Uploaded by ij648001

express-installation-guide

advertisement
For Additional Technical Assistance Call +1.509.332.1890
Express Installation Guide
SEL-710 Motor Protection Relay
Package Contents
SEL-710
Blank Pushbutton LED Label
Product Literature
7.36
(187.0)
Contents:
CD Installation:
• Express Installation Guide
• Instruction Manual
• Configurable Label
Instructions & Template
• Option Cards Instruction Sheet
• DeviceNet User’s Guide
• DeviceNet Eleectronic Data
Sheet (EDS)
• ReadMe.txt
• Adobe® Reader®
1. Insert the CD into the drive.
2. If Windows autorun is
enabled, the Contents.html file
will load automatically.
3. If Windows autorun is not
enabled, access files via
Windows Explorer.
Blank Target LED Label
Label Removal Tool
2350 NE Hopkins Court • Pullman, WA 99163 USA
Tel: +1.509.332.1890 • Fax: +1.509.332.7990
www.selinc.com • info@selinc.com
5.47
(139.0)
Panel Cutout Template
LEFT
© 2009 Schweitzer Engineering Laboratories, Inc.
All rights reserved
PM710-01-CD/UCD02076
UP
198-0424
UP
RIGHT
198–0424
*UCD02076*
20090327
Product Literature CD
No. 8-32 Mounting Screws
& Gasket
Configurable Label Kit
Safety Information
Dangers, Warnings, and Cautions
See the product manual for additional safety information. The product documentation uses three kinds of hazard statements, defined as
follows:
DANGER
WARNING
Indicates an imminently hazardous situation that, if not
avoided, will result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation that, if not
avoided, could result in death or serious injury.
Indicates a potentially hazardous situation that, if not
avoided, may result in minor or moderate injury or
equipment damage.
Safety Symbols
The following symbols are often marked on SEL products.
CAUTION
ATTENTION
Refer to accompanying documents.
Se reporter à la documentation.
Earth (ground)
Terre
Protective earth (ground)
Terre de protection
Direct current
Courant continu
Alternating current
Courant alternatif
Both direct and alternating current
Courant continu et alternatif
Instruction manual
Manuel d’instructions
Safety Marks
The following statements apply to this device.
General Safety Marks
Motor Overload: Class 10, 20, and 30.
Surcharge du Moteur: Classe 10, 20 et 30.
For use in Pollution Degree 2 environment.
Pour l'utilisation dans un environnement de Degré de Pollution 2.
Ambient air temperature shall not exceed 50°C (122°F).
La température ambiante de l'air ne doit pas dépasser 50°C (122°F).
For use on a flat surface of a Type 12 enclosure.
Pour l’utilisation sur une surface plane d'un boîtier de Type 12.
Terminal Ratings
Wire Material
Use 75°C (167°F) copper conductors only.
Valeurs nominales des bornes
Matériau de fil
Utiliser seulement conducteurs en cuivre 75°C (167°F).
Couple de serrage
Bornier : 0,9–1,4 Nm (8–12 livres-pouce)
Fiche à compression : 0,5–1,0 Nm (4,4–8,8 livres-pouce)
Vis à oreille de montage de la fiche à compression : 0,18–0,25 Nm
(1,6–2,2 livres-pouce)
Tightening Torque
Terminal Block: 0.9–1.4 Nm (8–12 in-lb)
Compression Plug: 0.5–1.0 Nm (4.4–8.8 in-lb)
Compression Plug Mounting Ear Screw: 0.18–0.25 Nm
(1.6–2.2 in-lb)
2
Safety Information
Hazardous Locations Safety Marks
WARNING – EXPLOSION HAZARD
AVERTISSEMENT – DANGER D'EXPLOSION
Open circuit before removing cover.
Ouvrir le circuit avant de déposer le couvercle.
WARNING – EXPLOSION HAZARD
AVERTISSEMENT – DANGER D'EXPLOSION
Substitution of components may impair suitability for Class I, Division 2.
La substitution de composants peut détériorer la conformité à Classe I, Division 2.
Operating Temperature Range: –40°C to +85°C (–40°F to +185°F).
Plage de température de fonctionnement : –40°C à +85°C (–40°F à +185°F).
Hazardous Locations Operating Temperature Range: –20°C to +40°C
(–4°F to +104°F).
Emplacements Plage de température de fonctionnement d’emplacements
dangereux : –20°C à +40°C (–4°F à +104°F).
3
Typical Connections
Stop
120/240 Vac
50/60 Hz
Start
CR
CR
A01 A02
GND +/H
A03 A04 A05 A06 A07 A08 A09 A10
A11
A12
-/N
OUT_01*
OUT_02*
OUT_03*(TRIP)
IN_01
CONTROL
INPUTS
OUTPUT CONTACTS
INPUT POWER
IN_02
(Trip Fail-Safe Contactor Wiring Shown)
Front
5
4
9
3
2
8
7
SEL-710
Motor Relay
1
6
Port 3
5
4
9
3
2
8
7
1
6
Optional Input Output Cards
Optional Ethernet (single or dual)
1–12 RTDs
+
+
—
+
—
+
—
+
—
+
—
+
—
+
4 Digital Inputs / 4 Digital Outputs
OR
Winding
Bearing
Others
+
—
10 RTDs
+
—
IRIG-B/PTC
—
IRIG-B Time Source
—
PTC Thermistor
Copper Wire
SEL-2600
External
RTD Module
(Optional)
Multimode Fiber
≤ 1000 m
RX
Fiber-Optic
Input
TX
Fiber-Optic
Output
FO Cable**
TX—
RX+
RX—
SHIELD
4 Analog Inputs / 4 Analog Outputs
(Optional)
TX+
Port 4A EIA-485
V—
CAN_L
SHIELD
CAN_H
V+
Spare
Input
8 Analog Inputs
Port 4 DeviceNet
(Optional)
Ambient
3 Digital Inputs / 4 Digital Outputs / 1 Analog Output
8 Digital Inputs
CURRENT INPUTS
VOLTAGE INPUTS (Optional)
* Factory Default Function
** SEL Fiber Optic Cables
240-1506 – 1 m (3.3 feet) ST/ST
240-1507 – 5 m (16.4 feet) ST/ST
240-1508 – 15 m (49.2 feet) ST/ST
Other lengths available by request
VA
VB
VC
N
E01
E02
E03
E04
*
A diagram from a four-wire Wye
connection also available in the
instruction manual. Also,
differential elements connections
are shown in the manual.
IA
Z01 Z02
IB
Z03 Z04
IC
Z05 Z06
IN
Z07 Z08
CR
A
B
C
MOTOR
Open-Delta Potential and Residual Ground CT Connections
4
Rack Mounting
You can mount the SEL-710 in a sheltered indoor environment (a building or an enclosed cabinet) that does not exceed the temperature
rating of –40°C to +85°C. For mounting consideration the relay dimensions are shown below.
7.56
(192.0)
7.36
(187.0)
5.67
(144.0)
1.12
(28.5)
5.80
(147.4)
5.47
(139.0)
New Control Center
1. Place the enclosed panel
2. Make smooth cut around
cutout over desired mounting
cutout.
location and trace.
3. Place mounting gasket
around relay and insert
unit into hole. (The
photo displays optional
appearance bezel.)
4. Fasten relay to mounting
plate with included screws.
3. Place mounting gasket
around relay and insert unit
into retrofitting plate.
4. Fasten relay to mounting
plate with included screws.
Retrofitting
1. Remove old relay.
2. Insert retrofitting plate and
fasten (see www.selinc.com/
sel-710.htm for retrofits).
5
Connections
Shown for SEL-710 with IRIG-B, Ethernet, EIA-232, Fiber Optic, Voltage Option, RTD option, and 4 DO/3 DI/1 AO option. Refer to
the SEL-710 manual for additional details and other options.
Wire sizes for connections are dictated by the terminal blocks and expected load currents. You may use the following table as a guide in
selecting wire sizes:
Connection Type
Minimum Wire Size
Maximum Wire Size
2
Grounding (Earthing) Connection
18 AWG (0.8 mm )
14 AWG (2.1 mm2)
Current Connection
16 AWG (1.3 mm2)
12 AWG (3.3 mm2)
Potential (Voltage) Connection
18 AWG (0.8 mm2)
14 AWG (2.1 mm2)
Contact I/O
18 AWG (0.8 mm2)
14 AWG (2.1 mm2)
Other Connection
18 AWG (0.8 mm2)
14 AWG (2.1 mm2)
Card Slot A: Power Supply Card With 2 DI/3 DO
Step 1.
Connect appropriate power supply to terminal 01 (+/H) and terminal 02 (-/N). Note that power terminals are isolated from
chassis ground.
Step 2.
Connect ground terminal GND to a rack frame or switchgear ground for proper safety and performance.
Step 3.
Connect as many as 2 digital inputs per application requirements, to optoisolated inputs IN_01
(terminals 10 and 11), and IN_02 (terminals 11 and 12).
Step 4.
Connect the 3 output contacts per application requirements to OUT_01 (terminals 03 and 04), OUT_02
(terminals 05 and 06), and OUT_03 (terminals 07, 08, and 09).
Card Slot B: Main Board With IRIG-B, Ethernet, EIA-232, Fiber Optic
Step 1.
Connect communications devices as required to front DB-9 serial Port F (EIA-232), rear DB-9 serial Port 3 (EIA-232),
10/100BASE-T Ethernet port (RJ45 connector) and fiber-optic (ST® connector) serial Port 2.
Step 2.
Connect IRIG-B time-code input to terminals 01 (+) and 02 (-).
Card Slot C: 3 Digital Inputs, 4 Digital Outputs, 1 Analog Output Card (3 DI/4 DO/1 AO)
Step 1.
Connect additional digital inputs (IN_01, IN_02, IN_03) and outputs (OUT_01, OUT_02, OUT_03, OUT_04), if required
by application, using the connection diagram.
Step 2.
Connect the analog (transducer) output AO_01 using terminals 09 and 10.
6
Connections
Card Slot D: 10 RTD Inputs Card
Connect as many as ten RTDs as required by application. Example: Connect RTD1 (+) to terminal 01, RTD1 (-) to terminal 02, RTD1
(common or return) and RTD1 (shield, if available) to terminal 03.
v
Card Slot E: Voltage Inputs Card
Connect 4-wire wye-connected PTs or open-delta connected PTs as shown in the typical connections diagram. For other PT connection options refer to Section 2 of the SEL-710 manual.
Card Slot Z: Current Inputs Card
Connect phase current and neutral current inputs as shown in the typical connections diagram.
Step 1.
Connect Phase A, Phase B, and Phase C current inputs to terminals 01 and 02; terminals 03 and 04; and terminals 05 and 06,
respectively, following the convention shown in the typical connections diagram.
Step 2.
Connect neutral current IN inputs to terminals 07 and 08.
Refer to Section 2 of the SEL-710 manual for additional details and other connection options.
7
Communication With Relay
There are two ways of communicating with the SEL-710 Motor Relay. You can communicate with the relay using the human-machine
interface (HMI) on the front panel or through serial port communications with a computer. For communications, the computer must
have a serial port and the operating system should be Windows® 2000 or newer. A standard EIA-232 crossover cable or an SEL-234A
cable will also be required.
HMI Pushbuttons
Press the TARGET RESET pushbutton
to clear targets that have been alarmed.
Press the directional (up, down, left, right)
pushbuttons to scroll through options.
TARGET
RESET
ESC
ENT
Press the ENT pushbutton
for selection to see next menu.
Press the ESC pushbutton
to return to previous menu.
Computer Connection Steps
Step 1.
Connect the PC and the relay using a serial communications cable.
Step 2.
Apply power to both the PC and the relay.
Step 3.
Open a terminal emulation program.
Option 1: ACSELERATOR QuickSet SEL-5030 Software
Open ACSELERATOR QuickSet and proceed to Step 4. If you do not
have ACSELERATOR QuickSet, you can download the program from
www.selinc.com/sel-5030.htm. Refer to Section 3 of the SEL-710
manual for more information about ACSELERATOR QuickSet.
Option 2: HyperTerminal
To open HyperTerminal go to Start > Programs > Accessories >
Communications > HyperTerminal. Once there you will be
prompted to enter a name of your choice for the connection. Then
you will choose which port to connect through. Make sure you select
the same port that you connected the cable to, then click OK.
Step 4.
Set the PC terminal emulation program to the same communications
port settings as shown in the figure to the right and click OK.
Step 5.
Press the <Enter> key on the PC keyboard to check the
communications link. You should see the = prompt. If you do not see
the = prompt, check the cable connections, confirm that the settings
in the terminal emulation program are the default values, and that the
emulation mode is set to VT100.
Step 6.
Once connected, you can set all other relay settings and obtain values
as needed. Refer to Section 6 in the SEL-710 manual for more
information.
SEL-710 Relays are shipped with default passwords. To prevent unauthorized access, change default passwords
to private passwords at installation. SEL shall not be responsible for damage resulting from unauthorized access.
8
Relay Settings
This section of the Express Installation Guide provides a step-by-step process to set the SEL-710 for basic protection purposes. For
more in-depth relay setting procedures, please refer to the SEL-710 manual or contact your local SEL representative. To get more directions on relay setting using PC configuration, please refer to Section 3 of the SEL-710 manual.
Step 1.
Locate the values listed below. Some of the values needed are located on the control center nameplate while others can be
found directly on the motor nameplate.
Find the Values:
CT Ratio (CTR1) =
Full Load Amps (FLA1) =
Service Factor (SF) =
CT Ratio to Ground (CTRN) =
Phase PT Ratio (PTR) =
Line Voltage (VNOM) =
Delta/Wye Connection (DELTA_Y) =
Single V Input (SINGLEV) =
Step 2.
Enter Access Level 2. Whenever prompted for a password, enter the corresponding password. To change the
character, use the arrow keys and press the ENT pushbutton to select the character. Once the full password has been
entered, scroll to Accept and press the ENT pushbutton.
Valid Password Characters
Step 3.
Factory Default Passwords for Access Levels 1 and 2
Alpha
ABCDEFGHIJKLMNOPQRSTUVWXYZ
abcdefghijklmnopqrstuvwxyz
Numeric
0123456789
Special
!"#$%&'()*+,-./:;<=>?@[\]^_`{|}~
Access Level
Factory Default Password
1
OTTER
2
TAIL
There are three settings sections that need to be set in order to provide basic protection. Navigate to ENT >
SET/SHOW > GLOBAL > General Settings. Once in this menu the following parameters can be set. Complete
these settings to fit the motor connected to the SEL-710 making sure to select NAMEPLATE for the APP
parameter. The other settings should be set to the values taken off the motor nameplate and to your preference.
The warning that scrolls across the top lets you know that the relay will only provide basic and default protection,
which is fine for beginning functionality. This setting will need to be changed to FULL at later date.
APPLICATION (FULL, NAMEPLATE)
APP
:=
PHASE ROTATION (ABC, ACB)
PHROT
:=
RATED FREQ. (50, 60 Hz)
FNOM
:=
DATE FORMAT (MDY, YMD, DMY)
DATE_F
:=
Step 4.
The second setting section is Group settings. Navigate to ENT > SET/SHOW > GROUP > 1. In this menu there
are five sections (ID Settings, Config Settings, Thermal Overload, Neutral Overcurrent, Residual Overcurrent) and
there are parameters in each section that must be set. These values can be set from the values taken off the motor
nameplate and control center.
Step 5.
The last setting section is Logic settings. The logic output 103 Fail Safe must be set to Y. The default factory
settings are set to Y so there are no changes that need to be made during this step.
9
Relay Settings
When APP = NAMEPLATE the following protection is provided by the SEL-710 based on the settings listed previously and hidden
settings (all other protections and warning functions are disabled):
➤ Thermal stator and rotor protection based on motor ratings
➤ Current unbalance protection (20% unbalance, 5 second delay)
➤ Instantaneous phase overcurrent trip level set based on IEEE C37.96 recommendation for phase overcurrent protection
➤ Ground overcurrent protection
➤ Phase overvoltage protection (1.1*VNOM, 0.5 second delay)
➤ Phase reversal protection
➤ Breaker failure protection
To reference all other applications and exact default settings when in this mode, please refer to Section 4 in the SEL-710 manual. The
nameplate application settings and the HMI menu structure are shown below.
Setting Name (Prompt)
Range
Main Menu
Meter
Events
Monitor
Targets
Control
Set/Show
Status
Quit
Global Settings
APP (APPLICATION)
FULL, NAMEPLATE
PHROT (PHASE ROTATION)
ABC, ACB
FNOM (RATED FREQ)
50, 60 Hz
DATE_F (DATE FORMAT)
MDY, YMD, DMY
Group Settings
RID (UNIT ID LINE 1)
16 characters
TID (UNIT ID LINE 2)
16 characters
CTR1 (PHASE CT RATIO)
1–5000
FLA1 (MOTOR FLA)
0.2–5000.0 A
CTRN (NEUTRAL CT RATIO)
1–2000
PTR (PHASE PT RATIO)
1.00–250.00
VNOM (LINE VOLTAGE)
100–30000 V
DELTA_Y (XFMR CONNECTION)
Delta, Wye
SINGLEV (SINGLE V INPUT)
Y, N
SF (SERVICE FACTOR)
1.01–1.50
LRA1 (MOTOR LRA)
LRTHOT1 (LOCKED ROTOR
Press to
return to the
previous list.
OFF, 0.01–25.00 A
50N1D (NEU OC TRIP DLAY)
0.00–5.00 sec
Set/Show Menu
Global
Group
Port
Active Group
Date
Time
Group 1 Menu
ID Settings
Config Settings
Thermal Overload
•
•
Trip/Close Logic
Motor Control
1.0–600.0 sec
50N1P (NEUT OC TRIP LVL)
Press to select an
underlined menu item.
Group Menu
GROUP
1
2
3
2.5–12.0 xFLA
TIME)a
Press to move
within the list.
Config Menu
CTR1
50G1P (RES OC TRIP LVL)
50G1D (RES OC TRIP DLAY)
OFF, 0.10–20.00 xFLA
100
FLA1
0.00–5.00 sec
250.0 A
•
•
•
SINGLEV
Logic Setting
OUT103FS (OUT103 FAIL-SAFE)
Y, N
N
a.
LRTHOT1 defines the time a motor can safely withstand
locked rotor starting when the motor is at operating temperature. The default setting is 10 seconds at 600 percent
overload (Class 10 protection). This setting is adequate for
typical motor starting.
FLA1 Setting
MOTOR FLA
FLA1 = 0250.0 A
10
Notes
11
*PLS00012*
© 2006–2015 Schweitzer Engineering Laboratories, Inc. All rights reserved.
Date Code 20150130
12
Download