1. A balanced three-phase Y-connected source has, using a positive sequence Van = 390 Vrms at 30 degrees angle. Find Vab. 2. In a polyphase system, voltages Va = 120∠45oV and Vb = 10∠-15oV with respect to a reference node o. Find voltage Vba in polar form. 3. The terminals of a three-phase supply are labelled a, b, c. Between any pair a voltmeter measures 115 V. A resistor of 100 ohms and a capacitor of 100 ohms at the frequency of the supply are connected in series from a to b with the resistor connected to a. The point of connection of the elements to each other is labelled in n. Determine the voltmeter reading between c and n if phase sequence is a-c-b. 4. Three impedances of 4-j3 ohms are connected in Y to a 208 V, three-phase line. Find the complex power. 5. Three equal star connected circuit components take 8kW at a power factor of 0.8 lagging when connected across 410V, 3 phase, 3 ≤wire, 50 Hz. Find the inductance component per phase of the load. 6. In a balanced three-phase system the Yconnected impedances are 10≤30 ohms. If Vbc = 416∠90 volts, solve for Icn. 7. Three identical delta=connected load when supplied from a 230 volts, 60 Hz, 3-phase, 3 wire supply draws a line current of 10 A at a pf of 0.8 lagging. Determine the inductance of the load per phase. 8. A balanced 3-phase load consumes a total power of 100 kW at a power factor of 0.6 lagging, the line voltage being 1000V. Determine the value of the reactive component per phase assuming delta connection with resistance and reactance in parallel. 9. Three delta connected resistors absorb 60kW when connected to a 3-phase line. If the resistors are connected in star, the power absorbed is. 10. A balanced delta-connected load with impedance Z= 30∠30 ohms per phase is connected to a three-phase, three wire 250 V system by conductors having an impedance of Z =0.4 + j0.3 ohm per conductor. Obtain the line to line voltage at the load. 11. A three-phase 120V circuit has a sequence of abc and delivers power to a group of delta connected impedances whose values are Zab= 10 + j0; Zbc = 5+j8.66 and Zca=8.66 +j5. Determine the line current in line a. 12. A balanced set of three-phase voltages is connected to an unbalanced set of Y-connected impedances. The following values are known: Vab = 212∠90π ; πππ = 212∠ − 150 π; πππ = 212∠ − 30 π ; πππ = 10πΊ ; πππ = 10 + π10πΊ; Zcn = -j20Ω. Find the line current in line a. 13. A 3-phase, 4 wire, ABC system, with Vbc + 294.2∠0 , has the Y-connected impedances , Za= 12∠45 Ω, Zb=10∠30πΊ , Zc= 8∠0 Ω. Obtain the current in the neutral wire. 14. A balance delta connected load Z = 9∠ − 30 ohms and a balance wye connected load, with Z = 5∠45 ohms, are supplied by the same ABC system, with effective line voltage 480V. Solve line current. 15. A balanced delta load consisting of pure resistances of 15 ohms per phase is in parallel with a balanced Y-load having phase impedances of 8+j6 ohms. Identical impedances of 2 + j5 ohms are in each of the three lines connecting the combined loads to a 110-V three phase supply. Find the line voltage at the combined loads. 16. A 4-wire 208V, three=phase 60Hz system is used to supply power to a three-phase 5 hp induction motor and a single phase 6 kW heater connected between line c and the neutral line. The operating efficiency and power factor of the motor are 82 and 71%, respectively. Determine the current in line c. 17. Three equal impedances of (8 + j7) ohms are connected in delta to lines a, b, and c of a 240 V, 3-phase, 3-wire line. What is the reading of a single-phase wattmeter connected with its current coil in line a and potential coil across lines b and c? Assume and abc sequence. 18. A 3-phase, 3 wire load draws the following line currents: Ia= 60 cis 330 A; Ib = 78.4cis 214 A; Ic = 75 cis 80 A. If the voltages impressed on the load are balanced 3-phase, having a magnitude of 4140 volts line to line, solve for the total power in kW. 19. A balanced 3-phase load draws 75 amperes line current at 230 volts line to line, and 0.848 lagging power factor. If the two-wattmeter method is used, solve for the readings of the wattmeters. 20. Two wattmeters in a three-phase, threewire system with effective line voltage of 120 V read 1500 W and 500 W. What is the impedance of the balanced delta connected load? 21. A wattmeter is used to measure power drawn by a 230V, 3-phase induction motor. The current coil is placed in line 1 while the potential coil is shifted from lines 1 and 2, then from lines 1 and 3 respectively. If the wattmeter registers 5760 and 3380 watts respectively, what is the line current drawn by the motor? 22. A 3-phase, 50hp, 440V, 50 Hz induction motor operates on full load with an efficiency of 89% and at a power factor of 0.85 lagging. Calculate the total kVAR rating of a capacitor bank required to raise the full load pf of 0.95 lagging. 23. Three loads are connected in parallel across a 12.47 kV three-phase supply. Load 1: Inductive 60kW and 660 kVAR Load 2: Capacitive load, 240kW at 0.8pf Load 3: Resistive load of 60kW A Y-connected capacitor bank is connected in parallel with the loads. What is the capacitance per phase in uF to improve the overall pf to 0.8 lagging? Constant Practice Makes You Perfect 1. On a 120/208-V four wire Y system, two lamps are connected from phase A to neutral, 5 lamps from phase B to neutral and four lamps have the same rating and each draws 2 A, find the current in the neutral wire. A. 0 A B. 8.66 A C. 6.93 A D. 5.29 A 2. Two balanced three-phase loads are connected in parallel. Load 1 draws 20 kW at a lagging power factor of 0.85; Load 2 draws 15 kW at a lagging power factor of 0.5. The line voltage at the terminals at the load is 440 V. The load terminals are connected to the source teminals by means of cables which have an impendance of 1 +j3 ohms each. Calculate the line voltage at the terminals of the source. A. 795 V C. 778 V B. 805 V D. 788 V 3. A three-phase, 339.4 V, ABC system has a delta connected load with ZAB = 10∠0 Ω, ZBC =10∠30Ω, and ZCA=15∠-30 ohms. Find the current in line A. A. 49.23 A B. 64.18 A C. 23.83 A D. 54.72 A 4. A 440 V three-phase three-wire system feeds two balanced Y-connected loads. One load is an induction motor which maybe represented by an impedance of 10 = j5 ohms per phase. The other is a lighting load equivalent to 15 ohms per phase. Find the total average power A. 32.11kW B. 25.52kW C. 30.28kW D. 28.37kW 5. A3-phase,50 hp, 440 V, 50 Hz induction motor operates a full load with an efficiency of 89% and at a power factor of 0.85 lagging. A capacitor bank is sonnected is parallel to raise the full load pf to 0.95 lagging. What will bw the capacitance per phase if the capacitors are delta-connected? A. 66.85 uF B. 9.23 uF C. 47.65 uF D. 12.65 uF 6. In a balanced three-phase, 208 V circuit, the line current is 100 A. The power is measured by two wattmeter method. If the power factor is unity, which one is a probable reading on one of the wattmeters? A. 20kW B. 18kW C.36kW D. 24kW 7. A three-phase, four-wire 150-V, CBA system has a Y-connected load, with ZA=6∠0 Ω, ZB= 6∠30Ω and Zc= 5∠45Ω. Solve the current in the neutral wire. A. 10.21 A B. 15.82 A C. 19.89 A D. 21.12 A 8. A three-phase, three-wire 500V, 60 Hz source supplies a three-phase inductor motor, a wye connected capacitor bank that draws 2 kVAR per phase, and a balanced three-phase heater that draws a total of 10 kW. The induction motor is operating at its rated 75 hp and has an efficiency and power of 90.5 and 89.5 percent, respectively. Determine the system complex power. A. 75.89 + j24.81 B. 71.82 + j24.81 C. 75.98 – j24.81 D. 71.82 – j24.81 9. Three 50- ohm resistor are connected in star across 400V, 3-phase supply. If one of the resistor is disconnected, then the line current will be ___. A. 8 A B. 13.85 A C. 4 A D. 0 10. A 400-V, 3-phase, 4-wire service mains supplies a star connected load. The resistance of each line is 0.1 ohm and that of the neutral 0.2 ohm. The load impedances are Z1= (6 +j9) ohms; Z2= 8 OHMS; Z3= (6-j8) ohms. Calculate the current in the neutral. A. 56.22 A B. 50.06 A C. 45.18 A D. 49.35 A 11. Three identical loads having an impedance of (8.66 +j5) ohms are connected in wye across a balanced three-phase system with consequence set with Vab =(300 + j0) volts. If a wattmeter is connected in the circuit with its current coil on line A and potential coil across lines A and C, determine the meter reading. A. 5.196 kW B. 5.264 kW C. 5.342 kW D. 5.428kW 12. A three-phase, 3-wire balanced delta connected load yields wattmeter readings of 1154 W and 557 W. Obtain the load resistance per phase if the line voltage is 100 V. A. 18Ω B. 12Ω C. 10Ω D. 13Ω 13. A factory is supplied at 11 kV, 50 Hz system and has the following balanced loads: Load A: 1.5 MW at 90% lagging pf; Load B: 600 kW at 100% pf; Load C: 2 MVA at 98% lagging pf; Load D: 3 MVA at 805 lagging pf. A 3-phase and of star connected capacitors is connected at the supply terminals to give power factor correction. Find the required capacitance per phase to given an overall power factor of 98% lagging when factory is operating at maximum load. 14. Three impedances of 3 + j4, ohms are connected in delta to a 220-V three-phase line. Find the complex power A. 6.92 + j5.19 kVA B. 6.92 +j5.19 kVA C. 17.4 + j23.2 kVA D. 17.4 – j23.2 kVA 15. A three-phase, three-wire system, with a line voltage Vbc= 339.4∠0 volts, has a balanced Y-connected load of ZY= 15∠60 ohms. The lines between the system and the load have impedances 2.24∠26.57 ohms. Find the line voltage magnitude at the load. A. 301.1 V B. 308.5 V C. 310.4 V D. 316.2 V 16. A three-phase 120-V circuit has a sequence of abc and delivers power to a group of delta connected impedances whose values are Zab= 10 +j0; Zbc= 5 +j8.66 and Zca= 8.66 +j5. Determine the line current in line b. A. 17 A B. 20 A C. 24 A D.12 A 17. Three equal impedances (60 + j30) ohms are connected in delta at the end of a three-phase transmission line which has an impedances of (1 + j2) ohms per conductor. If the line voltage at the generating station is maintained at 2300 V, find line to line voltage at the load. A. 2150 V B. 2122 V C. 2142 V D. 2126 V 18. A delta connected load with 50-Ω resistance, 209-Mh inductance and 50-Uf capacitance in series per phase is supplied at 500 rad/sec. With Vcn=390 cis 30 deg as reference, what is the phase C line current? A. 13.27 –j5.42 A B. 12.52 –j5.42 A C. 13.27 –j 4.28 A D. 12.52 –j4.28 A 19. The pf of each phase of balanced wyeconnected 5 ohm impedance is 0.6 lagging. This impedance is connected to a source having a 100-V phase voltage. Determine the apparent power drawn by the circuit. A. 6.0 kVA B. 3.6 kVA D. 5.4 kVA A. 42.9 uF B. 53.6 uF C. 4.8 kVA C. 33.7 uF D. 38.3 uF 20. A 3-phase, 40 Kw, 440 V, 60 Hz induction motor operates at full load with an efficiency of 90 % at 0.80 lagging pf. It is required to raise the full load power factor to 0.90 lagging. A threephase bank capacitors are connected across the load. What will be the capacitance per phase if the capacitors are delta-connected? A. 54 uF B. 39 uF C. 49 uF D. 11 uF 21. The phase a line voltage and the phase b line current of a balanced three-phase system are: V=220sin (wt-30) volts and I=10 sin (wt150) amps respectively. What is the impedance per phase? A. 33- j 19.1 Ω B. 24- j 10Ω C. 20 –J 14.5 Ω D. 34- J 15.2Ω 22. A balanced three phase Y-connected source has using positive phase sequence, Van=390∠30 V. Determine Vac. A. 675∠0 V B. 675∠120 V C. 675∠-60 V D. 675∠180 V 23. A balanced delta connected load of 15 + j18 ohms per phase is connected at the end of a three phase line. The line impedance is 1 +j2 ohms per phase. The line is supplied from a three-phase source with a line to line voltage of 207.85 V rms. Taking Van as reference, determine the magnitude of the line to line voltage at the load terminals. A. 162.32 V B. 166.18 V C. 168.56 V D. 164.75 V 24. Three similar resistors are connected in star across a 400-V, 3-phase lines. The line current is 10 A. To what value should the line voltage be changed to obtain the same line current with the resistors delta-connected? A. 230.94 V B.133.36 V C. 115.22 V D. 76.98 V 25. A balanced delta connected load contains 8+ j4 ohms per phase, while a balanced wye connected load consist of 2-j1 ohms per phase. Both loads are connected in parallel to a threephase three-wire system in which the line voltage is 120 V rms at the loads. The three line extending from the loads to the source each have a resistance of 0.2 ohm. Determine the power lost in the wires. A. 1.42kW B. 1.38 kW C. 1.24kW D.1.83kW 26. The power input to a 2000 V,50 Hz, 3-phase motor running on full load at an efficiency of 90% is measured by two wattmeters which indicates 300 kw and 100kw respectively. Calculate the line current of the motor. A. 137.4 A B. 169.6 A C. 152.7 A D. 115.5 A 27. The phase c voltage and phase a current of a balanced three-phase system are: V=200 sin (wt+90) volts and I=10 sin wt-45). Dtermine the total reactive power of the system. A. 1553 VARS B. 1672 VARS C. 1245 VARS D. 1842 VARS 28. A 500 kVA transformer is at full load and 0.60 lagging pf. A capacitor bank is added improving the power factor to 0.90 lagging. After improvement, what percent of rated kVA is the transformer carrying? A. 66.7% B. 57.7% C.86.6% D.63.6% 29. A wye-connected-load and a delta connected load are supplied by a four-wire 400 V three-phase, 50 Hz system. The connection for the wye loads are 2/20Ω at line a, 30∠50Ω to line c and 6∠75Ω to line b. The connections for the delta load are 50∠30Ω between lines a and b, 25∠-60Ω between lines b and c, and 17.3∠90Ω betweenlines a and c. Find the current on line b. A. 41.64 A B.26.26 A C. 38.53 A D. 31.38 A 30. A wattmeter reads 5,540 W when the current coil is connected in phase a and the voltage coil is connected between the neutral and phase a of a balanced 3-phase system supplying a balanced load of 30 A at 400 V. What will be the reading of the instrument if the connections to the current coil remain unchanged and the voltage coil is connected between phase b and c? Take a-b-c phase sequence. A. 7200 W B. 8600 W C. 6800 W D. 4500 W 31. Three condensers each having a capacity of 75 uF are connected in star to a 400 volts, three-phase, 50 cycle supply. Calculate the capacitance of each of the three condensers so that when they are connected in delta to the same supply, the line current will remain the same. A. 25uf uF C. 100 uF B. 150 uF D. 225 uF 32. At what power factor will the reading on one of the wattmeters in a two-wattmeter method be zero? A. 0.866 C. 0.707 B. 0.5 D. unity 33. Three identical resistors are connected in wye across a balanced 3-phase source. If one of the resistors is open, the total power drawn by the remaining two resistors is? A. increased by 50% B. increased by 25% C. reduced by 50% D. reduced by 25% 34. The two-wattmeter method is used in measuring power taken by a balanced delta connected load. The wattmeters read 1500 W and 500 W, respectively. If the line voltage is 120V, determine the magnitude of the impedance per phase. A. 24.25 ohms B. 16.33 ohms C. 28.20 ohms D. 9.76 ohms 35. A balanced delta connected load consisting of a pure resistance of 18 ohms per phase is in parallel with a purely resistive balanced Yconnected load of 12 ohms per phase. The combination is connected to a 3-phase balanced supply of 346.41 V (line to line) via 3-phase line having an inductive reactance of j3 ohms per phase. Determine the total complex power drawn from the supply. A. 19.2 –j14.4 KVA B. 19.2 +j14.4 KVA C. 24.2-j12.8KVA D. 24.2 –j12.8 KVA 36. A balanced three-phase three wire system supplies two balanced Y-connected loads. The first draws 6kW at 0.08 pf lagging while the second requires 12kW at 0.833 pf leading. If the current in each line is 8A, find the current in second load. A. 3.27 A B. 4.12 A C. 6.29 A D. 5.58 A 37. A 2300 V, three phase system supplies a 120-kW, 0.6 pf lagging 3-phase balanced load. Determine the capacitance in each phase of a Yconnected capacitor bank to adjust the power factor to 0.90 lagging. A. 45 uF B. 51 uF C. 58 uF D. 54 uF 38. A star-connected balanced load is supplied from a 416 V 50Hz, three phase balanced system. Each phase of load consists of a resistance and a capacitor joined in series. The readings of two wattmeters connected to measure the total power supplied are 782 W and 1980 W, both positive. Calculate the capacitance of each capacitor. A. 98.42 uF B. 106.10uF C. 79.57 uF D. 88.42 uF 39. Two wattmeters are used to measure the total power drawn by a balanced delta connected load. If the wattmeters read 1200 W and 800 W respectively, and the line to line voltage is 208 V, solve for the resistance per phase of the load. A. 51.31 ohms B. 31.72 ohms C. 57.94 ohms D. 20.07 ohms 40. The load on a three phase wye connected 220 V system consist of three 6 ohms resistances connected in wye and in parallel with three 9 ohm resistances connected in delta. Determine the magnitude of the line current. A. 62. 8 A B. 68.7 A C. 70.2 A D. 63.5 A 41. A 3-phase, 30wire balanced Y-load takes a line current of of 30 A at 0.7 pf lagging. Line voltage is 400 V. A single phase wattmeter is connected in the circuit with its current coil in line 1 while its potential coil in lines 2 and 3. Determine the reading of the wattmeter. A. 8400 W B. 9699W C. 8569 W None of these 42. A balanced delta load consisting of pure resistances of 15 ohms per phase is in parallel with a balanced Y-load having phase impedances of 8 +j6 ohms. Identical impedances of 2 + j5 ohms are in each of the three lines connecting the combined loads to a 110-V three phase supply. Find the current drawn from the supply. 48. Three 40 Ω non-inductive resistances are connected in star across a 200-V, 3 phase lines. Calculate the power taken from the mains. A. 4000 W B. 2000 W C. 1000 W D. 3000 W A. 10.52 A B. 8.05 A 49. Three impedances 3 + j4 , ohms are connected in delta to a 220V three phase line. Find the complex power. C. 9.62 A D. 11.18 A A. 6.92 + j5.19 kVA B. 6.92 - j5.19 kVA C. 17.4 + j23.2 kVA D. 17.4 - j23.2 kVA 43. A three-phase, 4 wire star connected system with 230-V between each phase and neutral has resistances of 4, 5 and 6 ohms respectively in the three phases, Estimate the current in the neutral. A. 16.7 A B. 19.3 A 50. A 440 V, three phase source supplies a wye connected 10 kVA load at 0.8 lagging power factor and a delta connected 10 kVA unity pf load. Calculate the total apparent power input to the two loads. C. 12.5 A D. None of these A. 18.97 kVA B. 22.84 kVA C. 20.56 kVA D. 26.19 kVA 44. A three phase ABC system, with Vbc = 294.2∠0 , has the delta connected load, Zab=5∠0 ohms, Zbc = 4∠30 ohms, Zca= 6∠15ohms. Obtain the current in line A. A. 127.9∠-43.3 A B. 103.2∠56.4 A C. 77.1∠-172.1 A D. 99.7∠99.7 A 45. Solve the total power factor of the following parallel connected loads; Load 1, 5 kW, pf=0.8 lagging; load 2, 4 kVA, 2 kVAR(capacitive); load 3, 6kVA, Pf = 0.9lagging. A. 0.954 lagging B. 0.977 leading C. 0.954 leading D. 0.977 lagging 46. The following load impedances are connected delta across a 220 V balanced abc system: Zab= 10∠36.87 ohms; Zbc =10∠0 ohms, Zca= 10∠45 ohms. Find the reading of a kW meter connected with its current coil connected in line b while the potential coil connected across lines b and c. A. 5.12 kW B. 4.08kW C. 4.26 kW D. 5.45 kW 47. The total power absorbed by a certain 3phase balanced load is 60kW, the reactive power being 10kVAR. Determine the reading on one of the two wattmeters properly connected to measure the total power. A. 1642.3 W B. 1573.2 W C. 1132.5 W D. 1262.8 W 51. A balanced wye connected load and a balanced delta connected load are supplies by a 3 phase 480 V, 50 Hz generator. The branch impedances of the wye and delta loads are 10<30 ohms and 20<-50 ohms respectively. Determine the complex equivalent of the total power drawn. A. 42.16- j14.95 kVA B. 22.21 –j11.52 kVA C. 42. 16-j11.52 kVA D. 22.21 –j14.95 kVA 52. Three loads are connected in parallel across a 12.47 kV three-phase supply Load 1: Inductive load, 60kW and 660 kVAR Load 2. Capacitive load, 240 kW at 0.8 pf Load 3: Resistive load of 60kW Find the total power factor. A. 0.866 C. 0.77 B. 0.60 D. 0.65 53. A three-phase, 60 Hz, 2200 volts induction motor delivers 500 hp, 0.8 lagging pf and efficient of 94%. The power factor is raised to 0.90 lagging by connecting a bank of condensers in delta across the lines. If each of the capacitance unit is built up of four similar 550 V, solve the required capacitance of each condenser. A. 56 uF C. 81 uF B. 77 uF D. 60 uF 54. Three identical impedances are connected in delta to a three-phase supply to 400 V. The line current is 34.65 A and the total power taken from the supply is 14.4 kW. Calculate the reactance of each impedance. A. 12Ω B. 10Ω C. 16Ω D. 14Ω 55. A balanced wye connected source, Van = 200∠0 volts rms is connected by four perfect conductors to an unbalanced Y-connected load, Zan = 8 + j6 ohms, Zbn = j20 and Zcn = 10Ω. Find the neutral current. A. 2.66 – j10.32 A C. 2.42 – j12.20 A B. 3.01 – j11.22 A D. -1.53 – j5.96 A 56. Given the magnitude of the line to line voltages of a 3-phase system, Vab = 200V; Vbc = 346 V; Vca= 400 V. If the phase sequence is abbc-ca, with Vab= 200∠0 volts, Vbc is equal to ____. A. 346<-60 C. 346<-90 B. 346<-150 D. 346<-120 57. A resistor of 300 ohms and a capacitor of 8 uF are connected in series across the lines A and B of a voltage between the junction of the resistor and capacitor and line C. Assume: VAB = 400∠0 V; VBC = 40∠-120 V; VCA = 400∠120 V. A. 548 V C. 542 V B. 536 V D. 539 V 58. A three phase Y connected system with 20 V per phase is connected to three loads: 10 ohms, 20∠20 ohms, and 12∠-35 to phase 1, 2 and 3, respectively. Find the current in the neutral line. A. 19.2 A C. 18.8 A B. 22.9 A D. 24.1 A 59. A 400-V 3-phase motor having full load output of 20hp at 0.88 efficiency and 0.80 power factor. Find the readings of the two wattmeters connected to measure the input. A. 14.25kW, 2.704kW C. 12.15kW, 4.806kW B. 10.50kW, 6.454 kW D. 8.75kW, 8.204 kW 60. Three delta-connected impedances, Z2 = 15∠38.9 ohms are connected across a 230-volts 3-phase balanced system through a line impedance of ZL = 1∠60 ohms. Determine the line to line voltage at load terminals. A. 194 V C. 202 V B. 197 V D. 209 V 61. A 230-V, three-phase, three-wire feeder is serving two different loads; The first is a threephase motor load drawing 10kVA at 0.70 pf. The second load is a 5kW heater load connected across lines 2 and 3. Determine the current in line 3. A. 21.7 A C. 46.4 A B. 50.6 A D. 25.1 A 62. A three-phase induction motor is drawing 10 A when a single-phasing takes place. The current drawn by the motor is ___ A. 5(sq rt of 2) C. 10( sq rt of 2) B. 10(sq rt of 3) D. 5 (sq rt of 3) 63. The power to a balanced three-phase system is measured by the two wattmeter method. One wattmeter reads 1986 watts, and the reading of the other is 2517 watts. Determine the line current if the line voltage is 208 volts. A. 11.34 A C. 12.76 A B. 10.45 A D. 15.22 A 64. Each phase of a star-connected load consist of a non-reactive resistance of 100 ohms in parallel with a capacitor of capacitance 31.8 uF. Determine the total kVA when connected to a 416-V 3-phase, 50 Hz supply. A. 2.45 C. 1.73 B.3.39 D. 2.67 65. A balanced three phase wye connected load 150 kW takes a leading current of 100 A, when the line is 2400 V, 60 Hz. What is the capacitance per phase? A. 100 uF C. 150 uF B. 303 uF D. 205 uF 66. A balanced delta connected load of 15 + j18 ohms per phase is connected at the end of a three phase line. The line impedance is 1 + j2 ohms per phase. The line is supplied from a three phase source with a line to line voltage of 207.85 V. Determine the line current A. 16 A C. 12 A B. 14 A D. 18 A 67. A balanced delta connected load with impedance 10∠-36.9 ohms , and a balanced Y- connected load are supplied by the same three phase ABC system having Vca= 141.4∠240 V. If the current in line B is 40.44∠13.41 A, what are the impedance of the Y connected load? A. 5∠-60 ohms B. 5∠-53.3 ohms C. 4∠-30 ohms D. 4∠-66.7 ohms 68. A 3-phase, induction motor is connected across a 220-V, 3-phase source. A wattmeter reads 600 W when its current coil is connected in line 1 and its potential coil across line 1 and 2. If the potential coil of the wattmeter is transferred to lines 2 and 3, the reading of the wattmeter is the same. Calculate the current drawn by motor. A. 5.45 A C. 3.56 A B. 4.32 A D. 6.81 A 69. A 230-V balanced three-phase source is supplying a parallel combination of Y-connected load and a delta connected load. if the Y and delta loads are balanced with phase impedances of 8 – j8 ohms and 24 + j24 ohms respectively, find the total line current. A. 16.6 A C. 17.5 A B. 15.8 A D. 18.5 A 70. A balanced, 3-phase, star connected load of 150 kW takes a lagging current of 100 A with a line voltage of 1100 V, 60 Hz. Find the reactance of the load per phase. A. 5.1 ohms C, 3.3 ohms B. 3.9 ohms D. 2.8 ohms 71.A 3-phase, 2200 V, wye connected power system with grounded neutral supplies energy to a 3-phase Y connected impedances, Zao = 10∠0 ohms, Zbo = 10∠0 ohms, and Zco = 10 + j10 ohms, with point O as common point of the Y connected impedances. Calculate the potential difference between point O and the system ground. Assume point O is not grounded and an a-b-c phase sequence, with Vab as reference. A. 1100 V C. 439 V B. 220 V D. 352 V 72. The load connected to a e-phase supply comprises three similar coils connected in star. The line currents are 25 A and the kVA and kW are 20 and 11 respectively. Determine the reactance of the coil. A. 10.67 ohms B. 9.12 ohms C. 8.91 ohms D. 5.87 ohms 73. The terminals of a three phase supply are labelled a, b and c. Between any pair a voltmeter measures 115 V. A resistor of 100 ohms and a capacitor of 100 ohms at the frequency of the supply are connected in series from a to b with the resistor connected to a. The point of connection of the elements to each other is labelled n. Determine the voltmeter reading between c and n if phase sequence is abc. A. 148.4 V C. 161.2 V B. 153.3 V D. 157.1 V 74. Three parallel three-phase loads are supplied from a 207.85 V rms, 60 Hz threephase supply. The loads are as follows: Load 1; A 15 hp motor operating at full load, 93.25% efficiency and 0.6 lagging power factor; Load 2: A balanced resistive load that draws a total of 6 kW; Load 3: A Y-connected capacitor bank with a total rating of 16kVAR. What is the total supply current? A. 50 A C. 46 A B. 54 A D. 60 A 75. A balanced three-phase, three wire abc system has delta-connected load with a 50 ohms resistor, a 5 uF capacitor, and a 0.56 H inductor in series in each phase. Using positive phase sequence with Van = 390∠30 V rms and w= 500 rad/s, find the current in line b. A. 9∠97.4 A B.9∠-22.6 A C. 9∠-142.6 A D. 9∠127.4 A 76. A certain load takes 40 kVA at 50% lagging pf while another load connected to the same source takes 80 kVA at 86.7% lagging pf. Find the total kVA A. 89.36 C. 120 B. 116.5 D. 74.68 77. Three identical loads having an impedance of 10 cis 30 ohms are connected in wye across a balanced three phase system with sequence set with Vab = 300 cis 0 volts. If a wattmeter is connected in the circuit with its current coil on line B and potential coil across lines B and C, determine the meter reading A. 2.946 kW C. 2.248 kW B. 2.204 kW D. 2.598 kW 78. A three-phase line has an impedance of 0.4 + j2.7 ohms per phase. The line feeds two balanced three-phase loads that are connected in parallel. The first load is absorbing 560.1 kVA at 0.707 pf lagging. The second load absorbs 123 kW at unity pf. The line to line voltage at the load end of the line is 3810.5 V. Determine the magnitude of the line voltage at the source end of the line. A. 4160 V C. 6600 V B. 4670 V D. 5440 V 79. Three wye-connected impedance of ( 3 + j5 ) ohms per phase are connected across a balanced three-phase source of 100V per phase through a line impedance of ( 1 + j1 )ohm. Determine the magnitude of the line current. A. 16.31 A C. 13.86 A B. 12.45 A D. 17.15 A 80. Three 100 uF capacitors are connected in mesh to a 500 V three phase 50 cps supply. What will be the values of each of three capacitors such that when connected in star across the same supply, the line current will be the same? A. 300 uF C. 33.33 uF B. 150 uF D. 173.2 uF 81. In a balanced three-phase circuit, two loads are connected in parallel. Load 1 draws 80 kW and 60 leading kVAR. Load 2 draws 120 kW and 160 lagging kVAR. The line voltage of the system is 1000 volts. Find the line current at the generator terminals. A. 115 A C. 129 A B. 156 A D. 172 A 82. Determine the operating power factor of a three phase balanced load if the reading of the two wattmeters properly connected to measure power is 3:1. A. 0.756 C. 0.671 B. 0.863 D. 0.707 83. A balanced wye connected source, Van = 200 cis 0 V is connected by four perfect conductors to and unbalanced Y-connected load, Zan = 10ohms, Zbn = 10 cis(-30) ohms and Zcn = 28.28 cis 75 ohms. Determine the power absorbed by the load. A. 7.42 kW C. 6.34 kW B. 8.04 kW D. 7.83 kW 84. Three identical star connected resistors are connected across a three-phase, 400 V mains. The circuit draws a total power of 690 W, determine the resistance of each resistor. A. 230 ohms C. 696 ohms B. 120 ohms D. 76.66 ohms 85. Two wattmeters in a three phase, three wire system with effective line voltage of 120 V reads 1500 W and 500 W. What is the impedance of the balanced delta-connected load? A. 18.7∠30 C. 17.8∠30 B. 13.6∠40.9 D. 16.3∠40.9 86. A three-phase delta connected load consists of 10∠45 ohms impedance. The load is connected across a 200-V three-phase source. If the power input to the load is measured by two wattmeters, find the reading of each wattmeter. A. 6425.6 W; 2058.4 W B. 6691.2 W, 1792.8 W C. 5925.2 W; 2558.8 W D. 6188 .6 W, 2295.4 W 87. A 3-phase motor takes 10 kVA at 0.6 pf lagging from a source of 220 V. It is parallel with a balanced delta connected having a 16 ohms resistance and –j12 reactance in series in each phase. Find the line current of the combination. A. 32.43 A C. 36.78 A B. 42.11 A D. 47.21 A 88. A balanced 3-phase star connected load of 150 kW takes a leading current of 100 A with a line voltage of 1100 V, 50 Hz. Find the circuit resistance of the load per phase. A. 10 ohms C. 12 ohms B. 5 ohms D. 8 ohms 89.In an unbalanced 3-phase wye system, the phase voltages are Vna = 132 cis 0; Vnb = 130 cis 235; and Vnc = 133 cis 117. Determine the line to line voltage Vac? A. 225.95 cis 148.37 C. 228.32 cis 125.46 B. 220.15 cis 134.42 D. 292.18 cis 130.85 90. Determine the total complex power of the following parallel connected loads; Load 1, 200 VA, pf =o.7 lagging; Load 2, 350 VA, pf = 0.5 lagging; Load 3, 275 VA, pf = 1. A. 590 +j444, VA C. 560 + j450 VA B. 550 + j480 VA D. 580 + j500 VA 91. It is required to raise the power factor of a 750 kW balanced three phase load from 70 % lagging to 90 % lagging. The line voltage is 6900 volts, 60 cycles. Specify the capacitor require for wye-connected bank in microfarads per phase. A. 22.4 uF C. 20.6 uF B. 28.3 uF D. 23.7 uF 92.A wattmeter has its current coil connected in line 1 while its potential coils is connected across line 2 and 3. If the wattmeter reads 1000 W, the total reactive power of the load is ___ A. 1000 VAR C. 1732 VAR B. 2000 VAR D. 0 VAR 93. A three-phase line has an impedance of 2 + j4 ohms. The line feeds two balanced threephase loads that are connected in parallel. The first load is Y- connected and has an impedance of 30 + j40 ohms per phase. The second load is delta connected and has an impedance of 60 – j45 ohms per phase. The line is energized at the sending end from a three phase balanced supply of line voltage 207.85 V. Determine the line to line voltage at combined loads. A, 193. 64 A C. 172.42 A B. 120.42 A D. 168.25 A 94. A 3-phase power supply to a factory has the following voltages and current measurements: Vab = 240 cis 0 V; Vbc = 240 cis 240 V; Vca= 240 c9s 120 V; Ia=120 cis 330 A; Ib= 157 cis 214 A; Ic = 150 cis 80 A. Solve for the total power. A. 50.5 kW C. 55.3 kW B. 52.7 kW D. 58.8 kW SOLUTIONS: πΌππ 1. πΌππ 416 ( ) ∠ − 60 √3 = 10∠30 = −π24 π΄ 7. πΌπ = 10 = 5.77 π΄ √3 −1 (0.8) π = πππ π = 36.87 ππ = πππ = √3(390)∠60 πππ = 675.5∠60 3. KVL at Loop x: πππ + πππ + πππ = 0 πππ = −πππ − πππ πππ = πππ − πππ πππ = πΌππ ππ πππ 115∠0 πΌππ = = π 100 − π100 πΌππ = 0.813∠ 45 4. ππ = 3ππ πΌπ 208 ππ = = 120 π √3 ππ 120∠0 πΌπ = = = 19.2 + π14.4 π΄ ππ 4 − π3 ππ = 3(120)(19.2 − π14.4) = 6912 − π5184 πππ΄ 5. Y-connection ππ‘ = 3ππ πΌπ (ππ) π = πππ −1 (0.8) πΌπ = 14.08 π΄ 410 ππ √3 ππ = = πΌπ (14.08∠ − 36.87) ππ = 13.45 + π10.09Ω π = 2πππΏ 10.09 = 2π(50)πΏ πΏ = 32.11 ππ» 6. πππ = πππ = πππ πππ πΌππ = ππ = 230∠0 5.77∠−36.87 = 31.89 + π = 2πππΏ = 63.43 ππ» ππ 230∠0 = = 31.89 + π23.92 Ω πΌπ 5.77∠ − 36.87 π = 2πππΏ = 63.43 ππ» ππ = 8. π = 3ππ πΌπ πππ π 100000 = 3(1000)πΌπ (0.6) πΌπ = 50.55 π΄ πΌπ = 55.55∠ − πππ −1 (π. 6) πΌπ = 33.33 − π44.44 π΄ ππ 1000 π= = = 22.5Ω πΌπ₯ 44.44 9. Δ − 3π πΔ = 3ππ¦ πΌΔ = 3πΌπ¦ πΔ = 3ππ¦ A – C – B sequence πππ = 115∠ − 60 (0.813∠45)(−π100) πππ = 42.105∠ − 89.983 πππ = 42.1 π ππ (π − π − π) πππ = 157.1 ππ (π − π − π) 410 ) 1π(0.8) √3 πΌπ π23.92 Ω 2. Reference at node O Va = Vao Vb = Vbo loop: Vao + Vab + Vba = 0 Vba = -Vao – Vob Vba = -Vao + Vbo πππ = −(120∠45) + (100∠ − 45) πππ = 111.35 ∠ − 83.95 5000 = 3 ( ππ π = 36.87 60 = 3ππ¦ ππ¦ = 20ππ 10. Δ − π¦ πΔ ππ¦ = 3 30∠30 ππ¦ = 3 ππ¦ = 10∠30 Ω ππ = 250 = 144.337 π£πππ‘π √3 π’π πππ ππ·π: (144.337)(10∠30) ππ π = (0.4 + π0.3) + (10∠30) = 137.57∠ − 0.3265 ππ πΏπΆ = √3(ππ π ) ππ −πΏπΏ = 238.174π 11. @ π: (πΎπΆπΏ) πΌπ + πΌππ = πΌππ πΌπ = πΌππ − πΌππ πππ πππ πΌπ = − πππ πππ 120∠0 120∠120 πΌπ = − 10 8.66 + π5 πΌπ = 16.97∠ − 45 |πΌπ | = 17 π΄ 12. πππ = 212∠90 π πππ = 10Ω πππ = 212∠ − 150 π πππ = 10 + π10Ω πππ = 212∠ − 30π πππ = −π120 Ω πππ = ππ ππ + ππ ππ + ππ ππ ππ πππ 10(10 + π10) + (10 + π10)(−π20) + (−π20)(10) = −π20 300 − π300 πππ = −π20 πππ = 15 + π15 Ω 300 − π300 πππ = 10 + π10 πππ = −π30Ω πΌππ = πΌππ − πΌππ πππ πππ πΌπ = − πππ πππ 212∠90 π 212∠ − 30π πΌπ = − 15 + π15Ω −π30Ω πΌπ = 3.658∠15 |πΌπ | = 3.66 π΄ 13. πππ = 294.2∠0 ππ = 12∠45πΊ ππ = 10∠30πΊ ππ = 8∠0πΊ πΌπ = πΌπ + πΌπ + πΌπ πππ πππ πππ + + πππ πππ πππ 169.85∠90 169.85∠ − 30 + 12∠45 10∠30 169.85∠ − 30 + 8∠0 πΌπ = 15.317 π΄ πΌπ = 14. β = π πβ ππ¦ = 3 9∠ − 30 ππ¦ = 3 ππ¦ = 3∠ − 30 (3∠ − 30)(5∠45) (3∠ − 30) + (5∠45) ππ = 2317 − π0.136Ω ππ πΌπΏ = πΌπ = ππ 480 ( ) √3 2.317 − π0.136 πΌπΏ = πΌπ = 119.34∠3.36 |πΌπΆ | = |πΌπ | = 119.34 π΄ ππ = 15. ππ¦ = πβ 3 = 15 3 = 5πΊ 5(8 + π6) ππ = (2 + π5) + [ ] 5(8 + π6) ππ = 5.414 + π5.73 Ω 110 ππ √3 πΌπ = = = 8.055 ∠ − 46.63 π΄ ππ 5.414 + π5.73 ππ − πΌπ ππΏ − ππΏ = 0 110 πππππ = − (8.055∠ − 46.63(2 + π5)) √3 πππππ = 28.285∠ − 34.05 πππππ πΏ−πΏ = √3(28.285) πππππ = 49 π 16. πΌπ = πΌβ + πΌππ πππ’π‘ πΌπ = √3ππΏ πππ 5(746) πΌπ = √3(208)(0.71)(81%) πΌπ = πΌππ = 18 π΄ π = πππ −1 (0.71) π=44.765 ππ 6000 πΌπ = = = 49.96 π΄ ππ (208 ⁄ ) √3 πΌπ = 49.96∠120 + 18∠(120 − 44.77) πΌπ = 64∠108.57 |πΌπ |= 64 A 17. πΌπ = πΌππ − πΌππ πππ πππ 240∠0 240∠120 πΌπ = − = − πππ πππ 8 + π7 8 + π7 πΌπ = 39.105 ∠ − 71.186 π΄ π = πππ πΌπ πππ π π = 240(39.105[cos 120 − 71.86]) π = 6180 π€ππ‘π‘π 18. π1 = πππ πΌπ πππ π π1 = (4140)(60)[(cos(30))] π1 = 215.12 ππ π2 = πππ πΌπ πππ π π2 = (4140)(78.4)[cos[(240) − (214)]] π2 = 291.73 ππ ππ = π1 + π2 = 215.12 + 291.73 ππ = 506.85 ππ 19. 3∅ πΌ = 75 π΄ @ 230 π π = πππ −1 (0.848) π = 32 0. .848 πππ π1 = ππΏ πΌπΏ cos(30 − π) π1 = (230)(75) cos(30 − 32) π1 = 17239 ππ 1500−500 20.π = π‘ππ−1 √3 [1500+500] π = 40.893 ππ = cos(40.843) ππ = 0.866 ππ§ = 3ππ πΌπ (ππ) 1500 + 500 = 3(180)πΌπ (0.866) πΌπ = 7.35 π΄ ππ 120∠0 ππ = = πΌπ 7.35∠40.893 ππ = 12.341 + π10.688 πΊ 1 2π(60)(740.48) C = 3.58uF C= 1. 21. πΌπ = πΌππ + πΌππ + πΌππ π1π π‘ = 5760 π€ π2ππ = 3380 π€ π1 π2 ] π1 + π2 5760 − 3380 π = tan−1 √3 [ ] 5760 + 3380 π = 24.276 ππ = cos π ππ = 0.912 π 3780 + 3380 πΌ= = √3ππΏ ππ √3(230)(0.912) πΌ = 25.168 π΄ππ π = tan−1 √3 [ = 4∠0 + 10∠ − 120 + 8∠120 πΌπ = 5.291∠ − 160.89° |πΌπ | = 5.29 A 2. ππ‘ = π1 + π2 20 15 =( ) ∠ cos −1 0.85 + ( ) ∠ cos−1 0.5 0.85 0.5 ππ‘ = 51.94∠47.634°, kVA → lagging ππ‘ 51,940 πΌπ‘ = = = 68.153 A √3ππΏ √3(440) ππ = ππ + πΌπ‘ πππππ 22. ππ = π1 + ππΆ ππΆ = ππ − π1 πππ’π‘ππ’π‘ 50(0.746) πππ = = = 41.91 kw π 0.89 41.91 ππΆ = ( ∠ cos−1 0.95) 0.95 −( ∠ cos −1 0.85) ππΆ = j12.198 Kvar = 440 ∠0 + √3ππΏ (68.153∠ − 47.634)(1 + j3) V phase ππ = √3(459.42) = 795.738 V, line to line ππ = 459.42∠10.97°, 3. πΌπ = πΌππ − πΌππ πππ πππ 339.4∠0 339.4∠120 = − = − πππ πππ 10∠0 15∠ − 30 πΌπ = 54.72∠ − 11.93° |πΌπ | = 54.72 A 23. ππΏ = π1 + π2 + π3 240 ππΏ = (60 + π½660) + ( ∠ − cos−1 0.8) + 60 0.8 ππΏ = 360 + j480 kVA ππΆ = ππ − ππΏ 360 ππΆ = [ ∠36.87] − [360 + π480] 0.8 ππΆ = −j210 kVAR 210 70KVAR ππΆ = = 3 PHASE ππ2 ππΆ = ππΆ 12470 ( ) √3 ππΆ = 70 πΎππ΄π ππΆ = 740.48 1 C= 2ππππΆ 4. ππ = 440 = 254 V √3 πΌπΏ = πΌ1 + πΌ 2 254∠0 254∠0 + = 38.619∠ − 15.255 A 10 + π5 15 ππ‘ = √3ππΏ πΌπΏ ∗= √3(440∠0)(38.619∠15.255) ππ‘ = 28.394 + j7.744, kVA |ππ‘| = 28.394 kW πΌπΏ =