Key plan:
Mention the Shop Drawing/As
Built ref for the fire protection
LEGEND
NEW PENDANT SPRINKLER
1/2 '' RECESESED PENDANT SPRINKLER HEAD K-5.6, 680c,QUICK RESPONSE
MAKE:SHIELD,MODEL NO:SD1030(QR)/ SIN NO:SD1030(QUICK)
RELOCATED PENDANT SPRINKLER
1/2 '' RECESESED PENDANT SPRINKLER HEAD K-5.6, 680c,QUICK RESPONSE
MAKE:SHIELD,MODEL NO:SD1030(QR)/ SIN NO:SD1030(QUICK)
CONNECT TO EXISTING
FIRE ZONE CONTROL VALVE
REFER TO DWG. NO. MTC-FP-02-TB-L1.0-513-001
FE
EXISTING PENDANT SPRINKLER
0
1/2 '' RECESESED PENDANT SPRINKLER HEAD K-5.6, 68 c,QUICK RESPONSE
MAKE:SHIELD,MODEL NO:SD1030(QR)/ SIN NO:SD1030(QUICK)
EXISTING UPRIGHT SPRINKLER
1/2 '' UPRIGHT SPRINKLER HEAD K-5.6, 680c,QUICK RESPONSE
MAKE:SHIELD,MODEL NO:SD1032(QR)/ SIN NO:SD1032(QUICK)
PF Comments:
1) Shop drawing shall be submitted in Stage2 drawing template.
2) Grid and Dimensions shall be provided.
3) Fire fighting Contractor name shall be provided.
4) New modified rooms shall be clouded.
FE
FIRE EXTINGUISHER DRY
POWDER 4.5 KG
FIRE EXTINGUISHER DRY
Co2 ,5 KG
FE
General Notes & Legends:
1-ALL PIPE SIZE SHOWN ARE NOMINAL PIPE DIAMETER IN
MILLIMETERS.
2-ALL OPENINGS IN THE SLABS SHALL BE SEALED
AGAINST AIR AND WATER INGRESS.
3-FINAL SETTING OUT OF ALL SERVICES WITH
IN THE FALSE CEILING TO BE COORDINATED WITH THE
RESPECTIVE CONTRACTORS/ARCHITECTS AND APPROVED RCP.
Remove this
DRY Chemical Powder
4-UPRIGHT SPRINKLER SHALL BE USED IN AREAS
WITHOUT FALSE CEILING OR ABOVE FALSE CEILING AREA.
5-SPRINKLER SYSTEM DESIGN IS BASED ON
NFPA-13 HAZARD CLASSIFICATION
EXISTING PIPE
6-PIPE EXPANSION JOINT ASSEMBLY SHALL BE
PROVIDED WHERE EVER IT IS REQUIRED.
NEW PIPE
House of Expertise Review Status
CODE 1 – No Exception Taken
CODE 2 – Exception As Noted,
Revise & Resubmit for Record
CODE 3 – Exception: Revise &
Resubmit Accordingly
CODE 4 – Rejected
CODE 5 – Review Not Required
Reviewed by: Ramesh
T.R
Date: 29-08-2023
Jayakumar
Reviewed for Fire and Life Safety
S.No ,Drawing Number ,Rev and
Drawing Title for the Fire fighting
Shop Drawing and AS BUILT
CLINIC AREA
ROOM NAME
00
MTB CLINIC , L1.0 - APRON , SECTOR 513
28.08.2023
Rev. No.
Description
Date
Submittal
Reference:
Owner:
HAZARD CLASSIFICATION
DENSITY L/M/SQ.M
Project Management:
00
00
CLINIC AREA
6.1 lpm/m2
ORDINARY GR-1
Consultant :
Text and image Not clear
Fire extinguishers shall be
installed in easily visible and
unobstructed area.
Main Contractor:
FE
Project Name :
FIT OUT WORKS FOR MTB CLINIC MODIFICATION
nurse counter
Show the Fitting
Project Description :
Provide Typical detail for Recessed Pendent
sprinkler as the proposed additional sprinkler is
Recessed Pendent type.
MTB CLINIC , L1.0 - APRON , SECTOR 513
guard rail /
wall protection
Drawing Title :
0000
FIRE FIGHTING LAYOUT
Typical Details for Fire Extinguisher
Fixing
Drawing No :
Revision No:
MTC.052B.2.F200.L100.S513.00001
0000
00
Submission Date :
FE
Show the Fittings
Scale / Sheet :
1:55 @ A1
19.08.2023
Remove this Section drawing and provide
the ceiling type as existing at site. There
is no baffle ceiling in that area.
Project Id :
Plan Id :
Design by
Drawn by
Armstrong
FE
ENGINEERS REVIEW STATUS
FE
FE
EXCEPTIONS AS NOTED,
CODE 2: REVISE & RESUBMIT
FOR RECORD
CODE 3: REVISE & RESUBMIT
FE
CODE 4: REJECTED
REVIEW NOT REQUIRED
REVIEWED BY
Mention the Shop Drawing/As Built ref for the
fire protection
CONNECT TO EXISTING
FIRE ZONE CONTROL VALVE
REFER TO DWG. NO. MTC-FP-02-TB-L1.0-513-001
SDS NO:
DATE
Khaleel
Eng.Mohanned
SITE NORTH
0
N
CODE 1: NO EXCEPTION TAKEN
FE
Checked by
Official Use Only :
100
200
400
DRAWING SCALE: 1cm=100m