Sethuraman Srinivasan Differential Protection Differential Protection is a unit type protection for a specified equipment or specified zone. It is since any fault within an electrical equipment would cause the current entering it to be different from leaving the equipment. Thus, differential protection compares the two currents magnitude or angle or both and issue a trip if there is a difference. This method of detecting fault is easy applied when both the end of the equipment protected are physically located near each other. So, differential protection can easily apply to equipment’s like transformer, generator, busbar or maybe a motor. When it comes to transmission line protection then ends of the line is far apart to apply a differential protection scheme to be applied. I. Principle of simple differential protection The advantage of adding a differential protection for internal fault detection are as follows: a) Differential protection provides faster detection of faults that appears on the internal zone of protection b) The location of the fault is determined by the size of the equipment protected c) The high-speed clearing of in-zone faults can significantly lower the arc flash incident energy levels. The principle of operation of differential protection is that vector difference of current passes through the operating coil. For example, from figure 1 if the CT ratio of the protected equipment is 1:1 on both the end, the operating current Id which the difference between the current entering at one end and the current leaving the other end can be expressed as, Id = I1 + I2 (or) Id = I1 + (-I2) Where, Id is the differential operating current I1 is the current entering at one end I2 is the current leaving at another end For differential protection following factors to be considered transformation ratio of the CT, Vector group and CT connection for avoiding mal-operation. II. During External fault Figure 1 In normal operating conditions the two currents at two ends of the protected equipment are equal and balance. So, no current flows through the operating coil and hence relay remains inoperative. But when any internal faults like phase to phase or phase to ground fault or inter turn fault the difference in current starts to flow through the operating coil and it trips the circuit breaker. Figure 2 Simple differential protection scheme should always remain stable for any fault which is outside protected zone. From the Figure 2 for an external fault such as through fault current at the terminals or maybe on the load connected the current entering and leaving the protected zone is same. Assuming CT ratio is same on both For power system studies consulting, individual training and corporate training requirements, contact us. www.powerprojectsindia.com Sethuraman Srinivasan end as 1500/ 1A. There is not fault current flowing in split path or the operating coil. III. During Internal Fault Figure 3 Now if any fault occurs within the protected zone internally within the protected equipment maybe a phase to phase fault or phase to ground fault the resultant fault will starts to follow through the operating coil and if the current exceeds the pickup value of the relay it will initiate trip to circuit breaker to protect the equipment. Therefore, from the above understanding if the fault or spill current is more than the pickup value of the simple differential relay it will initiate the trip. The minimum internal fault current that the operating coil of the simple differential relay is given by, Id, min = CT ratio × Differential pickup value. IV. Relay Stability on internal and external fault conditions So far for understanding the differential principle we have assumed CT’s are ideal. But in practical scenario’s CT’s are subjected to magnitude and phase angle errors. Both errors depend on CT’s Burden. These burdens depend on the lead lengths and the impedance of the relay coil. Generally, these CT errors occurs during any external faults or maybe during sudden increase of primary current of the CT. So, during the external fault or during a through fault current goes on increasing various imperfections of CT’s get magnified. This cause the spill current on the operating coil to build up. The imperfections of the CT’s on both ends will not same practically. Due to this there will be difference between the secondary current on CT’s exceeds the pickup value settings and relay initiate trips. So, without any internal fault due to CT errors simple differential relay may maloperate. In such condition relay lost its stability due to the external through fault occurred. The ability of the simple differential relay to restrain (block) for the external through fault current is defined as Through fault limit. Which means beyond this limit relay loses it stability. When it comes to internal fault, the minimum internal fault required to sense by the operating coil of the simple differential relay is decide by the pickup value of the relay in the operation coil path. So, for defining the minimum internal fault relay needs to operate and the maximum fault current beyond which the simple differential relay mal-operates, the stability ratio is defined. ๐๐๐ฅ๐๐๐ข๐ ๐กโ๐๐๐ข๐โ ๐๐๐ข๐๐ก ๐ ๐ก๐๐๐๐ ๐๐๐๐๐ก ๐ ๐ก๐๐๐๐๐ก๐๐ฆ ๐๐๐ก๐๐ = ๐๐๐๐๐๐ข๐ ๐๐๐๐๐ข๐ ๐ฃ๐๐๐ข๐ ๐๐๐๐ข๐๐๐๐ ๐๐๐ ๐๐๐ก๐๐๐๐๐ ๐๐๐ข๐๐ก For power system studies consulting, individual training and corporate training requirements, contact us. www.powerprojectsindia.com