Construction Specification Site Fencing Document No. 0000-10-SPE-0002 Quality Information Project Name: Oyu Tolgoi Document Company: Construction and Engineering Group (CEG) - Engineering Manager Revision History Revision 0 Issue Purpose Issued for Use Prepared By FH Approved By BP Date 01 July 2016 Oyu Tolgoi LLC Detailed Revision History Document Number 0000-10-SPE-0002 Document Type Specification Document Name Site Fencing Rev Clause No. A All Detailed Description of Changes Consolidation of CS-10-010 Rev 1 and CS-10-105 Rev 1 into 0000-10-SPE-0002 Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 2 of 15 Oyu Tolgoi LLC TABLE OF CONTENTS 1. 2. GENERAL ..................................................................................................................... 4 1.1 Summary ........................................................................................................... 4 1.2 References ........................................................................................................ 4 1.3 Storage and Protection .................................................................................... 7 1.4 Scheduling and Sequencing............................................................................ 7 1.5 Submittals ......................................................................................................... 7 PRODUCTS .................................................................................................................. 7 2.1 3. Materials ........................................................................................................... 7 EXECUTION ............................................................................................................... 12 3.1 Examination .................................................................................................... 12 3.2 Preparation ..................................................................................................... 12 3.3 Installation ...................................................................................................... 12 3.4 Grounding ....................................................................................................... 15 Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 3 of 15 Oyu Tolgoi LLC 1. GENERAL 1.1 Summary A. Scope of Specification This specification prescribes the requirements for the installation of chain link fence (galvanized or PVC coated), high tensile wire fence (galvanized) and the associated posts, rails, braces, terminal posts, gates, barbed wire, controls, and other related materials. B. Related Specifications The following specifications prescribe items of related work: 0000-10-SPE-0001 Earthworks and Roadways 0000-15-SPE-0001 Structural Steel and Other Metalwork - Fabrication and Erection 0000-15-SPE-0003 Structural Concrete and Reinforcing Coordinate work prescribed by this specification with Work prescribed by the above listed specifications. C. Terminology 1. Chain Link Fence Classification Chain link fencing shall be classified by fabric category as galvanized (zinc coated) or PVC coated (Polyvinyl chloride) galvanized steel. Wire to be referred to as galvanized or PVC coated. 2. High Tensile Wire Fence Classification High Tensile Wire Fence shall be classified by fabric category as galvanized (zinc coated) steel. Wire to be referred to as galvanized coated. 3. Barbed Wire Barbed wire for additional security shall be classified as galvanized (zinc coated) or galvanized, PVC coated. 4. NPS Nominal pipe size 1.2 References Unless stated otherwise in this specification, all design, material and equipment manufacturing, fabrication, testing, installation and construction for this project shall be in accordance with the current version of the following Mongolian standards. Additionally, the current version of standards published by the following agencies Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 4 of 15 Oyu Tolgoi LLC and institutions shall be used where applicable and not already covered by the Mongolian Standards. The publications listed below form part of this specification. Each publication shall be the latest revision and addendum in effect on the date this specification is issued for construction unless otherwise noted. Except as modified by the requirements specified herein or the details of the drawings, all Work included in this specification shall conform to the applicable provisions of these publications. A. B. C. Construction Norms and Rules of Mongolia 1 CNR 2.01-01-93 Climatic and Geophysical Parameters for Construction 2 CNR 22.01-01 Norms and Regulations on Construction Planning in Seismic Zones in Mongolia 3 CNR 2.01-07-90 Load and Effect 4 CNR 11-01-98 Regulation on Elaboration, Agreement and Confirmation of Design Documents 5 SNIP II-M.I-71 Master Plans of Industrial Enterprises 6 CNR 11-03-02 Regulations on Elaboration of Design Documents of the Construction Facilities on the Territory of Mongolia by Foreign Organizations People’s Republic of China Standards 1 GB50187-93 Code for Design of General Plan of Industrial Enterprises 2 GB/T 13912-92 Metallic Coating – Hot Dip galvanized Coating on Ferrous Product Specification 3. GB/T 139122002 Metallic Coating- Hot Dip galvanized Coating on Ferrous Product Specification ASTM American Society for Testing and Materials ASTM A53/A53M Specification for Pipe - Steel, Black, and Hot Dipped, Zinc-Coated, Welded, and Seamless ASTM A101/A101M Standard Specification for Steel, Sheet and Strip, HotRolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability, and Ultra-High Strength ASTM A116 Coated (Galvanized) Steel Woven Wire Fence Fabric ASTM A120 Specification for Pipe, Steel, Black, and Hot Dipped Zinc-Coated (Galvanized) Welded and Seamless, for Ordinary Uses ASTM A121 Specification Barbed Wire Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 for Zinc-Coated (Galvanized) Steel Page 5 of 15 Oyu Tolgoi LLC ASTM A123/A123M Specification for Zinc (Hot-Dipped Coatings on Iron and Steel Products ASTM A143 Recommended Practice for Safeguarding Against Embrittlement of Hot Dipped (Galvanized) Structural Steel Products and Procedure for Detecting Embrittleness ASTM A153/A153M Specification for Zinc Coating (Hot Dip) on Iron and Steel Hardware ASTM A392 Specification for Zinc-Coated Steel Chain Link Fence Fabric ASTM A475 Specification for Zinc-Coated Steel Wire Strand ASTM A525 Specification for General Requirements for Steel Sheet, Zinc-Coated (Galvanized) by the Hot Dip Process ASTM A570 Specification for Steel, sheet and strip, carbon, HotRolled, Structural Quality ASTM A641/A641M Specification for Zinc-Coated (Galvanized) Carbon Steel Wire ASTM A653/A653M Standard Specification for Steel Sheet and Zinc-Coated (Galvanized) or Zinc- Coated Alloy- Coated (Galvanized) by the Hot-Dip Process ASTM A809 Specification for Carbon Steel Wire ASTM A817 Specification for Metallic Coated Steel Wire for Chain Link Fence Fabric ASTM A854 Standard Specification for Metallic-coated Smooth High Tension Fence and Trellis Wire ASTM C33 Specification for Concrete Aggregate ASTM C94/C94M Standard Specification for Ready-MIXED Concrete ASTM C150 Specification for Portland Cement ASTM F567 Practice for Installation of Chain Link Fence ASTM F626 Specification for Fence Fittings ASTM F668 Specification for PVC (Polyvinyl Chloride) Coated Steel Chain Link Fence Fabric ASTM F669 Specification for Strength Requirements of Metal Posts and Rails for Industrial Chain Link Fence ASTM F934 Specification for Standard Colors for Polymer – Coated Chain Link Fence Materials Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Aluminum-Coated Galvanized) (Aluminized) Steel Page 6 of 15 Oyu Tolgoi LLC D. ASTM F1043 Standard Specification for Strength and Protective Coatings on Steel Industrial Chain Link Fence Framework ASTM F1083 Specification for Pipe, Steel, Hot-Dipped, Zinc-Coated (Galvanized), Welded for Fence Structures PIP CVS02830 Fabrication and Installation of Chain Link Fence and Gate OSHA Occupational Safety and Health Administration OSHA Construction Industry Standard, Title 29, Code of Federal Regulations, part 192, Safety and Health Regulations for Construction 1.3 1.4 Storage and Protection A. Store materials 300 mm off the ground or slab by using wood blocking or other approved materials. B. Store materials in areas of the job site designated or approved by the Company. Scheduling and Sequencing Certain portions of the work are specified to be completed and operational prior to completion of all Work. Sequence equipment and gate installation, and properly protect equipment to prevent contamination or damage to equipment in adjacent work areas. Phasing and sequencing shall be subject to the approval of the Company. 1.5 Submittals Materials are subject to testing. Mill certificates and product specification verification shall be submitted to the Company. 2. PRODUCTS 2.1 Materials A. General Fence fabric, posts, top rail, tension wire, corner posts, barbed wire, and appurtenances shall conform to the ASTM codes and standards for the appropriate type of materials as listed under Section 1.2 of this specification, and more specifically listed in the sections below. B. Materials shall be uniform, consistent, and meet the following requirements: 1. Fabric a. Galvanized fabric shall be one piece widths up to 3.6 m high, heavy galvanized chain link fence, conforming to ASTM A392, Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 7 of 15 Oyu Tolgoi LLC Class 2, of 50 mm mesh 9 gage wire (3.8 mm in diameter), with the top and bottom selvedges twisted and barbed. b. 2. Line Posts a. b. 3. PVC coated fabric shall be one piece widths up to 3.6 m high, ASTM F668, 7 mils (0.1778 mm)of thermally bonded PVC over 8.5 grams zinc substrate; 50 mm mesh 9 gage wire (3.8 mm in diameter); with the top and bottom selvedges twisted and barbed. Colors shall be in accordance to ASTM F934, (Brown). Galvanized i) For fabric up to 2.5 m high, line posts shall be 64 mm NPS schedule 40 galvanized steel pipe with an outside diameter of 60 mm in accordance with ASTM A53/A53M or 48 mm x 41 mm x 3 mm thick rolled formed C section from steel conforming to ASTM A570, grade 45 continuous coated in accordance with ASTM A525. ii) For fabric more than 2.5 m high, line posts shall be 76.2 mm NPS schedule 40 galvanized steel pipe with an outside diameter of 89 mm, in accordance with ASTM A53/A53M, or 57 mm x 43 mm x 3 mm thick C-section rolled formed from steel conforming to ASTM A570, grade 45, continuous coated in accordance with ASTM A525. iii) For high tensile wire fence, line posts shall be 76.2 mm NPS schedule 40 galvanized steel pipe with an outside diameter of 89 mm, in accordance with ASTM A53/A53M. PVC Coated i) For fabric up to 2.5 m high, line posts shall be C-section rolled from steel conforming to ASTM A570, grade 45, 48 mm x 41 mm x 3 mm thick, continuous coated in accordance with ASTM A525 and primed to receive 10 to 15 mils (0.254 – 0.381 mm) thermal fusion coating of PVC. ii) For fabric more than 2.5 m high, line posts shall be C-section rolled from steel conforming to ASTM A570, grade 45, 57 mm x 43 mm x 3 mm thick, continuous coated in accordance with ASTM A525, and primed to receive 10-15 mils (0.254 – 0.381 mm) thermal fusion coating of PVC. End, Corner and Pull Posts a. Galvanized i) Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 End, corner and pull posts 2.5 m high or less shall be 64 mm NPS schedule 40 galvanized steel pipe with an outside diameter of 73 mm in accordance with ASTM A53/A53M, or 89 mm x 89 mm x 3.4 mm thick rolled formed corner section, Page 8 of 15 Oyu Tolgoi LLC conforming to ASTM A570, grade 45, continuous coated in accordance with ASTM A525. ii) b. c. End, corner and pull posts over 2.5 m high shall be 75 mm NPS schedule 40 galvanized steel pipe with an outside diameter of 89 mm in accordance with ASTM A53/A53M. PVC Coated i) End corner and pull posts 2.5 m high or less shall be Csection rolled formed from steel conforming to ASTM A570, grade 45, coated in accordance with ASTM A525, and primed to receive 10 to 15 mils (0.254 – 0.381 mm) thermal fusion coating of PVC. ii) End corner and pull posts over 2.5 m high shall be C-section rolled formed from steel conforming to ASTM A570, grade 45, coated in accordance with ASTM A525 and primed to receive 10 to 15 mils (0.254 – 0.381 mm) thermal fusion coating of PVC. For high tensile wire fence: i) ii) 4. 5. Corner ,end and pull posts less than or equal to 2.4 m high shall be 3 inch (76.2 mm) NPS schedule 40 galvanized steel pipe with an outside diameter of 88.9mm in accordance with ASTM A53/A53M. The top rails & braces connected the end, corner and pull posts shall be 75 mm NPS schedule 40 galvanized steel pipe with an outside diameter of 88.9 mm, in accordance with ASTM A A53/A53M. Top Rails a. Galvanized top rails shall conform to 32 mm NPS schedule 40 galvanized steel pipe with outside diameter of 42 mm, in accordance with ASTM A120, or C-section rolled formed from steel conforming to 41 mm x 32 mm x 1.9 mm thick continuous coated in accordance with ASTM A525. b. PVC coated top rails shall conform to 32 mm NPS schedule 40 galvanized steel pipe in accordance with ASTM A525 and primed to receive 10 to 15 mils (0.254 –0.381 mm) thermal fusion coating of PVC. Tension Wire a. Galvanized tension wire shall be 7 gage US Steel wire galvanized in accordance with ASTM A116 coating class III. The tension wire shall be stretched near the bottom of the fence and attached at 600 mm intervals. If top rail is not used, a tension wire shall be stretched at the top also. Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 9 of 15 Oyu Tolgoi LLC 6. 7. 8. 9. b. PVC coated tension wire shall be 7 gage U.S. Steel wire galvanized in accordance with ASTM A116 and PVC coated of same quality, color, and process as specified for the fabric. The tension wire shall be stretched near the bottom of the fence and attached at 600 mm intervals. If top rail is not used, a tension wire shall be stretched at the top also. c. High Tensile wire shall be 121/2 gage steel, galvanized in accordance with ASTM A854, with a yielding strength of 200,000PSI (1380MPa). Appurtenances a. Galvanized brace bands, tension bands, and tension bars shall be fabricated of 3 mm x 22 mm galvanized steel with galvanized steel carriage bolts and nuts in accordance with ASTM A153. Tension bars shall be 6 mm x 19 mm galvanized steel bar in accordance with ASTM A123. b. PVC coated brace bands, tension bands, and tension bars shall be fabricated of 3 mm x 22 mm galvanized steel with galvanized steel carriage bolts and nuts as per ASTM A123. Tension bars shall be 6 mm x 22 mm galvanized and thermally fused PVC coated 10 to 15 mm. Fabric Ties a. Galvanized fabric ties shall be class I galvanized steel wire not less than 9 gage. b. PVC coated fabric ties shall be 9 gage, class I galvanized steel wire thermal fused and PVC coated 10 to 15 mils (0.254 – 0.381 mm). Post Tops a. Galvanized one post top shall be provided for each post, with openings to permit through passage of top rail. Materials shall be pressed steel or malleable iron that is designed as watertight closure cap for tubular posts and shall be galvanized per ASTM A153. b. PVC coated one post top shall be provided for each post, with openings to permit through passage of top rail. Materials shall be pressed steel or malleable iron that is designed as watertight closure cap for tubular posts and shall be thermally fusion coated with PVC 10 to 15 mm. Star Picket a. 1.5 inch (38.1mm) NPS schedule 40 star picket shall be galvanized steel pipe with an outside diameter of 48.3mm in accordance with ASTM A53/A53M. Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 10 of 15 Oyu Tolgoi LLC 10. 11. Barbed Wire a. Galvanized barbed wire shall consist of double stranded, 121/2 gage wire galvanized to ASTM A121 or ASTM A641/A641M, class 3, or aluminized to ASTM 585, Class II, with 14 gauge 4 point barbs spaced 125 mm apart. b. PVC coated barbed wire shall consist of 2 double stranded of 121/2 gage ASTM A121, class 3, thermally bonded PVC coated with 4 point round aluminum barbs, spaced on 125 mm centers. c. The top 300 mm of the fence shall consist of 3 strands of barbed wire attached to 45 degree angle heavy pressed arms capable of withstanding without failure 113 kg downward pull at the outermost end of the arm. Barbed wire will be installed on sections of fence as indicated on the drawings or as directed by the Company. Gates a. Galvanized Swing Gate Posts i. Gateleafs up to and including 2 m wide; 64 mm NPS schedule 40 pipe with outside diameter of 73 mm. ii. Gateleafs over 2 m and up to and including 4 m wide; 90 mm NPS schedule 40 pipe with outside diameter of 100 mm. iii. Gateleafs over 4 m and up to and including 5.5 m wide; 150 mm NPS schedule 40 pipe with outside diameter of 169 mm. iv. Gate leaves over 5.5 m and up to and including 9.1 m; 200 mm NPS schedule 40 pipe with outside diameter of 220 mm. v. Gateleafs for high tensile wire fence; 150 mm NPS schedule 40 pipe with outside diameter of 169 mm. vi. All pipes to be continuous galvanized in accordance with ASTM A120. b. c. Galvanized Gate Perimeter Frames i. Frames shall be of 38 mm schedule 40 pipe with outside diameter of 48 mm, galvanized in accordance with ASTM A53-A53M. ii. Gate materials such as fabric, bolts, nuts, tension bars, and barbed wire, shall be consistent with fence materials. iii. Gates shall be manually or electrically operated. Shop drawings for gates over 3.7 m wide shall be submitted for approval. PVC coated gate materials shall be consistent with the materials specified for PVC coated fence materials. Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 11 of 15 Oyu Tolgoi LLC C. Concrete Concrete shall be in accordance with 0000-15-SPE-0003 Structural Concrete and Reinforcing Concrete shall have a minimum of 25 MPa compressive strength at 28 days. D. Steelwork Fabrication All steelwork fabrication shall be in accordance with 0000-15-SPE-0001 Structural Steel and Other Metalwork - Fabrication and Erection. 3. EXECUTION 3.1 Examination The physical locations of features such as fence lines, and gates shall be in accordance with the Drawings. 3.2 Preparation Provide a reasonably smooth profile at the fence line. The bottom of the fence shall not be more than 50 mm above the finished ground line. Where the fence crosses features such as streams and drainage ditches and it is impractical to conform the fence to the ground contour, the fence shall span the depression, unless otherwise shown on the plans. Close the space below the bottom of the fence with extra fence fabric or barbed wire. If extra length fence posts are required at such locations, they shall be furnished and installed in lieu of standard length posts, together with any intermediate posts, stakes, braces, extra fabric, wire or other fixtures or appurtenances as may be required. 3.3 Installation A. Post Spacing Install line posts and brace posts at intervals not to exceed 3 m. Posts shall be evenly spaced. Install corner or slope posts where changes in grade exceed a 30 degree deflection. B. Installation of Line, Corner, Pull, and Terminal Posts 1. Set line, corner, pull, and terminal posts vertically in cylindrical concrete foundation in accordance with the schedule in Table 1 and in accordance with ASTM F567. For high tensile wire fence, the set line, corner, pull, and terminal posts vertically in cylindrical concrete foundation in accordance with the drawings. Table 1 Line, Corner, Pull, and Terminal Post Installation Schedule Foundation Foundation Post Diameter Depth Embedment Line post 230 mm 1.0 m 0.9 m Terminal post 300 mm 1.0 m 0.9 m Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 12 of 15 Oyu Tolgoi LLC Foundation Diameter Foundation Depth Post Embedment 64 mm 300 mm 1.0 m 0.9 m 89 mm 300 mm 1.0 m 0.9 m 150 mm 460 mm 1.2 m 1.0 m 200 mm 600 mm 1.8 m 1.6 m Gate post: C. D. 2. The exposed surface of the concrete foundation shall be a smooth 12 mm crown, sloping away from the post. The post shall be 150 mm from the bottom of the concrete pour. 3. Holes may be hand augered or drilled. Spread soil from the excavations uniformly adjacent to the fence line or as directed by the Company. If rock is encountered, drill into the rock for at least 300 mm for line posts, and 450 mm for corner or terminal posts. Drill holes 25 mm larger than the diameters as per the schedule (Refer to Table 1). If solid rock is below soil overburden, drill to full depth required, except penetration into rock need not exceed minimum depths specified. Setting Post 1. Remove any loose and foreign materials from the sides and bottoms of the holes; moisten the soil prior to placing the concrete. Center and align posts in the holes. Place the concrete in a continuous pour in the hole around the posts, and tamp to consolidate. Check post for vertical and horizontal alignment, and secure to allow proper curing of the concrete. 2. Extend footings for gate posts to the underside of the bottom of the hinge. Keep concrete surfaces moist for at least 7 days after placement, or cure with membrane curing material or other approved method. 3. Posts that are set in sleeved holes shall be grouted in place using a nonshrink portland cement grout approved by the Company. 4. Prior to placing components such as fabric, rails, tension wire, and gates, ensure that the concrete has reached at least 75 percent of the design strength stated in Section 2.1 C. or has cured a minimum of 7 days after setting the posts. Rails and Bracing 1. Install fence with a top rail and bottom tension wire. If a top rail is omitted for a temporary fence, install a top tension wire also. Top rails shall be continuous through post caps or extension arms bending to the radius for wired runs. Space 9 gage minimum fabric tie wire at 600 mm on centers. 2. Install tension wires parallel to the line of fabric by weaving wire, of not less than 6 gage, of the appropriate type through the fabric and tying to each post. Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 13 of 15 Oyu Tolgoi LLC 3. E. F. G. Install top rail and tension wire prior to installation of the chain link fabric. Provide an expansion/contraction coupling, standard with the manufacturer, every 30 m on straight runs, installed within 600 mm of a line post. Use end clamps for attaching the top rail or tension wire, and brace to the terminal and gate posts. Use corner clamps for attaching top rails or tension wire and brace to corner posts. Installing Fabric 1. Install the chain link fence fabric so that the posts are enclosed. Stretch the fabric taut, approximately 50 mm above the ground, and fasten securely to the posts. 2. Cut the fabric and attach each span independently at all terminal and corner posts. Use stretcher bars with fabric bands spaced at a maximum 380 mm intervals to fasten fabric to terminal posts. Use tie wire, metal bands, or other approved material attached at maximum 380 mm intervals to fasten fabric to line posts. Fasten the top edge of the fabric to the top rail or tension wire with wire ties at intervals not exceeding 380 mm. Fasten the bottom edge of fabric to the bottom tension wire with wire ties at intervals not exceeding 380 mm. High Tensile Wire 1. Install fence with four strands of tension wire between end/corner post, starting from bottom wire and up. 2. Cut the fabric and attach each span independently at all terminal and corner posts. Use each wire shall be stretched with 250LB (113kg) of tension. Tension in the wire is maintained by permanent in-line stretchers or tension springs. Barbed Wire Install barbed wire on gates to match that installed on the line fence. To accommodate barbed wire, extend the end members of gates 300 mm above the horizontal section of the gate frame. Space strands uniformly and attach to frame with bands, clips, or eyebolts. Incline extension arms on line posts and corner posts toward the property enclosed at approximately 45 degrees. Stretch the strands of barbed wire to remove sag, and anchor firmly to extension arms. Use 3 strands of barbed wire. Barbed wire will be installed on sections of fence as indicated on the drawings or as directed by the Company. H. Installing Gates 1. Install gates according to the locations and size indicated on the drawings. 2. Gates shall be properly braced and trussed to prevent sagging, buckling, and weaving, and shall be covered with same type of fabric as the fence. Vertical members of the gate shall carry the top of 3 strands of barbed wire. Fixed end ratchet bands shall be furnished for fastening the barbed Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 14 of 15 Oyu Tolgoi LLC wire. Furnish gates with necessary fittings and hardware. Latches provided for use with padlocks and hinges shall allow swing gates to swing 180 degrees. Plunger bars shall have top, bottom, and middle locking points with the middle point arranged for padlocking. Gates shall have keepers that engage automatically when the gate is swung open. I. 3.4 3. Install gates plumb, level, and secure for the full opening without interferences. 4. Install ground items set in concrete in accordance with gate manufacturer's recommendations. Inspect all parts and attachments for defects; and install, lubricate, and adjust equipment to ensure smooth operation. Miscellaneous Installation 1. Use U-shaped tie wires, conforming to the diameters of pipe, that clasp the pipe and fabric firmly with ends twisted at least 2 full turns. 2. Bend ends of exposed wires to minimize hazards to persons or clothing. 3. Install nuts for fasteners on tension bands, and hardware bolts on the side of the fence opposite the fabric. The ends of bolts, once secure and checked for smooth operation, shall be peened to prevent removal of nuts. 4. Repair coatings damaged in the field with methods and techniques as recommended by the manufacturer. Grounding A. Fence Fence shall be grounded at each side of every gate, at points 45 m each side of overhead power-transmission lines, at intervals of every 300 to 450 m of length when fences are located in isolated place, and every 150 to 225 m when in close proximity (30 m or less) to public road, highways, and buildings. Fence shall be grounded at location where the fence alignment changes more than 15 degrees. B. Fence Posts Each fence post to be grounded shall be connected to a ground electrode consisting of a copper-clad steel ground rod 19 mm in diameter and 3 m long, driven not less than 3.4 m into the ground with rod located at the fence line or as near the fence line as is practicable. Connection of fence post to ground electrode shall be made below grade with not less than No. 4 AWG strandedcopper wire with TW insulation by approved molded exothermic weld process or approved clamp-type fitting on fence post and electrode. Each gate panel shall be bonded with a flexible bond strap to its gate post. Standard Specification Site Fencing Document No. 0000-10-SPE-0002 Revision 0 Page 15 of 15