Key plan: Mention the Shop Drawing/As Built ref for the fire protection LEGEND NEW PENDANT SPRINKLER 1/2 '' RECESESED PENDANT SPRINKLER HEAD K-5.6, 680c,QUICK RESPONSE MAKE:SHIELD,MODEL NO:SD1030(QR)/ SIN NO:SD1030(QUICK) RELOCATED PENDANT SPRINKLER 1/2 '' RECESESED PENDANT SPRINKLER HEAD K-5.6, 680c,QUICK RESPONSE MAKE:SHIELD,MODEL NO:SD1030(QR)/ SIN NO:SD1030(QUICK) CONNECT TO EXISTING FIRE ZONE CONTROL VALVE REFER TO DWG. NO. MTC-FP-02-TB-L1.0-513-001 FE EXISTING PENDANT SPRINKLER 0 1/2 '' RECESESED PENDANT SPRINKLER HEAD K-5.6, 68 c,QUICK RESPONSE MAKE:SHIELD,MODEL NO:SD1030(QR)/ SIN NO:SD1030(QUICK) EXISTING UPRIGHT SPRINKLER 1/2 '' UPRIGHT SPRINKLER HEAD K-5.6, 680c,QUICK RESPONSE MAKE:SHIELD,MODEL NO:SD1032(QR)/ SIN NO:SD1032(QUICK) PF Comments: 1) Shop drawing shall be submitted in Stage2 drawing template. 2) Grid and Dimensions shall be provided. 3) Fire fighting Contractor name shall be provided. 4) New modified rooms shall be clouded. FE FIRE EXTINGUISHER DRY POWDER 4.5 KG FIRE EXTINGUISHER DRY Co2 ,5 KG FE General Notes & Legends: 1-ALL PIPE SIZE SHOWN ARE NOMINAL PIPE DIAMETER IN MILLIMETERS. 2-ALL OPENINGS IN THE SLABS SHALL BE SEALED AGAINST AIR AND WATER INGRESS. 3-FINAL SETTING OUT OF ALL SERVICES WITH IN THE FALSE CEILING TO BE COORDINATED WITH THE RESPECTIVE CONTRACTORS/ARCHITECTS AND APPROVED RCP. Remove this DRY Chemical Powder 4-UPRIGHT SPRINKLER SHALL BE USED IN AREAS WITHOUT FALSE CEILING OR ABOVE FALSE CEILING AREA. 5-SPRINKLER SYSTEM DESIGN IS BASED ON NFPA-13 HAZARD CLASSIFICATION EXISTING PIPE 6-PIPE EXPANSION JOINT ASSEMBLY SHALL BE PROVIDED WHERE EVER IT IS REQUIRED. NEW PIPE House of Expertise Review Status CODE 1 – No Exception Taken CODE 2 – Exception As Noted, Revise & Resubmit for Record CODE 3 – Exception: Revise & Resubmit Accordingly CODE 4 – Rejected CODE 5 – Review Not Required Reviewed by: Ramesh T.R Date: 29-08-2023 Jayakumar Reviewed for Fire and Life Safety S.No ,Drawing Number ,Rev and Drawing Title for the Fire fighting Shop Drawing and AS BUILT CLINIC AREA ROOM NAME 00 MTB CLINIC , L1.0 - APRON , SECTOR 513 28.08.2023 Rev. No. Description Date Submittal Reference: Owner: HAZARD CLASSIFICATION DENSITY L/M/SQ.M Project Management: 00 00 CLINIC AREA 6.1 lpm/m2 ORDINARY GR-1 Consultant : Text and image Not clear Fire extinguishers shall be installed in easily visible and unobstructed area. Main Contractor: FE Project Name : FIT OUT WORKS FOR MTB CLINIC MODIFICATION nurse counter Show the Fitting Project Description : Provide Typical detail for Recessed Pendent sprinkler as the proposed additional sprinkler is Recessed Pendent type. MTB CLINIC , L1.0 - APRON , SECTOR 513 guard rail / wall protection Drawing Title : 0000 FIRE FIGHTING LAYOUT Typical Details for Fire Extinguisher Fixing Drawing No : Revision No: MTC.052B.2.F200.L100.S513.00001 0000 00 Submission Date : FE Show the Fittings Scale / Sheet : 1:55 @ A1 19.08.2023 Remove this Section drawing and provide the ceiling type as existing at site. There is no baffle ceiling in that area. Project Id : Plan Id : Design by Drawn by Armstrong FE ENGINEERS REVIEW STATUS FE FE EXCEPTIONS AS NOTED, CODE 2: REVISE & RESUBMIT FOR RECORD CODE 3: REVISE & RESUBMIT FE CODE 4: REJECTED REVIEW NOT REQUIRED REVIEWED BY Mention the Shop Drawing/As Built ref for the fire protection CONNECT TO EXISTING FIRE ZONE CONTROL VALVE REFER TO DWG. NO. MTC-FP-02-TB-L1.0-513-001 SDS NO: DATE Khaleel Eng.Mohanned SITE NORTH 0 N CODE 1: NO EXCEPTION TAKEN FE Checked by Official Use Only : 100 200 400 DRAWING SCALE: 1cm=100m