THREE PHASE CIRCUITS A three-phase system is equivalent to three single-phase circuits Balanced phase voltages are equal in magnitude and are out of phase with each other by 120◦ Three – Phase Voltage Source *** double subscript notation. Phase voltages Line voltages Balanced voltages Phase sequences - is the time order in which the voltages pass through their respective maximum values abc or positive sequence - produced when the rotor rotates counter-clockwise acb or negative sequence - produced when the rotor in the clockwise direction A balanced load is one in which the phase impedances are equal in magnitude and in phase Possible Connections of Source and Loads Y-Y connection Y-∆ connection ∆-∆ connection ∆-Y connection BALANCED WYE-WYE CONNECTION is a three-phase system with a balanced Y-connected source and a balanced Y-connected load Phase Voltages: (assuming the positive sequence) Source Load (assuming no line impedance): Line-to-line voltages Line Currents: Note: for a balanced system, the neutral current is always equal to zero. Single – phase Equivalent Circuit Example 1: Example 2: BALANCED WYE-DELTA CONNECTION consists of a balanced Y-connected source feeding a balanced -connected load. Line voltages: (Assuming the positive sequence: phase voltages) Source Load Phase Currents: Phase currents have the same magnitude but are out of phase with each other by 120◦ Line Currents: Note: alternative way of analyzing the Y-∆ circuit is to transform the ∆-connected load to an equivalent Yconnected load Example 1: BALANCED DELTA-DELTA CONNECTION both the balanced source and balanced load are ∆ - connected. Phase Voltages : (assuming a positive sequence) Source: Load: (assuming no line impedance) Phase Currents: Line Currents: Note: alternative way of analyzing the ∆-∆ circuit is to transform both the load and the source to their Y - equivalents Example 1: BALANCED DELTA-WYE CONNECTION consists of a balanced ∆ - connected source feeding a balanced Y-connected load. Phase Voltages : (assuming a positive sequence) Source: Load: (assuming no line impedance) Line Currents: Note: Another way to obtain the line currents is to replace the delta - connected source with its equivalent wye-connected source Example 1: Example 2: POWER IN A BALANCED SYSTEM Power per Phase Real Reactive Apparent/ Complex Three - Phase Power Real Reactive Apparent/ Complex Example 1: Example 2: UNBALANCED THREE-PHASE SYSTEMS is due to unbalanced voltage sources or an unbalanced load Unbalanced three-phase systems are solved by direct application of mesh and nodal analysis Total power is not simply three times the power in one phase but the sum of the powers in the three phases. Example 1: Three-Phase Power Measurement 1. Three-Wattmeter Method - well suited for power measurement in a three-phase system where the power factor is constantly changing. In a three-wattmeter method, the algebraic sum of three-wattmeter readings simply gives the total electric power consumed in the circuit, whether it is balanced or not Where: P1, P2, & P3 correspond to the readings of wattmeters W1, W2, and W3, respectively The one end of the three wattmeters’ potential coils is connected to the common point o. If a neutral point is available in the three-phase system, then the common point o should be connected to that neutral point. 2. Two-Wattmeter Method - most commonly used method for three-phase power measurement. Notice that the current coil of each wattmeter measures the line current, while the respective voltage coil is connected between the line and the third line and measures the line voltage Although the individual wattmeters no longer read the power taken by any particular phase, the algebraic sum of the two wattmeter readings equals the total average power absorbed by the load, regardless of whether it is wye- or delta-connected, balanced or unbalanced The total real power is equal to the algebraic sum of the two wattmeter readings, Consider the figure Assume the source is in the abc sequence and the load impedance ZY θ. Each phase voltage leads its respective phase current by θ Each line voltage leads the corresponding phase voltage by 30°. Thus, the total phase difference between the phase current Ia and line voltage Vab is θ + 30° The average power read by wattmeter W1 is Similarly, we can show that the average power read by wattmeter 2 is We now use the following trigonometric identities to find the sum and the difference of the two wattmeter reading P1 and P2 Thus, the sum of the wattmeter readings gives the total average power Similarly, Thus, the difference of the wattmeter readings is proportional to the total reactive power, the apparent power can calculated as the tangent of the power factor angle is Thus the power factor is, Thus, the two-wattmeter method not only provides the total real and reactive powers, it can also be used to compute the power factor. Although these results are derived from a balanced Y-connected load, they are equally valid for a balanced Δ-connected load The two-wattmeter method cannot be used for power measurement in a 3-phase 4wire system unless the current through the neutral line is zero. We can use the three-wattmeter method to measure the real power in a 3-phase 4wire system Example 1: Calculate the readings of the two wattmeters ( W1 & W2 ) connected to measure the total power for a balanced star-connected load shown in the figure below, fed from a three-phase, 400 V balanced supply with phase sequence as abc. The load impedance per phase is (20 + j15) Ω. Also find the line and phase currents, power factor, total power, total reactive VA and total VA Calculate the readings of the two wattmeters (W1 & W2) connected to measure the total power for a balanced delta-connected load shown in the figure, fed from a three=phase, 200 V balanced supply with phase sequence as abc. The load impedance per phase is (14 – j14) Ω. Also find the line and phase currents, power factor, total power, total reactive VA and total VA