ANSI/ASHRAE Standard 209-2018 Energy Simulation Aided Design for Buildings Except Low-Rise Residential Buildings Approved by ASHRAE on March 30, 2018, and by the American National Standards Institute on April 2, 2018. ASHRAE® Standards are scheduled to be updated on a five-year cycle; the date following the Standard number is the year of ASHRAE approval. The latest edition of an ASHRAE Standard may be purchased on the ASHRAE website (www.ashrae.org) or from ASHRAE Customer Service, 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. E-mail: orders@ashrae.org. Fax: 678-539-2129. Telephone: 404-636-8400 (worldwide) or toll free 1-800-527-4723 (for orders in US and Canada). For reprint permission, go to www.ashrae.org/permissions. © 2018 ASHRAE ISSN 1041-2336 ASHRAE Standard Project Committee 209 Cognizant TC: 4.7, Energy Calculations SPLS Liaison: Julie Ferguso Jason J. Glazer*, Chair Christopher B. Baker* Mangesh S. Basarkar Mahabir S. Bhandari William J. Bishop* John Bixler Yu Chen* Michael M. Collarin Drury B. Crawley* Margaret P. Curtz* Lee DeBaillie Clark R. Denson* Gregory Dobbs* Mathew Edwards Delia Estrada Ross C. Farris* Paul A Fiejdasz* Ellen M. Franconi* Lixing Gu* Jeff S. Haberl Kamel Haddad Daniel A. Katzenberger* Erik P. Kolderup Luka Matutinovic* Dembia Ndiaye* Ronald O. Nelson* Jerry W. Phelan* David Reddy* Andrew Reilman* Marcus B. Sheffer* Kim E. Shinn* Som S. Shrestha* Aaron R. Smith* Seth P. Spangler Liangcai Tan* Scott P. West* Yun K. Yi * Denotes members of voting status when the document was approved for publication ASHRAE STANDARDS COMMITTEE 2017–2018 Steven J. Emmerich, Chair Donald M. Brundage, Vice-Chair Niels Bidstrup Michael D. Corbat Drury B. Crawley Julie M. Ferguson Michael W. Gallagher Walter T. Grondzik Vinod P. Gupta Susanna S. Hanson Roger L. Hedrick Rick M. Heiden Jonathan Humble Srinivas Katipamula Kwang Woo Kim Larry Kouma Arsen K. Melikov R. Lee Millies, Jr. Karl L. Peterman Erick A. Phelps David Robin Peter Simmonds Dennis A. Stanke Wayne H. Stoppelmoor, Jr. Richard T. Swierczyna Jack H. Zarour Lawrence C. Markel, BOD ExO M. Ginger Scoggins, CO Steven C. Ferguson, Senior Manager of Standards SPECIAL NOTE This American National Standard (ANS) is a national voluntary consensus Standard developed under the auspices of ASHRAE. Consensus is defined by the American National Standards Institute (ANSI), of which ASHRAE is a member and which has approved this Standard as an ANS, as “substantial agreement reached by directly and materially affected interest categories. This signifies the concurrence of more than a simple majority, but not necessarily unanimity. Consensus requires that all views and objections be considered, and that an effort be made toward their resolution.” Compliance with this Standard is voluntary until and unless a legal jurisdiction makes compliance mandatory through legislation. ASHRAE obtains consensus through participation of its national and international members, associated societies, and public review. ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The Project Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE members, all must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests on all Project Committees. The Senior Manager of Standards of ASHRAE should be contacted for a. interpretation of the contents of this Standard, b. participation in the next review of the Standard, c. offering constructive criticism for improving the Standard, or d. permission to reprint portions of the Standard. DISCLAIMER ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available information and accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or performance of any products, components, or systems tested, installed, or operated in accordance with ASHRAE’s Standards or Guidelines or that any tests conducted under its Standards or Guidelines will be nonhazardous or free from risk. ASHRAE INDUSTRIAL ADVERTISING POLICY ON STANDARDS ASHRAE Standards and Guidelines are established to assist industry and the public by offering a uniform method of testing for rating purposes, by suggesting safe practices in designing and installing equipment, by providing proper definitions of this equipment, and by providing other information that may serve to guide the industry. The creation of ASHRAE Standards and Guidelines is determined by the need for them, and conformance to them is completely voluntary. In referring to this Standard or Guideline and in marking of equipment and in advertising, no claim shall be made, either stated or implied, that the product has been approved by ASHRAE. CONTENTS ANSI/ASHRAE Standard 209-2018 Energy Simulation Aided Design for Buildings Except Low-Rise Residential Buildings SECTION PAGE Foreword .....................................................................................................................................................................2 1 Purpose.............................................................................................................................................................2 2 Scope ................................................................................................................................................................2 3 Definitions, Abbreviations, and Acronyms.........................................................................................................2 4 Utilization...........................................................................................................................................................4 5 General Requirements ......................................................................................................................................4 6 Design Modeling Cycles....................................................................................................................................7 7 Construction and Operations Modeling.............................................................................................................8 8 Postoccupancy Modeling ..................................................................................................................................9 9 Normative References ....................................................................................................................................10 Informative Appendix A: Climate Information ........................................................................................................11 Informative Appendix B: Benchmark Information ..................................................................................................12 Informative Appendix C: Simple Box Modeling .....................................................................................................13 Informative Appendix D: Owner’s Project Requirements ......................................................................................14 Informative Appendix E: Quality Assurance and Quality Control Checklists.........................................................16 Informative Appendix F: Informative References ..................................................................................................20 NOTE Approved addenda, errata, or interpretations for this standard can be downloaded free of charge from the ASHRAE website at www.ashrae.org/technology. © 2018 ASHRAE 1791 Tullie Circle NE · Atlanta, GA 30329 · www.ashrae.org · All rights reserved. ASHRAE is a registered trademark of the American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ANSI is a registered trademark of the American National Standards Institute. (This foreword is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.) FOREWORD ASHRAE Standard 209 describes a methodology to apply building energy modeling to the design process. The Standard Project Committee recognizes the important role building energy modeling plays in informing the design and operation of low-energy buildings. The standard was created to define reliable and consistent procedures that advance the use of timely energy modeling to quantify the impact of design decisions at the point in time at which they are being made. The committee believes such an approach will improve modeling effectiveness, realize greater savings, and support achieving increasingly aggressive energy savings targets. The standard defines general modeling requirements coupled with eleven modeling cycles, each with specific modeling goals that align with distinct phases of the design, construction, or operation process. Each modeling cycle is an extension of the general modeling requirements, which represents a bestpractices approach for using modeling to inform design. Seven of the modeling cycles coincide with the building design phase, three modeling cycles are applied during building construction, and one occurs postoccupancy. The postoccupancy analysis is included to help both the owner and modeler understand how modeled results compare to actual energy performance to inform operation and assumptions used in future modeling projects. The minimum requirements of the standard can be met by completing a load-reducing modeling cycle early in the design process, as well as one additional design-phase modeling cycle. The full set of modeling cycles were developed to provide holistic modeling guidance and are included for completeness. They can be selectively adopted by organizations that desire a more robust treatment for realizing their specific project objectives. While the standard can be applied with any design process, it is best utilized when included as part of an integrative design process. It is expected the standard will be adopted by organizations that certify high-performance buildings, as well as by utilities and agencies that provide incentives for using modeling to inform design. It can be referenced as part of a project scope of work by building owners and architects seeking an effective, uniform way to use energy modeling to achieve performance objectives. 1. PURPOSE Define minimum requirements for providing energy design assistance using building energy simulation and analysis. during the design process. This standard does not apply to single-family houses, multifamily structures of three stories or fewer above grade, manufactured houses (mobile homes), or modular homes. 3. DEFINITIONS, ABBREVIATIONS, AND ACRONYMS 3.1 General Certain terms, abbreviations, and acronyms are defined in this section for the purposes of this standard. These definitions are applicable to all sections of this standard. 3.2 Definitions actual meteorological year (AMY): a data set comprising one year of historical, hourly measured or derived weather observations for a specific location. authority having jurisdiction (AHJ): the agency or agent responsible for enforcing this standard. balance-point temperature: the outdoor temperature at which a building’s heat loss to the environment is equal to internal heat gains from people, lights, and equipment. baseline: the building design or level of energy performance used as the basis of comparison against other project alternatives, usually based on a hypothetical design defined by building standards or based on the currently proposed building design at the time of modeling cycle analysis. building energy simulation: building energy estimation using a computer simulation program. building performance rating system: a program to assess energy and/or environmental performance of a building design. (Informative Note: e.g., the Leadership in Energy and Environmental Design [LEED] program developed by the U.S. Green Building Council and the Green Globes program developed by the Green Building Initiative.) change order: a request to modify the original scope of work after construction has begun. The need for a change order can include product substitutions, design changes, and differing site conditions. A request for a change order may be originated by the owner, a member of the design team, the contractor, or a subcontractor and typically is initiated using either a change order proposal request, a change order proposal, or a change directive. If approved, change orders permanently modify the scope of work and contract. charrette: a meeting of project stakeholders to discuss design goals and design strategies. comparative analysis: a modeling exercise comparing the performance of two or more design alternatives in which the important result is the relative performance of alternatives. compliance analysis: a modeling exercise to demonstrate design compliance with energy standards or other program requirements. 2. SCOPE construction document phase: the final portion of the design process in which detailed plans and specifications are completed. This standard applies to new buildings or major renovations of, or additions to, existing buildings using energy simulation design constraint: a condition that must be satisfied as a part of an optimization process in order for a design to be feasible. 2 ANSI/ASHRAE Standard 209-2018 design variable: a building parameter or specification that is controllable from the point of view of the designer. energy design assistance: the process of using energy modeling to provide information to the owner and building design team regarding the energy performance of project alternatives with the intent to achieve an energy efficient design. energy efficiency measure (EEM): an action taken in the operation of, or a change to, equipment in a building that reduces the energy use of the building while maintaining or enhancing the building’s safety, comfort, and functionality. energy end use: a component of building energy consumption due to a specific application, including but not limited to lights, internal equipment loads, service water heating equipment, space heating equipment, space cooling and heat rejection equipment, fans, and other HVAC system equipment (such as pumps). energy model: a computer representation that provides information on the systems (e.g., HVAC, lighting, occupancy, plug loads, building envelope) that affect energy consumption in a building. The representation of the building serves, along with weather data, as the input data for a computer simulation program. When run, the program will simulate the energy use and demand in the described building for a time interval. Depending on the kind of program and how it is set up to run, various kinds of output may be produced. local weather station: the weather station geographically closest to the building site or having similar climate characteristics as the building site. modeling cycle: an energy modeling activity with a specific purpose, applicability, and analysis approach. optimization: an energy modeling aided process in which one or more design variables are selected and analyzed through a given test range or set of design constraints in order to maximize or minimize an optimization objective relating to one or more of the project performance goals. optimization objective: a numerical value that is to be maximized or minimized as a part of an optimization process. owner’s project requirements (OPR): a written document that details the requirements of a project and the expectations for how it will be designed, constructed, and operated. This includes project goals, measurable performance criteria, cost considerations, benchmarks, success criteria, and supporting information. (Informative Note: The terms project intent or design intent are used interchangeably with OPR by some owners. See Informative Appendix D.) process energy: energy consumed in support of a manufacturing, industrial, or commercial process other than conditioning spaces and maintaining comfort and amenities for the occupants of a building. energy modeler: an individual with primary responsibility for performance of the activities defined in this standard. process load: the load on a building resulting from the consumption or release of process energy. energy modeling: the process of developing an energy model and running a building energy simulation. project alternative: an energy efficiency measure, proposed value engineering measure, change order proposal, or other change to the building design or operation that impacts building energy performance and is being considered for evaluation. energy source: electricity, natural gas, fuel oil, propane, purchased heating, purchased cooling, and other building energy utility inputs. green building concepts: measures that minimize the impact of buildings on the natural environment or that improve the indoor environment for occupants. gross floor area: the sum of the floor areas of all the spaces within the building with no deductions for floor penetrations other than atria. Gross floor area is measured from the exterior faces of exterior walls or from the centerline of walls separating buildings, but it excludes covered walkways, open roofed-over areas, porches and similar spaces, pipe trenches, exterior terraces or steps, roof overhangs, parking garages, surface parking, and similar features. schematic design: the early design phase in which fundamental elements of design, such as building form and HVAC system type, are typically determined. simple box model: a simplified building representation used during the early design stage. (Informative Note: See Informative Appendix C for additional information.) simulation program: a computer program that is capable of simulating the energy performance of building systems. site energy: energy consumed by the building as measured by the local utility and/or nonutility meters. HVAC system: the equipment, distribution systems, and terminals that provide, either collectively or individually, the processes of heating, ventilating, or air conditioning to a building or portion of a building. value engineering (VE): a process through which one or more project alternatives are identified that affect the cost and/or function of a building, system, or component. The typical goal is to maximize value by providing the necessary function at minimum cost. Also known as value management, value methodology, or value analysis. insolation: incident or incoming solar radiation to a specific location. whole-building simulation software: see simulation program. life-cycle cost analysis (LCCA): an economic method for evaluating a project or project alternatives in which the net present value of costs arising from owning, operating, maintaining, and ultimately disposing of a project are computed for each alternative and then compared over a designated study period. 3.3 Abbreviations and Acronyms ANSI/ASHRAE Standard 209-2018 AFUE annual fuel utilization efficiency AHJ authority having jurisdiction AMY actual meteorological year BEMP building energy modeling professional 3 BESA building energy simulation analyst VLT visible light transmittance bhp brake horsepower W watt Btu British thermal unit W/ft² watt per square foot Btu/h British thermal unit per hour C Celsius CDD cooling degree days cfm cubic feet per minute CHW chilled water CO change orders COP coefficient of performance CVRMSE coefficient of variation of the root-mean-square error ECI Energy Cost Index EEM energy efficiency measure EER energy efficiency ratio EF energy factor EUI energy use intensity F Fahrenheit ft foot gpm gallons per minute gpf gallons per flush h hour HDD heating degree days hp horsepower HSPF heating seasonal performance factor HVAC heating, ventilating, and air conditioning IEER integrated energy efficiency ratio I-P inch-pound IPLV integrated part-load value IMT inverse modeling toolkit in. inch LCCA life-cycle cost analysis LPD lighting power density NMBE normalized mean bias error LSG light to solar gain OPR owner’s project requirements QA quality assurance QC quality control SEER seasonal energy efficiency ratio SHGC solar heat gain coefficient SWH service water heating 5. GENERAL REQUIREMENTS TMY typical meteorological year UA overall heat transfer coefficient × area VE value engineering 5.1 Simulation Software Requirements. Whole-building simulation software used to comply with the standard shall meet the minimum requirements of ASHRAE/IES Standard 90.1 1, Section G2.2. 4 4. UTILIZATION 4.1 Timing of Work. The energy modeler shall perform energy modeling at each phase of the planning, design, and construction or operation of the building as specified in the owner’s project requirements (OPR) or in the owner/energy modeler agreement and using information obtained from relevant project stakeholders, which may include the owner, design team, constructors, and operators. The modeler shall provide the results of the required simulations with opinions and recommendations, as required and appropriate for the modeling cycle being evaluated, in order to inform decision making by stakeholders. 4.2 Compliance 4.2.1 The building design process shall meet the requirements of a. Section 5, b. Section 6.3, “Modeling Cycle #3—Load Reduction Modeling,” and c. at least one of the following sections: 1. Section 6.1, “Modeling Cycle #1—Simple Box Modeling” 2. Section 6.2, “Modeling Cycle #2—Conceptual Design Modeling” 3. Section 6.4, “Modeling Cycle #4—HVAC System Selection Modeling” 4. Section 6.5, “Modeling Cycle #5—Design Refinement” 5. Section 6.6, “Modeling Cycle #6—Design Integration and Optimization” 6. Section 6.7, “Modeling Cycle #7—Energy Simulation Aided Value Engineering” 4.2.2 The adopting authority shall have the option of requiring additional levels of compliance: a. Additional modeling cycles. b. As-designed compliance. Meet the requirements listed in Section 4.2.1 and, additionally, the requirements in Section 7.1, “Modeling Cycle #8—As-Designed Energy Performance.” c. As-built compliance. Meet the requirements listed in Section 4.2.1 and, additionally, the requirements in Section 7.3, “Modeling Cycle #10—As-Built Energy Performance.” d. As-operated compliance. Meet the requirements listed in Section 4.2.1 and, additionally, the requirements in Section 8.1, “Modeling Cycle #11—Postoccupancy Energy Performance Comparison.” ANSI/ASHRAE Standard 209-2018 5.2 Modeler Credentials. The energy modeler or the individual supervising the work of the energy modeler shall be a. a certified Building Energy Modeling Professional (BEMP), or b. a certified Building Energy Simulation Analyst (BESA) who also fulfills the BEMP eligibility requirements, or c. an equivalent individual meeting qualifications established by the authority having jurisdiction (AHJ). Informative Note: ASHRAE and AEE are two organizations that can certify a modeler for BEMP or BESA, respectively. 5.3 Climate and Site Analysis 5.3.1 Prior to Modeling Cycle #2, if Modeling Cycle #2 is used for compliance, or prior to Modeling Cycle #3, review local climate information. Record the minimum following information for the project site: a. Dry-bulb temperatures (monthly minimum, maximum, and mean) b. Relative humidity or wet-bulb temperature (monthly minimum, maximum, and mean) c. Wind speed and direction (monthly average and maximum) d. Insolation (average daily per month) e. Cloud cover (monthly minimum, maximum, and mean) f. Ground temperature (monthly average) g. Precipitation (monthly total) h. Heating and cooling degree days, including base temperature for each (monthly total) Informative Note: See informative Appendix A for resources on climate information. 5.3.2 Assess site characteristics to determine their impact on building energy performance. 5.3.3 In collaboration with relevant project stakeholders, document a list of building design strategies that are adapted to the local climate and site conditions. 5.4 Benchmarking. Determine the energy use of buildings with the same principal building activities in the same climate and determine their energy costs using applicable local utility rates. These data shall be used in the energy charrette described in Section 5.5 to inform the development of the project energy goals. Informative Note: See Informative Appendix B for additional information on benchmarking. 5.5 Energy Charrette 5.5.1 Prior to Modeling Cycle #2, if Modeling Cycle #2 is used for compliance, or prior to Modeling Cycle #3, the project team shall conduct at least one charrette. 5.5.2 The representatives that participate in the charrette shall, at a minimum, include the following: a. Owner or owner representatives b. Architect c. Engineer ANSI/ASHRAE Standard 209-2018 d. Building performance rating system consultant (if applicable) e. Energy modeler or the individual supervising the work of the energy modeler f. Other design team members required to reconcile technical requirements g. Contractor (if applicable) 5.5.3 Determine and document the purposes for including energy modeling in the proposed project. Energy modeling purposes to be discussed shall include both comparative analysis and compliance analysis. 5.5.4 Define the baseline or baselines to be used for comparative analysis. 5.5.5 Establish project performance metrics to be used as the basis for the energy goals. 5.5.6 Use benchmarking data generated in Section 5.4 to inform the discussion and determination of the energy performance goals. The resulting energy performance goals shall be incorporated into the draft owner’s project requirements (OPR) detailed in Section 5.6. 5.5.7 Discuss and determine the method for evaluating the potential energy efficiency measures (EEMs) for the project. 5.5.8 Generate a list of potential EEMs. 5.5.9 The energy modeler shall present the results of any previously performed modeling analysis deemed relevant to design decisions associated with the project. 5.5.10 Establish financial criteria for financial analysis and decision making. 5.5.11 Establish a project schedule for follow-up tasks related to items discussed during the charrette. 5.5.12 Establish the process, documentation, and review team for complying with Section 5.7.4 for each modeling cycle. 5.5.13 Create a written record of items discussed during the charrette. 5.6 Energy Performance Goals in OPR 5.6.1 Prior to Modeling Cycle #2, if Modeling Cycle #2 is used for compliance, or prior to Modeling Cycle #3, the owner, the energy modeler, and other building team members shall develop and document the energy performance goals in the OPR. 5.6.2 Document building performance rating systems that apply to this project. 5.6.3 Document the financial criteria for decision making and life-cycle cost analysis (LCCA). 5.6.4 Document the overall project energy performance goal. 5.6.5 Document the performance goals for the individual building systems and assemblies in the following subsections, with the intent that these goals be tracked throughout the design process. Informative Note: See Informative Appendix D. The OPR shall address the building systems for achieving the energy performance goal. 5 5.6.5.1 Building envelope, including roofs, walls, floors, doors, fenestration, and infiltration rate. 5.6.5.2 HVAC systems, ventilation, and control strategies. 5.6.5.3 Lighting systems and daylighting systems. 5.6.5.4 Service hot-water systems and flow rate restrictors to hot-water fixtures, fittings, and appliances. 5.6.5.5 Equipment related to plug and process energy use. 5.6.5.6 Specific owner and occupant requirements related to energy performance. 5.6.5.7 Green building concepts (optional). 5.6.6 Energy performance goals in the OPR shall be updated as required throughout the design process. 5.7 General Modeling Cycle Requirements. This section lists requirements that are common to all of the modeling cycles included within the standard. Cycle-specific requirements are included in their respective sections. 5.7.1 Energy Baselines and Goals. Prior to engaging a specific modeling cycle, review and update the following project-level items: a. The baseline or baselines used for comparison during energy analysis b. The energy performance goals as reported in Section 5.6.4 5.7.2 Input Data 5.7.2.1 Prior to each modeling cycle, the project team shall discuss the purpose, input data, and analysis methodology for each modeling cycle. 5.7.2.2 The input data necessary to perform the analysis, in conjunction with the purpose and goals of each modeling cycle, shall be gathered by the energy modeler and jointly supplied by the project team. 5.7.2.3 Where project-specific modeling inputs are provided, they shall be used in place of assumptions or simulation program default inputs. 5.7.2.4 Input data shall be subject to quality assurance review as described in Section 5.7.4.2. 5.7.2.5 When a modeling cycle requires the comparison of project alternatives, the project team shall identify the first-cost implications of each alternative. This shall include calculation of the incremental costs of individual strategies or bundles of strategies relative to a baseline cost. Include added construction costs as well as reductions in construction costs due to the downsizing or elimination of building systems, such as in the case of alternatives that reduce heating or cooling loads. Exception to 5.7.2.5: Quantification of first-cost impacts are not required for Modeling Cycles #1 and #2, and only a qualification of first costs is required for these modeling cycles. 5.7.3 Reporting. At a minimum, provide the following information, and explicitly display all units of measure. 5.7.3.1 Narrative. For each modeling cycle, provide a written narrative of the following items: a. A comparison of the modeling results to the energy performance goal 6 b. A discussion of the impact to the building peak heating and cooling loads c. A financial analysis of the overall costs and savings d. Discussion of areas of uncertainty in the analysis e. Recommendations for building design strategies and acceptance, rejection, or modification of alternatives that were analyzed f. Recommendations for additional analysis 5.7.3.2 Input Data Reporting. For each modeling cycle, provide the following information: a. Project title b. Project location and weather station name and type c. A narrative description of the building, including use type, occupancy, gross floor area, conditioned floor area, number of stories, occupancy pattern or patterns, internal loads, and schedules d. Simulation program and version e. A narrative description of the energy model baseline, including discussion of why the selected baseline is appropriate for the current analysis f. Utility rates g. A narrative description of any on-site energy generation h. For each project alternative, provide a narrative description of the alternative, including analysis methodology utilized, relevant baseline, and proposed parameters and values i. A summary table of the major energy modeling inputs 5.7.3.3 Output Data Reporting. For the baseline, and for each project alternative, report the following annual results: a. b. c. d. e. f. g. h. i. j. k. l. Total site energy consumption Total site energy consumption per unit gross floor area Site energy consumption by energy end use Total energy cost Consumption by energy source Cost by energy source Peak cooling demand and time of occurrence (date, day of week, day type, hour) Peak heating demand and time of occurrence (date, day of week, day type, hour) Calendar month peak electric demand and time of occurrence (date, day of week, day type, hour) Calendar month peak energy consumption by energy source Unmet heating and cooling load hours Construction cost as determined per Section 5.7.2.5 5.7.4 Quality Assurance. Each Section 6 and 7 modeling cycle shall have two reviews: an input review and an output review. When Modeling Cycle #11 is performed, it shall have an output review. 5.7.4.1 Quality Assurance Review Team. The review team shall include the following, at a minimum: a. Energy modeler b. Owner (or owner representative) c. Architect ANSI/ASHRAE Standard 209-2018 d. Mechanical designer e. Electrical or lighting designer f. Facility operator (for Modeling Cycle #11 reviews) 5.7.4.2 Modeling Cycle Input Reviews. The review team shall review the input data as listed in Section 5.7.3.2 and complete the quality assurance process and review documentation established in Section 5.5.12. The review team shall approve model inputs or suggest changes to model inputs. 5.7.4.3 Modeling Cycle Output Reviews. The review team shall a. b. c. d. review documentation for Sections 5.7.3; compare results to benchmark established in Section 5.4; compare results to energy performance goals in Section 5.6; evaluate results, including energy end uses, relative to inputs; and e. complete quality assurance process and review documentation established in Section 5.5.12. 5.7.5 Modeler Quality Control. The energy modeler shall follow a quality control process related to the energy model. At a minimum, this process shall include quality control procedures provided by the energy modeling software developer, or a generic quality control checklist. Informative Note: See Informative Appendix E for an example quality control checklist. 6. DESIGN MODELING CYCLES 6.1 Modeling Cycle # 1—Simple Box Modeling 6.1.1 Purpose. Identify the distribution of energy by end use. Evaluate energy end uses and demand characteristics that affect building conceptual design. 6.1.2 Applicability. This modeling cycle applies before the building’s geometry and site orientation have been set in the design process. This must be completed before or during the energy charrette described in Section 5.5. 6.1.3 Analysis. Create energy models to calculate annual building energy by end use and peak heating and cooling loads with identical HVAC systems. Perform a sensitivity analysis by varying the following building characteristics: a. Building geometry b. Window-to-wall ratio, by orientation, and shading options (if applicable) c. Orientation d. Thermal performance of the envelope and structure Informative Note: See Informative Appendix C for guidance. 6.2 Modeling Cycle #2—Conceptual Design Modeling 6.2.1 Purpose. Evaluate energy improvements that are tied to the form and architecture of the building. 6.2.2 Applicability. This modeling cycle applies to projects where the form and architecture of the building are still subject to design changes before schematic design begins. This modeling cycle applies to buildings with internal equipment/process loads less than 75% of overall energy breakdown. ANSI/ASHRAE Standard 209-2018 6.2.3 Analysis. Create energy models based on architectural conceptual designs to calculate annual building energy by end use and peak heating and cooling loads with identical HVAC systems. 6.2.3.1 Perform comparative analyses of the conceptual designs. 6.2.3.2 Provide recommendations to improve the energy performance of each conceptual design. 6.3 Modeling Cycle #3—Load Reduction Modeling 6.3.1 Purpose. Identify the distribution of energy by end use. Evaluate strategies that will reduce annual energy use and heating and cooling peak loads. 6.3.2 Applicability. Required for all projects, this modeling cycle shall be completed prior to the final selection of HVAC system type and prior to the end of schematic design. 6.3.3 Analysis 6.3.3.1 Create an energy model based on the baseline design, and calculate the annual energy end uses and heating and cooling peak loads. 6.3.3.2 Develop a list of at least three peak load reduction strategies selected from one or more of the following categories: a. Building envelope (including, but not limited to, insulation level, window-to-wall ratio, glazing performance, shading, infiltration, phase change materials, and thermal mass) b. Lighting and daylighting c. Internal equipment loads d. Outdoor air (including, but not limited to, outdoor airflow, exhaust air, and energy recovery) e. Passive conditioning and natural ventilation When internal equipment loads exceed 60% of the building energy end use, at least two of the strategies shall be selected from the internal equipment loads category. 6.3.3.3 Use energy modeling to evaluate each load reduction strategy compared to the baseline design using identical HVAC system types. 6.4 Modeling Cycle #4—HVAC System Selection Modeling 6.4.1 Purpose. Estimate the annual energy and demand impacts of HVAC system options. 6.4.2 Applicability. This modeling cycle shall be applicable prior to HVAC system selection. When this modeling cycle is used to show compliance with the standard, it shall be started after Modeling Cycle #3 is complete. 6.4.3 Analysis. Use energy modeling to evaluate a minimum of two alternate HVAC systems. 6.5 Modeling Cycle #5—Design Refinement 6.5.1 Purpose. Use energy modeling to evaluate systems in the building, confirm current design directions, and support further development of the building design. 6.5.2 Applicability 6.5.2.1 When this modeling cycle is used to show compliance with the standard, it shall be started after the completion 7 of Modeling Cycle #3 and completed before the end of the construction document phase. 6.5.2.2 Prior to commencing Modeling Cycle #5, a design direction shall be defined for the building form and orientation, the HVAC system type or types, service water heating system type or types, and a space programming scheme. 6.5.3 Analysis. Use energy modeling to refine and develop the design of at least one building system, including, but not limited to the following: a. b. c. d. e. HVAC systems Lighting systems Envelope systems Service water heating systems Process and plug-load systems 6.6 Modeling Cycle #6—Design Integration and Optimization 6.6.1 Purpose. Integrate building systems through an optimization process to assist in meeting one or more of the project performance goals by exploring the complex interactions of multiple variables. 6.6.2 Applicability. When this modeling cycle is used to show compliance with the standard, it shall be completed before the end of the construction document phase. 6.6.3 Analysis 6.6.3.1 The energy modeler shall identify one or more optimization objectives for the analysis that relates to the energy performance goals as identified in Section 5.6. 6.6.3.2 The energy modeler shall identify at least two design variables of interest for a multivariate optimization process. 6.6.3.3 The energy modeler shall identify the design constraints or test range for each analyzed design variable. 6.6.3.4 Conduct an optimization analysis using the defined optimization objective or optimization objectives, design variable or design variables, and design constraints. Informative Note: An optimization analysis does not guarantee that the global minimum or maximum of the optimization objective will be found, only a local minimum or maximum given the design variables, design constraints, initializing values, and optimization method. 6.6.4 Reporting. In addition to the general reporting requirements in Section 5.7.3, for each design optimization measure, report the following: a. b. c. d. Optimization objective or optimization objectives Design variable or design variables analyzed Design constraints or test range for each design variable Description of the optimization method 6.7 Modeling Cycle #7—Energy Simulation-Aided Value Engineering 6.7.1 Purpose. To provide information on the holistic implications of value engineering measures on project performance goals to ensure more informed design decisions. 6.7.2 Applicability 8 6.7.2.1 This modeling cycle shall be used only if first costs have been identified for each project alternative to be evaluated. 6.7.2.2 This modeling cycle shall be used only if the project alternative negatively affects project performance goals. 6.7.3 Analysis 6.7.3.1 Identify project alternatives arising from at least one value engineering proposal. 6.7.3.2 Identify first-cost and operating-cost consequences to building systems directly and indirectly affected by the value engineering proposal. 6.7.3.3 Use energy modeling to evaluate each project alternative. 7. CONSTRUCTION AND OPERATIONS MODELING 7.1 Modeling Cycle #8—As-Designed Energy Performance 7.1.1 Purpose. Develop an energy model to represent the final design in order to compare as-designed performance to project goals. 7.1.2 Applicability. This modeling cycle applies only after construction documents are complete. 7.1.3 Analysis. Develop an energy model with inputs representing the as-designed configuration. 7.2 Modeling Cycle #9—Change Orders 7.2.1 Purpose. Provide feedback on all requests for change orders (COs) that impact the project’s energy performance goals. 7.2.2 Applicability. This modeling cycle shall only be used if the CO negatively affects project performance goals. 7.2.3 Analysis. Prior to initiating construction, identify and document the process for addressing COs. The process shall address, at minimum, the topics in the following subsections. 7.2.3.1 Designated parties and responsibilities. 7.2.3.2 Timeframe for the energy modeler to respond to COs. 7.2.3.3 For each applicable CO, the energy modeler shall perform one of the following analyses. At least one CO response must be evaluated with a model update: a. Qualitative review. Energy modeler provides a written description of whether the CO will increase or decrease metrics defined in Section 5.6. b. Model update. Energy modeler revises the latest proposed design energy model inputs to represent the CO configuration and reports quantitative estimates of how the CO will increase or decrease metrics defined in Section 5.6. 7.2.4 Reporting. In addition to the general reporting requirements in Section 5.7.3, report the following: a. The process used for addressing COs. b. For each CO reviewed, identify the level of analysis performed and the decision to accept or reject the CO. 7.3 Modeling Cycle #10—As-Built Energy Performance ANSI/ASHRAE Standard 209-2018 7.3.1 Purpose. Develop an energy model to represent the as-built project in order to compare as-built performance to project goals. 7.3.2 Applicability. This modeling cycle applies only after construction is complete and as-built drawings and contractor submittals are complete. 7.3.3 Analysis 7.3.3.1 Develop an energy model with inputs representing the as-built conditions, including new design information determined during construction, including, at a minimum, asbuilt drawings and contractor submittals. 7.3.3.2 Occupant- and process-dependent schedules and loads shall reflect design phase inputs or be adjusted to reflect new information. 8. POSTOCCUPANCY MODELING 8.1 Modeling Cycle #11—Postoccupancy Energy Performance Comparison 8.1.1 Purpose. Compare the modeled performance of the last design- or construction-phase energy model to the actual measured energy use and weather conditions of the building in operation. This comparison is intended to inform future energy model assumptions and potentially identify operational energy savings opportunities. The scope of this section does not include adjusting model inputs to calibrate the energy model to the measured energy use, though the comparison described is a fundamental first step to any proposed calibration. 8.1.2 Applicability. This modeling cycle shall be performed no sooner than twelve months after initial occupancy. The comparison year shall include twelve consecutive months of building operations. 8.1.3 Input Data Sources 8.1.3.1 Typical Weather Year Simulation Results. Gather the model output data listed in Section 5.7.3.3 for the proposed design energy model, as simulated with a typical meteorological year (TMY) weather file. 8.1.3.2 Actual Weather Year Simulation Results. Acquire an actual meteorological year (AMY) weather file for the comparison year, and resimulate the same energy model referenced in Section 8.1.3.1 with the AMY weather file. After performing the simulation, recompile the model outputs defined in Section 5.7.3.3. Exceptions to 8.1.3.2: 1. A representative AMY simulation weather file is not publicly or commercially available. 2. The energy model input file or modeling software needed to resimulate the model is not freely available or provided to the energy modeler at the time of completing this modeling cycle. 8.1.3.3 Weather Data. Extract the hourly outdoor drybulb temperature data from the TMY and AMY weather files. If exempt from Section 8.1.3.2, obtain hourly outdoor drybulb temperature measurements for the comparison year as recorded at the building’s local weather station. ANSI/ASHRAE Standard 209-2018 Exceptions to 8.1.3.3: 1. If hourly weather data for the local weather station are not available, daily average, maximum, and minimum data or data from a different weather station may be used. 2. If the energy modeler determines the local weather station is not a good representation of the building’s local weather conditions, data from a different weather station may be used. 8.1.3.4 Energy Consumption and Demand Data. Obtain monthly (30 ± 2 days) or shorter time interval site energy use, and, if applicable, energy cost data for the comparison year for all of the building energy sources. If available, also obtain peak energy demand measurements for each measurement period. Exception to 8.1.3.4: The energy measurement interval may be longer than one month but shall not exceed 65 days. 8.1.4 Analysis. The analysis steps involving measured and simulated energy data shall be performed using the typical weather year simulation results. The same analysis shall also be performed using actual weather year simulation results, except where exceptions to Section 8.1.3.2 apply. 8.1.4.1 Energy Data Alignment. Align the measured and simulated energy data sets to correspond to the beginning and ending days of each calendar month. 8.1.4.2 Energy Data Normalization. Normalize the energy consumption for each aligned interval by dividing the value by the number of days in each interval and the building gross floor area. 8.1.4.3 Typical and Actual Year Weather Metrics. Calculate the following weather parameters for both the typical and actual comparison years. 8.1.4.3.1 Average, maximum, and minimum dry-bulb temperature for each month and the year. 8.1.4.3.2 Heating degree days (HDD) and cooling degree days (CDD), using a common base temperature, for each month and the year. 8.1.4.4 Modeling Uncertainty. For each energy source and total energy use, calculate the following metrics to quantify the differences between measured and simulated (TMY, and if applicable AMY) data sets. a. Normalized mean bias error (NMBE) as defined in ASHRAE Guideline 14 2: n i = 1 yi – ŷi NMBE = ---------------------------------n – p y b. Coefficient of variation of the root-mean-square error (CVRMSE) as defined in ASHRAE Guideline 14: y i – ŷ i 2 ---------------------------- n – p CVRMSE = -------------------------------y 9 where Table 1 Limits y = measured energy use for each month NMBE ±5% ŷ = simulated (typical or actual year) energy use for each month CVRMSE 15% y = arithmetic mean of the measured monthly data i = interval that the measured and simulated energy data are aligned to (such as monthly) n = number of intervals (greater than 1) included in the analysis p = 1 8.1.4.5 Regression Analysis. Use the ASHRAE Inverse Modeling Toolkit (IMT) 3 software or similar methodology to develop linear regression models that correlate energy use (by energy source) to outdoor air temperature, heating and cooling degree days, or other relevant independent variables. Develop regression models for both the measured and simulated (TMY and, if applicable, AMY) data sets, and, from these models, calculate or infer the following: a. Balance-point temperature or balance-point temperatures b. Annual base load energy use c. Annual energy use associated with heating and/or cooling seasons d. Uncertainty metrics defined in Section 8.1.4.4 for the regression models Exception to 8.1.4.5: Regression analysis is required only if Section 8.1.4.5 is specifically adopted by the AHJ. 8.2 Cycle-Specific Reporting 8.2.1 Background Information a. Definition of the comparison year b. A brief description of the modeling cycle or phase of design/construction represented by the latest energy model c. The TMY weather file location d. The AMY weather file location or the geographic location of the building’s local weather station e. A brief narrative describing differences between the simulated and actual building occupancy during the comparison year f. The source of measured energy data g. The floor area used to normalize energy data and costs 8.2.2 Comparison of Actual and Typical Year Weather. Provide graphical and/or tabular comparisons of the following actual and typical year weather conditions. a. Monthly and annual average dry-bulb temperature b. Monthly and annual heating and cooling degree days 10 8.2.3 Comparison of Measured and Simulated Energy Performance. Provide the following graphical and/or tabular comparisons of the normalized measured and simulated (TMY and, if applicable, AMY) data sets. 8.2.3.1 Monthly and total annual energy use for each energy source individually and for all energy sources combined. 8.2.3.2 Monthly and annual peak energy demand for each energy source if available. 8.2.3.3 Annual site energy use and cost, by source and total, divided by the building floor area used in Section 8.1.4.2. 8.2.3.4 An energy signature scatter plot, where the independent and dependent value (x-y coordinates) for each plotted point is defined as follows: a. Independent variable (x). The average outdoor air temperature for the measured or simulated period. b. Dependent variable (y). The normalized, total energy use for the measured or simulated period. 8.2.4 Regression Analysis. If Section 8.1.4.5 is completed, provide a graphical comparison of each regression model with its corresponding measured or simulated dataset. Additionally, provide a table summarizing the metrics defined in Section 8.1.4.5(a) through 8.1.4.5(d). 8.2.5 Narrative. If the uncertainty metrics calculated in Section 8.1.4.4 exceed the limits listed in Table 1, prepare a short, qualitative narrative describing the following. 8.2.5.1 How the measured and simulated (TMY and, if applicable, AMY) data sets differ. 8.2.5.2 A list of possible reasons for the differences. 8.2.5.3 Recommended next steps for resolving the differences or improving building energy performance. 9. NORMATIVE REFERENCES 1. ASHRAE. 2016. ANSI/ASHRAE/IES Standard 90.1, Energy Standard for Buildings Except Low-Rise Residential Buildings, I-P edition. Atlanta: ASHRAE. 2. ASHRAE. 2014. ASHRAE Guideline 14, Measurement of Energy, Demand, and Water Savings. Atlanta: ASHRAE. 3. Kissock, J.K., J.S. Haberl, and D.E. Claridge. 2003. Inverse modeling toolkit: Numerical algorithms (RP1050). ASHRAE Transactions 109(2):425–34. ANSI/ASHRAE Standard 209-2018 This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI. INFORMATIVE APPENDIX A CLIMATE INFORMATION This appendix provides information sources for climate data for building energy modeling. The basic difference between weather and climate is the period of time used when aggregating the original data. Weather data provide outdoor weather information, such as dry-bulb air temperature, or wind speed, for one representative year. Climate data look at the same outdoor weather variables over a multiyear timeframe to define trends in weather data that can affect a building or its energy simulation. Climate data are also being reviewed for the effects known as “climate change” or “global warming.” Some of the information sources may provide information on these topics. Climate change data can be incorporated into an energy modeling analysis to define the risk associated with predicted climate change effects on building energy use and equipment sizing for peak loads. Note About Typical Meteorological Year (TMY) and Actual Meteorological Year (AMY) Weather Data A typical meteorological year (TMY) weather file contains typical weather/climate data for a one-year period that has been statistically derived from the past ten to 30 years of actual meteorological year (AMY) weather/climate data. The TMY file is useful for typical baseline weather file input to an energy modeling analysis. However, the actual weather data files are not statistically modified. For example, the AMY files contain actual extremes for a given timeframe. These extremes may not be present in a TMY file due to the data analysis methods that define the TMY file. For climate analysis trends, both weather files can be useful, depending on the judgment of the energy modeler. 1. General information resources 1.1 Crawley, D.B. 1998. Which weather data should you use for energy simulations of commercial buildings? ASHRAE Transactions 104:2:498–515. 1.2 Rocky Mountain Institute (RMI) 1.2.1 Elements—software that can convert weather data file formats, perform statistical analysis, convert actual weather data into a given file format ANSI/ASHRAE Standard 209-2018 1.3 Energy Design Resources, UCLA Energy Design Tools Group 1.3.1 Climate consultant software 2. Climate data resources 2.1 National Oceanic and Atmospheric Administration (NOAA), part of the United States (U.S.) Department of Commerce 2.1.1 National Centers for Environmental Information (NCEI) 2.1.2 National Weather Service (NWS) Climate Services—provides climate information for U.S. cities: 2.1.2.1 Past weather 2.1.2.2 Climate Prediction Center (CPC): 6 to 14 days, 30 days, and 90 days predictions 2.2 U.S. Department of Energy (DOE) 2.2.1 EnergyPlus Energy Simulation Software 2.2.1.1 Weather Data Sources—website contains information on worldwide weather data sources that may be applicable for climate data use 2.2.2 National Renewable Energy Laboratory (NREL) 2.2.2.1 System Advisor Model (SAM) weather files 2.3 White Box Technologies (WBT) and ASHRAE 2.4 Climate.OneBuilding.org website contains extensive worldwide weather data sources 2.5 WeatherBank, Inc. 2.6 Weather Source 2.7 American Solar Energy Society (ASES)—primarily solar insolation data 2.8 Rocky Mountain Institute (RMI) 3. Climate change/global warming models and information 3.1 Intergovernmental Panel on Climate Change (IPCC) 3.2 National Center for Atmospheric Research (NCAR) community climate model 3.2.1 Community Earth System Model (CESM) 3.2.2 Whole Atmosphere Community Climate Model (WACCM) 3.3 National Oceanic and Atmospheric Administration (NOAA) (http://climate.gov) 3.4 Hadley Centre for Climate Change Prediction and Research at the U.K. Meteorological Office 3.4.1 HadCM3 model 3.5 International Energy Agency (IEA) 3.5.1 Addressing Climate Change Database 3.6 WeatherShift (http://weather-shift.com) 11 This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI. INFORMATIVE APPENDIX B BENCHMARK INFORMATION This appendix provides information sources for building energy use data. These data can be used to define a building energy use benchmark that identifies the energy use for buildings similar to the building undergoing energy modeling analysis. The term similar can refer to buildings that have similar a. b. c. d. use/occupants, location/climate, building energy use systems (HVAC, electrical, etc.), and size/orientation. Determining what similar qualities are most important to the energy modeling analysis is the job of the energy modeler. 1. General information resources 1.1 Brown, Richard E., T. Walter, L.N. Dunn, C.Y. Custodio, P.A. Mathew, D.M. Cheifetz, E. Alschuler, and J. Knapstein. 2014. Getting real with energy data: Using the building performance database to support data-driven analyses and decision-making. Proceedings of 2014 ACEEE Summer Study on Energy Efficiency in Buildings—The Next Generation: Reaching for High Energy Savings. American Council for an Energy Efficient Economy, Washington, DC. http://aceee.org/files/proceedings/2014/ data/index.htm. 2. National energy use data resources 2.1 United States (U.S.) Department of Energy (DOE) 2.1.1 Building Performance Database (BPD) 2.1.2 Federal Energy Management Program (FEMP) 12 2.1.2.1 Comprehensive Annual Energy Data and Sustainability Performance 2.1.3 Buildings Energy Data Book 2.1.4 U.S. Energy Information Administration (EIA) 2.1.4.1 Commercial Buildings Energy Consumption Survey (CBECS) 2.1.4.2 Residential Energy Consumption Survey (RECS) 2.1.5 High Performance Buildings Database 2.1.6 Commercial Building Energy Asset Scoring Tool 2.1.7 EnergyPlus Energy Simulation Software— Commercial Reference Buildings 2.2 United States (U.S.) Environmental Protection Agency (EPA) 2.2.1 Portfolio Manager—existing buildings database 2.2.2 Target Finder— new building energy use goal setter 2.3 Building Owners and Managers Association (BOMA) 2.3.1 BOMA BESt Energy and Environment Report 2.4 Lawrence Berkeley National Laboratory 2.4.1 LABS 21 2.5 ASHRAE 2.5.1 ASHRAE Standard 100 3. Regional, state, and city energy use data resources 3.1 Northwest Energy Efficiency Alliance (NEEA) 3.1.1 Commercial Building Stock Assessment (CBSA) 3.2 California Energy Commission 3.2.1 California Commercial End-Use Survey (CEUS) 3.3 Institute for Market Transformation 3.3.1 Building Energy Performance Policy— information on state and city building energy benchmarking and transparency policies ANSI/ASHRAE Standard 209-2018 This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI. INFORMATIVE APPENDIX C SIMPLE BOX MODELING 1. Create a simple box model using an energy simulation program. Some programs use preprocessor or expert (“wizard”) systems to help create these models. The simple box model energy simulation program may use monthly design day hourly information (288 hour in lieu of 8760 hour simulation). 2. Initial input parameters 2.1 Where design parameters are known, those should be used; otherwise, the following should be used to set input parameters. 2.2 Building type (e.g., assembly, healthcare, hotel/ motel, light manufacturing, office, restaurant, retail, school, warehouse, laboratory, etc.). The building type infers information about building program area allocations and locations (core or perimeter space) as well as occupancy and internal load information by program area. 2.3 Building form. If the rough building form has not been otherwise prescribed, follow the parameters given in Table 13 of NREL/TP-5500-46861 “U.S. Department of Energy Commercial Reference Building Models of the National Building Stock.” Aspect ratio is defined as the overall length in the east-west direction divided by the overall length in the northsouth direction. If the building type is not one given in Table 13, and no other information is known, use a rectangle with an aspect ratio of 1.62, floor-to-floor height 12.5 ft (3.81 m), flat roof, glazing fraction 30%. ANSI/ASHRAE Standard 209-2018 2.4 Site location by weather file location. See Section 5.6 for types and sources of weather files. 2.5 Total conditioned square footage. The accuracy of this parameter should be order of magnitude. 2.6 Number of floors, if known. If not known, use the number of floors given in Table 13 of NREL/TP-550046861 referenced above. Unless known otherwise, each of multiple floors shall have the same footprint. 2.7 Fenestration amount. Use Table 13 of NREL/TP5500-46861 or the applicable local energy code or ASHRAE/IES Standard 90.1, Table G3.1.1-1, to define default WWR percent for various building types if actual WWR is not known. Allocate percent windowto-wall ratio, by orientation if known, evenly distributed if not. 2.8 Internal loads (people, equipment, and lighting). If known, allocate by program area. If unknown, distribute evenly over the conditioned area. Lighting power densities should be the maximum allowed by applicable local energy code. If unknown, use applicable local energy code or Standard 90.1 User’s Manual, Appendix G tables, for schedules, equipment power, and occupant densities. Additional information on internal loads and schedules may be found in NREL/TP-5500-46861 Appendices A and B. 2.9 Ventilation shall be in accordance with applicable local building codes, ASHRAE Standard 62.1, outside air rate per occupant, or ASHRAE/ASHE Standard 170 air change rate by usage, whichever is largest. 2.10 Perimeter/core zoning. Perimeter zone depth shall be no greater than 1.5 times floor to floor height. 2.11 Building envelope assemblies shall be in accordance with the applicable local building codes or the baseline performance of ASHRAE/IES Standard 90.1, Table G3.1.5. 2.12 ASHRAE/IES Standard 90.1, Appendix G, baseline HVAC system type is only to be used when sufficient information on the HVAC system has not been provided to the energy modeler. Refer to Appendix C, Section 2.1. 13 This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI. INFORMATIVE APPENDIX D OWNER’S PROJECT REQUIREMENTS Per Section 5.6.1, the owner’s project requirements (OPR) shall be defined at an early stage of design. Table D-1 provides a list of suggested energy performance categories to be addressed in the OPR. For each category, one or more recommended metrics have been provided. This list is not intended to be exhaustive, nor are all metrics applicable to all designs. Table D-1 Owner’s Project Requirements (OPR) Overall Energy Budget Energy Use Intensity (EUI) kBtu/ft2·yr (GJ/m2·yr) Building Envelope Walls, roof, and floors Assembly U-factor Below-grade walls and slabs Assembly U-factor, F-factor Infiltration cfm/ft2 ([m3/s]/m2) of building envelope area @ 0.2 in. of water (50 Pa) or 0.3 in. of water (75 Pa) Windows U-value, SHGC, VLT, LSG ratio Daylighting Spatial daylight autonomy Percent of annual hours Contrast Maximum to minimum illuminance ratio Direct solar Annual sunlight exposure (IES LM-82), sun cutoff angle Lighting and Equipment Power Density Lighting (LPD) W/ft2 (W/m2) Light levels Footcandles for each space function Exterior lighting Percent of the ASHRAE/IES Standard 90.1 allowance, W/lin ft (W/lin m), W/ft2 (W/m2) Plug loads W/ft2 (W/m2) Plumbing Faucets and showers gpm (L/s) @ 60 psi (414 Pa) Toilets and urinals gpf ([L/s]/flush) Water heating efficiency EF, %, COP Loop design Riser locations, recirculation vs. no recirculation, booster pumps HVAC Cooling 14 Design conditions Assumptions and implications Peak load ft2/ton (m2/kW) Efficiency kW/ton, SEER, EER, IEER, COP, IPLV Hydronic loop flow gpm/ton ([L/s]/kW), loop T Cooling towers gpm/hp ([L/s]/kW) ANSI/ASHRAE Standard 209-2018 Table D-1 Owner’s Project Requirements (OPR) (Continued) HVAC (contd.) Natural cooling Percent of floor area, hours of year Heating Design conditions Assumptions and implications Peak load Btu/ft2 (J/m2) Efficiency AFUE, EF, %, HSPF, COP Hydronic loop flow Loop T, °F (°C) Heat recovery Percent of design or overall annual Fans Efficiency hp/cfm (W/[L/s]) or W/cfm (W/[L/s]) Design flow cfm/ft2 ([L/s]/m2) of floor area, cfm/ton ([L/s]/kW) Ventilation Standard ASHRAE Standards 62.1 and 62.2, IMC, Title 24 Design criteria Number of occupants by space function, zone and system ventilation efficiency, % oversized, Ev > Ez, ppm CO2 limit Controls CO2 and occupancy sensors Energy recovery Sensible/latent effectiveness, % summer, % winter Natural ventilation Percent of floor area, hours of year Controls Occupied/unoccupied schedules and temperature set points, humidity range Thermal comfort Hours set point not met, operative temperature Other Renewables ANSI/ASHRAE Standard 209-2018 Photovoltaics, solar water heating 15 This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI. Internal Loads • • • • INFORMATIVE APPENDIX E QUALITY ASSURANCE AND QUALITY CONTROL CHECKLISTS This appendix provides example quality assurance (QA) and quality control (QC) input and output checklists to support meeting the intent of Sections 5.7.4 and 5.7.5. Documentation templates and other QA and QC resources are provided at the end of this appendix. Example QA Input Checklist Project and Building Level • • • • • • • • • Energy performance goals Utility rates Weather file data, annual and monthly values as appropriate (see Section 5.3.1) Gross building area Conditioned building area Floor area by space type Number of floors Floor-to-floor height Thermal blocks Envelope • • • • 16 Roof by level—description of construction, area U-value, emissivity, reflectivity Wall assemblies—description of layers, total area, opaque wall area, location, U-value, infiltration modeling approach, infiltration rate Fenestration—frame type, VLT, SHGC, U-value center of glass, U-value assembly, area, percent glazing, exterior shading, interior shading Ground contact assemblies • Occupant density—building average, total number of occupants, ft2/program occupants Lighting density—building average, density by space type Equipment power density—building average, density by space type Elevator energy and use—power demand, energy use, number Ventilation and exhaust rates—cfm/person, cfm/ft2 total and by zone type External Loads • Exterior lighting HVAC Equipment • • • • • • • Temperature set points—heating/cooling set points for each zone Air-side system units—supply cfm, outdoor air cfm, supply temperature set point, supply fan power, flow control, minimum flow ratio, return fan cfm, return fan power, return fan flow control, heat recovery type/effectiveness/ power consumption/capacity control Exhaust fans—kW, schedule Cooling equipment—capacity, efficiency, part-load performance Water-source heat pumps—configuration (open/closed loop), capacity, efficiency varying by condenser water temperature, supply water temperature, loop T Pumps—bhp, gpm, head, capacity control, minimum flow ratio Domestic hot water—efficiency, hot-water supply temperature, storage tank size, storage tank UA Plant Equipment • • Efficiency, capacity, part-load performance Process chilled- and hot-water loads—peak load and load profile Schedules • By space type for weekdays, weekends, and holidays— occupancy, cooling and heating set points, lighting, plug loads ANSI/ASHRAE Standard 209-2018 Example Model Output Checklist Use the following checklists to compare model outputs to design values and/or benchmark values to verify correctness or reasonableness. In addition, compare output results between design alternatives. Project and Building Level Metric Units Energy cost index (ECI) $/ft2 ($/m2) Energy use intensity (EUI) kBtu/ft2 (GJ/m2) Cooling capacity ft2/ton (m2/W) Heating capacity Btu/(h·ft2) (J/h·m2) Supply airflow cfm (L/s) Supply airflow density cfm/ft2 (L/s·m2) Outdoor air ventilation rate cfm (L/s) Outdoor air ventilation rate fraction Fraction Outdoor air ventilation rate per person cfm/person (L/s·person) Number of people Number Lighting W/ft2 (W/m2) Task lights W/ft2 (W/m2) Miscellaneous internal loads W/ft2 (W/m2) Weather file Altitude ft (m) Orientation Conditioned floor area ft2 (m2) Floor area by space type ft2 (m2) Annual peak electric load W/ft2 (W/m2) Electric energy kBtu/ft2 (GJ/m2) Fuel energy kBtu/ft2 (GJ/m2) Electric end-use energy kBtu/ft2 (GJ/m2) Fuel end-use energy kBtu/ft2 (GJ/m2) Other energy sources (e.g., chilled water) kBtu/ft2 (GJ/m2) Unmet cooling hours hours/yr Unmet heating hours hours/yr System Level Checklist Metric Units Floor area served by each system ft2 (m2) Outdoor air fraction Ratio Cooling capacity tons (kW) Sensible heat ratio Ratio Heating capacity kBtu/h (kW) Supply airflow cfm (L/s) Fan power kW Maximum cooling load kBtu/h (kW) Maximum heating load kBtu/h (kW) Free cooling/economizer hours Hours ANSI/ASHRAE Standard 209-2018 17 Plant Level Checklist Metric Units Peak cooling load kBtu/hr (kW) Peak heating load kBtu/hr (kW) Cooling equipment capacity Ton (kW) Cooling equipment total annual load kBtu (GJ) Cooling equipment electricity use kWh Cooling equipment efficiency kW/ton Run hours cooling equipment Hours Heating equipment capacity kBtu/hr (kW) Heating equipment total annual load MMBtu (GJ) Heating equipment energy use kBtu (GJ) Heating equipment average efficiency % Run hours heating equipment Hours SWH equipment capacity set point kBtu/h (kW) SWH equipment total annual load MMBtu (GJ) SWH equipment energy use kBtu (GJ) SWH equipment average efficiency % 18 ANSI/ASHRAE Standard 209-2018 Additional Resources Some of the materials listed below have been developed by practitioners and have not been formally vetted by the modeling community. Table E-1 provides links to materials to support developing, documenting, and checking model input values. Table E-2 provides links to materials to support documenting and checking output for reasonableness. Table E-1 Documentation Templates and Quality Assurance Checklists for Model Input Name Source Description LEED EAc1, Section 1.4 Tables SevenGroup for the USGBC The spreadsheets assist the energy modeler in developing and documenting the ASHRAE/ IES Standard 90.1, Appendix G, building energy model inputs. Designed to be completed before developing the model, the forms support input quality control checks. Sample Energy Model Assumptions Tracking Log SERA Architects Supports the documentation of design data that underlie model input values. Also includes “schedules” tab for graphically depicting values and “outputs” tab for recording results to support accountability. Model Input Development Spreadsheet RMI Supports the calculation and documentation of model input values from design data. Some values are tied to ASHRAE/IES Standard 90.1, Appendix G, procedures. Example Building RMI Model eQUEST/DOE-2 Checklist A checklist to support quality assurance checking of a whole-building simulation model. Some of the items are eQUEST specific. https://www.rmi.org/our-work/buildings/ pathways-to-zero/deep-retrofit-tools-resources COMNET Appendix B Modeling Data COMNET Provides reasonable input values for plug loads by building and space type along with other data to support assigning model inputs values early in the design process. Advanced Energy Modeling for LEED USGBC Provides quality control checklists for both modeling inputs and outputs, particularly when creating a baseline model in accordance with ASHRAE/IES Standard 90.1, Appendix G. http://www.usgbc.org/Docs/Archive/General/Docs7795.pdf Table E-2 Documentation Templates and Quality Assurance Checklists for Model Output Name Source Description Example Building RMI Model eQUEST/DOE-2 Checklist A checklist to support quality assurance checking of a whole-building simulation model. Some of the items are eQUEST specific. https://www.rmi.org/our-work/buildings/ pathways-to-zero/deep-retrofit-tools-resources eQUEST Quality Control Checklists Jeff Hirsch and Associates Outlines general quality assurance principles and suggests values to check in DOE-2 output reports. Office Building Benchmark Values IBPSA-USA BEM Library Lists typical values of key performance metrics typical for a large office building. Three categories of efficiency are considered: inefficient existing, efficient, and low-energy. http://www.bemlibrary.com Building Performance Metrics James Waltz From Waltz’s book, Computerized Building Energy Simulation Handbook. http://www.rmi.org/Content/Files/WaltzGuide.pdf Recommended Metrics for QC Benchmarking IBPSA-USA BEM Library A list of parameters helpful for completing quality control checking of model input and output values. Practitioners can consider including them as part of their QC tools. Developers can consider having software calculate and report these values. ANSI/ASHRAE Standard 209-2018 19 This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may contain material that has not been subject to public review or a consensus process. Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI. INFORMATIVE APPENDIX F INFORMATIVE REFERENCES AIA. 2012. Architect’s Guide to Integrating Energy Modeling in the Design Process. Washington, DC: American Institute of Architects. http://www.aia.org/practicing/ AIAB097932. ASHRAE. 2015. ANSI/IES/ASHRAE 100, Energy Efficiency in Existing Buildings. Atlanta: ASHRAE. ASHRAE. 2016. ANSI/ASHRAE 62.1, Ventilation for Acceptable Indoor Air Quality. Atlanta: ASHRAE. ASHRAE. 2016. ANSI/ASHRAE 62.2, Ventilation for Acceptable Indoor Air Quality in Residential Buildings. Atlanta: ASHRAE. ASHRAE. 2017. ANSI/ASHRAE/ASHE 170, Ventilation of Health Care Facilities. Atlanta: ASHRAE. ASHRAE. 2017. ASHRAE Building Energy Modeling Professional (BEMP) Certification Candidate Guidebook. Atlanta: ASHRAE. ASHRAE. 2017. 2017 ASHRAE Handbook—Fundamentals, Chapter 19, “Energy estimating and modeling methods.” Atlanta: ASHRAE. CIBSE. 2015. Applications Manual 11, Building Performance Modelling. London: Chartered Institution of Building Services. http://www.cibse.org/knowledge/ cibse-am/am11-building-performance-modelling-new2015. Clarke, J.A. 2001. Energy Simulation in Building Design, 2nd ed. Oxford: Butterworth-Heinemann. Clayton, M.; J. Haberl; W. Yan; S. Kota; F. Farias; W.-S. Jeong; J. Kim; and J.L.B. Alcocer. 2013. Development of a Reference Building Information Model (BIM) for Thermal Model Compliance Testing. ASHRAE Research Project 1468 Final Report. Atlanta: ASHRAE. Dunn, J., L. Hemley, G. Gladics, and E. Djuaedy. 2013. UI-IDL building simulation protocols v. 1.0 DRAFT. Boise, ID: University of Idaho Integrated Design Lab. https://sites.google.com/site/idlbsug/modeling-resources/ui-idl-simulationprotocols-draft. Energy Design Resources. 2010. Design Guidelines: Advanced Simulation Guidebook, Volume II. San Francisco, CA: California Public Utilities Commission. https://energydesignresources.com/media/2299/ EDR_DesignGuidelines_Advanced_Simulation_Vol2.pdf. EVO. 2006. International Performance Measurement and Verification Protocol Applications Volume III, Part I: Concepts and Practices for Determining Energy Savings in New Construction. EVO 30000-1:2006. Washington, DC: Efficiency Valuation Organization. Franconi, E. 2011. Introducing a framework for advancing building energy modelling methods & processes. Pro20 ceedings of Building Simulation 2011: 12th Conference of International Building Performance Simulation Association, Sydney, 14–16 November. Fuller, S.K., S.R. Petersen, and R.T. Ruegg. 1996. Life-Cycle Costing Manual for the Federal Energy Management Program. Gaithersburg, MD: National Institute of Standards and Technology. Hensen, J., and R. Lamberts. (Eds.) 2011. Building Performance Simulation for Design and Operation. Abingdon, Oxon: Routledge. Hotchkiss, E., A. Walker, and N. Carlisle. 2012. Procuring Architectural and Engineering Services for Energy Efficiency and Sustainability: A Resource Guide for Federal Construction Project Managers. DOE/GO-102012-3292 Golden, CO: National Renewable Energy Laboratory. IBPSA-USA. BEMBook wiki. International Building Performance Simulation Association—USA Affiliate. IES. 2012. IES LM-82, Characterization of LED Light Engines and LED Lamps for Electrical and Photometric Properties as a Function of Temperature. New York: Illuminating Engineering Society. Kaplan, M., and P. Caner. 1992. Guidelines for Energy Simulation of Commercial Buildings. DOE/BP/26683--2 DE92 015597. Portland, OR: Bonneville Power Administration. Kota, S., F. Farias, W. Jeong, J. Kim, J.B. Alcocer, M.J. Clayton, W. Yan, and J.S. Haberl. 2016. Development of a reference building information model (BIM) for thermal model compliance testing (RP-1468) Part I: Guidelines for generating thermal model input files. ASHRAE Transactions 1(122):256–66. McCarry, B., and L. Montague. 2010. Guidelines for energy analysis integration into an architectural environment. Perkins & Will Research Journal 2 (2):72–96. Nall, D. H, and D.B. Crawley. 2011. Hall of fame: Energy simulation in the building design process: Mainframe computer simulation programs for energy analysis can provide important information throughout the building design process. ASHRAE Journal 53(7):36–43. NREL. 2011. U.S. Department of Energy Commercial Reference Building Models of the National Building Stock. NREL/TP-5500-46861, National Renewable Energy Laboratory, Lakewood, CO. USDOE. 2015. Energy Star multifamily high rise program simulation guidelines. Version 1.0, Revision 03 January 2015. Washington, DC: United States Department of Energy. USDOE. 2001. Low-Energy Building Design Guidelines. DOE/GO-102001-0950; DOE/EE-0249 NREL/BK-71025807. Golden, CO: National Renewable Energy Lab. USGBC. 2011. Advanced Energy Modeling for LEED Technical Manual v.2.0. Washington, DC: United States Green Building Council. http://www.usgbc.org/resources/ advanced-energy-modeling-leed-technical-manual-v20. Waltz, J.P. 2000. Computerized Building Energy Simulation Handbook. Lilburn, GA: Fairmont Press. Washington State Department of Enterprise Services Division of Engineering and Architectural Services. 2013. Energy Life Cycle Cost Analysis. Washington State Department of Enterprise Services, Olympia, WA. ANSI/ASHRAE Standard 209-2018 POLICY STATEMENT DEFINING ASHRAE’S CONCERN FOR THE ENVIRONMENTAL IMPACT OF ITS ACTIVITIES ASHRAE is concerned with the impact of its members’ activities on both the indoor and outdoor environment. ASHRAE’s members will strive to minimize any possible deleterious effect on the indoor and outdoor environment of the systems and components in their responsibility while maximizing the beneficial effects these systems provide, consistent with accepted Standards and the practical state of the art. ASHRAE’s short-range goal is to ensure that the systems and components within its scope do not impact the indoor and outdoor environment to a greater extent than specified by the Standards and Guidelines as established by itself and other responsible bodies. As an ongoing goal, ASHRAE will, through its Standards Committee and extensive Technical Committee structure, continue to generate up-to-date Standards and Guidelines where appropriate and adopt, recommend, and promote those new and revised Standards developed by other responsible organizations. Through its Handbook, appropriate chapters will contain up-to-date Standards and design considerations as the material is systematically revised. ASHRAE will take the lead with respect to dissemination of environmental information of its primary interest and will seek out and disseminate information from other responsible organizations that is pertinent, as guides to updating Standards and Guidelines. The effects of the design and selection of equipment and systems will be considered within the scope of the system’s intended use and expected misuse. The disposal of hazardous materials, if any, will also be considered. ASHRAE’s primary concern for environmental impact will be at the site where equipment within ASHRAE’s scope operates. However, energy source selection and the possible environmental impact due to the energy source and energy transportation will be considered where possible. Recommendations concerning energy source selection should be made by its members. ASHRAE · 1791 Tullie Circle NE · Atlanta, GA 30329 · www.ashrae.org About ASHRAE ASHRAE, founded in 1894, is a global society advancing human well-being through sustainable technology for the built environment. The Society and its members focus on building systems, energy efficiency, indoor air quality, refrigeration, and sustainability. Through research, Standards writing, publishing, certification and continuing education, ASHRAE shapes tomorrow’s built environment today. For more information or to become a member of ASHRAE, visit www.ashrae.org. To stay current with this and other ASHRAE Standards and Guidelines, visit www.ashrae.org/standards. Visit the ASHRAE Bookstore ASHRAE offers its Standards and Guidelines in print, as immediately downloadable PDFs, on CD-ROM, and via ASHRAE Digital Collections, which provides online access with automatic updates as well as historical versions of publications. Selected Standards and Guidelines are also offered in redline versions that indicate the changes made between the active Standard or Guideline and its previous version. For more information, visit the Standards and Guidelines section of the ASHRAE Bookstore at www.ashrae.org/bookstore. IMPORTANT NOTICES ABOUT THIS STANDARD To ensure that you have all of the approved addenda, errata, and interpretations for this Standard, visit www.ashrae.org/standards to download them free of charge. Addenda, errata, and interpretations for ASHRAE Standards and Guidelines are no longer distributed with copies of the Standards and Guidelines. ASHRAE provides these addenda, errata, and interpretations only in electronic form to promote more sustainable use of resources. Product code: 86608 4/18