INSTRUMENT INDEX WITH ALARM AND TRIP SCHEDULE INPUT OUTPUT LIST D C B A REV. 18.02.2023 24.01.2023 17.09.2022 17.08.2022 DATE NJ NJ NJ NJ ORIGINATOR ASG DM ASG DM ASG DM ASG DM REVIEWED APPROVED Issued for Review Issued for Review Issued for Review Isused for Review DESCRIPTION Page 1 of 2 INSTRUMENT INDEX WITH ALARM AND TRIP SCHEDULE Sr No Tag No (new) Instrument PID No Line/Equp no Type/Action Electronics type BAE-535005" S14 pressure MA-DW-0003 transmitter / PID control for dump control valve Process fluid Service Measuring SET POINT Range 0 to 20 kg/cm2g 16 kg/cm2g Location Signal Type Description of Alarm Field AI NA NA PLC Soft NA 0 to 120 bar g NA Field AO NA 4-20 ma NA Field DO NA 16 Kg/cm2 g 16 Kg/cm2 g steam pressure control steam valve Field - steam 16 Kg/cm2 g Dump COPT condenser Steam to Field Dump steam COPT condenser to - Dump steam COPT condenser - Dump steam COPT condenser steam 16 kg/cm2 Dump COPT condenser Steam 1 PT5710 03 2 PIC-5710 03 PID Conroller/ Direct action control of PV5710 03 BAE-53500MA-DW-0003 NA NA 3 PY-5710 03 Electro BAE-53500pneumatic MA-DW-0003 positioner for PV 5710 03 NA 4 SOV-5710 03 Solenoid Valve BAE-53500for Quick closing MA-DW-0003 steam dump valve PV 5710 3 NA Instrument Air/4-20ma signal from PLC controller DC24V Power from PLC 5 PV-5710 03 Pressure Control BAE-53500Valve/Steam MA-DW-0003 header pressure control NA 6 SDV-5710 Shut down valve BAE-53500/ Fail Close MA-DW-0003 5" E18 6 SOV-5710 Shut down valve BAE-53500Solenoid MA-DW-0003 - - 6 ZSC-5710 Shut down valve BAE-53500Limit Switch MA-DW-0003 - 6 ZSO-5710 Shut down valve BAE-53500Limit Switch MA-DW-0003 - 7 PZT5720 03 Pressure transmitter 8 Alarms/Trips Interlocks/Control action Notes NA Close loop control with PV- 1. Present pneumatic 5710 03 controller PIC5710-03 will be replaced with new PT5710 03 2.The solenoid of Dump control valve with current power supply of 110V AC, shall be replaced with 24V DC power supply NA Direct Action control of PV- During commissioning 5710 03 controller tuning required to achive fastest response on process variable change. NA NA Smart Positioner for PV New electro pneumatic type 5710 03 positioner to replaced exiting pneumatic positioner. DC 24V NA NA NA NA NA NA Interlocked High High pressure at COPT condenser ER-HE-5720 & Low-Low Flow at Sea cooling water pump ER-PC5330 discharge 3 way control valve, if level increasing grewater than set point valve change over to cascade tank instead of circulation to maintatin level in normal operation. - NA NA NA Shutdown Field DO NA NA NA Shutdown to Field DI NA NA NA Indication to Field DI NA NA NA Indication Transmit signal and indicate pressure of ER-HE-5720 Field AI COPT condenser pressure High / High High -1 bar to 1 bar NA Alarm and Trip PZAH-5720 03 Soft signal from BAE-53500NA NA PLC/High MA-DW-0002 pressure alarm PZAHH-5720 Soft signal from NA NA NA 03 PLC/High pressure alarm PZAL-5720 03 Soft signal from NA NA NA PLC/High pressure alarm PG-5720-05 Pressure guage BAE-535005" E18 Steam MA-DW-0002 FZT-5330 Electronics BAE-5240016" W139 / ER- Sea water transmitter MA-DW-0001 PC-5330 COPT Condenser pressure measurement COPT Condenser pressure measurement COPT Condenser pressure measurement Pressure of ER-HE5720 Transmit signal and indicate flow of ERPC-5330 discharge flow PLC Soft COPT condenser high pressure NA (53 cmHg) Alarm High pressure alarm only for operator attention PLC Soft COPT condenser high high pressure NA (60 cmHg) Alarm & shutdown Interlocked with PV 5710 03 & SDV 5720 PLC Soft COPT condenser low vaccum NA (-10 cmHg) Alarm Low vacuum alarm only for operator attention NA NA -1 bar to 1 bar NA Field AI SW cooling pump flow indication 13 FZAL-5330 BAE-5240016" W139 / ER- Sea water Soft signal from MA-DW-0001 PC-5330 PLC/Low flow alarm Transmit signal and indicate flow of ERPC-5330 PLC Soft Sea cooling water pump discharge flow Low NA 600 m3/h Alarm 14 FZALL-5330 Soft signal from BAE-5240016" W139 / ER- Sea water PLC/Low low MA-DW-0001 PC-5330 flow alarm Transmit signal and indicate flow of ERPC-5330 PLC Soft Sea cooling water pump discharge flow Low Low NA 500 m3/h Trip Electronics transmitter BAE-5240016" W139 / ER- Sea water MA-DW-0001 PC-5330 Field AI NA BAE-52400MA-DW-0001 NA PLC Soft BAE-52400MA-DW-0001 NA Sea water supply to COPT condenser PLC BAE-52400MA-DW-0001 NA Sea water supply to COPT condenser PLC Transmit signal and indicate level of ERHE-5720 Level Control of COPT condenser condensate Field AI Sea cooling water 0 Bag to 3 Barg pump discharge pressure Low and Low Low SW Cooling pump NA discharge pressure low alarm SW Cooling pump NA discharge pressure low alarm SW Cooling pump NA discharge pressure low alarm COPT condenser 0% to 100% condensate level 0-700 mm NA Soft signal from PLC/Low pressure alarm Soft signal from PLC/Low Low pressure alarm Soft signal from PLC/High pressure alarm Magnetostrictive Level Transmitter PID Conroller/ Direct action control of LV5720 Transmit signal and indicate pressure of ER-PC-5330 discharge. Sea water supply to COPT condenser NA NA PLC Soft NA 50% 80%* 9 10 11 12 15 PZT-5300 16 17 18 PZAL-5300 PZALL-5300 PZAH-5300 19 LT-5720 01 20 LC-5720 01 21 LY-5720-01 22 AIT-5720 (Salinity Analizer) 23 AI-5720 PLC Indication 24 AIH-5720 BAE-53500ER-HE-5720 MA-DW-0002 COPT condenser Steam NA NA NA to Soft Soft 7 Bar g for normal operation, 12 Bar for offtake/IG operation. Interlock with FZALL 5330 New shutdown valve of SIL 2 and PZAHH5720-03. It will rated to be installed be closed and will stop downstream of PV5710-03 dumping steam to condenser Interlocked with PV 5710 Present pneumatic switch 03 & SDV 5720 PS5720-03/04 will be replaced with PZT 5720 03 NA Suggest to select magnetic type flow meter, due to no straight piping orifice based flow measurement is not possible. Set point to be reviewed based on the actual flow measurement after new flow meter installed & commissioned 0 to 1200 m3/h Interlock with PV5710-03 and new SDV 5710 to stop dumping steam to condenser Alarm 1.2 Bar g Alarm/Trip 1.0 Bar g Alarm 2.2 Bar g BAE-53500ER-HE-5720 MA-DW-0002 Condensate BAE-53500ER-HE-5720 MA-DW-0002 NA BAE-53500ER-HE-5720 MA-DW-0002 Condensate regulate valve as per LIC output. Field AO COPT condenser condensate level BAE-53500ER-HE-5720 MA-DW-0002 Condensate Field AI NA 0-200 ppm 4-20 ma NA NA BAE-53500ER-HE-5720 MA-DW-0002 Condensate PLC Soft Salinity Indication 0-200 ppm NA NA * Soft signal for BAE-53500ER-HE-5720 high salinity MA-DW-0002 valarm Condensate Transmit signal and indicate salinity of condensate in ER-HE5720 Transmit signal and indicate salinity of condensate in ER-HE5720 indicate salinity of condensate in ER-HE5720 LV 5720 01 will get open and start transferring condensate to TZ-5730 when level increase > set point. LV 5720 01 will control level in circulation mode if level is < set point. * PLC Soft High Salinity Alarm Alarm * Electropneumatic positioner Electronics type Salinity analyzer 4-20 ma NA No change, exiting control valve will be in service. NA NA NA new solenoid valve DC24V with proper power rating to match PLC DO rating. 50 ppm Page 2 of 2