ALSOENERGY GENERAL INSTALLATION GUIDE September 2019 General Installation Guide © 2019 by AlsoEnergy™. All rights reserved. This document is the confidential and proprietary information of AlsoEnergy. No part of this document may be photocopied, reproduced, stored in a retrieval system, or transmitted in any form or by any means whether electronic, mechanical or otherwise without prior written permission. AlsoEnergy reserves the right to change details in this publication without notice. PowerTrack®, PowerLobby®, PowerDesigner® PowerInvoice®, PowerLogger®, and PowerManager® are the trademarks of AlsoEnergy™. Other product names and/or organization names mentioned may be trademarks and/or registered trademarks of their respective companies. Revision History Revision Date Author Comments 13 September 2019 Engineering Full Update Limitation of Liability AlsoEnergy™ Inc. (“AE”) reserves the right to make changes to its products and/or their specifications without notice. Obtain the latest version of the device specifications to ensure the most current information is available to the customer. AE assumes no liability for applications assistance, customer’s system design, or infringement of patents or copyrights of third parties by/or arising from the use of AE’s devices. AE SHALL NOT BE LIABLE FOR CONSEQUENTIAL DAMAGES SUSTAINED IN CONNECTION WITH AE PRODUCTS, EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW. FURTHERMORE, AE NEITHER ALLOWS NOR AUTHORIZES ANY OTHER PERSON TO ASSUME FOR IT ANY SUCH OBLIGATION OR LIABILITY. Although the information contained in this document is believed to be accurate, AE assumes no responsibility for any errors which may exist in this publication. Installation Personnel Installation and maintenance of the communications enclosure should only be performed by qualified, competent personnel who have appropriate training and experience with high voltage and current devices. The communications enclosure must be installed in accordance with all Local and National Electrical Safety Codes. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 2 General Installation Guide WARNING Failure to observe the following may result in severe injury or death: • • • • Keep these instructions. There are no user-serviceable parts inside. Refer service to an authorized service person. During normal operation of this device, hazardous voltages are present on the input terminals of the devices and throughout the connected power lines. With their primary circuit energized, current transformers (CTs) may generate a high voltage when their secondary windings are open. Follow standard safety precautions while performing any installation or service work (i.e., remove line/ PT fuses, short CT secondaries, disconnect power whenever adjusting terminations). This product must be used in accordance with the instructions in this manual. Otherwise, the product may not perform as expected and can cause hazards to the user. Danger Line voltages up to 600 VRMS are present on the input terminals of the device and throughout the connected line circuits during normal operation. These voltages may cause severe injury or death. Installation and servicing should be performed only by qualified, properly trained personnel. CSA - C22 Statement This product meets the requirements of Can/CSA-C22.2 no. 61010-1, second edition, including Amendment 1, or a later version of the same standard incorporating the same level of testing requirements. FCC Statement This device is classified as a Class A digital device. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operations. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 3 General Installation Guide Contents Limitation of Liability .................................................................................................................................... 2 Installation Personnel ................................................................................................................................... 2 WARNING ...................................................................................................................................................... 3 Danger ........................................................................................................................................................... 3 CSA - C22 Statement ..................................................................................................................................... 3 FCC Statement .............................................................................................................................................. 3 1.0 General .................................................................................................................................................... 7 1.0.1 Electrical Wiring ........................................................................................................................... 7 1.0.2 Documentation ............................................................................................................................ 7 1.0.3 Disclosure ..................................................................................................................................... 7 1.0.4 Warranty ...................................................................................................................................... 7 1.1 Product Overview ................................................................................................................................... 8 1.2 Options for Connecting Data Logger to the Internet .............................................................................. 9 2.0 AlsoEnergy Hardware.............................................................................................................................. 9 2.1 Data Logger Enclosure Operating Specifications .................................................................................... 9 2.2 AlsoEnergy Hardware Overview ........................................................................................................... 10 2.2.1 Communications Enclosure........................................................................................................ 10 2.2.2 Data Logger ................................................................................................................................ 11 2.2.3 Power Supply ............................................................................................................................. 11 2.2.4 Revenue Grade Energy Meter.................................................................................................... 12 2.2.5 RV50 Cell Modem....................................................................................................................... 13 2.2.6 SU201M Circuit Breaker Supply Terminal Card ......................................................................... 13 2.2.7 Entrelec Feed Through Terminal Block (DC and 485) ................................................................ 13 2.2.8 TDK-Lamda DC Power Supply..................................................................................................... 14 3.0 Installation Procedure ........................................................................................................................... 14 3.1 Required Tools ...................................................................................................................................... 14 3.2 Wiring Sequence ................................................................................................................................... 14 3.3 Typical AlsoEnergy Single-line System Diagram.................................................................................... 15 3.4 Enclosure Mounting Requirements ...................................................................................................... 16 3.5 Preventing Water Damage .................................................................................................................... 17 3.5.1 Weatherproofing the Enclosure ................................................................................................ 17 ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 4 General Installation Guide 3.5.2 Humidity Controlling DESI PAK .................................................................................................. 17 3.6 Grounding Considerations .................................................................................................................... 17 4.0 Installation Connections ....................................................................................................................... 18 4.1 Power .................................................................................................................................................... 18 4.1.1 Remote DC Power Connections ................................................................................................. 18 4.2 Modbus Data Connections.................................................................................................................... 19 4.2.1 Modbus Data Wire ..................................................................................................................... 19 4.2.2 Multiple Modbus Devices .......................................................................................................... 19 4.2.3 Device Programming: Setting a Unique Modbus Address ......................................................... 19 4.3 Revenue Grade Meter........................................................................................................................... 20 Production, Consumption or Grid Metering Locations ....................................................................... 21 4.3.1 Installing Current Transformers (CTs) ........................................................................................ 22 4.3.2 Current Transformer Installation Guide..................................................................................... 22 4.3.3 Identifying Swapped phases. ..................................................................................................... 23 4.3.4 Extending CT Leads to the Revenue Grade Meter ..................................................................... 23 4.3.5 Fusing of Revenue Grade Meter Voltage Taps .......................................................................... 24 4.3.6 Revenue Grade Meter Wiring Guide ......................................................................................... 24 4.3.7 CT Shorting ................................................................................................................................. 24 4.4 Cell Modem and Antenna Installation .................................................................................................. 27 4.4.1 Install Overview.......................................................................................................................... 27 4.4.2 Troubleshooting power and connectivity issues ....................................................................... 27 4.5 AlsoEnergy Weather Stations ............................................................................................................... 29 4.5.1 Installation Recommendations .................................................................................................. 29 4.6 Standard Weather Station .................................................................................................................... 30 4.7 Remote Enclosure Mounting and Connecting ...................................................................................... 30 4.8 Standard Weather Station Sensor Installation and Connections ......................................................... 31 5.0 Installation Verification and Operation ................................................................................................ 38 6.0 Troubleshooting .................................................................................................................................... 38 6.1 Elkor Mark II Meter ............................................................................................................................... 38 6.1.1 Elkor Mark II Status Indicators ................................................................................................... 38 6.2 PowerLogger 1000 ................................................................................................................................ 38 6.2.1 Screen Calibration ...................................................................................................................... 38 ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 5 General Installation Guide 6.2.2 No PowerTrack Connection ....................................................................................................... 38 6.2.3 RS-485 Devices Not Responding in PowerTrack ........................................................................ 38 6.3 MOXA Data Logger ................................................................................................................................ 39 6.3.1 MOXA Data Logger Lights .......................................................................................................... 39 6.3.2 MOXA Data Logger Beeps .......................................................................................................... 39 6.4 Data Logger Power Issues ..................................................................................................................... 40 6.4.1 Verify AC Power at DIN Mounted Circuit Breaker ..................................................................... 40 6.4.2 Verify DC Power at Data Logger ................................................................................................. 40 6.5 Data Logger Does Not Communicate with an End Device .................................................................... 40 6.6 RS-485 Modbus Troubleshooting ......................................................................................................... 41 6.7 Weather Station .................................................................................................................................... 42 6.7.1 Weather station communication issues .................................................................................... 42 6.7.2 Weather Station sensors ............................................................................................................ 42 - Temperature Sensors........................................................................................................................ 42 - Ambient Temperature (4-20mA, -29°C to 49°C) ............................................................................... 42 - Module Temperature (4-20mA, -40°C to 85°C) ................................................................................ 42 - Wind Direction .................................................................................................................................. 43 - Calibrate the Wind Vane ................................................................................................................... 43 - Wind Speed ....................................................................................................................................... 43 - Pyranometer Scale ............................................................................................................................ 44 - Apogee Pyranometer ........................................................................................................................ 45 7.0 Operations & Maintenance................................................................................................................... 45 Appendix A – RJ45 Wiring Guide................................................................................................................. 46 Appendix B - Data Logger Networking Considerations ............................................................................... 47 Appendix C – Connecting To AcquiSuite ..................................................................................................... 48 AlsoEnergy SupportTrack ............................................................................................................................ 49 For Onsite Appointments .................................................................................................................... 49 For phone assistance .......................................................................................................................... 49 Software Training ................................................................................................................................ 49 ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 6 General Installation Guide 1.0 General 1.0.1 Electrical Wiring Because of possible electrical shock or fire hazards, the connection of this equipment should only be made by qualified personnel in compliance with all local applicable electrical codes and standards. 1.0.2 Documentation This manual is meant to cover the installation and troubleshooting of standard installations. AlsoEnergy supports many configurations and specific installations. Please contact technical support if you have any questions. 1.0.3 Disclosure This publication contains information proprietary to AlsoEnergy. No part of this publication may be reproduced in any form without prior written consent from AlsoEnergy. 1.0.4 Warranty The AlsoEnergy communications enclosure is warranted to the original purchaser against defective material and workmanship. During the warranty period, AlsoEnergy will repair or replace, at its option, all defective equipment that is returned freight prepaid. There will be no charge for repair provided there is no evidence that the equipment has been mishandled or abused. If the equipment is found to be in proper working order, a service fee will be charged. The complete terms and conditions of the warranty are located at www.AlsoEnergy.com. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 7 General Installation Guide 1.1 Product Overview The AlsoEnergy communications enclosure interfaces RS-232, RS-485 and RS-422 devices with the AlsoEnergy database via an internet-accessible Ethernet connection. The AlsoEnergy communications enclosure optionally includes a Weather Station signal conditioner, an Ethernet switch and/or one or two Elkor WattsOn Mark II power meters. All data loggers come equipped with two available Modbus ports that are capable of RS-232, RS-485, and RS-422 communications. These components are housed in a powder-coated steel enclosure intended for mounting indoors or outdoors, close to the electrical equipment being monitored. Figure 1-1 Basic monitoring system diagram ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 8 General Installation Guide 1.2 Options for Connecting Data Logger to the Internet 1. Copper Cat5 Ethernet • Distance limitations: 300 feet from the data logger to a network port • Cat5 or better, shielded, twisted pair, UV and direct burial rated • Networking cable should be installed to NEC standards, i.e., minimum 18” separation from power runs, and always in separate conduit 2. Optical Fiber Ethernet • Distance limitations: 2 km between optical switches Our switches require multi-mode 50/125μm or 62.5/125μm fiber with SC Connectors. The fiber cable can be ordered with pre-terminated ends with pull ring for ease of install • Can be in the same conduit as power 3. Wireless Ethernet Radios • Monitored link on PowerTrack • One base with up to 16 remote radios • Rated for up to 15km distance • 2.4GHz for a line of sight connection 4. Cellular Internet Gateway • Preconfigured and tested on the Verizon network • One time install, protection from site IT issues or changes, remote access/troubleshooting • Monthly fee depending on the amount of data For detailed networking information, see Appendix C – Data Logger Networking Considerations. 2.0 AlsoEnergy Hardware 2.1 Data Logger Enclosure Operating Specifications Environment The NEMA 4 enclosure provides a degree of protection to personnel against incidental contact with the enclosed equipment, and provides a degree of protection against falling dirt, rain, sleet, snow, windblown dust, splashing water, hose-directed water, and external formation of ice on the enclosure Operating Temperature -40 to +60 °C Storage Temperature -50 to +85 °C Electrical Supply Voltage Supply Current Frequency Range Breaker 100 – 277 VAC, auto-ranging OR 480/600VAC 3 wire delta power supply 0.4A 50 – 60 Hz SU201M 6A Ethernet • 10 / 100 Ethernet • Network interface configured to customer needs (DHCP or Static) ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 9 General Installation Guide 2.2 AlsoEnergy Hardware Overview AlsoEnergy hardware comes prewired in a NEMA 4 enclosure for easy installation. The enclosure contains a data logger and may contain additional devices including a cell modem, revenue-grade meter, weather station digitizer, etc. The following pages provide an overview of the hardware solutions but are not a complete list of all the devices AlsoEnergy provides or supports. Please contact customer support if additional technical or installation information is needed. All operation information for the communications enclosure is transmitted via Ethernet to AlsoEnergy PowerTrack. No preventive maintenance or inspection is required. Below is a typical AlsoEnergy communications enclosure. Note there may be variations due to unique site requirements. Figure 2-1 Standard enclosure 2.2.1 Communications Enclosure The AlsoEnergy communications enclosure is a NEMA4 enclosure with a DIN-rail mounted, pre-configured data logger and custom set of devices for site monitoring. The powder-coated steel enclosure is intended for mounting indoors or outdoors, close to the electrical equipment being monitored. All models come equipped with two serial ports in the data logger that are capable of RS-485, RS-422 and RS-232 communications to devices such as inverters, meters, weather stations, and smart combiners. The AlsoEnergy communications enclosure optionally includes up to two additional devices such as a weather station, revenue-grade energy meter, Ethernet/fiber switch, or cell modem. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 10 General Installation Guide 2.2.2 Data Logger The AlsoEnergy PowerLogger 1000 comes pre-loaded with AlsoEnergy software and configuration. • Connects to inverters, meters and weather stations via MODBUS/RTU, MODBUS/TCP OR DNP3 (other protocols are available with vendor cooperation) • Supports up to 40 devices, recommended max 20 per Port • Securely uploads data to cloud-based servers • Typically, 3 to 5-minute uploads, depending on the number of devices • Automatic remote firmware updates • In the event of network outages, data is stored on a removable SD card and uploaded when network functionality is restored. Storage length depends on the number of devices connected. • Certifications and Agency Approvals: UL, CSA, FCC, CE, TUV, Ctick, VCCI This installation manual assumes the PowerLogger 1000 is being used. However, other data loggers (below) may be used: Moxa (Legacy) Obvius Acquisuite PowerManager 2000 (Legacy) PowerManager 2200 2.2.3 Power Supply The default power supply in the communications enclosure requires 100 – 277VAC at 0.4A – 0.2A, 50 -60 Hz, and is auto-ranging. There is also an option for a 480/600VAC 3 wire delta power supply. Either device should be protected by an adequate main circuit breaker rated up to 20 amps. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 11 General Installation Guide 2.2.4 Revenue Grade Energy Meter The WattsOn Mark II is a true revenue-grade meter, a three-phase device designed for energy management and building automation applications. The unit measures electrical parameters, including voltage, current, power, frequency, power factor, and net energy production. The information is available on a per-phase basis allowing the use of one WattsOn transducer in three single-phase systems (up to three individual loads), one three-phase load, or a combination single/split phase load. Features • Features a high accuracy chipset with thousands of measurements per second • Provides register updates two times per second • True-RMS inputs may be used even with distorted waveforms such as those generated by variable frequency drives • 24VDC power • Two pulse outputs • Rolling Window Demand calculations • Accepts up to 600V (line-to-line) directly without the need for potential transformers • ANSI C121.20 Class 2 • Small, DIN mount enclosure • LCD display for configuration and data reading purposes Meter CT Requirements • Three Voltage Taps and three Current Transformers (CT) are required to monitor three-phase power. One set per phase wired accordingly. • The proper CTs are determined by maximum amperage, wire size, number of wires passing through the window. All CTs for each meter must be identical. • The CTs may be either a solid core or a split core. o Split Cores are only recommended for adding to existing systems for a more straightforward installation; however, split Cores are typically less accurate. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 12 General Installation Guide 2.2.5 RV50 Cell Modem The RV50 is a compact, intelligent, and fully-featured communications platform that provides real-time wireless capabilities on 4G networks with fallback to 3g. Features • Operating Voltage Input voltage: 7–36V • 10/100/1000 Base-T RJ-45 Ethernet • 3 SMA antenna connectors (LTE, Diversity, Active GPS) • DIN rail mount screws • Peak Power Consumption: 8 W • Typical Power Consumption: 3.7 W 2.2.6 SU201M Circuit Breaker Supply Terminal Card The SU 200 M miniature circuit breaker is ABB’s solution for UL489 protection in branch circuits for voltages up to 480Y/277VAC, and 96VDC. This circuit breaker is an all-around device for universal use in AC and DC applications. Features • High-performance MCB with 10 kA interrupting capacity acc. to UL 489 / CSA 22.2 No. 5 and 15 kA breaking capacity acc. to IEC/EN 60947-2 • Certified up to In = 40 A at 480 Y/277 V AC acc. to UL 489 / CSA 22.2 No.5 • Certified for AC and DC use acc. to UL and CSA • 40 °C reference temperature acc. to UL and CSA • Current limiting acc. to UL 489 • Clear contact position indication in red/green (”real CPI“) 2.2.7 Entrelec Feed Through Terminal Block (DC and 485) Qualified for worldwide applications and severe environments (such as hazardous locations, railways, marine, and solar applications. Features • Rated impulse voltage (Uimp) - 8 kV • Rated Current (IEC) 32 A, (UL) 20A • Rated operating voltage, 1000 V, (UL/CSA) 600V • Compliment with standards: IEC60529, IEC60947-1,UL, CSA ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 13 General Installation Guide 2.2.8 TDK-Lamda DC Power Supply AC to DC converter with 24V output as well as an AC line frequency output line. Features • Low Profile for Building Automation • 24V Output • Wide Range AC Input (100-277VAC) • Evaluated to NEC NFPA70 Class 2 Output • Class II Double Insulation • AC Line Frequency Sync Signal • -25 to +71°C Operation • DIN Rail Mount 3.0 Installation Procedure Warning The AlsoEnergy enclosure contains sensitive electronics and high voltages. The enclosure needs to remain weather-tight for its entire expected lifetime. Proper installation is the best defense against future service calls and expenses. 3.1 Required Tools • • • • • • • Drill and Bit Set Knockout Set Wire Stripper/Cutter Small Flathead Screwdriver Large Flathead Screwdriver AC/DC voltmeter RJ45 head-maker • • • • • Network cable tester Mounting hardware to mount enclosures, sensors, and radios Outdoor-rated shielded STP Cat5 cable Conduit and rain-tight connectors Loctite® Epoxy Plastic Bonder and Foil Tape for Panel Temp Sensor 3.2 Wiring Sequence The following sections provide detailed wiring instructions and diagrams. For the devices that apply, the recommended order of wiring is: 1. 2. 3. 4. 5. 6. Power for the communications enclosure: Ground, AC Power Internet Connection (wired, fiber, Ethernet radios) External Modbus devices, i.e., inverters, external weather stations, and external meters Weather station sensors for an internal weather station Voltage and CTs for revenue-grade energy meters (Consumption and/or Production) Weather station sensors for the external remote weather station ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 14 General Installation Guide 3.3 Typical AlsoEnergy Single-line System Diagram Each monitoring package comes with a corresponding AlsoEnergy single-line diagram which shows: • • • • • The AlsoEnergy data logger communication configuration, either DHCP or Static IP settings Type of devices included in the AlsoEnergy communication package Data Logger connections, showing which devices belong on each communication bus Specific addressing information for all site devices Communications protocols and wiring types Figure 2.2 Typical single-line diagram. Best Practice: Wire Labeling All external electrical and communications wires should be labeled, e.g. “To Pad 1 Enclosure”, “To Meter 3”, etc. A colored tape can be used to designate CT and VT phases. Having labeled wires will save time during commissioning and troubleshooting. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 15 General Installation Guide 3.4 Enclosure Mounting Requirements Location Mount to an indoor or outdoor wall following the instructions in Section 3.4, Enclosure Mounting. • • • • The unit should be placed in a secure location, away from any potential tampering. Mount to an indoor or outdoor wall using four 2-¼” screws through the holes in the mounting flanges. Allow space beneath the enclosure for conduit runs for all input and output wires. Allow space in front of and behind the unit to allow the front door to open fully. Distance Limitations • Maximum 300 feet from an internet connected network port • No further than six feet from earth ground • Maximum 1,000 feet between any two RS-485 or RS-422 devices, including communications enclosure • Maximum 4,000 feet between communications enclosure and last RS-485 or RS-422 device • Maximum 100 feet to an RS-232 device • Maximum 6500 feet per fiber run Power • The standard power supply in the AlsoEnergy Communication Box requires 100 – 277VAC at 0.4A – 0.2A, 50 -60 Hz, and is auto-ranging. Other power supplies such as 480/600VAC 3 Wire delta available. • The monitoring system should be protected by a main circuit breaker rated up to 20 amps. • Allow access to a proper earth ground. Enclosure Penetrations • All conduits and wires must enter from the bottom of the enclosure. Do not penetrate the top or sides of the enclosure. • All entry points must be sealed using weatherproof connecters. • Warranty will be voided if there are entry points on the top or sides of the enclosure. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 16 General Installation Guide 3.5 Preventing Water Damage The enclosure contains electronics that are sensitive to water damage. Ambient humidity, condensation, and water infiltration are common causes of damage to circuitry. Avoid costly repairs and losses caused by water damage by using adequate weatherproofing techniques and managing humidity. 3.5.1 Weatherproofing the Enclosure Do not penetrate the top or sides of the enclosure or modify hardware/factory wiring. All penetrations to the enclosure should be liquid-tight to maintain the longevity of the electronics. All conduit connectors must be outdoor rated. 3.5.2 Humidity Controlling DESI PAK AlsoEnergy supplies desiccant packets within all enclosures to prevent excessive humidity and prolong the life of the sensitive electrical devices. Please leave the desiccant packets inside the enclosure after installation is complete. The supplied Humidity Indicator card should be placed in a visible location in the enclosure. Replace the Desiccant packet when the Humidity Indicator Card shows 40% humidity or higher. 3.6 Grounding Considerations Ground the enclosure according to NEC requirements and local regulations. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 17 General Installation Guide 4.0 Installation Connections Connections for power, measurement signals for the revenue grade meter(s) and data signal wires from inverters and remote weather stations or revenue-grade meters are made to DIN Rail terminal blocks as listed in the sections below. Weather station connections are made directly to the weather station signal conditioner boards. An Ethernet cable also needs to be connected to the top of the data logger. 4.1 Power All input connections are made to DIN Rail terminal blocks as listed to the right. Connect 600VAC stranded wire to the terminal blocks pre-labeled with the proper power supply connection with the Line, Neutral, and Ground wires. Table 4-1. Power connections External AC Source Terminal Block Line(s) 1, 2, 3 Neutral 4 Ground 5 Figure 4-1 DIN rail terminals. 4.1.1 Remote DC Power Connections For remote enclosures containing weather stations or meters, two DC power terminals, 24V(+) and 24V(-), are available on the bottom center of the main enclosure. The two terminals are labeled 6 and 7 and are located to the right of the power supply in the center of the lower DIN rail. Power and Modbus can be transmitted via one outdoor shielded Cat5 cable. See 4.7 Remote Enclosure Mounting and Connecting for more detail. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 18 General Installation Guide 4.2 Modbus Data Connections Connect the external devices (inverters, remote revenue-grade meters, remote weather stations) to data Port 1, or Port 2 (see single-line) on the DIN mounted terminal blocks which are hardwired directly to the data logger. Be sure to wire the site’s devices according to the single-line diagram supplied by AlsoEnergy with the shipment. 4.2.1 Modbus Data Wire Connect the Modbus devices using Belden 3106A shielded wire or equivalent. Land the Modbus shield only in the data logger enclosure. Do not land the shield at the other end of the bus. 4.2.2 Multiple Modbus Devices If there are multiple devices on one Modbus port, attach the data+, data- and common wires to the Modbus terminals on the first device, and then daisy chain the ongoing devices. Do not use a starconfiguration, there should be no more than two wires on any terminal. Table 4-2. Data Logger Modbus Wiring Port 1 Inverters Port 2 Meters And Weather Stations Logger # and Terminal Block #1 #2 #3 Ground 10 20 30 Data+ 11 21 31 Data12 22 32 Shield 13 23 33 Ground 14 24 34 Data+ 15 25 35 DataShield 16 17 26 27 36 37 Figure 4-2 RS-485 daisy chain diagram. 4.2.3 Device Programming: Setting a Unique Modbus Address All devices on each Modbus port need a unique address between 1 and 254. If two devices on the Modbus network have the same address, the system will not function. AlsoEnergy weather stations and revenuegrade meters come preconfigured with unique Modbus addresses. Inverters need to be connected and programmed by the installer. Refer to the supplied site-specific single-line diagram for addressing information and supplemental inverter-specific setup guides or inverter installation manual for connecting and programming information. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 19 General Installation Guide 4.3 Revenue Grade Meter For sites with a single revenue-grade meter, the meter is used to capture all production. However, some sites may have other production, grid, or consumption meters based on customer needs. Install Current Transformers (CTs) and make all connections with all system AC and DC power turned OFF. If you have any questions, please call AlsoEnergy technical support before turning the power on. Danger This is a Class III Measurement Device. Line voltages up to 600 VRMS are present on the input terminals of the device and throughout the connected line circuits during normal operation. These voltages may cause severe injury or death. Installation and servicing should be performed only by qualified, properly trained personnel. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 20 General Installation Guide Production, Consumption or Grid Metering Locations The location of meter CTs and voltage taps is dependent on the meter type. Typical sites will use a production meter to monitor PV production with the option of additional consumption, grid or utility meters. Option #1: Production meter and Consumption meter If the extra meter only measures building loads, it is known as a Consumption meter in PowerTrack, and the energy will only flow one direction through this meter. From PV System Grid Production Meter + Utility Meter - Building Load Consumption Meter + + Calculated Utility meter = Consumption meter – Production meter Calculated Load = Consumption meter Figure 4-3 Production, consumption, and optional utility meter. Option #2: Production meter and grid meter If the extra meter is placed on the same wires as the utility meter, then it is known as a Grid meter in PowerTrack and energy can flow either direction through the meter depending on the sum of PV production and building loads. From PV System Grid - Utility Meter + Production Meter + Grid Meter - Calculated Utility meter = Grid meter + Building Load Calculated Load = Grid meter + Production meter Figure 4-4 Production, grid, and optional utility meter. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 21 General Installation Guide 4.3.1 Installing Current Transformers (CTs) CTs provide power readings from the production meter by scaling large primary currents to smaller, easy to measure, secondary currents. Like a traditional transformer, the ratio of the windings determines the relation between the input and output currents. A CT with a rating of 500:5 will change a primary current of 500A into a secondary current of 5A; similarly the same CT will converter a primary current of 250A to a secondary current of 2.5A. The CTs are specified according to the maximum inverter voltage, type of distribution service, wire size and number of wires. Split core or solid core CTs can be used. CTs must all be identical for the system to operate. CT Location The location of CTs can vary depending on the site. They should be placed in the same general location as voltage taps (i.e. same side of the transformer) and in a location that captures all intended production. Service panels and AC disconnect cabinets typically supply ample space and weather protection for CTs. If uncertain about CT placement, contact AlsoEnergy support. 4.3.2 Current Transformer Installation Guide Proper installation of Current Transformers (CTs) is crucial to the operation of any meter: 1) Always observe the voltage and current relationship. In a three-phase system, it is imperative that the CTs match voltage from the same phase, i.e., the CT installed on phase A, must be wired to I11, I12 and the voltage from this phase must be wired to V1 and so on. 2) It is highly recommended to label the CTs wire leads before pulling the wire through conduit; this will help prevent a mismatch of the in installed phases. 3) Observe the orientation of the CT on the wire. Each CT is labeled with a dot or marking “H1”. This side must face the source — some CTs show an arrow indicating the current direction. If Figure 4-5. CTs should be oriented with the the CTs are installed in reverse, the power dot facing the source. measurements will be of the opposite sign! 4) Observe the polarity of the CT wiring into the input terminals. X1 of each CT must be wired to the I11, I21, I31 terminals respectively. For other manufacturers' CTs, please refer to the CT labeling or associated documentation. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 22 General Installation Guide 5) 5A output CTs should always be wired into a shorting block mechanism to provide a method of shorting the CTs for maintenance & safety purposes. Once properly installed, make sure the shorting bars are retracted or removed to supply proper signal to the meter. 6) CTs must be mounted on rated insulated conductors. 4.3.3 Identifying Swapped phases. If two CTs are on the wrong phases, this will show in a power factor of 0.5 on two of the phases. Additionally, there are status indicator LEDs that can alert the user to this condition. These Current and Power indicators are outlined below. For a full description of LEDs status indicators see the WattsOn Mark II user guide here: https://www.elkor.net/pdfs/WattsOn-Mark_II_Manual.pdf Code Description Solid Green LED Solid green indicates that current is present. If voltage is present, solid green indicates that active power (kW) is being imported Blinking Green LED Blinking green indicates that power is being exported. (Voltage must be present). Blinking Red LED Solid red indicates that active power (kW) is being imported, but absolute reactive power (kVAR) exceeds absolute active power (kW). (Voltage must be present). Blinking red indicates that active power is being exported, but absolute reactive power (kVAR) exceeds absolute active power (kW). (Voltage must be present). LED off By default, the LED is off when the current is less than 0.1% of the full-scale input. Solid Red LED 4.3.4 Extending CT Leads to the Revenue Grade Meter AlsoEnergy recommends CT lead lengths be less than 20ft. If CT leads are extended without considering the burden, CT output may flat-line before the max CT amperage is reached. If CT leads need to be extended to the meter, use the chart below to determine the maximum recommended distance based on CT wire gauge. The CT VA rating reflects the maximum allowable power on the CT secondary before the CTs rated accuracy the . The length specifies the total distance between the Elkor meter and the CT, considering the total burden of the CT leads in both directions. Table 4-3. CT VA Rating Wire AWG 20 18 16 14 12 CT VA Rating (found on CT label or datasheet) 2.5 7.5 10 15 25 Ohms/ft 0.01015 4.7ft 14.5 19.5 29.3 49.0 0.00639 7.4 23.1 30.9 46.6 77.9 0.00402 11.8 36.7 49.1 74.0 123.8 0.002525 18.8 58.4 78.2 117.8 197.0 0.001588 29.9 92.9 124.4 187.3 313.3 35 68.7 109.2 173.5 276.2 439.2 ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 23 General Installation Guide 4.3.5 Fusing of Revenue Grade Meter Voltage Taps Per NEC requirements and good practice, the input voltage lines should be protected. In some cases, the voltage may be tapped off existing fuses or breakers. If this is not possible, Elkor recommends a 1A or lower fuse (fast-acting) for the protection of the installation wiring. The WattsOn voltage inputs are high impedance (> 1.5MΩ) and draw negligible current (less than 0.3mA max) 4.3.6 Revenue Grade Meter Wiring Guide The terminal blocks inside the AlsoEnergy communications enclosure are labeled according to Table 4-4: Table 4-4. Revenue Grade Meter Wiring Table 4.4. Revenue Grade Meter Wiring Meter # and Terminal Block Phase Voltage Taps #1 #2 #3 L1 / A V1 40 50 60 L2 / B V2 41 51 61 L3 / C V3 42 52 62 N N 43 53 63 Meter # and Terminal Block Phase CT #1 #2 #3 L1 / A I11 44 54 64 I12 45 55 65 L2 / B I21 46 56 66 I22 47 57 67 L3 / C I31 48 58 68 I32 49 59 69 4.3.7 CT Shorting To service the CTs it is necessary to remove the high current path from the working area. This may be accomplished by shorting the contacts as seen in Figure 4-1-1 Figure 4-1-1 Feed-Through block with CT shorting pins ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 24 General Installation Guide Typical Meter Installation The wiring configurations for four-wire (wye) systems and three-wire (delta) systems are described in figs. 4-6 and 4-7, below. Figure 4-6. Four-wire (wye) wiring diagram. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 25 General Installation Guide Figure 4-7. Three-wire (delta) wiring diagram. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 26 General Installation Guide 4.4 Cell Modem and Antenna Installation This section describes how to connect and start the Sierra Wireless RV50 cell modem. It also lays out the front panel LEDs and I/O functionality. For full reference, please visit https://source.sierrawireless.com/ Note: Field wiring and connections in hazardous locations must be connected per the wiring methods requirement for Class 2 circuits per the National Electric Code and the Canadian Electric Code. Modem Accessories • A SIM Card, typically loaded by AlsoEnergy • Cellular antenna 4.4.1 Install Overview 1. Connect Antenna 2. Connect ethernet cable 3. Connect power 4. Observe LED, check if the logger is communicating RV50 Power The RV50 supports a voltage range between 7 V and 36 V and is designed for both 12 VDC and 24 VDC electrical systems. Check the gateway operation When power is supplied to the AirLink RV50 gateway, it powers up automatically, as indicated by the flashing LEDs. If it does not turn on, ensure that the: • The power connector is plugged in • The power connector is plugged in and supplying voltage between 7 V and 36 V • Ignition Sense (pin 3) is connected to the battery or power source 4.4.2 Troubleshooting power and connectivity issues The following lays out best practices for troubleshooting the connectivity issues as well as a description of the indicator LEDs. 1) 2) 3) 4) Verify that the antenna is mounted outside of the metal enclosure Using the Single Line Diagram, verify the wiring is correct. Verify that the location of the antenna allows for good signal strength. Consult Table 4-0 below for a description of fault LEDs. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 27 General Installation Guide Table 4-0 RV50 LED LED Color/Pattern Power Off Solid Green Power is present. Green with Amber Flash Solid Red Power is present, and the gateway has a GPS fix. Flashing Green Solid Green Solid Amber When you press the reset button, flashing green indicates when to reset the reset button to reboot the gateway. When you press the reset button, flashing red indicates when to release the reset the gateway to the factory default settings. Good signal (equivalent to 4-5 bars) Fair signal (equivalent to 2-3 bars) Weak signal (equivalent to 1 bar) If possible, move the gateway to a location with a better signal. Inadequate (equivalent to 0 bars) it is recommended to move the gateway to a location with a better signal. Connected to an LTE network Connected to a 3G or 2G network Flashing Green Connecting to the network No network available Flashing Red/Amber Flashing Green No network available Flashing Red Traffic is being transmitted or received over the serial port. This behavior only appears if the RV50 is configured to display it. Traffic is being transmitted or received over both the WAN interface and the serial port. This behavior only appears if the RV50 is configured to display Radio Module reconfiguration/firmware update or Network Operator Switching is in progress ALEOS Software update is in Progress Flashing Red Signal Solid Green Solid Amber Flashing Amber Flashing Red Network Activity Flashing Amber ALL Description No power or input voltage >= 36VDC or =< 7VDC Green LED chase Amber LED Chase Standby mode Network Operator Switching is enabled, but the gateway is unable to locate the required firmware. Traffic is being transmitted or received over the WAN interface ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 28 General Installation Guide 4.5 AlsoEnergy Weather Stations AlsoEnergy standard weather stations have the capability of monitoring module (panel) temperature, ambient temperature, solar irradiance, and wind speed and direction. Optionally, humidity, barometric pressure, and rain gauges can be added. 4.5.1 Installation Recommendations • Apogee pyranometers come equipped with 20 meters of cable. Make sure the weather station enclosure is installed within 20 meters of the pyranometer mounting location. • Kipp and Zonen, LiCor and Hukselfux pyranometers come equipped with 10 meters of cable. Make sure the weather station enclosure is installed within 10 meters of the pyranometer mounting location. • Mount the ambient temperature sensor on a north-facing location that is never in direct sunlight • Install the module temp sensor in the centered on a cell in the middle of a module on the underside. • Make sure the adhesive used for the sensor module is rated for up to 180° F. AlsoEnergy recommends high-temperature epoxy. • Outdoor shielded Cat. 5 can be used to extend temp sensors a maximum of 300ft. All splices need to be made inside a weather-tight enclosure. • Sensor leads for analog pyranometers, and wind sensors should not be extended, as extending the leads will effect the measured output. For splicing sensors to outdoor shielded Cat. 5, AlsoEnergy recommends using filled 3M Scotchlok Connectors. These will make a liquid-tight connection for the minimal voltage signals. Pyranometer Mounting Depending on the desired use of the pyranometer data, there are two prevailing mounting orientations: Plane of Array (POA): For systems with only one pyranometer, AlsoEnergy recommends mounting the pyranometer on top of the north side of the array at the same angle as the panels. This orientation allows for the most accurate calculation of the predicted site power output. The pyranometer must not be shaded at any time of the day. Global Horizontal Irradiance (GHI) A pyranometer mounted for GHI should be mounted above any surrounding obstructions to prevent shading. It should also be mounted away from any light-colored or reflective walls that are likely to reflect light on it. It should also be mounted completely level in all directions. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 29 General Installation Guide 4.6 Standard Weather Station All sensor wires should be brought into the enclosure through the bottom with liquid-tight strain relief. The weather station communicates to Port 2 of the data logger over Modbus and has a preconfigured address using the DIP switches. After power-up, the weather station should have one LED blinking green. The two yellow lights will blink when data is being transmitted and received, about every 3 minutes. 4.7 Remote Enclosure Mounting and Connecting If needed, the weather station card can be in a remote enclosure. Mount the remote enclosure following these distance guidelines: • • Less than 1000 ft. from the communications enclosure Less than 20 ft. from the pyranometer mounting location The remote enclosure requires the following connections from the main communications enclosure which can be carried through a single run of outdoor shielded Cat.5 cable. All connections are made on DIN mounted terminal blocks. Table 4-5. Terminal wiring guide for remote enclosures. Wire Color Main Enclosure Remote Terminal Terminal Orange and 6 6 Orange/White Green and 7 7 Green/White Blue/White 15 / 25 / 35 15 / 25 / 35 Enclosure Function 24V(+) 24V(-) Data+ Blue 16 / 26 / 36 16 / 26 / 36 Data- Brown 14 / 24 / 34 14 / 24 / 34 Data ground Note: 2X and 3X numbers are used when there are multiple data loggers onsite. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 30 General Installation Guide 4.8 Standard Weather Station Sensor Installation and Connections The connections are made on the screw terminals from left to right while following the sections below. Figure 4-8. Weather station sensor terminals. The farthest row contains the odd-numbered pins. Anemometer - Wind Speed and Direction Follow the directions that come with the anemometer to assemble and mount the sensor. Make sure to position the anemometer mount pointing north. Connect the anemometer to the correct terminals on the weather station per the table below. Table 4-6. Terminal wiring guide for the anemometer. Wire Color Terminals Function Green WDI (P10) Direction Red Yellow Black AGND (P11) Ground WD REF (P12) 2.5VDC WSI (P14) Speed ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 31 General Installation Guide Module Temperature Sensors: Mounted in the BAPI Enclosure Mount the BAPI enclosure and extend the module temperature sensor to the center of a cell in the middle of a module on the backside. Make sure the adhesive used for the sensor module is rated for up to 180° F. AlsoEnergy recommends high-temperature epoxy. Plug any holes in the BAPI Enclosure to make it weather tight. Note: Do not splice or extend the sensor wire. It has been calibrated to provide accurate measurements. The wire leading to the weather station can be extended up to 500ft using 22AWG wire. Inside the cover are red and black wires which must be extended to the weather station enclosure. AlsoEnergy recommends using outdoor shielded Cat 5 and splicing with filled 3M Scotchlok Connectors. Connect the module temperature sensor to the correct terminals on the weather station with the table below. Table 4-7. Terminal wiring guide for the module temp sensor. Wire Color Terminals Function Red +24V Out (P1) +24V Black MOD TEMP (P4) Signal Ambient Temperature Sensor Mounted in a BAPI Enclosure This air temperature sensor is designed to be mounted outdoors. The UV-resistant plastic shield keeps the sensor protected from weather and sunlight and allows for excellent air circulation. Note: Do not splice or extend the sensor wire. It has been calibrated to provide accurate measurements. The wire leading to the weather station can be extended as needed. Mount the BAPI enclosure in a north-facing, always-shaded location with the sensor pointing down. Plug any holes in the enclosure to make it weather tight. Inside the cover are red and black wires which must be extended to the weather station enclosure. AlsoEnergy recommends using outdoor shielded Cat 5 and splicing with filled 3M Scotchlok Connectors. Connect temp sensor wires to the terminals on the weather station per the table below. Table 4-8. Terminal wiring guide for the ambient temp sensor. Wire Color Terminals Function Red +24V Out (P2) +24V Black AMB TEMP (P6) Signal ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 32 General Installation Guide CMP Pyranometer with Mounting Bracket Mount the pyranometer using the included brackets and mounting hardware. Mount the pyranometer with the wire pointing north, minimizing sun exposure. See Section 4.4.1 for specifics on the mounting location. Connect the pyranometer to the correct terminals on the weather station per the table below. Table 4-9. Terminal wiring guide for CMP pyranometer. Wire Color Terminals Function Mounting Black Chassis Ground Shield POA Blue AGND (P7) Return POA Red PYR (P8) Signal Black Chassis Ground Shield GHI Blue Red AGND (P11) WDI (P10) GHI GHI Return Signal POA Apogee Pyranometer with Mounting Bracket Mount the pyranometer using the included brackets and mounting hardware. See Section 4.4.1 for specifics on the mounting location. Connect the pyranometer to the correct terminals on the weather station per the table below. Table 4-10. Terminal wiring guide for Apogee pyranometer. Model: SP-110 Wire Color Clear Black Terminals Chassis Ground AGND (P7) Function Shield Return Mounting POA POA Red Clear PYR (P8) Chassis Ground Signal Shield POA GHI Black Red AGND (P11) Return WDI (P10) Signal Model: SP-212 / 201 GHI GHI Wire Color Clear Terminals Chassis Ground Function Shield Mounting POA Green AGND (P7) Return POA White Clear PYR (P8) Chassis Ground Signal Shield POA GHI Green White AGND (P11) WDI (P10) Return Signal GHI GHI ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 33 General Installation Guide LI-COR Pyranometer with Mounting Bracket Mount the pyranometer using the included brackets and mounting hardware. Mount the pyranometer with the wire pointing north. See Section 4.4.1 for specifics on the mounting location. Connect the pyranometer to the correct terminals on the weather station per the table below. Table 4-11. Terminal wiring guide for LI-COR pyranometer. Wire Color Terminals Function Mounting Clear Jacket AGND (P7) Return POA Braid PYR (P8) Signal Clear Jacket AGND (P11) Return Braid WDI (P10) Signal POA GHI GHI Hukseflux SR-20, SR-20-T2 Pyranometer with Mounting Bracket Mount the pyranometer using the included brackets and mounting hardware. Mount the pyranometer with the wire pointing north. See Section 4.4.1 for specifics on the mounting location. Connect the pyranometer to the correct terminals on the weather station with the table below. Table 4-12. Terminal wiring guide for Hukseflux pyranometer. Wire Color Terminals Function Mounting Black Chassis Ground Shield POA Green (Blue) AGND (P7) Return POA White PYR (P8) Signal POA Black Chassis Ground Shield GHI Green (Blue) AGND (P11) Return GHI White WDI (P10) Signal GHI Heater Wiring (SR20-T2 models only) Brown 18 Heater Yellow 19 Heater ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 34 General Installation Guide Hukseflux SR-20-D2 Pyranometer with Mounting Bracket This sensor communicates via Modbus independently from the AlsoEnergy weather station digitizer. Mount the pyranometer using the included brackets and mounting hardware. Mount the pyranometer with the wire pointing north. See Section 4.4.1 for specifics on the mounting location. Connect the pyranometer to the correct terminals on the weather station with the table below. Table 4-13. Terminal wiring guide for Hukseflux pyranometer. Wire Color Terminals Function Mounting Red 24V+ (6) V+ POA, GHI Blue 24V- (7) VPOA, GHI Black Chassis Ground Shield White Green Data+ (15) Data- (16) POA, GHI RS-485+ POA, GHI RS-485- POA, GHI Hukseflux SR-30 Pyranometer with Mounting Bracket This sensor communicates via Modbus independently from the AlsoEnergy weather station digitizer. Mount the pyranometer using the included brackets and mounting hardware. Mount the pyranometer with the wire pointing north. See Section 4.4.1 for specifics on the mounting location. Connect the pyranometer to the correct terminals on the weather station with the table below. Table 4-14. Terminal wiring guide for Hukseflux pyranometer. Wire Color Terminals Function Mounting Brown 24V+ (6) V+ POA, GHI Black 24V- (7) VPOA, GHI Yellow White Grey Chassis Ground Shield POA, GHI Data+ (15) RS-485+ POA, GHI Data- (16) RS-485- POA, GHI ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 35 General Installation Guide Relative Humidity Sensor Mounted in a BAPI Enclosure The relative humidity sensor is designed to be mounted outdoors. The UV-resistant plastic shield keeps the sensor protected from weather and sunlight and allows for excellent air circulation. Mount the BAPI enclosure with the sensor pointing down. Plug any holes in the enclosure to make it weather-tight. Inside the cover are red and black wires which must be extended to the weather station enclosure. AlsoEnergy recommends using outdoor shielded Cat 5 and splicing with filled 3M Scotchlok Connectors. Connect humidity sensor wires to the terminals on the weather station per the table below. Table 4-15. Terminal wiring guide for relative humidity sensor. Wire Color Terminals Function Red +24V Out (P1) +24V Black MOD TEMP (P4) Signal Barometric Pressure This barometric pressure sensor is designed to be mounted indoors and is usually mounted and wired in the remote weather station enclosure prior to shipping. If the barometric pressure sensor is field installed, connect the sensor wires to the terminals on the weather station per the table below. Table 4-16. Terminal wiring guide for the barometric pressure sensor. Wire Color Terminals Function Red +24V Out (P2) +24V White AMB TEMP (P6) Signal Rain Collector The rain collector is designed to be mounted outdoors on a level surface, away from overhead obstructions and any object that is attracted to a magnet. An unobstructed path for water runoff from the drain screen is also needed. Connect the rain collector wires to the terminals on the weather station per the table below. Table 4-17. Terminal wiring guide for rain collector. Wire Color Terminals Function Red D1 (P16) N/O Green AGND (P15) Ground ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 36 General Installation Guide IMT - Silicon Irradiance Sensor Silicon irradiance sensors (Si sensor) is a cost-effective, but rugged and reliable solution for the measurement of solar irradiance, especially for the monitoring of Photovoltaic (PV) systems. Setup and mounting The reference cell is to be mounted directly to the array, see mechanical drawing for exact bolt pattern, Figure 49. The reference cell is designed to accommodate one auxiliary temperature (ambient or module) and one wind speed sensor. Dual temperature sensors are not supported. If a temperature sensor is to be used it should be mounted to the back of the reference cell away from the edge of the array. Table 4-18. IMT wiring scheme IMT Device Cable Wire Color RED BLACK BROWN ORANGE BLACK (THICK) Signal SUPPLY POWER POSITIVE SUPPLY POWER NEGATIVE RS484 DATA + RS484 DATA SHIELD Figure 4-9 Mechanical drawing of IMT reference sensor ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 37 General Installation Guide 5.0 Installation Verification and Operation After all the connections have been made, the Internet is connected and active at the data logger, and power is on to the whole system, please call AlsoEnergy for installation verification. If there are any issues with the installation, see Section 6 – Troubleshooting, or call AlsoEnergy Support. 6.0 Troubleshooting This section provides steps in solving a known problem in the monitoring system. Contact AlsoEnergy for verification of the monitoring system after the Internet is connected at the data logger and site power is on. 6.1 Elkor Mark II Meter 6.1.1 Elkor Mark II Status Indicators PWR – Green ‘power ON’ LED indicates the presence of power supply to the transducer. DIAG – Red Wiring Diagnostic LED • LED will flash quickly (10 times per second) if the voltage inputs are below the 20V threshold. • Repeating Double-Flash: Hardware error (contact Elkor for support) 6.2 PowerLogger 1000 6.2.1 Screen Calibration If there are issues with the touchscreen interface, screen calibration can be accessed by tapping the screen 3 times during startup. 6.2.2 No PowerTrack Connection Check the Last Upload and Last Heartbeat on the main screen. The device should heartbeat every 3-5 minutes. If not, there is likely a network configuration issue or cable issue. • • • Select Network. Net Type should typically be DHCP. If set to static, ensure that the logger’s IP address, subnet mask, and gateway match the information on the single-line diagram. Check that the cell modem or other Internet connection is online. Check cable. 6.2.3 RS-485 Devices Not Responding in PowerTrack • Navigate to Utilities -> Port Tools > Port Scan. • Select Baud Rate 9600, press Start. The output will show “OK” for any device addresses that have been detected on the bus. o If “ERR” shows for a device that should be detectable, there is probably a physical layer issue, e.g., wiring. Check the RS-485 bus. o If “OK” but no device in PowerTrack after 30 minutes, contact AlsoEnergy Support. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 38 General Installation Guide 6.3 MOXA Data Logger 6.3.1 MOXA Data Logger Lights Use the following table to understand the lights on the data logger. Name Power SD Port 1 Transmit Indication Green Green Green Port 1 Receive Yellow Port 2 Transmit Green Port 2 Receive Yellow Network Connection Link Green Yellow Network Connection Activity Green Diagnostic Network Link Green Yellow Diagnostic Network Activity Green Condition Solid Solid Flashing 1/minute Flashing 1/minute Flashing 1/minute Flashing 1/minute Solid Solid Flashing 1/min Solid Solid Flashing 1/min Description Data Logger Powered ON SD Card Present Transmitting to Devices Connected to Port1 Receiving from Devices Connected to Port1 Transmitting to Devices Connected to Port2 Receiving from Devices Connected to Port2 100Mb link Established 10Mb link Established Data Transfer 100Mb link Established 10Mb link Established Data Transfer 6.3.2 MOXA Data Logger Beeps The data logger will beep on power-on (two short beeps) and after about one minute of operation (three short beeps). Other beeps alert the user to possible problems. Beeps Two Short Three Short Two Long Three Long Four Long One Long, Two Short Two Long, Two Short Condition Power On Startup Complete No Network No IP AlsoEnergy.com Failed IP Issue Resolved SD Card Not Detected Description Power-On Self-Test Passed Startup has Succeeded Check Cable and Network Connection Unable to Obtain IP Address Check Status of Network and DNS Data Logger Resolved IP Remove Power, Cycle SD Card Seating, Restart ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 39 General Installation Guide 6.4 Data Logger Power Issues 6.4.1 Verify AC Power at DIN Mounted Circuit Breaker • Using a voltmeter, check if AC power is present. Refer to the supplied single-line drawing. • If AC power is not present, check the status of feeder fuses and circuit breakers. • Otherwise, refer the issue to a licensed electrician. 6.4.2 Verify DC Power at Data Logger • Using a voltmeter, verify 12-24VDC is present on the data logger, and meters. Check DIN mounted power supply for green status light. Refer to the supplied single-line drawing. • If DC power is not present, check the breaker in the terminal block. • If the breaker is good, disconnect AC power and disconnect all loads. Reconnect AC power. If DC power is still not present on the output of the power supply, replace the power supply. • Otherwise individually reconnect DC power to each load until the faulty load is identified. 6.5 Data Logger Does Not Communicate with an End Device • • • • • • Refer to the supplied single-line drawing. Verify power at the device. Verify Modbus wiring to the device. o If channels appear correctly arranged, but there is still no communication, attempt to switch the RS485 lines. Note the starting configuration. Verify device Modbus address and communication parameters. Refer to the appropriate installation document supplied by AlsoEnergy for inverter configuration. If this does not resolve the communication problem, contact AlsoEnergy to troubleshoot the device. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 40 General Installation Guide 6.6 RS-485 Modbus Troubleshooting Most problems are caused by improper or broken wiring. If you have a daisy chain of devices and only the first three are showing up, then there is likely a problem at device three or at device four. 1. Verify the Modbus connections are secure, and enough insulation is removed. 2. If using solid-strand wire, verify that the wires are not broken in insulation. 3. Verify that devices are daisy-chained and not in a star configuration, i.e. maximum of two wires on any terminal. 4. Verify the data logger is powered up. 5. If the RS-485 cable length is longer than 30 feet, verify that shielded cable is used, and the shield is grounded at only one end. 6. If a device does not respond, try reversing data+ and data- to see if the device will respond. (no damage will occur) 7. Make sure the port card is properly connected to the device(s). 8. Proper grounding should be observed over longer runs/noisy environments. 9. Often devices will specify the terminal connections as A/B instead of +/-. Usually, A is connected to – and B is connected to +. However, there may be an instance where this is reversed. Check the user manual of the device(s) in question. 10. Make sure that each device is assigned a unique address, and that the address of the unit in question is identical to the configuration as shown on the single-line diagram. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 41 General Installation Guide 6.7 Weather Station The AlsoEnergy Weather Station consists of sensors that connect to an integrated Signal Conditioner / Digitizer. The digitizer connects to the AlsoEnergy Data Logger via a Modbus connection. 6.7.1 Weather station communication issues • Check the data logger is working o Power light is illuminated o SD and Modbus lights flash when in use • Check the Power light on the weather station • Check Modbus Address • Check RS-485 connection, + to +, - to • Check that Receive and Transmit lights flash 6.7.2 Weather Station sensors If the weather station is communicating, but sensor readings are wrong, check the sensor troubleshooting listed below. - Temperature Sensors • Measure the voltage between the terminals where the sensor is connected. It should be between +18 and +22 VDC. If it is not, replace the signal conditioner / digitizer assembly. - Ambient Temperature (4-20mA, -29°C to 49°C) • Voltage test to determine if the sensor is malfunctioning: o Measure the voltage between the terminals where the sensor is connected. o The voltage should be about 4.2V at 80° F. If the voltage is less than 1V, the sensor is not connected, or needs to be replaced. If the voltage is higher than 5V, inspect the black card in the thermometer housing for damage. If no damage is visible swap the input from the ambient and module to verify the location of the issue. If the high voltage follows the thermometer, replace the temperature module. If the high voltage is stationary, replace the digitizer and the signal conditioner. • mA test to confirm the sensor is malfunctioning: o Confirm wiring and splices are connected o Place a milliamp meter in line with the return (black) wire from sensor to the GND terminal on the conditioner card o The meter should read around 15mA for 80 degrees F. • If these steps do not work, please call AlsoEnergy for service. - Module Temperature (4-20mA, -40°C to 85°C) • Voltage test to determine if the sensor is malfunctioning: o Measure the voltage between the terminals where the sensor is connected. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 42 General Installation Guide o • • The voltage should be about 3.3V at 80° F. If the voltage is less than 1V, the sensor is not connected, or needs to be replaced. If the voltage is higher than 5V, inspect the black card in the thermometer housing for damage. If no damage is visible swap the input from the ambient and module to verify the location of the issue. If the high voltage follows the thermometer replace the temperature module. If the high voltage is stationary, replace the digitizer and the signal conditioner. mA test to confirm the sensor is malfunctioning: o Confirm wiring and splices are connected o Place a milliamp meter in line with the return (black) wire from the sensor to the GND terminal on the conditioner card o The meter should read around 12.5mA for 80 degrees F. If these steps do not work, please call AlsoEnergy for service. - Wind Direction The voltage between Wind Direction P10 GRN and P11 Red indicates the direction the wind vane is pointing: 0V for North, 0.625V for East, 1.25V for South and 1.875V for West. If the Wind Direction is incorrect, check the voltage between P12 YEL and P14 Blk. It should be 2.5V. If it is not, remove the P12 YEL sensor wire and re-measure P12 YEL to P14 Blk. If it is 2.5V, replace the wind vane / anemometer assembly. Otherwise, replace the integrated weather station. Rotate the wind vane. The voltage between wind direction P10 GRN and P11 Red should change. If it does not, remove the sensor wire on P10 GRN and repeat the test. If the voltage changes, replace the integrated weather station; otherwise, replace the wind vane. - Calibrate the Wind Vane • Slowly turn the wind direction shaft until the voltage between J4 Wind Direction GRN and Red is zero • Being careful to keep the stainless steel shaft from turning, place the wind vane on the shaft with the bullet-shaped nose of the vane pointing north • Slide the wind vane down onto the shaft as far as it will go • Use the Allen wrench provided to tighten the set screw on the side of the wind vane - Wind Speed The P1 LED on the digitizer card flashes once per revolution of the anemometer cups. If it does not, disconnect the P14 Wind Spd BLK wire. The LED should be OFF. With a short piece of wire, connect Wind Speed terminals P11 to P14. The LED should be on. If the LED toggles, the wind sensor or its wiring is bad. Otherwise, replace the integrated weather station. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 43 General Installation Guide - Pyranometer Scale If the scale of the pyranometer data appears to be off by roughly a scale of 10 (i.e., 120 W/m2 during full sunlight), the gain may be off. Unscrew the two screws on the front side of the AlsoEnergy weather station digitizer. Remove the cover and note two sets of DIP switches on the upper left side of the board. See photo below. The leftmost pair of switches sets the channel gain for POA sensors. The rightmost pair sets the channel gain for GHI sensors or wind sensors. Ensure that the gain is set correctly according to the table below: Left switch Down Down Up Up Right switch Down Up Down Up Gain 101 10.091 1 1 Use Low level pyranometers (Kipp & Zonen, Hukseflux, LiCor) High-level pyranometers (Apogee) Wind direction input Wind direction input ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 44 General Installation Guide - Apogee Pyranometer Measure the voltage between the terminals marked J3 pyranometer SIG and RET on the signal conditioner card. Refer to figure 2 for terminal markings. The voltage should be between 0.00V in total darkness and 0.260V DC in full sun. If it is not, disconnect the SIG lead and measure it. If the voltage does not lie between these values, the Apogee pyranometer is defective and should be replaced. Otherwise, replace the Signal Conditioner / Digitizer assembly. 7.0 Operations & Maintenance At least once every 6 months: • Check Desi pack indicators and change if necessary • Check for water intrusion Additionally: • Pay subscription and data plan renewals when due (typical plans are 1 and 5 years) • Follow recalibration recommendations for meters and sensors ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 45 General Installation Guide Appendix A – RJ45 Wiring Guide Standard, Straight-Through Wiring (both ends are the same) OR Crossover Wiring (one end wired T568B – other end wired T568A) Jack Head T568B- Standard Wiring RJ45 Pin # Wire Color Wire Diagram 10Base-T Signal 1000Base-T Signal (T568B) (T568B) 100Base-TX Signal 1 White/Orange Transmit+ BI_DA+ 2 Orange Transmit- BI_DA- 3 White/Green Receive+ BI_DB+ 4 Blue Unused BI_DC+ 5 White/Blue Unused BI_DC- 6 Green Receive- BI_DB- 7 White/Brown Unused BI_DD+ 8 Brown Unused BI_DD- T568A RJ45 Pin # Wire Color Wire Diagram 10Base-T Signal 1000Base-T Signal (T568A) (T568A) 100Base-TX Signal 1 White/Green Transmit+ BI_DA+ 2 Green Transmit- BI_DA- 3 White/Orange Receive+ BI_DB+ 4 Blue Unused BI_DC+ 5 White/Blue Unused BI_DC- 6 Orange Receive- BI_DB- 7 White/Brown Unused BI_DD+ 8 Brown Unused BI_DD- ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 46 General Installation Guide Appendix B - Data Logger Networking Considerations The data logger gathers data from devices and sends the data over the internet to a hosted database: 1. The Data Logger (DL) powers up 2. The DL gets its IP address via either DHCP or its static assigned network configuration. Contact AlsoEnergy™ for the correct documentation for configuring the DL environment. 3. The DL resolves www.AlsoEnergy.com via DNS services. 4. The DL periodically updates its real-time clock using network time services. 5. The DL contacts AE Web Services (AEWS) supplying its MAC address and current code version. 6. The AEWS responds as: 6.1. The code is not correct. Update the program with the code that follows then reboot. 6.2. The code is correct. Configuration data follows. 7. The DL uses the configuration data to query devices connected to it. 8. The DL packetizes the received device data and sends it to the AEWS via TCP. 9. The DL sleeps for the configured length of time. 10. The DL wakes up and repeats the process at step 3. Ports The DL is designed to exist in a DHCP or static IP environment behind a firewall. It does not need an external internet IP address or ports forwarded. This table shows the unique ports opened. Inbound Ports Outbound Ports ✓ HTTP: Port 80 (TCP) ✓ HTTPS: Port (443) TCP ✓ SNTP: Port 123 (UDP) ✓ SMTP Port 25 (TCP) FTP: Port 20 & 21 (TCP) Only if local diagnostic PC present Telnet: Port 23 (TCP) Only if local diagnostic PC present ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 47 General Installation Guide Appendix C – Connecting To AcquiSuite 1. Check to see if the AcquiSuite is connected directly to a modem (or cable run to an inaccessible location) or to an easily accessible Ethernet switch. 1.1. If the AcquiSuite is connected directly to a modem (or a cable run to an unknown/inaccessible networking location), continue to step 2. 1.2. If the AcquiSuite is connected to an easily accessible Ethernet switch, connect your laptop to that same Ethernet switch, then skip to step 5. 2. Disconnect the Ethernet connection between the AcquiSuite and LAN/modem, then connect your laptop directly to the AcquiSuite with an Ethernet cable. (not crossover cable, just a standard patch cable) 3. Check the IP address listed on the AcquiSuite. The IP address should cycle through on the screen every minute or so. 4. Now you’ll need to adjust your Laptop’s IP configuration to match the IP settings used on the AcquiSuite to see it in your laptop’s web browser: 4.1. Windows 10 ONLY: On your laptop, do a search for “Settings” and hit Enter to open your Windows Settings Menu. Then click on the “Network & Internet” option. On the left side of the screen, click “Ethernet” and then click “Change adapter options” in the top right corner. Skip to step 4.3. 4.2. Windows 7 ONLY: From the Windows Start menu, do a search for “Network and Sharing Center” and press enter. 4.2.1. A window like the one shown below should pop up. Click on “Change adapter settings” in the top right, highlighted below. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 48 General Installation Guide 4.3. This should display a “Network Connections” window like the one shown below. Right-click on the appropriate connection device and click “Properties”. NOTE: The number of devices shown here will vary depending on your laptop. You should look for a connected device called “Ethernet” or “Local Area Connection” 4.3.1. Double click on “Internet Protocol Version 4 (TCP/IPv4)” as shown below. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 49 General Installation Guide 4.3.2. The window shown below should pop up. Click on “Use the following IP address” 4.3.3. Next, set your computer to the same network as the AcquiSuite by inputting a unique IP address on the same network range. For example; if the Acquisuite IP address is 192.168.50.12, then you could set your laptop’s IP address to 192.168.50.13 or something similar. Your laptop needs to be on the same IP range as the AcquiSuite, but cannot use the exact same address. Lastly, click on the “Subnet Mask” field and Windows should auto-fill the appropriate subnet mask for you. Do not worry about filling in the gateway or DNS information. Click OK and then also click OK on the previous window from step 4.3.1. 5. Open a web browser. In the address bar at the very top of the window, type the IP address from the AcquiSuite. 6. If all the proper steps were taken, the window below should pop up. Click on the “Click here for System Configuration” option. 6.1. NOTE: If the window below does not appear and you see a connection error message instead; whether you are connecting to the AcquiSuite through an Ethernet switch OR directly, go back to step 2 and proceed from that point. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 50 General Installation Guide 7. A login prompt will appear. The username will be “admin” and the password should be one of the three passwords listed below IF the device was supplied by AlsoEnergy. 7.1. The AlsoEnergy default password is “changeme” 7.2. The factory default password is “admin” 7.3. The DECK Monitoring default password is “deckXXXX” (where “XXXX” is the last 4 characters of the AcquiSuite serial number) Note: If the XXXX portion contains letters, they should be capitalized. The “deck” portion should always be lowercase. 8. To ensure the AcquiSuite is uploading to the right servers, go to Log File Data > Setup / Upload as seen below. Then add the PowerTrack or DECK server URL and password into the respective fields in Channel 1. PowerTrack Upload URL - http://dataobvius.alsoenergy.com/aeservlet/obvius.handler Password - Ru4FpEf3 DECK Monitoring Upload URL - http://data.deckmonitoring.com/upload.php Password – password LocusNOC Upload URL – https://data01.datareadings.com/ObviusApp/AcquiSuiteListener Password – password LocusNOC through an RV50 Upload URL – http://obvius-listener-staticip.datareadings.com/ObviusApp/AcquiSuiteListener Password – (leave password blank) ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 51 General Installation Guide AlsoEnergy SupportTrack Direct access 7 days a week to best-in-class support resources and specialists Open a case at www.alsoenergy.com/wp/support For Onsite Appointments If you know you are going to be onsite, it’s best to schedule an appointment beforehand with our call center support staff. Use our easy scheduling tool.at alsoenergysupport.setmore.com/ If you would like to schedule a site visit from an AlsoEnergy Field Technician, please send an email to onsiteservice@alsoenergy.com. For phone assistance Contact us at 866-303-5668 Weekdays: 8 am – 9 pm US-EST Weekends: 11 am – 7 pm US-EST Software Training For video tutorials, login to PowerTrack and go to the Help menu. Request 1-to-1 training: alsoenergytraining.setmore.com Explore the self-guided options with the Software Onboarding Course kb.alsoenergy.com/article.php?id=168&oid=128 NOTE: Use your PowerTrack username and password to login to the KB. ALSO ENERGY INC - 5400 AIRPORT BLVD STE 100 - BOULDER, CO 80301 - WWW.ALSOENERGY.COM - 866-303-5668 - v13 52