PLUMBING

advertisement
14.48
3.00
10.00
9.28
1.50
5.50
2.50
2.20
3.00
FIREWALL
W.C F.D LAV.
2.20
FIRE EXIT
TOILET
4.75
U
C.O
1.50
2.46
1.50
D
FIREWALL
9.47
FIREWALL
SS
3
UP
1.40
8.21
PARKING AREA
RENTABLE SPACE
8.23
R
D1
6'' Ø PVC SOIL PIPE
OPEN SPACE
A
17.70
O
EXIT
GATE
150Ø S.P TAPPED TO
SEWER LINE (VERIFY
TAPPING POINT)
SEPTIC TANK
RENTABLE SPACE
JC AQUINO AVENUE
2
6'' Ø PVC SOIL PIPE
1.98
FIREWALL
6.36
C.O
U
FIRE EXIT
FIREWALL
2.20
1.07
TOILET
FIREWALL
W.C F.D LAV.
3.00
9.36
2.50
SANITARY LAYOUT
GROUND FLOOR PLAN
SCALE:
11.49
14.50
1: 100
MTS.
2.18
PROJECT TITLE :
DE JESUS & ASSOCIATES
JOVEN GENEROSO S. DE JESUS, II
architecture+planning+interior design
Architect
PRC.No.0009668
TIN 144-047-428
253 DAR SUBDIVISION, BUTUAN CITY
3.00
uap
PTR NO. 2173492
DATE: 1-07-2022
1.45
PROPOSED COMMERCIAL BUILDING
LOCATION: J. C. AQUINO AVENUE, BUTUAN CITY
OWNER :
SHEET NO.
MR. & MRS. LAURENCE C. TING
S I G N A T U R E
P
01
14.48
3.00
13.00
9.28
1.50
2.50
10.00
2.20
3.00
4.75
FIREWALL
0.50
D
FIREWALL
SS
2
R
8.21
3
FIRE EXIT
1.40
6'' Ø PVC SOIL PIPE
RENTABLE SPACE
8.23
O
17.70
OPEN SPACE BELOW
A
6'' Ø PVC SOIL PIPE
JC AQUINO AVENUE
9.47
FIREWALL
1.98
FIREWALL
6.36
C.O
U
FIREWALL
W.C F.D LAV.
2.00
1.00
0.50
9.36
2.50
SANITARY LAYOUT
SECOND FLOOR PLAN
SCALE:
11.49
14.50
1: 100
MTS.
2.18
DE JESUS & ASSOCIATES
JOVEN GENEROSO S. DE JESUS, II
architecture+planning+interior design
Architect
PRC.No.0009668
TIN 144-047-428
253 DAR SUBDIVISION, BUTUAN CITY
FIREWALL
2.20
1.07
TOILET
3.00
uap
PTR NO. 2173492
DATE: 1-07-2022
PROJECT TITLE :
OWNER :
PROPOSED COMMERCIAL BUILDING
MR. & MRS. LAURENCE C. TING
LOCATION: J. C. AQUINO AVENUE, BUTUAN CITY
SHEET NO.
S I G N A T U R E
P
02
14.48
3.00
10.00
9.28
1.50
5.50
2.50
2.20
3.00
FIREWALL
W.C F.D LAV.
2.20
FIRE EXIT
TOILET
4.75
U
GV
1.50
2.46
1.50
D
FIREWALL
8.21
PARKING AREA
25Ø MM PPR PIPE
D1
3
UP
JC AQUINO AVENUE
R
2
GV WATER
SOURCE
RENTABLE SPACE
8.23
O
EXIT
GATE
CV
RENTABLE SPACE
OPEN SPACE
17.70
A
25Ø MM PPR PIPE
1.40
M
9.47
FIREWALL
RISER
1.98
FIREWALL
6.36
GV
FIRE EXIT
U
FIREWALL
2.20
1.07
TOILET
FIREWALL
W.C F.D LAV.
3.00
9.36
2.50
WATER DISTRIBUTION LAYOUT
GROUND FLOOR PLAN
SCALE:
11.49
14.50
1: 100
MTS.
2.18
PROJECT TITLE :
DE JESUS & ASSOCIATES
JOVEN GENEROSO S. DE JESUS, II
architecture+planning+interior design
Architect
PRC.No.0009668
TIN 144-047-428
253 DAR SUBDIVISION, BUTUAN CITY
3.00
uap
PTR NO. 2173492
DATE: 1-07-2022
1.45
PROPOSED COMMERCIAL BUILDING
LOCATION: J. C. AQUINO AVENUE, BUTUAN CITY
OWNER :
SHEET NO.
MR. & MRS. LAURENCE C. TING
S I G N A T U R E
P
03
14.48
3.00
13.00
9.28
1.50
2.50
10.00
2.20
3.00
4.75
FIREWALL
0.50
D
FIREWALL
9.47
FIREWALL
R
8.21
3
FIRE EXIT
RISER
1.40
RENTABLE SPACE
8.23
O
17.70
OPEN SPACE BELOW
A
JC AQUINO AVENUE
2
1.98
FIREWALL
GV
6.36
U
FIREWALL
W.C F.D LAV.
2.00
1.00
0.50
9.36
2.50
WATER DISTRIBUTION LAYOUT
SECOND FLOOR PLAN
SCALE:
11.49
14.50
1: 100
MTS.
2.18
DE JESUS & ASSOCIATES
JOVEN GENEROSO S. DE JESUS, II
architecture+planning+interior design
Architect
PRC.No.0009668
TIN 144-047-428
253 DAR SUBDIVISION, BUTUAN CITY
FIREWALL
2.20
1.07
TOILET
3.00
uap
PTR NO. 2173492
DATE: 1-07-2022
PROJECT TITLE :
OWNER :
PROPOSED COMMERCIAL BUILDING
MR. & MRS. LAURENCE C. TING
LOCATION: J. C. AQUINO AVENUE, BUTUAN CITY
SHEET NO.
S I G N A T U R E
P
04
14.48
3.00
10.00
9.28
1.50
5.50
2.50
2.20
3.00
FIREWALL
2.20
W.C F.D LAV.
D
CB
FIRE EXIT
150Ø S.P TAPPED TO
SEWER LINE
(VERIFY TAPPING POINT)
TOILET
4.75
U
D
CB
JC AQUINO AVENUE
8.21
1.40
8.23
O
RENTABLE SPACE
D
CB
150Ø S.P TAPPED TO
SEWER LINE
(VERIFY TAPPING POINT)
CB
D
FIREWALL
1.98
R
3
150Ø S.P TAPPED TO
SEWER LINE
(VERIFY TAPPING POINT)
150Ø S.P TAPPED TO
SEWER LINE
(VERIFY TAPPING POINT)
6.36
FIRE EXIT
U
CB
D
150Ø S.P TAPPED TO
SEWER LINE
(VERIFY TAPPING POINT)
FIREWALL
TOILET
2.20
1.07
PARKING AREA
D1
CB
D
D
CB
FIREWALL
W.C F.D LAV.
3.00
UP
150Ø S.P TAPPED TO
SEWER LINE
(VERIFY TAPPING POINT)
3.00
9.36
2.50
STORM DRAINAGE LAYOUT
GROUND FLOOR PLAN
SCALE:
11.49
14.50
1: 100
MTS.
2.18
PROJECT TITLE :
DE JESUS & ASSOCIATES
JOVEN GENEROSO S. DE JESUS, II
architecture+planning+interior design
Architect
PRC.No.0009668
TIN 144-047-428
253 DAR SUBDIVISION, BUTUAN CITY
2
150Ø S.P TAPPED TO
SEWER LINE
(VERIFY TAPPING POINT)
RENTABLE SPACE
OPEN
SPACE
9.47
A
17.70
FIREWALL
D
CB
150Ø S.P TAPPED TO
SEWER LINE
(VERIFY TAPPING POINT)
EXIT
GATE
1.50
2.46
1.50
D
FIREWALL
uap
PTR NO. 2173492
DATE: 1-07-2022
1.45
PROPOSED COMMERCIAL BUILDING
LOCATION: J. C. AQUINO AVENUE, BUTUAN CITY
OWNER :
SHEET NO.
MR. & MRS. LAURENCE C. TING
S I G N A T U R E
P
05
14.48
3.00
13.00
9.28
1.50
2.50
10.00
2.20
3.00
FIREWALL
4.75
D
0.50
D
FIREWALL
D
D
2
8.21
RENTABLE SPACE
D
D
3
FIRE EXIT
D
D
1.40
R
8.23
O
17.70
OPEN SPACE BELOW
A
JC AQUINO AVENUE
9.47
FIREWALL
1.98
FIREWALL
6.36
U
1.07
FIREWALL
W.C F.D LAV.
2.00
1.00
0.50
9.36
2.50
STORM DRAINAGE LAYOUT
SECOND FLOOR PLAN
SCALE:
11.49
14.50
1: 100
MTS.
2.18
DE JESUS & ASSOCIATES
JOVEN GENEROSO S. DE JESUS, II
architecture+planning+interior design
Architect
PRC.No.0009668
TIN 144-047-428
253 DAR SUBDIVISION, BUTUAN CITY
FIREWALL
2.20
TOILET
D
3.00
uap
PTR NO. 2173492
DATE: 1-07-2022
PROJECT TITLE :
OWNER :
PROPOSED COMMERCIAL BUILDING
MR. & MRS. LAURENCE C. TING
LOCATION: J. C. AQUINO AVENUE, BUTUAN CITY
SHEET NO.
S I G N A T U R E
P
06
0.70
13.78
14.50
FIREWALL
GUTTER
RD
4.75
FLASHING
FLASHING
FIREWALL
FIREWALL
RD
RD
2
9.46
GUTTER
SLOPE
SLOPE
RIDGELINE
GUTTER
RD
GUTTER
RD
GUTTER
OPEN SPACE BELOW
FLASHING
3
RD
RD
CONCRETE GUTTER
FIREWALL
1.50
FLASHING
FIREWALL
2.00
1.00
9.36
2.50
STORM DRAINAGE LAYOUT
ROOF PLAN
SCALE:
11.49
14.50
1: 100
2.18
PROJECT TITLE :
DE JESUS & ASSOCIATES
JOVEN GENEROSO S. DE JESUS, II
architecture+planning+interior design
Architect
PRC.No.0009668
TIN 144-047-428
253 DAR SUBDIVISION, BUTUAN CITY
FIREWALL
2.20
FLASHING
RD
uap
PTR NO. 2173492
DATE: 1-07-2022
PROPOSED COMMERCIAL BUILDING
LOCATION: J. C. AQUINO AVENUE, BUTUAN CITY
MTS.
OWNER :
SHEET NO.
MR. & MRS. LAURENCE C. TING
S I G N A T U R E
P
07
100mm Ø PVC CO
2.50
GENERAL NOTES
12mm Ø BAR
FERRULE DIRECTLY ABOVE
1
ALL PLUMBING WORKS INCLUDED HEREIN SHALL BE EXECUTED ACCORDING TO THE PHILIPPINES
PLUMBING CODE, THE NATIONAL BUILDING CODE, AND THE RULES AND REGULATION OF LOCAL
GOVERNMENT AUTHORITIES CONCERNED.
2
COORDINATE THE DRAWING WITH OTHER RELATED DRAWINGS AND SPECIFICATIONS, THE ENGINEER
SHALL BE NOTIFIED IMMEDIATELY OF ANY DISCREPANCY FOUND THEREIN.
3
ALL PIPES SHALL BE INSTALLED AS INDICATED ON PLANS, ANY RELOCATIONS REQUIRED FOR
PROPER EXECUTION OF OTHER TRADES SHALL BE WITH PRIOR APPROVAL OF THE ARCHITECT OR
ENGINEER.
4
PROPOSED SANITARY UTILITIES SHALL CONFORM TO THE ACTUAL LOCATION, DEPTH AND INVERT
ELEVATION OF ALL EXISTING PIPES AND STRUCTURES AS VERIFIED BY THE CONTRACTOR.
5
ALL SLOPES FOR HORIZONTAL DRAINAGE SHALL MAINTAIN 1% UNLESS OTHERWISE SPECIFIED.
6
SIZE OF WATER SUPPLY PIPES TO FIXTURES SHALL BE IN ACCORDANCE WITH THE MANUFACTURERS
INSTRUCTIONS.
7
THE CONTRACTOR SHALL VERIFY ALL EXISTING UTILITIES AT SITE AND COORDINATES THE WORK
WITH THE SEWER LINE EFFLUENT DISPOSAL POINT AND WATER LINE SERVICE CONNECTING POINT.
8
ALL PIPES SIZE ARE IN MILLIMETERS AND ALL DIMENSIONS ARE IN METERS UNLESS OTHERWISE
SPECIFIED.
SOIL TEE BUT NOT CONNECTOR
1.00
CO
MH
CO
0.40
DIGESTIVE CHAMBER
LEACHING
CHAMBER
1.00
1.10
INLET
0.15
10 % SLOPE
6" CHB
0.15
1.50
OUTLET
MH
0.30 0.15
CO
1.70
1.50
MATERIAL SPECIFICATIONS:
10mmØ REBARS @
PLAN
300mm BOTHWAYS
SECTION
SEPTIC VAULT DETAIL
SCALE:
1.60
1 : 30
RD
0.30 0.40 0.30
E
AC
SP RD
EN
R
OP
FIR
FL
W
LO
R
BE
TE
UT
AS
H
IN
MANUFACTURED BY "KITZ" BRAND OR APPROVED EQUAL.
FIR
E
OP
AL
L
E
0.10
4"THK. CHB
DOWNSPOUT
RE
EW
AL
L
6''
RE
Ø
PV
C
SO
E
PIP
RE
NT
AB
V.
FIR
EW
AL
L
NT
AB
LE
SP
AC
E
C
U .O
V.
FIR
EW
AL
L
EW
A
LE
FIR
6''
SP
RD 3
Ø
NTC.OU TOIL
AB ET
LE
FIRS
EP
PV
C
V.
E
EW
AL
L
SS
AC
E
25Ø
M6M
'' PØ
FIR
PR
PVP
EW
CIPS
AL
EO
EX
L
IL
IT
PIP
E
RIS F
ER IRE
3
RIS
ERC
DB
UP
PTIC
INO
QUW
RK
PA
A
M
JKC GV
CV
SE
DCB
15
E 0Ø
(VS
ERWERS.P
IFY L TA
TAINE PPE
PP
ING D TO
PO
INT
)
TA
N
ING
A
UE
EN
AV
2
15
TASEW0Ø S
PP ER .P
IN LINTA
G
PP
PO E (V
IN EED T
T) RIF O
Y
A
RE
INO
QU
E
NU
E
AV
A
JC
SECTION
GREASE TRAP DETAIL
CATCH BASIN DETAIL
ISOMETRIC VIEW
SCALE:
SCALE:
SCALE:
MTS.
1 : 30
DE JESUS & ASSOCIATES
JOVEN GENEROSO S. DE JESUS, II
architecture+planning+interior design
Architect
PRC.No.0009668
TIN 144-047-428
uap
PTR NO. 2173492
DATE: 1-07-2022
MTS.
FD
FLOOR DRAIN
CO
CLEAN OUT
SH
SHOWER HEAD
SOIL STACK
WS
SO AT
UR ER
CE
3
300mm BOTHWAYS
SECTION
URINAL
FAN COIL UNIT
SS
2
CBSS
D1
15
(V SEW0Ø S
ER ER .P
IFY L TA
TA INE PPE
PP
DT
IN
O
G
PO
IN
T)
10mmØ REBARS @
FIR
E
WA
LL
IL
PIP
E
SO
LL
AC
URI
FCU
TT
GU
WA
FIR IPE
R PEWA
PP
LL
MM
25Ø
E
PIP
IL
O
S
C
PV
Ø
6''
GU
RD
ER
LL
W.C
F.D
LA
TO
ILE
T
W.C
F.D
LA
TT
E MA
WA T TH XTEIN V
LLHE ROUND ENT
RO G ED
OF H
IL
TO
ILE
T
2
ER
FIR
FIR
E
EXMAIN
THTHR TEN VE
E R OU DE NT
OOGH D
F
C
U .O
RD
NC
RE
TE
GU
FIR
TT
EW
ER
AL
L
P
EXMAIN
THTHR TEN VE
E ROU DE NT
OOGH D
F
FIR
4"THK. CHB
CO
E
AC
W.C
F.D
LA
LAVATORY
E
DOWNSPOUT
NS
WATER CLOSET
OP
SL
AS
HIN
G
15
(V SEW0Ø S
ER ER .P
FIR
IFY L TA
EW
TA INE PP C D
ED B ALL
PP
IN
TOF
G
IRE
PO
EX
IN
IT
T)
SOIL STACK
DOWNSPOUT
DOWNSPOUT
E
OP
WC
LAV
G
FL
15
E 0Ø
(VS
ERWERS.P
IFY L TA
TAINE PPE C D
PP
B
ING D TO
PO
INT
)
15
E
(VSEW0Ø S GA XIT
ER ER .P TE
IFY L TA
D
TAINE PP
ED CB
PP
IN
TO
1
G
5
PO
(VSEW0Ø S
FIR
ER ER .P
IN
EW
T
IFY L TA
AL)
TAINE PP C D
L
ED B
PP
15
IN
TO
G
(V SEW0Ø S
PO
ER ER .P
IN
IFY L TA
T)
TA INE PPE CB
PP
D DT
F
IR
IN
O
EE
G
PO
XIT
IN
T)
EW
AL
L
HIN
WA
LL
DOWNSPOUT
COVER
A
SP
EN
FIR
FL
AS
FIR
E
RISER
0.10 0.60 0.10
0.80
INLET
W
DOWNSPOUT
PLAN
COVER
LIN
GE
RID
G
OP
INLET
LEGEND
EW
SL
DOWNSPOUT
COVER
OUTLET
MANUFACTURED BY "METMA" BRAND OR APPROVED EQUAL.
HIN
G
EW LO
BAEL
CE L
PLAN
0.60 0.10
G.I. PIPES OR EQUAL.
VALVES
FL
AS
FIR
0.60
0.20 0.400.20
0.80
INLET
253 DAR SUBDIVISION, BUTUAN CITY
G.I. PIPES OR EQUAL.
E
COVER
1 : 30
COLD WATER LINE
HOT WATER LINE
G
GU
RD
IN
10mmØ REBARS @
300mm BOTHWAYS
SIMILAR TO EMERALD BRAND OR APPROVED EQUAL.
TT
0.40
AS
H
OUTLET
VENT PIPE
FLOOR DRAINS
FL
COVER
EW
AL
L
G
RD
COVER
OUTLET
POLY VINYL CHLORIDE (PVC) PIPE SERIES 1000, AND CLASS 35
RD
ER
TT
GU
MTS.
0.60
0.60
DRAIN, WASRE &
M
WASTE STACK
VTR
VENTILATION THRU ROOF
ST
SEPTIC TANK
MH
MANHOLE
DS
DOWN SPOUT
CB
CATCH BASIN
GT
GREASE TRAP
GV
GATE VALVE
CV
CHECK VALVE
WATER METER
M
NTS.
VENTILATION THRU ROOF
PROJECT TITLE :
OWNER :
PROPOSED COMMERCIAL BUILDING
MR. & MRS. LAURENCE C. TING
LOCATION: J. C. AQUINO AVENUE, BUTUAN CITY
SHEET NO.
S I G N A T U R E
P
08