwdDir.Op 8 50/51Q.RevDir.Op The forward direction element of negative-sequence overcurrent protection operates The reverse direction element of negative-sequence overcurrent protection operates 3.10.4 Logic 3 SET I2>[50/51Qx.I2_Set] SIG 50/51Q.FwdDir.Op SIG 50/51Q.RevDir.Op SET [50/51Qx.Opt_Dir] SIG 50/51Qx.Pkp SET [50/51Qx.Opt_Trp/Alm]=Trp 50/51Qx.St & Direction selection & Timer t t & 50/51Qx.Op & 50/51Qx.Alm SET [50/51Qx.Opt_Trp/Alm]=Alm Figure 3.10-10 Logic diagram of negative-sequence overcurrent protection 3.10.5 Settings ⚫ Access path: MainMenu Settings Protection Settings NegOC Settings Table 3.10-2 Settings of negative-sequence overcurrent protection No. Settings Default Range value Unit Step Description The relay characteristic angle 1 50/51Q.DIR.RCA -180~179 45 deg 1 of the direction control element of negative-sequence overcurrent protection The minimum boundary of the 2 50/51Q.DIR.phi_Min_ Fwd 10~90 90 deg 1 forward direction element of negative-sequence overcurrent protection PCS-9613S Differential Relay 3-105 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The maximum boundary of the 3 50/51Q.DIR.phi_Max _Fwd 10~90 90 deg 1 forward direction element of negative-sequence overcurrent protection The minimum boundary of the 4 50/51Q.DIR.phi_Min_ Rev 10~90 90 deg 1 reverse direction element of negative-sequence overcurrent protection 3 The maximum boundary of the 5 50/51Q.DIR.phi_Max _Rev 10~90 90 deg 1 reverse direction element of negative-sequence overcurrent protection The minimum operating current setting for the direction 6 50/51Q.DIR.I2_Min (0.05~1)In 0.05 - 0.001 control element of negative-sequence overcurrent protection The minimum operating voltage setting for the direction 7 50/51Q.DIR.U2_Min 1.0~10.0 4 V 0.001 control element of negative-sequence overcurrent protection Logic setting to determine the behaviour of negative-sequence overcurrent protection when VT circuit supervision function is enabled and VT circuit 8 50/51Q.En_VTS_Blk Disabled; Enabled failure happens. Disabled - - Disabled: negative-sequence overcurrent protection will not affected by VT circuit failure Enabled: voltage controlled negative-sequence overcurrent protection will be blocked by VT circuit failure signal The current setting of stage 1 9 50/51Q1.I2_Set 0.05~200 15 A 0.001 of negative-sequence overcurrent protection PCS-9613S Differential Relay 3-106 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The operating time setting of 10 50/51Q1.t_Op 0.03 ~100 0.1 s 0.001 stage 1 of negative-sequence overcurrent protection The dropout time setting of 11 50/51Q1.t_DropOut 0 ~100 0 s 0.001 stage 1 of negative-sequence overcurrent protection Non_Direction 12 50/51Q1.Opt_Dir The setting used to select the al Non_Directio Forward nal - - Reverse directional mode of stage 1 of overcurrent protection. The 13 50/51Q1.En Disabled; Enabled 3 negative-sequence Enabled - - logic setting for enabling/disabling the stage 1 of negative-sequence overcurrent protection Enabling stage 1 of negative-sequence 14 50/51Q1.Opt_Trp/Alm Trp; Alm Trp - - overcurrent protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 15 50/51Q1.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - - characteristic curve of stage 1 of IECV; operation negative-sequence overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine PCS-9613S Differential Relay 3-107 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The setting for selecting the inverse-time 16 50/51Q1.Opt_Curve_ DropOut characteristic curve of stage 1 Inst; DefTime; dropout Inst - - IDMT of negative-sequence overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout 3 The time multiplier setting of 17 50/51Q1.TMS 0.04~ 20 1 - 0.001 stage 1 of negative-sequence overcurrent protection The minimum operating time 18 50/51Q1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of of the negative-sequence overcurrent protection The constant customized 19 50/51Q1.K 0.001~120 0.14 - 0.0001 operation “k” inverse-time characteristic of stage 1 of negative-sequence overcurrent protection The constant customized 20 50/51Q1.Alpha 0.01 ~3 0.02 - 0.0001 operation “α” of the inverse-time characteristic of stage 1 of negative-sequence overcurrent protection The constant customized 21 50/51Q1.C 0 ~1 0 - 0.0001 operation “C” of the inverse-time characteristic of stage 1 of negative-sequence overcurrent protection The current setting of stage 2 22 50/51Q2.I2_Set 0.05~200 15 A 0.001 of negative-sequence overcurrent protection The operating time setting of 23 50/51Q2.t_Op 0.03 ~100 0.1 s 0.001 stage 2 of negative-sequence overcurrent protection The dropout time setting of 24 50/51Q2.t_DropOut 0 ~100 0 s 0.001 stage 2 of negative-sequence overcurrent protection PCS-9613S Differential Relay 3-108 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Non_Direction 25 50/51Q2.Opt_Dir Description The setting used to select the al Non_Directio Forward nal - - Reverse directional mode of stage 2 of negative-sequence overcurrent protection. The 26 50/51Q2.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 2 of negative-sequence overcurrent protection Enabling stage 2 of negative-sequence 27 50/51Q2.Opt_Trp/Alm Trp; Alm Trp - - overcurrent protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 28 50/51Q2.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - - characteristic curve of stage 2 of IECV; operation negative-sequence overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 29 50/51Q2.Opt_Curve_ DropOut characteristic curve of stage 2 Inst; DefTime; dropout Inst - - IDMT of negative-sequence overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 30 50/51Q2.TMS 0.04~ 20 1 - 0.001 stage 2 of negative-sequence overcurrent protection PCS-9613S Differential Relay 3-109 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range value Unit Step Description The minimum operating time 31 50/51Q2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of of the negative-sequence overcurrent protection The constant customized 32 50/51Q2.K 0.001~120 0.14 - 0.0001 operation “k” inverse-time characteristic of stage 2 of negative-sequence 3 overcurrent protection The constant customized 33 50/51Q2.Alpha 0.01 ~3 0.02 - 0.0001 operation “α” of the inverse-time characteristic of stage 2 of negative-sequence overcurrent protection The constant customized 34 50/51Q2.C 0 ~1 0 - 0.0001 operation “C” of the inverse-time characteristic of stage 2 of negative-sequence overcurrent protection 3.11 RMS Overcurrent Protection (50/51R) When the capacitive equipment such as a capacitor bank or the inductive equipment such as a rotating electrical machine in the system has a serious fault, the fundamental component in the fault current will be relatively low, and the higher harmonic components will be higher. The conventional phase overcurrent protection uses filtering algorithms to filter out higher harmonics and perform calculation based on the fundamental component, resulting in failure to truly reflect the fault condition and the protection sensitivity is affected. The RMS overcurrent protection calculates the full-current RMS value includes 2nd~11th harmonic components, which can sensitively reflect the actual fault current, so the fault can be removed quickly and accurately. 3.11.1 Function Description The device can provide two stages of RMS overcurrent protection with independent logic. When the fault current with more harmonic components is generated in the system, the amplitude is larger than the current threshold of RMS overcurrent protection, the RMS overcurrent protection will operate. Each stage of RMS overcurrent protection can be independently set as definite-time characteristics or inverse-time characteristics. The drop-out characteristics can be set as instantaneous drop-out, definite-time drop-out or inverse-time drop-out. RMS overcurrent protection can operate to trip or alarm, it can be enabled or blocked by the external binary input. RMS overcurrent protection can be enabled or disabled via the settings or binary input signals, for PCS-9613S Differential Relay 3-110 Date: 2020-09-02 3 Protection Functions some specific applications, the protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block RMS overcurrent protection. The enabling and blocking logic of RMS overcurrent protection is shown in the figure below: EN & 50/51Rx.En 50/51Rx.On SIG 50/51Rx.Enable SIG 50/51Rx.Block SIG Fail_Device & ≥1 50/51Rx.Blocked 3 & 50/51Rx.Valid Figure 3.11-1 The enabling and blocking logic of RMS overcurrent protection The logic diagram of the fault detector element of RMS overcurrent protection is as follows: SET IRMS >0.95*[50/51Rx.I_Set] & 0 50/51Rx.Pkp 500ms & & SIG 50/51Rx.On SIG 50/51Rx.Valid EN [50/51Rx.Opt_Trp/Alm]=Alm FD.Pkp Figure 3.11-2 Logic diagram of the fault detector element of RMS overcurrent protection 3.11.1.1 Operation Characteristic RMS overcurrent protection can operate without time delay or operate with a definite-time limit, it can also operate with an inverse-time limit, the characteristic curve meets the IEC60255-3 and ANSI C37.112 standards. RMS overcurrent protection can support definite-time limit, IEC & ANSI standard inverse time limit and user-defined inverse-time limit, users can select the wanted operating curve by the setting [50/51Rx.Opt_Curve] (x=1~6), the relationship between the value of the setting and the curve is shown in the table below. 50/51Rx.Opt_Curve Time Characteristic k α c tr ANSIE ANSI Extremely Inverse 28.2 2.0 0.1217 29.1 ANSIV ANSI Very inverse 19.61 2.0 0.491 21.6 ANSIN ANSI Normal Inverse 0.0086 0.02 0.0185 0.46 ANSIM ANSI Moderately Inverse 0.0515 0.02 0.114 4.85 ANSIDefTime ANSI Definite Time - - - - ANSILTE ANSI Long Time Extremely Inverse 64.07 2.0 0.25 30 ANSILTV ANSI Long Time Very Inverse 28.55 2.0 0.712 13.46 ANSILT ANSI Long Time Inverse 0.086 0.02 0.185 4.6 IECN IEC Normal Inverse 0.14 0.02 0 - PCS-9613S Differential Relay 3-111 Date: 2020-09-02 3 Protection Functions 3 50/51Rx.Opt_Curve Time Characteristic k α c tr IECV IEC Very inverse 13.5 1.0 0 - IEC IEC Inverse 0.14 0.02 0 - IECE IEC Extremely inverse 80.0 2.0 0 - IECST IEC Short-time inverse 0.05 0.04 0 - IECLT IEC Long-time inverse 120.0 1.0 0 - IECDefTime IEC Definite Time - - - - UserDefine Programmable Only when the setting [50/51Rx.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time characteristic is selected, the settings [50/51Rx.K], [50/51Rx.C] and [50/51Rx.Alpha] are useful, the inverse-time operating curve is determined by the three settings. ⚫ Without time delay When IRMS>IRMSp, phase overcurrent protection operates immediately. ⚫ Definite-time characteristic When IRMS>IRMSp, the protection operates with a time delay of top (i.e. the value of the setting [50/51Rx.t_Op]), and the operation characteristic curve is shown in the following figure: t t 0p IRMSp IRMS Figure 3.11-3 Definite-time operation characteristic curve of RMS overcurrent protection ⚫ Inverse-time characteristic When IRMS>IRMSp, the inverse-time accumulator begins to accumulate, and the operating time is affected by the applied current IRMS. The operating time will decrease with the current increasing, but the operating time shall not less than operation characteristic equation is: tmin , i.e. the setting [50/51Rx.tmin]. The inverse-time k t= + c TMS ( I RMS / I RMSP ) − 1 PCS-9613S Differential Relay 3-112 Date: 2020-09-02 3 Protection Functions Where: IRMSp is the current setting [50/51Rx.I_Set]; TMS is the inverse-time time multiplier, i.e. the setting [50/51Rx.TMS]; k is the inverse-time coefficient K, i.e. the setting [50/51Rx.K]; c is the inverse-time coefficient C, i.e. the setting [50/51Rx.C]; is the inverse-time coefficient Alpha, i.e. the setting [50/51Px.Alpha]; 3 IRMS is the measured current. The inverse-time operation characteristic curve is shown as below: t t min I RMSP ID I RMS Figure 3.11-4 Inverse-time operation characteristic curve of RMS overcurrent protection When the applied current is not a fixed value, but changes with time, the operating behaviour of the protection is shown in the following equation: T0 t(I 0 1 RMS ) dt = 1 Where: T0 is the operating time of the protection element; t(IRMS) is the theoretical operating time when the current is IRMS. 3.11.1.2 Dropout Characteristic The supported dropout characteristics of the RMS overcurrent protection include instantaneous dropout, definite-time dropout and ANSI inverse-time dropout. PCS-9613S Differential Relay 3-113 Date: 2020-09-02 3 Protection Functions When the operating curve is selected as definite-time, IEC inverse-time or user-defined inverse-time characteristic, the dropout characteristic can only be selected as instantaneous dropout or definite-time dropout, if inverse-time dropout is selected, the alarm signal "Fail_Settings" will be issued and the device will be blocked. When the operating curve is selected as ANSI inverse-time characteristic, the dropout characteristic can be selected as instantaneous dropout, definite-time dropout and ANSI inverse-time dropout. ⚫ 3 Instantaneous dropout When ⚫ I RMS <0.95* I RMSP , the protection drops out immediately. Definite-time dropout When I RMS <0.95* I RMSP , the protection drops out with a time delay of tdr (i.e. the value of the setting [50/51Rx.t_DropOut]), and the dropout characteristic curve is shown in the following figure: Start time IRMS >Iset Start signal Operating signal Protection operate Operating threshold Operating counter t dr Dropout time setting t dr t dr Dropout time Dropout time Figure 3.11-5 Definite-time dropout characteristic of RMS overcurrent protection ⚫ Inverse-time dropout When IRMS>IRMSp, the inverse-time operating accumulator begins to accumulate, the accumulated value after t p (Assuming t p is less than the theoretical operating time) is calculated according PCS-9613S Differential Relay 3-114 Date: 2020-09-02 3 Protection Functions to the following equation: tp I tp = 1 t ( I RMS ) 0 dt At this time, if IRMS<0.95*IRMSp, the protection element starts dropout, and the dropout characteristic meets the following equation: TR I tp − 0 1 dt = 0 t R ( I RMS ) 3 Where: T R is the dropout time; tR( I RMS ) is the dropout characteristic equation When IRMS<0.95*IRMSp, the inverse-time dropout characteristic equation is as follows: tr tR = TMS 2 1 − ( I RMS / I RMSP ) Where: IRMSp is the current setting [50/51Rx.I_Set]; TMS is the inverse-time factor, i.e. the setting [50/51Rx.TMS]; tr is the dropout time coefficient, it is the dropout time required for the current to drop to 0 after the protection operates. IRMS is the measured current. When 0.95*IRMSp <IRMS <IRMSp, the accumulator will neither accumulate nor drop out The inverse time dropout characteristic curve is shown in the figure below. PCS-9613S Differential Relay 3-115 Date: 2020-09-02 3 Protection Functions t 3 tr I RMSP I RMS Figure 3.11-6 Inverse-time dropout characteristic curve of RMS overcurrent protection The correspondence between the start signal, operating signal, and operating accumulator in the inverse-time dropout characteristic is shown in the figure below: Start time IRMS >IRMSp Start signal Operating signal Operating threshold Protection operate Operating counter tr Dropout time coefficient Dropout time Dropout time Figure 3.11-7 Inverse-time dropout characteristic of RMS overcurrent protection PCS-9613S Differential Relay 3-116 Date: 2020-09-02 3 Protection Functions 3.11.2 Function Block Diagram 50/51R 50/51Rx.On 50/51Rx.Enable 50/51Rx.Block 50/51Rx.Blocked 50/51Rx.Valid 50/51Rx.St 50/51Rx.StA 50/51Rx.StB 3 50/51Rx.StC 50/51Rx.Op 50/51Rx.Op.PhA 50/51Rx.Op.PhB 50/51Rx.Op.PhC 50/51Rx.Alm 3.11.3 I/O Signal Table 3.11-1 Input/output signals of RMS overcurrent protection No. Input signal 1 50/51Rx.Enable 2 50/51Rx.Block No. Description Stage x of RMS overcurrent protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~2) Stage x of RMS overcurrent protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~2) Output signal Description 1 50/51Rx.On Stage x of RMS overcurrent protection is enabled 2 50/51Rx.Blocked Stage x of RMS overcurrent protection is blocked 3 50/51Rx.Valid Stage x of RMS overcurrent protection is valid 4 50/51Rx.St Stage x of RMS overcurrent protection starts 5 50/51Rx.StA Stage x of RMS overcurrent protection starts (Phase A) 6 50/51Rx.StB Stage x of RMS overcurrent protection starts (Phase B) 7 50/51Rx.StC Stage x of RMS overcurrent protection starts (Phase C) 8 50/51Rx.Op Stage x of RMS overcurrent protection operates 9 50/51Rx.Op.PhA Stage x of RMS overcurrent protection operates (Phase A) 10 50/51Rx.Op.PhB Stage x of RMS overcurrent protection operates (Phase B) 11 50/51Rx.Op.PhC Stage x of RMS overcurrent protection operates (Phase C) 12 50/51Rx.Alm Stage x of RMS overcurrent protection alarms PCS-9613S Differential Relay 3-117 Date: 2020-09-02 3 Protection Functions 3.11.4 Logic 50/51Rx.St SET IRMS >[50/51Rx.I_Set] SIG 50/51Rx.Pkp SET [50/51Rx.Opt_Trp/Alm]=Trp & Timer t & t 50/51Rx.Op & 50/51Rx.Alm 3 SET [50/51Rx.Opt_Trp/Alm]=Alm Figure 3.11-8 Logic diagram of RMS overcurrent protection 3.11.5 Settings ⚫ Access path: MainMenu Settings Protection Settings RMS OC Settings Table 3.11-2 Settings of RMS overcurrent protection No. Settings Default Range value Unit Step Description The current setting of 1 50/51R1.I_Set 0.05~200 15 A 0.001 stage 1 of RMS overcurrent protection The 2 50/51R1.t_Op 0 ~100 0.1 s 0.001 operating time setting of stage 1 of RMS overcurrent protection The 3 50/51R1.t_DropOut 0 ~100 0 s 0.001 drop-out time setting of stage 1 of RMS overcurrent protection The logic setting for 4 50/51R1.En Disabled; Enabled Enabled - - enabling/disabling stage 1 of the RMS overcurrent protection Enabling stage 1 of 5 50/51R1.Opt_Trp/Alm Trp; Alm Trp - - RMS overcurrent protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 3-118 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting ANSILTV; 6 50/51R1.Opt_Curve ANSILT; the IECDefTime IECN; - - inverse-time operation characteristic curve of stage 1 of RMS IECV; overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time dropout characteristic curve of stage Inst; 7 50/51R1.Opt_Curve_DropOut 1 of RMS overcurrent protection DefTime; Inst - - IDMT Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The 8 50/51R1.TMS 0.04~ 20 1 - 0.001 time multiplier setting of stage 1 of RMS overcurrent protection The minimum operating 9 50/51R1.tmin 0 ~10 0.02 s 0.001 time setting of stage 1 of RMS overcurrent protection The constant “k” of the customized 10 50/51R1.K 0.001~120 0.14 - 0.0001 inverse-time operation characteristic of stage 1 of RMS overcurrent protection PCS-9613S Differential Relay 3-119 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range value Unit Step Description The constant “α” of the customized 11 50/51R1.Alpha 0.01 ~3 0.02 - 0.0001 inverse-time operation characteristic of stage 1 of RMS overcurrent protection The constant “C” of the customized 3 12 50/51R1.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 1 of RMS overcurrent protection The current setting of 13 50/51R2.I_Set 0.05~200 15 A 0.001 stage 2 of RMS overcurrent protection The 14 50/51R2.t_Op 0 ~100 0.1 s 0.001 operating time setting of stage 2 of RMS overcurrent protection The 15 50/51R2.t_DropOut 0 ~100 0 s 0.001 drop-out time setting of stage 2 of RMS overcurrent protection The logic setting for 16 50/51R2.En Disabled; Enabled Enabled - - enabling/disabling stage 2 of the RMS overcurrent protection Enabling stage 2 of 17 50/51R2.Opt_Trp/Alm Trp; Alm Trp - - RMS overcurrent protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 3-120 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting ANSILTV; 18 50/51R2.Opt_Curve ANSILT; the IECDefTime IECN; - - inverse-time operation characteristic curve of stage 2 of RMS IECV; overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time dropout characteristic curve of stage Inst; 19 50/51R2.Opt_Curve_DropOut 2 of RMS overcurrent protection DefTime; Inst - - IDMT Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The 20 50/51R2.TMS 0.04~ 20 1 - 0.001 time multiplier setting of stage 2 of RMS overcurrent protection The minimum operating 21 50/51R2.tmin 0 ~10 0.02 s 0.001 time setting of stage 2 of RMS overcurrent protection The constant “k” of the customized 22 50/51R2.K 0.001~120 0.14 - 0.0001 inverse-time operation characteristic of stage 2 of RMS overcurrent protection PCS-9613S Differential Relay 3-121 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range value Unit Step Description The constant “α” of the customized 23 50/51R2.Alpha 0.01 ~3 0.02 - 0.0001 inverse-time operation characteristic of stage 2 of RMS overcurrent protection The constant “C” of the customized 3 24 50/51R2.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 2 of RMS overcurrent protection 3.12 Broken Conductor Protection (46BC) Single-phase earthing fault and two-phases earthing fault are the most common fault on circuits, the fault is easy to detect because the fault current will increase obviously. Broken-conductor fault is difficult to detect since there is no increase of current but negative-sequence current, so negative-sequence overcurrent protection can be considered to detect broken-conductor fault. However, under heavy load condition, negative-sequence current is relative large due to unbalance loading, but negative-sequence current because of broken-conductor fault under light load condition is relative small. If negative-sequence current protection is set larger than maximum negative-sequence current under loading, negative-sequence overcurrent protection may be failure to operate if broken-conductor fault happens under light load condition, negative-sequence overcurrent protection is therefore not suitable to apply for broken-conductor fault. The network of single-phase broken condition is similar to that of two-phases earthing fault, positive-sequence, negative-sequence and zero-sequence network is connected in parallel, I2/I1= Z0/(Z0+Z2), generally, zero-sequence impedance is larger than positive-sequence impedance, i.e. I2/I1>0.5. The network of two-phases broken condition is similar to that of single-phase earthing fault, positive-sequence, negative-sequence and zero-sequence network is connected in series, so I2/I1=1. Hence, broken conductor protection based on the ratio of negative-sequence current to positive sequence current can detect the broken-conductor fault. 3.12.1 Function Description Broken-conductor fault mainly is single-phase broken or two-phases broken. According to the ratio of negative-sequence current to positive-sequence current (I2/I1), it is used to judge whether there is a broken-conductor fault. Negative-sequence current under normal operating condition (i.e. unbalance current) is due to CT error and unbalance load, so the ratio of negative-sequence current to positive-sequence current (amplitude) is relative steady. The value with margin can then be used as the setting of broken conductor protection. It is mainly used to detect broken-conductor PCS-9613S Differential Relay 3-122 Date: 2020-09-02 3 Protection Functions fault and CT circuit failure as well. 3.12.2 Function Block Diagram 46BC 46BC.Enable 46BC.Block 46BC.On 46BC.Blocked 46BC.Valid 46BC.St 3 46BC.Op 46BC.Alm 3.12.3 I/O Signals Table 3.12-1 Input/Output signals of broken conductor protection No. Input Signal Description 1 46BC.Enable Input signal of enabling broken conductor protection 2 46BC.Block Input signal of blocking broken conductor protection No. Output Signal Description 1 46BC.On Broken conductor protection is enabled. 2 46BC.Blocked Broken conductor protection is blocked. 3 46BC.Valid Broken conductor protection is valid. 4 46BC.St Broken conductor protection starts. 5 46BC.Op Broken conductor protection operates. 6 46BC.Alm Broken conductor protection alarms. PCS-9613S Differential Relay 3-123 Date: 2020-09-02 3 Protection Functions 3.12.4 Logic EN [46BC.En] & 46BC.On SIG 46BC.Enable & SIG 46BC.Block 46BC.Blocked >=1 SIG Fail_Device & 46BC.Valid 3 SIG 46BC.Valid SET Ia>[46BC.I_Min] >=1 & SET Ib>[46BC.I_Min] 46BC.St SET Ic>[46BC.I_Min] [46BC.t_Op] 0ms & SET I2/I1>[46BC.I2/I1_Set] 46BC.Op SET [46BC.Opt_Trp/Alm]=Trp & 46BC.Alm SET [46BC.Opt_Trp/Alm]=Alm Figure 3.12-1 Logic of broken conductor protection 3.12.5 Settings Table 3.12-2 Settings of broken conductor protection No. 1 Setting 46BC.I_Min Range (0.05~40) In Default 1.000 Unit Step A 0.001 Description Minimum operating current setting of broken conductor protection Ratio 2 46BC.I2/I1_Set 0~5 0.500 - 0.001 setting (negative-sequence current to positive-sequence current) of broken conductor protection 3 46BC.t_Op 4 46BC.En 0~10 Disabled Enabled 1.000 s 0.001 Enabled - - Time delay of broken conductor protection Enabling/disabling broken conductor protection Enabling/disabling broken conductor 5 46BC.Opt_Trp/Alm Trp Alm Trp - - protection operate to trip or alarm Trp: for tripping purpose Alm: for alarm purpose 3.13 Phase Overvoltage Protection (59P) Some abnormal conditions in the power system will generate high voltage, which may damage PCS-9613S Differential Relay 3-124 Date: 2020-09-02 3 Protection Functions the insulation performance of transformers, capacitors, motors and transmission lines, resulting in equipment damage. Phase overvoltage protection can effectively detect the overvoltage that may be generated in the system. 3.13.1 Function Description The device can provide two stages of phase overvoltage protection with independent logic. When a high voltage occurs in the system, it is greater than the voltage threshold, phase overvoltage protection will operate to remove the device from the system after a time delay. In addition, the overvoltage protection also provides the alarm function, prompting the overvoltage of the system, it allows users to find the cause timely, and preventing further deterioration of the fault. Each stage of phase overvoltage protection can be independently set as definite-time characteristics or inverse-time characteristics. The dropout characteristics can be set as instantaneous dropout and definite-time dropout. Users can select phase voltage or phase-to-phase voltage for the protection calculation via the setting [59P.Opt_Up/Upp]. If it is set as “Up”, phase voltage criterion is selected, and if it is set to “Upp”, phase-to-phase voltage criterion is selected. Users can select “1-out-of-3” or “3-out-of-3” logic for the protection criterion via the setting [59P.Opt_1P/3P]. If it is set as “1P”, phase overvoltage protection can operate if any phase/phase-to-phase voltage is greater than the voltage setting. If it is set as “3P”, phase overvoltage protection cannot operate unless three phase/phase-to-phase voltages are greater than the voltage setting. Phase overvoltage protection can be enabled or disabled via the settings or binary input signals, for some specific applications, overvoltage protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block overvoltage protection. In addition, if the VT of the local side is out of service, phase overvoltage protection will be disabled. The enabling and blocking logic of phase overvoltage protection is shown in the figure below: EN & 59Px.En 59Px.On SIG 59Px.Enable SIG 59Px.Block SIG Fail_Device EN [En_VT] & ≥1 59Px.Blocked & & 59Px.Valid SIG BI_En_VT Figure 3.13-1 The enabling and blocking logic of phase overvoltage protection The logic diagram of the fault detector element of phase overvoltage protection is as follows: PCS-9613S Differential Relay 3-125 Date: 2020-09-02 3 3 Protection Functions SET [59P.Opt_Up/Upp]=Upp SET Uab>U_DropOut >=1 SET Ubc>U_DropOut & SET Uca>U_DropOut SET [59P.Opt_1P/3P]=1P & SET [59P.Opt_1P/3P]=3P SET Uab>U_DropOut >=1 & & SET Ubc>U_DropOut 3 SET Uca>U_DropOut SET Ua>U_DropOut >=1 SET Ub>U_DropOut & SET Uc>U_DropOut SET [59P.Opt_1P/3P]=1P SET [59P.Opt_1P/3P]=3P SET Ua>U_DropOut >=1 & & SET Ub>U_DropOut >=1 & SET Uc>U_DropOut & 0 500ms & 59Px.Pkp SET [59P.Opt_Up/Upp]=Up SIG 59Px.On & SIG 59Px.Valid FD.Pkp SET [59Px.Opt_Trp/Alm]=Alm Figure 3.13-2 Logic diagram of the fault detector element of phase overvoltage protection Where: U_DropOut: the dropout voltage value, i.e. [59Px.K_DropOut]*[59Px.U_Set] 3.13.1.1 Operation Characteristic Phase overvoltage protection can operate with a definite-time limit, it can also operate with an inverse-time limit. Phase overvoltage protection can support definite-time limit, IEC & ANSI standard inverse time limit and user-defined inverse-time limit, users can select the wanted operating curve by the setting [59Px.Opt_Curve] (x=1, 2), the relationship between the value of the setting and the curve is shown in the table below. 59Px.Opt_Curve Time Characteristic α k c ANSIDefTime ANSI Definite Time - - - IECDefTime IEC Definite Time - - - UserDefine UserDefine InvTime_U InvCrv_U 1 1 0 When the setting [59Px.Opt_Curve] is set as “InvTime_U”, the operation characteristic is the corresponding selected operating curve type, and the settings [59Px.K], [59Px.C] and PCS-9613S Differential Relay 3-126 Date: 2020-09-02 3 Protection Functions [59Px.Alpha] are useless. When the setting [59Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time characteristic is selected, the inverse-time operating curve is determined by the settings [59Px.K], [59Px.C] and [59Px.Alpha]. When the setting [59Px.Opt_Curve] is set as “ANSIDefTime” or “IECDefTime”, it is definite-time overvoltage protection. ⚫ Definite-time characteristic When U > Up , the protection operates with a time delay of top (i.e. the value of the setting [59Px.t_Op]), and the operation characteristic curve is shown in the following figure: t t op Up U Figure 3.13-3 Definite-time operation characteristic curve of phase overvoltage protection ⚫ Inverse-time characteristic When U > Up , the inverse-time accumulator begins to accumulate, and the operating time is affected by the applied voltage U . The larger voltage is, the smaller the operating time is, but not unlimited. When the voltage is large enough to a certain threshold ( Up ), the inverse-time operating time will not continue to decrease, then the operation characteristic becomes the definite-time characteristic, and the operating time is tmin , i.e. the setting [59Px.tmin]. The inverse-time operation characteristic equation is: k t= + c TMS (U / U P ) − 1 Where: Up is the voltage setting [59Px.U_Set]; TMS is the inverse-time time multiplier, i.e. the setting [59Px.TMS]; k is the inverse-time coefficient K, i.e. the setting [59Px.K]; PCS-9613S Differential Relay 3-127 Date: 2020-09-02 3 3 Protection Functions c is the inverse-time coefficient C, i.e. the setting [59Px.C]; is the inverse-time coefficient Alpha, i.e. the setting [59Px.Alpha]; U is the measured voltage. The inverse-time operation characteristic curve is shown as below: t 3 t min UP UD U Figure 3.13-4 Inverse-time operation characteristic curve of phase overvoltage protection When the applied voltage is not a fixed value, but changes with time, the operating behaviour of the protection is shown in the following equation: T0 1 t (U )dt =1 0 Where: T0 is the operating time of the protection element; t (U ) is the theoretical operating time when the voltage is U . 3.13.1.2 Dropout Characteristic The supported dropout characteristics of the phase overvoltage protection include instantaneous dropout and definite-time dropout. ⚫ Instantaneous dropout When U <[ 59Px.K_DropOut]* Up , the protection drops out immediately. ⚫ Definite-time dropout When U <[59Px.K_DropOut]* Up , the protection drops out with a time delay of tdr (i.e. the value of the setting [59Px.t_DropOut]), and the dropout characteristic curve is shown in the following figure: PCS-9613S Differential Relay 3-128 Date: 2020-09-02 3 Protection Functions Start time U>Up Start signal Operating signal 3 Protection operate Operating threshold Operating counter t dr t dr Dropout time setting t dr Dropout time Dropout time Figure 3.13-5 Definite-time dropout characteristic of phase overvoltage protection 3.13.2 Function Block Diagram 59P 59Px.Enable 59Px.Block 59Px.On 59Px.Blocked 59Px.Valid 59Px.St 59Px.StA 59Px.StB 59Px.StC 59Px.Op 59Px.Op.PhA 59Px.Op.PhB 59Px.Op.PhC 59Px.Alm PCS-9613S Differential Relay 3-129 Date: 2020-09-02 3 Protection Functions 3.13.3 I/O Signal Table 3.13-1 Input/output signals of phase overvoltage protection No. 1 59Px.Enable 2 59Px.Block No. 3 Input signal Description Stage x of phase overvoltage protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~2) Stage x of phase overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~2) Output signal Description 1 59Px.On Stage x of phase overvoltage protection is enabled 2 59Px.Blocked Stage x of phase overvoltage protection is blocked 3 59Px.Valid Stage x of phase overvoltage protection is valid 4 59Px.St Stage x of phase overvoltage protection starts 5 59Px.StA Stage x of phase overvoltage protection starts (Phase A or AB) 6 59Px.StB Stage x of phase overvoltage protection starts (Phase B or BC) 7 59Px.StC Stage x of phase overvoltage protection starts (Phase C or CA) 8 59Px.Op Stage x of phase overvoltage protection operates 9 59Px.Op.PhA Stage x of phase overvoltage protection operates (Phase A or AB) 10 59Px.Op.PhB Stage x of phase overvoltage protection operates (Phase B or BC) 11 59Px.Op.PhC Stage x of phase overvoltage protection operates (Phase C or CA) 12 59Px.Alm Stage x of phase overvoltage protection alarms PCS-9613S Differential Relay 3-130 Date: 2020-09-02 3 Protection Functions 3.13.4 Logic SET [59P.Opt_Up/Upp]=Upp SET Uab>[59Px.U_Set] >=1 SET Ubc>[59Px.U_Set] & SET Uca>[59Px.U_Set] SET [59P.Opt_1P/3P]=1P & SET [59P.Opt_1P/3P]=3P >=1 >=1 & SET Uab>[59Px.U_Set] 3 & SET Ubc>[59Px.U_Set] SET Uca>[59Px.U_Set] SET [59P.Opt_Up/Upp]=Up SET Ua>[59Px.U_Set] >=1 SET Ub>[59Px.U_Set] & SET Uc>[59Px.U_Set] SET [59P.Opt_1P/3P]=1P & SET [59P.Opt_1P/3P]=3P >=1 & SET Ua>[59Px.U_Set] & 59Px.St SET Ub>[59Px.U_Set] & SET Uc>[59Px.U_Set] Timer t t SIG 59Px.Pkp & 59Px.Op SET [59Px.Opt_Trp/Alm]=Trp & 59Px.Alm SET [59Px.Opt_Trp/Alm]=Alm Figure 3.13-6 Logic diagram of phase overvoltage protection 3.13.5 Settings ⚫ Access path: MainMenu Settings Protection Settings OV Settings PCS-9613S Differential Relay 3-131 Date: 2020-09-02 3 Protection Functions Table 3.13-2 Settings of phase overvoltage protection No. Settings Default Range value Unit Step Description Option of phase-to-phase voltage or phase voltage for 1 59P.Opt_Up/Upp Up; Upp Upp - - overvoltage protection Up: phase voltage Upp: phase-to-phase voltage Option of 1-out-of-3 mode or 3 2 59P.Opt_1P/3P 3-out-of-3 3P; 3P 1P - - mode for overvoltage protection 3P: 3-out-of-3 mode 1P: 1-out-of-3 mode The voltage setting of stage 3 59P1.U_Set 57.7~200 115 V 0.001 1 of phase overvoltage protection The dropout coefficient of 4 59P1.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 1 of phase overvoltage protection The operating time setting of 5 59P1.t_Op 0.1 ~100 1 s 0.001 stage 1 of phase overvoltage protection The dropout time setting of 6 59P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase overvoltage protection The 7 59P1.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 1 of phase overvoltage protection Enabling stage 1 of phase 8 59P1.Opt_Trp/Alm overvoltage Trp; Trp Alm - - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose The setting for selecting the ANSIDefTime; 9 59P1.Opt_Curve IECDefTime; UserDefine; inverse-time IECDefTime - - characteristic curve of stage 1 InvTime_U operation of phase overvoltage protection. PCS-9613S Differential Relay 3-132 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The setting for selecting the inverse-time dropout characteristic curve of stage 10 59P1.Opt_Curve_DropOut Inst; DefTime Inst - - 1 of phase overvoltage protection Inst: instantaneous dropout DefTime: definite-time dropout The time multiplier setting of 11 59P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase overvoltage protection The minimum operating time 12 59P1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of phase overvoltage protection The constant “k” of the customized 13 59P1.K 0.001~120 1 - 0.0001 inverse-time operation characteristic of stage 1 of phase overvoltage protection The constant “α” of the customized 14 59P1.Alpha 0.01 ~3 1 - 0.0001 inverse-time operation characteristic of stage 1 of phase overvoltage protection The constant “C” of the customized 15 59P1.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 1 of phase overvoltage protection The voltage setting of stage 16 59P2.U_Set 57.7~200 115 V 0.001 2 of phase overvoltage protection The dropout coefficient of 17 59P2.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 2 of phase overvoltage protection The operating time setting of 18 59P2.t_Op 0.1 ~100 1 s 0.001 stage 2 of phase overvoltage protection The dropout time setting of 19 59P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase overvoltage protection PCS-9613S Differential Relay 3-133 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range value Unit Step Description The 20 59P2.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 2 of phase overvoltage protection Enabling stage 2 of phase 21 59P2.Opt_Trp/Alm overvoltage Trp; Trp Alm - - protection operate to trip or alarm. Trp: for tripping purpose 3 Alm: for alarm purpose The setting for selecting the ANSIDefTime; 22 59P2.Opt_Curve IECDefTime; UserDefine; inverse-time IECDefTime - - 2 InvTime_U operation characteristic curve of stage of phase overvoltage protection. The setting for selecting the inverse-time dropout characteristic curve of stage 23 59P2.Opt_Curve_DropOut Inst; DefTime Inst - - 2 of phase overvoltage protection Inst: instantaneous dropout DefTime: definite-time dropout The time multiplier setting of 24 59P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase overvoltage protection The minimum operating time 25 59P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase overvoltage protection The constant “k” of the customized 26 59P2.K 0.001~120 1 - 0.0001 inverse-time operation characteristic of stage 2 of phase overvoltage protection The constant “α” of the customized 27 59P2.Alpha 0.01 ~3 1 - 0.0001 inverse-time operation characteristic of stage 2 of phase overvoltage protection PCS-9613S Differential Relay 3-134 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The constant “C” of the customized 28 59P2.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 2 of phase overvoltage protection 3.14 Residual Overvoltage Protection (59G) If an earth fault occurs in the feeder of a high-resistance grounding system, the residual current changes little and is difficult to detect. However, the amplitude of the residual voltage changes significantly and can be used as a criterion for earth fault. In addition, the neutral point gap of the transformer is grounded, once a fault occurs, the residual voltage increases, and the residual overvoltage protection can also be used as the backup protection of the transformer, the residual voltage is calculated internally by the protection device using three-phase voltage. 3.14.1 Function Description The device can provide two stages of residual overvoltage protection with independent logic. When the residual voltage is greater than the voltage threshold, the residual overvoltage protection will operate to remove the device from the system after a time delay. In addition, the residual overvoltage protection also provides the alarm function, it prompt that there is an earth fault leading to residual voltage generation, it allows users to find the cause timely, and preventing further deterioration of the fault. The dropout characteristics of residual overvoltage protection can be set as instantaneous dropout and definite-time dropout. Residual overvoltage protection can be enabled or disabled via the settings or binary input signals, for some specific applications, residual overvoltage protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block residual overvoltage protection. In addition, if the residual voltage used by residual overvoltage protection is the calculated residual voltage, once the VT of the local side is out of service, residual overvoltage protection will be disabled. The enabling and blocking logic of residual overvoltage protection is shown in the figure below: EN & 59Gx.En 59Gx.On SIG 59Gx.Enable SIG 59Gx.Block SIG Fail_Device EN [En_VT] & ≥1 59Gx.Blocked & & 59Gx.Valid SIG BI_En_VT Figure 3.14-1 The enabling and blocking logic of residual overvoltage protection PCS-9613S Differential Relay 3-135 Date: 2020-09-02 3 3 Protection Functions The logic diagram of the fault detector element of residual overvoltage protection is as follows: & SET 3U0_Cal >3U0_DropOut 59Gx.Pkp 0ms SIG 3 500ms & & 59Gx.On SIG 59Gx.Valid EN [59Gx.Opt_Trp/Alm]=Alm FD.Pkp Figure 3.14-2 Logic diagram of the fault detector element of residual overvoltage protection Where: 3U0_DropOut: the dropout voltage value, i.e. [59Gx.K_DropOut]*[59Gx.3U0_Set] 3.14.1.1 Operation Characteristic Residual overvoltage protection can operate with a settable time delay. When U 0 > U 0 p , the protection operates with a time delay of top (i.e. the value of the setting [59Gx.t_Op]), and the operation characteristic curve is shown in the following figure: t t op U0p U0 Figure 3.14-3 Definite-time operation characteristic curve of residual overvoltage protection 3.14.1.2 Dropout Characteristic The supported dropout characteristics of the residual overvoltage protection include instantaneous dropout and definite-time dropout. ⚫ Instantaneous dropout When U 0 <[59Gx.K_DropOut]* U 0 p , the protection drops out immediately. PCS-9613S Differential Relay 3-136 Date: 2020-09-02 3 Protection Functions ⚫ Definite-time dropout When U 0 <[59Gx.K_DropOut]* U 0 p , the protection drops out with a time delay of tdr (i.e. the value of the setting [59Gx.t_DropOut]), and the dropout characteristic curve is shown in the following figure: Start time U0>U0p 3 Start signal Operating signal Protection operate Operating threshold Operating counter t dr Dropout time setting t dr t dr Dropout time Dropout time Figure 3.14-4 Definite-time dropout characteristic of residual overvoltage protection 3.14.2 Function Block Diagram 59G 59Gx.Enable 59Gx.On 59Gx.Block 59Gx.Blocked 59Gx.Valid 59Gx.St 59Gx.Op 59Gx.Alm 3.14.3 I/O Signal Table 3.14-1 Input/output signals of residual overvoltage protection No. 1 Input signal 59Gx.Enable Description Stage x of residual overvoltage protection enabling input, it is triggered from PCS-9613S Differential Relay 3-137 Date: 2020-09-02 3 Protection Functions binary input or programmable logic etc. (x=1~2) 2 No. 3 Stage x of residual overvoltage protection blocking input, it is triggered from 59Gx.Block binary input or programmable logic etc. (x=1~2) Output signal Description 1 59Gx.On Stage x of residual overvoltage protection is enabled 2 59Gx.Blocked Stage x of residual overvoltage protection is blocked 3 59Gx.Valid Stage x of residual overvoltage protection is valid 4 59Gx.St Stage x of residual overvoltage protection starts 5 59Gx.Op Stage x of residual overvoltage protection operates 6 59Gx.Alm Stage x of residual overvoltage protection alarms 3.14.4 Logic 59Gx.St SET & 3U0_Cal> [59Gx.3U0_Set] [59Gx.t_Op] [59Gx.t_DropOut] & 59Gx.Op SIG 59Gx.Pkp SET [59Gx.Opt_Trp/Alm] = Trp SET [59Gx.Opt_Trp/Alm] = Alm & 59Gx.Alm Figure 3.14-5 Logic diagram of residual overvoltage protection 3.14.5 Settings ⚫ Access path: MainMenu Settings Protection Settings ROV Settings Table 3.14-2 Settings of residual overvoltage protection No. Settings Range Default value Unit Step 1 59G1.3U0_Set 1~200 50 V 0.001 2 59G1.K_DropOut 0.93 ~1 0.98 - 0.001 3 59G1.t_Op 0.1 ~100 1 s 0.001 4 59G1.t_DropOut 0 ~100 0 s 0.001 5 59G1.En Enabled - - Disabled; Enabled Description The voltage setting of stage 1 of residual overvoltage protection The dropout coefficient of stage 1 of residual overvoltage protection The operating time setting of stage 1 of residual overvoltage protection The dropout time setting of stage 1 of residual overvoltage protection The logic setting for enabling/disabling the stage 1 of residual overvoltage protection PCS-9613S Differential Relay 3-138 Date: 2020-09-02 3 Protection Functions No. Settings Range Default value Unit Step Description Enabling stage 1 of residual overvoltage 6 59G1.Opt_Trp/Alm Trp; Alm Trp - - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 7 59G2.3U0_Set 1~200 50 V 0.001 8 59G2.K_DropOut 0.93 ~1 0.98 - 0.001 9 59G2.t_Op 0.1 ~100 1 s 0.001 10 59G2.t_DropOut 0 ~100 0 s 0.001 11 59G2.En Enabled - - Disabled; Enabled The voltage setting of stage 2 of residual overvoltage protection The dropout coefficient of stage 2 of residual overvoltage protection The operating time setting of stage 2 of residual overvoltage protection The dropout time setting of stage 2 of residual overvoltage protection The logic setting for enabling/disabling the stage 2 of residual overvoltage protection Enabling stage 2 of residual overvoltage 12 59G2.Opt_Trp/Alm Trp; Alm Trp - - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 3.15 Negative-sequence Overvoltage Protection (59Q) When the system has a broken-conductor, reverse phase sequence or inter-phase voltage imbalance, the negative-sequence voltage increases, and the negative-sequence overvoltage protection can reflect the system imbalance fault. It is used to protect the equipment from insulation breakdown or premature aging due to overvoltage. The negative-sequence overvoltage protection can also be used to alarm for prompting users the system voltage state is abnormal at this moment. 3.15.1 Function Description This device provides two stages of negative-sequence overvoltage protection. If the negative-sequence voltage is larger than the predefined setting, this protection will operate. The negative-sequence overvoltage protection is with independent definite-time delay characteristic and with definite-time delay or instantaneous dropout characteristic. Negative-sequence overvoltage protection can be enabled or disabled via the settings or binary input signals, for some specific applications, overvoltage protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block overvoltage protection. In addition, if the VT of the local side is out of service, negative-sequence overvoltage protection will be disabled.The enabling and blocking logic of negative-sequence overvoltage protection is shown in the figure below: PCS-9613S Differential Relay 3-139 Date: 2020-09-02 3 3 Protection Functions EN & 59Qx.En 59Qx.On SIG 59Qx.Enable SIG 59Qx.Block SIG Fail_Device EN [En_VT] & ≥1 59Qx.Blocked & & 59Qx.Valid SIG 3 BI_En_VT Figure 3.15-1 Logic diagram of enabling/disabling negative-sequence overvoltage protection When the negative-sequence overvoltage protection is enabled and no external blocking signal is input, if the negative-sequence voltage is larger than the voltage setting multiplied by the dropout coefficient setting of the negative-sequence overvoltage protection, the negative-sequence overvoltage protection will pick up. The logic diagram of the fault detector of the negative-sequence overvoltage protection is shown as below. SET U2 >U2_DropOut & 59Qx.Pkp 0ms SIG 500ms SIG 59Qx.Valid EN [59Qx.Opt_Trp/Alm]=Alm & & 59Qx.On FD.Pkp Figure 3.15-2 Logic diagram of the fault detector of negative-sequence overvoltage protection Where: U2_DropOut: the dropout voltage value, i.e. [59Qx.K_DropOut]*[59Qx.U2_Set] 3.15.1.1 Operation Characteristic Negative-sequence overvoltage protection can operate with a definite-time limit. When the negative-sequence voltage is larger than the voltage setting, the protection operates with a time delay of top (i.e. the value of the setting [59Qx.t_Op]), and the operation characteristic curve is shown in the following figure: PCS-9613S Differential Relay 3-140 Date: 2020-09-02 3 Protection Functions t t op 3 U2p U2 Figure 3.15-3 Operation characteristic curve of negative-sequence overvoltage protection 3.15.1.2 Dropout Characteristic The supported dropout characteristics of the negative-sequence overvoltage protection include instantaneous dropout and definite-time dropout. ⚫ Instantaneous dropout When U2 <[ 59Qx.K_DropOut]*[59Qx.U2_Set] (x: 1~2), the protection drops out immediately. ⚫ Definite-time dropout When U2 <[59Qx.K_DropOut]*[59Qx.U2_Set] (x: 1~2), the protection drops out with a time delay of tdr (i.e. the value of the setting [59Qx.t_DropOut]), and the dropout characteristic curve is shown in the following figure: PCS-9613S Differential Relay 3-141 Date: 2020-09-02 3 Protection Functions Start time U 2> U2p Start signal Operating signal 3 Protection operate Operating threshold Operating counter t dr Dropout time setting t dr t dr Dropout time Dropout time Figure 3.15-4 Definite-time dropout characteristic of negative-sequence overvoltage protection 3.15.2 Function Block Diagram 59Q 59Qx.Enable 59Qx.On 59Qx.Block 59Qx.Blocked 59Qx.Valid 59Qx.St 59Qx.Op 59Qx.Alm 3.15.3 I/O Signals Table 3.15-1 Input/output signals of negative-sequence overvoltage protection No. Input Signal 1 59Qx.Enable 2 59Qx.Block No. 1 Description Stage x of negative-sequence overvoltage protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~2) Stage x of negative-sequence overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~2) Output Signal 59Qx.On Description Stage x of negative-sequence overvoltage protection is enabled PCS-9613S Differential Relay 3-142 Date: 2020-09-02 3 Protection Functions 2 59Qx.Blocked Stage x of negative-sequence overvoltage protection is blocked 3 59Qx.Valid Stage x of negative-sequence overvoltage protection is valid 4 59Qx.St Stage x of negative-sequence overvoltage protection starts 5 59Qx.Op Stage x of negative-sequence overvoltage protection operates 6 59Qx.Alm Stage x of negative-sequence overvoltage protection alarms 3.15.4 Logic 59Qx.St SET & U2 > [59Qx.U2_Set] [59Qx.t_Op] [59Qx.t_DropOut] SIG 59Qx.Pkp SET [59Qx.Opt_Trp/Alm] = Trp SET & 59Qx.Op & 59Qx.Alm 3 [59Qx.Opt_Trp/Alm] = Alm Figure 3.15-5 Logic diagram of negative-sequence overvoltage protection 3.15.5 Settings ⚫ Access path: MainMenu Settings Protection Settings NegOV Settings Table 3.15-2 Settings of negative-sequence overvoltage protection No. 1 Setting 59Q1.U2_Set Range 2~100 Default 15 Unit Step V 0.001 Description The voltage setting of the stage 1 of negative-sequence overvoltage protection The dropout coefficient setting of the stage 2 59Q1.K_DropOut 0.93~1 0.98 - 0.001 1 of negative-sequence overvoltage protection 3 59Q1.t_Op 0.1~100 1 s 0.001 4 59Q1.t_DropOut 0~100 0 s 0.001 5 59Q1.En Enabled - - Disabled; Enabled The time setting of the stage 1 of negative-sequence overvoltage protection The dropout time setting of the stage 1 of negative-sequence overvoltage protection The logic setting of the stage 1 of negative-sequence overvoltage protection Enabling stage 1 of negative-sequence 6 59Q1.Opt_Trp/Alm Trp; Alm Trp - - overvoltage operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 7 59Q2.U2_Set 2~100 15 V 0.001 PCS-9613S Differential Relay The voltage setting of the stage 2 of negative-sequence overvoltage protection 3-143 Date: 2020-09-02 3 Protection Functions The dropout coefficient setting of the stage 8 59Q2.K_DropOut 0.93~1 0.98 - 0.001 2 of negative-sequence overvoltage protection 9 59Q2.t_Op 0.1~100 1 s 0.001 10 59Q2.t_DropOut 0~100 0 s 0.001 11 59Q2.En Enabled - - Disabled; Enabled The time setting of the stage 2 of negative-sequence overvoltage protection The dropout time setting of the stage 2 of negative-sequence overvoltage protection The logic setting of the stage 2 of negative-sequence overvoltage protection Enabling stage 2 of negative-sequence 3 12 59Q2.Opt_Trp/Alm Trp; Alm Trp - - overvoltage operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 3.16 Positive-sequence Overvoltage Protection (59Pos) 3.16.1 Function Description This device provides one stage of positive-sequence overvoltage protection. If the positive-sequence voltage is larger than the pre-defined setting, this protection will operate. The positive-sequence overvoltage protection can operate with a definite-time limit, and the supported dropout characteristics include instantaneous dropout and definite-time dropout. Positive-sequence overvoltage protection can be enabled or disabled via the settings or binary input signals, for some specific applications, overvoltage protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block overvoltage protection. In addition, if the VT of the local side is out of service, positive-sequence overvoltage protection will be disabled. The enabling and blocking logic of positive-sequence overvoltage protection is shown in the figure below: The logic diagram of enabling/disabling positive-sequence overvoltage protection is shown as below. EN & 59Pos.En 59Pos.On SIG 59Pos.Enable SIG 59Pos.Block SIG Fail_Device EN [En_VT] & ≥1 59Pos.Blocked & & 59Pos.Valid SIG BI_En_VT Figure 3.16-1 Logic diagram of enabling/disabling positive-sequence overvoltage protection PCS-9613S Differential Relay 3-144 Date: 2020-09-02 3 Protection Functions When the positive-sequence overvoltage protection is enabled and no external blocking signal is input, if the positive-sequence voltage is larger than the voltage setting multiplied by the dropout coefficient setting of the positive-sequence overvoltage protection, the positive-sequence overvoltage protection will pick up. The logic diagram of the fault detector of the positive-sequence overvoltage protection is shown as below. & SET U1 >U1_DropOut 59Pos.Pkp 0ms SIG 500ms & & 59Pos.On SIG 59Pos.Valid EN [59Pos.Opt_Trp/Alm]=Alm 3 FD.Pkp Figure 3.16-2 Logic diagram of the fault detector of positive-sequence overvoltage protection Where: U1: the positive-sequence voltage; U1_DropOut: the dropout voltage value, i.e. [59Pos.K_DropOut]*[59Pos.U1_Set]. 3.16.1.1 Operation Characteristic Positive-sequence overvoltage protection can operate with a definite-time limit. When the positive-sequence voltage is larger than the voltage setting, the protection operates with a time delay of top (i.e. the value of the setting [59Pos.t_Op]), and the operation characteristic curve is shown in the following figure: t t op U 1p U1 Figure 3.16-3 Operation characteristic curve of positive-sequence overvoltage protection PCS-9613S Differential Relay 3-145 Date: 2020-09-02 3 Protection Functions 3.16.1.2 Dropout Characteristic The supported dropout characteristics of the positive-sequence overvoltage protection include instantaneous dropout and definite-time dropout. ⚫ Instantaneous dropout When U <[ 59Pos.K_DropOut]*[59Pos.U1_Set] (x: 1~2), the protection drops out immediately. 1 ⚫ Definite-time dropout When U <[59Pos.K_DropOut]*[59Pos.U1_Set] (x: 1~2), the protection drops out with a time delay of tdr (i.e. the value of the setting [59Pos.t_DropOut]), and the dropout characteristic curve is 1 3 shown in the following figure: Start time U 1> U1p Start signal Operating signal Protection operate Operating threshold Operating counter t dr Dropout time setting t dr t dr Dropout time Dropout time Figure 3.16-4 Definite-time dropout characteristic of positive-sequence overvoltage protection PCS-9613S Differential Relay 3-146 Date: 2020-09-02 3 Protection Functions 3.16.2 Function Block Diagram 59Pos 59Pos.Enable 59Pos.On 59Pos.Block 59Pos.Blocked 59Pos.Valid 59Pos.St 59Pos.Op 59Pos.Alm 3 3.16.3 I/O Signals Table 3.16-1 Input/output signals of positive-sequence overvoltage protection No. Input Signal 1 59Pos.Enable 2 59Pos.Block No. Description Positive-sequence overvoltage protection enabling input, it is triggered from binary input or programmable logic etc. Positive-sequence overvoltage protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 59Pos.On Positive-sequence overvoltage protection is enabled 2 59Pos.Blocked Positive-sequence overvoltage protection is blocked 3 59Pos.Valid Positive-sequence overvoltage protection is valid 4 59Pos.St Positive-sequence overvoltage protection starts 5 59Pos.Op Positive-sequence overvoltage protection operates 6 59Pos.Alm Positive-sequence overvoltage protection alarms 3.16.4 Logic 59Pos.St SET U1 > [59Pos.U1_Set] & [59Pos.t_Op] [59Pos.t_DropOut] SIG 59Pos.Pkp SET [59Pos.Opt_Trp/Alm] = Trp SET & 59Pos.Op & 59Pos.Alm [59Pos.Opt_Trp/Alm] = Alm Figure 3.16-5 Logic diagram of positive-sequence overvoltage protection 3.16.5 Settings ⚫ Access path: MainMenu Settings Protection Settings PosOV Settings PCS-9613S Differential Relay 3-147 Date: 2020-09-02 3 Protection Functions Table 3.16-2 Settings of positive-sequence overvoltage protection No. Setting Range Default Unit Step 6 59Pos.U1_Set 2~100 60 V 0.001 7 59Pos.K_DropOut 0.93~1 0.98 - 0.001 8 59Pos.t_Op 0.1~100 1 s 0.001 9 59Pos.t_DropOut 0~100 0 s 0.001 10 59Pos.En Enabled - - 3 Disabled; Enabled Description The voltage 59Pos.Opt_Trp/Alm Trp; Alm Trp - - of the positive-sequence overvoltage protection The dropout coefficient setting of the positive-sequence overvoltage protection The time setting of the positive-sequence overvoltage protection The dropout time setting of the positive-sequence overvoltage protection The logic setting of the positive-sequence overvoltage protection Enabling 11 setting the positive-sequence overvoltage operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 3.17 Phase Undervoltage Protection (27P) Some abnormal conditions in the power system will lead to low voltage. Electric equipment such as motors cannot operate for a long time under the rated voltage and need to be removed from the system in time. In addition, the voltage reduction may also be related to the shortage of system reactive power. Reducing part of the reactive power load through the undervoltage protection can help increase the voltage level of the system. 3.17.1 Function Description The device can provide two stages of phase undervoltage protection with independent logic. When the voltage drops in the system and it is lower than the voltage threshold, phase undervoltage protection will operate. Taking into account that the role of undervoltage protection is to remove the running device from the system, but in order to prevent that undervoltage protection is always operating when it is not charged, the breaker closed position check criterion is added, users can choose to detect the breaker position, current or no-check as the releasing condition for the protection. In addition, the undervoltage protection also provides the alarm function, prompting the voltage drop of the system, it allows users to find the cause timely, and preventing further deterioration of the fault. Each stage of phase undervoltage protection can be independently set as definite-time characteristics or inverse-time characteristics. The dropout characteristics can be set as instantaneous dropout and definite-time dropout. Users can select phase voltage or phase-to-phase voltage for the protection calculation via the setting [27P.Opt_Up/Upp]. If it is set as “Up”, phase voltage criterion is selected, and if it is set to “Upp”, phase-to-phase voltage criterion is selected. Users can select “1-out-of-3” or “3-out-of-3” logic for the protection criterion via the setting PCS-9613S Differential Relay 3-148 Date: 2020-09-02 3 Protection Functions [27P.Opt_1P/3P]. If it is set as “1P”, phase undervoltage protection can operate if any phase/phase-to-phase voltage is smaller than the voltage setting. If it is set as “3P”, phase undervoltage protection cannot operate unless three phase/phase-to-phase voltages are smaller than the voltage setting. The breaker closed position check mode is configured via the setting [27P.Opt_LogicMode], it includes: [27P.Opt_LogicMode]=None: no-check; [27P.Opt_LogicMode]=Curr: check the current; 3 [27P.Opt_LogicMode]=CBPos: check the breaker position; [27P.Opt_LogicMode]=CurrAndCBPos: check the current and the breaker position; [27P.Opt_LogicMode]=CurrOrCBPos: check the current or the breaker position. Undervoltage protection can be enabled or disabled via the settings or binary input signals, for some specific applications, undervoltage protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block undervoltage protection. In addition, if the VT of the local side is out of service, undervoltage protection will be disabled. The enabling and blocking logic of undervoltage protection is shown in the figure below: EN & 27Px.En 27Px.On SIG 27Px.Enable SIG 27Px.Block SIG Fail_Device EN [En_VT] & ≥1 27Px.Blocked & & 27Px.Valid SIG BI_En_VT Figure 3.17-1 The enabling and blocking logic of phase undervoltage protection The logic diagram of the fault detector element of phase undervoltage protection is as follows: PCS-9613S Differential Relay 3-149 Date: 2020-09-02 3 Protection Functions SET [27P.Opt_1P/3P]=3P & SET [27P.Opt_Up/Upp]=Upp SET Uab<[U_DropOut] & SET Ubc<[U_DropOut] >=1 SET Uca<[U_DropOut] & SET [27P.Opt_1P/3P]=1P SET Uab<[U_DropOut] 3 >=1 SET Ubc<[U_DropOut] SET Uca<[U_DropOut] SET [27P.Opt_1P/3P]=3P & SET [27P.Opt_Up/Upp]=Up SET Ua<[U_DropOut] & SET Ub<[U_DropOut] >=1 Pickup voltage criterion >=1 SET Uc<[U_DropOut] & SET [27P.Opt_1P/3P]=1P SET Ua<[U_DropOut] >=1 SET Ub<[U_DropOut] SET Uc<[U_DropOut] SET [27P.Opt_LogicMode]=None SET [27P.Opt_LogicMode]=Curr & >=1 >=1 SIG Ia, Ib and Ic > 0.04In SET [27P.Opt_LogicMode]=CBPos Auxiliary criterion & SIG CB closed position >=1 & >=1 SET [27P.Opt_LogicMode]=CurrOrCBPos & & SET [27P.Opt_LogicMode]=CurrAndCBPos PCS-9613S Differential Relay 3-150 Date: 2020-09-02 3 Protection Functions SIG Pickup voltage criterion & 0 SIG Auxiliary criterion 500ms 27Px.Pkp & & SIG VTS.Alm FD.Pkp & & EN [27Px.En_VTS_Blk] SIG 27Px.On SIG 27Px.Valid SET [27Px.Opt_Trp/Alm]=Alm 3 Figure 3.17-2 Logic diagram of the fault detector element of phase undervoltage protection Where: U_DropOut: the dropout voltage value, i.e. [27Px.K_DropOut]*[27Px.U_Set] 3.17.1.1 Operation Characteristic Undervoltage protection can operate with a definite-time limit, it can also operate with an inverse-time limit. Undervoltage protection can support definite-time limit, IEC & ANSI standard inverse time limit and user-defined inverse-time limit, users can select the wanted operating curve by the setting [27Px.Opt_Curve] (x=1 or 2), the relationship between the value of the setting and the curve is shown in the table below. 27Px.Opt_Curve Time Characteristic α k c ANSIDefTime ANSI Definite Time - - - IECDefTime IEC Definite Time - - - UserDefine UserDefine InvTime_U InvCrv_U 1 1 0 When the setting [27Px.Opt_Curve] is set as “InvTime_U”, the operation characteristic is the corresponding selected operating curve type, and the settings [27Px.K], [27Px.C] and [27Px.Alpha] are useless. When the setting [27Px.Opt_Curve] is set as “UserDefine”, i.e. the user-defined inverse-time characteristic is selected, the inverse-time operating curve is determined by the settings [27Px.K], [27Px.C] and [27Px.Alpha]. When the setting [27Px.Opt_Curve] is set as “ANSIDefTime” or “IECDefTime”, it is definite-time undervoltage protection. ⚫ Definite-time characteristic When U < Up , the protection operates with a time delay of top (i.e. the value of the setting [27Px.t_Op]), and the operation characteristic curve is shown in the following figure: PCS-9613S Differential Relay 3-151 Date: 2020-09-02 3 Protection Functions t t op 3 Up U Figure 3.17-3 Definite-time operation characteristic curve of phase undervoltage protection ⚫ Inverse-time characteristic When U < Up , the inverse-time accumulator begins to accumulate, and the operating time is affected by the applied voltage U . The lower voltage is, the smaller the operating time is, but not unlimited. When the voltage is low enough to a certain threshold ( Up ), the inverse-time operating time will not continue to decrease, then the operation characteristic becomes the definite-time characteristic, and the operating time is tmin , i.e. the setting [27Px.tmin]. The inverse-time operation characteristic equation is: k t= + c TMS 1 − (U / U P ) Where: Up is the voltage setting [27Px.U_Set]; TMS is the inverse-time time multiplier, i.e. the setting [27Px.TMS]; k is the inverse-time coefficient K, i.e. the setting [27Px.K]; c is the inverse-time coefficient C, i.e. the setting [27Px.C]; is the inverse-time coefficient Alpha, i.e. the setting [27Px.Alpha]; U is the measured voltage. The inverse-time operation characteristic curve is shown as below: PCS-9613S Differential Relay 3-152 Date: 2020-09-02 3 Protection Functions t 3 t min UD UP U Figure 3.17-4 Inverse-time operation characteristic curve of phase undervoltage protection When the applied voltage is not a fixed value, but changes with time, the operating behaviour of the protection is shown in the following equation: T0 1 t (U )dt =1 0 Where: T0 is the operating time of the protection element; t (U ) is the theoretical operating time when the voltage is U . 3.17.1.2 Dropout Characteristic The supported dropout characteristics of the undervoltage protection include instantaneous dropout and definite-time dropout. ⚫ Instantaneous dropout When U >[27Px.K_DropOut]* Up , the protection drops out immediately. ⚫ Definite-time dropout When U >[27Px.K_DropOut]* Up , the protection drops out with a time delay of tdr (i.e. the value of the setting [27Px.t_DropOut]), and the dropout characteristic curve is shown in the following figure: PCS-9613S Differential Relay 3-153 Date: 2020-09-02 3 Protection Functions Start time U<Up Start signal 3 Operating signal Protection operate Operating threshold Operating counter t dr t dr Dropout time setting t dr Dropout time Dropout time Figure 3.17-5 Definite-time dropout characteristic of undervoltage protection 3.17.2 Function Block Diagram 27P 27Px.Enable 27Px.Block 27Px.On 27Px.Blocked 27Px.Valid 27Px.St 27Px.StA 27Px.StB 27Px.StC 27Px.Op 27Px.Op.PhA 27Px.Op.PhB 27Px.Op.PhC 27Px.Alm PCS-9613S Differential Relay 3-154 Date: 2020-09-02 3 Protection Functions 3.17.3 I/O Signal Table 3.17-1 Input/output signals of phase undervoltage protection No. Input signal 1 27Px.Enable 2 27Px.Block No. Description Stage x of phase undervoltage protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~2) Stage x of phase undervoltage protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~2) Output signal Description 1 27Px.On Stage x of phase undervoltage protection is enabled 2 27Px.Blocked Stage x of phase undervoltage protection is blocked 3 27Px.Valid Stage x of phase undervoltage protection is valid 4 27Px.St Stage x of phase undervoltage protection starts 5 27Px.StA Stage x of phase undervoltage protection starts (Phase A or AB) 6 27Px.StB Stage x of phase undervoltage protection starts (Phase B or BC) 7 27Px.StC Stage x of phase undervoltage protection starts (Phase C or CA) 8 27Px.Op Stage x of phase undervoltage protection operates 9 27Px.Op.PhA Stage x of phase undervoltage protection operates (Phase A or AB) 10 27Px.Op.PhB Stage x of phase undervoltage protection operates (Phase B or BC) 11 27Px.Op.PhC Stage x of phase undervoltage protection operates (Phase C or CA) 12 27Px.Alm Stage x of undervoltage protection alarms PCS-9613S Differential Relay 3 3-155 Date: 2020-09-02 3 Protection Functions 3.17.4 Logic SET [27P.Opt_1P/3P]=3P & SET [27P.Opt_Up/Upp]=Upp SET Uab<[27Px.U_Set] & SET Ubc<[27Px.U_Set] >=1 SET Uca<[27Px.U_Set] & SET [27P.Opt_1P/3P]=1P 3 SET Uab<[27Px.U_Set] >=1 SET Ubc<[27Px.U_Set] SET Uca<[27Px.U_Set] SET [27P.Opt_1P/3P]=3P & SET [27P.Opt_Up/Upp]=Up SET Ua<[27Px.U_Set] & SET Ub<[27Px.U_Set] >=1 Voltage criterion >=1 SET Uc<[27Px.U_Set] & SET [27P.Opt_1P/3P]=1P SET Ua<[27Px.U_Set] >=1 SET Ub<[27Px.U_Set] SET Uc<[27Px.U_Set] SIG Voltage criterion SIG Auxiliary criterion SIG VTS.Alm EN [27Px.En_VTS_Blk] SIG 27Px.On SIG 27Px.Pkp SET [27Px.Opt_Trp/Alm]=Trp 27Px.St & & Timer t t & & & 27Px.Op & 27Px.Alm SET [27Px.Opt_Trp/Alm]=Alm Figure 3.17-6 Logic diagram of phase undervoltage protection PCS-9613S Differential Relay 3-156 Date: 2020-09-02 3 Protection Functions Where: Auxiliary criterion: please refer to Figure 3.17-2. 3.17.5 Settings ⚫ Access path: MainMenu Settings Protection Settings UV Settings Table 3.17-2 Settings of phase undervoltage protection No. Settings Default Range value Unit Step Description 3 Option of phase-to-phase voltage or phase voltage 1 27P.Opt_Up/Upp for Up; Upp Upp - - stage x of undervoltage protection Up: phase voltage Upp: phase-to-phase voltage Option of 1-out-of-3 mode or 3-out-of-3 mode for 2 27P.Opt_1P/3P 3P; 3P 1P - - stage x of undervoltage protection 3P: 3-out-of-3 mode 1P: 1-out-of-3 mode Breaker closed position check mode None: no check Curr: check the current 3 27P.Opt_LogicMode None; CBPos: Curr; normally CBPos; Curr - - check open the auxiliary contact CurrOrCBPos; CurrOrCBPos: check the CurrAndCBPos current or normally open auxiliary contact CurrAndCBPos: check the current and normally open auxiliary contact The voltage setting of 4 27P1.U_Set 5~120 80 V 0.001 stage 1 of phase undervoltage protection The dropout coefficient of 5 27P1.K_DropOut 1~1.2 1.03 - 0.001 stage 1 of phase undervoltage protection PCS-9613S Differential Relay 3-157 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The operating time setting 6 27P1.t_Op 0.1 ~100 1 s 0.001 of stage 1 of phase undervoltage protection The dropout time setting 7 27P1.t_DropOut 0 ~100 0 s 0.001 of stage 1 of phase undervoltage protection Logic setting to determine the behaviour of stage 1 of 3 phase undervoltage protection when VT circuit 8 27P1.En_VTS_Blk supervision Disabled; Disabled Enabled - - function is enabled and VT circuit failure happens. Disabled: it is not affected by VT circuit failure Enabled: it will be blocked by VT circuit failure signal The 9 27P1.En Disabled; Enabled Enabled - - logic setting enabling/disabling stage 1 of for the phase undervoltage protection Enabling stage 1 of phase 10 27P1.Opt_Trp/Alm undervoltage Trp; Trp Alm - - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose The setting for selecting ANSIDefTime; 11 27P1.Opt_Curve IECDefTime; UserDefine; the inverse-time operation IECDefTime - - characteristic stage InvTime_U 1 curve of of phase undervoltage protection. The setting for selecting the inverse-time dropout characteristic 12 27P1.Opt_Curve_DropOut Inst; DefTime stage Inst - - 1 curve of of phase undervoltage protection Inst: instantaneous dropout DefTime: definite-time dropout PCS-9613S Differential Relay 3-158 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The time multiplier setting 13 27P1.TMS 0.04~ 20 1 - 0.001 of stage 1 of phase undervoltage protection The minimum operating 14 27P1.tmin 0.03 ~10 0.03 s 0.001 time setting of stage 1 of phase undervoltage protection The constant “k” of the customized 15 27P1.K 0.001~120 0.14 - 0.0001 inverse-time operation characteristic of stage 1 of phase undervoltage protection The constant “α” of the customized 16 27P1.Alpha 0.01 ~3 0.02 - 0.0001 inverse-time operation characteristic of stage 1 of phase undervoltage protection The constant “C” of the customized 17 27P1.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 1 of phase undervoltage protection The voltage setting of 18 27P2.U_Set 5~120 80 V 0.001 stage 2 of phase undervoltage protection The dropout coefficient of 19 27P2.K_DropOut 1~1.2 1.03 - 0.001 stage 2 of phase undervoltage protection The operating time setting 20 27P2.t_Op 0.1 ~100 1 s 0.001 of stage 2 of phase undervoltage protection The dropout time setting 21 27P2.t_DropOut 0 ~100 0 s 0.001 of stage 2 of phase undervoltage protection PCS-9613S Differential Relay 3-159 Date: 2020-09-02 3 3 Protection Functions No. Settings Default Range value Unit Step Description Logic setting to determine the behaviour of stage 2 of phase undervoltage protection when VT circuit 22 27P2.En_VTS_Blk supervision Disabled; Disabled Enabled - - function is enabled and VT circuit failure happens. Disabled: it is not affected 3 by VT circuit failure Enabled: it will be blocked by VT circuit failure signal The 23 27P2.En Disabled; Enabled Enabled - - logic setting enabling/disabling stage 2 of for the phase undervoltage protection Enabling stage 2 of phase 24 27P2.Opt_Trp/Alm undervoltage Trp; Trp Alm - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose The setting for selecting ANSIDefTime; 25 27P2.Opt_Curve IECDefTime; UserDefine; the inverse-time operation IECDefTime - - characteristic stage InvTime_U curve 2 of of phase undervoltage protection. The setting for selecting the inverse-time dropout characteristic 26 27P2.Opt_Curve_DropOut Inst; DefTime stage Inst - - curve 2 of of phase undervoltage protection Inst: instantaneous dropout DefTime: definite-time dropout The time multiplier setting 27 27P2.TMS 0.04~ 20 1 0.001 of stage 2 of phase undervoltage protection The minimum operating 28 27P2.tmin 0.03 ~10 0.03 s 0.001 time setting of stage 2 of phase undervoltage protection PCS-9613S Differential Relay 3-160 Date: 2020-09-02 3 Protection Functions No. Settings Default Range value Unit Step Description The constant “k” of the customized 29 27P2.K 0.001~120 0.14 - 0.0001 inverse-time operation characteristic of stage 2 of phase undervoltage protection The constant “α” of the customized 30 27P2.Alpha 0.01 ~3 0.02 - 0.0001 inverse-time operation characteristic of stage 2 of phase undervoltage protection The constant “C” of the customized 31 27P2.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 2 of phase undervoltage protection 3.18 Overfrequency Protection (81O) Frequency is an important index of the power quality, which can reflect the balance of the output power of the generator and the active power of the load. The increase of frequency indicates that the output power of the system is much larger than that of the load. When the system frequency is greater than the predefined setting, the overfrequency protection will operate for removing some part of active power supplies from the system. 3.18.1 Function Description The device can provide six stages of overfrequency protection. If the system frequency is greater than the setting, overfrequency protection will operate to remove some part of active power supplies from the system. Overfrequency protection is with independent definite-time characteristics and with instantaneous dropout characteristics. Overfrequency protection can be enabled or disabled via the settings or binary input signals, for some specific applications, overfrequency protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block overfrequency protection. The enabling and blocking logic of overfrequency protection is shown in the figure below: PCS-9613S Differential Relay 3-161 Date: 2020-09-02 3 3 Protection Functions EN & 81Ox.En SIG 81Ox.Enable SIG 81Ox.Block SIG Fail_Device 81Ox.On & 81Ox.Blocked ≥1 & 3 81Ox.Valid Figure 3.18-1 Logic diagram of enabling/disabling overfrequency protection When the overfrequency protection is enabled and no external blocking signal is input, if the system frequency is greater than the frequency setting of the overfrequency protection and all the phase-to-phase voltages are greater than the setting of the voltage blocking element of the overfrequency protection, the overfrequency protection will pick up. The logic diagram of the fault detector of the overfrequency protection is shown in Figure 3.18-2. SET f > [81Ox.f_Set] SET Upp_min > [81.Upp_Blk] & & 81Ox.Pkp 0ms SIG 500ms & 81Ox.On FD.Pkp SIG 81Ox.Valid Figure 3.18-2 Logic diagram of the fault detector of overfrequency protection 3.18.1.1 Operation Characteristic The overfrequency protection has definite-time delay characteristic complied with IEC 60255-3 and ANSI C37.112. If the system frequency is greater than the frequency setting [81Ox.f_Set] (x: 1~6), the overfrequency protection will operate after the time setting [81Ox.t_Op] (x: 1~6). The operation characteristic curve of overfrequency protection is shown in Figure 3.18-3. PCS-9613S Differential Relay 3-162 Date: 2020-09-02 3 Protection Functions t t op 3 fp f Figure 3.18-3 Operation characteristic curve of overfrequency protection 3.18.1.2 Dropout Characteristic The overfrequency protection is with instantaneous dropout characteristic. If the system frequency is less than the setting [81Ox.f_Set] (x: 1~6), the overfrequency protection will drop out at once. 3.18.2 Function Block Diagram 81O 81Ox.On 81Ox.Enable 81Ox.Blocked 81Ox.Block 81Ox.Valid 81Ox.St 81Ox.Op 3.18.3 I/O Signals Table 3.18-1 Input/output signals of overfrequency protection No. Input Signal 1 81Ox.Enable 2 81Ox.Block No. Description Stage x of overfrequency protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~6) Stage x of overfrequency protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~6) Output Signal Description 1 81Ox.On Stage x of overfrequency protection is enabled. 2 81Ox.Blocked Stage x of overfrequency protection is blocked. 3 81Ox.Valid Stage x of overfrequency protection is valid. 4 81Ox.St Stage x of overfrequency protection starts. PCS-9613S Differential Relay 3-163 Date: 2020-09-02 3 Protection Functions 5 81Ox.Op Stage x of overfrequency protection operates. 3.18.4 Logic SET f>[81Ox.f_Set] 81Ox.St & & [81Ox.t_Op] 0 SET Upp_min>[81.Upp_Blk] 81Ox.Op SIG 81Ox.Pkp 3 Figure 3.18-4 Logic diagram of overfrequency protection 3.18.5 Settings ⚫ Access path: MainMenu Settings Protection Settings FreqProt Settings Table 3.18-2 Settings of overfrequency protection No. Setting Range Default Unit Step Description The setting of the low voltage blocking 1 81.Upp_Blk 10~150 70 V 0.001 element of the frequency protection (phase-to-phase voltage) 2 81O1.f_Set 50~65 52 Hz 0.001 3 81O1.t_Op 0.1~100 0.3 s 0.001 4 81O1.En Enabled - - 5 81O2.f_Set 50~65 52 Hz 0.001 6 81O2.t_Op 0.1~100 0.3 s 0.001 7 81O2.En Enabled - - 8 81O3.f_Set 50~65 52 Hz 0.001 9 81O3.t_Op 0.1~100 0.3 s 0.001 10 81O3.En Enabled - - 11 81O4.f_Set 50~65 52 Hz 0.001 12 81O4.t_Op 0.1~100 0.3 s 0.001 Disabled; Enabled Disabled; Enabled Disabled; Enabled The frequency setting of the stage 1 of overfrequency protection The time setting of the stage 1 of overfrequency protection The logic setting of the stage 1 of overfrequency protection The frequency setting of the stage 2 of overfrequency protection The time setting of the stage 2 of overfrequency protection The logic setting of the stage 2 of overfrequency protection The frequency setting of the stage 3 of overfrequency protection The time setting of the stage 3 of overfrequency protection The logic setting of the stage 3 of overfrequency protection The frequency setting of the stage 4 of overfrequency protection The time setting of the stage 4 of overfrequency protection PCS-9613S Differential Relay 3-164 Date: 2020-09-02 3 Protection Functions 13 81O4.En 14 81O5.f_Set 15 81O5.t_Op 16 81O5.En 17 81O6.f_Set 18 81O6.t_Op 19 81O6.En Disabled; Enabled - - 50~65 52 Hz 0.001 0.1~100 0.3 s 0.001 Enabled - - 50~65 52 Hz 0.001 0.1~100 0.3 s 0.001 Enabled - - Enabled Disabled; Enabled Disabled; Enabled The logic setting of the stage 4 of overfrequency protection The frequency setting of the stage 5 of overfrequency protection The time setting of the stage 5 of overfrequency protection The logic setting of the stage 5 of overfrequency protection The frequency setting of the stage 6 of overfrequency protection The time setting of the stage 6 of overfrequency protection The logic setting of the stage 6 of overfrequency protection 3.19 Underfrequency Protection (81U) Frequency is an important index of the power quality, which can reflect the balance of the output power of the generator and the active power of the load. The decrease of frequency indicates that the output power of the system is much less than that of the load. When the system frequency is less than the predefined setting, the underfrequency protection will operate for shedding some part of loads from the system. 3.19.1 Function Description This device provides six stages of underfrequency protection. If the system frequency is less than the predefined setting, this protection will operate for shedding some part of loads from the system. The underfrequency protection is with independent definite-time delay characteristic and with instantaneous dropout characteristic. Underfrequency protection can be enabled or disabled via the settings or binary input signals, for some specific applications, underfrequency protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block underfrequency protection. The enabling and blocking logic of underfrequency protection is shown in the figure below: PCS-9613S Differential Relay 3-165 Date: 2020-09-02 3 3 Protection Functions EN & 81Ux.En SIG 81Ux.Enable SIG 81Ux.Block SIG Fail_Device 81Ux.On & 81Ux.Blocked ≥1 & 3 81Ux.Valid Figure 3.19-1 Logic diagram of enabling/disabling underfrequency protection When the underfrequency protection is enabled and no external blocking signal is input, if the system frequency is less than the setting of the underfrequency protection and all the phase-to-phase voltages are greater than the setting of the voltage blocking element of the underfrequency protection, the underfrequency protection will pick up. The logic diagram of the fault detector of the underfrequency protection is shown in Figure 3.19-2. SET f < [81Ux.f_Set] SET Upp_min > [81.Upp_Blk] & & 81Ux.Pkp 0ms SIG 500ms & 81Ux.On FD.Pkp SIG 81Ux.Valid Figure 3.19-2 Logic diagram of the fault detector of underfrequency protection 3.19.1.1 Operation Characteristic The underfrequency protection has definite-time delay characteristic complied with IEC 60255-3 and ANSI C37.112. If the system frequency is less than the frequency setting [81Ux.f_Set] (x: 1~6), the underfrequency protection will operate after the time setting [81Ux.t_Op] (x: 1~6). The operation characteristic curve of underfrequency protection is shown in Figure 3.19-3. PCS-9613S Differential Relay 3-166 Date: 2020-09-02 3 Protection Functions t t op 3 fp f Figure 3.19-3 Operation characteristic curve of underfrequency protection 3.19.1.2 Dropout Characteristic The underfrequency protection is with instantaneous dropout characteristic. If the system frequency is greater than the setting [81Ux.f_Set] (x: 1~6), the underfrequency protection will drop out at once. 3.19.2 Function Block Diagram 81U 81Ux.Enable 81Ux.On 81Ux.Blocked 81Ux.Block 81Ux.Valid 81Ux.St 81Ux.Op 3.19.3 I/O Signals Table 3.19-1 Input/output signals of underfrequency protection No. Input Signal 1 81Ux.Enable 2 81Ux.Block No. Description Stage x of underfrequency protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~6) Stage x of underfrequency protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~6) Output Signal Description 1 81Ux.On Stage x of underfrequency protection is enabled. 2 81Ux.Blocked Stage x of underfrequency protection is blocked. 3 81Ux.Valid Stage x of underfrequency protection is valid. 4 81Ux.St Stage x of underfrequency protection starts. PCS-9613S Differential Relay 3-167 Date: 2020-09-02 3 Protection Functions 5 81Ux.Op Stage x of underfrequency protection operates. 3.19.4 Logic SET f<[81Ux.f_Set] 81Ux.St & & [81Ux.t_Op] 0 SET Upp_min>[81.Upp_Blk] 81Ux.Op SIG 81Ux.Pkp 3 Figure 3.19-4 Logic diagram of underfrequency protection 3.19.5 Settings ⚫ Access path: MainMenu Settings Protection Settings FreqProt Settings Table 3.19-2 Settings of underfrequency protection No. Setting Range Default Unit Step Description The setting of the low voltage blocking 1 81.Upp_Blk 10~150 70 V 0.001 element of the frequency protection (phase-to-phase voltage) 2 81U1.f_Set 45~60 48 Hz 0.001 3 81U1.t_Op 0.1~100 0.3 s 0.001 4 81U1.En Enabled - - 5 81U2.f_Set 45~60 48 Hz 0.001 6 81U2.t_Op 0.1~100 0.3 s 0.001 7 81U2.En Enabled - - 8 81U3.f_Set 45~60 48 Hz 0.001 9 81U3.t_Op 0.1~100 0.3 s 0.001 10 81U3.En Enabled - - 11 81U4.f_Set 45~60 48 Hz 0.001 12 81U4.t_Op 0.1~100 0.3 s 0.001 Disabled; Enabled Disabled; Enabled Disabled; Enabled The frequency setting of the stage 1 of underfrequency protection The time setting of the stage 1 of underfrequency protection The logic setting of the stage 1 of underfrequency protection The frequency setting of the stage 2 of underfrequency protection The time setting of the stage 2 of underfrequency protection The logic setting of the stage 2 of underfrequency protection The frequency setting of the stage 3 of underfrequency protection The time setting of the stage 3 of underfrequency protection The logic setting of the stage 3 of underfrequency protection The frequency setting of the stage 4 of underfrequency protection The time setting of the stage 4 of underfrequency protection PCS-9613S Differential Relay 3-168 Date: 2020-09-02 3 Protection Functions 13 81U4.En 14 81U5.f_Set 15 81U5.t_Op 16 81U5.En 17 81U6.f_Set 18 81U6.t_Op 19 81U6.En Disabled; Enabled - - 45~60 48 Hz 0.001 0.1~100 0.3 s 0.001 Enabled - - 45~60 48 Hz 0.001 0.1~100 0.3 s 0.001 Enabled - - Enabled Disabled; Enabled Disabled; Enabled The logic setting of the stage 4 of underfrequency protection The frequency setting of the stage 5 of underfrequency protection The time setting of the stage 5 of underfrequency protection The logic setting of the stage 5 of underfrequency protection The frequency setting of the stage 6 of underfrequency protection The time setting of the stage 6 of underfrequency protection The logic setting of the stage 6 of underfrequency protection 3.20 Frequency Rate-of-change Protection (81R) Frequency rate-of-change reflects the balance of the generator output power and the active power of the load. It can reflect the increase of active load power and the decrease of frequency. When the frequency changes too fast, it is generally considered that the system has a fault, and the frequency rate-of-change protection can operate in such a situation. 3.20.1 Function Description This device provides six stages of frequency rate-of-change protection. If the system frequency rate-of-change is greater than the predefined setting, this protection will operate. The frequency rate-of-change protection is with independent definite-time delay characteristic and with instantaneous dropout characteristic. The frequency rate-of-change protection protection can be enabled or disabled via the settings or binary input signals, for some specific applications, frequency rate-of-change protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block frequency rate-of-change protection. The enabling and blocking logic of frequency rate-of-change protection is shown in the figure below: PCS-9613S Differential Relay 3-169 Date: 2020-09-02 3 3 Protection Functions EN & 81Rx.En SIG 81Rx.Enable SIG 81Rx.Block SIG Fail_Device 81Rx.On & 81Rx.Blocked ≥1 & 3 81Rx.Valid Figure 3.20-1 Logic diagram of enabling/disabling frequency rate-of-change protection When the frequency rate-of-change protection is enabled and no external blocking signal is input, if the absolute value of the system frequency rate-of-change is greater than the absolute value of setting of the frequency rate-of-change protection, the frequency rate-of-change protection will pick up. The logic diagram of the fault detector of the frequency rate-of-change protection is shown in Figure 3.20-2. SET [81Rx.df/dt_Set] > 0 & df/dt > [81Rx.df/dt_Set] SET Upp_min > [81.Upp_Blk] SET [81Rx.df/dt_Set] < 0 & df/dt < [81Rx.df/dt_Set] SET Upp_min > [81.Upp_Blk] & ≥1 & & 81Rx.Pkp 0ms SIG 81Rx.On SIG 81Rx.Valid 500ms & FD.Pkp Figure 3.20-2 Logic diagram of the fault detector of frequency rate-of-change protection 3.20.1.1 Operation Characteristic The frequency rate-of-change protection has definite-time delay characteristic complied with IEC 60255-3 and ANSI C37.112. If the absolute value of the system frequency rate-of-change is greater than the absolute value of setting [81Rx.df/dt_Set] (x: 1~6), the frequency rate-of-change protection will operate after the time setting [81Rx.t_Op] (x: 1~6). The operation characteristic curve of the frequency rate-of-change protection is shown in Figure 3.20-3. PCS-9613S Differential Relay 3-170 Date: 2020-09-02 3 Protection Functions t top 3 -df/dtset -df/dt df/dtset df/dt Figure 3.20-3 Operation characteristic curve of frequency rate-of-change protection 3.20.1.2 Dropout Characteristic The frequency rate-of-change protection is with instantaneous dropout characteristic. If the absolute value of the system frequency rate-of-change is less than the absolute value of setting [81Rx.df/dt_Set] (x: 1~6), the frequency rate-of-change protection will drop out at once. 3.20.2 Function Block Diagram 81R 81Rx.On 81Rx.Enable 81Rx.Blocked 81Rx.Block 81Rx.Valid 81Rx.St 81Rx.Op 3.20.3 I/O Signals Table 3.20-1 Input/output signals of frequency rate-of-change protection No. Input Signal 1 81Rx.Enable 2 81Rx.Block No. Description Stage x of frequency rate-of-change protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~6) Stage x of frequency rate-of-change protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~6) Output Signal Description 1 81Rx.On Stage x of frequency rate-of-change protection is enabled. 2 81Rx.Blocked Stage x of frequency rate-of-change protection is blocked. 3 81Rx.Valid Stage x of frequency rate-of-change protection is valid. 4 81Rx.St Stage x of frequency rate-of-change protection starts. 5 81Rx.Op Stage x of frequency rate-of-change protection operates. PCS-9613S Differential Relay 3-171 Date: 2020-09-02 3 Protection Functions 3.20.4 Logic SET [81Rx.df/dt_Set] > 0 & df/dt > [81Rx.df/dt_Set] SET f > [81Rx.f_Pkp] SET Upp_min > [81.Upp_Blk] & 81Rx.St ≥1 SET & [81Rx.df/dt_Set] < 0 & df/dt < [81Rx.df/dt_Set] [81Rx.t_Op] & 3 SET f < [81Rx.f_Pkp] SET Upp_min > [81.Upp_Blk] SIG 81Rx.Pkp 0 81Rx.Op Figure 3.20-4 Logic diagram of frequency rate-of-change protection 3.20.5 Settings ⚫ Access path: MainMenu Settings Protection Settings FreqProt Settings Table 3.20-2 Settings of frequency rate-of-change protection No. Setting Range Default Unit Step Description The setting of the low voltage blocking 1 81.Upp_Blk 10~150 70 V 0.001 element of the frequency protection (phase-to-phase voltage) 2 81R1.df/dt_Set -5~5 0.5 Hz/s 0.001 3 81R1.t_Op 0.1~100 0.1 s 0.001 4 81R1.f_Pkp 45~65 50 Hz 0.001 5 81R1.En Enabled - - 6 81R2.df/dt_Set -5~5 0.5 Hz/s 0.001 7 81R2.t_Op 0.1~100 0.1 s 0.001 8 81R2.f_Pkp 45~65 50 Hz 0.001 9 81R2.En Enabled - - 10 81R3.df/dt_Set 0.5 Hz/s 0.001 Disabled; Enabled Disabled; Enabled -5~5 The rate-of-change setting of the stage 1 of frequency rate-of-change protection The time setting of the stage 1 of frequency rate-of-change protection The pickup frequency setting of the stage 1 of frequency rate-of-change protection The logic setting of the stage 1 of frequency rate-of-change protection The rate-of-change setting of the stage 2 of frequency rate-of-change protection The time setting of the stage 2 of frequency rate-of-change protection The pickup frequency setting of the stage 2 of frequency rate-of-change protection The logic setting of the stage 2 of frequency rate-of-change protection The rate-of-change setting of the stage 3 of frequency rate-of-change protection PCS-9613S Differential Relay 3-172 Date: 2020-09-02 3 Protection Functions 11 81R3.t_Op 0.1~100 0.1 s 0.001 12 81R3.f_Pkp 45~65 50 Hz 0.001 13 81R3.En Enabled - - 14 81R4.df/dt_Set -5~5 0.5 Hz/s 0.001 15 81R4.t_Op 0.1~100 0.1 s 0.001 16 81R4.f_Pkp 45~65 50 Hz 0.001 17 81R4.En Enabled - - 18 81R5.df/dt_Set -5~5 0.5 Hz/s 0.001 19 81R5.t_Op 0.1~100 0.1 s 0.001 20 81R5.f_Pkp 45~65 50 Hz 0.001 21 81R5.En Enabled - - 22 81R6.df/dt_Set -5~5 0.5 Hz/s 0.001 23 81R6.t_Op 0.1~100 0.1 s 0.001 24 81R6.f_Pkp 45~65 50 Hz 0.001 25 81R6.En Enabled - - Disabled; Enabled Disabled; Enabled Disabled; Enabled Disabled; Enabled The time setting of the stage 3 of frequency rate-of-change protection The pickup frequency setting of the stage 3 of frequency rate-of-change protection The logic setting of the stage 3 of frequency rate-of-change protection The rate-of-change setting of the stage 4 of frequency rate-of-change protection The time setting of the stage 4 of frequency rate-of-change protection The pickup frequency setting of the stage 4 of frequency rate-of-change protection The logic setting of the stage 4 of frequency rate-of-change protection The rate-of-change setting of the stage 5 of frequency rate-of-change protection The time setting of the stage 5 of frequency rate-of-change protection The pickup frequency setting of the stage 5 of frequency rate-of-change protection The logic setting of the stage 5 of frequency rate-of-change protection The rate-of-change setting of the stage 6 of frequency rate-of-change protection The time setting of the stage 6 of frequency rate-of-change protection The pickup frequency setting of the stage 6 of frequency rate-of-change protection The logic setting of the stage 6 of frequency rate-of-change protection 3.21 Reverse Power Protection (32R) If a power supply failure occurs on the feeder, the synchronous motors become generators due to the inertia of their load and the induction motors become generators. The aim of the reverse power protection is to detect the inverse flow of energy and to ensure that the motor does not feed the fault which has appeared on the network. 3.21.1 Function Description This device provides two stages of reverse power protection. If the reverse power is detected and it is greater than the predefined setting, the reverse power protection will operate. The reverse power protection is with independent definite-time delay characteristic and with instantaneous dropout characteristic. PCS-9613S Differential Relay 3-173 Date: 2020-09-02 3 3 Protection Functions The reverse power protection can be enabled or disabled via the settings or binary input signals, for some specific applications, reverse power protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block reverse power protection. The enabling and blocking logic of reverse power protection is shown in the figure below: EN & 32Rx.En SIG 32Rx.Enable SIG 32Rx.Block SIG Fail_Device 32Rx.On & 3 32Rx.Blocked ≥1 & 32Rx.Valid Figure 3.21-1 Logic diagram of enabling/disabling reverse power protection When the reverse power protection is enabled and no external blocking signal is input, if the reverse power is greater than the power setting of the reverse power protection, the reverse power protection will pick up. The logic diagram of the fault detector of the reverse power protection is shown in Figure 3.21-2. SET SIG |P| > 0.95*[32Rx.P_Set] & P<0 32Rx.Pkp SET U1 < [32R.U1_VCE] SET I1 < [32R.I1_CCE] SET U2 > [32R.U2_VCE] SIG 32Rx.On SIG 32Rx.Valid EN [32Rx.Opt_Trp/Alm]=Alm & & 0ms 500ms & & ≥1 FD.Pkp Figure 3.21-2 Logic diagram of the fault detector of reverse power protection Where: The power value is positive-sequence power, P1 = 3×U1×I1×cosθ (θ is the phase angle between positive-sequence voltage and positive-sequence current). [32Rx.P_Set] (x: 1~2) is the power setting of the stage x reverse power protection. [32R.U1_VCE] is the setting of the positive-sequence voltage control element of the reverse power protection. PCS-9613S Differential Relay 3-174 Date: 2020-09-02 3 Protection Functions [32R.I1_CCE] is the positive-sequence current setting of the current control element of the reverse power protection. [32R.U2_VCE] is the setting of the negative-sequence voltage control element of the reverse power protection. “I1” is the positive-sequence current. “U1” is the positive-sequence voltage. “U2” is the negative-sequence voltage. 3.21.1.1 Operation Characteristic The reverse power protection has definite-time delay characteristic complied with IEC 60255-3 and ANSI C37.112. If the power value is less than “0”, and the absolute power value is greater than the power setting of the reverse power protection [32Rx.P_Set] (x: 1~2), the reverse power protection will operate after the time setting [32Rx.t_Op] (x: 1~2). The operation characteristic curve of reverse power protection is shown in Figure 3.21-3. t top P1 P1set Figure 3.21-3 Operation characteristic curve of reverse power protection 3.21.1.2 Dropout Characteristic The reverse power protection is with instantaneous dropout characteristic. If the power is greater than “0” or the power is less than the power setting [32Rx.P_Set] (x: 1~2) multiplied by 0.95, the reverse power protection will drop out at once. PCS-9613S Differential Relay 3-175 Date: 2020-09-02 3 3 Protection Functions 3.21.2 Function Block Diagram 32R 32Rx.Enable 32Rx.On 32Rx.Blocked 32Rx.Block 32Rx.Valid 32Rx.St 32Rx.Op 32Rx.Alm 3 3.21.3 I/O Signals Table 3.21-1 Input/output signals of reverse power protection No. Input Signal 1 32Rx.Enable 2 32Rx.Block No. Description Stage x of reverse power protection enabling input, it is triggered from binary input or programmable logic etc. (x=1~2) Stage x of reverse power protection blocking input, it is triggered from binary input or programmable logic etc. (x=1~2) Output Signal Description 1 32Rx.On Stage x of reverse power protection is enabled. 2 32Rx.Blocked Stage x of reverse power protection is blocked. 3 32Rx.Valid Stage x of reverse power protection is valid. 4 32Rx.St Stage x of reverse power protection picks up. 5 32Rx.Op Stage x of reverse power protection operates. 6 32Rx.Alm Stage x of reverse power protection alarms. 3.21.4 Logic SET |P| > [32Rx.P_Set] SIG P<0 SET U1 < [32R.U1_VCE] SET I1 < [32R.I1_CCE] SET U2 > [32R.U2_VCE] & 32Rx.St & ≥1 & [32Rx.t_Op] SIG 32Rx.Pkp SET [32Rx.Opt_Trp/Alm] = Trp 0 & & SET 32Rx.Op 32Rx.Alm [32Rx.Opt_Trp/Alm] = Alm Figure 3.21-4 Logic diagram of reverse power protection PCS-9613S Differential Relay 3-176 Date: 2020-09-02 3 Protection Functions 3.21.5 Settings ⚫ Access path: MainMenu Settings Protection Settings RevPower Settings Table 3.21-2 Settings of reverse power protection No. Setting Range Default Unit Step Description The 1 32R.U1_VCE 5~60 5 V 0.001 voltage setting of the positive-sequence voltage control element of the reverse power protection The positive-sequence current setting of 2 32R.I1_CCE 0.01~1 0.1 p.u. 0.001 the current control element of the reverse power protection The 3 32R.U2_VCE 8~60 8 V 0.001 voltage setting of the negative-sequence voltage control element of the reverse power protection 4 32R1.P_Set 0.1~10 0.15 p.u. 0.001 5 32R1.t_Op 0.01~100 0.1 s 0.001 6 32R1.En Disabled; Enabled Enabled - - The power setting of the stage 1 of reverse power protection The time setting of the stage 1 of reverse power protection The logic setting of the stage 1 of reverse power protection Enabling 7 32R1.Opt_Trp/Alm Trp; Alm Trp - - stage 1 of reverse power protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 8 32R2.P_Set 0.1~10 0.15 p.u. 0.001 9 32R2.t_Op 0.01~100 0.1 s 0.001 10 32R2.En Enabled - - Disabled; Enabled The power setting of the stage 2 of reverse power protection The time setting of the stage 2 of reverse power protection The logic setting of the stage 2 of reverse power protection Enabling 11 32R2.Opt_Trp/Alm Trp; Alm Trp - - stage 2 of reverse power protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 3.22 Undercurrent Protection (37) The undercurrent protection can remove the device from the system by detecting the smaller load current when the load is lost, the capacitor is in loss of voltage and the motor is running without any load. PCS-9613S Differential Relay 3-177 Date: 2020-09-02 3 3 Protection Functions 3.22.1 Function Description The device can provide one stage of undercurrent protection for tripping purpose or alarm purpose. For different protected equipment, the single-phase criterion or three-phase criterion can be selected. The position of circuit breaker, the load current also can be taken as the enabling conditions for the undercurrent protection. The undercurrent protection is with definite-time operation characteristic and instantaneous dropout characteristic. Undercurrent protection can operate to trip or alarm, it can be enabled or blocked by the external binary input. 3 Undercurrent protection can be enabled or disabled via the settings or binary input signals, for some specific applications, undercurrent protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block undercurrent protection. The enabling and blocking logic of undercurrent protection is shown in the figure below: EN 37.En SIG 37.Enable SIG 37.Block SIG Fail_Device & 37.On & 37.Blocked ≥1 & 37.Valid Figure 3.22-1 Logic diagram of enabling/disabling undercurrent protection When the undercurrent protection is enabled and no external blocking signal is input, if the detected current is less than the current setting multiplied by 1.10 of the undercurrent protection, the undercurrent protection will pick up. Users can select “1-out-of-3” or “3-out-of-3” logic for the protection criterion via the setting [37.Opt_1P/3P]. If it is set as “1P”, undercurrent protection can operate if any phase current is smaller than the current setting. If it is set as “3P”, undercurrent protection cannot operate unless three phase currents are smaller than the current setting. The circuit breaker position with/without the current condition can be used as an auxiliary criterion for undercurrent protection, which can be configured via the setting [37.Opt_LogicMode]. The logic diagram of the fault detector of the undercurrent protection is shown as below. PCS-9613S Differential Relay 3-178 Date: 2020-09-02 3 Protection Functions SIG Ia<1.10×[37.I_Set] SIG Ib<1.10×[37.I_Set] SIG Ic<1.10×[37.I_Set] >=1 & >=1 Pickup current criterion SET [37.Opt_1P/3P]=1P SIG Ia<1.10×[37.I_Set] SIG Ib<1.10×[37.I_Set] SIG Ic<1.10×[37.I_Set] & & 3 SET [37.Opt_1P/3P]=3P SET [37.Opt_LogicMode]=None SET [37.Opt_LogicMode]=Curr SIG Ip>0.04In SET [37.Opt_LogicMode]=CBPos SIG CB closed position & >=1 >=1 Auxiliary criterion & >=1 & >=1 SET [37.Opt_LogicMode]=CurrOrCBPos & & SET [37.Opt_LogicMode]=CurrAndCBPos SIG Pickup current criterion SIG Auxiliary criterion SIG 37.On SIG 37.Valid SET [37.Opt_Trp/Alm]=Alm & 0 500ms & 37.Pkp & FD.Pkp Figure 3.22-2 Logic diagram of the fault detector of undercurrent protection 3.22.1.1 Operation Characteristic The undercurrent protection has definite-time operation characteristic complied with IEC 60255-3 and ANSI C37.112. If the load current is less than the current setting of the undercurrent protection [37.I_Set], the undercurrent protection will operate after the time setting [37.t_Op]. The operation characteristic curve of undercurrent protection is shown as below. PCS-9613S Differential Relay 3-179 Date: 2020-09-02 3 Protection Functions t t op 3 Ip I Figure 3.22-3 Operation characteristic curve of undercurrent protection 3.22.1.2 Dropout Characteristic The undercurrent protection is with instantaneous dropout characteristic. If the load current is larger than the current setting [37.I_Set] multiplied by 1.10, the undercurrent protection will drop out immediately. 3.22.2 Function Block Diagram 37 37.Enable 37.Block 37.On 37.Blocked 37.Valid 37.St 37.StA 37.StB 37.StC 37.Op 37.Op.PhA 37.Op.PhB 37.Op.PhC 37.Alm PCS-9613S Differential Relay 3-180 Date: 2020-09-02 3 Protection Functions 3.22.3 I/O Signals Table 3.22-1 Input/output signals of undercurrent protection No. Input Signal 1 37.Enable 2 37.Block No. Description Undercurrent protection enabling input, it is triggered from binary input or programmable logic etc. Undercurrent protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 37.On Undercurrent protection is enabled. 2 37.Blocked Undercurrent protection is blocked. 3 37.Valid Undercurrent protection is valid. 4 37.St Undercurrent protection starts. 5 37.StA Undercurrent protection starts (Phase A) 6 37.StB Undercurrent protection starts (Phase B) 7 37.StC Undercurrent protection starts (Phase C) 8 37.Op Undercurrent protection operates. 9 37.Op.PhA Undercurrent protection operates (Phase A) 10 37.Op.PhB Undercurrent protection operates (Phase B) 11 37.Op.PhC Undercurrent protection operates (Phase C) 12 37.Alm Undercurrent protection alarms. PCS-9613S Differential Relay 3 3-181 Date: 2020-09-02 3 Protection Functions 3.22.4 Logic SIG Ia<[37.I_Set] SIG Ib<[37.I_Set] SIG Ic<[37.I_Set] >=1 & >=1 Current criterion SET [37.Opt_1P/3P]=1P 3 SIG Ia<[37.I_Set] SIG Ib<[37.I_Set] SIG Ic<[37.I_Set] & & SET [37.Opt_1P/3P]=3P SIG Current criterion SIG Auxiliary criterion SIG 37.On SIG 37.Pkp & 37.St & [37.t_Op] 0 & 37.Op SET [37.Opt_Trp/Alm]=Trp & 37.Alm SET [37.Opt_Trp/Alm]=Alm Figure 3.22-4 Logic diagram of undercurrent protection Where: Auxiliary criterion: please refer to Figure 3.22-2. 3.22.5 Settings ⚫ Access path: MainMenu Settings Protection Settings UC Settings Table 3.22-2 Settings of undercurrent protection No. Setting Range Default Unit Step 1 37.I_Set 0.1~5 0.5 A 0.001 2 37.t_Op 0.1~100 0.1 s 0.001 3 37.Opt_1P/3P 1P; 3P Description The - - setting of the undercurrent protection The time setting of the undercurrent protection The 3P current setting three-phase for selecting criterion (3P) the or single-phase criterion (1P) PCS-9613S Differential Relay 3-182 Date: 2020-09-02 3 Protection Functions None; Curr; 4 37.Opt_LogicMode CBPos; CurrAndCBPos; CurrAnd CBPos - - - - The setting of the CB position check mode. CurrOrCBPos 5 37.En Disabled; Enabled Enabled The logic setting of the undercurrent protection Enabling undercurrent protection 6 37.Opt_Trp/Alm Trp; Alm Trp - - operate to trip or alarm. Trp: for tripping purpose 3 Alm: for alarm purpose 3.23 Breaker Failure Protection (50BF) When a fault happens to the power system, the device will operate to trip the circuit breaker, and the fault will be isolated by opening the circuit breaker. If the circuit breaker fails to open within the certain time due to some abnormalities (for example, low tripping pressure), the fault may cause system stability being destroyed or electrical equipment being damaged. Breaker failure protection is adopted to issue a backup tripping command to trip adjacent circuit breakers, and isolate the fault as requested by the device. According to the tripping information from the device and the auxiliary information (the current and the position) of target circuit breaker, breaker failure protection constitutes the criterion to discriminate whether the target circuit fails to open. If the criterion is confirmed, breaker failure protection will operate to trip the target circuit breaker with the time delay [50BF.t_ReTrp], trip it again with the time delay [50BF.t1_Op] and trip the adjacent circuit breakers with the time delay [50BF.t2_Op]. As a special backup protection, breaker failure protection can quickly isolate the fault, reduce the affected range by the fault, keep system stability and prevent generators, transformers and other primary equipments from seriously damaged. 3.23.1 Function Description For breaker failure protection, re-trip and two time delays are available. 3.23.1.1 Re-trip When breaker failure protection receives initiating signal of tripping and phase overcurrent element of any phase operates, the device will issue tripping command to re-trip the target circuit breaker with the time delay [50BF.t_ReTrp]. In order to improve the sensitivity, both zero-sequence overcurrent element and negative-sequence overcurrent element are added, which can be enabled or disabled by the settings [50BF.En_3I0_3P] and [50BF.En_I2_3P]. 3.23.1.2 First Time Delay As similar as re-trip, the device will operate to re-trip the target circuit breaker again with the time delay [50BF.t1_Op] when the relevant operating criterion is satisfied. PCS-9613S Differential Relay 3-183 Date: 2020-09-02 3 Protection Functions 3.23.1.3 Second Time delay As similar as re-trip, the device will operate to trip the adjacent circuit breakers with the time delay [50BF.t2_Op] when the relevant operating criterion is satisfied. 3.23.1.4 Current Criterion 1. Phase overcurrent element 𝐼𝜑 > [50𝐵𝐹. 𝐼_𝑆𝑒𝑡] Where: 3 𝜑 = A, B or C 2. Zero-sequence overcurrent element 3I0 > [50𝐵𝐹. 3𝐼0_𝑆𝑒𝑡] Where: 3I0 is the calculated residual current 3. Negative-sequence overcurrent element I2 > [50𝐵𝐹. 𝐼2_𝑆𝑒𝑡] Where: I2 is the negative-sequence current For some special faults (for example, mechanical protection or overvoltage protection operating), maybe faulty current is very small and current criterion of breaker failure protection is not met, in order to make breaker failure protection can also operate under the above situation, an input signal "50BF.ExTrp_WOI" is equipped to initiate breaker failure protection, once the input signal is energized, normally closed auxiliary contact of circuit breaker is chosen in addition to breaker failure current check to trigger breaker failure timer. The device takes current as priority with CB auxiliary contact "50BF.52b" as an option criterion for breaker failure check. When the initiating signal of breaker failure protection is energized for longer than 10s, an alarm signal "50BF.Alm_Init" will be issued, and will drop out with a time delay of 10s. PCS-9613S Differential Relay 3-184 Date: 2020-09-02 3 Protection Functions 3.23.2 Function Block Diagram 50BF 50BF.Enable 50BF.On 50BF.Block 50BF.Blocked 50BF.Valid 50BF.ExTrp3P 50BF.St 50BF.ExTrp_WOI 50BF.Op_ReTrp3P 3 50BF.Op_t1 50BF.Op_t2 50BF.Alm_Init 3.23.3 I/O Signals Table 3.23-1 Input/output signals of breaker failure protection No. Input Signal 1 50BF.Enable 2 50BF.Block 3 50BF.ExtTrp3P 4 50BF.ExtTrp_WOI No. Description Breaker failure protection enabling input, it is triggered from binary input or programmable logic etc. Breaker failure protection blocking input, it is triggered from binary input or programmable logic etc. Input signal of initiating breaker failure protection (three-phases) Input signal of initiating breaker failure protection with the position check of the circuit breaker Output Signal Description 1 50BF.On Breaker failure protection is enabled. 2 50BF.Blocked Breaker failure protection is blocked. 3 50BF.Valid Breaker failure protection is valid. 4 50BF.St Breaker failure protection starts 5 50BF.Op_ReTrp3P Breaker failure protection operates to re-trip three-phases circuit breaker. 6 50BF.Op_t1 Breaker failure protection operates with the time delay [50BF.t1_Op]. 7 50BF.Op_t2 Breaker failure protection operates with the time delay [50BF.t2_Op]. 8 50BF.Alm_Init The initiating signal of breaker failure protection is energized consistently. PCS-9613S Differential Relay 3-185 Date: 2020-09-02 3 Protection Functions 3.23.4 Logic EN [50BF.En] & 50BF.On SIG 50BF.Enable & SIG 50BF.Block 50BF.Blocked >=1 SIG Fail_Device & 50BF.Valid 3 Figure 3.23-1 Logic of enabling breaker failure protection SIG 50BF.ExtTrp3P 10s 10s SIG 50BF.ExtTrp_WOI 10s 10s EN [50BF.En_Alm_Init] SIG 50BF.Valid >=1 & 50BF.Alm_Init Figure 3.23-2 Logic of breaker failure initiating signal abnormality SIG 50BF.Valid & SIG 50BF.Alm_Init EN [50BF.En_ReTrp] EN [50BF.En_Ip] SET IA>[50BF.I_Set] & >=1 [50BF.t_ReTrp] 0 SET IB>[50BF.I_Set] 50BF.Op_ReTrp3P & SET IC>[50BF.I_Set] SIG 50BF.ExtTrp3P & EN [50BF.En_3I0_3P] & >=1 SET 3I0>[50BF.3I0_Set] EN [50BF.En_I2_3P] & & [50BF.t1_Op] 0 >=1 50BF.Op_t1 & SET I2>[50BF.I2_Set] SIG 50BF.ExtTrp_WOI EN >=1 50BF.St & [50BF.En_CB_Ctrl] SIG 50BF.52b EN [50BF.En_t1] & [50BF.t2_Op] 0 50BF.Op_t2 EN [50BF.En_t2] Figure 3.23-3 Logic of breaker failure protection PCS-9613S Differential Relay 3-186 Date: 2020-09-02 3 Protection Functions Where: 50BF.52b: Input signal of three-phase open position of circuit breaker. 3.23.5 Settings ⚫ Access path: MainMenu Settings Protection Settings BFP Settings Table 3.23-2 Settings of breaker failure protection No. Setting Range Default Unit Step 1 50BF.I_Set 0.05~200 1.000 A 0.001 2 50BF.3I0_Set 0.05~200 1.000 A 0.001 3 50BF.I2_Set 0.05~200 1.000 A 0.001 4 50BF.t_ReTrp 0~20 0.050 s 0.001 5 50BF.t1_Op 0~20 0.100 s 0.001 6 50BF.t2_Op 0~20 0.200 s 0.001 7 50BF.En Enabled - - 8 50BF.En_ReTrp Enabled - - 9 50BF.En_t1 Disabled - - 10 50BF.En_t2 Disabled - - 11 50BF.En_Ip Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Description The phase current setting of breaker failure protection The zero-sequence current setting of breaker failure protection The negative-sequence current setting of breaker failure protection The re-trip time delay of breaker failure protection The first time delay of breaker failure protection The second time delay of breaker failure protection Enabling/disabling - - Enabling/disabling re-trip 50BF.En_3I0_3P Disabled Enabled function of breaker failure protection Enabling/disabling first time delay of breaker failure protection Enabling/disabling second time delay of breaker failure protection phase overcurrent element of breaker failure protection via three-phases initiating signal Enabling/disabling 12 failure protection Enabling/disabling Disabled breaker Disabled - - zero-sequence overcurrent element of breaker failure protection via three-phases initiating signal Enabling/disabling 13 50BF.En_I2_3P Disabled Enabled Disabled - - negative-sequence overcurrent element of breaker failure protection via three-phases initiating signal 14 50BF.En_CB_Ctrl Disabled Enabled Enabling/disabling Disabled - - breaker failure protection be initiated by normally closed contact of circuit breaker PCS-9613S Differential Relay 3-187 Date: 2020-09-02 3 3 Protection Functions 15 50BF.En_Alm_Init Disabled Enabled Disabled - Enabling/disabling abnormality check of - breaker failure initiating signal 3.24 Switch-on-to-Fault Protection (SOTF) When the line is put into operation or the power is restored, the circuit breaker is necessary to be closed automatically, it is possible to switch on to a permanent fault. The conventional phase overcurrent protection or earth fault overcurrent protection requires a time delay to operate and isolate the fault, which will affect the power system seriously. Switch-on-to-fault (SOTF) protection can quickly operate to remove the fault and reduce the impact of the fault on the system. 3 3.24.1 Function Description The device can provide one stage of phase overcurrent SOTF protection and one stage of earth fault overcurrent SOTF protection. The SOTF protection is with definite-time delay characteristic and instantaneous dropout characteristic, it can be enabled or blocked by the external binary input. The SOTF protection can be enabled or disabled via the settings or binary input signals, for some specific applications, the protection needs to be blocked by the external signal, so the device provides a function block input signal to be used to block RMS overcurrent protection. The enabling and blocking logic of the SOTF protection is shown in the figure below: EN 50PSOTF.En & 50PSOTF.On SIG 50PSOTF.Enable SIG 50PSOTF.Block SIG Fail_Device & ≥1 50PSOTF.Blocked & 50PSOTF.Valid EN 50GSOTF.En & 50GSOTF.On SIG 50GSOTF.Enable SIG 50GSOTF.Block SIG Fail_Device & ≥1 50GSOTF.Blocked & 50GSOTF.Valid Figure 3.24-1 The enabling and blocking logic of SOTF protection The SOTF protection must be initiated by auto-reclosing signal or manual closing signal, the initiating time can be set by the setting [STOF.t_En]. After the acceleration condition is satisfied, PCS-9613S Differential Relay 3-188 Date: 2020-09-02 3 Protection Functions the SOTF protection will operate with a time delay of [50PSOTF.t_Op]/ [50GSOTF.t_Op_3P]. If the three-phase current changes from “no” to “have”, and the breaker position changes from “open” to “closed”, it will be judged that the acceleration condition for manual closing is satisfied. Then the manual closing signal will be kept for a certain time which is determined by the setting [SOTF.t_En], and SOTF protection will be enabled. When the SOTF protection is used for the transformer bay, large inrush current generated during manual closing and auto-reclosing maybe lead to an undesired operation of SOTF protection. Second harmonic blocking can be selected by the setting [50PSOTF.En_Hm2_Blk]/[50GSOTF.En_Hm2_Blk] to prevent the mal-operation due to inrush current. The harmonic blocking characteristic of the phase overcurrent SOTF protection is consistent with that of phase overcurrent protection. The harmonic blocking characteristic of the earth fault overcurrent SOTF protection is consistent with that of earth fault overcurrent protection. In order to improve the reliability, phase overcurrent SOTF protection can select phase voltage element, phase-to-phase voltage element, zero-sequence voltage element and negative-sequence voltage element as auxiliary criterion. 3.24.2 Function Block Diagram 50PSOTF 50PSOTF.Enable 50PSOTF.Block 50PSOTF.On 50GSOTF 50PSOTF.Blocked 50PSOTF.Valid 50PSOTF.Op 50GSOTF.Enable 50GSOTF.Block 50GSOTF.On 50GSOTF.Blocked 50PSOTF.St 50GSOTF.Valid 50PSOTF.StA 50GSOTF.Op 50PSOTF.StB 50GSOTF.St 50PSOTF.StC 3.24.3 I/O Signals Table 3.24-1 Input/output signals of SOTF protection No. Input Signal 1 50PSOTF.Enable 2 50PSOTF.Block 3 50GSOTF.Enable 4 50GSOTF.Block No. Description Phase overcurrent SOTF protection enabling input, it is triggered from binary input or programmable logic etc. Phase overcurrent SOTF protection blocking input, it is triggered from binary input or programmable logic etc. Earth fault overcurrent SOTF protection enabling input, it is triggered from binary input or programmable logic etc. Earth fault overcurrent SOTF protection blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description PCS-9613S Differential Relay 3-189 Date: 2020-09-02 3 3 Protection Functions 3 1 50PSOTF.On Phase overcurrent SOTF protection is enabled. 2 50PSOTF.Blocked Phase overcurrent SOTF protection is blocked 3 50PSOTF.Valid Phase overcurrent SOTF protection is valid 4 50PSOTF.Op Phase overcurrent SOTF protection operates. 5 50PSOTF.St Phase overcurrent SOTF protection starts. 6 50PSOTF.StA Phase overcurrent SOTF protection starts (Phase A). 7 50PSOTF.StB Phase overcurrent SOTF protection starts (Phase B). 8 50PSOTF.StC Phase overcurrent SOTF protection starts (Phase C). 9 50GSOTF.On Earth fault overcurrent SOTF protection is enabled. 10 50GSOTF.Op Earth fault overcurrent SOTF protection operates. 11 50GSOTF.Blocked Earth fault overcurrent SOTF protection is blocked 12 50GSOTF.Valid Earth fault overcurrent SOTF protection is valid 13 50GSOTF.St Earth fault overcurrent SOTF protection starts. 3.24.4 Logic SIG 0 79.Close [SOTF.t_En] AR signal Figure 3.24-2 Logic of auto-reclosing signal SIG Breaker position: open ->closed SIG FD.Pkp SIG FD.Pkp SIG Current: no -> have & >=1 & 0 [SOTF.t_En] Manual closing signal Figure 3.24-3 Logic of manual closing signal If the three-phase current changes from “no” to “have”, and the breaker position changes from “open” to “closed”, it will be judged that the acceleration condition for manual closing is satisfied. PCS-9613S Differential Relay 3-190 Date: 2020-09-02 3 Protection Functions SIG AR signal SIG Manual closing signal >=1 SET Ia>[50PSOTF.I_Set] >=1 SET Ib>[50PSOTF.I_Set] SET Ic>[50PSOTF.I_Set] SIG I3P EN [50PSOTF.En_Hm2_Blk] 2nd Hm Detect SET Ua<[50PSOTF.Up_Set] & & >=1 SET Ub<[50PSOTF.Up_Set] 3 & SET Uc<[50PSOTF.Up_Set] EN [50PSOTF.En_Up_UV] SET Uab<[50PSOTF.Upp_Set] >=1 SET Ubc<[50PSOTF.Upp_Set] >=1 & SET Uca<[50PSOTF.Upp_Set] EN [50PSOTF.En_Upp_UV] SET U2>[50PSOTF.U2_Set] & >=1 >=1 EN [50PSOTF.En_U2_OV] SET 3U0>[50PSOTF.3U0_Set] EN [50PSOTF.En_3U0_OV] EN [50PSOTF.En_Up_UV] EN [50PSOTF.En_Upp_UV] EN [50PSOTF.En_U2_OV] EN [50PSOTF.En_3U0_OV] SIG 50PSOTF.Valid & >=1 & [50PSOTF.t_Op] 0 50PSOTF.Op 50PSOTF.St Figure 3.24-4 Logic of phase overcurrent SOTF protection SIG I3P/I1P 2nd Hm Detect & SET [50/51G1.En_Hm2_Blk] SIG AR signal >=1 SIG Manual closing signal & 50GSOTF.St [50GSOTF.t_Op] 0 SET 3I0>[50GSOTF.3I0_Set] 50GSOTF.Op SIG 50GSOTF.Valid Figure 3.24-5 Logic of earth fault overcurrent SOTF protection PCS-9613S Differential Relay 3-191 Date: 2020-09-02 3 Protection Functions 3.24.5 Settings ⚫ Access path: MainMenu Settings Protection Settings SOTF Settings Table 3.24-2 Settings of SOTF protection No. 3 Setting Range Default Unit Step 1 SOTF.t_En 0.2~100 0.4 s 0.001 2 50PSOTF.I_Set 0.05~200 1 A 0.001 3 50PSOTF.Up_Set 0~200 1 V 0.001 4 50PSOTF.Upp_Set 0~200 1 V 0.001 5 50PSOTF.U2_Set 0~200 1 V 0.001 6 50PSOTF.3U0_Set 0~200 1 V 0.001 7 50PSOTF.t_Op 0~100 0.1 s 0.001 8 50PSOTF.En Enabled - - 9 50PSOTF.En_Hm2_Blk Disabled - - 10 11 50PSOTF.En_Up_UV 50PSOTF.En_Upp_UV Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Description The initiating time for the SOTF protection Current setting of phase overcurrent SOTF protection Voltage setting for phase undervoltage supervision logic Voltage setting for phase-to-phase undervoltage supervision logic Voltage setting for negative-sequence overvoltage supervision logic Voltage setting for zero-sequence overvoltage supervision logic Time delay for phase overcurrent SOTF protection Enabling/disabling phase overcurrent SOTF protection Enabling/disabling second harmonic blocking for phase overcurrent SOTF protection Enabling/disabling Disabled - - phase undervoltage supervision logic for phase overcurrent SOTF protection Enabling/disabling Disabled - - phase-to-phase undervoltage supervision logic for phase overcurrent SOTF protection Enabling/disabling 12 50PSOTF.En_U2_OV Disabled Enabled Disabled - - negative-sequence supervision logic overvoltage for phase overcurrent SOTF protection 13 50PSOTF.En_3U0_OV Disabled Enabled Enabling/disabling Disabled - - overvoltage zero-sequence supervision logic for phase overcurrent SOTF protection The option of the residual current 14 50GSOTF.Opt_3I0 Ext Cal used by earth fault overcurrent SOTF Cal - - protection Ext: the measured residual current Cal: the calculated residual current PCS-9613S Differential Relay 3-192 Date: 2020-09-02 3 Protection Functions 15 50GSOTF.3I0_Set 0.05~200 1 A 0.001 16 50GSOTF.t_Op_3P 0~100 0.1 s 0.001 17 50GSOTF.En Enabled - - 18 50GSOTF.En_Hm2_Blk Disabled Enabled Disabled Enabled Current setting - - earth fault overcurrent SOTF protection Time delay for earth fault overcurrent SOTF protection Enabling/disabling earth fault overcurrent SOTF protection Enabling/disabling Disabled of earth fault overcurrent SOTF protection blocked by harmonic 3 3.25 Thermal Overload Protection (49) When the power equipment is overloaded, a large current may cause the temperature of the equipment to rise. When the temperature is high, the internal insulation of the equipment may be aged, thereby increasing the possibility of internal failure. Thermal overload protection considers the continuous heating state of the device, the thermal model of the device is established based on the measured current and the time constant. 3.25.1 Function Description The device provides two thermal overload calculation methods: 1) only calculated by current; 2) for the scenario with oil temperature measurement function, calculate the temperature difference between the equipment (such as transformer windings) and the oil, and then plus the oil temperature measured by the sensor, to obtain the final temperature. ⚫ Method 1: Two stages overload protection are available, one stage for alarm purpose and the other stage for trip purpose. The two stages are timed separately. When the thermal overload calculation reaches the alarm setting value, an alarm signal will be issued to remind the operating personnel. If the temperature continues to rise to reach the tripping setting value, the thermal overload protection operates to trip. The operating time of thermal overload protection complies with the IEC60255-8 standard and it is calculated via the fundamental current or 1st to 11th harmonic current. PCS-9613S Differential Relay 3-193 Date: 2020-09-02 3 Protection Functions Refer to IEC60255-8 t Ip P=— IB P = 0.0 P = 0.6 P = 0.8 P = 0.9 3 kIB I Figure 3.25-1 The operation characteristic curve of thermal overload protection There are two kinds of thermal overload calculation modes: cold start mode and hot start mode. The calculation formulas for the two modes are as follows: 1) Cold start mode t = ln 2) I eq I eq − (k I B ) Hot start mode t = ln I eq − I p I eq − (k I B ) Where: t is the theoretical operating time for the corresponding current. τ is the thermal time constant of the protected device, i.e. [49.Tau]. When the current Ieq is lower than 0.04In, the thermal time constant adopts the value of [49.Tau]*[49.C_Disspt]. Ieq is the actual measured current. IP is the steady-state load for a period of time before the overload. The result is that the transformer is in a stable thermal equilibrium state (the duration needs to be several times longer than the time constant τ), which is equivalent to the previous memoried current, the value is “0” for the cold start mode. ln is the natural logarithm. IB is the reference current and it corresponds to the setting [49.Ib_Set]. k is the thermal overload factor, it corresponds to the setting [49.K_Trp] or [49.K_Alm]. PCS-9613S Differential Relay 3-194 Date: 2020-09-02 3 Protection Functions If the device adopts the hot start model, the device calculates the I P in real time through the external input current, and users do not need to set the value of IP. The tripping of the protection is controlled by the current. After the current disappears, the protection will drop-out immediately even if the heat accumulation is still greater than the tripping setting. The alarm of the protection is not controlled by the current, as long as the heat accumulation is greater than the alarm setting, it will always be alarmed and it can be used to block the automatic closing of the device. ⚫ Method 2: The temperature of the equipment can be calculated from the actual measured oil temperature (via the PT100 sensor) plus the temperature difference between the equipment and the oil. T_Equipment = T_Oil + T_Diff The temperature difference between the equipment and the oil can be calculated by actual measurement and it will change with the device current. When the current changes from “0” to “1”, the temperature can be calculated by the following formula. T_Diff = [49. K_T_Diff] × ( α −t I ) × (1 − eTau ) [49. Ib_Set] Finally, the steady-state temperature difference is as follows: T_Diff = [49. K_T_Diff] × ( α I ) [49. Ib_Set] Where: I is the measured current; α is the cooling factor, it usually takes 1.6 or 2; t is the time; Tau is the time constant; Users can compare the calculated temperature with the set temperature and set the time delay through logic programming, it can be selected to operate to trip or alarm. The logic diagram of enabling/disabling thermal overload protection is shown as below: PCS-9613S Differential Relay 3-195 Date: 2020-09-02 3 3 Protection Functions EN [49.En_Trp] EN [49.En_Alm] >=1 & 49.On SIG 49.Enable & SIG 49.Block 49.Blocked >=1 SIG Fail_Device & 49.Valid 3 Figure 3.25-2 Logic diagram of enabling/disabling thermal overload protection The logic diagram of the fault detector of thermal overload protection is shown as below. SIG 49.in_I3P SET [49.Ib_Set] & 0 SIG 49.On 500ms & 49.Pkp FD.Pkp SIG 49.Valid Figure 3.25-3 Logic diagram of the fault detector of thermal overload protection (method 1) PCS-9613S Differential Relay 3-196 Date: 2020-09-02 3 Protection Functions 3.25.2 Function Block Diagram 49 49.Accu_A 49.Enable 49.Accu_B 49.Block 49.Accu_C 49.Clr 49.T_Diff_A 49.T_Diff_B 49.T_Diff_C 49.On 3 49.Blocked 49.Valid 49.St 49.St_A 49.St_B 49.St_C 49.Op 49.Op_A 49.Op_B 49.Op_C 49.Alm 3.25.3 I/O Signals Table 3.25-1 Input/output signals of thermal overload protection No. Input Signal 1 49.Enable 2 49.Block 3 49.Clr No. Description Thermal overload protection enabling input, it is triggered from binary input or programmable logic etc. Thermal overload protection blocking input, it is triggered from binary input or programmable logic etc. Clear thermal overload statistics Output Signal Description 1 49.Accu_A Phase-A thermal state of thermal overload protection. 2 49.Accu_B Phase-B thermal state of thermal overload protection. 3 49.Accu_C Phase-C thermal state of thermal overload protection. 4 49.T_Diff_A 5 49.T_Diff_B 6 49.T_Diff_C 7 49.On Thermal overload protection is enabled 8 49.Blocked Thermal overload protection is blocked 9 49.Valid Thermal overload protection is valid The calculated temperature difference of phase-A between winding temperature and oil temperature. The calculated temperature difference of phase-B between winding temperature and oil temperature. The calculated temperature difference of phase-C between winding temperature and oil temperature. PCS-9613S Differential Relay 3-197 Date: 2020-09-02 3 Protection Functions 3 10 49.St Thermal overload protection starts 11 49.StA Phase-A thermal overload protection starts. 12 49.StB Phase-B thermal overload protection starts. 13 49.StC Phase-C thermal overload protection starts. 14 49.Op Thermal overload protection operates to trip. 15 49.Op.PhA Phase-A thermal overload protection operates to trip. 16 49.Op.PhB Phase-B thermal overload protection operates to trip. 17 49.Op.PhC Phase-C thermal overload protection operates to trip. 18 49.Alm Thermal overload protection operates to alarm. 3.25.4 Logic SIG 49.Pkp SIG 49.in_I3P SET [49.Ib_Set] & EN 49.St & Timer t [49.En_Alm] & EN [49.En_Trp] SIG 49.Clr 49.Alm t Timer t 49.Op t Figure 3.25-4 Logic diagram of thermal overload protection (method 1) 3.25.5 Settings ⚫ Access path: MainMenu Settings Protection Settings ThOvLd Settings Table 3.25-2 Settings of thermal overload protection No. Setting Range Default Unit Step 1 49.Ib_Set 0.05~200 15 A 0.001 2 49.K_Trp 1~3 1.2 - 0.001 3 49.K_Alm 1~3 1.1 - 0.001 4 49.t_Tau 0.1~100 1 min 0.001 5 49.K_T_Diff 0~200 30 - 0.001 6 49.Alpha_Cold 1~2 2 - 0.001 Description The reference current setting of thermal overload protection The thermal overload factor setting for tripping The thermal overload factor setting for alarm The heat accumulation time constant of thermal overload protection The temperature constant of thermal overload protection The cooling factor of thermal overload protection PCS-9613S Differential Relay 3-198 Date: 2020-09-02 3 Protection Functions Heat dissipation time constant setting. 7 49.C_Disspt 0.100~10 .000 1.000 - 0.001 When the current Ieq is lower than 0.04In, the thermal time constant adopts the value of [49.Tau]*[49.C_Disspt]. 8 49.En_Trp 9 49.En_Alm Disabled; Enabled Disabled; Enabled Disabled - - Disabled - - Enabling/Disabling thermal overload protection operate to trip Enabling/Disabling thermal overload protection operate to alarm 3.26 Transfer Trip (TT) When breaker failure protection, dead zone protection or overvoltage protection, etc. of the opposite end operates, it is required that the device at the local end operates quickly. The device provides transfer trip to fulfill the application, including phase-segregated and non-phase-segregated input signals used to initiate transfer trip, which can receive transfer trip signals from the opposite end. After receiving transfer trip signal from the opposite end, simultaneous tripping at both ends can be ensured. 3.26.1 Function Description The device provides phase-segregated transfer trip and three-phases transfer trip, which can be controlled by local fault detector by the settings [TT.En_FD_Ctrl]. In addition, the input signals [TT.Init_A], [TT.Init_B], [TT.Init_C] and [TT.Init_3P] are always supervised, and the device will issue an alarm [TT.Alm] and block transfer trip once the binary input is energized for longer than the setting [TT.t_Op]+5s and drop off after resumed to normal with a time delay of 10s. Both phase-segregated transfer trip and three-phase transfer trip operate to block AR if the setting [TT.En_BlkAR] is set as "Enabled". 3.26.2 Function Block Diagram TT TT.Enable TT.Block TT.On TT.Blocked TT.Init_3P TT.Valid TT.Alm TT.Op_3P 3.26.3 I/O Signals Table 3.26-1 Input/Output signals of transfer trip No. Input Signal Description 1 TT.Enable Input signal of enabling transfer trip 2 TT.Block Input signal of blocking transfer trip PCS-9613S Differential Relay 3-199 Date: 2020-09-02 3 3 Protection Functions 3 TT.Init_3P No. Input signal of initiating transfer trip (Three phases) Output Signal Description 1 TT.On Transfer trip is enabled. 2 TT.Blocked Transfer trip is blocked. 3 TT.Valid Transfer trip is valid. 4 TT.Alm The initiating signal of transfer trip is abnormal. 5 TT.Op_3P Transfer trip operates. (Three phases) 3.26.4 Logic 3 EN [TT.En] BI TT.Enable BI TT.Block & TT.On & TT.Blocked >=1 SIG Fail_Device & TT.Valid [TT.t_Op]+5s 10s SIG TT.Init_3P TT.Alm SIG TT.Alm EN [TT.En_FD_Ctrl] >=1 & SIG Local fault detector & SIG TT.Valid [TT.t_Op] 0 TT.Op_3P SIG TT.Init_3P Figure 3.26-1 Logic of transfer trip 3.26.5 Settings ⚫ Access path: MainMenu Settings Protection Settings TT Settings Table 3.26-2 Settings of transfer trip No. Setting 1 TT.t_Op 2 TT.En 3 TT.En_FD_Ctrl Range 0.000~60 0.000 Disabled Enabled Disabled Enabled Default Unit Step Description 0.005 s 0.001 Time delay of transfer trip Enabled - - Enabling/disabling transfer trip Enabled - - Enabling/disabling transfer trip controlled by local fault detector element PCS-9613S Differential Relay 3-200 Date: 2020-09-02 3 Protection Functions 4 TT.En_BlkAR Disabled Enabled Enabled - - Enabling/disabling transfer trip operate to block AR 3.27 Automatic Reclosure (79) To maintain the integrity of the overall electrical transmission system, the device is installed on the transmission system to isolate faulted segments during system disturbances. Faults caused by lightning, wind, or tree branches could be transient in nature and may disappear once the circuit is de-energized. According to statistics, for overhead transmission line, 80%~90% of the faults on overhead lines are the transient faults. AR are installed to restore the faulted section of the transmission system once the fault is extinguished (providing it is a transient fault). For certain transmission systems, AR is used to improve system stability by restoring critical transmission paths as soon as possible. Besides overhead lines, other equipment failure, such as cables, busbar, transformer fault and so on, are generally permanent fault, and AR is not initiated after faulty feeder is tripped. For some mixed circuits, such as overhead line with a transformer unit, hybrid transmission lines, etc., it is required to ensure that AR is only initiated for faults overhead line section, or make a choice according to the situation. 3.27.1 Function Description AR can be used with either integrated device or external device. When AR is used with integrated device, the internal protection logic can initiate AR, moreover, a tripping contact from external device can be connected to the device via input signal to initiate integrated AR. When AR is used as an independent device, it can be initiated by operating signal of protections. The device can output some configurable output signals (such as, contact signals or digital signal, for example, GOOSE signal) to initiate external AR or block external AR. The contact signals includes tripping signal, blocking AR signal and protection operating signal, etc,. According to requirement, these contacts can be selectively connected to external AR and the device can be set as one-shot or multi-shot AR. 3.27.1.1 Enable AR When the setting [79.Opt_Enable] is set as "Setting&Config", AR is determined whether it is enabled or disabled by the external input signal and the internal setting. Otherwise, it is only determined by the internal setting. When AR is enabled, the device outputs the signal "79.On", otherwise the device outputs the signal "79.Off". The logic of enabling AR is: PCS-9613S Differential Relay 3-201 Date: 2020-09-02 3 3 Protection Functions EN [79.En] SET [79.Opt_Enable]=Setting SET [79.Opt_Enable]=Setting&Config SIG 79.Enable SIG 79.Block & >=1 79.On & 79.Off & Figure 3.27-1 Logic of enabling AR 3 3.27.1.2 Synchronism Check for AR When the synchronism check mode of auto-reclosing is independent of that of manual closing, the device provides dedicated settings used by synchronism check for AR. The synchronism check mode can be determined by the settings or configuration signals. When the setting [79.Opt_RSYN_ValidMode] is set as "Setting", the synchronism check mode for AR is determined by the settings, [79.En_SynChk], [79.En_SynDd_RefDd], [79.En_SynLv_RefDd], [79.En_SynDd_RefLv] and [79.En_NoChk]. When the setting [79.Opt_RSYN_ValidMode] is set as "Config", the synchronism check mode for AR is determined by configuration signals, "79.Sel_SynChk", "79.Sel_SynDd_RefDd", "79.Sel_SynLv_RefDd", "79.Sel_SynDd_RefLv" and "79.Sel_NoChk". EN 1 [79.En_SynChk] 79.On_SynChk SIG 79.Sel_SynChk EN [79.En_SynDd_RefDd] 0 1 79.On_SynDd_RefDd SIG 79.Sel_SynDd_RefDd EN [79.En_SynLv_RefDd] SIG 79.Sel_SynLv_RefDd EN [79.En_SynDd_RefLv] SIG 79.Sel_SynDd_RefLv EN [79.En_NoChk] SIG 79.Sel_NoChk EN [79.Opt_RSYN_ValidMode] 0 1 79.On_SynLv_RefDd 0 1 79.On_SynDd_RefLv 0 1 79.On_NoChk 0 Figure 3.27-2 Logic of synchronism check mode selection for AR PCS-9613S Differential Relay 3-202 Date: 2020-09-02 3 Protection Functions Based on the chosen synchronism check mode for AR, the device judges whether the synchronism condition is satisfied, and then implement reclosing. When none of the synchronism check modes for AR is selected, the device will issue an alarm "79.Alm_RSYN_Mode". 3.27.1.3 AR Ready AR must be ready to operate before performing reclosing. The output signal [79.Ready] means that the auto-reclosure can perform at least one time of reclosing function, i.e., breaker open-close-open. When the device is energized or after the settings are modified, AR cannot be ready unless the following conditions are met: 1. AR is enabled. 2. The circuit breaker is ready, such as, normal storage energy and no low pressure signal. 3. The duration of the circuit breaker in closed position pre-fault is greater than the setting [79.t_CBClsd]. 4. There is no the signal of blocking AR. After AR operates, it must reset, i.e. [79.Active]=0, in addition to the above conditions for reclosing again. When there is a fault on an overhead line, the concerned circuit breakers will be tripped normally. After the fault is cleared, the tripping signal will drop out immediately. In case the circuit breaker is in failure, etc., and the tripping signal of the circuit breaker maintains and in excess of the time delay [79.t_PersistTrp], AR will be blocked, as shown in Figure 3.27-3. The input signal [79.CB_Healthy] must be energized before AR gets ready. Because most circuit breakers can finish one complete process: open-closed-open, it is necessary that circuit breaker has enough energy before reclosing. When the time delay of AR is exhausted, AR will be blocked if the input signal [79.CB_Healthy] is still not energized within time delay [79.t_CBReady]. If this function is not required, the input signal [79.CB_Healthy] can be not to configure, and its state will be thought as “1” by default. In order to block AR reliably even if the signal of manually open circuit breaker not connected to the input signal of blocking AR, when the circuit breaker is open by manually and there is CB position input under normal conditions, AR will be blocked with the time delay of 100ms if AR is not initiated and no any trip signal. SIG Any tripping signal [79.t_PersistTrp] 0 >=1 0 SIG [79.t_DDO_Blk] 79.Blocked 79.LockOut Figure 3.27-3 Logic of AR block When AR is disabled, AR fails, synchronism check fails or last shot is reached, or when the internal blocking condition of AR is met. AR will be discharged immediately and next AR will be PCS-9613S Differential Relay 3-203 Date: 2020-09-02 3 3 Protection Functions disabled. When the input signal [79.LockOut] is energized, AR will be blocked immediately. The blocking flag of AR will be also controlled by the internal blocking condition of AR. When the blocking flag of AR is valid, AR will be blocked immediately. The logic of AR ready is shown in Figure 3.27-4. AR will be blocked immediately once the blocking condition of AR appears, but the blocking condition of AR will drop out with a time delay [79.t_DDO_Blk] after blocking signal disappears. >=1 SIG CB closed position 3 [79.t_CBClsd] SIG 79.Active 100ms & >=1 SIG Any tripping signal & & 2s 0 79.Ready SIG 79.Inprog BI [79.CB_Healthy] SIG 79.Blocked 0 [79.t_CBReady] & >=1 >=1 SIG 79.Lockout SIG 79.Failed & >=1 SIG 79.Fail_Chk SIG Last shot is made SIG 79.On Figure 3.27-4 Logic of AR ready When any protection element operates to trip, the device will output a signal [79.Active] until AR drop out (Reset Command). Any tripping signal can be from external protection device or internal protection element. 3.27.1.4 AR Initiation AR can be initiated by the tripping signal of line protection or CB state. 1. AR initiated by tripping signal of line protection AR can be initiated by tripping signal of line protection, and the tripping signal may be from internal trip signal or external trip signal. When AR is ready to reclosing (“79.Ready”=1) and the tripping signal is received, this tripping signal will be kept in the device, and AR will be initiated after the tripping signal drops out. The tripping signal kept in the device will be cleared after the completion of AR sequence (Reset Command). Its logic is shown in Figure 3.27-5. PCS-9613S Differential Relay 3-204 Date: 2020-09-02 3 Protection Functions SIG Reset Command & >=1 SIG Trip Signal & SIG AR Initiation 79.Ready Figure 3.27-5 Tripping initiating AR 2. 3 AR initiated by CB state AR can be initiated by CB state by setting the setting [79.En_CBInit]. Under normal conditions, when AR is ready to reclose (“79.Ready”=1), AR will be initiated if circuit breaker is open and corresponding phase current is nil. AR initiated by CB state logic is shown in Figure 3.27-6 respectively. Usually normally closed contact of circuit breaker is used to reflect CB state. SIG CB open EN [79.En_CBInit] SIG 79.Ready & AR Initiation & Figure 3.27-6 CB state initiating AR 3.27.1.5 AR Reclosing When the dead time delay of AR expires after AR is initiated, if the synchronism check is enabled, the release of reclosing signal shall be subject to the result of synchronism check. After the dead time delay of AR expires, if the synchronism check is still unsuccessful within the time delay [79.t_wait_Chk], the signal of synchronism check failure ("79.Fail_Chk") will be output and the AR will be blocked. If 3-pole AR with no-check is enabled, the condition of synchronism check success ("25.RSYN_OK") will always be established. And the signal of synchronism check success ("25.RSYN_OK") from the synchronism check logic can be applied by AR inside the device or outside the device. [79.t_Dd_3PS1] SIG 79.Inhibit_AR SIG 3-pole AR Initiation 0 & If 79.Inhibit_AR operates, then circuit of time delay will be interrupted. AR Pulse >=1 & [79.t_Wait_Chk] 0 79.Fail_Chk SIG 79.Ok_Chk Figure 3.27-7 One-shot AR PCS-9613S Differential Relay 3-205 Date: 2020-09-02 3 Protection Functions Reclosing pulse length may be set through the setting [79.t_PW]. For the circuit breaker without anti-pump interlock, the setting [79.En_CutPulse] is available to control the reclosing pulse. When this function is enabled, if the device operates to trip during reclosing, the reclosing pulse will drop out immediately, so as to prevent multi-shot reclosing onto fault. After the reclosing signal is issued, AR will drop out with time delay [79.t_Reclaim], and can carry out next reclosing. The reclaim timer is started when the CB closing signal is given. The reclaim timer defines a time from the issue of the reclosing command, after which the reclosing function resets. Should a new trip occur during this time, it is treated as a continuation of the first fault. SIG 3 0ms AR Pulse SIG Three - phase Trip EN [ 79.En _ CutPulse ] [79.t_PW] & & 79.Out >=1 SIG & 79.Out [79.t_ Reclaim] 0ms Reset Command Figure 3.27-8 Reclosing output logic 3.27.1.6 Reclosing Failure and Success For line fault, the fault will be cleared after the device operates to trip. When the following cases appear, the reclosing is unsuccessful. 1. If any protection element operates to trip when AR is enabled ("79.On"=1) and AR is not ready ("79.Ready"=0), the device will output the signal "79.Failed". 2. For one-shot AR, if the tripping signal is received again within reclaim time after the reclosing pulse is issued, the reclosing shall be considered as unsuccessful. 3. For multi-shot AR, if the reclosing times are equal to the setting value of AR number and the tripping signal is received again after the last reclosing pulse is issued, the reclosing shall be considered as unsuccessful. 4. The setting [79.En_FailCheck] is available to judge whether the reclosing is successful by CB state, when it is set as “Enabled”. If CB is still in open position with a time delay [79.t_Fail] after the reclosing pulse is issued, the reclosing shall be considered as unsuccessful. For this case, the device will issue a signal "79.Failed" to indicate that the reclosing is unsuccessful, and this signal will drop out after (Reset Command). AR will be blocked if the reclosing shall be considered as unsuccessful. After unsuccessful AR is confirmed, AR will be blocked. PCS-9613S Differential Relay 3-206 Date: 2020-09-02 3 Protection Functions SIG 79.On SIG 79.Ready SIG Any tripping command SIG Last shot is made & & >=1 0 SIG 79.Inprog SIG 79.Blocked 100ms >=1 79.Failed & 3 >=1 SIG AR Pulse SIG CB closed EN & [79.t_Fail ] 0 & [79.En_ FailCheck ] & & 0 SIG 0s 2s Reset Command 79.Succeeded [79.t_Fail ] 79.Completed Figure 3.27-9 Reclosing failure and success 3.27.1.7 Reclosing Numbers Control The device may be set up into one-shot or multi-shot AR. Through the setting [79.Num], the maximum number of reclosing attempts may be set up to 4 times. Generally, only one-shot AR is selected. Some corresponding settings may be hidden if one-shot AR is selected. ⚫ [79.Num]=1 It means one-shot reclosing. Line protection device will operate to trip when a transient fault occurs on the line and AR will be initiated. After the dead time delay for AR is expired, the device will send reclosing pulse, and then AR will drop out after the time delay [79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed, and the device will output the signal of reclosing failure "79.Failed". ⚫ [79.Num]>1 It means multi-shot reclosing. For multi-shot reclosing, line protection device will operate to trip when a transient fault occurs on the line and AR will be initiated. After the dead time delay of the first reclosing is expired, the device will send reclosing pulse, and then AR will drop out after the time delay [79.t_Reclaim] to ready for the next reclosing. For permanent fault, the device will operate to trip again after the reclosing is performed, and then AR is initiated after the tripping contact drops off. After the time delay for AR is expired, the device will send reclosing pulse. The sequence is repeated until the reclosing is successful or the maximum permit reclosing number [79.Num] is reached. PCS-9613S Differential Relay 3-207 Date: 2020-09-02 3 Protection Functions 3.27.1.8 AR Time Sequence Diagram The following two examples indicate typical time sequence of AR process for transient fault and permanent fault respectively. Signal Fault 3 Trip CB 52b Open [79.t_Reclaim] 79.t_Reclaim 79.Active 79.Inprog [79.t_Dd_3PS1] 79.Inprog_3P [79.t_Dd_3PS1] 79.Ok_Chk AR Out [79.t_PW] 79.Perm_Trp3P 79.Failed Time Figure 3.27-10 Transient fault PCS-9613S Differential Relay 3-208 Date: 2020-09-02 3 Protection Functions Signal Fault Trip 52b Open Open [79.t_Reclaim] 79.t_Reclaim 79.Active 3 79.Inprog 79.Inprog_3P1 79.Inprog_3PS2 [79.t_Dd_3PS1] [79.t_Dd_3PS2] 79.Ok_Chk AR Out [79.t_PW] [79.t_PW] 79.Perm_Trp3P 79.Failed 200ms Time Figure 3.27-11 Permanent fault ([79.Num]=2) PCS-9613S Differential Relay 3-209 Date: 2020-09-02 3 Protection Functions 3.27.2 Function Block Diagram 79 79. Enable 79.On 79.Block 79.Off 79.Trp3P 79. Close 79. Ready 79. Lockout 3 79.CB_ Healthy 79.AR_Blkd 79.Clr_ Counter 79. Active 79. Inprog 79. Inprog_3P 79.Inprog _ 3PS1 79.Inprog _ 3PS2 79.Inprog _ 3PS3 79.Inprog _ 3PS4 79. Rcls_ Status 79.Failed 79.Succeeded 79.Completed 79.Fail_Chk 3.27.3 I/O Signals Table 3.27-1 Input/Output signals of AR No. Input Signal 1 79.Enable 2 79.Block 3 79.Trp3P Description Input signal of enabling AR, it is triggered from binary input or programmable logic etc. Input signal of blocking AR, it is triggered from binary input or programmable logic etc. Input signal of three-phase tripping from line protection to initiate AR Input signal of blocking reclosing, usually it is connected with the operating 4 79.Lockout signals of definite-time protection, transformer protection and busbar differential protection, etc. 5 79.CB_Healthy 6 79.Clr_Counter No. The input for indicating whether circuit breaker has enough energy to perform the close function Clear the reclosing counter Output Signal Description PCS-9613S Differential Relay 3-210 Date: 2020-09-02 3 Protection Functions 1 79.On AR is enabled. 2 79.Off AR is disabled. 3 79.Close AR operates. 4 79.Ready AR have been ready for reclosing cycle. 5 79.Blocked AR is blocked. 6 79.Active AR logic is active. 7 79.Inprog AR cycle is in progress 8 79.Inprog_3P 3-pole AR cycle is in progress 9 79.Inprog_3PS1 First 3-pole AR cycle is in progress 10 79.Inprog_3PS2 Second 3-pole AR cycle is in progress 11 79.Inprog_3PS3 Third 3-pole AR cycle is in progress 12 79.Inprog_3PS4 Fourth 3-pole AR cycle is in progress 3 AR status 0: AR is preprocessed 13 79.Status 1: AR is ready. 2: AR is in progress. 3: AR is successful. 14 79.Failed Auto-reclosing fails 15 79.Succeeded Auto-reclosing is successful 16 79.Fail_Chk Synchro-check for AR fails 17 79.Completed AR is completed. 3.27.4 Settings ⚫ Access path: MainMenu Settings Protection Settings AR Settings Table 3.27-2 Settings of AR No. Settings Range Default value Unit Step 1 79.Num 1~4 1 - 1 2 79.t_Dd_3PS1 0~600 0.600 s 0.001 3 79.t_Dd_3PS2 0~600 0.600 s 0.001 4 79.t_Dd_3PS3 0~600 0.600 s 0.001 5 79.t_Dd_3PS4 0~600 0.600 s 0.001 6 79.t_CBClsd 0~600 5.000 s 0.001 PCS-9613S Differential Relay Description Maximum number of reclosing attempts Dead time of first shot 3-pole reclosing Dead time of second shot 3-pole reclosing Dead time of third shot 3-pole reclosing Dead time of fourth shot 3-pole reclosing Time delay of circuit breaker in closed position before reclosing 3-211 Date: 2020-09-02 3 Protection Functions No. Settings Range Default value Unit Step Description Time delay to wait for CB healthy, and begin to timing when the input 7 79.t_CBReady 0~600 5.000 s 0.001 signal [79.CB_Healthy] de-energized and if it is is not energized within this time delay, AR will be blocked. 3 8 79.t_Wait_Chk 0~600 10.000 s 0.001 9 79.t_Reclaim 0~600 15.000 s 0.001 Maximum wait time for synchronism check Reclaim time of AR Dropout time delay of blocking AR, 10 79.t_DDO_Blk 0~600 5.000 s 0.001 when blocking signal for AR disappears, AR blocking condition drops out after this time delay 11 79.t_PersistTrp 0~600 0.200 s 0.001 Time delay of excessive trip signal to block AR Time delay allow for CB status 12 79.t_Fail 0~600 0.200 s 0.001 change to conform reclosing successful 13 14 79.t_PW 79.En_FailCheck 15 79.En_CutPulse 16 79.En 0~600 Disabled Enabled Disabled Enabled Disabled Enabled 0.120 s 0.001 Pulse width of AR closing signal Enabling/disabling confirm whether Disabled - - AR is successful by checking CB state Disabled - - Enabled - - Enabling/disabling adjust the length of reclosing pulse Enabling/disabling auto-reclosing Enabling/disabling AR by external input signal besides logic setting 17 79.Opt_Enable Setting Setting&Config Setting - - [79.En] Setting: only the setting Setting&Config: the setting and configuration signal 18 79.En_CBInit Disabled Enabled Disabled - - Enabling/disabling AR be initiated by open state of circuit breaker Selection of decision mode for AR 19 79.Opt_RSYN_Valid Setting; Mode Config synchronism check Setting - - Setting: determined by the setting Config: determined by the configuration signal PCS-9613S Differential Relay 3-212 Date: 2020-09-02 3 Protection Functions No. Settings Range Default value Unit Step Description Enabling/disabling 20 79.En_SynChk Disabled Enabled Disabled - - synchro-check of AR (valid only if the setting [79.Opt_RSYN_ValidMode] = Setting) Enabling/disabling dead check for both the reference side and the 21 79.En_SynDd_RefDd Disabled Enabled Disabled - - synchronization side (valid only if the setting [79.Opt_RSYN_ValidMode] = Setting) Enabling/disabling live check for synchronization 22 79.En_SynLv_RefDd Disabled Enabled Disabled - - side and dead check for reference side (valid only if the [79.Opt_RSYN_ValidMode] setting = Setting) Enabling/disabling dead check for 23 79.En_SynDd_RefLv Disabled Enabled synchronization side and live check Disabled - - for reference side (valid only if the setting [79.Opt_RSYN_ValidMode] = Setting) Enabling/disabling AR without any 24 79.En_NoChk Disabled Enabled Enabled - - check (valid only if the setting [79.Opt_RSYN_ValidMode] = Setting) 3.28 VT Circuit Supervision (VTS) 3.28.1 General Application The purpose of VT circuit supervision is to detect whether VT circuit is normal. Some protection functions should be disabled when measurement from VT circuit fails. VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault, poor contact of VT circuit, VT maintenance and so on. The device can detect them and issue an alarm signal to block relevant protection functions. However, the alarm of VT circuit failure should not be issued when the following cases happen. ⚫ Line VT is used as protection VT and the protected line is out of service. ⚫ Only current protection functions are enabled and VT is not connected to the device. ⚫ The specific current protection has picked up before the satisfaction of conditions of VT circuit failure alarm. PCS-9613S Differential Relay 3-213 Date: 2020-09-02 3 3 Protection Functions 3.28.2 Function Description VT circuit supervision can detect failure of single-phase, two-phase and three-phase on VT. Under normal condition, the device continuously supervises input voltage from VT. The VT circuit failure alarm will be issued with configurable time delay if residual voltage exceeds or negative-voltage exceeds the threshold value or positive-sequence voltage is less than the threshold value. If a specific current protection (such as breaker failure protection) operates to pick up, the time delay count-down will be paused until the protection returns to normal state. 3 Under normal conditions, the device detects residual voltage that is greater than the setting [VTS.3U0_Set] or negative-sequence voltage that is greater than the setting [VTS.U2_Set] to distinguish a single-phase or two-phase VT circuit failure, and detects positive-sequence voltage that is less than the setting [VTS.U1_Set] to distinguish a three-phase VT circuit failure. Upon detecting abnormality on VT circuit, an alarm will come up after a time delay of [VTS.t_DPU] and drop-off with a time delay of [VTS.t_DDO] after that VT is restored to normal. Upon abnormality detection on VT circuit, an instant alarm will be issued after a time delay of 25ms and drop-off without time delay. VT (secondary circuit) MCB auxiliary contact can be connected to the binary input circuit of the device as a binary signal. If the MCB has been opened (i.e. "VTS.MCB_VT" is energized), the device will consider that the VT circuit is in a bad condition and issue an alarm without a time delay. If the auxiliary contact is not connected to the device, VT circuit supervision will be issued with time delay as mentioned in previous paragraph. When VT is not connected into the device, the alarm shall be not issued if the logic setting [En_VT] is set as "Disabled". However, the alarm is still issued if the binary input "VTS.MCB_VT" is energized, no matter that the logic setting [En_VT] is set as "Disabled" or "Enabled". 3.28.3 Function Block VTS VTS.Enable VTS.Block VTS.Alm VTS.InstAlm VTS.MCB_VT VTS.in_52b 3.28.4 I/O Signals Table 3.28-1 Input/output signals of VT circuit supervision No. Input Signal 1 VTS.Enable 2 VTS.Block Description VT circuit supervision enabling input, it is triggered from binary input or programmable logic etc. VT circuit supervision blocking input, it is triggered from binary input or programmable logic etc. PCS-9613S Differential Relay 3-214 Date: 2020-09-02 3 Protection Functions 3 VTS.MCB_VT Binary input for VT MCB auxiliary contact 4 VTS.in_52b Phase A opening position input of circuit breaker No. Output Signal Description 1 VTS.Alm Alarm signal to indicate VT circuit fails 2 VTS.InstAlm Instantaneous alarm signal to indicate VT circuit failure 3.28.5 Logic SIG Pickup of specific current prot. SET 3U0>[VTS.3U0_Set] SET U2>[VTS.U2_Set] SET U1<[VTS.U1_Set] >=1 SET [VTS.Opt_VT]=Bay SIG 52b (three phase) SIG Ip > 0.04In EN [En_VT] 3 & If specific current prot. picks up, the time delay count-down will be paused. >=1 & [VTS.t_DPU] [VTS.t_DDO] >=1 & >=1 & VTS.Alm VTS.MCB_VT BI EN [VTS.En] SIG VTS.Enable SIG VTS.Block & Figure 3.28-1 VT circuit supervision logic diagram SIG Pickup of specific current prot. SET 3U0>[VTS.3U0_Set] SET U2>[VTS.U2_Set] SET U1<[VTS.U1_Set] >=1 & >=1 SET [VTS.Opt_VT]=Bay SIG 52b (three phase) SIG Ip > 0.04In EN [En_VT] & If specific current prot. picks up, the time delay count-down will be paused. 25ms BI >=1 0ms & >=1 & VTS.InstAlm VTS.MCB_VT EN [VTS.En] SIG VTS.Enable SIG VTS.Block & Figure 3.28-2 Instantaneous VT circuit supervision logic diagram Where: Ip is any measured single-phase current; In is the rated phase current; In this device, the specific current protection refers to phase overcurrent protection, earth fault overcurrent protection and breaker failure protection. ⚫ If the specific protection picks up firstly and then an abnormality on VT circuit is detected. The PCS-9613S Differential Relay 3-215 Date: 2020-09-02 3 Protection Functions VT circuit failure alarm should not be issued before the specific protection returns to normal state; ⚫ If an abnormality on VT circuit is detected firstly and then the specific protection operates to pick up. The time delay count-down of VT circuit failure alarm shall be paused until the protection return to normal state. ⚫ If the specific protection operates and VT circuit failure alarm has been issued, the alarm will be maintained. 3.28.6 Settings 3 ⚫ Access path: MainMenu Settings Global Settings Superv Settings Table 3.28-2 Settings of VT circuit supervision No. Setting Default Range Step Unit 1 VTS.U1_Set 30.00 0~100 0.01 V 2 VTS.3U0_Set 8.00 0~100 0.01 V 3 VTS.U2_Set 8.00 0~100 0.01 V 4 VTS.t_DPU 1.500 0.2~30 0.001 s 5 VTS.t_DDO 10.000 0.2~30 0.001 s 6 VTS.En Enabled - - 7 VTS.Opt_VT Bus - - Disabled Enabled Bus or Bay or Description Positive-sequence voltage threshold for VT circuit supervision Zero-sequence voltage (calculated) threshold for VT circuit supervision Negative-sequence voltage setting of VT circuit supervision function. Delay pickup setting for the alarm of VT circuit supervision Delay drop off setting for the alarm of VT circuit supervision Logic setting for alarm function of VT circuit supervision Selection of Bay VT or Bus VT 3.29 CT Circuit Supervision (CTS) The purpose of the CT circuit supervision is to detect any abnormality on CT secondary circuit. When CT secondary circuit is abnormal, the current acquired by the device is not accurate, which will affect protection functions related to the current. Therefore, it is necessary to monitor the CT abnormal condition. When CT abnormality is detected, the device shall issue an alarm signal and block the relevant protection functions. 3.29.1 Function Description Under normal conditions, CT secondary signal is continuously supervised by detecting the residual current and voltage. If residual current is larger than [CTS.3I0_Set] whereas residual voltage is less than [CTS.3U0_Set], and any phase current is less than 0.04In, CT circuit failure is considered. The concerned protection functions are blocked and an alarm is issued with a time delay of [CTS.t_DPU] and drop off with a time delay of [CTS.t_DDO] after CT circuit is restored to normal condition. PCS-9613S Differential Relay 3-216 Date: 2020-09-02 3 Protection Functions 3.29.2 Function Block Diagram CTS CTS.Enable CTS.On CTS.Block CTS.Blocked CTS.Valid CTS.Alm 3 3.29.3 I/O Signals Table 3.29-1 Input/output signals of CT circuit supervision No. Input Signal 1 CTS.Enable 2 CTS.Block No. Description CT circuit supervision enabling input, it is triggered from binary input or programmable logic etc. CT circuit supervision blocking input, it is triggered from binary input or programmable logic etc. Output Signal Description 1 CTS.Alm Alarm signal to indicate CT circuit fails 2 CTS.On CT circuit supervision is enabled. 3 CTS.Blocked CT circuit supervision is blocked. 4 CTS.Valid CT circuit supervision is valid. 3.29.4 Logics EN [CTS.En] SIG CTS.Enable SIG CTS.Block SIG Fail_Device & CTS.On & CTS.Blocked >=1 & CTS.Valid SIG CTS.Valid SET 3I0>[CTS.3I0_Set] SET 3U0<[CTS.3U0_Set] SIG IA<0.04In SIG IB<0.04In SIG IC<0.04In & [CTS.t_DPU] [CTS.t_DDO] CTS.Alm & >=1 Figure 3.29-1 Logic of CT circuit failure PCS-9613S Differential Relay 3-217 Date: 2020-09-02 3 Protection Functions 3.29.5 Settings ⚫ Access path: MainMenu Settings Global Settings Superv Settings Table 3.29-2 Settings of CT circuit supervision No. Settings Range Default value Unit Step Remark The 1 CTS.3I0_Set 0.00~200.00 0.1 A 0.001 3 calculated residual current setting of CT circuit supervision function. The 2 CTS.3U0_Set 0.00~200.00 30 V 0.001 calculated residual voltage setting of CT circuit supervision function. 3 CTS.t_DPU 0.000~100.000 1.25 s 0.001 4 CTS.t_DPO 0.000~100.000 10 s 0.001 5 CTS.En Disabled - - Disabled Enabled Delay pick-up time setting for CT circuit failure Delay drop-off time setting for CT circuit failure Enabling/disabling CT circuit supervision function. 3.30 Fault Location (FL) The main objective of line protection is fast, selective and reliable operation for faults on a protected line section. Besides this, information on distance to fault is very important for those involved in operation and maintenance. Reliable information on the fault location greatly decreases the outage of the protected lines and increases the total availability of a power system. This fault location function cannot be used for the transmission line with series compensation. 3.30.1 Function Description For a permanent fault, it is necessary to find out and eliminate the fault point and as soon as possible so as to reduce the time of power off. Therefore, accurate fault location is very important. Single-end fault location is available in the device. Fault location picks up after the device operates to trip when there is a fault in the line. If the pickup time is greater than 25ms, fault location is calculated with a time delay of 10ms after the device operates to trip. If the pickup time is smaller than 25ms, fault location is calculated with a time delay of 20ms after the device operates to trip. When there is a protection tripping with faulty phase selection, the calculation of the fault impedance is initiated. According to the fault impedance to locate the fault point, two calculation results are provided, which is the length of the fault point distance from the end of the device and its percentage of the lines length. For parallel lines, there is a mutual coupling between each phase, and there is also a mutual PCS-9613S Differential Relay 3-218 Date: 2020-09-02 3 Protection Functions coupling between parallel lines. The coupling strength between parallel lines associated with the transposition way. For parallel lines with fully transposition, positive-sequence and negative-sequence mutual coupling is very small, and usually can be ignored. But zero-sequence mutual coupling has a greater influence on the line, so the measured impedance must consider the effect. 3.30.1.1 Fault Location Algorithm The device adopts single-end fault location, which only uses the measured value of the voltage and the current at one end. The error is mainly from the effect of fault resistance of fault point and infeed current from power source of the opposite end. When a short-circuit fault with fault resistance occurs, additional voltage will be generated in the fault resistance by infeed current from power source of the opposite end, which will have a great impact on the measurement result. Generally, the larger the fault resistance is, the larger the impact will be. EM UM ZM Bus M ZF ZL-ZF IM IN IF UN ZN EN Bus N RF Figure 3.30-1 Equivalent circuit of single-phase fault with fault resistance Where: U̇M is busbar voltage at side M. İM is line phase current at side M. İ0 is line zero-sequence current at side M. İF is the fault current of fault resistance. K 0 is zeros-sequence compensation coefficient R F is fault resistance. U̇M = (İM + K 0 × 3İ0 ) × ZF + İF × R F İF = CM0 3İ0 CM0 ZN0 + ZL0 − ZF0 = ZM0 + ZN0 + ZL0 K0 = Equation 3.30-1 ZF0 − ZF1 3ZF1 CM0 is zero-sequence distribution coefficient at side M. PCS-9613S Differential Relay 3-219 Date: 2020-09-02 3 3 Protection Functions ZM0 is zero-sequence impedance at side M. ZN0 is zero-sequence impedance at side N. ZL0 is line zero-sequence impedance. ZF1 is line positive-sequence impedance from side M to fault point. ZF0 is line zero-sequence impedance from side M to fault point. 3 U̇M, İM and İ0 can be measured. Because the parameters of zero-sequence impedance circuit between the system at both sides are generally similar. CM0 can be approximately thought as real number. Therefore, ZF1 can be calculated by Equation 3.30-1. 3İ0 Equation 3.30-2 U̇M = (İM + K 0 × 3İ0 ) × ZF1 + × RF CM0 The two ends are multiplied by conjugate complex number of İ0. I0′ × U̇M = (İM + K 0 × 3İ0 ) × I0′ × ZF1 + 3|I0 |2 × RF CM0 Equation 3.30-3 Take the imaginary part of Equation 3.30-3, Im[I0′ × U̇M ] = Im[(İM + K 0 × 3İ0 ) × I0′ × ZF1 ] Equation 3.30-4 The result of fault location can be obtained directly by solving ZF1 . The distance from the location of the device to the fault point (i.e., Fault Location) is: Fault Location = Im[ZF1 ] × Line Length (km) X1L Fault Location (Percent) = Fault Location × 100% Line Length Where: ZF1 is the measured impedance from the location of the device to the fault point. X1L is line positive-sequence impedance. Line Length is the length of transmission line (km) 3.30.2 Function Block Diagram FL Fault_Location Fault_Phase Max_Diff_Curr PCS-9613S Differential Relay 3-220 Date: 2020-09-02 3 Protection Functions 3.30.3 I/O Signals Table 3.30-1 Output signals of fault location No. Output Signal Description 1 Fault_Location The result of fault location 2 Faulty_Phase The selected faulty phase 3 Max_Diff_Curr The maximum differential current at the moment of fault location 3.30.4 Settings ⚫ Access path: 3 MainMenu Settings Protection Settings Line Settings Table 3.30-2 Settings of fault location No. Settings Range Default value Unit Step 1 X1L 0~600 10 Ω 0.001 2 R1L 0~600 1 Ω 0.001 3 X0L 0~600 20 Ω 0.001 4 R0L 0~600 3 Ω 0.001 5 LineLength 0~6000 100 km 0.01 PCS-9613S Differential Relay Remark Positive-sequence reactance of the whole line (secondary value) Positive-sequence resistance of the whole line (secondary value) Zero-sequence reactance of the whole line (secondary value) Zero-sequence resistance of the whole line (secondary value) Total length of the whole line 3-221 Date: 2020-09-02 3 Protection Functions 3 PCS-9613S Differential Relay 3-222 Date: 2020-09-02 4 Control Functions 4 Control Functions Table of Contents 4.1 Switchgear Control .......................................................................................... 4-1 4.1.1 Functional Description .......................................................................................................... 4-1 4.1.2 Operation Theory.................................................................................................................. 4-2 4.1.3 Function Block Diagram ....................................................................................................... 4-5 4.1.4 I/O Signals ............................................................................................................................ 4-5 4.1.5 Logics ................................................................................................................................... 4-7 4.1.6 Settings ............................................................................................................................... 4-11 4.2 Manual Closing Synchronism Check ........................................................... 4-12 4.2.1 Operation Theory................................................................................................................ 4-13 4.2.2 Function Block Diagram ..................................................................................................... 4-15 4.2.3 I/O Signals .......................................................................................................................... 4-15 4.2.4 Logics ................................................................................................................................. 4-16 4.2.5 Settings ............................................................................................................................... 4-18 List of Figures Figure 4.1-2 DPS synthesis logic............................................................................................... 4-8 Figure 4.1-3 DPS alarm logic ...................................................................................................... 4-8 Figure 4.1-4 Interlocking logic ................................................................................................... 4-8 Figure 4.1-5 Manual control logic .............................................................................................. 4-9 Figure 4.1-6 Logic diagram of closing operation ................................................................... 4-10 Figure 4.1-7 Logic diagram of opening operation ................................................................. 4-11 Figure 4.2-1 Relationship between reference and synchronous voltages ......................... 4-13 Figure 4.2-2 Synchronism check logic.................................................................................... 4-16 Figure 4.2-2 Synchro-check logic ............................................................................................ 4-17 Figure 4.2-4 Dead charge check logic ..................................................................................... 4-18 List of Tables PCS-9613S Differential Relay 4-a Date: 2020-09-02 4 4 Control Functions Table 4.1-1 Remote/Local control mode switch logic.............................................................. 4-2 Table 4.1-2 Input/Output signals of control function ............................................................... 4-5 Table 4.1-3 Settings of DPS function....................................................................................... 4-11 Table 4.1-4 Settings of control function .................................................................................. 4-12 Table 4.1-5 Settings of interlocking function ......................................................................... 4-12 Table 4.2-1 Input/Output signals of manual closing synchronism check ........................... 4-15 Table 4.2-2 Settings of synchronism check ........................................................................... 4-18 4 PCS-9613S Differential Relay 4-b Date: 2020-09-02 4 Control Functions 4.1 Switchgear Control The switchgear control function is mainly used to realize operation of primary equipment such as circuit breaker (CB), disconnect switch (DS) and earthing switch (ES). This function can be divided into remote control and local control according to the control source location. A remote control mainly refers to remote control commands from substation automation system (SAS) or network control center (NCC). However, a control triggered manually from the device LCD, by a terminal contact or by a panel handle is a local control. The switchgear control function is closely related to interlocking, double point status (DPS), remote/local control mode switching and tripping statistics. 4.1.1 Functional Description A control command can realize various control signals such as the CB/DS/ES opening/closing. In order to ensure the reliability of the control output, a locking circuit is added to each control object. The operation is strictly in accordance with the selection, check and execution steps, to ensure that the control operation can be safely and reliably implemented. In addition, the device has a hardware self-checking and blocking function to prevent hardware damage from mal-operation output. When the device is in the remote-control mode, the control command may be sent via communication protocol; when it is in the local control mode, the local operation may be performed on the device LCD or panel handle. A complete control process is: 1. Protocol module sends a selection command; 2. Control module responds the success or failure result of selection; 3. If the selection is successful, the protocol module sends an execution command, otherwise it sends a cancel command; 4. Control module responds the success or failure result of execution; 5. The control operation may be open/close or up/down/stop. When the device is in the maintenance status, it can still respond to local control commands. The switchgear control function can cooperate with functions such as synchronism check and interlocking criteria calculation to complete the output of the corresponding operation command. It can realize the normal control output in one bay and the interlocking and programmable logic configuration between bays. This device supports the following functional control module: Module Description CSWI Control of circuit breaker (CB), disconnector switch (DS) or earthing switch (ES) RMTLOC Remote or local control mode XCBR Synthesis of CB position, three-phase or phase separated PCS-9613S Differential Relay 4-1 Date: 2020-09-02 4 4 Control Functions Module Description XSWI Synthesis of DS/ES position SXCBR/SCSWI Trip counter of CB/DS/ES RSYN Synchronism check for CB closing CILO Interlocking logic for CB/DS/ES control MCSWI Manual control of CB/DS/ES CHKPOS Position verification for switchgear control 4.1.2 Operation Theory The initiation of a control command may be sent to the device by the SCADA or the NCC through communication protocol. It may also be the operation of the device LCD or the manual triggering through configured signal. The command is sent by the CPU to the control module for processing, and a control record is made on the CPU module according to the control result. 4 4.1.2.1 Remote/Local Control Mode Switch Since the source of a control command may be SAS or NCC, or may be triggered by the device LCD or terminal contact, it is necessary to provide a remote/local control mode switch function. The remote/local control mode switch function determines whether the device is in the remote or the local control permission state through the configuration of terminal contact, function key, or binary signal. Each control object provides a remote/local input, and the control module determines the current control authority to be remote or local according to the input value. By default, if the input is not configured, any control operation is blocked. Table 4.1-1 Remote/Local control mode switch logic in_Remote in_Local Remote Control Local Control NULL NULL Disable Disable 0 NULL Disable Enable 1 NULL Enable Disable NULL 0 Enable Disable NULL 1 Disable Enable 0 0 Disable Disable 0 1 Disable Enable 1 0 Enable Disable 1 1 Enable Enable 4.1.2.2 Double Point Status A double point status (DPS), which usually indicates switchgear status, can be derived from 2 ordinary binary inputs. The signification of a DPS is shown in the following table. For switchgear status, only the 2 statuses "01" and "10" indicating respectively the positions opening and closing are valid. The other 2 statuses "00" and "11", i.e. intermediate or bad status, will cause the alarm "DPS.Alm". PCS-9613S Differential Relay 4-2 Date: 2020-09-02 4 Control Functions DPS Bit0 = 0 Bit0 = 1 Bit1 = 0 DPS_INT DPS_OFF Bit1 = 1 DPS_ON DPS_BAD The unit also supports the DPS synthesis through switchgear opening and closing positions after jittering processing. The synthetic DPS contains original SOE timestamp. The CB control function supports phase-segregated position inputs and can synthesize these inputs into general position. In accordance with the control object, the DPS synthesis function is divided into 2 modules: XCBR and XSWI. The XCBR is mainly used for CB position synthesis, including phase-segregated positions, while the XSWI is used DS or ES position synthesis. For the convenient use in user-defined logic programming, this functional module derives four single-bit outputs to indicate each DSP state. DPS State Indication Signal DPS_ON DPS_OFF DPS_INT DPS_BAD ON 1 0 0 0 OFF 0 1 0 0 INT 0 0 1 0 BAD 0 0 0 1 4 4.1.2.3 Trip Counter The trip counter function takes the DPS of switchgear position as input count the trip times. For CB, this device supports phase-segregated and general trip statistics. The trip counter function is triggered by DPS change. The counting result is stored in non-volatile memory for power-off holding. Use the clear command from the menu in local LCD or customized binary signal to reset trip counter. 4.1.2.4 Interlocking The interlocking function will influence the control operation output. When the function is enabled, the device determines whether the control operation is permitted based on the interlocking logic result. Each control object is equipped with an independent interlocking logic which supports unlocking operation through a binary signal. The interlocking function is very important for the control operation of switchgears. During the operation of primary equipment, the positions of the relevant equipment must be correct for operation permission. For remote control, i.e. command from SAS or NCC, this device could judge the interlocking logic depending on the message within the command; for local control through device LCD or terminal contact, please use the corresponding logic setting to enable/disable the interlocking function. 4.1.2.5 Manual Control The switchgear control function supports manual control function that can be configured with a terminal contact or binary signal to trigger the control operation. PCS-9613S Differential Relay 4-3 Date: 2020-09-02 4 Control Functions The manual control function supports the control input configuration of selection and open/close. When the control object selection input is configured, the signal "1" indicates that the current control object has to be selected before a control operation; if the control object selection input is not configured, the control command can be directly issued without judgment of selection. 4.1.2.6 Switchgear Position Verification The position verification function is provided during switchgear control process. In a control function block of circuit breaker, disconnector or earthing switch, if the input “in_CheckPos_En” is set as 1, the CB/DS/ES position shall be verified when receiving a remote or local control command. The verification logic complies with IEC 61850 standard is: 4 ⚫ A control object only permits to be opened when its DPS is CLOSE; ⚫ A control object only permits to be closed when its DPS is OPEN; ⚫ The device shall respond control command failed with the cause of failure when its DPS is INT, BAD or opposite (i.e. OPEN while opening or CLOSE while closing). 4.1.2.7 Direct Control For applications such as signal reset and function enable/disable, the control mode is generally direct control, i.e. execution without selection before, direct control with normal security in IEC 61850. The direct control function provides remote/local switch and interlocking configurations. The control command is usually issued directly by the SAS. It also supports the command triggered by binary signal. PCS-9613S Differential Relay 4-4 Date: 2020-09-02 4 Control Functions 4.1.3 Function Block Diagram 4 XCBR: circuit breaker; XSWI: disconnector switch or earthing switch 4.1.4 I/O Signals The prefix CB** for circuit breaker and DS** for disconnector switch in the following lists are hidden since their description (if valid) are similar. Table 4.1-2 Input/Output signals of control function No. 1 Input Signal in_en Description Enabling function PCS-9613S Differential Relay 4-5 Date: 2020-09-02 4 Control Functions 4 2 In_blk Disabling function 3 in_Remote Remote control mode 4 in_Local Local control mode 5 in_Pos_NO Normally opened contact input for DPS opening position 6 in_Pos_NC Normally closed contact input for DPS closing position 7 in_Pos_A_NO Phase A normally opened contact input for DPS opening position 8 in_Pos_A_NC Phase A normally closed contact input for DPS closing position 9 in_Pos_B_NO Phase B normally opened contact input for DPS opening position 10 in_Pos_B_NC Phase B normally closed contact input for DPS closing position 11 in_Pos_C_NO Phase C normally opened contact input for DPS opening position 12 in_Pos_C_NC Phase C normally closed contact input for DPS closing position 13 in_N_Trp Opening command for trip counter 14 in_N_Trp_A Phase A opening command for trip counter 15 in_N_Trp_B Phase B opening command for trip counter 16 in_N_Trp_C Phase C opening command for trip counter 17 in_Clr_Cnt Clear trip counters 18 in_Rsyn Structure pointer of synchronism check element 19 in_EnaOpn Opening permission for interlocking 20 in_EnaCls Closing permission for interlocking 21 in_CILO_Bypass Bypass for interlocking 22 in_Manual_Sel Selection for manual control 23 in_Manual_Opn Opening for manual control 24 in_Manual_Cls Closing for manual control 25 in_CheckPos_En Input signal of enabling of position verification function for switchgear control No. Output Signal Description 1 NO_DPS DPS opening position 2 NC_DPS DPS closing position 3 NO_DPS_A Phase A DPS opening position 4 NC_DPS_A Phase A DPS closing position 5 NO_DPS_B Phase B DPS opening position 6 NC_DPS_B Phase B DPS closing position 7 NO_DPS_C Phase C DPS opening position 8 NC_DPS_C Phase C DPS closing position 9 DPS Synthetic DPS for switchgear position 10 DPS_A Synthetic DPS for switchgear phase A position 11 DPS_B Synthetic DPS for switchgear phase B position 12 DPS_C Synthetic DPS for switchgear phase C position 13 N_Trp Trip counter 14 N_Trp_A Phase A trip counter 15 N_Trp_B Phase B trip counter 16 N_Trp_C Phase C trip counter 17 Opn_Enabled Permission of opening operation 18 Cls_Enabled Permission of closing operation PCS-9613S Differential Relay 4-6 Date: 2020-09-02 4 Control Functions 19 Opn/Cls_Enabled Permission of operation (Opn_Enabled OR Cls_Enabled) 20 Opn_Exec Opening operation 21 Cls_Exec Closing operation 22 Opn_Sel Opening selection 23 Cls_Sel Closing selection 24 DPS.Alm Alarm signal when DPS status is BAD or INT 25 Cmd_ManSel Selection command for manual control 26 Cmd_ManOpn Opening command for manual control 27 Cmd_ManCls Closing command for manual control 28 RSYN_ChkInprog Synchronism check is in progress 29 DPS_ON Single-bit DPS state indication of ON 30 DPS_OFF Single-bit DPS state indication of OFF 31 DPS_INT Single-bit DPS state indication of INT 32 DPS_BAD Single-bit DPS state indication of BAD 33 DPS_A_ON Phase A single-bit DPS state indication of ON 34 DPS_A_OFF Phase A single-bit DPS state indication of OFF 35 DPS_A_INT Phase A single-bit DPS state indication of INT 36 DPS_A_BAD Phase A single-bit DPS state indication of BAD 37 DPS_B_ON Phase B single-bit DPS state indication of ON 38 DPS_B_OFF Phase B single-bit DPS state indication of OFF 39 DPS_B_INT Phase B single-bit DPS state indication of INT 40 DPS_B_BAD Phase B single-bit DPS state indication of BAD 41 DPS_C_ON Phase C single-bit DPS state indication of ON 42 DPS_C_OFF Phase C single-bit DPS state indication of OFF 43 DPS_C_INT Phase C single-bit DPS state indication of INT 44 DPS_C_BAD Phase C single-bit DPS state indication of BAD 4 In above table, the prefix can be “CB” or “DS01”~“DS09”. 4.1.5 Logics The prefix CB** for circuit breaker and DS** for disconnector switch in the following diagrams are hidden since their logics (if valid) are similar. PCS-9613S Differential Relay 4-7 Date: 2020-09-02 4 Control Functions SIG DPS_A = OFF SIG DPS_B = OFF SIG DPS_C = OFF SIG DPS_A = ON SIG DPS_B = ON SIG DPS_C = ON SIG DPS_A = INT SIG DPS_B = INT SIG DPS_C = INT SIG DPS_A = BAD SIG DPS_B = BAD SIG DPS_C = BAD ≥1 DPS = OFF & DPS = ON ≥1 DPS = INT ≥1 4 DPS = BAD Figure 4.1-1 DPS synthesis logic SIG CSWI**.DPS = BAD SIG CSWI**.DPS = INT >=1 & [CSWI**.DPS.t_Alm] SET [CSWI**.DPS.t_Alm] Alm_DPS [CSWI**.DPS.En_Alm] Figure 4.1-2 DPS alarm logic SIG Remote command from SAS/NCC with "Interlocking" flag SIG Local command from device LCD with "InterlockChk" ≥1 CSWI** interlocking function activated ≥1 & SIG Contact triggered manual opening/closing operation EN [CSWI**.En_Opn_Blk] EN [CSWI**.En_Cls_Blk] ≥1 Figure 4.1-3 Interlocking logic PCS-9613S Differential Relay 4-8 Date: 2020-09-02 4 Control Functions SIG in_Manual_Sel = NUL & >=1 SIG in_Manual_Opn SIG in_Manual_Sel & SIG in_Manual_Opn & SIG Opn_Enabled Opn_Exec_Man SIG Control mode = Local SIG in_Manual_Sel = NUL & SIG in_Manual_Cls SIG in_Manual_Sel >=1 & SIG in_Manual_Cls 4 & SIG Cls_Enabled Cls_Exec_Man SIG Control mode = Local Figure 4.1-4 Manual control logic PCS-9613S Differential Relay 4-9 Date: 2020-09-02 4 Control Functions ≥1 EN [CB.En_CILO_Cls] SIG CB.Cls_Enabled SIG CB Control Mode = Remote SIG CB.Cmd_ManCls SIG CB closing cmd. from device local HMI & ≥1 ≥1 & & SIG CB closing cmd. from SCADA or Gateway SIG CB.25.RSYN_OK SIG CB.25.SynChk_Enabled SIG CB.25.DdChk_Enabled EN [DS**.En_CILO_Cls] SIG DS**.Cls_Enabled SIG DS** Control Mode = Remote SIG CB.Cmd_ManCls SIG DS** closing cmd. from device local HMI 0ms [CB.t_PW_Cls] 0ms [DS**.t_PW_Cls] CB.Cls_Exec ≥1 & 4 ≥1 & ≥1 & ≥1 DS**.Cls_Exec & SIG DS** closing cmd. from SCADA or Gateway Figure 4.1-5 Logic diagram of closing operation PCS-9613S Differential Relay 4-10 Date: 2020-09-02 4 Control Functions EN [CB.En_CILO_Opn] SIG CB.Opn_Enabled SIG CB Control Mode = Remot e SIG CB.Opn_Exec_Man SIG CB opening cmd. from device local HMI ≥1 & ≥1 & 0ms [CB.t_PW_Opn] CB.Opn_Exec ≥1 & SIG CB opening cmd. from SCADA or Gateway EN [DS**.En_CILO_Opn] SI G DS**.Opn_Enabled SI G DS** Control Mode = Remote SIG DS**.Opn_Exec_Man SIG DS** opening cmd. from device local HMI ≥1 4 & ≥1 & 0ms [DS**.t_PW_Opn] DS**.Opn_Exec ≥1 & SIG DS** opening cmd. from SCADA or Gateway Figure 4.1-6 Logic diagram of opening operation In above figures, CSWI** can be “Breaker” or “Switch 01”~“Switch 09”. 4.1.6 Settings Table 4.1-3 Settings of DPS function No. Setting Default Range Step Unit Description Delay Pick Up (DPU) time, i.e. 1 CB.DPS.t_DPU 500 0~60000 1 ms debounce time, for DPS of the circuit breaker 2 CB.DPS.En_Alm Disabled 3 CB.DPS.t_Alm 500 Disabled or Enabled 0~60000 - - 1 ms Logic setting for DPS alarm of the circuit breaker Operation time delay of DPS alarm of the circuit breaker Delay Pick Up (DPU) time, i.e. 4 DS**.DPS.t_DPU 500 0~60000 1 ms debounce time, for DPS of disconnector switch ** (**=01~09) 5 DS**.DPS.En_Alm Disabled Disabled Enabled or - PCS-9613S Differential Relay - Logic setting for DPS alarm of the circuit breaker of disconnector switch 4-11 Date: 2020-09-02 4 Control Functions No. Setting Default Range Step Unit Description ** (**=01~09) Operation time delay of DPS alarm of 6 DS**.DPS.t_Alm 500 0~60000 1 ms the circuit breaker of disconnector switch ** (**=01~09) Table 4.1-4 Settings of control function No. Setting Default Range Step Unit Description Pulse Width (PW), i.e. holding time, 1 CB.t_PW_Opn 500 0~60000 1 ms for opening output of the circuit breaker Pulse Width (PW), i.e. holding time, 2 CB.t_PW_Cls 500 0~60000 1 ms for closing output of the circuit breaker 4 Pulse Width (PW), i.e. holding time, 3 DS**.t_PW_Opn 500 0~60000 1 ms for direct opening output of disconnector switch ** (**=01~09) Pulse Width (PW), i.e. holding time, 4 DS**.t_PW_Cls 500 0~60000 1 ms for direct closing output of disconnector switch ** (**=01~09) Table 4.1-5 Settings of interlocking function No. 1 2 3 4 Setting CB.En_CILO_Opn CB.En_CILO_Cls DS**.En_CILO_Opn DS**.En_CILO_Cls Default Disabled Disabled Disabled Disabled Range Disabled Step or Enabled Disabled or Enabled Logic setting for interlocking logic - - control of closing output of the circuit Logic setting for interlocking logic - - control of opening output of the circuit breaker or Enabled Disabled Description breaker Enabled Disabled Unit Logic setting for interlocking logic - - control of direct closing output of disconnector switch ** (**=01~09) or Logic setting for interlocking logic - - control of direct opening output of disconnector switch ** (**=01~09) 4.2 Manual Closing Synchronism Check The purpose of synchronism check is to ensure two systems are synchronous before they are going to be connected. When two asynchronous systems are connected together, due to phase difference between the two systems, larger impact will be led to the system during closing. Thus, closing operation is applied with the synchronism check to avoid this situation and maintain the system stability. The synchronism check includes synchro-check and dead charge check. PCS-9613S Differential Relay 4-12 Date: 2020-09-02 4 Control Functions 4.2.1 Operation Theory 4.2.1.1 Synchro-check The comparative relationship between the reference side voltage and the synchronous side voltage for synchro-check is as follow. Furthermore, the measured three-phase voltages for synchro-check should not exceed the overvoltage threshold [25.U_OV] or lag the undervoltage threshold [25.U_UV]. U_Ref U_Syn 4 Figure 4.2-1 Relationship between reference and synchronous voltages This figure shows the characteristics of synchro-check element used for CB closing if both reference and synchronous sides are live. The element operates if the voltage difference, frequency difference, slip frequency difference and phase angle difference are all within their setting ranges. ⚫ The voltage difference between the reference side and the synchronous side is checked by the following equation [25.U_UV] ≤ U_Ref ≤ [25.U_OV] [25.U_UV] ≤ U_Syn ≤ [25.U_OV] |U_Ref - U_Syn| ≤ [25.U_Diff_Set] ⚫ The frequency difference between the reference side and the synchronization side is checked by the following equation [25.f_UF] ≤ f(U_Ref) ≤ [25.f_OF] [25.f_UF] ≤ f(U_Syn) ≤ [25.f_OF] |f(U_Ref) - f(U_Syn)| ≤ [25.f_Diff_Set] ⚫ The slip frequency variation is checked by the following equation df/dt ≤ [25.df/dt_Set] ⚫ The phase difference between the reference side voltage and the synchronous side voltage PCS-9613S Differential Relay 4-13 Date: 2020-09-02 4 Control Functions is checked by the following equation ∆δ ≤ [25.phi_Diff_Set] 4.2.1.2 Dead Charge Check The dead charge check mode checks either the reference side or the synchronous side voltage. Several dead charge check modes are supported in using the setting [25.Opt_Mode_DdChk]. The device compares the reference side and the synchronous side voltages at both ends of a circuit breaker with the settings [25.U_LvChk] and [25.U_DdChk]. When the voltage is higher than [25.U_LvChk], the corresponding side is regarded as live. When the voltage is lower than [25.U_DdChk], the corresponding side is regarded as dead. 4.2.1.3 Voltage Input Channel 4 The synchronism check function is suitable for several applications. According to different application scenarios, user needs to configure different voltage input channel. For both the reference side and the synchronous side, the voltage input channel may be single phase or three-phase. While configuring through the PCS-Studio software, user can configure three phase or single phase voltage channel for reference and synchronous sides inputs. In the meantime, the voltage switching logic can be adopted for the synchronism check input channel, please refer to the following section. For synchronism check voltage input channel configuration, please MAKE SURE that the voltage source to connect to the inputs "in_ref" and "in_syn" should be the same with that used in measurement function, such as BayMMXU and UMMXN. Otherwise, the alarm "25.Alm_Cfg_Ch" will be issued. 4.2.1.4 Enabling Logic If one of the following conditions is met, the synchro-check for CB closing is enabled. ⚫ [25.Opt_ValidMode] = Setting, [25.En_SynChk] = Enabled; ⚫ [25.Opt_ValidMode] = Config, “25.in_syn_chk” = 1. If one of the following conditions is met, the dead charge check for CB closing is enabled. ⚫ [25.Opt_ValidMode] = Setting, [25.En_DdChk] = Enabled; ⚫ [25.Opt_ValidMode] = Config, “25.in_vol_chk” = 1. If none of synchro-check and dead charge check is enabled, the synchronism check for CB closing is disabled. PCS-9613S Differential Relay 4-14 Date: 2020-09-02 4 Control Functions 4.2.2 Function Block Diagram 4 4.2.3 I/O Signals Table 4.2-1 Input/Output signals of manual closing synchronism check No. Input Signal Description 1 in_en Enabling function 2 In_blk Disabling function 3 in_ref_A Reference voltage channel (phase A or single phase) 4 in_ref_B Reference voltage channel (phase B) 5 in_ref_C Reference voltage channel (phase C) 6 in_syn_A Synchronization voltage channel (phase A or single phase) 7 in_syn_B Synchronization voltage channel (phase B) 8 in_syn_C Synchronization voltage channel (phase C) 9 in_25_Blk Signal to block synchronism check logic 10 in_Dd_Blk Signal to block dead charge logic 11 in_Lv_Blk Signal to block live check logic 12 in_SYN_Blk Signal to block synchro-check logic 13 in_25_Bypass Signal to temporarily bypass synchronism check logic 14 in_syn_chk Activate synchro-check (valid only if the setting [25.Opt_ValidMode] = Config) 15 in_vol_chk Activate dead charge check (valid only if the setting [25.Opt_ValidMode] = Config) No. Output Signal Description 1 25.RSYN Pointer to struct of synchronism check element 2 25.U_Ref_Sec Reference side voltage secondary value 3 25.U_Ref_Pri Reference side voltage primary value 4 25.f_Ref Reference side frequency 5 25.U_Syn_Sec Synchronous side voltage secondary value 6 25.U_Syn_Pri Synchronous side voltage primary value PCS-9613S Differential Relay 4-15 Date: 2020-09-02 4 Control Functions 4 7 25.f_Syn Synchronous side frequency 8 25.U_Diff_Sec Voltage difference secondary value 9 25.U_Diff_Pri Voltage difference primary value 10 25.phi_Diff Phase angle difference 11 25.f_Diff Frequency difference 12 25.df/dt Frequency rate-of-change 13 25.SynChk_OK Satisfaction of synchro-check logic 14 25.DdChk_OK Satisfaction of dead charge check logic 15 25.RSYN_OK Satisfaction of synchronism check logic, i.e. SynChk_OK or DdChk_OK 16 25.Alm_Cfg_Ch Channel configuration for reference or synchronization is not correct. 17 25.SynChk_Enabled Synchro-check is enabled 18 25.DdChk_Enabled Dead charge check is enabled 19 25.U_Diff_OK Voltage difference within setting range 20 25.f_Diff_OK Frequency difference within setting range 21 25.df/dt_OK Frequency variation difference within setting range 22 25.phi_Diff_OK Phase difference within setting range 23 25.RefDd The reference side is dead. 24 25.RefLv The reference side is live. 25 25.SynDd The synchronous side is dead. 26 25.SynLv The synchronous side is live. 4.2.4 Logics EN [25.Opt_ValidMode] = Setting EN [25.En_SynChk] EN [25.Opt_ValidMode] = Config SIG 25.in_syn_chk EN [25.Opt_ValidMode] = Setting EN [25.En_DdChk] EN [25.Opt_ValidMode] = Config SIG 25.in_vol_chk SIG 25.SynChk_Enabled SIG 25.DdChk_Enabled & ≥1 25.SynChk_Enabled & & ≥1 25.DdChk_Enabled & & Synchronism check for CB closing is disabled Figure 4.2-2 Synchronism check logic PCS-9613S Differential Relay 4-16 Date: 2020-09-02 4 Control Functions SIG in_25_Bypass SIG in_25_Blk SIG in_SYN_Blk SET df/dt ≤ [25.df/dt_Set] SET [25.En_df/dt_Chk] = Disa bled SET ΔU ≤ [25.U_Diff_Set] SET Δf ≤ [25.f_Diff_Set] SET [25.En_f_Diff_Chk] = Disa bled SET Δδ ≤ [25.phi_Diff_Set] SET U_Ref ≤ [25.U_UV] ≥1 ≥1 SET U_Ref ≥ [25.U_OV] SET U_Syn ≤ [25.U_UV] SET U_Syn ≥ [25.U_OV] SET f_Ref ≤ [25.f_UF] SET f_Ref ≥ [25.f_OF] SET f_Syn ≤ [25.f_UF] SET f_Syn ≥ [25.f_OF] SIG & ≥1 25.SynChk_OK ≥1 ≥1 4 Cmd without synchro-check SIG 25.SynChk_OK SET [25.Opt_Vali dMode] = Setting EN [25.En_SynChk] SET [25.Opt_Vali dMode] = Config SIG in_syn_chk SIG Cmd with synchro-check ≥1 SynChk Success & & ≥1 & Figure 4.2-3 Synchro-check logic SIG Ua_Ref < [25.U_DdChk] SIG Ub_Ref < [25.U_DdChk] SIG Uc_Ref < [25.U_DdChk] SIG U_Ref is three-phase voltage SIG U_Ref < [25.U_DdChk] SIG U_Ref is single-phase voltage SIG Ua_Syn < [25.U_DdChk] SIG Ub_Syn < [25.U_DdChk] SIG Uc_Syn < [25.U_DdChk] SIG U_Syn is three-phase voltage SIG U_Syn < [25.U_DdChk] SIG U_Syn is single-phase voltage & >=1 25.RefDd & & >=1 25.SynDd & PCS-9613S Differential Relay 4-17 Date: 2020-09-02 4 Control Functions SIG Ua_Ref > [25.U_LvChk] SIG Ub_Ref > [25.U_LvChk] SIG Uc_Ref > [25.U_LvChk] SIG U_Ref is three-phase voltage SIG U_Ref > [25.U_LvChk] SIG U_Ref is single-phase voltage SIG Ua_Syn > [25.U_LvChk] SIG Ub_Syn > [25.U_LvChk] SIG Uc_Syn > [25.U_LvChk] SIG U_Syn is three-phase voltage SIG U_Syn > [25.U_LvChk] SIG U_Syn is single-phase voltage SIG in_25_Bypass SIG in_25_Blk SIG in_Dd_Blk SIG in_Lv_Blk SET [25.Opt_Mode_DdChk] SIG 25.RefDd SIG 25.RefLv SIG 25.SynDd SIG 25.SynLv SIG Cmd. without dead charge check SIG 25.DdChk_Ok SIG 25.DdChk_Enabled SIG Cmd. with dead charge check & >=1 25.RefLv & & >=1 4 25.SynLv & >=1 25.DdChk_OK >=1 Dead check crite ria sel ection & >=1 & DdChk Success Figure 4.2-4 Dead charge check logic 4.2.5 Settings Table 4.2-2 Settings of synchronism check No. 1 Setting 25.Opt_ValidMode Default Setting Range Setting or Config Step Unit - - Description Selection of decision mode for synchronism PCS-9613S Differential Relay 4-18 Date: 2020-09-02 4 Control Functions No. Setting Default Range Step Unit Description check Logic setting synchro-check 2 25.En_SynChk Enabled Disabled or Enabled - - only if the for (valid setting [25.Opt_ValidMode] = Setting) Logic setting for dead charge check (valid 3 25.En_DdChk Enabled Disabled or Enabled - - only if the setting [25.Opt_ValidMode] = Setting) Percentage threshold 4 25.U_UV 80.00 0~100 0.01 % of under voltage for 4 CB closing blocking Percentage threshold 5 25.U_OV 170.00 100~170 0.01 % of over voltage for CB closing blocking Percentage threshold 6 25.f_UF 45.000 45~65 0.001 Hz of under frequency for CB closing blocking Percentage threshold 7 25.f_OF 65.000 45~65 0.001 Hz of over frequency for CB closing blocking 8 25.Opt_U_SynChk Ua Ua, Ub, Uc, Uab, Ubc, Uca - - Selection of voltage for synchronism check Threshold of voltage 9 25.U_Diff_Set 10.00 0~100 0.01 V difference for synchronism check Logic 10 25.En_f_Diff_Chk Enabled Disabled or Enabled - - setting frequency for difference check 11 25.f_Diff_Set 0.50 0~2 0.01 Hz Threshold of frequency difference for synchronism check Logic 12 25.En_df/dt_Chk Enabled Disabled or Enabled - - setting frequency for variation difference check Threshold 13 25.df/dt_Set 1.00 0~2 0.01 Hz/s of frequency variation for synchronism check. Threshold of phase 14 25.phi_Diff_Set 15.00 0~180 0.01 ° difference for synchronism check PCS-9613S Differential Relay 4-19 Date: 2020-09-02 4 Control Functions No. Setting Default Range Step Unit Description Compensation angle 15 25.phi_Comp 0.00 0~360 0.01 ° of phase difference for synchronism check SynDdRefDd SynLvRefDd SynDdRefLv 16 25.Opt_Mode_DdChk AnySideDd RefDd - - Selection of dead charge check mode SynDd SynLvRefDd/SynDdRefLv AnySideDd 4 17 25.U_DdChk 17.32 0~100 0.01 V 18 25.U_LvChk 34.64 0~100 0.01 V 19 25.t_Reset 5 0~60 1 s Threshold for voltage dead check Threshold for voltage live check Threshold of duration for synchro-check Circuit breaker closing time. It is the time 20 25.t_Close_CB 20 0~2000 1 from receiving closing ms command pulse till the CB is completely closed. ⚫ 25.Opt_Mode_DdChk No. Setting Value Dead charge check mode 1 SynDdRefDd Dead check for both the reference and the synchronization sides 2 SynLvRefDd Live check for synchronization side and dead check for reference side 3 SynDdRefLv Dead check for synchronization side and live check for reference side 4 RefDd Dead check for reference side 5 SynDd Dead check for synchronization side 6 SynLvRefDd/SynDdRefLv Option 2 or 3 7 AnySideDd Option 1, 2 or 3 PCS-9613S Differential Relay 4-20 Date: 2020-09-02 5 Measurement 5 Measurement Table of Contents 5.1 Primary Values ................................................................................................. 5-1 5.1.1 General Values ..................................................................................................................... 5-1 5.1.2 Angle Values ......................................................................................................................... 5-1 5.1.3 Sequence Components Values ............................................................................................ 5-2 5.1.4 Power Values........................................................................................................................ 5-2 5.1.5 Harmonics ............................................................................................................................ 5-3 5.2 Secondary Values ............................................................................................ 5-3 5.2.1 General Values ..................................................................................................................... 5-3 5.2.2 Angle Values ......................................................................................................................... 5-4 5.2.3 Sequence Components Values ............................................................................................ 5-4 5.2.4 Power Values........................................................................................................................ 5-4 5.2.5 Harmonics ............................................................................................................................ 5-5 5.3 Calculation Values ........................................................................................... 5-5 5.3.1 Synchro-check...................................................................................................................... 5-6 5.3.2 Differential Current ............................................................................................................... 5-6 5.3.3 Thermal Overload ................................................................................................................. 5-7 5.4 Energy Metering............................................................................................... 5-8 5.5 Power Quality ................................................................................................... 5-8 PCS-9613S Differential Relay 5-a Date: 2020-09-02 5 5 Measurement 5 PCS-9613S Differential Relay 5-b Date: 2020-09-02 5 Measurement 5.1 Primary Values Access path: MainMenu “Measurements” “Primary Values” 5.1.1 General Values No. Symbol Definition Unit 1 Ia_Pri Phase-A current A 2 Ib_Pri Phase-B current A 3 Ic_Pri Phase-C current A 4 Ua_Pri Phase-A protection voltage kV 5 Ub_Pri Phase-B protection voltage kV 6 Uc_Pri Phase-C protection voltage kV 7 Uab_Pri Phase-AB protection voltage kV 8 Ubc_Pri Phase-BC protection voltage kV 9 Uca_Pri Phase-CA protection voltage kV 10 f Frequency of protection voltage Hz 11 Neu.I_Pri External measured residual current A 12 Syn.U_Pri Voltage for synchronism check kV 5.1.2 Angle Values No. Symbol Definition Unit 1 Ang (Ua-Ia) Phase angle between phase-A voltage and phase-A current ° 2 Ang (Ub-Ib) Phase angle between phase-B voltage and phase-B current ° 3 Ang (Uc-Ic) Phase angle between phase-C voltage and phase-C current ° 4 Ang (Ua-Ub) Phase angle between phase-A voltage and phase-B voltage ° 5 Ang (Ub-Uc) Phase angle between phase-B voltage and phase-C voltage ° 6 Ang (Uc-Ua) Phase angle between phase-C voltage and phase-A voltage ° 7 Ang (Ia-Ib) Phase angle between phase-A current and phase-B current ° 8 Ang (Ib-Ic) Phase angle between phase-B current and phase-C current ° 9 Ang (Ic-Ia) Phase angle between phase-C current and phase-A current ° Phase angle between phase-A voltage and the referenced angle, 10 Ang (Ua) currently, the angle of the positive voltage is used as the referenced angle (if voltage is not connected, the angle of the positive current is used as ° the referenced angle). 11 Ang (Ub) Phase angle between phase-B voltage and the referenced angle ° 12 Ang (Uc) Phase angle between phase-C voltage and the referenced angle ° 13 Ang (Ia) Phase angle between phase-A current and the referenced angle ° 14 Ang (Ib) Phase angle between phase-B current and the referenced angle ° PCS-9613S Differential Relay 5-1 Date: 2020-09-02 5 5 Measurement No. Symbol 15 Ang (Ic) 16 Neu.Ang (I) 17 Syn.Ang (U) Definition Unit Phase angle between phase-C current and the referenced angle Phase angle between the external measured residual current and the referenced angle Phase angle between the synchronism check used voltage and the referenced angle ° ° ° 5.1.3 Sequence Components Values No. 5 Symbol Definition Unit 1 I1_Pri The positive-sequence current A 2 I2_Pri The negative-sequence current A 3 3I0_Pri Residual current A 4 U1_Pri The positive-sequence voltage kV 5 U2_Pri The negative-sequence voltage kV 6 3U0_Pri The calculated residual voltage kV 5.1.4 Power Values No. Sign 1 Pa_Pri 2 Pb_Pri 3 Pc_Pri 4 Qa_Pri 5 Qb_Pri 6 Qc_Pri 7 Sa_Pri 8 Sb_Pri 9 Sc_Pri 10 Description The primary values of three-phases active powers. Unit MW The primary values of three-phases reactive powers. MVAr The primary values of three-phases apparent powers. MVA P_Pri The primary value of active power. MW 11 Q_Pri The primary value of reactive power. MVAr 12 S_Pri The primary value of apparent power. MVA 13 Cosa 14 Cosb 15 Cosc 16 Cos Three-phases power factors. Power factor PCS-9613S Differential Relay 5-2 Date: 2020-09-02 5 Measurement 5.1.5 Harmonics No. Sign Description Unit 1 U_Hm01_Pri kV 2 U_Hm02_Pri kV 3 U_Hm03_Pri kV 4 U_Hm04_Pri kV 5 U_Hm05_Pri kV 6 U_Hm06_Pri kV 7 U_Hm07_Pri kV 8 U_Hm08_Pri 9 U_Hm09_Pri kV 10 U_Hm10_Pri kV 11 U_Hm11_Pri kV 12 U_Hm12_Pri kV 13 U_Hm13_Pri kV 14 U_Hm14_Pri kV 15 U_Hm15_Pri kV The primary value of the 1st~15th voltage harmonic kV 5.2 Secondary Values Access path: MainMenu “Measurements” “Secondary Values” 5.2.1 General Values No. Symbol Definition Unit 1 Ia_Sec Phase-A current (summation current for double circuit breakers mode) A 2 Ib_Sec Phase-B current (summation current for double circuit breakers mode) A 3 Ic_Sec Phase-C current (summation current for double circuit breakers mode) A 4 Ua_Sec Phase-A protection voltage V 5 Ub_Sec Phase-B protection voltage V 6 Uc_Sec Phase-C protection voltage V 7 Uab_Sec Phase-AB protection voltage V 8 Ubc_Sec Phase-BC protection voltage V 9 Uca_Sec Phase-CA protection voltage V 10 f Frequency of protection voltage Hz 11 Neu.I_Sec External measured residual current A 12 Syn.U_Sec Voltage for synchronism check V PCS-9613S Differential Relay 5-3 Date: 2020-09-02 5 5 Measurement 5.2.2 Angle Values No. Symbol Definition Unit 1 Ang (Ua-Ia) Phase angle between phase-A voltage and phase-A current ° 2 Ang (Ub-Ib) Phase angle between phase-B voltage and phase-B current ° 3 Ang (Uc-Ic) Phase angle between phase-C voltage and phase-C current ° 4 Ang (Ua-Ub) Phase angle between phase-A voltage and phase-B voltage ° 5 Ang (Ub-Uc) Phase angle between phase-B voltage and phase-C voltage ° 6 Ang (Uc-Ua) Phase angle between phase-C voltage and phase-A voltage ° 7 Ang (Ia-Ib) Phase angle between phase-A current and phase-B current ° 8 Ang (Ib-Ic) Phase angle between phase-B current and phase-C current ° 9 Ang (Ic-Ia) Phase angle between phase-C current and phase-A current ° Phase angle between phase-A voltage and the referenced angle, 10 Ang (Ua) currently, the angle of the positive voltage is used as the referenced angle (if voltage is not connected, the angle of the positive current is used as ° the referenced angle). 5 11 Ang (Ub) Phase angle between phase-B voltage and the referenced angle ° 12 Ang (Uc) Phase angle between phase-C voltage and the referenced angle ° 13 Ang (Ia) Phase angle between phase-A current and the referenced angle ° 14 Ang (Ib) Phase angle between phase-B current and the referenced angle ° 15 Ang (Ic) Phase angle between phase-C current and the referenced angle ° 16 Neu.Ang (I) 17 Syn.Ang (U) Phase angle between the external measured residual current and the referenced angle Phase angle between the synchronism check used voltage and the referenced angle ° ° 5.2.3 Sequence Components Values No. Symbol Definition Unit 1 I1_Sec The positive-sequence current A 2 I2_Sec The negative-sequence current A 3 3I0_Sec Residual current A 4 U1_Sec The positive-sequence voltage V 5 U2_Sec The negative-sequence voltage V 6 3U0_Sec The calculated residual voltage V 5.2.4 Power Values No. 1 Sign Pa_Sec Description The secondary values of three-phases active powers. Unit W PCS-9613S Differential Relay 5-4 Date: 2020-09-02 5 Measurement No. Sign 2 Pb_Sec 3 Pc_Sec 4 Qa_Sec 5 Qb_Sec 6 Qc_Sec 7 Sa_Sec 8 Sb_Sec 9 Sc_Sec 10 Description Unit The secondary values of three-phases reactive powers. Var The secondary values of three-phases apparent powers. VA P_Sec The primary value of active power. W 11 Q_Sec The primary value of reactive power. Var 12 S_Sec The primary value of apparent power. VA 13 Cosa 14 Cosb 15 Cosc 16 Cos Three-phases power factors. 5 Power factor 5.2.5 Harmonics No. Sign Description Unit 1 U_Hm01_Sec V 2 U_Hm02_Sec V 3 U_Hm03_Sec V 4 U_Hm04_Sec V 5 U_Hm05_Sec V 6 U_Hm06_Sec V 7 U_Hm07_Sec V 8 U_Hm08_Sec 9 U_Hm09_Sec V 10 U_Hm10_Sec V 11 U_Hm11_Sec V 12 U_Hm12_Sec V 13 U_Hm13_Sec V 14 U_Hm14_Sec V 15 U_Hm15_Sec V The secondary value of the 1st~15th voltage harmonic V 5.3 Calculation Values Access path: MainMenu “Measurements” “Function Values” PCS-9613S Differential Relay 5-5 Date: 2020-09-02 5 Measurement 5.3.1 Synchro-check No. 5 Sign Description Unit 1 25.U_Ref_Sec Secondary voltage of reference side V 2 25.U_Ref_Pri Primary voltage of reference side kV 3 25.f_Ref Frequency of reference side Hz 4 25.U_Syn_Sec Secondary voltage of synchronization side V 5 25.U_Syn_Pri Primary voltage of synchronization side kV 6 25.f_Syn Synchronization side frequency Hz 7 25.U_Diff_Sec Secondary voltage difference for CB synchronism check V 8 25.U_Diff_Pri Primary voltage difference for CB synchronism check kV 9 25.phi_Diff Phase angle difference for CB synchronism check deg 10 25.f_Diff Frequency difference for CB synchronism check Hz 11 25.df/dt Frequency variation difference for CB synchronism check 12 25.RSYN_OK Synchronism check is passed. 13 25.SynChk_OK Synchro-check is passed. 14 25.DdChk_OK Dead charge check is passed. 15 25.U_Diff_OK Voltage difference criteria is satisfied. 16 25.f_Diff_OK Frequency difference criteria is satisfied. 17 25.dfdt_OK Voltage variation difference criteria is satisfied. 18 25.phi_Diff_OK Phase difference criteria is satisfied. 19 25.RefDd Dead check of reference side is passed. 20 25.RefLv Live check of reference side is passed. 21 25.SynDd Dead check of synchronization side is passed. 22 25.SynLv Live check of synchronization side is passed. Hz/s 5.3.2 Differential Current No. Sign 1 87L.FO1.Ia_Loc Phase-A current of optical fibre channel 1 at the local end V 2 87L.FO1.Ib_Loc Phase-B current of optical fibre channel 1 at the local end kV 3 87L.FO1.Ic_Loc Phase-C current of optical fibre channel 1 at the local end Hz 4 87L.FO1.Ia_Rmt Phase-A current of optical fibre channel 1 from the opposite end V 5 87L.FO1.Ib_Rmt Phase-B current of optical fibre channel 1 from the opposite end kV 6 87L.FO1.Ic_Rmt Phase-C current of optical fibre channel 1 from the opposite end Hz 87L.FO1.Ang Phase angle between local phase-A current and remote phase-A current (Ia_Loc-Ia_Rmt) of optical fibre channel 1 87L.FO1.Ang Phase angle between local phase-B current and remote phase-B current (Ib_Loc-Ib_Rmt) of optical fibre channel 1 7 8 Description Unit V kV PCS-9613S Differential Relay 5-6 Date: 2020-09-02 5 Measurement No. Sign Description Unit 87L.FO1.Ang Phase angle between local phase-C current and remote phase-C current (Ic_Loc-Ic_Rmt) of optical fibre channel x 10 87L.FO1.Ida Phase-A differential current of optical fibre channel 1 Hz 11 87L.FO1.Idb Phase-B differential current of optical fibre channel 1 Hz/s 12 87L.FO1.Idc Phase-C differential current of optical fibre channel 1 13 87L.FO1.Ira Phase-A restrained current of optical fibre channel 1 14 87L.FO1.Irb Phase-B restrained current of optical fibre channel 1 15 87L.FO1.Irc Phase-C restrained current of optical fibre channel 1 16 87L.FO2.Ia_Loc Phase-A current of optical fibre channel 2 at the local end 17 87L.FO2.Ib_Loc Phase-B current of optical fibre channel 2 at the local end 18 87L.FO2.Ic_Loc Phase-C current of optical fibre channel 2 at the local end 19 87L.FO2.Ia_Rmt Phase-A current of optical fibre channel 2 from the opposite end 20 87L.FO2.Ib_Rmt Phase-B current of optical fibre channel 2 from the opposite end 21 87L.FO2.Ic_Rmt Phase-C current of optical fibre channel 2 from the opposite end 87L.FO2.Ang Phase angle between local phase-A current and remote phase-A current (Ia_Loc-Ia_Rmt) of optical fibre channel 2 87L.FO2.Ang Phase angle between local phase-B current and remote phase-B current (Ib_Loc-Ib_Rmt) of optical fibre channel 2 87L.FO2.Ang Phase angle between local phase-C current and remote phase-C current (Ic_Loc-Ic_Rmt) of optical fibre channel 2 25 87L.FO2.Ida Phase-A differential current of optical fibre channel 2 26 87L.FO2.Idb Phase-B differential current of optical fibre channel 2 27 87L.FO2.Idc Phase-C differential current of optical fibre channel 2 28 87L.FO2.Ira Phase-A restrained current of optical fibre channel 2 29 87L.FO2.Irb Phase-B restrained current of optical fibre channel 2 30 87L.FO2.Irc Phase-C restrained current of optical fibre channel 2 9 22 23 24 Deg 5 5.3.3 Thermal Overload No. Sign Description 1 49.Accu_A Phase-A thermal state of thermal overload protection 2 49.Accu_B Phase-B thermal state of thermal overload protection 3 49.Accu_C Phase-C thermal state of thermal overload protection 4 49.T_Diff_A 5 49.T_Diff_B 6 49.T_Diff_C The calculated temperature difference of phase-A between the equipment and the oil. The calculated temperature difference of phase-B between the Unit ℃ ℃ equipment and the oil. The calculated temperature difference of phase-C between the PCS-9613S Differential Relay ℃ 5-7 Date: 2020-09-02 5 Measurement No. Sign Description Unit equipment and the oil. 5.4 Energy Metering Access path: MainMenu “Measurements” “Energy Metering” No. Symbol Definition Unit 1 MMTR.EA_Accu_Fwd Positive active energy kWh 2 MMTR.EA_Accu_Rev Negative active energy kWh 3 MMTR.ER_Accu_Fwd Positive reactive energy kVarh 4 MMTR.ER_Accu_Rev Negative reactive energy kVarh 5.5 Power Quality Access path: MainMenu “Measurements” “Power Quality” No. Symbol 5 Definition Unit 1 Ua_Devn Deviation of phase A voltage = U a 3 − U nn U nn % 2 Ub_Devn Deviation of phase B voltage = U b 3 − U nn U nn % 3 Uc_Devn Deviation of phase C voltage = U c 3 − U nn U nn % 4 f_Devn Deviation of frequency = f_meas - fn Hz 5 UnbalRate_U2 Unbalance rate of negative-sequence voltage = U2/U1 % 6 UnbalRate_3U0 Unbalance rate of zero-sequence voltage (calculated) = 3U0/U1 % Total Harmonic Distortion (THD) of phase A voltage 15 7 THD_Ua THD = U 2 % Hm _ i i=2 U Hm _1 Total Harmonic Distortion (THD) of phase B voltage 15 8 THD_Ub THD = 9 THD_Uc U i=2 2 % Hm _ i U Hm _1 Total Harmonic Distortion (THD) of phase C voltage % PCS-9613S Differential Relay 5-8 Date: 2020-09-02 5 Measurement No. Symbol Definition Unit 15 THD = 10 UnbalRate_I2 11 UnbalRate_3I0 U i=2 2 Hm _ i U Hm _1 Unbalance rate of negative-sequence current = I2/I1 Unbalance rate of zero-sequence current (calculated) = 3I0/I1 % % 5 PCS-9613S Differential Relay 5-9 Date: 2020-09-02 5 Measurement 5 PCS-9613S Differential Relay 5-10 Date: 2020-09-02 6 Supervision 6 Supervision Table of Contents 6.1 Overview........................................................................................................... 6-1 6.2 Device Hardware Supervision ........................................................................ 6-1 6.2.1 Hardware Resource Consumption Supervision ................................................................... 6-2 6.2.2 Hardware Status Supervision............................................................................................... 6-2 6.2.3 Hardware Configuration Supervision ................................................................................... 6-3 6.2.4 Device Firmware Supervision .............................................................................................. 6-3 6.2.5 CPU Process and Module Supervision ................................................................................ 6-3 6.3 Analog Input Supervision ............................................................................... 6-3 6.4 Secondary Circuit Supervision....................................................................... 6-4 6.5 Binary Input Supervision ................................................................................ 6-5 6.5.1 Debounce Time .................................................................................................................... 6-5 6.5.2 Jitter Processing ................................................................................................................... 6-7 6.6 Tripping Counter Statistics ............................................................................. 6-9 6.7 Supervision Alarms and Handling Suggestion ............................................. 6-9 List of Figures Figure 6.4-1 Principle of the TCS function with two binary inputs ........................................ 6-4 Figure 6.5-1 Sequence chart of debounce technique ............................................................. 6-5 Figure 6.5-2 Debounce time configuration page...................................................................... 6-6 Figure 5.5-3 Sequence chart of jitter processing..................................................................... 6-8 List of Tables Table 6.7-1 Alarm description..................................................................................................... 6-10 Table 6.7-2 Alarm handling suggestion .................................................................................... 6-17 PCS-9613S Differential Relay 6-a Date: 2020-09-02 6 6 Supervision 6 PCS-9613S Differential Relay 6-b Date: 2020-09-02 6 Supervision 6.1 Overview Protection system is in quiescent state under normal conditions, and it is required to respond promptly for faults occurred on power system. When the device is in energizing process before the LED “HEALTHY” is on, the device needs to be checked to ensure no abnormality. Therefore, the automatic supervision function, which checks the health of the protection system when startup and during normal operation, plays an important role. The numerical relay based on the microprocessor operations is suitable for implementing this automatic supervision function of the protection system. In case a defect is detected during initialization when DC power supply is provided to the device, the device will be blocked with indication and alarm of relay out of service. It is suggested a trial recovery of the device by re-energization. Please contact supplier if the device is still failure. When a failure is detected by the automatic supervision, it is followed by a LCD message, LED indication and alarm contact outputs. The failure alarm is also recorded in event recording report and can be printed if required. 6.2 Device Hardware Supervision All hardware has real-time monitoring functions, such as CPU module monitoring, communication interface status monitoring, power supply status monitoring. The monitoring function of CPU module also includes processor self-check, memory self-check and so on. The processor self-check is checked by designing execution instructions and data operations. Check whether the processor can execute all instructions correctly, and whether it can correctly calculate complex data operations to determine whether it works normally. For peripherals, it can monitor the status of the interface module, check the input and output data, send the communication interface and receive self-loop detection. Memory self-check is used to detect unexpected memory errors in the running process. It can effectively prevent program logic abnormality caused by memory errors. The status monitoring of communication interface also includes Ethernet communication interface monitoring and differential channel communication interface monitoring. By accessing the status register of the communication interface, the state of the corresponding interface is obtained, such as the state of connection, the number of sending frames, the number of frames received, and the number of wrong frames. According to the statistics of the acquired interface state, it is detected whether the interface work is abnormal. The hardware supervision also includes the power supply status monitoring. The voltage monitoring chip is used by all the power supplies. The reset voltage threshold is pre-set to the reset monitoring circuit. When the power supply is abnormal, the voltage monitoring chip will output the reset signal to control CPU to be in the reset state and avoid the wrong operation. PCS-9613S Differential Relay 6-1 Date: 2020-09-02 6 6 Supervision 6.2.1 Hardware Resource Consumption Supervision 1. Logic component total execution time monitoring In the process of operation, the safety allowance should always be kept and no overload phenomenon is allowed. When the user configures logic components with PCS-Studio, the PCS-Studio automatically calculates the time required for the theoretical execution of the configured components. When the security limit is exceeded, the PCS-Studio will indicate that the configuration error is not allowed to download the current configuration to the device. 2. Module data exchange monitoring During the operation of the device, there is a lot of data exchange between modules. The number of data exchanges is related to the number of logical components configured by the user. When the configuration is too large to cause the number of data exchange to exceed the upper limit supported by the device, the PCS-Studio prompts the configuration error. 3. Configuration file size monitoring The initialization of the device depends on the configuration files of each module. The user configured logical components will eventually be embodied in the configuration file, limited to the hardware memory space. When the configuration file size is more than the upper limit, the PCS-Studio prompts the configuration error. 6.2.2 Hardware Status Supervision 6 1. Memory ECC and parity functions. The DDR3 memory chip has the function of ECC (Error Checking and Correcting) to eliminate unexpected changes in memory caused by electromagnetic interference. The chip memory has parity function. When an error occurs, the system can detect anomalies immediately, and eliminate the logic abnormity caused by memory errors. 2. Memory error monitoring in code area and constant data area In addition to the above hardware memory reliability measures, the device software is also constantly checking the memory during operation, including code, constant data, and so on. Once the error detection, the system will automatically restart the restore operation. If they detect the error immediately after the restart, it may be the result of a permanent fault locking device hardware, only at the moment and not restart. 3. Binary output relay drive monitoring The reliability of the device is largely determined by the reliability of the export drive. By reading the driving state of the binary output relay, the alarm signal will be generated and the device is immediately blocked to prevent the relay from mal-operation when the device is not given a tripping order and the binary output relay driver is detected in the effective state. 4. CPU temperature monitoring The CPU chip needs to be able to ensure long-term stability under the permissible working temperature of the specification. Therefore, it is necessary to monitor the working temperature PCS-9613S Differential Relay 6-2 Date: 2020-09-02 6 Supervision monitored by CPU. 6.2.3 Hardware Configuration Supervision The device is blocked when the actual hardware configuration is not consistent with the hardware configuration file. Compared with pre-configured modules, this device will be blocked if more module is inserted, fewer module is inserted, and wrong modules is inserted. 6.2.4 Device Firmware Supervision 1. Each hardware module configuration check code needs to be consistent with CPU module. The device CPU module stores the configuration check codes of other modules. In initialization procedure, it checks whether the configuration check code of each module is consistent with the stored code in CPU module, and if it is not consistent, this device is blocked. The hardware modules and process interface versions need to be consistent with the CPU module. 2. If the system is incompatible with the upgrade, it will upgrade the internal interface version. At this moment, each hardware module and process will be upgraded synchronously, otherwise the version of the interface will be inconsistent. 3. Configuration text is correct. The configuration text formed by the device calibration visualization project includes checking whether the check code is wrong or not. 4. Whether any setting is over the range, whether it needs to confirm the settings. If the setting exceeds the configuration range, the device is blocked; if some settings are added, it is necessary to confirm the new values through the LCD. 6.2.5 CPU Process and Module Supervision 1. Monitor the heartbeat of the module. In the operation procedure, the CPU module sends a time synchronization command to other module, each module repeats heartbeat message to the CPU module, if it does not respond or the heartbeat is abnormal, then this device is blocked. 2. Check whether the settings of other modules are consistent with the CPU module. The actual values of all the settings in the CPU module are initialized to send to the corresponding slave modules. In the process of operation, the setting values stored in the CPU module and the setting values of other modules will be checked one by one. If they are not consistent, this device will issue the alarm signal "Fail_Settings". 6.3 Analog Input Supervision The sampling circuit of this device is designed as dual-design scheme. Each analog sampling PCS-9613S Differential Relay 6-3 Date: 2020-09-02 6 6 Supervision channel is sampled by two groups of ADC. The sampling data is self checking and inter checking in real time. If any sampling circuit is abnormal, the device reports the alarm signal “Alm_Sample”, and the protection function related to the sampling channel is disabled at the same time. When the sampling circuit returns to normal state, the related protection is not blocked after 10s. 6.4 Secondary Circuit Supervision The secondary circuit supervision function includes current transformer supervision (CTS), voltage transformer supervision (VTS) and tripping/closing circuit supervision. ⚫ CTS function The purpose of the CTS function is to detect whether the current transformer circuit is failed. In some cases, if the CT is failed (broken-conductor, short-circuit), related protective element should be blocked for preventing this device from mal-operation. See further details about the CTS function, please refer Chapter 3. ⚫ VTS function The purpose of the VTS function is to detect whether the VT analog input is normal. Because some function, such as synchronism check, will be influenced by a voltage input failure. 6 The VT circuit failure can be caused by many reasons, such as fuse blown due to short-circuit fault, poor contact of VT circuit, VT maintenance and so on. The device can detect the failure, and then issue an alarm signal and block relevant function. See further details about the VTS function, please refer to Chapter 3. ⚫ Tripping circuit supervision function The tripping circuit supervision function can be realized by program the logic function of this device through the PCS-Studio according to the practical application experience of the user. In this manual, a scheme which uses two independent binary inputs to supervise the tripping circuit is recommended. The following figure show the recommended scheme for tripping circuit supervision and the logic diagram of the TCS function. DC+ DC- 52a BTJ TC 52b Protection Device [BI_01] [BI_02] Circuit Breaker & 600ms [Alm_TCS] Figure 6.4-1 Principle of the TCS function with two binary inputs PCS-9613S Differential Relay 6-4 Date: 2020-09-02 6 Supervision Where: “BTJ” is the protection tripping output contact; “TC” is the tripping coil of the circuit breaker; [BI_01] is the binary input which is parallel connected with “BTJ”; [BI_02] is the binary input which is serial connected with the “52b” contact. 6.5 Binary Input Supervision 6.5.1 Debounce Time The well-designed debounce technique is adopted in this device, and the state change of binary input within “Debounce time” will be ignored. As shown in Figure 6.5-1. Binary input state SOE report timestamps SOE report timestamps Validated binary input state changes 1 Validated binary input state changes 6 0 Debounce time of delayed pickup Debounce time of delayed dropout Time Figure 6.5-1 Sequence chart of debounce technique All binary inputs should setup necessary debounce time to prevent the device from undesired operation due to transient interference or mixed connection of AC system and DC system. When the duration of binary input is less than the debounce time, the state of the binary input will be ignored. When the duration of binary input is greater than the debounce time, the state of the binary input will be validated and wrote into SOE. In order to meet flexible configurable requirement for different project field, all binary inputs provided by the device are configurable. Through the configuration tool, this device provides two parameters to setup debounce time of delayed pickup and dropout based on specific binary signal. PCS-9613S Differential Relay 6-5 Date: 2020-09-02 6 Supervision Figure 6.5-2 Debounce time configuration page The configurable binary signals can be classified as follows: 1. Type 1 This type of binary inputs includes enable/disable of protection functions, AR mode selection, “BI_RstTarg”, “BI_Maintenance”, disconnector position, settings group switch, open and close command of circuit breaker and disconnector, enable/disable of auxiliary functions (for example, manually trigger recording). They are on the premise of reliability, and the debounce time of delayed pickup and delayed dropout is recommended to set as 100ms at least. 6 2. Type 2 This type of binary inputs include breaker failure “CSWIxx.Cmd_LocCtrl”, “CSWIxx.Cmd_RmtCtrl” and so on. initiating binary inputs, Debounce time BI Input Signal.X1 t1 t2 & Time delay Output SIG Operation condition ⚫ Time delay is equal to 0 The debounce time of delayed pickup and delayed dropout is recommended to set as 15ms, in order to prevent binary signals from mal-operation due to mixed connection of AC system and DC system. ⚫ Time delay is not equal to 0 The debounce time of delayed pickup and delayed dropout is recommended to set as (-t1+ t2+Time delay)≥15ms, in order to prevent binary signals from mal-operation due to mixed connection of AC system and DC system. Where, “t1” is the debounce time of delayed pickup, and “t2” is the debounce time of delayed dropout. 3. Type 3 PCS-9613S Differential Relay 6-6 Date: 2020-09-02 6 Supervision This type of binary inputs is usually used as auxiliary input condition, and the debounce time of delayed pickup and delayed dropout is recommended to set as 5ms. When users have their own reasonable setting principles, they can set the debounce time related settings according to their own setting principles. 6.5.2 Jitter Processing This device can handle repetitive signal or so-called jitter via binary input module with the following settings: [Mon_Window_Jitter] T, monitoring window of binary input jitter processing [Num_Blk_Jitter] N, times threshold to block binary input status change due to jitter [Blk_Window_Jitter] T', blocking window of binary input status change due to jitter [Num_Reblk_Jitter] N', times threshold to initiate immediately another blocking window of binary input status change due to continuous jitter For a binary input voltage variation, if the jitter processing function is enabled, its handling principle is: 1. 2. During the T, ⚫ If the actual jitter times < N, the block will not be initiated and the status change of this binary input will be considered. ⚫ If the actual jitter times ≥ N, the T' is initiated, and the status change of binary input will be ignored during the T'. During the T', ⚫ If the actual jitter times < N', the block window will expire. The final status of this binary input will be compared to the original one before T', so as to determine whether there is a change or not. ⚫ If the actual jitter times ≥ N', the T' will be initiated again immediately (i.e. restart the timer), and the status change of binary input will be ignored during the next T'. An example of jitter processing is shown in the following sequence chart: PCS-9613S Differential Relay 6-7 Date: 2020-09-02 6 6 Supervision Input voltage level Debounce time (falling edge) Debounce time (rising edge) Jitter blocking flag n=N initiate jitter block Signal after debounce & jitter processing n=N Prolong blocking window n=6<N=7 T T t5 T t1 t7 t8 t6 T t2 t3 T t4 t9 t10 t Figure 6.5-3 Sequence chart of jitter processing 6 ①Red line Voltage variation of binary input ②Green line Blocking signal of binary input status change due to jitter ③Blue line Binary input status after debounce and jitter processing n Actual jitter times We take N = 7 and N' = 5 in this example. 1. 2. 3. T = t2 - t1 ⚫ n=6<N ⚫ No blocking, ② stays at 0 and ③ is tracing the voltage variation to create SOE. T = t4 - t3, at t5 ⚫ n=7=N ⚫ The processing initiates the blocking immediately due to jitter ⚫ Jitter blocking, no more SOE event, ② changes its status to 1 and ③ stops the tracing. T' = t6 - t5 ⚫ At t7, n = 5 =N', the processing prolongs the blocking immediately due to jitter PCS-9613S Differential Relay 6-8 Date: 2020-09-02 6 Supervision ⚫ 4. 5. Jitter blocking continues, no SOE event, ② stays at 1 and ③ keeps its status. T'= t8 - t7 ⚫ At t9, n = 5 =N', the processing prolongs the blocking immediately due to jitter. ⚫ Jitter blocking continues, no SOE event, ② stays at 1 and ③ keeps its status. T'= t10 - t9 ⚫ n = 2 < N' ⚫ At t10, jitter unblocking, ② changes its status to 0, the blocking window expires and ③ restart to trace the voltage varation immediately. At this point, no debounce time takes effect and SOE can be created since then. 6.6 Tripping Counter Statistics The tripping counter statistics function supports statistics of the tripping operation, such as circuit breakers, disconnectors and so on. For phase separation circuit breaker, when the position of phase A, B, and C is detected from close state to open state, the total position tripping counter is added, and the tripping counter is added once when the position of the disconnector is detected from close state to open state. In addition, the statistics of the number of state change of circuit breakers and disconnectors are also provided. The state change counter will add one when the position is detected from close state to open state or from open state to close state. 6.7 Supervision Alarms and Handling Suggestion Hardware circuit and operation status of this device are self-supervised continuously. If any abnormal condition is detected, information or report will be displayed and a corresponding alarm will be issued. A minor abnormality may block a certain number of protections functions while the other functions can still work. However, if severe hardware failure or abnormality, such as PWR module failure, DC converter failure and so on, are detected, all protection functions will be blocked and the LED “HEALTHY” will be extinguished and blocking output contacts “BO_Fail” will be given. The protective device then cannot work normally and maintenance is required to eliminate the failure. All the alarm signals and the corresponding handling suggestions are listed below. If the device is blocked or alarm signal is sent during operation, please do find out its reason with the help of self-diagnostic record. If the reason cannot be found at site, please notify the factory NR. Please do not simply press button “TARGET RESET” on the protection panel or re-energize on the device. PCS-9613S Differential Relay 6-9 Date: 2020-09-02 6 6 Supervision Table 6.7-1 Alarm description Running Status LED No. Item HEALTHY ALARM Description Modifiable Fail Signals (Device will be blocked) This signal will be issued if 1 Fail_Device OFF ON NO any fail signal picks up and it will drop off when all fail signals drop off. This signal will be issued if any hardware or software 2 Fail_DeviceInit OFF ON NO failure, or configuration detected serious error in the is device initialization process. This signal will be issued due to mismatch between the 3 Fail_BoardConfig OFF ON NO configuration of plug-in modules and the designing drawing of an applied-specific project. This signal will be issued if 6 the 4 Fail_ProcLevelConfig OFF ON NO CCD configure process file is level parsed wrongly or the type in the file is inconsistent with the actual device. After configuration file is updated, settings of the file and settings saved on the device are not matched. This 5 Fail_SettingItem_Chgd OFF ON NO signal will be issued instantaneously and will be latched unless recommended the handling suggestion is adopted. The value of any setting is out of scope. This signal will 6 Fail_Setting_OvRange OFF ON NO be issued instantaneously and will be latched unless the recommended handling suggestion is adopted. 7 Fail_Memory OFF ON NO The alarm signal will be issued instantaneously when PCS-9613S Differential Relay 6-10 Date: 2020-09-02 6 Supervision Running Status LED No. Item HEALTHY ALARM Description Modifiable an error is found during checking memory data, and usually, it will automatically drop out. The board fails to register the variable, 8 Fail_BoardRegister OFF ON NO because of abnormal board, insufficient memory space, or incorrect configuration. 9 Fail_ProcessConfig OFF ON NO The configuration process does not run properly. The board fails initialized, 10 Fail_BoardInit OFF ON NO to because be of abnormal board, insufficient memory space, or incorrect configuration. Error is found during checking settings. It means inappropriate or incorrect settings for some application 11 Fail_Settings OFF ON NO scenarios are checked. This signal will be issued instantaneously and will be latched unless recommended the handling suggestion is adopted. A/D sampling data push error, the possible cause is 12 Fail_Sample OFF ON NO that the data verification fails or no data is sampled by A/D converter. 13 Fail_Output OFF ON NO The output module is abnormal Alarm Signals (Device will not be blocked) The device is abnormal. This signal will be issued if any 14 Alm_Device ON ON NO alarm signal picks up and it will drop off when all alarm signals drop off. 15 Alm_DeviceInit ON OFF PCS-9613S Differential Relay NO This signal will be issued if any hardware or software 6-11 Date: 2020-09-02 6 6 Supervision Running Status LED No. Item HEALTHY ALARM Description Modifiable configuration detected wrong in the is device initialization process. The error is found during checking 16 Alm_Version ON ON NO the version of software downloaded to the device. This signal will be issued instantaneously and will drop off instantaneously. Alarm signal indicating that the 17 Alm_Maintenance ON ON YES equipment maintenance is state in (the binary input [BI_Maintenance] is energized. The device is in the communication test mode. 18 Alm_CommTest ON ON NO This signal will be issued instantaneously and will drop 6 off instantaneously. The device is in the GOOSE 19 Alm_GOOSETest ON OFF NO test mode. This signal will be issued instantaneously and will drop off instantaneously. Management procedure will upload and check the parameters and settings of 20 Alm_Settings_MON ON ON NO each protection module regularly, plug-in if the parameters and settings are inconsistent, the alarm signal will be issued. The active group set by settings in device and that 21 Alm_BI_SettingGrp ON OFF NO set by binary input are not matched. This signal will be issued instantaneously and will drop off instantaneously. 22 Alm_TimeSyn ON ON YES 23 Alm_Insuf_Memory ON ON NO The time synchronization abnormality alarm. The memory of CPU plug-in PCS-9613S Differential Relay 6-12 Date: 2020-09-02 6 Supervision Running Status LED No. Item HEALTHY ALARM Description Modifiable module is insufficient. The configuration file of IEC103 is detected to be not 24 Alm_CfgFile_IEC103 ON ON NO correct when this file is parsed in the device initialization process. CPU module detects that 25 Alm_Board ON OFF NO some module is reset due to the abnormality during the device operating. An abnormality is detected 26 Bx.Alm_Board ON ON NO during the module self-check. No 27 Alm_Insuf_NORflash ON OFF NO sufficient NOR flash space used to store the program in CPU module The settings which are stored in CPU module are 28 Alm_Settings ON ON NO different with the settings which are used by other modules. 29 Alm_Settings_DFR ON OFF NO Disturbance fault recording settings are set wrongly The network mode is inconsistent, such as the 30 Alm_NetMode_Unmatched ON OFF NO setting is set as HSR mode, but the actual operation mode is PRP mode. The device's master process 31 Alm_master ON ON NO is abnormal and it is blocked for more than 1 minute. 32 Alm_CfgFile_FPGA ON OFF NO 33 Alm_DSP_HTM_Comm ON ON NO Error is detected in the FPGA configuration file. Error is detected in internal communication. Error is detected in the 34 Alm_CRC_ProcLevel ON OFF NO configuration file of process level by CRC. 35 Alm_CfgFile_TCP1_DNP ON OFF NO 36 Alm_CfgFile_TCP2_DNP ON OFF NO PCS-9613S Differential Relay The configuration file of DNP client 1 is incorrect. The configuration file of DNP 6-13 Date: 2020-09-02 6 6 Supervision Running Status LED No. Item HEALTHY ALARM Description Modifiable client 2 is incorrect. 37 Alm_CfgFile_TCP3_DNP ON OFF NO 38 Alm_CfgFile_TCP4_DNP ON OFF NO 39 Alm_BOTest ON OFF NO The configuration file of DNP client 3 is incorrect. The configuration file of DNP client 4 is incorrect. The device is in the binary output test mode. This signal will be issued if the sampled values from the dual 40 Alm_Sample ON ON NO A/D converters are inconsistent or the sampled value contains a large DC component during the self or mutual supervision of sampling channels. 41 Alm_Quality ON ON NO The quality of sampled data is abnormal. DPS abnormality signal, if the circuit breaker position is 6 intermediate or 42 CB.DPS.Alm ON OFF YES bad, this alarm will be issued. This signal will pick up and drop off with a time delay defined by [CSWI**.DPS.t_Alm]. DPS abnormality signal, if the switch 0x position is intermediate or 43 DS0x.DPS.Alm (x=1~9) ON OFF YES bad, this alarm will be issued. This signal will pick up and drop off with a time delay defined by [CSWI**.DPS.t_Alm]. The 44 50BF.Alm_Init ON ON YES initiating signal of breaker failure protection is energized consistently. CT circuit fails. This signal will pick-up with a 45 CTS.Alm ON ON YES time delay of [CTS.t_DPU] and will drop-out with a time delay of [CTS.t_DDO]. PCS-9613S Differential Relay 6-14 Date: 2020-09-02 6 Supervision Running Status LED No. Item HEALTHY ALARM Description Modifiable VT circuit fails. This signal will pick-up with a 46 VTS.Alm ON ON YES time delay of [VTS.t_DPU] and will drop-out with a time delay of [VTS.t_DDO]. Input signal of receiving transfer trip is energized for 47 TT.Alm ON ON YES longer than the [TT.t_Op]+5s and setting it will drop-out with a time delay of 10s. 48 87L.FOx.Alm_Diff ON ON YES The differential current of channel No.x is abnormal. Pilot channel alarm signals (Device will not be blocked) Received ID from the remote end is not as same as the setting [FOx.RmtID] of the 49 FOx.Alm_ID ON ON YES device in local end This signal will pick up with a time delay of 100ms and will drop off with a time delay of 1s. Channel x is abnormal This signal will pick up with a 50 FOx.Alm ON ON YES time delay of 100ms and will drop off with a time delay of 1s. No valid frame of channel x is received. 51 FOx.Alm_NoValFram ON ON YES This signal will pick up with a time delay of 100ms and will drop off with a time delay of 1s. Rate of error code of channel x is larger than 40 error 52 FOx.Alm_CRC ON ON YES codes per second. This signal will pick up instantaneously and will drop off with a time delay of 10s. 53 FOx.Alm_Off ON ON PCS-9613S Differential Relay YES Channel x is out of service due to receive error codes 6-15 Date: 2020-09-02 6 6 Supervision Running Status LED No. Item HEALTHY ALARM Description Modifiable after device picking up. This signal will pick up instantaneously and will drop off instantaneously. Optical fibre of channel x is connected wrongly. 54 FOx.Alm_Connect ON ON YES This signal will pick up with a time delay of 100ms and will drop off with a time delay of 1s. The 55 FOx.Alm_87L_Unmatched ON ON YES status of protection between differential of channel local end x and remote end is inconsistent. GOOSE alarm signals (Device will not be blocked) The GOOSE communication is abnormal. It is an overall alarm signal 6 56 GAlm_Overall ON ON NO and will be issued if any GOOSE alarm signal picks up and it will drop-out when all these alarm signals GOOSE alarm signal indicating that drop-out. 57 GAlm_CfgFile ON ON NO GOOSE configuration file is incorrect. For GOOSE link, the incoming data with test=true 58 GAlm_Maint_Unmatched ON ON NO & validity=good operatorBlocked=false, & but the quality status (q) of the device equals to "on". Network A of corresponding GOOSE link is disconnected 59 @Bx.Name_n_GCommLink. GAlm_ADisc ON ON NO (No GOOSE message is received within two times TAL from corresponding GOOSE link) 60 @Bx.Name_n_GCommLink. GAlm_BDisc Network B of corresponding ON ON NO GOOSE link is disconnected (No GOOSE message is PCS-9613S Differential Relay 6-16 Date: 2020-09-02 6 Supervision Running Status LED No. Item HEALTHY ALARM Description Modifiable received within two times TAL from corresponding GOOSE link) The GOOSE control blocks received on network and the GOOSE 61 @Bx.Name_n_GCommLink. GAlm_CfgUnmatched ON ON NO control defined in configuration blocks GOOSE file are unmatched (Including config version, number of data sets and data type). Table 6.7-2 Alarm handling suggestion No. Item Handling suggestion Fail Signals (Device will be blocked) 1 Fail_Device 2 Fail_DeviceInit The signal is issued with other specific fail signals, and please refer to the handling suggestion other specific alarm signals. Please inform the manufacturer or the agent for repair. 1. Go to the menu “Information→Borad Info”, check the abnormality information. 3 Fail_BoardConfig 2. For the abnormality board, if the board is not used, then remove, and if the board is used, then check whether the board is installed properly and work normally. Check whether the CCD process level configuration file of this device is 4 Fail_ProcLevelConfig existed and whether the file content is correct. May need to download and update the correct CCD process level configuration file. Please check the settings mentioned in the prompt message on the LCD, 5 Fail_SettingItem_Chgd and go to the menu “Settings” and select “Confirm_Settings” item to confirm settings. Then, the device will restore to normal operation stage. Please reset setting values according to the range described in the 6 Fail_Setting_OvRange instruction manual, then re-power or reboot the device and the device will restore to normal operation state. 7 Fail_Memory 8 Fail_BoardRegister 9 Fail_ProcessConfig View the menu "Initialization Error" to check the detailed reason, and 10 Fail_BoardInit send the reason to manufacturer the manufacturer or the agent. 11 Fail_Settings Please check the settings and set them correctly 12 Fail_Sample Please check the connection of CPU plug-in module. 13 Fail_Output Please inform manufacturer the manufacturer or the agent for repair. Put the protective device out of service at once. Inform the manufacturer or the agent to maintain it. PCS-9613S Differential Relay 6-17 Date: 2020-09-02 6 6 Supervision No. Item Handling suggestion Alarm Signals (Device will not be blocked) 14 Alm_Device 15 Alm_DeviceInit The signal is issued with other specific alarm signals, and please refer to the handling suggestion other specific alarm signals. Please inform manufacturer the manufacturer or the agent to deal with it. Users may pay no attention to the alarm signal in the project commissioning stage, but it is needed to download the latest package file (including correct version checksum file) provided by R&D engineer to 16 Alm_Version make the alarm signal disappear. Then users get the correct software version. It is not allowed that the alarm signal is issued on the device already has been put into service. The devices having being put into service so that the alarm signal disappears. 17 Alm_Maintenance Check the binary input [BI_Maintenance]. 18 Alm_CommTest No special treatment is needed, and disable the communication test 19 Alm_GOOSETest function after the completion of the test. 20 Alm_Settings_MON Put the protective device out of service at once. Inform the manufacturer or the agent to maintain it. Please check the value of setting [Active_Grp] and binary input of 21 Alm_BI_SettingGrp 6 indicating active group, and make them matched. Then the “ALARM” LED will be extinguished and the corresponding alarm message will disappear and the device will restore to normal operation state. 1. Check whether the selected clock synchronization mode matches the clock synchronization source; 2. Check whether the wiring connection between the device and the clock synchronization source is correct 22 Alm_TimeSyn 3. Check whether the setting for selecting clock synchronization (i.e. [Opt_TimeSyn]) is set correctly. If there is no clock synchronization, please set the setting [Opt_TimeSyn] as “No TimeSyn”. After the abnormality is removed, the “ALARM” LED will be extinguished and the corresponding alarm message will disappear and the device will restore to normal operation state. 23 Alm_Insuf_Memory Please inform manufacturer the manufacturer or the agent to deal with it. 24 Alm_CfgFile_IEC103 Please inform manufacturer the manufacturer or the agent to deal with it. 25 Alm_Board 26 Bx.Alm_Board 27 Alm_Insuf_NORflash 28 Alm_Settings 29 Alm_Settings_DFR 30 Alm_NetMode_Unmatched 31 Alm_master Please inform manufacturer the manufacturer or the agent to deal with it. Please refer to the fault recording configuration related contents, i.e. Section 7.4. Check the setting of network mode, or upload the device log and confirm with the manufacturer or agent whether the network mode is supported. Please check the load of the device. PCS-9613S Differential Relay 6-18 Date: 2020-09-02 6 Supervision No. Item Handling suggestion 32 Alm_CfgFile_FPGA Please inform the manufacturer or the agent for repair. 33 Alm_DSP_HTM_Comm Please inform the manufacturer or the agent for repair. 34 Alm_CRC_ProcLevel Please check the configuration and network of the process level. 35 Alm_CfgFile_TCP1_DNP 36 Alm_CfgFile_TCP2_DNP Please contact the configuration engineer to check and confirm the 37 Alm_CfgFile_TCP3_DNP contents of DNP configuration file. 38 Alm_CfgFile_TCP4_DNP 39 Alm_BOTest 40 Alm_Sample Please check the connection of AC AI module and CPU module. 41 Alm_Quality Please check SV quality if adopting IED 61850-9-2. 42 CB.DPS.Alm 43 No special treatment is needed, and disable the binary output test function after the completion of the test. Check the corresponding DPS signal DS0x.DPS.Alm (x=1~9) 44 50BF.Alm_Init 45 CTS.Alm 46 VTS.Alm Check the initiating contact of breaker failure protection Please check the corresponding CT secondary circuit. After the abnormality is eliminated, the device returns to normal operation state. Please check the corresponding VT secondary circuit. After the abnormality is eliminated, the device returns to normal operation state. Please check the corresponding binary input secondary circuit. After the 47 abnormality is eliminated, “ALARM” LED will go off automatically and TT.Alm device returns to normal operation state with a time delay of 10s. 48 87L.FOx.Alm_Diff Please check whether the CT circuit is normal. Pilot channel alarm signals (Device will not be blocked) 49 FOx.Alm_ID 50 FOx.Alm 51 FOx.Alm_NoValFram 52 FOx.Alm_CRC 53 FOx.Alm_Off Please check the connection of optical fibre channel. Please check the connection of optical fibre channel. (For example, 54 FOx.Alm_Connect receiving and sending are inconsistent, or channel 1 and channel 2 are inconsistent) 55 FOx.Alm_87L_Unmatched Please check the device's enabling/disabling status of current differential protection at both ends, ensure that their status are consistent GOOSE alarm signals (Device will not be blocked) The signal is issued with other specific GOOSE alarm signals, and please 56 GAlm_Overall 57 GAlm_CfgFile Inform commissioning personnel to check the GOOSE configuration file. 58 GAlm_Maint_Unmatched Please check the quality status (q) of the incoming data and the device. 59 @Bx.Name_n_GCommLink. GAlm_ADisc refer to the handling suggestion of them. Please check the GOOSE network and GOOSE configuration file. PCS-9613S Differential Relay 6-19 Date: 2020-09-02 6 6 Supervision No. 60 61 Item Handling suggestion @Bx.Name_n_GCommLink. GAlm_BDisc @Bx.Name_n_GCommLink. GAlm_CfgUnmatched Where: @Bx.Name_n_GCommLink is the set value of the label setting of [Bx.Name_n_GCommLink] (n=00~63) 6 PCS-9613S Differential Relay 6-20 Date: 2020-09-02 7 System Functions 7 System Functions Table of Contents 7.1 Clock Synchronization .................................................................................... 7-1 7.1.1 Clock Synchronization Mode................................................................................................ 7-1 7.1.2 Clock Synchronization Abnormality ...................................................................................... 7-1 7.1.3 Clock Synchronization Priority ............................................................................................. 7-1 7.1.4 SNTP Setup.......................................................................................................................... 7-1 7.2 State Information ............................................................................................. 7-2 7.2.1 Overview............................................................................................................................... 7-2 7.2.2 Access Method ..................................................................................................................... 7-2 7.3 Event Recording .............................................................................................. 7-3 7.3.1 Overview............................................................................................................................... 7-3 7.3.2 Disturbance Records ............................................................................................................ 7-3 7.3.3 Supervision Events............................................................................................................... 7-3 7.3.4 Binary Events ....................................................................................................................... 7-4 7.3.5 Device Logs .......................................................................................................................... 7-4 7.3.6 Control Logs ......................................................................................................................... 7-4 7.3.7 High-frequency Recording ................................................................................................... 7-4 7.3.8 Access Method ..................................................................................................................... 7-4 7.4 Fault Recording ............................................................................................... 7-5 7.4.1 Overview............................................................................................................................... 7-5 7.4.2 Fault Report .......................................................................................................................... 7-5 7.4.3 Fault Waveform .................................................................................................................... 7-6 7.4.4 Access Method ..................................................................................................................... 7-7 7.5 Maintenance State ........................................................................................... 7-7 7.6 Communication Test ....................................................................................... 7-7 7.7 Output Test ....................................................................................................... 7-8 7.8 Target Reset ..................................................................................................... 7-9 PCS-9613S Differential Relay 7-a Date: 2020-09-02 7 7 System Functions 7.9 Switch Setting Groups .................................................................................... 7-9 7 PCS-9613S Differential Relay 7-b Date: 2020-09-02 7 System Functions 7.1 Clock Synchronization 7.1.1 Clock Synchronization Mode The device supports both hardware-based and software-based clock synchronization modes. 1. 2. Hardware-based clock synchronization ([Opt_TimeSyn]=Conventional) ⚫ IRIG-B: IRIG-B via RS-485 differential level, TTL level or optical fibre interface ⚫ PPS: Pulse per second (PPS) via RS-485 differential level or binary input ⚫ PPM: Pulse per minute (PPM) via RS-485 differential level or binary input ⚫ IEEE 1588: Clock message based on IEEE 1588 via Ethernet network Software-based clock synchronization ([Opt_TimeSyn]=SAS) ⚫ SNTP (PTP): Unicast (point-to-point) SNTP mode via Ethernet network ⚫ SNTP (BC): Broadcast SNTP mode via Ethernet network ⚫ Message (IEC 60870-5-103 / Modbus / DNP3): Clock messages through IEC 60870-5-103 protocol, Modbus protocol and DNP3 protocol 7.1.2 Clock Synchronization Abnormality The device provides an alarm signal "Alm_TimeSyn", which indicates the signal of clock synchronization is abnormal or is lost. The setting [Opt_TimeSyn] should be set reasonably according to actual clock synchronization source. But if the setting [Opt_TimeSyn] is set as "NoTimeSyn" and no clock synchronization signal is inputted, the device will not issue the alarm signal. 7.1.3 Clock Synchronization Priority The device provides a priority-based adaptive clock synchronization scheme, which means that it can automatically identify multiple clock synchronization sources in the same clock synchronization mode and choose the highest priority of clock synchronization sources. Clock synchronization mode Hardware-based Software-based Input signal The Highest priority IRIG-B + IEEE 1588 + PPS/PPM IRIG-B IEEE 1588 + PPS/PPM IEEE1588 SNTP + Message SNTP 7.1.4 SNTP Setup When the device adopts SNTP to realize clock synchronization, [IP_Server_SNTP] and [IP_StandbyServer_SNTP] shall be set correctly. [IP_Server_SNTP] is the address of SNTP clock synchronization server which sends SNTP timing messages to the relay or BCU. [IP_StandbyServer_SNTP] is the address of standby SNTP clock PCS-9613S Differential Relay 7-1 Date: 2020-09-02 7 7 System Functions synchronization server. Both [IP_Server_SNTP] and [IP_StandbyServer_SNTP] are ineffective unless SNTP clock synchronization is valid. When both [IP_Server_SNTP] and [IP_StandbyServer_SNTP] are set as "000.000.000.000", the device receives broadcast SNTP synchronization message. When either [IP_Server_SNTP] or [IP_StandbyServer_SNTP] is set as "000.000.000.000", the device adopts the setting whose value is not equal to "000.000.000.000" as SNTP server address and receives unicast SNTP synchronization message. If neither [IP_Server_SNTP] nor [IP_StandbyServer_SNTP] is set as "000.000.000.000", the device adopts the setting [IP_Server_SNTP] as SNTP server address to receive unicast SNTP synchronization message. If the device does not receive any server response after 30s, it adopts the setting [IP_StandbyServer_SNTP] as SNTP server address to receive unicast SNTP synchronization message. The device will switch between [IP_Server_SNTP] and [IP_StandbyServer_SNTP] repeatedly if it does not receive any server response in 30s. 7.2 State Information 7.2.1 Overview 7 The device can provide real-time state information, including analog quantities (such primary measurement value, secondary measurement value, metering value and so on) and status quantities (supervision status, input status, output status and so on). By check these state information, operators can know operation state of the protected equipment and whether the device is healthy. 7.2.2 Access Method 7.2.2.1 Access by Local HMI (Human Machine Interface) These state information can be gained via local HMI. The menu path is: 1. 2. Analog quantities ⚫ MainMenu "Measurements" "Primary Values" ⚫ MainMenu "Measurements" "Secondary Values" ⚫ MainMenu "Measurements" "Function Values" "Synchronism Check" ⚫ MainMenu "Measurements" "Energy Metering" ⚫ MainMenu "Measurements" "Power Quality" ⚫ MainMenu "Measurements" "UserDef Values" "UserDef Values1/2" Status quantities PCS-9613S Differential Relay 7-2 Date: 2020-09-02 7 System Functions ⚫ MainMenu "Status" "Inputs" ⚫ MainMenu "Status" "Outputs" ⚫ MainMenu "Status" "Superv Status" ⚫ MainMenu "Status" "Logic Links Status" ⚫ MainMenu "Status" "Running Status" ⚫ MainMenu "Status" "UserDef Status" "UserDef Status1/2" 7.2.2.2 Access by Virtual HMI Using the virtual LCD tool, the corresponding content can be viewed through the same menu path as local LCD. 7.2.2.3 Access by Communication Client Device's state information can be uploaded into clients through message communication. For differential protocols, the state information can be gained through corresponding communication service. 7.2.2.4 Access by Printer The device can print the current state information, so that the operator can observe and save the current operation condition. The access path is: MainMenu "Print" "Device Status" 7.3 Event Recording 7 7.3.1 Overview The device can store the latest 1024 time-stamped disturbance records, 1024 time-stamped binary events, 1024 time-stamped supervision events, 256 time-stamped control logs and 1024 time-stamped device logs. All the records are stored in non-volatile memory, and when the available space is exhausted, the oldest record is automatically overwritten by the latest one. 7.3.2 Disturbance Records When any protection element operates or drops out, such as fault detector, distance protection etc., they will be logged in event records. Disturbance records include signal name, its value before and after changing, and the time precision is up to 1ms. 7.3.3 Supervision Events The device is under automatic supervision all the time. If there are any failure or abnormal condition detected, such as, chip damaged, VT circuit failure and so on, it will be logged in event records. Supervision events include signal name, its value before and after changing, and the time precision is up to 1ms. PCS-9613S Differential Relay 7-3 Date: 2020-09-02 7 System Functions 7.3.4 Binary Events When there is a binary input is energized or de-energized, i.e., its state has changed from “0” to “1” or from “1” to “0”, it will be logged in event records. Binary events include signal name, its value before and after changing, and the time precision is up to 1ms. 7.3.5 Device Logs If an operator executes some operations on the device, such as reboot protective device, modify setting, etc., they will be logged in event records. Device logs include signal name, its value before and after changing, and the time precision is up to 1ms. 7.3.6 Control Logs When an operator executes a control command via local LCD, PCS-Studio or communication client, it will be logged in control logs. Control logs include time stamp, controlled object, control origination, control position, operation condition ,interlocking condition, control command and operation result. 7.3.7 High-frequency Recording The high-frequency recording is available by PCS-Studio. By switching the option "Disabled" or "Enabled" to enable or disable the function in the following path through the PCS-Studio configuration tool: Project Node → Device Node → Device Setup → Global Config → System Config. 7 When high-frequency recording is enabled, a high-frequency waveforms record (9.6kHz sampling) can also be gained besides the normal disturbance waveforms record (1.2kHz sampling). The difference between high-frequency waveforms records and normal disturbance waveforms records is only the sampling rate. This kind of high-resolution records is convenient to perform post-fault system and device operation analysis. 7.3.8 Access Method 7.3.8.1 Access by Local HMI The device provides corresponding menus to view event recorders. The menu path is: MainMenu "Test" "Disturb Records" MainMenu "Records" "Superv Events" PCS-9613S Differential Relay 7-4 Date: 2020-09-02 7 System Functions MainMenu "Records" "IO Events" MainMenu "Records" "Device Logs" MainMenu "Records" "Control Logs" MainMenu "Records" "HighFreqRecords" 7.3.8.2 Access by Virtual HMI Using the virtual LCD tool, the corresponding content can be viewed through the same menu path as local LCD. 7.3.8.3 Access by Communication Client Event recorders can be uploaded into clients through corresponding communication service of the protocol (including IEC60870-5-103, IEC61850, DNP3). 7.3.8.4 Access by Printer The device can print event recorders, so that the operator can observe and save the current operation condition. The access path is: MainMenu "Print" "Superv Events" MainMenu "Print" "IO Events" 7.4 Fault Recording 7.4.1 Overview Fault recorder can be used to have a better understanding of the behaviour of the power network and related primary and secondary equipment during and after a disturbance. Analysis of the recorded data provides valuable information that can be used to improve existing equipment. This information can also be used when planning for and designing new installations. The fault recorder is comprised of the report and the waveform, which can be triggered by pickup signals, trip signals and configurable binary signal “BI_TrigDFR”. The fault memory of the device is automatically updated with every recording. When the fault memory is filled completely, the oldest records are overwritten automatically. Thus, the most recent recordings are always stored safely. The maximum number of recordings is 64. 7.4.2 Fault Report For each fault report, the following items are included: 1. Sequence number Each operation will be recorded with a sequence number in the record and displayed on LCD screen. 2. Date and time of fault occurrence PCS-9613S Differential Relay 7-5 Date: 2020-09-02 7 7 System Functions The date and time are recorded when a system fault is detected. The time resolution is 1ms. 3. Relative operating time An operating time (not including the operating time of output relays) is recorded in the record. The time resolution is 1ms. 4. Fault information Including faulty phase, fault location and protection elements 7.4.3 Fault Waveform A fault waveform contains all analog and digital quantities related to protection such as currents, voltages, differential current, alarm elements, binary inputs and etc. The overall duration of a single fault recording comprises the total duration of the configurable recording criterion, the pre-trigger time and the post-trigger time. With the fault recording parameter, these components can be individually set. The pre-trigger waveform recorded duration is configured via the setting [RecDur_PreTrigDFR]. The waveform recorded duration after the fault disappears is configured via the setting [RecDur_PostFault]. The maximum post-trigger waveform recorded duration is configured via the setting [MaxRecDur_PostTrigDFR]. 4. [MaxRecDur_PostTrigDFR] 1. [RecDur_PreTrigDFR] 2.Pickup 3. [RecDur_PostFault] Trigger point Total recording time 7 1. Pre-trigger recording time Use the setting [RecDur_PreTrigDFR] to set this time. 2. Pickup recording time The pickup recording time cannot be set. It continues as long as any valid trigger condition, binary or analog, persists (unless limited by the limit time, which is determined by the setting [MaxRecDur_PostTrigDFR]). 3. Post-fault recording time The recording time begins after all activated triggers are reset. Use the setting [RecDur_PostFault] to set this time. 4. Maximal post-trigger recording time Use the setting [MaxRecDur_PostTrigDFR] to set this time. If the summation of pickup recording time and post-fault recording time is larger than maximal post-trigger recording time, the post-trigger recording time shall be equal to the setting [MaxRecDur_PostTrigDFR]. PCS-9613S Differential Relay 7-6 Date: 2020-09-02 7 System Functions 7.4.4 Access Method 7.4.4.1 Access by Local HMI The device provides corresponding menus to check fault recording. The menu path is: MainMenu "Records" "Disturb Records" 7.4.4.2 Access by Virtual HMI Using the virtual LCD tool, the corresponding content can be viewed through the same menu path as local LCD. 7.4.4.3 Access by Communication Client Fault recording can be uploaded into clients through corresponding communication service of the protocol (including IEC60870-5-103, IEC61850, DNP3). 7.4.4.4 Access by Printer The device can print fault recording, so that the operator can observe and save the current operation condition. The access path is: MainMenu "Print" "Disturb Records" 7.5 Maintenance State The device provides maintenance state, i.e., the binary input [BI_Maintenance] is energized, which is convenient for maintenance work. For adopting conventional CT/VT, binary inputs and binary outputs, maintenance state has no influence on protection logics. For binary inputs and binary outputs by GOOSE connections. During device maintenance, the object will send GOOSE message with Test quality attribute. The Test quality attribute indicates to the receiver device that the object received via a GOOSE message was created under test conditions and not operating conditions. If the Test quality attribute received is different with the object's Test quality attribute, binary inputs and binary outputs by GOOSE connections will be affected based on different types of binary inputs and binary outputs. For SV (Sampling Value) message, if the Test quality attribute received is different with the object's Test quality attribute, the relevant protection functions will be blocked. For IEC60870-5-103 protocol, only the messages in link layer maintained, service messages in the application layer which is uploaded automatically are blocked, and service messages in the application layer which is issued by the client are rejected. For IEC61850 protocol, all Test quality attribute set as "1". For DNP3 and ModBus protocol, they are not affected. 7.6 Communication Test The device provides Test Mode to allow all protection elements, supervision events and binary events to fulfill communication test, but to avoid the output contacts to close. During communication test, protection functions are not affected, the signals generated by PCS-9613S Differential Relay 7-7 Date: 2020-09-02 7 7 System Functions communication test are recorded in relevant reports, and event recording and fault recording will not stop recording disturbance information. The alarm signal "Alm_CommTest" will be issued to indicate the operator when activating Test Mode and exiting Test Mode. Communication test can be gained via local HMI and the virtual HMI, the corresponding content can be viewed through the following menu paths: ⚫ Events Simulation Main Menu "Test" "Device Test" "Disturb Events" Main Menu "Test" "Device Test" "Superv Events" Main Menu "Test" "Device Test" "IO Events" ⚫ Forced Measurements Main Menu "Test" "Device Test" "Measurements" Forced measurement ONLY affects the values modified and transmitted to station control or control center. Primary circuit, secondary circuit and device local logic will not be influenced. Forced value will remain during the test until the exit of this menu. If no input operation is carried out within 60s, this test will exit and return to the previous menu automatically. 7 7.7 Output Test The device provides Output Test Mode to test all outputs. Through this mode, there will be real operations, such as contact closing and GOOSE output value change, triggered by the device to test output circuits and links. So, protection functions outputs and the connecting primary equipments are affected. The output signals generated by output test are not recorded, while the entering and exiting of output test mode will be recorded in Superv Events. During the output test, the protection functions will not stop, nor will the all recording functions. Output test can be gained via the local LCD or virtual HMI of a debugging PC, the corresponding content can be viewed through the following menu paths: ⚫ Contacts Outputs Main Menu "Test" "Device Test" "Contact Outputs" ⚫ GOOSE Outputs Main Menu "Test" "Device Test" "GOOSE Outputs" PCS-9613S Differential Relay 7-8 Date: 2020-09-02 7 System Functions Dismantle the wiring connection if any influence on relevant primary equipment is undesired. The output test will cause operation of relay contacts through secondary circuit and GOOSE link. 7.8 Target Reset The device provides target reset which can be used to reset local signals (including magnetic latching output relays), latched LEDs, and confirm pop-up windows of reports. The function does not affect the protection logic and communication function. There are several ways to reset. 1. 2. Reset via local HMI ⚫ Access menu path: MainMenu "Local Cmd" "Reset Target" ⚫ Press the command pushbutton “ESC”+“ENT” on operation panel of the device under main interface ⚫ Press the command pushbutton " TARGET RESET" on operation panel of the device Reset via virtual HMI Access menu path: MainMenu "Local Cmd" "Reset Target" 3. Reset via binary input Energize the binary input "BI_RstTarg" 4. Reset via IEC61870-5-103 Use ASDU20, INF19 of IEC61870-5-103 protocol 5. 7 Reset via remote control Use standard remote service of corresponding protocol 7.9 Switch Setting Groups For different applications users can save the respective function settings in so-called settings groups, and if necessary enable them quickly. Up to 20 different settings groups can be saved in the device. In the process, only one settings group is active at any given time. During operation, the operator can switch between setting groups. The device will be temporarily blocked during switching setting groups. During temporary device blocking, the device will loss protection functions and communication functions. Alarm signals "Fail_Device" and "Alm_Device" will be issued. There are several ways to switch setting groups. 1. Switch via local HMI ⚫ Access menu path: MainMenu "Setting" "Global Settings" "System Settings", change the value of the setting [Active_Grp] PCS-9613S Differential Relay 7-9 Date: 2020-09-02 7 System Functions ⚫ 2. Press the command pushbutton “MENU” under main interface (password is required) Switch via virtual HMI Access menu path: MainMenu "Setting" "Global Settings" "System Settings", modify the setting [Active_Grp] 3. Switch via communication client The communication protocols IEC 60870-5-103 or IEC 61850 can be used for switching the setting groups via a communication connection. 4. ⚫ Use "General Service" of IEC61870-5-103 protocol to modify the setting [Active_Grp] ⚫ Use "SelectActiveSG" of IEC61850 protocol to switch setting groups. Switch via binary signals The device also provides an available function by configuring associated binary signals via PCS-Studio to switch setting group, which can be external binary inputs or internal logic signals. By default, no binary signals are configured, so the function is invalid. (The specificed confiuration method can refer to the application manual). Each input signal is coded with a sequence number that corresponds to a setting group. When the associated input signal changes, the device scans all input signals and selects the input with the smallest sequence number as the valid input. The device switches to the setting range corresponding to the input signal. The device can switch up to 20 setting groups. 7 PCS-9613S Differential Relay 7-10 Date: 2020-09-02 8 Hardware 8 Hardware Table of Contents 8.1 Overview........................................................................................................... 8-1 8.2 Typical Wiring .................................................................................................. 8-4 8.3 CT Requirement ............................................................................................... 8-7 8.3.1 CT Types .............................................................................................................................. 8-7 8.3.2 CT Requirement ................................................................................................................... 8-8 8.4 Plug-in Module Description ............................................................................ 8-9 8.4.1 Human-machine Interface Module (NR6855/NR6856) ........................................................ 8-9 8.4.2 Power Supply Module (NR6305/NR6310) ........................................................................... 8-9 8.4.3 CPU Module (NR6106) ...................................................................................................... 8-12 8.4.4 Analog Input Module (NR6641) .......................................................................................... 8-16 8.4.5 Binary Input Module (NR6601/NR6610) ............................................................................ 8-19 8.4.6 Binary Output Module (NR6651/NR6652/NR6660/NR6663)............................................. 8-23 8.4.7 Binary Input/Output Module (NR6661)............................................................................... 8-28 List of Figures Figure 8.1-1 Hardware diagram .................................................................................................. 8-1 Figure 8.1-2 Front view of this device.......................................................................................... 8-3 Figure 8.1-3 Typical rear view of this device (pin-ferrule-terminal modules) ............................ 8-3 Figure 8.1-4 Typical rear view of this device (ring-ferrule-terminal modules) ........................... 8-4 Figure 8.2-1 Typical hardware configuration 1 (pin-ferrule-terminal modules) ......................... 8-4 Figure 8.2-2 Typical wiring 1 (pin-ferrule-terminal modules)...................................................... 8-5 Figure 8.2-3 Typical hardware configuration 2 (ring-ferrule-terminal modules)........................ 8-6 Figure 8.2-4 Typical wiring 2 (ring-ferrule-terminal modules) .................................................... 8-7 Figure 8.4-1 View of power supply module ............................................................................... 8-10 Figure 8.4-2 View of CPU module .............................................................................................. 8-14 Figure 8.4-3 Connection of communication terminal ............................................................ 8-15 PCS-9613S Differential Relay 8-a Date: 2020-09-02 8 8 Hardware Figure 8.4-4 Jumpers of printer/RS-485 port .......................................................................... 8-15 Figure 8.4-5 Schematic diagram of CT circuit automatically closed ................................... 8-16 Figure 8.4-6 Terminal definition of analog input module ...................................................... 8-17 Figure 8.4-7 Current connection examples ............................................................................ 8-18 Figure 8.4-8 Voltage connection examples............................................................................. 8-18 Figure 8.4-9 Voltage dependence for binary inputs............................................................... 8-19 Figure 8.4-10 View of binary input module (NR6601A) ......................................................... 8-20 Figure 8.4-11 View of binary input module (NR6610A).......................................................... 8-22 Figure 8.4-12 View of binary output module NR6651A ......................................................... 8-24 Figure 8.4-13 View of binary output module NR6651B ......................................................... 8-25 Figure 8.4-14 View of binary output module NR6652A ......................................................... 8-26 Figure 8.4-15 View of binary output module (NR6660A) ....................................................... 8-27 Figure 7.4-9 View of binary output module (NR6663A) ......................................................... 8-28 Figure 7.4-16 View of binary input/output module (NR6661A) ............................................. 8-29 List of Tables Table 8.4-1 Terminal definition and description of power supply module ............................... 8-11 Table 8.4-2 Terminal definition and description of power supply module ............................... 8-11 Table 8.4-3 Configuration and terminal definition of CPU module........................................... 8-14 Table 8.4-4 Terminal definition and description of binary input module (NR6601A)............... 8-20 8 Table 8.4-5 Terminal definition and description of binary input module (NR6610A) .............. 8-22 Table 7.4-6 Terminal definition and description of NR6661A ................................................... 8-29 PCS-9613S Differential Relay 8-b Date: 2020-09-02 8 Hardware 8.1 Overview The modular design of this device allows this device to be easily upgraded or repaired by a qualified service person. The faceplate is hinged to allow easy access to the configurable modules, and back-plugging structure design makes it easy to repair or replace any module. This device adopts one 32-bit ARM core in the CPU chip as control core for management and monitoring function, and adopts another 32-bit ARM core in the CPU chip for all the protection calculation. The parallel processing of sampled data can be realized in each sampling interval to ensure ultrahigh reliability and safety of the device. This device is developed on the basis of our latest software and hardware platform, and the new platform major characteristics are of high reliability, networking and great capability in anti-interference. See Figure 8.1-1 for the hardware diagram. External Binary Input Conventional CT/VT A/D Output Relay ARM1 A/D Pickup Relay ECVT ETHERNET +E LCD Uaux Power Supply LED Clock SYN ARM2 Keypad RJ45 PRINT 8 Figure 8.1-1 Hardware diagram The working process of the device is shown in above figure: the currents and voltages from conventional CT/VT are converted into small voltage signal and sent to ARM1 core after filtered and A/D conversion for protection calculation and fault detector respectively (ECVT signals are sent to the device without small signal and A/D conversion). The ARM1 core carries out fault detector, protection logic calculation, tripping output, and the ARM2 core performs SOE (sequence of event) record, waveform recording, printing, communication between the device and SAS and communication between HMI and CPU. When the fault detector detects a fault and picks up, the positive power supply for output relay is provided. The items can be flexibly configured depending on the situations like sampling method of the device (conventional CT/VT or ECT/EVT), and the mode of binary output (conventional binary output or GOOSE binary output). The configurations for PCS S series based on microcomputer are classified into standard and optional modules. PCS-9613S Differential Relay 8-1 Date: 2020-09-02 8 Hardware Table 8.1-1 Module configuration of this device Module ID Module description Remark NR6855/NR6856 Human machine interface module (HMI module) Mandatory NR6305/6310 Power supply module (PWR module) Mandatory NR6106 Main CPU module (CPU module) Mandatory NR6641 Analog input module (AI module) Mandatory NR6601/NR6610 Binary input module (BI module) Mandatory NR6651/NR6652/NR6660/NR6663 Binary output module (BO module) Mandatory NR6661 Binary Input/output module (BI/BO module) Mandatory ⚫ HMI module is comprised of LCD, keypad, LED indicators and multiplex RJ45 ports for user as human-machine interface. ⚫ PWR module converts DC 250/220/125/110V into various DC voltage levels for modules of the device. ⚫ CPU module provides functions like communication with SAS, event record, setting management etc., and performs filtering, sampling, protection calculation and fault detector calculation. ⚫ AI module converts AC current and voltage from current transformers and voltage transformers respectively to small voltage signal. ⚫ BI module provides binary inputs via opto-couplers with rating voltage among AC110V/220V or DC24V/48V/110V/125V/220V/250V (configurable). ⚫ BO module provides output contacts for tripping, and signal output contact for annunciation signal, remote signal, fault and disturbance signal, operation abnormal signal etc. ⚫ BI/BO module not only provides binary inputs via opto-couplers with rating voltage among AC110V/220V or DC24V~250V (configurable), but also provides output contacts for tripping, and signal output contact for annunciation signal, remote signal, fault and disturbance signal, operation abnormal signal, etc. 8 Following figures show front and rear views of this device respectively. PCS-9613S Differential Relay 8-2 Date: 2020-09-02 8 Hardware Figure 8.1-2 Front view of this device 8 Figure 8.1-3 Typical rear view of this device (pin-ferrule-terminal modules) PCS-9613S Differential Relay 8-3 Date: 2020-09-02 8 Hardware Figure 8.1-4 Typical rear view of this device (ring-ferrule-terminal modules) 8.2 Typical Wiring B01 B02&B03 B04 B05 B06 P1 B01 B02&B03 B04 P1 NR6106AB NR6641-4I4U Option Option Option NR6310A NR6106AB NR6641-4I4U Option NR6310A 01 03 NET 8 05 Ia Ian 02 Ib Ibn 04 Ic Icn 06 BI_01+ BI_01_ BI_02+ 01 BI_02- 04 BI_COM BI_03 LC 07 LC I0 I0n 09 TX1 RX1 TX2 RX2 08 10 BI_04 BI_05 BI_06 12 BI_07 13 14 BI_08 BI_09 15 16 BO_01 18 BO_02 11 17 Usyn Usynn 01 04 BI_01+ BI_01_ BI_02+ BI_02- 04 06 BI_COM 05 BI_03 06 BI_04 BI_05 07 09 BI_06 09 10 12 BI_07 10 11 13 14 BI_08 BI_09 TX2 15 16 BO_01 RX2 17 18 BO_02 19 Ua Uan 20 21 Ub Ubn 22 Uc Ucn 24 01 Ia Ian 02 03 Ib Ibn Icn 02 03 NET 05 06 LC 07 07 08 05 LC Ic I0 I0n 09 08 10 11 TX1 11 12 RX1 13 14 15 Usyn Usynn 16 01 1A 02 1B 03 SG ND 04 2A 05 2B 06 SG ND 07 SY N+ 08 SY N- 09 SG ND 10 SY N-TTL CONSOLE 19 Ua Uan 20 21 Ub Ubn 22 23 Uc Ucn BO_03 BO_04 24 BO_05 BO_FAIL 17 01 1A 18 02 1B 19 03 SG ND 20 04 2A 21 05 2B 22 06 SG ND 23 07 SY N+ 24 08 SY N- 09 SG ND PWR+ 25 PWR- 26 Ground 23 BO_03 BO_04 BO_05 BO_FAIL 02 03 08 12 13 14 15 16 17 18 19 20 21 22 23 24 10 SY N-TTL PWR+ 25 PWR- 26 Ground CONSOLE Figure 8.2-1 Typical hardware configuration 1 (pin-ferrule-terminal modules) PCS-9613S Differential Relay 8-4 Date: 2020-09-02 8 Hardware The following wiring is given based on above hardware configuration SGND 0103 485-2A 0104 485-2B 0105 SGND 0106 0107 SYN- 0108 SGND 0109 TTL 0110 Clock SYN SYN+ Optional optical or electrical Ethernet to SCADA 0102 COM 0101 485-1B COM 485-1A Multiplex RJ45 + P102 - P103 + P104 - P106 + BI_01 0206 0207 I0 0208 0209 0210 0211 0212 0213 0214 BI_02 0215 0216 0217 BI_03 + BI_04 … BI_09 P105 P113 BO_01 P114 PWR plug-in module + 0218 0219 Ua P112 0204 0205 Ic Usyn P107 0202 0203 Ib AI plug-in module - P101 0201 Ia 0220 0221 Ub 0222 0223 Uc 0224 P115 BO_02 P116 P122 … P121 BO_05 P123 P124 External DC power supply PWR+ P125 PWR- P126 BO_Fail 8 Power Supply Grounding Bus Figure 8.2-2 Typical wiring 1 (pin-ferrule-terminal modules) PCS-9613S Differential Relay 8-5 Date: 2020-09-02 8 Hardware B01 B02 & B03 B04 B05 B06 P1 B01 B02 & B03 B04 P1 NR6106AB NR6641-4I4U Option Option Option NR6305A NR6106AB NR6641-4I4U Option NR6305A NET LC LC 01 Ia Ian 02 01 BI_01+ BI_01- 02 01 Ia Ian 02 01 BI_01+ BI_01- 02 03 Ib Ibn 04 03 BI_02+ BI_02- 04 03 Ib Ibn 04 03 BI_02+ BI_02- 04 05 Ic Icn 06 05 BI_COM BI_03 06 05 Ic Icn 06 05 BI_COM BI_03 06 07 I0 I0n 08 07 BI_04 BI_05 08 LC 07 I0 I0n 08 07 BI_04 BI_05 08 09 10 09 BI_06 BI_07 10 LC 09 10 09 BI_06 BI_07 10 BI_09 12 BI_09 12 NET 11 12 11 BI_08 11 12 11 BI_08 RX1 13 14 13 BO_01 14 RX1 13 14 13 BO_01 14 TX2 15 16 15 BO_02 16 TX2 15 16 15 BO_02 16 18 17 BO_03 18 17 18 17 BO_03 18 20 19 BO_04 20 19 Ua Uan 20 19 BO_04 20 21 Ub Ubn 22 21 BO_05 22 23 Uc Ucn 24 23 BO_Fail 24 TX1 RX2 01 1A 02 1B 03 SGND 04 2A 05 2B 06 SGND 07 08 09 10 TX1 RX2 17 19 Usyn Usynn Ua Uan 21 Ub Ubn 22 21 BO_05 22 23 Uc Ucn 24 23 BO_Fail 24 01 1A 02 1B 03 SGND 04 2A 05 2B 06 SGND SYN+ 07 SYN+ SYN- 08 SYN- SGND 09 SGND SYN-TTL 10 SYN-TTL CONSOLE 25 PWR+ PWR- 26 Ground Usyn Usynn 25 PWR+ PWR- 26 CONSOLE Ground Figure 8.2-3 Typical hardware configuration 2 (ring-ferrule-terminal modules) The following wiring is given based on above hardware configuration 8 PCS-9613S Differential Relay 8-6 Date: 2020-09-02 8 Hardware SGND 0103 485-2A 0104 485-2B 0105 SGND 0106 0107 SYN- 0108 SGND 0109 TTL 0110 Clock SYN SYN+ Optional optical or electrical Ethernet to SCADA 0102 COM 0101 485-1B COM 485-1A Multiplex RJ45 + P102 - P103 + P104 - P106 + BI_01 0206 0207 I0 0208 0209 0210 0211 0212 0213 0214 BI_02 0215 0216 0217 BI_03 + BI_04 … BI_09 P105 P113 BO_01 P114 PWR plug-in module + 0218 0219 Ua P112 0204 0205 Ic Usyn P107 0202 0203 Ib AI plug-in module - P101 0201 Ia 0220 0221 Ub 0222 0223 Uc 0224 P115 BO_02 P116 P122 … P121 BO_05 P123 P124 External DC power supply PWR+ P125 PWR- P126 BO_Fail Power Supply 8 Grounding Bus Figure 8.2-4 Typical wiring 2 (ring-ferrule-terminal modules) 8.3 CT Requirement 8.3.1 CT Types Generally there are three types of CT: high remanence, low remanence and no remanence. ⚫ High remanence: TPX, TPS, P, PX. ⚫ Low remanence: TPY, PR, and the residual magnetism does not exceed 10% of the saturation flux. PCS-9613S Differential Relay 8-7 Date: 2020-09-02 8 Hardware ⚫ No remanence: TPZ level, residual magnetism can actually be ignored. The high residual magnetism CT may have large residual magnetism. When the fault non-periodic component and residual magnetism are in the same direction, the CT saturation degree will be more serious. The following CT type checking calculation takes into account the maximum residual magnetism of CT and the maximum non periodic component on the site. 8.3.2 CT Requirement Rated secondary limit e.m.f (volts) formula: Esl = Kalf × Isn × (Rct + Rbn) Kalf Accuracy limit factor: Kalf = Ipal / Ipn Isn Rated secondary current (amps) Rct Current transformer secondary winding resistance (ohms) Sbn Rated burden (VAs) Rbn Rated resistance burden (ohms): Rbn = Sbn / Isn2 Actual secondary limit e.m.f (volts) under different fault conditions: Esl1′ = k1×Ipcf1 ×Isn×(Rct+Rb)/Ipn Esl2′ = k2×Ipcf2 ×Isn×(Rct+Rb)/Ipn Esl3′ = k3×Ipnt×Isn×(Rct+Rb)/Ipn Esl4′ = k4×Ipcf4×Isn×(Rct+Rb)/Ipn k1, k2, k3, k4 are transient factors. Ipcf1 Maximum through fault current when out-zone fault (amps) Maximum fault current through two bridge CB but not transformer when Ipcf2 8 out-zone fault (amps) Ipcf4 Maximum fault current when in-zone fault (amps) Ipnt Transformer rated primary current (amps) Ipn CT rated primary current (amps) Isn CT rated secondary current (amps) Rct Current transformer secondary winding resistance (ohms) Rb Real resistance burden (ohms): Rb = Rr + 2RL RL Resistance of a single lead from relay to the CT (ohms) Rr Impedance of relay phase current input (ohms) 1. K Value Requirement 1) Single CB connection, the following condition should be fulfilled Esl > Esl1′ PCS-9613S Differential Relay 8-8 Date: 2020-09-02 8 Hardware Esl > min (Esl3′, Esl4′) While: k1=2,k3=30,k4=1. 2) Double CB connection, the following condition should be fulfilled: Esl > Esl1′ Esl > Esl2′ Esl > min (Esl3′, Esl4′) If both CTs of double CB are low remanence type, and with the same model, then k1=2, k2=1.5, k3=30, k4=1. Otherwise: k1=2,k2=2,k3=30,k4=1. 2. Example Kalf=30, Isn=5A, Rct=1Ω, Sbn=60VA Ipcf1=40000A, RL=0.5Ω, Rr=0.1Ω, Rc=0.1Ω, Ipn=2000A, Ipnt=1500A Esl = kalf×Isn×(Rct+Rbn) = kalf×Isn×(Rct+ Sbn/Isn2) = 30×5×(1+60/25)=510V Esl1′ = k1×Ipcf1×Isn×(Rct+Rb)/Ipn = 2×Ipcf1 ×Isn×(Rct+(Rr+2×RL))/Ipn = 2×40000×5×(1+(0.1+2×0.5))/2000=420V Esl3′ = k3×Ipnt×Isn×(Rct+Rb)/Ipn =30×1500*5*(1+(0.1+2×0.5)) /2000=236.25V Thus, Esl > Esl1′ and Esl > Esl3′ 8 8.4 Plug-in Module Description The device consists of power supply module (PWR), main CPU module (CPU), AI module, BI module, BO plug-in module, CH plug-in module and NET-DSP plug-in module. Terminal definitions and application of each plug-in module are introduced as follows. 8.4.1 Human-machine Interface Module (NR6855/NR6856) The human machine interface (HMI) module is installed on the front panel of this device. It is used to observe the running status and event information on the LCD, and configure the protection settings and device operation mode. It can help the user to know the status of this device and detailed event information easily, and provide convenient and friendly access interface for the user. 8.4.2 Power Supply Module (NR6305/NR6310) The power supply module is a DC/DC converter with electrical insulation between input and PCS-9613S Differential Relay 8-9 Date: 2020-09-02 8 Hardware output. It has an input voltage range as described in Chapter 2 Technical Data. The standardized output voltages are +5Vdc and +12Vdc. The tolerances of the output voltages are continuously monitored. The +5Vdc output provides power supply for all the electrical elements that need +5Vdc power supply in this device. The use of an external miniature circuit breaker is recommended. The miniature circuit breaker must be in the on position when the device is in operation and in the off position when the device is in cold reserve. 8 Figure 8.4-1 View of power supply module Three types of power supply modules are provided: NR6305A, NR6305B and NR6310A. The NR6305B is same as the NR6305A except that the NR6305B can support at least 500ms power supply interruption. ⚫ NR6305A & NR6305B The power supply module also provides 9 binary inputs, 5 binary outputs and a device failure binary output. A 26-pin connector is fixed on the power supply module. The terminal definition of the connector is described as below. PCS-9613S Differential Relay 8-10 Date: 2020-09-02 8 Hardware Table 8.4-1 Terminal definition and description of power supply module Pin No. Symbol Description 01 BI_01+ 02 BI_01- 03 BI_02+ 04 BI_02- 05 BI_COM The common negative connection of the BI_01 to BI_09 06 BI_03 The No.3 programmable binary input 07 BI_04 The No.4 programmable binary input 08 BI_05 The No.5 programmable binary input 09 BI_06 The No.6 programmable binary input 10 BI_07 The No.7 programmable binary input 11 BI_08 The No.8 programmable binary input 12 BI_09 The No.9 programmable binary input BO_01 The No.1 programmable binary output BO_02 The No.2 programmable binary output BO_03 The No.3 programmable binary output BO_04 The No.4 programmable binary output BO_05 The No.5 programmable binary output BO_Fail The device failure signal output 25 PWR+ DC power supply positive input 26 PWR- DC power supply negative input 13 14 15 16 17 18 19 20 21 22 23 24 The No.1 programmable binary input The No.2 programmable binary input 8 Grounded connection of the power supply ⚫ NR6310A The power supply module also provides 9 binary inputs, 5 binary outputs and a device failure binary output. A 22-pin connector and a 4-pin connector are fixed on the power supply module. The terminal definition of the connector is described as below. Table 8.4-2 Terminal definition and description of power supply module Pin No. 22-pin Symbol 01 BI_01+ 02 BI_01- 03 BI_02+ 04 BI_02- 05 BI_COM Description The No.1 programmable binary input The No.2 programmable binary input The common negative connection of the BI_01 to BI_09 PCS-9613S Differential Relay 8-11 Date: 2020-09-02 8 Hardware 06 BI_03 The No.3 programmable binary input 07 BI_04 The No.4 programmable binary input 08 BI_05 The No.5 programmable binary input 09 BI_06 The No.6 programmable binary input 10 BI_07 The No.7 programmable binary input 11 BI_08 The No.8 programmable binary input 12 BI_09 The No.9 programmable binary input BO_01 The No.1 programmable binary output BO_02 The No.2 programmable binary output BO_03 The No.3 programmable binary output BO_04 The No.4 programmable binary output BO_05 The No.5 programmable binary output BO_Fail The device failure signal output 25 PWR+ DC power supply positive input 26 PWR- DC power supply negative input 13 14 15 16 17 18 19 20 21 22 23 4-pin 24 Grounded connection of the power supply The standard rated voltage of the PWR module is self-adaptive to 88~300Vdc or 88~275Vac. For a non-standard rated voltage power supply module please specify when place order, and check if the rated voltage of power supply module is the same as the voltage of power source before the device being put into service. 8 The PWR module a grounding screw for device grounding. The grounding screw shall be connected to grounding screw and then connected to the earth copper bar of panel via dedicated grounding wire. Effective grounding is the most important measure for a device to prevent EMI, so effective grounding must be ensured before the device is put into service. 8.4.3 CPU Module (NR6106) The CPU module is the central part of this device, and contains a multi-core 32-bit powerful processor and some necessary electronic elements. This powerful processor performs all of the functions for this device: protection function, communication function, human-machine interface function and so on. There are several A/D conversion circuits on this module, which are used to PCS-9613S Differential Relay 8-12 Date: 2020-09-02 8 Hardware convert the AC analog signals to corresponding DC signals for fulfilling the demand of the electrical level standard. A high-accuracy clock chip is contained in this module, it provide accurate current time for this device. The main functional details of the CPU module are listed as below: ⚫ Protection calculation and logical judgment function The CPU module can calculate protective elements (such as overcurrent element) on the basis of the analog sampled values (voltages and currents) and binary inputs, then it does logical judgment function and decides whether the device needs to trip or close. ⚫ Communication function The CPU module can effectively manage all communication procedures, and reliably send out some useful information through its various communication interfaces. These interfaces are used to communicate with a SAS or a RTU. It also can communicate with the human machine interface module. If an event occurs (such as SOE, protective tripping event etc.), this module will send out the relevant event information through these interfaces, and make it be easily observed by the user. ⚫ Auxiliary calculation Based on the voltage and current inputs, the CPU module also can calculate out the metering values, such as active power, reactive power and power factor etc. All these values can be sent to a SAS or a RTU through the communication interfaces. ⚫ Human-machine interface function This module can respond the commands from the keypad of this device and show the results on the LCD and LED indicators of this device. It also can show the operation situation and event information for the users through the LCD and LED indicators. ⚫ Time synchronization This module has a local clock chip and an interface to receive time synchronized signals from external clock source. These signals include PPS (pulse per second) signal and IRIG-B signal. Basing on the timing message (from SAS or RTU) and the PPS signal, or basing on the IRIG-B signal, this module can synchronize local clock with the standard clock. PCS-9613S Differential Relay 8-13 Date: 2020-09-02 8 8 Hardware Figure 8.4-2 View of CPU module Do NOT look into the end of an optical fiber connected to an optical port. Do NOT look into an optical port/connector. A direct sight to laser light may cause temporary or permanent blindness. 8 The configuration and terminal definition of the CPU modules are listed in following table. Table 8.4-3 Configuration and terminal definition of CPU module Module ID Memory Interface Terminal No. 2 RJ45 Ethernet Ethernet 2 SFP Ethernet communication Optical 2 Fiber-Optic NR6106AB 1G DDR Usage RS-485 RS-485 01 A 02 B 03 SGND 04 A 05 B 06 SGND Physical Layer Twisted pair wire channel for Optical fiber pilot protection (single-mode) To SCADA Twisted pair wire To SCADA or printer Twisted pair wire PCS-9613S Differential Relay 8-14 Date: 2020-09-02 8 Hardware RS-485 TTL 07 SYN+ 08 SYN- To clock 09 SGND synchronization 10 SYN-TTL 1 RJ45 Ethernet Cable Cable For debugging Twisted pair wire The correct connection is shown in Figure 8.4-3. Generally, the shielded cable with two pairs of twisted pairs inside shall be applied. One pair of the twisted pairs are respectively used to connect the “+” and “–” terminals of difference signal. The other pair of twisted pairs are used to connect the signal ground of the communication interface. The module reserves a free terminal for all the communication ports. The free terminal has no connection with any signal of the device, and it is used to connect the external shields of the cable when connecting multiple devices in series. The external shield of the cable shall be grounded at one of the ends only. Twisted pair wire 01 B 02 SGND 03 COM A Twisted pair wire SYN+ 01 SYN- 02 SGND 03 Clock SYN To the screen of other coaxial cable with single point earthing 04 04 Cable 05 TXD 06 SGND 07 PRINT RTS Figure 8.4-3 Connection of communication terminal 8 Figure 8.4-4 Jumpers of printer/RS-485 port PCS-9613S Differential Relay 8-15 Date: 2020-09-02 8 Hardware The 2nd RS-485 port also can be configured as a printer port through the jumpers “J10” and “J11”. Jumper RS-485 Printer J10 Pin-1 and Pin-2 are connected Pin-2 and Pin-3 are connected J11 Pin-1 and Pin-2 are connected Pin-2 and Pin-3 are connected 8.4.4 Analog Input Module (NR6641) The analog input module is applicable for power plant or substation with conventional VT and CT, and it can transform high AC input values to relevant low AC output value, which are suited to the analog inputs of the CPU module. The transformers are used both to step-down the currents and voltages to levels appropriate to the device’s electronic circuitry and to provide effective isolation between this device and the power system. A low pass filter circuit is connected to each transformer (CT or VT) secondary circuit for reducing the noise of each analog AC input signal. For the analog input module, if the plug is not put in the socket, external CT circuit is closed itself. Just shown as below. Socket Plug In Out 8 plug is not put in the socket In Out Put the plug in the socket Figure 8.4-5 Schematic diagram of CT circuit automatically closed There are several types of analog input modules. The rated current is adaptive (1A/5A). Please PCS-9613S Differential Relay 8-16 Date: 2020-09-02 8 Hardware declare which kind of AI module is needed before ordering. Maximum linear range of the current converter is 40In. ⚫ NR6641-4I4U: 4CT+4VT The terminal definition of the analog input module is shown as below. NR6641-4I4U 01 Ia Ian 02 03 Ib Ibn 04 05 Ic Icn 06 07 I0 I0n 08 09 10 11 12 13 14 15 17 16 Usyn Usynn 18 19 Ua Uan 20 21 Ub Ubn 22 23 Uc Ucn 24 Figure 8.4-6 Terminal definition of analog input module 8 NEVER allow the current transformer (CT) secondary circuit connected to this device to be opened while the primary system is energized. The opened CT secondary circuit will produce a dangerously high voltage. If this safety precaution is disregarded, personal death, severe personal injury or considerable equipment damage will occur. Each analog input channel can be configured according to practical application through PCS-Studio. Some connection examples of the current transformers and voltage transformers which are supported by this relay are shown in this section. If one of the analog inputs has no input in a practical engineering, the relevant input terminals should be disconnected. PCS-9613S Differential Relay 8-17 Date: 2020-09-02 8 Hardware 1. Current connections examples A B C A B C A B C Ia Ia Ia Ian Ian Ian Ib Ib Ib Ibn Ibn Ibn Ic Ic Ic Icn Icn Icn I0 I0 I0n I0n I0 I0n (1) (2) (3) Figure 8.4-7 Current connection examples Where: (1) Current connections to three current transformers with a star-point connection for ground current. (2) Current connections to three current transformers with a separate ground current transformer (summation current transformer or core balance current transformer). (3) Current connections to two current transformers with a separate ground current transformer (summation current transformer or core balance current transformer), only for ungrounded or compensated networks. 2. Voltage connections examples 8 A B C 52 52 52 Ua Ub Uc Un Usyn Usynn Figure 8.4-8 Voltage connection examples Where: Voltage connections to three star-connected voltage transformers and additionally to any PCS-9613S Differential Relay 8-18 Date: 2020-09-02 8 Hardware phase/phase-to-phase voltage (for synchronism check, just takes phase-C line voltage as an example). 8.4.5 Binary Input Module (NR6601/NR6610) The binary input module contains some binary inputs which are used to monitor the contact positions of the corresponding bay, and all the binary inputs are configurable through PCS-Studio according to practical application. There are two kinds of BI modules available, NR6601A and NR6610A. The binary input module can respectively provide 25 or 32 binary inputs. The rated voltage of binary input is optional: 24Vdc, 30Vdc, 48Vdc, 110Vdc, 125V, 220V, 110Vac or 220Vac (@50Hz), which must be specified when placed order. It is necessary to check whether the rated voltage of binary input module complies with site DC power supply rating before put this device in service. Voltage 300 157.5 8 138.6 125 110 78.75 69.3 62.5 55 Operation 30.24 24 15.12 12 0 Operation uncertain No operation 24V 48V 110V 125V 220V 250V Figure 8.4-9 Voltage dependence for binary inputs PCS-9613S Differential Relay 8-19 Date: 2020-09-02 8 Hardware ⚫ NR6601A Each BI module is with a 26-pin connector for 25 binary inputs which share one common negative power input and can be configurable. The pickup voltages and dropout voltages of the binary inputs are settable by the setting [U_Pickup_BI] and [U_Dropoff_BI], and the range is from 50%Un to 80%Un. 01 BI_01 BI_02 02 03 BI_03 BI_04 04 05 BI_05 BI_06 06 07 BI_07 BI_08 08 09 BI_09 BI_10 10 11 BI_11 BI_12 12 13 BI_13 BI_14 14 15 BI_15 BI_16 16 17 BI_17 BI_18 18 19 BI_19 BI_20 20 21 BI_21 BI_22 22 23 BI_23 BI_24 24 25 BI_25 BI_COM 26 Figure 8.4-10 View of binary input module (NR6601A) 8 A 26-pin connector is fixed on the binary input module. The terminal definition of the connector is described as below. Table 8.4-4 Terminal definition and description of binary input module (NR6601A) Pin No. Symbol Description 01 BI_01 The No.1 programmable binary input 02 BI_02 The No.2 programmable binary input 03 BI_03 The No.3 programmable binary input 04 BI_04 The No.4 programmable binary input 05 BI_05 The No.5 programmable binary input 06 BI_06 The No.6 programmable binary input 07 BI_07 The No.7 programmable binary input 08 BI_08 The No.8 programmable binary input 09 BI_09 The No.9 programmable binary input 10 BI_10 The No.10 programmable binary input PCS-9613S Differential Relay 8-20 Date: 2020-09-02 8 Hardware ⚫ 11 BI_11 The No.11 programmable binary input 12 BI_12 The No.12 programmable binary input 13 BI_13 The No.13 programmable binary input 14 BI_14 The No.14 programmable binary input 15 BI_15 The No.15 programmable binary input 16 BI_16 The No.16 programmable binary input 17 BI_17 The No.17 programmable binary input 18 BI_18 The No.18 programmable binary input 19 BI_19 The No.19 programmable binary input 20 BI_20 The No.20 programmable binary input 21 BI_21 The No.21 programmable binary input 22 BI_22 The No.22 programmable binary input 23 BI_23 The No.23 programmable binary input 24 BI_24 The No.24 programmable binary input 25 BI_25 The No.25 programmable binary input 26 BI_COM The common negative connection of the BI_01 to BI_25. NR6610A Each BI module is with two 18-pin connectors for 32 binary inputs. The first 16 binary inputs share one common negative power input and the last 16 binary inputs share another common negative power input. All binary inputs are configurable. The pickup voltages and dropout voltages of the binary inputs are settable by the setting [U_Pickup_BI] and [U_Dropoff_BI], and the range is from 50%Un to 80%Un. 8 PCS-9613S Differential Relay 8-21 Date: 2020-09-02 8 Hardware 01 BI_01 19 BI_17 02 BI_02 20 BI_18 03 BI_03 21 BI_19 04 BI_04 22 BI_20 05 BI_05 23 BI_21 06 BI_06 24 BI_22 07 BI_07 25 BI_23 08 BI_08 26 BI_24 09 BI_09 27 BI_25 10 BI_10 28 BI_26 11 BI_11 29 BI_27 12 BI_12 30 BI_28 13 BI_13 31 BI_29 14 BI_14 32 BI_30 15 BI_15 33 BI_31 16 BI_16 34 BI_32 17 BI_COM 35 BI_COM 18 BI_COM 36 BI_COM Figure 8.4-11 View of binary input module (NR6610A) The terminal definition of the connector is described as below. Table 8.4-5 Terminal definition and description of binary input module (NR6610A) Pin No. 8 18-pin Pin No. Symbol Description 01 BI_01 The No.1 programmable binary input 02 BI_02 The No.2 programmable binary input 03 BI_03 The No.3 programmable binary input 04 BI_04 The No.4 programmable binary input 05 BI_05 The No.5 programmable binary input 06 BI_06 The No.6 programmable binary input 07 BI_07 The No.7 programmable binary input 08 BI_08 The No.8 programmable binary input 09 BI_09 The No.9 programmable binary input 10 BI_10 The No.10 programmable binary input 11 BI_11 The No.11 programmable binary input 12 BI_12 The No.12 programmable binary input 13 BI_13 The No.13 programmable binary input 14 BI_14 The No.14 programmable binary input 15 BI_15 The No.15 programmable binary input 16 BI_16 The No.16 programmable binary input PCS-9613S Differential Relay 8-22 Date: 2020-09-02 8 Hardware 17 BI_COM The common negative connection of the BI_01 to BI_16. 19 BI_17 The No.17 programmable binary input 20 BI_18 The No.18 programmable binary input 21 BI_19 The No.19 programmable binary input 22 BI_20 The No.20 programmable binary input 23 BI_21 The No.21 programmable binary input 24 BI_22 The No.22 programmable binary input 25 BI_23 The No.23 programmable binary input 26 BI_24 The No.24 programmable binary input 27 BI_25 The No.25 programmable binary input 28 BI_26 The No.26 programmable binary input 29 BI_27 The No.27 programmable binary input 30 BI_28 The No.28 programmable binary input 31 BI_29 The No.29 programmable binary input 32 BI_30 The No.30 programmable binary input 33 BI_31 The No.31 programmable binary input 34 BI_32 The No.32 programmable binary input BI_COM The common negative connection of the BI_17 to BI_32. 18 18-pin 35 36 8.4.6 Binary Output Module (NR6651/NR6652/NR6660/NR6663) The binary output module consists of some necessary contact outputs, and the binary outputs are used as tripping and closing (protection, auto-reclosing or remote control) outputs or signal outputs. It can receive tripping commands or closing commands from the CPU module, and then executes these commands. It also can output some alarm signals from the CPU module. The device can provide five types of binary output modules: NR6651A, NR6651B, NR6652A, NR6660A and NR6663A. ⚫ 8 NR6651A The NR6651A provides 13 normal open contacts (NOC) with pickup relay control. A 26-pin connector is fixed on the binary input module. The terminal definition of the connector is shown as below. PCS-9613S Differential Relay 8-23 Date: 2020-09-02 8 Hardware BO_01 01 02 BO_02 03 04 BO_03 05 06 BO_04 07 08 BO_05 09 10 BO_06 11 12 BO_07 13 14 BO_08 15 16 BO_09 17 18 BO_10 19 20 BO_11 21 22 BO_12 23 24 BO_13 25 26 Figure 8.4-12 View of binary output module NR6651A ⚫ NR6651B The NR6651B provides 11 normal open contacts (NOC, the first 11 contacts) and 2 normal close contacts (NCC, the last 2 contacts). These binary outputs are controlled by pickup relay. A 26-pin connector is fixed on the binary input module. The terminal definition of the connector is shown in as below. 8 PCS-9613S Differential Relay 8-24 Date: 2020-09-02 8 Hardware BO_01 01 02 BO_02 03 04 BO_03 05 06 BO_04 07 08 BO_05 09 10 BO_06 11 12 BO_07 13 14 BO_08 15 16 BO_09 17 18 BO_10 19 20 BO_11 21 22 BO_12 23 24 BO_13 25 26 Figure 8.4-13 View of binary output module NR6651B ⚫ NR6652A The NR6652A provides 4 normal open contacts (NOC, the first 4 contacts) with heavy capacity for controlling the circuit breaker directly, and provides 4 general normal open contacts (NOC, the last 4 contacts). These binary outputs are controlled by pickup relay. A 26-pin connector is fixed on the binary input module. 8 The terminal definition of the connector is shown in as below. PCS-9613S Differential Relay 8-25 Date: 2020-09-02 8 Hardware BO_01 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 BO_05 19 20 BO_06 21 22 BO_07 23 24 BO_08 25 26 BO_02 BO_03 BO_04 Figure 8.4-14 View of binary output module NR6652A ⚫ NR6660A The NR6660A provides 17 normally open contacts (NOC, the first 17 contacts) and 2 normally close contacts (NCC, the 16th and the 17th contacts). These binary outputs are controlled by pickup relay. Two 18-pin connectors are fixed on the binary input module. 8 The terminal definition of the connector is shown in Figure 8.4-15. PCS-9613S Differential Relay 8-26 Date: 2020-09-02 8 Hardware BO_01 01 02 BO_02 03 04 BO_03 05 06 BO_04 07 08 BO_05 09 10 BO_06 11 12 BO_07 13 14 BO_08 15 16 BO_09 17 18 BO_10 19 20 BO_11 21 22 BO_12 23 24 BO_13 25 26 BO_14 27 28 BO_15 29 30 BO_16 32 31 BO_16 33 BO_17 35 34 BO_17 36 Figure 8.4-15 View of binary output module (NR6660A) ⚫ NR6663A The NR6663A provides 4 normal open contacts (NOC, the first 4 contacts) with heavy capacity for controlling the circuit breaker directly, and provides 4 general normal open contacts (NOC, the last 4 contacts). These binary outputs are controlled by pickup relay. Two 18-pin connectors are fixed on the binary input module. 8 The terminal definition of the connector is shown as below. PCS-9613S Differential Relay 8-27 Date: 2020-09-02 8 Hardware 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 BO_01 BO_02 BO_03 BO_04 BO_05 BO_06 BO_07 BO_08 General tripping/signaling contact 02 03 Heavy-capacity tripping contact 01 Figure 8.4-16 View of binary output module (NR6663A) Each binary output can be set as a specified tripping output contact or a signal output contact through PCS-Studio according to practical application. 8 8.4.7 Binary Input/Output Module (NR6661) NR6661A module provides both binary inputs and binary outputs. Two 18-pin connectors are fixed on the NR6661A module: The upper 18-pin connector provides 16 binary inputs, the supported rated voltages of binary inputs are listed in Chapter 2 Technical Data. The lower 18-pin connector provides 6 normally open contacts (NOC) and 2 normally open contacts & normally closed contacts (NOC/NCC). These binary outputs are controlled by pickup relay. PCS-9613S Differential Relay 8-28 Date: 2020-09-02 8 Hardware 01 BI_01 02 BI_02 03 BI_03 04 BI_04 05 BI_05 BO_01 19 20 06 BI_06 BO_02 21 22 07 BI_07 BO_03 23 24 08 BI_08 BO_04 25 26 09 BI_09 BO_05 27 28 10 BI_10 BO_06 29 30 11 BI_11 BO_07_NO 12 BI_12 BO_07_NC 13 BI_13 BO_08_NO 14 BI_14 BO_08_NC 15 BI_15 16 BI_16 17 18 32 31 33 35 34 36 COM(01-16) COM(01-16) Figure 8.4-17 View of binary input/output module (NR6661A) The terminal definition of NR6661A is described as below. Table 8.4-6 Terminal definition and description of NR6661A Pin No. 18-pin Symbol Description 01 BI_01 The No.1 programmable binary input 02 BI_02 The No.2 programmable binary input 03 BI_03 The No.3 programmable binary input 04 BI_04 The No.4 programmable binary input 05 BI_05 The No.5 programmable binary input 06 BI_06 The No.6 programmable binary input 07 BI_07 The No.7 programmable binary input 08 BI_08 The No.8 programmable binary input 09 BI_09 The No.9 programmable binary input 10 BI_10 The No.10 programmable binary input 11 BI_11 The No.11 programmable binary input 12 BI_12 The No.12 programmable binary input 13 BI_13 The No.13 programmable binary input 14 BI_14 The No.14 programmable binary input 15 BI_15 The No.15 programmable binary input 16 BI_16 The No.16 programmable binary input PCS-9613S Differential Relay 8 8-29 Date: 2020-09-02 8 Hardware 17 COM- 18 (01-16) 19 20 21 22 23 24 25 26 18-pin 27 28 29 30 BO_01 BO_03 The No.03 binary output contact. It is a normally open contact. BO_04 The No.04 binary output contact. It is a normally open contact. BO_05 The No.05 binary output contact. It is a normally open contact. BO_06 The No.06 binary output contact. It is a normally open contact. BO_07 34 36 (NOC). The No.02 binary output contact. It is a normally open contact. 33 35 The No.01 binary output contact. It is a normally open contact BO_02 31 32 The common negative connection of the BI_01 to BI_16. BO_08 The No.07 binary output contact. It can be selected as a normally open contact or a normally closed contact (NCC). The No.08 binary output contact. It can be selected as a normally open contact or a normally closed contact. 8 PCS-9613S Differential Relay 8-30 Date: 2020-09-02 9 Settings 9 Settings Table of Contents 9.1 Global Settings ................................................................................................ 9-1 9.1.1 System Settings.................................................................................................................... 9-1 9.1.2 Device Settings..................................................................................................................... 9-2 9.1.3 Communication Settings ...................................................................................................... 9-3 9.1.4 Disturbance Fault Recording Settings ............................................................................... 9-16 9.1.5 Label Settings ..................................................................................................................... 9-16 9.1.6 Clock Synchronization Settings.......................................................................................... 9-17 9.1.7 OutMap Settings ................................................................................................................. 9-19 9.1.8 Supervision Settings........................................................................................................... 9-19 9.2 Protection Settings ........................................................................................ 9-20 9.2.1 Fault Detector (FD)............................................................................................................. 9-20 9.2.2 Optical Pilot Channel (FO) ................................................................................................. 9-20 9.2.3 Current Differential Protection (87L) .................................................................................. 9-21 9.2.4 Phase Overcurrent Protection Settings.............................................................................. 9-22 9.2.5 Earth Fault Overcurrent Protection Settings ...................................................................... 9-38 9.2.6 Negative-sequence Overcurrent Protection Settings......................................................... 9-54 9.2.7 RMS Overcurrent Protection Settings ................................................................................ 9-59 9.2.8 Broken Conductor Protection (46BC) ................................................................................ 9-63 9.2.9 Phase Overvoltage Protection Settings ............................................................................. 9-63 9.2.10 Residual Overvoltage Protection Settings ....................................................................... 9-67 9.2.11 Negative-sequence Overvoltage Protection Settings ...................................................... 9-68 9.2.12 Positive-sequence Overvoltage Protection Settings ........................................................ 9-68 9.2.13 Phase Undervoltage Protection Settings ......................................................................... 9-69 9.2.14 Frequency Protection Settings ......................................................................................... 9-73 9.2.15 Reverse Power Protection Settings ................................................................................. 9-76 9.2.16 Undercurrent Settings ...................................................................................................... 9-77 PCS-9613S Differential Relay 9-a Date: 2020-09-02 9 9 Settings 9.2.17 Breaker Failure Protection Settings ................................................................................. 9-78 9.2.18 Switch-on-to-Fault ProtectionSettings.............................................................................. 9-79 9.2.19 Thermal Overload Protection Settings ............................................................................. 9-80 9.2.20 Transfer Trip Settings ....................................................................................................... 9-81 9.2.21 Automatic Reclosure Settings .......................................................................................... 9-81 9.2.22 Fault Location Settings ..................................................................................................... 9-83 9.3 Measurement and Control Settings ............................................................. 9-84 9.3.1 Function Settings ................................................................................................................ 9-84 9.3.2 Synchronism Check Settings ............................................................................................. 9-84 9.3.3 Double Point Status Settings ............................................................................................. 9-86 9.3.4 Control Settings .................................................................................................................. 9-88 9.3.5 Interlocking Logic Settings ................................................................................................. 9-89 9.4 Logic Links ..................................................................................................... 9-91 9.4.1 Function Links .................................................................................................................... 9-91 9.4.2 GOOSE Receiving Links .................................................................................................... 9-91 List of Tables Table 9.1-1 System settings ....................................................................................................... 9-1 Table 9.1-2 Device settings......................................................................................................... 9-2 Table 9.1-3 General communication settings ........................................................................... 9-3 Table 9.1-4 IEC61850 communication settings ........................................................................ 9-7 Table 9.1-5 DNP communication settings ................................................................................. 9-8 9 Table 9.1-6 IEC103 communication settings .......................................................................... 9-14 Table 9.1-7 GOOSE communication settings ......................................................................... 9-16 Table 9.1-8 Disturbance fault recording settings ................................................................... 9-16 Table 9.1-9 Label settings ......................................................................................................... 9-16 Table 9.1-10 Clock synchronization settings ......................................................................... 9-17 Table 9.1-11 Outmap settings ................................................................................................... 9-19 Table 9.1-11 Supervision settings ............................................................................................ 9-19 Table 9.2-1 Settings of fault detector ...................................................................................... 9-20 PCS-9613S Differential Relay 9-b Date: 2020-09-02 9 Settings Table 9.2-2 Settings of optical pilot channel .......................................................................... 9-21 Table 9.2-3 Settings of current differential protection .......................................................... 9-21 Table 9.2-4 Settings of phase overcurrent protection ........................................................... 9-22 Table 9.2-5 Settings of earth fault overcurrent protection .................................................... 9-38 Table 9.2-6 Settings of negative-sequence overcurrent protection..................................... 9-54 Table 9.2-7 Settings of RMS overcurrent protection ............................................................. 9-59 Table 9.2-5 Settings of broken conductor protection ............................................................ 9-63 Table 9.2-8 Settings of phase overvoltage protection ........................................................... 9-64 Table 9.2-9 Settings of residual overvoltage protection ....................................................... 9-67 Table 9.2-10 Settings of negative-sequence overvoltage protection .................................. 9-68 Table 9.2-11 Settings of positive-sequence overvoltage protection.................................... 9-69 Table 9.2-12 Settings of phase undervoltage protection ...................................................... 9-69 Table 9.2-13 Settings of frequency protection ....................................................................... 9-73 Table 9.2-14 Settings of reverse power protection ................................................................ 9-76 Table 9.2-15 Settings of undercurrent protection .................................................................. 9-77 Table 9.2-16 Settings of breaker failure protection................................................................ 9-78 Table 9.2-17 Settings of SOTF protection ............................................................................... 9-79 Table 9.2-19 Settings of thermal overload protection ........................................................... 9-80 Table 9.2-18 Settings of transfer trip ....................................................................................... 9-81 Table 9.2-19 Settings of AR ...................................................................................................... 9-81 Table 9.2-20 Settings of fault location ..................................................................................... 9-83 Table 9.4-1 Function links ......................................................................................................... 9-91 Table 9.4-2 GOOSE receiving links.......................................................................................... 9-91 PCS-9613S Differential Relay 9-c Date: 2020-09-02 9 9 Settings 9 PCS-9613S Differential Relay 9-d Date: 2020-09-02 9 Settings 9.1 Global Settings 9.1.1 System Settings ⚫ Access path: MainMenu Settings Global Settings System Settings Table 9.1-1 System settings No. Settings Default Range value Unit Step Remark The number of active setting group, 1 Active_Grp 1~30 1 - 1 several setting groups can be configured for protection settings, and only one is active at a time. 2 PrimaryEquip_Name Max 20 characters Name - - - of the protected primary equipment, such as feeder, transformer, etc. 3 Opt_SysFreq 50, 60 50Hz Hz The system frequency. 4 Prot.I1n 0~9999 1000 A 1 5 Prot.I2n 1, 5 1 A - 6 Neu.I1n 0~9999 1000 A 1 7 Neu.I2n 1, 5 1 A - 8 Prot.U1n 0~1100 10 kV 0.001 Rated primary value of protection VT 9 Prot.U2n 1~200 100 V 0.001 Rated secondary value of protection VT 10 Syn.U1n 0~1100 10 kV 0.001 Rated primary value of synchro-check VT 11 Syn.U2n 1~200 100 V 0.001 Rated primary value of protection phase CT Rated secondary value of protection phase CT Rated primary value of the No.1 zero-sequence CT Rated secondary value of the No.1 zero-sequence CT Rated secondary value of synchro-check VT The logic setting determines that whether 12 Prot.En_RevCT Disabled; Enabled the CT polarity of the three-phase Disabled - - protection CT is reversed. Enabled: The CT polarity is reversed Disabled: The CT polarity is not reversed The logic setting determines that whether 13 Neu.En_RevCT Disabled; Enabled the Disabled - - CT polarity of the No.1 zero-sequence CT is reversed. Enabled: The CT polarity is reversed Disabled: The CT polarity is not reversed 14 Opt_PhSeq ABC; ACB ABC - PCS-9613S Differential Relay - This setting informs the device of the actual system phase sequence, either 9-1 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Remark ABC or ACB. CT and VT inputs on the device, labelled as A, B and C, must be connected to system phase A, B and C for correct operation. 15 Disabled; En_VT Enabled Enabled - - Logic setting to put VT into service 9.1.2 Device Settings ⚫ Access path: MainMenu Settings Global Settings Device Settings Table 9.1-2 Device settings No. Settings Range Default value Unit Step Remark Logic setting to enable/disable the 1 En_DebugPort Disabled Enabled Enabled - - debugging port. Used for debugging tool connection, program download, variable debugging, etc. 2 En_TelnetPort Disabled Enabled Enabled - - Logic setting to enable/disable the Telnet port. Enabled: Connecting to the device via 3 En_VirtualLCDPort Disabled Enabled Enabled - - the software Teldevice is supported Disabled: Connecting to the device via the software Teldevice is not supported Enabled: printing data to the software 4 En_NetPrintPort Disabled Enabled Enabled - - Netpts is supported Disabled: printing data to the software Netpts is not supported 9 5 En_NoCtrlPwd 6 Ctrl_Password 7 Un_BinaryInput Disabled Enabled - - 000~999 111 - - 24~250 220 V - DC - - Enabled DC 8 Opt_Pwr_BI AC50Hz AC60Hz 9 U_Pickup_BI 50%Un~80%Un 63 % 0.1 10 U_DropOut_BI 50%Un~80%Un 55 % 0.1 11 Mon_Window_Jitter 0.000~500.000 1 0.001 s Override control password via local LCD The control password via local LCD. This setting is used to set the voltage level of the binary input module. Power supply mode of binary input module This setting is used to set pickup voltage of the binary input module. This setting is used to set drop-out voltage of the binary input module. Monitoring window of binary input jitter PCS-9613S Differential Relay 9-2 Date: 2020-09-02 9 Settings No. Settings Range Default value Unit Step Remark processing 12 Num_Blk_Jitter 2~500000 10 1 - 13 Blk_Window_Jitter 0.000~500.000 1 0.001 s 14 Num_Reblk_Jitter 1~500000 10 1 - Times threshold to block binary input status change due to jitter Blocking window of binary input status change due to jitter Times threshold to initiate immediately another blocking window of binary input status change due to continuous jitter 15 En_Jitter_Blk Disabled Enabled The logic setting to enable/disable the Disabled - - jitter processing function in case of binary input voltage variation 9.1.3 Communication Settings 9.1.3.1 General Communication Settings ⚫ Access path: MainMenu Settings Global Settings Comm Settings General Comm Settings Table 9.1-3 General communication settings No. Settings 1 IP_LAN1 2 Mask_LAN1 3 IP_LAN2 4 Mask_LAN2 5 En_LAN2 6 IP_LAN3 7 Mask_LAN3 8 En_LAN3 9 IP_LAN4 10 Mask_LAN4 11 En_LAN4 Range 0.0.0.0~ 255.255.255.255 0.0.0.0~ 255.255.255.255 0.0.0.0~ 255.255.255.255 0.0.0.0~ 255.255.255.255 Disabled Enabled 0.0.0.0~ 255.255.255.255 0.0.0.0~ 255.255.255.255 Disabled Enabled 0.0.0.0~ 255.255.255.255 0.0.0.0~ 255.255.255.255 Disabled Default value Unit Step 198.120.0.100 - - 255.255.0.0 - - 198.121.0.100 - - 255.255.0.0 - - Enabled - - 198.122.0.100 - - 255.255.0.0 - - Disabled - - 198.123.0.100 - - 255.255.0.0 - - Disabled - - PCS-9613S Differential Relay Remark IP address of Ethernet port A Subnet mask of Ethernet port A IP address of Ethernet port B Subnet mask of Ethernet port B Put Ethernet port B into service IP address of Ethernet port C Subnet mask of Ethernet port C Put Ethernet port C into service IP address of Ethernet port D Subnet mask of Ethernet port D Put Ethernet port D into 9-3 Date: 2020-09-02 9 9 Settings No. Settings Range Default value Unit Step Enabled 12 Gateway 0.0.0.0~ 255.255.255.255 Remark service 0.0.0.0 - - 19200 bps - Disabled - - IP address of the gateway (router) 4800 9600 13 Baud_Printer 19200 38400 Baud rate of printer port 57600 115200 14 En_AutoPrint Disabled Enabled Enable/disable Communication 15 Protocol_RS485-1 IEC103 Modbus automatic printing function protocol of rear RS-485 serial port 1. IEC103 - - IEC103: IEC60870-5-103 protocol Modbus: Modbus protocol Communication 16 Protocol_RS485-2 IEC103 Modbus protocol of rear RS-485 serial port 2. IEC103 - - IEC103: IEC60870-5-103 protocol Modbus: Modbus protocol 4800 9600 17 Baud_RS485-1 19200 38400 19200 bps - 19200 bps - Baud rate of rear RS-485 serial port 1. 57600 115200 4800 9600 18 Baud_RS485-2 19200 38400 Baud rate of rear RS-485 serial port 2. 57600 9 115200 Communication 19 Addr_RS485-1 0~255 100 - 1 address between the device and the SCADA or RTU via RS-485 serial port 1. Communication 20 Addr_RS485-2 0~255 100 - 1 address between the device and the SCADA or RTU via RS-485 serial port 2. 21 Cfg_NetPorts_Bond 0~255 0 - - The setting is used to set the Ethernet ports that are used PCS-9613S Differential Relay 9-4 Date: 2020-09-02 9 Settings No. Settings Range Default value Unit Step Remark as hot standby each other. Normal; 22 B01.Opt_NetMode The network method of the 1-2:Normal,3-4:HSR; Normal 1-2:Normal,3-4:PRP; - - CPU module located in slot No.1 1-2:Normal,3-4:RSTP The setting is used to set IP address of syslog server 01, and the device can upload audit log to syslog server. 23 IP_SyslogServer01 000.000.000.000~ 255.255.255.255 The setting is invalid unless 0.0.0.0 - - cyber security is configured in the device. Syslog is a communication protocol for message logging, it is used for security auditing in this device. The setting is used to set IP address of syslog server 02, and the device can upload audit log to syslog server. 24 IP_SyslogServer02 000.000.000.000~ 255.255.255.255 The setting is invalid unless 0.0.0.0 - - cyber security is configured in the device. Syslog is a communication protocol for message logging, it is used for security auditing in this device. The setting is used to set IP address of syslog server 03, and the device can upload audit log to syslog server. 25 IP_SyslogServer03 000.000.000.000~ 255.255.255.255 The setting is invalid unless 0.0.0.0 - - cyber security is configured in the device. Syslog is a communication protocol for message logging, it is used for security auditing in this device. The setting is used to set IP 26 IP_SyslogServer04 000.000.000.000~ 255.255.255.255 address of syslog server 04, 0.0.0.0 - - and the device can upload audit log to syslog server. The setting is invalid unless PCS-9613S Differential Relay 9-5 Date: 2020-09-02 9 9 Settings No. Settings Range Default value Unit Step Remark cyber security is configured in the device. Syslog is a communication protocol for message logging, it is used for security auditing in this device. 1. [Cfg_NetPorts_Bond] The setting is used to configure dual-networks switching, and it means that no dual-networks switching is created when the setting is set as “0”. The device supports a bond between any two Ethernet ports, and the bond among three or above Ethernet ports is impermissible. The devices communicate with SAS by station level network. In order to ensure reliable communication, dual networks (i.e., network 1 and network 2) are adopted. Another special communication mode based on dual networks is that Ethernet port 1 and Ethernet port 2 of the device own the same IP address and MAC address, and network 1 and network 2 are used as hot standby each other. When both network 1 and network 2 are normal, any of them is used to communicate between the device and SAS. The device will automatically switch to the other healthy network when one network is abnormal, which will not affect normal communication. Taking a CPU module with four Ethernet ports as an example, each bit is corresponding with an Ethernet port, i.e., Bit0, Bit1, Bit2 and Bit3 are corresponding with Ethernet port 1, Ethernet port 2, Ethernet port 3 and Ethernet port 4 respectively. If a bond between Ethernet port 1 and Ethernet 2 is created, the setting [Cfg_NetPorts_Bond] is set as “3”. The specific setting is as below. Ethernet port 1 Port 4 Port 3 Port 2 Port 1 Bit 3 Bit 2 Bit 1 Bit 0 0 0 1 1 Binary Setting Value 0011 3 Port 4 Port 3 Port 2 Port 1 Bonding Bonding Bit 3 Bit 2 Bit 1 Bit 0 1 0 0 1 Binary Setting Value 1001 9 Ethernet port 2 Port 4 Port 3 Port 2 Port 1 Bit 3 Bit 2 Bit 1 Bit 0 0 1 0 1 Binary Setting Value 0101 5 Port 4 Port 3 Port 2 Port 1 Bonding Bonding Bit 3 Bit 2 Bit 1 Bit 0 0 1 1 0 Binary Setting Value 0110 6 Ethernet port 3 Port 4 Port 3 Port 2 Port 1 9 Bit 3 Bit 2 Bit 1 Bit 0 1 0 1 0 Binary Setting Value 1010 10 Port 4 Port 3 Port 2 Port 1 Bonding Bonding Bit 3 Bit 2 Bit 1 Bit 0 1 1 0 0 Binary Setting Value 1100 12 Ethernet port 4 CPU Module The switching logic is as below. ⚫ After the device is powered on, network 1 is selected when the link status of both network 1 and network 2 are normal. ⚫ When the link status of network 1 is abnormal, network 2 is selected if network 2 is normal. PCS-9613S Differential Relay 9-6 Date: 2020-09-02 9 Settings ⚫ When the link status of network 1 is abnormal, network 1 is kept to work if network 2 is also abnormal. ⚫ When network 2 is working, network 2 is kept to work even if network 1 has been restored to normal. The device will be switched to network 1 only if network 2 is abnormal. 9.1.3.2 IEC61850 Communication Settings ⚫ Access path: MainMenu Settings Global Settings Comm Settings IEC61850 Settings Table 9.1-4 IEC61850 communication settings No. Settings Default Range Unit value Step Remark The identification of the IED in IEC 61850 protocol. It cannot be an empty string and shall be unique within an SCL file. IEDNAME should be less 1 IEDNAME - TEMPLATE - - than 20 characters comprising letters or digits or underline ( _ ), and it is case sensitive. If this setting is modified, the IED name in ".cid" changed file will simultaneously be and vice versa. It is used to set the change detection threshold for suddenly 2 Threshold_Measmt_Net 0~100.00 1 % 0.01 sending measurement value to the SCADA via the device's Ethernet port using IEC 61850 protocol 3 ThAbs_Measmt 0.001~0.5 0.02 - 0.001 Measurement values zero drift suppression threshold If users need to support the 4 En_Send_MMS_Qual_Chg Disabled Enabled Disabled - - quality change upload function, this parameter should be set as “Enabled” It is used to select the network mode of MMS network for the SingleNet 5 Opt_DualNetMode_MMS HotStdby communication with SCADA SingleNet ColdStdby - - SingleNet: Single network HotStdby: Hot standby mode (always two ports in service) ColdStdby: Cold standby mode PCS-9613S Differential Relay 9-7 Date: 2020-09-02 9 9 Settings No. Settings Default Range Unit value Step Remark (only one port in service) 6 En_IEC62351_TCP_Port 7 En_IEC61850_TCP_Port The Disabled Disabled Enabled - - logic setting enable/disable TCP to port in IEC62351 protocol The Disabled Enabled Enabled - - logic setting enable/disable TCP to port in IEC61850 protocol 9.1.3.3 DNP Communication Settings ⚫ Access path: MainMenu Settings Global Settings Comm Settings DNP Settings Table 9.1-5 DNP communication settings No. 1 Settings En_TCP1_DNP Default Range value Unit Step The Disabled Disabled Enabled - - Addr_Slave_TCP1_DNP 0~65519 2 - 1 3 Addr_Master_TCP1_DNP 0~65519 1 - 1 IP_Master_TCP1_DNP logic setting to enable/disable the No.1 network DNP client 2 4 Remark The local address of the No.1 network DNP client The master address of the No.1 network DNP client The IP address of the 0.0.0.0~ 255.255.255.255 0.0.0.0 - - master of the No.1 network DNP client The communication map 5 Opt_Map_TCP1_DNP 0~4 0 - 1 of the No.1 network DNP client The 6 t_AppLayer_TCP1_DNP 1~5 3 s 1 timeout of the application layer of the No.1 network DNP client 9 The heartbeat time interval 7 t_KeepAlive_TCP1_DNP 0~7200 120 s 1 of the No.1 network DNP client The 8 En_UR_TCP1_DNP Disabled Enabled logic setting to enable/disable Disabled - - unsolicited function the message of the No.1 network DNP client 9 Num_URRetry_TCP1_DNP 2~10 3 - 1 The online retransmission number for sending the PCS-9613S Differential Relay 9-8 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Remark unsolicited message of the No.1 network DNP client The offline retransmission 10 t_UROfflRetry_TCP1_DNP 1~5000 60 s 1 interval for sending the unsolicited message of the No.1 network DNP client The default class level of 11 Class_BI_TCP1_DNP 0~3 1 - 1 the “Binary Input” of the No.1 network DNP client The default class level of 12 Class_AI_TCP1_DNP 0~3 2 - 1 the “Analog Input” of the No.1 network DNP client The selection timeout of 13 t_Select_TCP1_DNP 0~240 30 s 1 the remote control and remote adjustment of No.1 network DNP client The time interval of the 14 t_TimeSynIntvl_TCP1_DNP 0~3600 180 s 1 time synchronization function of the No.1 network DNP client 15 Obj01DefltVar_TCP1_DNP The 1-BISingleBit 2-BIWithStatus 1-BIChWoutT 16 Obj02DefltVar_TCP1_DNP 2-BIChWithAbsTime 3-BIChWithRelTime 1-BISingleBit - - “OBJ1” variation of default the No.1 network DNP client 2-BIChWithA bsTime The - - “OBJ2” variation of default the No.1 network DNP client 1-AI32Int 2-AI16Int 17 Obj30DefltVar_TCP1_DNP 3-AI32IntWoutF 4-AI16IntWoutF 3-AI32IntWo utF The - - “OBJ30” variation of default the No.1 network DNP client 5-AI32Flt 1-AI32IntEvWoutT 18 Obj32DefltVar_TCP1_DNP 2-AI16IntEvWoutT 5-AI32FltEvWoutT 1-AI32IntEv WoutT The - - Obj40DefltVar_TCP1_DNP 2-AO16Int The 1-AO32Int - - 3-AO32Flt 20 21 En_TCP2_DNP Addr_Slave_TCP2_DNP Disabled Enabled 0~65519 variation of default the No.1 network DNP client 1-AO32Int 19 “OBJ32” “OBJ40” variation of default the No.1 network DNP client The Disabled - - logic setting to enable/disable the No.2 network DNP client 2 PCS-9613S Differential Relay - 1 The local address of the No.2 network DNP client 9-9 Date: 2020-09-02 9 9 Settings No. 22 23 Settings Addr_Master_TCP2_DNP IP_Master_TCP2_DNP Default Range value 0~65519 1 Unit Step - 1 Remark The master address of the No.2 network DNP client The IP address of the 0.0.0.0~ 255.255.255.255 0.0.0.0 - - master of the No.2 network DNP client The communication map 24 Opt_Map_TCP2_DNP 0~4 0 - 1 of the No.2 network DNP client The 25 t_AppLayer_TCP2_DNP 1~5 3 s 1 timeout of the application layer of the No.2 network DNP client The heartbeat time interval 26 t_KeepAlive_TCP2_DNP 0~7200 120 s 1 of the No.2 network DNP client The 27 En_UR_TCP2_DNP Disabled Enabled logic setting to enable/disable Disabled - - unsolicited function the message of the No.2 network DNP client The online retransmission 28 Num_URRetry_TCP2_DNP 2~10 3 - 1 number for sending the unsolicited message of the No.2 network DNP client The offline retransmission 29 t_UROfflRetry_TCP2_DNP 1~5000 60 s 1 interval for sending the unsolicited message of the No.2 network DNP client The default class level of 30 Class_BI_TCP2_DNP 0~3 1 - 1 the “Binary Input” of the No.2 network DNP client The default class level of 9 31 Class_AI_TCP2_DNP 0~3 2 - 1 the “Analog Input” of the No.2 network DNP client The selection timeout of 32 t_Select_TCP2_DNP 0~240 30 s 1 the remote control and remote adjustment of No.2 network DNP client The time interval of the 33 t_TimeSynIntvl_TCP2_DNP 0~3600 180 s 1 time synchronization function of the No.2 network DNP client 34 Obj01DefltVar_TCP2_DNP 1-BISingleBit 1-BISingleBit - - The “OBJ1” default PCS-9613S Differential Relay 9-10 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step 2-BIWithStatus Remark variation of the No.2 network DNP client 1-BIChWoutT 35 Obj02DefltVar_TCP2_DNP 2-BIChWithAbsTime 3-BIChWithRelTime 2-BIChWithA bsTime The - - “OBJ2” variation of default the No.2 network DNP client 1-AI32Int 2-AI16Int 36 Obj30DefltVar_TCP2_DNP 3-AI32IntWoutF 4-AI16IntWoutF 3-AI32IntWo utF The - - “OBJ30” variation of default the No.2 network DNP client 5-AI32Flt 1-AI32IntEvWoutT 37 Obj32DefltVar_TCP2_DNP 2-AI16IntEvWoutT 5-AI32FltEvWoutT 1-AI32IntEv WoutT The - - Obj40DefltVar_TCP2_DNP The 2-AO16Int 1-AO32Int - - 3-AO32Flt 39 En_TCP3_DNP the “OBJ40” variation The Disabled Disabled Enabled - - No.2 of default the No.2 logic setting to enable/disable the No.3 network DNP client Addr_Slave_TCP3_DNP 0~65519 2 - 1 41 Addr_Master_TCP3_DNP 0~65519 1 - 1 IP_Master_TCP3_DNP of network DNP client 40 42 variation default network DNP client 1-AO32Int 38 “OBJ32” The local address of the No.3 network DNP client The master address of the No.3 network DNP client The IP address of the 0.0.0.0~ 255.255.255.255 0.0.0.0 - - master of the No.3 network DNP client The communication map 43 Opt_Map_TCP3_DNP 0~4 0 - 1 of the No.3 network DNP client The 44 t_AppLayer_TCP3_DNP 1~5 3 s 1 timeout of the application layer of the No.3 network DNP client The heartbeat time interval 45 t_KeepAlive_TCP3_DNP 0~7200 120 s 1 of the No.3 network DNP client The 46 En_UR_TCP3_DNP Disabled Enabled logic setting to enable/disable Disabled - - unsolicited function the message of the No.3 network DNP client 47 Num_URRetry_TCP3_DNP 2~10 3 PCS-9613S Differential Relay - 1 The online retransmission number for sending the 9-11 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Remark unsolicited message of the No.3 network DNP client The offline retransmission 48 t_UROfflRetry_TCP3_DNP 1~5000 60 s 1 interval for sending the unsolicited message of the No.3 network DNP client The default class level of 49 Class_BI_TCP3_DNP 0~3 1 - 1 the “Binary Input” of the No.3 network DNP client The default class level of 50 Class_AI_TCP3_DNP 0~3 2 - 1 the “Analog Input” of the No.3 network DNP client The selection timeout of 51 t_Select_TCP3_DNP 0~240 30 s 1 the remote control and remote adjustment of No.3 network DNP client The time interval of the 52 t_TimeSynIntvl_TCP3_DNP 0~3600 180 s 1 time synchronization function of the No.3 network DNP client 53 Obj01DefltVar_TCP3_DNP The 1-BISingleBit 2-BIWithStatus 1-BIChWoutT 54 Obj02DefltVar_TCP3_DNP 2-BIChWithAbsTime 3-BIChWithRelTime 1-BISingleBit - - “OBJ1” variation of default the No.3 network DNP client 2-BIChWithA bsTime The - - “OBJ2” variation of default the No.3 network DNP client 1-AI32Int 2-AI16Int 55 Obj30DefltVar_TCP3_DNP 3-AI32IntWoutF 4-AI16IntWoutF 3-AI32IntWo utF The - - “OBJ30” variation of default the No.3 network DNP client 5-AI32Flt 9 1-AI32IntEvWoutT 56 Obj32DefltVar_TCP3_DNP 2-AI16IntEvWoutT 5-AI32FltEvWoutT 1-AI32IntEv WoutT The - - Obj40DefltVar_TCP3_DNP 2-AO16Int The 1-AO32Int - - 3-AO32Flt 58 59 En_TCP4_DNP Addr_Slave_TCP4_DNP Disabled Enabled 0~65519 variation of default the No.3 network DNP client 1-AO32Int 57 “OBJ32” “OBJ40” variation of default the No.3 network DNP client The Disabled - - logic setting to enable/disable the No.4 network DNP client 2 - 1 The local address of the No.4 network DNP client PCS-9613S Differential Relay 9-12 Date: 2020-09-02 9 Settings No. 60 61 Settings Addr_Master_TCP4_DNP IP_Master_TCP4_DNP Default Range value 0~65519 1 Unit Step - 1 Remark The master address of the No.4 network DNP client The IP address of the 0.0.0.0~ 255.255.255.255 0.0.0.0 - - master of the No.4 network DNP client The communication map 62 Opt_Map_TCP4_DNP 0~4 0 - 1 of the No.4 network DNP client The 63 t_AppLayer_TCP4_DNP 1~5 3 s 1 timeout of the application layer of the No.4 network DNP client The heartbeat time interval 64 t_KeepAlive_TCP4_DNP 0~7200 120 s 1 of the No.4 network DNP client The 65 En_UR_TCP4_DNP Disabled Enabled logic setting to enable/disable Disabled - - unsolicited function the message of the No.4 network DNP client The online retransmission 66 Num_URRetry_TCP4_DNP 2~10 3 - 1 number for sending the unsolicited message of the No.4 network DNP client The offline retransmission 67 t_UROfflRetry_TCP4_DNP 1~5000 60 s 1 interval for sending the unsolicited message of the No.4 network DNP client The default class level of 68 Class_BI_TCP4_DNP 0~3 1 - 1 the “Binary Input” of the No.4 network DNP client The default class level of 69 Class_AI_TCP4_DNP 0~3 2 - 1 the “Analog Input” of the No.4 network DNP client The selection timeout of 70 t_Select_TCP4_DNP 0~240 30 s 1 the remote control and remote adjustment of No.4 network DNP client The time interval of the 71 t_TimeSynIntvl_TCP4_DNP 0~3600 180 s 1 time synchronization function of the No.4 network DNP client 72 Obj01DefltVar_TCP4_DNP 1-BISingleBit 1-BISingleBit PCS-9613S Differential Relay - - The “OBJ1” default 9-13 Date: 2020-09-02 9 9 Settings No. Settings Default Range Unit value Step Remark 2-BIWithStatus variation of the No.4 network DNP client 1-BIChWoutT 73 Obj02DefltVar_TCP4_DNP 2-BIChWithAbsTime 3-BIChWithRelTime 2-BIChWithA bsTime The - - “OBJ2” variation of default the No.4 network DNP client 1-AI32Int 2-AI16Int 74 Obj30DefltVar_TCP4_DNP 3-AI32IntWoutF 4-AI16IntWoutF 3-AI32IntWo utF The - - “OBJ30” variation of default the No.4 network DNP client 5-AI32Flt 1-AI32IntEvWoutT 75 Obj32DefltVar_TCP4_DNP 2-AI16IntEvWoutT 5-AI32FltEvWoutT 1-AI32IntEv WoutT The - - variation Obj40DefltVar_TCP4_DNP The 2-AO16Int of default the No.4 network DNP client 1-AO32Int 76 “OBJ32” 1-AO32Int - - “OBJ40” variation 3-AO32Flt of default the No.4 network DNP client 9.1.3.4 IEC103 Communication Settings ⚫ Access path: MainMenu Settings Global Settings Comm Settings IEC103 Settings Table 9.1-6 IEC103 communication settings No. Settings Range Default value Unit Step Current The language of group caption of Language; 1 Opt_Caption_103 Remark Fixed Current Chinese; Language IEC103 protocol - - It is recommended to be set as “Fixed Chinese” if the device communicate with Fixed SCADA in Chinese. English This setting is only used for IEC 103 protocol. If NR network IEC103 protocol 9 is used, the setting must be set as 2 En_Broadcast_LAN1 Disabled Enabled Disabled - - “Enabled”. Disabled: the device does not send UDP messages through Ethernet port A; Enabled: the device sends UDP messages through Ethernet port A. This setting is only used for IEC 103 3 En_Broadcast_LAN2 Disabled Enabled Disabled - - protocol. If NR network IEC103 protocol is used, the setting must be set as “Enabled”. PCS-9613S Differential Relay 9-14 Date: 2020-09-02 9 Settings No. Settings Range Default value Unit Step Remark Disabled: the device does not send UDP messages through Ethernet port B; Enabled: the device sends UDP messages through Ethernet port B. This setting is only used for IEC 103 protocol. If NR network IEC103 protocol is used, the setting must be set as 4 En_Broadcast_LAN3 Disabled Enabled Disabled - - “Enabled”. Disabled: the device does not send UDP messages through Ethernet port C; Enabled: the device sends UDP messages through Ethernet port C. This setting is only used for IEC 103 protocol. If NR network IEC103 protocol is used, the setting must be set as 5 En_Broadcast_LAN4 Disabled Enabled Disabled - - “Enabled”. Disabled: the device does not send UDP messages through Ethernet port D; Enabled: the device sends UDP messages through Ethernet port D. This setting is used to set the data format for sending waveform list using 6 Format_Wave_Sent DisturbData; File IEC 60870-5-103. File - - DisturbData: Send the waveform list in ASDU23 mode; File: Send the waveform list in ASDU222 mode. It is used to set the change detection threshold 7 Threshold_Measmt_Net 0~100.00 1.00 % 0.01 for suddenly sending measurement value to the SCADA via the device's Ethernet port using IEC 60870-5-103 It is used to set the time period for 8 Period_Measmt_Net 0~65535 30 s 1 sending the measurement value to SCADA via the device's Ethernet port using IEC 60870-5-103 or IEC 61850. 9.1.3.5 GOOSE Communication Settings ⚫ Access path: MainMenu Settings Global Settings Comm Settings GOOSE Settings PCS-9613S Differential Relay 9-15 Date: 2020-09-02 9 9 Settings Table 9.1-7 GOOSE communication settings No. Settings Range Default value Unit Step Remark The GOOSE receiving mode. 1 Opt_RecvMode_GOOSE DoubleFrameChk: double frame DoubleFrameChk SingleFrameChk SingleFrameChk - - check mode; SingleFrameChk: single frame check mode; 2 En_NetA_GOOSE 3 En_DualNet_GOOSE Disabled Enabled Disabled Enabled Enabled - - Disabled - - Logic setting to enable/disable GOOSE net A Logic setting to enable/disable GOOSE double-net mode Logic setting to enable/disable GOOSE 4 En_ComplexNet_GOOSE complex-net mode. GOOSE complex-net mode: for Disabled Disabled Enabled - - the GOOSE control receiving, blocks adopt some dual-net receiving and other control blocks adopt single-net receiving. 9.1.4 Disturbance Fault Recording Settings ⚫ Access path: MainMenu Settings Global Settings DFR Settings Table 9.1-8 Disturbance fault recording settings No. Settings Range Default value Unit Step 1 RecDur_PreTrigDFR 0~1 0.1 s 0.001 2 RecDur_PostFault 0~10 5 s 0.001 Remark Waveform recorded duration before the trigger element operating Waveform recorded duration after the fault happens The 3 MaxRecDur_PostTrigDFR 0~10 10 s 0.001 9 maximum duration after waveform recorded the trigger element operating 9.1.5 Label Settings ⚫ Access path: MainMenu Settings Global Settings Label Settings Table 9.1-9 Label settings No. 1 Symbol Bx.Name_00_GCommLink Default value GOOSE_Link00 Description Label setting of GOOSE communication link 00 of the module located in slot No.x. PCS-9613S Differential Relay 9-16 Date: 2020-09-02 9 Settings 2 …… …… …… 3 Bx.Name_63_ommLink GOOSE_Link63 Label setting of GOOSE communication link 63f the module located in slot No.x. These settings are used to definite the label of each GOOSE communication link. The label of each GOOSE communication link will influence the displayed contents of all reports, settings and metering that related with each GOOSE communication link. 9.1.6 Clock Synchronization Settings ⚫ Access path: MainMenu Settings Global Settings ClockSyn Settings Table 9.1-10 Clock synchronization settings No Settings . Default Range value Unit Step Conventional 1 Opt_TimeSyn Remark Select SAS NoTimeSyn - - NoTimeSyn the time synchronization mode of the device. The local time zone also 2 OffsetHour_UTC -12~12 8 - 1 refered to as the hour offset hour from UTC . 3 OffsetMinute_UTC 0~60 0 - 1 The offset minute of local time from UTC. The IP address of the server 4 IP_Server_SNTP 0.0.0.0~ 255.255.255.255 0.0.0.0 - - when SNTP synchronization time mode is selected The IP address of the standby 5 IP_StandbyServer_S 0.0.0.0~ NTP 255.255.255.255 0.0.0.0 - - server when SNTP synchronization mode time is selected 6 DST.En The logic setting is used to Disabled Disabled Enabled - - enable or disable Daylight Saving Time (DST) It is used to set the minute 7 DST.OffsetMinute 0~255 60 - 1 offset of DST, i.e. the difference between DST time and local time 8 Jan, Feb, Mar, DST.MonthInYear_St Apr, May, Jun, art Jul, Aug, Sep, Mar - - 1st - - It is used to set the start month of DST. Oct, Nov, Dec 9 DST.WeekInMonth_S 1st, 2nd, 3nd, PCS-9613S Differential Relay It is used to set the start week 9-17 Date: 2020-09-02 9 9 Settings No Settings . tart Default Range value Unit Step 4th, Last Remark of DST. Sunday, Monday, 10 DST.DayInWeek_Star t Tuesday, Wednesday, Sunday - - 3 - 1 Oct - - 1st - - Sunday - - 9 - 1 Thursday, Friday, It is used to set the start day of DST. Saturday 11 12 DST.HourInDay_Start 0~23 Jan, Feb, Mar, DST.MonthInYear_En Apr, May, Jun, d Jul, Aug, Sep, It is used to set the start hour of DST. It is used to set the end month of DST. Oct, Nov, Dec 13 DST.WeekInMonth_E 1st, 2nd, nd 4th, Last 3nd, It is used to set the end week of DST. Sunday, Monday, Tuesday, 14 DST.DayInWeek_End Wednesday, Thursday, Friday, It is used to set the end day of DST. Saturday 15 1. DST.HourInDay_End 0~23 It is used to set the end hour of DST. [Opt_TimeSyn] There are three selections for clock synchronization of the device, each selection includes different time clock synchronization signals shown in following table. Item Description IRIG-B (RS-485): IRIG-B via RS-485 differential level. PPS (RS-485): Pulse per second (PPS) via RS-485 differential level. IRIG-B (Fiber): IRIG-B via optical-fibre interface. Conventional PPS (Fiber): Pulse per second (PPS) via optical-fibre interface. IEEE1588 (Fiber): Clock message via IEEE1588. 9 PPM (DIN): Pulse per minute (PPM) via the binary input [BI_TimeSyn]. PPS (DIN): Pulse per second (PPS) via the binary input [BI_TimeSyn]. SNTP(PTP): Unicast (point to point) SNTP mode via Ethernet network. SNTP(BC): Broadcast SNTP mode via Ethernet network. SAS IEC103: Clock messages through IEC103 protocol. MODBUS: Clock messages through MODBUS protocol. NoTimeSyn 1) If time synchronization function is not needed for the device, this option can be selected. When “SAS” is selected, if there is no conventional clock synchronization signal, the device will not send the alarm signal [Alm_TimeSyn]. When “Conventional” mode is selected, if there PCS-9613S Differential Relay 9-18 Date: 2020-09-02 9 Settings is no conventional clock synchronization signal, “SAS” mode will be enabled automatically with the alarm signal [Alm_TimeSyn] being issued simultaneously. 2) When “NoTimeSyn” mode is selected, the device will not send time synchronization alarm signal. The clock message via IEC103 protocol is INVALID when the device receives the IRIG-B signal through RC-485 port. 9.1.7 OutMap Settings ⚫ Access path: MainMenu Settings Global Settings OutMap Settings Table 9.1-11 Outmap settings No. 1 2 Name Range OutMapxxx 00000000~ (xxx=001, 002…032) FFFFFFFF t_Dwell_xxx_OutMap 0.000~0.500 (xxx=001, 002…032) Unit Default - 0 s 0.060 Description Tripping logic setting of programmable trip output map xxx The pulse width setting of programmable trip output map xxx 9.1.8 Supervision Settings ⚫ Access path: MainMenu Settings Global Settings Superv Settings Table 9.1-12 Supervision settings No. Settings Range Default value Unit Step Remark The calculated residual current 1 CTS.3I0_Set 0~200 0.1 A 0.001 setting of CT circuit supervision function. The calculated residual voltage 2 CTS.3U0_Set 0~200 30 V 0.001 setting of CT circuit supervision function. 3 CTS.t_DPU 0~100 10 s 0.001 4 CTS.t_DPO 0~100 10 s 0.001 5 CTS.En Disabled - - 6 VTS.U1_Set 30.00 V 0.01 Disabled Enabled 0~100 PCS-9613S Differential Relay Delay pick-up time setting for CT circuit failure Delay drop-out time setting for CT circuit failure Enabling/disabling CT circuit supervision function. Positive-sequence threshold for voltage VT circuit 9-19 Date: 2020-09-02 9 9 Settings No. Settings Range Default value Unit Step Remark supervision 7 VTS.3U0_Set 0~100 8.00 V 0.01 Zero-sequence voltage (calculated) for threshold VT circuit supervision Negative-sequence 8 VTS.U2_Set 0~100 8.00 V 0.01 voltage setting of VT circuit supervision function. 9 VTS.t_DPU 0.2~30 1.500 s 0.001 10 VTS.t_DDO 0.2~30 10.000 s 0.001 11 VTS.En Enabled - - 12 VTS.Opt_VT Bus - - Disabled or Enabled Bus or Bay Delay pickup setting for the alarm of VT circuit supervision Delay drop off setting for the alarm of VT circuit supervision Logic setting for alarm function of VT circuit supervision Selection of Bay VT or Bus VT 9.2 Protection Settings 9.2.1 Fault Detector (FD) ⚫ Access path: MainMenu Settings Protection Settings FD Settings Table 9.2-1 Settings of fault detector No. Settings Range Default value Unit Step 1 FD.DPFC.I_Set (0.050~40.000)×In 0.100 A 0.001 2 FD.ROC.3I0_Set (0.050~40.000)×In 0.100 A 0.001 Description Current setting of DPFC current fault detector element Current FD.NOC.I2_Set (0.050~40.000)×In 0.100 A 0.001 9 of residual current fault detector element Current 3 setting setting of negative-sequence current fault detector element 4 FD.NOC.En Disabled Enabled Enabling/disabling Enabled - - negative-sequence current fault detector element 9.2.2 Optical Pilot Channel (FO) ⚫ Access path: MainMenu Settings Protection Settings Rmt CommCh Settings PCS-9613S Differential Relay 9-20 Date: 2020-09-02 9 Settings Table 9.2-2 Settings of optical pilot channel No. Settings Default Range Unit value Step 1 LocID 0~65535 1 - 1 2 RmtID 0~65535 2 - 1 3 BaudRate 2048 kbps - 4 Protocol C37.94 - - 64 2048 Description Identity code of the device at local end Identity code of the device at remote end Baud rate of optical pilot channel G.703 It is used to select protocol type, G.703 or C37.94 C37.94 The setting for the times of 64kbit/s, 5 FOx.Nx64k_C37.94 1~12 12 - 1 which is an N*64kbit/s standard defined by IEEE C37.94 standard Option of internal clock or external 6 FOx.Opt_ClkSrc Ext Int Int - clock - Ext: external clock Int: internal clock 7 FOx.En Disabled Enabled Enabled - - Enabling/disabling channel x 9.2.3 Current Differential Protection (87L) ⚫ Access path: MainMenu Settings Protection Settings Diff Settings Table 9.2-3 Settings of current differential protection No. Settings Range Default Unit value Step 1 87L.I_Pkp (0.05~40)×In 0.300 A 0.001 2 87L.I_Alm (0.05~40)×In 0.300 A 0.001 3 87L.I_Pkp_CTS (0.05~40)×In 1.0×In A 0.001 4 87L.K_Cr_CT 0.2~10 1.0 - 0.001 5 87L.I_Knee1 (0.05~40)×In 1.0×In A 0.001 6 87L.I_Knee2 (0.05~40)×In 3.0×In A 0.001 7 87L.Slope1 0.3~0.75 0.500 - 0.01 8 87L.Slope2 0.3~0.75 0.700 - 0.01 PCS-9613S Differential Relay Description Minimum pickup current setting of current differential protection Current setting of differential current abnormality alarm Current setting of differential protection when CT circuit failure The factor of CT ratio Current setting of knee point 1 for current differential protection Current setting of knee point 2 for current differential protection Slope 1 of steady-state current differential element Slope 2 of steady-state current differential element 9-21 Date: 2020-09-02 9 9 Settings No. 9 10 11 12 Settings 87L.En 87L.En_Biased1 87L.En_Biased2 87L.InterTrp Range Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Default Unit value Enabled - Step Description Enabling/disabling - differential protection Enabling/disabling Enabled - current - stage 1 of steady-state current differential element Enabling/disabling Enabled - - stage 2 of steady-state current differential element Enabled - Enabling/disabling - inter-tripping element Enabling/disabling local independent current differential 13 87L.En_LocDiff Disabled Enabled protection (independent current Enabled - - differential protection means local current differential protection can operate without permissive signal from remote end) 14 87L.En_CTS_Blk Disabled Enabled Enabling/disabling Disabled - - differential current protection blocked during CT circuit failure 9.2.4 Phase Overcurrent Protection Settings ⚫ Access path: MainMenu Settings Protection Settings OC Settings Table 9.2-4 Settings of phase overcurrent protection No. Settings Default Range value Unit Step Description The low voltage blocking setting 1 50/51P.VCE.Upp 10~100 70 V 0.001 of the voltage control element of phase overcurrent protection 9 The negative-sequence voltage 2 50/51P.VCE.U2 2~57 8 V 0.001 blocking setting of the voltage control element of phase overcurrent protection The residual voltage setting (set 3 50/51P.VCE.3U0 2~57 8 V 0.001 according to 3U0) of voltage control element of phase overcurrent protection PCS-9613S Differential Relay 9-22 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The relay characteristic angle of 4 50/51P.DIR.RCA -180~179 45 deg 1 the direction control element of phase overcurrent protection The relay negative-sequence 5 50/51P.DIR.RCA_N egOC -180~179 45 deg 1 characteristic direction angle control of the element of phase overcurrent protection 6 7 8 9 50/51P.DIR.phi_Min _Fwd 50/51P.DIR.phi_Ma x_Fwd 50/51P.DIR.phi_Min _Rev 50/51P.DIR.phi_Ma x_Rev The minimum boundary of the 10~90 90 deg 1 forward direction element of phase overcurrent protection The maximum boundary of the 10~90 90 deg 1 forward direction element of phase overcurrent protection The minimum boundary of the 10~90 90 deg 1 reverse direction element of phase overcurrent protection The maximum boundary of the 10~90 90 deg 1 reverse direction element of phase overcurrent protection The voltage polarization mode for direction control element of phase overcurrent protection 10 50/51P.DIR.Opt_Pol arizedVolt Upp; Up; Upp: Upp - - U1 phase-to-phase voltage polarized Up: phase-to-ground voltage polarized U1: positive-sequence voltage polarized The minimum operating current 11 50/51P.DIR.I_Min (0.05~1)In 0.05 - 0.001 setting for the direction control element of phase overcurrent protection The minimum operating voltage 12 50/51P.DIR.U_Min 1~10 4 V 0.001 setting for the direction control element of phase overcurrent protection PCS-9613S Differential Relay 9-23 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Description Logic setting to determine the behaviour of phase overcurrent protection when VT circuit supervision function is enabled and VT circuit failure happens. 13 50/51P.En_VTS_Blk Disabled; Enabled Disabled - - Disabled: phase overcurrent protection will not affected by VT circuit failure Enabled: voltage controlled phase overcurrent protection will be blocked by VT circuit failure signal 14 50/51P.HMB.K_Hm 2 The 0.1~1 0.2 - 0.001 percent setting of the harmonic control element of phase overcurrent protection The current setting for releasing 15 50/51P.HMB.I_Rls 2~150 20 A 0.001 the harmonic control element of phase overcurrent protection The setting used to select the harmonic 16 50/51P.HMB.Opt_Bl k PhaseBlk CrossBlk blocking mode of phase overcurrent protection PhaseBlk - - MaxPhaseBlk PhaseBlk: phase blocking CrossBlk: cross blocking MaxPhaseBlk: maximum phase blocking 17 50/51P1.I_Set 0.05~200 15 A 0.001 The current setting of stage 1 of phase overcurrent protection The operating time setting of 18 50/51P1.t_Op 0 ~100 0.1 s 0.001 stage 1 of phase overcurrent protection The dropout time setting of 9 19 50/51P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase overcurrent protection PCS-9613S Differential Relay 9-24 Date: 2020-09-02 9 Settings No. Settings Range Default value Unit Step Description The logic setting for enabling/disabling the voltage control element of stage 1 of phase overcurrent protection Disabled: stage 1 of phase 20 50/51P1.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 1 of phase overcurrent protection is controlled by the voltage control element Non_Directional 21 50/51P1.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 1 of phase overcurrent protection. The logic setting for enabling/disabling the harmonic control element of stage 1 of phase overcurrent protection Disabled: stage 1 of phase 22 50/51P1.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 1 of phase overcurrent controlled protection by the is harmonic control element 23 50/51P1.En Disabled; Enabled The Enabled - - logic setting for enabling/disabling the stage 1 of phase overcurrent protection Enabling stage 1 of phase 24 50/51P1.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 9-25 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 25 50/51P1.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime - - IECV; inverse-time operation characteristic curve of stage 1 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 26 50/51P1.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 1 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 27 50/51P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase overcurrent protection The minimum operating time 28 50/51P1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of phase overcurrent protection The 9 29 50/51P1.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 1 of phase overcurrent protection The 30 50/51P1.Alpha 0.01 ~3 0.02 - 0.000 1 constant customized “α” of the inverse-time operation characteristic of stage 1 of phase overcurrent protection PCS-9613S Differential Relay 9-26 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The 31 50/51P1.C 0 ~1 0 - 0.000 1 constant “C” customized of the inverse-time operation characteristic of stage 1 of phase overcurrent protection 32 50/51P2.I_Set 0.05~200 15 A 0.001 The current setting of stage 2 of phase overcurrent protection The operating time setting of 33 50/51P2.t_Op 0 ~100 0.1 s 0.001 stage 2 of phase overcurrent protection The dropout time setting of 34 50/51P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase overcurrent protection The logic setting for enabling/disabling the voltage control element of stage 2 of phase overcurrent protection Disabled: stage 2 of phase 35 50/51P2.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 2 of phase overcurrent protection is controlled by the voltage control element Non_Directional 36 50/51P2.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 2 of phase overcurrent protection. The logic setting for enabling/disabling the harmonic control element of stage 2 of phase overcurrent protection Disabled: stage 2 of phase 37 50/51P2.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 2 of phase overcurrent controlled protection by the is harmonic control element PCS-9613S Differential Relay 9-27 Date: 2020-09-02 9 9 Settings No. 38 Settings 50/51P2.En Default Range Disabled; Enabled value Unit Step Description The Enabled - - logic setting for enabling/disabling the stage 2 of phase overcurrent protection Enabling stage 2 of phase 39 50/51P2.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 40 50/51P2.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime - - IECV; inverse-time operation characteristic curve of stage 2 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 41 50/51P2.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 2 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout 9 The time multiplier setting of 42 50/51P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase overcurrent protection The minimum operating time 43 50/51P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase overcurrent protection The 44 50/51P2.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 2 of phase overcurrent protection PCS-9613S Differential Relay 9-28 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The 45 50/51P2.Alpha 0.01 ~3 0.02 - 0.000 1 constant “α” customized of the inverse-time operation characteristic of stage 2 of phase overcurrent protection The 46 50/51P2.C 0 ~1 0 - 0.000 1 constant “C” customized of the inverse-time operation characteristic of stage 2 of phase overcurrent protection 47 50/51P3.I_Set 0.05~200 15 A 0.001 The current setting of stage 3 of phase overcurrent protection The operating time setting of 48 50/51P3.t_Op 0 ~100 0.1 s 0.001 stage 3 of phase overcurrent protection The dropout time setting of 49 50/51P3.t_DropOut 0 ~100 0 s 0.001 stage 3 of phase overcurrent protection The logic setting for enabling/disabling the voltage control element of stage 3 of phase overcurrent protection Disabled: stage 3 of phase 50 50/51P3.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 3 of phase overcurrent protection is controlled by the voltage control element Non_Directional 51 50/51P3.Opt_Dir Forward Reverse Non_Directio nal PCS-9613S Differential Relay The setting used to select the - - directional mode of stage 3 of phase overcurrent protection. 9-29 Date: 2020-09-02 9 9 Settings No. Settings Range Default value Unit Step Description The logic setting for enabling/disabling the harmonic control element of stage 3 of phase overcurrent protection Disabled: stage 3 of phase 52 50/51P3.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 3 of phase overcurrent controlled protection by the is harmonic control element 53 50/51P3.En Disabled; Enabled The Enabled - - logic setting for enabling/disabling the stage 3 of phase overcurrent protection Enabling stage 3 of phase 54 50/51P3.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 55 50/51P3.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime IECV; - - inverse-time operation characteristic curve of stage 3 of phase overcurrent protection. IEC; IECE; 9 IECST; IECLT; IECDefTime; UserDefine PCS-9613S Differential Relay 9-30 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The setting for selecting the inverse-time 56 50/51P3.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 3 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 57 50/51P3.TMS 0.04~ 20 1 - 0.001 stage 3 of phase overcurrent protection The minimum operating time 58 50/51P3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of phase overcurrent protection The 59 50/51P3.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 3 of phase overcurrent protection The 60 50/51P3.Alpha 0.01 ~3 0.02 - 0.000 1 constant customized “α” of the inverse-time operation characteristic of stage 3 of phase overcurrent protection The 61 50/51P3.C 0 ~1 0 - 0.000 1 constant customized “C” of the inverse-time operation characteristic of stage 3 of phase overcurrent protection 62 50/51P4.I_Set 0.05~200 15 A 0.001 The current setting of stage 4 of phase overcurrent protection The operating time setting of 63 50/51P4.t_Op 0 ~100 0.1 s 0.001 stage 4 of phase overcurrent protection The dropout time setting of 64 50/51P4.t_DropOut 0 ~100 0 s 0.001 stage 4 of phase overcurrent protection PCS-9613S Differential Relay 9-31 Date: 2020-09-02 9 9 Settings No. Settings Range Default value Unit Step Description The logic setting for enabling/disabling the voltage control element of stage 4 of phase overcurrent protection Disabled: stage 4 of phase 65 50/51P4.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 4 of phase overcurrent protection is controlled by the voltage control element Non_Directional 66 50/51P4.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 4 of phase overcurrent protection. The logic setting for enabling/disabling the harmonic control element of stage 4 of phase overcurrent protection Disabled: stage 4 of phase 67 50/51P4.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 4 of phase overcurrent controlled protection by the is harmonic control element 68 50/51P4.En Disabled; Enabled The Enabled - - logic setting for enabling/disabling the stage 4 of phase overcurrent protection Enabling stage 4 of phase 9 69 50/51P4.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 9-32 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 70 50/51P4.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime - - IECV; inverse-time operation characteristic curve of stage 4 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 71 50/51P4.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 4 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 72 50/51P4.TMS 0.04~ 20 1 - 0.001 stage 4 of phase overcurrent protection The minimum operating time 73 50/51P4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of phase overcurrent protection The 74 50/51P4.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 4 of phase overcurrent protection The 75 50/51P4.Alpha 0.01 ~3 0.02 - 0.000 1 constant customized “α” of the inverse-time operation characteristic of stage 4 of phase overcurrent protection PCS-9613S Differential Relay 9-33 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Description The 76 50/51P4.C 0 ~1 0 - 0.000 1 constant “C” customized of the inverse-time operation characteristic of stage 4 of phase overcurrent protection 77 50/51P5.I_Set 0.05~200 15 A 0.001 The current setting of stage 5 of phase overcurrent protection The operating time setting of 78 50/51P5.t_Op 0 ~100 0.1 s 0.001 stage 5 of phase overcurrent protection The dropout time setting of 79 50/51P5.t_DropOut 0 ~100 0 s 0.001 stage 5 of phase overcurrent protection The logic setting for enabling/disabling the voltage control element of stage 5 of phase overcurrent protection Disabled: stage 5 of phase 80 50/51P5.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 5 of phase overcurrent protection is controlled by the voltage control element Non_Directional 81 50/51P5.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 5 of phase overcurrent protection. The logic setting for enabling/disabling the harmonic control element of stage 5 of 9 phase overcurrent protection Disabled: stage 5 of phase 82 50/51P5.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 5 of phase overcurrent controlled protection by the is harmonic control element PCS-9613S Differential Relay 9-34 Date: 2020-09-02 9 Settings No. 83 Settings 50/51P5.En Default Range Disabled; Enabled value Unit Step Description The Enabled - - logic setting for enabling/disabling the stage 5 of phase overcurrent protection Enabling stage 5 of phase 84 50/51P5.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 85 50/51P5.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime - - IECV; inverse-time operation characteristic curve of stage 5 of phase overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 86 50/51P5.Opt_Curve _DropOut Inst; DefTime; dropout characteristic curve of stage 5 of Inst - - IDMT phase overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 87 50/51P5.TMS 0.04~ 20 1 - 0.001 stage 5 of phase overcurrent protection The minimum operating time 88 50/51P5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of phase overcurrent protection The 89 50/51P5.K 0.001~120 0.14 - 0.000 1 constant customized “k” of the inverse-time operation characteristic of stage 5 of phase overcurrent protection PCS-9613S Differential Relay 9-35 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Description The 90 50/51P5.Alpha 0.01 ~3 0.02 - 0.000 1 constant “α” customized of the inverse-time operation characteristic of stage 5 of phase overcurrent protection The 91 50/51P5.C 0 ~1 0 - 0.000 1 constant “C” customized of the inverse-time operation characteristic of stage 5 of phase overcurrent protection 92 50/51P6.I_Set 0.05~200 15 A 0.001 The current setting of stage 6 of phase overcurrent protection The operating time setting of 93 50/51P6.t_Op 0 ~100 0.1 s 0.001 stage 6 of phase overcurrent protection The dropout time setting of 94 50/51P6.t_DropOut 0 ~100 0 s 0.001 stage 6 of phase overcurrent protection The logic setting for enabling/disabling the voltage control element of stage 6 of phase overcurrent protection Disabled: stage 6 of phase 95 50/51P6.En_Volt_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the voltage control element Enabled: stage 6 of phase overcurrent protection is controlled by the voltage control element Non_Directional 9 96 50/51P6.Opt_Dir Forward Reverse Non_Directio nal The setting used to select the - - directional mode of stage 6 of phase overcurrent protection. PCS-9613S Differential Relay 9-36 Date: 2020-09-02 9 Settings No. Settings Range Default value Unit Step Description The logic setting for enabling/disabling the harmonic control element of stage 6 of phase overcurrent protection Disabled: stage 6 of phase 97 50/51P6.En_Hm_Bl Disabled; k Enabled Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 6 of phase overcurrent controlled protection by the is harmonic control element 98 50/51P6.En Disabled; Enabled The Enabled - - logic setting for enabling/disabling the stage 6 of phase overcurrent protection Enabling stage 6 of phase 99 50/51P6.Opt_Trp/Al Trp; m Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; ANSILTV; 100 50/51P6.Opt_Curve ANSILT; IECN; The setting for selecting the IECDefTime IECV; - - inverse-time operation characteristic curve of stage 6 of phase overcurrent protection. IEC; IECE; 9 IECST; IECLT; IECDefTime; UserDefine PCS-9613S Differential Relay 9-37 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The setting for selecting the inverse-time 101 50/51P6.Opt_Curve _DropOut Inst; dropout characteristic curve of stage 6 of DefTime; Inst - - phase overcurrent protection IDMT Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 102 50/51P6.TMS 0.04~ 20 1 - 0.001 stage 6 of phase overcurrent protection The minimum operating time 103 50/51P6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of phase overcurrent protection The 104 50/51P6.K 0.001~120 0.14 0.000 - 1 constant customized “k” of the inverse-time operation characteristic of stage 6 of phase overcurrent protection The 105 50/51P6.Alpha 0.01 ~3 0.02 0.000 - 1 constant customized “α” of the inverse-time operation characteristic of stage 6 of phase overcurrent protection The 106 50/51P6.C 0 ~1 0 0.000 - 1 constant customized “C” of the inverse-time operation characteristic of stage 6 of phase overcurrent protection 9.2.5 Earth Fault Overcurrent Protection Settings ⚫ 9 Access path: MainMenu Settings Protection Settings ROC Settings Table 9.2-5 Settings of earth fault overcurrent protection No. Settings Range Default Uni value t Step Description The relay characteristic angle 1 50/51G.DIR.RCA -180~179 45 deg 1 of the element direction of earth control fault overcurrent protection PCS-9613S Differential Relay 9-38 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description The minimum boundary of the 2 50/51G.DIR.phi_Min_ Fwd 10~90 90 deg 1 forward direction element of earth fault overcurrent protection The maximum boundary of the 3 50/51G.DIR.phi_Max_ Fwd 10~90 90 deg 1 forward direction element of earth fault overcurrent protection The minimum boundary of the 4 50/51G.DIR.phi_Min_ Rev 10~90 90 deg 1 reverse direction element of earth fault overcurrent protection The maximum boundary of the 5 50/51G.DIR.phi_Max_ Rev 10~90 90 deg 1 reverse direction element of earth fault overcurrent protection The 6 50/51G.DIR.3I0_Min (0.05~1)In 0.05 - 0.001 minimum operating current setting for the direction control element of earth fault overcurrent protection The 7 50/51G.DIR.3U0_Min 1~10 4 V 0.001 minimum operating voltage setting for the direction control element of earth fault overcurrent protection Logic setting to determine the behaviour of earth fault overcurrent protection when VT circuit supervision function is enabled and VT circuit 8 50/51G.En_VTS_Blk Disabled; Enabled failure happens. Disabled - - Disabled: earth fault overcurrent protection will not affected by VT circuit failure Enabled: earth voltage controlled fault overcurrent protection will be blocked by VT circuit failure signal The percent setting of the 9 50/51G.HMB.K_Hm2 0.1~1 0.2 - 0.001 harmonic control element of earth fault overcurrent protection PCS-9613S Differential Relay 9-39 Date: 2020-09-02 9 9 Settings No. Settings Range Default Uni value t Step Description The 10 50/51G.HMB.I_Rls 2~150 20 A 0.001 current setting for releasing the harmonic control element of earth fault overcurrent protection The setting used to select the residual current that used for stage 11 50/51G1.Opt_3I0 Ext; Cal Ext - - 1 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 1 12 50/51G1.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection The operating time setting of 13 50/51G1.t_Op 0 ~100 0.1 s 0.001 stage 1 of earth fault overcurrent protection The dropout time setting of 14 50/51G1.t_DropOut 0 ~100 0 s 0.001 stage 1 of earth fault overcurrent protection Non_Direction 15 50/51G1.Opt_Dir The setting used to select the al; Non_Directio Forward; nal - - Reverse directional mode of stage 1 of earth fault overcurrent protection. The logic setting enabling/disabling for the harmonic control element of the stage 1 of earth fault overcurrent protection 9 16 50/51G1.En_Hm_Blk Disabled; Enabled Disabled: stage 1 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 1 of earth fault overcurrent protection is controlled by the harmonic control element The 17 50/51G1.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 1 of earth fault overcurrent protection PCS-9613S Differential Relay 9-40 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description Enabling stage 1 earth fault 18 50/51G1.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 19 50/51G1.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - - characteristic curve of stage 1 of IECV; operation earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 20 50/51G1.Opt_Curve_ DropOut characteristic curve of stage 1 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 21 50/51G1.TMS 0.04~ 20 1 - 0.001 stage 1 of earth fault overcurrent protection The minimum operating time 22 50/51G1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of earth fault overcurrent protection The constant customized 23 50/51G1.K 0.001~120 0.14 - 0.0001 “k” of operation characteristic stage of 1 the inverse-time earth of fault overcurrent protection PCS-9613S Differential Relay 9-41 Date: 2020-09-02 9 9 Settings No. Settings Range Default Uni value t Step Description The constant customized 24 50/51G1.Alpha 0.01 ~3 0.02 - 0.0001 “α” of inverse-time operation characteristic stage of 1 the earth of fault overcurrent protection The constant customized 25 50/51G1.C 0 ~1 0 - 0.0001 “C” of inverse-time operation characteristic stage of 1 the earth of fault overcurrent protection The setting used to select the residual current that used for stage 26 50/51G2.Opt_3I0 Ext; Cal Ext - - 2 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 2 27 50/51G2.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection The operating time setting of 28 50/51G2.t_Op 0 ~100 0.1 s 0.001 stage 2 of earth fault overcurrent protection The dropout time setting of 29 50/51G2.t_DropOut 0 ~100 0 s 0.001 stage 2 of earth fault overcurrent protection Non_Direction 30 50/51G2.Opt_Dir The setting used to select the al; Non_Directio Forward; nal Reverse - - directional mode of stage 2 of earth fault overcurrent protection. 9 PCS-9613S Differential Relay 9-42 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description The logic setting enabling/disabling for the harmonic control element of the stage 2 of earth fault overcurrent protection 31 50/51G2.En_Hm_Blk Disabled; Enabled Disabled: stage 2 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 2 of earth fault overcurrent protection is controlled by the harmonic control element The 32 50/51G2.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 2 of earth fault overcurrent protection Enabling stage 2 earth fault 33 50/51G2.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 34 50/51G2.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - - characteristic curve of stage 2 of IECV; operation earth fault overcurrent 9 protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine PCS-9613S Differential Relay 9-43 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description The setting for selecting the inverse-time 35 50/51G2.Opt_Curve_ DropOut characteristic curve of stage 2 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 36 50/51G2.TMS 0.04~ 20 1 - 0.001 stage 2 of earth fault overcurrent protection The minimum operating time 37 50/51G2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of earth fault overcurrent protection The constant customized 38 50/51G2.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 2 the earth of fault overcurrent protection The constant customized 39 50/51G2.Alpha 0.01 ~3 0.02 - 0.0001 “α” of inverse-time operation characteristic stage of 2 the earth of fault overcurrent protection The constant customized 40 50/51G2.C 0 ~1 0 - 0.0001 “C” of operation characteristic stage of 2 the inverse-time earth of fault overcurrent protection The setting used to select the residual current that used for 9 stage 41 50/51G3.Opt_3I0 Ext; Cal Ext - - 3 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 3 42 50/51G3.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection PCS-9613S Differential Relay 9-44 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description The operating time setting of 43 50/51G3.t_Op 0 ~100 0.1 s 0.001 stage 3 of earth fault overcurrent protection The dropout time setting of 44 50/51G3.t_DropOut 0 ~100 0 s 0.001 stage 3 of earth fault overcurrent protection Non_Direction 45 50/51G3.Opt_Dir The setting used to select the al; Non_Directio Forward; nal - - Reverse directional mode of stage 3 of earth fault overcurrent protection. The logic setting enabling/disabling for the harmonic control element of the stage 3 of earth fault overcurrent protection 46 50/51G3.En_Hm_Blk Disabled; Enabled Disabled: stage 3 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 3 of earth fault overcurrent protection is controlled by the harmonic control element The 47 50/51G3.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 3 of earth fault overcurrent protection Enabling stage 3 earth fault 48 50/51G3.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 9 9-45 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 49 50/51G3.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - - characteristic curve of stage 3 of IECV; operation earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 50 50/51G3.Opt_Curve_ DropOut characteristic curve of stage 3 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 51 50/51G3.TMS 0.04~ 20 1 - 0.001 stage 3 of earth fault overcurrent protection The minimum operating time 52 50/51G3.tmin 0 ~10 0.02 s 0.001 setting of stage 3 of earth fault overcurrent protection The 9 constant customized 53 50/51G3.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 3 the earth of fault overcurrent protection The constant customized 54 50/51G3.Alpha 0.01 ~3 0.02 - 0.0001 “α” of operation characteristic stage of 3 the inverse-time earth of fault overcurrent protection PCS-9613S Differential Relay 9-46 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description The constant “C” customized 55 50/51G3.C 0 ~1 0 - 0.0001 of the inverse-time operation characteristic stage of 3 earth of fault overcurrent protection The setting used to select the residual current that used for stage 56 50/51G4.Opt_3I0 Ext; Cal Ext - - 4 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 4 57 50/51G4.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection The operating time setting of 58 50/51G4.t_Op 0 ~100 0.1 s 0.001 stage 4 of earth fault overcurrent protection The dropout time setting of 59 50/51G4.t_DropOut 0 ~100 0 s 0.001 stage 4 of earth fault overcurrent protection Non_Direction 60 50/51G4.Opt_Dir The setting used to select the al; Non_Directio Forward; nal - - Reverse directional mode of stage 4 of earth fault overcurrent protection. The logic setting enabling/disabling for the harmonic control element of the stage 4 of earth fault overcurrent protection 61 50/51G4.En_Hm_Blk Disabled; Enabled Disabled: stage 4 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 4 of earth fault overcurrent protection is controlled by the harmonic control element PCS-9613S Differential Relay 9-47 Date: 2020-09-02 9 9 Settings No. Settings Range Default Uni value t Step Description The 62 50/51G4.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 4 of earth fault overcurrent protection Enabling stage 4 earth fault 63 50/51G4.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 64 50/51G4.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - - characteristic curve of stage 4 of IECV; operation earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 65 50/51G4.Opt_Curve_ DropOut characteristic curve of stage 4 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout 9 IDMT: inverse-time dropout The time multiplier setting of 66 50/51G4.TMS 0.04~ 20 1 - 0.001 stage 4 of earth fault overcurrent protection The minimum operating time 67 50/51G4.tmin 0 ~10 0.02 s 0.001 setting of stage 4 of earth fault overcurrent protection PCS-9613S Differential Relay 9-48 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description The constant customized 68 50/51G4.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 4 the earth of fault overcurrent protection The constant customized 69 50/51G4.Alpha 0.01 ~3 0.02 - 0.0001 “α” of inverse-time operation characteristic stage of 4 the earth of fault overcurrent protection The constant customized 70 50/51G4.C 0 ~1 0 - 0.0001 “C” of operation characteristic stage of 4 the inverse-time earth of fault overcurrent protection The setting used to select the residual current that used for stage 71 50/51G5.Opt_3I0 Ext; Cal Ext - - 5 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 5 72 50/51G5.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection The operating time setting of 73 50/51G5.t_Op 0 ~100 0.1 s 0.001 stage 5 of earth fault overcurrent protection The dropout time setting of 74 50/51G5.t_DropOut 0 ~100 0 s 0.001 stage 5 of earth fault overcurrent protection Non_Direction 75 50/51G5.Opt_Dir The setting used to select the al; Non_Directio Forward; nal Reverse - - directional mode of stage 5 of earth fault overcurrent protection. PCS-9613S Differential Relay 9-49 Date: 2020-09-02 9 9 Settings No. Settings Range Default Uni value t Step Description The logic setting enabling/disabling for the harmonic control element of the stage 5 of earth fault overcurrent protection 76 50/51G5.En_Hm_Blk Disabled; Enabled Disabled: stage 5 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 5 of earth fault overcurrent protection is controlled by the harmonic control element The 77 50/51G5.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 5 of earth fault overcurrent protection Enabling stage 5 earth fault 78 50/51G5.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 79 50/51G5.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - characteristic curve of stage 5 of IECV; 9 - operation earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine PCS-9613S Differential Relay 9-50 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description The setting for selecting the inverse-time 80 50/51G5.Opt_Curve_ DropOut characteristic curve of stage 5 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 81 50/51G5.TMS 0.04~ 20 1 - 0.001 stage 5 of earth fault overcurrent protection The minimum operating time 82 50/51G5.tmin 0 ~10 0.02 s 0.001 setting of stage 5 of earth fault overcurrent protection The constant customized 83 50/51G5.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 5 the earth of fault overcurrent protection The constant customized 84 50/51G5.Alpha 0.01 ~3 0.02 - 0.0001 “α” of inverse-time operation characteristic stage of 5 the earth of fault overcurrent protection The constant customized 85 50/51G5.C 0 ~1 0 - 0.0001 “C” of operation characteristic stage of 5 the inverse-time earth of fault overcurrent protection The setting used to select the residual current that used for stage 86 50/51G6.Opt_3I0 Ext; Cal Ext - - 6 of earth fault overcurrent protection Ext: the measured residual current Cal: the calculated residual current The current setting of stage 6 87 50/51G6.3I0_Set 0.05~200 15 A 0.001 of earth fault overcurrent protection PCS-9613S Differential Relay 9-51 Date: 2020-09-02 9 9 Settings No. Settings Range Default Uni value t Step Description The operating time setting of 88 50/51G6.t_Op 0 ~100 0.1 s 0.001 stage 6 of earth fault overcurrent protection The dropout time setting of 89 50/51G6.t_DropOut 0 ~100 0 s 0.001 stage 6 of earth fault overcurrent protection Non_Direction 90 50/51G6.Opt_Dir The setting used to select the al; Non_Directio Forward; nal - - Reverse directional mode of stage 6 of earth fault overcurrent protection. The logic setting enabling/disabling for the harmonic control element of the stage 6 of earth fault overcurrent protection 91 50/51G6.En_Hm_Blk Disabled; Enabled Disabled: stage 6 of earth fault Disabled - - overcurrent protection is not controlled by the harmonic control element Enabled: stage 6 of earth fault overcurrent protection is controlled by the harmonic control element The 92 50/51G6.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 6 of earth fault overcurrent protection Enabling stage 6 earth fault 93 50/51G6.Opt_Trp/Alm Trp; Alm overcurrent protection operate Trp - - to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 9 PCS-9613S Differential Relay 9-52 Date: 2020-09-02 9 Settings No. Settings Range Default Uni value t Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 94 50/51G6.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - - characteristic curve of stage 6 of IECV; operation earth fault overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 95 50/51G6.Opt_Curve_ DropOut characteristic curve of stage 6 Inst; DefTime; dropout Inst - - IDMT of earth fault overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 96 50/51G6.TMS 0.04~ 20 1 - 0.001 stage 6 of earth fault overcurrent protection The minimum operating time 97 50/51G6.tmin 0 ~10 0.02 s 0.001 setting of stage 6 of earth fault overcurrent protection The constant customized 98 50/51G6.K 0.001~120 0.14 - 0.0001 “k” of inverse-time operation characteristic stage of 6 the earth of fault overcurrent protection The constant customized 99 50/51G6.Alpha 0.01 ~3 0.02 - 0.0001 “α” of operation characteristic stage of 6 the inverse-time earth of fault overcurrent protection PCS-9613S Differential Relay 9-53 Date: 2020-09-02 9 9 Settings No. Settings Range Default Uni value t Step Description The constant customized 100 50/51G6.C 0 ~1 0 - 0.0001 “C” of inverse-time operation characteristic stage of 6 the earth of fault overcurrent protection 9.2.6 Negative-sequence Overcurrent Protection Settings ⚫ Access path: MainMenu Settings Protection Settings NegOC Settings Table 9.2-6 Settings of negative-sequence overcurrent protection No. Settings Default Range value Unit Step Description The relay characteristic angle 1 50/51Q.DIR.RCA -180~179 45 deg 1 of the direction control element of negative-sequence overcurrent protection The minimum boundary of the 2 50/51Q.DIR.phi_Min_ Fwd 10~90 90 deg 1 forward direction element of negative-sequence overcurrent protection The maximum boundary of the 3 50/51Q.DIR.phi_Max _Fwd 10~90 90 deg 1 forward direction element of negative-sequence overcurrent protection The minimum boundary of the 4 50/51Q.DIR.phi_Min_ Rev 10~90 90 deg 1 reverse direction element of negative-sequence overcurrent protection The maximum boundary of the 9 5 50/51Q.DIR.phi_Max _Rev 10~90 90 deg 1 reverse direction element of negative-sequence overcurrent protection The minimum operating current setting for the direction 6 50/51Q.DIR.I2_Min (0.05~1)In 0.05 - 0.001 control element of negative-sequence overcurrent protection PCS-9613S Differential Relay 9-54 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The minimum operating voltage setting for the direction 7 50/51Q.DIR.U2_Min 1.0~10.0 4 V 0.001 control element of negative-sequence overcurrent protection Logic setting to determine the behaviour of negative-sequence overcurrent protection when VT circuit supervision function is enabled and VT circuit 8 50/51Q.En_VTS_Blk Disabled; Enabled failure happens. Disabled - - Disabled: negative-sequence overcurrent protection will not affected by VT circuit failure Enabled: voltage controlled negative-sequence overcurrent protection will be blocked by VT circuit failure signal The current setting of stage 1 9 50/51Q1.I2_Set 0.05~200 15 A 0.001 of negative-sequence overcurrent protection The operating time setting of 10 50/51Q1.t_Op 0.03 ~100 0.1 s 0.001 stage 1 of negative-sequence overcurrent protection The dropout time setting of 11 50/51Q1.t_DropOut 0 ~100 0 s 0.001 stage 1 of negative-sequence overcurrent protection Non_Direction 12 50/51Q1.Opt_Dir The setting used to select the al Non_Directio Forward nal - - Reverse directional mode of stage 1 of negative-sequence The 13 50/51Q1.En Disabled; Enabled 9 overcurrent protection. Enabled - - logic setting for enabling/disabling the stage 1 of negative-sequence overcurrent protection PCS-9613S Differential Relay 9-55 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description Enabling stage 1 of negative-sequence 14 50/51Q1.Opt_Trp/Alm Trp; Alm Trp - - overcurrent protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 15 50/51Q1.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - - characteristic curve of stage 1 of IECV; operation negative-sequence overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 16 50/51Q1.Opt_Curve_ DropOut characteristic curve of stage 1 Inst; DefTime; dropout Inst - - IDMT of negative-sequence overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 9 17 50/51Q1.TMS 0.04~ 20 1 - 0.001 stage 1 of negative-sequence overcurrent protection The minimum operating time 18 50/51Q1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of of the negative-sequence overcurrent protection The constant customized 19 50/51Q1.K 0.001~120 0.14 - 0.0001 operation “k” inverse-time characteristic of stage 1 of negative-sequence overcurrent protection PCS-9613S Differential Relay 9-56 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The constant customized 20 50/51Q1.Alpha 0.01 ~3 0.02 - 0.0001 operation “α” of the inverse-time characteristic of stage 1 of negative-sequence overcurrent protection The constant customized 21 50/51Q1.C 0 ~1 0 - 0.0001 operation “C” of the inverse-time characteristic of stage 1 of negative-sequence overcurrent protection The current setting of stage 2 22 50/51Q2.I2_Set 0.05~200 15 A 0.001 of negative-sequence overcurrent protection The operating time setting of 23 50/51Q2.t_Op 0.03 ~100 0.1 s 0.001 stage 2 of negative-sequence overcurrent protection The dropout time setting of 24 50/51Q2.t_DropOut 0 ~100 0 s 0.001 stage 2 of negative-sequence overcurrent protection Non_Direction 25 50/51Q2.Opt_Dir The setting used to select the al Non_Directio Forward nal - - Reverse directional mode of stage 2 of negative-sequence overcurrent protection. The 26 50/51Q2.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 2 of negative-sequence overcurrent protection Enabling stage 2 of negative-sequence 27 50/51Q2.Opt_Trp/Alm Trp; Alm Trp - - overcurrent protection operate to trip or alarm. 9 Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 9-57 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting the ANSILTV; 28 50/51Q2.Opt_Curve ANSILT; IECN; inverse-time IECDefTime - - characteristic curve of stage 2 of IECV; operation negative-sequence overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time 29 50/51Q2.Opt_Curve_ DropOut characteristic curve of stage 2 Inst; DefTime; dropout Inst - - IDMT of negative-sequence overcurrent protection Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The time multiplier setting of 30 50/51Q2.TMS 0.04~ 20 1 - 0.001 stage 2 of negative-sequence overcurrent protection The minimum operating time 31 50/51Q2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of of the negative-sequence overcurrent protection The 9 constant customized 32 50/51Q2.K 0.001~120 0.14 - 0.0001 operation “k” inverse-time characteristic of stage 2 of negative-sequence overcurrent protection The constant customized 33 50/51Q2.Alpha 0.01 ~3 0.02 - 0.0001 operation “α” of the inverse-time characteristic of stage 2 of negative-sequence overcurrent protection PCS-9613S Differential Relay 9-58 Date: 2020-09-02 9 Settings No. Settings Default Range Unit value Step Description The constant “C” customized 34 50/51Q2.C 0 ~1 0 - 0.0001 operation of the inverse-time characteristic of stage 2 of negative-sequence overcurrent protection 9.2.7 RMS Overcurrent Protection Settings ⚫ Access path: MainMenu Settings Protection Settings RMS OC Settings Table 9.2-7 Settings of RMS overcurrent protection No. Settings Default Range value Unit Step Description The current setting of 1 50/51R1.I_Set 0.05~200 15 A 0.001 stage 1 of RMS overcurrent protection The 2 50/51R1.t_Op 0 ~100 0.1 s 0.001 operating time setting of stage 1 of RMS overcurrent protection The 3 50/51R1.t_DropOut 0 ~100 0 s 0.001 drop-out time setting of stage 1 of RMS overcurrent protection The logic setting for 4 50/51R1.En Disabled; Enabled Enabled - - enabling/disabling stage 1 of the RMS overcurrent protection Enabling stage 1 of 5 50/51R1.Opt_Trp/Alm Trp; Alm Trp - - RMS overcurrent protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 9-59 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting ANSILTV; 6 50/51R1.Opt_Curve ANSILT; the IECDefTime IECN; - - inverse-time operation characteristic curve of stage 1 of RMS IECV; overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time dropout characteristic curve of stage Inst; 7 50/51R1.Opt_Curve_DropOut 1 of RMS overcurrent protection DefTime; Inst - - IDMT Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The 8 50/51R1.TMS 0.04~ 20 1 - 0.001 time multiplier setting of stage 1 of RMS overcurrent protection The minimum operating 9 9 50/51R1.tmin 0 ~10 0.02 s 0.001 time setting of stage 1 of RMS overcurrent protection The constant “k” of the customized 10 50/51R1.K 0.001~120 0.14 - 0.0001 inverse-time operation characteristic of stage 1 of RMS overcurrent protection PCS-9613S Differential Relay 9-60 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The constant “α” of the customized 11 50/51R1.Alpha 0.01 ~3 0.02 - 0.0001 inverse-time operation characteristic of stage 1 of RMS overcurrent protection The constant “C” of the customized 12 50/51R1.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 1 of RMS overcurrent protection The current setting of 13 50/51R2.I_Set 0.05~200 15 A 0.001 stage 2 of RMS overcurrent protection The 14 50/51R2.t_Op 0 ~100 0.1 s 0.001 operating time setting of stage 2 of RMS overcurrent protection The 15 50/51R2.t_DropOut 0 ~100 0 s 0.001 drop-out time setting of stage 2 of RMS overcurrent protection The logic setting for 16 50/51R2.En Disabled; Enabled Enabled - - enabling/disabling stage 2 of the RMS overcurrent protection Enabling stage 2 of 17 50/51R2.Opt_Trp/Alm Trp; Alm Trp - - RMS overcurrent protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 9-61 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Description ANSIE; ANSIV; ANSIN; ANSIM; ANSIDefTime; ANSILTE; The setting for selecting ANSILTV; 18 50/51R2.Opt_Curve ANSILT; the IECDefTime IECN; - - inverse-time operation characteristic curve of stage 2 of RMS IECV; overcurrent protection. IEC; IECE; IECST; IECLT; IECDefTime; UserDefine The setting for selecting the inverse-time dropout characteristic curve of stage Inst; 19 50/51R2.Opt_Curve_DropOut 2 of RMS overcurrent protection DefTime; Inst - - IDMT Inst: instantaneous dropout DefTime: definite-time dropout IDMT: inverse-time dropout The 20 50/51R2.TMS 0.04~ 20 1 - 0.001 time multiplier setting of stage 2 of RMS overcurrent protection The minimum operating 9 21 50/51R2.tmin 0 ~10 0.02 s 0.001 time setting of stage 2 of RMS overcurrent protection The constant “k” of the customized 22 50/51R2.K 0.001~120 0.14 - 0.0001 inverse-time operation characteristic of stage 2 of RMS overcurrent protection PCS-9613S Differential Relay 9-62 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The constant “α” of the customized 23 50/51R2.Alpha 0.01 ~3 0.02 - 0.0001 inverse-time operation characteristic of stage 2 of RMS overcurrent protection The constant “C” of the customized 24 50/51R2.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 2 of RMS overcurrent protection 9.2.8 Broken Conductor Protection (46BC) ⚫ Access path: MainMenuSettingsProtection SettingsBCP Settings Table 9.2-8 Settings of broken conductor protection No. 1 Setting 46BC.I_Min Range (0.05~40) In Default 1.000 Unit Step A 0.001 Description Minimum operating current setting of broken conductor protection Ratio 2 46BC.I2/I1_Set 0~5 0.500 - 0.001 setting (negative-sequence current to positive-sequence current) of broken conductor protection 3 46BC.t_Op 4 46BC.En 0~10 Disabled Enabled 1.000 s 0.001 Enabled - - Time delay of broken conductor protection Enabling/disabling broken conductor protection Enabling/disabling broken conductor 5 46BC.Opt_Trp/Alm Trp Alm Trp - - protection operate to trip or alarm Trp: for tripping purpose 9 Alm: for alarm purpose 9.2.9 Phase Overvoltage Protection Settings ⚫ Access path: MainMenu Settings Protection Settings OV Settings PCS-9613S Differential Relay 9-63 Date: 2020-09-02 9 Settings Table 9.2-9 Settings of phase overvoltage protection No. Settings Default Range value Unit Step Description Option of phase-to-phase voltage or phase voltage for 1 59P.Opt_Up/Upp Up; Upp Upp - - overvoltage protection Up: phase voltage Upp: phase-to-phase voltage Option of 1-out-of-3 mode or 2 59P.Opt_1P/3P 3-out-of-3 3P; 3P 1P - - mode for overvoltage protection 3P: 3-out-of-3 mode 1P: 1-out-of-3 mode The voltage setting of stage 3 59P1.U_Set 57.7~200 115 V 0.001 1 of phase overvoltage protection The dropout coefficient of 4 59P1.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 1 of phase overvoltage protection The operating time setting of 5 59P1.t_Op 0.1 ~100 1 s 0.001 stage 1 of phase overvoltage protection The dropout time setting of 6 59P1.t_DropOut 0 ~100 0 s 0.001 stage 1 of phase overvoltage protection The 7 59P1.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 1 of phase overvoltage protection Enabling stage 1 of phase 9 8 59P1.Opt_Trp/Alm overvoltage Trp; Trp Alm - - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose The setting for selecting the ANSIDefTime; 9 59P1.Opt_Curve IECDefTime; UserDefine; inverse-time IECDefTime - - characteristic curve of stage 1 InvTime_U operation of phase overvoltage protection. PCS-9613S Differential Relay 9-64 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The setting for selecting the inverse-time dropout characteristic curve of stage 10 59P1.Opt_Curve_DropOut Inst; DefTime Inst - - 1 of phase overvoltage protection Inst: instantaneous dropout DefTime: definite-time dropout The time multiplier setting of 11 59P1.TMS 0.04~ 20 1 - 0.001 stage 1 of phase overvoltage protection The minimum operating time 12 59P1.tmin 0 ~10 0.02 s 0.001 setting of stage 1 of phase overvoltage protection The constant “k” of the customized 13 59P1.K 0.001~120 1 - 0.0001 inverse-time operation characteristic of stage 1 of phase overvoltage protection The constant “α” of the customized 14 59P1.Alpha 0.01 ~3 1 - 0.0001 inverse-time operation characteristic of stage 1 of phase overvoltage protection The constant “C” of the customized 15 59P1.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 1 of phase overvoltage protection The voltage setting of stage 16 59P2.U_Set 57.7~200 115 V 0.001 2 of phase overvoltage protection The dropout coefficient of 17 59P2.K_DropOut 0.93 ~1.00 0.98 - 0.001 stage 2 of phase overvoltage protection The operating time setting of 18 59P2.t_Op 0.1 ~100 1 s 0.001 stage 2 of phase overvoltage protection The dropout time setting of 19 59P2.t_DropOut 0 ~100 0 s 0.001 stage 2 of phase overvoltage protection PCS-9613S Differential Relay 9-65 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Description The 20 59P2.En Disabled; Enabled Enabled - - logic setting for enabling/disabling the stage 2 of phase overvoltage protection Enabling stage 2 of phase 21 59P2.Opt_Trp/Alm overvoltage Trp; Trp Alm - - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose The setting for selecting the ANSIDefTime; 22 59P2.Opt_Curve IECDefTime; UserDefine; inverse-time IECDefTime - - 2 InvTime_U operation characteristic curve of stage of phase overvoltage protection. The setting for selecting the inverse-time dropout characteristic curve of stage 23 59P2.Opt_Curve_DropOut Inst; DefTime Inst - - 2 of phase overvoltage protection Inst: instantaneous dropout DefTime: definite-time dropout The time multiplier setting of 24 59P2.TMS 0.04~ 20 1 - 0.001 stage 2 of phase overvoltage protection The minimum operating time 25 59P2.tmin 0 ~10 0.02 s 0.001 setting of stage 2 of phase overvoltage protection The constant “k” of the customized 26 59P2.K 0.001~120 1 - 0.0001 9 inverse-time operation characteristic of stage 2 of phase overvoltage protection The constant “α” of the customized 27 59P2.Alpha 0.01 ~3 1 - 0.0001 inverse-time operation characteristic of stage 2 of phase overvoltage protection PCS-9613S Differential Relay 9-66 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The constant “C” of the customized 28 59P2.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 2 of phase overvoltage protection 9.2.10 Residual Overvoltage Protection Settings ⚫ Access path: MainMenu Settings Protection Settings ROV Settings Table 9.2-10 Settings of residual overvoltage protection No. Settings Range Default value Unit Step 1 59G1.3U0_Set 1~200 50 V 0.001 2 59G1.K_DropOut 0.93 ~1 0.98 - 0.001 3 59G1.t_Op 0.1 ~100 1 s 0.001 4 59G1.t_DropOut 0 ~100 0 s 0.001 5 59G1.En Enabled - - Disabled; Enabled Description The voltage setting of stage 1 of residual overvoltage protection The dropout coefficient of stage 1 of residual overvoltage protection The operating time setting of stage 1 of residual overvoltage protection The dropout time setting of stage 1 of residual overvoltage protection The logic setting for enabling/disabling the stage 1 of residual overvoltage protection Enabling stage 1 of residual overvoltage 6 59G1.Opt_Trp/Alm Trp; Alm Trp - - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 7 59G2.3U0_Set 1~200 50 V 0.001 8 59G2.K_DropOut 0.93 ~1 0.98 - 0.001 9 59G2.t_Op 0.1 ~100 1 s 0.001 10 59G2.t_DropOut 0 ~100 0 s 0.001 11 59G2.En Enabled - - Disabled; Enabled The voltage setting of stage 2 of residual overvoltage protection The dropout coefficient of stage 2 of residual overvoltage protection The operating time setting of stage 2 of residual overvoltage protection The dropout time setting of stage 2 of residual overvoltage protection The logic setting for enabling/disabling the stage 2 of residual overvoltage protection Enabling stage 2 of residual overvoltage 12 59G2.Opt_Trp/Alm Trp; Alm Trp - - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose PCS-9613S Differential Relay 9-67 Date: 2020-09-02 9 9 Settings 9.2.11 Negative-sequence Overvoltage Protection Settings ⚫ Access path: MainMenu Settings Protection Settings NegOV Settings Table 9.2-11 Settings of negative-sequence overvoltage protection No. 1 Setting 59Q1.U2_Set Range 2~100 Default 15 Unit Step V 0.001 Description The voltage setting of the stage 1 of negative-sequence overvoltage protection The dropout coefficient setting of the stage 2 59Q1.K_DropOut 0.93~1 0.98 - 0.001 1 of negative-sequence overvoltage protection 3 59Q1.t_Op 0.1~100 1 s 0.001 4 59Q1.t_DropOut 0~100 0 s 0.001 5 59Q1.En Enabled - - Disabled; Enabled The time setting of the stage 1 of negative-sequence overvoltage protection The dropout time setting of the stage 1 of negative-sequence overvoltage protection The logic setting of the stage 1 of negative-sequence overvoltage protection Enabling stage 1 of negative-sequence 6 59Q1.Opt_Trp/Alm Trp; Alm Trp - - overvoltage operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 7 59Q2.U2_Set 2~100 15 V 0.001 The voltage setting of the stage 2 of negative-sequence overvoltage protection The dropout coefficient setting of the stage 8 59Q2.K_DropOut 0.93~1 0.98 - 0.001 2 of negative-sequence overvoltage protection 9 59Q2.t_Op 0.1~100 1 s 0.001 10 59Q2.t_DropOut 0~100 0 s 0.001 11 59Q2.En Enabled - - 9 Disabled; Enabled The time setting of the stage 2 of negative-sequence overvoltage protection The dropout time setting of the stage 2 of negative-sequence overvoltage protection The logic setting of the stage 2 of negative-sequence overvoltage protection Enabling stage 2 of negative-sequence 12 59Q2.Opt_Trp/Alm Trp; Alm Trp - - overvoltage operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose 9.2.12 Positive-sequence Overvoltage Protection Settings ⚫ Access path: MainMenu Settings Protection Settings PosOV Settings PCS-9613S Differential Relay 9-68 Date: 2020-09-02 9 Settings Table 9.2-12 Settings of positive-sequence overvoltage protection No. Setting Range Default Unit Step 1 59Pos.U1_Set 2~100 60 V 0.001 2 59Pos.K_DropOut 0.93~1 0.98 - 0.001 3 59Pos.t_Op 0.1~100 1 s 0.001 4 59Pos.t_DropOut 0~100 0 s 0.001 5 59Pos.En Enabled - - Disabled; Enabled Description The voltage 59Pos.Opt_Trp/Alm Trp; Trp Alm - of the positive-sequence overvoltage protection The dropout coefficient setting of the positive-sequence overvoltage protection The time setting of the positive-sequence overvoltage protection The dropout time setting of the positive-sequence overvoltage protection The logic setting of the positive-sequence overvoltage protection Enabling 6 setting the positive-sequence overvoltage operate to trip or alarm. - Trp: for tripping purpose Alm: for alarm purpose 9.2.13 Phase Undervoltage Protection Settings ⚫ Access path: MainMenu Settings Protection Settings UV Settings Table 9.2-13 Settings of phase undervoltage protection No. Settings Range Default value Unit Step Description Option of phase-to-phase voltage or phase voltage 1 27P.Opt_Up/Upp Up; Upp for Upp - - stage x of undervoltage protection Up: phase voltage Upp: phase-to-phase voltage Option of 1-out-of-3 mode or 3-out-of-3 mode for 2 27P.Opt_1P/3P 3P; 1P 3P - - stage x of undervoltage protection 3P: 3-out-of-3 mode 1P: 1-out-of-3 mode PCS-9613S Differential Relay 9-69 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Description Breaker closed position check mode None: no check Curr: check the current 3 27P.Opt_LogicMode None; CBPos: Curr; normally CBPos; Curr - - check open the auxiliary contact CurrOrCBPos; CurrOrCBPos: check the CurrAndCBPos current and normally open auxiliary contact CurrAndCBPos: check the current or normally open auxiliary contact The voltage setting of 4 27P1.U_Set 5~120 80 V 0.001 stage 1 of phase undervoltage protection The dropout coefficient of 5 27P1.K_DropOut 1~1.2 1.03 - 0.001 stage 1 of phase undervoltage protection The operating time setting 6 27P1.t_Op 0.1 ~100 1 s 0.001 of stage 1 of phase undervoltage protection The dropout time setting 7 27P1.t_DropOut 0 ~100 0 s 0.001 of stage 1 of phase undervoltage protection Logic setting to determine the behaviour of stage 1 of phase undervoltage protection when VT circuit 8 27P1.En_VTS_Blk 9 Disabled; Enabled supervision Disabled - - function is enabled and VT circuit failure happens. Disabled: it is not affected by VT circuit failure Enabled: it will be blocked by VT circuit failure signal The 9 27P1.En Disabled; Enabled Enabled - - logic setting enabling/disabling stage 1 of for the phase undervoltage protection PCS-9613S Differential Relay 9-70 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description Enabling stage 1 of phase 10 27P1.Opt_Trp/Alm undervoltage Trp; Trp Alm - - protection operate to trip or alarm. Trp: for tripping purpose Alm: for alarm purpose The setting for selecting ANSIDefTime; 11 27P1.Opt_Curve IECDefTime; UserDefine; the inverse-time operation IECDefTime - - characteristic stage InvTime_U curve 1 of of phase undervoltage protection. The setting for selecting the inverse-time dropout characteristic 12 27P1.Opt_Curve_DropOut Inst; DefTime stage Inst - - curve 1 of of phase undervoltage protection Inst: instantaneous dropout DefTime: definite-time dropout The time multiplier setting 13 27P1.TMS 0.04~ 20 1 - 0.001 of stage 1 of phase undervoltage protection The minimum operating 14 27P1.tmin 0.03 ~10 0.03 s 0.001 time setting of stage 1 of phase undervoltage protection The constant “k” of the customized 15 27P1.K 0.001~120 0.14 - 0.0001 inverse-time operation characteristic of stage 1 of phase undervoltage protection The constant “α” of the customized 16 27P1.Alpha 0.01 ~3 0.02 - 0.0001 inverse-time operation characteristic of stage 1 of phase undervoltage protection The constant “C” of the customized 17 27P1.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 1 of phase undervoltage protection PCS-9613S Differential Relay 9-71 Date: 2020-09-02 9 9 Settings No. Settings Default Range value Unit Step Description The voltage setting of 18 27P2.U_Set 5~120 80 V 0.001 stage 2 of phase undervoltage protection The dropout coefficient of 19 27P2.K_DropOut 1~1.2 1.03 - 0.001 stage 2 of phase undervoltage protection The operating time setting 20 27P2.t_Op 0.1 ~100 1 s 0.001 of stage 2 of phase undervoltage protection The dropout time setting 21 27P2.t_DropOut 0 ~100 0 s 0.001 of stage 2 of phase undervoltage protection Logic setting to determine the behaviour of stage 2 of phase undervoltage protection when VT circuit 22 27P2.En_VTS_Blk supervision Disabled; Disabled Enabled - - function is enabled and VT circuit failure happens. Disabled: it is not affected by VT circuit failure Enabled: it will be blocked by VT circuit failure signal The 23 27P2.En Disabled; Enabled Enabled - - logic setting enabling/disabling stage 2 of for the phase undervoltage protection Enabling stage 2 of phase 24 27P2.Opt_Trp/Alm undervoltage Trp; Trp Alm - - protection operate to trip or alarm. Trp: for tripping purpose 9 Alm: for alarm purpose The setting for selecting ANSIDefTime; 25 27P2.Opt_Curve IECDefTime; UserDefine; the inverse-time operation IECDefTime - - characteristic stage InvTime_U 2 curve of of phase undervoltage protection. PCS-9613S Differential Relay 9-72 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description The setting for selecting the inverse-time dropout characteristic 26 27P2.Opt_Curve_DropOut stage Inst; Inst DefTime - - curve 2 of of phase undervoltage protection Inst: instantaneous dropout DefTime: definite-time dropout The time multiplier setting 27 27P2.TMS 0.04~ 20 1 - 0.001 of stage 2 of phase undervoltage protection The minimum operating 28 27P2.tmin 0.03 ~10 0.03 s 0.001 time setting of stage 2 of phase undervoltage protection The constant “k” of the customized 29 27P2.K 0.001~120 0.14 - 0.0001 inverse-time operation characteristic of stage 2 of phase undervoltage protection The constant “α” of the customized 30 27P2.Alpha 0.01 ~3 0.02 - 0.0001 inverse-time operation characteristic of stage 2 of phase undervoltage protection The constant “C” of the customized 31 27P2.C 0 ~1 0 - 0.0001 inverse-time operation characteristic of stage 2 of phase undervoltage protection 9 9.2.14 Frequency Protection Settings ⚫ Access path: MainMenu Settings Protection Settings FreqProt Settings Table 9.2-14 Settings of frequency protection No. Setting Range Default Unit Step Description The setting of the low voltage blocking 1 81.Upp_Blk 10~150 70 V 0.001 element of the frequency protection (phase-to-phase voltage) PCS-9613S Differential Relay 9-73 Date: 2020-09-02 9 Settings 9 2 81O1.f_Set 50~65 52 Hz 0.001 3 81O1.t_Op 0.1~100 0.3 s 0.001 4 81O1.En Enabled - - 5 81O2.f_Set 50~65 52 Hz 0.001 6 81O2.t_Op 0.1~100 0.3 s 0.001 7 81O2.En Enabled - - 8 81O3.f_Set 50~65 52 Hz 0.001 9 81O3.t_Op 0.1~100 0.3 s 0.001 10 81O3.En Enabled - - 11 81O4.f_Set 50~65 52 Hz 0.001 12 81O4.t_Op 0.1~100 0.3 s 0.001 13 81O4.En Enabled - - 14 81O5.f_Set 50~65 52 Hz 0.001 15 81O5.t_Op 0.1~100 0.3 s 0.001 16 81O5.En Enabled - - 17 81O6.f_Set 50~65 52 Hz 0.001 18 81O6.t_Op 0.1~100 0.3 s 0.001 19 81O6.En Enabled - - 26 81U1.f_Set 45~60 48 Hz 0.001 27 81U1.t_Op 0.1~100 0.3 s 0.001 28 81U1.En Enabled - - 29 81U2.f_Set 48 Hz 0.001 Disabled; Enabled Disabled; Enabled Disabled; Enabled Disabled; Enabled Disabled; Enabled Disabled; Enabled Disabled; Enabled 45~60 The frequency setting of the stage 1 of overfrequency protection The time setting of the stage 1 of overfrequency protection The logic setting of the stage 1 of overfrequency protection The frequency setting of the stage 2 of overfrequency protection The time setting of the stage 2 of overfrequency protection The logic setting of the stage 2 of overfrequency protection The frequency setting of the stage 3 of overfrequency protection The time setting of the stage 3 of overfrequency protection The logic setting of the stage 3 of overfrequency protection The frequency setting of the stage 4 of overfrequency protection The time setting of the stage 4 of overfrequency protection The logic setting of the stage 4 of overfrequency protection The frequency setting of the stage 5 of overfrequency protection The time setting of the stage 5 of overfrequency protection The logic setting of the stage 5 of overfrequency protection The frequency setting of the stage 6 of overfrequency protection The time setting of the stage 6 of overfrequency protection The logic setting of the stage 6 of overfrequency protection The frequency setting of the stage 1 of underfrequency protection The time setting of the stage 1 of underfrequency protection The logic setting of the stage 1 of underfrequency protection The frequency setting of the stage 2 of underfrequency protection PCS-9613S Differential Relay 9-74 Date: 2020-09-02 9 Settings 30 81U2.t_Op 31 81U2.En 32 81U3.f_Set 33 81U3.t_Op 34 81U3.En 35 81U4.f_Set 36 81U4.t_Op 37 81U4.En 38 81U5.f_Set 39 81U5.t_Op 40 81U5.En 41 81U6.f_Set 42 81U6.t_Op 43 81U6.En 44 81R1.df/dt_Set 45 46 0.3 s 0.001 Enabled - - 45~60 48 Hz 0.001 0.1~100 0.3 s 0.001 Enabled - - 45~60 48 Hz 0.001 0.1~100 0.3 s 0.001 Enabled - - 45~60 48 Hz 0.001 0.1~100 0.3 s 0.001 Enabled - - 45~60 48 Hz 0.001 0.1~100 0.3 s 0.001 Enabled - - -5~5 0.5 Hz/s 0.001 81R1.t_Op 0.1~100 0.1 s 0.001 81R1.f_Pkp 45~65 50 Hz 0.001 47 81R1.En 48 81R2.df/dt_Set 49 0.1~100 Disabled; Enabled Disabled; Enabled Disabled; Enabled Disabled; Enabled Disabled; Enabled Disabled; Enabled - - -5~5 0.5 Hz/s 0.001 81R2.t_Op 0.1~100 0.1 s 0.001 50 81R2.f_Pkp 45~65 50 Hz 0.001 51 81R2.En Enabled - - Enabled Disabled; Enabled PCS-9613S Differential Relay The time setting of the stage 2 of underfrequency protection The logic setting of the stage 2 of underfrequency protection The frequency setting of the stage 3 of underfrequency protection The time setting of the stage 3 of underfrequency protection The logic setting of the stage 3 of underfrequency protection The frequency setting of the stage 4 of underfrequency protection The time setting of the stage 4 of underfrequency protection The logic setting of the stage 4 of underfrequency protection The frequency setting of the stage 5 of underfrequency protection The time setting of the stage 5 of underfrequency protection The logic setting of the stage 5 of underfrequency protection The frequency setting of the stage 6 of underfrequency protection The time setting of the stage 6 of underfrequency protection The logic setting of the stage 6 of underfrequency protection The rate-of-change setting of the stage 1 of frequency rate-of-change protection The time setting of the stage 1 of frequency rate-of-change protection The pickup frequency setting of the stage 1 9 of frequency rate-of-change protection The logic setting of the stage 1 of frequency rate-of-change protection The rate-of-change setting of the stage 2 of frequency rate-of-change protection The time setting of the stage 2 of frequency rate-of-change protection The pickup frequency setting of the stage 2 of frequency rate-of-change protection The logic setting of the stage 2 of frequency rate-of-change protection 9-75 Date: 2020-09-02 9 Settings 9 52 81R3.df/dt_Set -5~5 0.5 Hz/s 0.001 53 81R3.t_Op 0.1~100 0.1 s 0.001 54 81R3.f_Pkp 45~65 50 Hz 0.001 55 81R3.En Enabled - - 56 81R4.df/dt_Set -5~5 0.5 Hz/s 0.001 57 81R4.t_Op 0.1~100 0.1 s 0.001 58 81R4.f_Pkp 45~65 50 Hz 0.001 59 81R4.En Enabled - - 60 81R5.df/dt_Set -5~5 0.5 Hz/s 0.001 61 81R5.t_Op 0.1~100 0.1 s 0.001 62 81R5.f_Pkp 45~65 50 Hz 0.001 63 81R5.En Enabled - - 64 81R6.df/dt_Set -5~5 0.5 Hz/s 0.001 65 81R6.t_Op 0.1~100 0.1 s 0.001 66 81R6.f_Pkp 45~65 50 Hz 0.001 67 81R6.En Enabled - - Disabled; Enabled Disabled; Enabled Disabled; Enabled Disabled; Enabled The rate-of-change setting of the stage 3 of frequency rate-of-change protection The time setting of the stage 3 of frequency rate-of-change protection The pickup frequency setting of the stage 3 of frequency rate-of-change protection The logic setting of the stage 3 of frequency rate-of-change protection The rate-of-change setting of the stage 4 of frequency rate-of-change protection The time setting of the stage 4 of frequency rate-of-change protection The pickup frequency setting of the stage 4 of frequency rate-of-change protection The logic setting of the stage 4 of frequency rate-of-change protection The rate-of-change setting of the stage 5 of frequency rate-of-change protection The time setting of the stage 5 of frequency rate-of-change protection The pickup frequency setting of the stage 5 of frequency rate-of-change protection The logic setting of the stage 5 of frequency rate-of-change protection The rate-of-change setting of the stage 6 of frequency rate-of-change protection The time setting of the stage 6 of frequency rate-of-change protection The pickup frequency setting of the stage 6 of frequency rate-of-change protection The logic setting of the stage 6 of frequency rate-of-change protection 9.2.15 Reverse Power Protection Settings ⚫ Access path: MainMenu Settings Protection Settings RevPower Settings Table 9.2-15 Settings of reverse power protection No. Setting Range Default Unit Step Description The 1 32R.U1_VCE 5~60 5 V 0.001 voltage setting of the positive-sequence voltage control element of the reverse power protection PCS-9613S Differential Relay 9-76 Date: 2020-09-02 9 Settings The positive-sequence current setting of 2 32R.I1_CCE 0.01~1 0.1 p.u. 0.001 the current control element of the reverse power protection The 3 32R.U2_VCE 8~60 8 V 0.001 voltage setting of the negative-sequence voltage control element of the reverse power protection 4 32R1.P_Set 0.1~10 0.15 p.u. 0.001 5 32R1.t_Op 0.01~100 0.1 s 0.001 6 32R1.En Disabled; Enabled Enabled - The power setting of the stage 1 of reverse power protection The time setting of the stage 1 of reverse power protection The logic setting of the stage 1 of reverse - power protection Enabling 7 32R1.Opt_Trp/Alm Trp; Trp Alm - stage 1 of reverse power protection operate to trip or alarm. - Trp: for tripping purpose Alm: for alarm purpose 8 32R2.P_Set 0.1~10 0.15 p.u. 0.001 9 32R2.t_Op 0.01~100 0.1 s 0.001 10 32R2.En Enabled - - Disabled; Enabled The power setting of the stage 2 of reverse power protection The time setting of the stage 2 of reverse power protection The logic setting of the stage 2 of reverse power protection Enabling 11 32R2.Opt_Trp/Alm Trp; Trp Alm - stage 2 of reverse power protection operate to trip or alarm. - Trp: for tripping purpose Alm: for alarm purpose 9.2.16 Undercurrent Settings ⚫ Access path: MainMenu Settings Protection Settings UC Settings Table 9.2-16 Settings of undercurrent protection No. Setting Range Default Unit Step 1 37.I_Set 0.1~5 0.5 A 0.001 2 37.t_Op 0.1~100 0.1 s 0.001 3 37.Opt_1P/3P 1P; 3P Description The - - setting of the undercurrent protection The time setting of the undercurrent protection The 3P current setting three-phase for selecting criterion (3P) the or single-phase criterion (1P) PCS-9613S Differential Relay 9-77 Date: 2020-09-02 9 9 Settings None; Curr; 4 37.Opt_LogicMode CurrAnd CBPos; CurrAndCBPos; CBPos - - - - The setting of the CB position check mode. CurrOrCBPos 5 37.En Disabled; Enabled Enabled The logic setting of the undercurrent protection Enabling undercurrent protection 6 37.Opt_Trp/Alm Trp; Trp Alm - operate to trip or alarm. - Trp: for tripping purpose Alm: for alarm purpose 9.2.17 Breaker Failure Protection Settings ⚫ Access path: MainMenu Settings Protection Settings BFP Settings Table 9.2-17 Settings of breaker failure protection No. 9 Setting Range Default Unit Step 1 50BF.I_Set 0.05~200 1.000 A 0.001 2 50BF.3I0_Set 0.05~200 1.000 A 0.001 3 50BF.I2_Set 0.05~200 1.000 A 0.001 4 50BF.t_ReTrp 0~20 0.050 s 0.001 5 50BF.t1_Op 0~20 0.100 s 0.001 6 50BF.t2_Op 0~20 0.200 s 0.001 7 50BF.En Enabled - - 8 50BF.En_ReTrp Enabled - - 9 50BF.En_t1 Disabled - - 10 50BF.En_t2 Disabled - - 11 50BF.En_Ip Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Description The phase current setting of breaker failure protection The zero-sequence current setting of breaker failure protection The negative-sequence current setting of breaker failure protection The re-trip time delay of breaker failure protection The first time delay of breaker failure protection The second time delay of breaker failure protection Enabling/disabling - - failure protection Enabling/disabling re-trip function of breaker failure protection Enabling/disabling first time delay of breaker failure protection Enabling/disabling second time delay of breaker failure protection Enabling/disabling Disabled breaker phase overcurrent element of breaker failure protection via three-phases initiating signal PCS-9613S Differential Relay 9-78 Date: 2020-09-02 9 Settings Enabling/disabling 12 50BF.En_3I0_3P Disabled Enabled Disabled - zero-sequence overcurrent element of breaker failure - protection via three-phases initiating signal Enabling/disabling 13 50BF.En_I2_3P Disabled Enabled Disabled - negative-sequence overcurrent element of breaker failure - protection via three-phases initiating signal 14 15 50BF.En_CB_Ctrl 50BF.En_Alm_Init Disabled Enabled Disabled Enabled Enabling/disabling Disabled - - breaker failure protection be initiated by normally closed contact of circuit breaker Disabled - Enabling/disabling abnormality check of - breaker failure initiating signal 9.2.18 Switch-on-to-Fault ProtectionSettings ⚫ Access path: MainMenu Settings Protection Settings SOTF Settings Table 9.2-18 Settings of SOTF protection No. Setting Range Default Unit Step 1 SOTF.t_En 0.2~100 0.4 s 0.001 2 50PSOTF.I_Set 0.05~200 1 A 0.001 3 50PSOTF.Up_Set 0~200 1 V 0.001 4 50PSOTF.Upp_Set 0~200 1 V 0.001 5 50PSOTF.U2_Set 0~200 1 V 0.001 6 50PSOTF.3U0_Set 0~200 1 V 0.001 7 50PSOTF.t_Op 0~100 0.1 s 0.001 8 50PSOTF.En Enabled - - 9 10 50PSOTF.En_Hm2_Blk 50PSOTF.En_Up_UV Disabled Enabled Disabled Enabled Disabled Enabled Description The initiating time for the SOTF protection Current setting of phase overcurrent SOTF protection Voltage setting for phase undervoltage supervision logic Voltage setting for phase-to-phase undervoltage supervision logic Voltage setting for negative-sequence overvoltage supervision logic Voltage setting for zero-sequence overvoltage supervision logic Time delay for phase overcurrent SOTF protection Enabling/disabling phase overcurrent SOTF protection Enabling/disabling second harmonic Disabled - - blocking for phase overcurrent SOTF protection Enabling/disabling Disabled - - phase undervoltage supervision logic for phase overcurrent SOTF protection PCS-9613S Differential Relay 9-79 Date: 2020-09-02 9 9 Settings 11 50PSOTF.En_Upp_UV Enabling/disabling Disabled Disabled Enabled - - phase-to-phase undervoltage supervision logic for phase overcurrent SOTF protection Enabling/disabling 12 Disabled 50PSOTF.En_U2_OV Disabled Enabled - negative-sequence - supervision overvoltage logic for phase overcurrent SOTF protection 13 50PSOTF.En_3U0_OV Enabling/disabling Disabled Disabled Enabled - - overvoltage zero-sequence supervision logic for phase overcurrent SOTF protection The option of the residual current 14 used by earth fault overcurrent SOTF Ext 50GSOTF.Opt_3I0 Cal Cal - - protection Ext: the measured residual current Cal: the calculated residual current 15 50GSOTF.3I0_Set 0.05~200 1 A 0.001 16 50GSOTF.t_Op_3P 0~100 0.1 s 0.001 17 50GSOTF.En Enabled - - 18 Disabled Enabled 50GSOTF.En_Hm2_Blk Current setting of Disabled Enabled - - fault overcurrent SOTF protection Time delay for earth fault overcurrent SOTF protection Enabling/disabling earth fault overcurrent SOTF protection Enabling/disabling Disabled earth earth fault overcurrent SOTF protection blocked by harmonic 9.2.19 Thermal Overload Protection Settings ⚫ Access path: MainMenu Settings Protection Settings ThOvLd Settings Table 9.2-19 Settings of thermal overload protection No. 9 Setting Range Default Unit Step 1 49.Ib_Set 0.05~200 15 A 0.001 2 49.K_Trp 1~3 1.2 - 0.001 3 49.K_Alm 1~3 1.1 - 0.001 4 49.t_Tau 0.1~100 1 min 0.001 5 49.K_T_Diff 0~200 30 - 0.001 6 49.Alpha_Cold 1~2 2 - 0.001 Description The reference current setting of thermal overload protection The thermal overload factor setting for tripping The thermal overload factor setting for alarm The heat accumulation time constant of thermal overload protection The temperature constant of thermal overload protection The cooling factor of thermal overload protection PCS-9613S Differential Relay 9-80 Date: 2020-09-02 9 Settings Heat dissipation time constant setting. 7 49.C_Disspt 0.100~10 .000 1.000 - When the current Ieq is lower than 0.04In, 0.001 the thermal time constant adopts the value of [49.Tau]*[49.C_Disspt]. 8 49.En_Trp 9 49.En_Alm Disabled; Enabled Disabled; Enabled Disabled - - Disabled - - Enabling/Disabling thermal overload protection operate to trip Enabling/Disabling thermal overload protection operate to alarm 9.2.20 Transfer Trip Settings ⚫ Access path: MainMenu Settings Protection Settings TT Settings Table 9.2-20 Settings of transfer trip No. Setting 1 TT.t_Op 2 TT.En 3 TT.En_FD_Ctrl 4 TT.En_BlkAR Range 0.000~60 0.000 Disabled Enabled Disabled Enabled Disabled Enabled Default Unit Step Description 0.005 s 0.001 Time delay of transfer trip Enabled - - Enabling/disabling transfer trip Enabled - - Enabled - - Enabling/disabling transfer trip controlled by local fault detector element Enabling/disabling transfer trip operate to block AR 9.2.21 Automatic Reclosure Settings ⚫ Access path: MainMenu Settings Protection Settings AR Settings Table 9.2-21 Settings of AR No. Settings Range Default value Unit Step 1 79.Num 1~4 1 - 1 2 79.t_Dd_3PS1 0~600 0.600 s 0.001 3 79.t_Dd_3PS2 0~600 0.600 s 0.001 4 79.t_Dd_3PS3 0~600 0.600 s 0.001 5 79.t_Dd_3PS4 0~600 0.600 s 0.001 PCS-9613S Differential Relay Description Maximum number of reclosing 9 attempts Dead time of first shot 3-pole reclosing Dead time of second shot 3-pole reclosing Dead time of third shot 3-pole reclosing Dead time of fourth shot 3-pole reclosing 9-81 Date: 2020-09-02 9 Settings No. 6 Settings 79.t_CBClsd Range 0~600 Default value 5.000 Unit Step s 0.001 Description Time delay of circuit breaker in closed position before reclosing Time delay to wait for CB healthy, and begin to timing when the input 7 79.t_CBReady 0~600 5.000 s 0.001 signal [79.CB_Healthy] de-energized and if it is is not energized within this time delay, AR will be blocked. 8 79.t_Wait_Chk 0~600 10.000 s 0.001 9 79.t_Reclaim 0~600 15.000 s 0.001 Maximum wait time for synchronism check Reclaim time of AR Drop-out time delay of blocking AR, 10 79.t_DDO_Blk 0~600 5.000 s 0.001 when blocking signal for AR disappears, AR blocking condition drops out after this time delay 11 79.t_PersistTrp 0~600 0.200 s 0.001 12 79.t_Fail 0~600 0.200 s 0.001 Time delay of excessive trip signal to block AR Time delay allow for CB status change to conform reclosing successful 13 79.t_PW 14 79.En_FailCheck 15 79.En_CutPulse 16 79.En 0~600 Disabled Enabled Disabled Enabled Disabled Enabled 0.120 s 0.001 Disabled - - Pulse width of AR closing signal Enabling/disabling confirm whether AR is successful by checking CB state Disabled - - Enabled - - Enabling/disabling adjust the length of reclosing pulse Enabling/disabling auto-reclosing Enabling/disabling AR by external input signal besides logic setting 9 17 79.Opt_Enable Setting Setting&Config Setting - - [79.En] Setting: only the setting Setting&Config: the setting and configuration signal 18 79.En_CBInit Disabled Enabled Disabled - - Enabling/disabling AR be initiated by open state of circuit breaker Selection of decision mode for AR 19 79.Opt_RSYN_Valid Setting; Mode Config synchronism check Setting - - Setting: determined by the setting Config: determined by the configuration signal PCS-9613S Differential Relay 9-82 Date: 2020-09-02 9 Settings No. Settings Default Range value Unit Step Description Enabling/disabling 20 79.En_SynChk Disabled Disabled Enabled - synchro-check of AR (valid only if the setting - [79.Opt_RSYN_ValidMode] = Setting) Enabling/disabling dead check for both the reference side and the 21 79.En_SynDd_RefDd Disabled Disabled Enabled - synchronization side (valid only if - the setting [79.Opt_RSYN_ValidMode] = Setting) Enabling/disabling live check for synchronization 22 79.En_SynLv_RefDd Disabled Disabled Enabled - side and dead check for reference side (valid only - if the [79.Opt_RSYN_ValidMode] setting = Setting) Enabling/disabling dead check for 23 79.En_SynDd_RefLv synchronization side and live check Disabled Disabled Enabled - - for reference side (valid only if the setting [79.Opt_RSYN_ValidMode] = Setting) Enabling/disabling AR without any 24 79.En_NoChk Disabled Enabled Enabled - check (valid only if the setting - [79.Opt_RSYN_ValidMode] = Setting) 9.2.22 Fault Location Settings ⚫ Access path: MainMenu Settings Protection Settings FL Settings Table 9.2-22 Settings of fault location No. Settings Range Default value Unit Step 1 X1L 0~600 10 Ω 0.001 2 R1L 0~600 1 Ω 0.001 3 X0L 0~600 20 Ω 0.001 4 R0L 0~600 3 Ω 0.001 PCS-9613S Differential Relay 9 Remark Positive-sequence reactance of the whole line (secondary value) Positive-sequence resistance of the whole line (secondary value) Zero-sequence reactance of the whole line (secondary value) Zero-sequence resistance of the whole line (secondary value) 9-83 Date: 2020-09-02 9 Settings No. 5 Settings LineLength Range 0~6000 Default value 100 Unit Step km 0.01 Remark Total length of the whole line 9.3 Measurement and Control Settings In this section, the "XXXX" stands for bay indication. By default, it could be BayMMXU, BusMMXU, etc. and it is configurable through the configuration tool PCS-Studio. 9.3.1 Function Settings ⚫ Access path: Main Menu Settings Meas Control Settings Function Settings No. Setting Default 1 Opt_CT_Measmt Ia-Ib-Ic 2 ZeroDrift_U 0.20 3 ZeroDrift_I 0.20 Range Step Unit - - 0.00~1.00 0.01 % 0.00~1.00 0.01 % Ia-Ib-Ic or Ia-Ic Remark Source selection of current measurement Threshold to limit the zero-drift influence of voltage, current or power due to temperature or other environmental factors. A measured value less than this setting will be regarded as a zero 4 ZeroDrift_PQ 0.50 0.00~1.00 0.01 % drift and ignored. Threshold to limit the zero-drift influence of corresponding current due to temperature or 5 Neu.ZeroDrift_I 0.20 0.00~1.00 0.01 % other environmental factors. A measured value less than this setting will be regarded as a zero drift and ignored. Threshold to limit the zero-drift influence of corresponding voltage due to temperature or 9 6 Syn.ZeroDrift_U 0.20 0.00~1.00 0.01 % other environmental factors. A measured value less than this setting will be regarded as a zero drift and ignored. 9.3.2 Synchronism Check Settings ⚫ Access path: Main Menu Settings Meas Control Settings Syn Settings No. 1 Setting 25.Opt_ValidMode Default Setting Range Setting or Config Step Unit - - Description Selection of decision PCS-9613S Differential Relay 9-84 Date: 2020-09-02 9 Settings No. Setting Default Range Step Unit Description mode for synchronism check Setting: the mode depends on the setting values of [25.En_SynChk] and [25.En_DdChk]; Config: the mode depends on the input values of "in_syn_chk" and "in_vol_chk" terminals. Logic setting synchro-check 2 25.En_SynChk Enabled Disabled or Enabled - - only if the for (valid setting [25.Opt_ValidMode] = Setting) Logic setting for dead charge check (valid 3 25.En_DdChk Enabled Disabled or Enabled - - only if the setting [25.Opt_ValidMode] = Setting) Percentage threshold 4 25.U_UV 80.00 0~100 0.01 % of under voltage for CB closing blocking Percentage threshold 5 25.U_OV 170.00 100~170 0.01 % of over voltage for CB closing blocking Percentage threshold 6 25.f_UF 45.000 45~65 0.001 Hz of under frequency for CB closing blocking Percentage threshold 7 25.f_OF 65.000 45~65 0.001 Hz of over frequency for CB closing blocking 8 25.Opt_U_SynChk Ua Ua, Ub, Uc, Uab, Ubc, Uca - - Selection of voltage for synchronism check Threshold of voltage 9 25.U_Diff_Set 10.00 0~100 0.01 V difference for synchronism check 10 25.En_f_Diff_Chk Enabled Disabled or Enabled PCS-9613S Differential Relay - - Logic setting frequency for difference 9-85 Date: 2020-09-02 9 9 Settings No. Setting Default Range Step Unit Description check 11 25.f_Diff_Set 0.50 0~2 0.01 Hz Threshold of frequency difference for synchronism check Logic 12 25.En_df/dt_Chk Enabled Disabled or Enabled - - setting frequency for variation difference check Threshold 13 25.df/dt_Set 1.00 0~2 0.01 Hz/s of frequency variation for synchronism check. Threshold of phase 14 25.phi_Diff_Set 15.00 0~180 0.01 ° difference for synchronism check Compensation angle 15 25.phi_Comp 0.00 0~360 0.01 ° of phase difference for synchronism check SynDdRefDd SynLvRefDd SynDdRefLv 16 25.Opt_Mode_DdChk AnySideDd RefDd - - Selection of dead charge check mode SynDd SynLvRefDd/SynDdRefLv AnySideDd 17 25.U_DdChk 17.32 0~100 0.01 V 18 25.U_LvChk 34.64 0~100 0.01 V 19 25.t_Reset 5 0~60 1 s Threshold for voltage dead check Threshold for voltage live check Threshold of duration for synchro-check Circuit breaker closing time. It is the time 9 20 25.t_Close_CB 20 0~2000 1 ms from receiving closing command pulse till the CB is completely closed. 9.3.3 Double Point Status Settings ⚫ Access path: Main Menu Settings Meas Control Settings DPS Settings No. 1 Setting CB.DPS.t_DPU Default 500 Range 0~60000 Step Unit 1 ms Description Delay Pick Up (DPU) time, i.e. debounce time, for DPS of the circuit breaker PCS-9613S Differential Relay 9-86 Date: 2020-09-02 9 Settings 2 CB.DPS.En_Alm Disabled 3 CB.DPS.t_Alm 500 4 DS01.DPS.t_DPU 500 5 DS01.DPS.En_Alm Disabled 6 DS01.DPS.t_Alm 500 7 DS02.DPS.t_DPU 500 8 DS02.DPS.En_Alm Disabled 9 DS02.DPS.t_Alm 500 10 DS03.DPS.t_DPU 500 11 DS03.DPS.En_Alm Disabled 12 DS03.DPS.t_Alm 500 13 DS04.DPS.t_DPU 500 14 DS04.DPS.En_Alm Disabled 15 DS04.DPS.t_Alm 500 16 DS05.DPS.t_DPU 500 17 DS05.DPS.En_Alm Disabled 18 DS05.DPS.t_Alm 500 19 DS06.DPS.t_DPU 500 20 DS06.DPS.En_Alm Disabled 21 DS06.DPS.t_Alm 500 22 DS07.DPS.t_DPU 500 23 DS07.DPS.En_Alm Disabled Disabled or - - 0~60000 1 ms 0~60000 1 ms - - 0~60000 1 ms 0~60000 1 ms - - 0~60000 1 ms 0~60000 1 ms - - 0~60000 1 ms 0~60000 1 ms - - 0~60000 1 ms 0~60000 1 ms - - 1 ms Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled 0~60000 0~60000 1 ms - - 0~60000 1 ms 0~60000 1 ms - - Disabled or Enabled Disabled Enabled or PCS-9613S Differential Relay Logic setting for DPS alarm of the circuit breaker Operation time delay of DPS alarm of the circuit breaker Delay Pick Up (DPU) time, i.e. debounce time, for DPS of disconnector switch 01 Logic setting for DPS alarm of disconnector switch 01 Operation time delay of DPS alarm of disconnector switch 01 Delay Pick Up (DPU) time, i.e. debounce time, for DPS of disconnector switch 02 Logic setting for DPS alarm of disconnector switch 02 Operation time delay of DPS alarm of disconnector switch 02 Delay Pick Up (DPU) time, i.e. debounce time, for DPS of disconnector switch 03 Logic setting for DPS alarm of disconnector switch 03 Operation time delay of DPS alarm of disconnector switch 03 Delay Pick Up (DPU) time, i.e. debounce time, for DPS of disconnector switch 04 Logic setting for DPS alarm of disconnector switch 04 Operation time delay of DPS alarm of disconnector switch 04 Delay Pick Up (DPU) time, i.e. debounce time, for DPS of disconnector switch 05 Logic setting for DPS alarm of disconnector switch 05 Operation time delay of DPS alarm of 9 disconnector switch 05 Delay Pick Up (DPU) time, i.e. debounce time, for DPS of disconnector switch 06 Logic setting for DPS alarm of disconnector switch 06 Operation time delay of DPS alarm of disconnector switch 06 Delay Pick Up (DPU) time, i.e. debounce time, for DPS of disconnector switch 07 Logic setting for DPS alarm of disconnector switch 07 9-87 Date: 2020-09-02 9 Settings 24 DS07.DPS.t_Alm 500 0~60000 1 ms 25 DS08.DPS.t_DPU 500 0~60000 1 ms 26 DS08.DPS.En_Alm Disabled - - 27 DS08.DPS.t_Alm 500 0~60000 1 ms 28 DS09.DPS.t_DPU 500 0~60000 1 ms 29 DS09.DPS.En_Alm Disabled - - 30 DS09.DPS.t_Alm 500 1 ms Disabled or Enabled Disabled or Enabled 0~60000 Operation time delay of DPS alarm of disconnector switch 07 Delay Pick Up (DPU) time, i.e. debounce time, for DPS of disconnector switch 08 Logic setting for DPS alarm of disconnector switch 08 Operation time delay of DPS alarm of disconnector switch 08 Delay Pick Up (DPU) time, i.e. debounce time, for DPS of disconnector switch 09 Logic setting for DPS alarm of disconnector switch 09 Operation time delay of DPS alarm of disconnector switch 09 9.3.4 Control Settings ⚫ Access path: Main Menu Settings Meas Control Settings Control Settings No. 9 Setting Default Range Step Unit 1 CB.t_PW_Opn 500 0~60000 1 ms 2 CB.t_PW_Cls 500 0~60000 1 ms 3 DS01.t_PW_Opn 500 0~60000 1 ms 4 DS01.t_PW_Cls 500 0~60000 1 ms 5 DS02.t_PW_Opn 500 0~60000 1 ms 6 DS02.t_PW_Cls 500 0~60000 1 ms 7 DS03.t_PW_Opn 500 0~60000 1 ms 8 DS03.t_PW_Cls 500 0~60000 1 ms 9 DS04.t_PW_Opn 500 0~60000 1 ms 10 DS04.t_PW_Cls 500 0~60000 1 ms 11 DS05.t_PW_Opn 500 0~60000 1 ms 12 DS05.t_PW_Cls 500 0~60000 1 ms Description Pulse Width (PW), i.e. holding time, for opening output of the circuit breaker Pulse Width (PW), i.e. holding time, for closing output of the circuit breaker Pulse Width (PW), i.e. holding time, for direct opening output of disconnector switch 01 Pulse Width (PW), i.e. holding time, for direct closing output of disconnector switch 01 Pulse Width (PW), i.e. holding time, for direct opening output of disconnector switch 02 Pulse Width (PW), i.e. holding time, for direct closing output of disconnector switch 02 Pulse Width (PW), i.e. holding time, for direct opening output of disconnector switch 03 Pulse Width (PW), i.e. holding time, for direct closing output of disconnector switch 03 Pulse Width (PW), i.e. holding time, for direct opening output of disconnector switch 04 Pulse Width (PW), i.e. holding time, for direct closing output of disconnector switch 04 Pulse Width (PW), i.e. holding time, for direct opening output of disconnector switch 05 Pulse Width (PW), i.e. holding time, for direct PCS-9613S Differential Relay 9-88 Date: 2020-09-02 9 Settings No. Setting Default Range Step Unit Description closing output of disconnector switch 05 13 DS06.t_PW_Opn 500 0~60000 1 ms 14 DS06.t_PW_Cls 500 0~60000 1 ms 15 DS07.t_PW_Opn 500 0~60000 1 ms 16 DS07.t_PW_Cls 500 0~60000 1 ms 17 DS08.t_PW_Opn 500 0~60000 1 ms 18 DS08.t_PW_Cls 500 0~60000 1 ms 19 DS09.t_PW_Opn 500 0~60000 1 ms 20 DS09.t_PW_Cls 500 0~60000 1 ms Pulse Width (PW), i.e. holding time, for direct opening output of disconnector switch 06 Pulse Width (PW), i.e. holding time, for direct closing output of disconnector switch 06 Pulse Width (PW), i.e. holding time, for direct opening output of disconnector switch 07 Pulse Width (PW), i.e. holding time, for direct closing output of disconnector switch 07 Pulse Width (PW), i.e. holding time, for direct opening output of disconnector switch 08 Pulse Width (PW), i.e. holding time, for direct closing output of disconnector switch 08 Pulse Width (PW), i.e. holding time, for direct opening output of disconnector switch 09 Pulse Width (PW), i.e. holding time, for direct closing output of disconnector switch 09 9.3.5 Interlocking Logic Settings ⚫ Access path: Main Menu Settings Meas Control Settings Interlock Settings No. Setting Default 1 CB.En_CILO_Opn Disabled 2 CB.En_CILO_Cls Disabled 3 4 5 6 7 DS01.En_CILO_Opn DS01.En_CILO_Cls DS02.En_CILO_Opn DS02.En_CILO_Cls DS03.En_CILO_Opn Disabled Disabled Disabled Disabled Disabled Range Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Step Unit - - - - Description Logic setting for interlocking logic control of opening output of the circuit breaker. Logic setting for interlocking logic control of closing output of the circuit breaker. Logic setting for interlocking logic control - - of direct opening output of disconnector switch 01. Logic setting for interlocking logic control - - of direct closing output of disconnector 9 switch 01. Logic setting for interlocking logic control - - of direct opening output of disconnector switch 02. Logic setting for interlocking logic control - - of direct closing output of disconnector switch 02. Logic setting for interlocking logic control - PCS-9613S Differential Relay - of direct opening output of disconnector switch 03. 9-89 Date: 2020-09-02 9 Settings No. 8 9 10 11 12 13 14 15 16 17 18 Setting DS03.En_CILO_Cls DS04.En_CILO_Opn DS04.En_CILO_Cls DS05.En_CILO_Opn DS05.En_CILO_Cls DS06.En_CILO_Opn DS06.En_CILO_Cls DS07.En_CILO_Opn DS07.En_CILO_Cls DS08.En_CILO_Opn DS08.En_CILO_Cls Default Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled Disabled 9 19 20 DS09.En_CILO_Opn DS09.En_CILO_Cls Disabled Disabled Range Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Disabled or Enabled Step Unit Description Logic setting for interlocking logic control - - of direct closing output of disconnector switch 03. Logic setting for interlocking logic control - - of direct opening output of disconnector switch 04. Logic setting for interlocking logic control - - of direct closing output of disconnector switch 04. Logic setting for interlocking logic control - - of direct opening output of disconnector switch 05. Logic setting for interlocking logic control - - of direct closing output of disconnector switch 05. Logic setting for interlocking logic control - - of direct opening output of disconnector switch 06. Logic setting for interlocking logic control - - of direct closing output of disconnector switch 06. Logic setting for interlocking logic control - - of direct opening output of disconnector switch 07. Logic setting for interlocking logic control - - of direct closing output of disconnector switch 07. Logic setting for interlocking logic control - - of direct opening output of disconnector switch 08. Logic setting for interlocking logic control - - of direct closing output of disconnector switch 08. Logic setting for interlocking logic control - - of direct opening output of disconnector switch 09. Logic setting for interlocking logic control - - of direct closing output of disconnector switch 09. PCS-9613S Differential Relay 9-90 Date: 2020-09-02 9 Settings 9.4 Logic Links Logic link is a special logic setting which can be configured through local HMI or remote PC. These logic links provide a convenient way for the operator to put the function in service or out of service remotely away from an unattended substation. 9.4.1 Function Links ⚫ Access path: Main Menu Settings Logic Links Function Links Table 9.4-1 Function links No. Settings 1 Link_01 2 Link_02 3 Link_03 4 Link_04 5 Link_05 6 Link_06 7 Link_07 8 Link_08 Range Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Default Remark value Enabled Function link setting 01 Enabled Function link setting 02 Enabled Function link setting 03 Enabled Function link setting 04 Enabled Function link setting 05 Enabled Function link setting 06 Enabled Function link setting 07 Enabled Function link setting 08 9 9.4.2 GOOSE Receiving Links ⚫ Access path: MainMenu Settings Logic Links GOOSE Recv Links Table 9.4-2 GOOSE receiving links No. 1 Settings Range @Bx.Name_00_GCommLink.G Disabled Link_Recv Enabled Default Remark value Enabled GOOSE receiving link 00 is enabled or disabled PCS-9613S Differential Relay 9-91 Date: 2020-09-02 9 Settings No. 2 3 Settings …… Range Disabled Enabled @Bx.Name_63_GCommLink.G Disabled Link_Recv Enabled Default Remark value Enabled …… Enabled GOOSE receiving link 63 is enabled or disabled Enabling/disabling the allowance for the acceptance of GOOSE messages 4 GLink_RecvSim Disabled Enabled Disabled Disabled: not receiving the GOOSE message (simulation=1) Enabled: receiving the GOOSE message (simulation=1) @Bx.Name_00_GCommLink is the set value of the label setting of [Bx.Name_00_GCommLink], @Bx.Name_63_GCommLink is the set value of the label setting of [Bx.Name_63_GCommLink]. 9 PCS-9613S Differential Relay 9-92 Date: 2020-09-02 Appendix A Glossary Appendix A Glossary The abbreviations adopted in this manual are listed as below. A BOM Binary Output Module "a" Contact is breaker auxiliary contact (ANSI Standard Device Number 52A) that closes when the breaker is closed and opens when the breaker is open. C AC Alternating current CB Circuit breaker A/D converter Analog-to-digital converter CID Configured IED Description AI Analog input COMTRADE Standard Common Format for Transient Data Exchange format for Disturbance recorder according to IEEE/ANSI C37.111, 1999 / IEC 60255-24 ANSI American National Standards Institute AR Autoreclosing C37.94 IEEE/ANSI protocol used sending binary signals between IEDs ASDU Application Service Data Unit – An ASDU can consist of one or more identical information objects. A sequence of the same information elements, for example measured values, is identified by the address of the information object. The address of the information object defines the associated address of the first information element of the sequence. A consecutive number identifies the subsequent information elements. The number builds on this address in integral increments (+1). CPU Central Processing Unit B DLLB Dead Line Live Bus "b" Contact is breaker auxiliary contact (ANSI Standard Device Number 52B) that closes when the breaker is open and opens when the breaker is closed. BFP Breaker failure protection BI Binary Input BO Binary Output BIM Binary Input Module when CRC Cyclic Redundancy Check CT Current Transformer CTS Current Circuit Supervision D DBDL Dead Bus Dead Line DBLL Dead Bus Live Line DC Direct Current DNP Distributed Network Protocol as per IEEE Std 1815-2012 DPFC Deviation of Power Frequency Component–In case of a fault occurred in the power system, the fault component could be analyzed into three parts: the power frequency components before the fault, the power frequency variables during the fault and the transient variables during the fault. DPFC is the power frequency variable during the fault. PCS-9613S Differential Relay 1 Date: 2020-09-02 A Appendix A Glossary DSP Digital Signal Processor LCD Liquid Crystal Display LED Light-emitting Diode E M EHV Extra High Voltage EMC Electromagnetic Compatibility MCB Miniature Circuit Breaker MMS Manufacturing Message Specification F MOV Metal-oxide Varistor FL Fault Location P FR Fault Recorder PD Pole Discrepancy G PL Programmable Logic G.703 Electrical and functional description for digital lines used by local telephone companies. Can be transported over balanced and unbalance lines PPM Pulse Per Minute PPS Pulse Per Second PRP Parallel Redundancy Protocol GIS Gas-insulated Switchgear GOOSE Generic Object-Oriented Substation Event GPS Global Positioning System R RMS Root Mean Square RSTP Rapid Spanning Tree Protocol H RTD Resistance Temperature Detector RTU Remote Terminal Unit HMI Human-machine Interface HSR High-availability Seamless Redundancy HV High-voltage S SA Substation Automation HVDC High-voltage Direct Current SCADA Supervision, Acquisition I Control And Data SCD Substation Configuration Description ICD IED Capability Description A IEC International Electrotechnical Commission SCL Substation Configuration Description Language IED Intelligent Electronic Device SLD Single-line Diagram IRIG-B InterRange Instrumentation Group Time code format B SIR Source-to-line Impedance Ratio L SNMP Simple Network Management Protocol –An Internet standard protocol and serves for PCS-9613S Differential Relay 2 Date: 2020-09-02 Appendix A Glossary the administration of nodes in an IP network. SNTP Simple Network Time Protocol – A protocol for the synchronization of clocks via the Internet. With SNTP, client computers can synchronize their clocks via the Internet with a time server. SOE Sequence of Events – An ordered, time-stamped log of status changes at binary inputs (also referred to as state inputs). SOE is used to restore or analyze the performance, or an electrical power system itself, over a certain period of time. SOTF Switch-Onto-Fault T TCS Trip Circuit Supervision TCP/IP Transmission Control Protocol over Internet Protocol U UTC Coordinated Universal Time V VT Voltage transformer VTS Voltage Circuit Supervision STP Rapid Spanning Tree Protocol A list of function numbers used to represent electrical protection and control element. The device function numbers used in this manual include the following: 25 Synchronism-check element element 27 Undervoltage element 52 AC circuit breaker 32 Power element 59 Overvoltage element 37 Undercurrent element 67 Directional overcurrent element 46 Phase-balance current element 79 Reclosing element 49 Thermal overload element 81 Frequency element 50 Instantaneous overcurrent element 87 Differential element 51 Definite-time or inverse-time overcurrent These numbers are frequently used within a suffix letter to further designate their application. The suffix letters used in this instruction manual include the following: P Phase element Q Negative-sequence element G Residual/Ground element A PCS-9613S Differential Relay 3 Date: 2020-09-02 Appendix A Glossary A PCS-9613S Differential Relay 2 Date: 2020-09-02