For Additional Technical Assistance Call +1.509.332.1890 Express Installation Guide SEL-710 Motor Protection Relay Package Contents SEL-710 Blank Pushbutton LED Label Product Literature 7.36 (187.0) Contents: CD Installation: • Express Installation Guide • Instruction Manual • Configurable Label Instructions & Template • Option Cards Instruction Sheet • DeviceNet User’s Guide • DeviceNet Eleectronic Data Sheet (EDS) • ReadMe.txt • Adobe® Reader® 1. Insert the CD into the drive. 2. If Windows autorun is enabled, the Contents.html file will load automatically. 3. If Windows autorun is not enabled, access files via Windows Explorer. Blank Target LED Label Label Removal Tool 2350 NE Hopkins Court • Pullman, WA 99163 USA Tel: +1.509.332.1890 • Fax: +1.509.332.7990 www.selinc.com • info@selinc.com 5.47 (139.0) Panel Cutout Template LEFT © 2009 Schweitzer Engineering Laboratories, Inc. All rights reserved PM710-01-CD/UCD02076 UP 198-0424 UP RIGHT 198–0424 *UCD02076* 20090327 Product Literature CD No. 8-32 Mounting Screws & Gasket Configurable Label Kit Safety Information Dangers, Warnings, and Cautions See the product manual for additional safety information. The product documentation uses three kinds of hazard statements, defined as follows: DANGER WARNING Indicates an imminently hazardous situation that, if not avoided, will result in death or serious injury. CAUTION Indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation that, if not avoided, may result in minor or moderate injury or equipment damage. Safety Symbols The following symbols are often marked on SEL products. CAUTION ATTENTION Refer to accompanying documents. Se reporter à la documentation. Earth (ground) Terre Protective earth (ground) Terre de protection Direct current Courant continu Alternating current Courant alternatif Both direct and alternating current Courant continu et alternatif Instruction manual Manuel d’instructions Safety Marks The following statements apply to this device. General Safety Marks Motor Overload: Class 10, 20, and 30. Surcharge du Moteur: Classe 10, 20 et 30. For use in Pollution Degree 2 environment. Pour l'utilisation dans un environnement de Degré de Pollution 2. Ambient air temperature shall not exceed 50°C (122°F). La température ambiante de l'air ne doit pas dépasser 50°C (122°F). For use on a flat surface of a Type 12 enclosure. Pour l’utilisation sur une surface plane d'un boîtier de Type 12. Terminal Ratings Wire Material Use 75°C (167°F) copper conductors only. Valeurs nominales des bornes Matériau de fil Utiliser seulement conducteurs en cuivre 75°C (167°F). Couple de serrage Bornier : 0,9–1,4 Nm (8–12 livres-pouce) Fiche à compression : 0,5–1,0 Nm (4,4–8,8 livres-pouce) Vis à oreille de montage de la fiche à compression : 0,18–0,25 Nm (1,6–2,2 livres-pouce) Tightening Torque Terminal Block: 0.9–1.4 Nm (8–12 in-lb) Compression Plug: 0.5–1.0 Nm (4.4–8.8 in-lb) Compression Plug Mounting Ear Screw: 0.18–0.25 Nm (1.6–2.2 in-lb) 2 Safety Information Hazardous Locations Safety Marks WARNING – EXPLOSION HAZARD AVERTISSEMENT – DANGER D'EXPLOSION Open circuit before removing cover. Ouvrir le circuit avant de déposer le couvercle. WARNING – EXPLOSION HAZARD AVERTISSEMENT – DANGER D'EXPLOSION Substitution of components may impair suitability for Class I, Division 2. La substitution de composants peut détériorer la conformité à Classe I, Division 2. Operating Temperature Range: –40°C to +85°C (–40°F to +185°F). Plage de température de fonctionnement : –40°C à +85°C (–40°F à +185°F). Hazardous Locations Operating Temperature Range: –20°C to +40°C (–4°F to +104°F). Emplacements Plage de température de fonctionnement d’emplacements dangereux : –20°C à +40°C (–4°F à +104°F). 3 Typical Connections Stop 120/240 Vac 50/60 Hz Start CR CR A01 A02 GND +/H A03 A04 A05 A06 A07 A08 A09 A10 A11 A12 -/N OUT_01* OUT_02* OUT_03*(TRIP) IN_01 CONTROL INPUTS OUTPUT CONTACTS INPUT POWER IN_02 (Trip Fail-Safe Contactor Wiring Shown) Front 5 4 9 3 2 8 7 SEL-710 Motor Relay 1 6 Port 3 5 4 9 3 2 8 7 1 6 Optional Input Output Cards Optional Ethernet (single or dual) 1–12 RTDs + + — + — + — + — + — + — + 4 Digital Inputs / 4 Digital Outputs OR Winding Bearing Others + — 10 RTDs + — IRIG-B/PTC — IRIG-B Time Source — PTC Thermistor Copper Wire SEL-2600 External RTD Module (Optional) Multimode Fiber ≤ 1000 m RX Fiber-Optic Input TX Fiber-Optic Output FO Cable** TX— RX+ RX— SHIELD 4 Analog Inputs / 4 Analog Outputs (Optional) TX+ Port 4A EIA-485 V— CAN_L SHIELD CAN_H V+ Spare Input 8 Analog Inputs Port 4 DeviceNet (Optional) Ambient 3 Digital Inputs / 4 Digital Outputs / 1 Analog Output 8 Digital Inputs CURRENT INPUTS VOLTAGE INPUTS (Optional) * Factory Default Function ** SEL Fiber Optic Cables 240-1506 – 1 m (3.3 feet) ST/ST 240-1507 – 5 m (16.4 feet) ST/ST 240-1508 – 15 m (49.2 feet) ST/ST Other lengths available by request VA VB VC N E01 E02 E03 E04 * A diagram from a four-wire Wye connection also available in the instruction manual. Also, differential elements connections are shown in the manual. IA Z01 Z02 IB Z03 Z04 IC Z05 Z06 IN Z07 Z08 CR A B C MOTOR Open-Delta Potential and Residual Ground CT Connections 4 Rack Mounting You can mount the SEL-710 in a sheltered indoor environment (a building or an enclosed cabinet) that does not exceed the temperature rating of –40°C to +85°C. For mounting consideration the relay dimensions are shown below. 7.56 (192.0) 7.36 (187.0) 5.67 (144.0) 1.12 (28.5) 5.80 (147.4) 5.47 (139.0) New Control Center 1. Place the enclosed panel 2. Make smooth cut around cutout over desired mounting cutout. location and trace. 3. Place mounting gasket around relay and insert unit into hole. (The photo displays optional appearance bezel.) 4. Fasten relay to mounting plate with included screws. 3. Place mounting gasket around relay and insert unit into retrofitting plate. 4. Fasten relay to mounting plate with included screws. Retrofitting 1. Remove old relay. 2. Insert retrofitting plate and fasten (see www.selinc.com/ sel-710.htm for retrofits). 5 Connections Shown for SEL-710 with IRIG-B, Ethernet, EIA-232, Fiber Optic, Voltage Option, RTD option, and 4 DO/3 DI/1 AO option. Refer to the SEL-710 manual for additional details and other options. Wire sizes for connections are dictated by the terminal blocks and expected load currents. You may use the following table as a guide in selecting wire sizes: Connection Type Minimum Wire Size Maximum Wire Size 2 Grounding (Earthing) Connection 18 AWG (0.8 mm ) 14 AWG (2.1 mm2) Current Connection 16 AWG (1.3 mm2) 12 AWG (3.3 mm2) Potential (Voltage) Connection 18 AWG (0.8 mm2) 14 AWG (2.1 mm2) Contact I/O 18 AWG (0.8 mm2) 14 AWG (2.1 mm2) Other Connection 18 AWG (0.8 mm2) 14 AWG (2.1 mm2) Card Slot A: Power Supply Card With 2 DI/3 DO Step 1. Connect appropriate power supply to terminal 01 (+/H) and terminal 02 (-/N). Note that power terminals are isolated from chassis ground. Step 2. Connect ground terminal GND to a rack frame or switchgear ground for proper safety and performance. Step 3. Connect as many as 2 digital inputs per application requirements, to optoisolated inputs IN_01 (terminals 10 and 11), and IN_02 (terminals 11 and 12). Step 4. Connect the 3 output contacts per application requirements to OUT_01 (terminals 03 and 04), OUT_02 (terminals 05 and 06), and OUT_03 (terminals 07, 08, and 09). Card Slot B: Main Board With IRIG-B, Ethernet, EIA-232, Fiber Optic Step 1. Connect communications devices as required to front DB-9 serial Port F (EIA-232), rear DB-9 serial Port 3 (EIA-232), 10/100BASE-T Ethernet port (RJ45 connector) and fiber-optic (ST® connector) serial Port 2. Step 2. Connect IRIG-B time-code input to terminals 01 (+) and 02 (-). Card Slot C: 3 Digital Inputs, 4 Digital Outputs, 1 Analog Output Card (3 DI/4 DO/1 AO) Step 1. Connect additional digital inputs (IN_01, IN_02, IN_03) and outputs (OUT_01, OUT_02, OUT_03, OUT_04), if required by application, using the connection diagram. Step 2. Connect the analog (transducer) output AO_01 using terminals 09 and 10. 6 Connections Card Slot D: 10 RTD Inputs Card Connect as many as ten RTDs as required by application. Example: Connect RTD1 (+) to terminal 01, RTD1 (-) to terminal 02, RTD1 (common or return) and RTD1 (shield, if available) to terminal 03. v Card Slot E: Voltage Inputs Card Connect 4-wire wye-connected PTs or open-delta connected PTs as shown in the typical connections diagram. For other PT connection options refer to Section 2 of the SEL-710 manual. Card Slot Z: Current Inputs Card Connect phase current and neutral current inputs as shown in the typical connections diagram. Step 1. Connect Phase A, Phase B, and Phase C current inputs to terminals 01 and 02; terminals 03 and 04; and terminals 05 and 06, respectively, following the convention shown in the typical connections diagram. Step 2. Connect neutral current IN inputs to terminals 07 and 08. Refer to Section 2 of the SEL-710 manual for additional details and other connection options. 7 Communication With Relay There are two ways of communicating with the SEL-710 Motor Relay. You can communicate with the relay using the human-machine interface (HMI) on the front panel or through serial port communications with a computer. For communications, the computer must have a serial port and the operating system should be Windows® 2000 or newer. A standard EIA-232 crossover cable or an SEL-234A cable will also be required. HMI Pushbuttons Press the TARGET RESET pushbutton to clear targets that have been alarmed. Press the directional (up, down, left, right) pushbuttons to scroll through options. TARGET RESET ESC ENT Press the ENT pushbutton for selection to see next menu. Press the ESC pushbutton to return to previous menu. Computer Connection Steps Step 1. Connect the PC and the relay using a serial communications cable. Step 2. Apply power to both the PC and the relay. Step 3. Open a terminal emulation program. Option 1: ACSELERATOR QuickSet SEL-5030 Software Open ACSELERATOR QuickSet and proceed to Step 4. If you do not have ACSELERATOR QuickSet, you can download the program from www.selinc.com/sel-5030.htm. Refer to Section 3 of the SEL-710 manual for more information about ACSELERATOR QuickSet. Option 2: HyperTerminal To open HyperTerminal go to Start > Programs > Accessories > Communications > HyperTerminal. Once there you will be prompted to enter a name of your choice for the connection. Then you will choose which port to connect through. Make sure you select the same port that you connected the cable to, then click OK. Step 4. Set the PC terminal emulation program to the same communications port settings as shown in the figure to the right and click OK. Step 5. Press the <Enter> key on the PC keyboard to check the communications link. You should see the = prompt. If you do not see the = prompt, check the cable connections, confirm that the settings in the terminal emulation program are the default values, and that the emulation mode is set to VT100. Step 6. Once connected, you can set all other relay settings and obtain values as needed. Refer to Section 6 in the SEL-710 manual for more information. SEL-710 Relays are shipped with default passwords. To prevent unauthorized access, change default passwords to private passwords at installation. SEL shall not be responsible for damage resulting from unauthorized access. 8 Relay Settings This section of the Express Installation Guide provides a step-by-step process to set the SEL-710 for basic protection purposes. For more in-depth relay setting procedures, please refer to the SEL-710 manual or contact your local SEL representative. To get more directions on relay setting using PC configuration, please refer to Section 3 of the SEL-710 manual. Step 1. Locate the values listed below. Some of the values needed are located on the control center nameplate while others can be found directly on the motor nameplate. Find the Values: CT Ratio (CTR1) = Full Load Amps (FLA1) = Service Factor (SF) = CT Ratio to Ground (CTRN) = Phase PT Ratio (PTR) = Line Voltage (VNOM) = Delta/Wye Connection (DELTA_Y) = Single V Input (SINGLEV) = Step 2. Enter Access Level 2. Whenever prompted for a password, enter the corresponding password. To change the character, use the arrow keys and press the ENT pushbutton to select the character. Once the full password has been entered, scroll to Accept and press the ENT pushbutton. Valid Password Characters Step 3. Factory Default Passwords for Access Levels 1 and 2 Alpha ABCDEFGHIJKLMNOPQRSTUVWXYZ abcdefghijklmnopqrstuvwxyz Numeric 0123456789 Special !"#$%&'()*+,-./:;<=>?@[\]^_`{|}~ Access Level Factory Default Password 1 OTTER 2 TAIL There are three settings sections that need to be set in order to provide basic protection. Navigate to ENT > SET/SHOW > GLOBAL > General Settings. Once in this menu the following parameters can be set. Complete these settings to fit the motor connected to the SEL-710 making sure to select NAMEPLATE for the APP parameter. The other settings should be set to the values taken off the motor nameplate and to your preference. The warning that scrolls across the top lets you know that the relay will only provide basic and default protection, which is fine for beginning functionality. This setting will need to be changed to FULL at later date. APPLICATION (FULL, NAMEPLATE) APP := PHASE ROTATION (ABC, ACB) PHROT := RATED FREQ. (50, 60 Hz) FNOM := DATE FORMAT (MDY, YMD, DMY) DATE_F := Step 4. The second setting section is Group settings. Navigate to ENT > SET/SHOW > GROUP > 1. In this menu there are five sections (ID Settings, Config Settings, Thermal Overload, Neutral Overcurrent, Residual Overcurrent) and there are parameters in each section that must be set. These values can be set from the values taken off the motor nameplate and control center. Step 5. The last setting section is Logic settings. The logic output 103 Fail Safe must be set to Y. The default factory settings are set to Y so there are no changes that need to be made during this step. 9 Relay Settings When APP = NAMEPLATE the following protection is provided by the SEL-710 based on the settings listed previously and hidden settings (all other protections and warning functions are disabled): ➤ Thermal stator and rotor protection based on motor ratings ➤ Current unbalance protection (20% unbalance, 5 second delay) ➤ Instantaneous phase overcurrent trip level set based on IEEE C37.96 recommendation for phase overcurrent protection ➤ Ground overcurrent protection ➤ Phase overvoltage protection (1.1*VNOM, 0.5 second delay) ➤ Phase reversal protection ➤ Breaker failure protection To reference all other applications and exact default settings when in this mode, please refer to Section 4 in the SEL-710 manual. The nameplate application settings and the HMI menu structure are shown below. Setting Name (Prompt) Range Main Menu Meter Events Monitor Targets Control Set/Show Status Quit Global Settings APP (APPLICATION) FULL, NAMEPLATE PHROT (PHASE ROTATION) ABC, ACB FNOM (RATED FREQ) 50, 60 Hz DATE_F (DATE FORMAT) MDY, YMD, DMY Group Settings RID (UNIT ID LINE 1) 16 characters TID (UNIT ID LINE 2) 16 characters CTR1 (PHASE CT RATIO) 1–5000 FLA1 (MOTOR FLA) 0.2–5000.0 A CTRN (NEUTRAL CT RATIO) 1–2000 PTR (PHASE PT RATIO) 1.00–250.00 VNOM (LINE VOLTAGE) 100–30000 V DELTA_Y (XFMR CONNECTION) Delta, Wye SINGLEV (SINGLE V INPUT) Y, N SF (SERVICE FACTOR) 1.01–1.50 LRA1 (MOTOR LRA) LRTHOT1 (LOCKED ROTOR Press to return to the previous list. OFF, 0.01–25.00 A 50N1D (NEU OC TRIP DLAY) 0.00–5.00 sec Set/Show Menu Global Group Port Active Group Date Time Group 1 Menu ID Settings Config Settings Thermal Overload • • Trip/Close Logic Motor Control 1.0–600.0 sec 50N1P (NEUT OC TRIP LVL) Press to select an underlined menu item. Group Menu GROUP 1 2 3 2.5–12.0 xFLA TIME)a Press to move within the list. Config Menu CTR1 50G1P (RES OC TRIP LVL) 50G1D (RES OC TRIP DLAY) OFF, 0.10–20.00 xFLA 100 FLA1 0.00–5.00 sec 250.0 A • • • SINGLEV Logic Setting OUT103FS (OUT103 FAIL-SAFE) Y, N N a. LRTHOT1 defines the time a motor can safely withstand locked rotor starting when the motor is at operating temperature. The default setting is 10 seconds at 600 percent overload (Class 10 protection). This setting is adequate for typical motor starting. FLA1 Setting MOTOR FLA FLA1 = 0250.0 A 10 Notes 11 *PLS00012* © 2006–2015 Schweitzer Engineering Laboratories, Inc. All rights reserved. Date Code 20150130 12