Uploaded by PPPATEL747

et200sp ha f di 16x24vdc manual en-US en-US

advertisement
Security information
1
Preface
2
SIMATIC
Product overview
3
ET 200SP HA
F-DI 16x24VDC HA
Wiring
4
Parameters/address space
5
Applications of the F-I/O
module
6
Displays, alarms and
messages
7
Technical specifications
8
Response times
A
Equipment Manual
6DL1136-6BA00-0PH1
01/2021
A5E45647528-AC
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage
to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices
referring only to property damage have no safety alert symbol. These notices shown below are graded according to
the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will be
used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property
damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended or
approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance
are required to ensure that the products operate safely and without any problems. The permissible ambient
conditions must be complied with. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of Siemens AG. The remaining trademarks in this publication may
be trademarks whose use by third parties for their own purposes could violate the rights of the owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software described.
Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this
publication is reviewed regularly and any necessary corrections are included in subsequent editions.
Siemens AG
Digital Industries
Postfach 48 48
90026 NÜRNBERG
GERMANY
A5E45647528-AC
Ⓟ 06/2021 Subject to change
Copyright © Siemens AG 2021.
All rights reserved
Table of contents
1
Security information.............................................................................................................................. 5
2
Preface ................................................................................................................................................... 7
3
Product overview ................................................................................................................................... 9
3.1
4
5
6
7
Properties of the F-DI 16x24VDC HA I/O module ................................................................... 9
Wiring .................................................................................................................................................. 13
4.1
Terminal blocks for the I/O module ..................................................................................... 13
4.2
Pin assignment of the F-DI 16x24VDC HA I/O module ......................................................... 15
4.3
Schematic circuit diagram .................................................................................................. 17
Parameters/address space ................................................................................................................... 19
5.1
Parameters ........................................................................................................................ 20
5.2
5.2.1
5.2.2
5.2.3
5.2.4
5.2.5
5.2.6
5.2.7
Description of parameters .................................................................................................. 24
F-parameters ..................................................................................................................... 24
Cross-channel parameters .................................................................................................. 25
Parameters of the module .................................................................................................. 26
Parameters of the channel pairs ......................................................................................... 27
Parameters of the channels ................................................................................................ 29
Parameters of the potential group ...................................................................................... 35
Additional parameters on the "Redundancy" tab for redundant modules ............................. 36
5.3
Address space .................................................................................................................... 37
Applications of the F-I/O module ......................................................................................................... 39
6.1
Applications of the electronic module................................................................................. 39
6.2
Application 1: Safety mode SIL3/Cat.3/PLd .......................................................................... 41
6.3
Application 2: Safety mode SIL3/Cat.3/PLe .......................................................................... 43
6.4
6.4.1
6.4.2
Application 3: Safety mode SIL3/Cat.4/PLe .......................................................................... 46
Application 3.1 (SIL3/Cat.4/PLe) ......................................................................................... 47
Application 3.2 (SIL3/Cat.4/PLe) ......................................................................................... 48
6.5
Requirements placed on sensors for fail-safe modules ........................................................ 51
6.6
IO redundancy ................................................................................................................... 53
Displays, alarms and messages ........................................................................................................... 55
7.1
Status and fault displays of the F-DI 16x24VDC HA I/O module............................................ 55
7.2
Interrupts .......................................................................................................................... 58
7.3
Diagnostic messages.......................................................................................................... 60
7.4
Maintenance messages ...................................................................................................... 66
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
3
Table of contents
8
Technical specifications ....................................................................................................................... 67
A
Response times.................................................................................................................................... 75
Index .................................................................................................................................................... 77
4
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Security information
1
Siemens provides products and solutions with industrial security functions that support the
secure operation of plants, systems, machines, and networks.
In order to protect plants, systems, machines and networks against cyber threats, it is necessary
to implement – and continuously maintain – a holistic, state-of-the-art industrial security
concept. Siemens’ products and solutions form one element of such a concept.
Customers are responsible for preventing unauthorized access to their plants, systems,
machines and networks. These systems, machines and components should only be connected
to the enterprise network or the Internet if and only to the extent necessary and with appropriate
security measures (firewalls and/or network segmentation) in place.
You can find more information on protective measures in the area of industrial security by
visiting:
https://www.siemens.com/industrialsecurity.
Siemens’ products and solutions undergo continuous development to make them more secure.
Siemens strongly recommends performing product updates as soon as they are available and
using only the latest product versions. Use of product versions that are no longer supported, and
failure to apply latest updates may increase customer’s exposure to cyber threats.
To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed
under
https://www.siemens.com/industrialsecurity.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
5
Security information
6
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
2
Preface
Validity of the documentation
This device manual describes the I/O module F-DI 16x24VDC HA with the article number
6DL1136-6BA00-0PH1.
It supplements the system manual "Distributed I/O System ET 200SP HA (https://
support.industry.siemens.com/cs/ww/en/view/109761547)".
Functions that generally relate to the system are described in the system manual.
The information in this device manual and the system/function manuals enables you to put the
ET 200SP HA into operation.
You can find additional information in the programming and operating manual "SIMATIC
Industrial Software S7 F/FH Systems - Configuring and Programming (https://
support.industry.siemens.com/cs/ww/en/view/109773062)".
Conventions
Please also observe notes marked as follows:
Note
A note contains important information on the product described in the documentation, on the
handling of the product or on the section of the documentation to which particular attention
should be paid.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
7
Preface
Important notes for maintaining operational safety of your plant
Note
Operation of systems with safety aspects in mind
Safety-related systems are subject to special operational safety requirements on the part of the
operator. The supplier is also obliged to comply with special product monitoring measures. For
this reason, we provide you with information on product developments and features that are (or
could be) relevant to operation of systems with safety aspects in mind. In order to obtain the
latest information and to enable you to undertake any necessary modifications to your system,
you must subscribe to the corresponding notifications To subscribe, go to the Internet (https://
support.industry.siemens.com/My/ww/de/).
Log on to this website and under "My Notifications" select the notifications for the following
topics, for example:
• S7-300 / S7-300F
• S7-400 / S7-400H / S7-400F/FH
• Distributed I/O
• SIMATIC Industrial Software
• S7 F/FH Systems
• SIMATIC PCS 7
• ET 200SP HA
You can find additional information on setting up notifications on the page "Helpful Functions in
Online Support (https://support.industry.siemens.com/cs/ww/en/sc/2063)".
Security concepts and communication
The PCS 7 security concepts described in the document "PCS 7 Compendium Part F - Industrial
Security" must be observed for secure operation of the system.
You can find additional information on this document in the table above under "PCS 7".
In particular, we recommend the following:
• Protection of the devices/systems, e.g. PCS 7 OS server and clients
• Ensuring the integrity and confidentiality of communication between the devices/systems,
e.g.:
– By means of encrypted and authenticated communication between the systems involved,
such as the PCS 7 OS system and/or between engineering stations (ES)
– When using Industrial Ethernet CPs: by means of a VPN tunnel between the OS systems
and/or automation systems (AS).
8
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
3
Product overview
3.1
Properties of the F-DI 16x24VDC HA I/O module
View of the module
F-DI
16x 24V DC
HA
DIA G MT
1
3
5
7
9
11
13
15
DI.0 +
DI.2 +
DI.4 +
DI.6 +
DI.8 +
DI.10 +
DI.12 +
DI.1 4 +
17
19
21
23
25
27
29
31
UV0
UV2
UV4
UV6
UV8
UV1 0
UV12
UV1 4
F-D I
DI.1+
DI.3 +
DI.5 +
DI.7 +
DI.9 +
DI.11+
DI.1 3 +
DI.15 +
2
4
6
8
10
12
14
16
UV
UV1 18
UV3 20
UV5 22
UV7 24
UV9 26
UV11 28
UV1 3 30
UV15 32
1P1 L+ 24V
2P1 L+ 24V DC M 1P2
DC
MA X. 10 A M 2P2
.0
F0
.2
F2
.4
F4
.6
F6
.8
F8
.10
F10
.12
F12
.14
F14
.1
F1
.3
F3
.5
F5
.7
F7
.9
F9
.11
F11
.13
F13
.15
F15
③
④
⑤
⑥
X 2
3 4
PW R
CC0 1
6DL1131-6BH
00-
①
②
0PH1
Module type and designation
LED for diagnostics
LED for maintenance
2D matrix code
Wiring diagram
LEDs for channel status/channel
fault
⑧
⑨
⑩
⑪
⑫
⑬
Output disable switch
Color coding
•
Basic module type: "White" = Digital input module
•
Supplemental type information: "Yellow" = Fail-safe I/O
module
Product version
Color code for selection of the color-coded labels
Serial number
Article number
⑦ LED for supply voltage
Figure 3-1
View of the module F-DI 16×24VDC HA
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
9
Product overview
3.1 Properties of the F-DI 16x24VDC HA I/O module
Properties
The I/O module has the following properties:
• Technical properties
– 16 fail-safe digital inputs (SIL3/Cat.4/PLe)
– 16 outputs for sensor supply
– PROFIsafe Profile V2.6.1
– 1oo1 and 1oo2 evaluation can be configured for each channel or channel pair. 1oo2
evaluation can be configured in pairs with a permanently assigned partner channel (e.g.
channel 0 configured, channel 8 is assigned)
– Module-specific configurable diagnostics for missing supply voltage L+
– Sinking input
– Suitable for connection of 2-/3-/4-wire sensors in accordance with IEC 61131, type 1
– Channel-specific configurable input delay
– Channel-specific configurable pulse stretching
– Internal short-circuit-proof sensor supplies for each input
– External sensor supply possible
– Diagnostics display LED DIAG (red/green)
– Maintenance messages and maintenance display LED MT (yellow)
– Channel-specific status display LED "Channel status" (green)
– Channel-specific error display LED "Channel fault" (red)
– Channel-specific diagnostics, e.g. short-circuit/wire break
– Modular diagnostics, e.g. load voltage missing
– Channel-specific or module-wide passivation
• Supported functions
– Firmware update
– I&M identification data
– Value status QI
– IO redundancy
– High-precision time stamping (accuracy 10 ms)
– Output disable switch
10
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Product overview
3.1 Properties of the F-DI 16x24VDC HA I/O module
WARNING
Validity of safety parameters
The safety parameters in the technical specifications are valid for a mission time of 20 years and
a repair time of 100 hours. If a repair is not possible within 100 hours, remove the relevant
module from the terminal block or switch off its supply voltage before 100 hours elapse. After
100 hours elapse, the module switches off on its own.
For repairs, follow the procedure described in section "Diagnostic messages (Page 60)".
(FDIW-001)
Output disable switch
If you want to pull the I/O module in runtime, you have to press the output disable switch for 3
seconds for the I/O module to be deenergized.
When the output disable switch has been pressed for 3 seconds, the LED DIAG flashes red, the
LED MT lights up yellow and the I/O module generates a diagnostics message. You can find
additional information in section "Status and fault displays of the F-DI 16x24VDC HA I/O module
(Page 55)".
Note
Pressing the output disable switch interrupts any ongoing firmware update. A firmware update
cannot be performed when the device is deenergized.
Accessories
The following accessories must be ordered separately:
• Labeling strips
• Color-coded labels
• Reference identification labels
• Slot cover
• Shield connector
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
11
Product overview
3.1 Properties of the F-DI 16x24VDC HA I/O module
12
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
4
Wiring
4.1
Terminal blocks for the I/O module
Terminal blocks
You can operate the I/O module with the following terminal blocks:
• 6DL1193-6TP00-0DH1, light
• 6DL1193-6TP00-0BH1, dark
• 6DL1193-6TP00-0DM1, light, for redundant configuration
• 6DL1193-6TP00-0BM1, dark, for redundant configuration
The terminal block is not included in the scope of delivery of the I/O module and must be ordered
separately.
WARNING
Provisions for IO redundancy
• With a redundant configuration, you need to ensure that not only one I/O module is
permanently operated on the terminal block.
• When plugging a I/O module in a redundant configuration, you must ensure that you use
identical module types.
(FDIW-013)
Note
Further information on the configuration can be found in the system manual for ET 200SP HA.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
13
Wiring
4.1 Terminal blocks for the I/O module
Connections on the slot and I/O module
6ORWRIWKH,2PRGXOH
&RQQHFWRUVLGHRIWKH,2
PRGXOH
;
&DUULHUPRGXOHFRQWDFWVRIWKHEDFNSODQHEXV
0D[LPXP9'&
0D[LPXPP$
;
7HUPLQDOEORFNFRQWDFWVRIWKH,2PRGXOH
0D[LPXP9'&
0D[LPXP$SHUSLQ$SHUPRGXOH
7HUPLQDOEORFN
3URFHVVWHUPLQDOV
6XSSO\RIWKH,2PRGXOH
Figure 4-1
Slot and I/O module connections
Information on the pin assignment of the I/O module (terminal block) can be found in the
sections below.
14
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Wiring
4.2 Pin assignment of the F-DI 16x24VDC HA I/O module
4.2
Pin assignment of the F-DI 16x24VDC HA I/O module
General pin assignment
Table 4-1
Pin assignment of the F-DI 16×24VDC HA
Terminal
Assignment
Terminal
Assignment
Explanations
1
F-DI /DI.0+
2
F-DI /DI.1+
F-DI /DI.n+: Input signal, channel n (0…15)
3
F-DI /DI.2+
4
F-DI /DI.3+
UV /UVn: Sensor supply, channel n (0…15)
5
F-DI /DI.4+
6
F-DI /DI.5+
1P1: Supply voltage L+ of the voltage bus 1P
7
F-DI /DI.6+
8
F-DI /DI.7+
2P1: Supply voltage L+ of the voltage bus 2P
9
F-DI /DI.8+
10
F-DI /DI.9+
1P2: Ground reference of the voltage bus 1P
11
F-DI /DI.10+
12
F-DI /DI.11+
2P2: Ground reference of the voltage bus 2P
13
F-DI /DI.12+
14
F-DI /DI.13+
15
F-DI /DI.14+
16
F-DI /DI.15+
17
UV /UV0
18
UV /UV1
19
UV /UV2
20
UV /UV3
21
UV /UV4
22
UV /UV5
23
UV /UV6
24
UV /UV7
25
UV /UV8
26
UV /UV9
27
UV /UV10
28
UV /UV11
29
UV /UV12
30
UV /UV13
31
UV /UV14
32
UV /UV15
1P1
L+
1P2
M
2P1
L+
2P2
M
1
1
3
5
7
9
11
13
15
DI.0 +
DI.2 +
DI.4 +
DI.6 +
DI.8 +
DI.10 +
DI.12 +
DI.14 +
17
19
21
23
25
27
29
31
UV0
UV2
UV4
UV6
UV8
UV10
UV12
UV14
F-DI
DI.1+
DI.3 +
DI.5 +
DI.7+
DI.9 +
DI.11+
DI.13 +
DI.15 +
2
4
6
8
10
12
14
16
UV1
UV3
UV5
UV7
UV9
UV11
UV13
UV15
18
20
22
24
26
28
30
32
UV
1P1 L+ 24VDC M 1P2
2P1 L+ 24VDC M 2P2
MAX. 10 A
1
If the module is plugged into a TB45R-P32 terminal block suitable for IO redundancy, the potential at this terminal is 1P3.
Table 4-2
Circuit diagrams
1-wire
', Q ',Q
9'&
2-wire
3-wire
4-wire
',Q
',Q
89Q
+
DI.n
89Q
0
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
UVn
DI.n+8
-
M
15
Wiring
4.2 Pin assignment of the F-DI 16x24VDC HA I/O module
Note
Connection with multicore cables at function status 1 (FS01) of the I/O module
If you use multi-core cables to connect the signals to the inputs of the I/O module, make sure that
any unused cores of this cable are grounded on one side.
This note can be ignored for I/O modules with function status 2 (FS02) and higher.
Note
To prevent wire-break diagnostics in the case of simple encoder contacts, you have the option
of connecting a resistor in parallel to the encoder contact.
Recommended ohmic resistance value: 18 kOhm to 30 kOhm, typically: 26 kOhm
16
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Wiring
4.3 Schematic circuit diagram
4.3
Schematic circuit diagram
The following figure shows the schematic circuit diagram of the F-DI 16x24VDC HA.
,QSXWFLUFXLW
7HUPLQDO
', ವ
ವ
ವ
%DFNSODQHEXVLQWKHFDUULHUPRGXOH
w&
*DOYDQLF
LVRODWLRQ
(763+$
EDFNSODQHEXV
LQWHUIDFH
89
w&
3RZHUEXVLP
7HUPLQDOEORFN
',
ವ
ವ
ವ
89
0
/
Figure 4-2
5HYHUVHSRODULW\
SURWHFWLRQ
&KDQQHOVWDWXV/('V
&KDQQHOGLDJQRVWLF/('V
Schematic circuit diagram of F-DI 16x24VDC HA
Firmware update
The supply voltage L+ must be available on the I/O module at the start of the firmware update
and during the update. The firmware can only be updated in the STOP mode of the F-CPU.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
17
Wiring
4.3 Schematic circuit diagram
18
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5
Configuration
The following software is required to configure the I/O module:
• S7 F Systems V6.3 (or higher)
• Additionally optional:
– PCS 7 V9.0 SP3 (or higher)
or
– SIS compact V9.0 SP3 (or higher)
Parameters
You define the functioning of the I/O module via parameters.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
19
Parameters/address space
5.1 Parameters
5.1
Parameters
Introduction
The parameters of the F-DI 16×24VDC HA are described below.
The parameters of the I/O module are displayed in the "Properties" dialog of the module in HW
Config on the following tabs:
• "Parameters" tab
• "Redundancy" tab
This tab is displayed for redundant I/O modules.
• "Time stamp" tab
This tab is used to configure the time stamp for the I/O module.
For more information on time stamping, refer to the function manual "SIMATIC; Process
Control System PCS 7; High-precision Time Stamping with ET 200SP HA (https://
support.industry.siemens.com/cs/ww/en/view/109772337)".
Parameters in the "Parameters" tab
You have the following setting options:
Parameter
Value range
Default value
Parameter
reassign‐
ment in RUN
Scope
F_source_address
1 (display only) *a)
1
No
Module
F_destination_address
1 to 65534
Preset
automatically *b)
No
Module
F_monitoring time (ms)
10 ms to 65535 ms
2500
No
Module
•
Enabled
Enabled
No
All channels
•
Disabled
•
Enabled
Disabled
No
All channels
•
Disabled
•
0.4 ms
3.2 ms
No
All channels
•
0.8 ms
•
1.6 ms
•
3.2 ms
•
6.4 ms
•
10.0 ms
•
12.8 ms
•
20 ms
F-parameters
•
Cross-channel
Channel activated
Diagnostics: Wire break
Input delay (ms)
The value of the input delay depends
on the time for the short-circuit test
of the sensor and the discrepancy
time.
20
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5.1 Parameters
Parameter
Value range
Default value
Parameter
reassign‐
ment in RUN
Scope
Pulse stretching (s)
•
None
None
No
All channels
•
0.05 s
•
0.1 s
•
0.5 s
•
1s
•
2s
•
Enabled
Disabled
No
All channels
•
Disabled
Flutter monitoring
Number of signal changes
2 to 31
5
No
All channels
Monitoring window (s)
0.5 to 100 s
2s
No
All channels
Internal
No
All channels
Enabled
No
All channels
(If 0 s is set, the monitoring window
is 0.5 s long.)
Sensor supply
Short-circuit test
•
Internal
•
External
•
Enabled
•
Disabled
Time for short-circuit test (ms)
1 ms to 2 s (in 17 steps)
10 ms
No
All channels
Startup time of sensor after
short-circuit test (ms)
0.5 ms to 2 s (in 18 steps)
10 ms
No
All channels
Diagnostics missing supply volt‐
age L+
Enabled (display only)
Enabled
No
Module
Behavior after channel fault
•
Passivate the entire module
Passivate channel
No
Module
•
Passivate channel
1oo1 evaluation
No
Channel pair
Each sensor has its
own sensor supply
No
Channel pair
Supply last valid val‐
ue
No
Channel pair
Module parameters
•
Channel n, n+8 (channel pair)
Sensor evaluation
Sensor supply for 1oo2
Discrepancy behavior
•
1oo1 evaluation
•
1oo2 evaluation, equivalent
•
1oo2 evaluation, non-equivalent
•
Each sensor has its own sensor
supply
•
Both sensors on one sensor sup‐
ply
•
Supply value 0
•
Supply last valid value
Discrepancy time (ms)
10 ms to 30 s
30 ms
No
Channel pair
Reintegration after discrepancy
error
•
Test 0-Signal not necessary
No
Channel pair
•
Test 0-Signal necessary
Test 0-Signal not
necessary
•
Enabled
Enabled
No
Channel
•
Disabled
•
Channel n
Channel activated
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
21
Parameters/address space
5.1 Parameters
Parameter
Value range
Default value
Parameter
reassign‐
ment in RUN
Scope
Diagnostics: Wire break
•
Enabled
Disabled
No
Channel
•
Disabled
•
0.4 ms
3.2 ms
No
Channel
•
0.8 ms
•
1.6 ms
•
3.2 ms
•
6.4 ms
•
10.0 ms
•
12.8 ms
•
20 ms
None
No
Channel
Disabled
No
Channel
Input delay (ms)
The value of the input delay depends
on the time for the short-circuit test
of the sensor and the discrepancy
time.
Pulse stretching (s)
•
None
•
0.05 s
•
0.1 s
•
0.5 s
•
1s
•
2s
Flutter monitoring
•
Enabled
•
Disabled
Number of signal changes
2 to 31
5
No
Channel
Monitoring window (s)
0.5 to 100 s
2s
No
Channel
Internal
No
Channel
Enabled
No
Channel
(If 0 s is set, the monitoring window
is 0.5 s long.)
Sensor supply
Short-circuit test
•
Internal
•
External
•
Enabled
•
Disabled
Time for short-circuit test (ms)
1 ms to 2 s (in 17 steps)
10 ms
No
Channel
Startup time of sensor after
short-circuit test (ms)
0.5 ms to 2 s (in 18 steps)
10 ms
No
Channel
•
Use potential group of left mod‐
ule (dark terminal block)
No
Terminal
block
•
Enable new potential group
(light terminal block)
Use potential group
of left module (dark
terminal block)
•
Potential group
Potential group
*a) The F_source_address is automatically preset with the value "1" in S7 F/FH Systems and
cannot be changed in the properties of the I/O module.
*b) The F_destination_address is automatically preset uniquely throughout the station.
22
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5.1 Parameters
You can find more information on these parameters in the section "F-parameters (Page 24)".
Parameters in the "Redundancy" tab
For redundant digital input modules, define additional parameters in the "Additional
parameters" section of the "Redundancy" tab.
Parameter
Value range
Parameter reas‐
signment in RUN
Scope
0 to 30 s
No
Redundant modules
"Parameters" group
Discrepancy time (ms)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
23
Parameters/address space
5.2 Description of parameters
5.2
Description of parameters
5.2.1
F-parameters
F_source_address
Together, the F-source address "F_source_address" and the F-destination address
"F_destination_address" form the PROFIsafe address. The PROFIsafe address is used for the
unique identification of the F-I/O modules.
The F-source address is a unique address of the fail-safe CPU for the entire network. In S7 F/FH
systems, it is automatically preset with the value "1" and cannot be changed in the properties of
the I/O module.
F_destination_address
Together, the F-destination address "F_destination_address" and the F-source address
"F_source_address" form the PROFIsafe address. The PROFIsafe address is used for the unique
identification of the F-I/O modules.
Station-wide uniqueness:
• The F-source address "F_source_address" of the F-CPU is unique station-wide. In S7 F/FH
systems, it is automatically preset with the value "1".
• The F-destination address of the F-I/O module is automatically unique station-wide.
To prevent an incorrect parameter assignment, a station-wide unique F-destination address
is automatically assigned when the F-I/O module is placed in HW Config.
If you change F-destination address, the station-wide uniqueness of F-destination address is
automatically checked.
You must assign the F-destination address to the F-I/O module before you commission it.
Note
Requirement for type R1 system redundancy
With type R1 system redundancy for distributed I/O, the left interface module must be
plugged in so that a new F_destination_address can be assigned to the module.
24
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5.2 Description of parameters
WARNING
PROFIsafe addresses have to be unique for the station
• Station-wide uniqueness:
Fail-safe I/O modules of the ET 200SP HA are uniquely addressed station-wide by a
combination of F-source address (PROFIsafe basic address of the assigned F-CPU) and Fdestination address. The F-system itself ensures that the F-destination addresses of all F-I/O
modules within the assigned F-CPU are unique.
• Cross-station uniqueness:
To guarantee uniqueness across stations, you must verify that the PROFIsafe addresses
("F_source_address" + "F_destination_address") of the F-I/O modules are unique across
stations.
• Verification following a change:
Because the F-source address "F_source_address" of the PROFIsafe address of the F-CPU is
automatically set to "1", you can only change the preset address "F_destination_address" for
F-I/O modules of the ET 200SP HA.
Note that the PROFIsafe address of the F-I/O module must be unique across all stations!
For Ethernet subnets and mixed configurations of PROFIBUS and Ethernet subnets, the
following also applies:
The combination of F-source address and F-destination address of all F-I/O modules only has to
be unique throughout the Ethernet subnet including all lower-level PROFIBUS subnets, under
the exclusion of cyclic PROFINET IO communication between Ethernet subnets.
(FDIW-002)
F_monitoring time (ms)
With this parameter you set the monitoring time for safety-related communication between the
F-CPU and F-I/O (PROFIsafe monitoring time) for safety operation.
The parameter is assigned a default value, but you can change it.
The configured F-monitoring time influences the response time of the system to a system error.
For this reason, the selected time must be as short as possible, but still long enough to prevent
timeouts when no error is occurring.
5.2.2
Cross-channel parameters
Distinction between "Cross-channel parameters" / "Channel parameters":
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
25
Parameters/address space
5.2 Description of parameters
Cross-channel parameters act on all identically named parameters of the channels of the module
and thus allow a higher-level setting.
Note
Due to dependencies, the parameters of the channels can be reset to default values if crosschannel parameters are changed.
Therefore, check the setting of the channel parameters after changing a cross-channel
parameter.
The function of the cross-channel parameters is identical to the parameters of the channels.
• "Channel activated"
• "Diagnostics: Wire break"
• "Input delay (ms)"
• "Pulse stretching (s)"
• "Flutter monitoring"
• "Number of signal changes"
• "Monitoring window (s)"
• "Sensor supply"
• "Short-circuit test"
• "Time for short-circuit test (ms)"
• "Startup time of sensor after short-circuit test (ms)"
You can find detailed information on this in section "Parameters of the channels (Page 29)".
5.2.3
Parameters of the module
Diagnostics missing supply voltage L+
Enabling of the diagnostics for missing or insufficient supply voltage L+.
By default, this parameter is "Activated", cannot be changed and is only used for display.
Behavior after channel fault
With this parameter you specify whether the entire F-module is passivated after channel faults
or just the faulty channel(s):
• "Passivate entire module"
• "Passivate channel"
26
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5.2 Description of parameters
5.2.4
Parameters of the channel pairs
Sensor evaluation
You select the type of sensor evaluation with the "Sensor evaluation" parameter:
• 1oo1 evaluation
With 1oo1 evaluation one sensor is connected.
The sensor occupies one input channel.
• 1oo2 evaluation, equivalent/non-equivalent
With 1oo2 evaluation equivalent/non-equivalent, two input channels are occupied by one of
the following:
– A two-channel, equivalent/non-equivalent sensor
– Two single-channel sensors
The input signals are compared internally for equivalence or non-equivalence.
Note that in 1oo2 evaluation, two channels are grouped into a channel pair. The number of
available process signals of the F-module is reduced accordingly.
The evaluation result for the channel pair is available at the input of the channel with the low
channel number (channel "n").
Dependencies:
• If the "1oo2 evaluation, equivalent" or "1oo2 evaluation, non-equivalent" option is selected
for the "Sensor evaluation" parameter, the "Input delay (ms)" of a channel must be less than
the configured "Discrepancy time (ms)".
Discrepancy analysis:
If you are using a two-channel sensor or two single-channel sensors that measure the same
process variable, the response of the sensors will be delayed relative to one another due to the
limited precision of their arrangement, for example.
The discrepancy analysis for equivalence/non-equivalence is used for fail-safe inputs to detect
errors from the time sequence of two signals of the same functionality. The discrepancy analysis
is started when different levels are detected for two associated input signals (when testing for
non-equivalence: the same level). On expiration of a configurable time interval, i.e. the so-called
discrepancy time, a check is made to determine whether the difference in the signal levels has
disappeared (when testing for non-equivalence: the equivalence of the signal levels). If not,
there is a discrepancy error.
Sensor supply for 1oo2
You use this parameter to select the sensor supplies for 1oo2 evaluation:
• Each sensor has its own sensor supply
• Both sensors on one sensor supply
In this setting, the sensor supply of the channel with the low channel number (channel "n")
is used, for example, the sensor supply of channel "0" is used for channel pair 0/8.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
27
Parameters/address space
5.2 Description of parameters
Discrepancy behavior
Requirement:
You have configured the following:
• "Sensor evaluation": "1oo2 evaluation, equivalent" or "1oo2 evaluation, non-equivalent"
Function:
For "Discrepancy behavior", you configure the value that is supplied to the safety program in the
F-CPU during the discrepancy between the two affected input channels, i.e. while the
discrepancy time is running. You configure the discrepancy behavior as follows:
• "Supply last valid value"
• "Supply 0 value"
Option "Supply last valid value":
The last valid value (old value) before the discrepancy occurred is supplied to the safety program
in the F-CPU as soon as a discrepancy is detected between the signals of the two affected input
channels. This value is supplied until the discrepancy disappears or the discrepancy time expires,
and a discrepancy error is detected. The sensor-actuator response time is correspondingly
extended by this time.
This means that the discrepancy time of connected sensors with 1oo2 evaluation must be
matched with short response times for fast responses. Accordingly, it makes no sense, for
example, when connected sensors with a discrepancy time of 500 ms trigger a time-critical
shutdown. In the worst-case scenario, the sensor-actuator response time is extended by an
amount equal to the discrepancy time, which you can calculate in section "Response times":
• For this reason, arrange the sensors in the process in such a way as to minimize
discrepancy.
• Then, select as short a discrepancy time as possible that also has a sufficient margin to
prevent false triggering of discrepancy errors.
Option "Supply 0 value":
The value "0" is supplied to the safety program in the F-CPU as soon as a discrepancy between
the signals of the two affected input channels is detected.
If you have configured "Supply 0 value", the sensor-actuator response time is not affected by the
discrepancy time.
Discrepancy time (ms)
Requirement:
You have configured the following:
• "Sensor evaluation": "1oo2 evaluation, equivalent" or "1oo2 evaluation, non-equivalent"
In most cases, the discrepancy time is started but does not completely elapse because the signal
differences even out after a short time.
Select a sufficiently long discrepancy time so that in the error-free case the difference between
the two signals always disappears before the discrepancy time expires (when testing for nonequivalence: the equivalence of the two signals).
28
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5.2 Description of parameters
Function:
You can specify the discrepancy time for each channel pair.
Behavior while discrepancy time is running:
While the configured discrepancy time is running inside the module, the affected input channels
supply either the last valid value or "0" to the safety program in the F-CPU, depending on the
configured discrepancy behavior.
Behavior after expiration of the discrepancy time:
If after expiration of the configured discrepancy time the input signals are still different (when
testing for non-equivalence: input signals are still the same), e.g. due to a sensor wire break, a
discrepancy error is detected and the diagnostics message "Discrepancy error" is generated
along with information on the faulty channels.
Reintegration after discrepancy error
Requirement:
You have configured the following:
• "Sensor evaluation": "1oo2 evaluation, equivalent" or "1oo2 evaluation, non-equivalent"
Function:
You use this parameter to specify when a discrepancy error is regarded as corrected, thus
enabling reintegration of the affected input channels. You have the following parameter
assignment options:
• "Test 0-Signal necessary"
• "Test 0-Signal not necessary"
Option "Test 0-Signal necessary":
If you have configured "Test 0-Signal necessary", a discrepancy error is not regarded as corrected
until a 0-signal is present again at both of the affected input channels.
If you are using non-equivalent sensors, i.e. "Sensor evaluation" is set to "1oo2 evaluation, nonequivalent", the result of the channel pair must be "0" again.
Option "Test 0-Signal not necessary":
If you have configured "Test 0-Signal not necessary", a discrepancy error is regarded as corrected
when a discrepancy is no longer present at both of the affected input channels.
5.2.5
Parameters of the channels
Channel activated
Specifies whether a channel is activated or deactivated.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
29
Parameters/address space
5.2 Description of parameters
Diagnostics: Wire break
Enables the wire break test. The wire break test must be activated for wire break detection to take
place.
Input delay (ms)
To suppress injected interference, you can set an input delay for a channel or channel pair.
Interference pulses whose pulse time is less than the set input delay (in ms) are suppressed.
Suppressed interference pulses are not visible in the process image input (PII).
A long input delay suppresses longer interference pulses but results in a longer response time.
Dependencies:
• The values available for the input delay depend on the "Time for short-circuit test (ms)" of the
configured sensor supply.
• The value "Time for short-circuit test (ms)" must be more than twice as large as the
configured "Input delay (ms)".
• The "Input delay (ms)" of a channel must be less than the configured "Discrepancy time (ms)"
if the "1oo2 evaluation, equivalent" or "1oo2 evaluation, non-equivalent" option is selected
for the "Sensor evaluation" parameter in the respective channel pair.
In 1oo2 evaluation, the input delay of the lower-order channel (channel n) also applies
automatically to the higher-order channel (channel n+8).
Note
Due to physical properties, crosstalk of signals can occur on longer unshielded signal wires (see
section "Electromagnetic compatibility" in system manual Distributed I/O System ET 200SP HA
(https://support.industry.siemens.com/cs/ww/en/view/109761547)).
Adjust the input delay or use shielded signal wires to avoid possible passivation of fail-safe digital
inputs and shutdown of the sensor supply.
Pulse stretching (s)
Pulse stretching is a function for extending a digital input signal. A pulse on a digital input is
extended to at least the configured length. If the input pulse is already longer than the
configured length, the pulse is not changed.
How the fail-safe input module works:
The fail-safe input module only stretches pulses with the value "0". That is because the safety
concept is based on existence of a safe state for all process variables. For digital F-I/O, this is the
value "0". This applies to sensors and actuators. Impulses with the value "1" are ignored.
With "1oo2" evaluation, the first pulse with value "0" triggers pulse stretching.
After pulse stretching starts, further impulses with the value "0" are ignored.
Principle:
The following figure shows pulse stretching of the fail-safe input module.
30
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5.2 Description of parameters
3XOVHVWUHWFKLQJIRUSXOVHVZLWKWKHYDOXH
Only pulses with the value "0" are stretched. Pulses with the value
"1" are ignored.
RRHYDOXDWLRQ
1
Process value
0
Process value with
pulse stretching
1
Time "Pulse stretching (s)"
0
A
B
RRHYDOXDWLRQ
1
Channel "n"
0
1
Channel "n+8"
0
1
Process value
without pulse
stretching
0
Process value with
pulse stretching
0
Time "Pulse
stretching (s)"
Time "Pulse
stretching (s)"
1
A
B
C
D
Event "A": Pulse with the value "0" at channel "n" triggers pulse stretching up to time "B". Pulses with the value "0"
on channel "n+8" are ignored between "A" and "B".
Event "C": Pulse with the value "0" on channel "n+8" triggers pulse stretching up to time "D". Pulses with the value
"0" on channel "n" are ignored between "C" and "D".
Figure 5-1
Principle of pulse stretching
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
31
Parameters/address space
5.2 Description of parameters
Note
If you configure pulse stretching for an input channel, it also affects chatter monitoring enabled
for this channel. The "pulse-stretched" signal is the input signal for chatter monitoring. This
means you need to adapt the parameter settings of pulse stretching and chatter monitoring to
each other. You can adapt the functions to your process by selecting the appropriate parameter
values.
Flutter monitoring
Function:
Flutter monitoring is a process control function for digital input signals. It detects and reports
unusual signal sequences for the process, for example, too frequent input signal changes
between "0" and "1", during 1oo1 evaluation. If signal characteristics like these occur, it is a sign
that the sensors are faulty or that there are instabilities from a process engineering viewpoint.
Recognizing unusual signal patterns:
A configured monitoring window is available for each input channel. A monitoring window is
started every time the input signal changes. If the input signal changes within a monitoring
window more often than the configured "Number of signal changes", it is recognized as a
flutter error. If no flutter error is detected within the monitoring window, the monitoring
window is restarted at the next signal change.
If a flutter error is detected, a diagnostics message is output. When the flutter error does not
occur for three times the configured monitoring window time, the diagnostic is reset.
Principle of flutter monitoring:
The following figure shows the principle of flutter monitoring.
32
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5.2 Description of parameters
Parameter "Number of signal changes" = 7
Time "Monitoring window (s)" = y
3 x "Monitoring window (s)" = 3y
8 signal changes
detected
Process value
8 signal changes
detected
6 signal changes
detected
Diagnostics
Diagnostics "Flutter error"
Incoming => "Signal"
Figure 5-2
Diagnostics "Flutter error"
Outgoing => "Reset"
Principle of flutter monitoring
Number of signal changes
Specifies the number of permissible signal changes within a monitoring window. A flutter error
is signaled after the configured number is exceeded.
Value range: 2 to 31
Monitoring window (s)
Specifies the time for the monitoring window of the flutter monitoring.
You have the option of setting times from 0.5 s to 100 s for the monitoring window.
Sensor supply
You use this parameter to select between the internal or external sensor supply.
An internal sensor supply must be selected for use of the short-circuit test.
Dependencies:
• If the following conditions are fulfilled at the same time, then the "Sensor supply" parameter
for channel "n+8" is set to "external" and cannot be edited. The setting of the sensor supply
for channel "n" remains editable.
– With the "Sensor evaluation" parameter, the option "1oo2 (2v2) evaluation, equivalent"
or "1oo2 (2v2) evaluation, non-equivalent" is selected.
– With the parameter "Sensor supply for 1oo2" the option "Both sensors on one sensor
supply" is selected.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
33
Parameters/address space
5.2 Description of parameters
Short-circuit test
Here, you enable the short-circuit detection for the channels of the F-module for which one of
the internal sensor supplies is set.
The short-circuit test only makes sense if an internal sensor supply is set. A short-circuit test is
not possible for sensors with power supply, e.g. 3-/4-wire proximity switches.
The short-circuit detection briefly switches off the sensor supply. The switch-off duration is the
same as the configured "Time for short-circuit test (ms)".
If a short-circuit is detected, the F-module triggers a diagnostic interrupt in the F-CPU and the
input is passivated.
The following short-circuits are detected:
• Input shorted to L+
• Input shorted to a sensor supply of another channel
• Sensor supply shorted to M
Also detected with disabled short-circuit detection if the sensor supply is configured
"internally".
When a 1 signal is active at the input, the following short-circuits are also recognized:
• Short circuit on an input with the input of another channel
• Sensor supply shorted to sensor supply of another channel
• Short circuit of a sensor supply to L+
If the short-circuit test is disabled, you must route your cables in a short-circuit-proof and crosscircuit-proof manner.
Note
During the execution time of the short-circuit test ("Time for short-circuit test (ms)" + "Startup
time of sensor after short-circuit test"), the last valid value before the start of the short-circuit
test is passed to the F-CPU. Activation of the short-circuit test thus affects the response time of
the respective channel or channel pair.
Time for short-circuit test (ms)
When the short-circuit test is enabled, the corresponding sensor supply is switched off for the
configured time. If the module does not detect a "0" signal at the input within the configured
time, a diagnostics message is generated.
34
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5.2 Description of parameters
Note the following for the parameter assignment:
• If the channel is passivated, this can also be due to excessively high capacitance between the
sensor supply and input. This consists of the capacitance per unit length of the cable and the
capacitance of the employed sensor. If the connected capacitance is not discharged within
the configured time, you must adjust the "Time for short-circuit test (ms)" parameter.
• Dependencies:
– The values available for the input delay depend on the "Time for short-circuit test (ms)" of
the configured sensor supply.
– The value "Time for short-circuit test (ms)" must be more than twice as large as the
configured "Input delay (ms)".
Startup time of sensor after short-circuit test (ms)
Requirement:
The short-circuit test is enabled.
Function:
In addition to the switch-off time "Time for short-circuit test (ms)", a startup time must also be
specified for performing the short-circuit test. You use this parameter to notify the module how
long the utilized sensor needs to start up after the sensor supply is switched on again. This
prevents an undefined input state due to transient reactions in the sensor.
Note the following for the parameter assignment:
• This parameter must be greater than the transient recovery time of the employed sensor.
• Because the configured time affects the response time of the module, we recommend that
you set the time as short as possible but long enough for reliable transient recovery of your
sensor.
See also
Cross-channel parameters (Page 25)
5.2.6
Parameters of the potential group
Potential group
Specifies whether the I/O module is located on a terminal block with supply voltage infeed
Function:
A potential group consists of a group of directly adjacent I/O modules within an ET 200SP HA
station that are supplied via a common supply voltage.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
35
Parameters/address space
5.2 Description of parameters
A potential group begins with a light terminal block, via which the required supply voltage is fed
to all I/O modules of the potential group. The light terminal block interrupts the self-assembling
voltage buses to the left neighbor.
All other I/O modules of this potential group are plugged into dark terminal blocks. I/O modules
on dark terminal blocks take the potentials of self-assembling voltage rails from the left
neighbor.
A potential group ends with the dark terminal block, which follows a light terminal block or a
server module in the station configuration.
Further information on the configuration of the potential group can be found in system manual
"Distributed I/O System ET 200SP HA (https://support.industry.siemens.com/cs/ww/en/view/
109761547)".
5.2.7
Additional parameters on the "Redundancy" tab for redundant modules
Introduction
For redundant digital input modules, define additional parameters in the "Additional
parameters" section of the "Redundancy" tab.
Discrepancy time (ms)
The parameter is displayed if redundancy is configured.
The discrepancy time is the maximum permissible time in which the redundant input signals
may differ.
• If the discrepancy time = "0" is configured, the discrepancy analysis is disabled.
• If a discrepancy time not equal to "0" is configured, a discrepancy analysis is performed.
36
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Parameters/address space
5.3 Address space
5.3
Address space
Address assignment of the digital input module F-DI 16x24VDC HA
The digital input module F-DI 16x24VDC HA occupies the following address areas in the F-CPU:
Table 5-1
Address assignment in the F-CPU
Assigned bytes in the F-CPU:
In the input range
In the output range
IB x + 0 to x + 8
QB x + 0 to x + 4
x = module start address
Address assignment of the user data and the value status of the digital input module F-DI 16x24VDC
HA
The user data occupies the following addresses in the F-CPU out of all the assigned addresses of
the digital input module F-DI 16x24VDC HA:
Table 5-2
Address assignment by user data
Byte in the
F-CPU
Assigned bits in the F-CPU per F-module:
7
6
5
4
3
2
1
0
x+0
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI0
x+1
DI15
DI14
DI13
DI12
DI11
DI10
DI9
DI8
x+2
Value sta‐
tus for DI7
Value sta‐
tus for DI6
Value sta‐
tus for DI5
Value sta‐
tus for DI4
Value sta‐
tus for DI3
Value sta‐
tus for DI2
Value sta‐
tus for DI1
Value sta‐
tus for DI0
x+3
Value sta‐
tus for DI15
Value sta‐
tus for DI14
Value sta‐
tus for DI13
Value sta‐
tus for DI12
Value sta‐
tus for DI11
Value sta‐
tus for DI10
Value sta‐
tus for DI9
Value sta‐
tus for DI8
x = module start address
Note
• You may only access the addresses occupied by user data.
• In S7 F/FH systems, the value status is automatically processed by the F-channel drivers.
• With I/O redundancy, you only access the channels of the left I/O module. The input values
of the corresponding channels of the redundant I/O module are automatically processed by
the F channel drivers.
• For 1oo2 sensor evaluation, the two channels are combined, e.g. channel 0 (input bit DI0)
with channel 8 (input bit DI8). With 1oo2 evaluation of the sensors, you may only access the
input bit of the lower channel number in the safety program, in this example channel 0.
• The other address areas occupied by the F-modules are assigned for functions including
safety-related communication between the F-modules and F-CPU in accordance with
PROFIsafe.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
37
Parameters/address space
5.3 Address space
"Value status" bit
For each input signal, the F-DI 16x24VDC HA module provides information on its validity, the
"value status" (qualifier bit). The value status is stored in the process image of the inputs.
In S7 F/FH Systems, you may only access the addresses (DIx) occupied by user data. The value
status is automatically processed by the F-channel drivers.
Additional information
You can find additional information on address assignment as well as evaluation and processing
of the value status in the programming and operating manual "SIMATIC Industrial Software S7
F/FH Systems - Configuring and Programming (https://support.industry.siemens.com/cs/ww/en/
view/109773062)".
38
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
6
Applications of the F-I/O module
6.1
Applications of the electronic module
Selecting the application
The diagram below supports you in selecting the application that suits your fail-safe
requirements. In the following sections, you will learn how to wire the F-I/O module for each
application, which specific parameters you need to set in STEP 7 and which errors are detected.
Required
Safety class?
SIL3/Cat.3/PLd
SIL3/Cat.3/PLe
SIL3/Cat.4/PLe
Applications 1 to 3
1
2
3
See case
1
See case
2
See cases
3.1
3.2
Figure 6-1
Selecting the application ‑ Digital input module F-DI 16x24VDC HA
IO redundancy
All application cases can also be set up with IO redundancy to increase availability.
WARNING
Achievable safety class
The achievable safety class depends on the sensor quality and the proof-test interval according
to the IEC standard 61508:2010. If the sensor quality is not as high as required by the required
safety class, the sensor must be used redundantly, have a 2-channel connection and 2-channel
evaluation.
(FDIW-003)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
39
Applications of the F-I/O module
6.1 Applications of the electronic module
Conditions for achieving SIL/Cat./PL
The table below lists the conditions which have to be met for achieving at least the
corresponding safety requirements.
Table 6-1
Conditions for achieving SIL/Cat./PL
Application
Sensor evaluation
Sensor supply
Achievable SIL/
Cat./PL
1
1oo1
Internal or external
3/3/d
2
1oo2
equivalent
Internal, without short circuit
test
3/3/e
External
3.1
1oo2
equivalent
Internal, with short circuit test
3.2
1oo2
non-equivalent
External/internal, with short
circuit test
3/4/e
Note
You can operate the various inputs of an F-I/O module simultaneously in SIL3/Cat.3/PLd and in
SIL3/Cat.3 or Cat.4/PLe. You only have to interconnect the inputs and assign parameters as
described in the following sections.
Sensor requirements
You can find information on the requirements placed on sensors for F-I/O modules in safetyrelated use in section "Requirements placed on sensors for fail-safe modules (Page 51)".
40
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Applications of the F-I/O module
6.2 Application 1: Safety mode SIL3/Cat.3/PLd
6.2
Application 1: Safety mode SIL3/Cat.3/PLd
Wiring
You perform the wiring on the appropriate terminal block. You can find additional information
on this in section "Pin assignment of the F-DI 16x24VDC HA I/O module (Page 15)".
Sensor supply
The sensor supply can be powered internally or externally.
Wiring diagram – connecting one sensor via one channel
One 1-channel sensor (1oo1 evaluation) is connected per process signal. A sensor supply of the
module is assigned to each input.
89Q
',Q
Figure 6-2
One sensor connected via one channel, internal sensor supply
You can also supply the sensor by means of an external sensor supply.
89Q
/
',Q
Figure 6-3
One sensor connected via one channel, external sensor supply
WARNING
Requirement for sensor
To achieve SIL3/Cat.3/PLd using this wiring, you must use a qualified sensor.
(FDIW-004)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
41
Applications of the F-I/O module
6.2 Application 1: Safety mode SIL3/Cat.3/PLd
Parameter assignment
Set the following parameters for the corresponding channel:
Table 6-2
Configuration for internal/external sensor supply
Parameter
Channel with internal sensor sup‐ Channel with external sensor sup‐
ply
ply
Sensor evaluation
1oo1 evaluation
Short-circuit test
•
Disabled
•
Enabled
Sensor supply
Disabled
Internal
External
Fault detection
The following table shows the fault detection depending on the sensor supply and the
configuration of the short-circuit test:
Table 6-3
Fault detection with internal/external sensor supply
Fault
Fault detection
Internal sensor supply,
and short-circuit test ena‐
bled
Internal sensor supply, and
short-circuit test disabled
External sensor sup‐
ply
Yes*
No
No
Input shorted to the associated
sensor supply
No
No
No
Shorted to L+ at DIn
Yes
No
No
Shorted to M at DIn
Yes*
Yes*
No
—
—
—
Yes**
No
—
Yes
Yes
—
Input shorted to other channels or
other sensor supplies
(short circuit with other channels
is detected only if they use a differ‐
ent sensor supply)
Discrepancy error
Shorted to L+ at UVn
Shorted to M at UVn or defect
*) Fault detection only if signals are corrupted. That is, the read signal differs from the sensor signal. If there is no signal corruption
with respect to the sensor signal, fault detection is not possible and is not required from a safety standpoint.
**) If the input has a "1" signal.
WARNING
Short-circuit-proof cable routing
If the short-circuit test is not activated or the sensor supply for digital inputs is set to "External",
you must lay the cable to protect against short-circuits.
(FDIW-005)
42
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Applications of the F-I/O module
6.3 Application 2: Safety mode SIL3/Cat.3/PLe
6.3
Application 2: Safety mode SIL3/Cat.3/PLe
Assigning inputs to each other
Digital input module F-DI 16x24VDC HA has 16 fail-safe inputs DI0 to DI15 (SIL3). You can
combine two of these inputs in pairs to form one input.
The following inputs can be combined in pairs:
• DI0 and DI8
• DI1 and DI9
• DI2 and DI10
• DI3 and DI11
• DI4 and DI12
• DI5 and DI13
• DI6 and DI14
• DI7 and DI15
The process signals are read from channels DI0, DI1, DI2, DI3, DI4, DI5, DI6 and DI7.
Note
You can mix a 1oo1 evaluation and 1oo2 evaluation on an F-digital input module. You must
connect and configure the inputs according to the fail-safe requirements (SIL3/Cat.3/PLd and
SIL3/Cat.3 or Cat.4/PLe).
Wiring
You perform the wiring on the appropriate terminal block. You can find additional information
on this in section "Pin assignment of the F-DI 16x24VDC HA I/O module (Page 15)".
Sensor supply
The sensor supply can be powered internally or externally.
Wiring diagram – connecting a two-channel sensor equivalent
For each process signal, a two-channel sensor is connected equivalent to two inputs of the Fdigital input module (1oo2 evaluation).
89Q
',Q
89Q
',Q
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
43
Applications of the F-I/O module
6.3 Application 2: Safety mode SIL3/Cat.3/PLe
Figure 6-4
One two-channel sensor connected via two channels, internal sensor supply
You can also supply the sensor by means of an external sensor supply.
89Q
/
/
',Q
89Q
',Q
Figure 6-5
One two-channel sensor connected via two channels, external sensor supply
Wiring diagram – connecting two single-channel sensors via two channels
For each process signal, two single-channel sensors, which acquire the same process value, are
connected to two inputs of the F-digital input module (1oo2 evaluation).
89Q
',Q
89Q
',Q
Figure 6-6
Two single-channel sensors connected via two channels, internal sensor supply
You can also supply the sensors by means of an external sensor supply.
89Q
/
',Q
89Q
/
',Q
Figure 6-7
Two single-channel sensors connected via two channels, external sensor supply
WARNING
Requirement for sensor
To achieve SIL3/Cat.3/PLe using this wiring, you must use a qualified sensor.
(FDIW-006)
44
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Applications of the F-I/O module
6.3 Application 2: Safety mode SIL3/Cat.3/PLe
Parameter assignment
Assign the following parameters for the corresponding channel:
Table 6-4
Configuration for internal/external sensor supply
Parameter
Channel with internal sensor
supply
Sensor evaluation
1oo2 evaluation, equivalent
Short circuit test
•
Disabled
•
Enabled
Sensor supply
Channel with external sensor
supply
Disabled
Internal
External
Fault detection
The following table presents fault detection according to the sensor supply and the parameter
assignment for the short circuit test:
Table 6-5
Fault detection with internal/external sensor supply
Fault
Fault detection
Internal sensor supply, and
short-circuit test disabled
Shorted within the channel pair
External sensor supply
No
No
Shorted to other channels or other
sensor supplies
Yes*
Yes
Shorted to L+ at DIn
Yes*
Yes*
Shorted to M at DIn
Yes*
Yes*
Discrepancy error
Yes
Yes
Shorted to L+ at UVn
No
No
Shorted to M at UVn or defect
Yes
—
*) Fault detection only if signals are corrupted. That is, the read signal differs from the sensor signal
(discrepancy error). If there is no signal corruption with respect to the sensor signal, fault detection is not
possible and is not required from a safety standpoint.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
45
Applications of the F-I/O module
6.4 Application 3: Safety mode SIL3/Cat.4/PLe
6.4
Application 3: Safety mode SIL3/Cat.4/PLe
Assigning inputs to each other
Digital input module F-DI 16x24VDC HA has 16 fail-safe inputs DI0 to DI15 (SIL3). You can
combine two of these inputs in pairs to form one input.
The following inputs can be combined in pairs:
• DI0 and DI8
• DI1 and DI9
• DI2 and DI10
• DI3 and DI11
• DI4 and DI12
• DI5 and DI13
• DI6 and DI14
• DI7 and DI15
The process signals are read from channels DI0,DI1,DI2, DI3, DI4, DI5, DI6 and DI7.
Wiring
You perform the wiring on the appropriate terminal block. You can find additional information
on this in section "Pin assignment of the F-DI 16x24VDC HA I/O module (Page 15)".
Sensor supply
The sensor must be supplied internally by at least one channel for application 3.1.
The sensor can be supplied internally or externally for application 3.2.
Requirements for applications in machine protection with Cat.4
Both conditions must be met for applications in machine protection with Cat.4:
• The wiring between sensors and automation system and between automation system and
actuators must be designed to state-of-the-art engineering and standards to prevent short
circuits.
• The sensors are wired as shown in the sections Application 3.1 (SIL3/Cat.4/PLe) (Page 47)
or Application 3.2 (SIL3/Cat.4/PLe) (Page 48). You only need to detect one short circuit
because two faults are required to generate it. This means both signal cables in short circuit
have an isolation fault. A multiple short circuit analysis is not required.
Procedures for locating all short circuits are also permitted if single short circuits are not located.
One of the two conditions must be met for this purpose:
• Short circuits may not corrupt the read signals compared to the sensor signals.
• Short circuits cause a corruption of the read signals compared to sensor signals in the
direction that ensures safety.
46
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Applications of the F-I/O module
6.4 Application 3: Safety mode SIL3/Cat.4/PLe
6.4.1
Application 3.1 (SIL3/Cat.4/PLe)
Wiring diagram – connecting a two-channel sensor via two channels
For each process signal, a two-channel sensor is connected to two inputs of the F-I/O module
(1oo2 evaluation).
Supply the sensors from two different sensor supplies.
89Q
',Q
89Q
',Q
Figure 6-8
One two-channel sensor connected via two channels, internal sensor supply
You can also connect two single-channel sensors via two channels. In this case, the same process
variable is acquired with two mechanically separate sensors.
89Q
',Q
89Q
',Q
Figure 6-9
Two single-channel sensors connected via two channels, internal sensor supply
WARNING
Requirement for sensors
To achieve SIL3/Cat.4/PLe using this wiring, you must use a suitably qualified sensor.
(FDIW-007)
Parameter assignment
Assign the following parameters for the corresponding channel:
Table 6-6
Configuration for evaluation of the sensors, short-circuit test, sensor supply
Parameter
Sensor evaluation
1oo2 evaluation, equivalent
Short circuit test
Enabled
Sensor supply
Internal (at least for one channel internal)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
47
Applications of the F-I/O module
6.4 Application 3: Safety mode SIL3/Cat.4/PLe
Fault detection
The following table presents fault detection according to the sensor supply and the parameter
assignment for the short circuit test:
Table 6-7
Fault detection depending on the sensor supply and short-circuit test
Fault
Fault detection
Shorted within the channel pair, to other chan‐
nels or other sensor supplies
Yes*
Shorted to L+ at DIn
Yes* / Yes (on channel whose short-circuit test is ena‐
bled)
Shorted to M at DIn
Yes*
Discrepancy error
Yes
Shorted to L+ at UVn
Shorted to M at UVn or defect
Yes**
Yes, with "Internal" sensor supply
*) Fault detection only if signals are corrupted. That is, the read signal differs from the sensor signal
(discrepancy error). If there is no signal corruption with respect to the sensor signal, fault detection is not
possible and is not required from a safety standpoint.
**) If the input has a "1" signal and the short-circuit test is enabled.
6.4.2
Application 3.2 (SIL3/Cat.4/PLe)
Wiring diagram – connecting a non-equivalent sensor
For each process signal, an antivalent sensor is connected to two inputs of the F-I/O module
(1oo2 evaluation, antivalent).
89Q
',Q
89Q
',Q
Figure 6-10
Non-equivalent sensor connected, internal sensor supply
You can also supply the sensor by means of an external sensor supply.
89Q
/
',Q
89Q
',Q
Figure 6-11
48
Non-equivalent sensor connected, external sensor supply
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Applications of the F-I/O module
6.4 Application 3: Safety mode SIL3/Cat.4/PLe
WARNING
Requirement for sensors
To achieve SIL3/Cat.4/PLe using this wiring, you must use a suitably qualified sensor.
(FDIW-008)
Wiring diagram – connecting two single-channel sensors non-equivalent
For each process signal, 2 single-channel sensors are connected antivalent to two inputs of the
F-I/O module (1oo2 evaluation).
89Q
',Q
89Q
',Q
Figure 6-12
Two single-channel sensors connected non-equivalent, internal sensor supply
You can also supply the sensors by means of an external sensor supply.
89Q
/
',Q
89Q
/
',Q
Figure 6-13
Two single-channel sensors connected non-equivalent, external sensor supply
WARNING
Requirement for sensors
To achieve SIL3/Cat.4/PLe using this wiring, you must use a suitably qualified sensor.
(FDIW-009)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
49
Applications of the F-I/O module
6.4 Application 3: Safety mode SIL3/Cat.4/PLe
Parameter assignment
Assign the following parameters for the corresponding channel:
Table 6-8
Configuration for evaluation of the sensors, short-circuit test, sensor supply
Parameter
Sensor evaluation
1oo2 evaluation, non-equivalent
Short circuit test
•
Disabled
•
Enabled
•
Internal
•
External
Sensor supply
Fault detection
The following table presents fault detection according to the sensor supply and the parameter
assignment for the short circuit test:
Table 6-9
Fault detection depending on the sensor supply and short-circuit test
Fault
Fault detection
Shorted within the channel pair, to other
channels or other sensor supplies
Yes
Shorted to L+ at DIn
Yes* / Yes (on channel whose short-circuit test is enabled)
Shorted to M at DIn
Yes*
Discrepancy error
Yes
Shorted to L+ at UVn
Shorted to M at UVn or defect
Yes**
Yes, with "Internal" sensor supply
*) Fault detection only if signals are corrupted. That is, the read signal differs from the sensor signal
(discrepancy error). If there is no signal corruption with respect to the sensor signal, fault detection is not
possible and is not required from a safety standpoint.
**) If the input has a "1" signal and the short-circuit test is enabled.
50
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Applications of the F-I/O module
6.5 Requirements placed on sensors for fail-safe modules
6.5
Requirements placed on sensors for fail-safe modules
General sensor requirements
For safety-related use of sensors, you must observe the following important warning:
WARNING
Sensor requirements
Note that a significant responsibility for safety of instrumentation lies with the sensors. Also
keep in mind that sensors generally do not have proof-test intervals of 20 years according to
IEC 61508:2010 without a significant loss of safety.
The probability of dangerous faults or the rate of dangerous faults of a safety function must
adhere to an SIL-dependent upper limit.
You will find the values achieved by the F-modules in their technical specifications.
To achieve the respective safety class, correspondingly qualified sensors are required.
(FDIW-010)
Additional sensor requirements
The following table shows which safety class can be implemented with a given sensor
configuration.
Safety class?
Sensor configuration
SIL3/Cat. 3/PLe
•
With a single-channel connected sensor, if this sensor itself is capable of SIL3/
Cat. 3/PLe.
•
With a two-channel connected sensor that is not capable of SIL3/Cat. 3/PLe.
•
With a two-channel connected sensor.
SIL3/Cat. 4/PLe
WARNING
Safe response of the safety program when the sensor has "0" status
In the case of fail-safe input modules, the value "0" is passed to the F‑CPU after detection of
faults. Therefore you must ensure that sensors are implemented in such a way that the safety
program reacts safely to a "0" state of the sensors.
Example: The safety program of the EMERGENCY OFF sensor must ensure the opening action
on the affected actuator with "0" state (EMERGENCY OFF pushbutton pressed).
(FDIW-011)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
51
Applications of the F-I/O module
6.5 Requirements placed on sensors for fail-safe modules
Requirements for the duration of the sensor signals
WARNING
Sensor signal requirements
Observe the following requirements for the sensor signals:
• To guarantee the correct acquisition of the sensor signals by F-modules with inputs, you
must ensure that the sensor signals have a certain minimum duration.
• So that pulses are reliably detected, the time between two signal changes (pulse duration)
must be greater than the PROFIsafe monitoring time.
(FDIW-012)
Reliable acquisition by F-modules with inputs
The minimum duration of the sensor signals for F-modules with inputs is dependent on the
configured input delay, the parameters of the short-circuit test of the sensor supplies and the
configured discrepancy behavior for 1oo2 (2v2) evaluation.
The duration of the sensor signal must be longer than the maximum response time of the
configured application case. For information on calculating the maximum response time, refer
to section "Response times" of the respective F-module.
The minimum durations yield the maximum permissible switching frequency of the sensor
signals.
Technical specifications of the sensors
Also refer to the device manuals of the F-modules for information on the technical
specifications for selecting the sensors.
52
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Applications of the F-I/O module
6.6 IO redundancy
6.6
IO redundancy
Overview of IO redundancy
For the configuration of IO redundancy, you insert 2 F-DI 16×24VDC HA I/O modules of the same
type next to each other on a redundant block. You can find additional information on the possible
terminal blocks in section "Terminal blocks for the I/O module (Page 13)".
This terminal block connects the respective process signals of the two modules to a common
process terminal.
• The wiring work is lower compared to connecting separate I/O modules, because the
interconnection of the process signals is integrated into the system.
• The redundant signal processing of the sensors at module level increases the availability of
the system.
Note
IO redundancy is briefly described below.
You can find detailed information on this in system manual ET 200SP HA Distributed I/O System.
Configuration and use
For configuration and use of F-DI 16×24VDC HA I/O modules in IO redundancy, the following
requirements apply:
Selection of hardware:
• Redundantly used I/O modules must be identical. This means they must have the same article
number, the same firmware version, and a compatible hardware version.
Installation:
• I/O modules of the same type are plugged in pairs next to each other in the same redundant
terminal block (type "TB45R-P32").
IO redundancy:
• The master module must always be configured at an even slot, the slave module at the
following odd slot.
• The two redundant I/O modules operate simultaneously and independently. Both modules
generate diagnostics, interrupts, messages, process values, etc.
Configuration:
• Assign the redundancy parameters for the I/O module.
• The settings you make for an I/O module always apply to the module pair.
Response to failure
If an I/O module or a channel fails, the following applies to one of the two I/O modules:
• Error-free inputs remain available in the system.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
53
Applications of the F-I/O module
6.6 IO redundancy
54
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Displays, alarms and messages
7.1
7
Status and fault displays of the F-DI 16x24VDC HA I/O module
LED displays
The following figure shows the LED displays of the I/O module:
HA
F-DI
16x24VDC
DIAG MT
F-DI
1
3
5
7
9
11
13
15
DI.0 +
DI.2 +
DI.4 +
DI.6 +
DI.8 +
DI.10 +
DI.12 +
DI.14 +
17
19
21
23
25
27
29
31
UV0
UV2
UV4
UV6
UV8
UV10
UV12
UV14
DI.1+ 2
DI.3 + 4
DI.5 6
DI.7 + 8
DI.9 + 10
DI.11+ 12
DI.13 + 14
DI.15 + 16
+
UV
UV1 18
UV3 20
UV5 22
UV7 24
UV9 26
UV10 28
UV13 30
UV15 32
1P1 L+ 24VDC M 1P2
2P1 L+ 24VDC M 2P2
MAX. 10 A
.0
F0
.2
F2
.4
F4
.6
F6
.8
F8
.10
F10
.12
F12
.14
F14
.1
F1
.3
F3
.5
F5
.7
F7
.9
F9
.11
F11
.13
F13
.15
F15
PWR
X 2
3 4
CC01
6DL1136-6BA00-0PH1
①
②
③
④
⑤
DIAG LED (green/red)
MT LED (yellow)
Channel status LED (green)
Channel fault LED (red)
PWR LED (green)
Figure 7-1
LED displays
Meaning of the LED displays
The tables below explain the meaning of the status and error displays. Measures for dealing with
diagnostics messages can be found in the section "Diagnostic messages (Page 60)".
WARNING
LED of a single input is not safety-related
The LEDs "DIAG", "Channel status" and "Channel fault" of an input are not safety-related and
must therefore not be evaluated for safety-related activities.
(FDIW-015)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
55
Displays, alarms and messages
7.1 Status and fault displays of the F-DI 16x24VDC HA I/O module
DIAG LED
Table 7-1
Diagnostics display of the DIAG LED
DIAG LED
Meaning
The supply voltage of the ET 200SP HA is switched off.
Off
Module is not configured.
Flashes
Module is configured, a diagnostics message is not pending.
On
Module is configured, at least one diagnostics message is pending.
Flashes
/
Module is waiting for user acknowledgment
Alternately flashing
MT LED
Table 7-2
MT LED
Status display of the LED MT
Meaning
No maintenance required.
Off
Maintenance is required, i.e. at least one maintenance event has occurred.
On
LEDs DIAG/MT
Table 7-3
DIAG LED
Meaning of the combination
MT LED
Flashes
on
Meaning
The release button of the I/O module was pressed for at least 3 s
and the I/O module was thereby disconnected from the load.
In addition to this status display, the I/O module sends a corre‐
sponding diagnostics message.
LEDs for channel status/channel fault
Regardless of the parameter assignment, the green "Channel status" LED shows the signal level
at the input terminal.
56
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Displays, alarms and messages
7.1 Status and fault displays of the F-DI 16x24VDC HA I/O module
The red LED "Channel fault" is lit when channel diagnostics for an enabled channel are pending.
Table 7-4
Meaning of the combination
Channel status
LED
Channel fault
LED
Off
Off
Meaning
•
Module is switched off
•
Process signal = 0 and no channel diagnostics pending
Process signal = 1 and no channel diagnostics pending
On
Off
Channel enabled and channel diagnostics pending
Off
On
LEDs Channel status/DIAG/Channel fault
Table 7-5
Channel
status
Off
Flashing
Meaning of the combination
DIAG
Flash‐
ing
Channel
fault
All On
Flash‐
ing
Off
Meaning
•
The PROFIsafe address is different from the configured PRO‐
FIsafe address.
•
Module fault/defect
•
Fault on all channels
Identification of the module for assignment of the PROFIsafe ad‐
dress
PWR LED
Table 7-6
PWR LED
Status display of the PWR LED
Meaning
Supply voltage P (L+) missing.
Off
Supply voltage P (L+) available.
On
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
57
Displays, alarms and messages
7.2 Interrupts
7.2
Interrupts
Introduction
Fail-safe digital input module F-DI 16x24VDC HA supports diagnostics interrupts and
maintenance messages.
Diagnostic interrupts
The F-module generates a diagnostic interrupt for each diagnostics message described in
section "Diagnostic messages (Page 60)".
The following table provides an overview of the diagnostics interrupts of the F-module. The
diagnostics interrupts are assigned either to one channel or to the entire F-module.
Table 7-7
Diagnostic interrupts of F-DI 16x24VDC HA
Diagnostic interrupt
Error code
Effective range
of diagnostic in‐
terrupt
Configurable
Overtemperature
5H
F-module
No
Wire break
6H
Channel
Yes
Parameter error
10H
F-module
No
No supply voltage
11H
F-module
No
Communication error
13H
F-module
No
Channel/component temporarily unavailable
1FH
F-module
No
Mismatch of safety destination address (F_Dest_Add)
40H
F-module
No
Safety destination address not valid (F_Dest_Add)
41H
F-module
No
Safety source address not valid (F_Source_Add)
42H
F-module
No
Safety watchdog time value is 0 ms (F_WD_Time)
43H
F-module
No
Parameter F_SIL exceeds SIL from specific device application
44H
F-module
No
Parameter F_CRC_Length does not match the generated values
45H
F-module
No
Version of F-parameter set incorrect
46H
F-module
No
CRC1 fault
47H
F-module
No
Device-specific diagnostics information, see manual
48H
F-module
No
Save iParameter watchdog time exceeded
49H
F-module
No
Restore iParameter watchdog time exceeded
4AH
F-module
No
Inconsistent iParameters (iParCRC error)
4BH
F-module
No
F_Block_ID not supported
4CH
F-module
No
Transfer error: Inconsistent data (CRC error)
4DH
F-module
No
Transfer error: Timeout (monitoring time 1 or 2 expired)
4EH
F-module
No
Module is defective
100H
F-module
No
Watchdog tripped
103H
F-module
No
Invalid/inconsistent firmware present
11BH
F-module
No
Redundancy partner has different hardware/firmware version
120H
F-module
No
IO redundancy warning
121H
F-module
No
58
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Displays, alarms and messages
7.2 Interrupts
Diagnostic interrupt
Error code
Effective range
of diagnostic in‐
terrupt
Configurable
Shutdown with key operation
122H
F-module
No
Diagnostic queue overflow
13EH
F-module
No
Invalid terminal block
152H
F-module
No
Carrier module or memory in carrier module defective
154H
F-module
No
Terminal block (TB) or memory in terminal block defective
155H
F-module
No
Discrepancy error, channel status 0/0
300H
Channel
No
Discrepancy error, channel status 0/1
301H
Channel
No
Discrepancy error, channel status 1/0
302H
Channel
No
Discrepancy error, channel status 1/1
303H
Channel
No
Overload or internal sensor supply short-circuit to ground
307H
Channel
No
F-address memory not accessible
30DH
F-module
No
No valid F-address available
30EH
F-module
No
Sensor signal flutters
310H
Channel
Yes
Frequency too high
311H
Channel
No
Undertemperature
312H
F-module
No
Discrepancy error
314H
Channel
No
Internal discrepancy error
315H
Channel
No
Input shorted to P
31CH
Channel
Yes
Auxiliary voltage too high
321H
F-module
No
Auxiliary voltage too low
322H
F-module
No
Maintenance messages
The I/O module generates a maintenance message for the following events:
• Redundancy partner has different hardware/firmware
• IO redundancy warning
• Retentive memory in carrier module defective
• Retentive memory in the terminal block defective
You can find additional information on this in section "Maintenance messages (Page 66)".
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
59
Displays, alarms and messages
7.3 Diagnostic messages
7.3
Diagnostic messages
Overview
The F-module generates a diagnostic interrupt for each diagnostics message described in the
following table. In addition, the DIAG LED on the I/O module flashes red or the MT LED lights up
yellow.
In addition, channel-specific diagnostics are indicated by the corresponding channel fault/status
LEDs.
The diagnostics messages can be read from the diagnostics buffer of the CPU, for example.
Module faults are indicated as diagnostics (module status).
After fault correction, you must reintegrate the F-module in the safety program.
You can find additional information on passivation and reintegration of F-I/O in the
programming and operating manual "SIMATIC Industrial Software S7 F/FH Systems Configuring and Programming (https://support.industry.siemens.com/cs/ww/en/view/
109773062)".
Table 7-8
Diagnostics messages of F-DI 16×24VDC HA
Diagnostics message
Error
code
Meaning
Remedy
Overtemperature
5H
An excessively high temperature was
measured in the F-module.
Operate the F-module in the specified
temperature range. (See section "Tech‐
nical specifications (Page 67)")
Once the fault has been eliminated, the
F-module must be removed and inser‐
ted or the power switched OFF and ON
Wire break
6H
Possible causes:
•
Establish a cable connection.
•
The cable between the module and
the sensor is broken. The channel is
not wired (open).
•
Disable wire break detection for the
channel in the configuration.
•
Eliminate the short-circuit.
•
There is a short-circuit between
channels with different signals.
See the note below *1) regarding this
message.
Parameter error
10H
Parameter assignment errors include:
•
The F-module cannot use the pa‐
rameters (unknown, invalid combi‐
nation, etc.).
•
The F-module parameters have not
been configured.
Correct the parameter assignment.
No supply voltage
11H
Supply voltage missing or too low
Communication error
13H
A communication error has occurred.
The solution depends on the cause.
The possible causes depend on the
module type used.
You can find information on this in the
manual for the F-module.
60
•
Check the supply voltage P on the
terminal block
•
Check the terminal block type
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Displays, alarms and messages
7.3 Diagnostic messages
Diagnostics message
Error
code
Meaning
Remedy
Channel/component temporari‐ 1FH
ly unavailable
Possible causes:
Perform the firmware update again.
Mismatch of safety destination
address (F_Dest_Add)
40H
The F-module has detected a different F- Check the parameter assignment of the
destination address.
PROFIsafe driver and the address setting
of the F-module.
Safety destination address not
valid (F_Dest_Add)
41H
The F-module has detected an invalid F- Check the parameter assignment of the
destination address.
PROFIsafe driver.
Safety source address not valid
(F_Source_Add)
42H
The F-module has detected an invalid Fsource address.
Safety watchdog time value is
0 ms (F_WD_Time)
43H
The F-module has detected an invalid
watchdog time.
Parameter F_SIL exceeds SIL
from specific device application
44H
The F-module has detected a discrepan‐
cy between the SIL setting of the com‐
munication and the application.
Parameter F_CRC_Length does 45H
not match the generated values
The F-module has detected a discrepan‐
cy in the CRC length.
Version of F-parameter set in‐
correct
46H
The F-module has detected an invalid
version of the F-parameters.
CRC1 fault
47H
The F-module has detected inconsis‐
tent F-parameters.
Device-specific diagnostics in‐
formation, see manual
48H
The F-module has detected inconsis‐
tent F-parameters.
•
Error in firmware update
Save iParameter watchdog time 49H
exceeded
iPar server does not respond to "Save"
request.
Check configuration / parameter assign‐
ment of the iPar server.
Restore iParameter watchdog
time exceeded
4AH
iPar server does not respond to "Re‐
store" request.
Check configuration / parameter assign‐
ment of the iPar server.
Inconsistent iParameters
(iParCRC error)
4BH
The F-module has detected inconsis‐
tent iParameters.
Check the parameter assignment.
F_Block_ID not supported
4CH
The F-module has detected an incorrect Check the parameter assignment of the
block ID.
PROFIsafe driver.
Transfer error: Inconsistent da‐
ta (CRC error)
4DH
The F-module has detected a CRC error.
Transfer error: Timeout (moni‐
toring time 1 or 2 expired)
•
Possible causes:
4EH
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
•
The communication between F-CPU •
and F-module is disturbed.
•
Electromagnetic interference is too
high.
•
An error has occurred in the sign-oflife monitoring.
Check the communication connec‐
tion between F-module and F-CPU.
Eliminate the electromagnetic inter‐
ference.
The F-module has detected a timeout.
•
Check the parameter assignment.
Possible causes:
•
Ensure that communication is func‐
tioning.
•
The F-monitoring time is set incor‐
rectly.
•
There is a bus fault.
61
Displays, alarms and messages
7.3 Diagnostic messages
Diagnostics message
Error
code
Meaning
Remedy
Module is defective
100H
Possible causes:
•
Eliminate the interference. The mod‐
ule must then be pulled and plug‐
ged, or the power switched OFF and
ON
•
Replace the F-module.
•
Eliminate the interference. The mod‐
ule must then be pulled and plug‐
ged, or the power switched OFF and
ON
Watchdog tripped
Invalid/inconsistent firmware
present
103H
11BH
•
Impermissibly high electromagnet‐
ic interference is present.
•
The F-module is defective.
Possible causes:
•
Impermissibly high electromagnet‐
ic interference is present.
•
The F-module has detected an inter‐
•
nal error and responded to it in a
safety-related manner.
The firmware is incomplete and/or firm‐ •
ware added to the F-module is incom‐
patible. This leads to errors or function‐
al limitations when operating the F•
module.
If the F-module cannot be put back
into operation, consider replacing it.
Perform a firmware update of the Fmodule and watch out for any error
messages.
Use only firmware versions released
for this F-module.
Shutdown on button activation 122H
The release button of the I/O module
was pressed for at least 3 s and the I/O
module was thereby disconnected from
the load.
Diagnostics memory overflow
13EH
Overflow of the diagnostics memory.
Correct the cause of the diagnostic
Not all pending diagnostics information memory overflow.
could be sent. This fault can lead to dis‐
abling of the F-module until the supply
voltage is switched off/on.
Invalid terminal block
152H
The terminal block cannot be used with
the current F-module.
Replace the terminal block.
Carrier module or memory in
carrier module defective
154H
An error of the carrier module or of the
memory module on the carrier module
was detected during operation.
Replace carrier module
Terminal block (TB) or memory
in terminal block defective
155H
An error of the terminal block or the
Replace carrier module
memory chip on the terminal block was
detected during operation.
62
The enable button is pressed to pull the
I/O module during operation and to be
able to replace it, for example. Perform
the desired action.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Displays, alarms and messages
7.3 Diagnostic messages
Diagnostics message
Error
code
Meaning
Remedy
Discrepancy error, channel sta‐
tus 0/0
300H
Possible causes:
•
Check the process signal.
•
The process signal is faulty.
Discrepancy error, channel sta‐
tus 0/1
301H
•
Replace the sensor.
•
The sensor is defective.
•
Discrepancy error, channel sta‐
tus 1/0
302H
•
The configured discrepancy time is
too low.
Check the parameter assignment of
the discrepancy time.
•
Check the process wiring.
Discrepancy error, channel sta‐
tus 1/1
303H
Possible causes:
•
Eliminate the overload.
•
The internal sensor supply is shortcircuited to ground.
•
Eliminate the short circuit in the
process wiring.
•
Impermissibly high electromagnet‐
ic interference is present.
•
Check the "Sensor supply" parame‐
ter.
See the note below *1) regarding this
message.
•
Eliminate/reduce the electromag‐
netic interference.
No valid PROFIsafe address is stored in
the retentivity memory.
•
Assign the PROFIsafe address during
initial commissioning or when delib‐
erately changing parameters.
•
Check the consistency between the
nominal and actual configuration.
Overload or internal sensor sup‐ 307H
ply short-circuit to ground
F-address memory not accessi‐
ble
30DH
•
There is a short-circuit between the
cable of an "unconnected sensor"
and the sensor supply cable.
•
Wire break in the line of a "connec‐
ted sensor" or the sensor supply ca‐
ble
•
An error occurred during the dis‐
crepancy check.
Possible causes:
•
Initial commissioning
•
Deliberate parameter change of the
PROFIsafe address
•
Deviation between set and actual
configuration of the plant
No valid F-address available
30EH
F_source_address and F_destina‐
tion_address parameters invalid
Sensor signal flutters
310H
Too many signal changes have occurred •
within the time configured with the
"Monitoring window" parameter.
•
• The "Monitoring window" setting is
too high.
•
• The "Number of signal changes" pa‐
•
rameter setting is too low.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Check F_source_address and F_destina‐
tion_address parameters
•
A momentary interruption/short cir‐
•
cuit of the sensor cable (loose con‐
tact) is present.
•
Impermissibly high electromagnet‐
ic interference is present.
•
The sensor/switch bounces.
•
The sensor is defective.
Check the "Monitoring window" pa‐
rameter.
Check the "Number of signal
changes" parameter.
Check the process wiring.
Eliminate/reduce the electromag‐
netic interference.
Replace the sensor.
63
Displays, alarms and messages
7.3 Diagnostic messages
Diagnostics message
Error
code
Meaning
Remedy
Frequency too high
311H
The maximum switching frequency of
the F-module has been exceeded.
Reduce the switching frequency of the
sensor.
Undertemperature
312H
The minimum permissible temperature
limit has been violated.
Operate the F-module in the specified
temperature range. (See section "Tech‐
nical specifications (Page 67)")
Discrepancy error
314H
The 1oo2 discrepancy time set for op‐
eration has been exceeded.
Check the discrepancy time, the sensors
and their wiring.
Possible causes:
Internal discrepancy error
Input shorted to P
315H
31CH
•
Incorrect parameter assignment
•
Wire break of the supply cable of the
sensor
An error occurred during the plausibility •
check of the input signal between the
processors. You must correct the error
•
within 100 hours.
•
Possible causes:
•
The input signal is disturbed, For ex‐
ample, by impermissibly high elec‐
tromagnetic interference.
•
A high-frequency input signal is
present. for example, due to mutual
interference of sensors or because
the signal is above the sampling fre‐
quency of the input signal.
•
There is a brief interruption / transi‐
ent short-circuit of the sensor line
(loose contact).
•
The sensor/switch bounces.
Use shielded cables to reduce influ‐
ences on EMC
Reduce the input frequency
Check the wiring of the sensor.
Possible causes:
•
Check the wiring.
•
The input signal is short-circuited
with P.
•
Check the configured test time and
the process wiring.
•
There is a short-circuit in the inter‐
nal sensor supply with P.
•
Replace the sensor.
•
There is a short circuit of two sensor
supplies.
•
The capacitance of the connected
sensor for the configured test time is
too high.
•
The sensor is defective.
Auxiliary voltage too high
321H
The supply voltage is too high.
Check the supply voltage.
Auxiliary voltage too low
322H
The supply voltage is too low.
Check the supply voltage.
64
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Displays, alarms and messages
7.3 Diagnostic messages
Note
Note *1) for the messages "Overload or internal sensor supply short-circuit to ground"
(307H) and "Wire break" (6H)
With incoming diagnostics message "Overload or internal sensor supply short-circuit to ground",
a wire break (incoming/going) may also be signaled. The wire break signal (6H) can be ignored
in this case.
Supply voltage outside the nominal range
If the supply voltage P is outside the specified value range, the DIAG LED flashes and the module
is passivated.
After subsequent voltage recovery (level must be within the specified value range for at least 1
minute (see section "Technical specifications (Page 67)": Voltages, currents, potentials), the
DIAG LED stops flashing. The module remains passivated and waits for user acknowledgment.
Behavior in case of cross circuit/short circuit to the sensor supply
With configured internal sensor supply and deactivated short-circuit test, M short-circuits to the
sensor supplies are detected. Channels for which the relevant sensor supply is configured will be
passivated.
Short-circuits from ground to the sensor supply are detected for a configured internal sensor
supply and activated short-circuit test. Channels for which the relevant sensor supply is
configured will be passivated.
Special features for fault detection
The detection of some faults (e.g. short-circuits, discrepancy errors) depends on the application,
the wiring, the configuration of the short-circuit test and the configuration of the sensor supply.
You can find the corresponding tables for fault detection for the applications in section
"Applications of the F-I/O module (Page 39)".
General information on diagnostics
You can find additional information on diagnostics that pertains to all F-modules (e.g. readout
of diagnostic functions, passivation of channels) in the programming and operating manual
"SIMATIC Industrial Software S7 F/FH Systems - Configuring and Programming (https://
support.industry.siemens.com/cs/ww/en/view/109773062)".
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
65
Displays, alarms and messages
7.4 Maintenance messages
7.4
Maintenance messages
Overview
A maintenance event is generated every time a maintenance requirement is determined. The
MT LED lights up on the module.
Maintenance messages do not have a direct influence on the functions of the module or digital
inputs.
Table 7-9
Maintenance messages of F-DI 16×24VDC HA
Maintenance message
Error
code
Assign‐ Meaning / Cause
ment
Remedy
Redundancy partner has
different hardware/firm‐
ware version
120H
Module
The redundantly configured I/O
modules are not compatible.
Check the hardware version and firmware
version of the modules and replace modules
or perform a firmware update.
IO redundancy warning
121H
Module
Unable to correctly communi‐
cate with the partner module
•
Check/replace right module
•
Check/replace left module
•
Check/replace terminal block
See also system manual ET 200SP HA Distrib‐
uted I/O System, section "Communication er‐
rors", "I/O redundancy warning" (Mainte‐
nance event: Error code 121H)"
Carrier module or memo‐ 154H
ry in carrier module de‐
fective
Module
A fault of the carrier module or
of the memory module on the
carrier module was detected
during operation.
Replace carrier module
Terminal block (TB) or
memory in terminal
block defective
Module
A fault of the terminal block or
the memory chip on the termi‐
nal block was detected during
operation.
Replace carrier module
66
155H
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Technical specifications
8
Technical specifications of F-DI 16x24VDC HA
Note
Power supply
The supply and input voltages of the ET 200SP HA system must always be generated with
voltage/current supplies with protection by electrical separation (SELV/PELV according to IEC/UL
61010-2-201) with a nominal value of 24 V DC ±20%.
Note
Bridging of supply failures
For compliance with IEC 61131-2, EN 298 and the NAMUR Recommendation NE 21, use only
power supplies (230 V AC --> 24 V DC) with bridging of supply failures of at least 20 ms. You can
find up-to-date information on PS components on the Internet (http://
mall.automation.siemens.com).
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
67
Technical specifications
Article number
6DL1136-6BA00-0PH1
General information
Firmware version
V1.0.1
•
Yes
FW update possible
Usable terminal block
TB type H1 and M1
Color code for module-specific color identifica‐
tion plate
CC01
Product function
•
I&M data
Yes; I&M0 to I&M3
Engineering with
•
PCS 7 configurable/integrated from version
V9.0 SP3
Operating mode
•
DI
Yes
Redundancy
•
Redundancy capability
Yes; With TB type M1
Supply voltage
Rated value (DC)
24 V
permissible range, lower limit (DC)
19.2 V
permissible range, upper limit (DC)
28.8 V
Reverse polarity protection
Yes
Input current
Current consumption (rated value)
80 mA
Current consumption, max.
150 mA
Encoder supply
Number of outputs
16
24 V encoder supply
•
24 V
Yes; Min. L+ (-1 V)
•
Short-circuit protection
Yes; electronic (response threshold 0.7 A to 1.5 A;
for IO redundancy up to 3 A). Ensure sufficient ca‐
ble cross-section to attain the response threshold.
Depending on the cable cross-section used, there
may be constraints regarding the usable length of
cable
•
Output current per channel, max.
0.5 A
•
Output current per module, max.
8A
Power
Power available from the backplane bus
90 mW
Power loss
Power loss, typ.
3.2 W; All channels equipped with internal encoder
supply and switch contacts, at rated voltage and
ambient temperature
Address area
Address space per module
•
68
Inputs
9 byte
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Technical specifications
Article number
•
Outputs
6DL1136-6BA00-0PH1
5 byte
Hardware configuration
Automatic encoding
Yes
Digital inputs
Number of digital inputs
16
Digital inputs, parameterizable
Yes
Source/sink input
Yes; P-reading
Input characteristic curve in accordance with IEC
61131, type 1
Yes
Input characteristic curve in accordance with IEC
61131, type 2
No
Input characteristic curve in accordance with IEC
61131, type 3
No
Pulse extension
Yes
•
off, 50 ms, 100 ms, 200 ms, 500 ms, 1 s, 2 s
Length
Time stamping
Yes; Resolution 10 ms
Signal change flutter
Yes
Flutter observation window
Yes
Input voltage
•
Rated value (DC)
24 V
•
for signal "0"
-30 to +5 V
•
for signal "1"
+15 to +30 V
Input current
•
for signal "1", typ.
2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
– parameterizable
Yes
Cable length
•
shielded, max.
1 000 m
•
unshielded, max.
600 m
Encoder
Connectable encoders
•
2-wire sensor
Yes
– permissible quiescent current (2-wire
sensor), max.
1.5 mA
Interrupts/diagnostics/status information
Diagnostics function
Yes
Alarms
•
Diagnostic alarm
Yes
•
Maintenance interrupt
Yes
Diagnostic messages
•
Diagnostic information readable
Yes
•
Monitoring the supply voltage
Yes; Module-wise
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
69
Technical specifications
Article number
6DL1136-6BA00-0PH1
– parameterizable
Yes
•
Monitoring of encoder power supply
Yes; channel by channel
•
Wire-break
Yes; channel by channel, optional protective circuit
for preventing wire-break diagnostics in the case of
simple encoder contacts: 18 kOhm to 30 kOhm,
typical 26 kOhm
•
Short-circuit to M
Yes; Encoder supply to M, channel by channel
Diagnostics indication LED
•
MAINT LED
Yes; Yellow LED
•
Monitoring of the supply voltage (PWR-LED)
Yes; green PWR LED
•
Channel status display
Yes; green LED
•
for channel diagnostics
Yes; red LED
•
for module diagnostics
Yes; green/red LED
Potential separation
Potential separation channels
No
•
between the channels
•
between the channels and backplane bus
Yes
between the channels and the power supply
of the electronics
No
•
Isolation
Isolation tested with
1 500 V DC/1 min, type test
Standards, approvals, certificates
Highest safety class achievable in safety mode
•
Performance level according to ISO 13849-1
Up to PLe
•
Category according to ISO 13849-1
Cat. 4
•
SIL acc. to IEC 61508
Up to SIL 3
Probability of failure (for service life of 20 years
and repair time of 100 hours)
– Low demand mode: PFDavg in accord‐
ance with SIL3
< 3.00E-05
– High demand/continuous mode: PFH in
accordance with SIL3
< 2.00E-09 1/h
Ambient conditions
Ambient temperature during operation
•
horizontal installation, min.
-40 °C
•
horizontal installation, max.
70 °C
•
vertical installation, min.
-40 °C
•
vertical installation, max.
60 °C
Dimensions
Width
22.5 mm
Height
115 mm
Depth
138 mm
Weights
Weight, approx.
70
210 g
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Technical specifications
Derating curve
• The following figures show the load current derating of the internal sensor supply in
horizontal and vertical mounting position.
The underlying scenario provides for wiring of the inputs with a maximum value of 30V as
defined in IEC 61131-2 for Type 1 sensors.
7RWDOFXUUHQWRI
HQFRGHUVXSSO\>$@
Total current I [A]
Horizontal mounting position
(28.8/30V)
$PELHQWWHPSHUDWXUH>R&@
Figure 8-1
Load current derating of the sensor supply in horizontal mounting position (scenario according to IEC 61131-2,
Type 1)
7RWDOFXUUHQWRI
HQFRGHUVXSSO\>$@
Detailed description
Total current I [A]
Horizontal mounting position
(28.8/30V)
$PELHQWWHPSHUDWXUH> &@
R
Figure 8-2
Enlarged section of the load current derating of the sensor supply in horizontal mounting position (scenario
according to IEC 61131-2, Type 1)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
71
Technical specifications
7RWDOFXUUHQWRI
HQFRGHUVXSSO\>$@
Total current I [A]
Vertical mounting position
(28.8/30V)
$PELHQWWHPSHUDWXUH> &@
R
Figure 8-3
Load current derating of the sensor supply in vertical mounting position (scenario according to IEC 61131-2, Type
1)
• The following figures show the load current derating of the internal sensor supply in
horizontal and vertical mounting position. The underlying scenario provides for wiring of the
inputs with a typical value of 24V.
7RWDOFXUUHQWRI
HQFRGHUVXSSO\>$@
Total current I [A]
Horizontal mounting position
(24/24V)
$PELHQWWHPSHUDWXUH> &@
R
Figure 8-4
72
Load current derating of the sensor supply in horizontal mounting position (typical scenario)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Technical specifications
7RWDOFXUUHQWRI
HQFRGHUVXSSO\>$@
Total current I [A]
Vertical mounting position
(24/24V)
$PELHQWWHPSHUDWXUH>R&@
Figure 8-5
Load current derating of the sensor supply in vertical mounting position (typical scenario)
Load current when using up to 12 channels
• Horizontal mounting position:
Up to 70 °C when using the internal sensor supplies
(Total current of the outputs 1.5 A)
• Vertical mounting position:
Up to 60 °C when using the internal sensor supplies
(Total current of the outputs 1 A)
Cycle time
The cycle time describes the time during which signals from the inputs are recorded and
processed. The cycle time of the I/O module is approx. 4 ms.
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
73
Technical specifications
74
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Response times
A
Introduction
The response times of digital input module F-DI 16x24VDC HA are found below. The response
times of the digital input module go into the calculation of the F-system response time.
Definition of response time for fail-safe digital inputs
The response time represents the interval between a signal change at the digital input and
reliable availability of the safety frame on the backplane bus.
Times required for the calculation
• Max. cycle time: Tcycle = 6 ms
• Max. acknowledgment time (Device Acknowledgement Time): TDAT = 12 ms
The maximum response time when a fault is present (One Fault Delay Time, OFDT) corresponds
to the maximum response time under fault-free conditions (Worst Case Delay Time, WCDT).
Maximum response time under fault-free conditions (Worst Case Delay Time, WCDT), with 1oo1
evaluation
• The following formula applies to a sensor supply without short-circuit test:
t <= 2 * Tcycle + Input delay
• The following formula applies to a sensor supply with short-circuit test:
t <= 2 * Tcycle + Input delay + T1 + T2
T1
T2
Time for short-circuit test
Startup time of the sensor after the short-circuit test
Maximum response time under fault-free conditions (Worst Case Delay Time, WCDT), with 1oo2
evaluation
• The following formula applies to a sensor supply without short-circuit test:
t <= 2 * Tcycle + Input delay + Discrepancy time*)
• The following formula applies to a sensor supply with short-circuit test:
t <= 2 * Tcycle + 2 * Input delay + max. (T1p + T2p, T1s + T2s) + Discrepancy time*)
*)
Not applicable for behavior at discrepancy "provide value 0".
T1p
T2p
Test time for sensor supply of sensor 1
Startup time of sensors after the short-circuit test (sensor 1)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
75
Response times
T1s
T2s
Test time for sensor supply of sensor 2
Startup time of sensors after the short-circuit test (sensor 2)
Maximum response time to external short-circuits
t <= 2 * Tcycle + 2 * (n * 10 * Tcycle) + 2 * Total [x=0…15](T1x + T2x)
T1x
T2x
n
x
Time for sensor test
Startup time of the sensor after the short-circuit test
Number of sensor supplies with enabled short-circuit test
Sensor supply
Maximum response time to discrepancy error with 1oo2 evaluation
t <= 2 * Tcycle + 2 * Input delay + Discrepancy time + max. (T1p + T2p, T1s + T2s)
T1p
T2p
T1s
T2s
76
Test time for sensor supply of sensor 1
Startup time of sensors after the short-circuit test (sensor 1)
Test time for sensor supply of sensor 2
Startup time of sensors after the short-circuit test (sensor 2)
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Index
Output disable switch, 11
C
Channel fault LED, 55
Channel parameters, 20
Channel status LED, 55
Conventions, 7
P
Parameter, 19
Pin assignment, 15
PWR LED, 57
D
R
DIAG LED, 56
Diagnostic interrupt, 58
Documentation
Range of validity, 7
Redundant I/O, 53
S
Schematic circuit diagram, 17
F
F-DI 16x24VDC HA
Accessories, 11
Channel parameters, 20
Functions, 10
Module parameters, 20
Parameters, 19
Pin assignment, 15
Properties, 10
Schematic circuit diagram, 17
T
Terminal block, 13
V
Value status, 38
I
IO redundancy, 53
L
LED displays, 55
M
Maintenance message, 59
Module parameters, 20
MT LED, 56
O
Operational safety
Safety aspects, 8
Security concepts and communication, 8
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
77
Index
78
F-DI 16x24VDC HA
Equipment Manual, 01/2021, A5E45647528-AC
Download