Uploaded by esteban.sepulveda

TWD1643GE

advertisement
Technical data TWD1643GE
General
In-line four stroke diesel engine with direct injection. Rotation direction, anti-clockwise viewed towards flywheel.
Turbocharged
Number of cylinders
6
Displacement, total
16,12
litre
3
in
983,7
Firing order
1-5-3-6-2-4
Bore
mm
144
in
5,67
Stroke
mm
165
6,50
in
Compression ratio
16,5:1
Engine only, excluding cooling
Dry weight
kg
1700
system
lb
3748
GenPac
kg
2200
4850
lb
Engine only, excluding cooling
1770
Wet weight
kg
system
3902
lb
GenPac
2370
kg
5225
lb
Performance
Prime Power
without fan
with fan
Standby Power
without fan
with fan
Torque at:
Prime Power
Standby Power
Mean piston speed
Effective mean pressure at:
Prime Power
Effective mean pressure at:
Standby Power
Max combustion pressure at:
Prime Power
Max combustion pressure at:
Standby Power
Total mass moment of inertia, J (mR2)
Degree of irregularity at:
Friction Power
r/min
kW
hp
kW
hp
kW
hp
kW
hp
Nm
lbft
Nm
lbft
m/s
ft/sec
MPa
psi
MPa
psi
MPa
psi
MPa
psi
2
kgm
2
lbft
Prime Power
Standby Power
kW
hp
1500
553
752
536
729
613
834
596
811
3521
2596
3902
2878
8,3
27,1
2,7
398
3,0
441
18,8
2727
20,0
2901
1800
615
836
585
796
674
917
644
876
3263
2406
3576
2637
9,9
32,6
2,5
369
2,8
404
19,6
2843
19,8
2872
4,20
99,7
1:33
1:29
38
52,088
1:55
1:51
55
74,936
Technical data TWD1643GE
Derating
The engine may be operated up to 1500 m altitude without derating.
For operation at higher altitudes the power will be derated according to the graph below.
There is no derating for ambient temperature or humidity.
Engine noise emission
Test Standards: ISO 3744-1981 (E) sound power (with fan & radiator without intake and exhaust noise)
r/min
1500
Tolerance ± 0.75 dB(A)
dB(A)
113
No load
Measured sound power Lw
dB(A)
117
Prime Power
dB(A)
117
Standby Power
No load
dB(A)
101
Calculated sound pressure Lp at 1 m
dB(A)
105
Prime Power
dB(A)
105
Standby Power
1800
117
120
120
105
108
108
Unsilenced exhaust noise
Data calculated as sound pressure Lp.
Assumed microphone distance 1 m
Prime Power
Standby Power
1800
120
120
r/min
dB(A)
dB(A)
1500
116
117
Test conditions for load acceptance data
Warm engine.
Generator
Model
Type of AVR
Stamford
MX341
HCI534F1
Load acceptance performance can vary due to actual alternator inertia, voltage regulator, type of load and local ambient conditions.
UFRO: STD-setting 47 / 57Hz / 400V/ Dipp=50%.
Single step load performance at 1500 rpm
Recovery time (s)
Speed diff (%)
Load (%)
Prime
Standby Prime
Standby
0-20
2,8
1,8
0-40
5,6
1,9
0-48
7,0
2,6
0-60
8,8
2,8
0-65
10,0
3,1
0-80
13,6
4,0
0-100
18,7
5,5
100-0
0-20
0-40
0-44
0-59
0-60
0-80
0-98
8,8
Remaining load
(%)
20-100
40-100
48-100
60-100
65-100
80-100
Speed diff (%)
Prime
Standby
11,6
7,3
6,3
5,5
4,6
3,1
Recovery time (s)
Prime
Standby
3,7
2,7
2,1
1,9
1,5
1,5
2,4
3,2
6,3
7,0
10,0
10,2
15,9
20,4
1,9
2,1
2,7
3,3
3,4
4,5
8,8
98-0
9,1
2,4
Recovery time = Speed within 1% of nominal speed.
20-98
40-98
44-98
59-98
60-98
80-98
12,5
7,5
7,0
5,8
5,7
3,0
9,2
9,0
7,8
4,3
3,9
1,6
Technical data TWD1643GE
Single step load performance at 1800 rpm
Speed diff %
Recovery time (s)
Load (%)
Standby
Prime
Standby Prime
0-20
1,6
1,4
0-40
3,6
1,5
0-60
5,5
1,7
0-69
7,0
1,8
0-80
8,6
2,0
0-86
10,0
2,0
0-100
11,9
2,0
100-0
5,8
0-20
0-40
0-60
0-64
0-79
0-80
0-99
Remaining load
(%)
20-100
40-100
60-100
69-100
80-100
86-100
Speed diff (%)
Prime
Standby
7,3
4,8
3,7
2,9
1,8
1,2
Recovery time (s)
Prime
Standby
2,2
2,0
1,6
1,3
1,3
1,2
2,6
1,8
4,0
6,2
7,0
10,0
10,2
13,5
1,5
1,7
1,8
1,8
1,9
1,9
8,1
20-99
40-99
60-99
64-99
79-99
80-99
7,7
5,5
3,8
3,6
1,8
1,7
14,8
11,2
4,4
4,3
1,4
1,3
99-0
6,6
2,6
Recovery time = Speed within 1% of nominal speed.
Cold start performance
Time from start to no load speed at ambient
temperature:
20
5
-15*
°C
r/min
s
s
s
1500
4,2
6,8
4,8
1800
6,0
7,7
5,7
* With manifold heater and block heater engaged, lubrication oil 15W/40
Usage of manifold heater (c.w). Engaged below:
Ambient temp. °C
-15°C
Block heater type and make
Volvo Penta no: 889858
°C
Power kW
2000 W
+20°C
Engaged hours
10 h
Cooling water temp
engine block
+16°C
Technical data TWD1643GE
Lubrication system
Lubricating oil consumption
Prime Power
Standby Power
Oil system capacity including filters
max
Oil sump capacity:
min
Oil change intervals/specifications:
Engine angularity limits:
VDS-2/VDS-3*
VDS, ACEA, E3*
ACEA E2, API CD, CF, CF-4, CG-4*
front up
front down
side tilt
Oil pressure at rated speed
Lubrication oil temperature in oil sump:
max
Oil filter micron size
* See also general section in the sales guide
Fuel system
Prime Power
Specific fuel consumption at:
25%
50%
75%
100%
Standby Power
Specific fuel consumption at:
25%
50%
75%
100%
r/min
litre/h
US gal/h
litre/h
US gal/h
litre
US gal
litre
US gal
litre
US gal
h
h
h
°
°
°
kPa
psi
°C
°F
µ
1500
0,10
0,026
0,11
0,029
r/min
g/kWh
lb/hph
g/kWh
lb/hph
g/kWh
lb/hph
g/kWh
lb/hph
g/kWh
lb/hph
g/kWh
lb/hph
g/kWh
lb/hph
g/kWh
lb/hph
1500
215
0,349
196
0,318
196
0,318
199
0,323
210
0,340
195
0,316
196
0,318
200
0,324
1800
0,10
0,026
0,11
0,029
48
12,7
42
11,1
32
8,5
600
400
200
30
30
30
300 - 650
44 - 94
130
266
0,040
1800
224
0,363
201
0,326
197
0,319
202
0,327
220
0,357
200
0,324
198
0,321
204
0,331
Technical data TWD1643GE
Fuel system
Fuel to conform to
r/min
1500
1800
ASTM-D975-No1 and 2-D
JIS KK 2204, EN 590
25
liter/h
6,6
US gal/h
liter/h
190
210
US gal/h
10,0
kPa
1,5
psi
0,0
kPa
0,0
psi
20,0
kPa
2,9
psi
60
°C
140
°F
0,010
mm
Volvo / EMS 2
Delphi / E3
System return flow
System supply flow at rated speed
Fuel supply line max restriction
Fuel supply line max pressure, engine stopped
Fuel return line max restriction
Maximum allowable inlet fuel temp
Prefilter / Water separator
Governor type/make, standard
Injection pump type/make
Intake and exhaust system
Air consumption at:
Prime Power
Standby Power
Air intake restriction, clean filter(s)
Max allowable air intake restriction
Air filter type
Air filter cleaning efficiency
Heat rejection to exhaust at:
Prime Power
Standby Power
Exhaust gas temperature
after Low Pressure turbine at:
Prime Power
Standby Power
Max allowable back pressure in exhaust line
Exhaust gas flow at:
Prime Power
Standby Power
r/min
1500
1800
3
m /min
43,65
53,07
cfm
1541
1874
3
m /min
46,96
54,85
cfm
1658
1937
kPa
1,5
2
in wc
6,0
8,0
kPa
5
5
in wc
20,1
20,1
Single stage paper cartridge
99,85
%
kW
415
472
BTU/min
23601
26842
kW
463
530
BTU/min
26330
30141
o
C
450
422
o
F
842
792
o
C
463
461
o
F
865
862
kPa
10
10
In wc
40,2
40,2
3
m /min
101,6
119,0
cfm
3586
4201
3
m /min
111,8
130,1
cfm
3949
4593
Technical data TWD1643GE
r/min
1500
1800
kW
23
26
BTU/min
1308
1479
kW
33
33
Standby Power
BTU/min
1877
1877
kW
208
246
Prime Power
Heat rejection to coolant engine radiator at:
BTU/min
11829
13990
kW
226
270
Standby Power
BTU/min
12852
15355
kW
116
121
Heat rejection to coolant CAC radiator at:
Prime Power
BTU/min
6597
6881
kW
125
135
Standby Power
BTU/min
7109
7677
Volvo Penta coolant "ready mix" or Volvo Penta coolant
Coolant
mixed with clean fresh water 40 / 60
Radiator cooling system type
Closed circuit
1,68
m²
Engine radiator core area
18,08
foot²
CAC radiator core area
m²
1,68
foot²
18,08
mm
965
Fan diameter
in
37,99
kW
17
30
Fan power consumption
hp
23
41
Fan drive ratio
1,04 : 1
litre
Coolant capacity,
engine
33
US gal
8,72
litre
Engine radiator and
95
US gal
CAC-radiator with hoses
25,10
drive/ratio
Coolant pump
Belt / 1,85 : 1
l/s
4,8
6,0
Coolant flow engine radiator (at fully opened thermostat)
US gal/s
1,3
1,6
Coolant flow CAC-radiator (at fully opened thermostat)
l/s
1,5
1,6
US gal/s
0,4
0,4
kPa
34
50
Maximum external coolant system restriction, including piping
Engine radiator
in wc
137
201
kPa
24
25
Maximum external coolant system restriction, including piping
CAC-radiator
in wc
96
100
start to open
°C
82
Thermostat
°F
180
fully open
°C
92
198
°F
100
kPa
Maximum static pressure head
(expansion tank height + pressure cap setting)
402
in wc
kPa
70
Minimum static pressure head
281
in wc
(expansion tank height + pressure cap setting)
kPa
75
Standard pressure cap setting
in wc
301
°C
Maximum top tank temperature
103
217
°F
Draw down capacity
4% of total cooling system capacity
°C
50
50
Charge air temperature.
Inlet manifuld, max allowed.
(At air inlet temp. 25 degr. C)
°F
Cooling system
Heat rejection radiation from engine at:
Prime Power
Technical data TWD1643GE
Cooling performance
Cooling air flow and external restriction at different radiator air temperatures based on 103°C TTT and 50% antifreeze (radiator and
cooling fan, see optional equipment)
Engine speed
Air on
PRIME POWER
STANDBY POWER
rpm
temp
Air flow
Air flow
External restriction
External restriction
°C
kg/s
kg/s
Pa
Pa
1500
33
8,0
1000
39
1000
8,0
43
10,0
600
49
600
10,0
50
200
12,0
54
0
13,0
55
200
12,0
58
0
13,0
1800
35
10,0
1000
42
10,0
1000
44
600
12,0
50
200
14,0
51
600
12,0
55
15,0
0
56
14,0
100
58
15,0
0
Note! Calculated values >0 Pa
Engine management system
Functionality
Governor mode
Governor droop
Governor response
Dual speed
Idle speed
Fine speed adjustment
Stop function
Preheating function
Lamp test
Alternatives
Isochronous/droop
0-8%
Adjustable PID-constants (VODIA)
1500 / 1800
600-1200
±120
Energized to Run / Stop
On / Off
On / Off
Default setting
Isochronous
4%
Not adjusted
According to customer
900
0
Energized to stop
Off
On
Technical data TWD1643GE
Engine protection
Parameter
Oil temp
Oil pressure
Low idle
1500 rpm
1800 rpm
Oil level
Piston cooling pressure
>1000 rpm
Coolant temp
Coolant level
Fuel feed
Low idle
pressure
>1400 rpm
Water in fuel
Crank case pressure
Air filter pressure droop
Altitude, above sea
Charge air temp
Charge air pressure
Engine speed
Alarm level
Unit
°C
kPa
kPa
kPa
kPa
°C
kPa
kPa
kPa
m
°C
kPa
rpm
Setting range
120 - 130
-
Default setting
125
190
250
300
Min level
150
95 - 103
-
98
On
150
250
High level
Increased pressure
5,0
-
Setting +5
Low level
Increased pressure
1500
100 - 120% of rated
speed
-
80
500 (absolute)
115% of rated speed
85
510 (absolute)
Alarm level
Shut down. ON/OFF*
Shut down. ON/OFF*
Shut down. OFF/ON*
580
25 ,5
610
-
Shut down. ON/OFF*
-
°C
Exhaust temp**
V
Low voltage
* Off means no shut down, alarm only
** Between high pressure turbin and low pressure turbin
Electrical system
Voltage and type
Alternator:
make/output
tacho output
drive ratio
Starter motor
Starter motor solenoid,
Number of teeth on:
Inrush current at +20°C
Cranking current at +20°C
Crank engine speed at 20°C
Starter motor battery capacity:
Inlet manifold heater (at 20 V)
Power relay for the manifold heater
Engine protection
Action.
Level
Default/Alternative
Setting +5
Shut down. ON/OFF*
160
Shut down. ON/OFF*
220
Shut down. ON/OFF*
270
Shut down. ON/OFF*
150
Shut down. ON/OFF*
pull current
hold current
flywheel
starter motor
max
min at +5°C
Shut down. ON/OFF*
Shut down. ON/OFF*
Shut down. ON/OFF*
Automatic derating, see
section derating
r/min
1500
1800
24V / insulated from earth
Bosch / 80
Amp
Hz/alt. Rev
6
3,9 : 1
Melco
make
105P70
type
7,0
kW
Amp
2,3
Amp
153
12
750
Amp
300
Amp
rpm
155
Ah
2x225
Ah
kW
4,0
1
Amp
Technical data TWD1643GE
Power take off
Front end in line with crank shaft max:
Front end belt pulley load. Direction of load viewed from
flywheel side:
max left
max down
max right
Timing gear at compressor PTO max:
Speed ratio direction of rotation viewed from flywheel side
Timing gear at servo pump PTO max:
Max allowed bending moment in flywheel housing
Max. rear main bearing load
r/min
1500
1800
Nm
lbft
kW
hp
kW
hp
kW
hp
Nm
160
lbft
118
1,31:1 / anti-clockwise
Nm
100
lbft
74
Nm
15000
lbft
11063
N
NA
lbf
Download