0 1 2 3 4 5 6 7 8 9 Daikin Europe N.V. Project Description : WIRING DIAGRAM ∙ Unit name : EWAQ 130-260 EWYQ 130-250 OPIF ∙ Wiring diagram number : 4TW57596-2 ∙ Revision :B ∙ Number of pages : 30 Daikin Europe N.V. Description Unit name Front Page EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number B 1 0 1 2 3 4 5 6 7 8 9 Page overview Page Page Description Page Revision 1 Front Page B 2 Page Overview B 3 Notes A 4 Legend A 5 PCB interconnection diagram - 6 PCB I/O overview + fuses A 7 PCB changeable I/O overview A 8 Unit outlook A 9 Switchbox outlook A 15 Main power supply A 16 Trafo + PCB power supply B 20 Circuit 1: compressor & fan A 21 Circuit 1: compressor & fan (2) A 22 Circuit 1: control compressors A 23 Circuit 1: control fans A 24 Circuit 1: control fans (2) - 25 Circuit 2: compressor & fan A 26 Circuit 2: compressor & fan (2) A 27 Circuit 2: control compressors A 28 Circuit 2: control fans A 29 Circuit 2: control fans (2) A 30 Control circuit (DI 230V) A 31 Control circuit and EEV - 32 Circuit 1: sensors A 33 Circuit 2: sensors A 40 Fieldwiring DI, changeable DI A 41 Fieldwiring changeable AI/AO - 42 Fieldwiring DO,changeable DO - 43 Fieldwiring DO,changeable DO A Daikin Europe N.V. Description Unit name Page Overview EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number B 2 0 1 2 3 4 5 6 7 8 9 Notes to go through before starting the unit : L1,L2,L3 1-99 100-199 200U-Z 15 15 : : : : : Main terminals Fieldwiring terminals Factory upwiring terminals Internal wiring terminals Main terminals in compressor switchbox : : : : Earth wiring Wire number 15 Terminal number 15 Field supply : Option Factory installed: : Wiring depending on model User installed: : PCB ! N-model = Low noise (OPIF+Compressorhousing) OPTP OPSC OPTC OPIF = Twinpump = Single pump contactor = Twin pump contactor = Inverter fans for low ambient (-15 °C) = Hi ESP Pump = Single pump = Buffertank EKACPG = Address card including: - RS485 (Integrated modbus) - F1,F2 (DICN + DBACS Connection) EKRUPG = Remote user interface 1..14: 15..19: 20..29: 30..39: 40..49: : Several wiring possibilities General Power supply Main circuits Control circuits Fieldwiring Definitions: : unit with no options included. DI: DO: AI: AO: Ch: Y1R, Y2R reversing valves are activated in cooling mode. Daikin Europe N.V. OPLN Page numbers: : Connection ** continues on page 12 column 2 : Pin against miswiring (example: X10Z 1!) 1 = Heater tape = A - Meter, V - Meter OPHP OPSP OPBT : Not mounted in switchbox **/12.2 OP10 OP57 Digital input Digital output Analog input Analog output Changeable (function can be selected by the customer) Description Unit name Notes EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 3 0 1 2 3 4 5 6 7 8 9 Translation of this legend can be found in the manual. Daikin Europe N.V. Description Unit name Legend EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 4 0 1 2 3 4 6 7 8 9 EKRUPG 1 1 A4P HAP A4P HAP SUB SUB S1A S1A S1A HBP ON X1M OFF + RS485 DC 24V GND TERM S2A HBP MAIN TERM S2A ON ADDRESS=MAIN TERM=ON X1M OFF MAIN + RS485 DC 24V GND HBP MAIN A5P HAP SUB TERM S2A ON OFF X1M + RS485 DC 24V GND Std 5 ADDRESS=SUB TERM=ON ADDRESS=MAIN TERM=OFF 3 V1C ON ON A11P TERM S2A OFF X53A X52A X51A ACS EKACPG X88A ACS F1 HCP F2 + RS485 - DICN MODBUS 2 V2C X1M HEP A01P OFF ON ADDRESS=1 OFF X53A X52A X89A A71P * ON DS1 only for EWYQ TERM S3A OFF HDP ON For S3A setting see installation manual EKACPG HAP X88A ACS OFF HAP ADDRESS=2 X89A A72P H1P H2P HAP HBP * X88A ACS OFF HAP S1A ADDRESS=1 H1P H2P HAP HBP only for EWYQ 230-250 ON ON OFF A21P TERM S2A HAP A02P DS1 ADDRESS=3 ON X89A OFF A73P * S1A ADDRESS=2 shortcut on last * = EEV PCB (319) = DIPSWITCH Daikin Europe N.V. Description Unit name PCB interconnection diagram EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number - 5 0 1 Daikin Europe N.V. 2 3 4 5 6 7 Description Unit name PCB I/O overview + fuses EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 8 9 Page Drawing number A 6 0 1 Daikin Europe N.V. 2 3 4 5 6 7 Description Unit name PCB changeable I/O overview EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 8 9 Page Drawing number A 7 0 1 2 3 4 5 6 7 8 9 TOP VIEW OF UNIT (FANS) M13F M14F M14F M13F M15F M13F M14F M15F M16F M23F M24F M24F M23F M25F M23F M24F M25F M26F MxxF : Inverter controlled fan TOP VIEW OF UNIT (COMP+ SB) M22C M12C M21C M22C M11C M12C M21C M22C SWITCHBOX M21C M11C SWITCHBOX M12C SWITCHBOX M11C EWAQ 130-150 EWAQ 180-210 EWAQ 240-260 EWYQ 130-150 EWYQ 180-210 EWYQ 230-250 Daikin Europe N.V. Description Unit name Unit outlook EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 8 4 5 6 A13P A11P X11Y X18Y K2A K23..26S A S1M V1C E1HS <0 K3A F8B F9B F6B T1A T1V S1T TR1 K11M/F11B A4P A71P K12M/F12B X19Y L=300 K21M/F21B K1A A01P 9 TR1A K22M/F22B A72P A23P 8 X26Y/X27Y K13..16S A73P K13..16F K23..26F A21P 7 K2P/F17B 3 K1P/F16B 2 F15B F14B 1 F25B F24B 0 Earth supply M1F A (1:4) X12..X23Y X14..24Y X17Y X10Y X15..25Y X16Y Daikin Europe N.V. Description Unit name Switchbox outlook EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 9 0 1 2 L1C1 / 20.0 L2C1 / 20.0 L3C1 / 20.0 L2C1./ 16.0 L3C1./ 16.0 3 4 5 6 OPTC 7 2 X26Y X26Y X26Y 1 2 3 3 5 14 I I 1 11 F16B L1C2./ 25.0 L2C2./ 25.0 L3C2./ 25.0 4 6 1 3 5 5 OP10 11 14 I 2 3 F17B I K1P I I 2 4 6 1 3 5 2 4 6 12 MODELS WITHOUT OPSP/OPTP/OPHP K2P 2 23.8 4 6 43.3 TR1A 502 12 T1A X10Y 0 OP57 11 T1A 23 R1 22.9 / 32.4 U 300A/5A V W U M M1P OPSP/OPTP/OPHP 3˜ PE / 32.4 R2 W M M2P 3˜ V 0 PE OPTP E3H 2 OPSP/OPHP 1 2 3 4 3 5 F16B 6 I F2 F3 M1P 11 L3 1 2 I I 2 4 6 2 4 6 OPBT 24 2 4 1 3 5 1 3 5 1 3 2 4 6 2 4 6 1 6 7 4 3 10 U V W U V W S2M K2P M 12 X17Y F4 F5 M M2P 3˜ 9 3˜ X17Y 9 PE PE PE Power supply 1˜50Hz 230V Power supply 3˜50Hz 400V Daikin Europe N.V. OPSP/OPTP /OPHP 14 I PE L2 5 5 X17Y L1 3 F17B I K1P F1 1 11 14 I S1M 1 3 E6H 2 1 X10Y 1 E4H max. 1kW 2 X26Y X26Y X26Y 12 Q1T K3A E5H 2 9 OPSC 1 501 8 Description Unit name Main power supply EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 15 0 1 2 3 4 5 6 7 8 9 15.2 /L2C1. 15.2 /L3C1. 1 3 5 I I 2 4 OP57 6 E1 62 60 61 12 T1V / 32.6 11 T1V X77A:3 I X77A:1 A73P F6B / 32.6 400 VAC 1 5 TR1 31 32 33 only for EWYQ 230-250 34 63 230 VAC X11Y 3 X11Y 3 X11Y 3 64 X11Y 1 X11Y 1 X11Y 1 65 X11Y 2 X11Y 2 X11Y 2 F9B I A11P A21P X1A:1 F1U 5A 5A SN A11P SL A11P F1U SN A21P SL A21P F1U / 30.0 X2A:1 X3A / 30.5 X77A:1 E1 M M1F 1˜ A72P 253 152 151 203 102 M 2 A71P 101 t° S1T E1HS X18Y E1 / 30.5 X2A:2 1 X77A:3 X18Y 2 / 30.0 X2A:2 I F8B 66 F1U X2A:1 X3A X1A:3 X77A:1 X1A:1 X77A:3 X1A:3 1 only for EWYQ SN A11P X2A SL A11P X2A 22.0 22.0 SL A11P 22.0 230 VAC Daikin Europe N.V. SN A21P X2A SL A21P X2A 27.0 27.0 SL A21P 27.0 230 VAC Description Unit name Trafo + PCB power supply EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number B 16 0 1 2 3 4 5 6 7 8 9 EWAQ 130-150/180-210 EWYQ 130-150/180-210 15.2 / L1C1 15.2 / L2C1 15.2 / L3C1 3 1 3 5 1 F14B I 2 F11B I 30.3 14 I I 2 4 1 11 3 5 F12B 4 I 6 11 I I I 2 4 6 K13F 4 6 1 3 5 2 4 6 2 4 6 2 K14F 4 6 K15F 1 3 5 1 K14S 3 M12C Q11C V W M 3~ 5 W 2 4 6 1 3 5 M14F 95 K15S 4 6 7 8 9 U1 V1 W2 U2 K13S 96 2 4 6 13 14 15 W1 U1 V1 V2 W2 U2 M X14Y M15F 3˜ X14Y 4 6 W1 U1 V1 W1 V2 W2 U2 V2 X14Y 4 M M13F PE X14Y 10 96 2 3˜ PE PE 96 23.2 2 Q12C PE V 95 23.3 X14Y U U K13F 95 W 10 328 R1P M 3~ L3 11 8 X12A X12A X12A :1 :3 :5 L1 L2 L3 M11C L2 14 A11P V L1 A13P K12M U L3 31.2 2 K11M L2 325 5 5 6 L1 V1F 13 3 I 4 14 6 1 I 2 23.1 5 I 30.3 3 5 F15B I 1 3 M 3˜ PE 16 Only for EWAQ 180-210 EWYQ 180-210 Daikin Europe N.V. Description Unit name Circuit 1: compressor & fan EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 20 0 1 2 3 4 5 6 7 8 9 EWAQ 240-260 EWYQ 230-250 3 1 3 5 1 F14B 3 5 F15B I I 2 I 4 I 6 325 5 13 I I 2 4 6 L1 L2 L3 10 A13P 11 31.2 K13F 326 14 8 U V W 2 4 6 13 K15F 14 328 2 4 6 2 K14F 4 6 K16F 1 3 5 K13F 1 3 5 1 3 K15F 5 2 4 6 1 3 5 95 7 8 9 U1 V1 W2 U2 K16S K13S 2 4 6 19 20 21 W1 U1 V1 V2 W2 U2 96 X14Y M14F M X14Y M16F 3˜ 4 6 W1 U1 V1 V2 W2 U2 M 10 Daikin Europe N.V. X14Y PE X14Y K15S 96 2 4 6 W1 U1 V1 W1 V2 W2 U2 V2 4 M13F 3˜ PE X14Y 96 2 96 24.1 6 24.1 4 24.3 2 24.3 K14S 95 95 95 M M15F 3˜ PE M 3˜ PE 22 Description Unit name Circuit 1: compressor & fan (2) EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 21 0 16.1 / 16.2 / 1 SL A11P X2A 2 3 4 5 6 7 8 102 SL A11P X2A 102 102 SL A11P 9 102 203 SL A11P 203 11 / 23.0 / 23.0 K1A 14 30.4 204 A11P A11P X14A:2 X17A:2 X15A:7 21 K1R K2R K11M K5R 21 22 22 X10Y X10Y 3 107 106 X15A:4 105 X17A:1 212 X14A:1 211 X13A:3 K3R K12M X10Y 6 213 X13A:1 X12Y 7 X13Y 6 Q11C Q12C L1 A1 A1 K11M K12M A2 Y1R PE E11HC E12HC 1 L1 A1 PE K3A A2 A2 N N Only for EWYQ 16.1 / X10Y SN A11P X2A X10Y 4 8 X10Y 9 X12Y 2 X13Y 101 2 4 6 14 22 20.0 20.1 20.1 42.0 .5 SN A11P X2A 101 101 1 3 5 13 21 6 1 3 5 13 21 Daikin Europe N.V. 2 4 6 14 22 101 Only for EWAQ 150/180-210/240-260 EWYQ 150/180-210/230-250 20.2 20.2 20.2 42.1 .6 Description Unit name Circuit 1: control compressors EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 R1 / 23.0 R2 15.7 Page Drawing number A 22 0 22.9 / 22.9 / 1 2 SL A11P X2A 3 4 5 6 7 8 102 SL A11P 9 102 203 / SL A11P 203 EWAQ 130-150/180-210 EWYQ 130-150/180-210 / 43.2 203 110 4 X27Y 110 115 2 120 11 95 95 K13S K15S 96 95 14 K14S 96 20.6 112 20.9 F16B 96 20.5 X27Y 116 / Only for EWAQ 180-210 A01P 4 12 EWYQ 180-210 111 X72A:3 121 12 AO X72A:4 A11P K2*S A11P / 24.2 K3*S A11P / 24.3 K4R / 24.4 323 A11P X19A:1 K8R X16A:1 X20A:2 13 K9R 13 K7R X19A:5 324 K1*S A11P 121 116 111 X16A:3 A13P X19A:3 X19A:7 X20A:1 (0V) 2 (AIN+) 3 (AIN-) 4 X27Y 3 A1 A1 K13F K15F 22.9 / A2 A1 K14F A2 SN A11P X2A 222 221 220 A1 K1P A2 A2 OPSP/OPTP/OPSC/ OPTC/OPHP Only for EWAQ 180-210 101 X27Y 1 101 SN A11P X2A 101 EWYQ 180-210 2 4 6 13 1 3 5 14 20.8 20.8 20.8 20.7 Daikin Europe N.V. 2 4 6 1 20.6 3 20.6 5 20.6 2 4 6 1 20.5 3 20.5 5 20.5 1 3 5 13 Description Unit name Circuit 1: control fans EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 2 4 6 14 / 43.3 15.3 15.3 15.4 40.1 Page Drawing number A 23 0 1 2 3 4 5 6 7 8 9 EWAQ 240-260 EWYQ 230-250 203 4 110 115 120 95 95 K13S K14S 96 96 21.1 122 116 112 21.4 95 95 K15S K16S 96 111 96 121 A11P K2*S A11P / 23.1 X19A:1 K3*S A11P / 23.2 X19A:5 K7R X20A:2 K8R K9R A1 222 X20A:1 220 X19A:7 220 X19A:3 A1 K13F A1 K15F A2 / 23.3 222 K1*S A11P 121 116 21.2 111 21.6 K14F A1 K16F A2 A2 A2 101 2 4 6 13 Daikin Europe N.V. 1 3 5 14 21.3 21.4 21.4 21.3 2 4 6 13 1 3 5 14 21.5 21.5 21.5 21.3 2 4 6 1 21.1 3 21.1 5 21.1 2 4 6 1 21.2 3 21.2 5 21.2 Description Unit name Circuit 1: control fans (2) EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number - 24 0 1 2 3 4 5 6 7 8 9 EWAQ 130-150/180-210 EWYQ 130-150/180-210 15.2 /L1C2. 15.2 /L2C2. 15.2 /L3C2. 5 1 3 5 1 F24B 3 5 F21B I 30.8 14 I I 2 4 1 11 3 5 F22B I 2 11 I 4 I 6 14 I 6 I I 2 4 5 F25B I I I 2 4 6 L1 L2 L3 L1 L2 L3 V2F 30.8 1 3 6 375 5 3 5 2 4 6 K21M 1 3 5 2 4 6 13 K22M 10 A23P 11 K23F 31.9 1 14 8 A21P U V W 2 4 6 1 3 5 378 X12A X12A X12A :1 :3 :5 L1 L2 L3 R2P 2 4 6 2 K24F 4 6 K25F 1 3 5 K23F 1 3 5 95 95 K25S 6 7 8 9 U1 V1 W2 U2 96 K23S 2 4 6 X24Y U M21C V W M 3~ U M22C Q21C V W M 3~ M24F 13 14 15 W1 U1 V1 V2 W2 U2 M Q22C PE X24Y M25F 3˜ X24Y 96 2 4 6 W1 U1 V1 W1 V2 W2 U2 V2 X24Y 3 M M23F 3˜ PE PE 96 28.2 4 28.3 2 28.1 K24S 95 PE X24Y 10 M 3˜ PE 16 Only for EWAQ 180-210 EWYQ 180-210 Daikin Europe N.V. Description Unit name Circuit 2: compressor & fan EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 25 0 1 2 3 4 5 6 7 8 9 EWAQ 240-260 EWYQ 230-250 5 1 3 5 1 F24B 3 5 F25B I I 2 I 4 I 375 6 5 13 I I 2 4 6 L1 L2 L3 10 A23P 31.9 K23F 14 U V W 2 4 6 376 8 11 13 K25F 14 378 6 2 4 6 K26F 1 3 5 K23F 1 3 5 1 95 X24Y M24F 4 6 7 8 9 U1 V1 W2 U2 96 K26S 2 4 6 19 20 21 W1 U1 V1 V2 W2 U2 29.4 2 M X24Y M26F 3˜ 5 10 Daikin Europe N.V. K23S 4 6 W1 U1 V1 V2 W2 U2 M 1 3 5 K25S 96 2 4 6 W1 U1 V1 W1 V2 W2 U2 V2 3 M23F PE X24Y 6 95 96 2 X24Y 4 95 96 3˜ PE X24Y 3 95 29.4 K24S 2 K25F 29.1 4 29.1 2 K24F M M25F 3˜ PE M 3˜ PE 22 Description Unit name Circuit 2: compressor & fan (2) EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 26 0 16.4 / 16.5 / 1 SL A21P X2A 2 3 4 5 6 7 8 152 SL A21P X2A 152 152 SL A21P 9 152 253 SL A21P 253 11 / 28.0 / 28.0 K2A 14 30.8 254 A21P X13A:1 X14A:2 X17A:2 21 K1R K2R K21M K5R 21 K22M 22 X10Y X10Y 15 157 156 155 X17A:1 262 X14A:1 261 X13A:3 22 17 X10Y X22Y 18 Q21C A1 A1 K21M K22M A2 Y2R E21HC PE E22HC X23Y 1 1 Q22C L1 L1 N N PE A2 Only for EWYQ 16.4 / X10Y SN A21P X2A X10Y 16 19 X10Y 20 X22Y 2 X23Y 151 2 4 6 14 22 25.0 25.1 25.1 42.2 .5 SN A21P X2A 151 151 1 3 5 13 21 2 1 3 5 13 21 Daikin Europe N.V. 2 4 6 14 22 151 Only for EWAQ 150/180-210/240-260 EWYQ 150/180-210/230-250 25.2 25.2 25.2 42.3 .6 Description Unit name Circuit 2: control compressors EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 / 28.0 Page Drawing number A 27 0 27.9 / 27.9 / 1 2 SL A21P X2A 3 4 5 6 7 152 SL A21P 8 9 152 253 / 253 / EWAQ 130-150/180-210 EWYQ 130-150/180-210 253 6 160 165 95 95 K23S K25S 96 95 K24S 96 25.6 96 25.5 166 162 25.9 170 Only for EWAQ 180-210 EWYQ 180-210 A01P 161 171 AO K1*S A21P X74A:5 171 166 161 X74A:4 K2*S A21P / 29.2 K3*S A21P / 29.3 / 29.4 A21P X20A:2 K7R K8R 374 X19A:5 373 X19A:1 K9R X19A:3 X19A:7 X20A:1 A23P A1 A1 K23F K25F SN A21P X2A A1 A2 A2 Only for EWAQ 180-210 151 (AIN-) 4 K24F A2 27.9 / (AIN+) 3 272 271 270 (0V) 2 151 / EWYQ 180-210 2 4 6 13 1 3 5 14 25.8 25.8 25.8 25.7 Daikin Europe N.V. 2 4 6 1 25.6 3 25.6 5 25.6 2 4 6 1 25.4 3 25.5 5 25.5 Description Unit name Circuit 2: control fans EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 28 0 1 2 3 4 5 6 7 8 9 EWAQ 180-210 EWYQ 180-210 253 6 160 165 170 95 95 K24S K23S 96 96 26.1 172 166 162 26.4 95 95 K26S K25S 96 161 96 171 K1*S A21P 171 166 26.2 161 26.6 K2*S A21P / 28.1 K3*S A21P / 28.2 / 28.3 A21P X19A:1 X19A:5 K8R K9R A1 272 X20A:1 270 X19A:7 270 X19A:3 A1 K23F A1 K25F A2 272 K7R X20A:2 K24F A1 K26F A2 A2 A2 151 2 4 6 13 Daikin Europe N.V. 1 3 5 14 26.3 26.4 26.4 26.3 2 4 6 13 1 3 5 14 26.5 26.5 26.6 26.3 2 4 6 1 26.1 3 26.1 5 26.1 2 4 6 1 26.2 3 26.2 5 26.2 Description Unit name Circuit 2: control fans (2) EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 29 16.1 / 2 3 4 5 A21P SL A11P F1U 230 X4A:1 16.5 / X10Y 10 6 SL A21P F1U 7 8 280 X4A:1 X10Y S1PH P> 11 X4A:3 231 14 X5A:2 F11B 5 DI X12Y 281 14 X5A:2 F21B 3 14/M2 25.1 6 11/M1 4 X22Y X22Y 282 DI 283 X6A:3 F22B 25.2 238 X13Y 5' 3 X13Y 6 6 6' 3 14/M2 X23Y 234 DI X13Y 4 284 X6A:1 DI 235 4 14 For EWAQ 130 EWYQ 130 X7A:2 K1*S A11P / DI X8A:1 11 6' 3 X8A:3 K2*S A11P / DI X9A:1 X9A:3 K3*S A11P / DI X10A:3 X23Y X23Y 6 285 161 K1*S A21P / 166 K2*S A21P / 171 K3*S A21P / X7A:2 X8A:3 X9A:3 X10A:3 A1 K1A K2A A2 X10A:1 DI X11:1 SN A11P A2 X10A:1 X11:1 236 X11A:2 16.5 / 11 14 22.1 CIRCUIT 1 Daikin Europe N.V. 11/M1 6 X6A:1 A1 16.1 / 3 14/M2 X9A:1 121 DI X23Y X8A:1 116 DI For EWAQ 150/ 180-210/240-260 EWYQ 150/ 180-210/230-250 X7A:1 111 DI 11/M1 4 Q22C 11/M1 4 X7A:1 DI 6 14/M2 Q21C Q12C X13Y X22Y X5A:1 11 20.2 11 X22Y For EWAQ 150/ 180-210/240-260 EWYQ 150/ 14 For EWAQ 130 180-210/230-250 EWYQ 130 F12B 22 X4A:3 4 233 5' X12Y X12Y X5A:1 X6A:3 DI Q11C 3 X12Y 232 5 11 20.1 X10Y 289 237 DI 21 S2PH P> X10Y 239 9 287 A11P 1 288 0 SN A21P 286 X11A:2 11 14 27.1 CIRCUIT 2 Description Unit name Control circuit (DI 230V) EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 30 0 1 2 3 4 5 6 7 8 9 A11P A13P 20.9 3 X2B:1 X2B:3 3 X1M:24V 4 312 X1M:- X53A:2 311 X1M:+ X53A:1 304 2 X52A:4 304 X52A:3 303 1 A4P X1B:1 X1B:2 X1B:3 X1B:4 X1B:5 S1L 10 X52A:2 RS485 303 BLK WHT X19Y A13P A01P V1C X52A:1 302 X2B:3 302 X2B:1 BLU 6 BLU 5 BLU X16Y BLU 3 X1B:1 X1B:2 X1B:3 X1B:4 X1B:5 301 X30A:2 301 X30A:1 WHT X27A:2 246 X18Y X27A:1 RS485 244 X29A:3 DI 247 X29A:4 249 X51A:2 248 X51A:1 DI 245 DI X1M:GND RS485 11 ALARM A21P X53A:2 RS485 314 313 X53A:1 DI 11 12 X25Y 9 4 10 A23P 5 498 3 497 496 X87A:1 2 495 493 492 10 5 11 12 10 BLK 9 4 A23P 25.9 Y11E Y21E M Y22E Y12E M M only for EWYQ Daikin Europe N.V. Y13E M only for EWYQ 230-250 11 ALARM Y23E M X27A:2 X89A:2 GRN X15Y 491 490 8 3 WHT 7 X86A:1 2 X89A:1 RED 6 488 487 486 5 5 X88A:2 BLK X25Y 4 X88A:1 GRN 8 3 BLK 7 X87A:1 2 485 483 482 6 5 X89A:2 GRN 5 4 WHT X15Y 3 X89A:1 RED 4 481 480 X86A:1 2 BLK 3 X88A:2 GRN 36 5 478 477 4 X88A:1 RED 1 3 GRN X25Y 476 475 4 X89A:2 X87A:1 2 WHT 3 BLK 2 5 473 4 472 471 36 3 GRN RED X15Y WHT 470 X86A:1 2 X89A:1 BLK X88A:2 RED X88A:1 X27A:1 A73P WHT A72P WHT A71P 317 318 296 315 316 RED * * 319 297 * M *= shortcut on last EEV PCB (319) Description Unit name Control circuit and EEV EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number - 31 0 1 2 3 4 5 6 7 8 A11P A01P 7 8 1 2 3 4 X15Y 19 20 29 30 X15Y 25 26 27 28 X15Y 21 22 23 24 X15Y X67A:1 31 32 33 R1T R2T R3T R14T R17T R16T R26T R15T R25T R18T R28T -t° -t° -t° -t° -t° -t° -t° -t° -t° -t° -t° Only for EWYQ Only for EWYQ 230-250 Only for EWYQ X67A:2 421 X66A:2 420 X66A:1 AI 419 X41A:2 418 X41A:1 AI 417 X40A:2 416 X40A:1 415 X39A:2 AI 414 X39A:1 413 X38A:2 AI 412 X38A:1 AI 411 X37A:2 410 X37A:1 AI 409 X36A:2 407 X36A:1 AI 406 X35A:2 405 X35A:1 403 X34A:2 AI 408 AI 402 X34A:1 401 X33A:3 400 X33A:1 AI 404 AI X16Y 9 34 Only for EWYQ 230-250 A11P 31 11 32 31 11 11 T1A / 15.1 X45A:4 32 12 16.3 / 11 T1V 61 T1V 0-500V/0-20mA 502 12 T1A X45A:3 514 X45A:2 513 X45A:1 T1A 0-5A/0-20mA 15.1 / Daikin Europe N.V. X44A:4 12 B1PL 501 B1PH X44A:3 504 OP57 18 X44A:2 AI 60 17 503 X44A:1 455 454 16 X43A:4 RED X15Y 15 AI X43A:3 WHT 14 X43A:2 453 X43A:1 RED 13 X42A:4 452 X42A:3 BLK WHT X15Y X42A:2 451 450 X42A:1 AI BLK AI 12 T1V / 16.3 Description Unit name Circuit 1: sensors EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 32 0 1 2 3 4 5 6 7 8 9 A21P X25Y 31 X25Y 32 33 34 X25Y 19 X25Y 20 29 30 X25Y 25 26 X25Y 27 28 X25Y X40A:2 X41A:1 21 22 X25Y R38T R48T R34T R37T R36T R46T R35T R45T -t° -t° -t° -t° -t° -t° -t° -t° Only for EWYQ Only for EWYQ 230-250 Only for EWYQ X41A:2 437 X40A:1 436 X39A:2 AI 435 X39A:1 AI 433 X38A:2 432 X38A:1 431 X37A:2 AI 434 AI 429 X37A:1 428 X36A:2 427 425 X36A:1 AI 430 AI X35A:2 424 X35A:1 423 X34A:2 422 X34A:1 AI 426 AI 23 24 only for EWYQ 230-250 A21P 16 461 X43A:4 17 18 RED WHT RED X43A:3 460 459 X43A:2 X25Y 15 B2PH Daikin Europe N.V. X43A:1 458 X42A:4 14 BLK 13 WHT X25Y X42A:3 457 X42A:2 456 X42A:1 AI BLK AI B2PL Description Unit name Circuit 2: sensors EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 33 0 1 2 3 4 5 6 7 8 9 A01P 46 47 Changeable DI3 48 49 X65A:2 X65A:3 50 52 X65A:1 Changeable DI4 51 X32A:1 49 X32A:2 48 X32A:3 47 46 X32A:4 45 X31A:3 44 X31A:1 Changeable DI2 50 Changeable DI1 DI 51 X65A:4 53 A11P 52 53 7 X27Y 44 7 X27Y 8 45 13 13 S1S S2S 14 13 S3S 14 13 S4S 14 14 13 K1P 14 23.8 Example: remote start/stop Example: remote cool/heat OBLIGATORY MODELS WITHOUT OPSC/OPTC/OPSP/OPTP/OPHP OPTP/OPTC X27Y 7 44 X27Y 8 45 7 OPSP/OPSC/OPHP 13 K1P 23.8 13 K2P 14 43.3 14 OPSC/OPTC/OPSP/OPTP/OPHP Daikin Europe N.V. Description Unit name Fieldwiring DI, changeable DI EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 40 0 1 2 3 4 5 6 7 8 9 A01P 70 71 72 76 73 74 75 8 -t° Daikin Europe N.V. 73 74 77 78 79 80 X73A:1 X73A:2 81 91 GND X70A:3 90 IN X70A:2 80 79 5V X70A:1 90 91 + + + 0 to 20mA 0 to 20mA - - Example mA measurement (5V power supply by PCB) GND X71A:3 Changeable AO1 75 8 R8T Ch. AI1 example: temp. sensor IN X71A:2 78 5V X71A:1 77 GND X68A:3 Changeable AI4 81 Changeable AI3 76 IN X68A:2 74 5V X68A:1 73 GND X69A:3 72 IN X69A:2 71 70 5V X69A:1 Changeable AI2 75 Changeable AI1 0 to 10VDC + 13 0 to 20mA or 10V S5S 14 - Ch. AI3 example: V measurement Example mA measurement (External power supply) - Ch. AI4 example: Switch Description Unit name Fieldwiring changeable AI/AO EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Example mA output V output Page Drawing number - 41 1 2 3 4 5 AC15: max.3A-230V Operation M11C Operation M12C 6 7 8 9 Changeable DO: Maximum load: 2A-230VAC, Minimum load: 10mA-5VDC Operation M21C Operation M22C Changeable DO1 (Default: Alarm, NO contact 8-9) Changeable DO2 (Default: Gen. operation) A11P A11P X22A:5 X22A:3 13 K22M K12R 25 4 5 6 22 23 24 H12P H21P 10 7 8 9 External Power supply (ex 24VAC or 230VAC) External Power supply (ex 24VAC or 230VAC) 9 8 11 9 H2P External Power supply (ex 24VAC or 230VAC) External Power supply (ex 24VAC or 230VAC) Safety active = contact closed No power = contact open No safety = contact open Daikin Europe N.V. 7 H22P H1P External Power supply (ex 24VAC or 230VAC) 10 8 X24A:1 Alarm NC Software selection necessary 25 9 H11P 7 X22A:1 Alarm NO Default 3 K14R 14 23 22 14 6 5 14 4 14 3 13 K21M 9 13 K12M 24 13 K11M X24A:2 11 0 H1P External Power supply (ex 24VAC or 230VAC) External Power supply (ex 24VAC or 230VAC) Safety active = contact closed No power = contact closed No safety = contact open Description Unit name Fieldwiring DO,changeable DO EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number - 42 0 1 2 3 4 5 6 7 8 9 Ch. DO: Maximum load: 2A-230VAC, Minimum load: 10mA-5VDC DO pump Changeable DO3 A11P A11P K20R X64A:7 X63A:3 12 X27Y 3 13 16 10 X27Y 6 14 X27Y 10 15 5 X27Y 6 14 X27Y 5 H3P 17 18 19 21 20 19 18 17 16 15 13 X64A:3 14 K1S X63A:1 K22R X25A:3 12 4 X64A:5 K21R X16A:3 A01P X64:1 K15R Changeable DO6 A01P X25A:1 K4R Changeable DO5 A01P X16A:1 X27Y Changeable DO4 20 21 15 H4P H5P H6P K1P 11 F17B K2P 14 X27Y 2 X27Y SL A11P External Power supply (ex 24VAC or 230VAC) 1 External Power supply (ex 24VAC or 230VAC) SN A11P X2A 23.9 23.9 Changeable DO3 (Default: 2nd pump) Changeable DO3 (no predefined function) MODELS WITH OPTC/OPTP NOT FOR MODELS WITH OPSC/OPTC/OPSP/OPTP/OPHP Daikin Europe N.V. 1 3 5 13 External Power supply (ex 24VAC or 230VAC) External Power supply (ex 24VAC or 230VAC) External Power supply (ex 24VAC or 230VAC) MODELS WITHOUT OPTC/OPTP 2 4 6 14 15.5 15.5 15.5 40.2 Description Unit name Fieldwiring DO,changeable DO EWAQ 130-260 EWYQ 130-250 OPIF 4TW57596-2 Page Drawing number A 43